data sheet | curtain controls skc-sc · skc-sc controls fire curtains and smoke curtains. the...
TRANSCRIPT
SKC-SC controls fire curtains and smoke curtains. The system is modular and can be configured ona PC via a USB interface to provide the requiredfunctionality for a project. Activation is via afire alarm system or its own smoke alarm andmanual control points. When the alarm is raised, the system provides status messages and opticalor acoustic signalling. It monitors cables for wire-break and short circuit.
The control panel is designed for the safeoperation of automatic smoke and fire curtains. Itcontains programs for intermediate positions forboth drive up / drive down and ‚‘gravity fail-safe‘‘operation, as well as for the re-opening of thecurtain after it has been lowered.
The control panel is designed to meet therequirements of the pr12101-9 product standard. It has a local power supply system to maintainall control functions over a period of at least 72hours, meeting the requirements of EN 12101-10. The control panel meets all the requirementsof CE marking under the Construction ProductsRegulation.
Its features and benefits are described overleaf.
SKC-SC
PRODUCT DATA SHEET | SKC-SC CONTROL
DATA SHEET | CURTAIN CONTROLS
360°
360°
360°
360°
360°
KL monitoring
Safety bottom bar
Attached to the bottom bar
LS monitoring
Obstruction warning system
Installed in the wall opening
WN Function
Emergency opening by people escaping
Button adjacent tocurtain
WF Function
Emergency opening by fire-fighters
Manual release
Break glass push button
Button adjacent tocurtain
Auto release
Smoke or heat detector
In front of or behind the curtain
S Signals
Multi-tone siren / strobe light
Installed in the immediate vicinity of
the curtain
S Signals
Multi-tone siren / strobe light / voice
warning system
Installed in the immediate vicinity of
the curtain
SKC-SCCONTROLS
Modular design for
your safetyEV
Supply modulewith backup
AMConnection
module
BMHeart modulewith processor
and USB
ZMAuxiliary module
for addedfunctions
WRe-transmission
module
SSignallingmodule
rest position rest position rest position
hold t2 HWD hold t2 HWD-1 hold t2 HWD +2,0 m
hold t4 HWD-2
FFL curtain dropped FFL curtain dropped FFL curtain dropped
sketch 1 sketch 2 sketch 3
way
t1
way
t1
way
t3
way
t1
HWD (half way down) program
SOME FEATURES OF THE SKC-SC CON-TROL SYSTEM
Processor controls:A wide range of modesModular designUSB interfaceConfiguration via a PC72 hours local power supplyMonitoring of cablesIntermediate drop position option
Developed for automatic smoke and fire curtainsOperation with ASB types 1 to 4
Designed and tested in accordance with prEN 12101-9, EN 12101-10 and BS 8524. Certification being prepared.
Can control up to four groups of curtains, if necessary each with different functions.
PRODUCT DATA SHEET | SKC-SC CONTROL
SKC-SC controls fire curtains and smokecurtains. It has been tested in accordancewith prEN 12101-9 and BS 8524. Ithas a power supply to maintain thecontrol functions for at least 72 hours inaccordance with EN 12101-10.
It provides the following functions:• Maintains the curtains in the raised position in the event of a temporary interruption to the power supply assuming the optional uninterruptible power supply (UPS) has been supplied and connected.• Automatically lowers the curtain in case of alarm.• Intermediate stop for curtains before they descend completely to the floor (HWD-1 + 2).• Emergency opening button to enable personnel leaving an area to be able to open the curtain once it has been lowered.• Fire-fighter’s override button.• Safety bottom bar to stop the curtain if there is an obstruction.• Beam detector to monitor the opening for obstructions.• Combination multi-tone siren and strobe light with the option of a voice warning system.• Manual operation• Status reports to building management. The system is modular and can beconfigured on a PC via a USB interfaceto provide the required functionality fora project.
The history relating to the system statusand fault events is stored within theinternal memory.
The panel has a switch for service andmaintenance purposes.
“People feel better in Colt conditions.” | Version 08-2016© Colt International Licensing Limited 2016www.coltgroup.com
rest position rest position rest position
hold t2 HWD hold t2 HWD-1 hold t2 HWD +2,0 m
hold t4 HWD-2
FFL curtain dropped FFL curtain dropped FFL curtain dropped
sketch 1 sketch 2 sketch 3
way
t1
way
t1
way
t3
way
t1
Emergency opening program
ASB types 2 and 4Without fail-safe
function
ASB types 1 and 3With fail-safe func-
tion
Parameters entered by use of the ''SmokiControl'' program
t1 t
rave
lt3
tra
vel
Curtain up
HWD-1
HWD-2
Curtain downFloor level
Stop t2
Stop t4
Curtain up
HWD-2.0m
Curtain downFloor level
Stop t2
t1 t
rave
l
Key switch with profile half-cylinder