data bookremote control (option) wired : rc-ex3a , rc-e5 , rch-e3 wireless : rcn-t-5aw-e2 room...
TRANSCRIPT
(Split system, air to air heat pump type)
DUCT CONNECTED-LOW/MIDDLE STATIC PRESSURE TYPESingle type
FDUM100VNAWVH100VSAWVH125VNAWVH125VSAWVH140VNAWVH140VSAWVH
Twin type FDUM100VNAWPVH
100VSAWPVH125VNAWPVH125VSAWPVH140VNAWPVH140VSAWPVH
Triple type FDUM140VNAWTVH
140VSAWTVH
CEILING CASSETTE-4 WAY COMPACT TYPETwin type FDTC100VNAWPVH
100VSAWPVH125VNAWPVH125VSAWPVH
Single type FDT100VNAWVH
100VSAWVH125VNAWVH125VSAWVH140VNAWVH140VSAWVH
CEILING CASSETTE-4 WAY TYPETwin type FDT100VNAWPVH
100VSAWPVH125VNAWPVH125VSAWPVH140VNAWPVH140VSAWPVH
Triple type FDT140VNAWTVH
140VSAWTVH
Triple type FDTC140VNAWTVH
140VSAWTVH
MICRO INVERTER PACKAGED AIR-CONDITIONERS
Single type SRK100VNAWZR
100VSAWZR
WALL MOUNTED TYPETwin type
SRK100VNAWPZSX100VSAWPZSX125VNAWPZSX125VSAWPZSX140VNAWPZR140VSAWPZR
Triple typeSRK140VNAWTZSX
140VSAWTZSX
DUCT CONNECTED-HIGH STATIC PRESSURE TYPESingle type
FDU100VNAWVH100VSAWVH125VNAWVH125VSAWVH140VNAWVH140VSAWVH
(OUTDOOR UNIT)FDC100VNA-W
100VSA-W125VNA-W125VSA-W140VNA-W140VSA-W
(INDOOR UNIT)FDT50VH
60VH71VH
FDE50VH60VH71VH
V Multi System
Single type FDE100VNAWVH
100VSAWVH125VNAWVH125VSAWVH140VNAVWH140VSAVWH
Twin type FDE100VNAWPVH
100VSAWPVH125VNAWPVH125VSAWPVH140VNAWPVH140VSAWPVH
CEILING SUSPENDED TYPETriple type FDE140VNAWTVH
140VSAWTVH
Manual No.'19 • PAC-DB-308D
DATA BOOK
DRAFT
'19 • PAC-DB-308D
- 1 -
TABLE OF CONTENTS
1. MICRO INVERTER PACKAGED AIR-CONDITIONERS ................................................. 22. V MULTI SYSTEM ...........................................................................................................208
'19 • PAC-DB-308D
- 2 -
CONTENTS1.1 SPECIFICATIONS ........................................................................................ 3
(1) Ceiling cassette-4 way type (FDT) .......................................................... 3
(5) Ceiling suspended type (FDE) ................................................................ 43(6) Wall mounted type (SRK) ......................................................................... 57
(7) Wall mounted type (SRK) ............................................................................165
(3) Duct connected-High static pressure type (FDU) .................................... 23
1.2 EXTERIOR DIMENSIONS ............................................................................ 67(1) Indoor units .............................................................................................. 67(2) Outdoor units ........................................................................................... 79
1.4 NOISE LEVEL1.5 CHARACTERISTICS OF FAN
1.7 PIPING SYSTEM1.6 TEMPERATURE AND VELOCITY DISTRIBUTION
1.3 ELECTRICAL WIRING ................................................................................. 83
1.8 RANGE OF USAGE & LIMITATIONS
(1) Indoor units .............................................................................................. 83(2) Outdoor units ........................................................................................... 92
(3) Remote control (Option parts) .................................................................. 80
1.9 SELECTION CHART1.9.1 Capacity tables
1.9.2 Correction of cooling and heating capacity in relation to air flow rate control (fan speed)
(2) Ceiling cassette-4 way compact type (FDTC) ......................................... 17
(4) Duct connected-Low/Middle static pressure type (FDUM) ...................... 29
(1) Ceiling cassette-4 way type (FDT) ..............................................................134
(3) Ceiling suspended type (FDE) ....................................................................144
(6) Floor standing type (FDF) ...........................................................................161
(4) Duct connected-High static pressure type (FDU) ........................................151
(2) Ceiling cassette-4 way compact type (FDTC) .............................................141
(5) Duct connected-Low/Middle static pressure type (FDUM) ..........................154
1.9.3 Correction of cooling and heating capacity in relation to one way length of refrigerant piping1.9.4 Height difference between the indoor unit and outdoor unit
1.10 APPLICATION DATA1.10.1 Installation of indoor unit .....................................................................171
...................................................................................171
........................................................................................134
(1) Ceiling cassette-4 way type (FDT) ..............................................................171
(3) Ceiling suspended type (FDE) ....................................................................184(4) Duct connected-High static pressure type (FDU) ........................................188
(2) Ceiling cassette-4 way compact type (FDTC) .............................................178
..........170.....170
..............170
.................................................................................................108........................................................................113
........................................119.............................................................................................128
............................................................130.......................................................................................134
1. MICRO INVERTER PACKAGED AIR-CONDITIONERS
■How to read the model name
FDT : Ceiling cassette-4 way type
SRK : Wall mounted type
FDTC : Ceiling cassette-4 way compact typeFDU : Duct connected-High static pressure typeFDUM : Duct connected-Low/Middle static pressure type
Example: FDT 100 VNAW P VH
Series code
P : Twin type
: Single type
T : Triple typeApplicable power source...See the specificationProduct capacityModel name
FDC : Outdoor unit
(blank)
..........................................................................336(1) List of troubles ...........................................................................................336(2) Troubleshooting ........................................................................................338
1.12.2 Troubleshooting flow
(1) Selfdiagnosis function ...............................................................................301(2) Troubleshooting procedure .......................................................................306(3) Troubleshooting at the indoor unit .............................................................306(4) Troubleshooting at the outdoor unit ..........................................................321(5) Check of anomalous operation data with the remote control ....................331(6) Inverter checker for diagnosis of inverter output ......................................333(7) Outdoor unit control failure diagnosis circuit diagram ...............................334
1.12 MAINTENANCE DATA ...............................................................................3011.12.1 Diagnosing of microcomputer circuit ...............................................301
1.4 TECHNICAL INFORMATION ....................................................................... 94(1) Ceiling cassette-4 way type (FDT) .......................................................... 94
(5) Ceiling suspended type (FDE) ................................................................166(6) Wall mounted type (SRK) .......................................................................191
(3) Duct connected-High static pressure type (FDU) ...................................130(2) Ceiling cassette-4 way compact type (FDTC) .........................................119
1.13 DISASSEMBLY PROCEDURE ...................................................................418(1) Indoor unit ...............................................................................................418(2) Outdoor unit .............................................................................................432
(4) Duct connected-Low/Middle static pressure type (FDUM) .....................141
FDE : Ceiling suspended type
'19 • PAC-DB-308D
ModelItem
FDT100VNAWVHIndoor unit FDT100VH Outdoor unit FDC100VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 10.0 [ 4.0(Min.) - 11.2(Max.)]Nominal heating capacity (range) kW 11.2 [ 4.0(Min.) - 12.5(Max.)]
Power consumptionCooling
kW2.73
Heating 2.54Max power consumption 6.40
Running currentCooling
A13.2 / 13.8
Heating 12.4 / 13.0Inrush current, max current 5, 24
Power factorCooling
%90
Heating 89EER Cooling 3.66COP Heating 4.41
Sound power levelCooling
dB(A)
6269
Heating 70
Sound pressure levelCooling P-Hi: 47 Hi: 39 Me: 36 Lo: 30 54Heating P-Hi: 47 Hi: 39 Me: 36 Lo: 29 55
Silent mode sound pressure level — 48 /44(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm Unit 298 x 840 x 840Panel 35 x 950 x 950 845x970x370
Exterior appearance(Munsell color)(RAL color )
Plaster white(6.8Y8.9/0.2) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg Unit 25 Panel 5 77Compressor type & Q'ty — RMT5126SWP3 x 1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Turbo fan x1 Propeller fan x1Fan motor (Starting method) W 140 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 37 Hi: 26 Me: 23 Lo: 1775
Heating 73Available external static pressure Pa 0 0Outside air intake Possible —Air filter, Quality / Quantity Pocket plastic net x1(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-T-5AW-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 9.52 (3/8") Pipe φ 9.52 (3/8")x0.8 O/U φ 9.52 (3/8")
Gas line φ 15.88 (5/8") Pipe φ 15.88(5/8")x1.0 φ 15.88 (5/8")Connecting method Flare piping Flare piping
Attached length of piping m — —
Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP25(O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 850 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mm x3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-T-5W-E
PJF000Z589 B
(1) Ceiling cassette-4 way type (FDT) (a) Single type
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
1.1 SPECIFICATIONS
- 3 -
'19 • PAC-DB-308D
PJF000Z589 B
ModelItem
FDT100VSAWVHIndoor unit FDT100VH Outdoor unit FDC100VSA-W
Power source 3 Phase, 380 - 415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 10.0 [ 4.0(Min.) - 11.2(Max.)]Nominal heating capacity (range) kW 11.2 [ 4.0(Min.) - 12.5(Max.)]
Power consumptionCooling
kW2.73
Heating 2.54Max power consumption 10.20
Running currentCooling
A4.2 / 4.4
Heating 3.9 / 4.1Inrush current, max current 5, 15
Power factorCooling
%94
Heating 93EER Cooling 3.66COP Heating 4.41
Sound power levelCooling
dB(A)
6269
Heating 70
Sound pressure levelCooling P-Hi: 47 Hi: 39 Me: 36 Lo: 30 54Heating P-Hi: 47 Hi: 39 Me: 36 Lo: 29 55
Silent mode sound pressure level — 48 /44(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm Unit 298 x 840 x 840Panel 35 x 950 x 950 845x970x370
Exterior appearance(Munsell color)(RAL color )
Plaster white(6.8Y8.9/0.2) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg Unit 25 Panel 5 78Compressor type & Q'ty — RMT5126SWP4 x 1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Turbo fan x1 Propeller fan x1Fan motor (Starting method) W 140 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 37 Hi: 26 Me: 23 Lo: 1775
Heating 73Available external static pressure Pa 0 0Outside air intake Possible —Air filter, Quality / Quantity Pocket plastic net x1(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-T-5AW-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 9.52 (3/8") Pipe φ 9.52 (3/8")x0.8 O/U φ 9.52 (3/8")
Gas line φ 15.88 (5/8") Pipe φ 15.88(5/8")x1.0 φ 15.88 (5/8")Connecting method Flare piping Flare piping
Attached length of piping m — —
Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP25(O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 850 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mm x3 cores + earth cable / Terminal block (Screw fixing type)IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-T-5W-E
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 4 -
'19 • PAC-DB-308D
ModelItem
FDT125VNAWVHIndoor unit FDT125VH Outdoor unit FDC125VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 12.5 [ 5.0(Min.) - 14.0(Max.)]Nominal heating capacity (range) kW 14.0 [ 4.0(Min.) - 16.0(Max.)]
Power consumptionCooling
kW4.05
Heating 3.59Max power consumption 6.40
Running currentCooling
A18.7 / 19.6
Heating 16.8 / 17.5Inrush current, max current 5, 24
Power factorCooling
%94
Heating 93EER Cooling 3.09COP Heating 3.90
Sound power levelCooling
dB(A)
6371
Heating 64
Sound pressure levelCooling P-Hi: 48 Hi: 41 Me: 39 Lo: 31 54Heating P-Hi: 48 Hi: 41 Me: 38 Lo: 31 56
Silent mode sound pressure level — 48 /45(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm Unit 298 x 840 x 840Panel 35 x 950 x 950 845x970x370
Exterior appearance(Munsell color )(RAL color )
Plaster white(6.8Y8.9/0.2) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg Unit 25 Panel 5 77Compressor type & Q'ty — RMT5126SWP3 x 1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Turbo fan x1 Propeller fan x1Fan motor (Starting method) W 140 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 38 Hi: 28 Me: 25 Lo: 1875
Heating 73Available external static pressure Pa 0 0Outside air intake Possible —Air filter, Quality / Quantity Pocket plastic net x1(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-T-5AW-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 9.52 (3/8") Pipe φ 9.52 (3/8")x0.8 O/U φ 9.52 (3/8")
Gas line φ 15.88 (5/8") Pipe φ 15.88(5/8")x1.0 φ 15.88 (5/8")Connecting method Flare piping Flare piping
Attached length of piping m — —
Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP25(O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 850 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mmx 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-T-5W-E
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
PJF000Z589 B
- 5 -
'19 • PAC-DB-308D
PJF000Z589 B
ModelItem
FDT125VSAWVHIndoor unit FDT125VH Outdoor unit FDC125VSA-W
Power source 3 Phase, 380 - 415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 12.5 [ 5.0(Min.) - 14.0(Max.)]Nominal heating capacity (range) kW 14.0 [ 4.0(Min.) - 16.0(Max.)]
Power consumptionCooling
kW4.05
Heating 3.59Max power consumption 10.20
Running currentCooling
A6.2 / 6.5
Heating 5.5 / 5.7Inrush current, max current 5, 15
Power factorCooling
%94
Heating 95EER Cooling 3.09COP Heating 3.90
Sound power levelCooling
dB(A)
6371
Heating 64
Sound pressure levelCooling P-Hi: 48 Hi: 41 Me: 39 Lo: 31 54Heating P-Hi: 48 Hi: 41 Me: 38 Lo: 31 56
Silent mode sound pressure level — 48 /45(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm Unit 298 x 840 x 840Panel 35 x 950 x 950 845x970x370
Exterior appearance(Munsell color )(RAL color )
Plaster white(6.8Y8.9/0.2) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg Unit 25 Panel 5 78Compressor type & Q'ty — RMT5126SWP4 x 1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Turbo fan x1 Propeller fan x1Fan motor (Starting method) W 140 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 38 Hi: 28 Me: 25 Lo: 1875
Heating 73Available external static pressure Pa 0 0Outside air intake Possible —Air filter, Quality / Quantity Pocket plastic net x1(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-T-5AW-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 9.52 (3/8") Pipe φ 9.52 (3/8")x0.8 O/U φ 9.52 (3/8")
Gas line φ 15.88 (5/8") Pipe φ 15.88(5/8")x1.0 φ 15.88 (5/8")Connecting method Flare piping Flare piping
Attached length of piping m — —
Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP25(O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 850 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mmx 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-T-5W-E
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 6 -
'19 • PAC-DB-308D
ModelItem
FDT140VNAWVHIndoor unit FDT140VH Outdoor unit FDC140VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 13.6 [ 5.0(Min.) - 14.5(Max.)]Nominal heating capacity (range) kW 15.5 [ 4.0(Min.) - 16.5(Max.)]
Power consumptionCooling
kW4.79
Heating 4.18Max power consumption 6.40
Running currentCooling
A21.5 / 22.4
Heating 18.5 / 19.4Inrush current, max current 5, 24
Power factorCooling
%97
Heating 98EER Cooling 2.84COP Heating 3.71
Sound power levelCooling
dB(A)
63 72Heating 64 73
Sound pressure levelCooling P-Hi: 48 Hi: 42 Me: 39 Lo: 32 56Heating P-Hi: 48 Hi: 41 Me: 38 Lo: 31 58
Silent mode sound pressure level — 49 /45(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm Unit 298 x 840 x 840Panel 35 x 950 x 950 845x970x370
Exterior appearance(Munsell color )(RAL color )
Plaster white(6.8Y8.9/0.2) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg Unit 25 Panel 5 77Compressor type & Q'ty — RMT5126SWP3 x 1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Turbo fan x1 Propeller fan x1Fan motor (Starting method) W 140 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 38 Hi: 29 Me: 26 Lo: 1975
Heating 73Available external static pressure Pa 0 0Outside air intake Possible —Air filter, Quality / Quantity Pocket plastic net x1(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-T-5AW-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 9.52 (3/8") Pipe φ 9.52 (3/8")x0.8 O/U φ 9.52 (3/8")
Gas line φ 15.88 (5/8") Pipe φ 15.88(5/8")x1.0 φ 15.88 (5/8")Connecting method Flare piping Flare piping
Attached length of piping m — —
Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP25(O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 850 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mmx 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-T-5W-E
PJF000Z589 B
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 7 -
'19 • PAC-DB-308D
PJF000Z589 B
ModelItem
FDT140VSAWVHIndoor unit FDT140VH Outdoor unit FDC140VSA-W
Power source 3 Phase, 380 - 415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 13.6 [ 5.0(Min.) - 14.5(Max.)]Nominal heating capacity (range) kW 15.5 [ 4.0(Min.) - 16.5(Max.)]
Power consumptionCooling
kW4.79
Heating 4.18Max power consumption 10.20
Running currentCooling
A7.4 / 7.7
Heating 6.6 / 7.0Inrush current, max current 5, 15
Power factorCooling
%94
Heating 91EER Cooling 2.84COP Heating 3.71
Sound power levelCooling
dB(A)
63 72Heating 64 73
Sound pressure levelCooling P-Hi: 48 Hi: 42 Me: 39 Lo: 32 56Heating P-Hi: 48 Hi: 41 Me: 38 Lo: 31 58
Silent mode sound pressure level — 49 /45(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm Unit 298 x 840 x 840Panel 35 x 950 x 950 845x970x370
Exterior appearance(Munsell color )(RAL color )
Plaster white(6.8Y8.9/0.2) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg Unit 25 Panel 5 78Compressor type & Q'ty — RMT5126SWP4 x 1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Turbo fan x1 Propeller fan x1Fan motor (Starting method) W 140 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 38 Hi: 29 Me: 26 Lo: 1975
Heating 73Available external static pressure Pa 0 0Outside air intake Possible —Air filter, Quality / Quantity Pocket plastic net x1(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-T-5AW-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35 (1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line φ 12.7 (1/2") ②φ12.7(1/2")x0.8 ①φ15.88(5/8")x1.0 φ15.88 (5/8")Connecting method Flare piping Flare piping
Attached length of piping m — —
Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP25(O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 850 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mmx 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-T-5W-E
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 8 -
'19 • PAC-DB-308D
PJF000Z589 B
(b) Twin type
ModelItem
FDT100VNAWPVHIndoor unit FDT50VH (2 units) Outdoor unit FDC100VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 10.0 [ 4.0(Min.) - 11.2(Max.)]Nominal heating capacity (range) kW 11.2 [ 4.0(Min.) - 12.5(Max.)]
Power consumptionCooling
kW2.82
Heating 2.73Max power consumption 6.40
Running currentCooling
A12.4 / 12.9
Heating 12.0 / 12.5Inrush current, max current 5, 24
Power factorCooling
%99
Heating 99EER Cooling 3.55COP Heating 4.11
Sound power levelCooling
dB(A)
55 69Heating 56 70
Sound pressure levelCooling P-Hi: 41 Hi: 33 Me: 30 Lo: 26 54Heating P-Hi: 42 Hi: 33 Me: 28 Lo: 20 55
Silent mode sound pressure level — 48 /44(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm Unit 236 x 840 x 840Panel 35 x 950 x 950 845x970x370
Exterior appearance(Munsell color )(RAL color )
Plaster white(6.8Y8.9/0.2) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg Unit 19 Panel 5 77Compressor type & Q'ty — RMT5126SWP3 x 1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Pre - charged up to the piping length of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Turbo fan x1 Propeller fan x1Fan motor (Starting method) W 50 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 22 Hi: 16 Me: 13 Lo: 1075
Heating 73Available external static pressure Pa 0 0Outside air intake Possible —Air filter, Quality / Quantity Pocket plastic net x1(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-T-5AW-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35 (1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line φ 12.7 (1/2") ②φ12.7(1/2")x0.8 ①φ15.88(5/8")x1.0 φ15.88 (5/8")Connecting method Flare piping Flare piping
Attached length of piping m — —
Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP25(O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 850 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mmx 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-T-5W-E
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1G"×1(Option). ① : Pipe of O/U - Branch, ② : Pipe of Branch - I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 9 -
'19 • PAC-DB-308D
PJF000Z589 B
ModelItem
FDT100VSAWPVHIndoor unit FDT50VH (2 units) Outdoor unit FDC100VSA-W
Power source 3 Phase, 380 - 415V 50Hz / 380 60Hz
Operation data
Nominal cooling capacity (range) kW 10.0 [ 4.0(Min.) - 11.2(Max.)]Nominal heating capacity (range) kW 11.2 [ 4.0(Min.) - 12.5(Max.)]
Power consumptionCooling
kW2.82
Heating 2.73Max power consumption 10.20
Running currentCooling
A4.1 / 4.3
Heating 4.0 / 4.2Inrush current, max current 5, 15
Power factorCooling
%99
Heating 98EER Cooling 3.55COP Heating 4.11
Sound power levelCooling
dB(A)
55 69Heating 56 70
Sound pressure levelCooling P-Hi: 41 Hi: 33 Me: 30 Lo: 26 54Heating P-Hi: 42 Hi: 33 Me: 28 Lo: 20 55
Silent mode sound pressure level — 48 /44(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm Unit 236 x 840 x 840Panel 35 x 950 x 950 845x970x370
Exterior appearance(Munsell color )(RAL color )
Plaster white(6.8Y8.9/0.2) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg Unit 19 Panel 5 78Compressor type & Q'ty — RMT5126SWP4 x 1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Pre - charged up to the piping length of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Turbo fan x1 Propeller fan x1Fan motor (Starting method) W 50 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 22 Hi: 16 Me: 13 Lo: 1075
Heating 73Available external static pressure Pa 0 0Outside air intake Possible —Air filter, Quality / Quantity Pocket plastic net x1(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-T-5AW-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35 (1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line φ 12.7 (1/2") ②φ12.7(1/2")x0.8 ①φ15.88(5/8")x1.0 φ15.88 (5/8")Connecting method Flare piping Flare piping
Attached length of piping m — —
Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP25(O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 850 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mmx 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-T-5W-E
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1G"×1(Option). ① : Pipe of O/U - Branch, ② : Pipe of Branch - I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 10 -
'19 • PAC-DB-308D
PJF000Z589 B
ModelItem
FDT125VNAWPVHIndoor unit FDT60VH (2 units) Outdoor unit FDC125VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 12.5 [ 5.0(Min.) - 14.0(Max.)]Nominal heating capacity (range) kW 14.0 [ 4.0(Min.) - 16.0(Max.)]
Power consumptionCooling
kW3.79
Heating 3.31Max power consumption 6.40
Running currentCooling
A16.6 / 17.4
Heating 14.5 / 15.2Inrush current, max current 5, 24
Power factorCooling
%99
Heating 99EER Cooling 3.30COP Heating 4.23
Sound power levelCooling
dB(A)
5871
Heating 59
Sound pressure levelCooling P-Hi: 44 Hi: 34 Me: 30 Lo: 27 54Heating P-Hi: 44 Hi: 34 Me: 30 Lo: 20 56
Silent mode sound pressure level — 48 /45(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm Unit 236 x 840 x 840Panel 35 x 950 x 950 845x970x370
Exterior appearance(Munsell color )(RAL color )
Plaster white(6.8Y8.9/0.2) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg Unit 21 Panel 5 77Compressor type & Q'ty — RMT5126SWP3 x 1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Pre - charged up to the piping length of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Turbo fan x1 Propeller fan x1Fan motor (Starting method) W 50 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 26 Hi: 17 Me: 14 Lo: 1175
Heating 73Available external static pressure Pa 0 0Outside air intake Possible —Air filter, Quality / Quantity Pocket plastic net x1(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-T-5AW-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35 (1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line φ 12.7 (1/2") ②φ12.7(1/2")x0.8 ①φ15.88(5/8")x1.0 φ15.88 (5/8")Connecting method Flare piping Flare piping
Attached length of piping m — —
Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP25(O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 850 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mmx 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-T-5W-E
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1G"×1(Option). ① : Pipe of O/U - Branch, ② : Pipe of Branch - I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 11 -
'19 • PAC-DB-308D
PJF000Z589 B
ModelItem
FDT125VSAWPVHIndoor unit FDT60VH (2 units) Outdoor unit FDC125VSA-W
Power source 3 Phase, 380 - 415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 12.5 [ 5.0(Min.) - 14.0(Max.)]Nominal heating capacity (range) kW 14.0 [ 4.0(Min.) - 16.0(Max.)]
Power consumptionCooling
kW3.79
Heating 3.31Max power consumption 10.20
Running currentCooling
A5.5 / 5.8
Heating 4.8 / 5.1Inrush current, max current 5, 15
Power factorCooling
%99
Heating 99EER Cooling 3.30COP Heating 4.23
Sound power levelCooling
dB(A)
5871
Heating 59
Sound pressure levelCooling P-Hi: 44 Hi: 34 Me: 30 Lo: 27 54Heating P-Hi: 44 Hi: 34 Me: 30 Lo: 20 56
Silent mode sound pressure level — 48 /45(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm Unit 236 x 840 x 840Panel 35 x 950 x 950 845x970x370
Exterior appearance(Munsell color )(RAL color )
Plaster white(6.8Y8.9/0.2) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg Unit 21 Panel 5 78Compressor type & Q'ty — RMT5126SWP4 x 1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Pre - charged up to the piping length of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Turbo fan x1 Propeller fan x1Fan motor (Starting method) W 50 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 26 Hi: 17 Me: 14 Lo: 1175
Heating 73Available external static pressure Pa 0 0Outside air intake Possible —Air filter, Quality / Quantity Pocket plastic net x1(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-T-5AW-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35 (1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line φ 12.7 (1/2") ②φ12.7(1/2")x0.8 ①φ15.88(5/8")x1.0 φ15.88 (5/8")Connecting method Flare piping Flare piping
Attached length of piping m — —
Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP25(O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 850 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mmx 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-T-5W-E
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1G"×1(Option). ① : Pipe of O/U - Branch, ② : Pipe of Branch - I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 12 -
'19 • PAC-DB-308D
PJF000Z589 B
ModelItem
FDT140VNAWPVHIndoor unit FDT71VH (2 units) Outdoor unit FDC140VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 13.6 [ 5.0(Min.) - 14.5(Max.)]Nominal heating capacity (range) kW 15.5 [ 4.0(Min.) - 16.5(Max.)]
Power consumptionCooling
kW4.22
Heating 3.57Max power consumption 6.40
Running currentCooling
A18.5 / 19.4
Heating 15.7 / 16.4Inrush current, max current 5, 24
Power factorCooling
%99
Heating 99EER Cooling 3.22COP Heating 4.34
Sound power levelCooling
dB(A)
59 72Heating 60 73
Sound pressure levelCooling
P-Hi: 46 Hi: 34 Me: 31 Lo: 2656
Heating 58Silent mode sound pressure level — 49 /45(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm Unit 236 x 840 x 840Panel 35 x 950 x 950 845x970x370
Exterior appearance(Munsell color )(RAL color )
Plaster white(6.8Y8.9/0.2) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg Unit 21 Panel 5 77Compressor type & Q'ty — RMT5126SWP3 x 1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Pre - charged up to the piping length of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Turbo fan x1 Propeller fan x1Fan motor (Starting method) W 50 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 28 Hi: 18 Me: 15 Lo: 1275
Heating 73Available external static pressure Pa 0 0Outside air intake Possible —Air filter, Quality / Quantity Pocket plastic net x1(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-T-5AW-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 9.52 (3/8") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line φ 15.88 (5/8") ②φ15.88(5/8")x1.0 ①φ15.88(5/8")x1.0 φ15.88 (5/8")Connecting method Flare piping Flare piping
Attached length of piping m — —
Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP25(O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 850 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mmx 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-T-5W-E
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1G"×1(Option). ① : Pipe of O/U - Branch, ② : Pipe of Branch - I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 13 -
'19 • PAC-DB-308D
PJF000Z589 B
ModelItem
FDT140VSAWPVHIndoor unit FDT71VH (2 units) Outdoor unit FDC140VSA-W
Power source 3 Phase, 380 - 415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 13.6 [ 5.0(Min.) - 14.5(Max.)]Nominal heating capacity (range) kW 15.5 [ 4.0(Min.) - 16.5(Max.)]
Power consumptionCooling
kW4.22
Heating 3.57Max power consumption 10.20
Running currentCooling
A6.2 / 6.5
Heating 5.2 / 5.5Inrush current, max current 5, 15
Power factorCooling
%99
Heating 99EER Cooling 3.22COP Heating 4.34
Sound power levelCooling
dB(A)
59 72Heating 60 73
Sound pressure levelCooling
P-Hi: 46 Hi: 34 Me: 31 Lo: 2656
Heating 58Silent mode sound pressure level — 49 /45(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm Unit 236 x 840 x 840Panel 35 x 950 x 950 845x970x370
Exterior appearance(Munsell color )(RAL color )
Plaster white(6.8Y8.9/0.2) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg Unit 21 Panel 5 78Compressor type & Q'ty — RMT5126SWP4 x 1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Pre - charged up to the piping length of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Turbo fan x1 Propeller fan x1Fan motor (Starting method) W 50 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 28 Hi: 18 Me: 15 Lo: 1275
Heating 73Available external static pressure Pa 0 0Outside air intake Possible —Air filter, Quality / Quantity Pocket plastic net x1(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-T-5AW-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 9.52 (3/8") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line φ 15.88 (5/8") ②φ15.88(5/8")x1.0 ①φ15.88(5/8")x1.0 φ15.88 (5/8")Connecting method Flare piping Flare piping
Attached length of piping m — —
Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP25(O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 850 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mmx 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-T-5W-E
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1G"×1(Option). ① : Pipe of O/U - Branch, ② : Pipe of Branch - I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 14 -
'19 • PAC-DB-308D
PJF000Z589 B
ModelItem
FDT140VNAWTVHIndoor unit FDT50VH (3 units) Outdoor unit FDC140VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 13.6 [ 5.0(Min.) - 14.5(Max.)]Nominal heating capacity (range) kW 15.5 [ 4.0(Min.) - 16.5(Max.)]
Power consumptionCooling
kW4.22
Heating 3.57Max power consumption 6.40
Running currentCooling
A18.5 / 19.4
Heating 15.7 / 16.4Inrush current, max current 5, 24
Power factorCooling
%99
Heating 99EER Cooling 3.22COP Heating 3.88
Sound power levelCooling
dB(A)
55 72Heating 56 73
Sound pressure levelCooling P-Hi: 41 Hi: 33 Me: 30 Lo: 26 56Heating P-Hi: 42 Hi: 33 Me: 28 Lo: 20 58
Silent mode sound pressure level — 49 /45(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm Unit 236 x 840 x 840Panel 35 x 950 x 950 845x970x370
Exterior appearance(Munsell color )(RAL color )
Plaster white(6.8Y8.9/0.2) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg Unit 19 Panel 5 77Compressor type & Q'ty — RMT5126SWP3 x 1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Pre - charged up to the piping length of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Turbo fan x1 Propeller fan x1Fan motor (Starting method) W 50 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 22 Hi: 16 Me: 13 Lo: 1075
Heating 73Available external static pressure Pa 0 0Outside air intake Possible —Air filter, Quality / Quantity Pocket plastic net x1(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-T-5AW-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35 (1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line φ 12.7 (1/2") ②φ12.7(1/2")x0.8 ①φ15.88(5/8")x1.0 φ15.88 (5/8")Connecting method Flare piping Flare piping
Attached length of piping m — —
Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP25(O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 850 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mmx 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-T-5W-E
The pipe length is 7.5m.
(c) Triple type
Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is three indoor units are combined and run together.(7) Branching pipe set "DIS-TB1G"×1(Option). ① : Pipe of O/U - Branch, ② : Pipe of Branch - I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 15 -
'19 • PAC-DB-308D
PJF000Z589 B
ModelItem
FDT140VSAWTVHIndoor unit FDT50VH (3 units) Outdoor unit FDC140VSA-W
Power source 3 Phase, 380 - 415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 13.6 [ 5.0(Min.) - 14.5(Max.)]Nominal heating capacity (range) kW 15.5 [ 4.0(Min.) - 16.5(Max.)]
Power consumptionCooling
kW4.22
Heating 3.57Max power consumption 10.20
Running currentCooling
A6.2 / 6.5
Heating 5.2 / 5.5Inrush current, max current 5, 15
Power factorCooling
%99
Heating 99EER Cooling 3.22COP Heating 3.88
Sound power levelCooling
dB(A)
55 72Heating 56 73
Sound pressure levelCooling P-Hi: 41 Hi: 33 Me: 30 Lo: 26 56Heating P-Hi: 42 Hi: 33 Me: 28 Lo: 20 58
Silent mode sound pressure level — 49 /45(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm Unit 236 x 840 x 840Panel 35 x 950 x 950 845x970x370
Exterior appearance(Munsell color )(RAL color )
Plaster white(6.8Y8.9/0.2) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg Unit 19 Panel 5 78Compressor type & Q'ty — RMT5126SWP4 x 1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Pre - charged up to the piping length of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Turbo fan x1 Propeller fan x1Fan motor (Starting method) W 50 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 22 Hi: 16 Me: 13 Lo: 1075
Heating 73Available external static pressure Pa 0 0Outside air intake Possible —Air filter, Quality / Quantity Pocket plastic net x1(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-T-5AW-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35 (1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line φ 12.7 (1/2") ②φ12.7(1/2")x0.8 ①φ15.88(5/8")x1.0 φ15.88 (5/8")Connecting method Flare piping Flare piping
Attached length of piping m — —
Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP25(O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 850 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mmx 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-T-5W-E
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is three indoor units are combined and run together.(7) Branching pipe set "DIS-TB1G"×1(Option). ① : Pipe of O/U - Branch, ② : Pipe of Branch - I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 16 -
'19 • PAC-DB-308D
PJF000Z517 B
ModelItem
FDTC100VNAWPVHIndoor unit FDTC50VH (2 units) Outdoor unit FDC100VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 10.0 [ 4.0(Min.) - 11.2(Max.)]Nominal heating capacity (range) kW 11.2 [ 4.0(Min.) - 12.5(Max.)]
Power consumptionCooling
kW3.15
Heating 3.05Max power consumption 6.40
Running currentCooling
A13.8 / 14.5
Heating 13.4 / 14.0Inrush current, max current 5, 24
Power factorCooling
%99
Heating 99EER Cooling 3.17COP Heating 3.67
Sound power levelCooling
dB(A)
5969
Heating 70
Sound pressure levelCooling
P-Hi: 44 Hi 40 Me: 35 Lo: 2754
Heating 55Silent mode sound pressure level — 48 / 44 (Normal / Silent)
Exterior dimensions (Height x Width x Depth) mm Unit 248 x 570 x 570Panel 10 x 620 x 620 845x970x370
Exterior appearance(Munsell color )(RAL color )
Fine snow(8.0Y9.3/0.1) near equivalent(RAL 9001) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg Unit 14 Panel 2.5 77Compressor type & Q'ty — RMT5126SWP3 x 1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m )Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Turbo fan x1 Propeller fan x 1Fan motor (Starting method) W 50 < Direct line start > 86 (Direct line start)
Air flow Cooling
m3/min P-Hi: 13 Hi: 11 Me: 9 Lo: 775
Heating 73Available external static pressure Pa 0 0Outside air intake Possible —Air filter, Quality / Quantity Pocket plastic net x1(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20 (Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A, RC-E5, RCH-E3 Wireless : RCN-TC-5AW-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35 (1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line I/U φ 12.7 (1/2") ②φ12.7(1/2")x0.8 ①φ15.88(5/8")x1.0 O/Uφ15.88 (5/8")Connecting method Flare piping Flare piping
Attached length of piping m — —
Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 ( Outdoor unit is higher ) / Max.15 ( Outdoor unit is lower ) Drain hose Hose connectable with VP25(O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 850 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ1.6mmx 3 cores + earth cable / Terminal block (Screw fixing type)IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts OA Spacer : TC-OAS-E2 , TC-OAD-E , Motion sensor : LB-TC-5W-E
The pipe length is 7.5m.
(2) Ceiling cassette-4 way compact type (FDTC) (a) Twin type
Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1G"×1(Option). ① : Pipe of O/U - Branch, ② : Pipe of Branch - I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 17 -
'19 • PAC-DB-308D
PJF000Z517 B
ModelItem
FDTC100VSAWPVHIndoor unit FDTC50VH (2 units) Outdoor unit FDC100VSA-W
Power source 3 Phase, 380 - 415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 10.0 [ 4.0(Min.) - 11.2(Max.)]Nominal heating capacity (range) kW 11.2 [ 4.0(Min.) - 12.5(Max.)]
Power consumptionCooling
kW3.15
Heating 3.05Max power consumption 10.20
Running currentCooling
A4.6 / 4.9
Heating 4.4 / 4.7Inrush current, max current 5, 15
Power factorCooling
%98
Heating 99EER Cooling 3.17COP Heating 3.67
Sound power levelCooling
dB(A)
5969
Heating 70
Sound pressure levelCooling
P-Hi: 44 Hi 40 Me: 35 Lo: 2754
Heating 55Silent mode sound pressure level — 48 / 44 (Normal / Silent)
Exterior dimensions (Height x Width x Depth) mm Unit 248 x 570 x 570Panel 10 x 620 x 620 845x970x370
Exterior appearance(Munsell color )(RAL color )
Fine snow(8.0Y9.3/0.1) near equivalent(RAL 9001) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg Unit 14 Panel 2.5 78Compressor type & Q'ty — RMT5126SWP4 x 1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m )Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Turbo fan x1 Propeller fan x 1Fan motor (Starting method) W 50 < Direct line start > 86 (Direct line start)
Air flow Cooling
m3/min P-Hi: 13 Hi: 11 Me: 9 Lo: 775
Heating 73Available external static pressure Pa 0 0Outside air intake Possible —Air filter, Quality / Quantity Pocket plastic net x1(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20 (Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A, RC-E5, RCH-E3 Wireless : RCN-TC-5AW-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35 (1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line I/U φ 12.7 (1/2") ②φ12.7(1/2")x0.8 ①φ15.88(5/8")x1.0 O/Uφ15.88 (5/8")Connecting method Flare piping Flare piping
Attached length of piping m — —
Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 ( Outdoor unit is higher ) / Max.15 ( Outdoor unit is lower ) Drain hose Hose connectable with VP25(O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 850 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ1.6mmx 3 cores + earth cable / Terminal block (Screw fixing type)IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts OA Spacer : TC-OAS-E2 , TC-OAD-E , Motion sensor : LB-TC-5W-E
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1G"×1(Option). ① : Pipe of O/U - Branch, ② : Pipe of Branch - I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 18 -
'19 • PAC-DB-308D
PJF000Z517 B
ModelItem
FDTC125VNAWPVHIndoor unit FDTC60VH (2 units) Outdoor unit FDC125VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 12.5 [ 5.0(Min.) - 14.0(Max.)]Nominal heating capacity (range) kW 14.0 [ 4.0(Min.) - 16.0(Max.)]
Power consumptionCooling
kW4.90
Heating 4.30Max power consumption 6.40
Running currentCooling
A21.5 / 22.5
Heating 18.9 / 19.7Inrush current, max current 5, 24
Power factorCooling
%99
Heating 99EER Cooling 2.55COP Heating 3.26
Sound power levelCooling
dB(A)
59 71Heating
Sound pressure levelCooling
P-Hi: 44 Hi 40 Me: 35 Lo: 2754
Heating 56Silent mode sound pressure level — 48 / 45 (Normal / Silent)
Exterior dimensions (Height x Width x Depth) mm Unit 248 x 570 x 570Panel 10 x 620 x 620 845x970x370
Exterior appearance(Munsell color )(RAL color )
Fine snow(8.0Y9.3/0.1) near equivalent(RAL 9001) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg Unit 14 Panel 2.5 77Compressor type & Q'ty — RMT5126SWP3 x 1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m )Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Turbo fan x1 Propeller fan x 1Fan motor (Starting method) W 50 < Direct line start > 86 (Direct line start)
Air flow Cooling
m3/min P-Hi: 13 Hi: 11 Me: 9 Lo: 775
Heating 73Available external static pressure Pa 0 0Outside air intake Possible —Air filter, Quality / Quantity Pocket plastic net x1(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20 (Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A, RC-E5, RCH-E3 Wireless : RCN-TC-5AW-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35 (1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line I/U φ 12.7 (1/2") ②φ12.7(1/2")x0.8 ①φ15.88(5/8")x1.0 O/Uφ15.88 (5/8")Connecting method Flare piping Flare piping
Attached length of piping m — —
Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 ( Outdoor unit is higher ) / Max.15 ( Outdoor unit is lower ) Drain hose Hose connectable with VP25(O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 850 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ1.6mmx 3 cores + earth cable / Terminal block (Screw fixing type)IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts OA Spacer : TC-OAS-E2 , TC-OAD-E , Motion sensor : LB-TC-5W-E
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1G"×1(Option). ① : Pipe of O/U - Branch, ② : Pipe of Branch - I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 19 -
'19 • PAC-DB-308D
PJF000Z517 B
ModelItem
FDTC125VSAWPVHIndoor unit FDTC60VH (2 units) Outdoor unit FDC125VSA-W
Power source 3 Phase, 380 - 415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 12.5 [ 5.0(Min.) - 14.0(Max.)]Nominal heating capacity (range) kW 14.0 [ 4.0(Min.) - 16.0(Max.)]
Power consumptionCooling
kW4.90
Heating 4.30Max power consumption 10.20
Running currentCooling
A7.1 / 7.5
Heating 6.3 / 6.6Inrush current, max current 5, 15
Power factorCooling
%99
Heating 99EER Cooling 2.55COP Heating 3.26
Sound power levelCooling
dB(A)
59 71Heating
Sound pressure levelCooling
P-Hi: 44 Hi 40 Me: 35 Lo: 2754
Heating 56Silent mode sound pressure level — 48 / 45 (Normal / Silent)
Exterior dimensions (Height x Width x Depth) mm Unit 248 x 570 x 570Panel 10 x 620 x 620 845x970x370
Exterior appearance(Munsell color )(RAL color )
Fine snow(8.0Y9.3/0.1) near equivalent(RAL 9001) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg Unit 14 Panel 2.5 78Compressor type & Q'ty — RMT5126SWP4 x 1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m )Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Turbo fan x1 Propeller fan x 1Fan motor (Starting method) W 50 < Direct line start > 86 (Direct line start)
Air flow Cooling
m3/min P-Hi: 13 Hi: 11 Me: 9 Lo: 775
Heating 73Available external static pressure Pa 0 0Outside air intake Possible —Air filter, Quality / Quantity Pocket plastic net x1(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20 (Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A, RC-E5, RCH-E3 Wireless : RCN-TC-5AW-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35 (1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line I/U φ 12.7 (1/2") ②φ12.7(1/2")x0.8 ①φ15.88(5/8")x1.0 O/Uφ15.88 (5/8")Connecting method Flare piping Flare piping
Attached length of piping m — —
Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 ( Outdoor unit is higher ) / Max.15 ( Outdoor unit is lower ) Drain hose Hose connectable with VP25(O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 850 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ1.6mmx 3 cores + earth cable / Terminal block (Screw fixing type)IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts OA Spacer : TC-OAS-E2 , TC-OAD-E , Motion sensor : LB-TC-5W-E
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1G"×1(Option). ① : Pipe of O/U - Branch, ② : Pipe of Branch - I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 20 -
'19 • PAC-DB-308D
PJF000Z517 B
ModelItem
FDTC140VNAWTVHIndoor unit FDTC50VH (3 units) Outdoor unit FDC140VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 13.6 [ 5.0(Min.) - 14.5(Max.)]Nominal heating capacity (range) kW 15.5 [ 4.0(Min.) - 16.5(Max.)]
Power consumptionCooling
kW4.75
Heating 4.60Max power consumption 6.40
Running currentCooling
A20.9 / 21.8
Heating 20.2 / 21.1Inrush current, max current 5, 24
Power factorCooling
%99
Heating 99EER Cooling 2.86COP Heating 3.37
Sound power levelCooling
dB(A)
5972
Heating 73
Sound pressure levelCooling
P-Hi: 44 Hi 40 Me: 35 Lo: 2756
Heating 58Silent mode sound pressure level — 49 / 45 (Normal / Silent)
Exterior dimensions (Height x Width x Depth) mm Unit 248 x 570 x 570Panel 10 x 620 x 620 845x970x370
Exterior appearance(Munsell color )(RAL color )
Fine snow(8.0Y9.3/0.1) near equivalent(RAL 9001) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg Unit 14 Panel 2.5 77Compressor type & Q'ty — RMT5126SWP3 x 1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m )Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Turbo fan x1 Propeller fan x 1Fan motor (Starting method) W 50 < Direct line start > 86 (Direct line start)
Air flow Cooling
m3/min P-Hi: 13 Hi: 11 Me: 9 Lo: 775
Heating 73Available external static pressure Pa 0 0Outside air intake Possible —Air filter, Quality / Quantity Pocket plastic net x1(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20 (Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A, RC-E5, RCH-E3 Wireless : RCN-TC-5AW-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35 (1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line I/U φ 12.7 (1/2") ②φ12.7(1/2")x0.8 ①φ15.88(5/8")x1.0 O/Uφ15.88 (5/8")Connecting method Flare piping Flare piping
Attached length of piping m — —
Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 ( Outdoor unit is higher ) / Max.15 ( Outdoor unit is lower ) Drain hose Hose connectable with VP25(O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 850 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ1.6mmx 3 cores + earth cable / Terminal block (Screw fixing type)IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts OA Spacer : TC-OAS-E2 , TC-OAD-E , Motion sensor : LB-TC-5W-E
The pipe length is 7.5m.
(b) Triple type
Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1G"×1(Option). ① : Pipe of O/U - Branch, ② : Pipe of Branch - I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 21 -
'19 • PAC-DB-308D
PJF000Z517 B
ModelItem
FDTC140VSAWTVHIndoor unit FDTC50VH (3 units) Outdoor unit FDC140VSA-W
Power source 3 Phase, 380 - 415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 13.6 [ 5.0(Min.) - 14.5(Max.)]Nominal heating capacity (range) kW 15.5 [ 4.0(Min.) - 16.5(Max.)]
Power consumptionCooling
kW4.75
Heating 4.60Max power consumption 10.20
Running currentCooling
A6.9 / 7.3
Heating 6.7 / 7.1Inrush current, max current 5, 15
Power factorCooling
%99
Heating 99EER Cooling 2.86COP Heating 3.37
Sound power levelCooling
dB(A)
5972
Heating 73
Sound pressure levelCooling
P-Hi: 44 Hi 40 Me: 35 Lo: 2756
Heating 58Silent mode sound pressure level — 49 / 45 (Normal / Silent)
Exterior dimensions (Height x Width x Depth) mm Unit 248 x 570 x 570Panel 10 x 620 x 620 845x970x370
Exterior appearance(Munsell color )(RAL color )
Fine snow(8.0Y9.3/0.1) near equivalent(RAL 9001) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg Unit 14 Panel 2.5 78Compressor type & Q'ty — RMT5126SWP4 x 1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m )Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Turbo fan x1 Propeller fan x 1Fan motor (Starting method) W 50 < Direct line start > 86 (Direct line start)
Air flow Cooling
m3/min P-Hi: 13 Hi: 11 Me: 9 Lo: 775
Heating 73Available external static pressure Pa 0 0Outside air intake Possible —Air filter, Quality / Quantity Pocket plastic net x1(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20 (Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A, RC-E5, RCH-E3 Wireless : RCN-TC-5AW-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35 (1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line I/U φ 12.7 (1/2") ②φ12.7(1/2")x0.8 ①φ15.88(5/8")x1.0 O/Uφ15.88 (5/8")Connecting method Flare piping Flare piping
Attached length of piping m — —
Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 ( Outdoor unit is higher ) / Max.15 ( Outdoor unit is lower ) Drain hose Hose connectable with VP25(O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 850 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ1.6mmx 3 cores + earth cable / Terminal block (Screw fixing type)IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts OA Spacer : TC-OAS-E2 , TC-OAD-E , Motion sensor : LB-TC-5W-E
Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1G"×1(Option). ① : Pipe of O/U - Branch, ② : Pipe of Branch - I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
The pipe length is 7.5m.
- 22 -
'19 • PAC-DB-308D
Notes (1) The data are measured at the following conditions.
PJG000Z625 A
ModelItem
FDU100VNAWVHIndoor unit FDU100VH Outdoor unit FDC100VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 10.0 [ 4.0(Min.) - 11.2(Max.)]Nominal heating capacity (range) kW 11.2 [ 4.0(Min.) - 12.5(Max.)]
Power consumptionCooling
kW2.99
Heating 2.66Max power consumption 6.40
Running currentCooling
A14.3 / 14.9
Heating 12.7 / 13.3Inrush current, max current 5, 26
Power factorCooling
%91
Heating 91EER Cooling 3.35COP Heating 4.21
Sound power levelCooling
dB(A)
6569
Heating 70
Sound pressure levelCooling
P-Hi: 44 Hi: 38 Me: 36 Lo: 3054
Heating 55Silent mode sound pressure level — 48 / 44(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 280 × 1,370 × 740 845 × 970 × 370Exterior appearance(Munsell color )(RAL color )
—Stucco white
(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 54 77Compressor type & Q'ty — RMT5126SWP3 ( Twin rotary type )×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 ( M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan ×3 Propeller fan ×1Fan motor (Starting method) W 100 + 130 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 36 Hi: 28 Me: 25 Lo: 1975
Heating 73Available external static pressure Pa Standard: 60 Max: 200 0Outside air intake Possible —Air filter, Quality / Quantity Procure locally —Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20 (Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A,RC-E5,RCH-E3 Wireless : RCN-KIT4-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 9.52 (3/8") Pipeφ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line φ 15.88 (5/8") φ15.88(5/8")x1.0 φ15.88 (5/8")Connecting method Flare piping Flare piping
Attached length of piping m — —
Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable VP25 (I.D.25, O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 600 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ1.6mmx 3 cores + earth cable / Terminal block (Screw fixing type)IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-KIT
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) When wireless remote control is used, fan is 3 speed setting (Hi-Me-Lo) only.(6) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.(7) The factory E.S.P. setting is set within the range of 80 - 150 Pa.If SW8-4 is turned to "ON",
E.S.P. setting range can be changed to 10 - 200 Pa.(For RC-EX3A and RC-E5 only)
ItemOperation
Indoor air temperature Outdoor air temperature External static pressure of indoor unit Standards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C
60PaISO5151-T1
Heating 20˚C — 7˚C 6˚C ISO5151-H1
(3) Duct connected-High static pressure type (FDU) Single type
The pipe length is 7.5m.
- 23 -
'19 • PAC-DB-308D
PJG000Z625 A
ModelItem
FDU100VSAWVHIndoor unit FDU100VH Outdoor unit FDC100VSA-W
Power source 3 Phase, 380 - 415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 10.0 [ 4.0(Min.) - 11.2(Max.)]Nominal heating capacity (range) kW 11.2 [ 4.0(Min.) - 12.5(Max.)]
Power consumptionCooling
kW2.99
Heating 2.66Max power consumption 10.20
Running currentCooling
A4.6 / 4.9
Heating 4.1 / 4.3Inrush current, max current 5, 17
Power factorCooling
%93
Heating 93EER Cooling 3.35COP Heating 4.21
Sound power levelCooling
dB(A)
6569
Heating 70
Sound pressure levelCooling
P-Hi: 44 Hi: 38 Me: 36 Lo: 3054
Heating 55Silent mode sound pressure level — 48 / 44(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 280 × 1,370 × 740 845 × 970 × 370Exterior appearance(Munsell color )(RAL color )
—Stucco white
(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 54 78Compressor type & Q'ty — RMT5126SWP4 ( Twin rotary type )×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 ( M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan ×3 Propeller fan ×1Fan motor (Starting method) W 100 + 130 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 36 Hi: 28 Me: 25 Lo: 1975
Heating 73Available external static pressure Pa Standard: 60 Max: 200 0Outside air intake Possible —Air filter, Quality / Quantity Procure locally —Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20 (Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A,RC-E5,RCH-E3 Wireless : RCN-KIT4-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 9.52 (3/8") Pipeφ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line φ 15.88 (5/8") φ15.88(5/8")x1.0 φ15.88 (5/8")Connecting method Flare piping Flare piping
Attached length of piping m — —
Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable VP25 (I.D.25, O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 600 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ1.6mmx 3 cores + earth cable / Terminal block (Screw fixing type)IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-KIT
Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) When wireless remote control is used, fan is 3 speed setting (Hi-Me-Lo) only.(6) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.(7) The factory E.S.P. setting is set within the range of 80 - 150 Pa.If SW8-4 is turned to "ON",
E.S.P. setting range can be changed to 10 - 200 Pa.(For RC-EX3A and RC-E5 only)
ItemOperation
Indoor air temperature Outdoor air temperature External static pressure of indoor unit Standards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C
60PaISO5151-T1
Heating 20˚C — 7˚C 6˚C ISO5151-H1
The pipe length is 7.5m.
- 24 -
'19 • PAC-DB-308D
PJG000Z625 A
ModelItem
FDU125VNAWVHIndoor unit FDU125VH Outdoor unit FDC125VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 12.5 [ 5.0(Min.) - 14.0(Max.)]Nominal heating capacity (range) kW 14.0 [ 4.0(Min.) - 16.0(Max.)]
Power consumptionCooling
kW4.36
Heating 3.69Max power consumption 6.40
Running currentCooling
A20.4 / 21.3
Heating 17.8 / 18.6Inrush current, max current 5, 26
Power factorCooling
%93
Heating 90EER Cooling 2.87COP Heating 3.79
Sound power levelCooling
dB(A)
67 71Heating
Sound pressure levelCooling
P-Hi: 45 Hi: 40 Me: 34 Lo: 2954
Heating 56Silent mode sound pressure level — 48 / 45 (Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 280 × 1,370 × 740 845 × 970 × 370Exterior appearance(Munsell color )(RAL color )
—Stucco white
(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 54 77Compressor type & Q'ty — RMT5126SWP3 ( Twin rotary type )×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 ( M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan ×3 Propeller fan ×1Fan motor (Starting method) W 100 + 200 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 39 Hi: 32 Me: 26 Lo: 2075
Heating 73Available external static pressure Pa Standard: 60 Max: 200 0Outside air intake Possible —Air filter, Quality / Quantity Procure locally —Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20 (Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A,RC-E5,RCH-E3 Wireless : RCN-KIT4-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 9.52 (3/8") Pipeφ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line φ 15.88 (5/8") φ15.88(5/8")x1.0 φ15.88 (5/8")Connecting method Flare piping Flare piping
Attached length of piping m — —
Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable VP25 (I.D.25, O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 600 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ1.6mmx 3 cores + earth cable / Terminal block (Screw fixing type)IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-KIT
Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) When wireless remote control is used, fan is 3 speed setting (Hi-Me-Lo) only.(6) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.(7) The factory E.S.P. setting is set within the range of 80 - 150 Pa.If SW8-4 is turned to "ON",
E.S.P. setting range can be changed to 10 - 200 Pa.(For RC-EX3A and RC-E5 only)
ItemOperation
Indoor air temperature Outdoor air temperature External static pressure of indoor unit Standards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C
60PaISO5151-T1
Heating 20˚C — 7˚C 6˚C ISO5151-H1
The pipe length is 7.5m.
- 25 -
'19 • PAC-DB-308D
PJG000Z625 A
ModelItem
FDU125VSAWVHIndoor unit FDU125VH Outdoor unit FDC125VSA-W
Power source 3 Phase, 380 - 415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 12.5 [ 5.0(Min.) - 14.0(Max.)]Nominal heating capacity (range) kW 14.0 [ 4.0(Min.) - 16.0(Max.)]
Power consumptionCooling
kW4.36
Heating 3.69Max power consumption 10.20
Running currentCooling
A6.8 / 7.2
Heating 5.9 / 6.2Inrush current, max current 5, 17
Power factorCooling
%92
Heating 90EER Cooling 2.87COP Heating 3.79
Sound power levelCooling
dB(A)
67 71Heating
Sound pressure levelCooling
P-Hi: 45 Hi: 40 Me: 34 Lo: 2954
Heating 56Silent mode sound pressure level — 48 / 45 (Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 280 × 1,370 × 740 845 × 970 × 370Exterior appearance(Munsell color )(RAL color )
—Stucco white
(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 54 78Compressor type & Q'ty — RMT5126SWP4 ( Twin rotary type )×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 ( M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan ×3 Propeller fan ×1Fan motor (Starting method) W 100 + 200 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 39 Hi: 32 Me: 26 Lo: 2075
Heating 73Available external static pressure Pa Standard: 60 Max: 200 0Outside air intake Possible —Air filter, Quality / Quantity Procure locally —Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20 (Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A,RC-E5,RCH-E3 Wireless : RCN-KIT4-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 9.52 (3/8") Pipeφ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line φ 15.88 (5/8") φ15.88(5/8")x1.0 φ15.88 (5/8")Connecting method Flare piping Flare piping
Attached length of piping m — —
Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable VP25 (I.D.25, O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 600 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ1.6mmx 3 cores + earth cable / Terminal block (Screw fixing type)IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-KIT
Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) When wireless remote control is used, fan is 3 speed setting (Hi-Me-Lo) only.(6) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.(7) The factory E.S.P. setting is set within the range of 80 - 150 Pa.If SW8-4 is turned to "ON",
E.S.P. setting range can be changed to 10 - 200 Pa.(For RC-EX3A and RC-E5 only)
ItemOperation
Indoor air temperature Outdoor air temperature External static pressure of indoor unit Standards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C
60PaISO5151-T1
Heating 20˚C — 7˚C 6˚C ISO5151-H1
The pipe length is 7.5m.
- 26 -
'19 • PAC-DB-308D
PJG000Z625 A
ModelItem
FDU140VNAWVHIndoor unit FDU140VH Outdoor unit FDC140VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 13.6 [ 5.0(Min.) - 14.5(Max.)]Nominal heating capacity (range) kW 15.5 [ 4.0(Min.) - 16.5(Max.)]
Power consumptionCooling
kW5.13
Heating 4.21Max power consumption 6.40
Running currentCooling
A23.7 / 24.8
Heating 20.3 / 21.3Inrush current, max current 5, 27
Power factorCooling
%94
Heating 90EER Cooling 2.65COP Heating 3.68
Sound power levelCooling
dB(A)
7072
Heating 73
Sound pressure levelCooling
P-Hi: 47 Hi: 40 Me: 35 Lo: 3056
Heating 58Silent mode sound pressure level — 49 / 45 (Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 280 × 1,370 × 740 845 × 970 × 370Exterior appearance(Munsell color )(RAL color )
—Stucco white
(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 54 77Compressor type & Q'ty — RMT5126SWP3 ( Twin rotary type )×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 ( M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan ×3 Propeller fan ×1Fan motor (Starting method) W 100 + 200 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 48 Hi: 35 Me: 28 Lo: 2275
Heating 73Available external static pressure Pa Standard: 60 Max: 200 0Outside air intake Possible —Air filter, Quality / Quantity Procure locally —Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20 (Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A,RC-E5,RCH-E3 Wireless : RCN-KIT4-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 9.52 (3/8") Pipeφ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line φ 15.88 (5/8") φ15.88(5/8")x1.0 φ15.88 (5/8")Connecting method Flare piping Flare piping
Attached length of piping m — —
Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable VP25 (I.D.25, O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 600 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ1.6mmx 3 cores + earth cable / Terminal block (Screw fixing type)IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-KIT
Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) When wireless remote control is used, fan is 3 speed setting (Hi-Me-Lo) only.(6) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.(7) The factory E.S.P. setting is set within the range of 80 - 150 Pa.If SW8-4 is turned to "ON",
E.S.P. setting range can be changed to 10 - 200 Pa.(For RC-EX3A and RC-E5 only)
ItemOperation
Indoor air temperature Outdoor air temperature External static pressure of indoor unit Standards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C
60PaISO5151-T1
Heating 20˚C — 7˚C 6˚C ISO5151-H1
The pipe length is 7.5m.
- 27 -
'19 • PAC-DB-308D
PJG000Z625 A
ModelItem
FDU140VSAWVHIndoor unit FDU140VH Outdoor unit FDC140VSA-W
Power source 3 Phase, 380 - 415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 13.6 [ 5.0(Min.) - 14.5(Max.)]Nominal heating capacity (range) kW 15.5 [ 4.0(Min.) - 16.5(Max.)]
Power consumptionCooling
kW5.13
Heating 4.21Max power consumption 10.20
Running currentCooling
A8.1 / 8.6
Heating 6.8 / 7.2Inrush current, max current 5, 18
Power factorCooling
%91
Heating 89EER Cooling 2.65COP Heating 3.68
Sound power levelCooling
dB(A)
7072
Heating 73
Sound pressure levelCooling
P-Hi: 47 Hi: 40 Me: 35 Lo: 3056
Heating 58Silent mode sound pressure level — 49 / 45 (Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 280 × 1,370 × 740 845 × 970 × 370Exterior appearance(Munsell color )(RAL color )
—Stucco white
(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 54 78Compressor type & Q'ty — RMT5126SWP4 ( Twin rotary type )×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 ( M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan ×3 Propeller fan ×1Fan motor (Starting method) W 100 + 200 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 48 Hi: 35 Me: 28 Lo: 2275
Heating 73Available external static pressure Pa Standard: 60 Max: 200 0Outside air intake Possible —Air filter, Quality / Quantity Procure locally —Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20 (Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A,RC-E5,RCH-E3 Wireless : RCN-KIT4-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 9.52 (3/8") Pipeφ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line φ 15.88 (5/8") φ15.88(5/8")x1.0 φ15.88 (5/8")Connecting method Flare piping Flare piping
Attached length of piping m — —
Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable VP25 (I.D.25, O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 600 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ1.6mmx 3 cores + earth cable / Terminal block (Screw fixing type)IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-KIT
Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) When wireless remote control is used, fan is 3 speed setting (Hi-Me-Lo) only.(6) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.(7) The factory E.S.P. setting is set within the range of 80 - 150 Pa.If SW8-4 is turned to "ON",
E.S.P. setting range can be changed to 10 - 200 Pa.(For RC-EX3A and RC-E5 only)
ItemOperation
Indoor air temperature Outdoor air temperature External static pressure of indoor unit Standards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C
60PaISO5151-T1
Heating 20˚C — 7˚C 6˚C ISO5151-H1
The pipe length is 7.5m.
- 28 -
'19 • PAC-DB-308D
PJG000Z491 B
ModelItem
FDUM100VNAWVHIndoor unit FDUM100VH Outdoor unit FDC100VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 10.0 [ 4.0(Min.) - 11.2(Max.)]Nominal heating capacity (range) kW 11.2 [ 4.0(Min.) - 12.5(Max.)]
Power consumptionCooling
kW2.99
Heating 2.66Max power consumption 6.40
Running currentCooling
A14.3 / 14.9
Heating 12.7 / 13.3Inrush current, max current 5, 26
Power factorCooling
%91
Heating 91EER Cooling 3.35COP Heating 4.21
Sound power levelCooling
dB(A)
6569
Heating 70
Sound pressure levelCooling
P-Hi: 44 Hi: 38 Me: 36 Lo: 3054
Heating 55Silent mode sound pressure level — 48 / 44 (Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 280 × 1,370 × 740 845 × 970 × 370Exterior appearance(Munsell color )(RAL color )
—Stucco white
(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 54 77Compressor type & Q'ty — RMT5126SWP3 ( Twin rotary type )×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 ( M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan ×3 Propeller fan ×1Fan motor (Starting method) W 100 + 130 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 36 Hi: 28 Me: 25 Lo: 1975
Heating 73Available external static pressure Pa Standard: 60 Max: 100 0Outside air intake Possible —Air filter, Quality / Quantity Procure locally —Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20 (Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A,RC-E5,RCH-E3 Wireless : RCN-KIT4-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 9.52 (3/8") Pipeφ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line φ 15.88 (5/8") φ15.88(5/8")x1.0 φ15.88 (5/8")Connecting method Flare piping Flare pipingInsulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable VP25 (I.D.25, O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 600 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ1.6mm×3 cores + earth cable / Terminal block (Screw fixing type)IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Filter set : UM-FL3EF , Motion sensor : LB-KIT
Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.(6) Static pressure of option air filter "UM-FL3EF" is 5Pa initially.(7) The external static pressure setting can be changed to 10-100Pa. (For RC-EX3A and RC-E5 only)
ItemOperation
Indoor air temperature Outdoor air temperature External static pressure of indoor unit Standards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C
60PaISO5151-T1
Heating 20˚C — 7˚C 6˚C ISO5151-H1
(4) Duct connected-Low / Middle static pressure type (FDUM)(a) Single type
The pipe length is 7.5m.
- 29 -
'19 • PAC-DB-308D
PJG000Z491 B
ModelItem
FDUM100VSAWVHIndoor unit FDUM100VH Outdoor unit FDC100VSA-W
Power source 3 Phase, 380 - 415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 10.0 [ 4.0(Min.) - 11.2(Max.)]Nominal heating capacity (range) kW 11.2 [ 4.0(Min.) - 12.5(Max.)]
Power consumptionCooling
kW2.99
Heating 2.66Max power consumption 10.20
Running currentCooling
A4.6 / 4.9
Heating 4.1 / 4.3Inrush current, max current 5, 17
Power factorCooling
%93
Heating 93EER Cooling 3.35COP Heating 4.21
Sound power levelCooling
dB(A)
6569
Heating 70
Sound pressure levelCooling
P-Hi: 44 Hi: 38 Me: 36 Lo: 3054
Heating 55Silent mode sound pressure level — 48 / 44 (Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 280 × 1,370 × 740 845 × 970 × 370Exterior appearance(Munsell color )(RAL color )
—Stucco white
(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 54 78Compressor type & Q'ty — RMT5126SWP4 ( Twin rotary type )×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 ( M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan ×3 Propeller fan ×1Fan motor (Starting method) W 100 + 130 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 36 Hi: 28 Me: 25 Lo: 1975
Heating 73Available external static pressure Pa Standard: 60 Max: 100 0Outside air intake Possible —Air filter, Quality / Quantity Procure locally —Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20 (Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A,RC-E5,RCH-E3 Wireless : RCN-KIT4-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 9.52 (3/8") Pipeφ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line φ 15.88 (5/8") φ15.88(5/8")x1.0 φ15.88 (5/8")Connecting method Flare piping Flare pipingInsulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable VP25 (I.D.25, O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 600 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ1.6mm×3 cores + earth cable / Terminal block (Screw fixing type)IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Filter set : UM-FL3EF , Motion sensor : LB-KIT
Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.(6) Static pressure of option air filter "UM-FL3EF" is 5Pa initially.(7) The external static pressure setting can be changed to 10-100Pa. (For RC-EX3A and RC-E5 only)
ItemOperation
Indoor air temperature Outdoor air temperature External static pressure of indoor unit Standards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C
60PaISO5151-T1
Heating 20˚C — 7˚C 6˚C ISO5151-H1
The pipe length is 7.5m.
- 30 -
'19 • PAC-DB-308D
PJG000Z491 B
ModelItem
FDUM125VNAWVHIndoor unit FDUM125VH Outdoor unit FDC125VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 12.5 [ 5.0(Min.) - 14.0(Max.)]Nominal heating capacity (range) kW 14.0 [ 4.0(Min.) - 16.0(Max.)]
Power consumptionCooling
kW4.36
Heating 3.69Max power consumption 6.40
Running currentCooling
A20.4 / 21.3
Heating 17.8 / 18.6Inrush current, max current 5, 26
Power factorCooling
%93
Heating 90EER Cooling 2.87COP Heating 3.79
Sound power levelCooling
dB(A)
67 71Heating
Sound pressure levelCooling
P-Hi: 45 Hi: 40 Me: 34 Lo: 2954
Heating 56Silent mode sound pressure level — 48 / 45 (Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 280 × 1,370 × 740 845 × 970 × 370Exterior appearance(Munsell color )(RAL color )
—Stucco white
(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 54 77Compressor type & Q'ty — RMT5126SWP3 ( Twin rotary type )×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 ( M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan ×3 Propeller fan ×1Fan motor (Starting method) W 100 + 200 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 39 Hi: 32 Me: 26 Lo: 2075
Heating 73Available external static pressure Pa Standard: 60 Max: 100 0Outside air intake Possible —Air filter, Quality / Quantity Procure locally —Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20 (Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A,RC-E5,RCH-E3 Wireless : RCN-KIT4-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 9.52 (3/8") Pipeφ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line φ 15.88 (5/8") φ15.88(5/8")x1.0 φ15.88 (5/8")Connecting method Flare piping Flare pipingInsulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable VP25 (I.D.25, O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 600 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ1.6mm×3 cores + earth cable / Terminal block (Screw fixing type)IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Filter set : UM-FL3EF , Motion sensor : LB-KIT
Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.(6) Static pressure of option air filter "UM-FL3EF" is 5Pa initially.(7) The external static pressure setting can be changed to 10-100Pa. (For RC-EX3A and RC-E5 only)
ItemOperation
Indoor air temperature Outdoor air temperature External static pressure of indoor unit Standards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C
60PaISO5151-T1
Heating 20˚C — 7˚C 6˚C ISO5151-H1
The pipe length is 7.5m.
- 31 -
'19 • PAC-DB-308D
PJG000Z491 B
ModelItem
FDUM125VSAWVHIndoor unit FDUM125VH Outdoor unit FDC125VSA-W
Power source 3 Phase, 380 - 415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 12.5 [ 5.0(Min.) - 14.0(Max.)]Nominal heating capacity (range) kW 14.0 [ 4.0(Min.) - 16.0(Max.)]
Power consumptionCooling
kW4.36
Heating 3.69Max power consumption 10.20
Running currentCooling
A6.8 / 7.2
Heating 5.9 / 6.2Inrush current, max current 5, 17
Power factorCooling
%92
Heating 90EER Cooling 2.87COP Heating 3.79
Sound power levelCooling
dB(A)
67 71Heating
Sound pressure levelCooling
P-Hi: 45 Hi: 40 Me: 34 Lo: 2954
Heating 56Silent mode sound pressure level — 48 / 45 (Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 280 × 1,370 × 740 845 × 970 × 370Exterior appearance(Munsell color )(RAL color )
—Stucco white
(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 54 78Compressor type & Q'ty — RMT5126SWP4 ( Twin rotary type )×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 ( M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan ×3 Propeller fan ×1Fan motor (Starting method) W 100 + 200 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 39 Hi: 32 Me: 26 Lo: 2075
Heating 73Available external static pressure Pa Standard: 60 Max: 100 0Outside air intake Possible —Air filter, Quality / Quantity Procure locally —Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20 (Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A,RC-E5,RCH-E3 Wireless : RCN-KIT4-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 9.52 (3/8") Pipeφ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line φ 15.88 (5/8") φ15.88(5/8")x1.0 φ15.88 (5/8")Connecting method Flare piping Flare pipingInsulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable VP25 (I.D.25, O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 600 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ1.6mm×3 cores + earth cable / Terminal block (Screw fixing type)IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Filter set : UM-FL3EF , Motion sensor : LB-KIT
Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.(6) Static pressure of option air filter "UM-FL3EF" is 5Pa initially.(7) The external static pressure setting can be changed to 10-100Pa. (For RC-EX3A and RC-E5 only)
ItemOperation
Indoor air temperature Outdoor air temperature External static pressure of indoor unit Standards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C
60PaISO5151-T1
Heating 20˚C — 7˚C 6˚C ISO5151-H1
The pipe length is 7.5m.
- 32 -
'19 • PAC-DB-308D
PJG000Z491 B
ModelItem
FDUM140VNAWVHIndoor unit FDUM140VH Outdoor unit FDC140VNA-W
Power source 1 Phase, 220-240V - 50Hz / 220V - 60Hz
Operation data
Nominal cooling capacity (range) kW 13.6 [ 5.0(Min.) - 14.5(Max.)]Nominal heating capacity (range) kW 15.5 [ 4.0(Min.) - 16.5(Max.)]
Power consumptionCooling
kW5.13
Heating 4.21Max power consumption 6.40
Running currentCooling
A23.7 / 24.8
Heating 20.3 / 21.3Inrush current, max current 5, 27
Power factorCooling
%94
Heating 90EER Cooling 2.65COP Heating 3.68
Sound power levelCooling
dB(A)
7072
Heating 73
Sound pressure levelCooling
P-Hi: 47 Hi: 40 Me: 35 Lo: 3056
Heating 58Silent mode sound pressure level — 49 / 45 (Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 280 × 1,370 × 740 845 × 970 × 370Exterior appearance(Munsell color )(RAL color )
—Stucco white
(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 54 77Compressor type & Q'ty — RMT5126SWP3 ( Twin rotary type )×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 ( M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan ×3 Propeller fan ×1Fan motor (Starting method) W 100 + 200 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 48 Hi: 35 Me: 28 Lo: 2275
Heating 73Available external static pressure Pa Standard: 60 Max: 100 0Outside air intake Possible —Air filter, Quality / Quantity Procure locally —Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20 (Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A,RC-E5,RCH-E3 Wireless : RCN-KIT4-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 9.52 (3/8") Pipeφ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line φ 15.88 (5/8") φ15.88(5/8")x1.0 φ15.88 (5/8")Connecting method Flare piping Flare pipingInsulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable VP25 (I.D.25, O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 600 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ1.6mm×3 cores + earth cable / Terminal block (Screw fixing type)IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Filter set : UM-FL3EF , Motion sensor : LB-KIT
Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.(6) Static pressure of option air filter "UM-FL3EF" is 5Pa initially.(7) The external static pressure setting can be changed to 10-100Pa. (For RC-EX3A and RC-E5 only)
ItemOperation
Indoor air temperature Outdoor air temperature External static pressure of indoor unit Standards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C
60PaISO5151-T1
Heating 20˚C — 7˚C 6˚C ISO5151-H1
The pipe length is 7.5m.
- 33 -
'19 • PAC-DB-308D
PJG000Z491 B
ModelItem
FDUM140VSAWVHIndoor unit FDUM140VH Outdoor unit FDC140VSA-W
Power source 3 Phase, 380 - 415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 13.6 [ 5.0(Min.) - 14.5(Max.)]Nominal heating capacity (range) kW 15.5 [ 4.0(Min.) - 16.5(Max.)]
Power consumptionCooling
kW5.13
Heating 4.21Max power consumption 10.20
Running currentCooling
A8.1 / 8.6
Heating 6.8 / 7.2Inrush current, max current 5, 18
Power factorCooling
%91
Heating 89EER Cooling 2.65COP Heating 3.68
Sound power levelCooling
dB(A)
7072
Heating 73
Sound pressure levelCooling
P-Hi: 47 Hi: 40 Me: 35 Lo: 3056
Heating 58Silent mode sound pressure level — 49 / 45 (Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 280 × 1,370 × 740 845 × 970 × 370Exterior appearance(Munsell color )(RAL color )
—Stucco white
(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 54 78Compressor type & Q'ty — RMT5126SWP4 ( Twin rotary type )×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 ( M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan ×3 Propeller fan ×1Fan motor (Starting method) W 100 + 200 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 48 Hi: 35 Me: 28 Lo: 2275
Heating 73Available external static pressure Pa Standard: 60 Max: 100 0Outside air intake Possible —Air filter, Quality / Quantity Procure locally —Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20 (Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A,RC-E5,RCH-E3 Wireless : RCN-KIT4-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 9.52 (3/8") Pipeφ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line φ 15.88 (5/8") φ15.88(5/8")x1.0 φ15.88 (5/8")Connecting method Flare piping Flare pipingInsulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable VP25 (I.D.25, O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 600 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ1.6mm×3 cores + earth cable / Terminal block (Screw fixing type)IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Filter set : UM-FL3EF , Motion sensor : LB-KIT
Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.(6) Static pressure of option air filter "UM-FL3EF" is 5Pa initially.(7) The external static pressure setting can be changed to 10-100Pa. (For RC-EX3A and RC-E5 only)
ItemOperation
Indoor air temperature Outdoor air temperature External static pressure of indoor unit Standards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C
60PaISO5151-T1
Heating 20˚C — 7˚C 6˚C ISO5151-H1
The pipe length is 7.5m.
- 34 -
'19 • PAC-DB-308D
PJG000Z491 B
ModelItem
FDUM100VNAWPVHIndoor unit FDUM50VH (2 units) Outdoor unit FDC100VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 10.0 [ 4.0(Min.) - 11.2(Max.)]Nominal heating capacity (range) kW 11.2 [ 4.0(Min.) - 12.5(Max.)]
Power consumptionCooling
kW3.25
Heating 3.04Max power consumption 6.40
Running currentCooling
A14.6 / 15.2
Heating 13.6 / 14.2Inrush current, max current 5, 26
Power factorCooling
%97
Heating 97EER Cooling 3.08COP Heating 3.68
Sound power levelCooling
dB(A)
6069
Heating 70
Sound pressure levelCooling
P-Hi: 37 Hi: 32 Me: 29 Lo: 2654
Heating 55Silent mode sound pressure level — 48 / 44 (Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 280 × 750 × 635 845 × 970 × 370Exterior appearance(Munsell color )(RAL color )
—Stucco white
(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 29 77Compressor type & Q'ty — RMT5126SWP3 ( Twin rotary type )×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 ( M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan ×1 Propeller fan ×1Fan motor (Starting method) W 100 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 13 Hi: 10 Me: 9 Lo: 875
Heating 73Available external static pressure Pa Standard: 35 Max: 100 0Outside air intake Possible —Air filter, Quality / Quantity Procure locally —Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20 (Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A,RC-E5,RCH-E3 Wireless : RCN-KIT4-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35 (1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line φ 12.7 (1/2") ②φ12.7(1/2")x0.8 ①φ15.88(5/8")x1.0 φ15.88 (5/8")Connecting method Flare piping Flare pipingInsulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable VP25 (I.D.25, O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 600 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ1.6mm×3 cores + earth cable / Terminal block (Screw fixing type)IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Filter set : UM-FL1EF , Motion sensor : LB-KIT
(b) Twin type
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1G"×1(Option). ① : Pipe of O/U-Branch,② : Pipe of Branch-I/U(8) Static pressure of option air filter "UM-FL1EF" is 5Pa initially.(9) The external static pressure setting can be changed to 10-100Pa. (For RC-EX3A and RC-E5 only)
ItemOperation
Indoor air temperature Outdoor air temperature External static pressure of indoor unit Standards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C
35PaISO5151-T1
Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 35 -
'19 • PAC-DB-308D
PJG000Z491 B
ModelItem
FDUM100VSAWPVHIndoor unit FDUM50VH (2 units) Outdoor unit FDC100VSA-W
Power source 3 Phase, 380-415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 10.0 [ 4.0(Min.) - 11.2(Max.)]Nominal heating capacity (range) kW 11.2 [ 4.0(Min.) - 12.5(Max.)]
Power consumptionCooling
kW3.25
Heating 3.04Max power consumption 10.20
Running currentCooling
A4.9 / 5.2
Heating 4.6 / 4.8Inrush current, max current 5, 17
Power factorCooling
%95
Heating 96EER Cooling 3.08COP Heating 3.68
Sound power levelCooling
dB(A)
6069
Heating 70
Sound pressure levelCooling
P-Hi: 37 Hi: 32 Me: 29 Lo: 2654
Heating 55Silent mode sound pressure level — 48 / 44 (Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 280 × 750 × 635 845 × 970 × 370Exterior appearance(Munsell color )(RAL color )
—Stucco white
(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 29 78Compressor type & Q'ty — RMT5126SWP4 ( Twin rotary type )×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 ( M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan ×1 Propeller fan ×1Fan motor (Starting method) W 100 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 13 Hi: 10 Me: 9 Lo: 875
Heating 73Available external static pressure Pa Standard: 35 Max: 100 0Outside air intake Possible —Air filter, Quality / Quantity Procure locally —Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20 (Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A,RC-E5,RCH-E3 Wireless : RCN-KIT4-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35 (1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line φ 12.7 (1/2") ②φ12.7(1/2")x0.8 ①φ15.88(5/8")x1.0 φ15.88 (5/8")Connecting method Flare piping Flare pipingInsulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable VP25 (I.D.25, O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 600 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ1.6mm×3 cores + earth cable / Terminal block (Screw fixing type)IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Filter set : UM-FL1EF , Motion sensor : LB-KIT
Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1G"×1(Option). ① : Pipe of O/U-Branch,② : Pipe of Branch-I/U(8) Static pressure of option air filter "UM-FL1EF" is 5Pa initially.(9) The external static pressure setting can be changed to 10-100Pa. (For RC-EX3A and RC-E5 only)
ItemOperation
Indoor air temperature Outdoor air temperature External static pressure of indoor unit Standards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C
35PaISO5151-T1
Heating 20˚C — 7˚C 6˚C ISO5151-H1
The pipe length is 7.5m.
- 36 -
'19 • PAC-DB-308D
PJG000Z491 B
ModelItem
FDUM125VNAWPVHIndoor unit FDUM60VH (2 units) Outdoor unit FDC125VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 12.5 [ 5.0(Min.) - 14.0(Max.)]Nominal heating capacity (range) kW 14.0 [ 4.0(Min.) - 16.0(Max.)]
Power consumptionCooling
kW4.53
Heating 3.52Max power consumption 6.40
Running currentCooling
A20.3 / 21.2
Heating 15.8 / 16.5Inrush current, max current 5, 26
Power factorCooling
%97
Heating 97EER Cooling 2.76COP Heating 3.98
Sound power levelCooling
dB(A)
60 71Heating
Sound pressure levelCooling
P-Hi: 36 Hi: 31 Me: 28 Lo: 2554
Heating 56Silent mode sound pressure level — 48 / 45 (Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 280 × 950 × 635 845 × 970 × 370Exterior appearance(Munsell color )(RAL color )
—Stucco white
(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 34 77Compressor type & Q'ty — RMT5126SWP3 ( Twin rotary type )×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 ( M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan ×2 Propeller fan ×1Fan motor (Starting method) W 130 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 20 Hi: 15 Me: 13 Lo: 1075
Heating 73Available external static pressure Pa Standard: 35 Max: 100 0Outside air intake Possible —Air filter, Quality / Quantity Procure locally —Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20 (Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A,RC-E5,RCH-E3 Wireless : RCN-KIT4-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35 (1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line φ 12.7 (1/2") ②φ12.7(1/2")x0.8 ①φ15.88(5/8")x1.0 φ15.88 (5/8")Connecting method Flare piping Flare pipingInsulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable VP25 (I.D.25, O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 600 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ1.6mm×3 cores + earth cable / Terminal block (Screw fixing type)IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Filter set : UM-FL2EF , Motion sensor : LB-KIT
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1G"×1(Option). ① : Pipe of O/U-Branch,② : Pipe of Branch-I/U(8) Static pressure of option air filter "UM-FL2EF" is 5Pa initially.(9) The external static pressure setting can be changed to 10-100Pa. (For RC-EX3A and RC-E5 only)
ItemOperation
Indoor air temperature Outdoor air temperature External static pressure of indoor unit Standards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C
35PaISO5151-T1
Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 37 -
'19 • PAC-DB-308D
PJG000Z491 B
ModelItem
FDUM125VSAWPVHIndoor unit FDUM60VH (2 units) Outdoor unit FDC125VSA-W
Power source 3 Phase, 380-415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 12.5 [ 5.0(Min.) - 14.0(Max.)]Nominal heating capacity (range) kW 14.0 [ 4.0(Min.) - 16.0(Max.)]
Power consumptionCooling
kW4.53
Heating 3.52Max power consumption 10.20
Running currentCooling
A6.7 / 7.0
Heating 5.2 / 5.5Inrush current, max current 5, 17
Power factorCooling
%98
Heating 97EER Cooling 2.76COP Heating 3.98
Sound power levelCooling
dB(A)
60 71Heating
Sound pressure levelCooling
P-Hi: 36 Hi: 31 Me: 28 Lo: 2554
Heating 56Silent mode sound pressure level — 48 / 45 (Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 280 × 950 × 635 845 × 970 × 370Exterior appearance(Munsell color )(RAL color )
—Stucco white
(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 34 78Compressor type & Q'ty — RMT5126SWP4 ( Twin rotary type )×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 ( M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan ×2 Propeller fan ×1Fan motor (Starting method) W 130 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 20 Hi: 15 Me: 13 Lo: 1075
Heating 73Available external static pressure Pa Standard: 35 Max: 100 0Outside air intake Possible —Air filter, Quality / Quantity Procure locally —Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20 (Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A,RC-E5,RCH-E3 Wireless : RCN-KIT4-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35 (1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line φ 12.7 (1/2") ②φ12.7(1/2")x0.8 ①φ15.88(5/8")x1.0 φ15.88 (5/8")Connecting method Flare piping Flare pipingInsulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable VP25 (I.D.25, O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 600 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ1.6mm×3 cores + earth cable / Terminal block (Screw fixing type)IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Filter set : UM-FL2EF , Motion sensor : LB-KIT
Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1G"×1(Option). ① : Pipe of O/U-Branch,② : Pipe of Branch-I/U(8) Static pressure of option air filter "UM-FL2EF" is 5Pa initially.(9) The external static pressure setting can be changed to 10-100Pa. (For RC-EX3A and RC-E5 only)
ItemOperation
Indoor air temperature Outdoor air temperature External static pressure of indoor unit Standards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C
35PaISO5151-T1
Heating 20˚C — 7˚C 6˚C ISO5151-H1
The pipe length is 7.5m.
- 38 -
'19 • PAC-DB-308D
PJG000Z491 B
ModelItem
FDUM140VNAWTVHIndoor unit FDUM71VH (2 units) Outdoor unit FDC140VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 13.6 [ 5.0(Min.) - 14.5(Max.)]Nominal heating capacity (range) kW 15.5 [ 4.0(Min.) - 16.5(Max.)]
Power consumptionCooling
kW5.02
Heating 4.20Max power consumption 6.40
Running currentCooling
A22.5 / 23.5
Heating 18.8 / 19.7Inrush current, max current 5, 27
Power factorCooling
%97
Heating 97EER Cooling 2.71COP Heating 3.69
Sound power levelCooling
dB(A)
6572
Heating 73
Sound pressure levelCooling
P-Hi: 38 Hi: 33 Me: 29 Lo: 2556
Heating 58Silent mode sound pressure level — 49 / 45 (Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 280 × 950 × 635 845 × 970 × 370Exterior appearance(Munsell color )(RAL color )
—Stucco white
(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 34 77Compressor type & Q'ty — RMT5126SWP3 ( Twin rotary type )×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 ( M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan ×2 Propeller fan ×1Fan motor (Starting method) W 130 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 24 Hi: 19 Me: 15 Lo: 1075
Heating 73Available external static pressure Pa Standard: 35 Max: 100 0Outside air intake Possible —Air filter, Quality / Quantity Procure locally —Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20 (Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A,RC-E5,RCH-E3 Wireless : RCN-KIT4-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 9.52 (3/8") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line φ 15.88 (5/8") ②φ15.88(5/8")x1.0 ①φ15.88(5/8")x1.0 φ15.88 (5/8")Connecting method Flare piping Flare pipingInsulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable VP25 (I.D.25, O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 600 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ1.6mm×3 cores + earth cable / Terminal block (Screw fixing type)IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Filter set : UM-FL2EF , Motion sensor : LB-KIT
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1G"×1(Option). ① : Pipe of O/U-Branch,② : Pipe of Branch-I/U(8) Static pressure of option air filter "UM-FL2EF" is 5Pa initially.(9) The external static pressure setting can be changed to 10-100Pa. (For RC-EX3A and RC-E5 only)
ItemOperation
Indoor air temperature Outdoor air temperature External static pressure of indoor unit Standards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C
35PaISO5151-T1
Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 39 -
'19 • PAC-DB-308D
PJG000Z491 B
ModelItem
FDUM140VSAWPVHIndoor unit FDUM71VH (2 units) Outdoor unit FDC140VSA-W
Power source 3 Phase, 380 - 415V 50Hz / 380V 60H
Operation data
Nominal cooling capacity (range) kW 13.6 [ 5.0(Min.) - 14.5(Max.)]Nominal heating capacity (range) kW 15.5 [ 4.0(Min.) - 16.5(Max.)]
Power consumptionCooling
kW5.02
Heating 4.20Max power consumption 10.20
Running currentCooling
A7.5 / 7.9
Heating 6.1 / 6.4Inrush current, max current 5, 18
Power factorCooling
%97
Heating 99EER Cooling 2.71COP Heating 3.69
Sound power levelCooling
dB(A)
6572
Heating 73
Sound pressure levelCooling
P-Hi: 38 Hi: 33 Me: 29 Lo: 2556
Heating 58Silent mode sound pressure level — 49 / 45 (Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 280 × 950 × 635 845 × 970 × 370Exterior appearance(Munsell color )(RAL color )
—Stucco white
(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 34 78Compressor type & Q'ty — RMT5126SWP4 ( Twin rotary type )×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 ( M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan ×2 Propeller fan ×1Fan motor (Starting method) W 130 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 24 Hi: 19 Me: 15 Lo: 1075
Heating 73Available external static pressure Pa Standard: 35 Max: 100 0Outside air intake Possible —Air filter, Quality / Quantity Procure locally —Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20 (Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A,RC-E5,RCH-E3 Wireless : RCN-KIT4-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 9.52 (3/8") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line φ 15.88 (5/8") ②φ15.88(5/8")x1.0 ①φ15.88(5/8")x1.0 φ15.88 (5/8")Connecting method Flare piping Flare pipingInsulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable VP25 (I.D.25, O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 600 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ1.6mm×3 cores + earth cable / Terminal block (Screw fixing type)IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Filter set : UM-FL2EF , Motion sensor : LB-KIT
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1G"×1(Option). ① : Pipe of O/U-Branch,② : Pipe of Branch-I/U(8) Static pressure of option air filter "UM-FL2EF" is 5Pa initially.(9) The external static pressure setting can be changed to 10-100Pa. (For RC-EX3A and RC-E5 only)
ItemOperation
Indoor air temperature Outdoor air temperature External static pressure of indoor unit Standards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C
35PaISO5151-T1
Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 40 -
'19 • PAC-DB-308D
PJG000Z491 B
ModelItem
FDUM140VNAWTVHIndoor unit FDUM50VH (3 units) Outdoor unit FDC140VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 13.6 [ 5.0(Min.) - 14.5(Max.)]Nominal heating capacity (range) kW 15.5 [ 4.0(Min.) - 16.5(Max.)]
Power consumptionCooling
kW5.02
Heating 4.20Max power consumption 6.40
Running currentCooling
A22.5 / 23.5
Heating 18.8 / 19.7Inrush current, max current 5, 27
Power factorCooling
%97
Heating 97EER Cooling 2.71COP Heating 3.69
Sound power levelCooling
dB(A)
6072
Heating 73
Sound pressure levelCooling
P-Hi: 37 Hi: 32 Me: 29 Lo: 2656
Heating 58Silent mode sound pressure level — 49 / 45 (Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 280 × 750 × 635 845 × 970 × 370Exterior appearance(Munsell color )(RAL color )
—Stucco white
(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 29 77Compressor type & Q'ty — RMT5126SWP3 ( Twin rotary type )×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 ( M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan ×1 Propeller fan ×1Fan motor (Starting method) W 100 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 13 Hi: 10 Me: 9 Lo: 875
Heating 73Available external static pressure Pa Standard: 35 Max: 100 0Outside air intake Possible —Air filter, Quality / Quantity Procure locally —Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20 (Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A,RC-E5,RCH-E3 Wireless : RCN-KIT4-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35 (1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line φ 12.7 (1/2") ②φ12.7(1/2")x0.8 ①φ15.88(5/8")x1.0 φ15.88 (5/8")Connecting method Flare piping Flare pipingInsulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable VP25 (I.D.25, O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 600 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ1.6mm×3 cores + earth cable / Terminal block (Screw fixing type)IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Filter set : UM-FL1EF , Motion sensor : LB-KIT
(c) Triple type
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is three indoor units are combined and run together.(7) Branching pipe set "DIS-TA1G"×1(Option). ① : Pipe of O/U-Branch,② : Pipe of Branch-I/U(8) Static pressure of option air filter "UM-FL1EF" is 5Pa initially.(9) The external static pressure setting can be changed to 10-100Pa. (For RC-EX3A and RC-E5 only)
ItemOperation
Indoor air temperature Outdoor air temperature External static pressure of indoor unit Standards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C
35PaISO5151-T1
Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 41 -
'19 • PAC-DB-308D
PJG000Z491 B
ModelItem
FDUM140VSAWTVHIndoor unit FDUM50VH (3 units) Outdoor unit FDC140VSA-W
Power source 3 Phase, 380-415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 13.6 [ 5.0(Min.) - 14.5(Max.)]Nominal heating capacity (range) kW 15.5 [ 4.0(Min.) - 16.5(Max.)]
Power consumptionCooling
kW5.02
Heating 4.20Max power consumption 10.20
Running currentCooling
A7.5 / 7.9
Heating 6.1 / 6.4Inrush current, max current 5, 18
Power factorCooling
%97
Heating 99EER Cooling 2.71COP Heating 3.69
Sound power levelCooling
dB(A)
6072
Heating 73
Sound pressure levelCooling
P-Hi: 37 Hi: 32 Me: 29 Lo: 2656
Heating 58Silent mode sound pressure level — 49 / 45 (Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 280 × 750 × 635 845 × 970 × 370Exterior appearance(Munsell color )(RAL color )
—Stucco white
(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 29 78Compressor type & Q'ty — RMT5126SWP4 ( Twin rotary type )×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 ( M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan ×1 Propeller fan ×1Fan motor (Starting method) W 100 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 13 Hi: 10 Me: 9 Lo: 875
Heating 73Available external static pressure Pa Standard: 35 Max: 100 0Outside air intake Possible —Air filter, Quality / Quantity Procure locally —Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20 (Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A,RC-E5,RCH-E3 Wireless : RCN-KIT4-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35 (1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/Uφ 9.52 (3/8")
Gas line φ 12.7 (1/2") ②φ12.7(1/2")x0.8 ①φ15.88(5/8")x1.0 φ15.88 (5/8")Connecting method Flare piping Flare pipingInsulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable VP25 (I.D.25, O.D.32) Hole size φ 20 x 3pcs
Drain pump, max lift height mm Built-in drain pump , 600 —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ1.6mm×3 cores + earth cable / Terminal block (Screw fixing type)IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Filter set : UM-FL1EF , Motion sensor : LB-KIT
Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is three indoor units are combined and run together.(7) Branching pipe set "DIS-TA1G"×1(Option). ① : Pipe of O/U-Branch,② : Pipe of Branch-I/U(8) Static pressure of option air filter "UM-FL1EF" is 5Pa initially.(9) The external static pressure setting can be changed to 10-100Pa. (For RC-EX3A and RC-E5 only)
ItemOperation
Indoor air temperature Outdoor air temperature External static pressure of indoor unit Standards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C
35PaISO5151-T1
Heating 20˚C — 7˚C 6˚C ISO5151-H1
The pipe length is 7.5m.
- 42 -
'19 • PAC-DB-308D
PFA004Z088 B
ModelItem
FDE100VNAWVHIndoor unit FDE100VH Outdoor unit FDC100VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 10.0 [ 4.0(Min.) - 11.2(Max.)]Nominal heating capacity (range) kW 11.2 [ 4.0(Min.) - 12.5(Max.)]
Power consumptionCooling
kW2.85
Heating 2.54Max power consumption 6.40
Running currentCooling
A13.8 / 14.4
Heating 12.4 / 13.0Inrush current, max current 5, 24
Power factorCooling
%90
Heating 89EER Cooling 3.51COP Heating 4.41
Sound power levelCooling
dB(A)
6469
Heating 70
Sound pressure levelCooling
P-Hi: 48 Hi: 43 Me: 38 Lo: 3454
Heating 55Silent mode sound pressure level — 48 /44(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 250 x 1,620 x 690 845 x 970 x 370Exterior appearance(Munsell color )(RAL color )
Plaster white(6.8Y8.9/0.2) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 43 77Compressor type & Q'ty — RMT5126SWP3 ( Twin rotary type )x1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan x4 Propeller fan x1Fan motor (Starting method) W 80 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 32 Hi: 26 Me: 21 Lo: 16.575
Heating 73Available external static pressure Pa 0 0Outside air intake Not possible —Air filter, Quality / Quantity Pocket plastic net x2(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-E-E3Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Connecting method
Liquid linemm
I/U φ 9.52 (3/8") Pipe φ 9.52 (3/8")x0.8 O/U φ 9.52 (3/8")Gas line φ 15.88 (5/8") φ 15.88(5/8")x1.0 φ 15.88 (5/8")
Connecting method Flare piping Flare pipingInsulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP20(O.D.26) Hole size φ 20 x 3pcs
Drain pump, max lift height mm — —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mm x 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-E
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
(5) Ceiling suspended type (FDE) (a) Single type
- 43 -
'19 • PAC-DB-308D
PFA004Z088 B
ModelItem
FDE100VSAWVHIndoor unit FDE100VH Outdoor unit FDC100VSA-W
Power source 3 Phase, 380 - 415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 10.0 [ 4.0(Min.) - 11.2(Max.)]Nominal heating capacity (range) kW 11.2 [ 4.0(Min.) - 12.5(Max.)]
Power consumptionCooling
kW2.85
Heating 2.54Max power consumption 10.20
Running currentCooling
A4.6 / 4.8
Heating 4.0 / 4.2Inrush current, max current 5, 15
Power factorCooling
%90
Heating 91EER Cooling 3.51COP Heating 4.41
Sound power levelCooling
dB(A)
6469
Heating 70
Sound pressure levelCooling
P-Hi: 48 Hi: 43 Me: 38 Lo: 3454
Heating 55Silent mode sound pressure level — 48 /44(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 250 x 1,620 x 690 845 x 970 x 370Exterior appearance(Munsell color )(RAL color )
Plaster white(6.8Y8.9/0.2) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 43 78Compressor type & Q'ty — RMT5126SWP4 ( Twin rotary type )x1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan x4 Propeller fan x1Fan motor (Starting method) W 80 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 32 Hi: 26 Me: 21 Lo: 16.575
Heating 73Available external static pressure Pa 0 0Outside air intake Not possible —Air filter, Quality / Quantity Pocket plastic net x2(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-E-E3Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Connecting method
Liquid linemm
I/U φ 9.52 (3/8") Pipe φ 9.52 (3/8")x0.8 O/U φ 9.52 (3/8")Gas line φ 15.88 (5/8") φ 15.88(5/8")x1.0 φ 15.88 (5/8")
Connecting method Flare piping Flare pipingInsulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP20(O.D.26) Hole size φ 20 x 3pcs
Drain pump, max lift height mm — —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mm x 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-E
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 44 -
'19 • PAC-DB-308D
PFA004Z088 B
ModelItem
FDE125VNAWVHIndoor unit FDE125VH Outdoor unit FDC125VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 12.5 [ 5.0(Min.) - 14.0(Max.)]Nominal heating capacity (range) kW 14.0 [ 4.0(Min.) - 16.0(Max.)]
Power consumptionCooling
kW4.45
Heating 3.74Max power consumption 6.40
Running currentCooling
A20.4 / 21.3
Heating 17.5 / 18.3Inrush current, max current 5, 24
Power factorCooling
%95
Heating 93EER Cooling 2.81COP Heating 3.74
Sound power levelCooling
dB(A)
64 71Heating
Sound pressure levelCooling
P-Hi: 48 Hi: 45 Me: 40 Lo: 3554
Heating 56Silent mode sound pressure level — 48 /45(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 250 x 1,620 x 690 845 x 970 x 370Exterior appearance(Munsell color )(RAL color )
Plaster white(6.8Y8.9/0.2) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 43 77Compressor type & Q'ty — RMT5126SWP3 ( Twin rotary type )x1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan x4 Propeller fan x1Fan motor (Starting method) W 80 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 32 Hi: 29 Me: 23 Lo: 1775
Heating 73Available external static pressure Pa 0 0Outside air intake Not possible —Air filter, Quality / Quantity Pocket plastic net x2(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-E-E3Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Connecting method
Liquid linemm
I/U φ 9.52 (3/8") Pipe φ 9.52 (3/8")x0.8 O/U φ 9.52 (3/8")Gas line φ 15.88 (5/8") φ 15.88(5/8")x1.0 φ 15.88 (5/8")
Connecting method Flare piping Flare pipingInsulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP20(O.D.26) Hole size φ 20 x 3pcs
Drain pump, max lift height mm — —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mm x 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-E
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 45 -
'19 • PAC-DB-308D
PFA004Z088 B
ModelItem
FDE125VSAWVHIndoor unit FDE125VH Outdoor unit FDC125VSA-W
Power source 3 Phase, 380 - 415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 12.5 [ 5.0(Min.) - 14.0(Max.)]Nominal heating capacity (range) kW 14.0 [ 4.0(Min.) - 16.0(Max.)]
Power consumptionCooling
kW4.45
Heating 3.74Max power consumption 10.20
Running currentCooling
A6.9 / 7.3
Heating 5.9 / 6.2Inrush current, max current 5, 15
Power factorCooling
%93
Heating 91EER Cooling 2.81COP Heating 3.74
Sound power levelCooling
dB(A)
64 71Heating
Sound pressure levelCooling
P-Hi: 48 Hi: 45 Me: 40 Lo: 3554
Heating 56Silent mode sound pressure level — 48 /45(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 250 x 1,620 x 690 845 x 970 x 370Exterior appearance(Munsell color )(RAL color )
Plaster white(6.8Y8.9/0.2) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 43 78Compressor type & Q'ty — RMT5126SWP4 ( Twin rotary type )x1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan x4 Propeller fan x1Fan motor (Starting method) W 80 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 32 Hi: 29 Me: 23 Lo: 1775
Heating 73Available external static pressure Pa 0 0Outside air intake Not possible —Air filter, Quality / Quantity Pocket plastic net x2(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-E-E3Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Connecting method
Liquid linemm
I/U φ 9.52 (3/8") Pipe φ 9.52 (3/8")x0.8 O/U φ 9.52 (3/8")Gas line φ 15.88 (5/8") φ 15.88(5/8")x1.0 φ 15.88 (5/8")
Connecting method Flare piping Flare pipingInsulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP20(O.D.26) Hole size φ 20 x 3pcs
Drain pump, max lift height mm — —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mm x 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-E
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 46 -
'19 • PAC-DB-308D
PFA004Z088 B
ModelItem
FDE140VNAWVHIndoor unit FDE140VH Outdoor unit FDC140VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 13.6 [ 5.0(Min.) - 14.5(Max.)]Nominal heating capacity (range) kW 15.5 [ 4.0(Min.) - 16.5(Max.)]
Power consumptionCooling
kW5.05
Heating 4.18Max power consumption 6.40
Running currentCooling
A22.2 / 23.2
Heating 18.4 / 19.2Inrush current, max current 5, 24
Power factorCooling
%99
Heating 99EER Cooling 2.69COP Heating 3.71
Sound power levelCooling
dB(A)
6572
Heating 73
Sound pressure levelCooling
P-Hi: 49 Hi: 45 Me: 40 Lo: 3656
Heating 58Silent mode sound pressure level — 49 /45(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 250 x 1,620 x 690 845 x 970 x 370Exterior appearance(Munsell color)(RAL color )
Plaster white(6.8Y8.9/0.2) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 43 77Compressor type & Q'ty — RMT5126SWP3 ( Twin rotary type )x1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan x4 Propeller fan x1Fan motor (Starting method) W 90 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 34 Hi: 29 Me: 23 Lo: 1875
Heating 73Available external static pressure Pa 0 0Outside air intake Possible —Air filter, Quality / Quantity Pocket plastic net x2(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-E-E3Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 9.52 (3/8") Pipe φ 9.52 (3/8")x0.8 O/U φ 9.52 (3/8")
Gas line φ 15.88 (5/8") φ 15.88(5/8")x1.0 φ 15.88 (5/8")Connecting method Flare piping Flare pipingInsulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP20(O.D.26) Hole size φ 20 x 3pcs
Drain pump, max lift height mm — —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mm x 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-E
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 47 -
'19 • PAC-DB-308D
ModelItem
FDE140VSAWVHIndoor unit FDE140VH Outdoor unit FDC140VSA-W
Power source 3 Phase, 380 - 415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 13.6 [ 5.0(Min.) - 14.5(Max.)]Nominal heating capacity (range) kW 15.5 [ 4.0(Min.) - 16.5(Max.)]
Power consumptionCooling
kW5.05
Heating 4.18Max power consumption 10.20
Running currentCooling
A7.8 / 8.2
Heating 6.5 / 6.8Inrush current, max current 5, 15
Power factorCooling
%94
Heating 93EER Cooling 2.69COP Heating 3.71
Sound power levelCooling
dB(A)
6572
Heating 73
Sound pressure levelCooling
P-Hi: 49 Hi: 45 Me: 40 Lo: 3656
Heating 58Silent mode sound pressure level — 49 /45(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 250 x 1,620 x 690 845 x 970 x 370Exterior appearance(Munsell color)(RAL color )
Plaster white(6.8Y8.9/0.2) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 43 78Compressor type & Q'ty — RMT5126SWP4 ( Twin rotary type )x1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing Straight fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan x4 Propeller fan x1Fan motor (Starting method) W 90 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 34 Hi: 29 Me: 23 Lo: 1875
Heating 73Available external static pressure Pa 0 0Outside air intake Not possible —Air filter, Quality / Quantity Pocket plastic net x2(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-E-E3Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 9.52 (3/8") Pipe φ 9.52 (3/8")x0.8 O/U φ 9.52 (3/8")
Gas line φ 15.88 (5/8") φ 15.88(5/8")x1.0 φ 15.88 (5/8")Connecting method Flare piping Flare pipingInsulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP20(O.D.26) Hole size φ 20 x 3pcs
Drain pump, max lift height mm — —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mm x 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-E
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
PFA004Z088 B
- 48 -
'19 • PAC-DB-308D
PFA004Z088 B
ModelItem
FDE100VNAWPVHIndoor unit FDE50VH (2 units) Outdoor unit FDC100VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 10.0 [ 4.0(Min.) - 11.3(Max.)]Nominal heating capacity (range) kW 11.2 [ 4.0(Min.) - 12.5(Max.)]
Power consumptionCooling
kW3.12
Heating 2.99Max power consumption 6.40
Running currentCooling
A14.0 / 14.6
Heating 13.4 / 14.0Inrush current, max current 5, 24
Power factorCooling
%97
Heating 97EER Cooling 3.21COP Heating 3.75
Sound power levelCooling
dB(A)
6069
Heating 70
Sound pressure levelCooling
P-Hi: 46 Hi: 38 Me: 36 Lo: 3154
Heating 55Silent mode sound pressure level — 48 /44(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 210 x 1,070 x 690 845 x 970 x 370Exterior appearance(Munsell color)(RAL color )
Plaster white(6.8Y8.9/0.2) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 28 77Compressor type & Q'ty — RMT5126SWP3 ( Twin rotary type )x1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan x2 Propeller fan x1Fan motor (Starting method) W 30 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 13 Hi: 10 Me: 9 Lo: 775
Heating 73Available external static pressure Pa 0 0Outside air intake Possible —Air filter, Quality / Quantity Pocket plastic net x2(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-E-E3Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35(1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/U φ 9.52 (3/8")
Gas line φ 12.7 (1/2") ②φ 12.7(1/2")x0.8 ①φ 15.88 (5/8")x1.0 φ 15.88 (5/8")Connecting method Flare piping Flare pipingInsulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP20(O.D.26) Hole size φ 20 x 3pcs
Drain pump, max lift height mm — —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mm x 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-E
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1G"×1(Option). ① : Pipe of O/U-Branch, ② : Pipe of Branch-I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
(b) Twin type
- 49 -
'19 • PAC-DB-308D
ModelItem
FDE100VSAWPVHIndoor unit FDE50VH (2 units) Outdoor unit FDC100VSA-W
Power source 3 Phase, 380 - 415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 10.0 [ 4.0(Min.) - 11.2(Max.)]Nominal heating capacity (range) kW 11.2 [ 4.0(Min.) - 12.5(Max.)]
Power consumptionCooling
kW3.12
Heating 2.99Max power consumption 10.20
Running currentCooling
A4.6 / 4.8
Heating 4.4 / 4.6Inrush current, max current 5, 15
Power factorCooling
%98
Heating 98EER Cooling 3.21COP Heating 3.75
Sound power levelCooling
dB(A)
6069
Heating 70
Sound pressure levelCooling
P-Hi: 46 Hi: 38 Me: 36 Lo: 3154
Heating 55Silent mode sound pressure level — 48 /44(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 210 x 1,070 x 690 845 x 970 x 370Exterior appearance(Munsell color)(RAL color )
Plaster white(6.8Y8.9/0.2) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 28 78Compressor type & Q'ty — RMT5126SWP4 ( Twin rotary type )x1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan x2 Propeller fan x1Fan motor (Starting method) W 30 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 13 Hi: 10 Me: 9 Lo: 775
Heating 73Available external static pressure Pa 0 0Outside air intake Not possible —Air filter, Quality / Quantity Pocket plastic net x2(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-E-E3Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35(1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/U φ 9.52 (3/8")
Gas line φ 12.7 (1/2") ②φ 12.7(1/2")x0.8 ①φ 15.88 (5/8")x1.0 φ 15.88 (5/8")Connecting method Flare piping Flare pipingInsulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP20(O.D.26) Hole size φ 20 x 3pcs
Drain pump, max lift height mm — —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mm x 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-E
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1G"×1(Option). ① : Pipe of O/U-Branch, ② : Pipe of Branch-I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
PFA004Z088 B
- 50 -
'19 • PAC-DB-308D
ModelItem
FDE125VNAWPVHIndoor unit FDE60VH (2 units) Outdoor unit FDC125VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 12.5 [ 4.0(Min.) - 14.0(Max.)]Nominal heating capacity (range) kW 14.0 [ 4.0(Min.) - 16.0(Max.)]
Power consumptionCooling
kW4.16
Heating 3.54Max power consumption 6.40
Running currentCooling
A18.3 / 19.1
Heating 15.5 / 16.3Inrush current, max current 5, 24
Power factorCooling
%99
Heating 99EER Cooling 3.00COP Heating 3.95
Sound power levelCooling
dB(A)
60 71Heating
Sound pressure levelCooling
P-Hi: 47 Hi: 41 Me: 37 Lo: 3254
Heating 56Silent mode sound pressure level — 48 /45(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 210 x 1,320 x 690 845 x 970 x 370Exterior appearance(Munsell color)(RAL color )
Plaster white(6.8Y8.9/0.2) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 33 77Compressor type & Q'ty — RMT5126SWP3 ( Twin rotary type )x1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan x4 Propeller fan x1Fan motor (Starting method) W 50 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 20 Hi: 16 Me: 13 Lo: 1075
Heating 73Available external static pressure Pa 0 0Outside air intake Possible —Air filter, Quality / Quantity Pocket plastic net x2(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-E-E3Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35(1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/U φ 9.52 (3/8")
Gas line φ 12.7 (1/2") ②φ 12.7(1/2")x0.8 ①φ 15.88 (5/8")x1.0 φ 15.88 (5/8")Connecting method Flare piping Flare pipingInsulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP20(O.D.26) Hole size φ 20 x 3pcs
Drain pump, max lift height mm — —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mm x 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-E
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1G"×1(Option). ① : Pipe of O/U-Branch, ② : Pipe of Branch-I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
PFA004Z088 B
- 51 -
'19 • PAC-DB-308D
ModelItem
FDE125VSAWPVHIndoor unit FDE60VH (2 units) Outdoor unit FDC125VSA-W
Power source 3 Phase, 380 - 415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 12.5 [ 5.0(Min.) - 14.0(Max.)]Nominal heating capacity (range) kW 14.0 [ 4.0(Min.) - 16.0(Max.)]
Power consumptionCooling
kW4.16
Heating 3.54Max power consumption 10.20
Running currentCooling
A6.1 / 6.4
Heating 5.2 / 5.5Inrush current, max current 5, 15
Power factorCooling
%99
Heating 98EER Cooling 3.00COP Heating 3.95
Sound power levelCooling
dB(A)
60 71Heating
Sound pressure levelCooling
P-Hi: 47 Hi: 41 Me: 37 Lo: 3254
Heating 56Silent mode sound pressure level — 49 /45(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 210 x 1,320 x 690 845 x 970 x 370Exterior appearance(Munsell color)(RAL color )
Plaster white(6.8Y8.9/0.2) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 33 78Compressor type & Q'ty — RMT5126SWP4 ( Twin rotary type )x1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan x4 Propeller fan x1Fan motor (Starting method) W 50 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 20 Hi: 16 Me: 13 Lo: 1075
Heating 73Available external static pressure Pa 0 0Outside air intake Not possible —Air filter, Quality / Quantity Pocket plastic net x2(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-E-E3Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35(1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/U φ 9.52 (3/8")
Gas line φ 12.7 (1/2") ②φ 12.7(1/2")x0.8 ①φ 15.88 (5/8")x1.0 φ 15.88 (5/8")Connecting method Flare piping Flare pipingInsulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP20(O.D.26) Hole size φ 20 x 3pcs
Drain pump, max lift height mm — —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mm x 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-E
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1G"×1(Option). ① : Pipe of O/U-Branch, ② : Pipe of Branch-I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
PFA004Z088 B
- 52 -
'19 • PAC-DB-308D
ModelItem
FDE140VNAWPVHIndoor unit FDE71VH (2 units) Outdoor unit FDC140VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 13.6 [ 5.0(Min.) - 14.5(Max.)]Nominal heating capacity (range) kW 15.5 [ 4.0(Min.) - 16.5(Max.)]
Power consumptionCooling
kW4.74
Heating 4.21Max power consumption 6.40
Running currentCooling
A20.8 / 21.8
Heating 18.5 / 19.3Inrush current, max current 5, 24
Power factorCooling
%99
Heating 99EER Cooling 2.87COP Heating 3.68
Sound power levelCooling
dB(A)
6072
Heating 73
Sound pressure levelCooling
P-Hi: 47 Hi: 41 Me: 37 Lo: 3256
Heating 58Silent mode sound pressure level — 49 /45(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 210 x 1,320 x 690 845 x 970 x 370Exterior appearance(Munsell color)(RAL color )
Plaster white(6.8Y8.9/0.2) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 33 77Compressor type & Q'ty — RMT5126SWP3 ( Twin rotary type )x1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan x4 Propeller fan x1Fan motor (Starting method) W 50 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 20 Hi: 16 Me: 13 Lo: 1075
Heating 73Available external static pressure Pa 0 0Outside air intake Not possible —Air filter, Quality / Quantity Pocket plastic net x2(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-E-E3Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 9.52(3/8") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/U φ 9.52 (3/8")
Gas line φ 15.88 (5/8") ②φ 15.88(5/8")x1.0 ①φ 15.88 (5/8")x1.0 φ 15.88 (5/8")Connecting method Flare piping Flare pipingInsulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP20(O.D.26) Hole size φ 20 x 3pcs
Drain pump, max lift height mm — —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mm x 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-E
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1G"×1(Option). ① : Pipe of O/U-Branch, ② : Pipe of Branch-I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
PFA004Z088 B
- 53 -
'19 • PAC-DB-308D
PFA004Z088 B
ModelItem
FDE140VSAWPVHIndoor unit FDE71VH (2 units) Outdoor unit FDC140VSA-W
Power source 3 Phase, 380 - 415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 13.6 [ 5.0(Min.) - 14.5Max.)]Nominal heating capacity (range) kW 15.5 [ 4.0(Min.) - 16.5(Max.)]
Power consumptionCooling
kW4.74
Heating 3.21Max power consumption 10.20
Running currentCooling
A6.9 / 7.3
Heating 6.2 / 6.5Inrush current, max current 5, 15
Power factorCooling
%99
Heating 98EER Cooling 2.87COP Heating 3.68
Sound power levelCooling
dB(A)
6072
Heating 73
Sound pressure levelCooling
P-Hi: 47 Hi: 41 Me: 37 Lo: 3256
Heating 58Silent mode sound pressure level — 49 /45(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 210 x 1,320 x 690 845 x 970 x 370Exterior appearance(Munsell color)(RAL color )
Plaster white(6.8Y8.9/0.2) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 33 78Compressor type & Q'ty — RMT5126SWP4 ( Twin rotary type )x1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan x4 Propeller fan x1Fan motor (Starting method) W 50 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 20 Hi: 16 Me: 13 Lo: 1075
Heating 73Available external static pressure Pa 0 0Outside air intake Not possible —Air filter, Quality / Quantity Pocket plastic net x2(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-E-E3Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 9.52(3/8") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/U φ 9.52 (3/8")
Gas line φ 15.88 (5/8") ②φ 15.88(5/8")x1.0 ①φ 15.88 (5/8")x1.0 φ 15.88 (5/8")Connecting method Flare piping Flare pipingInsulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP20(O.D.26) Hole size φ 20 x 3pcs
Drain pump, max lift height mm — —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mm x 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-E
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1G"×1(Option). ① : Pipe of O/U-Branch, ② : Pipe of Branch-I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 54 -
'19 • PAC-DB-308D
PFA004Z088 B
ModelItem
FDE140VNAWTVHIndoor unit FDE50VH (3 units) Outdoor unit FDC140VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 13.6 [ 5.0(Min.) - 14.5(Max.)]Nominal heating capacity (range) kW 15.5 [ 4.0(Min.) - 16.5(Max.)]
Power consumptionCooling
kW4.74
Heating 4.21Max power consumption 6.40
Running currentCooling
A20.8 / 21.8
Heating 18.5 / 19.3Inrush current, max current 5, 24
Power factorCooling
%99
Heating 99EER Cooling 2.87COP Heating 3.68
Sound power levelCooling
dB(A)
6072
Heating 73
Sound pressure levelCooling
P-Hi: 46 Hi: 38 Me: 36 Lo: 3156
Heating 58Silent mode sound pressure level — 49 /45(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 210 x 1,070 x 690 845 x 970 x 370Exterior appearance(Munsell color)(RAL color )
Plaster white(6.8Y8.9/0.2) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 28 77Compressor type & Q'ty — RMT5126SWP3 ( Twin rotary type )x1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan x2 Propeller fan x1Fan motor (Starting method) W 30 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 13 Hi: 10 Me: 9 Lo: 775
Heating 73Available external static pressure Pa 0 0Outside air intake Not possible —Air filter, Quality / Quantity Pocket plastic net x2(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-E-E3Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35(1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/U φ 9.52 (3/8")
Gas line φ 12.7 (1/2") ②φ 12.7(1/2")x0.8 ①φ 15.88 (5/8")x1.0 φ 15.88 (5/8")Connecting method Flare piping Flare pipingInsulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP20(O.D.26) Hole size φ 20 x 3pcs
Drain pump, max lift height mm — —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mm x 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-E
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-TA1G"×1(Option). ① : Pipe of O/U-Branch, ② : Pipe of Branch-I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
(c) Triple type
- 55 -
'19 • PAC-DB-308D
PFA004Z088 B
ModelItem
FDE140VSAWTVHIndoor unit FDE50VH (3 units) Outdoor unit FDC140VSA-W
Power source 3 Phase, 380 - 415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 13.6 [ 5.0(Min.) - 14.5Max.)]Nominal heating capacity (range) kW 15.5 [ 4.0(Min.) - 16.5(Max.)]
Power consumptionCooling
kW4.74
Heating 3.21Max power consumption 10.20
Running currentCooling
A6.9 / 7.3
Heating 6.2 / 6.5Inrush current, max current 5, 15
Power factorCooling
%99
Heating 98EER Cooling 2.87COP Heating 3.68
Sound power levelCooling
dB(A)
6072
Heating 73
Sound pressure levelCooling
P-Hi: 46 Hi: 38 Me: 36 Lo: 3156
Heating 58Silent mode sound pressure level — 49 /45(Normal/Silent)
Exterior dimensions (Height x Width x Depth) mm 210 x 1,070 x 690 845 x 970 x 370Exterior appearance(Munsell color)(RAL color )
Plaster white(6.8Y8.9/0.2) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 28 78Compressor type & Q'ty — RMT5126SWP4 ( Twin rotary type )x1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Centrifugal fan x2 Propeller fan x1Fan motor (Starting method) W 30 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/min P-Hi: 13 Hi: 10 Me: 9 Lo: 775
Heating 73Available external static pressure Pa 0 0Outside air intake Not possible —Air filter, Quality / Quantity Pocket plastic net x2(Washable) —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-E-E3Room temperature control Thermostat by electronicsOperation display —
Safety equipments
Overload protection for fan motorFrost protection thermostat
Internal thermostat for fan motorAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35(1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/U φ 9.52 (3/8")
Gas line φ 12.7 (1/2") ②φ 12.7(1/2")x0.8 ①φ 15.88 (5/8")x1.0 φ 15.88 (5/8")Connecting method Flare piping Flare pipingInsulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP20(O.D.26) Hole size φ 20 x 3pcs
Drain pump, max lift height mm — —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mm x 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Drain hose —Option parts Motion sensor : LB-E
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-TA1G"×1(Option). ① : Pipe of O/U-Branch, ② : Pipe of Branch-I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 56 -
'19 • PAC-DB-308D
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
PCA001Z857 A
ModelItem
SRK100VNAWZRIndoor unit SRK100ZR-W Outdoor unit FDC100VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 10.0 [ 4.0(Min.) - 11.2(Max.)]Nominal heating capacity (range) kW 11.2 [ 4.0(Min.) - 12.5(Max.)]
Power consumptionCooling
kW3.19
Heating 3.04Max power consumption 6.40
Running currentCooling
A14.3 / 14.9
Heating 13.6 / 14.2Inrush current, max current 5, 24
Power factorCooling
%97
Heating 97EER Cooling 3.13COP Heating 3.68
Sound power levelCooling
dB(A)
6369
Heating 70
Sound pressure levelCooling P-Hi: 48 Hi: 45 Me: 40 Lo: 27 54Heating P-Hi: 48 Hi: 43 Me: 38 Lo: 30 55
Silent mode sound pressure level — 48 /44(Normal/Silent)Exterior dimensions (Height x Width x Depth) mm 339 x 1,197 x 262 845 x 970 x 370Exterior appearance(Munsell color)(RAL color )
Fine snow(8.0Y9.3/0.1) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 16.5 77Compressor type & Q'ty — RMT5126SWP3×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Pre-charged up to the piping length of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Tangential fan x 1 Propeller fan x1Fan motor (Starting method) W 56 x 1 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/minHi: 24.5 Me: 21.3 Lo: 17.6 ULo: 10.4 75
Heating Hi: 27.5 Me: 23.2 Lo: 19.1 ULo: 13.6 73Available external static pressure Pa 0 0Outside air intake Not possible —Air filter, Quality / Quantity Polypropylene net (Washable) x 2 —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A, RC-E5 , RCH-E3 Interface kit : SC-BIKN2-ERoom temperature control Thermostat by electronicsOperation display RUN: Green, TIMER: Yellow, ECO: Blue
Safety equipmentsInternal thermostat for fan motor
Frost protection thermostatAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 9.52 (3/8") Pipe φ 9.52 (3/8")x0.8 O/U φ 9.52 (3/8")
Gas line φ 15.88 (5/8") φ 15.88(5/8")x1.0 φ 15.88 (5/8")Connecting method Flare piping Flare pipingAttached length of piping — —Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP16 Hole size φ 20 x 3pcs
Drain pump, max lift height mm — —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mm x 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Clean filter —Option parts —
(6) Wall mounted type (SRK)
(a) Single type
- 57 -
'19 • PAC-DB-308D
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
PCA001Z857 A
ModelItem
SRK100VSAWZRIndoor unit SRK100ZR-W Outdoor unit FDC100VSA-W
Power source 3 Phase, 380 - 415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 10.0 [ 4.0(Min.) - 11.2(Max.)]Nominal heating capacity (range) kW 11.2 [ 4.0(Min.) - 12.5(Max.)]
Power consumptionCooling
kW3.19
Heating 3.04Max power consumption 10.20
Running currentCooling
A4.8 / 5.1
Heating 4.6 / 4.8Inrush current, max current 5, 15
Power factorCooling
%95
Heating 96EER Cooling 3.13COP Heating 3.68
Sound power levelCooling
dB(A)
6369
Heating 70
Sound pressure levelCooling P-Hi: 48 Hi: 45 Me: 40 Lo: 27 54Heating P-Hi: 48 Hi: 43 Me: 38 Lo: 30 55
Silent mode sound pressure level — 48 /44(Normal/Silent)Exterior dimensions (Height x Width x Depth) mm 339 x 1,197 x 262 845 x 970 x 370Exterior appearance(Munsell color)(RAL color )
Fine snow(8.0Y9.3/0.1) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 16.5 78Compressor type & Q'ty — RMT5126SWP4×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Pre-charged up to the piping length of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Tangential fan x1 Propeller fan x1Fan motor (Starting method) W 56 x 1 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/minHi: 24.5 Me: 21.3 Lo: 17.6 ULo: 10.4 75
Heating Hi: 27.5 Me: 23.2 Lo: 19.1 ULo: 13.6 73Available external static pressure Pa 0 0Outside air intake Not possible —Air filter, Quality / Quantity Polypropylene net (Washable) x 2 —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A, RC-E5 , RCH-E3 Interface kit : SC-BIKN2-ERoom temperature control Thermostat by electronicsOperation display RUN: Green, TIMER: Yellow, ECO: Blue
Safety equipmentsInternal thermostat for fan motor
Frost protection thermostatAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 9.52 (3/8") Pipe φ 9.52 (3/8")x0.8 O/U φ 9.52 (3/8")
Gas line φ 15.88 (5/8") φ 15.88(5/8")x1.0 φ 15.88 (5/8")Connecting method Flare piping Flare pipingAttached length of piping — —Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP16 Hole size φ 20 x 3pcs
Drain pump, max lift height mm — —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mm x 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Clean filter —Option parts —
- 58 -
'19 • PAC-DB-308D
PCA001Z857 A
ModelItem
SRK100VNAWPZSXIndoor unit SRK50ZSX-W (2 units) Outdoor unit FDC100VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 10.0 [ 4.0(Min.) - 11.2(Max.)]Nominal heating capacity (range) kW 11.2 [ 4.0(Min.) - 12.5(Max.)]
Power consumptionCooling
kW2.89
Heating 2.61Max power consumption 6.40
Running currentCooling
A12.7 / 13.3
Heating 11.5 / 12.0Inrush current, max current 5, 24
Power factorCooling
%99
Heating 99EER Cooling 3.46COP Heating 4.29
Sound power levelCooling
dB(A)
59 69Heating 62 70
Sound pressure levelCooling P-Hi: 44 Hi: 39 Me: 31 Lo: 22 54Heating P-Hi: 46 Hi: 41 Me: 33 Lo: 23 55
Silent mode sound pressure level — 48 /44(Normal/Silent)Exterior dimensions (Height x Width x Depth) mm 305 x 920 x 220 845 x 970 x 370Exterior appearance(Munsell color)(RAL color )
Fine snow(8.0Y9.3/0.1) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 13 77Compressor type & Q'ty — RMT5126SWP3×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Pre-charged up to the piping length of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Tangential fan x1 Propeller fan x1Fan motor (Starting method) W 42 x 1 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/minHi: 14.3 Me: 12.4 Lo: 7.8 ULo: 5.4 75
Heating Hi: 17.3 Me: 14.3 Lo: 9.8 ULo: 6.2 73Available external static pressure Pa 0 0Outside air intake Not possible —Air filter, Quality / Quantity Polypropylene net (Washable) x 2 —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A, RC-E5 , RCH-E3 Interface kit : SC-BIKN2-ERoom temperature control Thermostat by electronicsOperation display RUN: Green, TIMER: Yellow, ECO: Blue
Safety equipmentsInternal thermostat for fan motor
Frost protection thermostatAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35(1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/U φ 9.52 (3/8")
Gas line φ 12.7 (1/2") ②φ 12.7(1/2")x0.8 ①φ 15.88 (5/8")x1.0 φ 15.88 (5/8")Connecting method Flare piping Flare pipingAttached length of piping — —Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP16 Hole size φ 20 x 3pcs
Drain pump, max lift height mm — —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mm x 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Clean filter —Option parts —
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1"×1(Option). ① : Pipe of O/U-Branch, ② : Pipe of Branch-I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
(b) Twin type
- 59 -
'19 • PAC-DB-308D
ModelItem
SRK100VSAWPZSXIndoor unit SRK50ZSX-W (2 units) Outdoor unit FDC100VSA-W
Power source 3 Phase, 380 - 415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 10.0 [ 4.0(Min.) - 11.2(Max.)]Nominal heating capacity (range) kW 11.2 [ 4.0(Min.) - 12.5(Max.)]
Power consumptionCooling
kW2.89
Heating 2.61Max power consumption 10.20
Running currentCooling
A4.2 / 4.4
Heating 3.8 / 4.0Inrush current, max current 5, 15
Power factorCooling
%99
Heating 99EER Cooling 3.46COP Heating 4.29
Sound power levelCooling
dB(A)
59 69Heating 62 70
Sound pressure levelCooling P-Hi: 44 Hi: 39 Me: 31 Lo: 22 54Heating P-Hi: 46 Hi: 41 Me: 33 Lo: 23 55
Silent mode sound pressure level — 48 /44(Normal/Silent)Exterior dimensions (Height x Width x Depth) mm 305 x 920 x 220 845 x 970 x 370Exterior appearance(Munsell color)(RAL color )
Fine snow(8.0Y9.3/0.1) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 13 78Compressor type & Q'ty — RMT5126SWP4×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Pre-charged up to the piping length of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Tangential fan x1 Propeller fan x1Fan motor (Starting method) W 42 x 1 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/minHi: 14.3 Me: 12.4 Lo: 7.8 ULo: 5.4 75
Heating Hi: 17.3 Me: 14.3 Lo: 9.8 ULo: 6.2 73Available external static pressure Pa 0 0Outside air intake Not possible —Air filter, Quality / Quantity Polypropylene net (Washable) x 2 —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A, RC-E5 , RCH-E3 Interface kit : SC-BIKN2-ERoom temperature control Thermostat by electronicsOperation display RUN: Green, TIMER: Yellow, ECO: Blue
Safety equipmentsInternal thermostat for fan motor
Frost protection thermostatAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35(1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/U φ 9.52 (3/8")
Gas line φ 12.7 (1/2") ②φ 12.7(1/2")x0.8 ①φ 15.88 (5/8")x1.0 φ 15.88 (5/8")Connecting method Flare piping Flare pipingAttached length of piping — —Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP16 Hole size φ 20 x 3pcs
Drain pump, max lift height mm — —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mm x 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Clean filter —Option parts —
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1"×1(Option). ① : Pipe of O/U-Branch, ② : Pipe of Branch-I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
PCA001Z857 A
- 60 -
'19 • PAC-DB-308D
ModelItem
SRK125VNAWPZSXIndoor unit SRK60ZSX-W (2 units) Outdoor unit FDC125VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 12.5 [ 5.0(Min.) - 14.0(Max.)]Nominal heating capacity (range) kW 14.0 [ 4.0(Min.) - 16.0(Max.)]
Power consumptionCooling
kW4.54
Heating 3.58Max power consumption 6.40
Running currentCooling
A19.9 / 20.8
Heating 15.7 / 16.4Inrush current, max current 5, 24
Power factorCooling
%99
Heating 99EER Cooling 2.76COP Heating 3.91
Sound power levelCooling
dB(A)
6271
Heating 63
Sound pressure levelCooling P-Hi: 44 Hi: 41 Me: 33 Lo: 22 54Heating P-Hi: 46 Hi: 42 Me: 34 Lo: 23 56
Silent mode sound pressure level — 48 /45(Normal/Silent)Exterior dimensions (Height x Width x Depth) mm 305 x 920 x 220 845 x 970 x 370Exterior appearance(Munsell color)(RAL color )
Fine snow(8.0Y9.3/0.1) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 13 77Compressor type & Q'ty — RMT5126SWP3×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Pre-charged up to the piping length of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Tangential fan x1 Propeller fan x1Fan motor (Starting method) W 42 x 1 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/minHi: 16.3 Me: 13.4 Lo: 8.9 ULo: 5.4 75
Heating Hi: 17.8 Me: 13.7 Lo: 10.9 ULo: 6.2 73Available external static pressure Pa 0 0Outside air intake Not possible —Air filter, Quality / Quantity Polypropylene net (Washable) x 2 —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A, RC-E5 , RCH-E3 Interface kit : SC-BIKN2-ERoom temperature control Thermostat by electronicsOperation display RUN: Green, TIMER: Yellow, ECO: Blue
Safety equipmentsInternal thermostat for fan motor
Frost protection thermostatAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35(1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/U φ 9.52 (3/8")
Gas line φ 12.7 (1/2") ②φ 12.7(1/2")x0.8 ①φ 15.88 (5/8")x1.0 φ 15.88 (5/8")Connecting method Flare piping Flare pipingAttached length of piping — —Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP16 Hole size φ 20 x 3pcs
Drain pump, max lift height mm — —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mm x 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Clean filter —Option parts —
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1"×1(Option). ① : Pipe of O/U-Branch, ② : Pipe of Branch-I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
PCA001Z857 A
- 61 -
'19 • PAC-DB-308D
ModelItem
SRK125VSAWPZSXIndoor unit SRK60ZSX-W (2 units) Outdoor unit FDC125VSA-W
Power source 3 Phase, 380 - 415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 12.5 [ 5.0(Min.) - 14.0(Max.)]Nominal heating capacity (range) kW 14.0 [ 4.0(Min.) - 16.0(Max.)]
Power consumptionCooling
kW4.54
Heating 3.58Max power consumption 10.20
Running currentCooling
A6.6 / 7.0
Heating 5.2 / 5.5Inrush current, max current 5, 15
Power factorCooling
%99
Heating 99EER Cooling 2.76COP Heating 3.91
Sound power levelCooling
dB(A)
6271
Heating 63
Sound pressure levelCooling P-Hi: 46 Hi: 41 Me: 33 Lo: 22 54Heating P-Hi: 46 Hi: 42 Me: 34 Lo: 23 56
Silent mode sound pressure level — 48 /45(Normal/Silent)Exterior dimensions (Height x Width x Depth) mm 305 x 920 x 220 845 x 970 x 370Exterior appearance(Munsell color)(RAL color )
Fine snow(8.0Y9.3/0.1) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 13 78Compressor type & Q'ty — RMT5126SWP4×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Pre-charged up to the piping length of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Tangential fan x1 Propeller fan x1Fan motor (Starting method) W 42 x 1 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/minHi: 16.3 Me: 13.4 Lo: 8.9 ULo: 5.4 75
Heating Hi: 17.8 Me: 13.7 Lo: 10.9 ULo: 6.2 73Available external static pressure Pa 0 0Outside air intake Not possible —Air filter, Quality / Quantity Polypropylene net (Washable) x 2 —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A, RC-E5 , RCH-E3 Interface kit : SC-BIKN2-ERoom temperature control Thermostat by electronicsOperation display RUN: Green, TIMER: Yellow, ECO: Blue
Safety equipmentsInternal thermostat for fan motor
Frost protection thermostatAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35(1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/U φ 9.52 (3/8")
Gas line φ 12.7 (1/2") ②φ 12.7(1/2")x0.8 ①φ 15.88 (5/8")x1.0 φ 15.88 (5/8")Connecting method Flare piping Flare pipingAttached length of piping — —Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP16 Hole size φ 20 x 3pcs
Drain pump, max lift height mm — —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mm x 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Clean filter —Option parts —
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1"×1(Option). ① : Pipe of O/U-Branch, ② : Pipe of Branch-I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
PCA001Z857 A
- 62 -
'19 • PAC-DB-308D
ModelItem
SRK140VNAWPZRIndoor unit SRK71ZR-W (2 units) Outdoor unit FDC140VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 13.6 [ 5.0(Min.) - 14.5(Max.)]Nominal heating capacity (range) kW 15.5 [ 4.0(Min.) - 16.5(Max.)]
Power consumptionCooling
kW4.26
Heating 4.03Max power consumption 6.40
Running currentCooling
A18.7 / 19.6
Heating 17.7 / 18.5Inrush current, max current 5, 24
Power factorCooling
%99
Heating 99EER Cooling 3.19COP Heating 3.85
Sound power levelCooling
dB(A)
57 72Heating 60 73
Sound pressure levelCooling P-Hi: 44 Hi: 41 Me: 37 Lo: 25 56Heating P-Hi: 46 Hi: 39 Me: 35 Lo: 28 58
Silent mode sound pressure level — 49 /45(Normal/Silent)Exterior dimensions (Height x Width x Depth) mm 339 x 1,197 x 262 845 x 970 x 370Exterior appearance(Munsell color)(RAL color )
Fine snow(8.0Y9.3/0.1) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 15.5 77Compressor type & Q'ty — RMT5126SWP3×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Pre-charged up to the piping length of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Tangential fan x1 Propeller fan x1Fan motor (Starting method) W 56 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/minHi: 20.5 Me: 18.6 Lo: 16.2 ULo: 10.4 75
Heating Hi: 25.0 Me: 19.8 Lo: 17.3 ULo: 13.3 73Available external static pressure Pa 0 0Outside air intake Not possible —Air filter, Quality / Quantity Polypropylene net (Washable) x 2 —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A, RC-E5 , RCH-E3 Interface kit : SC-BIKN2-ERoom temperature control Thermostat by electronicsOperation display RUN: Green , TIMER: Yellow , HI POWER: Green , 3D AUTO: Orange
Safety equipmentsInternal thermostat for fan motor
Frost protection thermostatAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 9.52(3/8") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/U φ 9.52 (3/8")
Gas line φ 15.88 (5/8") ②φ 15.88(5/8")x1.0 ①φ 15.88 (5/8")x1.0 φ 15.88 (5/8")Connecting method Flare piping Flare pipingAttached length of piping Liquid line : 0.78 / Gas line : 0.72 —Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with (VP16) Hole size φ 20 x 3pcs
Drain pump, max lift height mm — —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mm x 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24
Standard accessoriesMounting kit, Clean filter
(Allergen clear filter ×1 , Photocatalytic washable deodorizing filter × 1)
Option parts —
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1"×1(Option). ① : Pipe of O/U-Branch, ② : Pipe of Branch-I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
PCA001Z857 A
- 63 -
'19 • PAC-DB-308D
PCA001Z857 A
ModelItem
SRK140VSAWPZRIndoor unit SRK71ZR-W (2 units) Outdoor unit FDC140VSA-W
Power source 3 Phase, 380 - 415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 13.6 [ 5.0(Min.) - 14.5(Max.)]Nominal heating capacity (range) kW 15.5 [ 4.0(Min.) - 16.5(Max.)]
Power consumptionCooling
kW4.26
Heating 4.03Max power consumption 10.20
Running currentCooling
A6.2 / 6.5
Heating 5.9 / 6.2Inrush current, max current 5, 15
Power factorCooling
%99
Heating 99EER Cooling 3.19COP Heating 3.85
Sound power levelCooling
dB(A)
57 72Heating 60 73
Sound pressure levelCooling P-Hi: 44 Hi: 41 Me: 37 Lo: 25 56Heating P-Hi: 46 Hi: 39 Me: 35 Lo: 28 58
Silent mode sound pressure level — 49 /45(Normal/Silent)Exterior dimensions (Height x Width x Depth) mm 339 x 1,197 x 262 845 x 970 x 370Exterior appearance(Munsell color)(RAL color )
Fine snow(8.0Y9.3/0.1) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 15.5 78Compressor type & Q'ty — RMT5126SWP4×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Pre-charged up to the piping length of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Tangential fan x1 Propeller fan x1Fan motor (Starting method) W 56 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/minHi: 20.5 Me: 18.6 Lo: 16.2 ULo: 10.4 75
Heating Hi: 25.0 Me: 19.8 Lo: 17.3 ULo: 13.3 73Available external static pressure Pa 0 0Outside air intake Not possible —Air filter, Quality / Quantity Polypropylene net (Washable) x 2 —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A, RC-E5 , RCH-E3 Interface kit : SC-BIKN2-ERoom temperature control Thermostat by electronicsOperation display RUN: Green , TIMER: Yellow , HI POWER: Green , 3D AUTO: Orange
Safety equipmentsInternal thermostat for fan motor
Frost protection thermostatAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 9.52(3/8") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/U φ 9.52 (3/8")
Gas line φ 15.88 (5/8") ②φ 15.88(5/8")x1.0 ①φ 15.88 (5/8")x1.0 φ 15.88 (5/8")Connecting method Flare piping Flare pipingAttached length of piping Liquid line : 0.78 / Gas line : 0.72 —Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with (VP16) Hole size φ 20 x 3pcs
Drain pump, max lift height mm — —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mm x 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24
Standard accessoriesMounting kit, Clean filter
(Allergen clear filter ×1 , Photocatalytic washable deodorizing filter × 1)
Option parts —
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-WA1"×1(Option). ① : Pipe of O/U-Branch, ② : Pipe of Branch-I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 64 -
'19 • PAC-DB-308D
PCA001Z857 A
ModelItem
SRK140VNAWTZSXIndoor unit SRK50ZSX-W (3 units) Outdoor unit FDC140VNA-W
Power source 1 Phase, 220 - 240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 13.6 [ 5.0(Min.) - 14.5(Max.)]Nominal heating capacity (range) kW 15.5 [ 4.0(Min.) - 16.5(Max.)]
Power consumptionCooling
kW4.26
Heating 3.74Max power consumption 6.40
Running currentCooling
A18.7 / 19.6
Heating 16.4 / 17.2Inrush current, max current 5, 24
Power factorCooling
%99
Heating 99EER Cooling 3.19COP Heating 4.14
Sound power levelCooling
dB(A)
57 72Heating 62 73
Sound pressure levelCooling P-Hi: 44 Hi: 39 Me: 31 Lo: 22 56Heating P-Hi: 46 Hi: 41 Me: 33 Lo: 23 58
Silent mode sound pressure level — 49 /45(Normal/Silent)Exterior dimensions (Height x Width x Depth) mm 305 x 920 x 220 845 x 970 x 370Exterior appearance(Munsell color)(RAL color )
Fine snow(8.0Y9.3/0.1) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 13 77Compressor type & Q'ty — RMT5126SWP3×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Pre-charged up to the piping length of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Tangential fan x1 Propeller fan x1Fan motor (Starting method) W 42 x 1 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/minHi: 14.3 Me: 12.4 Lo: 7.8 ULo: 5.4 75
Heating Hi: 17.3 Me: 14.3 Lo: 9.8 ULo: 6.2 73Available external static pressure Pa 0 0Outside air intake Not possible —Air filter, Quality / Quantity Polypropylene net (Washable) x 2 —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A, RC-E5 , RCH-E3 Interface kit : SC-BIKN2-ERoom temperature control Thermostat by electronicsOperation display RUN: Green, TIMER: Yellow, ECO: Blue
Safety equipmentsInternal thermostat for fan motor
Frost protection thermostatAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35(1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/U φ 9.52 (3/8")
Gas line φ 12.7 (1/2") ②φ 12.7(1/2")x0.8 ①φ 15.88 (5/8")x1.0 φ 15.88 (5/8")Connecting method Flare piping Flare pipingAttached length of piping — —Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP16 Hole size φ 20 x 3pcs
Drain pump, max lift height mm — —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mm x 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Clean filter —Option parts —
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-TA1"×1(Option). ① : Pipe of O/U-Branch, ② : Pipe of Branch-I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
(c) Triple type
- 65 -
'19 • PAC-DB-308D
ModelItem
SRK140VSAWTZSXIndoor unit SRK50ZSX-W (3 units) Outdoor unit FDC140VSA-W
Power source 3 Phase, 380 - 415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 13.6 [ 5.0(Min.) - 14.5(Max.)]Nominal heating capacity (range) kW 15.5 [ 4.0(Min.) - 16.5(Max.)]
Power consumptionCooling
kW4.26
Heating 3.74Max power consumption 10.20
Running currentCooling
A18.7 / 19.6
Heating 16.4 / 17.2Inrush current, max current 5, 15
Power factorCooling
%99
Heating 98EER Cooling 3.19COP Heating 4.14
Sound power levelCooling
dB(A)
59 72Heating 62 73
Sound pressure levelCooling P-Hi: 44 Hi: 39 Me: 31 Lo: 22 56Heating P-Hi: 46 Hi: 41 Me: 33 Lo: 23 58
Silent mode sound pressure level — 49 /45(Normal/Silent)Exterior dimensions (Height x Width x Depth) mm 305 x 920 x 220 845 x 970 x 370Exterior appearance(Munsell color)(RAL color )
Fine snow(8.0Y9.3/0.1) near equivalent(RAL 9003) near equivalent
Stucco white(4.2Y7.5/1.1) near equivalent(RAL 7044) near equivalent
Net weight kg 13 78Compressor type & Q'ty — RMT5126SWP4×1Compressor motor (Starting method) kW — Direct line startRefrigerant oil (Amount, type) L — 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Pre-charged up to the piping length of 30m)Heat exchanger Louver fin & inner grooved tubing M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Tangential fan x1 Propeller fan x1Fan motor (Starting method) W 42 x 1 < Direct line start > 86 < Direct line start >
Air flow Cooling
m3/minHi: 14.3 Me: 12.4 Lo: 7.8 ULo: 5.4 75
Heating Hi: 17.3 Me: 14.3 Lo: 9.8 ULo: 6.2 73Available external static pressure Pa 0 0Outside air intake Not possible —Air filter, Quality / Quantity Polypropylene net (Washable) x 2 —Shock & vibration absorber Rubber sleeve(for fan motor) Rubber sleeve (for fan motor & compressor)Electric heater W — 20(Crank case heater)
Operation control
Remote control (Option) Wired : RC-EX3A, RC-E5 , RCH-E3 Interface kit : SC-BIKN2-ERoom temperature control Thermostat by electronicsOperation display RUN: Green, TIMER: Yellow, ECO: Blue
Safety equipmentsInternal thermostat for fan motor
Frost protection thermostatAbnormal discharge temperature protection
Installation data
Refrigerant piping size (O.D)Liquid line
mmI/U φ 6.35(1/4") ②φ 9.52(3/8")x0.8 ①φ 9.52(3/8")x0.8 O/U φ 9.52 (3/8")
Gas line φ 12.7 (1/2") ②φ 12.7(1/2")x0.8 ①φ 15.88 (5/8")x1.0 φ 15.88 (5/8")Connecting method Flare piping Flare pipingAttached length of piping — —Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50Vertical height diff. between O/U and I/U m Max.50 (Outdoor unit is higher) Max.15 (Outdoor unit is lower)Drain hose Hose connectable with VP16 Hole size φ 20 x 3pcs
Drain pump, max lift height mm — —Recommended breaker size A —L.R.A. (Locked rotor ampere) A 5.0Interconnecting wires Size x Core number φ 1.6mm x 3 cores + earth cable / Terminal block (Screw fixing type) IP number IPX0 IP24Standard accessories Mounting kit, Clean filter —Option parts —
The pipe length is 7.5m.Notes (1) The data are measured at the following conditions.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) Select the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.(6) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.(7) Branching pipe set "DIS-TA1"×1(Option). ① : Pipe of O/U-Branch, ② : Pipe of Branch-I/U
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
PCA001Z857 A
- 66 -
'19 • PAC-DB-308D
PJF000Z552
15.88(
5 8")(F
lare)
9.52(3
8")(F
lare)
71
d
1.2 EXTERIOR DIMENSIONS(1) Indoor units
(a) Ceiling cassette-4 way type (FDT)
Models FDT50VH, 60VH, 71VH
- 67 -
'19 • PAC-DB-308D
Models FDT100VH, 125VH, 140VH
PJF000Z553
- 68 -
Deco
rativ
e pa
nel
Note
s(1) T
he m
odel
nam
e la
bel is
atta
ched
to th
e
con
trol b
ox lid
.
(2) S
uspe
nsio
n bo
lt pi
tch
P1,P
2 is
adju
stab
le
by
a pa
ttern
of t
he ri
ght t
able
.
(
3) D
raft
prev
entio
n fu
nctio
n (※
1) is
pro
vided
on
the
pane
l T-P
SAE-
5AW
-E o
nly.
Unit:
mm
Obsta
cle
Mak
e a
spac
e of
500
0 or
mor
e be
twee
nth
e un
its w
hen
insta
lling
mor
e th
an o
ne.
or more
or mo
re10
00
1000
Spac
e fo
r ins
talla
tion
and
serv
ice
177
02
770ー
800
725
725ー
770
P1P2
Patte
rnSy
mbol
Susp
ensio
n bo
lt pitc
h ra
nge
ACo
ntent
Gas p
iping
φ15
.88(5/
8")(Fla
re)B
Liquid
pipin
gφ
9.52(3
/8")(
Flare)
CDr
ain pi
ping
VP25(
O.D.
32)
DHo
le for
wirin
gF
Susp
ensio
n bolt
s(M
10 or
M8)
G
Hang
er pla
te for
susp
ensio
n bolt
(Max. drain lift)
H1φ
125(K
nock
out)
Contr
ol bo
x
Symb
ol
H2φ
200(K
nock
out)
Outsi
de ai
r ope
ning
for du
cting
Air ou
tlet o
penin
gfor
ducti
ng
Contr
olbo
x
Susp
ensio
n bolt
s pitc
h:P1(7
78)
Suspension bolts pitch:P2(725)
(Ins
talled
on si
te)
Drain
hose
piec
e(A
cces
sory)
Hole
Holes
for
tappin
g scre
ws
Holes
for
tappin
g scre
ws
(Kno
ck ou
t)
Hole
Hole
Holes
for
tappin
g sc
rews
Air su
pply
Air re
turn g
rille
Draft
prev
entio
n fun
ction(
※1)
□630
□950
860ー
910(C
eiling
hole
size)
568420
42024
5 303
333
50 or more140
188
□840
131173
298 35
215ー
245
850 or less
140100
10060140
140
6-φ4
140100
130
240
1406-φ
420
076
112
137
129
5038
9940
65
5-φ4
167
4413
H1,2
G
H1,2
H1,2
BA
FC
H1H2
H1,2
D
G
Unit:
mm
AGa
s pipi
ngφ
15.88(
5/8")(
Flare)
BLiq
uid pi
ping
φ9.5
2(3/8
")(Fla
re)C
Drain
pipin
gVP
25(O.
D.32)
DHo
le for
wirin
gF
Susp
ensio
n bolt
s(M
10 or
M8)
G
Spac
e for
instal
lation
and s
ervice
Obsta
cle
H1,2
G
H1,2
H1,2
Drain
hose
piec
e
BA
FC
(Max. Drain lift)
H1H2
φ12
5(Kno
ck ou
t)φ
200(K
nock
out)
H1,2
D
G
177
02
770-8
0072
572
5-770
P1P2
Patte
rnSymb
olPit
ch ar
ea ta
ble of
susp
ensio
n bolt
Symb
olCo
ntent
Outsid
e air o
penin
gfor
ductin
gAir
outle
t ope
ning
for du
cting
(Kno
ck ou
t)
or more
or mo
re
Make
a sp
ace o
f 500
0 or m
ore be
twee
n th
e unit
s whe
n ins
tallin
g more
than
one.
Holes
for
tappin
g scre
wsHo
les fo
r tap
ping s
crews
Deco
rative
pane
l
Air su
pply
Air re
turn g
rille
Susp
ensio
n bolt
s pitc
h:P1
(Ceil
ing ho
le siz
e)
box
Contr
ol
Suspension bolts pitch:P2
(Acc
esso
ry)(I
nstal
led on
site)
susp
ensio
n bolt
Hang
er pla
te for
Contr
ol bo
x
Hole
Hole
Holes
for
tappin
g sc
rews
Hole
H1 H2
Anti d
raft fu
nctio
n(※1)
Note
s (1)
The
mod
el na
me
label
is at
tach
ed to
the
con
trol b
ox lid
.
(
2)Su
spen
sion
bolt p
itch
P1,P
2 is
adjus
table
b
y a p
atte
rn o
f the
righ
t tab
le. (
3)Se
ction
1(※
1)is
prov
ided
on th
e pa
nel
T-P
SAE-
5AW
-E o
nly.
1000
1000
□630
□950
(778)
860-9
10
(725)568
420
42024
5 303
333
50 or more140
188
□840
131173
298 35
215-2
45
850 or less
140100
10060140
140
6-φ4
140100
130
240
1406-φ
420
0
76
112
137
129
5038
9940
65
5-φ4
167
4413
'19 • PAC-DB-308D
Unit:
mm
ACo
ntent
Gas p
iping
BLiq
uid pi
ping
CDr
ain pi
ping
VP25(
O.D.
32)
D1Po
wer s
ource
conn
ectio
n
FSu
spen
sion b
olts
(M10
or M
8)
G
Spac
e fo
r ins
talla
tion
and
serv
ice
Obsta
cle
Mak
e a
spac
e of
400
0 or
mor
e be
twee
n
Hφ
125(K
nock
out)
Symb
ol
for du
cting
Outsi
de ai
r ope
ning
for du
cting
Air o
utlet
open
ing
or more
or mo
re
the
units
whe
n in
stal
ling
mor
e th
an o
ne.
(Kno
ck ou
t)
Note
s (1)
The
mod
el n
ame
labe
l is a
ttach
ed to
the
cont
rol b
ox lid
.
(
2)Th
is un
it is
desig
ned
for 2
x2 g
rid c
eilin
g.
If it
is in
stal
led
on a
cei
ling
othe
r tha
n 2x
2 gr
id c
eilin
g,
prov
ide
an in
spec
tion
open
ing
on th
e co
ntro
l box
sid
e.
(3)
Draf
t pre
vent
ion
func
tion(
※) i
s pr
ovid
ed o
n th
e pa
nel T
C-PS
AE-5
AW-E
onl
y.
φ6.3
5(1/4
")(Fla
re)
Hang
er p
late
for
box
susp
ensio
n bo
lt
(Ac
cess
ory)
(In
stalle
d on
site)
Drain
hos
e pie
ce
Draf
t pre
vent
ion fu
nctio
n(※
)
Deco
rative
pane
l
Air s
upply
Air r
etur
n gr
ille
Hole Ho
le
6-φ4
Holes
for
tappin
g scre
ws
4-φ4
Holes
for
tappin
g scre
ws
D2Re
mote
contr
ol co
de an
dsig
nal w
iring c
onne
ction
Contr
ol
JIns
pecti
on op
ening
450×
450
φ12
.7(1/
2")(Fla
re)
H
H
H
BA
CF
G
D2D1
H GD1
Cont
rol b
ox
J
Insp
ectio
n op
enin
g(Re
fer t
o no
te(2)
)
1000
1000
530
530
□570
248
130190
10210
130
288
110
50
46722
517
518
5
354325
73
184
63
Susp
ensio
n bo
lts p
itch
Suspension bolts pitch(
)()
8960
140
140
88 77
89
100
100
158
Max. drain lift ()or less
-245
215
850
or more
□400
□620
□576
-600
□576
-610
Ceilin
g ho
le siz
e(
)Sy
stem
ceilin
g ho
le siz
e(
)
φ10
0
150-200
(b) Ceiling cassette-4 way compact type (FDTC)
Models FDTC50VH, 60VH
PJF000Z515 A
- 69 -
'19 • PAC-DB-308D
(c) Duct connected-High static pressure type(FDU)
Models FDU100VH, 125VH, 140VH
PJG000Z579
- 70 -
(Duct dimension)
(Du
ct dim
ensio
n)
Note(c)
Fan unit
View M
tapping screwsHoles for
Return air duct
Hole
A Gas pipingB Liquid piping
D Hole for wiringE Suspension bolts M10
FOutside air opening
Air outlet openingG
Symbol Content
φ9.52(3/8")(Flare)
for ducting
for ducting
Drain pipingC2
(Gravity drainage)
φ15.88(5/8")(Flare)
(Knock out)
(Knock out)
Drain hose piece(Accessory)
(Installed on site)
H Inspection hole (450×450)
φ170
φ124
φ170
tapping screwsHoles for
Space for installation and service
or m
ore
or m
ore
or m
ore
or m
ore
(Case 1) From side of unitSelect either of two cases to keep space for installation and services.
or m
ore
or m
ore
(Case 2) From bottom of unit
Notes(a)There must not be obstacle to draw out 2 fan units. For fan units maintenance, refer to the service manual. (b)Install refrigerant pipes, drain pipe, and wiring so as not to cross marked area. (c)The case that pipes are installed to upper(bottom)of fan unit, keep space of 60mm or more to upper(bottom)of unit.
C1 Drain piping VP25(O.D.32)
VP20
Unit:mm
4-φ4
(Suspension bolts pitch)
Air supply duct
Control box
(Duct dimension)
(Du
ct dim
ensio
n)
18 1368 181404
suspension boltHanger plate for
104 1200 104
92 250
184.
513
4.5
467
405468
63573830 30
280
71
59
86284
152 285
23.5
235
21.5
64 1280 64
139
□90
600
(M
ax. d
rain
lift)
(Su
spen
sion
bolts
pitc
h)28
530
180
or le
ss
113
69
295�325
4317
0
4-φ4
100015
0─ 200
100―200
100
Slab
2020
Note(a)370
Ceiling
Note(b)
600
1720
100
Inspectionhole
725
Note(a)
1550
F G
M
C2
D
AC1
BG
F
E
H
Note(1)The model name label is attached on the lid of the control box.
'19 • PAC-DB-308D
Notes (a) There must not be obstacle to draw out fan unit. For fan unit maintenance, refer to the service manual. (b) Install refrigerant pipes, drain pipe,and wiring so as not to cross marked area. (c) The case that pipes are installed to upper (bottom) of fan unit, keep space of 60mm or more to upper (bottom) of unit.
295~325
Note (c)
Fan unit
View M
tapping screwsHoles for
Return air duct
Drain hose piece(Accessory)
(Installed on site)
Hole
tapping screwHoles for
A Gas pipingB Liquid piping
C1 Drain piping VP25(O.D.32)
D Hole for wiringE Suspension bolts (M10)
FOutside air opening
Air outlet openingG
Symbol Content
φ12.7(1/2")(Flare)
for ducting
for ducting
(φ150)(Knock out)
(φ125)(Knock out)
Drain pipingC2
(Gravity drainage)VP20
φ6.35(1/4")(Flare)
H Inspection opening (450×450)
φ170
φ124
φ170
tapping screwsHoles for
Space for installation and service
or m
ore
or m
ore
or m
ore
or m
ore
(Case 1) From side of unit
or m
ore
or m
ore
(Case 2) From bottom of unit
(Suspension bolts pitch)
Air supply duct
Control box
600
(M
ax. d
rain
lift)
or le
ss
(Duct dimension)
(Du
ct d
imen
sion)
4317
028
472
135
18 750 18786
suspension boltHanger plate for
55 680 55
76
6758
86284
152 262
41200
39
65 660 65
139
□90
46 200200 4620031
170
31
280
467
413471
510635 3030
105
175
250
(Duct dimension)
(Du
ct d
imen
sion)
69 113
100015
0-20
0
100-200
100
Slab
2020
Note (a)
370Ceiling
Note (b)
600
1100 10
0
Inspectionopening
620
Note (a)
Unit:mm
1550
(Su
spen
sion
bolts
pitc
h)
F G
M
E
C2
D
A
1C
B
G
F
H
Note(1) The model name label is attached on the lid of the control box.
Select either of two cases to keep space for installation and services.
12-φ4
4-φ44-φ4
(d) Duct connected-Low / Middle static pressure type (FDUM)
Model FDUM50VH
PJG000Z485
- 71 -
'19 • PAC-DB-308D
Models FDUM60VH, 70VH
PJG000Z486
- 72 -
295~325
View M
tapping screwsHoles for
Return air duct
Drain hose piece(Accessory)
(Installed on site)
tapping screwHoles for
A Gas piping
Model
B Liquid piping
C1 Drain piping
D Hole for wiringE Suspension bolts (M10)
FOutside air opening
Air outlet openingG
Symbol Content
φ6.35(1/4")(Flare)
for ducting
for ducting
Drain pipingC2
(Gravity drainage)
(φ150)(Knock out)
(φ125)(Knock out)
φ12.7(1/2")(Flare)
60 71
φ9.52(3/8")(Flare)
φ15.88(5/8")(Flare)
H Inspection opening (450×450)
Hole
φ170
φ124
φ170
tapping screwsHoles for 4-φ4
(Suspension bolts pitch)
Control box
600
(M
ax. d
rain
lift)
or le
ss
(Duct dimension)
(Du
ct d
imen
sion)
(Su
spen
sion
bolts
pitc
h)
2847
213
5
18 950 18986
suspension boltHanger plate for
55 880 55
76 250 17
510
5
467
413471
51063530 30
280
67
86284
152 262
41200
39
65 860 65
139
□90
46 4×200=800 46
3117
031
14-φ4
58
113
Air supply duct
4317
0(
Duct
dim
ensio
n)
(Duct dimension)
69
4-φ4
200
1550M
C2
D
A
C1
B
G
F
F G
E
Space for installation and service
or m
ore
or m
ore
or m
ore
or m
ore
(Case 1) From side of unitSelect either of two cases to keep space for installation and services.
or m
ore
or m
ore
(Case 2) From bottom of unit
Notes (a) There must not be obstacle to draw out fan unit. For fan unit maintenance, refer to the service manual. (b) Install refrigerant pipes, drain pipe,and wiring so as not to cross marked area. (c) The case that pipes are installed to upper (bottom) of fan unit, keep space of 60mm or more to upper (bottom) of unit.
100015
0-20
0
100-200
100
Slab
2020
Note (a)
370Ceiling
Note (b)
600
1300 10
0
Inspectionopening
620
H
Note (c)
Fan unit
Note (a)
Note(1) The model name label is attached on the lid of the control box.
VP25( O.D.32)
VP20
'19 • PAC-DB-308D
Models FDUM100VH, 125VH, 140VH
PJG000Z487
- 73 -
Note c
Fan unit
View M
Holes fortapping screws
Return air duct
Hole
tapping screwHoles for
A Gas pipingB Liquid piping
D Hole for wiringE Suspension bolts (M10)
FOutside air opening
Air outlet openingG
Symbol Content
9.52(3 8")(Flare)
for ducting
for ducting
Drain pipingC2 (Gravity drainage)
15.88(5 8")(Flare)
( 150)(Knock out)
( 125)( Knock out)
Drain hose piece(Accessory)(Installed on site)
H Inspection opening 450×450
170
124
170
Holes fortapping screws
Space for installation and service
or m
ore
or m
ore
or m
ore
or m
ore
(Case 1) From side of unitSelect either of two cases to keep space for installation and services.
or m
ore
or m
ore
(Case 2) From bottom of unit
Note(1) The model name labelis attached on the lid
of the control box.
Notes a) There must not be obstacle to draw out 2 fan units. For fan units maintenance, refer to service manual.
b Install refrigerant pipes, drain pipe,and wiring so as not to cross marked area.
c The case that pipes are installed to upper bottom of fan unit, keep space of 60mm or more to upper bottom of unit.
C1 Drain piping VP25 O.D.32
VP20
Unit:mm
4 4
Suspension bolts pitch
Air supply duct
Control box
Duct dimension
Duct
dim
ensio
n
18 1368 181404
Hanger plate forsuspension bolt
104 1200 104
92 250
184.
513
4.5
467
405468
63573830 30
280
71
59
86284
152 285
23.5
235
21.5
64 1280 64
139
90
100 100
24.5
205
24.5 14 4
600
Max
. dra
in lif
t
Susp
ensio
n bo
lts p
itch
2853
018
0
or le
ss
4 280=1120
113
69
295 325
4317
0Du
ct d
imen
sion
Duct dimension
280
4 4
100015
0 200
100 200
100
Slab
2020
Note (a)370
Ceiling
Note (b)
600
1720
100
Inspectionopening
725
Note (a)
1545
F G
M
C2
D
AC1
BG
F
E
H
'19 • PAC-DB-308D
(e) Ceiling suspended type (FDE)
Model FDE50VH
PFA004Z084
C 2
C 1,C
2
C 1,C
2
C 1A
B
GE
F
D
B A
- 74 -
'19 • PAC-DB-308D
C 2C 1
AB
AB
D
C 1,C
2
C 1,C
2
EG
F
Models FDE60VH, 71VH
PFA004Z085
- 75 -
'19 • PAC-DB-308D
Models FDE100VH, 125VH, 140VH
PFA004Z086
- 76 -
C 1,C
2
C 1,C
2
C 2C1
A
E
GF
AB
B
D
'19 • PAC-DB-308D
RLF000Z202
(f) Wall mounted type (SRK)
Models SRK50ZSX-W, 60ZSX-W
- 77 -
Hole
on w
all fo
r righ
t rea
r pipi
ngHo
le on
wall
for l
eft r
ear p
iping
Gas p
iping
Outle
t for
pipi
ngDr
ain h
ose
FEC D
Sym
bol
A
(φ
65)
VP16
Cont
ent
(φ
65)
φ9.
52(
3/8"
)(
Flar
e)
Wire
less r
emot
e co
ntro
l
Wire
d re
mot
e co
ntro
l(
Optio
n)
φ6.
35(
1/4"
)(
Flar
e)Liq
uid p
iping
B
Uni
t:mm
Not
es(
1)Th
e m
odel
nam
e la
bel i
s at
tach
ed
on th
e rig
ht s
ide
of th
e un
it.
(
2)To
con
nect
the
wire
d re
mot
e co
ntro
l,
the
inte
rface
kit(
SC
-BIK
N2-
E) is
requ
ired.
□120
19
6024
167
□120
19
920
305
6045
55
6035
55
59.5 12.5
45
59.5 12.5
61
220
3
100
100
118.
511
8.5
683
145
630
145
176
568
176
460
460
10.3 277.3 17.4
56.4
47
48.6
76.6
47
6570
548
533
65 120
88.6
(Service space)
480
(Se
rvice
spac
e)
(Service space)
(Se
rvice
spac
e)
Outle
t for
dow
nwar
d pip
ing(
Refe
r to
the
top
view)
Unit
Insta
llatio
n bo
ard
Term
inal b
lock
Spac
e fo
r ins
talla
tion
and
serv
ice w
hen
viewi
ng fr
om th
e fro
nt
DB
AE
C
FF
FF
'19 • PAC-DB-308D
43.5
64
55
G
Hole
on w
all fo
r righ
t rea
r pipi
ngHo
le on
wall
for l
eft r
ear p
iping
Gas p
iping
Outle
t for
wirin
g(on
bot
h sid
e)Dr
ain h
ose
Liquid
pipi
ng
FEC DB
Sym
bol
A
(φ
65)
VP16
Cont
ent
(φ
65)
Outle
t for
pipi
ng(on
bot
h sid
e)G
Wire
less
rem
ote
cont
rol
Wire
d re
mot
e co
ntro
l(
Opt
ion)
φ6.
35(1/
4")(
Flar
e)φ
15.8
8(5/
8")(
Flar
e)SR
K 71
φ9.
52(3/
8")(
Flar
e)SR
K 10
0
Spac
e fo
r Ser
vice
Unit
Spac
e fo
r ins
talla
tion
and
serv
ice w
hen
viewi
ng fr
om th
e fro
nt
768
157
48 240
6.7322.4
214.
521
4.5
883
157
10
326
2
1964
55
47
5377
47
1197
339
150
50Sp
ace
for s
ervic
e
Space for service Space for service 15100
780
715 75
9
55
Insta
llatio
n bo
ard
Outle
t for
dow
nwar
d pip
ing(
Refe
r to
the
top
view)
Term
inal b
lock
60
24043
470
363.
536
3.5
568.
556
8.5
1160
Unit:m
m
Note
s(1)
The
mod
el n
ame
labe
l is a
ttach
ed
on
the
unde
rsid
e of
the
indo
or u
nit.
(2)
To c
onne
ct th
e wi
red
rem
ote
cont
rol,
th
e in
terfa
ce k
it(SC
-BIK
N2-E) i
s re
quire
d.
DE
CA
B
G
G F
□120
19
6024
167
Models SRK71ZR-W, 100ZR-W
RLD000Z005 A
- 78 -
'19 • PAC-DB-308D
51
40
40
103
110 50195242279
970
5016
55
37039 3941019 19
56
60
325
263
39
7618
958
020
160
16
10316
502752
110 50195
67
70 50150
41
Term
inal b
lock
Note
s (
1) It
mus
t not
be
surro
unde
d by
wal
ls on
the
four
sid
es.
(2)
The
uni
t mus
t be
fixed
with
anc
hor b
olts
. An
anch
or b
olt m
ust n
ot
pr
otru
de m
ore
the
15m
m.
(3)
Whe
re th
e un
it is
subj
ect t
o st
rong
win
ds, l
ay it
in s
uch
a
dire
ctio
n th
at th
e bl
ower
out
let f
aces
per
pend
icula
rly
to th
e do
min
ant w
ind
dire
ctio
n. (
4) L
eave
1m
or m
ore
spac
e ab
ove
the
unit.
(5)
A w
all in
fron
t of t
he b
lowe
r out
let m
ust n
ot e
xcee
d th
e un
its h
eigh
t. (
6) T
he m
odel
nam
e la
bel is
atta
ched
on
the
lowe
r rig
ht c
orne
r of t
he fr
ont p
anel
.
φ15
.88(
5/8")(
Flar
e)Co
ntent
CPi
pe/
cable
dra
w-ou
t hole
D EAn
chor
bolt
hole
Drain
disc
harg
e ho
le
Symb
ol
BASe
rvice
valve
conn
ectio
n(ga
s side)
M10
×4 p
laces
φ20
×3 p
laces
Serv
ice va
lve co
nnec
tion(
liquid
side)
φ9.
52(3/
8")(
Flar
e)
L2L4
L2 L3 L4L130
015
015
0
OpenI
Ⅱ
Open
150
150
500
Ⅲ
Open
150
3005
FCa
ble d
raw-
out h
oleφ
30×3
plac
es
Exam
ples o
f
Dimen
sions ins
tallation
9
Unit:
mm
84510
C3
C1
C2Cent
er o
f Gra
vity
FDC1
00,12
5,140
VNA-
W37
838
0C1
178
178
370
382C2
C3
FDC1
00,12
5,140
VSA-
W
MOD
ELL1L3
Intak
e
Outle
t
Intak
e
Min
imum
inst
alla
tion
spac
e
spac
eSe
rvice
C
E
C
D
AB
FF
B
A
CCF
(2) Outdoor units
Model FDC100VNA-W, 125VNA-W, 140VNA-W
100VSA-W, 125VSA-W, 140VSA-W
PCA001Z853
- 79 -
'19 • PAC-DB-308D
Installation space
30mm
30mm
30mm
120mm
配線
30mm 30mm
30mm
120m
m
Wiring
R/C temperature sensor
Secure minimum spaces for disassembling the case.Upper left and Upper right sides ……30mm or moreBottom side…120mm or moreIf using L-shaped screwdriver, 50mm or more is available.
Dimensions (Viewed from front)
37 23 23
固定穴
18.3
83.5
120
19120
37 23 23 19120
Fixing holes 83.5
120
18.3
≦ 200 m 0.5 mm2 x 2 cores
≦ 300m 0.75 mm2 x 2 cores
≦ 400m 1.25 mm2 x 2 cores
≦ 600m 2.0 mm2 x 2 cores
● Do not install the remote control at following places. 1) It could cause break-down or deformation of remote control.・Where it is exposed to direct sunlight・Where the ambient temperature becomes 0 °C or below, or 40 °C or above・Where the surface is not flat・Where the strength of installation area is insufficient
2) Moisture may be attached to internal parts of the remote control, resulting in a display failure.・Place with high humidity where condensation occurs on the remote control・Where the remote control gets wet
3) Accurate room temperature may not be detected using the temperature sensor of the remote control.・Where the average room temperature cannot be detected・Place near the equipment to generate heat・Place affected by outside air in opening/closing the door・Place exposed to direct sunlight or wind from air-conditioner・Where the difference between wall and room temperature is large
4) When you are using the automatic grille up and down panel in the IU, you may not be able to confirm the up and down motion.・Where the IU cannot be visually confirmed
● When installing the unit at a hospital, telecommunication facility, etc., take measures tosuppress electric noises.
It could cause malfunction or break-down due to hazardous effects on the inverter, private power generator,high frequency medical equipment, radio communication equipment, etc.The influences transmitted from the remote control to medical or communication equipment could disrupt medicalactivities, video broadcasting or cause noise interference.
R/C cable:0.3mm2x2 coresWhen the cable length is longer than 100 m, the max size for wires used in the R/C case is 0.5 mm2 . Connect them to wires of larger size near the outside of R/C. When wires are connected, take measures to prevent water, etc. from entering inside.
Adapted RoHS directive
(3) Remote control (Option parts)
(a) Wired remote control
Model RC-EX3A
PJZ000Z333
- 80 -
'19 • PAC-DB-308D
TEMP ON/OFF
48
120
L C D
Wall surface
Wiring
Electrical boxNot included
19
Wiring specifications
Exposed mounting
2346
11.5 11
Remote control outline
12045
83.5
42
120
Remote control installation dimensions
Wiring oulet
Installation hole12×7 slot hole
9.5×5 slot hole 4 places
1 Installation screw for remote controlM4 screw (2 pieces)
44
1) If the prolongation is over 100m, change to the size below. But, wiring in the remote control case should be under 0.5mm2. Change the wire size outside of the case according to wire connecting. Waterproof treatment is necessary at the wire connecting section. Be careful about contact failure.
Length Wiring thickness
100 to 200m 0.5mm2×2 cores0.75mm2×2 cores1.25mm2×2 cores2.0mm2×2 cores
Under 300mUnder 400mUnder 600m
Upper part
Lower part
Lower case
Sheath
Upper cace
Board
Wiring
Upper
Lower
X Y
Sheath
Upper cace
Board
Wiring
Upper
Lower
YX
Tighten the screws aftercutting off the thin part ofscrew mounting part.
Embedded mounting
The peeling-off length of sheath
The peeling-off length of sheath
In case of pulling out fromupper left
In case of pulling out from upper left
In case of pulling out from upper left
X wiring : 170mmY wiring : 190mm
Pulling out from center
X wiring : 215mmY wiring : 195mm
Pulling out from upper left
In case of pulling out from center
In case of pulling out from center
In case of pulling out from center
Wiring outletCut off the upper thin part of remote control lower case with a nipper or knife,and grind burrs with a file etc.
0.3mm2×2 cores
X, Y terminal blockAttach M3 screw with washer
Unit:mm
Exterior appearance(Munsell color)
Pearl white(N8.5) near equivalent
Model RC-E5
PJZ000Z295
- 81 -
'19 • PAC-DB-308D
(b) Wireless remote controlRCN-E2(Option parts) (Except SRK series)
60 2416
7
(3) Remote control
Unit : mm
60 24
167
SRK series only
- 82 -
Unit: mm
Unit: mm
'19 • PAC-DB-308D1.3 ELECTRICAL WIRING
(1) Indoor units
(a) Ceiling cassette-4 way type (FDT)
Models FDT50VH, 60VH, 71VH, 100VH, 125VH, 140VH
PJF000Z554
- 83 -
Notes
1.
ind
icates
wirin
g on s
ite.
2. Se
e the
wirin
g diag
ram of
outsi
de un
it abo
ut the
line b
etwee
n
3. U
se tw
in co
re co
rd(0.3
mm2 )
at rem
ote co
ntrol
line.
See
spec
shee
t of re
mote
contr
ol in
case
that
the to
tal le
ngth
is mo
re tha
n 100
m.
indoo
r unit
and o
utdoo
r unit
.
4. D
o not
put re
mote
contr
ol lin
e alon
gside
powe
r sou
rce lin
e.
5.
Secti
on 1(
※1)
is pro
vided
on th
e pan
el T-P
SAE-
5AW-
E only
.
CNTA BL
12
Th -A
CNI
BL
CNJ1 WH
LM4
LM1
LM2
LM3
CNJ2 GY
M AM4
M AM1
1
M AM2
M AM3
6 5 4 3 2 1
CNN
YE
Thi-R
3
Thi-R
2
Thi-R
1t°t°t°
2 1CN
CWHCN
LBK
CNH
BK
12
t°I
SW6
SW7
DM
12 CN
RWH
M
CNM1 WH
FMi M
F2
CNB
BK
LED・
3LE
D・2
23
45
12
34
51
23
45
12
34
5
12
34
56
78
910
1112
1314
1516
1718
1920
3 1 2 1
RD RDRDRDYEBKBK YE
2
14
56
7
Pow
er c
ircui
t
XR1
XR5
(Oper
ation)
(Heat
ing)
(Com
presso
r ON)
(Insp
ection
)
Prep
are on
site
XR2
XR3
XR4
1 2 3 4 5 6
FS
X YX Y
t°
Rem
ote
cont
rol
TB2
WH BKTh
C
1 2TB1
Earth
YE/
GN
F1
CNWO WH
13
5
MM
1
MM
BK
23
45
12
34
51
23
45
12
34
5
12
34
56
78
910
1112
1314
1516
1718
1920
BKBK
BKBK
BKBK
BKBK
BK
BLRD
BROR
WH
YE/
GN
RD
+12
+12
+12
3
Powe
r sou
rce lin
eSig
nal lin
e1
2
3
CNW3 WH1 3
WH BL
(2.0
A)(
3.15A
)
WHYE
/GN
PIS
WHWH
WHWH
WHWH
WHWH
WHWH
BLBL
BLBL
BLBL
BLBL
BLBL
RDRD
RDRD
RDRD
RDRD
RDRD
SW2
※1
BKBKBK
BKBK
RDWH
E1
Indoo
r unit
PCB
1 2
Optio
n
Remo
te oper
ation in
put(v
olt-fre
e cont
act)
The
line
betw
een
indoo
r unit
and
out
door
unit
[ ]
CNT
BL
HSBKBK
Remo
te op
eratio
n inp
ut(
volt-f
ree co
ntact)
Opera
tion ch
eck,dr
ain pu
mp m
otor te
st run
Temp
eratur
e sen
sor(
Remo
te co
ntrol)
Mode
l cap
acity
settin
gSW
6
Term
inal bl
ock(P
ower
source
)(□ ma
rk)TB
1TB
2
SW2
Remo
te co
ntrol
comm
unica
tion a
ddres
s
SW7-1
Thi-A
Thi-R
1,2,3
Th C
Term
inal b
lock(
Signa
l line)
( □ m
ark)
Temp
eratur
e sen
sor(
Retur
n air)
Temp
eratur
e sen
sor(
Heat
exch
ange
r)
Drain
pump
moto
r
Fan m
otor
DMFu
seF1
,2
Conn
ector
CNB-
Z
FMi
Desc
riptio
nIte
mDr
aft p
reve
ntion
func
tion
mot
orAM
1-4
Louv
er m
otor
Float
switc
h
LM1-
4
FS
Indica
tion l
amp(
Red-I
nspe
ction)
LED・
2Ind
icatio
n lam
p(Gr
een-N
omal
opera
tion)
LED・
3
LRe
actor
PISMo
tion s
enso
r
Humi
dity s
enso
rHS SW
5Plu
ral un
its Ma
ster/
Slave
settin
g
Color
mark
sMa
rkCo
lor
Blue
BK BLBr
own
Oran
geBR OR
Red
RD
Black
Mark
Color
Yello
wWH YE
Gray
Yellow
/Gree
nGY YE
/GN
White
Prep
are on
site
SW5
'19 • PAC-DB-308D
Thi-A
[ ]
Opera
tion ch
eck,dr
ain pu
mp m
otor te
st run
Tempe
rature
senso
r(Rem
ote co
ntrol)
Mode
l capa
city se
tting
SW6
Termin
al bloc
k(Pow
er sou
rce)(□
mark)
TB1
TB2
SW2
Remo
te con
trol co
mmun
ication
addre
ss
SW7-1
Thi-A
Thi-R
1,2,3
Thc
Termin
al bloc
k(Sign
al line)(□
mark)
Tempe
rature
senso
r(Retu
rn air)
Tempe
rature
senso
r(Hea
t exch
ange
r)
Drain p
ump m
otor
Fan m
otor
DMFu
seF1
,2
Conn
ector
CNB-Z
FMi
Descr
iption
Item
Draft p
reven
tion fu
nction
moto
rAM
1-4
Louve
r moto
r
Float
switch
LM1-4
FS
Indica
tion lam
p(Red
-Inspe
ction)
LED・2
Indica
tion lam
p(Gree
n-Nom
al ope
ration)
LED・3
PISMo
tion se
nsor
Humid
ity sen
sorHS SW
5Plu
ral un
its Ma
ster/
Slave
setting
Color
mark
s
Mean
ing of
mark
s
Mar
kCo
lor
Blue
BK BLBr
own
Oran
geBR OR
Red
RD
Black
Mar
kCo
lor
Yello
wWH YE
Gray
Yellow/G
reen
GY YE/G
N
White
CNTA BL
12
CNI
BL
CNJ1
WHCN
J2 GY
AM4
AM1
AM2
AM3
6 5 4 3 2 1
CNN
YE
Thi-R
3
Thi-R
2
Thi-R
1t°t°t°
2 1CN
CWH
CNH
BK
12
t°DM
12 CN
RWH
M
CNM1 WH
FMi M
F2
CNB
BK
12
34
56
78
910
1112
1314
1516
1718
1920
2 1
RD RDRDRDYEBKBK YE
14
56
7
FSX Y
X Yt°
TB2 WH BK
Thc
TB1
YE/G
N
12
34
56
78
910
1112
1314
1516
1718
1920
BLRD
BROR
WH
+12
+12
(2.0A)
YE/G
N
※1
BKBK
RDWH
LM4
LM1
LM2
LM3
MM
1
MM
23
45
12
34
51
23
45
12
34
5
MM
1
MM
BK
23
45
12
34
51
23
45
12
34
5
BKBK
BKBK
BKBK
BKBK
BK
WHWH
WHWH
WHWH
WHWH
WHWH
BLBL
BLBL
BLBL
BLBL
BLBL
RDRD
RDRD
RDRD
RDRD
RDRD
E1
F1
CNWO WH
13
5
YE/G
N
RD
(3.15
A)
WH Powe
r circ
uit
Indoo
r unit
PCB
CNL
BK3 12
BKBKBKOp
tion
1 2
(volt
-free c
ontac
t)
HSBKBK
Remo
te op
eratio
n inp
ut
BKBK
BKBK
BKBK
BKBK
BKBK
RDRD
RDRD
RDRD
RDRD
RDRD
CNJ3 WH
CNJ4 WH
WHWH
WHWH
WHWH
WHWH
WHWH
BLBL
BLBL
BLBL
BLBL
BLBL
1 2
Earth
3
Powe
r sou
rce lin
eSig
nal lin
e1
2
3
CNW3 WH1 3
WH BL
The l
ine be
twee
nind
oor u
nit an
d outd
oor u
nit
XR1
XR5
(Ope
ration)
(Hea
ting)
(Com
presso
r ON)
(Ins
pecti
on)
Prep
are on
site
XR2
XR3
XR4
1 2 3 4 5 6
+12
Remo
te op
eratio
n inp
ut(v
olt-fre
e con
tact)
CNT
BL
CNM2 WH
BLRD
BROR
WH
PIS3 12
Remo
te con
trol
SW2
SW6
SW7
LED・
3LE
D・2
Prep
are on
site
SW5
Note
s 1
.
in
dica
tes
wirin
g on
site
.
2. S
ee th
e wi
ring
diag
ram
of o
utdo
or u
nit a
bout
the
line
betw
een
3. U
se tw
in c
ore
cord(
0.3m
m )
at re
mot
e co
ntro
l line
.2
ind
oor u
nit a
nd o
utdo
or u
nit.
4. D
o no
t put
rem
ote
cont
rol li
ne a
long
side
powe
r sou
rce
line.
5. D
raft
prev
entio
n fu
nctio
n(※1) i
s pr
ovid
ed o
n th
e pa
nel T
C-PS
AE-5
AW-E
onl
y.
(b) Ceiling casette-4 way compact type (FDTC)
Models FDTC50VH, 60VH
PJF000Z516 A
- 84 -
'19 • PAC-DB-308D
FMi1
FMi2
BL31
WHCN
W3 WH
RD RD
1 2CN
IBL
FS
CNZ
CNC
For H
A WH RD
RD
t°
Contr
ol PC
B
RD YE
t°YE BK
t°BK
1 2 3 4 5 6
BK
t°BK
1 2
XR1
XR2
XR3
XR4
1 2 3 4 5 6
+12
SW2
SW6
SW5
SW7
LED・
2LE
D・3
X Y1 3
TB2
WH BK WH8 9 10 11 12
CNW2 WH
CNW1 WH
CNB
WHCN
NYE CN
HBK CN
TBL
1 2WHRD
YE/G
N
3 5
CNW0 WH
1
(Ope
ration)
(Hea
ting)
(Com
presso
r ON)
(Ins
pecti
on)
3
Thi-R
1
Thi-R
2
Thi-R
3
Thi-A
WH WH WH WHWH WH WH WHWH WH WH WH5 6 72 3 41
YE/G
NCN
RWH
1 2DM
MRD WH
+12
8 9 10 11 125 6 72 3 41
1
PISCN
GBL CN
V2 BK
24 3
1 3
WH BK RD
WH RD BK
Prep
are on
site
TB1
M
14
56
7
RD
F4 (2A)
CNM2 BK
Powe
r circ
uit BKWH
BLYE
L
CNWR WH
13
Powe
r PCB
※1
Earth
The l
ine be
twee
n
21 3
Powe
r sou
rce lin
eSig
nal lin
e
indoo
r unit
and o
utdoo
r unit
Optio
n
X Yt°Th
cRe
mote
contr
ol
M
14
56
7
RD
F3 (2A)
CNM1 WH
BKWH
BLYE
F1(6.3
A)
1 2CN
TA BL(R
emote
opera
tion
inp
ut:vo
lt-free
conta
ct)
+12
Prep
are on
site
XR5(R
emote
opera
tion
input:
volt-f
ree co
ntact)
Thi-A
FMi1,
2FS
Float
switc
h
Indica
tion l
amp(R
ed-In
spec
tion)
Indica
tion l
amp(G
reen-N
ormal
opera
tion)
LED・
3LE
D・2
Conn
ector
CNB-Z
Mode
l cap
acity
settin
gSW
6Op
eratio
n che
ck,dr
ain pu
mp m
otor te
st run
SW7-1
SW5
Temp
eratur
e sen
sor(R
emote
contr
ol)
Temp
eratur
e sen
sor(H
eat e
xcha
nger)
Temp
eratur
e sen
sor(R
eturn
air)
Thc
Thi-R
1,2,3
TB2
Term
inal b
lock(S
ignal
line)(□m
ark)
TB1
Term
inal b
lock(P
ower
sourc
e)(□m
ark)
Remo
te co
ntrol
comm
unica
tion a
ddres
sSW
2Plu
ral un
its M
aster/S
lave s
etting
LRe
actor
F1,3,
4Fu
seFa
n moto
r
Drain
pump
moto
rDM
Motio
n sen
sor
PIS
Close
d-end
conn
ector
■mark
BKBla
ckBlu
e
Color
Mark
s
BLMark
Color
Red
RD WHYe
llow
White
Yello
w/Gr
een
YEYE/G
N
Item
Desc
riptio
nM
eanin
g of
mar
ks
Note
s 1
.
in
dica
tes
wirin
g on
site
.
2. S
ee th
e wi
ring
diag
ram
of o
utdo
or u
nit a
bout
the
line
betw
een
indo
or u
nit a
nd o
utdo
or u
nit.
3.
Use
twin
cor
e co
rd(0.
3mm
2)a
t rem
ote
cont
rol li
ne.
See
spec
she
et o
f rem
ote
cont
rol in
cas
e th
at th
e to
tal le
ngth
is m
ore
than
100
m.
4.
Do
not p
ut re
mot
e co
ntro
l line
alo
ngsid
e po
wer s
ourc
e lin
e.
5. S
ectio
n 1 (※
1)sh
ows
elec
tric
circu
it of
mot
ion
sens
or(O
ptio
n).
PJG000Z580
(c) Duct connected-High static pressure type (FDU)
Models FDU100VH, 125VH, 140VH
- 85 -
'19 • PAC-DB-308D
Note
s 1
.
in
dica
tes
wirin
g on
site
.
2. S
ee th
e wi
ring
diag
ram
of o
utdo
or u
nit a
bout
the
line
betw
een
indo
or u
nit a
nd o
utdo
or u
nit.
3.
Use
twin
cor
e co
rd(0.
3mm
2)a
t rem
ote
cont
rol li
ne.
See
spec
she
et o
f rem
ote
cont
rol in
cas
e th
at th
e to
tal le
ngth
is m
ore
than
100
m.
4.
Do
not p
ut re
mot
e co
ntro
l line
alo
ngsid
e po
wer s
ourc
e lin
e.
5. S
ectio
n 1(※
1)sh
ows
elec
tric
circu
it of
mot
ion
sens
or(O
ptio
n).FM
i1
RD RD
1 2CN
IBL
FS
CNZ
CNC
For H
A WH RD
RD
t°
Contr
ol PC
B
RD YE
t°YE BK
t°BK
1 2 3 4 5 6
BK
t°BK
1 2
XR1
XR2
XR3
XR4
1 2 3 4 5 6
+12
SW2
SW6
SW5
SW7
LED・
2LE
D・3
X Y1 3
X Yt°
TB2
WH BK WH8 9 10 11 12
CNW2 WH
CNW1 WH
CNB
WHCN
NYE CN
HBK CN
TBL
(Ope
ration)
(Hea
ting)
(Com
presso
r ON)
(Ins
pecti
on)
Thc
Thi-R
1
Thi-R
2
Thi-R
3
Thi-A
WH WH WH WH
Remo
te co
ntrol
WH WH WH WHWH WH WH WH5 6 72 3 41
CNR
WH1 2
DMM
RD WH
+12
8 9 10 11 125 6 72 3 41
1
PISCN
GBL CN
V2 BK
24 3
1 3
Optio
n
WH BK RD
WH RD BK
Prep
are on
site
M
14
56
7
RD
F3 (2A)
CNM1 WH
Powe
r PCB
Powe
r circ
uit
BL or BK
BR or WH
WH or BL
OR or YE
※1
BL31
WHCN
W3 WH
1 2WHRD
YE/G
N
3 5
CNW0 WH
1
3
YE/G
NTB
1
F1(3.1
5A)
LCN
WR2
W
H BK
F2(3.1
5A)
Earth
The l
ine be
twee
n
21 3
Powe
r sou
rce lin
eSig
nal lin
e
indoo
r unit
and o
utdoo
r unit
1 2CN
TA BL(R
emote
opera
tion
inp
ut:vo
lt-free
conta
ct)
+12
Prep
are on
site
XR5(R
emote
opera
tion
input:
volt-f
ree co
ntact)FM
i1FS
Float
switc
h
Indica
tion l
amp(R
ed-In
spec
tion)
Indica
tion l
amp(G
reen-N
ormal
opera
tion)
LED・
3LE
D・2
Conn
ector
CNB-Z
Mode
l cap
acity
settin
gSW
6Op
eratio
n che
ck,dr
ain pu
mp m
otor te
st run
SW7-1
SW5
Temp
eratur
e sen
sor (
Remo
te co
ntrol)
Temp
eratur
e sen
sor (
Heat
exch
ange
r)Te
mpera
ture s
enso
r (Re
turn a
ir)Th
c
Thi-R
1,2,3
Thi-A
TB2
Term
inal b
lock(S
ignal
line)(□m
ark)
TB1
Term
inal b
lock(P
ower
sourc
e)(□m
ark)
Remo
te co
ntrol
comm
unica
tion a
ddres
sSW
2Plu
ral un
its M
aster/S
lave s
etting
LRe
actor
F1-3
Fuse
Fan m
otor
Drain
pump
moto
rDM
Motio
n sen
sor
PIS
Close
d-end
conn
ector
■mark
BKBla
ckBlu
e
Color
Mark
s
BLMark
Color
BRBr
own
Oran
geOR
Red
RD WHYe
llow
White
Yello
w/Gr
een
YEYE/G
N
Item
Desc
riptio
nMe
aning
of m
arks
(d) Duct connected-Low / Middle static pressure type (FDUM)
Model FDUM50VH
PJG000Z488
- 86 -
'19 • PAC-DB-308D
Note
s 1
.
in
dica
tes
wirin
g on
site
.
2. S
ee th
e wi
ring
diag
ram
of o
utdo
or u
nit a
bout
the
line
betw
een
indo
or u
nit a
nd o
utdo
or u
nit.
3.
Use
twin
cor
e co
rd(0.
3mm
2)a
t rem
ote
cont
rol li
ne.
See
spec
she
et o
f rem
ote
cont
rol in
cas
e th
at th
e to
tal le
ngth
is m
ore
than
100
m.
4.
Do
not p
ut re
mot
e co
ntro
l line
alo
ngsid
e po
wer s
ourc
e lin
e.
5. S
ectio
n 1(※
1)sh
ows
elec
tric
circu
it of
mot
ion
sens
or(O
ptio
n).
FMi2
RD RD
1 2CN
IBL
FS
CNZ
CNC
For H
A WH RD
RD
t°
Contr
ol PC
B
RD YE
t°YE BK
t°BK
1 2 3 4 5 6
BK
t°BK
1 2
XR1
XR2
XR3
XR4
1 2 3 4 5 6
+12
SW2
SW6
SW5
SW7
LED・
2LE
D・3
X Y1 3
X Yt°
TB2
WH BK WH8 9 10 11 12
CNW2 WH
CNW1 WH
CNB
WHCN
NYE CN
HBK CN
TBL
(Ope
ration)
(Hea
ting)
(Com
presso
r ON)
(Ins
pecti
on)
Thc
Thi-R
1
Thi-R
2
Thi-R
3
Thi-A
WH WH WH WH
Remo
te co
ntrol
WH WH WH WHWH WH WH WH5 6 72 3 41
CNR
WH1 2
DMM
RD WH
+12
8 9 10 11 125 6 72 3 41
1
PISCN
GBL CN
V2 BK
24 3
1 3
Optio
n
WH BK RD
WH RD BK
Prep
are on
site
Powe
r PCB
Powe
r circ
uit
※1
Earth
The l
ine be
twee
n
21 3
Powe
r sou
rce lin
eSig
nal lin
e
indoo
r unit
and o
utdoo
r unit
M
14
56
7
F4 (2A)
CNM2 BK
RDBL or BK
BR or WH
WH or BL
OR or YE
BL31
WHCN
W3 WH
1 2WHRD
YE/G
N
3 5
CNW0 WH
1
3 TB1
F1(5A)
YE/G
N
1 2CN
TA BL(R
emote
opera
tion
inp
ut:vo
lt-free
conta
ct)
+12
Prep
are on
site
XR5(R
emote
opera
tion
input:
volt-f
ree co
ntact)FM
i2FS
Float
switc
h
Indica
tion l
amp(R
ed-In
spec
tion)
Indica
tion l
amp(G
reen-N
ormal
opera
tion)
LED・
3LE
D・2
Conn
ector
CNB-Z
Mode
l cap
acity
settin
gSW
6Op
eratio
n che
ck,dr
ain pu
mp m
otor te
st run
SW7-1
SW5
Temp
eratur
e sen
sor(R
emote
contr
ol)
Temp
eratur
e sen
sor(H
eat e
xcha
nger)
Temp
eratur
e sen
sor(R
eturn
air)
Thc
Thi-R
1,2,3
Thi-A
TB2
Term
inal b
lock(S
ignal
line)(□m
ark)
TB1
Term
inal b
lock(P
ower
sourc
e)(□m
ark)
Remo
te co
ntrol
comm
unica
tion a
ddres
sSW
2Plu
ral un
its M
aster/S
lave s
etting
F1,4
Fuse
Fan m
otor
Drain
pump
moto
rDM
Motio
n sen
sor
PIS
Close
d-end
conn
ector
■mark
BKBla
ckBlu
e
Color
Mark
s
BLMark
Color
BRBr
own
Oran
geOR
Red
RD WHYe
llow
White
Yello
w/Gr
een
YEYE/G
N
Item
Desc
riptio
nM
eanin
g of
mar
ks
Models FDUM60VH, 71VH
PJG000Z489
- 87 -
'19 • PAC-DB-308D
Note
s 1
.
in
dica
tes
wirin
g on
site
.
2. S
ee th
e wi
ring
diag
ram
of o
utdo
or u
nit a
bout
the
line
betw
een
indo
or u
nit a
nd o
utdo
or u
nit.
3.
Use
twin
cor
e co
rd(0.
3mm
2)a
t rem
ote
cont
rol li
ne.
See
spec
she
et o
f rem
ote
cont
rol in
cas
e th
at th
e to
tal le
ngth
is m
ore
than
100
m.
4.
Do
not p
ut re
mot
e co
ntro
l line
alo
ngsid
e po
wer s
ourc
e lin
e.
5. S
ectio
n 1(※
1)sh
ows
elec
tric
circu
it of
mot
ion
sens
or(O
ptio
n).
FMi1
FMi2
RD RD
1 2CN
IBL
FS
CNZ
CNC
For H
A WH RD
RD
t°
Contr
ol PC
B
RD YE
t°YE BK
t°BK
1 2 3 4 5 6
BK
t°BK
1 2
XR1
XR2
XR3
XR4
1 2 3 4 5 6
+12
SW2
SW6
SW5
SW7
LED・
2LE
D・3
X Y1 3
X Yt°
TB2
WH BK WH8 9 10 11 12
CNW2 WH
CNW1 WH
CNB
WHCN
NYE CN
HBK CN
TBL
(Ope
ration)
(Hea
ting)
(Com
presso
r ON)
(Ins
pecti
on)
Thc
Thi-R
1
Thi-R
2
Thi-R
3
Thi-A
WH WH WH WH
Remo
te co
ntrol
WH WH WH WHWH WH WH WH5 6 72 3 41
CNR
WH1 2
DMM
RD WH
+12
8 9 10 11 125 6 72 3 41
1
PISCN
GBL CN
V2 BK
24 3
1 3
Optio
n
WH BK RD
WH RD BK
Prep
are on
site
Powe
r PCB
Powe
r circ
uit
※1
Earth
The l
ine be
twee
n
21 3
Powe
r sou
rce lin
eSig
nal lin
e
indoo
r unit
and o
utdoo
r unit
M
14
56
7
F4 (2A)
CNM2 BK
RDBL or BK
BR or WH
WH or BL
OR or YE
BL31
WHCN
W3 WH
1 2WHRD
YE/G
N
3 5
CNW0 WH
1
3 TB1
F1(5A)
YE/G
N
M
14
56
7
RD
F3 (2A)
CNM1 WH
BL or BK
BR or WH
WH or BL
OR or YEL
CNWR WH
13
1 2CN
TA BL(R
emote
opera
tion
inp
ut:vo
lt-free
conta
ct)
+12
Prep
are on
site
XR5(R
emote
opera
tion
input:
volt-f
ree co
ntact)Th
i-R1,2
,3
FMi1,
2FS
Float
switc
h
Indica
tion l
amp(R
ed-In
spec
tion)
Indica
tion l
amp(G
reen-N
ormal
opera
tion)
LED・
3LE
D・2
Conn
ector
CNB-Z
Mode
l cap
acity
settin
gSW
6Op
eratio
n che
ck,dr
ain pu
mp m
otor te
st run
SW7-1
SW5
Temp
eratur
e sen
sor(R
emote
contr
ol)
Temp
eratur
e sen
sor(H
eat e
xcha
nger)
Temp
eratur
e sen
sor(R
eturn
air)
Thc
Thi-A
TB2
Term
inal b
lock(S
ignal
line)(□m
ark)
TB1
Term
inal b
lock(P
ower
sourc
e)(□m
ark)
Remo
te co
ntrol
comm
unica
tion a
ddres
sSW
2Plu
ral un
its M
aster/S
lave s
etting
LRe
actor
F1,3,
4Fu
seFa
n moto
r
Drain
pump
moto
rDM
Motio
n sen
sor
PIS
Close
d-end
conn
ector
■mark
BKBla
ckBlu
e
Color
Mark
s
BLMark
Color
BRBr
own
Oran
geOR
Red
RD WHYe
llow
White
Yello
w/Gr
een
YEYE/G
N
Item
Desc
riptio
nM
eanin
g of
mar
ks
Models FDUM100VH, 125VH, 140VH
PJG000Z490
- 88 -
'19 • PAC-DB-308D
(e) Ceiling suspended type (FDE)
Models FDE50VH, 60VH, 71VH, 100VH, 125VH, 140VH
PFA004Z087
- 89 -
Powe
r PCB
1 2 3 4 5CN
W1 WH
F1(3.1
5A)
3 5CNW0 WH
1
Powe
r circ
uit6 7 8 9 10 11 12
WHRD1 2 TB
1Ea
rth
M
14
56
7
F3(2
.0A) R D
B KW H
Y EB L
FMi
CNM1 WH
YE/G
N
3
BLWH1 3
CNW3 WHF2(
3.15A)
Mark BK BL BR OR
Color
Black
Blue
Brow
nOr
ange
RD WHRe
dWh
iteYe
llow
Yello
w/Gr
een
Pink
The l
ine be
twee
n
21 3
Powe
r sou
rce lin
eSig
nal lin
e
indoo
r unit
and o
utdoo
r unit
YE/G
N
PK YEYE/G
N
14
56
7
R DB K
W HY E
B LCN
F1WH
RD
WHRD
1 2CN
IBL
RD
t°
Contr
ol PC
B
t°YE YE BK
t°6
BK
1 2 3 4 5
BK
t°BK
1 2
XR1
XR2
XR3
XR4
XR5(R
emote
opera
tion
Prep
are on
site
1 2 3 4 5 6
+12
X Y1 3
X Yt°
TB2
WH BK
CNW2 WHCNB
WHCN
NYE CN
HBK CN
TBL
(Ope
ration)
(Hea
ting)
(Com
presso
r ON)
(Ins
pecti
on)
Thc
Thi-R
1
Thi-R
2
Thi-R
3
Thi-A
Remo
te co
ntrol
input:
volt-f
ree co
ntact)
1 2CN
TA BL(R
emote
opera
tion
inp
ut:vo
lt-free
conta
ct)
8 9 10 11 125 6 72 3 41WH WH WH WH WH WH WH WH WH WH WH WH
M
1 2 3 4 5
1 2 3 4 5
LM
6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
CNJ
WH
BL PK BR OR RD
+12
1
PISCN
GBL CN
V2 BK
24 3
1 3
Optio
n
WH BK RD
WH RD BK
WH RD BK
WH RD BK
CNL1
WHCN
L2 WH
Prep
are on
site
CNZ
CNC
For H
A WH RD
SW2
SW6
SW5
SW7
LED・
2LE
D・3
SW8
※1
5.
Sec
tion
1(※
1)sh
ows
elec
tric
circu
it of
mot
ion
sens
or(O
ptio
n).
Note
s 1
.
in
dica
tes
wirin
g on
site
.
2. S
ee th
e wi
ring
diag
ram
of o
utdo
or u
nit a
bout
the
line
betw
een
indo
or u
nit a
nd o
utdo
or u
nit.
3.
Use
twin
cor
e co
rd(0.
3mm
2)a
t rem
ote
cont
rol li
ne.
See
spec
she
et o
f rem
ote
cont
rol in
cas
e th
at th
e to
tal le
ngth
is m
ore
than
100
m.
4.
Do
not p
ut re
mot
e co
ntro
l line
alo
ngsid
e po
wer s
ourc
e lin
e.
Opera
tion c
heck
,drain
pump
moto
r test
run
Color
mark
s
Indica
tion l
amp(R
ed-In
spec
tion)
Indica
tion l
amp(G
reen-N
ormal
opera
tion)
LED・
3LE
D・2
Conn
ector
CNB-Z
Mode
l cap
acity
settin
gSW
6SW
7-1
SW5
L
Tempe
rature
senso
r(Rem
ote co
ntrol)
Tempe
rature
senso
r(Hea
t exc
hang
er)
Thc
Tempe
rature
senso
r(Retu
rn air)
Thi-R
1,2,3
Thi-A
TB2
Term
inal b
lock(S
ignal
line)(□m
ark)
TB1
Term
inal b
lock(P
ower
sourc
e)(□m
ark)
LM
Remo
te co
ntrol
comm
unica
tion a
ddres
sSW
2Plu
ral un
its M
aster/S
lave s
etting
Reac
tor
F1-3
Fuse
FMi
Louv
er mo
tor
Fan m
otor
Motio
n sen
sor
PIS
Item
Desc
riptio
n
Anti-f
reeze
contr
olSW
8-1
Mean
ing of
mark
s
'19 • PAC-DB-308D
(f) Wall mounted type (SRK)
Models SRK50ZSX-W, 60ZSX-W
RWA000Z413
- 90 -
F3.1
5AFU
SE
G2
L250
V
S/N
VARI
STOR
CNU
CNS
INTE
RFAC
E KI
T
CNG
CNE
DISPL
AYWI
RELE
SS RE
CEIVE
R
JCNF
U
M1 3 4 5 6
BACK
-UP S
W
52
L
BOAR
DCI
RCUI
TPR
INTE
DCN
LM M M M
5 5
RED
WHI
TE
RED
WHI
TEBL
ACK
BLUE
YELL
OW
YELL
OW/
GREE
N
BLAC
K
t t t
POW
ER C
ABLE
SIGN
AL W
IRE
M
5 5 5
M5
M5
LEFT
MOT
ORLO
UVER
RIGH
TM
OTOR
LOUV
ER
RIGH
TLO
WER
MOT
ORFL
AP
UPPE
RM
OTOR
FLAP
LEFT
MOT
ORIN
LET
RIGH
TM
OTOR
INLE
T
SWLIM
ITPA
NEL
INLE
T MOT
ORFA
N
STAC
KDI
ODE
13
EXCH
ANGE
RHE
AT
EXCH
ANGE
RHE
AT
Powe
r sou
rce
1 Ph
ase
220-
240V
50H
z22
0V 6
0Hz
TO O
UTDO
OR U
NIT
CNJ
3
SENS
ORRO
OM T
EMP.
SENS
OR 1
HEAT
EXC
HANG
ER
SENS
OR 2
HEAT
EXC
HANG
ER
SENS
ORHU
MID
ITY
SENS
ORM
OTIO
N
31
[
]
CNZ
CNX
CNY
CNM
CNP
Desc
riptio
nIte
mCo
nnec
tor
CNE
CNF
CNG
CNJ
CNL
CNM
CNP
CNS
CNU
CNX
CNY
CNZ
LEFT
LOW
ERM
OTOR
FLAP
7
YELL
OW/
GREE
N
BLOC
KTE
RMIN
AL
EART
H W
IRE
T2
N2
N
4
'19 • PAC-DB-308D
Models SRK71ZR-W, 100ZR-W
RWA000Z417A
- 91 -
tototo
TO O
UTDO
OR
UNIT
POW
ER C
ABLE
SIG
NAL
WIR
E
EART
H W
IRE
12/
N
3
POW
ER S
OUR
CE1
Phas
e 22
0-24
0V 5
0Hz
22
0V 6
0Hz
F 3.
15A
F
G S/N
Va
FMi
CNU
CNS
INTE
RFAC
E KIT
J
U
MHE
AT
1 3 4 5 6
5
TB 1 2/N 3
EXCH
ANGE
RL
HEAT
EXCH
ANGE
R
BOAR
DCI
RCUI
TPR
INTE
D
SM1
LM1
CNX
M M M
5 5LM
2
RDWH
RD WH
BK BLY
Y/G BK
CNG
CNE
DISP
LAY
WIRE
LESS
RECE
IVER
CNF
BACK
-UP
SW
28
Th21
Th22
Th1
Th3
CNY
Y/G
CNM
5
Colo
r Mar
ks
Blue
Blac
kBK
Red
BL RDW
hite
WH
Yello
w/G
reen
Y/G
Yello
wY
Colo
rM
ark
Heat
exch
ange
r temp
eratur
e sen
sor
Hum
idity
sen
sor
Fan
mot
or
Room
tem
pera
ture
sen
sor
Flap
mot
or
Th1
Th21
,2
Th3
Diod
e st
ack
DSFu
seF
Conn
ecto
rCN
E
FMi
Term
inal
blo
ckTB
Louv
er m
otor
LM1,
2
SM1
Desc
riptio
nIte
m
Varis
tor
VaCNF
CNG
CNM
CNS
CNU
CNX
CNY
L 250
V
DS
'19 • PAC-DB-308D
(2) Outdoor units
Models FDC100VNA-W, 125VNA-W, 140VNA-W
PCA001Z854
SW3-
3,4
SW3-
2
SW3-
1
Loca
l set
ting
switc
h SW
3,5,
7(Se
t up
at s
hipm
ent O
FF)
100
Mode
l
Powe
r cab
le, i
ndoo
r-out
door
con
nect
ing
wire
s
125
2422
φ1.
6mm
x 3
φ1.
6
100
Mode
l
※At
the
conn
ectio
n wi
th th
e du
ct ty
pe in
door
uni
t.
125
2620
φ1.
6mm
x 3
φ1.
6
The
spec
ificat
ions
sho
wn in
the
abov
e ta
ble
are
for u
nits
with
out h
eate
rs. F
or u
nits
with
hea
ters
, ref
erto
the
inst
alla
tion
inst
ruct
ions
or t
he c
onst
ruct
ion
inst
ruct
ions
of t
he in
door
uni
t.Sw
itchg
ear o
f circ
uit b
reak
er c
apac
ity w
hich
is c
alcu
late
d fro
m M
AX. o
ver c
urre
nt s
houl
d be
cho
sen
alon
g th
e re
gula
tions
in e
ach
coun
try.
The
cabl
e sp
ecific
atio
ns a
re b
ased
on
the
assu
mpt
ion
that
a m
etal
or p
last
ic co
ndui
t is
used
with
no
mor
e th
an th
ree
cabl
es c
onta
ined
in a
con
duit
and
a vo
ltage
dro
p is
2%. F
or a
n in
stal
latio
n fa
lling
outs
ide
of th
ese
cond
itions
, ple
ase
follo
w th
e in
tern
al c
ablin
g re
gula
tions
. Ada
pt it
to th
e re
gula
tion
in e
ffect
in e
ach
coun
try.
140
140
27
5.5
5.5
SW5-
2
SW7-
2
SW7-
3
Snow
gua
rd fa
n co
ntro
l
Defro
st co
ntro
l cha
nge
Trial
ope
ratio
n
wher
e ou
tside
tem
pera
ture
bec
omes
belo
w
21 3 op
erat
ion is
finish
ed.
4 SW
3-3
is ON
.
Met
hod
of tr
ial o
pera
tion
Be su
re to
turn
OFF
SW
3-3
afte
r the
trial
op
erat
ion w
hen
SW3-
4 is
ON
Cooli
ng tr
ial o
pera
tion
will b
e pe
rform
ed
Com
pres
sor w
ill be
in th
e op
erat
ion w
hen
Trial
ope
ratio
n ca
n be
per
form
ed b
y usin
g
runn
ing w
hen
the
unit i
s use
d in
a ve
ry
3°C
or lo
wer a
nd th
e co
mpr
esso
r is n
ot
minu
tes,
when
out
door
tem
pera
ture
falls
toun
it fan
will
run
for 3
0 se
cond
s in
ever
y 10
Whe
n th
is sw
itch
is tu
rned
ON,
the
outd
oor
This
switc
h sh
ould
be tu
rned
ON
in th
e ar
ea
shor
ter b
y tur
ning
ON th
is sw
itch.
Th
e de
frost
oper
ation
inte
rval
beco
mes
MAX
ove
r cur
rent
Powe
r cab
le s
ize(
mm
)2(
A)Po
wer c
able
lengt
h(
m)
indoo
r-out
door
wire
size
x nu
mbe
r Ea
rth w
ire s
ize(
mm)
MAX
ove
r cur
rent
Powe
r cab
le s
ize(
mm
)2(
A)Po
wer c
able
lengt
h(
m)
indoo
r-out
door
wire
size
x nu
mbe
r Ea
rth w
ire s
ize(
mm)
the
freez
ing p
oint.
snow
y cou
ntry,
set t
his sw
itch
to O
N.
SW3-
3,4.
wh
en S
W3-
4 is
OFF,
and
heat
ing tr
ial
High
heig
ht d
iffere
nce
unit b
y 30m
or m
ore.
insta
lled
at a
pos
ition
highe
r tha
n ind
oor
Set t
his sw
itch
to O
N wh
en o
utdo
or u
nit is
op
erat
ion co
ntro
l
exte
rnal
equip
men
t.op
erat
ion b
y rem
ote
cont
rol c
onne
cted
Set t
his sw
itch
to O
N wh
en m
anag
ing u
nit
Defro
st co
ntro
l cha
nge
spee
d be
com
es lo
wer i
n sil
ent m
ode.
Uppe
r lim
it of c
ompr
esso
r spe
ed a
nd fa
n Lo
wer n
oise
silen
t mod
e
Pow
erso
urce
1P
hase
220-
240V
50Hz
/ 22
0V
60Hz
Cran
kcas
e hea
ter
Mea
ning
of m
arks
Col
or m
arks
CHIte
mDe
scrip
tion
Comp
ress
or m
otor
CMCo
nnec
torCN
Curre
nt se
nsor
CT
1Dr
ain pa
n hea
terDH
Expa
nsion
valve
for c
oolin
gEE
VCEx
pans
ion va
lve fo
r hea
ting
EEVH
Intell
igent
powe
r mod
ule
FFa
n moto
rFM
1IP
MInd
icatio
n lam
p(GR
EEN)
LED1
Indica
tion l
amp(
RED)
LED2
Reac
torL1
,2
Switc
hSW
1SW
3,5,7
Loca
l sett
ing sw
itch
Term
inal b
lock
TBTe
mper
ature
sens
or(Ou
tdoor
air)
THo-
ATe
mper
ature
seso
r(Disc
harg
e pipe)
THo-
D
Temp
eratu
re se
nsor(
Sucti
on pi
pe)
THo-
R1,R
2
Solen
oid va
lve fo
r 4-w
ay va
lveAu
xillia
ry re
lay
THo-
S
Auxil
liary
relay
20S
Auxil
liary
relay(
for 20
S)
52X1
Auxil
liary
relay(
for C
H)
52X3
High
pres
sure
switc
h63
H1
Y/GN
Yello
w/Gr
een
YYe
llow
WH
Whit
eRD
Red
OROr
ange
GNGr
een
BRBr
own
BLBl
ueBK
Blac
kMa
rkCo
lor
52X1
152
X14
52X1
5Au
xillia
ry re
lay(for
DH)
Temp
eratu
re se
nsor(
Heat
exch
ange
r)
Fuse
IPM
T12
T22L2
CNP
(WH)
CNEE
V1(W
H)CN
EEV2
(RD)
CNFA
N1(W
H)
CNF
(BK)
CNR
( WH)
CNS
(RD)
CNH
(BR)
CNTH
(WH)
CNB
(RD)
LED1
LED2
SW5
SW1
52X3
52X1
5
52X1RD
RD
BLOR
WH
RD
BLOR
WH
WHORBRBLRD
64
32
16
43
21
76
54
1
BR
BR
BR
BR
BK
BK
BKBK
BKBK
RDRD
YY
BKBK
CH20
S
63H1
Tho-
R1Th
o-D
Tho-
STh
o-A
Tho-
R2
PCB1
RD WH
L NNO
ISE
FILT
ERPC
B2
23
41
MM
MEE
VCEE
VHFM
1
TB
t°t°
t°t°
t°
TB9
TB8
TB7
U VW
BLWH
RD
CNW
2(O
R)
WH
BL
WH
WH
DH
Optio
n
Y
Y
52X1
1
52X1
4
SW3
SW7
23
41
23
1
(2A)
CM
WH
WH
RD
WH
TB5
TB6
RD
TB4
TB3
1 2 3
TO I
NDOO
R UN
ITPO
WER
CAB
LE 1
2SI
GNAL
WIR
E 3
TB7
TB8
Y/GN
TB
WH
RD
GN
MCCB
ELCB
GN
CN1
(WH)
CT1
TB1
TB2
T1Y/
GN
L1PW
B7
Y/GN
E
CN1
MS
3~
F (2A)
F (3.15
A)
F
(8A)
F(3
0A)
F
CNPS
L(
WH)
BK
RD
PSLWH
Low
pres
sure
sens
orPS
L
- 92 -
'19 • PAC-DB-308D
Models FDC100VSA-W, 125VSA-W, 140VSA-W
PCA001Z855
Powe
r sou
rce 3P
hase
380ー4
15V 5
0Hz
100
Mode
l
Powe
r cab
le, i
ndoo
r-out
door
con
nect
ing
wire
s
125
153.
546
φ1.
6mm
x 3
φ1.
6
100
Mode
l
※At
the
conn
ectio
n wi
th th
e du
ct ty
pe in
door
uni
t.
125
1740
φ1.
6mm
x 3
The
spec
ificat
ions
sho
wn in
the
abov
e ta
ble
are
for u
nits
with
out h
eate
rs. F
or u
nits
with
hea
ters
, ref
erto
the
inst
alla
tion
inst
ruct
ions
or t
he c
onst
ruct
ion
inst
ruct
ions
of t
he in
door
uni
t.Sw
itchg
ear o
f circ
uit b
reak
er c
apac
ity w
hich
is c
alcu
late
d fro
m M
AX. o
ver c
urre
nt s
houl
d be
cho
sen
alon
g th
e re
gula
tions
in e
ach
coun
try.
The
cabl
e sp
ecific
atio
ns a
re b
ased
on
the
assu
mpt
ion
that
a m
etal
or p
last
ic co
ndui
t is
used
with
no
mor
e th
an th
ree
cabl
es c
onta
ined
in a
con
duit
and
a vo
ltage
dro
p is
2%. F
or a
n in
stal
latio
n fa
lling
outs
ide
of th
ese
cond
itions
, ple
ase
follo
w th
e in
tern
al c
ablin
g re
gula
tions
. Ada
pt it
to th
e re
gula
tion
in e
ffect
in e
ach
coun
try.
140
140
1838
3.5
φ1.
6
SW3-
3,4
SW3-
2
SW3-
1
Loca
l set
ting
switc
h SW
3,5,
7(Se
t up
at s
hipm
ent O
FF)
SW5-
2
SW7-
2
SW7-
3
Mea
ning
of m
arks
Col
or m
arks
MAX
ove
r cur
rent
Powe
r cab
le s
ize(
mm
)2(
A)Po
wer c
able
lengt
h(
m)
indoo
r-out
door
wire
size
x nu
mbe
r Ea
rth w
ire s
ize(
mm)
MAX
ove
r cur
rent
Powe
r cab
le s
ize(
mm
)2(
A)Po
wer c
able
lengt
h(
m)
indoo
r-out
door
wire
size
x nu
mbe
r Ea
rth w
ire s
ize(
mm)
Snow
gua
rd fa
n co
ntro
l
Defro
st co
ntro
l cha
nge
Trial
ope
ratio
n
wher
e ou
tside
tem
pera
ture
bec
omes
belo
w
21 3 op
erat
ion is
finish
ed.
4 SW
3-3
is ON
.
Met
hod
of tr
ial o
pera
tion
Be su
re to
turn
OFF
SW
3-3
afte
r the
trial
op
erat
ion w
hen
SW3-
4 is
ON
Cooli
ng tr
ial o
pera
tion
will b
e pe
rform
ed
Com
pres
sor w
ill be
in th
e op
erat
ion w
hen
Trial
ope
ratio
n ca
n be
per
form
ed b
y usin
g
runn
ing w
hen
the
unit i
s use
d in
a ve
ry
3°C
or lo
wer a
nd th
e co
mpr
esso
r is n
ot
minu
tes,
when
out
door
tem
pera
ture
falls
toun
it fan
will
run
for 3
0 se
cond
s in
ever
y 10
Whe
n th
is sw
itch
is tu
rned
ON,
the
outd
oor
This
switc
h sh
ould
be tu
rned
ON
in th
e ar
ea
shor
ter b
y tur
ning
ON th
is sw
itch.
Th
e de
frost
oper
ation
inte
rval
beco
mes
the
freez
ing p
oint.
snow
y cou
ntry,
set t
his sw
itch
to O
N.
SW3-
3,4.
wh
en S
W3-
4 is
OFF,
and
heat
ing tr
ial
High
heig
ht d
iffere
nce
unit b
y 30m
or m
ore.
insta
lled
at a
pos
ition
highe
r tha
n ind
oor
Set t
his sw
itch
to O
N wh
en o
utdo
or u
nit is
op
erat
ion co
ntro
l
exte
rnal
equip
men
t.op
erat
ion b
y rem
ote
cont
rol c
onne
cted
Set t
his sw
itch
to O
N wh
en m
anag
ing u
nit
Defro
st co
ntro
l cha
nge
spee
d be
com
es lo
wer i
n sil
ent m
ode.
Uppe
r lim
it of c
ompr
esso
r spe
ed a
nd fa
n Lo
wer n
oise
silen
t mod
e
IPM
T11
T12
L
CNW
3(
WH)
CNEE
V1(
WH)
CNEE
V2(
RD)
CNFA
N1(
WH)
LED1
LED2
SW5
SW1
52X2
52X1
5
52X1
BK
WH
RD
BLOR
WH
RD
BLOR
WH
WHORBRBLRD
64
32
16
43
21
76
54
1
PCB1
RD WH
TB7
L1 N
NOIS
E FI
LTER
PCB2
23
41
MM
M
EEVC
EEVH
FM1
TB
TB9
TB8
TB7
U VW
BLWH
RD
CNW
2(
OR)
CNW
1(
Y)
BK
RD
Y
Y
52X1
1
52X1
452
X6
SW3
SW7
23
41
23
1CM
Y
WH
TB3
TB2
TB1
RD
WH
BLTB
8BK
TB9
TB6
RD
TB2
TB3
TB4
TB1
1 2 3
TO I
NDOO
R UN
ITPO
WER
CAB
LE 1
2SI
GNAL
WIR
E 3
T12
TB5
L2 L3BL BK Y/
GN
BL
TBRD
BK
BK
Y/GN
GN
MCCB
ELCB
MS
3~
(10
A)F
(2A)
F (2A)
F (2A)
F
CNF
(BK)
CNR
(W
H)CN
S(
RD)
CNH
(BR)
CNTH
(W
H)CN
B(
RD)
BR
BR
BR
BR
BK
BK
BKBK
BKBK
RDRD
YY
BKBK
CH20
S
63H1
Tho-
R1Th
o-D
Tho-
STh
o-A
Tho-
R2
t°t°
t°t°
t°
WH
WH
DH
Optio
n
Cran
kcas
e hea
terCH
Item
Desc
riptio
n
Comp
ress
or m
otor
CMCo
nnec
torCN
Drain
pan h
eater
DHEx
pans
ion va
lve fo
r coo
ling
EEVC
Expa
nsion
valve
for h
eatin
gEE
VH
Intell
igent
powe
r mod
ule
FFa
n moto
rFM
1IP
M
Indica
tion l
amp(
GREE
N)LE
D1Ind
icatio
n lam
p(RE
D)LE
D2
Switc
h SW
1 SW
3,5,7
Loca
l sett
ing sw
itch
Term
inal b
lock
TBTe
mper
ature
sens
or(Ou
tdoor
air)
THo-
ATe
mper
ature
sens
or(Di
scha
rge p
ipe)
THo-
D
Temp
eratu
re se
nsor(
Sucti
on pi
pe)
THo-
R1,R
2
Solen
oid va
lve fo
r 4-w
ay va
lveAu
xillia
ry re
lay
THo-
S
Auxil
liary
relay
20S
Auxil
liary
relay(
for 20
S)
52X1
Auxil
liary
relay(
for C
H)
52X2
High
pres
sure
switc
h63
H1
52X1
152
X14
52X1
5Au
xillia
ry re
lay(for
DH)
Temp
eratu
re se
nsor(
Heat
exch
ange
r)
Fuse
Reac
torL
Auxil
iary r
elay (
for F
M1)
52X6
Y/GN
Yello
w/Gr
een
YYe
llow
WH
Whit
eRD
Red
OROr
ange
GNGr
een
BRBr
own
BLBl
ueBK
Blac
kMa
rkCo
lor
CNPS
L(
WH)
BK
RD
PSLWH
Low
pres
sure
sens
orPS
L
- 93 -
'19 • PAC-DB-308D1.4 TECHNICAL INFORMATION
(1) Ceiling cassette-4 way type (FDT)
FDT100VNAWVH
- 94 -
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season theIndoor unit model name FDT100VH information relates to. Indicated values should relate to oneOutdoor unit model name FDC100VNA-W heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory) Yescooling Yes Warmer(if designated) Noheating Yes Colder(if designated) No
Item symbol value unit Item symbol value classDesign load Seasonal efficiency and energy efficiency classcooling Pdesignc 10.0 kW cooling SEER 7.13 A++heating / Average Pdesignh 8.50 kW heating / Average SCOP/A 4.60 A++heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - -heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unitDeclared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignhheating / Average (-10℃) Pdh 8.50 kW heating / Average (-10℃) elbu 0 kWheating / Warmer (2℃) Pdh - kW heating / Warmer (2℃) elbu - kWheating / Colder (-22℃) Pdh - kW heating / Colder (-22℃) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19)℃ and Declared energy efficiency ratio, at indoor temperature 27(19)℃ andoutdoor temperature Tj outdoor temperature TjTj=35℃ Pdc 10.00 kW Tj=35℃ EERd 3.66 -Tj=30℃ Pdc 7.37 kW Tj=30℃ EERd 5.71 -Tj=25℃ Pdc 4.74 kW Tj=25℃ EERd 9.24 -Tj=20℃ Pdc 3.10 kW Tj=20℃ EERd 11.64 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh 7.40 kW Tj=-7℃ COPd 3.26 -Tj=2℃ Pdh 4.50 kW Tj=2℃ COPd 4.43 -Tj=7℃ Pdh 2.90 kW Tj=7℃ COPd 5.78 -Tj=12℃ Pdh 2.90 kW Tj=12℃ COPd 7.19 -Tj=bivalent temperature Pdh 8.50 kW Tj=bivalent temperature COPd 2.96 -Tj=operating limit Pdh 6.30 kW Tj=operating limit COPd 2.25 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh - kW Tj=-7℃ COPd - -Tj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -Tj=-15℃ Pdh - kW Tj=-15℃ COPd - -
Bivalent temperature Operating limit temperatureheating / Average Tbiv -10 ℃ heating / Average Tol -20 ℃heating / Warmer Tbiv - ℃ heating / Warmer Tol - ℃heating / Colder Tbiv - ℃ heating / Colder Tol - ℃
Cycling interval capacity Cycling interval efficiencyfor cooling Pcycc - kW for cooling EERcyc - -for heating Pcych - kW for heating COPcyc - -
Degradation coefficient Degradation coefficientcooling Cdc 0.25 - heating Cdh 0.25 -
Electric power input in power modes other than 'active mode' Annual electricity consumptionoff mode Poff 7 W cooling Qce 491 kWh/astandby mode Psb 7 W heating / Average Qhe 2590 kWh/athermostat-off mode Pto(cooling) 22 W heating / Warmer Qhe - kWh/a
Pto(heating) 34 W heating / colder Qhe - kWh/acrankcase heater mode Pck 5 W
Capacity control(indicate one of three options) Other itemsSound power level(indoor) Lwa 62 dB(A)Sound power level(outdoor) Lwa 69 dB(A)
fixed No Global warming potential GWP 675 kgCO2eq.staged No Rated air flow(indoor) - 2220 m3/hvariable Yes Rated air flow(outdoor) - 4500 m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative.more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd.
5 The Square, Stockley Park, Uxbridge, Middlesex,UB11 1ET, United kingdom
PJF000Z589 B
'19 • PAC-DB-308D
FDT100VSAWVH
- 95 -
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season theIndoor unit model name FDT100VH information relates to. Indicated values should relate to oneOutdoor unit model name FDC100VSA-W heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory) Yescooling Yes Warmer(if designated) Noheating Yes Colder(if designated) No
Item symbol value unit Item symbol value classDesign load Seasonal efficiency and energy efficiency classcooling Pdesignc 10.0 kW cooling SEER 7.13 A++heating / Average Pdesignh 8.50 kW heating / Average SCOP/A 4.60 A++heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - -heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unitDeclared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignhheating / Average (-10℃) Pdh 8.50 kW heating / Average (-10℃) elbu 0 kWheating / Warmer (2℃) Pdh - kW heating / Warmer (2℃) elbu - kWheating / Colder (-22℃) Pdh - kW heating / Colder (-22℃) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19)℃ and Declared energy efficiency ratio, at indoor temperature 27(19)℃ andoutdoor temperature Tj outdoor temperature TjTj=35℃ Pdc 10.00 kW Tj=35℃ EERd 3.66 -Tj=30℃ Pdc 7.37 kW Tj=30℃ EERd 5.71 -Tj=25℃ Pdc 4.74 kW Tj=25℃ EERd 9.24 -Tj=20℃ Pdc 3.10 kW Tj=20℃ EERd 11.64 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh 7.40 kW Tj=-7℃ COPd 3.26 -Tj=2℃ Pdh 4.50 kW Tj=2℃ COPd 4.43 -Tj=7℃ Pdh 2.90 kW Tj=7℃ COPd 5.78 -Tj=12℃ Pdh 2.90 kW Tj=12℃ COPd 7.19 -Tj=bivalent temperature Pdh 8.50 kW Tj=bivalent temperature COPd 2.96 -Tj=operating limit Pdh 6.30 kW Tj=operating limit COPd 2.25 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh - kW Tj=-7℃ COPd - -Tj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -Tj=-15℃ Pdh - kW Tj=-15℃ COPd - -
Bivalent temperature Operating limit temperatureheating / Average Tbiv -10 ℃ heating / Average Tol -20 ℃heating / Warmer Tbiv - ℃ heating / Warmer Tol - ℃heating / Colder Tbiv - ℃ heating / Colder Tol - ℃
Cycling interval capacity Cycling interval efficiencyfor cooling Pcycc - kW for cooling EERcyc - -for heating Pcych - kW for heating COPcyc - -
Degradation coefficient Degradation coefficientcooling Cdc 0.25 - heating Cdh 0.25 -
Electric power input in power modes other than 'active mode' Annual electricity consumptionoff mode Poff 7 W cooling Qce 491 kWh/astandby mode Psb 7 W heating / Average Qhe 2590 kWh/athermostat-off mode Pto(cooling) 22 W heating / Warmer Qhe - kWh/a
Pto(heating) 34 W heating / colder Qhe - kWh/acrankcase heater mode Pck 5 W
Capacity control(indicate one of three options) Other itemsSound power level(indoor) Lwa 62 dB(A)Sound power level(outdoor) Lwa 69 dB(A)
fixed No Global warming potential GWP 675staged No Rated air flow(indoor) - 2220variable Yes Rated air flow(outdoor) - 4500
Contact details for obtaining Name and address of the manufacturer or of its authorised representative.more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd.
5 The Square, Stockley Park, Uxbridge, Middlesex,UB11 1ET, United kingdom
kgCO2eq.m3/hm3/h
PJF000Z589 B
'19 • PAC-DB-308D
FDT100VNAWPVH
- 96 -
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season theIndoor unit model name FDT50VH (x2 units) information relates to. Indicated values should relate to oneOutdoor unit model name FDC100VNA-W heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory) Yescooling Yes Warmer(if designated) Noheating Yes Colder(if designated) No
Item symbol value unit Item symbol value classDesign load Seasonal efficiency and energy efficiency classcooling Pdesignc 10.0 kW cooling SEER 7.41 A++heating / Average Pdesignh 8.50 kW heating / Average SCOP/A 4.47 A+heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - -heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unitDeclared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignhheating / Average (-10℃) Pdh 8.50 kW heating / Average (-10℃) elbu 0 kWheating / Warmer (2℃) Pdh - kW heating / Warmer (2℃) elbu - kWheating / Colder (-22℃) Pdh - kW heating / Colder (-22℃) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19)℃ and Declared energy efficiency ratio, at indoor temperature 27(19)℃ andoutdoor temperature Tj outdoor temperature TjTj=35℃ Pdc 10.00 kW Tj=35℃ EERd 3.55 -Tj=30℃ Pdc 7.37 kW Tj=30℃ EERd 5.60 -Tj=25℃ Pdc 4.74 kW Tj=25℃ EERd 9.60 -Tj=20℃ Pdc 3.49 kW Tj=20℃ EERd 15.30 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh 7.40 kW Tj=-7℃ COPd 3.05 -Tj=2℃ Pdh 4.50 kW Tj=2℃ COPd 4.15 -Tj=7℃ Pdh 2.90 kW Tj=7℃ COPd 6.10 -Tj=12℃ Pdh 2.82 kW Tj=12℃ COPd 7.60 -Tj=bivalent temperature Pdh 8.50 kW Tj=bivalent temperature COPd 2.70 -Tj=operating limit Pdh 6.30 kW Tj=operating limit COPd 2.25 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh - kW Tj=-7℃ COPd - -Tj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -Tj=-15℃ Pdh - kW Tj=-15℃ COPd - -
Bivalent temperature Operating limit temperatureheating / Average Tbiv -10 ℃ heating / Average Tol -20 ℃heating / Warmer Tbiv - ℃ heating / Warmer Tol - ℃heating / Colder Tbiv - ℃ heating / Colder Tol - ℃
Cycling interval capacity Cycling interval efficiencyfor cooling Pcycc - kW for cooling EERcyc - -for heating Pcych - kW for heating COPcyc - -
Degradation coefficient Degradation coefficientcooling Cdc 0.25 - heating Cdh 0.25 -
Electric power input in power modes other than 'active mode' Annual electricity consumptionoff mode Poff 10 W cooling Qce 473 kWh/astandby mode Psb 10 W heating / Average Qhe 2665 kWh/athermostat-off mode Pto(cooling) 15 W heating / Warmer Qhe - kWh/a
Pto(heating) 30 W heating / colder Qhe - kWh/acrankcase heater mode Pck 5 W
Capacity control(indicate one of three options) Other itemsSound power level(indoor) Lwa 62 dB(A)Sound power level(outdoor) Lwa 69 dB(A)
fixed No Global warming potential GWP 675staged No Rated air flow(indoor) - 1200variable Yes Rated air flow(outdoor) - 4500
Contact details for obtaining Name and address of the manufacturer or of its authorised representative.more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd.
5 The Square, Stockley Park, Uxbridge, Middlesex,UB11 1ET, United kingdom
kgCO2eq.m3/hm3/h
PJF000Z589 B
'19 • PAC-DB-308D
FDT100VSAWPVH
- 97 -
kgCO2eq.m3/hm3/h
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season theIndoor unit model name FDT50VH (x2 units) information relates to. Indicated values should relate to oneOutdoor unit model name FDC100VSA-W heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory) Yescooling Yes Warmer(if designated) Noheating Yes Colder(if designated) No
Item symbol value unit Item symbol value classDesign load Seasonal efficiency and energy efficiency classcooling Pdesignc 10.0 kW cooling SEER 7.41 A++heating / Average Pdesignh 8.50 kW heating / Average SCOP/A 4.47 A+heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - -heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unitDeclared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignhheating / Average (-10℃) Pdh 8.50 kW heating / Average (-10℃) elbu 0 kWheating / Warmer (2℃) Pdh - kW heating / Warmer (2℃) elbu - kWheating / Colder (-22℃) Pdh - kW heating / Colder (-22℃) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19)℃ and Declared energy efficiency ratio, at indoor temperature 27(19)℃ andoutdoor temperature Tj outdoor temperature TjTj=35℃ Pdc 10.00 kW Tj=35℃ EERd 3.55 -Tj=30℃ Pdc 7.37 kW Tj=30℃ EERd 5.60 -Tj=25℃ Pdc 4.74 kW Tj=25℃ EERd 9.60 -Tj=20℃ Pdc 3.49 kW Tj=20℃ EERd 15.30 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh 7.40 kW Tj=-7℃ COPd 3.05 -Tj=2℃ Pdh 4.50 kW Tj=2℃ COPd 4.15 -Tj=7℃ Pdh 2.90 kW Tj=7℃ COPd 6.10 -Tj=12℃ Pdh 2.82 kW Tj=12℃ COPd 7.60 -Tj=bivalent temperature Pdh 8.50 kW Tj=bivalent temperature COPd 2.70 -Tj=operating limit Pdh 6.30 kW Tj=operating limit COPd 2.25 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh - kW Tj=-7℃ COPd - -Tj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -Tj=-15℃ Pdh - kW Tj=-15℃ COPd - -
Bivalent temperature Operating limit temperatureheating / Average Tbiv -10 ℃ heating / Average Tol -20 ℃heating / Warmer Tbiv - ℃ heating / Warmer Tol - ℃heating / Colder Tbiv - ℃ heating / Colder Tol - ℃
Cycling interval capacity Cycling interval efficiencyfor cooling Pcycc - kW for cooling EERcyc - -for heating Pcych - kW for heating COPcyc - -
Degradation coefficient Degradation coefficientcooling Cdc 0.25 - heating Cdh 0.25 -
Electric power input in power modes other than 'active mode' Annual electricity consumptionoff mode Poff 10 W cooling Qce 473 kWh/astandby mode Psb 10 W heating / Average Qhe 2665 kWh/athermostat-off mode Pto(cooling) 15 W heating / Warmer Qhe - kWh/a
Pto(heating) 30 W heating / colder Qhe - kWh/acrankcase heater mode Pck 5 W
Capacity control(indicate one of three options) Other itemsSound power level(indoor) Lwa 62 dB(A)Sound power level(outdoor) Lwa 69 dB(A)
fixed No Global warming potential GWP 675staged No Rated air flow(indoor) - 1200variable Yes Rated air flow(outdoor) - 4500
Contact details for obtaining Name and address of the manufacturer or of its authorised representative.more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd.
5 The Square, Stockley Park, Uxbridge, Middlesex,UB11 1ET, United kingdom
PJF000Z589 B
'19 • PAC-DB-308D
FDT125VNAWVH
- 98 -
Model(s) : FDC125VNA-W / FDT125VHOutdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space
cooling energy η s,c
efficiency
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 12.5 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 9.0 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 5.8 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.1 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.007 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.022 kW Standby mode PSB 0.007 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
309.0 %
Prated,c 12.5 kW 258.0 %
m3/h
486.0 %
773.0 %
Contact details
LWA 71.0 dB
NOx*** -
675
1164.0 %
0.25
4500
kgCO2eq.
PJF000Z589 B
'19 • PAC-DB-308D
- 99 -
Information to identify the model(s) to which the information relates : FDC125VNA-W / FDT125VHOutdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value Unit
Rated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /
and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 8.7 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.3 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.4 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+12℃ Pdh 2.9 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 9.8 kW Tbiv=bivalent COPd ortemperature
GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.4 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd or
Tj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heat
pumps:Operation limit
Degradation Tol temperature
coefficient Cdh -
heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater
back-up heating capacityOff mode POFF 0.007 kW
Thermostat-off mode PTO 0.034 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other items
For air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :
outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchanger
Emissions of nitrogen mg/kWh
oxides(if applicable) fuel input
GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
%172.1
No
Prated,h 14.0 kW
300.0 %
425.0 %
545.0 %
719.0 %
0.25
270.0 %
220.0 %
- %
- �
- kW
m3/h
LWA 71.0 dB- m3/h
PSB 0.007 kW
elbu
NOx*** -
675
Contact details
4380
kgCO2eq.
PJF000Z589 B
'19 • PAC-DB-308D
FDT125VSAWVH
- 100 -
Model(s) : FDC125VSA-W / FDT125VHOutdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space
cooling energy η s,c
efficiency
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 12.5 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 9.0 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 5.8 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.1 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.007 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.022 kW Standby mode PSB 0.007 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
309.0 %
Prated,c 12.5 kW 258.0 %
m3/h
486.0 %
773.0 %
Contact details
LWA 71.0 dB
NOx*** -
675
1164.0 %
0.25
4500
kgCO2eq.
PJF000Z589 B
'19 • PAC-DB-308D
- 101 -
Information to identify the model(s) to which the information relates : FDC125VSA-W / FDT125VHOutdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value Unit
Rated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /
and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 8.7 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.3 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.4 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+12℃ Pdh 2.9 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 9.8 kW Tbiv=bivalent COPd ortemperature
GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.4 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd or
Tj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heat
pumps:Operation limit
Degradation Tol temperature
coefficient Cdh -
heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater
back-up heating capacityOff mode POFF 0.007 kW
Thermostat-off mode PTO 0.034 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other items
For air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :
outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchanger
Emissions of nitrogen mg/kWh
oxides(if applicable) fuel input
GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
%172.1
No
Prated,h 14.0 kW
300.0 %
425.0 %
545.0 %
719.0 %
0.25
270.0 %
220.0 %
- %
- ℃
- kW
m3/h
LWA 71.0 dB- m3/h
PSB 0.007 kW
elbu
NOx*** -
675
Contact details
4380
kgCO2eq.
PJF000Z589 B
'19 • PAC-DB-308D
FDT140VNAWVH
- 102 -
Model(s) : FDC140VNA-W / FDT140VHOutdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space
cooling energy η s,c
efficiency
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 13.6 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 10.0 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 6.4 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.1 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.007 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.022 kW Standby mode PSB 0.007 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
284.0 %
Prated,c 13.6 kW 243.6 %
m3/h
443.0 %
717.0 %
Contact details
LWA 72.0 dB
NOx*** -
675
1164.0 %
0.25
4500
kgCO2eq.
PJF000Z589 B
'19 • PAC-DB-308D
- 103 -
Information to identify the model(s) to which the information relates : FDC140VNA-W / FDT140VHOutdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value Unit
Rated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /
and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 9.0 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.6 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.7 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+12℃ Pdh 2.9 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 10.5 kW Tbiv=bivalent COPd ortemperature
GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.9 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd or
Tj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heat
pumps:Operation limit
Degradation Tol temperature
coefficient Cdh -
heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater
back-up heating capacityOff mode POFF 0.007 kW
Thermostat-off mode PTO 0.034 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other items
For air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :
outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchanger
Emissions of nitrogen mg/kWh
oxides(if applicable) fuel input
GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
%173.9
No
Prated,h 15.5 kW
305.0 %
430.0 %
550.0 %
719.0 %
0.25
250.0 %
210.0 %
- %
- ℃
- kW
m3/h
LWA 73.0 dB- m3/h
PSB 0.007 kW
elbu
NOx*** -
675
Contact details
4380
kgCO2eq.
PJF000Z589 B
'19 • PAC-DB-308D
FDT140VSAWVH
- 104 -
Model(s) : FDC140VSA-W / FDT140VHOutdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space
cooling energy η s,c
efficiency
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 13.6 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 10.0 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 6.4 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.1 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.007 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.022 kW Standby mode PSB 0.007 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
284.0 %
Prated,c 13.6 kW 243.6 %
m3/h
443.0 %
717.0 %
Contact details
LWA 72.0 dB
NOx*** -
675
1164.0 %
0.25
4500
kgCO2eq.
PJF000Z589 B
'19 • PAC-DB-308D
- 105 -
Information to identify the model(s) to which the information relates : FDC140VSA-W / FDT140VHOutdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value Unit
Rated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /
and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 9.0 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.6 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.7 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+12℃ Pdh 2.9 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 10.5 kW Tbiv=bivalent COPd ortemperature
GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.9 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd or
Tj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heat
pumps:Operation limit
Degradation Tol temperature
coefficient Cdh -
heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater
back-up heating capacityOff mode POFF 0.007 kW
Thermostat-off mode PTO 0.034 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other items
For air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :
outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchanger
Emissions of nitrogen mg/kWh
oxides(if applicable) fuel input
GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
%173.9
No
Prated,h 15.5 kW
305.0 %
430.0 %
550.0 %
719.0 %
0.25
250.0 %
210.0 %
- %
- ℃
- kW
m3/h
LWA 73.0 dB- m3/h
PSB 0.007 kW
elbu
NOx*** -
675
Contact details
4380
kgCO2eq.
PJF000Z589 B
'19 • PAC-DB-308D
FDT125VNAWPVH
- 106 -
Model(s) : FDC125VNA-W / FDT60VH (x2 units)Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 12.5 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 9.2 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 5.9 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.6 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.000 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
0.25
4500 m3/h
Contact details
LWA 71.0 dB
NOx*** -
675
Prated,c 12.5 kW 315.5 %
330.0 %
519.0 %
950.0 %
1960.0 %
kgCO2eq.
PJF000Z589 B
'19 • PAC-DB-308D
- 107 -
Information to identify the model(s) to which the information relates : FDC125VNA-W / FDT60VH (x2 units)Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value Unit
Rated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /
and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 8.7 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.3 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.4 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+12℃ Pdh 3.0 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 9.8 kW Tbiv=bivalent COPd ortemperature
GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.4 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd or
Tj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heat
pumps:Operation limit
Degradation Tol temperature
coefficient Cdh -
heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater
back-up heating capacityOff mode POFF 0.008 kW
Thermostat-off mode PTO 0.020 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other items
For air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :
outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchanger
Emissions of nitrogen mg/kWh
oxides(if applicable) fuel input
GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
%205.1
No
Prated,h 14.0 kW
662.0 %
985.0 %
328.0 %
508.0 %
0.25
270.0 %
220.0 %
- %
- ℃
NOx*** -
675
Contact details
4380
- kW
m3/h
LWA 71.0 dB- m3/h
PSB 0.008 kW
elbu
kgCO2eq.
PJF000Z589 B
'19 • PAC-DB-308D
FDT125VSAWPVH
- 108 -
Model(s) : FDC125VSA-W / FDT60VH (x2 units)Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 12.5 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 9.2 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 5.9 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.6 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.000 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
330.0 %
Prated,c 12.5 kW 315.5 %
m3/h
519.0 %
950.0 %
Contact details
LWA 71.0 dB
NOx*** -
675
1960.0 %
0.25
4500
kgCO2eq.
PJF000Z589 B
'19 • PAC-DB-308D
- 109 -
Information to identify the model(s) to which the information relates : FDC125VSA-W / FDT60VH (x2 units)Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value Unit
Rated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /
and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 8.7 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.3 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.4 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+12℃ Pdh 3.0 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 9.8 kW Tbiv=bivalent COPd ortemperature
GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.4 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd or
Tj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heat
pumps:Operation limit
Degradation Tol temperature
coefficient Cdh -
heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater
back-up heating capacityOff mode POFF 0.008 kW
Thermostat-off mode PTO 0.020 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other items
For air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :
outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchanger
Emissions of nitrogen mg/kWh
oxides(if applicable) fuel input
GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
%205.1
No
Prated,h 14.0 kW
662.0 %
985.0 %
328.0 %
508.0 %
0.25
270.0 %
220.0 %
- %
- ℃
NOx*** -
675
Contact details
4380
- kW
m3/h
LWA 71.0 dB- m3/h
PSB 0.008 kW
elbu
kgCO2eq.
PJF000Z589 B
'19 • PAC-DB-308D
FDT140VNAWPVH
- 110 -
Model(s) : FDC140VNA-W / FDT71VH (x2 units)Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 13.6 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 10.0 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 6.4 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.7 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.000 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
322.0 %
Prated,c 13.6 kW 313.3 %
m3/h
530.0 %
870.0 %
Contact details
LWA 72.0 dB
NOx*** -
675
2200.0 %
0.25
4500
kgCO2eq.
PJF000Z589 B
'19 • PAC-DB-308D
- 111 -
Information to identify the model(s) to which the information relates : FDC140VNA-W / FDT71VH (x2 units)Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value Unit
Rated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /
and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 9.3 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.6 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.6 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+12℃ Pdh 3.0 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 10.5 kW Tbiv=bivalent COPd ortemperature
GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.9 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd or
Tj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heat
pumps:Operation limit
Degradation Tol temperature
coefficient Cdh -
heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater
back-up heating capacityOff mode POFF 0.008 kW
Thermostat-off mode PTO 0.020 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other items
For air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :
outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchanger
Emissions of nitrogen mg/kWh
oxides(if applicable) fuel input
GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
%201.6
No
Prated,h 15.5 kW
330.0 %
500.0 %
640.0 %
940.0 %
0.25
270.0 %
220.0 %
- %
- ℃
- kW
m3/h
LWA 73.0 dB- m3/h
PSB 0.008 kW
elbu
NOx*** -
675
Contact details
4380
kgCO2eq.
PJF000Z589 B
'19 • PAC-DB-308D
FDT140VSAWPVH
- 112 -
Model(s) : FDC140VSA-W / FDT71VH (x2 units)Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 13.6 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 10.0 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 6.4 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.7 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.000 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
322.0 %
Prated,c 13.6 kW 313.3 %
m3/h
530.0 %
870.0 %
Contact details
LWA 72.0 dB
NOx*** -
675
2200.0 %
0.25
4500
kgCO2eq.
PJF000Z589 B
'19 • PAC-DB-308D
- 113 -
Information to identify the model(s) to which the information relates : FDC140VSA-W / FDT71VH (x2 units)Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value Unit
Rated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /
and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 9.3 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.6 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.6 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+12℃ Pdh 3.0 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 10.5 kW Tbiv=bivalent COPd ortemperature
GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.9 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd or
Tj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heat
pumps:Operation limit
Degradation Tol temperature
coefficient Cdh -
heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater
back-up heating capacityOff mode POFF 0.008 kW
Thermostat-off mode PTO 0.020 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other items
For air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :
outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchanger
Emissions of nitrogen mg/kWh
oxides(if applicable) fuel input
GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
%201.6
No
Prated,h 15.5 kW
330.0 %
500.0 %
640.0 %
940.0 %
0.25
270.0 %
220.0 %
- %
- ℃
- kW
m3/h
LWA 73.0 dB- m3/h
PSB 0.008 kW
elbu
NOx*** -
675
Contact details
4380
kgCO2eq.
PJF000Z589 B
'19 • PAC-DB-308D
FDT140VNAWTVH
- 114 -
Model(s) : FDC140VNA-W / FDT50VH (x3 units)Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 13.6 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 10.0 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 6.4 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.7 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.000 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Prated,c 13.6 kW 313.3 %
322.0 %
530.0 %
2200.0 %
870.0 %
0.25
4500 m3/h
675
LWA 72.0 dB
Contact details
NOx*** -
kgCO2eq.
PJF000Z589 B
'19 • PAC-DB-308D
- 115 -
Information to identify the model(s) to which the information relates : FDC140VNA-W / FDT50VH (x3 units)Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value Unit
Rated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /
and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 9.3 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.6 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.6 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+12℃ Pdh 3.0 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 10.5 kW Tbiv=bivalent COPd ortemperature
GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.9 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd or
Tj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heat
pumps:Operation limit
Degradation Tol temperature
coefficient Cdh -
heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater
back-up heating capacityOff mode POFF 0.008 kW
Thermostat-off mode PTO 0.020 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other items
For air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :
outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchanger
Emissions of nitrogen mg/kWh
oxides(if applicable) fuel input
GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
%201.6
No
Prated,h 15.5 kW
640.0 %
940.0 %
330.0 %
500.0 %
0.25
270.0 %
220.0 %
- %
- ℃
NOx*** -
675
Contact details
4380
- kW
m3/h
LWA 73.0 dB- m3/h
PSB 0.008 kW
elbu
kgCO2eq.
PJF000Z589 B
'19 • PAC-DB-308D
FDT140VSAWTVH
- 116 -
Model(s) : FDC140VSA-W / FDT50VH (x3 units)Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 13.6 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 10.0 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 6.4 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.7 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.000 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Prated,c 13.6 kW 313.3 %
322.0 %
530.0 %
2200.0 %
870.0 %
0.25
4500 m3/h
675
LWA 72.0 dB
Contact details
NOx*** -
kgCO2eq.
PJF000Z589 B
'19 • PAC-DB-308D
- 117 -
Information to identify the model(s) to which the information relates : FDC140VSA-W / FDT50VH (x3 units)Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value Unit
Rated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /
and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 9.3 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.6 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.6 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+12℃ Pdh 3.0 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 10.5 kW Tbiv=bivalent COPd ortemperature
GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.9 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd or
Tj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heat
pumps:Operation limit
Degradation Tol temperature
coefficient Cdh -
heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater
back-up heating capacityOff mode POFF 0.008 kW
Thermostat-off mode PTO 0.020 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other items
For air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :
outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchanger
Emissions of nitrogen mg/kWh
oxides(if applicable) fuel input
GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
675
Contact details
4380
LWA 73.0 dB- m3/h
elbu - kW
PSB 0.008 kW
m3/h
NOx*** -
0.25
270.0 %
220.0 %
- %
- ℃
500.0 %
201.6
640.0 %
940.0 %
No
Prated,h 15.5 kW %
330.0 %
kgCO2eq.
PJF000Z589 B
'19 • PAC-DB-308D
Models FDT50VH, 60VH, 71VH, 100VH, 125VH, 140VH
- 118 -
Model(s) :
Item Symbol Value Unit Item Symbol Value Unit
Cooling capacity (sensible) Prated,c 3.9 kW Total electric power input Pelec 0.030 kW
Cooling capacity (latent) Prated,c 0.1 kW LWA 50.0 dB
Heating capacity Prated,h 4.5 kW
Mitsubishi heavy industries thermal systems,LTD
Model(s) :
Item Symbol Value Unit Item Symbol Value Unit
Cooling capacity (sensible) Prated,c 4.4 kW Total electric power input Pelec 0.040 kW
Cooling capacity (latent) Prated,c 0.6 kW LWA 55.0 dB
Heating capacity Prated,h 5.4 kW
Mitsubishi heavy industries thermal systems,LTD
Model(s) :
Item Symbol Value Unit Item Symbol Value Unit
Cooling capacity (sensible) Prated,c 5.5 kW Total electric power input Pelec 0.070 kW
Cooling capacity (latent) Prated,c 0.1 kW LWA 58.0 dB
Heating capacity Prated,h 6.7 kW
Mitsubishi heavy industries thermal systems,LTD
Model(s) :
Item Symbol Value Unit Item Symbol Value Unit
Cooling capacity (sensible) Prated,c 6.2 kW Total electric power input Pelec 0.080 kW
Cooling capacity (latent) Prated,c 0.9 kW LWA 59.0 dB
Heating capacity Prated,h 8.0 kW
Mitsubishi heavy industries thermal systems,LTD
Model(s) :
Item Symbol Value Unit Item Symbol Value Unit
Cooling capacity (sensible) Prated,c 8.4 kW Total electric power input Pelec 0.130 kW
Cooling capacity (latent) Prated,c 1.6 kW LWA 62.0 dB
Heating capacity Prated,h 11.2 kW
Mitsubishi heavy industries thermal systems,LTD
Model(s) :
Item Symbol Value Unit Item Symbol Value Unit
Cooling capacity (sensible) Prated,c 9.6 kW Total electric power input Pelec 0.140 kW
Cooling capacity (latent) Prated,c 2.9 kW LWA 63.0 dB
Heating capacity Prated,h 14.0 kW
Mitsubishi heavy industries thermal systems,LTD
Model(s) :
Item Symbol Value Unit Item Symbol Value Unit
Cooling capacity (sensible) Prated,c 10.4 kW Total electric power input Pelec 0.140 kW
Cooling capacity (latent) Prated,c 3.6 kW LWA 63.0 dB
Heating capacity Prated,h 16.0 kW
Mitsubishi heavy industries thermal systems,LTD
Contact details
FDT40VH
Sound power level(per speed setting,if applicable)
Contact details
FDT50VH
Sound power level(per speed setting,if applicable)
Contact details
FDT60VH
Sound power level(per speed setting,if applicable)
Contact details
FDT71VH
Sound power level(per speed setting,if applicable)
FDT140VH
Sound power level(per speed setting,if applicable)
Contact details
FDT100VH
Sound power level(per speed setting,if applicable)
Contact details
FDT125VH
Sound power level(per speed setting,if applicable)
Contact details
PJF000Z589 B
- 119 -
'19 • PAC-DB-308D
(2) Ceiling cassette-4 way compact type (FDTC)
FDTC100VNAWPVH
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season theIndoor unit model name FDTC50VH (x2 units) information relates to. Indicated values should relate to oneOutdoor unit model name FDC100VNA-W heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory) Yescooling Yes Warmer(if designated) Noheating Yes Colder(if designated) No
Item symbol value unit Item symbol value classDesign load Seasonal efficiency and energy efficiency classcooling Pdesignc 10.0 kW cooling SEER 6.17 A++heating / Average Pdesignh 8.5 kW heating / Average SCOP/A 4.38 A+heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - -heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unitDeclared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignhheating / Average (-10℃) Pdh 8.5 kW heating / Average (-10℃) elbu 0 kWheating / Warmer (2℃) Pdh - kW heating / Warmer (2℃) elbu - kWheating / Colder (-22℃) Pdh - kW heating / Colder (-22℃) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19)℃ and Declared energy efficiency ratio, at indoor temperature 27(19)℃ andoutdoor temperature Tj outdoor temperature TjTj=35℃ Pdc 10.00 kW Tj=35℃ EERd 3.17 -Tj=30℃ Pdc 7.37 kW Tj=30℃ EERd 4.80 -Tj=25℃ Pdc 4.74 kW Tj=25℃ EERd 7.50 -Tj=20℃ Pdc 3.25 kW Tj=20℃ EERd 12.00 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh 7.40 kW Tj=-7℃ COPd 3.04 -Tj=2℃ Pdh 4.50 kW Tj=2℃ COPd 4.30 -Tj=7℃ Pdh 2.90 kW Tj=7℃ COPd 5.50 -Tj=12℃ Pdh 2.82 kW Tj=12℃ COPd 6.60 -Tj=bivalent temperature Pdh 8.50 kW Tj=bivalent temperature COPd 2.50 -Tj=operating limit Pdh 6.20 kW Tj=operating limit COPd 2.10 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh - kW Tj=-7℃ COPd - -Tj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -Tj=-15℃ Pdh - kW Tj=-15℃ COPd - -
Bivalent temperature Operating limit temperatureheating / Average Tbiv -10 ℃ heating / Average Tol -20 ℃heating / Warmer Tbiv - ℃ heating / Warmer Tol - ℃heating / Colder Tbiv - ℃ heating / Colder Tol - ℃
Cycling interval capacity Cycling interval efficiencyfor cooling Pcycc - kW for cooling EERcyc - -for heating Pcych - kW for heating COPcyc - -
Degradation coefficient Degradation coefficientcooling Cdc 0.25 - heating Cdh 0.25 -
Electric power input in power modes other than 'active mode' Annual electricity consumptionoff mode Poff 10 W cooling Qce 567 kWh/astandby mode Psb 10 W heating / Average Qhe 2715 kWh/athermostat-off mode Pto(cooling) 15 W heating / Warmer Qhe - kWh/a
Pto(heating) 30 W heating / colder Qhe - kWh/acrankcase heater mode Pck 5 W
Capacity control(indicate one of three options) Other itemsSound power level(indoor) Lwa 59 dB(A)Sound power level(outdoor) Lwa 69 dB(A)
fixed No Global warming potential GWP 675 kgCO2eq.staged No Rated air flow(indoor) - 780 m3/hvariable Yes Rated air flow(outdoor) - 4500 m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative.more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd.
5 The Square, Stockley Park, Uxbridge, Middlesex, UB11 1ET,United Kingdom
PJF000Z517 B
- 120 -
'19 • PAC-DB-308D
FDTC100VSAWPVH
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season theIndoor unit model name FDTC50VH (x2 units) information relates to. Indicated values should relate to oneOutdoor unit model name FDC100VSA-W heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory) Yescooling Yes Warmer(if designated) Noheating Yes Colder(if designated) No
Item symbol value unit Item symbol value classDesign load Seasonal efficiency and energy efficiency classcooling Pdesignc 10.0 kW cooling SEER 6.17 A++heating / Average Pdesignh 8.5 kW heating / Average SCOP/A 4.38 A+heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - -heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unitDeclared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignhheating / Average (-10℃) Pdh 8.5 kW heating / Average (-10℃) elbu 0 kWheating / Warmer (2℃) Pdh - kW heating / Warmer (2℃) elbu - kWheating / Colder (-22℃) Pdh - kW heating / Colder (-22℃) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19)℃ and Declared energy efficiency ratio, at indoor temperature 27(19)℃ andoutdoor temperature Tj outdoor temperature TjTj=35℃ Pdc 10.00 kW Tj=35℃ EERd 3.17 -Tj=30℃ Pdc 7.37 kW Tj=30℃ EERd 4.80 -Tj=25℃ Pdc 4.74 kW Tj=25℃ EERd 7.50 -Tj=20℃ Pdc 3.25 kW Tj=20℃ EERd 12.00 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh 7.40 kW Tj=-7℃ COPd 3.04 -Tj=2℃ Pdh 4.50 kW Tj=2℃ COPd 4.30 -Tj=7℃ Pdh 2.90 kW Tj=7℃ COPd 5.50 -Tj=12℃ Pdh 2.82 kW Tj=12℃ COPd 6.60 -Tj=bivalent temperature Pdh 8.50 kW Tj=bivalent temperature COPd 2.50 -Tj=operating limit Pdh 6.20 kW Tj=operating limit COPd 2.10 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh - kW Tj=-7℃ COPd - -Tj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -Tj=-15℃ Pdh - kW Tj=-15℃ COPd - -
Bivalent temperature Operating limit temperatureheating / Average Tbiv -10 ℃ heating / Average Tol -20 ℃heating / Warmer Tbiv - ℃ heating / Warmer Tol - ℃heating / Colder Tbiv - ℃ heating / Colder Tol - ℃
Cycling interval capacity Cycling interval efficiencyfor cooling Pcycc - kW for cooling EERcyc - -for heating Pcych - kW for heating COPcyc - -
Degradation coefficient Degradation coefficientcooling Cdc 0.25 - heating Cdh 0.25 -
Electric power input in power modes other than 'active mode' Annual electricity consumptionoff mode Poff 10 W cooling Qce 567 kWh/astandby mode Psb 10 W heating / Average Qhe 2715 kWh/athermostat-off mode Pto(cooling) 15 W heating / Warmer Qhe - kWh/a
Pto(heating) 30 W heating / colder Qhe - kWh/acrankcase heater mode Pck 5 W
Capacity control(indicate one of three options) Other itemsSound power level(indoor) Lwa 59 dB(A)Sound power level(outdoor) Lwa 69 dB(A)
fixed No Global warming potential GWP 675 kgCO2eq.staged No Rated air flow(indoor) - 780 m3/hvariable Yes Rated air flow(outdoor) - 4500 m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative.more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd.
5 The Square, Stockley Park, Uxbridge, Middlesex, UB11 1ET,United Kingdom
PJF000Z517 B
- 121 -
'19 • PAC-DB-308D
FDT125VNAWPVH
Model(s) : FDC125VNA-W / FDTC60VH (x2 units)
Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 12.5 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 9.2 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 5.9 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.5 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.010 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.000 kW Standby mode PSB 0.010 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
255.0 %
Prated,c 12.5 kW 260.6 %
450.0 %
739.0 %
1782.0 %
0.25
4500 m3/h
Contact details
LWA 71.0 dB
NOx*** -
675kgCO2eq.
PJF000Z517 B
- 122 -
'19 • PAC-DB-308D
Information to identify the model(s) to which the information relates : FDC125VNA-W / FDTC60VH (x2 units)
Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value Unit
Rated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /
and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 8.7 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.3 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.4 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+12℃ Pdh 3.0 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 9.8 kW Tbiv=bivalent COPd ortemperature GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.4 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd or
Tj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heat
pumps:Operation limit
Degradation Tol temperature
coefficient Cdh -
heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater
back-up heating capacityOff mode POFF 0.010 kW
Thermostat-off mode PTO 0.020 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other items
For air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :
outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchanger
Emissions of nitrogen mg/kWh
oxides(if applicable) fuel input
GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
NOx*** -
675
Contact details
LWA 71.0 dB- m3/h
- %
- ℃
PSB 0.010 kW
4380 m3/h
0.25
No
Prated,h 14.0 kW 171.3 %
270.0 %
420.0 %
580.0 %
805.0 %
230.0 %
200.0 %
elbu - kW
kgCO2eq.
PJF000Z517 B
- 123 -
'19 • PAC-DB-308D
FDTC125VSAWPVH
Model(s) : FDC125VSA-W / FDTC60VH (x2 units)
Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 12.5 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 9.2 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 5.9 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.5 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.010 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.000 kW Standby mode PSB 0.010 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
255.0 %
Prated,c 12.5 kW 260.6 %
450.0 %
739.0 %
1782.0 %
0.25
4500 m3/h
Contact details
LWA 71.0 dB
NOx*** -
675kgCO2eq.
PJF000Z517 B
- 124 -
'19 • PAC-DB-308D
Information to identify the model(s) to which the information relates : FDC125VSA-W / FDTC60VH (x2 units)
Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value Unit
Rated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /
and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 8.7 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.3 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.4 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+12℃ Pdh 3.0 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 9.8 kW Tbiv=bivalent COPd ortemperature GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.4 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd or
Tj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heat
pumps:Operation limit
Degradation Tol temperature
coefficient Cdh -
heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater
back-up heating capacityOff mode POFF 0.010 kW
Thermostat-off mode PTO 0.020 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other items
For air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :
outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchanger
Emissions of nitrogen mg/kWh
oxides(if applicable) fuel input
GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
NOx*** -
675
Contact details
LWA 71.0 dB- m3/h
- %
- ℃
PSB 0.010 kW
4380 m3/h
0.25
No
Prated,h 14.0 kW 171.3 %
270.0 %
420.0 %
580.0 %
805.0 %
230.0 %
200.0 %
elbu - kW
kgCO2eq.
PJF000Z517 B
- 125 -
'19 • PAC-DB-308D
FDTC140VNAWTVH
Model(s) : FDC140VNA-W / FDTC50VH (x3 units)
Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 13.6 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 10.0 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 6.4 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.5 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.000 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
286.0 %
Prated,c 13.6 kW 271.4 %
442.0 %
773.0 %
1860.0 %
0.25
4500 m3/h
Contact details
LWA 72.0 dB
NOx*** -
675kgCO2eq.
PJF000Z517 B
- 126 -
'19 • PAC-DB-308D
Information to identify the model(s) to which the information relates : FDC140VNA-W / FDTC50VH (x3 units)
Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value Unit
Rated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /
and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 9.3 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.6 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.6 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+12℃ Pdh 3.0 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 10.5 kW Tbiv=bivalent COPd ortemperature GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.8 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd or
Tj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heat
pumps:Operation limit
Degradation Tol temperature
coefficient Cdh -
heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater
back-up heating capacityOff mode POFF 0.008 kW
Thermostat-off mode PTO 0.020 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other items
For air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :
outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchanger
Emissions of nitrogen mg/kWh
oxides(if applicable) fuel input
GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
NOx*** -
675
Contact details
LWA 73.0 dB- m3/h
- %
- ℃
PSB 0.008 kW
4380 m3/h
0.25
No
Prated,h 15.5 kW 196.0 %
317.0 %
474.0 %
660.0 %
963.0 %
240.0 %
200.0 %
elbu - kW
kgCO2eq.
PJF000Z517 B
- 127 -
'19 • PAC-DB-308D
FDTC140VSAWTVH
Model(s) : FDC140VSA-W / FDTC50VH (x3 units)
Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 13.6 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 10.0 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 6.4 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.5 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.000 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
286.0 %
Prated,c 13.6 kW 271.4 %
442.0 %
773.0 %
1860.0 %
0.25
4500 m3/h
Contact details
LWA 72.0 dB
NOx*** -
675kgCO2eq.
PJF000Z517 B
- 128 -
'19 • PAC-DB-308D
Information to identify the model(s) to which the information relates : FDC140VSA-W / FDTC50VH (x3 units)
Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value Unit
Rated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /
and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 9.3 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.6 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.6 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+12℃ Pdh 3.0 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 10.5 kW Tbiv=bivalent COPd ortemperature GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.8 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd or
Tj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heat
pumps:Operation limit
Degradation Tol temperature
coefficient Cdh -
heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater
back-up heating capacityOff mode POFF 0.008 kW
Thermostat-off mode PTO 0.020 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other items
For air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :
outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchanger
Emissions of nitrogen mg/kWh
oxides(if applicable) fuel input
GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
NOx*** -
675
Contact details
LWA 73.0 dB- m3/h
- %
- ℃
PSB 0.008 kW
4380 m3/h
0.25
No
Prated,h 15.5 kW 196.0 %
317.0 %
474.0 %
660.0 %
963.0 %
240.0 %
200.0 %
elbu - kW
kgCO2eq.
PJF000Z517 B
- 129 -
'19 • PAC-DB-308D
Models FDTC50VH, 60VH
Model(s) :
Item Symbol Vaiue Unit Item Symbol Vaiue Unit
Cooling capacity (sensible) Prated,c 3.8 kW Total electric power input Pelec 0.050 kW
Cooling capacity (latent) Prated,c 1.2 kW LWA 59.0 dB
Heating capacity Prated,h 5.4 kW
Mitsubishi heavy industries thermal systems,LTD
Model(s) :
Item Symbol Vaiue Unit Item Symbol Vaiue Unit
Cooling capacity (sensible) Prated,c 3.9 kW Total electric power input Pelec 0.060 kW
Cooling capacity (latent) Prated,c 1.7 kW LWA 60.0 dB
Heating capacity Prated,h 6.7 kW
Mitsubishi heavy industries thermal systems,LTD
FDTC50VH
Sound power level(per speed setting,if applicable)
Contact details
FDTC60VH
Sound power level(per speed setting,if applicable)
Contact details
PJF000Z517 B
- 130 -
'19 • PAC-DB-308D
PJG000Z625 A
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season theIndoor unit model name FDU100VH information relates to. Indicated values should relate to oneOutdoor unit model name FDC100VNA-W heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory) Yescooling Yes Warmer(if designated) Noheating Yes Colder(if designated) No
Item symbol value unit Item symbol value classDesign load Seasonal efficiency and energy efficiency classcooling Pdesignc 10.0 kW cooling SEER 6.11 A++heating / Average Pdesignh 8.5 kW heating / Average SCOP/A 4.19 A+heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - -heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unitDeclared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignhheating / Average (-10℃) Pdh 8.5 kW heating / Average (-10℃) elbu 0 kWheating / Warmer (2℃) Pdh - kW heating / Warmer (2℃) elbu - kWheating / Colder (-22℃) Pdh - kW heating / Colder (-22℃) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19)℃ and Declared energy efficiency ratio, at indoor temperature 27(19)℃ andoutdoor temperature Tj outdoor temperature TjTj=35℃ Pdc 10.00 kW Tj=35℃ EERd 3.35 -Tj=30℃ Pdc 7.37 kW Tj=30℃ EERd 5.00 -Tj=25℃ Pdc 4.74 kW Tj=25℃ EERd 8.05 -Tj=20℃ Pdc 3.10 kW Tj=20℃ EERd 9.50 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh 7.40 kW Tj=-7℃ COPd 3.14 -Tj=2℃ Pdh 4.50 kW Tj=2℃ COPd 4.02 -Tj=7℃ Pdh 2.90 kW Tj=7℃ COPd 5.24 -Tj=12℃ Pdh 2.90 kW Tj=12℃ COPd 6.27 -Tj=bivalent temperature Pdh 8.50 kW Tj=bivalent temperature COPd 2.50 -Tj=operating limit Pdh 6.30 kW Tj=operating limit COPd 2.10 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh - kW Tj=-7℃ COPd - -Tj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -Tj=-15℃ Pdh - kW Tj=-15℃ COPd - -
Bivalent temperature Operating limit temperatureheating / Average Tbiv -10 ℃ heating / Average Tol -20 ℃heating / Warmer Tbiv - ℃ heating / Warmer Tol -20 ℃heating / Colder Tbiv - ℃ heating / Colder Tol -20 ℃
Cycling interval capacity Cycling interval efficiencyfor cooling Pcycc - kW for cooling EERcyc - -for heating Pcych - kW for heating COPcyc - -
Degradation coefficient Degradation coefficientcooling Cdc 0.25 - heating Cdh 0.25 -
Electric power input in power modes other than 'active mode' Annual electricity consumptionoff mode Poff 8 W cooling Qce 574 kWh/astandby mode Psb 8 W heating / Average Qhe 2843 kWh/athermostat-off mode Pto(cooling) 65 W heating / Warmer Qhe - kWh/a
Pto(heating) 75 W heating / colder Qhe - kWh/acrankcase heater mode Pck 5 W
Capacity control(indicate one of three options) Other itemsSound power level(indoor) Lwa 65 dB(A)Sound power level(outdoor) Lwa 69 dB(A)
fixed No Global warming potential GWP 675 kgCO2eq.staged No Rated air flow(indoor) - 2,160 m3/hvariable Yes Rated air flow(outdoor) - 4,500 m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative.more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd.
5 The Square, Stockley Park, Uxbridge, Middlesex, UB11 1ET,United Kingdom
(3) Duct connected-High static pressure type (FDU)
FDU100VNAWVH
- 131 -
'19 • PAC-DB-308D
FDU100VSAWVH
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season theIndoor unit model name FDU100VH information relates to. Indicated values should relate to oneOutdoor unit model name FDC100VSA-W heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory) Yescooling Yes Warmer(if designated) Noheating Yes Colder(if designated) No
Item symbol value unit Item symbol value classDesign load Seasonal efficiency and energy efficiency classcooling Pdesignc 10.0 kW cooling SEER 6.11 A++heating / Average Pdesignh 8.5 kW heating / Average SCOP/A 4.19 A+heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - -heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unitDeclared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignhheating / Average (-10℃) Pdh 8.5 kW heating / Average (-10℃) elbu 0 kWheating / Warmer (2℃) Pdh - kW heating / Warmer (2℃) elbu - kWheating / Colder (-22℃) Pdh - kW heating / Colder (-22℃) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19)℃ and Declared energy efficiency ratio, at indoor temperature 27(19)℃ andoutdoor temperature Tj outdoor temperature TjTj=35℃ Pdc 10.00 kW Tj=35℃ EERd 3.35 -Tj=30℃ Pdc 7.37 kW Tj=30℃ EERd 5.00 -Tj=25℃ Pdc 4.74 kW Tj=25℃ EERd 8.05 -Tj=20℃ Pdc 3.10 kW Tj=20℃ EERd 9.50 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh 7.40 kW Tj=-7℃ COPd 3.14 -Tj=2℃ Pdh 4.50 kW Tj=2℃ COPd 4.02 -Tj=7℃ Pdh 2.90 kW Tj=7℃ COPd 5.24 -Tj=12℃ Pdh 2.90 kW Tj=12℃ COPd 6.27 -Tj=bivalent temperature Pdh 8.50 kW Tj=bivalent temperature COPd 2.50 -Tj=operating limit Pdh 6.30 kW Tj=operating limit COPd 2.10 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh - kW Tj=-7℃ COPd - -Tj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -Tj=-15℃ Pdh - kW Tj=-15℃ COPd - -
Bivalent temperature Operating limit temperatureheating / Average Tbiv -10 ℃ heating / Average Tol -20 ℃heating / Warmer Tbiv - ℃ heating / Warmer Tol -20 ℃heating / Colder Tbiv - ℃ heating / Colder Tol -20 ℃
Cycling interval capacity Cycling interval efficiencyfor cooling Pcycc - kW for cooling EERcyc - -for heating Pcych - kW for heating COPcyc - -
Degradation coefficient Degradation coefficientcooling Cdc 0.25 - heating Cdh 0.25 -
Electric power input in power modes other than 'active mode' Annual electricity consumptionoff mode Poff 8.0 W cooling Qce 574 kWh/astandby mode Psb 8.0 W heating / Average Qhe 2843 kWh/athermostat-off mode Pto(cooling) 65.0 W heating / Warmer Qhe - kWh/a
Pto(heating) 75.0 W heating / colder Qhe - kWh/acrankcase heater mode Pck 5.0 W
Capacity control(indicate one of three options) Other itemsSound power level(indoor) Lwa 65 dB(A)Sound power level(outdoor) Lwa 69 dB(A)
fixed No Global warming potential GWP 675 kgCO2eq.staged No Rated air flow(indoor) - 2,160 m3/hvariable Yes Rated air flow(outdoor) - 4,500 m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative.more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd.
5 The Square, Stockley Park, Uxbridge, Middlesex, UB11 1ET,United Kingdom
PJG000Z625 A
- 132 -
'19 • PAC-DB-308D
PJG000Z625 A
Model(s) : FDC125VNA-W / FDU125VH
Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 12.5 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 9.2 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 5.9 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.1 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.008 kW
Thermostat-off mode PTO 0.075 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Prated,c 12.5 kW 219.8 %
425.0 %
287.0 %
920.0 %
705.0 %
0.25
4,500 m3/h
LWA 71.0 dB
Contact details
NOx*** -
675kgCO2eq.
FDU125VNAWVH
- 133 -
'19 • PAC-DB-308D
Information to identify the model(s) to which the information relates : FDC125VNA-W / FDU125VH
Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value Unit
Rated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /
and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 8.7 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.3 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.4 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+12℃ Pdh 2.7 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 9.8 kW Tbiv=bivalent COPd ortemperature
GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.4 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd or
Tj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heat
pumps:Operation limit
Degradation Tol temperature
coefficient Cdh -
heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater
back-up heating capacityOff mode POFF 0.008 kW
Thermostat-off mode PTO 0.090 kW Type of energy inputCrankcase heater mode PCK 0.008 kW Standby mode
Other items
For air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :
outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchanger
Emissions of nitrogen mg/kWh
oxides(if applicable) fuel input
GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
300.0 %
No
Prated,h 14.0 kW 162.1 %
615.0 %
270.0 %
399.0 %
515.0 %
- ℃
0.25
210.0 %
- %
PSB 0.008 kW
elbu - kW
4,380 m3/h
LWA 71.0 dB- m3/h
Contact details
NOx*** -
675kgCO2eq.
PJG000Z625 A
- 134 -
'19 • PAC-DB-308D
PJG000Z625 A
Model(s) : FDC125VSA-W / FDU125VH
Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 12.5 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 9.2 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 5.9 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.1 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.008 kW
Thermostat-off mode PTO 0.075 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Prated,c 12.5 kW 219.8 %
425.0 %
287.0 %
920.0 %
705.0 %
0.25
4,500 m3/h
LWA 71.0 dB
Contact details
NOx*** -
675kgCO2eq.
FDU125VSAWVH
- 135 -
'19 • PAC-DB-308D
Information to identify the model(s) to which the information relates : FDC125VSA-W / FDU125VH
Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value Unit
Rated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /
and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 8.7 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.3 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.4 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+12℃ Pdh 2.7 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 9.8 kW Tbiv=bivalent COPd ortemperature
GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.4 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd or
Tj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heat
pumps:Operation limit
Degradation Tol temperature
coefficient Cdh -
heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater
back-up heating capacityOff mode POFF 0.008 kW
Thermostat-off mode PTO 0.090 kW Type of energy inputCrankcase heater mode PCK 0.008 kW Standby mode
Other items
For air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :
outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchanger
Emissions of nitrogen mg/kWh
oxides(if applicable) fuel input
GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
300.0 %
No
Prated,h 14.0 kW 162.1 %
615.0 %
270.0 %
399.0 %
515.0 %
- ℃
0.25
210.0 %
- %
PSB 0.008 kW
elbu - kW
4,380 m3/h
LWA 71.0 dB- m3/h
Contact details
NOx*** -
675kgCO2eq.
PJG000Z625 A
- 136 -
'19 • PAC-DB-308D
PJG000Z625 A
Model(s) : FDC140VNA-W / FDU140VH
Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 13.6 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 10.0 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 6.4 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.2 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.008 kW
Thermostat-off mode PTO 0.090 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Prated,c 13.6 kW 208.8 %
390.0 %
265.0 %
900.0 %
680.0 %
0.25
4,500 m3/h
LWA 72.0 dB
Contact details
NOx*** -
675kgCO2eq.
FDU140VNAWVH
- 137 -
'19 • PAC-DB-308D
Information to identify the model(s) to which the information relates : FDC140VNA-W / FDU140VH
Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value Unit
Rated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /
and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 9.3 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.6 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.6 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+12℃ Pdh 2.7 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 10.5 kW Tbiv=bivalent COPd ortemperature
GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.9 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd or
Tj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heat
pumps:Operation limit
Degradation Tol temperature
coefficient Cdh -
heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater
back-up heating capacityOff mode POFF 0.008 kW
Thermostat-off mode PTO 0.100 kW Type of energy inputCrankcase heater mode PCK 0.008 kW Standby mode
Other items
For air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :
outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchanger
Emissions of nitrogen mg/kWh
oxides(if applicable) fuel input
GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
295.0 %
No
Prated,h 15.5 kW 157.4 %
596.0 %
270.0 %
385.0 %
500.0 %
- ℃
0.25
220.0 %
- %
PSB 0.008 kW
elbu - kW
4,380 m3/h
LWA 73.0 dB- m3/h
Contact details
NOx*** -
675kgCO2eq.
PJG000Z625 A
- 138 -
'19 • PAC-DB-308D
PJG000Z625 A
Model(s) : FDC140VSA-W / FDU140VH
Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 13.6 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 10.0 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 6.4 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.2 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.008 kW
Thermostat-off mode PTO 0.090 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Prated,c 13.6 kW 208.8 %
390.0 %
265.0 %
900.0 %
680.0 %
0.25
4,500 m3/h
LWA 72.0 dB
Contact details
NOx*** -
675kgCO2eq.
FDU140VSAWVH
- 139 -
'19 • PAC-DB-308D
Information to identify the model(s) to which the information relates : FDC140VSA-W / FDU140VH
Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value Unit
Rated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /
and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 9.3 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.6 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.6 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+12℃ Pdh 2.7 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 10.5 kW Tbiv=bivalent COPd ortemperature
GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.9 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd or
Tj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heat
pumps:Operation limit
Degradation Tol temperature
coefficient Cdh -
heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater
back-up heating capacityOff mode POFF 0.008 kW
Thermostat-off mode PTO 0.100 kW Type of energy inputCrankcase heater mode PCK 0.008 kW Standby mode
Other items
For air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :
outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchanger
Emissions of nitrogen mg/kWh
oxides(if applicable) fuel input
GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
295.0 %
No
Prated,h 15.5 kW 157.4 %
596.0 %
270.0 %
385.0 %
500.0 %
- ℃
0.25
220.0 %
- %
PSB 0.008 kW
elbu - kW
4,380 m3/h
LWA 73.0 dB- m3/h
Contact details
NOx*** -
675kgCO2eq.
PJG000Z625 A
- 140 -
'19 • PAC-DB-308D
Models FDU100VH, 125VH, 140VH
Model(s) :
Item Symbol Vaiue Unit Item Symbol Vaiue Unit
Cooling capacity (sensible) Prated,c 7.7 kW Total electric power input Pelec 0.350 kW
Cooling capacity (latent) Prated,c 2.3 kW LWA 65.0 dB
Heating capacity Prated,h 11.2 kW
Mitsubishi heavy industries thermal systems,LTD
Model(s) :
Item Symbol Vaiue Unit Item Symbol Vaiue Unit
Cooling capacity (sensible) Prated,c 10.5 kW Total electric power input Pelec 0.400 kW
Cooling capacity (latent) Prated,c 2.0 kW LWA 67.0 dB
Heating capacity Prated,h 14.0 kW
Mitsubishi heavy industries thermal systems,LTD
Model(s) :
Item Symbol Vaiue Unit Item Symbol Vaiue Unit
Cooling capacity (sensible) Prated,c 11.2 kW Total electric power input Pelec 0.550 kW
Cooling capacity (latent) Prated,c 2.8 kW LWA 70.0 dB
Heating capacity Prated,h 16.0 kW
Mitsubishi heavy industries thermal systems,LTD
FDU140VH
Sound power level(per speed setting,if applicable)
Contact details
FDU100VH
Sound power level(per speed setting,if applicable)
Contact details
FDU125VH
Sound power level(per speed setting,if applicable)
Contact details
PJG000Z625 A
- 141 -
'19 • PAC-DB-308D
PJG000Z491 B
(4) Duct connected-Low/Middle static pressure type (FDUM)
FDUM100VNAWVH
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season theIndoor unit model name FDUM100VH information relates to. Indicated values should relate to oneOutdoor unit model name FDC100VNA-W heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory) Yescooling Yes Warmer(if designated) Noheating Yes Colder(if designated) No
Item symbol value unit Item symbol value classDesign load Seasonal efficiency and energy efficiency classcooling Pdesignc 10.0 kW cooling SEER 6.11 A++heating / Average Pdesignh 8.5 kW heating / Average SCOP/A 4.19 A+heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - -heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unitDeclared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignhheating / Average (-10℃) Pdh 8.5 kW heating / Average (-10℃) elbu 0 kWheating / Warmer (2℃) Pdh - kW heating / Warmer (2℃) elbu - kWheating / Colder (-22℃) Pdh - kW heating / Colder (-22℃) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19)℃ and Declared energy efficiency ratio, at indoor temperature 27(19)℃ andoutdoor temperature Tj outdoor temperature TjTj=35℃ Pdc 10.00 kW Tj=35℃ EERd 3.35 -Tj=30℃ Pdc 7.37 kW Tj=30℃ EERd 5.00 -Tj=25℃ Pdc 4.74 kW Tj=25℃ EERd 8.05 -Tj=20℃ Pdc 3.10 kW Tj=20℃ EERd 9.50 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh 7.40 kW Tj=-7℃ COPd 3.14 -Tj=2℃ Pdh 4.50 kW Tj=2℃ COPd 4.02 -Tj=7℃ Pdh 2.90 kW Tj=7℃ COPd 5.24 -Tj=12℃ Pdh 2.90 kW Tj=12℃ COPd 6.27 -Tj=bivalent temperature Pdh 8.50 kW Tj=bivalent temperature COPd 2.50 -Tj=operating limit Pdh 6.30 kW Tj=operating limit COPd 2.10 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh - kW Tj=-7℃ COPd - -Tj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -Tj=-15℃ Pdh - kW Tj=-15℃ COPd - -
Bivalent temperature Operating limit temperatureheating / Average Tbiv -10 ℃ heating / Average Tol -20 ℃heating / Warmer Tbiv - ℃ heating / Warmer Tol -20 ℃heating / Colder Tbiv - ℃ heating / Colder Tol -20 ℃
Cycling interval capacity Cycling interval efficiencyfor cooling Pcycc - kW for cooling EERcyc - -for heating Pcych - kW for heating COPcyc - -
Degradation coefficient Degradation coefficientcooling Cdc 0.25 - heating Cdh 0.25 -
Electric power input in power modes other than 'active mode' Annual electricity consumptionoff mode Poff 8 W cooling Qce 574 kWh/astandby mode Psb 8 W heating / Average Qhe 2843 kWh/athermostat-off mode Pto(cooling) 65 W heating / Warmer Qhe - kWh/a
Pto(heating) 75 W heating / colder Qhe - kWh/acrankcase heater mode Pck 5 W
Capacity control(indicate one of three options) Other itemsSound power level(indoor) Lwa 65 dB(A)Sound power level(outdoor) Lwa 69 dB(A)
fixed No Global warming potential GWP 675 kgCO2eq.staged No Rated air flow(indoor) - 2160 m3/hvariable Yes Rated air flow(outdoor) - 4500 m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative.more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd.
5 The Square, Stockley Park, Uxbridge, Middlesex, UB11 1ET,United Kingdom
- 142 -
'19 • PAC-DB-308D
PJG000Z491 B
FDUM100VSAWVH
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season theIndoor unit model name FDUM100VH information relates to. Indicated values should relate to oneOutdoor unit model name FDC100VSA-W heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory) Yescooling Yes Warmer(if designated) Noheating Yes Colder(if designated) No
Item symbol value unit Item symbol value classDesign load Seasonal efficiency and energy efficiency classcooling Pdesignc 10.0 kW cooling SEER 6.11 A++heating / Average Pdesignh 8.5 kW heating / Average SCOP/A 4.19 A+heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - -heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unitDeclared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignhheating / Average (-10℃) Pdh 8.5 kW heating / Average (-10℃) elbu 0 kWheating / Warmer (2℃) Pdh - kW heating / Warmer (2℃) elbu - kWheating / Colder (-22℃) Pdh - kW heating / Colder (-22℃) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19)℃ and Declared energy efficiency ratio, at indoor temperature 27(19)℃ andoutdoor temperature Tj outdoor temperature TjTj=35℃ Pdc 10.00 kW Tj=35℃ EERd 3.35 -Tj=30℃ Pdc 7.37 kW Tj=30℃ EERd 5.00 -Tj=25℃ Pdc 4.74 kW Tj=25℃ EERd 8.05 -Tj=20℃ Pdc 3.10 kW Tj=20℃ EERd 9.50 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh 7.40 kW Tj=-7℃ COPd 3.14 -Tj=2℃ Pdh 4.50 kW Tj=2℃ COPd 4.02 -Tj=7℃ Pdh 2.90 kW Tj=7℃ COPd 5.24 -Tj=12℃ Pdh 2.90 kW Tj=12℃ COPd 6.27 -Tj=bivalent temperature Pdh 8.50 kW Tj=bivalent temperature COPd 2.50 -Tj=operating limit Pdh 6.30 kW Tj=operating limit COPd 2.10 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh - kW Tj=-7℃ COPd - -Tj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -Tj=-15℃ Pdh - kW Tj=-15℃ COPd - -
Bivalent temperature Operating limit temperatureheating / Average Tbiv -10 ℃ heating / Average Tol -20 ℃heating / Warmer Tbiv - ℃ heating / Warmer Tol -20 ℃heating / Colder Tbiv - ℃ heating / Colder Tol -20 ℃
Cycling interval capacity Cycling interval efficiencyfor cooling Pcycc - kW for cooling EERcyc - -for heating Pcych - kW for heating COPcyc - -
Degradation coefficient Degradation coefficientcooling Cdc 0.25 - heating Cdh 0.25 -
Electric power input in power modes other than 'active mode' Annual electricity consumptionoff mode Poff 8 W cooling Qce 574 kWh/astandby mode Psb 8 W heating / Average Qhe 2843 kWh/athermostat-off mode Pto(cooling) 65 W heating / Warmer Qhe - kWh/a
Pto(heating) 75 W heating / colder Qhe - kWh/acrankcase heater mode Pck 5 W
Capacity control(indicate one of three options) Other itemsSound power level(indoor) Lwa 65 dB(A)Sound power level(outdoor) Lwa 69 dB(A)
fixed No Global warming potential GWP 675 kgCO2eq.staged No Rated air flow(indoor) - 2160 m3/hvariable Yes Rated air flow(outdoor) - 4500 m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative.more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd.
5 The Square, Stockley Park, Uxbridge, Middlesex, UB11 1ET,United Kingdom
- 143 -
'19 • PAC-DB-308D
FDUM100VNAWPVH
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season theIndoor unit model name FDUM50VH x2 information relates to. Indicated values should relate to oneOutdoor unit model name FDC100VNA-W heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory) Yescooling Yes Warmer(if designated) Noheating Yes Colder(if designated) No
Item symbol value unit Item symbol value classDesign load Seasonal efficiency and energy efficiency classcooling Pdesignc 10.0 kW cooling SEER 5.82 A+heating / Average Pdesignh 8.5 kW heating / Average SCOP/A 4.00 A+heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - -heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unitDeclared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignhheating / Average (-10℃) Pdh 8.5 kW heating / Average (-10℃) elbu 0 kWheating / Warmer (2℃) Pdh - kW heating / Warmer (2℃) elbu - kWheating / Colder (-22℃) Pdh - kW heating / Colder (-22℃) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19)℃ and Declared energy efficiency ratio, at indoor temperature 27(19)℃ andoutdoor temperature Tj outdoor temperature TjTj=35℃ Pdc 10.00 kW Tj=35℃ EERd 3.08 -Tj=30℃ Pdc 7.37 kW Tj=30℃ EERd 5.00 -Tj=25℃ Pdc 4.74 kW Tj=25℃ EERd 7.50 -Tj=20℃ Pdc 3.45 kW Tj=20℃ EERd 11.30 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh 7.40 kW Tj=-7℃ COPd 2.84 -Tj=2℃ Pdh 4.50 kW Tj=2℃ COPd 4.03 -Tj=7℃ Pdh 2.90 kW Tj=7℃ COPd 4.85 -Tj=12℃ Pdh 2.93 kW Tj=12℃ COPd 5.79 -Tj=bivalent temperature Pdh 8.50 kW Tj=bivalent temperature COPd 2.40 -Tj=operating limit Pdh 6.30 kW Tj=operating limit COPd 2.00 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh - kW Tj=-7℃ COPd - -Tj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -Tj=-15℃ Pdh - kW Tj=-15℃ COPd - -
Bivalent temperature Operating limit temperatureheating / Average Tbiv -10 ℃ heating / Average Tol -20 ℃heating / Warmer Tbiv - ℃ heating / Warmer Tol - ℃heating / Colder Tbiv - ℃ heating / Colder Tol - ℃
Cycling interval capacity Cycling interval efficiencyfor cooling Pcycc - kW for cooling EERcyc - -for heating Pcych - kW for heating COPcyc - -
Degradation coefficient Degradation coefficientcooling Cdc 0.25 - heating Cdh 0.25 -
Electric power input in power modes other than 'active mode' Annual electricity consumptionoff mode Poff 15 W cooling Qce 602 kWh/astandby mode Psb 15 W heating / Average Qhe 2974 kWh/athermostat-off mode Pto(cooling) 110 W heating / Warmer Qhe - kWh/a
Pto(heating) 130 W heating / colder Qhe - kWh/acrankcase heater mode Pck 5 W
Capacity control(indicate one of three options) Other itemsSound power level(indoor) Lwa 60 dB(A)Sound power level(outdoor) Lwa 69 dB(A)
fixed No Global warming potential GWP 675 kgCO2eq.staged No Rated air flow(indoor) - 780 m3/hvariable Yes Rated air flow(outdoor) - 4500 m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative.more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd.
5 The Square, Stockley Park, Uxbridge, Middlesex, UB11 1ET,United Kingdom
PJG000Z491 B
- 144 -
'19 • PAC-DB-308D
PJG000Z491 B
FDUM100VSAWPVH
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season theIndoor unit model name FDUM50VH x2 information relates to. Indicated values should relate to oneOutdoor unit model name FDC100VSA-W heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory) Yescooling Yes Warmer(if designated) Noheating Yes Colder(if designated) No
Item symbol value unit Item symbol value classDesign load Seasonal efficiency and energy efficiency classcooling Pdesignc 10.0 kW cooling SEER 5.82 A+heating / Average Pdesignh 8.5 kW heating / Average SCOP/A 4.00 A+heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - -heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unitDeclared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignhheating / Average (-10℃) Pdh 8.5 kW heating / Average (-10℃) elbu 0 kWheating / Warmer (2℃) Pdh - kW heating / Warmer (2℃) elbu - kWheating / Colder (-22℃) Pdh - kW heating / Colder (-22℃) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19)℃ and Declared energy efficiency ratio, at indoor temperature 27(19)℃ andoutdoor temperature Tj outdoor temperature TjTj=35℃ Pdc 10.00 kW Tj=35℃ EERd 3.08 -Tj=30℃ Pdc 7.37 kW Tj=30℃ EERd 5.00 -Tj=25℃ Pdc 4.74 kW Tj=25℃ EERd 7.50 -Tj=20℃ Pdc 3.45 kW Tj=20℃ EERd 11.30 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh 7.40 kW Tj=-7℃ COPd 2.84 -Tj=2℃ Pdh 4.50 kW Tj=2℃ COPd 4.03 -Tj=7℃ Pdh 2.90 kW Tj=7℃ COPd 4.85 -Tj=12℃ Pdh 2.93 kW Tj=12℃ COPd 5.79 -Tj=bivalent temperature Pdh 8.50 kW Tj=bivalent temperature COPd 2.40 -Tj=operating limit Pdh 6.30 kW Tj=operating limit COPd 2.00 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh - kW Tj=-7℃ COPd - -Tj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -Tj=-15℃ Pdh - kW Tj=-15℃ COPd - -
Bivalent temperature Operating limit temperatureheating / Average Tbiv -10 ℃ heating / Average Tol -20 ℃heating / Warmer Tbiv - ℃ heating / Warmer Tol - ℃heating / Colder Tbiv - ℃ heating / Colder Tol - ℃
Cycling interval capacity Cycling interval efficiencyfor cooling Pcycc - kW for cooling EERcyc - -for heating Pcych - kW for heating COPcyc - -
Degradation coefficient Degradation coefficientcooling Cdc 0.25 - heating Cdh 0.25 -
Electric power input in power modes other than 'active mode' Annual electricity consumptionoff mode Poff 15 W cooling Qce 602 kWh/astandby mode Psb 15 W heating / Average Qhe 2974 kWh/athermostat-off mode Pto(cooling) 110 W heating / Warmer Qhe - kWh/a
Pto(heating) 130 W heating / colder Qhe - kWh/acrankcase heater mode Pck 5 W
Capacity control(indicate one of three options) Other itemsSound power level(indoor) Lwa 60 dB(A)Sound power level(outdoor) Lwa 69 dB(A)
fixed No Global warming potential GWP 675 kgCO2eq.staged No Rated air flow(indoor) - 780 m3/hvariable Yes Rated air flow(outdoor) - 4500 m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative.more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd.
5 The Square, Stockley Park, Uxbridge, Middlesex, UB11 1ET,United Kingdom
- 145 -
'19 • PAC-DB-308D
FDUM125VNAWVH
Model(s) : FDC125VNA-W / FDUM125VH
Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 12.5 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 9.2 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 5.9 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.1 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.008 kW
Thermostat-off mode PTO 0.075 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Contact details
NOx*** -
675
LWA 71.0 dB
0.25
4,500 m3/h
920.0 %
705.0 %
425.0 %
287.0 %
Prated,c 12.5 kW 219.8 %
kgCO2eq.
PJG000Z491 B
- 146 -
'19 • PAC-DB-308D
PJG000Z491 B
Information to identify the model(s) to which the information relates : FDC125VNA-W / FDUM125VH
Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value UnitRated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 8.7 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,binTj=+2℃ Pdh 5.3 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,binTj=+7℃ Pdh 3.4 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,binTj=+12℃ Pdh 2.7 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,binTbiv=bivalent temperature Pdh 9.8 kW Tbiv=bivalent COPd or
temperature GUEh,bin / AEFh,binTOL=operation limit Pdh 7.4 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd orTj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heatpumps:Operation limit
Degradation Tol temperature
coefficient Cdh -heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater back-up heating capacity
Off mode POFF 0.008 kWThermostat-off mode PTO 0.090 kW Type of energy inputCrankcase heater mode PCK 0.008 kW Standby mode
Other itemsFor air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchangerEmissions of nitrogen mg/kWhoxides(if applicable) fuel input
GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
300.0 %
No
Prated,h 14.0 kW 162.1 %
615.0 %
270.0 %
399.0 %
515.0 %
- ℃
0.25
210.0 %
- %
PSB 0.008 kW
elbu - kW
4,380 m3/h
LWA 71.0 dB- m3/h
Contact details
NOx*** -
675kgCO2eq.
- 147 -
'19 • PAC-DB-308D
PJG000Z491 B
Model(s) : FDC125VSA-W / FDUM125VH
Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 12.5 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 9.2 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 5.9 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.1 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.008 kW
Thermostat-off mode PTO 0.075 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Contact details
NOx*** -
675
LWA 71.0 dB
0.25
4,500 m3/h
920.0 %
705.0 %
425.0 %
287.0 %
Prated,c 12.5 kW 219.8 %
kgCO2eq.
FDUM125VSAWVH
- 148 -
'19 • PAC-DB-308D
PJG000Z491 B
Information to identify the model(s) to which the information relates : FDC125VSA-W / FDUM125VH
Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value UnitRated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 8.7 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,binTj=+2℃ Pdh 5.3 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,binTj=+7℃ Pdh 3.4 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,binTj=+12℃ Pdh 2.7 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,binTbiv=bivalent temperature Pdh 9.8 kW Tbiv=bivalent COPd or
temperature GUEh,bin / AEFh,binTOL=operation limit Pdh 7.4 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd orTj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heatpumps:Operation limit
Degradation Tol temperature
coefficient Cdh -heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater back-up heating capacity
Off mode POFF 0.008 kWThermostat-off mode PTO 0.090 kW Type of energy inputCrankcase heater mode PCK 0.008 kW Standby mode
Other itemsFor air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchangerEmissions of nitrogen mg/kWhoxides(if applicable) fuel input
GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
300.0 %
No
Prated,h 14.0 kW 162.1 %
615.0 %
270.0 %
399.0 %
515.0 %
- ℃
0.25
210.0 %
- %
PSB 0.008 kW
elbu - kW
4,380 m3/h
LWA 71.0 dB- m3/h
Contact details
NOx*** -
675kgCO2eq.
- 149 -
'19 • PAC-DB-308D
PJG000Z491 B
Model(s) : FDC140VNA-W / FDUM140VH
Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 13.6 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 10.0 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 6.4 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.2 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.008 kW
Thermostat-off mode PTO 0.090 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Contact details
NOx*** -
675
LWA 72.0 dB
0.25
4,500 m3/h
900.0 %
680.0 %
390.0 %
265.0 %
Prated,c 13.6 kW 208.8 %
kgCO2eq.
FDUM140VNAWVH
- 150 -
'19 • PAC-DB-308D
PJG000Z491 B
Information to identify the model(s) to which the information relates : FDC140VNA-W / FDUM140VH
Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value UnitRated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 9.3 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,binTj=+2℃ Pdh 5.6 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,binTj=+7℃ Pdh 3.6 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,binTj=+12℃ Pdh 2.7 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,binTbiv=bivalent temperature Pdh 10.5 kW Tbiv=bivalent COPd or
temperature GUEh,bin / AEFh,binTOL=operation limit Pdh 7.9 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd orTj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heatpumps:Operation limit
Degradation Tol temperature
coefficient Cdh -heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater back-up heating capacity
Off mode POFF 0.008 kWThermostat-off mode PTO 0.100 kW Type of energy inputCrankcase heater mode PCK 0.008 kW Standby mode
Other itemsFor air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchangerEmissions of nitrogen mg/kWhoxides(if applicable) fuel input
GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
295.0 %
No
Prated,h 15.5 kW 157.4 %
596.0 %
270.0 %
385.0 %
500.0 %
- ℃
0.25
220.0 %
- %
PSB 0.008 kW
elbu - kW
4,380 m3/h
LWA 73.0 dB- m3/h
Contact details
NOx*** -
675kgCO2eq.
- 151 -
'19 • PAC-DB-308D
PJG000Z491 B
Model(s) : FDC140VSA-W / FDUM140VH
Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 13.6 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 10.0 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 6.4 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.2 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.008 kW
Thermostat-off mode PTO 0.090 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Contact details
NOx*** -
675
LWA 72.0 dB
0.25
4,500 m3/h
900.0 %
680.0 %
390.0 %
265.0 %
Prated,c 13.6 kW 208.8 %
kgCO2eq.
FDUM140VSAWVH
- 152 -
'19 • PAC-DB-308D
PJG000Z491 B
Information to identify the model(s) to which the information relates : FDC140VSA-W / FDUM140VH
Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value UnitRated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 9.3 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,binTj=+2℃ Pdh 5.6 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,binTj=+7℃ Pdh 3.6 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,binTj=+12℃ Pdh 2.7 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,binTbiv=bivalent temperature Pdh 10.5 kW Tbiv=bivalent COPd or
temperature GUEh,bin / AEFh,binTOL=operation limit Pdh 7.9 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd orTj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heatpumps:Operation limit
Degradation Tol temperature
coefficient Cdh -heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater back-up heating capacity
Off mode POFF 0.008 kWThermostat-off mode PTO 0.100 kW Type of energy inputCrankcase heater mode PCK 0.008 kW Standby mode
Other itemsFor air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchangerEmissions of nitrogen mg/kWhoxides(if applicable) fuel input
GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
295.0 %
No
Prated,h 15.5 kW 157.4 %
596.0 %
270.0 %
385.0 %
500.0 %
- ℃
0.25
220.0 %
- %
PSB 0.008 kW
elbu - kW
4,380 m3/h
LWA 73.0 dB- m3/h
Contact details
NOx*** -
675kgCO2eq.
- 153 -
'19 • PAC-DB-308D
PJG000Z491 B
Model(s) : FDC125VNA-W / FDUM60VH (2 units)
Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 12.5 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 9.2 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 5.9 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.6 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.000 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Contact details
NOx*** -
675
LWA 71.0 dB
0.25
4,500 m3/h
1730.0 %
810.0 %
480.0 %
276.0 %
Prated,c 12.5 kW 277.3 %
kgCO2eq.
FDUM125VNAWPVH
- 154 -
'19 • PAC-DB-308D
PJG000Z491 B
Information to identify the model(s) to which the information relates : FDC125VNA-W / FDUM60VH (2 units)
Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value UnitRated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 8.7 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,binTj=+2℃ Pdh 5.3 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,binTj=+7℃ Pdh 3.4 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,binTj=+12℃ Pdh 3.0 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,binTbiv=bivalent temperature Pdh 9.8 kW Tbiv=bivalent COPd or
temperature GUEh,bin / AEFh,binTOL=operation limit Pdh 7.4 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd orTj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heatpumps:Operation limit
Degradation Tol temperature
coefficient Cdh -heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater back-up heating capacity
Off mode POFF 0.008 kWThermostat-off mode PTO 0.000 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other itemsFor air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchangerEmissions of nitrogen mg/kWhoxides(if applicable) fuel input
GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
310.0 %
No
Prated,h 14.0 kW 188.3 %
855.0 %
250.0 %
470.0 %
596.0 %
- ℃
0.25
210.0 %
- %
PSB 0.008 kW
elbu - kW
4,380 m3/h
LWA 71.0 dB- m3/h
Contact details
NOx*** -
675kgCO2eq.
- 155 -
'19 • PAC-DB-308D
PJG000Z491 B
Model(s) : FDC125VSA-W / FDUM60VH (2 units)
Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 12.5 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 9.2 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 5.9 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.6 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.000 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Contact details
NOx*** -
675
LWA 71.0 dB
0.25
4,500 m3/h
1730.0 %
810.0 %
480.0 %
276.0 %
Prated,c 12.5 kW 277.3 %
kgCO2eq.
FDUM125VSAWPVH
- 156 -
'19 • PAC-DB-308D
PJG000Z491 B
Information to identify the model(s) to which the information relates : FDC125VSA-W / FDUM60VH (2 units)
Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value UnitRated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 8.7 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,binTj=+2℃ Pdh 5.3 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,binTj=+7℃ Pdh 3.4 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,binTj=+12℃ Pdh 3.0 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,binTbiv=bivalent temperature Pdh 9.8 kW Tbiv=bivalent COPd or
temperature GUEh,bin / AEFh,binTOL=operation limit Pdh 7.4 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd orTj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heatpumps:Operation limit
Degradation Tol temperature
coefficient Cdh -heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater back-up heating capacity
Off mode POFF 0.008 kWThermostat-off mode PTO 0.000 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other itemsFor air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchangerEmissions of nitrogen mg/kWhoxides(if applicable) fuel input
GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
310.0 %
No
Prated,h 14.0 kW 188.3 %
855.0 %
250.0 %
470.0 %
596.0 %
- ℃
0.25
210.0 %
- %
PSB 0.008 kW
elbu - kW
4,380 m3/h
LWA 71.0 dB- m3/h
Contact details
NOx*** -
675kgCO2eq.
- 157 -
'19 • PAC-DB-308D
PJG000Z491 B
Model(s) : FDC140VNA-W / FDUM71VH (2 units)
Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 13.6 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 10.0 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 6.4 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.3 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.000 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Contact details
NOx*** -
675
LWA 72.0 dB
0.25
4,500 m3/h
1680.0 %
850.0 %
500.0 %
285.0 %
Prated,c 13.6 kW 288.0 %
kgCO2eq.
FDUM140VNAWPVH
- 158 -
'19 • PAC-DB-308D
PJG000Z491 B
Information to identify the model(s) to which the information relates : FDC140VNA-W / FDUM71VH (2 units)
Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value UnitRated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 9.3 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,binTj=+2℃ Pdh 5.6 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,binTj=+7℃ Pdh 3.6 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,binTj=+12℃ Pdh 3.1 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,binTbiv=bivalent temperature Pdh 10.5 kW Tbiv=bivalent COPd or
temperature GUEh,bin / AEFh,binTOL=operation limit Pdh 7.9 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd orTj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heatpumps:Operation limit
Degradation Tol temperature
coefficient Cdh -heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater back-up heating capacity
Off mode POFF 0.008 kWThermostat-off mode PTO 0.000 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other itemsFor air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchangerEmissions of nitrogen mg/kWhoxides(if applicable) fuel input
GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
335.0 %
No
Prated,h 15.5 kW 205.7 %
933.0 %
250.0 %
506.0 %
678.0 %
- ℃
0.25
200.0 %
- %
PSB 0.008 kW
elbu - kW
4,380 m3/h
LWA 73.0 dB- m3/h
Contact details
NOx*** -
675kgCO2eq.
- 159 -
'19 • PAC-DB-308D
PJG000Z491 B
Model(s) : FDC140VSA-W / FDUM71VH (2 units)
Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 13.6 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 10.0 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 6.4 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.3 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.000 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Contact details
NOx*** -
675
LWA 72.0 dB
0.25
4,500 m3/h
1680.0 %
850.0 %
500.0 %
285.0 %
Prated,c 13.6 kW 288.0 %
kgCO2eq.
FDUM140VSAWPVH
- 160 -
'19 • PAC-DB-308D
PJG000Z491 B
Information to identify the model(s) to which the information relates : FDC140VSA-W / FDUM71VH (2 units)
Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value UnitRated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 9.3 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,binTj=+2℃ Pdh 5.6 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,binTj=+7℃ Pdh 3.6 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,binTj=+12℃ Pdh 3.1 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,binTbiv=bivalent temperature Pdh 10.5 kW Tbiv=bivalent COPd or
temperature GUEh,bin / AEFh,binTOL=operation limit Pdh 7.9 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd orTj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heatpumps:Operation limit
Degradation Tol temperature
coefficient Cdh -heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater back-up heating capacity
Off mode POFF 0.008 kWThermostat-off mode PTO 0.000 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other itemsFor air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchangerEmissions of nitrogen mg/kWhoxides(if applicable) fuel input
GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
335.0 %
No
Prated,h 15.5 kW 205.7 %
933.0 %
250.0 %
506.0 %
678.0 %
- ℃
0.25
200.0 %
- %
PSB 0.008 kW
elbu - kW
4,380 m3/h
LWA 73.0 dB- m3/h
Contact details
NOx*** -
675kgCO2eq.
- 161 -
'19 • PAC-DB-308D
PJG000Z491 B
Model(s) : FDC140VNA-W / FDUM50VH (3 units)
Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 13.6 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 10.0 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 6.4 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.3 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.000 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Contact details
NOx*** -
675
LWA 72.0 dB
0.25
4,500 m3/h
1680.0 %
850.0 %
500.0 %
285.0 %
Prated,c 13.6 kW 288.0 %
kgCO2eq.
FDUM140VNAWTVH
- 162 -
'19 • PAC-DB-308D
PJG000Z491 B
Information to identify the model(s) to which the information relates : FDC140VNA-W / FDUM50VH (3 units)
Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value UnitRated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 9.3 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,binTj=+2℃ Pdh 5.6 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,binTj=+7℃ Pdh 3.6 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,binTj=+12℃ Pdh 3.1 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,binTbiv=bivalent temperature Pdh 10.5 kW Tbiv=bivalent COPd or
temperature GUEh,bin / AEFh,binTOL=operation limit Pdh 7.9 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd orTj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heatpumps:Operation limit
Degradation Tol temperature
coefficient Cdh -heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater back-up heating capacity
Off mode POFF 0.008 kWThermostat-off mode PTO 0.000 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other itemsFor air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchangerEmissions of nitrogen mg/kWhoxides(if applicable) fuel input
GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
335.0 %
No
Prated,h 15.5 kW 205.7 %
933.0 %
250.0 %
506.0 %
678.0 %
- ℃
0.25
200.0 %
- %
PSB 0.008 kW
elbu - kW
4,380 m3/h
LWA 73.0 dB- m3/h
Contact details
NOx*** -
675kgCO2eq.
- 163 -
'19 • PAC-DB-308D
PJG000Z491 B
Model(s) : FDC140VSA-W / FDUM50VH (3 units)
Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 13.6 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 10.0 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 6.4 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.3 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.000 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Contact details
NOx*** -
675
LWA 72.0 dB
0.25
4,500 m3/h
1680.0 %
850.0 %
500.0 %
285.0 %
Prated,c 13.6 kW 288.0 %
kgCO2eq.
FDUM140VSAWTVH
- 164 -
'19 • PAC-DB-308D
PJG000Z491 B
Information to identify the model(s) to which the information relates : FDC140VSA-W / FDUM50VH (3 units)
Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value UnitRated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 9.3 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,binTj=+2℃ Pdh 5.6 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,binTj=+7℃ Pdh 3.6 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,binTj=+12℃ Pdh 3.1 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,binTbiv=bivalent temperature Pdh 10.5 kW Tbiv=bivalent COPd or
temperature GUEh,bin / AEFh,binTOL=operation limit Pdh 7.9 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd orTj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heatpumps:Operation limit
Degradation Tol temperature
coefficient Cdh -heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater back-up heating capacity
Off mode POFF 0.008 kWThermostat-off mode PTO 0.000 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other itemsFor air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchangerEmissions of nitrogen mg/kWhoxides(if applicable) fuel input
GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
335.0 %
No
Prated,h 15.5 kW 205.7 %
933.0 %
250.0 %
506.0 %
678.0 %
- ℃
0.25
200.0 %
- %
PSB 0.008 kW
elbu - kW
4,380 m3/h
LWA 73.0 dB- m3/h
Contact details
NOx*** -
675kgCO2eq.
- 165 -
'19 • PAC-DB-308D
PJG000Z491 B
Model(s) :
Item Symbol Vaiue Unit Item Symbol Vaiue Unit
Cooling capacity (sensible) Prated,c 3.7 kW Total electric power input Pelec 0.100 kW
Cooling capacity (latent) Prated,c 1.3 kW LWA 60.0 dB
Heating capacity Prated,h 5.4 kW
Mitsubishi heavy industries thermal systems,LTD
Model(s) :
Item Symbol Vaiue Unit Item Symbol Vaiue Unit
Cooling capacity (sensible) Prated,c 3.9 kW Total electric power input Pelec 0.160 kW
Cooling capacity (latent) Prated,c 1.7 kW LWA 60.0 dB
Heating capacity Prated,h 6.7 kW
Mitsubishi heavy industries thermal systems,LTD
Model(s) :
Item Symbol Vaiue Unit Item Symbol Vaiue Unit
Cooling capacity (sensible) Prated,c 5.8 kW Total electric power input Pelec 0.200 kW
Cooling capacity (latent) Prated,c 1.3 kW LWA 65.0 dB
Heating capacity Prated,h 8.0 kW
Mitsubishi heavy industries thermal systems,LTD
Model(s) :
Item Symbol Vaiue Unit Item Symbol Vaiue Unit
Cooling capacity (sensible) Prated,c 7.7 kW Total electric power input Pelec 0.290 kW
Cooling capacity (latent) Prated,c 2.3 kW LWA 65.0 dB
Heating capacity Prated,h 11.2 kW
Mitsubishi heavy industries thermal systems,LTD
Model(s) :
Item Symbol Vaiue Unit Item Symbol Vaiue Unit
Cooling capacity (sensible) Prated,c 10.5 kW Total electric power input Pelec 0.330 kW
Cooling capacity (latent) Prated,c 2.0 kW LWA 67.0 dB
Heating capacity Prated,h 14.0 kW
Mitsubishi heavy industries thermal systems,LTD
Model(s) :
Item Symbol Vaiue Unit Item Symbol Vaiue Unit
Cooling capacity (sensible) Prated,c 11.2 kW Total electric power input Pelec 0.450 kW
Cooling capacity (latent) Prated,c 2.8 kW LWA 70.0 dB
Heating capacity Prated,h 16.0 kW
Mitsubishi heavy industries thermal systems,LTD
FDUM50VH
Sound power level(per speed setting,if applicable)
Contact details
FDUM60VH
Sound power level(per speed setting,if applicable)
Contact details
FDUM71VH
Sound power level(per speed setting,if applicable)
Contact details
FDUM100VH
Sound power level(per speed setting,if applicable)
Contact details
FDUM125VH
Sound power level(per speed setting,if applicable)
Contact details
FDUM140VH
Sound power level(per speed setting,if applicable)
Contact details
Models FDUM50VH, 60VH, 71VH, 100VH, 125VH, 140VH
- 166 -
'19 • PAC-DB-308D
PFA004Z088 B
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season theIndoor unit model name FDE100VH information relates to. Indicated values should relate to oneOutdoor unit model name FDC100VNA-W heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory) Yescooling Yes Warmer(if designated) Noheating Yes Colder(if designated) No
Item symbol value unit Item symbol value classDesign load Seasonal efficiency and energy efficiency classcooling Pdesignc 10.0 kW cooling SEER 6.67 A++heating / Average Pdesignh 8.5 kW heating / Average SCOP/A 4.31 A+heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - -heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unitDeclared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignhheating / Average (-10℃) Pdh 8.5 kW heating / Average (-10℃) elbu 0 kWheating / Warmer (2℃) Pdh - kW heating / Warmer (2℃) elbu - kWheating / Colder (-22℃) Pdh - kW heating / Colder (-22℃) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19)℃ and Declared energy efficiency ratio, at indoor temperature 27(19)℃ andoutdoor temperature Tj outdoor temperature TjTj=35℃ Pdc 10.00 kW Tj=35℃ EERd 3.51 -Tj=30℃ Pdc 7.37 kW Tj=30℃ EERd 5.29 -Tj=25℃ Pdc 4.74 kW Tj=25℃ EERd 8.79 -Tj=20℃ Pdc 3.10 kW Tj=20℃ EERd 10.60 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh 7.40 kW Tj=-7℃ COPd 3.10 -Tj=2℃ Pdh 4.50 kW Tj=2℃ COPd 4.16 -Tj=7℃ Pdh 2.90 kW Tj=7℃ COPd 5.35 -Tj=12℃ Pdh 2.90 kW Tj=12℃ COPd 6.70 -Tj=bivalent temperature Pdh 8.50 kW Tj=bivalent temperature COPd 2.80 -Tj=operating limit Pdh 6.30 kW Tj=operating limit COPd 2.20 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh - kW Tj=-7℃ COPd - -Tj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -Tj=-15℃ Pdh - kW Tj=-15℃ COPd - -
Bivalent temperature Operating limit temperatureheating / Average Tbiv -10 ℃ heating / Average Tol -20 ℃heating / Warmer Tbiv - ℃ heating / Warmer Tol - ℃heating / Colder Tbiv - ℃ heating / Colder Tol - ℃
Cycling interval capacity Cycling interval efficiencyfor cooling Pcycc - kW for cooling EERcyc - -for heating Pcych - kW for heating COPcyc - -
Degradation coefficient Degradation coefficientcooling Cdc 0.25 - heating Cdh 0.25 -
Electric power input in power modes other than 'active mode' Annual electricity consumptionoff mode Poff 8 W cooling Qce 525 kWh/astandby mode Psb 8 W heating / Average Qhe 2764 kWh/athermostat-off mode Pto(cooling) 26 W heating / Warmer Qhe - kWh/a
Pto(heating) 43 W heating / colder Qhe - kWh/acrankcase heater mode Pck 5 W
Capacity control(indicate one of three options) Other itemsSound power level(indoor) Lwa 62 dB(A)Sound power level(outdoor) Lwa 69 dB(A)
fixed No Global warming potential GWP 675 kgCO2eq.staged No Rated air flow(indoor) - 1920 m3/hvariable Yes Rated air flow(outdoor) - 4500 m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative.more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd.
5 The Square, Stockley Park, Uxbridge, Middlesex, UB11 1ET,United Kingdom
(5) Ceiling suspended type (FDE)
FDE100VNAWVH
- 167 -
'19 • PAC-DB-308D
PFA004Z088 B
FDE100VSAWVH
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season theIndoor unit model name FDE100VH information relates to. Indicated values should relate to oneOutdoor unit model name FDC100VSA-W heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory) Yescooling Yes Warmer(if designated) Noheating Yes Colder(if designated) No
Item symbol value unit Item symbol value classDesign load Seasonal efficiency and energy efficiency classcooling Pdesignc 10.0 kW cooling SEER 6.67 A++heating / Average Pdesignh 8.5 kW heating / Average SCOP/A 4.31 A+heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - -heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unitDeclared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignhheating / Average (-10℃) Pdh 8.5 kW heating / Average (-10℃) elbu 0 kWheating / Warmer (2℃) Pdh - kW heating / Warmer (2℃) elbu - kWheating / Colder (-22℃) Pdh - kW heating / Colder (-22℃) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19)℃ and Declared energy efficiency ratio, at indoor temperature 27(19)℃ andoutdoor temperature Tj outdoor temperature TjTj=35℃ Pdc 10.00 kW Tj=35℃ EERd 3.51 -Tj=30℃ Pdc 7.37 kW Tj=30℃ EERd 5.29 -Tj=25℃ Pdc 4.74 kW Tj=25℃ EERd 8.79 -Tj=20℃ Pdc 3.10 kW Tj=20℃ EERd 10.60 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh 7.40 kW Tj=-7℃ COPd 3.10 -Tj=2℃ Pdh 4.50 kW Tj=2℃ COPd 4.16 -Tj=7℃ Pdh 2.90 kW Tj=7℃ COPd 5.35 -Tj=12℃ Pdh 2.90 kW Tj=12℃ COPd 6.70 -Tj=bivalent temperature Pdh 8.50 kW Tj=bivalent temperature COPd 2.80 -Tj=operating limit Pdh 6.30 kW Tj=operating limit COPd 2.20 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh - kW Tj=-7℃ COPd - -Tj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -Tj=-15℃ Pdh - kW Tj=-15℃ COPd - -
Bivalent temperature Operating limit temperatureheating / Average Tbiv -10 ℃ heating / Average Tol -20 ℃heating / Warmer Tbiv - ℃ heating / Warmer Tol - ℃heating / Colder Tbiv - ℃ heating / Colder Tol - ℃
Cycling interval capacity Cycling interval efficiencyfor cooling Pcycc - kW for cooling EERcyc - -for heating Pcych - kW for heating COPcyc - -
Degradation coefficient Degradation coefficientcooling Cdc 0.25 - heating Cdh 0.25 -
Electric power input in power modes other than 'active mode' Annual electricity consumptionoff mode Poff 8 W cooling Qce 525 kWh/astandby mode Psb 8 W heating / Average Qhe 2764 kWh/athermostat-off mode Pto(cooling) 26 W heating / Warmer Qhe - kWh/a
Pto(heating) 43 W heating / colder Qhe - kWh/acrankcase heater mode Pck 5 W
Capacity control(indicate one of three options) Other itemsSound power level(indoor) Lwa 62 dB(A)Sound power level(outdoor) Lwa 69 dB(A)
fixed No Global warming potential GWP 675 kgCO2eq.staged No Rated air flow(indoor) - 1920 m3/hvariable Yes Rated air flow(outdoor) - 4500 m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative.more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd.
5 The Square, Stockley Park, Uxbridge, Middlesex, UB11 1ET,United Kingdom
- 168 -
'19 • PAC-DB-308D
PFA004Z088 B
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season theIndoor unit model name FDE50VHx2 information relates to. Indicated values should relate to oneOutdoor unit model name FDC100VNA-W heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory) Yescooling Yes Warmer(if designated) Noheating Yes Colder(if designated) No
Item symbol value unit Item symbol value classDesign load Seasonal efficiency and energy efficiency classcooling Pdesignc 10.0 kW cooling SEER 6.16 A++heating / Average Pdesignh 8.5 kW heating / Average SCOP/A 4.10 A+heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - -heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unitDeclared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignhheating / Average (-10℃) Pdh 8.5 kW heating / Average (-10℃) elbu 0 kWheating / Warmer (2℃) Pdh - kW heating / Warmer (2℃) elbu - kWheating / Colder (-22℃) Pdh - kW heating / Colder (-22℃) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19)℃ and Declared energy efficiency ratio, at indoor temperature 27(19)℃ andoutdoor temperature Tj outdoor temperature TjTj=35℃ Pdc 10.00 kW Tj=35℃ EERd 3.21 -Tj=30℃ Pdc 7.37 kW Tj=30℃ EERd 5.20 -Tj=25℃ Pdc 4.74 kW Tj=25℃ EERd 7.40 -Tj=20℃ Pdc 3.30 kW Tj=20℃ EERd 12.40 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh 7.40 kW Tj=-7℃ COPd 2.89 -Tj=2℃ Pdh 4.50 kW Tj=2℃ COPd 4.14 -Tj=7℃ Pdh 2.90 kW Tj=7℃ COPd 4.89 -Tj=12℃ Pdh 2.87 kW Tj=12℃ COPd 5.85 -Tj=bivalent temperature Pdh 8.50 kW Tj=bivalent temperature COPd 2.30 -Tj=operating limit Pdh 6.30 kW Tj=operating limit COPd 2.25 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh - kW Tj=-7℃ COPd - -Tj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -Tj=-15℃ Pdh - kW Tj=-15℃ COPd - -
Bivalent temperature Operating limit temperatureheating / Average Tbiv -10 ℃ heating / Average Tol -20 ℃heating / Warmer Tbiv - ℃ heating / Warmer Tol - ℃heating / Colder Tbiv - ℃ heating / Colder Tol - ℃
Cycling interval capacity Cycling interval efficiencyfor cooling Pcycc - kW for cooling EERcyc - -for heating Pcych - kW for heating COPcyc - -
Degradation coefficient Degradation coefficientcooling Cdc 0.25 - heating Cdh 0.25 -
Electric power input in power modes other than 'active mode' Annual electricity consumptionoff mode Poff 15 W cooling Qce 569 kWh/astandby mode Psb 15 W heating / Average Qhe 2906 kWh/athermostat-off mode Pto(cooling) 35 W heating / Warmer Qhe - kWh/a
Pto(heating) 55 W heating / colder Qhe - kWh/acrankcase heater mode Pck 5 W
Capacity control(indicate one of three options) Other itemsSound power level(indoor) Lwa 62 dB(A)Sound power level(outdoor) Lwa 69 dB(A)
fixed No Global warming potential GWP 675 kgCO2eq.staged No Rated air flow(indoor) - 780 m3/hvariable Yes Rated air flow(outdoor) - 4500 m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative.more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd.
5 The Square, Stockley Park, Uxbridge, Middlesex, UB11 1ET,United Kingdom
FDE100VNAWPVH
- 169 -
'19 • PAC-DB-308D
PFA004Z088 B
FDE100VSAWPVH
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season theIndoor unit model name FDE50VHx2 information relates to. Indicated values should relate to oneOutdoor unit model name FDC100VSA-W heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory) Yescooling Yes Warmer(if designated) Noheating Yes Colder(if designated) No
Item symbol value unit Item symbol value classDesign load Seasonal efficiency and energy efficiency classcooling Pdesignc 10.0 kW cooling SEER 6.16 A++heating / Average Pdesignh 8.5 kW heating / Average SCOP/A 4.10 A+heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - -heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unitDeclared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignhheating / Average (-10℃) Pdh 8.5 kW heating / Average (-10℃) elbu 0 kWheating / Warmer (2℃) Pdh - kW heating / Warmer (2℃) elbu - kWheating / Colder (-22℃) Pdh - kW heating / Colder (-22℃) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19)℃ and Declared energy efficiency ratio, at indoor temperature 27(19)℃ andoutdoor temperature Tj outdoor temperature TjTj=35℃ Pdc 10.00 kW Tj=35℃ EERd 3.21 -Tj=30℃ Pdc 7.37 kW Tj=30℃ EERd 5.20 -Tj=25℃ Pdc 4.74 kW Tj=25℃ EERd 7.40 -Tj=20℃ Pdc 3.30 kW Tj=20℃ EERd 12.40 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh 7.40 kW Tj=-7℃ COPd 2.89 -Tj=2℃ Pdh 4.50 kW Tj=2℃ COPd 4.14 -Tj=7℃ Pdh 2.90 kW Tj=7℃ COPd 4.89 -Tj=12℃ Pdh 2.87 kW Tj=12℃ COPd 5.85 -Tj=bivalent temperature Pdh 8.50 kW Tj=bivalent temperature COPd 2.30 -Tj=operating limit Pdh 6.30 kW Tj=operating limit COPd 2.25 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh - kW Tj=-7℃ COPd - -Tj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -Tj=-15℃ Pdh - kW Tj=-15℃ COPd - -
Bivalent temperature Operating limit temperatureheating / Average Tbiv -10 ℃ heating / Average Tol -20 ℃heating / Warmer Tbiv - ℃ heating / Warmer Tol - ℃heating / Colder Tbiv - ℃ heating / Colder Tol - ℃
Cycling interval capacity Cycling interval efficiencyfor cooling Pcycc - kW for cooling EERcyc - -for heating Pcych - kW for heating COPcyc - -
Degradation coefficient Degradation coefficientcooling Cdc 0.25 - heating Cdh 0.25 -
Electric power input in power modes other than 'active mode' Annual electricity consumptionoff mode Poff 15 W cooling Qce 569 kWh/astandby mode Psb 15 W heating / Average Qhe 2906 kWh/athermostat-off mode Pto(cooling) 35 W heating / Warmer Qhe - kWh/a
Pto(heating) 55 W heating / colder Qhe - kWh/acrankcase heater mode Pck 5 W
Capacity control(indicate one of three options) Other itemsSound power level(indoor) Lwa 62 dB(A)Sound power level(outdoor) Lwa 69 dB(A)
fixed No Global warming potential GWP 675 kgCO2eq.staged No Rated air flow(indoor) - 780 m3/hvariable Yes Rated air flow(outdoor) - 4500 m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative.more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd.
5 The Square, Stockley Park, Uxbridge, Middlesex, UB11 1ET,United Kingdom
- 170 -
'19 • PAC-DB-308D
PFA004Z088 B
Model(s) : FDC125VNA-W / FDE125VHOutdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space
cooling energy η s,c
efficiency
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 12.5 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 9.2 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 5.9 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.1 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.030 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Contact details
LWA 71.0 dB
NOx*** -
675
1034.0 %
0.25
4,500 m3/h
281.0 %
Prated,c 12.5 kW 238.1 %
449.0 %
739.0 %
kgCO2eq.
FDE125VNAWVH
- 171 -
'19 • PAC-DB-308D
PFA004Z088 B
Information to identify the model(s) to which the information relates : FDC125VNA-W / FDE125VHOutdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :if applicable : electric motorParameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.Item Symbol Value Unit Item Symbol Value UnitRated heating capacity Seasonal space
heating energy η s,hefficiency
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 8.7 kW Tj=-7℃ COPd orGUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.3 kW Tj=+2℃ COPd orGUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.4 kW Tj=+7℃ COPd orGUEh,bin / AEFh,bin
Tj=+12℃ Pdh 3.0 kW Tj=+12℃ COPd orGUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 9.8 kW Tbiv=bivalent COPd ortemperature GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.4 kW TOL=operation limit COPd orGUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd orTj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heatpumps:Operation limit
Degradation Tol temperaturecoefficient Cdh -heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater back-up heating capacity
Off mode POFF 0.008 kWThermostat-off mode PTO 0.045 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other itemsFor air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchangerEmissions of nitrogen mg/kWhoxides(if applicable) fuel input
GCV
GWP of the refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.*** from 26 September 2018Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performanceof the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
NOx*** -
675
Contact details
4,380 m3/h
LWA 71.0 dB - m3/h
elbu - kW
PSB 0.008 kW
0.25
270.0 %
220.0 %
- %
- ℃
545.0 %
675.0 %
%
300.0 %
415.0 %
169.1
No
Prated,h 14.0 kW
kgCO2eq.
- 172 -
'19 • PAC-DB-308D
PFA004Z088 B
Model(s) : FDC125VSA-W / FDE125VHOutdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space
cooling energy η s,c
efficiency
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 12.5 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 9.2 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 5.9 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.1 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.030 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
281.0 %
Prated,c 12.5 kW 238.1 %
449.0 %
739.0 %
1034.0 %
0.25
4,500 m3/h
Contact details
LWA 71.0 dB
NOx*** -
675kgCO2eq.
FDE125VSAWVH
- 173 -
'19 • PAC-DB-308D
PFA004Z088 B
Information to identify the model(s) to which the information relates : FDC125VSA-W / FDE125VHOutdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :if applicable : electric motorParameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.Item Symbol Value Unit Item Symbol Value UnitRated heating capacity Seasonal space
heating energy η s,hefficiency
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 8.7 kW Tj=-7℃ COPd orGUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.3 kW Tj=+2℃ COPd orGUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.4 kW Tj=+7℃ COPd orGUEh,bin / AEFh,bin
Tj=+12℃ Pdh 3.0 kW Tj=+12℃ COPd orGUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 9.8 kW Tbiv=bivalent COPd ortemperature GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.4 kW TOL=operation limit COPd orGUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd orTj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heatpumps:Operation limit
Degradation Tol temperaturecoefficient Cdh -heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater back-up heating capacity
Off mode POFF 0.008 kWThermostat-off mode PTO 0.045 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other itemsFor air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchangerEmissions of nitrogen mg/kWhoxides(if applicable) fuel input
GCV
GWP of the refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.*** from 26 September 2018Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performanceof the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
NOx*** -
675
Contact details
4,380 m3/h
LWA 71.0 dB - m3/h
elbu - kW
PSB 0.008 kW
0.25
270.0 %
220.0 %
- %
- ℃
545.0 %
675.0 %
%
300.0 %
415.0 %
169.1
No
Prated,h 14.0 kW
kgCO2eq.
- 174 -
'19 • PAC-DB-308D
PFA004Z088 B
Model(s) : FDC140VNA-W / FDE140VHOutdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space
cooling energy η s,c
efficiency
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 13.6 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 10.0 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 6.4 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.1 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.030 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
269.0 %
Prated,c 13.6 kW 227.6 %
420.0 %
682.0 %
1034.0 %
0.25
4,500 m3/h
Contact details
LWA 72.0 dB
NOx*** -
675kgCO2eq.
FDE140VNAWVH
- 175 -
'19 • PAC-DB-308D
PFA004Z088 B
Information to identify the model(s) to which the information relates : FDC140VNA-W / FDE140VHOutdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :if applicable : electric motorParameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.Item Symbol Value Unit Item Symbol Value UnitRated heating capacity Seasonal space
heating energy η s,hefficiency
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 9.2 kW Tj=-7℃ COPd orGUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.6 kW Tj=+2℃ COPd orGUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.6 kW Tj=+7℃ COPd orGUEh,bin / AEFh,bin
Tj=+12℃ Pdh 3.0 kW Tj=+12℃ COPd orGUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 10.5 kW Tbiv=bivalent COPd ortemperature GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.9 kW TOL=operation limit COPd orGUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd orTj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heatpumps:Operation limit
Degradation Tol temperaturecoefficient Cdh -heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater back-up heating capacity
Off mode POFF 0.008 kWThermostat-off mode PTO 0.045 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other itemsFor air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchangerEmissions of nitrogen mg/kWhoxides(if applicable) fuel input
GCV
GWP of the refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.*** from 26 September 2018Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performanceof the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
No
Prated,h 15.5 kW %
290.0 %
410.0 %
166.6
540.0 %
675.0 %
0.25
250.0 %
210.0 %
- %
- ℃
elbu - kW
PSB 0.008 kW
4,380 m3/h
LWA 73.0 dB - m3/h
NOx*** -
675
Contact details
kgCO2eq.
- 176 -
'19 • PAC-DB-308D
PFA004Z088 B
Model(s) : FDC140VSA-W / FDE140VHOutdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space
cooling energy η s,c
efficiency
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 13.6 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 10.0 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 6.4 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.1 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.030 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
269.0 %
Prated,c 13.6 kW 227.6 %
420.0 %
682.0 %
1034.0 %
0.25
4,500 m3/h
Contact details
LWA 72.0 dB
NOx*** -
675kgCO2eq.
FDE140VSAWVH
- 177 -
'19 • PAC-DB-308D
PFA004Z088 B
Information to identify the model(s) to which the information relates : FDC140VSA-W / FDE140VHOutdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :if applicable : electric motorParameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.Item Symbol Value Unit Item Symbol Value UnitRated heating capacity Seasonal space
heating energy η s,hefficiency
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 9.2 kW Tj=-7℃ COPd orGUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.6 kW Tj=+2℃ COPd orGUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.6 kW Tj=+7℃ COPd orGUEh,bin / AEFh,bin
Tj=+12℃ Pdh 3.0 kW Tj=+12℃ COPd orGUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 10.5 kW Tbiv=bivalent COPd ortemperature GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.9 kW TOL=operation limit COPd orGUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd orTj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heatpumps:Operation limit
Degradation Tol temperaturecoefficient Cdh -heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater back-up heating capacity
Off mode POFF 0.008 kWThermostat-off mode PTO 0.045 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other itemsFor air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchangerEmissions of nitrogen mg/kWhoxides(if applicable) fuel input
GCV
GWP of the refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.*** from 26 September 2018Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performanceof the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
No
Prated,h 15.5 kW 166.6 %
290.0 %
410.0 %
540.0 %
675.0 %
%
- ℃
0.25
250.0 %
210.0 %
4,380 m3/h
LWA 73.0 dB - m3/h
elbu - kW
PSB 0.008 kW
-
NOx*** -
675
Contact details
kgCO2eq.
- 178 -
'19 • PAC-DB-308D
PFA004Z088 B
Model(s) : FDC125VNA-W / FDE60VH (2units)Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space
cooling energy η s,c
efficiency
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 12.5 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 9.2 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 5.9 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.5 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.000 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Contact details
LWA 71.0 dB
NOx*** -
675
1995.0 %
0.25
4,500 m3/h
487.0 %
853.0 %
303.0 %
Prated,c 12.5 kW 294.7 %
kgCO2eq.
FDE125VNAWPVH
- 179 -
'19 • PAC-DB-308D
PFA004Z088 B
Information to identify the model(s) to which the information relates : FDC125VNA-W / FDE60VH (2units)Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :if applicable : electric motorParameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.Item Symbol Value Unit Item Symbol Value UnitRated heating capacity Seasonal space
heating energy η s,hefficiency
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 8.7 kW Tj=-7℃ COPd orGUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.3 kW Tj=+2℃ COPd orGUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.4 kW Tj=+7℃ COPd orGUEh,bin / AEFh,bin
Tj=+12℃ Pdh 3.0 kW Tj=+12℃ COPd orGUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 9.8 kW Tbiv=bivalent COPd ortemperature GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.4 kW TOL=operation limit COPd orGUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd orTj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heatpumps:Operation limit
Degradation Tol temperaturecoefficient Cdh -heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater back-up heating capacity
Off mode POFF 0.008 kWThermostat-off mode PTO 0.020 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other itemsFor air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchangerEmissions of nitrogen mg/kWhoxides(if applicable) fuel input
GCV
GWP of the refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.*** from 26 September 2018Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performanceof the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
No
Prated,h 14.0 kW %
324.0 %
487.0 %
198.8
655.0 %
905.0 %
0.25
280.0 %
230.0 %
- %
- ℃
elbu - kW
PSB 0.008 kW
4,380 m3/h
LWA 71.0 dB - m3/h
NOx*** -
675
Contact details
kgCO2eq.
- 180 -
'19 • PAC-DB-308D
PFA004Z088 B
Model(s) : FDC125VSA-W / FDE60VH (2units)Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space
cooling energy η s,c
efficiency
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 12.5 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 9.2 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 5.9 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.5 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.000 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Contact details
LWA 71.0 dB
NOx*** -
675
1995.0 %
0.25
4,500 m3/h
487.0 %
853.0 %
303.0 %
Prated,c 12.5 kW 294.7 %
kgCO2eq.
FDE125VSAWPVH
- 181 -
'19 • PAC-DB-308D
PFA004Z088 B
Information to identify the model(s) to which the information relates : FDC125VSA-W / FDE60VH (2units)Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :if applicable : electric motorParameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.Item Symbol Value Unit Item Symbol Value UnitRated heating capacity Seasonal space
heating energy η s,hefficiency
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 8.7 kW Tj=-7℃ COPd orGUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.3 kW Tj=+2℃ COPd orGUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.4 kW Tj=+7℃ COPd orGUEh,bin / AEFh,bin
Tj=+12℃ Pdh 3.0 kW Tj=+12℃ COPd orGUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 9.8 kW Tbiv=bivalent COPd ortemperature GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.4 kW TOL=operation limit COPd orGUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd orTj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heatpumps:Operation limit
Degradation Tol temperaturecoefficient Cdh -heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater back-up heating capacity
Off mode POFF 0.008 kWThermostat-off mode PTO 0.020 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other itemsFor air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchangerEmissions of nitrogen mg/kWhoxides(if applicable) fuel input
GCV
GWP of the refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.*** from 26 September 2018Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performanceof the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
No
Prated,h 14.0 kW %
324.0 %
487.0 %
198.8
655.0 %
905.0 %
0.25
280.0 %
230.0 %
- %
- ℃
elbu - kW
PSB 0.008 kW
4,380 m3/h
LWA 71.0 dB - m3/h
NOx*** -
675
Contact details
kgCO2eq.
- 182 -
'19 • PAC-DB-308D
PFA004Z088 B
FDE140VNAWPVH
Model(s) : FDC140VNA-W / FDE71VH (2units)Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space
cooling energy η s,c
efficiency
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 13.6 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 10.0 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 6.4 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.7 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.000 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Contact details
LWA 72.0 dB
NOx*** -
675
2026.0 %
0.25
4,500 m3/h
456.0 %
789.0 %
287.0 %
Prated,c 13.6 kW 279.5 %
kgCO2eq.
- 183 -
'19 • PAC-DB-308D
PFA004Z088 B
Information to identify the model(s) to which the information relates : FDC140VNA-W / FDE71VH (2units)Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :if applicable : electric motorParameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.Item Symbol Value Unit Item Symbol Value UnitRated heating capacity Seasonal space
heating energy η s,hefficiency
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 9.3 kW Tj=-7℃ COPd orGUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.6 kW Tj=+2℃ COPd orGUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.6 kW Tj=+7℃ COPd orGUEh,bin / AEFh,bin
Tj=+12℃ Pdh 3.1 kW Tj=+12℃ COPd orGUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 10.5 kW Tbiv=bivalent COPd ortemperature GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.9 kW TOL=operation limit COPd orGUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd orTj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heatpumps:Operation limit
Degradation Tol temperaturecoefficient Cdh -heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater back-up heating capacity
Off mode POFF 0.008 kWThermostat-off mode PTO 0.020 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other itemsFor air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchangerEmissions of nitrogen mg/kWhoxides(if applicable) fuel input
GCV
GWP of the refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.*** from 26 September 2018Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performanceof the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
No
Prated,h 15.5 kW %
296.0 %
467.0 %
188.8
628.0 %
867.0 %
0.25
260.0 %
220.0 %
- %
- ℃
elbu - kW
PSB 0.008 kW
4,380 m3/h
LWA 73.0 dB - m3/h
NOx*** -
675
Contact details
kgCO2eq.
- 184 -
'19 • PAC-DB-308D
PFA004Z088 B
Model(s) : FDC140VSA-W / FDE71VH (2units)Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space
cooling energy η s,c
efficiency
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 13.6 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 10.0 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 6.4 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.7 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.000 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Contact details
LWA 72.0 dB
NOx*** -
675
2026.0 %
0.25
4,500 m3/h
456.0 %
789.0 %
287.0 %
Prated,c 13.6 kW 279.5 %
kgCO2eq.
FDE140VSAWPVH
- 185 -
'19 • PAC-DB-308D
PFA004Z088 B
Information to identify the model(s) to which the information relates : FDC140VSA-W / FDE71VH (2units)Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :if applicable : electric motorParameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.Item Symbol Value Unit Item Symbol Value UnitRated heating capacity Seasonal space
heating energy η s,hefficiency
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 9.3 kW Tj=-7℃ COPd orGUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.6 kW Tj=+2℃ COPd orGUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.6 kW Tj=+7℃ COPd orGUEh,bin / AEFh,bin
Tj=+12℃ Pdh 3.1 kW Tj=+12℃ COPd orGUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 10.5 kW Tbiv=bivalent COPd ortemperature GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.9 kW TOL=operation limit COPd orGUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd orTj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heatpumps:Operation limit
Degradation Tol temperaturecoefficient Cdh -heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater back-up heating capacity
Off mode POFF 0.008 kWThermostat-off mode PTO 0.020 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other itemsFor air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchangerEmissions of nitrogen mg/kWhoxides(if applicable) fuel input
GCV
GWP of the refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.*** from 26 September 2018Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performanceof the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
No
Prated,h 15.5 kW %
296.0 %
467.0 %
188.8
628.0 %
867.0 %
0.25
260.0 %
220.0 %
- %
- ℃
elbu - kW
PSB 0.008 kW
4,380 m3/h
LWA 73.0 dB - m3/h
NOx*** -
675
Contact details
kgCO2eq.
- 186 -
'19 • PAC-DB-308D
PFA004Z088 B
Model(s) : FDC140VNA-W / FDE50VH (3units)Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space
cooling energy η s,c
efficiency
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 13.6 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 10.0 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 6.4 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.7 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.000 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Contact details
LWA 72.0 dB
NOx*** -
675
2026.0 %
0.25
4,500 m3/h
456.0 %
789.0 %
287.0 %
Prated,c 13.6 kW 279.5 %
kgCO2eq.
FDE140VNAWTVH
- 187 -
'19 • PAC-DB-308D
PFA004Z088 B
Information to identify the model(s) to which the information relates : FDC140VNA-W / FDE50VH (3units)Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :if applicable : electric motorParameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.Item Symbol Value Unit Item Symbol Value UnitRated heating capacity Seasonal space
heating energy η s,hefficiency
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 9.3 kW Tj=-7℃ COPd orGUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.6 kW Tj=+2℃ COPd orGUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.6 kW Tj=+7℃ COPd orGUEh,bin / AEFh,bin
Tj=+12℃ Pdh 3.1 kW Tj=+12℃ COPd orGUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 10.5 kW Tbiv=bivalent COPd ortemperature GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.9 kW TOL=operation limit COPd orGUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd orTj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heatpumps:Operation limit
Degradation Tol temperaturecoefficient Cdh -heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater back-up heating capacity
Off mode POFF 0.008 kWThermostat-off mode PTO 0.020 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other itemsFor air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchangerEmissions of nitrogen mg/kWhoxides(if applicable) fuel input
GCV
GWP of the refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.*** from 26 September 2018Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performanceof the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
No
Prated,h 15.5 kW %
296.0 %
467.0 %
188.8
628.0 %
867.0 %
0.25
260.0 %
220.0 %
- %
- ℃
elbu - kW
PSB 0.008 kW
4,380 m3/h
LWA 73.0 dB - m3/h
NOx*** -
675
Contact details
kgCO2eq.
- 188 -
'19 • PAC-DB-308D
PFA004Z088 B
Model(s) : FDC140VSA-W / FDE50VH (3units)Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space
cooling energy η s,c
efficiency
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 13.6 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 10.0 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 6.4 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.7 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.000 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Contact details
LWA 72.0 dB
NOx*** -
675
2026.0 %
0.25
4,500 m3/h
456.0 %
789.0 %
287.0 %
Prated,c 13.6 kW 279.5 %
kgCO2eq.
FDE140VSAWTVH
- 189 -
'19 • PAC-DB-308D
PFA004Z088 B
Information to identify the model(s) to which the information relates : FDC140VSA-W / FDE50VH (3units)Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :if applicable : electric motorParameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.Item Symbol Value Unit Item Symbol Value UnitRated heating capacity Seasonal space
heating energy η s,hefficiency
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 9.3 kW Tj=-7℃ COPd orGUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.6 kW Tj=+2℃ COPd orGUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.6 kW Tj=+7℃ COPd orGUEh,bin / AEFh,bin
Tj=+12℃ Pdh 3.1 kW Tj=+12℃ COPd orGUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 10.5 kW Tbiv=bivalent COPd ortemperature GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.9 kW TOL=operation limit COPd orGUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd orTj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heatpumps:Operation limit
Degradation Tol temperaturecoefficient Cdh -heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater back-up heating capacity
Off mode POFF 0.008 kWThermostat-off mode PTO 0.020 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other itemsFor air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchangerEmissions of nitrogen mg/kWhoxides(if applicable) fuel input
GCV
GWP of the refrigerant (100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.*** from 26 September 2018Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performanceof the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
No
Prated,h 15.5 kW %
296.0 %
467.0 %
188.8
628.0 %
867.0 %
0.25
260.0 %
220.0 %
- %
- ℃
elbu - kW
PSB 0.008 kW
4,380 m3/h
LWA 73.0 dB - m3/h
NOx*** -
675
Contact details
kgCO2eq.
- 190 -
'19 • PAC-DB-308D
PFA004Z088 B
Models FDE50VH, 60VH, 71VH, 100VH, 125VH, 140VH
Model(s) :
Item Symbol Vaiue Unit Item Symbol Vaiue Unit
Cooling capacity (sensible) Prated,c 3.8 kW Total electric power input Pelec 0.050 kW
Cooling capacity (latent) Prated,c 1.2 kW LWA 60.0 dB
Heating capacity Prated,h 5.4 kW
Mitsubishi heavy industries thermal systems,LTD
Model(s) :
Item Symbol Vaiue Unit Item Symbol Vaiue Unit
Cooling capacity (sensible) Prated,c 5.0 kW Total electric power input Pelec 0.080 kW
Cooling capacity (latent) Prated,c 0.6 kW LWA 60.0 dB
Heating capacity Prated,h 6.7 kW
Mitsubishi heavy industries thermal systems,LTD
Model(s) :
Item Symbol Vaiue Unit Item Symbol Vaiue Unit
Cooling capacity (sensible) Prated,c 5.6 kW Total electric power input Pelec 0.080 kW
Cooling capacity (latent) Prated,c 1.5 kW LWA 60.0 dB
Heating capacity Prated,h 8.0 kW
Mitsubishi heavy industries thermal systems,LTD
Model(s) :
Item Symbol Vaiue Unit Item Symbol Vaiue Unit
Cooling capacity (sensible) Prated,c 8.4 kW Total electric power input Pelec 0.130 kW
Cooling capacity (latent) Prated,c 1.6 kW LWA 64.0 dB
Heating capacity Prated,h 11.2 kW
Mitsubishi heavy industries thermal systems,LTD
Model(s) :
Item Symbol Vaiue Unit Item Symbol Vaiue Unit
Cooling capacity (sensible) Prated,c 9.3 kW Total electric power input Pelec 0.130 kW
Cooling capacity (latent) Prated,c 3.2 kW LWA 64.0 dB
Heating capacity Prated,h 14.0 kW
Mitsubishi heavy industries thermal systems,LTD
Model(s) :
Item Symbol Vaiue Unit Item Symbol Vaiue Unit
Cooling capacity (sensible) Prated,c 10.2 kW Total electric power input Pelec 0.140 kW
Cooling capacity (latent) Prated,c 3.8 kW LWA 65.0 dB
Heating capacity Prated,h 16.0 kW
Mitsubishi heavy industries thermal systems,LTD
Contact details
FDE100VH
Sound power level(per speed setting,if applicable)
Contact details
FDE125VH
Sound power level(per speed setting,if applicable)
Contact details
FDE50VH
Sound power level(per speed setting,if applicable)
Contact details
FDE60VH
Sound power level(per speed setting,if applicable)
Contact details
FDE71VH
Sound power level(per speed setting,if applicable)
FDE140VH
Sound power level(per speed setting,if applicable)
Contact details
- 191 -
'19 • PAC-DB-308D
PCA001Z857 A
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season theIndoor unit model name SRK100ZR-W information relates to. Indicated values should relate to oneOutdoor unit model name FDC100VNA-W heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory) Yescooling Yes Warmer(if designated) Noheating Yes Colder(if designated) No
Item symbol value unit Item symbol value classDesign load Seasonal efficiency and energy efficiency classcooling Pdesignc 10.0 kW cooling SEER 6.13 A++heating / Average Pdesignh 8.50 kW heating / Average SCOP/A 4.33 A+heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - -heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unitDeclared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignhheating / Average (-10℃) Pdh 8.50 kW heating / Average (-10℃) elbu 0 kWheating / Warmer (2℃) Pdh - kW heating / Warmer (2℃) elbu - kWheating / Colder (-22℃) Pdh - kW heating / Colder (-22℃) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19)℃ and Declared energy efficiency ratio, at indoor temperature 27(19)℃ andoutdoor temperature Tj outdoor temperature TjTj=35℃ Pdc 10.00 kW Tj=35℃ EERd 3.10 -Tj=30℃ Pdc 7.37 kW Tj=30℃ EERd 4.95 -Tj=25℃ Pdc 4.74 kW Tj=25℃ EERd 7.75 -Tj=20℃ Pdc 3.00 kW Tj=20℃ EERd 10.05 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh 7.36 kW Tj=-7℃ COPd 2.75 -Tj=2℃ Pdh 4.47 kW Tj=2℃ COPd 4.18 -Tj=7℃ Pdh 2.88 kW Tj=7℃ COPd 5.74 -Tj=12℃ Pdh 2.95 kW Tj=12℃ COPd 7.46 -Tj=bivalent temperature Pdh 8.50 kW Tj=bivalent temperature COPd 2.77 -Tj=operating limit Pdh 6.30 kW Tj=operating limit COPd 2.10 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh - kW Tj=-7℃ COPd - -Tj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -Tj=-15℃ Pdh - kW Tj=-15℃ COPd - -
Bivalent temperature Operating limit temperatureheating / Average Tbiv -10 ℃ heating / Average Tol -20 ℃heating / Warmer Tbiv - ℃ heating / Warmer Tol - ℃heating / Colder Tbiv - ℃ heating / Colder Tol - ℃
Cycling interval capacity Cycling interval efficiencyfor cooling Pcycc - kW for cooling EERcyc - -for heating Pcych - kW for heating COPcyc - -
Degradation coefficient Degradation coefficientcooling Cdc 0.25 - heating Cdh 0.25 -
Electric power input in power modes other than 'active mode' Annual electricity consumptionoff mode Poff 7 W cooling Qce 571 kWh/astandby mode Psb 7 W heating / Average Qhe 2746 kWh/athermostat-off mode Pto(cooling) 30 W heating / Warmer Qhe - kWh/a
Pto(heating) 30 W heating / colder Qhe - kWh/acrankcase heater mode Pck 5 W
Capacity control(indicate one of three options) Other itemsSound power level(indoor) Lwa 63 dB(A)Sound power level(outdoor) Lwa 69 dB(A)
fixed No Global warming potential GWP 675 kgCO2eq.staged No Rated air flow(indoor) - 1470 m3/hvariable Yes Rated air flow(outdoor) - 4500 m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative.more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd.
5 The Square, Stockley Park, Uxbridge, Middlesex,UB11 1ET, United kingdom
(6) Wall mounted type (SRK)
SRK100VNAWZR
- 192 -
'19 • PAC-DB-308D
PCA001Z857 A
SRK100VSAWZR
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season theIndoor unit model name SRK100ZR-W information relates to. Indicated values should relate to oneOutdoor unit model name FDC100VSA-W heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory) Yescooling Yes Warmer(if designated) Noheating Yes Colder(if designated) No
Item symbol value unit Item symbol value classDesign load Seasonal efficiency and energy efficiency classcooling Pdesignc 10.0 kW cooling SEER 6.13 A++heating / Average Pdesignh 8.50 kW heating / Average SCOP/A 4.33 A+heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - -heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unitDeclared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignhheating / Average (-10℃) Pdh 8.50 kW heating / Average (-10℃) elbu 0 kWheating / Warmer (2℃) Pdh - kW heating / Warmer (2℃) elbu - kWheating / Colder (-22℃) Pdh - kW heating / Colder (-22℃) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19)℃ and Declared energy efficiency ratio, at indoor temperature 27(19)℃ andoutdoor temperature Tj outdoor temperature TjTj=35℃ Pdc 10.00 kW Tj=35℃ EERd 3.10 -Tj=30℃ Pdc 7.37 kW Tj=30℃ EERd 4.95 -Tj=25℃ Pdc 4.74 kW Tj=25℃ EERd 7.75 -Tj=20℃ Pdc 3.00 kW Tj=20℃ EERd 10.05 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh 7.36 kW Tj=-7℃ COPd 2.75 -Tj=2℃ Pdh 4.47 kW Tj=2℃ COPd 4.18 -Tj=7℃ Pdh 2.88 kW Tj=7℃ COPd 5.74 -Tj=12℃ Pdh 2.95 kW Tj=12℃ COPd 7.46 -Tj=bivalent temperature Pdh 8.50 kW Tj=bivalent temperature COPd 2.77 -Tj=operating limit Pdh 6.30 kW Tj=operating limit COPd 2.10 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh - kW Tj=-7℃ COPd - -Tj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -Tj=-15℃ Pdh - kW Tj=-15℃ COPd - -
Bivalent temperature Operating limit temperatureheating / Average Tbiv -10 ℃ heating / Average Tol -20 ℃heating / Warmer Tbiv - ℃ heating / Warmer Tol - ℃heating / Colder Tbiv - ℃ heating / Colder Tol - ℃
Cycling interval capacity Cycling interval efficiencyfor cooling Pcycc - kW for cooling EERcyc - -for heating Pcych - kW for heating COPcyc - -
Degradation coefficient Degradation coefficientcooling Cdc 0.25 - heating Cdh 0.25 -
Electric power input in power modes other than 'active mode' Annual electricity consumptionoff mode Poff 7 W cooling Qce 571 kWh/astandby mode Psb 7 W heating / Average Qhe 2746 kWh/athermostat-off mode Pto(cooling) 30 W heating / Warmer Qhe - kWh/a
Pto(heating) 30 W heating / colder Qhe - kWh/acrankcase heater mode Pck 5 W
Capacity control(indicate one of three options) Other itemsSound power level(indoor) Lwa 63 dB(A)Sound power level(outdoor) Lwa 69 dB(A)
fixed No Global warming potential GWP 675 kgCO2eq.staged No Rated air flow(indoor) - 1470 m3/hvariable Yes Rated air flow(outdoor) - 4500 m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative.more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd.
5 The Square, Stockley Park, Uxbridge, Middlesex,UB11 1ET, United kingdom
- 193 -
'19 • PAC-DB-308D
PCA001Z857 A
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season theIndoor unit model name SRK50ZSX-W (x2 units) information relates to. Indicated values should relate to oneOutdoor unit model name FDC100VNA-W heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory) Yescooling Yes Warmer(if designated) Noheating Yes Colder(if designated) No
Item symbol value unit Item symbol value classDesign load Seasonal efficiency and energy efficiency classcooling Pdesignc 10.0 kW cooling SEER 7.05 A++heating / Average Pdesignh 8.50 kW heating / Average SCOP/A 4.47 A+heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - -heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unitDeclared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignhheating / Average (-10℃) Pdh 8.50 kW heating / Average (-10℃) elbu 0 kWheating / Warmer (2℃) Pdh - kW heating / Warmer (2℃) elbu - kWheating / Colder (-22℃) Pdh - kW heating / Colder (-22℃) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19)℃ and Declared energy efficiency ratio, at indoor temperature 27(19)℃ andoutdoor temperature Tj outdoor temperature TjTj=35℃ Pdc 10.00 kW Tj=35℃ EERd 3.46 -Tj=30℃ Pdc 7.37 kW Tj=30℃ EERd 5.30 -Tj=25℃ Pdc 4.74 kW Tj=25℃ EERd 9.20 -Tj=20℃ Pdc 3.58 kW Tj=20℃ EERd 15.30 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh 7.40 kW Tj=-7℃ COPd 3.06 -Tj=2℃ Pdh 4.50 kW Tj=2℃ COPd 4.28 -Tj=7℃ Pdh 2.90 kW Tj=7℃ COPd 5.86 -Tj=12℃ Pdh 2.93 kW Tj=12℃ COPd 7.55 -Tj=bivalent temperature Pdh 8.50 kW Tj=bivalent temperature COPd 2.40 -Tj=operating limit Pdh 6.30 kW Tj=operating limit COPd 2.00 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh - kW Tj=-7℃ COPd - -Tj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -Tj=-15℃ Pdh - kW Tj=-15℃ COPd - -
Bivalent temperature Operating limit temperatureheating / Average Tbiv -10 ℃ heating / Average Tol -20 ℃heating / Warmer Tbiv - ℃ heating / Warmer Tol - ℃heating / Colder Tbiv - ℃ heating / Colder Tol - ℃
Cycling interval capacity Cycling interval efficiencyfor cooling Pcycc - kW for cooling EERcyc - -for heating Pcych - kW for heating COPcyc - -
Degradation coefficient Degradation coefficientcooling Cdc 0.25 - heating Cdh 0.25 -
Electric power input in power modes other than 'active mode' Annual electricity consumptionoff mode Poff 10 W cooling Qce 497 kWh/astandby mode Psb 10 W heating / Average Qhe 2661 kWh/athermostat-off mode Pto(cooling) 50 W heating / Warmer Qhe - kWh/a
Pto(heating) 65 W heating / colder Qhe - kWh/acrankcase heater mode Pck 5 W
Capacity control(indicate one of three options) Other itemsSound power level(indoor) Lwa 59 dB(A)Sound power level(outdoor) Lwa 69 dB(A)
fixed No Global warming potential GWP 675 kgCO2eq.staged No Rated air flow(indoor) - 858 m3/hvariable Yes Rated air flow(outdoor) - 4500 m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative.more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd.
5 The Square, Stockley Park, Uxbridge, Middlesex,UB11 1ET, United kingdom
SRK100VNAWPZSX
- 194 -
'19 • PAC-DB-308D
PCA001Z857 A
SRK100VSAWPZSX
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season theIndoor unit model name SRK50ZSX-W (x2 units) information relates to. Indicated values should relate to oneOutdoor unit model name FDC100VSA-W heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory) Yescooling Yes Warmer(if designated) Noheating Yes Colder(if designated) No
Item symbol value unit Item symbol value classDesign load Seasonal efficiency and energy efficiency classcooling Pdesignc 10.0 kW cooling SEER 7.05 A++heating / Average Pdesignh 8.50 kW heating / Average SCOP/A 4.47 A+heating / Warmer Pdesignh - kW heating / Warmer SCOP/W - -heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
unitDeclared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignhheating / Average (-10℃) Pdh 8.50 kW heating / Average (-10℃) elbu 0 kWheating / Warmer (2℃) Pdh - kW heating / Warmer (2℃) elbu - kWheating / Colder (-22℃) Pdh - kW heating / Colder (-22℃) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19)℃ and Declared energy efficiency ratio, at indoor temperature 27(19)℃ andoutdoor temperature Tj outdoor temperature TjTj=35℃ Pdc 10.00 kW Tj=35℃ EERd 3.46 -Tj=30℃ Pdc 7.37 kW Tj=30℃ EERd 5.30 -Tj=25℃ Pdc 4.74 kW Tj=25℃ EERd 9.20 -Tj=20℃ Pdc 3.58 kW Tj=20℃ EERd 15.30 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh 7.40 kW Tj=-7℃ COPd 3.06 -Tj=2℃ Pdh 4.50 kW Tj=2℃ COPd 4.28 -Tj=7℃ Pdh 2.90 kW Tj=7℃ COPd 5.86 -Tj=12℃ Pdh 2.93 kW Tj=12℃ COPd 7.55 -Tj=bivalent temperature Pdh 8.50 kW Tj=bivalent temperature COPd 2.40 -Tj=operating limit Pdh 6.30 kW Tj=operating limit COPd 2.00 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoortemperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature TjTj=-7℃ Pdh - kW Tj=-7℃ COPd - -Tj=2℃ Pdh - kW Tj=2℃ COPd - -Tj=7℃ Pdh - kW Tj=7℃ COPd - -Tj=12℃ Pdh - kW Tj=12℃ COPd - -Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -Tj=operating limit Pdh - kW Tj=operating limit COPd - -Tj=-15℃ Pdh - kW Tj=-15℃ COPd - -
Bivalent temperature Operating limit temperatureheating / Average Tbiv -10 ℃ heating / Average Tol -20 ℃heating / Warmer Tbiv - ℃ heating / Warmer Tol - ℃heating / Colder Tbiv - ℃ heating / Colder Tol - ℃
Cycling interval capacity Cycling interval efficiencyfor cooling Pcycc - kW for cooling EERcyc - -for heating Pcych - kW for heating COPcyc - -
Degradation coefficient Degradation coefficientcooling Cdc 0.25 - heating Cdh 0.25 -
Electric power input in power modes other than 'active mode' Annual electricity consumptionoff mode Poff 10 W cooling Qce 497 kWh/astandby mode Psb 10 W heating / Average Qhe 2661 kWh/athermostat-off mode Pto(cooling) 50 W heating / Warmer Qhe - kWh/a
Pto(heating) 65 W heating / colder Qhe - kWh/acrankcase heater mode Pck 5 W
Capacity control(indicate one of three options) Other itemsSound power level(indoor) Lwa 59 dB(A)Sound power level(outdoor) Lwa 69 dB(A)
fixed No Global warming potential GWP 675 kgCO2eq.staged No Rated air flow(indoor) - 858 m3/hvariable Yes Rated air flow(outdoor) - 4500 m3/h
Contact details for obtaining Name and address of the manufacturer or of its authorised representative.more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd.
5 The Square, Stockley Park, Uxbridge, Middlesex,UB11 1ET, United kingdom
- 195 -
'19 • PAC-DB-308D
PCA001Z857 A
Model(s) : FDC125VNA-W / SRK60ZSX-W (x2 units)Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 12.5 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 9.2 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 5.9 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.4 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.000 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
0.25
4500 m3/h
Contact details
LWA 71.0 dB
NOx*** -
675
Prated,c 12.5 kW 295.4 %
276.0 %
480.0 %
880.0 %
2130.0 %
kgCO2eq.
SRK125VNAWPZSX
- 196 -
'19 • PAC-DB-308D
PCA001Z857 A
Information to identify the model(s) to which the information relates : FDC125VNA-W / SRK60ZSX-W (x2 units)Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value Unit
Rated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /
and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 8.7 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.3 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.4 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+12℃ Pdh 3.0 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 9.8 kW Tbiv=bivalent COPd ortemperature
GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.4 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd or
Tj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heat
pumps:Operation limit
Degradation Tol temperature
coefficient Cdh -
heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater
back-up heating capacityOff mode POFF 0.008 kW
Thermostat-off mode PTO 0.020 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other items
For air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :
outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchanger
Emissions of nitrogen mg/kWh
oxides(if applicable) fuel input
GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
NOx*** -
675
Contact details
4380
- kW
m3/h
LWA 71.0 dB- m3/h
PSB 0.008 kW
elbu
0.25
270.0 %
210.0 %
- %
- ℃
944.0 %
310.0 %
458.0 %
%192.5
No
Prated,h 14.0 kW
671.0 %
kgCO2eq.
- 197 -
'19 • PAC-DB-308D
PCA001Z857 A
Model(s) : FDC125VSA-W / SRK60ZSX-W (x2 units)Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 12.5 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 9.2 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 5.9 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.4 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.008 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.000 kW Standby mode PSB 0.008 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
276.0 %
Prated,c 12.5 kW 295.4 %
m3/h
480.0 %
880.0 %
Contact details
LWA 71.0 dB
NOx*** -
675
2130.0 %
0.25
4500
kgCO2eq.
SRK125VSAWPZSX
- 198 -
'19 • PAC-DB-308D
Information to identify the model(s) to which the information relates : FDC125VSA-W / SRK60ZSX-W (x2 units)Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value Unit
Rated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /
and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 8.7 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.3 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.4 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+12℃ Pdh 3.0 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 9.8 kW Tbiv=bivalent COPd ortemperature
GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.4 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd or
Tj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heat
pumps:Operation limit
Degradation Tol temperature
coefficient Cdh -
heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater
back-up heating capacityOff mode POFF 0.008 kW
Thermostat-off mode PTO 0.020 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other items
For air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :
outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchanger
Emissions of nitrogen mg/kWh
oxides(if applicable) fuel input
GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
NOx*** -
675
Contact details
4380
- kW
m3/h
LWA 71.0 dB- m3/h
PSB 0.008 kW
elbu
0.25
270.0 %
210.0 %
- %
- ℃
944.0 %
310.0 %
458.0 %
%192.5
No
Prated,h 14.0 kW
671.0 %
kgCO2eq.
PCA001Z857 A
- 199 -
'19 • PAC-DB-308D
PCA001Z857 A
Model(s) : FDC140VNA-W / SRK71ZR-W (x2 units)Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 13.6 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 10.0 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 6.4 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.7 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.010 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.000 kW Standby mode PSB 0.010 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
319.0 %
Prated,c 13.6 kW 311.5 %
m3/h
540.0 %
890.0 %
Contact details
LWA 72.0 dB
NOx*** -
675
2270.0 %
0.25
4500
kgCO2eq.
SRK140VNAWPZR
- 200 -
'19 • PAC-DB-308D
Information to identify the model(s) to which the information relates : FDC140VNA-W / SRK71ZR-W (x2 units)Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value Unit
Rated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /
and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 9.3 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.6 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.6 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+12℃ Pdh 3.1 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 10.5 kW Tbiv=bivalent COPd ortemperature
GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.9 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd or
Tj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heat
pumps:Operation limit
Degradation Tol temperature
coefficient Cdh -
heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater
back-up heating capacityOff mode POFF 0.010 kW
Thermostat-off mode PTO 0.020 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other items
For air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :
outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchanger
Emissions of nitrogen mg/kWh
oxides(if applicable) fuel input
GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
NOx*** -
675
Contact details
4380
- kW
m3/h
LWA 73.0 dB- m3/h
PSB 0.010 kW
elbu
0.25
250.0 %
200.0 %
- %
- ℃
736.0 %
1090.0 %
320.0 %
504.0 %
%209.5
No
Prated,h 15.5 kW
kgCO2eq.
PCA001Z857 A
- 201 -
'19 • PAC-DB-308D
PCA001Z857 A
Model(s) : FDC140VSA-W / SRK71ZR-W (x2 units)Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 13.6 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 10.0 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 6.4 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.7 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.010 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.000 kW Standby mode PSB 0.010 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
319.0 %
Prated,c 13.6 kW 311.5 %
m3/h
540.0 %
890.0 %
Contact details
LWA 72.0 dB
NOx*** -
675
2270.0 %
0.25
4500
kgCO2eq.
SRK140VSAWPZR
- 202 -
'19 • PAC-DB-308D
Information to identify the model(s) to which the information relates : FDC140VSA-W / SRK71ZR-W (x2 units)Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value Unit
Rated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /
and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 9.3 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.6 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.6 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+12℃ Pdh 3.1 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 10.5 kW Tbiv=bivalent COPd ortemperature
GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.9 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd or
Tj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heat
pumps:Operation limit
Degradation Tol temperature
coefficient Cdh -
heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater
back-up heating capacityOff mode POFF 0.010 kW
Thermostat-off mode PTO 0.000 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other items
For air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :
outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchanger
Emissions of nitrogen mg/kWh
oxides(if applicable) fuel input
GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
NOx*** -
675
Contact details
4380
- kW
m3/h
LWA 73.0 dB- m3/h
PSB 0.010 kW
elbu
0.25
250.0 %
200.0 %
- %
- ℃
750.0 %
1120.0 %
349.0 %
529.0 %
%219.6
No
Prated,h 15.5 kW
kgCO2eq.
PCA001Z857 A
- 203 -
'19 • PAC-DB-308D
PCA001Z857 A
Model(s) : FDC140VNA-W / SRK50ZSX-W (x3 units)Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 13.6 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 10.0 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 6.4 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.7 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.010 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.000 kW Standby mode PSB 0.010 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Prated,c 13.6 kW 311.5 %
319.0 %
540.0 %
2270.0 %
890.0 %
0.25
4500 m3/h
675
LWA 72.0 dB
Contact details
NOx*** -
kgCO2eq.
SRK140VNAWTZSX
- 204 -
'19 • PAC-DB-308D
Information to identify the model(s) to which the information relates : FDC140VNA-W / SRK50ZSX-W (x3 units)Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value Unit
Rated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /
and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 9.3 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.6 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.6 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+12℃ Pdh 3.1 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 10.5 kW Tbiv=bivalent COPd ortemperature
GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.9 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd or
Tj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heat
pumps:Operation limit
Degradation Tol temperature
coefficient Cdh -
heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater
back-up heating capacityOff mode POFF 0.010 kW
Thermostat-off mode PTO 0.000 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other items
For air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :
outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchanger
Emissions of nitrogen mg/kWh
oxides(if applicable) fuel input
GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
NOx*** -
675
Contact details
4380
- kW
m3/h
LWA 73.0 dB- m3/h
PSB 0.010 kW
elbu
0.25
250.0 %
200.0 %
- %
- ℃
1120.0 %
349.0 %
529.0 %
%219.6
No
Prated,h 15.5 kW
750.0 %
kgCO2eq.
PCA001Z857 A
- 205 -
'19 • PAC-DB-308D
PCA001Z857 A
Model(s) : FDC140VSA-W / SRK50ZSX-W (x3 units)Outdoor side heat exchanger of air conditioner : airIndoor side heat exchanger of air conditioner : airType : vapour compression
if applicable : electric motor
Item Symbol Value Unit Item Symbol Value Unit
Rated cooling capacity Seasonal space cooling energy
efficiency ηs,c
Declared cooling capacity for part load at given outdoor temperatures Declared energy efficiency ratio or gas utilization efficiency /
Tj and indoor 27℃/19℃(dry/wet bulb) auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=+35℃ Pdc 13.6 kW Tj=+35℃ EERd or
GUEc,bin / AEFc,bin
Tj=+30℃ Pdc 10.0 kW Tj=+30℃ EERd or
GUEc,bin / AEFc,bin
Tj=+25℃ Pdc 6.4 kW Tj=+25℃ EERd or
GUEc,bin / AEFc,bin
Tj=+20℃ Pdc 3.7 kW Tj=+20℃ EERd or
GUEc,bin / AEFc,bin
Degradation
coefficient for Cdc -
air conditioners**
Power consumpiton in other than 'active mode'
Off mode POFF 0.010 kW Crankcase heater mode PCK 0.005 kW
Thermostat-off mode PTO 0.000 kW Standby mode PSB 0.010 kW
Other items
For air-to-air air conditioner:Capacity control variable air flow-rate,outdoor measured
Sound power level,
outdoor
If engine driven: mg/kWh
Emissions of nitrogen fuel input
oxides GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Prated,c 13.6 kW 311.5 %
319.0 %
540.0 %
2270.0 %
890.0 %
0.25
4500 m3/h
675
LWA 72.0 dB
Contact details
NOx*** -
kgCO2eq.
SRK140VSAWTZSX
- 206 -
'19 • PAC-DB-308D
Information to identify the model(s) to which the information relates : FDC140VSA-W / SRK50ZSX-W (x3 units)Outdoor side heat exchanger of heat pump : airIndoor side heat exchanger of heat pump : airIndication if the heater is equipped with a supplementary heater :
if applicable : electric motor
Parameters shall be declared for the average heating season , parameters for the warmer and colder heating seasons are optional.
Item Symbol Value Unit Item Symbol Value Unit
Rated heating capacity Seasonal space heating energy efficiency ηs,h
Declared heating capacity for part load at indoor temperature 20℃ Declared coefficient of performance or gas utilization efficiency /
and outdoor temperature Tj auxiliary energy factor for part load at given outdoor temperatures Tj
Tj=-7℃ Pdh 9.3 kW Tj=-7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+2℃ Pdh 5.6 kW Tj=+2℃ COPd or
GUEh,bin / AEFh,bin
Tj=+7℃ Pdh 3.6 kW Tj=+7℃ COPd or
GUEh,bin / AEFh,bin
Tj=+12℃ Pdh 3.1 kW Tj=+12℃ COPd or
GUEh,bin / AEFh,bin
Tbiv=bivalent temperature Pdh 10.5 kW Tbiv=bivalent COPd ortemperature
GUEh,bin / AEFh,bin
TOL=operation limit Pdh 7.9 kW TOL=operation limit COPd or
GUEh,bin / AEFh,bin
For air-to-water heat pumps : Pdh - kW For air-to-water heat COPd or
Tj=-15℃ pumps:Tj=-15℃ GUEh,bin / AEFh,bin
(if TOL<-20℃) (if TOL<-20℃)
Bivalent temperature Tbiv -10.0 ℃ For water-to-air heat
pumps:Operation limit
Degradation Tol temperature
coefficient Cdh -
heat pumps**
Power consumpiton in modes other than 'active mode' Supplementary heater
back-up heating capacityOff mode POFF 0.010 kW
Thermostat-off mode PTO 0.000 kW Type of energy inputCrankcase heater mode PCK 0.005 kW Standby mode
Other items
For air-to-air heat pumps:
Capacity control variable air flow-rate,outdoor measured
Sound power level, For water-/brine-to-air heat pumps :
outdoor measured Rated brine or water fiow-rate,
outdoor side heat exchanger
Emissions of nitrogen mg/kWh
oxides(if applicable) fuel input
GCV
GWP of the
refrigerant(100years)
Mitsubishi heavy industries thermal systems,LTD ** If Cdh is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.
*** from 26 September 2018
Where information relates to multi-spilt air conditioners,the test result and performance data be obtained on the basis of the performance
of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
No
Prated,h 15.5 kW %
349.0 %
529.0 %
219.6
750.0 %
1120.0 %
0.25
250.0 %
200.0 %
- %
- ℃
675
Contact details
4380
LWA 73.0 dB- m3/h
elbu - kW
PSB 0.010 kW
m3/h
NOx*** -
kgCO2eq.
PCA001Z857 A
- 207 -
'19 • PAC-DB-308D
PCA001Z857 A
Models SRK50ZSX-W, 60ZSX-W, 71ZR-W, 100ZR-W
Model(s) :
Item Symbol Vaiue Unit Item Symbol Vaiue Unit
Cooling capacity (sensible) Prated,c 4.0 kW Total electric power input Pelec 0.030 kW
Cooling capacity (latent) Prated,c 1.0 kW LWA 59.0 dB
Heating capacity Prated,h 6.0 kW
Mitsubishi heavy industries thermal systems,LTD
Model(s) :
Item Symbol Vaiue Unit Item Symbol Vaiue Unit
Cooling capacity (sensible) Prated,c 4.7 kW Total electric power input Pelec 0.040 kW
Cooling capacity (latent) Prated,c 1.4 kW LWA 62.0 dB
Heating capacity Prated,h 6.8 kW
Mitsubishi heavy industries thermal systems,LTD
Model(s) :
Item Symbol Vaiue Unit Item Symbol Vaiue Unit
Cooling capacity (sensible) Prated,c 5.2 kW Total electric power input Pelec 0.056 kW
Cooling capacity (latent) Prated,c 1.9 kW LWA 60.0 dB
Heating capacity Prated,h 7.1 kW
Mitsubishi heavy industries thermal systems,LTD
Model(s) :
Item Symbol Vaiue Unit Item Symbol Vaiue Unit
Cooling capacity (sensible) Prated,c 7.4 kW Total electric power input Pelec 0.060 kW
Cooling capacity (latent) Prated,c 2.6 kW LWA 63.0 dB
Heating capacity Prated,h 11.2 kW
Mitsubishi heavy industries thermal systems,LTD Contact details
SRK50ZSX-W
Sound power level(per speed setting,if applicable)
Contact details
SRK60ZSX-W
Sound power level(per speed setting,if applicable)
Contact details
SRK71ZR-W
Sound power level(per speed setting,if applicable)
Contact details
SRK100ZR-W
Sound power level(per speed setting,if applicable)
- 208 -
'19 • PAC-DB-308D
2. V MULTI SYSTEM
CONTENTS
2.1 GENERAL INFORMATION
2.1 GENERAL INFORMATION
....................................................................................208.........................................................................208
..............................................................................................209......................................................................209
2.1.1 How to read the model name
2.1.1 How to read the model name
2.1.2 Table of models2.1.3 Table of system combinations
2.2 SPECIFICATIONS(1) Indoor units
(a) Ceiling cassette-4 way type (FDT)(b) Ceiling suspended type (FDE)
(2) Outdoor units(3) Operation chart
2.3 EXTERIOR DIMENSIONS2.4 ELECTRICAL WIRING2.5 TECHNICAL INFORMATION
.................................................................................................210.........................................................................................................210
..................................................................210........................................................................213
......................................................................................................216....................................................................................................222
......................................................................................225...........................................................................................225
..................................................................................225
Example: FDT 50 VH
Series code
Product capacity
Model name FDT : Ceiling cassette-4 way typeFDE : Ceiling suspended type
Example: FDC 100 VNA-W
Applicable power source...See the specificationProduct capacityModel name (FDC : Outdoor unit)
- 209 -
'19 • PAC-DB-308D
2.1.2 Table of models
2.1.3 Table of system combinations
Notes(1) Always use the branch piping set (option) at branches in the refrigerant piping. Notes(2) If wireless specifications are used, use 1 wireless indoor unit in combination with wired indoor units.Notes(3) The combinations except the above table forbids.
CapacityModel
Ceiling cassette-4 way type (FDT)
Ceiling suspended type (FDE)
Outdoor unit to be combined (FDC)
50 60 71
FDC100VNA-WFDC100VSA-W(4 HP)
FDC125VNA-WFDC125VSA-W(5 HP)
FDC140VNA-WFDC140VSA-W(6 HP)
○
○
○
○
○
○
Indoor unit assembly capacity Branch pipe set(Option)
71+71
50+50+50
DIS-WA1G
DIS-TA1Gor
DIS-WA1G×2 sets
TypeOutdoor unit
50+50FDC100VNA-WFDC100VSA-W
60+6050+71
FDC125VNA-WFDC125VSA-W
FDC140VNA-WFDC140VSA-W
Twin
Twin
Triple
- 210 -
'19 • PAC-DB-308D
PJF000Z589 B
ModelItem
FDT50VH
Power source 1 Phase 220-240V 50Hz / 220V 60Hz
Operation data
Sound power levelCooling
dB(A)
55Heating 56
Sound pressure levelCooling P-Hi : 41 Hi : 33 Me : 30 Lo : 26Heating P-Hi : 42 Hi : 33 Me : 28 Lo : 20
Silent mode sound pressure level —
Exterior dimensions (Height × Width × Depth) mmUnit 236 × 840 × 840Panel 35 × 950 × 950
Exterior appearance( Munsell color )
Plaster white( 6.8Y8.9/0.2 ) near equivalent
Net weight kgUnit 19Panel 5
Heat exchanger Louver fin & inner grooved tubingFan type & Q'ty Turbo fan ×1Fan motor (Starting method) W 50 < Direct line start >
Air flow Cooling
m3/min P-Hi : 22 Hi : 16 Me : 13 Lo : 10Heating
Available external static pressure Pa 0Outside air intake PossibleAir filter, Quality / Quantity Pocket plastic net ×1 (Washable)Shock & vibration absorber Rubber sleeve (for fan motor)Electric heater W —
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-T-5AW-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipmentsInternal thermostat for fan motor.
Frost protection thermostat.
Installation data
Refrigerant piping size ( O.D. ) mmLiquid line: φ 6.35 (1/4") Gas line: φ 12.7 (1/2")
Connecting method Flare pipingAttached length of piping m —Insulation for piping Necessary (both Liquid & Gas lines)Drain hose Hose connectable VP25 (O.D.32)
Drain pump, max lift height mm Built-in drain pump, 850IP number IPX0Standard accessories Mounting kit, Drain hoseOption parts —Notes (1) The data are measured at the following conditions. The pipe length is 7.5m.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat
higher due to ambient conditions.(4) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
2.2 SPECIFICATIONS(1) Indoor units
(a) Ceiling cassette -4 way type (FDT)
- 211 -
'19 • PAC-DB-308D
ModelItem
FDT60VH
Power source 1 Phase 220-240V 50Hz / 220V 60Hz
Operation data
Sound power levelCooling
dB(A)
58Heating 59
Sound pressure levelCooling P-Hi : 44 Hi : 34 Me : 30 Lo : 27Heating P-Hi : 44 Hi : 34 Me : 30 Lo : 23
Silent mode sound pressure level —
Exterior dimensions (Height × Width × Depth) mmUnit 236 × 840 × 840Panel 35 × 950 × 950
Exterior appearance( Munsell color )
Plaster white( 6.8Y8.9/0.2 ) near equivalent
Net weight kgUnit 21Panel 5
Heat exchanger Louver fin & inner grooved tubingFan type & Q'ty Turbo fan ×1Fan motor (Starting method) W 50 < Direct line start >
Air flow Cooling
m3/min P-Hi : 26 Hi : 17 Me : 14 Lo : 11Heating
Available external static pressure Pa 0Outside air intake PossibleAir filter, Quality / Quantity Pocket plastic net ×1 (Washable)Shock & vibration absorber Rubber sleeve (for fan motor)Electric heater W —
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-T-5AW-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipmentsInternal thermostat for fan motor.
Frost protection thermostat.
Installation data
Refrigerant piping size ( O.D. ) mmLiquid line: φ 6.35 (1/4") Gas line: φ 12.7 (1/2")
Connecting method Flare pipingAttached length of piping m —Insulation for piping Necessary (both Liquid & Gas lines)Drain hose Hose connectable VP25 (O.D.32)
Drain pump, max lift height mm Built-in drain pump, 850IP number IPX0Standard accessories Mounting kit, Drain hoseOption parts —Notes (1) The data are measured at the following conditions. The pipe length is 7.5m.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat
higher due to ambient conditions.(4) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
PJF000Z589 B
- 212 -
'19 • PAC-DB-308D
ModelItem
FDT71VH
Power source 1 Phase 220-240V 50Hz / 220V 60Hz
Operation data
Sound power levelCooling
dB(A)
59Heating 60
Sound pressure levelCooling P-Hi : 46 Hi : 34 Me : 31 Lo : 26Heating P-Hi : 46 Hi : 34 Me : 31 Lo : 26
Silent mode sound pressure level —
Exterior dimensions (Height × Width × Depth) mmUnit 236 × 840 × 840Panel 35 × 950 × 950
Exterior appearance( Munsell color )
Plaster white( 6.8Y8.9/0.2 ) near equivalent
Net weight kgUnit 21Panel 5
Heat exchanger Louver fin & inner grooved tubingFan type & Q'ty Turbo fan ×1Fan motor (Starting method) W 50 < Direct line start >
Air flow Cooling
m3/min P-Hi : 28 Hi : 18 Me : 15 Lo : 12Heating
Available external static pressure Pa 0Outside air intake PossibleAir filter, Quality / Quantity Pocket plastic net ×1 (Washable)Shock & vibration absorber Rubber sleeve (for fan motor)Electric heater W —
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-T-5AW-E2Room temperature control Thermostat by electronicsOperation display —
Safety equipmentsInternal thermostat for fan motor.
Frost protection thermostat.
Installation data
Refrigerant piping size ( O.D. ) mmLiquid line: φ 9.52 (3/8") Gas line: φ 15.88 (5/8")
Connecting method Flare pipingAttached length of piping m —Insulation for piping Necessary (both Liquid & Gas lines)Drain hose Hose connectable VP25 (O.D.28)
Drain pump, max lift height mm Built-in drain pump, 850IP number IPX0Standard accessories Mounting kit, Drain hoseOption parts —Notes (1) The data are measured at the following conditions. The pipe length is 7.5m.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat
higher due to ambient conditions.(4) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
PJF000Z589 B
- 213 -
'19 • PAC-DB-308D
PFA004Z088 B
ModelItem FDE50VH
Power source 1 Phase 220-240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity kW 5.0Nominal heating capacity kW 5.4
Sound power levelCooling
dB(A)
60Heating
Sound pressure levelCooling
P-Hi : 46 Hi : 38 Me : 36 Lo : 31Heating
Silent mode sound pressure level —
Exterior dimensions (Height x Width x Depth) mm 210 × 1070 × 690
Exterior appearance( Munsell color )( RAL color )
Plaster white( 6.8Y8.9/0.2 ) near equivalent( RAL 9003 ) near equivalent
Net weight kg 28Heat exchanger Louver fin & inner grooved tubingFan type & Q'ty Centrifugal fan ×2Fan motor (Starting method) W 30 < Direct line start >
Air flowCooling
m3/min P-Hi : 13 Hi : 10 Me : 9 Lo : 7Heating
Available external static pressure Pa 0Outside air intake Not possibleAir filter, Quality / Quantity Pocket plastic net ×2(Washable)Shock & vibration absorber Rubber sleeve(for fan motor)Electric heater W —
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-E-E3Room temperature control Thermostat by electronicsOperation display —
Safety equipmentsOverload protection for fan motor
Frost protection thermostat
Installationdata
Refrigerant piping size ( O.D. ) mmLiquid line: φ6.35 (1/4")Gas line: φ12.7 (1/2")
Connecting method Flare pipingAttached length of piping m —Insulation for piping Necessary (both Liquid & Gas lines)Drain hose Hose connectable VP20(O.D.26)
Drain pump, max lift height mm —IP number IPX0Standard accessories Mounting kit, Drain hoseOption parts Motion sensor : LB-E
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.
Notes (1) The data are measured at the following conditions.
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
(b) Ceiling suspended type (FDE)
- 214 -
'19 • PAC-DB-308D
PFA004Z088 B
ModelItem FDE60VH
Power source 1 Phase 220-240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity kW 5.6Nominal heating capacity kW 6.7
Sound power levelCooling
dB(A)
60Heating
Sound pressure levelCooling
P-Hi : 47 Hi : 41 Me : 37 Lo : 32Heating
Silent mode sound pressure level —
Exterior dimensions (Height x Width x Depth) mm 210 × 1320 × 690
Exterior appearance( Munsell color )( RAL color )
Plaster white( 6.8Y8.9/0.2 ) near equivalent( RAL 9003 ) near equivalent
Net weight kg 33Heat exchanger Louver fin & inner grooved tubingFan type & Q'ty Centrifugal fan ×4Fan motor (Starting method) W 50 < Direct line start >
Air flowCooling
m3/min P-Hi : 20 Hi : 16 Me : 13 Lo : 10Heating
Available external static pressure Pa 0Outside air intake Not possibleAir filter, Quality / Quantity Pocket plastic net ×2(Washable)Shock & vibration absorber Rubber sleeve(for fan motor)Electric heater W —
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-E-E3Room temperature control Thermostat by electronicsOperation display —
Safety equipmentsOverload protection for fan motor
Frost protection thermostat
Installationdata
Refrigerant piping size ( O.D. ) mmLiquid line: φ6.35 (1/4")Gas line: φ12.7 (1/2")
Connecting method Flare pipingAttached length of piping m —Drain hose Hose connectable VP20(O.D.26)
Drain pump, max lift height mm —IP number IPX0Standard accessories Mounting kit, Drain hoseOption parts Motion sensor : LB-E
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.
Notes (1) The data are measured at the following conditions.
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 215 -
'19 • PAC-DB-308D
PFA004Z088 B
ModelItem FDE71VH
Power source 1 Phase 220-240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 7.1Nominal heating capacity (range) kW 8.0
Sound power levelCooling
dB(A)
60Heating
Sound pressure levelCooling
P-Hi : 47 Hi : 41 Me : 37 Lo : 32Heating
Silent mode sound pressure level —
Exterior dimensions (Height x Width x Depth) mm 210 × 1320 × 690
Exterior appearance( Munsell color )( RAL color )
Plaster white( 6.8Y8.9/0.2 ) near equivalent( RAL 9003 ) near equivalent
Net weight kg 33Heat exchanger Louver fin & inner grooved tubingFan type & Q'ty Centrifugal fan ×4Fan motor (Starting method) W 50 < Direct line start >
Air flowCooling
m3/min P-Hi : 20 Hi : 16 Me : 13 Lo : 10Heating
Available external static pressure Pa 0Outside air intake Not possibleAir filter, Quality / Quantity Pocket plastic net ×2(Washable)Shock & vibration absorber Rubber sleeve(for fan motor)Electric heater W —
Operation control
Remote control (Option) Wired : RC-EX3A , RC-E5 , RCH-E3 Wireless : RCN-E-E3Room temperature control Thermostat by electronicsOperation display —
Safety equipmentsOverload protection for fan motor
Frost protection thermostat
Installationdata
Refrigerant piping size ( O.D. ) mmLiquid line: φ9.52 (3/8")Gas line: φ15.88 (5/8")
Connecting method Flare pipingAttached length of piping m —Insulation for piping Necessary (both Liquid & Gas lines)Drain hose Hose connectable VP20(O.D.26)
Drain pump, max lift height mm —IP number IPX0Standard accessories Mounting kit, Drain hoseOption parts Motion sensor : LB-E
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.(4) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.
Notes (1) The data are measured at the following conditions.
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 216 -
'19 • PAC-DB-308D
PJF000Z589 B
ModelItem
FDC100VNA-W
Power source 1 Phase 220-240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 10.0 [ 4.0(Min.)-11.2(Max.)]Nominal heating capacity (range) kW 11.2 [ 4.0(Min.)-12.5(Max.)]
Sound power levelCooling
dB(A)
69Heating 70
Sound pressure levelCooling 54Heating 55
Silent mode sound pressure level 48/44 (Normal/Silent)
Exterior dimensions (Height × Width × Depth) mm 845×970×370
Exterior appearance( Munsell color )(RAL color)
Stucco white( 4.2Y7.5/1.1) near equivalent( RAL 7044 ) near equivalent
Net weight kg 77Compressor type & Q'ty RMT5126SWP3×1Compressor motor (Starting method) kW Direct line startRefrigerant oil (Amount, type) L 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Propeller fan ×1Fan motor (Starting method) W 86 < Direct line start >
Air flow Cooling
m3/min75
Heating 73Shock & vibration absorber Rubber sleeve (for fan motor & compressor)Electric heater W 20 (Crank case heater)
Safety equipmentsInternal thermostat for fan motor
Abnormal discharge temperature protection
Installation data
Refrigerant piping size ( O.D. ) mmLiquid line: φ9.52 (3/8") Gas line: φ15.88 (5/8")
Connecting method Flare pipingAttached length of piping m —Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50mVertical height diff. between O/U and I/U m Max.50m (Outdoor unit is higher) Max.15m (Outdoor unit is lower)Drain hose Hole size φ20 × 3 pcs
IP number IP24Standard accessories —Option parts —
Notes (1) The data are measured at the following conditions. The pipe length is 7.5m.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat
higher due to ambient conditions.(4) Slect the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
(2) Outdoor units
- 217 -
'19 • PAC-DB-308D
PJF000Z589 B
ModelItem
FDC100VSA-W
Power source 3 Phase 380-415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 10.0 [ 4.0(Min.)-11.2(Max.)]Nominal heating capacity (range) kW 11.2 [ 4.0(Min.)-12.5(Max.)]
Sound power levelCooling
dB(A)
69Heating 70
Sound pressure levelCooling 54Heating 55
Silent mode sound pressure level 48/44 (Normal/Silent)
Exterior dimensions (Height × Width × Depth) mm 845×970×370
Exterior appearance( Munsell color )(RAL color)
Stucco white( 4.2Y7.5/1.1) near equivalent( RAL 7044 ) near equivalent
Net weight kg 78Compressor type & Q'ty RMT5126SWP4×1Compressor motor (Starting method) kW Direct line startRefrigerant oil (Amount, type) L 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Propeller fan ×1Fan motor (Starting method) W 86 < Direct line start >
Air flow Cooling
m3/min75
Heating 73Shock & vibration absorber Rubber sleeve (for fan motor & compressor)Electric heater W 20 (Crank case heater)
Safety equipmentsInternal thermostat for fan motor
Abnormal discharge temperature protection
Installation data
Refrigerant piping size ( O.D. ) mmLiquid line: φ9.52 (3/8") Gas line: φ15.88 (5/8")
Connecting method Flare pipingAttached length of piping m —Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50mVertical height diff. between O/U and I/U m Max.50m (Outdoor unit is higher) Max.15m (Outdoor unit is lower)Drain hose Hole size φ20 × 3 pcs
IP number IP24Standard accessories —Option parts —
Notes (1) The data are measured at the following conditions. The pipe length is 7.5m.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat
higher due to ambient conditions.(4) Slect the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 218 -
'19 • PAC-DB-308D
PJF000Z589 B
ModelItem
FDC125VNA-W
Power source 1 Phase 220-240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 12.5 [ 5.0(Min.)-14.0(Max.)]Nominal heating capacity (range) kW 14.0 [ 4.0(Min.)-16.0(Max.)]
Sound power levelCooling
dB(A)
71Heating
Sound pressure levelCooling 54Heating 56
Silent mode sound pressure level 48/45 (Normal/Silent)
Exterior dimensions (Height × Width × Depth) mm 845×970×370
Exterior appearance( Munsell color )(RAL color)
Stucco white( 4.2Y7.5/1.1) near equivalent( RAL 7044 ) near equivalent
Net weight kg 77Compressor type & Q'ty RMT5126SWP3×1Compressor motor (Starting method) kW Direct line startRefrigerant oil (Amount, type) L 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Propeller fan ×1Fan motor (Starting method) W 86 < Direct line start >
Air flow Cooling
m3/min75
Heating 73Shock & vibration absorber Rubber sleeve (for fan motor & compressor)Electric heater W 20 (Crank case heater)
Safety equipmentsInternal thermostat for fan motor
Abnormal discharge temperature protection
Installation data
Refrigerant piping size ( O.D. ) mmLiquid line: φ9.52 (3/8") Gas line: φ15.88 (5/8")
Connecting method Flare pipingAttached length of piping m —Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50mVertical height diff. between O/U and I/U m Max.50m (Outdoor unit is higher) Max.15m (Outdoor unit is lower)Drain hose Hole size φ20 × 3 pcs
IP number IP24Standard accessories —Option parts —
Notes (1) The data are measured at the following conditions. The pipe length is 7.5m.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat
higher due to ambient conditions.(4) Slect the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 219 -
'19 • PAC-DB-308D
PJF000Z589 B
ModelItem
FDC125VSA-W
Power source 3 Phase 380-415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 12.5 [ 5.0(Min.)-14.0(Max.)]Nominal heating capacity (range) kW 14.0 [ 4.0(Min.)-16.0(Max.)]
Sound power levelCooling
dB(A)
71Heating
Sound pressure levelCooling 54Heating 56
Silent mode sound pressure level 48/45 (Normal/Silent)
Exterior dimensions (Height × Width × Depth) mm 845×970×370
Exterior appearance( Munsell color )(RAL color)
Stucco white( 4.2Y7.5/1.1) near equivalent( RAL 7044 ) near equivalent
Net weight kg 78Compressor type & Q'ty RMT5126SWP4×1Compressor motor (Starting method) kW Direct line startRefrigerant oil (Amount, type) L 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Propeller fan ×1Fan motor (Starting method) W 86 < Direct line start >
Air flow Cooling
m3/min75
Heating 73Shock & vibration absorber Rubber sleeve (for fan motor & compressor)Electric heater W 20 (Crank case heater)
Safety equipmentsInternal thermostat for fan motor
Abnormal discharge temperature protection
Installation data
Refrigerant piping size ( O.D. ) mmLiquid line: φ9.52 (3/8") Gas line: φ15.88 (5/8")
Connecting method Flare pipingAttached length of piping m —Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50mVertical height diff. between O/U and I/U m Max.50m (Outdoor unit is higher) Max.15m (Outdoor unit is lower)Drain hose Hole size φ20 × 3 pcs
IP number IP24Standard accessories —Option parts —
Notes (1) The data are measured at the following conditions. The pipe length is 7.5m.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat
higher due to ambient conditions.(4) Slect the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 220 -
'19 • PAC-DB-308D
PJF000Z589 B
ModelItem
FDC140VNA-W
Power source 1 Phase 220-240V 50Hz / 220V 60Hz
Operation data
Nominal cooling capacity (range) kW 13.6 [ 5.0(Min.)-14.5(Max.)]Nominal heating capacity (range) kW 15.5 [ 4.0(Min.)-16.5(Max.)]
Sound power levelCooling
dB(A)
72Heating 73
Sound pressure levelCooling 56Heating 58
Silent mode sound pressure level 49/45 (Normal/Silent)
Exterior dimensions (Height × Width × Depth) mm 845×970×370
Exterior appearance( Munsell color )(RAL color)
Stucco white( 4.2Y7.5/1.1) near equivalent( RAL 7044 ) near equivalent
Net weight kg 77Compressor type & Q'ty RMT5126SWP3×1Compressor motor (Starting method) kW Direct line startRefrigerant oil (Amount, type) L 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Propeller fan ×1Fan motor (Starting method) W 86 < Direct line start >
Air flow Cooling
m3/min75
Heating 73Shock & vibration absorber Rubber sleeve (for fan motor & compressor)Electric heater W 20 (Crank case heater)
Safety equipmentsInternal thermostat for fan motor
Abnormal discharge temperature protection
Installation data
Refrigerant piping size ( O.D. ) mmLiquid line: φ9.52 (3/8") Gas line: φ15.88 (5/8")
Connecting method Flare pipingAttached length of piping m —Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50mVertical height diff. between O/U and I/U m Max.50m (Outdoor unit is higher) Max.15m (Outdoor unit is lower)Drain hose Hole size φ20 × 3 pcs
IP number IP24Standard accessories —Option parts —
Notes (1) The data are measured at the following conditions. The pipe length is 7.5m.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat
higher due to ambient conditions.(4) Slect the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 221 -
'19 • PAC-DB-308D
PJF000Z589 B
ModelItem
FDC140VSA-W
Power source 3 Phase 380-415V 50Hz / 380V 60Hz
Operation data
Nominal cooling capacity (range) kW 13.6 [ 5.0(Min.)-14.5(Max.)]Nominal heating capacity (range) kW 15.5 [ 4.0(Min.)-16.5(Max.)]
Sound power levelCooling
dB(A)
72Heating 73
Sound pressure levelCooling 56Heating 58
Silent mode sound pressure level 49/45 (Normal/Silent)
Exterior dimensions (Height × Width × Depth) mm 845×970×370
Exterior appearance( Munsell color )(RAL color)
Stucco white( 4.2Y7.5/1.1) near equivalent( RAL 7044 ) near equivalent
Net weight kg 82Compressor type & Q'ty RMT5126SWP4×1Compressor motor (Starting method) kW Direct line startRefrigerant oil (Amount, type) L 0.9 (M-MB75)Refrigerant (Type, amount, pre-charge length) kg R32 3.3 in outdoor unit (Incl. the amount for the piping of 30m)Heat exchanger M shape fin & inner grooved tubingRefrigerant control Electronic expansion valveFan type & Q'ty Propeller fan ×1Fan motor (Starting method) W 86 < Direct line start >
Air flow Cooling
m3/min75
Heating 73Shock & vibration absorber Rubber sleeve (for fan motor & compressor)Electric heater W 20 (Crank case heater)
Safety equipmentsInternal thermostat for fan motor
Abnormal discharge temperature protection
Installation data
Refrigerant piping size ( O.D. ) mmLiquid line: φ9.52 (3/8") Gas line: φ15.88 (5/8")
Connecting method Flare pipingAttached length of piping m —Insulation for piping Necessary (both Liquid & Gas lines)Refrigerant line (one way) length m Max.50mVertical height diff. between O/U and I/U m Max.50m (Outdoor unit is higher) Max.15m (Outdoor unit is lower)Drain hose Hole size φ20 × 3 pcs
IP number IP24Standard accessories —Option parts —
Notes (1) The data are measured at the following conditions. The pipe length is 7.5m.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat
higher due to ambient conditions.(4) Slect the breaker size according to the own national standard.(5) The operation data indicate when the air-conditioner is operated at 400V 50Hz or 380V 60Hz.
ItemOperation
Indoor air temperature Outdoor air temperatureStandards
DB WB DB WBCooling 27˚C 19˚C 35˚C 24˚C ISO5151-T1Heating 20˚C — 7˚C 6˚C ISO5151-H1
- 222 -
'19 • PAC-DB-308D
Cooling power consumptionHeating power consumptionCooling running currentHeating running currentInrush current (L.R.A) <Max. running current>
(220-240V 50Hz/220V 60Hz)
Item Model FDC125VNA-W FDC140VNA-W
kW
A
A 5 <24>
FDC100VNA-W3.02/3.022.89/2.89
13.6-13.0/13.613.0-12.4/13.0
4.00/4.003.38/3.38
17.6-16.8/17.614.8-14.0/14.8
4.59/4.594.06/4.06
20.3-19.3/20.317.8-17.0/17.8
Cooling power consumptionHeating power consumptionCooling running currentHeating running currentInrush current (L.R.A) <Max. running current>
(380-415V 50Hz/380V 60Hz)
Item Model FDC100VSA-W FDC125VSA-W FDC140VSA-W
kW
A
A
3.02/3.022.89/2.89
4.5-4.3/4.54.3-4.1/4.3
4.00/4.003.38/3.38
5.9-5.6/5.95.0-4.7/5.0
5 <15>
4.59/4.594.06/4.066.8-6.4/6.86.0-5.7/6.0
(3) Operation chart The V Multi is a system that allows for different models and capacities of indoor units to be connected so the individual operating characteristics of the indoor and outdoor are provided. Use the procedure shown in item (c) to calculate the combined operating characteristics.
(a) Operating characteristic of outdoor unit
Note(1) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 “UNITARY AIR-CONDITIONERS”
(b) Operating characteristic of indoor unit
Notes(1) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 “UNITARY AIR-CONDITIONERS” Notes(2) The values shown in the above table are common to both cooling and heating operations.
ModelItem FDT50VH FDT60VH FDT71VH
Cooling power consumptionkW
0.04-0.04/0.04 0.07-0.07/0.07 0.08-0.08/0.08Heating power consumption 0.04-0.04/0.04 0.07-0.07/0.07 0.08-0.08/0.08Cooling running current
A0.36-0.33/0.36 0.62-0.57/0.62 0.70-0.64/0.70
Heating running current 0.36-0.33/0.36 0.62-0.57/0.62 0.70-0.64/0.70
FDT Series (220-240V 50Hz/220V 60Hz)
ModelItem FDE50VH FDE60VH FDE71VH
Cooling power consumptionkW
0.05-0.05/0.05 0.08-0.08/0.08Heating power consumption 0.05-0.05/0.05 0.08-0.08/0.08Cooling running current
A0.50-0.50/0.50 0.75-0.75/0.75
Heating running current 0.50-0.50/0.50 0.75-0.75/0.75
0.08-0.08/0.080.08-0.08/0.080.75-0.75/0.750.75-0.75/0.75
FDE Series (220-240V 50Hz/220V 60Hz)
- 223 -
'19 • PAC-DB-308D
(c) Calculation of total operation characteristics Since the operation characteristics of V Multi system depend on combination of indoor unit, calculate the total operation characteristics of the system by using the formulas below according to speciations of each indoor unit or outdoor unit. (i) 1 Phase models 1) Total power consumption Total power consumption (kW) = Power consumption of outdoor unit + ∑ (Power consumption of indoor unit)
2) Total running current Total running current (A) = Running current of outdoor unit + ∑ (Running current of indoor unit)
3) Total power factor Total power factor (%) = [Total power consumption (W) / Total running current (A) × Power source] × 100
Total operation characteristics = Operation characteristic value of outdoor unit + Operation characteristic value of indoor unit
[Example]
(Conditions) Operation voltage ········· Indoor unit: 220 V, 50 Hz
Outdoor unit: 220 V, 50 Hz
Operation mode ··········· Cooling and Heating
Unit······························· Outdoor unit: FDC140VNA-W × 1 unit
Indoor unit: FDT71VH × 2 units
Item Model FDC140VNA-W FDT71VH
Operation characteristics of each unit (Cooling/Heating)
Power consumption (kW)
Running current (A)
0.08/0.08
0.70/0.70
4.59/4.06
20.3/17.8
① Total power consumption (kW)
(Cooling) 4.59 + (0.08 × 2) = 4.75
(Heating) 4.06 + (0.08 × 2) = 4.22
② Total running current (A)
(Cooling) 20.3 + (0.70 × 2) = 21.7
(Heating) 17.8 + (0.70 × 2) = 19.2
③ Total power factor (%)
(Cooling) × 100 = 99 %
(Heating) × 100 = 99 %
4.75 × 100021.7 × 220
4.22 × 100019.2 × 220
. .
. .
(ii) 3 Phase models 1) Total power consumption Total power consumption (kW) = Power consumption of outdoor unit + ∑ (Power consumption of indoor unit)
2) Total running current Total running current (A) = Running current of outdoor unit + [∑ (Running current of indoor unit) × 1/3]
3) Total power factor Total power factor (%) = [Total power consumption (W) / √ × Total running current (A) × Power source] × 100
Total operation characteristics = Operation characteristic value of outdoor unit + Operation characteristic value of indoor
unit
3
- 224 -
'19 • PAC-DB-308D
[Example]
(Conditions) Operation voltage ········ Indoor unit: 220 V, 50 Hz
Outdoor unit: 380 V, 50 Hz
Operation mode ··········· Cooling and Heating
Unit······························· Outdoor unit: FDC125VSA-W × 1 unit
Indoor unit: FDT50VH × 1 unit, FDT71VH × 1 unit
Item Model FDC125VSA-W FDT50VH FDT71VH
Operation characteristics of each unit (Cooling/Heating)
Power consumption (kW)
Running current (A)
0.04/0.04
0.36/0.36
0.08/0.08
0.70/0.70
4.00/3.38
5.9/5.0
① Total power consumption (kW)
(Cooling) 4.00 + 0.04 + 0.08 = 4.12 (kW)
(Heating) 3.38 + 0.04 + 0.08 = 3.50 (kW)
② Total running current (A)
(Cooling) 5.9 + [(0.36 + 0.70) × )] = 6.3 (A)
(Heating) 5.0 + [(0.36 + 0.70) × )] = 5.4 (A)
31
③ Total power factor (%)
(Cooling) × 100 = 99 %
(Heating) × 100 = 98 %
4.12 × 10003 × 6.3 × 380
. .
. .
. .
. .
3.50 × 10003 × 5.4 × 380
31
- 225 -
'19 • PAC-DB-308D
2.3 EXTERIOR DIMENSIONS (1) Indoor units (a) Ceiling cassette-4 way type (FDT) .............................................................See page 67 (b) Ceiling suspended type (FDE) ...................................................................See page 74 (2) Outdoor units .............................................................................................See page 79 (3) Remote control (Option parts) ...................................................................See page 80 2.4 ELECTRICAL WIRING (1) Indoor units (a) Ceiling cassette-4 way type (FDT) .........................................................See page 83 (b) Ceiling suspended type (FDE) ................................................................See page 89 (2) Outdoor units ..............................................................................................See page 92 2.5 TECHNICAL INFORMATION (1) Ceiling cassette-4 way type (FDT) ............................................................See page 118 (2) Ceiling suspended type (FDE) .................................................................See page 190
HYPER INVERTER PACKAGED AIR-CONDITIONERS(Split system, Air to air heat pump type)
Twin type FDTC71VNXPVD FDTC100VNXPVD FDTC100VSXPVD FDTC125VNXPVD FDTC125VSXPVD
Triple type FDTC140VNXTVD FDTC140VSXTVD
CEILING CASSETTE- 4 WAY COMPACT TYPESingle type FDUM71VNXVD FDUM100VNXVD FDUM100VSXVD FDUM125VNXVD FDUM125VSXVD FDUM140VNXVD FDUM140VSXVD
Twin type FDUM100VNXPVD FDUM100VSXPVD FDUM125VNXPVD FDUM125VSXPVD FDUM140VNXPVD FDUM140VSXPVD
Triple type FDUM140VNXTVD FDUM140VSXTVD
DUCT CONNECTED-LOW/MIDDLE STATIC PRESSURE TYPE
Single type FDU71VNXVD FDU100VNXVD FDU100VSXVD FDU125VNXVD FDU125VSXVD FDU140VNXVD FDU140VSXVD
DUCT CONNECTED-HIGH STATIC PRESSURE TYPESingle type FDT71VNXVD FDT100VNXVD FDT100VSXVD FDT125VNXVD FDT125VSXVD FDT140VNXVD FDT140VSXVD
Twin type SRK100VNXPZIX SRK100VNXPZJX SRK100VSXPZIX SRK100VSXPZJX SRK125VNXPZIX SRK125VNXPZJX SRK125VSXPZIX SRK125VSXPZJX
Triple type SRK140VNXTZIX SRK140VNXTZJX SRK140VSXTZIX SRK140VSXTZJX
WALL MOUNTED TYPE
Twin type FDT71VNXPVD FDT100VNXPVD FDT100VSXPVD FDT125VNXPVD FDT125VSXPVD FDT140VNXPVD FDT140VSXPVD
Triple type FDT140VNXTVD FDT140VSXTVD
CEILING CASSETTE- 4 WAY TYPE
Single type FDEN71VNXVD FDEN100VNXVD FDEN100VSXVD FDEN125VNXVD FDEN125VSXVD FDEN140VNXVD FDEN140VSXVD
Twin type FDEN71VNXPVD FDEN100VNXPVD FDEN100VSXPVD FDEN125VNXPVD FDEN125VSXPVD FDEN140VNXPVD FDEN140VSXPVD
Triple type FDEN140VNXTVD FDEN140VSXTVD
CEILING SUSPENDED TYPE
Manual No. '10 • PAC - DB - 136
DATA BOOK
MICRO INVERTER PACKAGED AIR-CONDITIONERS
Air-Conditioning & Refrigeration Systems16-5, Konan 2-chome, Minato-ku, Tokyo, 108-8215 Japanhttp://www.mhi.co.jp
© Copyright MITSUBISHI HEAVY INDUSTRIES, LTD.
Because of our policy of continuous improvement, we reserve the right to make changes in all specifications without notice.
DATA BOOK
Manual No. '09 • PAC - DB -136
DRAFTINVERTER WALL MOUNTED TYPE RESIDENTIAL AIR-CONDITIONERS
HYPER INVERTER PACKAGED AIR-CONDITIONERS(Split system, Air to air heat pump type)
Single type FDT125VNXV 125VSXV 140VNXV 140VSXV
Twin type FDTC125VNXPVB 125VSXPVB
Triple type FDTC140VNXTVB 140VSXTVB
CEILING CASSETTE - 4WAY COMPACT TYPETwin type SRK125VNXPZIX 125VSXPZIX
Triple type SRK140VNXTZIX 140VSXTZIX
WALL MOUNTED TYPE
Twin type FDT125VNXPV 125VSXPV 140VNXPV 140VSXPV
Triple type FDT140VNXTV 140VSXTV
CEILING CASSETTE - 4WAY TYPE
Single type FDUM125VNXV 125VSXV 140VNXV 140VSXV
Twin type FDUM125VNXPV 125VSXPV 140VNXPV 140VSXPV
Triple type FDUM140VNXTV 140VSXTV
DUCT CONNECTED MIDDLE STATIC PRESSURE TYPE
Single type FDU125VNXV 125VSXV 140VNXV 140VSXV
DUCT CONNECTED HIGH STATIC PRESSURE TYPE
Single type FDEN125VNXV 125VSXV 140VNXV 140VSXV 125VNXVA 125VSXVA 140VNXVA 140VSXVA
Twin type FDEN125VNXPV 125VSXPV 140VNXPV 140VSXPV 125VNXPVA 125VSXPVA 140VNXPVA 140VSXPVA
Triple type FDEN140VNXTV 140VSXTV 140VNXTVA 140VSXTVA
CEILING SUSPENDED TYPE
Copyright MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD.Because of our policy of continuous improvement, we reserve the right to make changes in all specifications without notice.
C
MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD.16-5 Konan 2-chome, Minato-ku, Tokyo, 108-8215, Japanhttp://www.mhi-mth.co.jp/en/