Sheet1DANFOSS DRIVE - QUICK USER GUIDE VARIABLE SPEED(NON FEEDBACK) OPERATIONSModel No- FC 360NameSettings-Short NameValue to AssignedValue & its Corresponding State NoteConfiguration Mode1-000open loopTorque characteristics1-031variable torqeRef Range3-000Min-MaxRef Source3-152Reference source is Analog IP-54Motor Low Limit4-125.0 HZ- Low speed limit valueChangeble as per requirements within Motor LimitationsMotor High Limit4-1450.0 HZ High speed limit valueChangeble as per requirements within Motor LimitationsDI 18 Selection 5-108If DI 18 is high then motor will StartDigital Input (PLC Controllable)DI 27 Selection 5-122Coast Inverse24V DC supply to be given to this DI terminal; Without this it may not workAI 54 Low6-224.0maLow Level settings(AI)For Analog I/P channel 54 onlyAI 54 High6-2320maHigh Level settings(AI)For Analog I/P channel 54 onlyAI 54 Mode6-290Current ModeFor Analog I/P channel 54 onlyMotor Data:Motor Power 1-205For 0.37kw- 0.5hpFor other power range setting will changeMotor Voltage1-22

Special Attention:1. Keep the Drive In stop mode while doing settings/modifications