GRUNER AG PF 1149, D-78560 Wehingen Tel. (++49) 74 26 / 948 - 0 Fax (++49) 74 26 / 948 - 200 http://www.gruner.de E-Mail: [email protected] 16/07 · FSOE · Copyright by Gruner AG · Technical changes are reserved Actuator with spring return 5 Nm 20 Nm For the application with Fire dampers Smoke dampers ACTUATOR FOR DAMPERS Fire & Smoke Protection G R U N E R t h e f r i e n d l y a l t e r n a t i v e General overview fire & smoke protection Summary: Actuators for fire & smoke protection Technical characteristics, Type 229, 5 Nm Technical characteristics, Type 239, 20 Nm Your way to Gruner Content: 2 3 4 - 7 8 - 11 12 Page:

Upload: erdinc-klima

Post on 14-May-2015

414 views

Category:

Business


1 download

DESCRIPTION

Damper Servomotorları Gruner d fire-and-sm

TRANSCRIPT

Page 1: Damper Servomotorları Gruner d fire-and-smoke_en

GRUNER AGPF 1149, D-78560 Wehingen

Tel. (++49) 74 26 / 948 - 0Fax (++49) 74 26 / 948 - 200

http://www.gruner.deE-Mail: [email protected]

16/07 · FSOE · Copyright by Gruner AG · Technical changes are reserved

Actuator with spring return

5 Nm

20 Nm

For the application with

Fire dampersSmoke dampers

��� ACTUATOR FOR DAMPERS

F ire & Smoke Protect ion

G R U N E R – t h e f r i e n d l y a l t e r n a t i v e

���

General overview fire & smoke protection

Summary: Actuators for fire & smoke protection

Technical characteristics, Type 229, 5 Nm

Technical characteristics, Type 239, 20 Nm

Your way to Gruner

Content:

2

3

4 - 7

8 - 11

12

Page:

Page 2: Damper Servomotorları Gruner d fire-and-smoke_en

GRUNER AGPF 1149, D-78560 Wehingen

Tel. (++49) 74 26 / 948 - 0Fax (++49) 74 26 / 948 - 200

http://www.gruner.deE-Mail: [email protected]

20/06· FSOE · Copyright by Gruner AG · Technical changes are reserved

��� GENERAL OVERVIEW: FIRE & SMOKE PROTECTION

Applications

● = Standard

❍ = Optional

TypeSpring Return

Torque (Actuator)

Torque (Spring)

Angle of Rotation

ControlOn/Off

Power Supply24 VAC/DC

230 VAC

OptionsAuxiliary switch(es)

Thermal Tripping Device

(72°C)

Thermal Tripping Device

for Duct Mounting (72°C)

229●

5 Nm (ca. 1 m2)

4 Nm

100°

239●

20 Nm (ca. 4 m2)

15 Nm

100°

Fire Protection

���

2

Motorised control of fire and smoke dampers in

HVAC systems.

All actuators correspond to the DIN-VDE standards

and CE guidelines.

Page 3: Damper Servomotorları Gruner d fire-and-smoke_en

GRUNER AGPF 1149, D-78560 Wehingen

Tel. (++49) 74 26 / 948 - 0Fax (++49) 74 26 / 948 - 200

http://www.gruner.deE-Mail: [email protected]

16/07 · FSOE · Copyright by Gruner AG · Technical changes are reserved

��� SUMMARY: ACTUATORS FOR FIRE & SMOKE PROTECTION

TypeTorque (Actuator)

Torque (Spring)

On/Off Control

Angle of Rotation

Power Supply24 VAC/DC

230 VAC

OptionsThernal Tripping Device

(72°C)

Thernal Tripping Device

for Duct Mounting (72°C)

Auxiliary switch(es)

Page

5 Nm

4 Nm

100°

4

5 Nm

4 Nm

100°

4

5 Nm

4 Nm

100°

6

229-

024-

05-S

2

229T

A-024

-05-

S2

229-

230-

05-S

2● = Standard

❍ = Optional

3

Actuators typ 239 dispose of the manual override option by crank. Actuators according to US standard available upon demand.

5 Nm

4 Nm

100°

6

229T

A-230

-05-

S2

239-

024-

20-S

2

20 Nm

15 Nm

100°

8

239T

-024

-20-

S2

20 Nm

15 Nm

100°

8

239T

A-024

-20-

S2

20 Nm

15 Nm

100°

8

239-

230-

20-S

2

20 Nm

15 Nm

100°

10

239T

-230

-20-

S2

20 Nm

15 Nm

100°

10

239T

A-230

-20-

S2

20 Nm

15 Nm

100°

10

Important NoteThe modification and mounting of the actuator to the fire damper is made by the manufacturer of the damper. For this reason the spring-return actuator

is only supplied directly to manufacturers of fire dampers. The manufacturer then bears overall responsibility for proper functioning of the damper.

���

Page 4: Damper Servomotorları Gruner d fire-and-smoke_en

GRUNER AGPF 1149, D-78560 Wehingen

Tel. (++49) 74 26 / 948 - 0Fax (++49) 74 26 / 948 - 200

http://www.gruner.deE-Mail: [email protected]

16/07 · FSOE · Copyright by Gruner AG · Technical changes are reserved

��� 229-024-05-S2, 229TA-024-05-S2

229-024-05-S2

1 2 3

S1

4 5 6

S2

BUBN

229TA-024-05-S2

Applications

1 2 3

S1

4 5 6

S2

BUBN

TF1 TF2

TA

Connection scheme Connection scheme

���

To regulate fire and smoke dampers in HVAC

systems:

• Form-locking steel drive

• Torque 5 Nm / 4 Nm

• Angle of rotation 100°

• Hold safe position in case of high temperature

• no manual operation and position fixing

• reliable safe postion

• Electromagnetic compatibility controlled

4

Technical Characteristics

Control

Connecting voltage

Power consumption

Transformer sizing

Angle of rotation

Direction of rotation

Running time (90°)

Torque

Auxiliary switches

Switching power Auxiliary switches

Connection

Safety class

Protection

Dimensions

Ambient temperature

Maintenance

CE

Weight

On/Off

24 VAC (50/60 Hz) / DC ± 20%

Motion: 5.0 W / Power safe mode: 3.0 W

6.5 VA

100° (-5°...+95°)

can be selected by mounting back to front

Actuator: < 40...75 s / Spring: < 20 s

Actuator: 5 Nm / Spring: 4 Nm

2, position fixed to 5° and 80°

250 VAC / 5.0 (2.5) A, change-over switch

Cable 900 mm / 0.75 mm2

III

IP54 (Cable downwards)

158 x 66 x 61 mm

-30°C...+50°C

maintenance-free

73/23/EWG, 89/336/EWG

1,100 g

Page 5: Damper Servomotorları Gruner d fire-and-smoke_en

GRUNER AGPF 1149, D-78560 Wehingen

Tel. (++49) 74 26 / 948 - 0Fax (++49) 74 26 / 948 - 200

http://www.gruner.deE-Mail: [email protected]

16/07 · FSOE · Copyright by Gruner AG · Technical changes are reserved

��� 229-024-05-S2, 229TA-024-05-S2

Technical drawing

BU, BN

TA

1,2,3,4,5,6

66.00±1.00

93.00±0.50

157.00±1.00

R65.00

R11.00

48.5082.50

11.00

6.00

52.00

R2.00

12.20

12.20

,8,2

0

,4,6

1

61.00±1.00

12.00

66.00

2.002.00

13.0013.00

229-024-05-S2

���

5

Fixing of the shaft

Concentric form locking shaft: ❑ 8...12 mm

Thermal tripping devices (Fig. 1 + 2)

Auxiliary switches

The actuator has two position fixed auxiliary switches for indicating the damper postion. The position of

the damper can be read on the scale on front of the actuator.

Self test

Duct temperature

Ambient temperature

If 72°C are reached the actuator turns the damper back to its safe position.

Version

TA

Yes

Yes

Yes

66.0

0±1.

002.

0027

.60

Ø9.00

40.0

050

.00

50.00

2.8...Ø3

20.0

020

.00

107.

00±

2.00

2.8...Ø3

9.5...Ø10

2 Thermal tripping device TA

1

Page 6: Damper Servomotorları Gruner d fire-and-smoke_en

GRUNER AGPF 1149, D-78560 Wehingen

Tel. (++49) 74 26 / 948 - 0Fax (++49) 74 26 / 948 - 200

http://www.gruner.deE-Mail: [email protected]

16/07 · FSOE · Copyright by Gruner AG · Technical changes are reserved

��� 229-230-05-S2, 229TA-230-05-S2

229-230-05-S2

1 2 3

S1

4 5 6

S2

BUBN

NL

229TA-230-05-S2

Applications

1 2 3

S1

4 5 6

S2

BUBN

TF1 TF2

TA

NL

Connection scheme Connection scheme

���

To regulate fire and smoke dampers in HVAC

systems:

• Form-locking steel drive

• Torque 5 Nm / 4 Nm

• Angle of rotation 100°

• Hold safe position in case of high temperature

• no manual operation and position fixing

• reliable safe postion

• Electromagnetic compatibility controlled

6

Technical Characteristics

Control

Connecting voltage

Power consumption

Transformer sizing

Angle of rotation

Direction of rotation

Running time (90°)

Torque

Auxiliary switches

Switching power Auxiliary switches

Connection

Safety class

Protection

Dimensions

Ambient temperature

Maintenance

CE

Weight

On/Off

230 VAC (50/60 Hz) ± 15%

Motion: 5.0 W / Power safe mode: 2.5 W

5.5 VA

100° (-5°...+95°)

can be selected by mounting back to front

Actuator: < 40...75 s / Spring: < 20 s

Actuator: 5 Nm / Spring: 4 Nm

2, position fixed to 5° and 80°

250 VAC / 5.0 (2.5) A, change-over switch

Cable 900 mm / 0.75 mm2

II

IP54 (Cable downwards)

158 x 66 x 61 mm

-30°C...+50°C

maintenance-free

73/23/EWG, 89/336/EWG

1,100 g

Page 7: Damper Servomotorları Gruner d fire-and-smoke_en

GRUNER AGPF 1149, D-78560 Wehingen

Tel. (++49) 74 26 / 948 - 0Fax (++49) 74 26 / 948 - 200

http://www.gruner.deE-Mail: [email protected]

16/07 · FSOE · Copyright by Gruner AG · Technical changes are reserved

��� 229-230-05-S2, 229TA-230-05-S2

Technical drawing

BU, BN

TA

1,2,3,4,5,6

66.00±1.00

93.00±0.50

157.00±1.00

R65.00

R11.00

48.5082.50

11.00

6.00

52.00

R2.00

12.20

12.20

,8,2

0

,4,6

1

61.00±1.00

12.00

66.00

2.002.00

13.0013.00

229-230-05-S2

���

7

Fixing of the shaft

Concentric form locking shaft: ❑ 8...12 mm

Thermal tripping devices (Fig. 1 + 2)

Auxiliary switches

The actuator has two position fixed auxiliary switches for indicating the damper postion. The position of

the damper can be read on the scale on front of the actuator.

Self test

Duct temperature

Ambient temperature

If 72°C are reached the actuator turns the damper back to its safe position.

Version

TA

Yes

Yes

Yes

66.0

0±1.

002.

0027

.60

Ø9.00

40.0

050

.00

50.00

2.8...Ø3

20.0

020

.00

107.

00±

2.00

2.8...Ø3

9.5...Ø10

2 Thermal tripping device TA

1

Page 8: Damper Servomotorları Gruner d fire-and-smoke_en

GRUNER AGPF 1149, D-78560 Wehingen

Tel. (++49) 74 26 / 948 - 0Fax (++49) 74 26 / 948 - 200

http://www.gruner.deE-Mail: [email protected]

16/07 · FSOE · Copyright by Gruner AG · Technical changes are reserved

��� 239-024-20-S2, 239T-024-20-S2, 239TA-024-20-S2

239-024-20-S2

1 2 3

S1

4 5 6

S2

BUBN

239T-024-20-S2

Applications

1 2 3

S1

4 5 6

S2

BUBN

TF1

T

239TA-024-20-S2

1 2 3

S1

4 5 6

S2

BUBN

TF1 TF2

TA

Connection scheme Connection scheme Connection scheme

���

To regulate fire and smoke dampers in HVAC

systems:

• Form-locking steel drive

• Torque 20 Nm / 15 Nm

• Angle of rotation 100°

• Hold safe position in case of high temperature

• manual operation and position fixing

• reliable safe postion

• Electromagnetic compatibility controlled

8

Technical Characteristics

Control

Connecting voltage

Power consumption

Transformer sizing

Angle of rotation

Direction of rotation

Running time (90°)

Torque

Auxiliary switches

Switching power Auxiliary switches

Connection

Safety class

Protection

Dimensions

Ambient temperature

Maintenance

CE

Weight

On/Off

24 VAC (50/60 Hz) / DC ± 20%

Motion: 6.5 W / Power safe mode: 4,0 W

10 VA

100° (-5°...+95°)

can be selected by mounting back to front

Actuator: 150 s / Spring: < 20 s

Actuator: 20 Nm / Spring: 15 Nm

2, position fixed to 5° and 80°

250 VAC / 5.0 (2.5) A, change-over switch

Cable 900 mm / 0.75 mm2

III

IP54 (Cable downwards)

250 x 98 x 58 mm

-30°C...+50°C

maintenance-free

73/23/EWG, 89/336/EWG

2,500 g

Page 9: Damper Servomotorları Gruner d fire-and-smoke_en

GRUNER AGPF 1149, D-78560 Wehingen

Tel. (++49) 74 26 / 948 - 0Fax (++49) 74 26 / 948 - 200

http://www.gruner.deE-Mail: [email protected]

16/07 · FSOE · Copyright by Gruner AG · Technical changes are reserved

��� 239-024-20-S2, 239T-024-20-S2, 239TA-024-20-S2

Technical drawing

149

250

10

365

67

9880

Ø6(6x)

R12

582

2

43

15

24

80°

Motor

S1, S2

1, 2, 3, 4, 5, 6

bl, br

27

239-024-20-S2

���

9

Fixing of the shaft

Concentric form locking shaft: ❑ 8...12 mm

Auxiliary switches

The actuator has two position fixed auxiliary switches for indicating the damper postion. The position of

the damper can be read on the scale on front of the actuator.

66.0

0±1.

002.

0027

.60

Ø9.00

40.0

050

.00

50.00

2.8...Ø3

20.0

020

.00

107.

00±

2.00

2.8...Ø3

9.5...Ø10

2 Thermal tripping device TA

Thermal tripping devices (Fig. 1 + 2)

Self test

Duct temperature

Ambient temperature

If 72°C are reached the actuator turns the damper back to its safe position.

Version

TA

Yes

Yes

Yes

Version

T

No

No

Yes

1

Page 10: Damper Servomotorları Gruner d fire-and-smoke_en

GRUNER AGPF 1149, D-78560 Wehingen

Tel. (++49) 74 26 / 948 - 0Fax (++49) 74 26 / 948 - 200

http://www.gruner.deE-Mail: [email protected]

16/07 · FSOE · Copyright by Gruner AG · Technical changes are reserved

��� 239-230-20-S2, 239T-230-20-S2, 239TA-230-20-S2

239-230-20-S2

1 2 3

S1

4 5 6

S2

BUBN

NL

239T-230-20-S2

Applications

1 2 3

S1

4 5 6

S2

BUBN

TF1

T

NL

239TA-230-20-S2

1 2 3

S1

4 5 6

S2

BUBN

TF1 TF2

TA

NL

Connection scheme Connection scheme Connection scheme

���

To regulate fire and smoke dampers in HVAC

systems:

• Form-locking steel drive

• Torque 20 Nm / 15 Nm

• Angle of rotation 100°

• Hold safe position in case of high temperature

• manual operation and position fixing

• reliable safe postion

• Electromagnetic compatibility controlled

10

Technical Characteristics

Control

Connecting voltage

Power consumption

Transformer sizing

Angle of rotation

Direction of rotation

Running time (90°)

Torque

Auxiliary switches

Switching power Auxiliary switches

Connection

Safety class

Protection

Dimensions

Ambient temperature

Maintenance

CE

Weight

On/Off

230 VAC (50/60 Hz) ± 15%

Motion: 9.0 W / Power safe mode: 7,0 W

10.0 VA

100° (-5°...+95°)

can be selected by mounting back to front

Actuator: 150 s / Spring: < 20 s

Actuator: 20 Nm / Spring: 15 Nm

2, position fixed to 5° and 80°

250 VAC / 5.0 (2.5) A, change-over switch

Cable 900 mm / 0.75 mm2

II

IP54 (Cable downwards)

250 x 98 x 58 mm

-30°C...+50°C

maintenance-free

73/23/EWG, 89/336/EWG

2,500 g

Page 11: Damper Servomotorları Gruner d fire-and-smoke_en

GRUNER AGPF 1149, D-78560 Wehingen

Tel. (++49) 74 26 / 948 - 0Fax (++49) 74 26 / 948 - 200

http://www.gruner.deE-Mail: [email protected]

16/07 · FSOE · Copyright by Gruner AG · Technical changes are reserved

��� 239-230-20-S2, 239T-230-20-S2, 239TA-230-20-S2

Technical drawing

149

250

10

365

67

9880

Ø6(6x)

R12

582

2

43

15

24

80°

Motor

S1, S2

1, 2, 3, 4, 5, 6

bl, br

27

239-230-20-S2

���

11

Fixing of the shaft

Concentric form locking shaft: ❑ 8...12 mm

Thermal tripping devices (Fig. 1 + 2)

Auxiliary switches

The actuator has two position fixed auxiliary switches for indicating the damper postion. The position of

the damper can be read on the scale on front of the actuator.

Self test

Duct temperature

Ambient temperature

If 72°C are reached the actuator turns the damper back to its safe position.

Version

TA

Yes

Yes

Yes

66.0

0±1.

002.

0027

.60

Ø9.00

40.0

050

.00

50.00

2.8...Ø3

20.0

020

.00

107.

00±

2.00

2.8...Ø3

9.5...Ø10

2 Thermal tripping device TA

Version

T

No

No

Yes

1

Page 12: Damper Servomotorları Gruner d fire-and-smoke_en

GRUNER AGPF 1149, D-78560 Wehingen

Tel. (++49) 74 26 / 948 - 0Fax (++49) 74 26 / 948 - 200

http://www.gruner.deE-Mail: [email protected]

16/07 · FSOE · Copyright by Gruner AG · Technical changes are reserved

��� YOUR WAY TO GRUNER

���

���

MünchenStuttgart

Zürich

Singen

Freudenstadt

Wehingen

Offenburg

Strasbourg

Schramberg

Karlsruhe

A81

N3N1

Basel

34

A8

B14

B27

Donaueschingen

B27

Balingen

Tutt l ingen

Spaichingen

B33A5

Rottwei l

Aldingen

Gosheim

Schömberg

DenkingenFrit t l ingen

Freiburg

B31