daikin engineering data split (cooling only) j-series (2015)

62
EDHK011026 J-Series - Cooling Only -

Upload: adam-chan

Post on 31-Jan-2016

255 views

Category:

Documents


53 download

DESCRIPTION

Daikin Engineering Data Split (Cooling Only) J-Series (2015)

TRANSCRIPT

EDHK011026

J-Series

- Cooling Only -

EDHK011026

Room Air Conditioners J-Series 1

Split-SystemRoom Air Conditioners

J-Series

1. Power Supply ..........................................................................................22. Functions.................................................................................................33. Specifications ..........................................................................................44. Dimensions .............................................................................................5

4.1 Indoor Unit................................................................................................54.2 Outdoor Unit .............................................................................................6

5. Wiring Diagrams......................................................................................75.1 Indoor Unit................................................................................................75.2 Outdoor Unit .............................................................................................8

6. Piping Diagrams......................................................................................96.1 Indoor Unit................................................................................................96.2 Outdoor Unit .............................................................................................9

7. Capacity Tables ....................................................................................107.1 Cooling Only...........................................................................................107.2 Capacity Correction Factor by the Length of Refrigerant Piping

(Reference) ............................................................................................11

8. Operation Limit......................................................................................129. Sound Level ..........................................................................................13

9.1 Measuring Location ................................................................................139.2 Octave Band Level .................................................................................14

10.Electric Characteristics..........................................................................1511.Installation Manual ................................................................................16

11.1 Safety Precautions .................................................................................1611.2 50 Class .................................................................................................1711.3 60 Class .................................................................................................26

12.Operation Manual..................................................................................3513.Optional Accessories ............................................................................56

13.1 Option List ..............................................................................................5613.2 Installation Manual .................................................................................57

Cooling Only FTN50JV18FTN60JV18

RN50JV1RN60JV1

Power Supply EDHK011026

1. Power Supply

Note: Power Supply Intake ; Outdoor Unit

Indoor Units Outdoor Units Power Supply

FTN50JV18 RN50JV11 φ, 220 - 230 - 240 V, 50 Hz

FTN60JV18 RN60JV1

2 Room Air Conditioners J-Series

EDHK011026 Functions

2. Functions

Category Functions

FT

N50

/60J

V18

RN

50/6

0JV

1

Category Functions

FT

N50

/60J

V18

RN

50/6

0JV

1

Basic Function Inverter(with Inverter Power Control) — Health & Clean Air-Purifying Filter —

Operation Limit for Cooling (°CDB) 19.4~46 Photocatalytic Deodorizing Filter —

Operation Limit for Heating (°CWB) — Air-Purifying Filter with Photocatalytic Deodorizing Function

PAM Control — Titanium Apatite PhotocatalyticAir-Purifying Filter —

Compressor Oval Scroll Compressor — Air Filter (Prefilter)

Swing Compressor — Wipe-Clean Flat Panel

Rotary Compressor Washable Grille —

Reluctance DC Motor — MOLD PROOF Operation —

Comfortable Airflow

Power-Airflow Flap — Heating Dry Operation —

Power-Airflow Dual FlapsGood-Sleep Cooling Operation —

Timer 24-Hour ON/OFF TIMER

Power-Airflow Diffuser — NIGHT SET Mode

Wide-Angle Louvers Worry Free “Reliability & Durability”

Auto-Restart (after Power Failure)

Vertical Auto-Swing (Up and Down) Self-Diagnosis (Digital, LED) Display

Horizontal Auto-Swing (Right and Left) Wiring Error Check Function —

3-D Airflow Anti-Corrosion Treatment of Outdoor Heat ExchangerCOMFORT AIRFLOW Operation —

Comfort Control Auto Fan Speed Flexibility Multi-Split / Split Type Compatible Indoor Unit —

Indoor Unit Quiet Operation —

NIGHT QUIET Mode (Automatic) — Flexible Voltage Correspondence —

Outdoor Unit Quiet Operation (Manual) — Chargeless 10 m

INTELLIGENT EYE Operation — Either Side Drain (Right or Left)

Quick Warming Function (Preheating Operation) — Power Selection —

Hot-Start Function — Remote Control 5-Rooms Centralized Controller (Option) —

Automatic Defrosting — Remote Control Adaptor(Normal Open-Pulse Contact)(Option)

—Operation Automatic Operation —

Program Dry Operation Remote Control Adaptor (Normal Open Contact) (Option) —

Fan Only

Lifestyle Convenience

New POWERFUL Operation (Non-Inverter) DIII-NET Compatible (Adaptor) (Option) —

Inverter POWERFUL Operation — Remote Controller

Wireless

Priority-Room Setting — Wired (Option) —

COOL/HEAT Mode Lock —

HOME LEAVE Operation —

ECONO Operation —

Indoor Unit ON/OFF Button

Signal Receiving Sign

Temperature Display —

Note: : Holding Functions— : No Functions

Room Air Conditioners J-Series 3

Specifications EDHK011026

3. Specifications50 Hz, 220 V

Note: The data are based on the conditions shown in the table below.

ModelsIndoor Units FTN50JV18 FTN60JV18Outdoor Units RN50JV1 RN60JV1

Capacity (Rated)kW 5.3 6.7

Btu/h 18,090 22,860kcal/h 4,560 5,760

Moisture Removal L/h 2.9 3.9Running Current (Rated) A 7.5 10.2Power Consumption (Rated) W 1,640 2,210Power Factor % 98 98COP (Rated) W/W 3.23 3.03

Piping Connections

Liquid mm φ 6.4 φ 6.4Gas mm φ 12.7 φ 15.9Drain mm φ 18.0 φ 18.0

Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas PipesMax. Interunit Piping Length m 30 30Max. Interunit Height Difference m 20 20Chargeless m 10 10Amount of Additional Charge of Refrigerant g/m 20 20

Indoor Units FTN50JV18 FTN60JV18Front Panel Color White White

Airflow RateH

m³/min (cfm)

17.5 (618) 18.5 (653)M 14.7 (519) 15.1 (533)L 11.9 (420) 11.9 (420)

FanType Cross Flow Fan Cross Flow FanMotor Output W 43 43Speed Steps 5 Steps, Auto 5 Steps, Auto

Air Direction Control Right, Left, Horizontal, Downward Right, Left, Horizontal, DownwardAir Filter Removable / Washable / Mildew Proof Removable / Washable / Mildew ProofRunning Current A 0.2 0.2Power Consumption W 43 43Power Factor % 98 98Temperature Control Microcomputer Control Microcomputer ControlDimensions (H × W × D) mm 290 × 1,050 × 238 290 × 1,050 × 238Packaged Dimensions (H × W × D) mm 337 × 1,147 × 366 337 × 1,147 × 366Weight kg 12 12Gross Weight kg 17 17Operation Sound H / M / L dBA 45 / 40 / 35 47 / 41 / 36

Outdoor Units RN50JV1 RN60JV1Casing Color Ivory White Ivory White

CompressorType Hermetically Sealed Rotary Type Hermetically Sealed Rotary TypeModel RN196VHSMT PN25VAAMTMotor Output W 1,300 1,700

Refrigerant Oil

Type FV50S FV50SCharge L 0.52 0.90

RefrigerantType R-410A R-410ACharge kg 1.6 2.0

Airflow Rate Hm³/min 52.1 53.0

cfm 1,840 1,872

FanType Propeller PropellerMotor Output W 50 65

Running Current (Rated) A 7.3 10.0Power Consumption (Rated) W 1,597 2,167Power Factor % 98 98Starting Current A 33 54Dimensions (H × W × D) mm 735 × 825 × 300 770 × 900 × 320Packaged Dimensions (H × W × D) mm 784 × 960 × 390 900 × 925 × 390Weight kg 48 63Gross Weight kg 55 76Operation Sound H dBA 50 52

Drawing No. C:3D067874B C:3D067875A

Conversion Formulae

kcal/h = kW × 860Btu/h = kW × 3412

cfm = m³/min × 35.3

Cooling Piping Length

Indoor ; 27°CDB / 19°CWB Outdoor ; 35°CDB / 24°CWB 7.5 m

4 Room Air Conditioners J-Series

EDHK011026 Dimensions

4. Dimensions4.1 Indoor Unit

FTN50JV18

FTN60JV18

AIR FLOW (INDOOR)(FOR PERFORMANCE AND MAINTENANCE)

THE MARK (→) SHOWS PIPING DIRECTION

REARREAR 1050LEFT RIGHT

MIN

.30

( SPA

CE

FO

R P

ER

FO

RM

AN

CE

)

(SPACE FOR MAINTENANCE)

MIN.50 MIN.50(SPACE FOR MAINTENANCE) REQUIRED SPACEINCLUDING

INSTALLATION PLATE)(240238

OPERATION LAMP MODEL NAMEPLATESIGNAL RECEIVER

INDOOR UNIT ON/OFFSWITCH 29

0

ROOM TEMP. THERMISTOR(INSIDE)

TERMINAL BLOCK WITHEARTH TERMINAL(INSIDE)

DRAIN HOSE FOR VP13(CONNECTING PART I.D.14.0,O.D.18.0)

GAS PIPE 12.7 CuTTIMER LAMP (THE LENGTH OF PIPE OUTSIDE

THE UNIT: ABOUT 430)HOME LEAVE LAMPFRONT GRILLE FIXING SCREWS(INSIDE)

(THE HOSE LENGTH OF OUTSIDE THE UNIT: ABOUT 530)

FLAPS LIQUID PIPE 6.4 CuT(THE LENGTH OF PIPE OUTSIDE

THE UNIT: ABOUT 480)

1050

SIGNAL TRANSMITTER

BLADE ANGLES 14.5

52.5893.51858 30

HORIZONTAL BLADE(AUTOMATIC)

COOLING DRY

155.

5

290

10˚

163

5˚ 52

10˚40˚ 5˚35˚

40˚35˚

FAN 60 52VERTICAL BLADE(MANUAL) 99.5WALL HOLE φ80 HOLE

5˚ WALL HOLE FOR EMBEDDED PIPINGWIRELESS REMOTE

CONTROLLER φ80 HOLE STANDARD LOCATIONS OF WALL HOLES50˚5˚ 50˚(ARC433A26) 55˚55˚

3D065874B

(ARC433A26)

FAN

MODEL NAMEPLATE

HORIZONTAL BLADE(AUTOMATIC)

BLADE ANGLES

TERMINAL BLOCK WITHEARTH TERMINAL

SIGNALTRANSMITTER

(INSIDE)

COOLING

(INSIDE)

DRY

VERTICAL BLADE (AUTOMATIC)WIRELESS REMOTE

THE MARK (→) SHOWS PIPING DIRECTION

LEFTREAR 1050

INDOOR UNIT ON/OFFSWITCH

OPERATION LAMP

TIMER LAMP

SIGNAL RECEIVER

RIGHT

58

163

18

10˚

40˚ 10˚

40˚

50˚

35˚

50˚

55˚

FLAPS (INSIDE)

CONTROLLER

35˚

55˚

238

290

240

( )INCLUDINGINSTALLATION PLATE

REAR

FRONT GRILLE FIXING SCREWS

ROOM TEMP. THERMISTOR

(SPACE FORMAINTENANCE)

MIN.50 MIN.50

MIN

.30

(SPACE FORMAINTENANCE)

(FOR PERFORMANCE AND MAINTENANCE)

REQUIRED SPACE

(SPA

CE

FO

RP

ER

FO

RM

AN

CE

)AIR FLOW (INDOOR)

GAS PIPE 15.9 CuT

LIQUID PIPE 6.4 CuT

WALL HOLE FOR EMBEDDED PIPING

5214

.5

60

1050

893.5

WALL HOLE

155.

5

52

30

290

STANDARD LOCATIONS OF WALL HOLES

φ80 HOLE

φ80 HOLE

THE UNIT : ABOUT 430)(THE LENGTH OF PIPE OUTSIDE

52.5

(THE LENGTH OF PIPE OUTSIDETHE UNIT : ABOUT 480)

99.5

ABOUT 530)

(CONNECTING PARTI. D. 14.0, O. D. 18.0)

DRAIN HOSE FOR VP13

(THE HOSE LENGTH OFOUTSIDE THE UNIT :

3D059038E

Room Air Conditioners J-Series 5

Dimensions EDHK011026

4.2 Outdoor Unit

RN50JV1

RN60JV1

MINIMUM SPACE FOR AIR PASSAGE WALL HEIGHT ON AIR OUTLET SIDE=LESS THAN 1200

DRAIN OUTLET(I.D.φ15.9 HOSE FOR CONNECTION)

100

78825

325

124 580 100

350

2 50 5036 50

350

300

350

330

100

350

2510

4-HOLES FOR ANCHOR BOLTS(M8 OR M10)

NAME PLATE EARTH TERMINAL IN SWITCH BOXBRAND NAME LABEL WIRING INLET

735

6489

18155

30160LIQUID STOP VALVE(φ6.4CuT) GAS STOP VALVE

(φ12.7CuT)

SERVICE PORT

3D065853D

7

145

223

3

1919

143

4

84

620

70

900

95

142

352

52

55

89

320

329

1

48

4

96

54

376

30

95

16

30

55

5

140

71

6089

40

95

6

55

53

191

102

bolt 4 - M12Hole for anchor

350

45

67

140

58

5

16

2

30

117

6

28 80

4

13

54

770

φ 6.4 Flare

NOTE) 1.ATTACHED PIPING MAY NOT BE ATTACHED WITH A MODEL.

M5(in switch box)

(345

~35

5)

φ 15.9 FlareNO.

4

6

32

7

5

1 Gas pipe connection

Power supply wiring intake

Grounding terminal

Drain pipe connection

Liquid pipe connection

Control wiring intake

Refrigerant piping intake

Parts name

Outside Diameter φ 26 3points

φ 34 knock holeφ 27 knock hole

Remarks3D055315H

6 Room Air Conditioners J-Series

EDHK011026 Wiring Diagrams

5. Wiring Diagrams5.1 Indoor Unit

FTN50/60JV18

MM

2

1

3

3.15AFu

X1M

RECTIFIER

S1W

OUTDOOR

RECEIVERSIGNAL

LED1

H1P H2P

LED2

FIELD WIRING.

INDOOR

7

S32

S21

RED

RE

D

PN

K

5

R2T

H2

M1S

6

BLK

BLU

BLU

YLW

CONTROLLERREMOTE

WIRELESS

1

PCB1

SA1

RE

D

1S28

OR

G

1

FG

S6

S37

S29

YLW

V2

2

YLW

OR

G

3

M2S

S8

RED

H3

M1F

M

R1T

WHT

PCB4

S1

/

ORG

V1

BRN

WHT

PCB3

PCB2

1

BLU

S38

GRN

H1

MR2

BR

N

S27 S26

PN

K

~ ~

FGFu

H1P, H2PM1FM1S, M2S

PCB1~PCB4R1T, R2TS1~S38S1W

X1M

: SWING MOTOR

: THERMISTOR

: PROTECTIVE EARTH

THE MAIN POWER SUPPLY IS

ON AGAIN.TURNED OFF AND THEN BACK

NOTE THAT OPERATION WILLRESTART AUTOMATICALLY IF

CAUTION

: FRAME GROUND: FUSE

: PILOT LAMP: FAN MOTOR

: PRINTED CIRCUIT BOARD

: CONNECTOR: OPERATION SWITCH

: TERMINAL STRIP

MR2 : MAGNETIC RELAY

SA1 : SURGE ARRESTERV1, V2 : VARISTOR

H1~H3 : HARNESS

3D058895D

Room Air Conditioners J-Series 7

Wiring Diagrams EDHK011026

5.2 Outdoor Unit

RN50JV1

RN60JV1

FIELD WIRING

indoor

TO INDOOR UNIT X1M

outdoor

1 2 CBLURED11M

B1B2 1~RED YLWS3 4 A2 A122 REDREDRC11R

M1CRE

D5 6BLK33 S1TG

RN

/YLW

L3.15A W

HT

HBLKRED A1 A2L

6BLKF1UL t° BLKBLK

LRE

D

ORG 4CK1MV1R MBLK

BLK

NN ORGH4 1~1

3WHT RED4 3 RED2 3 12 1 WHT

X2M WHTM1F

C12RGRN/YLW BLKF1S X11A

POWER SUPPLY~ 50Hz220V-240V

S1T

L

N

: THERMOSTAT

: LIVE

: NEUTRAL

M1F

M1C

X11A

X1M, X2M

: FAN MOTOR

: COMPRESSOR MOTOR

: CONNECTOR

: TERMINAL STRIP

: PROTECTIVE EARTH

C11R, C12R

F1S

F1U

K1M

V1R

: RUNNING CAPACITOR

: SURGE ARRESTER

: FUSE

: MAGNETIC CONTACTOR

: RECTIFIER

3D066609A

FIELD WIRINGindoor

TO INDOOR UNIT X1M

outdoor

1 2 CBLURED11M

B2B1 1~YLWS3 4 A1 A222

REDRC11R M1C

RE

D

RE

D

5 6BLK33S1T

GR

N/Y

LW

L3.15A W

HT

HRED RED A1 A2L

BLK 6WH

T

F1UL t° BLKBLK

LRE

D

ORGC 4BLK

BLK K1M

V1R MNN ORGH2 4 1~

3WHT 2 REDRED

1 3 11 WHTX2M WHT M1F

C12RGRN/YLW REDF1S X11A

POWER SUPPLY~ 50Hz220V-240V

S1T: RUNNING CAPACITOR : FAN MOTOR

L: SURGE ARRESTER : COMPRESSOR MOTOR

N

: THERMOSTAT

: LIVE

: NEUTRAL: FUSE : CONNECTOR

: MAGNETIC CONTACTOR : TERMINAL STRIP

M1F

M1C

X11A

X1M, X2M

: PROTECTIVE EARTH

C11R, C12R

F1S

F1U

K1M

V1R : RECTIFIER

3D066807B

8 Room Air Conditioners J-Series

EDHK011026 Piping Diagrams

6. Piping Diagrams6.1 Indoor Unit

6.2 Outdoor Unit

FTN50JV18 FTN60JV18

FIELD PIPING

(6.4CuT)

FIELD PIPING

(12.7CuT)

CROSS FLOW FAN

FAN MOTOR

(7.9CuT)

INDOOR UNIT

(12.7CuT)

M

HEAT EXCHANGER

REFRIGERANT FLOW

THERMISTORON HEAT EXCH.

COOLING

4D051010F

INDOOR UNIT

(7.9CuT)

HEAT EXCHANGER

THERMISTORON HEAT EXCH.

CROSS FLOW FANFIELD PIPING

(6.4CuT) MFAN MOTOR

FIELD PIPING

(15.9CuT) (12.7CuT)

REFRIGERANT FLOWCOOLING

4D051016M

RN50JV1 RN60JV1

OUTDOOR UNIT

OUTDOOR TEMPERATUREHEAT EXCHANGERTHERMISTER

6.4CuT

FILT

ER

9.5C

uT

LIQUID STOPVALVEM FIELD PIPING

(6.4CuT)6.4C

uT

6.4CuT

CAPILLARY TUBEPROPELLER FAN

12.7CuT 12.7CuTFIELD PIPING(12.7CuT)

MUFFLER GAS STOP VALVEWITH SERVICE PORT

ACCUMULATOR

COMPRESSOR

REFRIGERANT FLOWCOOLING

4D065584B

OUTDOOR UNIT

HEAT EXCHANGER

6.4C

uT

MUF

FLER

M LIQUID STOPVALVE FIELD PIPING

(6.4CuT)6.4CuTPROPELLER FAN

FILT

ER

CAPILLARY TUBE

MUFFLER15.9CuTFIELD PIPING(15.9CuT)

12.7CuT 12.7CuT

9.5C

uT

GAS STOP VALVEWITH SERVICE PORT

ACCUMULATOR

COMPRESSOR

REFRIGERANT FLOWCOOLING

4D065585B

Room Air Conditioners J-Series 9

Capacity Tables EDHK011026

7. Capacity Tables7.1 Cooling Only

FTN50JV18 + RN50JV1 (50 Hz, 220 V)

3D068368

FTN60JV18 + RN60JV1 (50 Hz, 220 V)

3D068369

AFR 17.5

BF 0.280

INDOOR OUTDOOR TEMPERATURE (°CDB)

EWB EDB 20 25 30 32 35 40

°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

14.0 20 5.43 3.95 1.26 5.18 3.82 1.38 4.94 3.70 1.50 4.84 3.65 1.55 4.69 3.58 1.62 4.44 3.46 1.74

16.0 22 5.67 3.88 1.27 5.43 3.76 1.39 5.18 3.65 1.51 5.08 3.60 1.56 4.93 3.53 1.63 4.69 3.42 1.75

18.0 25 5.92 4.05 1.27 5.67 3.94 1.39 5.42 3.83 1.52 5.33 3.79 1.56 5.18 3.73 1.64 4.93 3.62 1.76

19.0 27 6.04 4.26 1.28 5.79 4.16 1.40 5.55 4.05 1.52 5.45 4.01 1.57 5.30 3.95 1.64 5.05 3.85 1.76

22.0 30 6.41 4.11 1.29 6.16 4.01 1.41 5.91 3.92 1.53 5.81 3.88 1.58 5.67 3.83 1.65 5.42 3.74 1.77

24.0 32 6.65 3.99 1.29 6.40 3.91 1.42 6.16 3.82 1.54 6.06 3.79 1.59 5.91 3.74 1.66 5.66 3.66 1.78

Symbols NOTE:

AFR : Airflow rate (m³/min.) 1. Ratings shown are net capacities which include a deduction for indoor fan motor heat.

2. shows nominal (rated) capacities and power input.3. TC, PI and SHC must be calculated by interpolation using the

figures in the above tables.(Figures out of the tables should not be used for calculation.)

4. About SHC which are not mentioned on the table, please calculate them with around values in direct proportion.

5. Capacities are based on the following conditions.Corresponding refrigerant piping length : 7.5 mLevel difference : 0 m

6. Airflow rate (AFR) and Bypass factor (BF) are tabulated above table.

BF : Bypass factor

EWB : Entering wet bulb temp. (°C)

EDB : Entering dry bulb temp. (°C)

TC : Total capacity (kW)

SHC : Sensible heat capacity (kW)

PI : Power input (kW)

AFR 18.5

BF 0.285

INDOOR OUTDOOR TEMPERATURE (°CDB)

EWB EDB 20 25 30 32 35 40

°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

14.0 20 6.44 4.54 1.65 6.44 4.54 1.85 6.24 4.43 2.02 6.12 4.36 2.09 5.93 4.27 2.19 5.62 4.10 2.35

16.0 22 7.17 4.68 1.71 6.86 4.52 1.87 6.55 4.36 2.03 6.42 4.30 2.10 6.24 4.21 2.20 5.93 4.06 2.36

18.0 25 7.48 4.85 1.72 7.17 4.70 1.88 6.86 4.55 2.04 6.73 4.49 2.11 6.55 4.41 2.21 6.23 4.26 2.37

19.0 27 7.64 5.06 1.72 7.32 4.91 1.88 7.01 4.77 2.05 6.89 4.71 2.11 6.70 4.63 2.21 6.39 4.49 2.37

22.0 30 8.10 4.86 1.73 7.79 4.73 1.90 7.47 4.60 2.06 7.35 4.55 2.13 7.16 4.48 2.22 6.85 4.36 2.39

24.0 32 8.41 4.71 1.74 8.10 4.59 1.91 7.78 4.48 2.07 7.66 4.43 2.14 7.47 4.37 2.23 7.16 4.25 2.40

Symbols NOTE:

AFR : Airflow rate (m³/min.) 1. Ratings shown are net capacities which include a deduction for indoor fan motor heat.

2. shows nominal (rated) capacities and power input.3. TC, PI and SHC must be calculated by interpolation using the

figures in the above tables.(Figures out of the tables should not be used for calculation.)

4. About SHC which are not mentioned on the table, please calculate them with around values in direct proportion.

5. Capacities are based on the following conditions.Corresponding refrigerant piping length : 7.5 mLevel difference : 0 m

6. Airflow rate (AFR) and Bypass factor (BF) are tabulated above table.

BF : Bypass factor

EWB : Entering wet bulb temp. (°C)

EDB : Entering dry bulb temp. (°C)

TC : Total capacity (kW)

SHC : Sensible heat capacity (kW)

PI : Power input (kW)

10 Room Air Conditioners J-Series

EDHK011026 Capacity Tables

7.2 Capacity Correction Factor by the Length of Refrigerant Piping (Reference)The cooling capacity of the unit has to be corrected in accordance with the length of refrigerant piping. (The distance between the indoor unit and the outdoor unit)

7.2.1 50 Class

7.2.2 60 Class

Note: 1. The graphs show the factor when additional refrigerant of the proper quantity is charged.

Cap

acity

cor

rect

ion

fact

or

1

5 10 15 20 25 30

0.9

0.8

R-410A (50 class)

Piping length (m)

(R12428)

Range of the Refrigerant Additional Charge

Cap

acity

cor

rect

ion

fact

or

1

5 10 15 20 25 30

0.9

0.8

R-410A (60 class)

Piping length (m)

(R12429)

Range of the Refrigerant Additional Charge

Room Air Conditioners J-Series 11

Operation Limit EDHK011026

8. Operation Limit

RN50/60JV1

50

46

40

30O

utdo

or te

mp.

(˚C

DB

)

Pul

l-dow

n pe

riod

Con

tinuo

us o

pera

tion

2019.4

0

14 302310 20 28Notes: Indoor temp. (˚CWB)The graph is based

on the following conditions.• Equivalent piping length 7.5m• Level difference 0m• Air flow rate High

4D063906C

12 Room Air Conditioners J-Series

EDHK011026 Sound Level

9. Sound Level9.1 Measuring Location

Note: 1. Operation sound is measured in an anechoic chamber.2. The data are based on the conditions shown in the table below.

Indoor Unit Outdoor Unit

1 m

0.8

m

(R1759)

1 m

(R1003)

Cooling Piping LengthIndoor ; 27°CDB / 19°CWB

Outdoor ; 35°CDB / 24°CWB 5 m

Room Air Conditioners J-Series 13

Sound Level EDHK011026

9.2 Octave Band Level9.2.1 Indoor Unit

9.2.2 Outdoor Unit

FTN50JV18 FTN60JV18

NC-60

NC-50

NC-40

NC-20

NC-30

POWER SOURCE

JIS STANDARD

OPERATING CONDITIONS

OC

TAV

E B

AN

D S

OU

ND

PR

ES

SU

RE

LE

VE

LdB

( 0dB

=0.

0002

µ ba

r)

70

60

20

30

50

40

THRESHOLD HEARINGAPPROXIMATE

FOR CONTINUOUSNOISE

63 125OCTAVE BAND CENTER FREQUENCY (Hz)

250 500 1000 2000 4000 8000

OVER ALL ( dB )

SCALE

A

( B.G.N IS ALREADY RECTIFIED )

220V~240V50Hz

45 35

STANDARD EXTERNAL STATIC PRESSURE

50Hz 220V~240V(L)

(H)220V~240V

50Hz

50Hz 220V~240V(H)

220V~240V 50Hz

(L)

4D058780C

POWER SOURCE

JIS STANDARD

OPERATING CONDITIONS

OC

TAV

E B

AN

D S

OU

ND

PR

ES

SU

RE

LE

VE

LdB

( 0dB

=0.

0002

µ ba

r)

70

60

20

30

50

40

THRESHOLD HEARINGAPPROXIMATE

FOR CONTINUOUSNOISE

63 125OCTAVE BAND CENTER FREQUENCY (Hz)

250 500 1000 2000 4000 8000

OVER ALL ( dB )

SCALE

A

( B.G.N IS ALREADY RECTIFIED )

NC-60

NC-50

NC-40

NC-30

NC-20

50Hz220V~240V

(H)

50Hz220V~240V

(L)

3647

220V~240V 50Hz

50Hz 220v~240V(H)

50Hz 220v~240V(L)

4D066673B

RN50JV1 RN60JV1

POWER SOURCE

JIS STANDARD

OPERATING CONDITIONS

OC

TAV

E B

AN

D S

OU

ND

PR

ES

SU

RE

LE

VE

LdB

( 0dB

=0.

0002

µ ba

r)

70

60

20

30

50

40

THRESHOLD HEARINGAPPROXIMATE

FOR CONTINUOUSNOISE

63 125OCTAVE BAND CENTER FREQUENCY (Hz)

250 500 1000 2000 4000 8000

OVER ALL ( dB )

SCALE

A

( B.G.N IS ALREADY RECTIFIED )

NC-60

NC-50

NC-40

NC-30

NC-20

50Hz220V

50

220V 50Hz

50Hz 220V

4D068090

POWER SOURCE

JIS STANDARD

OPERATING CONDITIONS

OC

TAV

E B

AN

D S

OU

ND

PR

ES

SU

RE

LE

VE

LdB

( 0dB

=0.

0002

µ ba

r)70

60

20

30

50

40

THRESHOLD HEARINGAPPROXIMATE

FOR CONTINUOUSNOISE

63 125OCTAVE BAND CENTER FREQUENCY (Hz)

250 500 1000 2000 4000 8000

OVER ALL ( dB )

SCALE

A

( B.G.N IS ALREADY RECTIFIED )

NC-60

NC-50

NC-40

NC-30

NC-20

50Hz220V

52

220V 50Hz

50Hz 220V

4D068091

14 Room Air Conditioners J-Series

EDHK011026 Electric Characteristics

10.Electric Characteristics

3D067567B

Unit combination Power supply Compressor OFM IFM

Indoor Outdoor Hz - Volts Voltage range MCA MFA LRA RLA W FLA W FLA

FTN50JV18 RN50JV1 50 - 220 MIN. 198 VMAX. 242 V 9.2 15 33 6.8 50 0.5 43 0.2

FTN60JV18 RN60JV1 50 - 220 MIN. 198 VMAX. 242 V 12.5 25 54 9.4 65 0.6 43 0.2

SYMBOLS: NOTE:

MCA : Min. circuit amps (A) 1. RLA is based on the following conditions.Indoor temp. 27°CDB / 19°CWBOutdoor temp. 35°CDB.

2. Maximum allowable voltage unbalance between phases is 2%.3. Select wire size based on the larger value of MCA.4. Instead of fuse, use circuit breaker.

MFA : Max. fuse amps (A)

LRA : Locked rotor amps (A)

RLA : Rated load amps (A)

OFM : Outdoor fan motor

IFM : Indoor fan motor

FLA : Full load amps (A)

W : Fan motor rated output (W)

Room Air Conditioners J-Series 15

Installation Manual EDHK011026

11. Installation Manual11.1 Safety Precautions

16 Room Air Conditioners J-Series

EDHK011026 Installation Manual

11.2 50 Class

Room Air Conditioners J-Series 17

Installation Manual EDHK011026

18 Room Air Conditioners J-Series

EDHK011026 Installation Manual

Indoor/outdoor Unit Installation Drawings

Room Air Conditioners J-Series 19

Installation Manual EDHK011026

20 Room Air Conditioners J-Series

EDHK011026 Installation Manual

Room Air Conditioners J-Series 21

Installation Manual EDHK011026

22 Room Air Conditioners J-Series

EDHK011026 Installation Manual

Room Air Conditioners J-Series 23

Installation Manual EDHK011026

24 Room Air Conditioners J-Series

EDHK011026 Installation Manual

3PN10898-2G

Room Air Conditioners J-Series 25

Installation Manual EDHK011026

11.3 60 Class

26 Room Air Conditioners J-Series

EDHK011026 Installation Manual

Indoor/outdoor Unit Installation Drawings

Room Air Conditioners J-Series 27

Installation Manual EDHK011026

Indoor/outdoor Unit Installation Drawings

28 Room Air Conditioners J-Series

EDHK011026 Installation Manual

Room Air Conditioners J-Series 29

Installation Manual EDHK011026

30 Room Air Conditioners J-Series

EDHK011026 Installation Manual

Room Air Conditioners J-Series 31

Installation Manual EDHK011026

32 Room Air Conditioners J-Series

EDHK011026 Installation Manual

Room Air Conditioners J-Series 33

Installation Manual EDHK011026

3PN10898-4G

34 Room Air Conditioners J-Series

EDHK011026 Operation Manual

12.Operation Manual

Room Air Conditioners J-Series 35

Operation Manual EDHK011026

36 Room Air Conditioners J-Series

EDHK011026 Operation Manual

Room Air Conditioners J-Series 37

Operation Manual EDHK011026

38 Room Air Conditioners J-Series

EDHK011026 Operation Manual

Room Air Conditioners J-Series 39

Operation Manual EDHK011026

40 Room Air Conditioners J-Series

EDHK011026 Operation Manual

Room Air Conditioners J-Series 41

Operation Manual EDHK011026

42 Room Air Conditioners J-Series

EDHK011026 Operation Manual

Room Air Conditioners J-Series 43

Operation Manual EDHK011026

44 Room Air Conditioners J-Series

EDHK011026 Operation Manual

Room Air Conditioners J-Series 45

Operation Manual EDHK011026

46 Room Air Conditioners J-Series

EDHK011026 Operation Manual

Room Air Conditioners J-Series 47

Operation Manual EDHK011026

48 Room Air Conditioners J-Series

EDHK011026 Operation Manual

Room Air Conditioners J-Series 49

Operation Manual EDHK011026

50 Room Air Conditioners J-Series

EDHK011026 Operation Manual

Room Air Conditioners J-Series 51

Operation Manual EDHK011026

52 Room Air Conditioners J-Series

EDHK011026 Operation Manual

20

Trouble Shooting

The following cases are not air conditioner troubles but have some reasons. You may just continue using it.

These cases are not troubles.

noitanalpxEesaCOperation does not start soon.• When ON/OFF button was

pressed soon afteroperation was stopped.

• When the mode was reselected.

• This is to protect the air conditioner.You should wait for about 3 minutes.

The outdoor unit emits water or steam.

In COOL or DRY mode• Moisture in the air condenses into water on the cool

surface of outdoor unit piping and drips.

Mists come out of the indoorunit.

This happens when the air in the room is cooled into mist by the cold airflow during cooling operation.

The indoor unit gives out odour. This happens when smells of the room, furniture, orcigarettes are absorbed into the unit and discharged with theairflow.(If this happens, we recommend you to have the indoor unit washed by a technician. Consult the service shop where youbought the air conditioner.)

The outdoor fan rotates whilethe air conditioner is not inoperation.

After operation is stopped:• The outdoor fan continues rotating for another 60

seconds for system protection.While the air conditioner is not in operation:• When the outdoor temperature is very high, the outdoor

fan starts rotating for system protection.

The operation stoppedsuddenly.(OPERATION lamp is on.)

For system protection, the air conditioner may stop operating on a sudden large voltage fluctuation.It automatically resumes operation in about 3 minutes.

No remote controller signals are displayed.The remote controller sensitivity

The display is low in contrast or blacked out.The display runs out of control.

A “PISHI-PISHI” squeaking sound is heard when the systemis in operation or after the stop of operation

• The batteries are dying and the remote controller is malfunctioning. Replace all the batteries with new size AAAalkaline batteries. For details, refer to “To set the batteries” of this manual. (page 7.)

* If the reset button is provided, press the reset button after thebatteries are replaced.

is low.

• Expansion and contraction of plastic parts caused by temperature change makes this noise.

Room Air Conditioners J-Series 53

Operation Manual EDHK011026

54 Room Air Conditioners J-Series

EDHK011026 Operation Manual

3PN10897-5D

Room Air Conditioners J-Series 55

Optional Accessories EDHK011026

13.Optional Accessories13.1 Option List13.1.1 Indoor Unit

13.1.2 Outdoor Unit

Option Name 50/60 Class

1 Air-Purifying Filter with Photocatalytic Deodorizing Function without Frame KAF952B42 (KAF952A42)

2 Remote Controller Loss Prevention with Chain KKF917A4

Option Name 50 Class 60 Class

1 Drain Plug KKP937A4 KKP945A4

2 Air Direction Adjustment Grille KPW945A4

56 Room Air Conditioners J-Series

EDHK011026 Optional Accessories

13.2 Installation Manual13.2.1 KKP945A4

3P089958-1B

Room Air Conditioners J-Series 57

Optional Accessories EDHK011026

13.2.2 KPW945A4

Check the following parts

Installation Procedure

Before installation

Name

Quantity

Louver

1piece

Truss tapping screw

M4x4screws(max.7.5kW class)M5x4screws(8.0/9.0kW class)

Installation manual

1piece

Shape

Selection of Installation Location

Installation of Louvers

Space Needed for Installation

Use when installing in a location that meets the following conditions.When installing near the border to a neighbor's houseIf exhaust blows directly on passers-by because outdoor unit is instal-led facing a road.If exhaust blows directly on vegetation

A minimum of 100mm is needed between the back of the outdoor unit and any obstructions(walls, etc.)

more than100

Attach the louvers overlapping the standard grill.Installing the louvers without the grill would allow hands to enter the fan area, which is dangerous, so be sure to install the standard grill.

Caution

When pointing up When pointing down

(1) Remove the 4 attachment screws fromthe standard grill.

Remove the 4 attachment screws fromthe standard grill.

(2) Install the louver pointed up.Overlap the standard grill andscrew both in together.

The attachment screwsare in the louvers.

Install the louver pointed down.Overlap the standard grill andscrew both in together.

The attachment screwsare in the louvers.

(3)

(1)

(2)

(3)Installation complete Installation complete

3P089958-2C

58 Room Air Conditioners J-Series

Warning Daikin Industries, Ltd.’s products are manufactured for export to numerous countries throughout the world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a particular country. Prior to purchase, please therefore confirm with your local authorised importer, distributor and/or retailer whether this product conforms to the applicable standards, and is suitable for use, in the region where the product will be used. This statement does not purport to exclude, restrict or modify the application of any local legislation.

Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.

Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.

Read the User's Manual carefully before using this product. The User's Manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings.

If you have any enquiries, please contact your local importer, distributor and/or retailer.

1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor.

Cautions on product corrosion

JMI-0107 JQA-1452

Organization:DAIKIN INDUSTRIES, LTD.AIR CONDITIONING MANUFACTURING DIVISION

Scope of Registration:THE DESIGN/DEVELOPMENT AND MANUFACTURE OF COMMERCIAL AIR CONDITIONING, HEATING, COOLING, REFRIGERATING EQUIPMENT, COMMERCIAL HEATING EQUIPMENT, RESIDENTIAL AIR CONDITIONING EQUIPMENT, HEAT RECLAIM VENTILATION, AIR CLEANING EQUIPMENT, MARINE TYPE CONTAINER REFRIGERATION UNITS, COMPRESSORS AND VALVES.

Organization:DAIKIN INDUSTRIES(THAILAND) LTD.

Scope of Registration:THE DESIGN/DEVELOPMENTAND MANUFACTURE OF AIR CONDITIONERS AND THE COMPONENTS INCLUDING COMPRESSORS USED FOR THEM

All of the Daikin Group’s business facilities and subsidiaries in Japan are certified under the ISO 14001 international standard for environment management.

DealerHead Office:Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,Kita-ku, Osaka, 530-8323 Japan

Tokyo Office:JR Shinagawa East Bldg., 2-18-1, Konan,Minato-ku, Tokyo, 108-0075 Japan

http://www.daikin.com/global_ac/

EDHK011026Printed in Japan 06/10/0007 FS.AK.B

gy

Specifications, designs and other content appearing in this brochure are current as of June 2010 but subject to change without notice.

All rights reservedc