1 RGB Digital Fiberoptic Sensor CZ-K1(P) Series Instruction Manual 142-001 SAFETY PRECAUTIONS This manual describes the instructions, operating procedures and precautions for using the CZ-K1(P) Series. Before beginning operation, please read this manual carefully to get the most from your CZ-K1(P) Series. Keep this manual handy for future reference. The CZ-K1(P) Series is intended for the detection of target objects. Do not use the CZ-K1(P) Series in a safety circuit to protect the human body. The CZ-K1(P) Series does not have an explosion-proof structure. Do not use it in a location where any flammable gases, liquid or powder exist. ACCESSORIES WARNING SPECIFICATIONS l e d o M t u p t u o N P N 1 K - Z C t u p t u o P N P P 1 K - Z C e c r u o s t h g i L D E L e u l B , D E L n e e r G , D E L d e R e m i t e s n o p s e R 0 0 3 µ ) e l b a t c e l e s h c t i w s ( s m 1 / s s r o t a c i d n I , D E L e g n a r O : n o i t a r b i l a C , D E L d e R : t u p t u O , D E L n e e r G : t u p n i n o i t a z i n o r h c n y s l a n r e t x E ) n e e r G / d e R ( D C L : y t i s n e t n i t h g i l d e v i e c e r / e t a r g n i h c t a M n o i t a c i d n i r o r r E , y t i s n e t n i t h g i l t n e i c i f f u s n i , y t i s n e t n i t h g i l s s e c x E e c n e r e f f i d r o l o c t n e i c i f f u s n i d o h t e m n o i t a r b i l a C ) e l b a t c e l e s h c t i w s ( n o i t a r b i l a c t n i o p - 2 / t n i o p - 1 e u l a v e c n a r e l o T t n e m t s u j d a y a l p s i d l a t i g i d n o g n i t t e s e u l a v l a c i r e m u N e d o m n o i t a i t n e r e f f i D ) e l b a t c e l e s h c t i w s ( e d o m I / e d o m I + C / e d o m C n o i t c n u f r e m i T ) e l b a t c e l e s h c t i w s ( ) s m 0 4 ( r e m i t y a l e d - F F O / F F O r e m i T e d o m t u p t u O n o i t c e l e s r o l o c t e g r a t n e h w n o s n r u T : t u p t u o h c t a M . r o l o c d e r e t s i g e r s e h c t a m t n e r e f f i d s i r o l o c t e g r a t n e h w n o s n r u T : t u p t u o h c t a m s i M ) e l b a t c e l e s h c t i w s ( . r o l o c d e r e t s i g e r m o r f - o r h c n y s l a n r e t x E t u p n i n o i t a z i n 0 0 5 : d e e p s e s n o p s e R , t u p n i e g a t l o v - n o N µ . x a m s n o i t a r b i l a c l a n r e t x E t u p n i . n i m s m 0 2 : e m i t e s n o p s e r t u p n I , t u p n i e g a t l o v - n o N r o l o c d e r e t s i g e R n o i t c e l e s , t u p n i e g a t l o v - n o N , ) t u p n i l a n r e t x e y B ( n o i t c e l e s k n a b - 8 . n i m s m 0 2 : e m i t e s n o p s e r t u p n I t u p t u o l o r t n o C . x a m C D V 0 4 : r o t c e l l o c - n e p o P N P r o N P N . x a m V 0 . 1 : e g a t l o v l a u d i s e R , ) . x a m A m 0 0 1 ( t i u c r i c n o i t c e t o r P t n e r r u c r e v o , ) y l p p u s r e w o p ( n o i t c e t o r p y t i r a l o p - e s r e v e R ) t u p t u o ( r e b r o s b a e g r u s , ) t u p t u o ( n o i t c e t o r p y l p p u s r e w o P C D V 4 2 o t 2 1 ± . x a m % 0 1 : ) P - P ( e l p p i R , % 0 1 t n e r r u C n o i t p m u s n o c . x a m A m 5 7 t h g i l t n e i b m A , . x a m x u l 0 0 0 , 5 : p m a l t n e c s e d n a c n I . x a m x u l 0 0 0 , 0 1 : t h g i l n u S t n e i b m A e r u t a r e p m e t . 1 5 5 + o t 0 1 - °C y t i d i m u h e v i t a l e R % 5 8 o t 5 3 n o i t a r b i V Z d n a , Y , X n i e d u t i l p m a e l b u o d m m 5 . 1 , z H 5 5 o t 0 1 y l e v i t c e p s e r s r u o h 2 , s n o i t c e r i d k c o h S s / m 0 0 5 2 y l e v i t c e p s e r s e m i t 3 , s n o i t c e r i d Z d n a , Y , X n i l a i r e t a m g n i s u o H e t a n o b r a c y l o P g n i d u l c n i ( t h g i e W ) e l b a c m 2 g 5 1 1 . x o r p p A 1. When several units are connected, the acceptable ambient temperature varies depending on the conditions given below. To connect several units, be sure to mount them to a DIN rail (metallic plate). Ensure that the output current is 20 mA max. • When 3 to 10 units are connected: -10 to +50°C • When 11 to 16 units are connected: -10 to +45°C Amplifier Fiber unit d o h t e m n o i t c e t e D e v i t c e l f e R l e d o M 0 4 - Z C 1 4 - Z C e p y T e c n a t s i d g n i t c e t e d g n o L t o p s m a e b l l a m S e g n a r n o i t c e t e D 0 7 ± m m 0 2 6 1 ± m m 4 r e t e m a i d t o p s t s e l l a m S . a i d m m 6 . a i d m m 1 s u i d a r d n e b m u m i n i M m m 5 2 R m m 5 1 R g n i t a r e r u s o l c n E 7 6 - P I e r u t a r e p m e t t n e i b m A 0 7 + o t 0 4 - °C y t i d i m u h e v i t a l e R % 5 8 o t 5 3 h t g n e l r e b i F ) t u c - e e r f ( m 2 l a i r e t a m g n i s u o H e t a l y r a y l o P t h g i e W g 7 2 . x o r p p A Instruction manual (This manual): 1 Mounting bracket: 1 Quick reference: 1 * Attach this sticker close to the CZ-V1 unit. Resin driver: 1 • 1-point calibration (DIP switch 3: OFF) DIP switch UP/DOWN button SET button Mode button [Fine sensitivity adjustment] [Calling preset value] Matching rate display Preset value display [Sensitivity setting] Using button With a target in place, . With a target in place, with the target removed, . , and Button Names Display Switching Error display Sensitivity Setting • 2-point calibration (DIP switch 3: ON) Received light intensity is too low. Received light intensity is too high. CZ-K1 Quick Reference [ : Briefly press the button.] [In C/C+I mode] M S S S S M M In I mode, button operation is the same as that of the FS-V1. * Fine sensitivity adjustment Press Press Precise Rough MODE SET S 1234 ON Using button

Upload: ernesto-alonso

Post on 24-Apr-2015

384 views

Category:

Documents


9 download

TRANSCRIPT

Page 1: Cz-k1p Dataseet Keyence

1

RGB Digital Fiberoptic Sensor

CZ-K1(P) SeriesInstruction Manual

142-001 SAFETY PRECAUTIONSThis manual describes the instructions, operating procedures andprecautions for using the CZ-K1(P) Series.Before beginning operation, please read this manual carefully to get themost from your CZ-K1(P) Series.Keep this manual handy for future reference.

• The CZ-K1(P) Series is intended for the detection of targetobjects. Do not use the CZ-K1(P) Series in a safety circuit toprotect the human body.

• The CZ-K1(P) Series does not have an explosion-proof structure.Do not use it in a location where any flammable gases, liquid orpowder exist.

ACCESSORIES

WARNING

SPECIFICATIONS

ledoMtuptuoNPN 1K-ZCtuptuoPNP P1K-ZC

ecruosthgiL DELeulB,DELneerG,DELdeRemitesnopseR 003 µ )elbatceleshctiws(sm1/s

srotacidnI,DELegnarO:noitarbilaC,DELdeR:tuptuO,DELneerG:tupninoitazinorhcnyslanretxE

)neerG/deR(DCL:ytisnetnithgildeviecer/etargnihctaM

noitacidnirorrE ,ytisnetnithgiltneiciffusni,ytisnetnithgilssecxEecnereffidroloctneiciffusni

dohtemnoitarbilaC )elbatceleshctiws(noitarbilactniop-2/tniop-1eulavecnareloT

tnemtsujda yalpsidlatigidnognitteseulavlaciremuN

edomnoitaitnereffiD )elbatceleshctiws(edomI/edomI+C/edomC

noitcnufremiT )elbatceleshctiws()sm04(remityaled-FFO/FFOremiT

edomtuptuOnoitceles

roloctegratnehwnosnruT:tuptuohctaM.rolocderetsigersehctam

tnereffidsiroloctegratnehwnosnruT:tuptuohctamsiM)elbatceleshctiws(.rolocderetsigermorf

-orhcnyslanretxEtupninoitazin 005:deepsesnopseR,tupniegatlov-noN µ .xams

noitarbilaclanretxEtupni .nimsm02:emitesnopsertupnI,tupniegatlov-noN

rolocderetsigeRnoitceles

,tupniegatlov-noN,)tupnilanretxeyB(noitcelesknab-8.nimsm02:emitesnopsertupnI

tuptuolortnoC .xamCDV04:rotcelloc-nepoPNProNPN.xamV0.1:egatlovlaudiseR,).xamAm001(

tiucricnoitcetorP tnerrucrevo,)ylppusrewop(noitcetorpytiralop-esreveR)tuptuo(rebrosbaegrus,)tuptuo(noitcetorp

ylppusrewoP CDV42ot21 ± .xam%01:)P-P(elppiR,%01tnerruC

noitpmusnoc .xamAm57

thgiltneibmA ,.xamxul000,5:pmaltnecsednacnI.xamxul000,01:thgilnuS

tneibmAerutarepmet .1 55+ot01- °C

ytidimuhevitaleR %58ot53

noitarbiV Zdna,Y,Xniedutilpmaelbuodmm5.1,zH55ot01ylevitcepsersruoh2,snoitcerid

kcohS s/m005 2 ylevitcepsersemit3,snoitceridZdna,Y,XnilairetamgnisuoH etanobracyloPgnidulcni(thgieW

)elbacm2 g511.xorppA

1. When several units are connected, the acceptable ambient temperature variesdepending on the conditions given below. To connect several units, be sure tomount them to a DIN rail (metallic plate). Ensure that the output current is 20mA max.• When 3 to 10 units are connected: -10 to +50°C• When 11 to 16 units are connected: -10 to +45°C

Amplifier Fiber unitdohtemnoitceteD evitcelfeR

ledoM 04-ZC 14-ZC

epyT ecnatsidgnitcetedgnoL topsmaebllamS

egnarnoitceteD 07 ± mm02 61 ± mm4

retemaidtopstsellamS .aidmm6 .aidmm1

suidardnebmuminiM mm52R mm51R

gnitarerusolcnE 76-PI

erutarepmettneibmA 07+ot04- °C

ytidimuhevitaleR %58ot53

htgnelrebiF )tuc-eerf(m2

lairetamgnisuoH etalyrayloP

thgieW g72.xorppA

Instruction manual (This manual): 1 Mounting bracket: 1

Quick reference: 1

* Attach this sticker close to theCZ-V1 unit.

Resin driver: 1

• 1-point calibration (DIP switch 3: OFF)

DIP switch

UP/DOWN button

SET button

Mode button

[Fine sensitivity adjustment]

[Calling preset value]

Matching rate display Preset value display

[Sensitivity setting]

Using button

With a target in place, .

With a target in place,

with the target removed, .

, and

Button Names Display Switching

Error displaySensitivity Setting

• 2-point calibration (DIP switch 3: ON)

Received light intensity is too low.

Received light intensity is too high.

CZ-K1 Quick Reference [ : Briefly press the button.][In C/C+I mode]

M

S

S

SS

M

M

In I mode, button operation is the same as that of the FS-V1.

*

Fine sensitivity adjustmentPress

PressPrecise Rough

MODE

SET

S1

23

4

ON

Using button

Page 2: Cz-k1p Dataseet Keyence

2

CONNECTING FIBER UNIT AND AMPLIFIER1. Tilt the quick-release lever.

2. Push the single-core fiber to the transmitter side, and the multiple-core fiber to the receiver side as far as they will go (Approx. 14 mm ofthe fiber will be inserted.).

* Inserting the fiber in the wrong side will decrease the originaldetection performance. Be sure to check the markings on theamplifier’s lateral side before inserting the fiber.

3. Raise the quick-release lever.

MOUNTING AMPLIFIER

■ Mounting/detaching amplifier to/from DIN rail ormounting bracket

Hook the claw on the rear side of the amplifier onto the DIN rail or themounting bracket, and then hook the front side claw to the rail orbracket while pressing the amplifier forward. To detach the amplifier,unhook the front claw by lifting the amplifier front side while pressing itforward.

■ Side mountingUsing the side holes of the suppliedmounting bracket, secure the amplifierwith the screws.

CONNECTING SEVERAL AMPLIFIERS

■ Mounting expansion unitsUp to 16 expansion units (FS-T2, FS-M2, FS-V12, PS-T2) can bemounted to the side of the CZ-K1(P) amplifier.

1. Remove the protective cover on theside of the amplifier.

2. Mount expansion units to the DIN railone at a time.

3. Slide one expansion unit toward the main unit or another unit. Alignthe front claws of the units and push them together until you hear aclick.

4. Secure the units together by pushing the end units (included in theexpansion unit) from both sides.

The sticker on the right isincluded with the expansionunit. Attach the stickerclose to the sensor units.

Quick-release lever

Mounting

Remove theprotective cover.

Main unit

DETACHING EXPANSION UNITS FROM DIN RAIL1. Detach the end units.

2. Slide the expansion unit that is to be detached. Detach it individuallyfrom the DIN rail.

Note 1: When connecting several amplifiers, be sure to use a DIN railand the end units.Note 2: Be sure to turn the power off before connecting/disconnectingamplifiers.Note 3: Do not remove the protective cover on the expansion connectorfrom the outermost unit.Note 4: Do not detach several units from the DIN rail while they areconnected to each other.Note 5: When several units are connected, confirm that the ambienttemperature is appropriate. (See “Specifications” on page 1.)

MOUNTING FIBER UNIT• Use the supplied special mounting bracket to mount the fiber unit in

the desired position according to the location.

• Be sure to limit the tightening torque to 0.3 Nm or less.

Mounting example 1 Mounting example 2

Reference: To cut the fiber to the desired length, use the special cutterincluded with the fiber unit.

INPUT/OUTPUT CIRCUIT

Connections

Output circuit

Input circuit

2

1 3

Single-core fiber(with markings)

Multiple-core fiber

Transmitter side(with markings)

Receiver side

Single-core(Transmitter side)

Multiple-core(Receiver side)

Detaching

Expansionunits

Align the claw.

End unit (included withthe expansion unit)

Up to 16 expansion units can be connected.

12 to 24 VDC

5 to 40 VDC

External synchronization input

External bank selection 1

External bank selection 2

External bankselection 3

External calibration

0 V

Brown

Black LoadPink

Purple

Orange/purple

Yellow/purple

Green/purple

Blue

100 mA max.

External calibration inputExternal synchronization inputExternal bank selection input 1 to 3

0 V

PLC, etc.

Blue

+5 V

Pho

toel

ectr

ic s

enso

r m

ain

circ

uit

-5 VPinkPurpleOrange/purpleYellow/purpleGreen/purple

Short-circuit current: Approx. 1 mA

NPN

12 to 24 VDC

Load 5 to 40 VDC

0 V

100 mA max.

Pho

toel

ectr

ic s

enso

r m

ain

circ

uit

Ove

rcur

rent

pr

otec

tion

Brown

Black

Blue

NPN PNP

PNP

12 to 24 VDC

External synchronization input

External bank selection 1

External bank selection 2

External bank selection 3

External calibration

0 V

Brown

BlackLoad

Pink

Purple

Orange/purple

Yellow/purple

Green/purple

Blue

100 mA max.

12 to 24 VDC

Load

0 V

100 mA max.

Pho

toel

ectr

ic s

enso

r m

ain

circ

uit

Ove

rcur

rent

pr

otec

tion

Brown

Black

Blue

NPN PNP

External calibration inputExternal synchronization inputExternal bank selection input 1 to 3

0 V

12 to 24 VDC

PinkPurpleOrange/purpleYellow/purpleGreen/purple

BluePho

toel

ectr

ic s

enso

r m

ain

circ

uit

Short-circuit current: Approx. 1 mA

PLC, etc.

Page 3: Cz-k1p Dataseet Keyence

3

PART NAMES

12

34

MODE

SET

N.ON.COFFDLY.

OUT TIM SET

HSPD FINE

2-P 1-P

C+I C

I

DIP switches for mode setting

High-speed/High-precision

2-point/1-point calibration

Differentiation modeselection

Output indicator

External synchronizationinput indicator

Timer selection switchSwitches between TimerOFF and 40 ms OFF-delay.

UP/DOWN key• Changes sensitivity setting value.• Changes channels.

LCD display monitor

MODE selection button• Changes display.• Shows matching rate.• Shows setting value.

SET buttonSets sensitivity.

Output selection switchSwitches between N.O. and N.C.

Calibration indicator

SETTING EACH MODE

12

34 MODE

SET

N.ON.COFFDLY.

OUT TIM SET

DIP switch

Timer selection switch Output selection switch

Factory setting“❋ ” indicates the factory-set mode. Normally, you should use the CZ-K1(P) with the setting indicated by “❋ ”, and only change the setting ifrequired.

■ Differentiation mode setting (Using DIP switches 1 and 2)Change the setting according to the detection conditions such as thetarget color or received light intensity.

edoM hctiwS noitpircseD

)roloC(CstnenopmocrolocgnisurolocstceteD

.)Bdna,G,R(I+C

dnaroloC()ytisnetni

stnenopmocrolocgnisurolocstceteDthgildeviecerdna)Bdna,G,R(.)ytitnauqthgildeviecer(ytisnetni

I)ytisnetnI(

thgildeviecergnisurolocstceteD.)ytitnauqthgildeviecer(ytisnetni

Sensitivity setting in C or C + I mode ➞ Go to page 4.Sensitivity setting in I mode ➞ Go to page 5.

■ 1-point/2-point calibration selection1. (Using DIP switch 3)Change the calibration method.

12

12

12

12

or

edoM hctiwS noitpircseD

P-1tniop-1(

)noitarbilac

ehT(.rolocdeificepsenostceteDtcetedottesyllacitamotuasiytivitisnes

gniruddetcelesrolocenoehtylno).noitarbilac

P-2tniop-2(

)noitarbilac

.srolocdeificepsowtsetaitnereffiDottesyllacitamotuasiytivitisnesehT(

ehtetaitnereffidoteulavlamitpoeht).noitarbilacgniruddetcelessrolocowt

1. The setting of DIP switch 3 is effective only in the C and C + I modes.The setting is unnecessary in I mode.

33

■ FINE/HSPD selection (Using DIP switch 4)Use HSPD when the detection requires a response speed less than 1ms.

■ N.O./N.C. selectionChange the setting to invert the output mode.

edoM hctiwS noitpircseDENIF)niaF(

hgihhtiwsrolocsetaitnereffiD.noisicerp

DPSH)deeps-hgiH(

deeps-hgihahtiwsrolocsetaitnereffiD003foesnopser µ .s

44

edoM hctiwS noitpircseD.O.N

hctamroloC()tuptuo

tegratehtnehwnodenrutsituptuO.rolocderetsigerehtsehctamroloc

.C.NroloC(

hctamsim)tuptuo

tegratehtnehwnodenrutsituptuOderetsigerehthctamtonseodroloc

.roloc

❋ N.C. N.O.

N.C. N.O.

■ Timer OFF/40 ms OFF-delay selectionChange the setting to delay the output timing.

edoM hctiwS noitpircseD

FFOremiT .yaledynatuohtiwnodenrutsituptuO

sm04yaled-FFO

.sm04rofdeyaledsituptuO

❋ DLY. OFF

DLY. OFF

Page 4: Cz-k1p Dataseet Keyence

4

OPERATING PROCEDURE FOR USING C OR C + I MODE

Setting sensitivity

Calibration indicator

■ 1-point calibration (Detection of one specified color)Place a target that is the reference color in the detection area of thefiber unit. Press the SET button and then release it.

The calibration indicator illuminates momentarily and the referencecolor is saved.

MODE

SET

N.ON.COFFDLY.

OUT TIM SET

Press thisbutton once.

● To ignore certain color differencesThere are two methods for ignoring color differences.

• Perform the sensitivity adjustment after calibration. (➞ See the lowerright part of page 4.)

• Use the quick color difference cancellation function.In 1-point calibration, hold down the SET button and continue thecalibration with targets of different colors. The CZ-K1(P) Seriesignores the color vibration and saves them as the reference color.

Calibration indicator(Illuminates while theSET button is held down.)

MODE

SET

N.ON.COFFDLY.

OUT TIM SET

Hold down theSET button.

■ 2-point calibration (Differentiation of two colors)1. Place a target that is the reference color in the detection area of the

fiber unit. Press the SET button and then release it.

The calibration indicator illuminates and the reference color issaved.

2. Place a target that is the color to be differentiated in the detectionarea. Press the SET button and then release it.

The calibration indicator goes off. The CZ-K1(P) Series sets theoptimal sensitivity to differentiate the two colors.

12

34

MODE

SET

N.ON.COFFDLY.

OUT TIM SET

Calibration indicatorPress theSET buttononce.

MODE

SET

N.ON.COFFDLY.

OUT TIM SET

Calibration indicatorPress theSET buttononce.

● When “- - -” is displayed:When the sensitivity difference is insufficient for proper detection, theLCD display monitor shows “- - -” for 3 seconds after calibration.In this case, see “When calibration/differentiation fails” on the upperright part of this page and try the calibration again.

● When calibration/differentiation failsCheck the following points.

• Check whether the fiber unit is mounted properly (detectiondistance and detection angle). (See page 7.)

• Perform the sensitivity adjustment. (See below.)• Select the other differentiation mode and then perform calibration

again. (See page 3.)

LCD display indication

Current value(Matching rate display)

● Matching rate displayDisplays the matching degree(matching rate) of the color of thecurrently detected target to thereference color registered duringcalibration.

* Displays a value between 0 and 999.(Higher value indicates a better match.)

MODE

Press the button once.

Setting value

The setting valueflashes on and off.

● Setting value displayDisplays the threshold value(criteria) of the matching rate todetermine if the color of thecurrently detected target is thesame color as the reference color.

When “nnnnnnnnnnnnnnn” or “VVVVVVVVVVVVVVV” is displayedThese displays indicate that the received light is insufficient orexcessive. ➞ See page 7.

Sensitivity adjustment

The tolerance of the detection can be adjusted.

1. Press the MODE button to show the setting value.

2. Press the UP/DOWN button to change the setting value.

MODE

SET

N.ON.COFF

M SET

Press

A higher value meansprecise detection.

Press

Narrow tolerance range

A lower value meansrough detection.

Wide tolerance range

* After the adjustment, press the MODE button to return to thematching rate display.

Page 5: Cz-k1p Dataseet Keyence

5

OPERATING PROCEDURE FOR USING I MODE

Setting sensitivity

Select the sensitivity setting procedure according to the target condi-tions.

■ To set sensitivity using a moving target (Fully-automaticcalibration)

1. Pass a target through the opticalaxis while pressing the SETbutton (3 seconds or more).

2. Confirm that the calibrationindicator (orange LED) flashes.

3. Release the SET button. Thecalibration indicator (orangeLED) goes off.

■ To detect a minute color difference (2-point calibration)1. With a target in place, press the

SET button and release it. Thecalibration indicator (orangeLED) illuminates.

2. With the target removed, pressthe SET button and release it.The calibration indicator (orangeLED) goes off.

■ For target positioning (Positioning calibration)1. With no target, press the SET

button and release it.The calibration indicator (orangeLED) illuminates.

2. Place a target in the positionwhere it is to be stopped.

3. Press the SET button for 3seconds or more and confirmthat the calibration indicator(orange LED) flashes.

4. Release the SET button.

■ For stable detection unaffected by dust or dirt (Maximumsensitivity setting)

1. Under the conditions shown inthe figure, press the SET buttonfor 3 seconds or more until thecalibration indicator (orangeLED) flashes.

2. Release the SET button.

12

34

MODE

SET

N.ON.COFFDLY.

OUT TIM SET

Calibrationindicator

Press the buttonfor 3 seconds ormore.

12

34

MODE

SET

N.ON.COFFDLY.

OUT TIM SET

Calibrationindicator

1. Press and releasethe button with atarget in place.

2. Press and releasethe button withoutthe target.

12

34

MODE

SET

N.ON.COFFDLY.

OUT TIM SET

Calibrationindicator

Press the buttonand release it.

With no target

● When the sensitivity difference is insufficient:“- - - - -” flashes for 3 seconds on the LCD display monitor aftercalibration.

12

34

MODE

SET

N.ON.COFFDLY.

OUT TIM SET

Calibrationindicator

Press the buttonfor 3 seconds ormore.

LCD display indication

The display is factory-set to show the received light intensity.

Received lightintensity (4 digits)

MODE

Press thisbutton once.

Setting value (4 digits)

* The setting value flasheson and off.

■ Received light intensity displayReceived light intensity is displayed in 4digit numbers by defining the maximumvalue as approximately 4000.

The maximum/minimum values vary depending on the fiber unitcharacteristics.

■ Setting value displayThe current setting value is displayed.This display enables sensitivityadjustment using the UP/DOWN button.

Changing the setting value

You can change the setting value in the “Setting value display”.

In setting value display mode

increases the sensitivity.MODE

SET

MODE

SET

(The setting value isdecreased.)decreases the sensitivity.

(The setting value isincreased.)

Reference: Holding down the UP/DOWN button quickly changesdisplayed values.

Page 6: Cz-k1p Dataseet Keyence

6

OTHER FUNCTIONS (COMMON TO C, C + I, AND I MODES)

Locking the sensitivity setting

* Be sure to hold down the MODE button first when operating theMODE and UP/DOWN buttons.

Hold down the MODE button and press the UP button for 3 seconds.This locks the operation buttons.

• “Loc” flashes on and off on the LCD display monitor.

• You can still change the display mode and channel when in settinglocked status.

● To cancel the locked statusRepeat the procedure above while in setting locked status. “UnL”flashes on and off on the LCD display monitor.

Setting sensitivity using an external input(External calibration function)

1. Lock the sensitivity setting using the procedure above. (If “UnL” isdisplayed, repeat the same procedure.)

2. Connect the pink cable to a switch or a PLC.The minimum input time is 20 ms.

3. The external calibration procedure is the same as using the SETbutton. (➞ All the setting procedures on pages 4 and 5 are availablewith the external input.)

12

34

MODE

SET

N.ON.COFFDRY.

OUT TIM SET

2 1➞

NPN +V

0 V

Brown

Blue

Pink

Selecting CH display

The CZ-K1(P) can internally store 8 colors (banks). The banks can beselected using an external input.

● Selecting registered colors (banks) using an external inputThe external bank selection cable allows the selection of 8 registeredcolors from A through H.

+V

0V

Brown

Blue

Orange/purple

Yellow/purple

Green/purple

rolocelbaCknaB

/egnarOelprup

/wolleYelprup

/neerGelprup

A X X X

B ● X X

C X ● X

D ● ● X

E X X ●

F ● X ●

G X ● ●

H ● ● ●

● :

X:

■ External synchronization functionWhen the external synchronization input cable (purple) receives asignal (connected to 0 V), the control output retains the condition at thatexact moment.

ON

OFF

ON

OFF

Detectioncondition

MatchMismatch

Externalsynchronizationinput

Control outputThis outputcondition isretained.

This output conditionis retained.

PNP+V

0 V

Brown

Blue

Pink

NPN

PNP

+V

0V

Brown

Blue

Orange/purple

Yellow/purple

Green/purple

Page 7: Cz-k1p Dataseet Keyence

7

HINTS ON CORRECT USE

Mounting amplifier

• If the amplifier cable is placed together with power lines or highvoltage lines in the same conduit, detection errors may occur due tonoise interference. Isolate the amplifier cable from these lines.

• If there are several colors in a single beam spot, the CZ-K1(P)determines the color by averaging those colors. Therefore, it mayproduce an output even though the color is different from theregistered color.

• To extend the cable length, use a cable with at least a 0.3 mm2

nominal cross-section area. Limit the length of cable extension to100 m or less. (To connect several units, contact Keyence for furtherinformation.)

• When using a commercially available switching regulator, ground theframe ground terminal and ground terminal.

• Do not use the CZ-K1(P) outdoors.

• Even when the same color is detected, the displayed value may varydepending on the characteristics of each amplifier, the length of thefiber cable and the location.

• When any of the external inputs (calibration, synchronization or bankselection) are not used, cut the appropriate input cables (pink, purple,orange/purple, yellow/purple or green/purple) at the root or connectthem to the "+" (CZ-K1) / "–"(CZ-K1P) terminal of the power supply.

Mounting fiber unit

• A detection error may occur when the target is subjected to direct orreflected light from high-frequency lighting equipment such as aninverter fluorescent lamp. In such a case, apply a light shield plate orchange the location of the fiber unit.

• When detecting a metal surface or glossy targetWhen a target has a metal or glossy surface, the calibration/differentia-tion may fail. To detect such a target, tilt the fiber unit by approximately10 to 15 degrees.

Inverter fluorescent lamp, etc.

Light shieldplate

10° to 15°

• Target movement and fiber unit orientationTo stabilize the sensor output at a border, mount the fiber unit parallel tothe border line as much as possible.

Fiber unit

• Prevent any objects from bumping the sensing surface.

• Do not pull the fiber cable using a strength greater than 0.3 N.

ERROR INDICATIONSThe following indications on the LCD display show the error events.Correct the problem using the following countermeasures.

Target movementdirection

Target movementdirection

Incorrect Correct

rorrEnoitacidni

esuaC serusaemretnuoC

nnn

thgildevieceRsiytisnetni.tneiciffusni

sitinurebifehtrehtehwkcehCgnitceteddeificepsehttadellatsni

ehtotnielbacrebifehttresnI.ecnatsid.xorppa(oglliwtisarafsatinurebif

.)mm41

vvv

thgildevieceRsiytisnetni.evissecxe

51ot01.xorppaybtinurebifehttliT(.seerged ➞ ”tinurebifgnitnuoM“eeS

).egapsihtfotraptfelehtno

----

ni(ecnereffidroloCecnereffid“,edomIsi)”ytisnetnithgilni

otllamsootsrolocetaitnereffid

tniop-2gnirud.noitarbilac

➞ /noitarbilacnehW“eeSdna4egapno”sliafnoitaitnereffid

.tnemtsujdaytivitisnesehtyrter

Page 8: Cz-k1p Dataseet Keyence

8

Worldwide HeadquartersKEYENCE CORPORATION1-3-14, Higashi-Nakajima, Higashi-Yodogawa-ku,Osaka, 533-8555, JapanPHONE: 81-6-6379-2211 FAX: 81-6-6379-2131

KEYENCE CORPORATION OF AMERICAPHONE: 201-930-0100 FAX: 201-930-0099

KEYENCE (UK) LIMITEDPHONE: 01908-696900 FAX: 01908-696777

KEYENCE DEUTSCHLAND GmbHPHONE: 0711-797371-0 FAX: 0711-7977799

KEYENCE FRANCE S.A.PHONE: 01 47 92 76 76 FAX: 01 47 92 76 77

KEYENCE SINGAPORE PTE LTDPHONE: 392-1011 FAX: 392-5055

KEYENCE (MALAYSIA) SDN BHDPHONE: 03-252-2211 FAX: 03-252-2131

KEYENCE (THAILAND) CO., LTDPHONE: 02-934-6777 FAX: 02-934-6775

KEYENCE KOREA CORPORATIONPHONE: 02-563-1270 FAX: 02-563-1271

© KEYENCE CORPORATION, 1998CZK-IM-1-1298 Printed in Japan

Specifications are subject to change without notice.

28.5

15

22

(12.

7)

5.8

8.4

53.5

35.46.5

1518.5

11.6

5

36.5

24

78

1.1

168

6.7

10.7

DIMENSIONS

CZ-K1(P)When mounted to DIN rail

ø5.2 x

Brown, blue, Black, Pink,Purple: 0.45 mm2

Orange/purple, green/purple,yellow/purple: 0.25 mm2

Cable length: 2 m

24 min.

24 min.

2 - ø3.2

2 - (4.4 x 3.4)

Stainless steel

CZ-40

Amplifier mounting bracket (accessory)

When mounting bracket is attached

200033

28

11.814

25.5

13

0.5 11.5

28.5

32

13

27

17.5 11.5

37 2000

ø3.3 ø2.2 x 2 2 - ø3.3 ø3.3 x 2

Slot (Note)

CZ-41

(Mounting hole)

(Free-cut)

(Note) Detail of slot

(Mounting hole)

(Free-cut)

Detail of slot

Fiber unit mounting bracket(accessory)

t = 1.2

t = 1.5

3.6

45

3.55

43.5

(32)

6

17.5

11.5

11.518.7

14.5

33

811

.518

3.6 9.5 2 x M3 screw

The fiber unit angle can be changedby a maximum of 45 degrees upwardand downward.

When mounting bracket isattached to CZ-40

Stainless steel