version 3.12
Cybro Hardware Manual
© 1998-2020 Cybrotech Ltd.
Cybrotech Ltd.14 Brinell WayHarfreys Industrial EstateNorfolk, NR31 0LUUnited [email protected]
Warning
This manual describes electrical and mechanical aspects of Cybro controller, IEX-2 modules and accessories. For information about software and programming, refer to CyPro User Manual.
This manual contains notices to which you should pay attention to ensure personnel safety, as well as to protect the controller and the connected equipment. These notices are highlighted with a warning triangle:
Safety guidelines
Manual
Warning
indicates that death, severe injury or substantial property damage can result if proper precautions are not taken
indicates that minor to medium injury or property damage can result if proper precautions are not taken
indicates hazard of severe electric shock, injury or property damage if proper precautions are not taken
Warning
Caution
This product can function correctly only when operated, maintained, transported, stored, installed and configured in accordance with recomendations. Failure to comply with applicable standards may result in damage to equipment or serious injury to personnel.
To minimize potential safety problems, you should follow all applicable local and national codes that regulate the installation and operation of your equipment. These codes vary geographically and usually change with time. It is your responsibility to determine which codes should be followed, and to verify that the equipment, installation, and operation comply with the latest revision of these codes.
Caution
Quick start
Cybrorouter
Windows PC
2. Install CyPro, check examples
3. Install CyBroMiniScada, check examples
1. Connect power supply and Ethernet
Objects and actions Analog clock Unicode
Floor plan GSM demo Pacman
Timeplot Solar tracker World weather
System
Cybro system consists of controller, i/o modules, and software tools for programming, monitoring and visualization. Internet connectivity is integral part od the system.
Cybro i/o modules
dBase
CyPro developmnet environmentMS Windows
CyBro Mini ScadaMS Windows
3rd party scada
CyBro Mini ScadaAndroid and iOS
CyBro Web Scadacloud services
CyBro Opc Servercommunication driver
internet
Overview
CyPro
opc server
iex loader
kiss logger
mini scada
http server
bin loader
scheduler
web view
scgi server
data tool
access
web scada
relay
com server
office gadget
development environment
user tools
administrator tools
communication drivers
visualization
Software
switchboard
field modules
+24V
GN
D
CA
NL
CA
NH
N1
N1
QX1-1
QX1-2
QX1-3
N0
N0
QX0-1
QX0-2
QX0-3
RE
LA
Y 0
RE
LA
Y 1
+24V
IEX-2
PWR
GNDIW0
QX0GND
QX1GND
QX2GND
QX3GND
GNDIW1
GNDIW2
GNDIW3
CANH
CANL
GND
SW-W2
Hardware
IX12 IX14 IX16C0 C0 C0IX13 IX15 IX17 IX18 IX20 IX22C0 C0 C0IX19 IX21 IX23
IX0 IX2 IX4C0 C0 C0IX1 IX3 IX5 IX6 IX8 IX10C0 C0 C0IX7 IX9 IX11
DALI controller
LC-DCGSM module
GSM-1GPRS
GSM
POWER
local
remote
Overview of software tools and hardware modules.
Protocols
A-bus
A-bus symbolic
HTTP
UART
SCGI
IEX-2 TCP/IP
Ethernet
RS232 RS485CAN
100BASE-T10BASE-T
Modbus
OPC 2.0 DA
access by address
access by name
application layer
gateway layer
network layer
hardware layer
standard
proprietary
physical layer
Cybro uses standard protocols whenever possible. Proprietary protocols are developed when it is necessary to keep hardware requirements low, or achieve extra functionality.
Comparing to Modbus, A-bus offers IP autodetection, NAT traversal (automatic connection to internet), CAN tunneling and symbolic extensions (access by name).
Comparing to CANopen and DeviceNet, IEX-2 serve basically the same function, but the software footprint is as low as 2kb, which makes it possible to use 8-bit controllers with a tiny bootloader.
Firmware
Cybro firmware (kernel) is updated with CyPro or CyBroBinLoader. To use the loader, program must be saved in binary form.
IEX-2 modules are updated with CyBroIexManager. Communication is going through controller, no additional hardware is needed. CyBroIexLoader is doing essentially the same task, but it is optimized for developers, and the aditional CAN adapter is needed.
Firmware upgrade is safe, device will never brick, whatever may happen during the process. To activate device that appear unresponsive, contact tech support.
IEX-2A-bus
loader loader loader loader
kernel firmware firmware firmware
plc pgm
Iex Loader
CyPro
Iex Manager
Bin Loader
administrator
plc developer
Mounting
Cybro controller and expansions should be mounted vertically onto the standard DIN rail (DIN EN 50022), within a suitable enclosure. Total power dissipation inside the enclosure must not exceed permissible enclosure dissipation. Cybro is designed for a natural convection cooling, you must provide a clearance of at least 30 mm above and below the unit.
Open the DIN clip to allow mounting, and snap close to secure the unit on the rail. When connecting units with zero-length cable, snap it first to the left unit, then snap the right unit onto the cable.
To disconnect units, use a small screwdriver to push connector clip, then pull the unit away.
When product is subject to high temperature, high humidity, excessive dust, corrosive gases, vibration or hard impacts, it may result in an electric shock, fire or malfunction. Install this product according to instructions. If installation is not performed correctly, it may result in unit malfunction or failure. Do not allow foreign objects, such as wire scraps, to enter the unit. This may cause fire, unit failure or malfunction.
Caution
2. pull
1. push
Safety
Provide a circuit breaker rated 10A/Type B that removes power from Cybro and the connected expansions. Circuit breaker or separate disconnect switch should be near the controller.
Separate AC wiring and high-energy DC wiring from low-energy signal wiring. Equip inductive loads with suppression circuits. Use 0.5-1.5 mm (22-14 AWG) wires. Use 85°C rated wires if there are no external heat sources nearby. Put ferrules and sleeves on wires before connecting to terminals.
Follow all applicable electrical codes. Install and operate all equipment according to national and local standards. All wirings should be performed by qualified personnel.
Control devices may fail in an unsafe condition, resulting in unexpected operation of managed equipment. Such unexpected action could result in death or serious personal injury, and/or equipment damage. Always install emergency stop switch, electromechanical override, and other redundant safeguards that are independent of the programmable controller.
Connect a power supply that meets the voltage rating, shown on the front panel. A Cybro controller may fail in an unsafe manner or present an electrical shock hazard to personnel if 230VAC is applied to terminals intended for 24V. Such failure could result in death or serious personal injury and/or equipment damage. Always supply 24V source that provides safe electrical separation from 230VAC. Never touch the terminals while the power is on. There is a risk of an electric shock, which could result in death or serious personal injury.
For AC loads switching use resistor/capacitor suppressors across either the load or the AC output.
R > 0.5 x Vrms [Ů]C = 2 to 4 nF for each 10VA of load
You can also use metal oxide varistor (MOV) to limit peak voltage. MOV voltage should be at least 20% greater than the nominal line voltage.
24V transistor outputs contain protective clamping diodes adequate for most applications. In case of large inductive load use external suppression diode (1N4007 or equivalent). You may also use suppression diode for DC loaded relay contacts.
VIN QX
+24V
0Vinductive
load
Warning
Warning
Caution
Caution
C
inductiveload
MOVR
C
QX C
inductiveload
MOV
R C
QX
Switch panel wiring
WRONGOK
Wiring
unshielded twisted pair 2x2 0.5mm2
Recommended bus cable
Bus wires (orange terminals)
Other wires (gray terminals)
0.25-0.75mm2
0.25-2.5mm2
10-12mm
10-12mm
Wire strip
Solid wire i
1. Push wire in the clamp hole
Stranded wire insertion
1. Push screwdriver in the operating slot2. Insert wire in the clamp hole
Solid/stranded wire removal
1. Push screwdriver in the operating slot2. Remove wire
nsertion
clamp hole
operating slot
Push-wire handling
solid
stranded
fine-stranded
fine-stranded, tined
fine stranded, tip bonded
stranded with ferrule (recomended)
Wire type
GN
D
incoming cable outgoing cable
CA
NL
CA
NH
+24V
24V
CAN
Field connection
50mm
10-12mm
1. Take one ingoing and one outgoing wire together, and remove insulation for about 10-12mm.
2. Crimp wires together into a ferrule.
3. Wrap wires together for a few centimeters.
4. Push ferrules into clamps.
Ferrule
Inside the switchboard bus is connected using flat cable assembly with modular RJ9 connectors. Outside the switchboard bus is connected using unshielded twisted-pair cable, inserted into orange push-wire terminals.
Switch panel and field modules
switchboard field modules
UTP
flat cable
IEX-2 bus
PWR (green)
IEX2 (red)
on
blinking
power supply ok
communication ok
ActionStatus
on no communication
-
check wiring
-
blinking internal error replace module
off
off
no power supply
no communication
check power supply
check wiring
Each IEX-2 module has PWR and IEX LEDs, visible when cover is lifted.
Status LED
Technical specifications
Power supply 24V (18..28V)Baud rate 20, 50, 100 (default), 250, 500kbpsBaud switching PLC: select when sending kernel
IEX: auto selectable on power onTermination resistor 120 Ohm 0.25WRecommended cable unshielded twisted pair 2x2 0.5mm2
IEX-2 bus connects peripheral devices to main controller. It is based on CAN 2.0B extended frame protocol. Four wires are used, +24V/GND for power supply and CANL/CANH for communication. CAN is deterministic bus with short prioritized messages, response time is in milliseconds.
Each module has unique 21-bit network address (NAD). Module can also have alias address, assigned with IEX Manager. When alias is set, original address can't be used. Setting alias to zero reverts module to the original address.
Residential modules (HIQ) are subset of IEX modules. They fully comply to the specification, but also have additional features: internal functionality, internally stored parameters and autoaddressing.
General
Regarding the bus length, two aspects should be considered:
1. Voltage dropWire resistance causes voltage drop. It depends on cable length, wire gauge and power consumption. Gauge must be selected to ensure each module has a minimum voltage, otherwise additional power supply must be inserted between the modules.
2. Signal delayCommunication speed is limited with propagation time and topology. With the default 100kbps, up to 100m can be used without restrictions. Longer cable must be connected as a line and properly terminated.
Bus length
Topology MESH LINE
100kbps 100m 300m 50kbps 200m 500m 20kbps 500m 1000m
Network topology
LINE
MESH
Termination
+24V
CANH120
CANL
GND
Bus termination ensures proper noise immunity. Cybro is terminated internally, other side should have external 120 Ohm resistor. With mesh topology, each stub is terminated, total resistance is 120 Ohm. As with previous example, with 4 stubs each should have 480 Ohm.
24V 23V 22V 21V 19V20V 18V 17V
WRONG
24V 23V 22V 21V 23V 22V 21V24V
OK
Secondary power supply
local functionalitydry contact inputsconfiguration in local EEautoaddressing by positionlimited stand-alone operation
Residential
simple I/Oopto-coupler inputsconfiguration in controlleraddressed by serial numbercan't work without controller
Industrial
simple I/Odry contact inputsconfiguration in controlleraddressed by serial numbercan't work without controller
Building
Product range
industrial
building
building
Legend
no ground
optionalground
ground
RS232 connection
RS232device
RS232max. 10m
RS485 connection
RS485device
RS232distance 20cm
CAD-232-A2
RS485max. 1000m
+24V line may be cut off, depending on type of power supplies. If they can work in parallel, leave it connected. GND line (digital ground) must be connected to all devices, failure to do so may result in severe damage. GND is never grounded, cable shield may be grounded or not. Generally, it is grounded in industrial, and left floating in home and building applications.
Connecting switch panels
+24V +24V
GNDCANLCANH+24V
GND GND
powersupply
optionalpowersupply
switch panel 1 switch panel 2230V230V
switchessensors
switchessensors
universalinput/output
IEX-2
actuators actuatorsCPU
powersupply
24Vdc
24Vdc
inputpowersupply
Industrial environment
230V
230V
230V
switchessensors
switchessensors
universalinput/output
IEX-2
actuators actuatorspowersupply
24Vdc
24Vdc
Home and building environment
230V230V
Supply and grounding
Cybro-2programmable controller10 opto-coupler inputs 24V8 relay outputs 5AEthernet, IEX-2, 2x RS-232
Wiring diagram
on - power onoff - power offblink - error
on - runoff - stopblink - error
collisionactivity
PWR led0.5Hz blinking,RUN led off
Error signaling
PWR led on,RUN led1Hz blinking
PWR led on,RUN led5Hz blinking
Diagnostics / Action
hardware error, replace unit
program error, send program
kernel error, send kernel
LED signalling
Outputs QX0-QX4 are galvanically separated from QX5-QX7. Mixing of 230V and 24V groups is allowed.
IX0-IX7 are 24V bidirectional inputs - both P-type and N-type connection is possible. IX8A and IX9B are unidirectional inputs for P-type connection only.
Each analog input can be set independently to voltage or current measurement:DIP switch ON: 0(4)..20 mADIP switch OFF: 0..10V
+24V
0V
+24V 0V
230V outputs
M M230V~
L
N
P-type inputs(common plus)
N-type inputs(common minus)
Analoginputs
V
Analog inputsand output
24V outputs
24V externalpower supply
+24V
0V
IX6
28
IX7
29
C4
30
IX8A
31
IX9B
32
Z
33
C2
34
IW2
35
IW3
36
+24V
19
0V
20
C3
21
IX0
22
IX1
23
IX2
24
IX3
25
IX4
26
IX5
27
10
C1
11
QX5
12
QX6
13
QX7
14 15
QW0
16
IW0
17
IW1
18
C2230V~1
L
2
N
3 4
C0
5
QX0
6
QX1
7
QX2
8
QX3
9
QX4
CYBRO-2-24-E 24V power supplyCYBRO-2-230-E 230V power supply
Order code
industrial building
The RUN/STOP switch determines the program state after applying power supply. If the switch is in the RUN position, CyBro-2 will automatically start executing the program. If the switch position is altered, the program state will be changed accordingly.
If CyBro-2 is connected to the PC, it is possible to send a new program and change the program state from the PC, regardless of the switch position.
RUN/STOP switch
No No
1 19
2 20
3 21
4 22
5 23
6 24
7 25
8 26
9 27
10 28
11 29
12 30
13 31
14 32
15 33
16 34
17 35
18 36
Name Name
230V~(+24V=) +24V
230V~(0V=) 0V
- C3
C0 IX0
QX0 IX1
QX1 IX2
QX2 IX3
QX3 IX4
QX4 IX5
C1 IX6
QX5 IX7
QX6 C4
QX7 IX8A
- IX9B
QW0 Z
IW0 C2
IW1 IW2
C2 IW3
Description Description
power supply 230V~(power supply 24V= version) power output
power supply 230V~(power supply 24V= version) power output
not connected common for ix000-ix007
common for qx000-qx004 ix000
qx000 ix001
qx001 ix002
qx002 ix003
qx003 ix004
qx004 ix005
common for qx005-qx007 ix006
qx005 ix007
qx006 common for ix008A-ix010Z
qx007 ix008A
not connected ix009B
qw000 Z
iw000 analog common
iw001 iw002
analog common iw003
Terminals
IEX
-2
1 - TxD2 - RxD4 - GND
RS-232 Ethernet UTPcable autodetection
STOP RUN
COM1 COM2 ETHERNET
10
C1
11
QX5
12
QX6
13
QX7
14 15
QW0
16
IW0
17
IW1
18
C2230V~1
L
2
N
3 4
C0
5
QX0
6
QX1
7
QX2
8
QX3
9
QX4
IX6
28
IX7
29
C4
30
IX8A
31
IX9B
32
Z
33
C2
34
IW2
35
IW3
36
+24V
19
0V
20
C3
21
IX0
22
IX1
23
IX2
24
IX3
25
IX4
26
IX5
27
12 - CANH3 - CANL4 - GND
- +24V
4 1
1 81 4
Ports
power
AB
Z
1920303132
33
+24V0VC4IX8AIX9B
Z
incrementalencoder
19power 20
3031A32
+24V0VC4
incrementalencoder IX8A
IX9B
counting up counting down
power
A
1920303132
+24V0VC4IX8AIX9Bincremental
encoder
power
AB
1920303132
+24V0VC4IX8AIX9Bincremental
encoder
1
1
x4
x1
2 3 40 - 8
20 3
5 96 107 11 10
2
9- 8 7 6
1
5 4
A
B
High speed counter
A x1 (single phase, single precision)
AB x1 (dual phase, single precision)AB x4 (dual phase, double precision)
AB+Z x1 (dual phase + zero, single precision)AB+Z x4 (dual phase + zero, double precision)
CyBro-2-230 (230VAC)
QX
IX
CPU IEX
IW
QW
230V~
24Vout
CyBro-2-24 (24VDC)
QX
IX
CPU IEX
IW
QW
24Vout
24V=
Galvanic isolation Technical specifications
System clock 24MHzInstruction execution 250ns per basic instructionProgram memory 512Kb flash, 64Kb available for user programData memory 128Kb RAM, 32Kb available for user dataData types bit, integer, long, real, word, timer, counterData retention min. 7 days (retentive variables)
unlimited (EE variables)Timer base 10ms, 100ms or 1sNumber of i/o points 10 digital inputs (2 shared with HSC)
1 dedicated digital input (HSC zero)8 digital outputs4 analog inputs1 analog output
Digital inputs
Input type IX0..IX7: 24V 7mA, opto isolated, bidirectionalInput type IX8..IX9: 24V 7mA, opto isolated, common groundDebounce filter 0 or 5ms software selectable
Digital outputs
Output type relay 5A/250VAC or 3A/30VDC resistive, normally open
Analog inputs
Input type 0..10V or 0(4)..20 mA, selectable by DIP switchesInput resistance 40 kohm (0..10V)
250 ohm (0..20mA)Resolution 8 bitsAccuracy typ. 2% of FSR at 25°C
Analog output
Output type 0..10VOutput current max. 10mAResolution 8 bitsAccuracy typ. 2% of FSR at 25°C
HSC (high speed counter)
Input frequency max. 10kHz (50% duty cycle)Operation mode single phase (A x1)
dual phase (up/down, AB x1)dual phase with zero (up/down, AB+Z x1)dual phase high precision glitch removal (up/down, AB x4)dual phase high precision g.r. with zero (up/down, AB+Z x4)
RTC (real-time clock)
Accuracy max. +/-5 sec/day, typ. +/-2 sec/day (at 25°C)
IEX-2 bus
Bus load max. 31 modulesBaud rate 20, 50, 100 (default), 250, 500kbps, software selectableCable length max. 300m (100kbps, terminated)
max. 100m (100kbps, non-terminated)
Operating conditions 0..50°C, 0..85% rh non-condensingLevel of ambient pollution 2Mounting DIN rail (35mm)Dimensions 106x117x58mmWeight 380gDegree of protection IP20Installation category IIStandards EN 61010-1, EN 61010-2-201, EN 61131-2
CyBro-2-230
Power supply 230VAC (100-240VAC), 50/60HzPower consumption typ. 4W (CPU, no external load)
typ. 5W (CPU + 8 relays, no external load)Power output (24Vout+IEX) 24V max. 320mA (at 85..260VAC, max. 50°C)
24V max. 500mA (at 230..240VAC, max. 40°C)
CyBro-2-24
Power supply 24VDC (19-28VDC)Nominal power rating typ. 4W (CPU, no external load)Power consumption typ. 5W (CPU + 8 relays, no external load)Power output (24Vout+IEX) 24V 2A
Cybro-3programmable controller12 opto-coupler inputs 24V10 relay outputs 8A4 universal input/outputsEthernet, USB, IEX-2, 2x RS-232EnOcean gateway (optional)24V DC power supply
Order code
Cybro-3-24 24V power supplyCybro-3-ENO-24 24V power supply, EnOcean gateway
PLC status
PWR
RUN
on
pause (2s)
program error (1s)
no kernel (1s)loader
kernel
hardware error (0.1s)
For more details, check CyPro status bar.
run
off
stop
CyPro/Examples/CybroDashboard
- A-bus programming port- power supply (CPU only)
- A-bus programming port- Modbus RTU slave- free programmable port
- programming port- Modbus TCP slave
A-bus
- IEX-2 expansion modules- A-bus programming port
+24V
0V
+24V
+24V
0V
0V230V
P-type inputs,common +
Power supply
N-type inputs,common -
universalinput/outputs
+24V L
0V N
or
+24V
+24V
digital input
digital output
0-10V input (signal converters)
0-20mA input (4-wire transmitter)
4-20mA input (2-wire transmitter)
0-10V output (dimmer, valve)
temperature sensor (ES)
19 20
IX1
21
IX2
22
IX3
23
IX4
24
IX5
25
IX6
26
IX7
27
C5 IX0
1 2
+24V 0V
3 4
QX0
5
C0
6
QX1
7
QX2
8
C1
9
QX3
10
QX4
11
C2 C3
12
QX5
13
QX6
14 15
QX7
16
QX8
17
C4
18
QX9
IX8
28
IX9
29
IX10
30
IX11
31 32
IO12C
33
IO13
34
IO14
35
IO15
36
Cybro-3
CAN
RJ912 - CANH3 - CANL4 - GND
- +24V
4 1
1 - TxD2 - RxD4 - GND
RS-232
RJ9
Ethernet
RJ45
USB
1 - Tx+2 - Tx-3 - Rx+6 - Rx-
1 81 4
industrial building
No No
1 19
2 20
3 21
4 22
5 23
6 24
7 25
8 26
9 27
10 28
11 29
12 30
13 31
14 32
15 33
16 34
17 35
18 36
Name Name
+24V DC C5
0V IX0
- IX1
QX0 IX2
C0 IX3
QX1 IX4
QX2 IX5
C1 IX6
QX3 IX7
QX4 IX8
C2 IX9
QX5 IX10
QX6 IX11
C3 C
QX7 IO12
QX8 IO13
C4 IO14
QX9 IO15
Description Description
power supply common for ix00..ix11
power supply digital input ix00
not connected digital input ix01
relay output qx00 digital input ix02
common for qx00 and qx01 digital input ix03
relay output qx01 digital input ix04
relay output qx02 digital input ix05
common for qx02 and qx03 digital input ix06
relay output qx03 digital input ix07
relay output qx04 digital input ix08
common for qx04 and qx05 digital input ix09
relay output qx05 digital input ix10
relay output qx06 digital input ix11
common for qx06 and qx07 common for io12..io15
relay output qx07 universal input/output io12
relay output qx08 universal input/output io13
common for qx08 and qx09 universal input/output io14
relay output qx09 universal input/output io15
Terminals
CAN diagnostic
Rx
Rx
CANH
Tx
Tx
CANL
CAN traffic
CAN error counters
CAN DC voltage
55 mps
1
2.82V
50 mps
2
2.81V
A set of indicators related to health. Irregular values, caused by chip defect or short circuit, are noticed before a major malfunction occur.
bus Number of transmitted and received messages per second. Overload may cause a slower response time.
Current state of CAN error counters. High number may be caused by harsh environment or bad wiring.
DC voltage measured on bus lines. More then 10% difference between lines indicate a hardware fault.
Galvanic isolation
230V
Legend
1.5kV
4kV
24V QX0QX1
COM1
QX2QX3
COM2 USB
IX0..IX11
QX4QX5
QX6QX7
QX8QX9
Ethernet
IO12..IO15
IEX-2CPU base
* Surge suppress diode
** Leakage compensation resistor
It is a good practice to connect a diode in parallel with inductive load. Universal i/o pins are protected, but spikes induced by switching the load could cause EMC problems on neighbouring cables and other equipment.
Because of leakage current, high-efficiency LED may faintly lit when output is off. To compensate the leakage, add 4k7 resistor.
analog input 0..20mA
analog input 0..10V
analog output 0..10V
digital input
high-speed counter
frequency meter
digital output
pulse train output
PWM output
temperature sensor
IQ
IQ
LED
LED
stepper motorwith control logic
dimmer
dimmer
**
**
C
CIQ
C
C
C
C
C
+24V
+24V
+24V
IQ
IQ
IQ
+24V
IQ
IQ
IQ
IQ
IQ
C
C
C
+
+
+5..24V
+5..24V
+12V
+3.3V
+3.3V
5k6
250
1k5
1k5
+
*
2-wiretransmitter
4-wiretransmitter
Universal input/output
Terminal C is internally connected to digital ground (GND).
A shielded cable is recommended. Shield is connected to C terminal.
A shielded cable is recommended. Shield is connected to C terminal.
Analog voltage measurement is available as iw input at the same time.
Analog voltage measurement is available as iw input at the same time.
Input type must be configured before sensor is connected. Failing to do so may permanently damage the sensor.
IQ
IQ
IQ
C
encoder
High-speed counter
number of pulses
1
1
2
2
3
3
4
+1+1 -1
4 5 6 7 8 9 10 11 12 13 14
encoder
single phase (up only) dual-phase (up/down)
A A
B
IO12
IO13
IO14
IO15
qx12
qx13
qx14
qx15
A A
A
B
B
A
A
A
A, B - counter inputsCNT - number of pulses countedRST - reset counter to zero
Extend counting range from 16 to 32-bit:
var long cnt, int iw12_old;
cnt := cnt + (iw12 - iw12_old);iw12_old := iw12;
RST
RST
RST
RST
CNT CNT
CNT
CNT
CNT
CNT
iw12
iw13
iw14
iw15
IO12
IO14
IO13
IO15
qx12
qx14
RS
TR
ST
iw12
iw14
Frequency meter
1000ms 1000ms 1000ms 1000ms 1000ms
V to fconverter
IO12
IO13
IO14
IO15
FREQ - measured frequency [Hz]
Pulses are counted in a period of 1000ms.
FREQ
FREQ
FREQ
FREQ
iw12
iw13
iw14
iw15
0% 10% 50% 90% 100%
PWM output
load
IO12
IO13
IO14
IO15
frequency
PWM
PWM
PWM
PWM
PWM - output pulse width 0..100%
Frequency setting is the same for all outputs [Hz].
Outputs must be assigned in order IO12, IO13, IO14, IO15.
qw12
qw13
qw14
qw15
ramp frequency
number of pulses
ramp
Pulse train output
steppermotor
IO12
IO13
IO14
IO15
qx12
qx13
qx14
qx15
ramp
frequency
ix12
ix13
ix14
ix15
iw12
iw13
iw14
iw15
PUL
PUL
PUL
PUL
PUL - number of pulses requestedRUN - start signal (1-run)CNT - total number of pulses countedSTA - status (0-stop, 1-running)
Frequency and ramp are sampled when pulse trainis started. After the run request is cleared, changesdoes not affect the output. That given, each channelcan run on it's own frequency.
RUN
RUN
RUN
RUN
STA
STA
STA
STA
CNT
CNT
CNT
CNT
qw12
qw13
qw14
qw15
System clockWatch dogProgram memoryData memoryData retentionRTC accuracy
Internal temperatureSupply measurement
Input typeDebounce filterSampling timeGalvanic isolation
Output type
Continuous load
Recommended fuse
Galvanic isolation
Contact type
Input typeDebounce filterSampling timeGalvanic isolation
Output typePermanent loadProtectionLeakage currentGalvanic isolation
Input typeMeasuring rangeResolutionReadoutInput resistanceAccuracyTemperature driftGalvanic isolationSampling time
Input typeMeasuring rangeResolutionReadoutInput resistanceAccuracyTemperature driftGalvanic isolationSampling time
100MHz, 10ns per instruction100ms software, 250ms hardware896Kb for user program64Kb for user variables7 days at 25°Ctyp. ±2 sec per day at 25°C0..42V, typ. ±1% of full scale-50..150°C, ±5°C, on CPU board
24V 7mA, opto isolated, bidirectional1ms (5x 200us)5ms230V IX to 24V supply, optocoupler
relay 8A/250VAC or 8A/30VDC resistive
6A each relay10A common terminal two relays25A all relays6A MCB type B each relay10A MCB type B common terminal two relays4kV QX to 24V supply230V QX0/1 to QX2/3, QX4/5 to QX6/7 to QX8/9
normally open
dry contact, internal pull-up 12V 3mA1ms (5x 200us)5msnone
NPN transistor 30V 1A1.5A qx12+qx13 and short circuit, overvoltage, overtemperature250uAnone
1.5A qx14+qx15
0..10V0..14V12 bitsmV (10V=10000)100 kohmtyp. ±1% of full scale at 25°C50ppm/°Cnone10ms
4..20mA0..24mA12 bitsuA (20mA=20000)250 ohmtyp. ±1% of full scale at 25°C100ppm/°Cnone10ms
CPU board
Technical specifications Universal input/output
Digital input (ix00..ix11)
Digital output (qx00..qx09)
Digital input (ix12..ix15)
Digital output (qx12..qx15)
Analog input 0..10V (iw12..iw15)
Analog input 4..20mA (iw12..iw15)
Analog output 0..10V (qw12..qw15)
Output typeOutput rangeResolutionReadoutOutput currentAccuracyTemperature driftGalvanic isolationSettling time
0..10V0..10.2V12 bitsmV (10V=10000)10mA sink/sourcetyp. ±1% of full scale at 25°C50ppm/°Cnone10ms
Input typeConnection protocolMeasuring rangeResolutionReadoutAccuracyCable lengthRecommended cable
ES digital sensor DS1-wire digital thermometer-50..+125°C12 bits (750ms conversion time)0.1°C (245=24.5°C)typ. ±0.2°C, max. ±0.5°C (-10°C to +85°C)20mUTP 0.25..0.5mm2
( 18B20)
Temperature sensor (iw12..iw15)
General
Operating conditionsStorage temperatureLevel of ambient pollutionPower supplyPower consumption
IEX-2 power outputResettable fuse trip timeResettable fuse recover timeResettable fuse life
TerminalsMountingDimensionsWeightDegree of protectionInstallation categoryStandards
0..50°C, 0..85% rh non-condensing-40..85°C224V (18..28V)50mA (no load)180mA (10 relays, 4x 10Vout)24V 2A (limited by resettable fuse)10s at 200% overload48 hours with power off100 cycles
2.5mm2, 15A, removableDIN rail (35mm)106x117x58mm280gIP20IIIEN 61010-1, EN 61010-2-201, EN 61131-2
IEX-2
COM1/COM2
High speed counter (iw12..iw15, qx12..qx15)
Frequency meter (iw12..iw15)
Pulse train output (qw12..qw15, qx12..qx15, ix12..ix15)
PWM output (qw12..qw15)
USB
Ethernet
Bus loadBaudrateGalvanic isolationCable length
ConnectorProtocol
TypeGalvanic isolationCable lengthConnectorProtocol
TypeCounting resolutionMaximum frequencyCounter sizeElectrical characteristics
Frequency rangeIntegration timeElectrical characteristics
Frequency rangeAcceleration/decelerationCounter sizeElectrical characteristics
Duty cycleOutput resolutionFrequency rangeElectrical characteristics
TypeProfileGalvanic isolationConnectorPower supplyProtocol
TypeAuto-MDIXGalvanic isolationConnectorProtocol
48 modules (Cybro + 47 IEX-2)20, 50, 100 (default), 250, 500kbpsnone100m (100kbps, non-terminated)300m (100kbps, terminated)500m (50kbps, terminated)RJ9IEX-2 master (CAN 2.0B)A-bus slave
RS232none10mRJ9A-bus slaveModbus RTU slavefree programmable
single phase (up) or dual phase (up/down)1x (single phase) or 4x (dual phase)5kHz with 50% duty cycle16-bit (-32768..32767)internal pull-up 3.3V 2mA, 24V tolerant
0..5kHz with 50% duty cycle1000msinternal pull-up 3.3V 2mA, 24V tolerant
20Hz..2.5kHz0..2500ms16 bits (1..65535 pulses)same as universal digital output
0..100%8 bits20Hz..2.5kHzsame as universal digital output
USB 2.0USB-SERIAL CH340nonemicro USB type B5V 100mA, only for CPUA-bus slave
10/100Mno1500V transformerRJ45A-bus slaveModbus TCP slave
Cybro-3Hprogrammable controller3 digital inputs4 relay outputs 8A4 universal input/outputsEthernet, USB, IEX-2, 2x RS232, 1x RS485EnOcean gateway (optional)230V AC power supply
Order code
Cybro-3H-230 230V AC power supplyCybro-3H-ENO-230 230V AC power supply, EnOcean gateway
Input type (ix00..ix02)Cable length
COM1 typeCable lengthTransmit/receiveGalvanic isolation
Power supplyPower consumptionPower output
Standards
Other specifications are the same as Cybro-3.
dry contact, internal pull-up 12V 2mA50m
RS485 two wire500mautomatic switching1kV
100..240VAC, 50/60Hz1W (no load), 10W max.24V 200mA (IEX-2+universal i/o)
EN 60730-1
Technical specifications
230V COM1RS485
IEX-2
L
N
universalinput/outputs
digitalinputs
IX0
28
IX1
29
IX2
30
+24V
31 32
IO12GND
33
IO13
34
IO14
35
IO15
36
Cybro-3H
1 2
L N
3 4
QX0
5
C0
6
QX1
7
QX2
8
C1
9
QX3100-240V~
10 11 12 13 14 15 16 17 18
A GND CANL CANH +24VB C
+24V
+24V
digital input
digital output
0-10V input (signal converters)
0-20mA input (4-wire transmitter)
4-20mA input (2-wire transmitter)
0-10V output (dimmer, valve)
temperature sensor (ES)
building
Cybro-Pi3Raspberry Pi 3B+16Gb micro SD (empty)PiCAN2 controllerwatchdog timerRS485/M-bus serial driver24-to-5V voltage regulator1 pushbutton2 digital inputs2 relay outputs 8A
PWRSTAERR
RXTXWDSIEX
SW1IX0IX1RE0RE1
power supplydevice statusdevice error
serial receiveserial transmitwatchdog signalCAN bus activity
push buttondigital inputdigital inputrelay outputrelay output
+5VGPIO2/SDAGPIO3/SCL
GPIO15/RXDGPIO14/TXDGPIO27CANH/CANL
GPIO4GPIO17GPIO18GPIO23GPIO24
-0-active0-active
0-active0-active0-active0-active
0-pressed0-closed0-closed1-active1-active
connected to +5V power supplydigital output, controlled by user applicationdigital output, controlled by user application
controled by primary UART (/dev/serial0)controled by primary UART (/dev/serial0)digital output, controlled by user applicationcontrolled by CAN controller (SPI0/CAN0)
digital input, readable by user applicationdigital input, readable by user applicationdigital input, readable by user applicationdigital output, controlled by user applicationdigital output, controlled by user application
Input/output mapping
RS485 M-BUS
serial port
watchdog
S0S1S2
0
1
ETH
IEXleft
IX0 C IX1
IEX right
ON OFF
IEX terminationHDMI
micro SD
USB USB
powersupply
230VAC
+24V 0V AM+
BM-
C RE0 C0 RE1
RX
SW1
TX WDS IEX
PWRPWR STAACT ERR
Raspberry Pi
building
Serial port (/dev/serial0)
Meter-Bus
M+M-M-BUS
M+ M+ M+M- M- M-
maximum 3 devices
Modbus
ABC
maximum 32 devices
RS485default
A A A A AB B B B BC C C C C
Push button
short press
long press (10s)keep pressed until PWR blinks
user-defined actionhandled by user application
hard resethandled by power supply hardware
action
SW1
STA
reset10s boot
PWR
SW1
Push button is accessable using a small 2mm screwdriver. It can be used to start a custom action (short press), or to reset device (long press).
IEX termination
When termination resistor is connected at the end of the CAN line, jumper must be in OFF position.
ONdefault
OFF
terminationresistor
normal operation application hangs
period
system boot
delay
WDS
PWR
0
0
1
1
1
1
1
0
1
1
0
1
1
0
1
60s
-
first edge
first edge
60s
1s
-
1s
10s
10s
-
production
disabled
-
development
SET2 SET1 SET0 delay period description
RPi WDG
WDS
PWR
Watchdog settings
S2 S1default
S0
1
0
Watchdog is hardware device used for monitoring your application. Application must send a continuous stream of pulses on WDS line. When pulse is missing, watchdog will reset your Raspberry. This prevents application to permanently lock up, for any reason.
Watchdog can be activated by the first WDS edge, or 60 seconds after power on. Period is configured between one pulse per second, or one pulse per 10 seconds. Minimum pulse width is 100ns, maximum frequency is not limited.
Application examples
Combine the abundance of Raspberry projects with reliability of Cybro controller and expansion modules
* IEX driver will be available soon
OpenIoT
Raspberry OS
Mosquitto
OpenThread
Node-RED
SCGI Server
Cybro IEX modules
TCP/IP IEX driver
CoAP WebScada
Apache
Input typeGalvanic isolation
Output typeContinuous load
Galvanic isolation
Power supplyMountingDimensionsWeightDegree of protection
1. Choose OS, write RPi bootable image on uSD2. Connect power supply and communication3. Install SCGI server and (optionally) web scada4. Install Raspberry project you are interested in5. Write code to integrate Cybro into your project
dry contact, internal pull-up 12V 2mAnone
relay 8A/250VAC resistive, normally open6A each relay10A both relays4kV, relay contact to 24V power supply
24V (18..28V), 120mA typ., 400mA max.DIN rail (35mm)106x117x32mm185gIP20
Technical specifications
Quick start
Raspberry aloneRaspberry, Cybro and IEX modules
Configuration
24V24V
Raspberry can read and write Cybro variablesthrough local TCP/IP network.
Integrated CAN controller enables Raspberry toread and write Cybro variables through IEX bus.
Raspberry-to-Cybro connection
1. TCP/IP
ETH ETH
2. CAN
Bio-24RIEX-2 module
12 relay outputs 5A12 opto-coupler inputs 24V
Wiring diagram
IX6
28
C9
29
IX7
30
IX8
31
C10
32
IX9
33
IX10
34
C11
35
IX11
36
IX0
19
C6
20
IX1
21
IX2
22
C7
23
IX3
24
IX4
25
C8
26
IX5
27
10
QX6
11
C3
12
QX7
13
QX8
14
C4
15
QX9
16
QX10
17
C5
18
QX11
1
QX0
2
C0
3
QX1
4
QX2
5
C1
6
QX3
7
QX4
8
C2
9
QX5
power supplyfor outputs
+24V
0VM 230V~
L
N
power supplyfor inputs
+24V
0V
Technical specifications
Input type 24V 7mA, opto isolated, bidirectionalDebounce filter 0, 5 or 100ms, software selectable
Output type relay 5A/250VAC or 3A/30VDC resistiveContact type normally openContinuous load 3A each relay
36A all relays
Power supply 24V (18..28V), 260mA(20mA+11mA*active outputs+9mA*active inputs)
Galvanic isolation 4kV between inputs and internal circuit4kV relay contact
Operating conditions 0..50°C, 0..85% rh non-condensingMounting DIN rail (35mm)Dimensions 106x117x58mmWeight 320gDegree of protection IP20Installation category IILevel of ambient pollution 2Standards EN 61010-1, EN 61010-2-201, EN 61131-2
industrial
Each group of two inputs (IX0/1, IX2/3...)can be connected as either common GNDor common +24V. Wiring diagram showsonly one of possible combinations.
building
Bio-24TIEX-2 module
12 opto-isolated PNP outputs 1A12 opto-coupler inputs 24V
Technical specifications
Input type 24V 7mA, opto isolated, bidirectionalDebounce filter 0, 5 or 100ms, software selectable
Output type PNP transistor 30V 1AProtection short circuit, overcurrent and reverse supply
Power supply 24V (18..28V), 80mAGalvanic isolation 4kV between inputs and internal circuit
4kV relay contact
Operating conditions 0..50°C, 0..85% rh non-condensingMounting DIN rail (35mm)Dimensions 106x117x58mmWeight 270gDegree of protection IP20Installation category IILevel of ambient pollution 2Standards EN 61010-1, EN 61010-2-201, EN 61131-2
Wiring diagram
power supplyfor inputs
+24V
0V
IX6
28
C4
29
IX7
30
IX8
31
C5
32
IX9
33
IX10
34
C6
35
IX11
36
IX0
19
C1
20
IX1
21
IX2
22
C2
23
IX3
24
IX4
25
C3
26
IX5
27
10
QX6
11
C0
12
QX7
13
QX8
14 15
QX9
16
QX10
17
0V +24V
18
QX11
1
QX0
2
C0
3
QX1
4
QX2
5
C0
6
QX3
7
QX4
8
C0
9
QX5
power supplyfor outputs
+24V
0V
Each group of two inputs (IX0/1, IX2/3...)can be connected as either common GNDor common +24V. Wiring diagram showsonly one of possible combinations.
industrial building
Bio-24PWMIEX-2 module
24V (4 pulse counters)12 opto-isolated PNP outputs 1A (6 PWM outputs)12 opto-coupler inputs
Technical specifications
Input type 24V 7mA, opto isolated, bidirectionalPulse counter IX0..IX3 (4 independent counters)Input frequency max. 1kHz, 50% duty cycle
Output type PNP transistor 30V 1AProtection overload, short circuit and reverse supplyPWM outputs QX0..QX5 (6 independent outputs)PWM frequency 250Hz or 500Hz, software selectablePWM range 0..100% in 40 steps (250Hz), 0..100% in 20 steps (500Hz)
Power supply 24V (18..28V), 80mAGalvanic isolation 4kV between inputs and internal circuit
4kV between internal circuit and output transistors
Operating conditions 0..50°C, 0..85% rh non-condensingMounting DIN rail (35mm)Dimensions 106x117x58mmWeight 270gDegree of protection IP20Installation category IILevel of ambient pollution 2Standards EN 61010-1, EN 61010-2-201, EN 61131-2
Wiring diagram
+24V+
0V
power supplyfor inputs
power supplyfor outputs
+24V
0V
+ + + + +
PWM outputs
pulse inputs
IX6
28
C4
29
IX7
30
IX8
31
C5
32
IX9
33
IX10
34
C6
35
IX11
36
IX0
19
C1
20
IX1
21
IX2
22
C2
23
IX3
24
IX4
25
C3
26
IX5
27
10
QX6
11
C0
12
QX7
13
QX8
14 15
QX9
16
QX10
17
0V +24V
18
QX11
1
QX0
2
C0
3
QX1
4
QX2
5
C0
6
QX3
7
QX4
8
C0
9
QX5
Each group of two inputs (IX0/1, IX2/3...)can be connected as either common GNDor common +24V. Wiring diagram showsonly one of possible combinations.
industrial building
Bi-24IEX-2 module12 digital inputs6 analog/digital inputs6 NPN outputs 1A (6 digital inputs)
Wiring diagram
IX12 IX14 IX16C0 C0 C0IX13 IX15 IX17 IX18 IX20 IX22C0 C0 C0IX19 IX21 IX23
24V power supply
+24V
0V
Input type , internal pull-up 12V 2mAAnalog input 0..10V, 6 kohmResolution 10 bits (0..1023)Accuracy typ. 2% of FSR at 25°C
Output type NPN transistor 30V 1AProtection short circuit, overcurrent, voltage clamp
Power supply 24V (18..28V), 60mAGalvanic isolation none
Operating conditions 0..50°C, 0..85% rh non-condensingMounting DIN rail (35mm)Dimensions 106x117x58mmWeight 250gDegree of protection IP20Level of ambient pollution 2Standards EN 60730-1
dry contact
Technical specifications
building
All common terminals are internallyconnected to GND. Wiring diagramis an example, it shows only one ofpossible combinations.
Bio-8R4IEX-2 module
8 relay outputs 16A with mains sense4 opto-coupler inputs 230V
Wiring diagram
Technical specifications
Input typeOutput type relay 16A/250VAC resistiveContinuous load 15A per relay
75A for all relays together
Power supply 24V (18..28V), 160mA(20mA+17mA*number of active relays)
Galvanic isolation 5kV between inputs and internal circuit5kV between internal circuit and relay contacts
Operating conditions 0..50°C, 0..85% rh non-condensingMounting DIN rail (35mm)Dimensions 106x117x58mmWeight 360gDegree of protection IP20Level of ambient pollution 2Standards EN 61010-1, EN 61010-2-201, EN 61131-2
230VAC 1mA, opto isolated
M
changeoverswitch
pushbuttonfor blinds
M
blinds motor
up dn
up dn
N
L
230V~
L
N
230V~
Order code
Bio-8R4-L power relay for lights and blinds
Mains sense is connected to the relaycommon contact. Wiring diagram is anexample, it shows only one of possiblecombinations.
industrial building
Bio-20RIEX-2 module10 digital inputs10 relay outputs 8A
Technical specifications
Input type dry contact, internal pull-up 12V 2mAOutput type relay 8A/250VAC or 8A/30VDC resistiveContact type normally openContinuous load 6A each relay
20A all relays (mk1)12A each relay group (mk2)
Power supply 24V (18..28V), 120mA(30mA+9mA*number of active outputs)
Galvanic isolation 4kV between internal circuit and relay contact
Operating conditions 0..50°C, 0..85% rh non-condensingMounting DIN rail (35mm)Dimensions 106x117x58mmWeight 300gDegree of protection IP20Level of ambient pollution 2Standards EN 60730-1
Wiring diagram
mk1 or no revision marking mk2
+ -
L
N
230V~
+ -
L
N
230V~
building
AiR-12IEX-2 module12 RTD inputs
2-wire
8
C
9
IW5
6
IW3
7
IW4
4
IW2
5
C
2
C
3
IW1
1
IW0
C
17
IW11
18
IW9
15
IW10
16
IW8
13
C
14
C
11
IW7
12
IW6
10
R5R4R2 R3R1R0
R11R10R8 R9R7R6
3-wire
8
C
9
IW5
6
IW3
7
IW4
4
IW2
5
C
2
C
3
IW1
1
IW0
C
17
IW11
18
IW9
15
IW10
16
IW8
13
C
14
C
11
IW7
12
IW6
10
R2R1R0
R5R4R3
Wiring diagram
Terminals
No
1
10
2
11
3
12
4
13
5
14
6
15
7
16
8
17
9
18
Name
IW0
IW6
C
C
IW1
IW7
IW2
IW8
C
C
IW3
IW9
IW4
IW10
C
C
IW5
IW11
Description
iw000
iw006
common for iw000 & iw001
common for iw006 & iw007
iw001
iw007
iw002
iw008
common for iw002 & iw003
common for iw008 & iw009
iw003
iw009
iw004
iw010
common for iw004 & iw005
common for iw010 & iw011
iw005
iw011
To achieve best accuracy, unused inputs must be short-circuited.
In 3-wire mode, temperature is iw0, iw2, iw4, iw6, iw8 and iw10; wire resistance is iw1, iw3, iw5, iw7, iw9 and iw11.
Input type Pt100/1000 (DIN751) auto selectable, measuring range -100..300°CNi100/1000 (DIN43760) auto selectable, measuring range -50..160°CNi100/1000 (Landis & Gyr) auto selectable, measuring range -50..160°Cpotentiometer 0..2000ohm
Sensor current 190uA (each sensor)Wire resistance 20ohm max. (3-wire mode)Resolution 14 bits in 0.1% mode
12 bits in 0.5% and 1% modeTemperature drift +/-0.01%/°C of measuring rangeCalibration reference 150.00ohm, 1500.0ohm
Input mode mode no.ch connection accuracy scan time integration time auto calibration0 12 2-wire 0.1% 1120ms 60ms each cycle1 12 2-wire 1% 480ms 20ms each cycle2 12 2-wire 5% 360ms 20ms every 10 minutes3 6 2-wire 0.1% 700ms 60ms each cycle4 6 2-wire 1% 300ms 20ms each cycle5 6 2-wire 5% 180ms 20ms every 10 minutes6 4 2-wire 0.1% 560ms 60ms each cycle7 4 2-wire 1% 240ms 20ms each cycle8 4 2-wire 5% 120ms 20ms every 10 minutes9 2 2-wire 0.1% 420ms 60ms each cycle
10 2 2-wire 1% 180ms 20ms each cycle11 2 2-wire 5% 60ms 20ms every 10 minutes12 1 2-wire 0.1% 350ms 60ms each cycle13 1 2-wire 1% 150ms 20ms each cycle14 1 2-wire 5% 30ms 20ms every 10 minutes15 6 3-wire 0.1% 1120ms 60ms each cycle16 3 3-wire 0.1% 700ms 60ms each cycle17 2 3-wire 0.1% 560ms 60ms each cycle18 1 3-wire 0.1% 420ms 60ms each cycle
Power supply 24V (18..28V), 50mAGalvanic isolation 1kV beetwen digital and analog circuit
no isolation between chanelsOperating conditions 0..50°C, 0..85% rh non-condensingMounting DIN rail (35mm)Dimensions 53x117x58mmWeight 160gDegree of protection IP20Level of ambient pollution 2Standards EN 61010-1, EN 61010-2-201, EN 61131-2
Technical specifications
industrial building
AiV-12IEX-2 module12 analog inputs 0..10V
Wiring diagram
Terminals
1
IW0
2
C
3
IW1
4
IW2
5
C
6
IW3
7
IW4
8
C
9
IW5
IW6
10
C
11
IW7
12
IW8
13
C
14
IW9
15
IW10
16
C
17
IW11
18
voltage input 0..10V
voltage input 0..10V
No
1
10
2
11
3
12
4
13
5
14
6
15
7
16
8
17
9
18
Name
IW0
IW6
C
C
IW1
IW7
IW2
IW8
C
C
IW3
IW9
IW4
IW10
C
C
IW5
IW11
Description
iw000
iw006
common for iw000 & iw001
common for iw006 & iw007
iw001
iw007
iw002
iw008
common for iw002 & iw003
common for iw008 & iw009
iw003
iw009
iw004
iw010
common for iw004 & iw005
common for iw010 & iw011
iw005
iw011
Input type 0..10VInput resistance 10KA/D converter V/f conversion with auto calibrationResolution 13 bits in 0.1% mode
11 bits in 0.5% and 1% modeTemperature drift +-0.01%/°C of measuring rangeScan time 30ms..980ms, depends on input modeIntegration time 60ms/20ms, depends on input modeCalibration reference 10.000V
Input mode mode no.ch accuracy scan time integration time auto calibration0 12 0.1% 980ms 60ms each cycle1 12 1% 420ms 20ms each cycle2 12 5% 360ms 20ms every 10 minutes3 6 0.1% 560ms 60ms each cycle4 6 1% 240ms 20ms each cycle5 6 5% 180ms 20ms every 10 minutes6 4 0.1% 420ms 60ms each cycle7 4 1% 180ms 20ms each cycle8 4 5% 120ms 20ms every 10 minutes9 2 0.1% 280ms 60ms each cycle
10 2 1% 120ms 20ms each cycle11 2 5% 60ms 20ms every 10 minutes12 1 0.1% 210ms 60ms each cycle13 1 1% 90ms 20ms each cycle14 1 5% 30ms 20ms every 10 minutes
Power supply 24V (18..28V), 50mAGalvanic isolation 1kV between digital and analog circuit
no isolation between chanels
Operating conditions 0..50°C, 0..85% rh non-condensingMounting DIN rail (35mm)Dimensions 53x117x58mmWeight 160gDegree of protection IP20Level of ambient pollution 2Standards EN 61010-1, EN 61010-2-201, EN 61131-2
Technical specifications
industrial building
AiC-12IEX-2 module12 analog inputs 0..20mA
Wiring diagram
Terminals
IW6
10
C
11
IW7
12
IW8
13
C
14
IW9
15
IW10
16
C
17
IW11
18
current input 0(4)..20mA
1
IW0
2
C
3
IW1
4
IW2
5
C
6
IW3
7
IW4
8
C
9
IW5
current input 0(4)..20mA
No
1
10
2
11
3
12
4
13
5
14
6
15
7
16
8
17
9
18
Name
IW0
IW6
C
C
IW1
IW7
IW2
IW8
C
C
IW3
IW9
IW4
IW10
C
C
IW5
IW11
Description
iw000
iw006
common for iw000 & iw001
common for iw006 & iw007
iw001
iw007
iw002
iw008
common for iw002 & iw003
common for iw008 & iw009
iw003
iw009
iw004
iw010
common for iw004 & iw005
common for iw010 & iw011
iw005
iw011
Input type 0..20mAInput resistance 50ohmA/D converter V/f conversion with auto calibrationResolution 13 bits in 0.1% mode
11 bits in 0.5% and 1% modeTemperature drift +-0.01%/°C of measuring rangeScan time 30ms..980ms, depends on input modeIntegration time 60ms/20ms, depends on input modeCalibration reference 10.000mA
Input mode mode no.ch accuracy scan time integration time auto calibration0 12 0.1% 980ms 60ms each cycle1 12 1% 420ms 20ms each cycle2 12 5% 360ms 20ms every 10 minutes3 6 0.1% 560ms 60ms each cycle4 6 1% 240ms 20ms each cycle5 6 5% 180ms 20ms every 10 minutes6 4 0.1% 420ms 60ms each cycle7 4 1% 180ms 20ms each cycle8 4 5% 120ms 20ms every 10 minutes9 2 0.1% 280ms 60ms each cycle
10 2 1% 120ms 20ms each cycle11 2 5% 60ms 20ms every 10 minutes12 1 0.1% 210ms 60ms each cycle13 1 1% 90ms 20ms each cycle14 1 5% 30ms 20ms every 10 minutes
Power supply 24V (18..28V), 50mAGalvanic isolation 1kV between digital and analog circuit
no isolation between chanels
Operating conditions 0..50°C, 0..85% rh non-condensingMounting DIN rail (35mm)Dimensions 53x117x58mmWeight 160gDegree of protection IP20Level of ambient pollution 2Standards EN 61010-1, EN 61010-2-201, EN 61131-2
Technical specifications
industrial building
AoV-12IEX-2 module12 analog outputs 0..10V
Wiring diagram
Terminals
1
QW0
2
C
3
QW1
4
QW2
5
C
6
QW3
7
QW4
8
C
9
QW5
QW6
10
C
11
QW7
12
QW8
13
C
14
QW9
15
QW10
16
C
17
QW11
18
voltage output 0..10V
V
V
V
V
V
V
voltage output 0..10V
V
V
V
V
V
V
No
1
10
2
11
3
12
4
13
5
14
6
15
7
16
8
17
9
18
Name
QW0
QW6
C
C
QW1
QW7
IW2
QW8
C
C
QW3
QW9
QW4
QW10
C
C
QW5
QW11
Description
qw000
qw006
common for qw000 & qw001
common for qw006 & qw007
qw001
qw007
qw002
qw008
common for qw002 & qw003
common for qw008 & qw009
qw003
qw009
qw004
qw010
common for qw004 & qw005
common for qw010 & qw011
qw005
qw011
Technical specifications
Output type 0..10VOutput current max. 10mA per chanel
max. 70mA for all chanelsResolution 8 bitsAccuracy 1% of FSRTemperature drift +-0.01%/°C of output rangeSettling time 50ms
Power supply 24V (18..28V), 120mA (50mA+output current)Galvanic Isolation 1kV between digital and analog circuit
no isolation between chanels
Operating conditions 0..50°C, 0..85% rh non-condensingMounting DIN rail (35mm)Dimensions 53x117x58mmWeight 160gDegree of protection IP20Level of ambient pollution 2Standards EN 61010-1, EN 61010-2-201, EN 61131-2
industrial building
OP-2IEX-2 module, operator panelLCD display 2x16 characters, black/green
I/O table
key_f Indicate status of operator panel F key (0-released, 1-pressed).key_e Indicate status of operator panel E (enter) key (0-released, 1-pressed).
Always zero while mask is active.key_dn Indicate status of operator panel down key (0-released, 1-pressed).
Always zero while mask is active.key_up Indicate status of operator panel up key (0-released, 1-pressed). Always
zero while mask is active.general_error A one or more system errors occured (timeout, program or bus error).timeout_error Communication failed, no messages are coming from the module.program_error Internal or configuration error detected, module is not functional.bus_error Module detected a number of communication errors, but it is still working.current_mask Indicates current mask number (read only). Zero means no mask is active.next_mask Write a mask number to send a new mask to the operator panel. After
mask is sent, will be automatically set to -1.ir_command Code received by IR receiver. Set by the system, should be cleared by
PLC program (to be able to detect same code again).lcd_dimmer Intensity of LCD backlight (0-maximum, 255-dark).lcd_timeout Time for LCD backlight to start dimming (0..120s).
IEX-2 connection RJ9Display LCD 2x16 charactersBacklight green LED, adjustable 0..100%Power supply 24V (18..28V), 40mAOperation conditions 0..50°C, 0..85% rh non-condensingDimensions 106x63x24mmWeight 120gDegree of protection IP54 (IP40 without rubber seal)Level of ambient pollution 2Standards EN 61010-1, EN 61010-2-201, EN 61131-2
Technical specifications
76.5
106
112
17
52
63
68
17
18
10
16
2.5
2.52.5
2.5
Mounting
Screw:3.5x10self-tapping
optionalrubber seal
viewdirection
9
industrial building
OP-4
Mounting
fly over on wall 100x100 dose
78 78 78
128
128
128
4.5
x50
13 25
acr
ylic
gla
ss
wall
mountin
g d
ose
deco
rativ
e f
oil
alu
min
um
fra
me
310
100
100
4.5
x70
33
acr
ylic
gla
ss
acr
ylic
gla
ss
rubber
space
r
wall
deco
rativ
e f
oil
alu
min
um
fra
me
123 810
4.5
x60
25
acr
ylic
gla
ss
acr
ylic
gla
ss
wall
deco
rativ
e f
oil
alu
min
um
fra
me
12310
Wiring diagram
rear view
IW3
/IX
3
IW2
/IX
2
IW1
/IX
1
IW0
/IX
0
TS
1
TS
0
+2
4V
CA
NH
CA
NL
GN
D
GN
D
GN
D
GN
Dtemperature
sensor
CANHCANLGND
+24V
10k
0..10V
Display LCD 2x20 charactersBacklight white LED, adjustable 0..100%IR receiver RC5 36kHz, receiving distance 5mInput type dry contact, internal pull-up 12V 2mA
analog input 0..10V (10 bit, 0..1023)External temperature sensor ES-P, ES-B or ES-WLight sensor day/night mode switching
Technical specifications
Power supply 24V (18..28V), 50mADegree of protection IP20Operating conditions 0..50°C, 0..85% rh non-condensingStorage temperature -20..75°CDimensions 142x114x25mmWeight 600gLevel of ambient pollution 2Standards EN 60730-1
IEX-2 module, operator panelLCD display 2x20 characters, white/bluelight sensor, IR receiver, beeper2 temperature sensor inputs4 switch/potentiometer inputs
9078
40
12
811
7
14
2
114
Dimensions
building
OP-5
Wiring diagramC
AN
H
CA
NL
GN
D
+24V
GN
D
TS
1
GN
D
IX0
windowswitch
temp.sens.
CANLCANH
GND
+24V
Technical specifications
Display LCD 2x20 charactersCharacters size 3x5mmKeys 5 keys, audible press feedback, adjustableBacklight blue LED, adjustable 0..100%IR receiver RC5 36kHz, receiving distance 5mInput type dry contact, internal pull-up 12V 2mA
analog input 0..10V (10 bit, 0..1023)
Temperature measurement range: 0°C to +50°Cerror: ±0.5°C typ. (0°C to +50°C, backlight at 20%) ±2°C max. (0°C to +50°C)resolution: 0.1°C (12 bit)readout: 0.1°C (254 equals 25.4°C)
Humidity measurement range: 0..100% rh, non-condensingerror: ±2% rh @ 25°Cresponse time 15sstability ±1% rh @ 50% rh in 5 years
resolution 1% (7 bit)readout 1% rh (45 equals 45% rh)
External temperature sensor ES-P, ES-B or ES-W
Power supply 24V (18..28V), 50mADegree of protection IP20Operating conditions 0..50°C, 0..85% rh non-condensingStorage temperature -20..75°CMounting wall surfaceDimensions 136x96x25mmWeight 420gLevel of ambient pollution 2Standards EN 60730-1
IEX-2 module, LCD display 2x20 characters, white/bluetemperature, humidity and light sensorIR receiver, beeper1 temperature sensor input1 switch/potentiometer input
operator panelbuilding
OP-8
Technical specifications
Display LCD 2x20 charactersCharacters size 3x5mmKeys 5 touch keys, tactile feedbackBacklight blue LED, adjustable 0..100%IR receiver RC5 36kHz, receiving distance 5mInput type dry contact, internal pull-up 12V 2mA
analog input 0..10V (10 bit, 0..1023)
Temperature measurement range: 0°C to +50°Cerror: ±0.5°C typ. (0°C to +50°C, backlight at 20%) ±2°C max. (0°C to +50°C)resolution: 0.1°C (12 bit)readout: 0.1°C (254 equals 25.4°C)
Humidity measurement range: 0..100% rh, non-condensingerror: ±2% rh @ 25°Cresponse time 15sstability ±1% rh @ 50% rh in 5 years
resolution 1% (7 bit)readout 1% rh (45 equals 45% rh)
External temperature sensor ES-P, ES-B or ES-W
Power supply 24V (18..28V), 50mADegree of protection IP20Operating conditions 0..50°C, 0..85% rh non-condensingStorage temperature -20..75°CMounting M4 installation boxDimensions 144x80x7mmWeight 200gLevel of ambient pollution 2Standards EN 60730-1
IEX-2 module, touch LCD display 2x20 characters, white/bluetemperature, humidity and light sensorIR receiver, beeper1 switch/potentiometer input1 temperature sensor input
operator panel
108
Wiring diagram
rear view
windowswitch
temperaturesensor
CA
NH
CA
NL
GN
D
+24V
GN
D
TS
1
GN
D
IX0
CANLCANH+24V
GND
building
TS-HIEX-2 moduletemperature and humidity sensor1 temperature sensor input
Wiring diagram
+24V
CANH
CANL
GND
TS1
GNDtemperature
sensor
CA
NH
CA
NL
GN
D
+2
4V
Technical specifications
Temperature measurement range: 0°C to +50°Cerror: ±0.5°C typ. (0°C to +50°C) ±2°C max. (0°C to +50°C)resolution: 0.1°C (12 bit)readout: 0.1°C (254 equals 25.4°C)
Humidity measurement range: 0..100% rh, non-condensingerror: ±2% rh @ 25°Cstability ±1% rh @ 50% rh in 5 yearsresolution 1% (7 bit)readout 1% rh (45 equals 45% rh)
External temperature sensor ES-P, ES-B or ES-W
Power supply 24V (18..28V), 15mADegree of protection IP20Operating conditions 0..50°C, 0..85% rh non-condensingStorage temperature -20..75°CMounting wall surfaceDimensions 71x71x27mmWeight 80gLevel of ambient pollution 2Standards EN 60730-1
Order code
TS temperature sensorTS-H temperature sensor + humidity
Mounting
47
Ø3
Dimensions
71 27
71
building
FCIEX-2 module, fan-coil controller5 relay outputs 5A1 binary/analog input2 temperature sensor inputs
Technical specifications
Input type dry contact, internal pull-up 12V 2mAanalog input 0..10V (10 bit, 0..1023)
Output type relay 5A/250VAC resistiveExternal temperature sensor ES-P, ES-B or ES-W
Power supply 24V (18..28V), 100mA(25mA+15mA*number of active outputs)
Galvanic isolation 4kV between internal circuit and relay contacts
Degree of protection IP20Operating conditions 0..45°C, 0..95% rh non-condensingStorage temperature -20..75°CMounting inside the fan coil unitDimensions 108x86x46mmWeight 200gStandards EN 60730-1
Wiring diagram
CA
NH
CA
NL
GN
D
+24V
PW
R-L
PW
R-N
PW
R-N
CO
LD
PW
R-N
HO
T 3
TS
0
2 1
GN
D
TS
1
230V
-N
230V
-N
230V
-L
GN
D
IW0/I
X0
SPEED
3 2 1
230VAC
temperaturesensor
windowswitch
CANHCANLGND
+24V
building
FC-2IEX-2 module, fan-coil controller1 analog output 0..10V2 relay outputs 5A1 binary/analog input2 temperature sensor inputs
Technical specifications
Input type dry contact, internal pull-up 12V 2mAanalog input 0..10V (10 bit, 0..1023)
Output type 0..10V 10mA (7 bit, 0..100%)relay 5A/250VAC resistive
External temperature sensor ES-P, ES-B or ES-W
Power supply 24V (18..28V), 100mA(25mA+15mA*number of active outputs)
Galvanic isolation 4kV between internal circuit and relay contacts
Degree of protection IP20Operating conditions 0..45°C, 0..95% rh non-condensingStorage temperature -20..75°CMounting inside the fan coil unitDimensions 108x86x46mmWeight 200gStandards EN 60730-1
Wiring diagram
230VAC
0..10Voutput
CA
NH
CA
NL
GN
D
+24V
QX
1 C
QX
0
QW
0
GN
D
TS
0
GN
D
TS
1
GN
D
IX0
temperaturesensor
windowswitch
CANHCANLGND
+24V
building
SW-W3IEX-2 module4 switch or potentiometer inputs4 LED outputs or switch inputs2 temperature sensor inputs (TIR only)1 IR receiver input (TIR only)
Wiring diagram
CA
NH
CA
NL
GN
D
+2
4VGND
IX0/IW0IX4/QX0
GND
IX5/QX1GND
IX6/QX2GND
IX7/QX3GND
GNDIX1/IW1
GNDIX2/IW2
GNDIX3/IW3
CANHCANLGND
+24V
10k0..10V
SW-W3
Technical specifications
Input type dry contact, internal pull-up 12V 2mA0..10V (10 bit, 0..1023) or potentiometer
LED output 5V 10mAExternal temperature sensor ES-P, ES-B or ES-WExternal IR receiver LRM1080
Power supply 24V (18..28V), 70mA(30mA+10mA*number of active LEDs)
Galvanic isolation none
Operating conditions 0..45°C, 0..95% rh non-condensingStorage temperature -20..75°CMounting in-wall, flush box fi60Dimensions 50x50x15mmWeight 40gStandards EN 60730-1
Order code
SW-W3 basic versionSW-W3-TIR temperature and IR sensor inputs
building
CA
NH
CA
NL
GN
D
+24VGND
IX0/IW0TS0
GND
TS1GND
+5VGND
IRGND
GNDIX1/IW1
GNDIX2/IW2
GNDIX3/IW3
CANHCANLGND
+24V
tem
pera
ture
senso
rIR
rece
iver
10k0..10V
SW-W3-TIR
O2IEX-2 module2 relay outputs 16A2 mains sense inputs
Technical specifications
Output type relay 16A/250VAC resistivePower supply 24V (18..28V), 60mAGalvanic isolation 5kV between internal circuit and relay contacts
Operating conditions 0..45°C, 0..95% rh non-condensingStorage temperature -20..75°CMounting in-wall, flush box fi80Dimensions 55x60x20mmWeight 80gStandards EN 60730-1
Order code
O2-L power relay for lights and blindsnormally open and normally closed contacts
Wiring diagram
CA
NL
CA
NH
+24V
GN
D
CANHCANLGND
+24V
QX0-3
QX0-2
QX0-1
N0
N0
S
QX1-3
QX1-2
QX1-1
N1
N1
S
M
N
L
230V~
N
L
230V~
Mains sense is connectedto the relay middle contact
building
LC-DC
Wiring diagram
DALIballast
DALIballast
DALI controller
LC-DC
10k
0..10V
1 +12V2 GND3 +5V4 LS5 IR6 MS
6 1
Technical specifications
Input type dry contact, internal pull-up 12V 2mAanalog input 0..10V (10 bit, 0..1023)potentiometer 0..10k (10 bit, 0..1023)
Sensor input LRI8134 (multisensor)
DALI output current 200mALoad protection short circuit protectedNumber of ballasts 64
Power supply 24V (18..28V), 120mAGalvanic isolation none (DALI ballasts must be SELV)
Operating conditions 0..45°C, 0..95% rh non-condensingStorage temperature -20..75°CDegree of protection IP20Dimensions 36x117x58mmWeight 120gStandards EN 60730-1
IEX-2 module, DALI light controllerDALI output2 analog/digital inputslight, motion and IR sensor input
building
Multisensor
multisensorLC-DC
+12V power supply+12V output1
2
3
4
5
6
Pin
GNDGND
+5V power supply+5V output
light sensorLS input 0..10V
IR receiverIR input
motion sensorMS input
LRI8134
LC-DIEX-2 module, DALI light controllerDALI output, 4 DSI outputs3 analog/digital inputs2 digital inputslight, motion and IR sensor input
Technical specifications
Input type dry contact, internal pull-up 12V 2mAanalog input 0..10V (10 bit, 0..1023)potentiometer 0..10k (10 bit, 0..1023)
Sensor input RHKF-U (light), IR-580-IQ (motion),LRI8134 (multisensor)
DALI output current 100mALoad protection short circuit protectedNumber of ballasts 32
DSI output current 250mA per channelLoad protection short circuit protectedNumber of ballasts 100
Light sensorPower supply output 12V 25mAInput range 0..10V (10 bit, 0..1023)Internal pull-up none
Motion detectorPower supply output 12V 25mASignal type dry contactInternal pull-up 12V 1mA
Infrared receiverPower supply output 5V 10mASignal type TTL level, active lowInternal pull-up 5V 0.5mA
Power supply 24V (18..28V), 150mAGalvanic isolation none (DALI ballasts must be SELV)
Operating conditions 0..45°C, 0..95% rh non-condensingDimensions 108x86x46mmWeight 200gDegree of protection IP42Standards EN 60730-1
Multisensor
multisensorLC-D
+12V power supply+12V output1
2
3
4
5
6
Pin
GNDGND
+5V power supply+5V output
light sensorLS input 0..10V
IR receiverIR input
motion sensorMS input
CyPro/Examples/DaliDemo.cypbuilding
Wiring diagramIRG
ND
+5
V
GN
D
+1
2V
LS
light sensor IR receiver
GN
D
D2-2
D0-2
CA
NL
D2-1
D0-1
GN
D
MS
D3-1
D1-1
CA
NH
+12V
D3-2
D1-2
+24V
DSI output
IEX-2
DALI
motion sensor
+++
++++
---
----
DA
LI-
DA
LI+
multisensor
IX0
GN
D
IX1
IW0
IW1
IW2
0-10V
1 +12V2 GND3 +5V4 LS5 IR6 MS
6 1
IR-580-IQRHKF-U LRI8134
LC-SIEX-2 module, analog light controller4 analog outputs 0..10V3 analog/digital inputs2 digital inputslight, motion and IR sensor input
building
Multisensor
multisensorLC-S
+12V power supply+12V output1
2
3
4
5
6
Pin
GNDGND
+5V power supply+5V output
light sensorLS input 0..10V
IR receiverIR input
motion sensorMS input
QW
2
QW
0
GN
D
GN
D
GN
D
GN
D
QW
3
QW
1
analog output
++++ ----
Wiring diagramIRG
ND
+5
V
GN
D
+1
2V
LS
light sensor IR receiver
GN
D
CA
NL
GN
D
MS
CA
NH
+12V
+24V
IEX-2
motion sensor
+++ ---
multisensor
IX0
GN
D
IX1
IW0
IW1
IW2
0-10V
1 +12V2 GND3 +5V4 LS5 IR6 MS
6 1
Technical specifications
Input type dry contact, internal pull-up 12V 2mAanalog input 0..10V (10 bit, 0..1023)potentiometer 0..10k (10 bit, 0..1023)
Sensor input RHKF-U (light), IR-580-IQ (motion),LRI8134 (multisensor)
Analog output 0..10V (8 bit, 0..255)Output current 10mA per channel, sink or sourceNumber of ballasts 50 per channel, 100 total
Light sensorPower supply output 12V 25mAInput range 0..10V (10 bit, 0..1023)Internal pull-up none
Motion detectorPower supply output 12V 25mASignal type dry contactInternal pull-up 12V 1mA
Infrared receiverPower supply output 5V 10mASignal type TTL level, active lowInternal pull-up 5V 0.5mA
Power supply 24V (18..28V), 150mAGalvanic isolation none (ballasts must be SELV)
Operating conditions 0..45°C, 0..95% rh non-condensingDimensions 108x86x46mmWeight 200gDegree of protection IP42Standards EN 60730-1
IR-580-IQRHKF-U LRI8134
CR-W2IEX-2 module2 RFID reader4 analog/digital inputs2 relay outputs 5A
Wiegand
Wiring diagram
IW0
10
C0
11
IW1
12
IW2
13
C0
14
IW3
15
QX0
16
C1
17
QX1
18
1
+12V
2
GND
3
D0-0+1
4
D1-0
5
D1-1
6
GN-0
7
GN-1
8
RD-0
9
RD-1
CR-W2card reader 2x
+12V
0VD1
D0
CL
MO
GR
RD
CA
RD
RE
AD
ER
0
+12V
0VD1
D0
CL
MO
GR
RD
CA
RD
RE
AD
ER
1
T1T0
10k
T3T2
230V~
N
L
0..10V
Technical specifications
Input type dry contact, internal pull-up 12V 2mAanalog input 0..10V or potentiometer 10k
Output type relay 5A/250VAC resistive
Reader protocol WiegandData input active low, internal pull-up 5V 1mAData timing 20us min. pulse on D0/D1, 20ms timeoutData format 26/34/44 bits processed, 1..64 bits rawPower supply output 12V 500mALED output 500mA NPN open collector, GN/RDLED connection output to +12V or +24V
Power supply 24V (18..28V), 120mAGalvanic isolation none
Operating conditions 0..45°C, 0..95% rh non-condensingStorage temperature -20..75°CDegree of protection IP20Dimensions 53x117x58mmWeight 160gStandards EN 60730-1
building
RC-AIEX-2 module, recuperator controller1 fan speed output 0..24V 2A1 fan direction PNP output 2A3 NPN open-collector outputs 2A2 temperature sensor inputs2 digital/analog inputs
Wiring diagram
T1T0
TS0
7
C
8
TS1
9
IW0
10
C
11
IW1
12
1
C0
2
FAN
3
DIR
4
QX0
5
QX1
6
QX2
recouperator controller
RC-A
temp.sens.
M0 to 24V
10k
0..10V
24V power supply
0V
+24V
Technical specifications
Input type dry contact, internal pull-up 12V 2mAanalog input 0..10V or potentiometer 10k
Output type NPN transistor 2A 30VAnalog output for fan 0..24VDC, max. 2ATemperature measurement ES digital sensor
Power supply 24V (18..28V), 90mAGalvanic isolation none
Operating conditions 0..45°C, 0..95% rh non-condensingStorage temperature -20..75°CDegree of protection IP20Dimensions 36x117x58mmWeight 100gStandards EN 60730-1
building
GW-MPIEX-2 moduleBelimo MP-bus gatewayfor valves and actuators
Wiring diagram
1
GND
2
MP-BUS
MP busdevice
MP busdevice
GW-MPgateway for MP-bus
MP bus
Technical specifications
Power supply 24V (18..28V), 30mAGalvanic isolation 1kV between internal circuit and communication
Operating conditions 0..50°C, 0..85% rh non-condensingMounting DIN rail (35mm)Degree of protection IP20Dimensions 36x117x58mmWeight 100gLevel of ambient pollution 2Standards EN 60730-1
CyPro/Examples/MpBusDemo.cypbuilding
GW-ENOIEX-2 EnOcean switchesreceiver for
Technical specifications
Interface EnOcean wireless protocolFrequency 868 MHzCoverage 10m indoor, 100m outdoorNumber of modules unlimited (no learning)
Power supply 24V (18..28V), 40mAOperating conditions 0..50°C, 0..85% rh non-condensingMounting DIN rail (35mm)Degree of protection IP20Dimensions 36x117x58mmWeight 100gLevel of ambient pollution 2Standards EN 60730-1
Wall switch, single or double
SUPPORTED MODULES
Soft remote
Card holder
CWS-2-1-01
MODEL PROFILE
F6-02-01
F6-04-01
F6-02-02CRC-2-6-0x
CCS-2-1-01
unique button code
eno_command
unique button code
unique button code
wall switchsingle
wall switchdouble
soft remotecard holder
GW-ENOEnOcean wireless receiver
building
EnOceanEnOcean Gateway, bidirectional
Technical specifications GW-ENO2
EnOcean specifications
Power supply 24V (18..28V), 40mAOperating conditions 0..50°C, 0..85% rh non-condensingMounting DIN rail (35mm)Degree of protection IP20Dimensions 36x117x58mmWeight 100gLevel of ambient pollution 2Standards EN 60730-1
Interface EnOcean wireless protocolFrequency 868 MHzCoverage 10m indoor, 100m outdoorNumber of modules 20
CyPro/Examples/EnOceanGateway
Wall switch, single or double
SUPPORTED MODULES
Soft remote
Card holder
Door sensor
Motion sensor
Temperature sensor
Temperature and humidity
Smart plug
Smart plug with metering
Micro smart plug with metering
Relay switch one channel
Relay switch two channels
Radiator valve
Soft button
CWS-2-1-01
MODEL PROFILE
F6-02-01
F6-04-01
A5-07-03
A5-04-01
D2-01-0B
D2-01-0F
F6-02-02
D5-00-01
A5-02-05
D2-01-0A
D2-01-0E
D2-01-12
A5-20-01
D2-03-0A
CRC-2-6-0x
CCS-2-1-01
SDO-2-1-05
PIR-2-1-01
STP-2-1-05
STPH-2-1-05
ASP-2-1-10
ASP-2-1-11
MSP-2-1-11
SIN-2-1-01
SIN-2-2-01
MVA004
TSB-2-2-01
input 0/1/2/4/8 -
input 0/1/2/4/8 -
input 0/1 -
input 0/1 -
input 0/1 battery [0.1V]
status bits DB2
battery [%]
temp [0.1°C] -
temp [0.1°C]
temp [0.1°C]
action 1/2/3/4
-
- -
-
-
energy [Wh]
energy [Wh]
- -
- -
-
-
-
-
-
-
-
-
output 0/1
output 0/1
output 0/1
output 0/1
output 0/1
setpoint %/°C
-
-
-
-
lightness [lux]
-
humidity [%]
position [%]
-
power [W]
power [W]
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
output 0/1
oper. mode DB1
eno_iw00[n] eno_iw02[n] eno_qw00[n]eno_iw01[n] eno_qw01[n]
Software
EnOceanGateway.cyp
Mini scada
Gateway is written as plc program, just copy code and variables to your application.
°C
1x 2x
Hardware options
Cybro-3-ENO Cybro-3
or
GW-ENO2
Both options have the same functionality and specifications. Not compatible with Cybro-2.
Repeater level
10m
Only powered devicecan be a repeater
10m 10m
1
2 2
building
ZigBeeIEX-2 gateway for ZigBee plug
ZigBee specifications
Technical specifications COM-NOK
Interface ZigBee Pro 3.5 (IEEE 802.15.4)Frequency 2.4GHzCoverage 30m indoor, 100m outdoorNumber of modules 8
Power supply 24V (18..28V), 40mAOperating conditions 0..50°C, 0..85% rh non-condensingMounting DIN rail (35mm)Degree of protection IP20Dimensions 36x117x58mmWeight 120gLevel of ambient pollution 2Standards EN 60730-1
Add new devices
Remove device from network
Destroy and rebuild network
- press "Add devices" button- wait until network state comes to "waiting keypress"- connect new RF actuator and briefly press device button- when device LED start blinking red, press device button again- new module will be ready in about 30 seconds- repeat the procedure for each module- press "Finish adding" button
If device is not recognized, or "addressing error" displays, first remove device from the network, then repeat the procedure. If not finished, network will automatically close in 5 minutes.
- press and hold device button- in about 6 seconds LED will turn green- in about 12 seconds LED will turn red- when LED turns red, release button- in a few seconds LED will turn yellow, with periodic blinking- in about 60 seconds device will disappear from the network
If procedure fails, unplug device, plug it again, and then repeat.
- remove devices one by one- press "Rebuild" button- add devices one by one
IEX-2
Cybro COM-NOK ZC-GW-485-EM ZR-PLUG-XX-M
RS-485 ZigBee
Connection diagram
SUPPORTED MODULES
ZR-PLUG-XX-M4-NOKS
MODELCOMPANY PROFILE
ZigBee PRO
ZigBee PROZR-SWITCH-M4-NOKS
Remote control plug
Wall-on steady device
CyPro/Examples/ZigbeeGateway
Order code
COM-NOK master controller for network controlZC-GW-485-EM protocol converter Modbus to ZigBeeZR-PLUG-XX-M electricity meter and remote control plugZR-SWITCH-M electricity meter and remote control relay
building
activate output with a call
activate output with a message
make a call when condition is met
send message when condition is met
read measurements with a message
authorize other users with a message
GSM-1IEX-2 module, CALL/SMS/GPRS4 analog/digital input2 relay output 1A
Technical specifications
Input type dry contact, internal pull-up 12V 2mAanalog input 0..10V (10 bit, 0..1023)
Output type relay 1A/250VAC resistive, normally openQuad band GSM/GPRS 850/900/1800/1900 MHzPerformance class 4 (2W) 850/900MHz, class 1 (1W) 800/1900MHzAntenna internal or external (SMA 50 ohm)Power supply 24V (18..28V), 70mA (standby), 100mA (active)Operating conditions 0..50°C, 0..85% rh non-condensingMounting DIN rail (35mm)Degree of protection IP20Dimensions 36x117x58mmWeight 160gLevel of ambient pollution 2Standards EN 301489-1, EN 301489-7, EN 301511,
EN 61010-1, EN 61010-2-201, EN 61131-2
Wiring diagram
T3T2T1T0
IW0
7
C
8
IW1
9
IW2
10
C
11
IW3
12
1 2 3 4
QX0+24V 0V
5
C0
6
QX1
GSM module
GSM-1GPRS
GSM
POWER
24V power supply
+24V
0V
0..10k
0..10V
L
N
230V~
Trigger events
ix
SMS
iw
1
0
hi
lo
Example
CyPro/Examples/GsmPlcDemo.cypindustrial building
COM moduleIEX-2 protocol converterRS-232 / RS-485 / CANgalvanically isolated
Technical specifications
Power supply 24V (18..28V), 40mAGalvanic isolation 1kV between internal circuit and com port
Operating conditions 0..50°C, 0..85% rh non-condensingMounting DIN rail (35mm)Degree of protection IP20Dimensions 36x117x58mmWeight 120gLevel of ambient pollution 2Standards EN 61010-1, EN 61010-2-201, EN 61131-2
Order code (serial)
Order code (CAN)
Example
-PGM-MB-DMX-WXT-PMI-EM6-SAT-SAN-KAC-BON-STU
Free-programmable portModbus RTU masterDMX controller for lightsVaisala WXT520 Iskra/Eastron power meterSchneider EM6400 power meterSatcon PV inverterSanrex PV central inverterKACO Powador PV inverterBonfiglioli PV inverterStuder PV inverter and BMS
weather station
-BAT-BCM-LIS
Alpha battery managementA123 battery managementLishen battery management
COM-COM-232-COM-485-
IEX-2 to RS-232/485IEX-2 to RS-232IEX-2 to RS-485
COM-CAN- IEX-2 to CAN
COM-485-WXT Vaisala WXT520 weather station connected using RS485
IEX-2
RS-232
RS-485
CAN port
A
1
B
2
C
3
COM-Serial 232/485 port
RS-485
RS-232
RJ9 left+right
RJ9
terminals
-
COM-
Cybro COM any serial device
terminals
terminals
-
-
COM-232
TXD
5
RXD
6
GND
7
serial RS232 port
COM-232
1
C0
2
CANL
3
CANH
4
+24V
IEX-2
RS-232
terminals
-
terminals
-
COM-485
A
5
B
6
C
7
1
C0
2
CANL
3
CANH
4
+24V
RS-485
IEX-2
COM-485serial RS485 port
RJ9 left+right
-
-
terminals
COM-CAN
CAN
CAN-to-CAN adapter
COM-CAN
CANH
3
CANL
2
GND
1
COM module allows connecting any serial device to IEX-2 network. Protocol translation is handled by firmware, so Cybro controller see device as native IEX-2 module. For example, power meter may be visible as pm00_real_power [W], pm00_reactive_power [VA] and pm00_total_energy [kWh]. Communication goes both ways.
COM module is available in three versions, with a different set of connectors and terminals. Each firmware is compatible with all hardware versions.
Fourth version, COM-CAN, allow connecting any CAN device to IEX-2 network. No matter the protocol, Cybro can see it as a native IEX-2 module.
For a serial device not listed here, ask quote.
industrial
building
CyPro/Examples/SerialPortDemo.cyp
CyPro/Examples/ModbusRtuMaster3.cyp
ESTemperature sensor
Technical specifications
ES-PHousing heatshrink tubeOperating range -50 to +100°CDegree of protection IP50Cable length 2m
ES-BHousing steel tubeOperating range -50 to +100°CDegree of protection IP67Cable length 5m
ES-WHousing plastic box, whiteOperating range 0 to +50°CDegree of protection IP20Mounting wall surfaceDimensions 71x71x27mm
Sensor type DS18B20 digital thermometerAccuracy ±0.2°C typ. (-10 to +85°C)
±0.5°C max. (-10 to +85°C)±2.0°C max. (-50 to +100°C)
Cable length 20m max.Recommended cable UTP 0.25..0.5mm2
Order code
ES-P heatshrinkES-B steel tubeES-W plastic box
ES-P
GNDGND
TSTS
ES-B
DS18B20 wiring diagram
ES-W
GND
TS
GND
TS
building
GND
TS123
3-Vdd2-DQ1-GND
Accessories
BE-PROTIEX-2 bus expander, RJ9 to terminals
Surge protection 1.5kW at 10/1000usError output 24V 10mA opto isolatedOrder code CAD-BE-PROT
CAD-BCIEX-2 bus expander, RJ9 to terminals
Order code CAD-BC
CAD-232-A2RS-232 to RS-485 converter, RJ9 to terminals
Galvanic isolation power supply/232 to 485Power supply 24V 50mA from IEX-2 busOrder code CAD-232-A2
CAD-PxIEX-2 cable,
CAD-P0 3cmCAD-P1 1mCAD-P2 2m CAD-P3 3m
RJ9 to RJ9
CAD-SPLIEX-2 bus splitter, 1x into 2x
Order code CAD-SPL
RJ9 RJ9
CAD-232-PxRS-232 cable, Cybro to CAD-232-A2
CAD-232-P0 20cmCAD-232-P2 2m
RJ9 to RJ9,
industrial building
1 +24V2 CANH3 CANL4 GND
4 +24V3 CANH2 CANL1 GND
1 GND23 RxD4 TxD
1 GND23 TxD4 RxD
RE-2 remote
Operating range 5mProtocol RC-5Battery 1x CR2025Dimensions 40x85x5mmWeight 20gOrder code RE-2
Accessories
1CAD-BC
4
3
2
1 CAD-BC
4
3
2
BE-PROT
CAD-BC
CAD-SPL
CAD-BC
BE-PROT
I/O schematicsinternal input/output wiring diagrams
Digital input opto isolated dry contact
Digital output relay PNP transistor NPN transistor
Analog input voltage
analog/digital
current resistance
Analog output voltage
Temperature sensor
Load limits
Relay contact 16A NO 16A NC 8A 5A
LED LAMPS
Compact E14/E27/GU10 700W 400W 400W N/AStripe or panel with electronic transformer 700W 400W 400W N/A
INCADESCENT LAMPS
Incadescent / halogen 230V 1800W 1000W 800W 300WHalogen 12/24V with electronic transformer 700W 400W 400W N/A
FLUORESCENT LAMPS
Compact fluorescent E14/E27 700W 400W 400W 100WWith electronic ballast 700W 400W 400W 100WWith parallel compensation 500W/80uF 300W/50uF 250W/30uF N/ADuo (lead-lag) connection 1800W 1000W 1000W 300W
GAS DISCHARGE LAMPS
Mercury/sodium-vapor without compensation 700W 400W 400W 150WMercury/sodium-vapor with parallel compensation 400W/50uF 250W/30uF 250W/30uF N/AMetal-halide (HID) without compensation 700W 400W 400W 150WMetal-halide (HID) with parallel compensation 400W/50uF 250W/30uF 250W/30uF N/A
ELECTRIC MOTOR
single-phase asynchronous motor 1200W 600W 600W N/Abrushed DC electric motor 1000W 500W 500W N/A
With the rated load, expected contact life is 20,000 cycles. With 50% load, expectancy goes to 100,000 cycles.
Nominal relay current is given for a resistive AC load. Real-life devices come with all sorts of trouble: transients, capacitive or inductive load, and non-linear voltage/current relation. To ensure the optimal service life, output current must be derated. Derating depends on load type, AC or DC voltage and required number of operations. Ignoring the guidelines may result in premature wear, contact sticking, overheating or destruction. recommended current is 100mA, otherwise oxidation layer buildup may rise contact resistance.
Minimum
Transient burst
Caused by: load capacitanceOverload ratio: 100..1000xTypical duration: 10..100usSolution: RC network, derating
0
510
610
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16current (A)
opera
tions
Contact life vs. current (resistive load)
8A16A
010
20
30
50
100
200
300
500
20 40 60 80 100current derating (%)
DC
volta
ge (
V)
DC breaking capability
Surge current
Caused by: non-linear loadOverload ratio: 5..10xTypical duration: 10..20msSolution: derating
Break sparking
Caused by: load inductanceOvervoltage: 100..1000VTypical duration: 5..20usSolution: surge protector, derating
Revision history
9.2.2000, CyBro.P, CyBro.B
27.2.2002, CyBro.C
24.5.2002, Integra-BM v1
3.10.2002, Integra-BM v8- RC, OP, TS, FC, LC
23.12.2005, CyBro-2 v10- AiR-12, AiV-12, AiC-12, AoV-12- Bio-24R, OP-2
2.3.2006, Integra-BM v15- OP-3, LC-S, LC-D, MS, SW, HR
26.4.2011, Integra-BM v16- CAD-UTP cable- TS-H, ES-A, SW-L
20.3.2017, CyBro Hardware Manual v1.0- industry and buildings integrated
12.4.2018, Cybro Hardware Manual v3.0- Cybro-3
29.5.2018, Cybro Hardware Manual v3.2- OP-3 removed
12.6.2018, Cybro Hardware Manual v3.3- Cybro-3H, Cybro-Pi0, Cybro-Pi3
9.2.2019, Cybro Hardware Manual v3.5- EnOcean, GW-ENO2
23.7.2019, Cybro Hardware Manual v3.7- Cybro-Pi0 dropped out- relay specifications updated
28.10.2019, Cybro Hardware Manual v3.9- RJ pin numbering corrected- cable wiring diagrams added