July 1998 PG.29B.01.T.U Cutler-Hammer 1 Moulded Case Circuit Breakers 16-2500 Amperes for IEC 947-2 Applications Contents Page Standards . . . . . . . . . . . . . . . . . . . . 1 General Information . . . . . . . . . . 2-3 Electrical Characteristics . . . . . . . 4-6 Rating Chart . . . . . . . . . . . . . . . . . . 7 Technical Data . . . . . . . . . . . . . . . 8-9 Electronic Trip Units . . . . . . . . 10-12 Catalogue Numbers/ Termination Accessories G-Frame, 16-100 Amperes . . . . . . . . . . 13 F-Frame, 16-225 Amperes . . . . . . . 14-15 J-Frame, 100-250 Amperes . . . . . . 16-17 K-Frame, 63-400 Amperes . . . . . . . 18-19 L-Frame, 315-800 Amperes . . . . . . 20-21 N-Frame, 400-1250 Amperes . . . . . 22-25 R-Frame, 800-2500 Amperes . . . . . 26-30 Motor Circuit Protectors . . . . . . . 31 Accessories and Modifications . . . . . . . . . . . . . . 32-35 Time-Current Curves for Coordination Tripping Characteristics (Breakers) G-Frame . . . . . . . . . . . . . . . . . 36 F-Frame . . . . . . . . . . . . . . . . 36-37 J-Frame . . . . . . . . . . . . . . . . 36-37 K-Frame . . . . . . . . . . . . . . . . 36-37 L-Frame . . . . . . . . . . . . . . . . . . 37 N-Frame . . . . . . . . . . . . . . . . . 38 R-Frame . . . . . . . . . . . . . . . . . . 38 Tripping Characteristics (Motor Protectors) F-, K-, L-Frames. . . . . . . . . . . . 39 Current Limiting Curves F- and L-Frames . . . . . . . . . . . 40 N- and R-Frames. . . . . . . . . . . 40 Dimensions . . . . . . . . . . . . . . . 41-42 Typical Specifications. . . Inside Back Cover Standards Series C Moulded Case Circuit Break- ers are designed to conform with the following international standards: Australian Standard AS 2184 and AS 3947-2 Moulded Case Circuit Breakers. British Standards Institution Standard BS 4752: Part 1, Switchgear and Control Gear Part 1, Circuit Breakers. International Electrotechnical Commission Recommendations IEC 947.2 Circuit Breakers. Japanese T-Mark Standard Moulded Case Circuit Breakers. National Electrical Manufacturers Association Standards Publication No. AB1-1975 Moulded Case Circuit Breakers. South African Bureau of Stand- ards, Standard SABS 156, Standard Specification for Moulded Case Circuit Breakers. Swiss Electro-Technical Associa- tion Standard SEV 947.2, Safety Regulations for Circuit Breakers. Union Technique de l’Electricite Standard NF C 63-120, Low Volt- age Switchgear and Control Gear Circuit Breaker Requirements. Verband Deutscher Elektrotech- nike (Association of German Elec- trical Engineers) Standard VDE 0660, Low Voltage Switchgear and Control Gear, Circuit Breakers. Series C Frame Sizes G through R

Upload: truongduong

Post on 26-May-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

July 1998

PG.29B.01.T.U

Cutler-Hammer

1Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

Contents

Page

Standards . . . . . . . . . . . . . . . . . . . . 1

General Information . . . . . . . . . . 2-3

Electrical Characteristics . . . . . . . 4-6

Rating Chart . . . . . . . . . . . . . . . . . . 7

Technical Data . . . . . . . . . . . . . . . 8-9

Electronic Trip Units . . . . . . . . 10-12

Catalogue Numbers/Termination Accessories

G-Frame, 16-100 Amperes . . . . . . . . . . 13

F-Frame, 16-225 Amperes . . . . . . . 14-15

J-Frame,100-250 Amperes . . . . . . 16-17

K-Frame, 63-400 Amperes . . . . . . . 18-19

L-Frame, 315-800 Amperes . . . . . . 20-21

N-Frame, 400-1250 Amperes . . . . . 22-25

R-Frame, 800-2500 Amperes . . . . . 26-30

Motor Circuit Protectors . . . . . . . 31

Accessories and Modifications . . . . . . . . . . . . . . 32-35

Time-Current Curves for CoordinationTripping Characteristics (Breakers)G-Frame . . . . . . . . . . . . . . . . . 36F-Frame . . . . . . . . . . . . . . . . 36-37J-Frame . . . . . . . . . . . . . . . . 36-37K-Frame. . . . . . . . . . . . . . . . 36-37L-Frame . . . . . . . . . . . . . . . . . . 37N-Frame . . . . . . . . . . . . . . . . . 38R-Frame. . . . . . . . . . . . . . . . . . 38

Tripping Characteristics (Motor Protectors)

F-, K-, L-Frames. . . . . . . . . . . . 39

Current Limiting CurvesF- and L-Frames . . . . . . . . . . . 40N- and R-Frames. . . . . . . . . . . 40

Dimensions . . . . . . . . . . . . . . . 41-42

Typical Specifications. . . Inside Back Cover

Standards

Series C Moulded Case Circuit Break-ers are designed to conform with the following international standards:

Australian Standard AS 2184 andAS 3947-2 Moulded Case Circuit Breakers.

British Standards Institution Standard BS 4752: Part 1, Switchgear and Control Gear Part 1, Circuit Breakers.

International Electrotechnical Commission Recommendations IEC 947.2 Circuit Breakers.

Japanese T-Mark Standard Moulded Case Circuit Breakers.

National Electrical Manufacturers Association Standards Publication No. AB1-1975 Moulded Case Circuit Breakers.

South African Bureau of Stand-ards, Standard SABS 156, Standard Specification for Moulded Case Circuit Breakers.

Swiss Electro-Technical Associa-tion Standard SEV 947.2, Safety Regulations for Circuit Breakers.

Union Technique de l’Electricite Standard NF C 63-120, Low Volt-age Switchgear and Control Gear Circuit Breaker Requirements.

Verband Deutscher Elektrotech-nike (Association of German Elec-trical Engineers) Standard VDE 0660, Low Voltage Switchgear and Control Gear, Circuit Breakers.

Series C Frame Sizes G through R

UK PG.29B.01.T.U A4 1-12 Page 1 Friday, March 12, 1999 3:54 PM

PG.29B.01.T.U

Cutler-Hammer

2

July 1998

Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

The Most Logically Designed

Contact Assembly

The flexibility and outstanding per-formance characteristics of Series C Circuit Breakers are made possible by one of the most logically designed contact assemblies in circuit breaker history. Based on previously patented Westinghouse contact conductor designs, the Series C contact assembly creates a high-speed “blow-open” action when it confronts the electrome-chanical forces produced by high-level fault currents.

Series C Circuit Breakers are oper-ated by a toggle-type handle that is mechanically trip-free from the han-dle so that the contacts cannot be held closed against short circuit cur-rents. Tripping due to overload or short circuits is clearly indicated by the position on the handle. This remarkably fast and dependable contact action is designed to enhance safety.

Thorough In-Plant Testing

The quality, dependability, and relia-bility of every Series C Circuit Breaker is assured by a thorough program of in-plant testing. Two calibration tests are conducted on every pole of every circuit breaker to verify the trip mech-anism, operating mechanism, conti-nuity, and accuracy.

ISO Certification

Series C Circuit Breakers are manu-factured in ISO certified facilities.

More Interrupting Capacity

in Less Space

Series C Circuit Breakers are physi-cally and electrically interchangeable with the “Classic” standard line of Westinghouse moulded case circuit breakers. This means Series C Break-ers are ideal for upgrading equip-ment designs and retrofitting existing installations.

Current Limiting Characteristics

All Series C Circuit Breakers are cur-rent limiting because of their high repulsion contact arrangement and incorporation of state-of-the-art arc extinguishing technology.

Operating Mechanisms

Series C Circuit Breakers have, in their basic version, a toggle handle operating mechanism, which also serves as switching position indica-tor. As well as ON and OFF, the fur-ther position TRIPPED is possible.

The toggle handle snaps into the TRIPPED position if the breaker is tripped by one of its overcurrent, short circuit, shunt or undervoltage releases. Before the circuit breaker can be reclosed following a trip-out, the toggle handle must be brought beyond the OFF position (RESET). The circuit breaker can then be reclosed.

As an additional switching position indicator for F- to R-Frame circuit breakers, there are two windows on the right and on the left of the toggle handle, in which the switching state is indicated by means of the colours red, green and white corresponding to the ON, OFF and TRIPPED posi-tions respectively.

General Information

Series C Moulded Case Circuit Breakers provide increased perform-ance in considerably less space than standard circuit breakers or compa-rable fusible devices. Reduced sys-tem costs can also be realized because Series C Circuit Breakers are used in series rated systems, allowing the use of lower interrupt-ing circuit breakers downstream.

Series C Circuit Breakers meet appli-cable IEC 947-2 standards, have been assigned ultimate and service interrupting ratings per IEC 947-2, and employ adjustable thermal and adjustable magnetic trips.

The Series C family includes seven frame sizes in ratings from 100 to 2500 amperes. Each frame size offers a choice of several interrupt-ing capacities up to 100 kA at 415 volts ac (200 kA at 240 volts ac). This provides greater design flexibility than ever before possible while also helping to save space.

Series C Circuit Breakers virtually eliminate the need for redesign and they can be used to replace older circuit breakers in the same panel-boards, feeder pillars, busbar trunk-ing tap-offs, individual enclosures, machine tool control panels, and motor control centres. In most cases, the same connecting straps, studs, and handle mechanisms can be retained and used.

Standard calibration is 40

°

C. For applications in high ambient tem-perature conditions, 50

°

C factory calibration is available.

Series C Circuit Breakers are also provided for dc applications. Inter-rupting ratings of 35 kA for the 600 ampere frame have been achieved for three-pole breakers in series at 600 volts dc.

Series C Frame Sizes G through R

Positions of the Toggle Handle Drive

OFFRESET

ONTripped

UK PG.29B.01.T.U A4 1-12 Page 2 Friday, March 12, 1999 3:54 PM

July 1998

PG.29B.01.T.U

Cutler-Hammer

3Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

Switchboard

Machine ToolControl Panel

BusbarTrunkingTap-Off

IndividualCircuitBreakerEnclosure

Panelboard

Panelboards

As both main and branch circuit pro-tection devices (G-, F-, J-, K-, L- and N-Frames).

Feeder Pillars

In distribution systems to provide main and branch circuit protection (F-, J-, K-, L-, N- and R-Frames).

Switchgear

In distribution systems to provide main and branch circuit protection up to 2500 amperes (R-Frame).

Busbar Trunking Tap-Offs

In busbar trunking tap-offs to provide branch circuit protection (F-Frame); and to provide feeder or branch circuit protection (J-, K- and L-Frames).

Individual Enclosures

Completely assembled in enclosures to meet specific customer require-ments (G-, F-, J-, K-, L-, N- and R-Frames).

Machine Tool Control Panels and

Motor Control Centres

Applied for specific equipment requirements (G-, F-, J-, K-, and L-Frames).

Additional Applications

Special versions of each Series C frame are available to provide safe equipment control and protection in mining and other applications. Con-tact your Cutler-Hammer agent or distributor for additional information.

Series C Frame Sizes G through R

Frame Continuous Ampere Rating Range

Type of Trip Unit Moulded Case SwitchAdjustable

ThermalFixed Magnetic

Fixed ThermalFixed Magnetic

Adjustable ThermalAdjustable Magnetic

Adjustable Thermal Fixed MagneticEarth Leakage

Digitrip RMSElectronicTrip Units

G 16-100

F 16-225

■ ■ ■ ■ ■

J 125-250

■ ■ ■

K 63-400

■ ■ ■ ■

L 315-800

■ ■ ■

N 400-1250

■ ■

R 800-2500

■ ■

Typical Series C Applications

UK PG.29B.01.T.U A4 1-12 Page 3 Friday, March 12, 1999 3:54 PM

PG.29B.01.T.U

Cutler-Hammer

4

July 1998

Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

Electrical Characteristics

G F J

Maximum Rated Current (Amperes) 100 160 200 225 250

Breaker Type GWF GWF FWF FW HFW FWC FWF HFWF FWCF JW HJW JWC

Breaker Capacity (kA rms) AC 50-60 Hz

IEC 947-2 220-240 VAC

I

cu

18 65 40 85 100 200 85 100 200 85 100 200

I

cs

9 35 40 85 100 150 85 100 150 85 100 150

380-415 VAC

I

cu

25 40 70 100 40 70 100 40 70 100

I

cs

13 40 70 75 40 70 75 40 70 75

660-690 VAC

I

cu

12 14 18 12 14 18 14 18 22

I

cs

6 7 9 6 7 9 7 9 11

250 VDC

I

cu

10 10 20 20 10 20 20 10 20 20

I

cs

5 5 10 10 5 10 10 5 10 10

NEMA 240 VAC 65 65 25

65 100 200 65 100 200 65 100 200

480 VAC 22 25 65 100 25 65 100 35 65 100

600 VAC 18 25 35 18 25 35 18 25 35

Number of Poles 1 2, 3 1 2, 3, 4 2, 3, 4

Ampere Range 16-100A 16-160A 16-225

16-225

➂➃

125-250A

Trip Units

Interchangeable

Built-in

■ ■ ■ ■ ■ ■ ■ ■

Thermal Magnetic

Fixed Thermal

■ ■ ■ ■ ■ ■

Adjustable Thermal

Fixed Fixed

■ ■ ■ ■

Magnetic Fixed Fixed Fixed, Opt Adj. Fixed Adjustable

Solid State rms

LS

LSI

LSG

LSIG

Dimensions(mm)

H W D H W D H W D

1-Pole 123.8 254.4 66.7 152.4 35 86 – – –

2-Pole 50.8 70 – – –

3-Pole 76.2 105 254 105 103

4-Pole – – – 140 140

2 poles in series.

At 277 VAC.

FWF 16-40A, 415 VAC maximum.

FWC 200A and FWCF 175-225A rated 14/7 kA at 690 V.

Adjustable Thermal Magnetic

Adjustable Thermal Magnetic

Adjustable Thermal Magnetic

Weight (approximate) Kgs. 1-Pole 2-Pole 3-Pole 1-Pole 2-Pole 3-Pole 4-Pole 3-Pole 4-Pole

0.4 0.7 1 0.7 1.8 2.4 3.1 5.2 7.0

Series C Frame Sizes G through J

UK PG.29B.01.T.U A4 1-12 Page 4 Friday, March 12, 1999 3:54 PM

July 1998

PG.29B.01.T.U

Cutler-Hammer

5Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

Electrical Characteristics

K L

Maximum Rated Current (Amperes) 400 630 800

Breaker Type KW HKW KWC LW HLW LWC LW

Breaker Capacity (kA rms) AC 50-60 Hz

IEC 947-2 220-240 VAC

I

cu

85 100 200 85 100 200 65

I

cs

85 100 150 85 100 150 33

380-415 VAC

I

cu

45 70 100 45 70 100 50

I

cs

45 70 75 45 70 75 25

660-690 VAC

I

cu

20 25 35 20 25 35 20

I

cs

10 13 18 10 13 18 10

250 VDC

I

cu

10 20 20 20 20 20 20

I

cs

5 10 10 10 10 10 10

NEMA 240 VAC 65 100 200 65 100 200 100

480 VAC 35 65 100 35 65 100 50

600 VAC 25 35 50 25 35 50 25

Number of Poles 2, 3, 4 2, 3, 4 3

Ampere Range 63-400A 315-630A 700-800A

Trip Units

Interchangeable

■ ■ ■

Built-in

■ ■

Thermal Magnetic

Fixed Thermal

■ ■ ■

Adjustable Thermal

➁ ■ ■

Magnetic Adjustable Adjustable Adjustable

Solid State rms

LS Standard Standard Standard

LSI Optional Optional Optional

LSG Optional

Optional Optional

LSIG Optional

Optional Optional

Dimensions(mm)

H W D H W D

1-Pole – – – – – –

2-Pole – – – – – –

3-Pole 258 140 104 630A = 273

800A = 406

210 104

4-Pole 183 280

Weight (approximate) Kgs. 3-Pole 4-Pole 3-Pole 4-Pole

6.1 7.3 630A = 9.4/800A = 11.3 630A = 11.1/800A = 14.4

2 poles in series.

For AC use only.

4-pole ground fault not available.

Adjustable Thermal Magnetic

Digitrip RMS 310Digitrip RMS 310

Adjustable Thermal Magnetic

Series C Frame Sizes K and L

UK PG.29B.01.T.U A4 1-12 Page 5 Friday, March 12, 1999 3:54 PM

PG.29B.01.T.U

Cutler-Hammer

6

July 1998

Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

Electrical Characteristics

N R

Maximum Rated Current (Amperes) 800, 1250 1600, 2000, 2500

Breaker Type NW HNW NWC RW RWC

Breaker Capacity (kA rms) AC 50-60 Hz

IEC 947-2 220-240 VAC

I

cu

85 100 200 135 200

I

cs

85 100 100 100 100

380-415 VAC

I

cu

50 70 100 70 100

I

cs

50 50 50 50 50

660-690 VAC

I

cu

20 25 35 25 35

I

cs

10 13 18 13 18

250 VDC I

cu

I

cs

NEMA 240 VAC 65 100 200 125 200

480 VAC 50 65 100 65 100

600 VAC 25 35 35 50 65

Number of Poles 2, 3, 4 3, 4

Ampere Range 400-1250A 800-2500A

Trip Units

Interchangeable

Built-in

■ ■

Thermal Magnetic

Fixed Thermal

Adjustable Thermal

Magnetic

Solid State rms

LS Standard Standard (LI is Optional in Digitrip 510, 610, 810 and 910)

LSI Optional Optional

LSG Optional Optional (LIG is Optional in Digitrip 510, 610, 810 and 910)

LSIG Optional Optional

Dimensions(mm)

H W D H W D

1-Pole – – – – – –

2-Pole – – – – – –

3-Pole 406 210 104 406 394 229

4-Pole 280 508

Weight (approximate) Kgs. 3-Pole 4-Pole 3-Pole 4-Pole

21.3 28.3 47 54

Digitrip RMS 310 Trip Unit

Digitrip RMS Trip Units

RMS 510

RMS 610

RMS 810

RMS 910

Standard

Digitrip RMS 310

Series C Frame Sizes N and R

UK PG.29B.01.T.U A4 1-12 Page 6 Friday, March 12, 1999 3:54 PM

July 1998

PG.29B.01.T.U

Cutler-Hammer

7Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

90° 90° 90° 90°

Electrical Characteristics

Technical Data G-Frame F-Frame J-Frame K-Frame L-Frame N-Frame R-Frame

Maximum Rated Current I

n

Depending on the Version

100A 160/205/225A 200/250A 315/400A 500/630/800A 800/1250A 1600/2000/2500A

Rated Insulation Voltage U, According to IEC 947-2Main Conducting Paths Auxiliary Circuits

750 VAC690 VAC

750 VAC690 VAC

750 VAC 690 VAC

750 VAC690 VAC

750 VAC690 VAC

750 VAC690 VAC

750 VAC690 VAC

Rated Impulse Withstand Voltage U

imp

Main Conducting PathsAuxiliary Circuits

8 kV4 kV

8 kV4 kV

8 kV4 kV

8 kV4 kV

8 kV4 kV

8 kV4 kV

8 kV4 kV

Rated Operational Voltage U

e

IECNEMA

440 VAC480 VAC

690 VAC

600 VAC 690 VAC600 VAC

690 VAC600 VAC

690 VAC600 VAC

690 VAC600 VAC

690 VAC600 VAC

Permissible Ambient Temperature -20 to +70

°

C -20 to +70

°

C -20 to +70

°

C -20 to +70

°

C -20 to +70

°

C -5 to +60

°

C -5 to +60

°

C

Permissible Load for Various Ambient Tempera-tures Close to the Circuit Breaker, Related to the Rated Current of the Circuit Breaker

Circuit Breakers for Plant Protection– At 40

°

C – At 50

°

C – At 55

°

C – At 60

°

C – At 70

°

C

100%96%93%91%86%

100%96%93%91%86%

100%92%87%83%73%

100%96%94%92%88%

100%94%90%87%80%

100%96%93%90%85%

100% 92% 87%84%75%

100%96%93%90%84%

100%91%86%82%70%

100%91%85%81%

100%100%100%100%–

Circuit Breakers for Motor Protection– At 40

°

C – At 50

°

C – At 55

°

C – At 60

°

C – At 70

°

C

–––––

100/100%100/96%100/90%100/86%100/77%

–––––

100%100%100%100%87%

100%100%100%100%90%

–––––

–––––

Circuit Breakers for Starter Combinations and Isolating Circuit Breakers– At 40

°

C – At 50

°

C – At 55

°

C – At 60

°

C – At 70

°

C

–––––

100%100%96%91%86%

100%100%96%82%88%

100%100%96%90%85%

100%100%95%90%84%

100%91%85%81%

100%100%100%100%–

Rated Short Circuit Breaking Capacity (DC) Not for Circuit Breakers for Motor Protection (Time Constant

t

= 10 rms)1 Conducting 2 Conducting 3 ConductingPath Paths in Series Paths in SeriesFor F to L up to:250 VDC 440 VDC 660 VDCNEMA (Time Constant

t

= 8 rms)1 Conducting 2 ConductingPath Paths in Series250 VDC –– 250 VDC

–10 kA (5rms)

20 kA Max.

10 kA22 kA

20 kA Max.

10 kA22 kA

20 kA Max.

10 kA22 kA

20 kA Max.

10 kA22 kA

Main Switch Characteristics According to IEC 947-2 in Combination with Lockable Rotary Drives

– Yes Yes Yes Yes Yes Yes

Rated Short Circuit Breaking Capacity According to IEC 947-2 (at AC 50/60 Hz) Rated Short Circuit Breaking Capacity See Table on Pages 4-5-6

Endurance (Operating Cycles) 10,000 10,000 10,000 8,000 8,000 3,000 3,000

Maximum Switching Frequency 300 1/h 300 1/h 240 1/h 240 1/h 240 1/h 60 1/h 20 1/h

Conductor Cross Sections and Terminal Types for Main Conductors

Solid or Stranded

Finely Stranded with End Sleeve

BusbarTightening Torque for Box TerminalsTightening Torque for Busbar Connection Pieces

Box Terminals

2.5 to 50 mm

2

––

5.1 Nm–

Box Terminals

2.5 to 70/95 mm

2

2.5 to 50/70 mm

2

–5/9 Nm

4.5/4.5 Nm

Box Terminals

50 to 150 mm

2

35 to 120 mm

2

–20 Nm15 Nm

Box Terminals

95 to 240 mm

2

70 to 150 mm

2

–42 Nm30 Nm

Flat Bar Terminals

––

800A31 Nm6 Nm

Flat Bar Terminals

––

Optional31 Nm50 Nm

Flat Bar Terminals

––

Optional–

37 Nm

Conductor Cross Sections for Auxiliary Circuits with Terminal Connection or Terminal Strip

Solid

Finely Stranded with End Sleeve

With Brought-out Cable Ends

Tightening Torque for Fitting Screws

0.75 to 2.5 mm

2

0.75 to 2.5 mm

2

––

0.75 to 2.5 mm

2

0.75 to 2.5 mm

2

0.82 (AWG 18) mm

2

0.8 to 1.4 Nm

0.75 to 2.5 mm

2

0.75 to 2.5 mm

2

0.82 (AWG 18) mm

2

0.8 to 1.4 Nm

0.75 to 2.5 mm

2

0.75 to 2.5 mm

2

0.82 (AWG 18) mm

2

0.8 to 1.4 Nm

0.75 to 2.5 mm

2

0.75 to 2.5 mm

2

0.82 (AWG 18) mm

2

0.8 to 1.4 Nm

Up to 2x4 mm

2

Up to 2x2.5 mm2

0.82 (AWG 18) mm2

0.8 to 1.4 Nm

Up to 2x4 mm2

Up to 2x2.5 mm2

0.82 (AWG 18) mm2

0.8 to 1.4 Nm

Power Loss per Circuit Breaker at Maximum Rated Current ln (The Power Losses of the Undervoltage Releases (“r” Releases) Must Be Observed if Necessary) at Three-Phase Symmetrical Load)■ For Plant Protection ■ As Isolating Circuit Breaker■ For Starter Combinations■ For Motor Protection

––––

60 W45 W45 W60 W

75 W75 W45 W

175 W107 W107 W75 W

255 W160 W160 W120 W

87/210 W87/210 W

––

220/270/400 W220/270/400 W

––

Permissible Mounting Position

➀ With circuit breakers with rated currents 40A: Ue maximum 415V.

➁ Not suitable for DC switching.

➂ Thermal overload release set to the upper value, resp. fixed-setting thermal overload releases.

➃ Thermal overload release set to the lower value.

Series C Frame Sizes G through R

UK PG.29B.01.T.U A4 1-12 Page 7 Friday, March 12, 1999 3:54 PM

PG.29B.01.T.U

Cutler-Hammer8July 1998

Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

Electrical Characteristics

Technical Data G-Frame F-Frame J-Frame K-Frame L-Frame N-Frame R-Frame

Auxiliary Switches

Rated Thermal Current lthRated Making Capacity

6A 10A

6A 20A

6A 20A

6A 20A

6A 20A

6A 20A

6A20A

AC (AC-15)– Rated Operational Voltage – Rated Operational Current

DC (DC-13)– Rated Operational Voltage – Rated Operational Current

Back-up Fuse Miniature Circuit Breaker

240V 6A

245

6A 6A

230/400/690V 6/3/0.25A

24/125/240V6/0.5/0.15A

46/4/4A 6/4A

230/400/690V 6/3/0.25A

24/125/240V6/0.5/0.15A

46/4/4A 6/4A

230/400/690V 6/3/0.25A

24/125/240V6/0.5/0.15A

46/4/4A 6/4A

230/400/690V6/3/0.25A

24/125/240V 6/0.5/0.15A

46/4/4A 6/4A

230/400/690V 6/3/0.25A

24/125/240V 6/0.5/0.15A

46/4/4A6/4A

230/400/690V6/3/0.25A

24/125/240V 6/0.5/0.15A

46/4/4A 6/4A

Releases

Undervoltage Releases (“r” Releases)Response Voltage:– Drop (Breaker Tripped) Us– Pickup (Breaker May Be Switched on) Us

Power Consumption in Continuous Operation at:– AC 50/60 Hz 12V – AC 50/60 Hz 24V – AC 50/60 Hz 48-60V

– AC 50/60 Hz 110-127V – AC 50/60 Hz 208-240V – AC 50/60 Hz 380-500V

– DC 12V – DC 24V – DC 48-60V

– DC 110-125V – DC 220-250V

Maximum Opening Time

35-70% 85-110%

–5.3 VA1.5 VA

1.8 VA 1.4 VA 4.8 VA

– ––

––

50 ms

35-70% 85-110%

2.5 VA 1.4 VA

1.2-1.9 VA

1.3 -1.7 VA 2.2 -2.9 VA 2.9 -5 VA

2.8 W 1.6 W

1.3-2.0 W

1.5-1.9 W 2.6-3.4 W

50 ms

35-70% 85-110%

1.9 VA 3.9 VA

2.5-3.8 VA

1.8 -2.4 VA 2.7-3.8 VA 3.4-5.8 VA

1.6 W 3.1 W

2.0-3.1 W

1.6-2.2 W 3.1-4 W

50 ms

35-70% 85-110%

1.9 VA 3.9 VA

2.5-3.8 VA

1.8 -2.4 VA 2.7-3.8 VA 3.4-5.8 VA

1.6 W 3.1 W

2.0-3.1 W

1.6-2.2 W 3.1-4 W

50 ms

35-70% 85-110%

1.9 VA 3.9 VA

2.5-3.8 VA

1.8-2.4 VA 2.7-3.8 VA 3.4-5.8 VA

1.6 W 3.1 W

2.0-3.1 W

1.6-2.2 W 3.1-4 W

50 ms

35-70% 85-110%

1.9 VA 2.4 VA

2.3-4.1 VA

3.4-4.2 VA 4.8-6.5 VA 6.8-12.0 VA

2.6 W 3.6 W

3.5 -5.5 W

2.9-3.6 W 4.8-6.3 W

80 ms

35-70% 85-110%

2.9 VA3.1 VA

3.4-6.0 VA

3.3-3.8 VA4.2-7.2 VA 3.8 10.0 VA

3.4 W4.3 W

4.8-7.2 W

3.3-3.8 W6.6-7.5 W

80 ms

Shunt Trips

Shunt Trips (“f” Releases)Response Voltage:– Pickup (Breaker Tripped) Us

Power Consumption in (Short Time) at:– AC 50/60 Hz 12-24V – AC 50/60 Hz 48-60V – AC 50/60 Hz 48-127V

– AC 50/60 Hz 110-240V – AC 50/60 Hz 380-440V– AC 50/60 Hz 380-600V – AC 50/60 Hz 480-600V

– DC 12-24V – DC 48-60V

– DC 110-125V – DC 220-250V

70-110%

– – –

135-500 VA–– –

– –

– –

70-110%

40-300 VA –

92-640 VA

51-240 VA –

278-700 VA –

54-400 W 100-160 W

55-71 W 110-140 W

70-110%

87-405 VA 710-1105 VA

66-432 VA 127-188 VA

– 34-60 VA

164-631 W 830-1580 W

112-150 W 40-58 W

70-110%

87-405 VA 710-1105 VA

66-432 VA 127-188 VA

– 34-60 VA

164-631 W 830-1580 W

112-150 W 40-58 W

70-110%

81-701 VA 58-90 VA

118-665 VA 125-181 VA

– 43-79 VA

79-1000 W 18-31 W

112-150 W 38-52 W

70-110%

86-631 VA 48-71 VA

81-505 VA 43-68 VA

– 41-69 VA

46-405 W 58-94 W

74-98 W 38-49 W

70-110%

177-1207 VA443-731 VA

323-1466 VA1193-1641 VA

–197-312 VA

289-865 W468-696 W

363-473 W513-665 W

Maximum Load Duration Interrupts Automatically

Maximum Opening Time 50 ms 50 ms 50 ms 50 ms 50 ms 62 ms 62 ms

Series C Frame Sizes G through R

UK PG.29B.01.T.U A4 1-12 Page 8 Friday, March 12, 1999 3:54 PM

July 1998

PG.29B.01.T.U

Cutler-Hammer 9Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

NSI-5181M

NSI-5180M

NSI-5179aM

NSI-5178aM

Electrical Characteristics

DC Switching Duty

The F- to L-Frame circuit breakers are also suitable for switching dc currents.

The N- and R-Frame circuit breakers, FWMP, KWMP, and LWMP circuit breakers for motor protection are not suitable for dc currents due to the solid state overcurrent release system.

For switching dc currents, however, the maximum permissible dc voltage per conducting path has to be con-sidered.

For voltages higher than 250 volts, the series connection of two or three conducting paths is required.

As the current has to flow through all conducting paths so as to maintain the thermal tripping characteristics, the following circuit arrangements are recommended. With dc, the trip values of the instantaneous short circuit release (“n” release) are increased by 30 to 40%.

For 3- and 4-Pole Circuit Breakers

Proposed Circuit Maximum Permissible VDC Ue

Remarks

250 VDC Double-pole switching.

If there is no risk of an earth fault, or if any earth fault which occurs is immediately eliminated (earth fault monitoring), the maximum permissible dc voltage can be 600 volts.

440 VDC Double-pole switching (earth system).

The earthed pole must always be assigned to the individual conducting path, so that two paths are always in series in the event of an earth fault.

600 VDC Single-pole switching (earthed system).

Three conducting paths in series. The earthed pole must be assigned to the nonswitched conducting path.

750 VDC Single-pole switching (earthed system).

Four conducting paths in series. The earthed pole must be assigned to the nonswitched conducting path.

Series C Frame Sizes F through L

UK PG.29B.01.T.U A4 1-12 Page 9 Friday, March 12, 1999 3:54 PM

PG.29B.01.T.U

Cutler-Hammer10July 1998

Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

Multi-Function Electronic Trip Units for All Applications

Digitrip™ RMS Trip Units

True RMS Sensing

Digitrip RMS Trip Units utilize our proprietary SuRE™ Chip and SuRE Plus™ Chip microprocessor-based intelligence to provide true rms sensing, permitting increased accu-racy and reliable system protection. True rms sensing is not susceptible to nuisance tripping when wave-forms containing high harmonic currents are present.

Digitrip RMS 310

Digitrip RMS 310 Electronic Trip Units are available with Series C Circuit Breakers K-, L-, N- and R-Frames 63 through 2500 amperes. Digitrip RMS 310 Trip Units are available in four styles with either fixed or adjustable rating plugs which establishes the continuous ampere rating of the breaker.

Rating Plugs

Digitrip RMS 310 Trip Units incor-porate rating plugs that are inter-changeable within a specific circuit breaker frame. This provides the user with versatility when establishing the continuous current rating of a breaker. Rating plugs are frequency sensitive and may be specified for 50 / 60 Hz applications. Both fixed and adjustable rating plugs are avail-able, providing further flexibility when applied to selectively coordi-nated systems.

Note: Digitrip RMS rating plugs are not interchangeable with SELTRONIC™ rating plugs.

Curve Shaping

When selectively coordinated sys-tems are called for, Digitrip RMS 310 will provide a cost-effective solution for a variety of applications.

The standard Digitrip RMS 310includes an adjustable short timepickup setting encompassing an I2tramp function which provides thebasic LS curve shaping function.

The optional Digitrip RMS 310 provides additional flat response short time delay adjustments on an instantaneous setting to provide LSI curve shaping capability.

Both Digitrip RMS 310 Trip Units are available with ground fault pickup and flat response ground fault delay which provide the trip unit with full function LSG and LSIG curve shap-ing flexibility.

Digitrip RMS 310 Trip Units can effectively coordinate with both sophisticated upstream power breakers as well as downstream thermal magnetic breakers…making Digitrip RMS 310 Trip Units the cost-effective reliable choice for selec-tively coordinated systems.

Thermal Memory

All Digitrip RMS Trip Units incorpo-rate a long delay and, when ordered with ground, a ground fault thermal memory feature. Thermal memory prevents the system from cumula-tive overheating due to repeated overcurrent events that may occur in quick succession.

Digitrip RMS 510, 610, 810, and 910

Digitrip RMS 510, 610, 810, and 910 Trip Units are available with Series C R-Frame Circuit Breakers 800 through 2500 amperes. Digitrip 510, 610, 810, and 910 Trip Units provide unparalleled system protection with fixed rating plugs to establish the continuous ampere rating of the breaker.

Curve Shaping

Digitrip RMS 510, 610, 810, and 910 Trip Units are available with up to nine curve shaping choices achieved by adjusting up to seven switches on the front of the unit for optimum system coordination. Maximum curve shaping flexibility is provided by dependent long and short delay adjustments that are long delay pickup (Ir) based, depicted on the front of the unit by the blue portion of the time-current curve.

Additional coordination capability can be provided by utilizing the short delay and ground fault zone selective interlocking features avail-able on these trip units.

R-Frame Digitrip RMS 310, 510, 610, 810, and 910 Trip Units (Noninterchangeable)

Series C Frame Sizes K through R

UK PG.29B.01.T.U A4 1-12 Page 10 Friday, March 12, 1999 3:54 PM

July 1998

PG.29B.01.T.U

Cutler-Hammer 11Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

System Diagnostics

All four Digitrip RMS models of trip units provide long delay, short delay, instantaneous, and ground fault cause of trip LEDs on the front of the unit. Digitrip RMS 610, 810, and 910 also offer a magnitude of trip information as well as remote signal contacts for improved system diagnostics.

System Monitoring

Digitrip 610, 810, and 910 Trip Units have the capability to monitor phase currents as well as neutral or ground currents. This information is dis-played on a large digital display mounted on the unit.

Digitrip RMS 810 and 910 Trip Units can also provide the user with power and energy monitoring capability. Peak power demand, present power demand, and total energy as well as forward and reverse energy can be monitored with this unit.

Digitrip RMS 910 Trip Units have the additional capability of monitoring line to line voltage as well as system power factor. Both parameters are displayed in the digital display win-dow and are supported by LEDs to indicate which parameter is being displayed.

Harmonics Monitoring

Digitrip RMS 910 Trip Units are capa-ble of displaying values of current harmonics in the digital display window. Percentage of harmonic content can be monitored for each phase, neutral or ground, up to the 27th harmonic. Additionally, a total harmonic distortion value can be calculated and displayed.

Communications

Digitrip RMS 810 and 910 have built-in communications options to allow all protection, monitoring, and con-trol information to be transmitted back to a central location via the Cutler-Hammer IMPACC System.

Field Testing

Integral field testing capability is provided on all 510, 610, 810 and 910 Trip Units. No additional test set is needed to perform both trip and no trip field testing.

Series C Frame Size R

UK PG.29B.01.T.U A4 1-12 Page 11 Friday, March 12, 1999 3:54 PM

PG.29B.01.T.U

Cutler-Hammer12July 1998

Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

Digitrip RMS Electronic Trip Unit Selection GuideDigitrip RMS 310 RMS 510 RMS 610 RMS 810 RMS 910

Breaker TypeFrame(s) Series C K-, L-, N- and R-Frames Series C R-Frame Series C R-Frame Series C R-Frame Series C R-FrameAmpere Rating 70A-2500A 800A-2500A 800A-2500A 800A-2500A 800A-2500AInterrupting Rating at 415V 35, 65, 100 kA 65, 100 kA 65, 100 kA 65, 100 kA 65, 100 kA

Trip Unit Sensingrms Sensing Yes Yes Yes Yes Yes

Protection and CoordinationProtection Ordering Options LS, LSG LSI, LSIG LI, LS, LSI, LIG,

LSG, LSIGLI, LSI, LIG, LSG, LSIG

LI, LS, LSI, LIG, LSG, LSIG

LI, LS, LSI, LIG, LSG, LSIG

Fixed Rating Plug (In) Yes Yes Yes Yes Yes YesOvertemperature Trip Yes Yes Yes Yes Yes Yes

Long Delay Adjustable Rating Plug (In) Yes Yes No No No NoLong Delay Setting 0.5-1.0 (ln)➀ 0.5-1.0 (ln)➀ 0.5-1.0 x (ln) 0.5-1.0 x (ln) 0.5-1.0 x (ln) 0.5-1.0 x (ln)Long Delay Time I2t 12 Seconds 12 Seconds 2-24 Seconds 2-24 Seconds 2-24 Seconds 2-24 SecondsLong Delay Thermal Memory Yes Yes Yes Yes Yes YesHigh Load Alarm No No No 0.85 x Ir 0.85 x Ir 0.85 x Ir

Short Delay

Short Delay Setting 200-800% x (ln)➅ 200-800% x (ln)➅ 200-600% S1 & S2 x (Ir)

200-600% S1 & S2 x (Ir)

200-600% S1 & S2 x (Ir)

200-600% S1 & S2 x (Ir)

Short Delay Time I2t 100 ms No 100-500 ms 100-500 ms 100-500 ms 100-500 msShort Delay Time Flat No I-300 ms 100-500 ms 100-500 ms 100-500 ms 100-500 msShort Delay Time ZSI No No Yes Yes Yes Yes

Instanta-neous

Instantaneous Setting No 200-800% x (ln) 200-600% M1 & M2 x (ln)

200-600% M1 & M2 x (ln)

200-600% M1 & M2 x (ln)

200-600% M1 & M2 x (ln)

Discriminator No No Yes➃ Yes➃ Yes➃ Yes➃

Instantaneous Override Yes Yes Yes Yes Yes YesGroundFault

Ground Fault Setting Var/Frame➂ Var/Frame➂ 25-100% x (ln)➂ 25-100% x (ln)➂ 25-100% x (ln)➂ 25-100% x (ln)➂Fault Delay I2t No No 100-500 ms 100-500 ms 100-500 ms 100-500 msGround Fault Delay Flat I-500 ms I-500 ms I-500 ms I-500 ms I-500 ms I-500 msGround Fault ZSI No No Yes Yes Yes YesGround Fault Thermal Memory Yes Yes Yes Yes Yes Yes

System DiagnosticsCause of Trip LEDs No No Yes Yes Yes YesMagnitude of Trip Information No No No Yes Yes YesRemote Signal Contacts No No No Yes Yes Yes

System MonitoringDigital Display No No No Yes Yes YesCurrent No No No Yes Yes YesVoltage No No No No No YesPower and Energy No➁ No➁ No No Yes YesPower Quality - Harmonics No No No No No YesPower Factor No No No No Yes➄ Yes

System CommunicationsIMPACC No No No No Yes Yes

Field TestingTesting Method➀ Test Set Test Set Integral Integral Integral Integral

➀ Set by adjustable rating plug➁ Yes, with addition of Energy Sentinal.➂ Not to exceed 1200A.

In = Rating plug rating.Ir = LDPU setting.

➃ LS, LSG only. ➄ Over IMPACC only.➅ 2500A R-frame 200-600% x (In)

Series C Frame Sizes K through R

UK PG.29B.01.T.U A4 1-12 Page 12 Friday, March 12, 1999 3:54 PM

July 1998

PG.29B.01.T.U

Cutler-Hammer

13Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

Special 50

°

C rating available. Order by description.

GWF is direct supersedure for GW fixed thermal magnetic breaker.

MaximumContinuousAmpereRatingat 40

°

C

Standard Interrupting Capacity Catalogue Number

U

e

Maximum 240 VAC U

e

Maximum 440 VAC

20 kA I

cu

at 240 VAC 25 kA I

cu

at 415 VAC

Type GWF

1-Pole 2-Pole 3-Pole

Fixed Thermal/Fixed Magnetic Circuit Breakers Sealed Breakers with Noninterchangeable Trip Units and Line and Load Terminals

1620253240

506380

100

GWF1016GWF1020GWF1025GWF1032GWF1040

GWF1050GWF1063GWF1080GWF1100

GWF2016GWF2020GWF2025GWF2032GWF2040

GWF2050GWF2063GWF2080GWF2100

GWF3016GWF3020GWF3025GWF3032GWF3040

GWF3050GWF3063GWF3080GWF3100

Terminals (Factory Fitted Only)

Frame Amperes Terminal Type Wire Type Wire Range

G 16-100 Pressure Type Copper 2.5-50

Series C Frame Size G, 16-100 Amperes

Selection Guide and Ordering Information

UK PG.29B.01.T.U A4 13-22 Page 13 Friday, March 12, 1999 3:56 PM

PG.29B.01.T.U

Cutler-Hammer

14

July 1998

Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

MaximumContinuousAmpere Ratingat 40

°

C

ThermalRange

MagneticRange

Standard Interrupting CapacityCatalogue Number

High Interrupting CapacityCatalogue Number

Ultra-High Interrupting CapacityCatalogue Number

StandardTerminalsOnly CatalogueNumber

MetricMountingHardwareCatalogueNumber

U

e

Maximum 690 VAC U

e

Maximum 690 VAC U

e

Maximum 690 VAC

40 kA I

cu

at 415 VAC 70 kA I

cu

at 415 VAC 100 kA I

cu

at 415 VAC

3-Pole 4-Pole

3-Pole 4-Pole

3-Pole 4-Pole

Adjustable Thermal/Fixed Magnetic Circuit Breakers – Sealed Breakers with Noninterchangeable Trip UnitsLine and Load Terminals Included

Type FW Type HFW Type FWC

1620253240

506380

100125

160200225

12- 1616- 2020- 2525- 3232- 40

40- 5050- 6363- 8080-100

100-125

125-160160-200200-225

FixedFixedFixedFixedFixed

FixedFixedFixedFixedFixed

FixedFixedFixed

FW3016LFW3020LFW3025LFW3032LFW3040L

FW3050LFW3063LFW3080LFW3100LFW3125L

FW3160LFW3200LFW3225L

FW4016LFW4020LFW4025LFW4032LFW4040L

FW4050LFW4063LFW4080LFW4100LFW4125L

FW4160LFW4200LFW4225L

HFW3016LHFW3020LHFW3025LHFW3032LHFW3040L

HFW3050LHFW3063LHFW3080LHFW3100LHFW3125L

HFW3160LHFW3200LHFW3225L

HFW4016LHFW4020LHFW4025LHFW4032LHFW4040L

HFW4050LHFW4063LHFW4080LHFW4100LHFW4125L

HFW4160LHFW4200LHFW4225L

FWC3016LFWC3020LFWC3025LFWC3032LFWC3040L

FWC3050LFWC3063LFWC3080LFWC3100LFWC3125L

FWC3160LFWC3200LFWC3225L

FWC4016LFWC4020LFWC4025LFWC4032LFWC4040L

FWC4050LFWC4063LFWC4080LFWC4100LFWC4125L

FWC4160LFWC4200LFWC4225L

T100FBT100FBT100FBT100FBT100FB

T100FBT100FBT100FBT100FBT100FB

T100FBTA225FDMTA225FDM

BMH1MBMH1MBMH1MBMH1MBMH1M

BMH1MBMH1MBMH1MBMH1MBMH1M

BMH1MBMH1MBMH1M

Adjustable Thermal/Adjustable Magnetic Circuit Breakers – Sealed Breakers with Noninterchangeable Trip Units

Type FW-J Type HFW-J Type FWC-J

2025324050

6380

100125160

200225

16- 2020- 2525- 3232- 4040- 50

50- 6363- 8080-100

100-125125-160

160-200200-225

100- 200125- 250160- 320200- 400300- 500

315- 630400- 800500-1000625-1250800-1600

1000-20001125-2250

FW3020JLFW3025JLFW3032JLFW3040JLFW3050JL

FW3063JLFW3080JLFW3100JLFW3125JLFW3160JL

FW3200JLFW3225JL

FW4020J0LFW4025J0LFW4032J0LFW4040J0LFW4050J0L

FW4063J0LFW4080J0LFW4100J0LFW4125J0LFW4160J0L

FW4200J0LFW4225J0L

HFW3020JLHFW3025JLHFW3032JLHFW3040JLHFW3050JL

HFW3063JLHFW3080JLHFW3100JLHFW3125JLHFW3160JL

HFW3200JLHFW3225JL

HFW4020J0LHFW4025J0LHFW4032J0LHFW4040J0LHFW4050J0L

HFW4063J0LHFW4080J0LHFW4100J0LHFW4125J0LHFW4160J0L

HFW4200J0LHFW4225J0L

FWC3020JLFWC3025JLFWC3032JLFWC3040JLFWC3050JL

FWC3063JLFWC3080JLFWC3100JLFWC3125JLFWC3160JL

FWC3200JLFWC3225JL

FWC40200LJFWC40250LJFWC40320LJFWC40400LJFWC40500LJ

FWC40630LJFWC40800LJFWC41000LJFWC41250LJFWC41600LJ

FWC42000LJFWC42250LJ

T100FBT100FBT100FBT100FBT100FB

T100FBT100FBT100FBT100FBT100FB

T225DFMTA225FDM

BMH1MBMH1MBMH1MBMH1MBMH1M

BMH1MBMH1MBMH1MBMH1MBMH1M

BMH1MBMH1M

Adjustable Thermal/Fixed Magnetic Earth Leakage Circuit Breakers – Sealed Breakers with Noninterchangeable Trip UnitsLine and Load Terminals Included

Type ELFW (U

e

Max. 415 VAC) Type ELHFW (U

e

Max. 415 VAC) Type ELFWC (U

e

Max. 415 VAC)

506380

100

125160200

40- 5050- 6363- 8080-100

100-125125-160160-200

FixedFixedFixedFixed

FixedFixedFixed

ELFW3050LELFW3063LELFW3080LELFW3100L

ELFW3125LELFW3160LELFW3200L

ELFW4050LELFW4063LELFW4080LELFW4100L

ELFW4125LELFW4160LELFW4200L

ELHFW3050LELHFW3063LELHFW3080LELHFW3100L

ELHFW3125LELHFW3160LELHFW3200L

ELHFW4050LELHFW4063LELHFW4080LELHFW4100L

ELHFW4125LELHFW4160LELHFW4200L

ELFWC3050LELFWC3063LELFWC3080LELFWC3100L

ELFWC3125LELFWC3160LELFWC3200L

ELFWC4050LELFWC4063LELFWC4080LELFWC4100L

ELFWC4125LELFWC4160LELFWC3200L

TF100FBTF100FBTF100FBTF100FB

TF100FBTF100FBTA225FDM

BMH1MBMH1MBMH1MBMH1M

BMH1MBMH1MBMH1M

Moulded Case Switches

Type FWF (U

e

Max. 690 VAC) Type HFWF (U

e

Max. 690 VAC)

3-Pole 4-Pole 3-Pole 4-Pole

100160225

– – FWF3100KLFWF3160KLFWF3225KL

FWF4100KLFWF4160KLFWF4225KL

HFWF3100KLHFWF3160KLHFWF3225KL

HFWF4100KLHFWF4160KLHFWF4225KL

– – T100FBT100FBTA225FDM

BMH1MBMH1MBMH1M

Selection Guide and Ordering Information

Maxi-mumContin-uousAmpereRatingat 40

°

C

Standard Interrupting CapacityCatalogue Number

High Interrupting Capacity Catalogue Number

Ultra-High Interrupting CapacityCatalogue Number

StandardTerminalsOnlyCatalogueNumber

MetricMountingHardwareCatalogueNumber

U

e

Max.240 VAC

U

e

Maximum 690 VAC U

e

Maximum240 VAC

U

e

Maximum 690 VAC U

e

Maximum 690 VAC

40 kA I

cu

at 240 VAC

40 kA I

cu

at 415 VAC 70 kA I

cu

at 240 VAC70 kA I

cu

at 415 VAC 100 kA I

cu

at 415 VAC

1-Pole 2-Pole 3-Pole 4-Pole

1-Pole 2-Pole 3-Pole 4-Pole

2-Pole 3-Pole 4-Pole

Fixed Thermal / Fixed Magnetic Circuit Breakers – Sealed Breakers with Noninterchangeable Trip UnitsLine and Load Terminals Included)

Type FWF (16-40A, 415 VAC Max.) Type HFWF (16-40A, 415 VAC Max.) Type FWCF (16-40A, 415 VAC Max.)

1620253240

506380

100

125160175200225

FWF1016LFWF1020LFWF1025LFWF1032LFWF1040L

FWF1050LFWF1063LFWF1080LFWF1100L

FWF1125LFWF1160L

–––

FWF2016LFWF2020LFWF2025LFWF2032LFWF2040L

FWF2050LFWF2063LFWF2080LFWF2100L

FWF2125LFWF2160LFWF2175LFWF2200LFWF2225L

FWF3016LFWF3020LFWF3025LFWF3032LFWF3040L

FWF3050LFWF3063LFWF3080LFWF3100L

FWF3125LFWF3160LFWF3175LFWF3200LFWF3225L

FWF4016L0FWF4020L0FWF4025L0FWF4032L0FWF4040L0

FWF4050L0FWF4063L0FWF4080L0FWF4100L0

FWF4125L0FWF4160L0FWF4175L0FWF4200L0FWF4225L0

HFWF1016LHFWF1020LHFWF1025LHFWF1032LHFWF1040L

HFWF1050LHFWF1063LHFWF1080LHFWF1100L

HFWF1125LHFWF1160L

–––

HFWF2016LHFWF2020LHFWF2025LHFWF2032LHFWF2040L

HFWF2050LHFWF2063LHFWF2080LHFWF2100L

HFWF2125LHFWF2160LHFWF2175LHFWF2200LHFWF2225L

HFWF3016LHFWF3020LHFWF3025LHFWF3032LHFWF3040L

HFWF3050LHFWF3063LHFWF3080LHFWF3100L

HFWF3125LHFWF3160LHFWF3175LHFWF3200LHFWF3225L

HFWF4016L0HFWF4020L0HFWF4025L0HFWF4032L0HFWF4040L0

HFWF4050L0HFWF4063L0HFWF4080L0HFWF4100L0

HFWF4125L0HFWF4160L0HFWF4175L0HFWF4200L0HFWF4225L0

FWCF2016LFWCF2020LFWCF2025LFWCF2032LFWCF2040L

FWCF2050LFWCF2063LFWCF2080LFWCF2100L

FWCF2125LFWCF2160LFWCF2175LFWCF2200LFWCF2225L

FWCF3016LFWCF3020LFWCF3025LFWCF3032LFWCF3040L

FWCF3050LFWCF3063LFWCF3080LFWCF3100L

FWCF3125LFWCF3160LFWCF3175LFWCF3200LFWCF3225L

FWCF4016L0FWCF4020L0FWCF4025L0FWCF4032L0FWCF4040L0

FWCF4050L0FWCF4063L0FWCF4080L0FWCF4100L0

FWCF4125L0FWCF4160L0FWCF4175L0FWCF4200L0FWCF4225L0

T100FBT100FBT100FBT100FBT100FB

T100FBT100FBT100FBT100FB

T100FBT100FBTA225FDMTA225FDMTA225FDM

BMH1MBMH1MBMH1MBMH1MBMH1M

BMH1MBMH1MBMH1MBMH1M

BMH1MBMH1MBMH1MBMH1MBMH1M

Special 50

°

C rating available. Order by description.

Add suffix 1 for 100% protected neutral. Neutral left pole.

Neutral left pole. 16-63A unprotected neutral only.Add suffix 1 for 100% protected neutral 80-100A.Add suffix 6 for 60% protected neutral 125-225A.

Series C Frame Size F, 16-225 Amperes

UK PG.29B.01.T.U A4 13-22 Page 14 Friday, March 12, 1999 3:56 PM

July 1998

PG.29B.01.T.U

Cutler-Hammer

15Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

Interphase Barriers

The interphase barrier is available for extended insulation between cir-cuit breaker poles. Specify quantity when ordering.

Package of 2

Catalogue Number – IPB1

Terminal Shields

The terminal shield is available for line terminal areas in 1-, 2-, 3-, and 4-pole circuit breakers. Special termi-nal shields are also available for use when an electrical (solenoid) opera-tor is mounted on the circuit breaker. The standard style number by pole for each terminal shield is for a pack-age of 10 and is priced per each package. Special terminal shields are packaged individually.

Terminal End Covers

The terminal end cover is available for 3-pole circuit breakers only. Two conductor opening sizes are availa-ble. Specify quantity (one per circuit breaker) when ordering.

NumberofPoles

StandardPackage of 10

SpecialPackaged Individually

Catalogue Numbers – Priced Individually

1 625B229G06 –

2 625B229G07 –

3 625B229G08 4210B95G01

4 625B229G09 4210B95G02

Conductor OpeningDiameter – mm (Inches)

CatalogueNumber

6.35 (0.25) TEC1

10.41 (0.41) TEC2

Screw

Washer

Collar

Conductor

Nut

Line and Load Terminals

F-Frame circuit breakers and moulded case switches have line and load terminals as standard equipment.

3T100FB, 3T150FB

Insert collar enclosing con-ductor as shown. Locate nut on top of conductor and tighten securely with screw and washer. Caution: Collar must surround conductor

3TA225FDM

Insert collar enclosing conductor and centre on extrusion. Install clip with legs on top of conductor and snap end around bot-tom of collar.

3TA225FDK

Assemble collar on top of conductor and tighten to 100 lbs. Slide the terminal shield into position; use the high-low screws to secure the shield in place.

KPEKM1 – Metric, KPEK1 – Imperial

Endcap kits are used on F-frame breaker line load to connect bus bar or similar electrical connec-tions. Includes hardware.

Control Wire Terminal Kit

For use with steel or stainless steel

terminals only.

Package of 12 – Priced Individually

Catalogue Number – FCWTK

Not for use with 3T20FB terminals

Selection Guide and Ordering Information

Package ofBreaker Amperes

BodyMaterial

Type WireRange mm

2

Range/NumberConductors

3 TerminalsCatalogue Number

Standard Pressure Type Terminals

160 Steel Cu/Al 2.5-50 #14-1/0 3T100FB

225 Aluminium Cu/Al 25-95 #4-4/0 3TA225FDM

Optional Pressure Type Terminals

160 Stainless Steel Copper 25-95 #4-4/0 3T150FB

225 Aluminium Cu/Al 16-150 6-300 MCM 3TA225FDK

Catalogue Number

ConductorExtrusion

Clip

Collar

NumberofPoles

Description Type ofMounting

CatalogueNumber

Metric Thread

1 M4-0.7 x80 mmPan-HeadSteel Screws,Lockwashers,and Clamps

Individual

Group (One Set of Hardwarefor Two CircuitBreakers)

4218B80G09

4218B80G10

2 M4-0.7 x38 mmPan-HeadSteel Screws,and Lock-washers

Individual 4218B80G11

3, 4 – Individual 4218B80G12

Imperial Thread

1 .164-32 x3.188 InchPan-HeadSteel Screws,Lockwashers,and Clamps

Individual

Group (One Set of Hardwarefor Two CircuitBreakers)

624B375G01

624B375G02

2 .164-32 x 1.5Inch Pan-Head SteelScrews andLockwashers

Individual 4218B80G01

3, 4 – Individual 4218B80G02

Base Mounting Hardware

Base mounting hardware is included with a circuit breaker or moulded case switch.

Series C Frame Size F, 16-225 Amperes

UK PG.29B.01.T.U A4 13-22 Page 15 Friday, March 12, 1999 3:56 PM

PG.29B.01.T.U

Cutler-Hammer

16

July 1998

Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

Special 50

°

C rating available. Order by description.

Individually packed.

60% protected neutral.

MaximumContinuousAmpereRating at 40

°

C

➀➁

NumberofPoles

ThermalRange

MagneticRange

Standard Interrupting Capacity High Interrupting Capacity Ultra-High Interrupting CapacityCurrent Limiting

ThermalMagneticTrip Unit Only

For Use withStandard or Highor Ultra-HighInterrogatingFrame

Adjustable Thermal

AdjustableMagnetic

StandardTerminals Only CatalogueNumber

MetricMountingHardwareCatalogueNumber

U

e

Max. 690 VAC U

e

Max. 690 VAC U

e

Max. 690 VAC

40 kA I

cu

at 415 VAC 70 kA I

cu

at 415 VAC 100 kA I

cu

at 415 VAC

FactoryAssembledCircuit BreakerConsisting ofFrame, Trip Unit,and Terminals

Frame Only FactoryAssembledCircuit BreakerConsisting ofFrame, Trip Unit,and Terminals

Frame Only FactoryAssembledCircuit BreakerConsisting ofFrame, Trip Unit,and Terminals

Frame Only

Catalogue Number

Adjustable Thermal Magnetic Circuit BreakersWith Interchangeable Trip Units

Type JW Type HJW Type JWC

125160200250

2-Pole 100-125125-160160-200200-250

625-1250 800-16001000-20001250-2500

JW2125JW2160JW2200JW2250

JW2250F HJW2125HJW2160HJW2200HJW2250

HJW2250F JWC2125JWC2160JWC2200JWC2250

JWC2250F JT2125TAJT2160TAJT2200TAJT2250TA

TA250KB

TA250KB

TA250KB

TA250KB

BMH2MBMH2MBMH2MBMH2M

125160200250

3-Pole 100-125125-160160-200200-250

625-1250 800-16001000-20001250-2500

JW3125JW3160JW3200JW3250

JW3250F HJW3125HJW3160HJW3200HJW3250

HJW3250F JWC3125JWC3160JWC3200JWC3250

JWC3250F JT3125TAJT3160TAJT3200TAJT3250TA

TA250KB

TA250KB

TA250KB

TA250KB

BMH2MBMH2MBMH2MBMH2M

125160200

250200250

4-Pole 100-125125-160160-200

200-250160-200200-250

625-1250 800-16001000-2000

1250-25001000-20001250-2500

JW4125JW4160JW4200

JW4250JW4200E

JW4250E

JW4250F HJW41250HJW41600HJW42000

HJW42500HJW42006HJW42506

HJW4250F JWC41250JWC41600JWC42000

JWC42500JWC42006JWC42506

JWC4250F JT4125TAJT4160TAJT4200TA

JT4250TAJT4200TEA

JT4250TEA

TA250KB

TA250KB

TA250KB

TA250KB

TA250KB

TA250KB

BMH2MBMH2MBMH2M

BMH2MBMH2MBMH2M

Adjustable Thermal Magnetic Earth Leakage Circuit BreakersWith Line and Load Terminals Included

Type ELJW (U

e

Max. 415 VAC) Type ELHJW (U

e

Max. 415 VAC) Type ELJWC (U

e

Max. 415 VAC)

125160200250

3-Pole 100-125125-160160-200200-250

625-1250 800-16001000-20001250-2500

ELJW3125ELJW3160ELJW3200ELJW3250

– ELHJW3125ELHJW3160ELHJW3200ELHJW3250

– ELJWC3125ELJWC3160ELJWC3200ELJWC3250

– – TA250KBTA250KBTA250KBTA250KB

BMH2MBMH2MBMH2MBMH2M

125160200250

4-Pole 100-125125-160160-200200-250

625-1250 800-16001000-20001250-2500

ELJW4125ELJW4160ELJW4200ELJW4250

– ELHJW4125ELHJW4160ELHJW4200ELHJW4250

– ELJWC4125ELJWC4160ELJWC4200ELJWC4250

– – TA250KBTA250KBTA250KBTA250KB

BMH2MBMH2MBMH2MBMH2M

Moulded Case SwitchesMCS Only without Line and Load Terminals

Type JW (U

e

Max. 690 VAC) Type HJW (U

e

Max. 690 VAC)

250 2-Pole3-Pole4-Pole

– – JW2250KWJW3250KWJW4250KW

– HJW2250KWHJW3250KWHJW4250KW

– – – – TA250KB

TA250KB

TA250KB

BMH2M

BMH2M

BMH2M

Selection Guide and Ordering Information

Series C Frame Size J, 100-250 Amperes

UK PG.29B.01.T.U A4 13-22 Page 16 Friday, March 12, 1999 3:56 PM

July 1998

PG.29B.01.T.U

Cutler-Hammer

17Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

Line and Load Terminals

J-Frame circuit breakers include Cu/Al terminals as standard. When optional copper only terminals are required, order by catalogue number.

Base Mounting Hardware

Base mounting hardware is included with a circuit breaker or moulded case switch.

Handle Extension

Not included with breaker. Must be purchased separately.

Numberof Poles

Description Type of Mounting

CatalogueNumber

Metric Thread

2, 3, 4 M6-0.7 x70 mm Pan-HeadSteel Screwsand Lock-washers

Individual

4218B80G13

Imperial Thread

2, 3, 4 0.250-20 x2.75 Inch Pan-Head Steel Screwsand Lock-washers

Individual

4218B80G03

Packaged Individually

Catalogue Number – HEX3

Maximum Breaker Amperes

TerminalBodyMaterial

WireType

MetricWireRange mm

2

AWG WireRange/NumberConductors

Catalogue Number

Standard Cu/Al Pressure Type Terminals

250 Aluminium Cu/AI 25-185 #4-350 MCM TA250KB

250 Stainless Steel Copper 25-185 #4-350 MCM T250KB

Control Wire Terminal Kit

For use with TA250KB terminals only.

Package of 12 – Priced Individually

Catalogue Number – KCWTK

Terminal Shields

Terminal shields are available for line and load terminal areas in 2-, 3- and 4-pole circuit breakers. Terminal shields must be ordered in multiples of 10 (for each style number). (Field installation only.

Interphase Barriers

Field installation only.

Location Number of Poles Style NumberPackage of 10

Line End 2, 34

1266C07G016631C01G01

Load End 2, 34

6641C16G016641C16G02

Package of 2

Catalogue Number – IPB3

Selection Guide and Ordering Information

Catalogue Number

T250KB TA250KB

NutSlottedScrew

Collar

Collar

SlottedScrew

KPEKM1 – Metric, KPEK1 – Imperial

Endcap kits are used on J-frame breaker line load to connect bus bar or similar electrical connections. Includes hardware.

Kit Catalogue Number

Metric Imperial

KPEKM2 KPEK2

Series C Frame Size J, 100-250 Amperes

UK PG.29B.01.T.U A4 13-22 Page 17 Friday, March 12, 1999 3:56 PM

PG.29B.01.T.U

Cutler-Hammer

18

July 1998

Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

Selection Guide and Ordering Information

Maximum Continuous Ampere Rating at 40

°

C

➀➁

Number of Poles

Thermal Range

Magnetic Range

Standard Interrupting CapacityCatalogue Number

High Interrupting CapacityCatalogue Number

Ultra-High Interrupting CapacityCatalogue Number

Thermal Magnetic Trip Unit Only

For Use with Standard or High or Ultra-High Inter-rupting Frame

Adjustable Thermal

Adjustable Magnetic

Standard Terminals Only Catalogue Number

MetricMountingHardwareCatalogueNumberU

e

Max. 690 VAC U

e

Max. 690 VAC U

e

Max. 690 VAC

45 kA I

cu

at 415 VAC 70 kA I

cu

at 415 VAC 100 kA I

cu

at 415 VAC

FactoryAssembledCircuit BreakerConsisting ofFrame, Trip Unit, and Terminals

Frame Only

FactoryAssembledCircuit BreakerConsisting ofFrame, Trip Unit, and Terminals

Frame Only

FactoryAssembledCircuit BreakerConsisting ofFrame, Trip Unit, and Terminals

Frame Only

Adjustable Thermal Magnetic Circuit Breakers with Interchangeable Trip Units

Type KW Type HKW Type KWC

200250315400

2-Pole 160-200200-250250-315315-400

1000-20001250-25001575-31502000-4000

KW2200KW2250KW2315KW2400

KW2400F HKW2200HKW2250HKW2315HKW2400

HKW240F KWC2200KWC2250KWC2315KWC2400

KWC2400F KT2200TAKT2250TAKT2315TAKT2400TA

TA300KM

TA300KM

TA350KM

TA350KM

BMH3MBMH3MBMH3MBMH3M

200250315400

3-Pole 160-200200-250250-315315-400

1000-20001250-25001575-31502000-4000

KW3200KW3250KW3315KW3400

KW3400F HKW3200HKW3250HKW3315HKW3400

HKW3400F KWC3200KWC3250KWC3315KWC3400

KWC3400F KT3200TAKT3250TAKT3315TAKT3400TA

TA300KM

TA300KM

TA350KM

TA350KM

BMH3MBMH3MBMH3MBMH3M

200250315

400315400

4-Pole 160-200200-250250-315

315-400250-315315-400

1000-20001250-25001575-3150

2000-40001575-31502000-4000

KW4200KW4250KW4315

KW4400KW4315E

KW4400E

KW4400F HKW4200HKW4250HKW4315

HKW4400HKW4315E

HKW4400E

HKW4400F KWC4200KWC4250KWC4315

KWC4400KWC4315E

KWC4400E

KWC4400F KT4200TAKT4250TAKT4315TA

KT4400TAKT4315TEA

KT4400TEA

TA300KM

TA300KM

TA350KM

TA350KM

TA350KM

TA350KM

BMH3MBMH3MBMH3M

BMH3MBMH3MBMH3M

Adjustable Thermal Magnetic Earth Leakage Circuit Breakers with Line and Load Terminals Included

Type ELKW (U

e

Max. 415 VAC) Type ELHKW (U

e

Max. 415 VAC)Type ELKWC (U

e

Max. 415 VAC)

200250315400

3-Pole 160-200200-250250-315315-400

1000-20001250-25001575-31502000-4000

ELKW3200ELKW3250ELKW3315ELKW3400

– ELHKW3200ELHKW3250ELHKW3315ELHKW3400

– ELKWC3200ELKWC3250ELKWC3315ELKWC3400

– – TA350KMTA350KMTA350KMTA350KM

BMH3MBMH3MBMH3MBMH3M

200250315400

4-Pole 160-200200-250250-315315-400

1000-20001250-25001575-31502000-4000

ELKW4200ELKW4250ELKW4315ELKW4400

– ELHKW4200ELHKW4250ELHKW4315ELHKW4400

– ELKWC4200ELKWC4250ELKWC4315ELKWC4400

– – TA350KMTA350KMTA350KMTA350KM

BMH3MBMH3MBMH3MBMH3M

Moulded Case Switches MCS Only without Line and Load Terminals

Type KW (U

e

Max. 690 VAC) Type HKW (U

e

Max. 690 VAC)

400 2-Pole3-Pole4-Pole

– – KW2400KWKW3400KWKW4400KW

– HKW2400KWHKW3400KWHKW4400KW

– – – – TA350KM➀TA350KM➀TA350KM➀

BMH3MBMH3MBMH3M

Electronic Circuit Breakers➃

With Interchangeable Type KES Digitrip RMS Trip Units – Order as Individual Components: Breaker Frame, Trip Unit, Rating Plug, Terminals, Mounting Hardware

Maximum Continu-ous Ampere Rating at 40°C➀➁

Number of Poles

Circuit Breaker Frame OnlyCatalogue Number

Digitrip RMS 310 Trip Unit Only Less Rating PlugCatalogue Number

Digitrip RMS 310 Only Rating PlugOrder as Individual Component

Standard Terminals Only Catalogue Number

Metric Mounting Hardware Catalogue NumberStandard

InterruptingCapacity

HighInterruptingCapacity

Ultra-HighInterruptingCapacity

L - Adjustable Long Delay Pickup (By Adjustable Rating Plug)

S - Adjustable Short Delay Pickup with Fixed Short Delay Time (I2t Response) or Adjustable Short Delay Time (Flat Response)

I - Adjustable Instantaneous Pickup by Setting Short Delay Time to Instantaneous

G - Adjustable Ground Fault Pickup with Adjustable Ground Fault Delay (Flat Response)

Fixed Rating Plug AdjustableRatingPlug

Ue Max. 690 VAC AmpereRating

CatalogueNumber

AmpereRatingCatalogueNumber

45 kA Icuat 415 VAC

70 kA Icuat 415 VAC

100 kA Icuat 415 VAC

Type KW Type HKW Type KWC LS LSI LSG LSIG

125 3-Pole KW3400F HKW3400F KWC3400F KES3125LS KES3125LSI KES3125LSG KES3125LSIG 637090

100125

1KES063T1KES070T1KES090T1KES100T1KES125T

Adjustable Settings are:63/80/100/125A1KES125T2

TA300KM➀TA300KM➀TA300KM➀TA300KM➀TA300KM➀

BMH3MBMH3MBMH3MBMH3MBMH3M

250 KW3400F HKW3400F KWC3400F KES3250LS KES3250LSI KES3250LSG KES3250LSIG 125160200225250

2KES125T2KES160T2KES200T2KES225T2KES250T

Adjustable Settings are:125/160/225/250A2KES250T2

TA300KM➀TA300KM➀TA300KM➀TA300KM➀TA300KM➀

BMH3MBMH3MBMH3MBMH3MBMH3M

400 KW3400F HKW3400F KWC3400F KES3400LS KES3400LSI KES3400LSG KES3400LSIG 200225250315400

4KES200T4KES225T4KES250T4KES315T4KES400T

Adjustable Settings are:200/250/315/400A4KES400T2

TA300KM➀TA300KM➀TA300KM➀TA350KM➀TA350KM➀

BMH3MBMH3MBMH3MBMH3MBMH3M

➀ Individually packed. ➁ Special 50ªC rating available. Order by description.

➂ 60% protected neutral - left pole➃ For AC application only.

Series C Frame Size K, 63-400 Amperes

UK PG.29B.01.T.U A4 13-22 Page 18 Friday, March 12, 1999 3:56 PM

July 1998

PG.29B.01.T.U

Cutler-Hammer 19Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

Handle Extension

Not included with breaker. Must be purchased separately.

Packaged Individually

Catalogue Number – HEX3

Endcap Kit

Endcap kits are used on K-Frame breaker line load to connect bus bar or similar electrical connections. Includes hardware.

Kit Catalogue Number

Metric Imperial

KPEKM3 KPEK3

Control Wire Terminal Kit

For use with aluminium or copper terminals only.

Package of 14 - Priced Individually

Catalogue Number – KCWTK

Line and Load Terminals

K-Frame circuit breakers include Cu/Al terminals as standard. When optional copper or Cu/1919Al termi-nals are required, order by cata-logue number.

Selection Guide and Ordering Information

Catalogue Number

TA300KM, TA300K, T300K TA350KM, TA350K, T350K TA400K, T400K TA401K

Interphase Barriers

NumberofPoles

Description Type ofMounting

CatalogueNumber

Metric Thread

2, 3, 4 M6-0.7 x38 mmPan-HeadSet-screws andLockwashers

Individual 4218B80G14

Imperial Thread

2, 3, 4 0.250-20 x1.5 InchPan-HeadSteel Screws andLockwashers

Individual 4218B80G14

Terminal Shields

Location Number of Poles

Catalogue NumberPackage of 10

Line End 2, 34

TS33LNTS34LN

Load End 3 TS33LD

Package of 2

Catalogue Number – IPB3

MaximumBreaker Amperes

Terminal BodyMaterial

Wire Type Metric WireRange mm2

AWG Wire Range/NumberConductors

Catalogue Number

Standard Pressure Type Terminals

225 Aluminium Cu/Al 35-185 3-350/(1) TA300KM➂

400 Aluminium Cu/Al 120-240 250-500/(1) TA350KM➂

Optional Copper and Cu/Al Pressure Type Terminals

225 Copper Cu 35-185 3-350/(1) T300K➂

400 Copper Cu 120-240 250-500/(1) T300K➂

400 Aluminium Cu/Al 95-120 3/0-250/(2) 2TA400K - 2-Pole Kit➃3TA400K - 3-Pole Kit➃4TA400K - 4-Pole Kit➃

400 Aluminium Cu 95-120 3/0-250/(2) 2T400K - 2-Pole Kit➃3T400K - 3-Pole Kit➃4T400K - 4-Pole Kit➃

400 Aluminium Cu/Al 70-24070-24070-240

2/0-250/(2)or

2/0-500/(1)

2TA401K - 2-Pole Kit➃3TA401K - 3-Pole Kit➃4TA401K - 4-Pole Kit➃

Base Mounting Hardware

Base mounting hardware is included with a circuit breaker or moulded case switch.

➀ Metric hardware.➁ Imperial hardware.➂ Individually packed.

➃ TA400K, T400K, and TA401K terminal kits contain one terminal for each pole and one terminal cover.

Series C Frame Size K, 63-400 Amperes

UK PG.29B.01.T.U A4 13-22 Page 19 Friday, March 12, 1999 3:56 PM

PG.29B.01.T.U

Cutler-Hammer20July 1998

Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

➀ Individually packed.➁ Special 50ªC rating available.

Order by description.➂ 2TA603KM, 3TA603LDKM and

4TA603LDKM terminal kits contain one ter-minal per each pole and one terminal cover.

➃ 60% protected neutral – left pole➄ Ampere rating is established by rating plug.➅ For AC application only.➆ 3-pole LES trip units are for use in 3-pole

frames only.

➇ Trip unit includes unprotected left neutral pole. For 100% protected left pole neutral add “P” to catalogue number, i.e., LES4630LSP.

Selection Guide and Ordering InformationMaximum Continuous Ampere Rating at 40°C①➁

Number of Poles

Standard Interrupting CapacityCatalogue Number

High Interrupting CapacityCatalogue Number

Ultra-High Interrupting CapacityCatalogue Number

Thermal Magnetic Trip Unit OnlyFor Use with Standard or High or Ultra-High Interrupting Frame Adjustable ThermalAdjustableMagnetic

Standard Terminals Only Catalogue Number

MetricMountingHardwareCatalogueNumber

Ue Max. 690 VAC Ue Max. 690 VAC Ue Max. 690 VAC

40 kA Icu at 415 VAC 70 kA Icu at 415 VAC 100 kA Icu at 415 VAC

FactoryAssembledCircuit BreakerConsisting ofFrame, Trip Unit, and Terminals

Frame Only FactoryAssembledCircuit BreakerConsisting ofFrame, Trip Unit, and Terminals

Frame Only FactoryAssembledCircuit BreakerConsisting ofFrame, Trip Unit, and Terminals

Frame Only

Adjustable Thermal Magnetic Circuit Breakers with Interchangeable Trip UnitsType LW Type HLW Type LWC

315400500630

2-Pole LW2315LW2400LW2500LW2630

LW2630F HLW2315HLW2400HLW2500HLW2630

HLW2630F LWC2315LWC2400LWC2500LWC2630

LWC2630F LT2315TALT2400TALT2500TALT2630TA

TA602LDM①TA602LDM①TA602LDM①TA603LDKM➂

BMH4MBMH4MBMH4MBMH4M

315400500630

3-Pole LW3315LW3400LW3500LW3630

LW3630F HLW3315HLW3400HLW3500HLW3630

HLW3630F LWC3315LWC3400LWC3500LWC3630

LWC3630F LT3315TALT3400TALT3500TALT3630TA

TA602LDM①TA602LDM①TA602LDM①TA603LDKM➂

BMH4MBMH4MBMH4MBMH4M

315400500

630500630

4-Pole LW4315⑧LW4400⑧LW4500⑧

LW4630⑧LW4500➃LW4630➃

LW4630F HLW4315HLW4400HLW4500

HLW4630HLW4500E➃HLW4630E➃

HLW4630F LWC4315LWC4400LWC4500

LWC4630LWC4500E➃LWC4630E➃

LWC4630F LT4315TALT4400TALT4500TA

LT4630TALT4500TA➃LT4630TAE➃

TA602LDM①TA602LDM①TA602LDM①

TA603LDKM➂TA602LDM①TA603LDKM➂

BMH4MBMH4MBMH4M

BMH4MBMH4MBMH4M

Thermal Magnetic Fixed Thermal Circuit Breakers with Noninterchangeable Trip Units and Bus ExtensionTypes LW (Ue Max. 690 VAC, 50 kA lcu @ 415 VAC)

700800

3-Pole LW3700WLW3800W

– – – – – – – BMH4MBMH4M

Moulded Case Switches MCS Only without Line and Load Terminals

Type LW (690 VAC Max.) Type HLW (690 VAC Max.)

630 2-Pole3-Pole4-Pole

LW2630KWLW3630WKLW4630WK

– HLW2630KWHLW3630WKHLW4630WK

– – – – TA603LDKM➂TA603LDKM➂TA603LDKM➂

BMH4MBMH4MBMH4M

800 3-Pole4-Pole

LW3800WKLW4800WK

– – – – – – – BMH4MBMH4M

Series C Frame Size L, 315-800 Amperes

Electronic Circuit Breakers➅With Interchangeable Type KES Digitrip RMS Trip Units – Order as Individual Components: Breaker Frame, Trip Unit, Rating Plug, Terminals, Mounting Hardware

Maximum Continu-ous Ampere Rating at 40°C➀➁

Number of Poles

Circuit Breaker Frame OnlyCatalogue Number

Digitrip RMS 310 Trip Unit Only Less Rating PlugCatalogue Number

Digitrip RMS 310 Only Rating PlugOrder as Individual Component

Standard Terminals Only Catalogue Number

Metric Mounting Hardware Catalogue NumberStandard

InterruptingCapacity

HighInterruptingCapacity

Ultra-HighInterrupt-ingCapacity

L - Adjustable Long Delay Pickup (By Adjustable Rating Plug)

S - Adjustable Short Delay Pickup with Fixed Short Delay Time (I2t Response) or Adjustable Short Delay Time (Flat Response)

I - Adjustable Instantaneous Pickup by Setting Short Delay Time to Instantaneous

G - Adjustable Ground Fault Pickup with Adjustable Ground Fault Delay (Flat Response)

Fixed Rating Plug AdjustableRatingPlug

660 VAC Max. AmpereRating

CatalogueNumber

AmpereRatingCatalogueNumber

45 kA Icuat 415 VAC

70 kA Icuat 415 VAC

100 kA Icuat 415 VAC

Type LW Type HLW Type LWC LS LSI LSG LSIG

630 3-Pole➆ LW3630F HLW3630F LWC3630F LES3630LS LES3630LSI LES3630LSG LES3630LSIG 315350400500630

6LES315T6LES350T6LES400T6LES500T6LES630T

Adjustable Settings are:315/400/500/630A6LES630T2

TA602LDM①TA602LDM①TA602LDM①TA603LDKM①TA603LDKM➂

BMH4MBMH4MBMH4MBMH4MBMH4M

4-Pole➇ LW4630F HLW4630F LWC4630F LES4630LS LES6430LSI LES4630LSG LES4630LSIG 315350400500630

6LES315T6LES350T6LES400T6LES500T6LES630T

Adjustable Settings are:315/400/500/630A6LES630T2

TA602LDM①TA602LDM①TA602LDM①TA603LDKM①TA603LDKM➂

BMH4MBMH4MBMH4MBMH4MBMH4M

Electronic Circuit Breakers Includes Circuit Breaker Frame, Digitrip RMS 310 Electronic Trip Units with Noninterchangeable Adjustable Rating Plug and Bus Extension

800 3-Pole➆ LW3800T33WLW3800T35WLW3800T35XW

– – – – – – – – Adjustable Settings are:400/500/630/800A8LES800T1

– BMH4MBMH4MBMH4M

4-Pole➇ LW4800T33W – – – – – – – – – BMH4M

UK PG.29B.01.T.U A4 13-22 Page 20 Friday, March 12, 1999 3:56 PM

July 1998

PG.29B.01.T.U

Cutler-Hammer 21Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

Circuit Breaker Line Terminal Cover

TA401LD or TA603LD Terminal (Step-Type Terminal Requires Terminal Cover and Warning Label. See Inset.)

Pan-Head Screws and Lockwashers

TA450LD, TA602LD, or T602LD Terminal

Pan-Head Screws and Lockwashers (Installed before Cable Clamping Screws)

Selection Guide and Ordering Information

Line and Load Terminals

L-Frame circuit breakers include Cu/Al terminals as standard equip-ment. When optional copper termi-nals are required, order by catalogue number. 800 ampere L-Frame circuit breakers include bus extensions only.

MaximumBreakerAmperes

TerminalBodyMaterial

WireType

MetricWireRange mm2

AWG WireRange / No.Conductors

Catalogue Number

Standard Cu/Al Pressure Type Terminals

400 Aluminium Cu/AI 120-300 4/0-600 (1) 3TA401LDKM - 3-Pole Kit➁4TA401LDKM - 4-Pole Kit➁

450 Aluminium Cu/AI 25-95 (2) 4-4/0 (2) TA450LDM➀

500 Aluminium Cu/AI 120-150 250-350 (2) TA602LDM➀

600 Aluminium Cu/AI 185-240 (2) 400-500 (2) 3TA603LDKM - 3-Pole Kit➁4TA603LDKM - 4-Pole Kit➁

Optional Copper Pressure Type Terminals

600 Copper Copper 120-150 250-350 (2) T602LDM➀

➀ Individually packed.➁ Terminal kits contain one terminal for each

pole and one terminal cover.

Terminal Shields

Terminal shields provide protection against accidental contact with live line side terminations. Terminal shields are fabricated from high die-lectric insulating material and fasten over the front terminal access openings. Small openings in the shields provide limited access to the terminals for tightening connectors. (Field installation only.)

Handle Extension

Not included with breaker. Must be purchased separately.

Keeper Nut

Not required on L-Frame. Terminal is threaded.

Package of 2

Style Number – 314C420G01

Packaged Individually

Catalogue Number – HEX4

Base Mounting Hardware

Base mounting hardware is included with a circuit breaker or moulded case switch.

Interphase Barriers

The interphase barriers provide addi-tional electrical clearance between circuit breaker poles for special termi-nation applications. The barriers are high dielectric insulating plates that are installed in the moulded slots

Number of Poles

Description Type of Mounting

StyleNumber

Metric Thread

2, 3 0.250-20 x Individual 5103A09G01

Imperial Thread

2, 3, 4 0.250-20 x 1.5 Inch Filister-HeadSteel Screwsand Lock-washers andFlat Washers

Individual 21C6782G05

Kit Catalogue Number

Metric Imperial

KPEKM4 KPEK4

between the terminals. (Field instal-lation only.) Two per package.

Endcap Kit

Endcap kits are used on L-Frame breaker line load to connect bus bar or similar electrical connections. Includes hardware.

Package of 2

Catalogue Number – IPB4

Kit Catalogue Number

Metric Imperial

KPEKM4 KPEK4

Terminal Cover

Warning Label

Retainer

Screws

Series C Frame Size L, 315-800 Amperes

UK PG.29B.01.T.U A4 13-22 Page 21 Friday, March 12, 1999 3:56 PM

PG.29B.01.T.U

Cutler-Hammer22July 1998

Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

➀ For AC use only.➁ Special 50˚C rating available. Order by

description.➂ For 2-pole applications, use outer poles of

3-pole moulded case switch.

Selection Guide and Ordering Information

Maximum Continuous Ampere Rating at 40°C➀➁

Number of Poles

Circuit Breaker Frame Including Digitrip RMS 310 Electronic Trip Unit Less Rating Plugs Order as Individual Component – Catalogue Number

Digitrip RMS 310Interchangeable Rating PlugsOrder as Individual Component

L - Adjustable Long Delay Pickup (By Adjustable Rating Plug)S - Adjustable Short Delay Pickup with Fixed Short Delay Time

(I2t Response) or Adjustable Short Delay Time (Flat Response)I - Adjustable Instantaneous Pickup by Setting Short Delay Time to InstantaneousG -Adjustable Ground Fault Pickup with Adjustable Ground Fault Delay (Flat Response)

Fixed Rating Plug

Adjustable Rating Plug

Ampere Rating

CatalogueNumber

Ampere Rating Catalogue Number

LS LSI LSG LSIG

Short Time Range 2-8 x In 2-8 x In 2-8 x In 2-8 x InShort Time Delay – 0-300 ms – 0-300 msGround Fault Pickup – – 200-1200A 200-1200AGround Fault Delay – – 0-500 ms 0-500 ms

Type NW Standard Interrupting Capacity – Ue Max. 690 VAC, 50 kA lcu at 415 VAC800 2-Pole NW2800T33W NW2800T32W NW2800T35W NW2800T36W 400

450500550

600630700800

8NES400T8NES450T8NES500T8NES550T

8NES600T8NES630T8NES700T8NES800T

Adjustable Settings Are:

400/500/630/8008NES800T2

3-Pole NW3800T33W NW3800T32W NW3800T35W NW3800T36W 400450500550

600630700800

8NES400T8NES450T8NES500T8NES550T

8NES600T8NES630T8NES700T8NES800T

400/500/630/8008NES800T2

4-Pole NW4800T33W NW4800T32W – – 400450500550

600630700800

8NES400T8NES450T8NES500T8NES550T

8NES600T8NES630T8NES700T8NES800T

400/500/630/8008NES800T2

1250 2-Pole NW2125T33W NW2125T32W NW2125T35W NW2125T36W 600630700800

900100012001250

12NES600T12NES630T12NES700T12NES800T

12NES900T12NES1000T12NES1200T12NES1250T

630/800/1000/1250A12NES1250T2

3-Pole NW3125T33W NW3125T32W NW3125T35W NW3125T36W 600630700800

900100012001250

12NES600T12NES630T12NES700T12NES800T

12NES900T12NES1000T12NES1200T12NES1250T

630/800/1000/1250A12NES1250T2

4-Pole NW4125T33W NW4125T32W – – 600630700800

900100012001250

12NES600T12NES630T12NES700T12NES800T

12NES900T12NES1000T12NES1200T12NES1250T

630/800/1000/1250A12NES1250T2

Moulded Case Switches➂

Ampere Rating Number of Poles Ue Max. 690 VAC Catalogue Number

800 3-Pole4-Pole

NW3800WKNW4800WK

MCS Only withoutLine and Load

1250 3-Pole4-Pole

NW3125WKNW4125WK

MCS Only withoutLine and Load

800 3-Pole4-Pole

HNW3800WKHNW4800WK

MCS Only withoutLine and Load

1250 3-Pole4-Pole

HNW3125WKHNW4125WK

MCS Only withoutLine and Load

Series C Frame Size N, 400-1250 Amperes

UK PG.29B.01.T.U A4 13-22 Page 22 Friday, March 12, 1999 3:56 PM

July 1998

PG.29B.01.T.U

Cutler-Hammer

23Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

Selection Guide and Ordering Information

MaximumContinuousAmpereRating at 40

°

C

➀➁

NumberofPoles

Circuit Breaker Frame Including Digitrip RMS 310 Electronic Trip Unit Less Rating PlugsOrder as Individual Component – Catalogue Number

Digitrip RMS 310 Interchangeable Rating PlugsOrder as Individual Component

L - Adjustable Long Delay Pickup (By Adjustable Rating Plug)S - Adjustable Short Delay Pickup with Fixed Short Delay Time

(I

2

t Response) or Adjustable Short Delay Time (Flat Response)I - Adjustable Instantaneous Pickup by Setting Short Delay Time to InstantaneousG - Adjustable Ground Fault Pickup with Adjustable Ground Fault Delay (Flat Response)

Fixed Rating Plug Adjustable Rating Plug

AmpereRating

CatalogueNumber

Ampere RatingCatalogue Number

LS LSI LSG LSIG

Short Time Range 2-8 x I

n

2-8 x I

n

2-8 x I

n

2-8 x I

n

Short Time Delay – 0-300 ms – 0-300 ms

Ground Fault Pickup – – 200-1200A 200-1200A

Ground Fault Delay – – 0-500 ms 0-500 ms

Type NW Standard Interrupting Capacity – U

e

Max. 690 VAC, 50 kA I

cu

at 415 VAC

800 2-Pole NW2800T33W NW2800T32W NW2800T35W NW2800T36W 400450500550

600630700800

8NES400T8NES450T8NES500T8NES550T

8NES600T8NES630T 8NES700T8NES800T

Adjustable Settings Are:

400/500/630/8008NES800T2

3-Pole NW3800T33W NW3800T32W NW3800T35W NW3800T36W 400450500550

600630700800

8NES400T8NES450T8NES500T8NES550T

8NES600T8NES630T 8NES700T8NES800T

400/500/630/8008NES800T2

4-Pole NW4800T33W NW4800T32W – – 400450500550

600630700800

8NES400T8NES450T8NES500T8NES550T

8NES600T8NES630T 8NES700T8NES800T

400/500/630/8008NES800T2

1250 2-Pole NW2125T33W NW2125T32W NW2125T35W NW2125T36W 600630700800

900100012001250

12NES600T12NES630T 12NES700T12NES800T

12NES900T12NES1000T12NES1200T12NES1250T

630/800/1000/1250A12NES1250T2

3-Pole NW3125T33W NW3125T32W NW3125T35W NW3125T36W 600630700800

900100012001250

12NES600T12NES630T 12NES700T12NES800T

12NES900T12NES1000T12NES1200T12NES1250T

630/800/1000/1250A12NES1250T2

4-Pole NW4125T33W NW4125T32W – – 600630700800

900100012001250

12NES600T12NES630T 12NES700T12NES800T

12NES900T12NES1000T12NES1200T12NES1250T

630/800/1000/1250A12NES1250T2

For AC use only.

Special 50˚C rating available.Order by description.

Series C Frame Size N, 400-1250 Amperes

UK PG.29B.01.T.U A4 23-33 Page 23 Friday, March 12, 1999 3:57 PM

PG.29B.01.T.U

Cutler-Hammer

24

July 1998

Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

Selection Guide and Ordering Information

MaximumContinuousAmpereRating at 40

°

C

➀➁

NumberofPoles

Circuit Breaker Frame Including Digitrip RMS 310 Electronic Trip Unit Less Rating PlugsOrder as Individual Component – Catalogue Number

Digitrip RMS 310 Interchangeable Rating PlugsOrder as Individual Component

L - Adjustable Long Delay Pickup (By Adjustable Rating Plug)S - Adjustable Short Delay Pickup with Fixed Short Delay Time

(I

2

t Response) or Adjustable Short Delay Time (Flat Response)I - Adjustable Instantaneous Pickup by Setting Short Delay Time to InstantaneousG - Adjustable Ground Fault Pickup with Adjustable Ground Fault Delay (Flat Response)

Fixed Rating Plug Adjustable Rating Plug

AmpereRating

CatalogueNumber

Ampere RatingCatalogue Number

LS LSI LSG LSIG

Short Time Range 2-8 x I

n

2-8 x I

n

2-8 x I

n

2-8 x I

n

Short Time Delay – 0-300 ms – 0-300 ms

Ground Fault Pickup – – 200-1200A 200-1200A

Ground Fault Delay – – 0-500 ms 0-500 ms

Type NW Standard Interrupting Capacity – U

e

Max. 690 VAC, 50 kA I

cu

at 415 VAC

800 2-Pole NWC2800T33W NWC2800T32W NWC2800T35W NWC2800T36W 400450500550

600630700800

8NES400T8NES450T8NES500T8NES550T

8NES600T8NES630T 8NES700T8NES800T

Adjustable Settings Are:

400/500/630/8008NES800T2

3-Pole NWC3800T33W NWC3800T32W NWC3800T35W NWC3800T36W 400450500550

600630700800

8NES400T8NES450T8NES500T8NES550T

8NES600T8NES630T 8NES700T8NES800T

400/500/630/8008NES800T2

4-Pole NWC4800T33W NWC4800T32W – – 400450500550

600630700800

8NES400T8NES450T8NES500T8NES550T

8NES600T8NES630T 8NES700T8NES800T

400/500/630/8008NES800T2

1250 2-Pole NWC2125T33W NWC2125T32W NWC2125T35W NWC2125T36W 600630700800

900100012001250

12NES600T12NES630T 12NES700T12NES800T

12NES900T12NES1000T12NES1200T12NES1250T

630/800/1000/1250A12NES1250T2

3-Pole NWC3125T33W NWC3125T32W NWC3125T35W NWC3125T36W 600630700800

900100012001250

12NES600T12NES630T 12NES700T12NES800T

12NES900T12NES1000T12NES1200T12NES1250T

630/800/1000/1250A12NES1250T2

4-Pole NWC4125T33W NWC4125T32W – – 600630700800

900100012001250

12NES600T12NES630T 12NES700T12NES800T

12NES900T12NES1000T12NES1200T12NES1250T

630/800/1000/1250A12NES1250T2

For AC use only.

Special 50˚C rating available.Order by description.

Series C Frame Size N, 400-1250 Amperes

UK PG.29B.01.T.U A4 23-33 Page 24 Friday, March 12, 1999 3:57 PM

July 1998

PG.29B.01.T.U

Cutler-Hammer

25Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

MaximumBreakerAmperes

TerminalBodyMaterial

Wire Type Metric WireRange mm

2

AWG WireNumber ofConductors

CatalogueNumber

Standard Cu/Al Pressure-Type Terminals

1250 Aluminium Cu/Al 120-300 4/0-500 MCM (3) TA1200NB3M

Optional Copper and Cu/Al Pressure Type Terminals

1250 Copper Copper 95-185 3/0-400 MCM (4) T1200NB3M

Base Mounting Hardware

Base mounting hardware is included with a circuit breaker or moulded case switch.

Keeper Nut

Not required on N-Frame. Terminals are threaded.

Handle Extension

Included with breaker. Additional handle extensions are available.

Interphase Barriers

The interphase barriers provide additional electrical clearance between circuit breaker poles for special termination applications. Barriers are high dielectric insulat-ing plates that are installed in the Moulded slots between the termi-nals. (Field installation only.)

Line and Load Terminals

N-Frame circuit breakers includeCu/Al terminals as standard.When optional copper or Cu/Alterminals are required, order bycatalogue number.

Imperial Thread

Number ofPoles

Description CatalogueNumber

2-, 3-,and 4-pole

0.3125-18 x 1.25 InchPan-Head Steel Screwsand Lock Washers

BMH5M

Single Handle Extension

Catalogue Number – HEX5

Interphase Barriers

Catalogue Number – IPB5

Selection Guide and Ordering Information

Series C Frame Size N, 400-1250 Amperes

UK PG.29B.01.T.U A4 23-33 Page 25 Friday, March 12, 1999 3:57 PM

PG.29B.01.T.U

Cutler-Hammer

26

July 1998

Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

Selection Guide and Ordering Information

MaximumContinuousAmpereRating at 40

°

C

➀➁

NumberofPoles

Circuit Breaker Frame Including Digitrip RMS 310 Electronic Trip Unit Less Rating PlugsOrder as Individual Component – Catalogue Number

Digitrip RMS 310 Interchangeable Rating PlugsOrder as Individual Component

L - Adjustable Long Delay Pickup (By Adjustable Rating Plug)S - Adjustable Short Delay Pickup with Fixed Short Delay Time

(I

2

t Response) or Adjustable Short Delay Time (Flat Response)I - Adjustable Instantaneous Pickup by Setting Short Delay Time to InstantaneousG - Adjustable Ground Fault Pickup with Adjustable Ground Fault Delay (Flat Response)

Fixed Rating Plug Adjustable Rating Plug

AmpereRating

CatalogueNumber

Ampere RatingCatalogue Number

LS LSI LSG

LSIG

Short Time Range 2-8 x I

n

2-8 x I

n

2-8 x I

n

2-8 x I

n

Short Time Delay – 0-300 ms – 0-300 ms

Ground Fault Pickup – – 200-1200A 200-1200A

Ground Fault Delay – – 0-500 ms 0-500 ms

Type RW with Digitrip 310 Standard Interrupting Capacity – U

e

Max. 690 VAC, 70 kA I

cu

at 415 VAC

1600

3-Pole RW316T33W RW316T32W RW316T35W RW316T36W 800100012001250

140015001600

16RES08T16RES10T16RES12T16RES125T

16RES14T16RES15T16RES16T

Adjustable Settings Are:

800/1000/1200/1600A16RES16T1

800/1000/1250/1600A16RES16T2

2000 RW320T33W RW320T32W RW320T35W RW320T36W 100012001250

140016002000

20RES10T20RES12TA20RES125T

A20RES14TA20RES16TA20RES20T

1000/1200/1600/2000A20RES20T1

1000/1250/1600/2000A20RES20T2

2500 RW325T33W RW325T32W RW325T35W RW325T36W 12001250160020002500

25RES12T25RES125TA25RES16TA25RES20TA25RES25T

1200/1600/2000/2500A25RES25T1

1250/1600/2000/2500A25RES25T2

1600

4-Pole

RW416T33W RW416T32W – – 800100012001250

140015001600

16RES08T16RES10T16RES12T16RES125T

16RES14T16RES15T16RES16T

800/1000/1200/1600A16RES16T1

800/1000/1250/1600A16RES16T2

2000 RW420T33W RW420T32W – – 100012001250

140016002000

20RES10T20RES12TA20RES125T

A20RES14TA20RES16TA20RES20T

1000/1200/1600/2000A20RES20T1

1000/1250/1600/2000A20RES20T2

2500 RW425T33W RW425T32W – – 12001250160020002500

25RES12T25RES125TA25RES16TA25RES20TA25RES25T

1200/1600/2000/2500A25RES25T1

1250/1600/2000/2500A25RES25T2

For SCR application, use 2000A frame.

Special 50˚C rating available.Order by description.

Unprotected left pole neutral. Add “P” tocatalogue number for 100% protected left pole neutral, add “E” for 60% protected, i.e., “RW416T33PW”, “RW416T33EW”.

Ground fault equipped trip units available with remote indicating panel. Add “R” tocatalogue number, i.e., “RW316T35RW”.

Series C Frame Size R, 800-2500 Amperes

UK PG.29B.01.T.U A4 23-33 Page 26 Friday, March 12, 1999 3:57 PM

July 1998

PG.29B.01.T.U

Cutler-Hammer

27Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

For SCR application, use 2000A frame.

Special 50˚C rating available.Order by description.

Unprotected left pole neutral. Add “P” to catalogue number for 100% protected left pole neutral, add “E” for 60% protected, i.e., “RW416T33PW”, “RW416T33EW”.

Ground fault equipped trip units available with remote indicating panel. Add “R” to catalogue number, i.e., “RW316T35RW”.

Selection Guide and Ordering Information

MaximumContinuousAmpereRating at 40

°

C

➀➁

NumberofPoles

Circuit Breaker Frame Including Digitrip RMS 310 Electronic Trip Unit Less Rating PlugsOrder as Individual Component – Catalogue Number

Digitrip RMS 310 Interchangeable Rating PlugsOrder as Individual Component

L - Adjustable Long Delay Pickup (By Adjustable Rating Plug)S - Adjustable Short Delay Pickup with Fixed Short Delay Time

(I

2

t Response) or Adjustable Short Delay Time (Flat Response)I - Adjustable Instantaneous Pickup by Setting Short Delay Time to InstantaneousG - Adjustable Ground Fault Pickup with Adjustable Ground Fault Delay (Flat Response)

Fixed Rating Plug Adjustable Rating Plug

AmpereRating

CatalogueNumber

Ampere RatingCatalogue Number

LS LSI LSG

LSIG

Short Time Range 2-8 x I

n

2-8 x I

n

2-8 x I

n

2-8 x I

n

Short Time Delay – 0-300 ms – 0-300 ms

Ground Fault Pickup – – 200-1200A 200-1200A

Ground Fault Delay – – 0-500 ms 0-500 ms

Type RWC with Digitrip 310 High Interrupting Capacity – U

e

Max. 690 VAC, 100 kA I

cu

at 415 VAC

1600

3-Pole RWC316T33W RWC316T32W RWC316T35W RWC316T36W 800100012001250

140015001600

16RES08T16RES10T16RES12T16RES125T

16RES14T16RES15T16RES16T

Adjustable Settings Are:

800/1000/1200/1600A16RES16T1

800/1000/1250/1600A16RES16T2

2000 RWC320T33W RWC320T32W RWC320T35W RWC320T36W 100012001250

140016002000

20RES10T20RES12TA20RES125T

A20RES14TA20RES16TA20RES20T

1000/1200/1600/2000A20RES20T1

1000/1250/1600/2000A20RES20T2

1600

4-Pole

RWC416T33W RWC416T32W – – 800100012001250

140015001600

16RES08T16RES10T16RES12T16RES125T

16RES14T16RES15T16RES16T

800/1000/1200/1600A16RES16T1

800/1000/1250/1600A16RES16T2

2000 RWC420T33W RWC420T32W – – 100012001250

140016002000

20RES10T20RES12TA20RES125T

A20RES14TA20RES16TA20RES20T

1000/1200/1600/2000A20RES20T1

1000/1250/1600/2000A20RES20T2

Moulded Case Switches

1600A2000A

3-Pole RW316WKRW320WK

1600A2000A

4-Pole RW416WKRW420WK

Series C Frame Size R, 800-2500 Amperes

UK PG.29B.01.T.U A4 23-33 Page 27 Friday, March 12, 1999 3:57 PM

PG.29B.01.T.U

Cutler-Hammer

28

July 1998

Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

Selection Guide and Ordering Information

MaximumContinuousAmpereRating at 40

°

C

➀➁

NumberofPoles

Circuit Breaker Frame Including Digitrip RMS 510 and 610 Electronic Trip Unit Less Rating PlugsOrder as Individual Component – Catalogue Number

Digitrip RMS InterchangeableRating PlugOrder as Individual Component

L - Adjustable Long Delay Pickup (I

r

) with Adjustable Long Delay TimeS - Adjustable Short Delay Pickup with Adjustable Short Delay Time (I

2

t or Flat Response)I - Adjustable Instantaneous PickupG - Adjustable Ground Fault Pickup with Adjustable Ground Fault Time Delay (I

2

t or Flat Response)

Fixed Rating Plug

AmpereRating

CatalogueNumber

LI LS LSI LIG LSG LSIG

Long Delay Pickup 0.5-1.0 x I

n

0.5-1.0 x I

n

0.5-1.0 x I

n

0.5-1.0 x I

n

0.5-1.0 x I

n

0.5-1.0 x I

n

Long Delay Time 2-24 Seconds 2-24 Seconds 2-24 Seconds 2-24 Seconds 2-24 Seconds 2-24 Seconds

Short Time Range 2-6 x I

r

2-6 x I

r

2-6 x I

r

2-6 x I

r

2-6 x I

r

2-6 x I

r

Short Time Delay – 100-500 ms 100-500 ms – 100-500 ms 100-500 ms

Instantaneous 2-6 x M1 & M2 – 2-6 x M1 & M2 2-6 x M1 & M2 – 2-6 x M1 & M2

Ground Fault Pickup – – – 0.25-1.0 x In

0.25-1.0 x In

0.25-1.0 x In

Ground Fault Delay – – – 100-500 ms 100-500 ms 100-500 ms

Type RW with Digitrip 510 Standard Interrupting Capacity – U

e

Max. 690 VAC, 70 kA I

cu

at 415 VAC

1600 3-Pole RW316T51W RW316T53W RW316T52W RW316T54W RW316T55W RW316T56W 8001000120012501600

RP6R16A080RP6R16A100RP6R16A120RP6R16A125RP6R16A160

2000 RW320T51W RW320T53W RW320T52W RW320T54W RW320T55W RW320T56W 10001200125016002000

RP6R20A100RP6R20A120RP6R20A125RP6R20A160RP6R20A200

2500 RW325T51W RW325T53W RW325T52W RW325T54W RW325T55W RW325T56W 160020002500

RP6R25A160RP6R25A200RP6R25A250

Type RWC with Digitrip 510 High Interrupting Capacity – U

e

Max. 690 VAC, 100 kA I

cu

at 415 VAC

1600 3-Pole RWC316T51W RWC316T53W RWC316T52W RWC316T54W RWC316T55W RWC316T56W 8001000120012501600

RP6R16A080RP6R16A100RP6R16A120RP6R16A125RP6R16A160

2000 RWC320T51W RWC320T53W RWC320T52W RWC320T54W RWC320T55W RWC320T56W 10001200125016002000

RP6R20A100RP6R20A120RP6R20A125RP6R20A160RP6R20A200

Type RW with Digitrip 610 Standard Interrupting Capacity – U

e

Max. 690 VAC, 70 kA I

cu

at 415 VAC

1600 3-Pole RW316T61W RW316T63W RW316T62W RW316T64W RW316T65W RW316T66W 8001000120012501600

RP6R16A080RP6R16A100RP6R16A120RP6R16A125RP6R16A160

2000 RW320T61W RW320T63W RW320T62W RW320T64W RW320T65W RW320T66W 10001200125016002000

RP6R20A100RP6R20A120RP6R20A125RP6R20A160RP6R20A200

2500 RW325T61W RW325T63W RW325T62W RW325T64W RW325T65W RW325T66W 160020002500

RP6R25A160RP6R25A200RP6R25A250

Type RWC with Digitrip 610 High Interrupting Capacity – U

e

Max. 690 VAC, 100 kA I

cu

at 415 VAC

1600 3-Pole RWC316T61W RWC316T63W RWC316T62W RWC316T64W RWC316T65W RWC316T66W 8001000120012501600

RP6R16A080RP6R16A100RP6R16A120RP6R16A125RP6R16A160

2000 RWC320T61W RWC320T63W RWC320T62W RWC320T64W RWC320T65W RWC320T66W 10001200125016002000

RP6R20A100RP6R20A120RP6R20A125RP6R20A160RP6R20A200

Not to exceed 1200A.

Special 50˚C rating available.Order by description.

Series C Frame Size R, 800-1250 Amperes

UK PG.29B.01.T.U A4 23-33 Page 28 Friday, March 12, 1999 3:57 PM

July 1998

PG.29B.01.T.U

Cutler-Hammer

29Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

Selection Guide and Ordering Information

MaximumContinuousAmpereRating at 40

°

C

➀➁

NumberofPoles

Circuit Breaker Frame Including Digitrip RMS 510 and 610 Electronic Trip Unit Less Rating PlugsOrder as Individual Component – Catalogue Number

Digitrip RMS InterchangeableRating PlugOrder as Individual Component

L - Adjustable Long Delay Pickup (I

r

) with Adjustable Long Delay TimeS - Adjustable Short Delay Pickup with Adjustable Short Delay Time (I

2

t or Flat Response)I - Adjustable Instantaneous PickupG - Adjustable Ground Fault Pickup with Adjustable Ground Fault Time Delay (I

2

t or Flat Response)

Fixed Rating Plug

AmpereRating

CatalogueNumber

LI LS LSI LIG LSG LSIG

Long Delay Pickup 0.5-1.0 x I

n

0.5-1.0 x I

n

0.5-1.0 x I

n

0.5-1.0 x I

n

0.5-1.0 x I

n

0.5-1.0 x I

n

Long Delay Time 2-24 Seconds 2-24 Seconds 2-24 Seconds 2-24 Seconds 2-24 Seconds 2-24 Seconds

Short Time Range 2-6 x I

r

2-6 x I

r

2-6 x I

r

2-6 x I

r

2-6 x I

r

2-6 x I

r

Short Time Delay – 100-500 ms 100-500 ms – 100-500 ms 100-500 ms

Instantaneous 2-6 x M1 & M2 – 2-6 x M1 & M2 2-6 x M1 & M2 – 2-6 x M1 & M2

Ground Fault Pickup – – – 0.25-1.0 x In

0.25-1.0 x In

0.25-1.0 x In

Ground Fault Delay – – – 100-500 ms 100-500 ms 100-500 ms

Type RW with Digitrip 810 Standard Interrupting Capacity – U

e

Max. 690 VAC, 70 kA I

cu

at 415 VAC

1600 3-Pole RW316T81W RW316T83W RW316T82W RW316T84W RW316T85W RW316T86W 8001000120012501600

RP6R16A080RP6R16A100RP6R16A120RP6R16A125RP6R16A160

2000 RW320T81W RW320T83W RW320T82W RW320T84W RW320T85W RW320T86W 10001200125016002000

RP6R20A100RP6R20A120RP6R20A125RP6R20A160RP6R20A200

2500 RW325T81W RW325T83W RW325T82W RW325T84W RW325T85W RW325T86W 160020002500

RP6R25A160RP6R25A200RP6R25A250

Type RWC with Digitrip 810 High Interrupting Capacity – U

e

Max. 690 VAC, 100 kA I

cu

at 415 VAC

1600 3-Pole RWC316T81W RWC316T83W RWC316T82W RWC316T84W RWC316T85W RWC316T86W 8001000120012501600

RP6R16A080RP6R16A100RP6R16A120RP6R16A125RP6R16A160

2000 RWC320T81W RWC320T83W RWC320T82W RWC320T84W RWC320T85W RWC320T86W 10001200125016002000

RP6R20A100RP6R20A120RP6R20A125RP6R20A160RP6R20A200

Type RW with Digitrip 910 Standard Interrupting Capacity – U

e

Max. 690 VAC, 70 kA I

cu

at 415 VAC

1600 3-Pole RW316T91W RW316T93W RW316T92W RW316T94W RW316T95W RW316T96W 8001000120012501600

RP6R16A080RP6R16A100RP6R16A120RP6R16A125RP6R16A160

2000 RW320T91W RW320T93W RW320T92W RW320T94W RW320T95W RW320T96W 10001200125016002000

RP6R20A100RP6R20A120RP6R20A125RP6R20A160RP6R20A200

2500 RW325T91W RW325T93W RW325T92W RW325T94W RW325T95W RW325T96W 160020002500

RP6R25A160RP6R25A200RP6R25A250

Type RWC with Digitrip 910 High Interrupting Capacity – U

e

Max. 690 VAC, 100 kA I

cu

at 415 VAC

1600 3-Pole RWC316T91W RWC316T93W RWC316T92W RWC316T94W RWC316T95W RWC316T96W 8001000120012501600

RP6R16A080RP6R16A100RP6R16A120RP6R16A125RP6R16A160

2000 RWC320T91W RWC320T93W RWC320T92W RWC320T94W RWC320T95W RWC320T96W 10001200125016002000

RP6R20A100RP6R20A120RP6R20A125RP6R20A160RP6R20A200

Not to exceed 1200A.

Special 50˚C rating available.Order by description.

Series C Frame Size R, 800-2500 Amperes

UK PG.29B.01.T.U A4 23-33 Page 29 Friday, March 12, 1999 3:57 PM

PG.29B.01.T.U

Cutler-Hammer

30

July 1998

Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

Conductor(Viewed from Frontof Circuit Breaker)

Conductor(Viewed from Rearof Circuit Breaker and Cut Away for Clarity)

Rear Connector (Cu)B2016RDB2016RDL (For 100% Application)(For 1600A and 2000A Frames)

SecuringHardware

Securing Hardware

Cu OnlyTerminalCatalogue NumberT1600RD(For 1600AFrame Only)

Al/CuTerminalCatalogue NumberTA1600RD(For 1600AFrame Only)

OR

Line and Load Terminals

MaximumBreakerAmperes

TerminalBodyMaterial

CatalogueNumber

Rear Connectors

200020002500

CopperCopperCopper

B2016RDMB2016RDLMB2500RDM

Line and Load Terminals

R-Frame circuit breakers have Cu/Al terminals as standard and copper only terminals as an option. Specify if factory installation is required.

For use with 2500A frame. Do not orderseparately unless for replacement purposes. Included in breaker carton when 2500A breaker is ordered.

Base Mounting Hardware

Supplied by customer.

Single Handle Extension

Catalogue Number – HEX6

Handle Extension

Included with breaker. Additional handle extensions are available.

Selection Guide and Ordering Information

RD Rear Connector Exploded View

Series C Frame Size R, 800-2500 Amperes

UK PG.29B.01.T.U A4 23-33 Page 30 Friday, March 12, 1999 3:57 PM

July 1998

PG.29B.01.T.U

Cutler-Hammer

31Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

Selection Guide and Ordering Information

Combination ratings with Cutler-Hammer Freedom® / ADVANTAGE® Control, contact Cutler-Hammer.

Circuit Breakers for Motor Protection

BreakerType

RatedCurrent I

n

Rated Output of 3-Phase Motors

to Be Protectedat 50 Hz

SettingCurrent ofInverse-TimeOverloadRelease I

r

InstantaneousShort CircuitRelease I

i

Trip ClassT

c

Standard SwitchingCapacityCatalogueNumber

High SwitchingCapacityCatalogueNumber

380/415VMax. kW

500VMax. kW

Without Adjustment of the Trip Class, without Phase Unbalance Detection

35 kA at 380/415 VAC 65 kA at 380/415 VAC

FWMPFWMPFWMPFWMP

80100160205

374575

110

5555

110132

40-8080-100

100-160160-205

15 x Ir15 x Ir15 x Ir13 x Ir

10101010

FWMP3080LFWMP3100LFWMP3160LFWMP3205L

HFWMP3080LHFWMP3100LHFWMP3160LHFWMP3205L

40 kA at 380/415 VAC

KWMPLWMP

315500

160250

200355

160-315250-500

15 x Ir15 x Ir

2020

KWMP3315WLWMP3500W

HKWMP3315WHLWMP3500W

With Adjustment of the Trip Class, with Phase Unbalance Detection

35 kA at 380/415 VAC 65 kA at 380/415 VAC

FWMP-JFWMP-JFWMP-JFWMP-J

80100160205

374575

110

5555

110132

40-8080-100

100-160160-205

15 x Ir15 x Ir15 x Ir13 x Ir

5/10/15/205/10/15/205/10/15/20

10

FWMP3080JLFWMP3100JLFWMP3160JLFWMP3205JL

HFWMP3080JLHFWMP3100JLHFWMP3160JLHFWMP3205JL

40 kA at 380/415 VAC

KWMP-JLWMP-J

315500

160250

200355

160-315250-500

15 x Ir15 x Ir

10/15/20/3020

KWMP3315JWLWMP3500JW

HKWMP3315JWHLWMP3500JW

Motor Circuit Protectors for Combination Starters

35 kA at 380/415 VAC 65 kA at 380/415 VAC➀

HMCPHMCPHMCPHMCPHMCP

HMCPHMCPHMCPHMCPHMCP

HMCPHMCP

Up to 63Up to 100Up to 150Up to 125Up to 160

Up to 200Up to 200Up to 250Up to 315Up to 315

Up to 400Up to 500

3045755575

9090

110160160

200250

3755

11075

110

132132160200200

250355

–––––

–––––

––

300-1000450-1500750-2500

1000-20001125-2250

1250-25001500-30001750-35002000-40001800-6000

1800-60001800-6000

–––––

–––––

––

–––––

–––––

––

HMCP100R3CHMCP150T4CHMCP150U4CHMCP250K5HMCP250L5

HMCP250W5HMCP400N5HMCP400R5HMCP400X5HMCP600L6W

HMCP600L6WHMCP600L6W

Motor Circuit Protectors

UK PG.29B.01.T.U A4 23-33 Page 31 Friday, March 12, 1999 3:57 PM

PG.29B.01.T.U

Cutler-Hammer32July 1998

Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

Accessory Fit Type Frame

G F J K L N R

External Accessory Catalogue Numbers

Non-PadlockableHandle Block

Field Fitted 1294C01H01 LKD1 LKD3 LKD3 LKD4 LKD4 –

PadlockableHandle Block

Field Fitted – – – – – – –

Field Fitted 223C77G03 – PHB3 PHB3 – – HLK6

PadlockableHandle Lock Hasp

Field Fitted – PHL1 PLK3 PLK3 HLK4 PLK5 –

Cylinder Lock Factory Fitted Order by Description

Key Interlock Kit(Provision Only)

Field Fitted – KYK1 KYK3 KYK3 KYK4 KYK4 KYK6

Slide Bar Interlock –Requires 2 Breakers

Field Fitted – SBK1 SBK2 SBK3 SBK4 SBK5 –

Walking Beam Interlock –Requires 2 Breakers

Factory Fitted Order by Description

Electrical Operator 120 VAC – E0P1P07 E0P2T07 E0P3T07 E0P4T07 E0P5T07 E0P6T08

240 VAC – E0P1P11 E0P2T11 E0P3T11 E0P4T11 E0P5T11 E0P6T11

120 VDC – E0P1P07DC E0P2T07DC E0P3T07DC E0P4T26 – –

240 VDC – E0P1P11DC E0P2T11DC E0P3T11DC – – –

48 VDC – - – – – E0P5T22 E0P6T21

125 VDC – – – – E0P4T21 E0P5T26 –

Plug-In Adapters➁ Field Fitted – ✓ ✓ ✓ ✓ ✓ –

Rear Connecting Studs➁ Field Fitted – ✓ ✓ ✓ ✓ ✓ –

Handle MechanismField Fitted Only➁

Flex Shaft – ✓ ✓ ✓ ✓ ✓ ✓

Type SM – ✓ ✓ ✓ ✓ – –

Series C Rotary

✓ ✓ ✓ ✓ ✓ ✓ –

Type MC – ✓ ✓ ✓ ✓ – –

Slide Plate – ✓ ✓ ✓ ✓ ✓ ✓

Test Kit

Electronic Portable Test Kit(Digitrip 310 Only)

– – – STK2 STK2 STK2 STK2

Special Calibration

Special non-UL listed calibrations are available for certain ambient temperatures other than 40˚C and for frequencies other than 50/60 Hz or dc. Reduced interrupting ratings will apply for 400 Hz applications.

Selection Guide and Ordering Information

50˚C Calibration➀

Add suffix “V” to catalogue number for complete breaker when ordering listed ampere ratings for breakers to be used in 50˚C ambients.

Contact Cutler-Hammer for availability.

Moisture-Fungus Treatment

All Series C Circuit Breaker cases are moulded from glass-polyester which does not support the growth of fun-gus. Any parts which are susceptible to the growth of fungus will require special treatment.

Order by description.

Accessory Frame

G F J K L N R

Special Calibration ✓ ✓ ✓ ✓ ✓ ✓ ✓

Moisture-Fungus Treatment ✓ ✓ ✓ ✓ ✓ ✓ ✓

➀ K-, L-, N- and R-Frame breakers equipped with electronic trip units can operate reliably in ambient temperatures of 50˚C.

➁ Contact Cutler-Hammer for cataloguenumbers.

Series C Frame Sizes G through R

UK PG.29B.01.T.U A4 23-33 Page 32 Friday, March 12, 1999 3:57 PM

July 1998

PG.29B.01.T.U

Cutler-Hammer 33Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

Accessory PoleLocation

Frame

G F J K L N R

Field Fit Kit Catalogue Numbers

Alarm Lockout Make/Break Left – A1L1LPK A1L2LPK A1L3LPK A1L4LPK A1L5LPK –

Right Factory Fit Only A1L1RPK A1L2RPK A1L3RPK A1L4RPK A1L5RPK A1L6RPK

2 Make/2 Break Left – A2L1LPK – A2L3LPK A2L4LPK A2L5LPK –

Right – A2L1RPK – A2L3RPK A2L4RPK A2L5RPK A2L6RPK

Auxiliary Switch 1A, 1B Left – A1X1PK A1X2PK A1X3PK A1X4PK A1X5LPK –

Right Factory Fit Only A1X1PK A1X2PK A1X3PK A1X4PK A1X5RP –

2A, 2B Left – A2X1LPK A2X2PK A2X3PK A2X4PK A2X5LPK –

Right Factory Fit Only A2X1RPK A2X2PK A2X3PK A2X4PK A2X5RPK A2X6RPK

3A, 3B Left – – – A3X3LPK A3X4PK A3X5LPK –

Right – – – A3X3RPK A3X4PK A3X5RPK –

Auxiliary Switch /Alarm Lockout

Left – AAL1LPK AAL2LPK AAL3LPK AA114LPK AA115LPK –

Right – AAL1RPK AAL2RPK AAL3RPK AA114RPK AA115RPK –

Shunt Trip –Standard➀

120 VAC Left Factory Fit Only SNT1LP08K SNT2P11K SNT3P11K SNT4LP11K SNT5LP11K –

Right – SNT1RP08K SNT2P11K SNT3P11K SNT4RP11K – SNT6P11K

240 VAC Left Factory Fit Only SNT1LP12K SNT2P11K SNT3P11K SNT4LP11K SNT5LP11K –

Right – SNT1RP12K SNT2P11K SNT3P11K SNT4RP11K – SNT6P11K

24 VDC Left Factory Fit Only SNT1LP03K SNT2P04K SNT3P04K SNT4LP03K SNT5LP03K –

Right – SNT1RP03K SNT2P04K SNT3P04K SNT4RP03K – SNT6P03K

48 VDC Left – SNT1LP08K SNT2P06K SNT3P06K SNT4LP23K SNT5LP23K –

Right – SNT1RP08K SNT2P06K SNT3P06K SNT4RP23K – SNT6P23K

Shunt Trip –Low Energy

Left – LST1LPK LST2LPK LST3LPK LST4LPK LST5LPK –

Right – LST1RPK LST2RPK LST3RPK LST4RPK – LST6RPK

UndervoltageReleaseMechanism➀

120 VAC Left Factory Fit Only UVH1LP08K UVH2LP08K UVH3LP08K UVH4LP08K UVH5LP08K –

Right – UVH1RP08K UVH2RP08K UVH3RP08K UVH4RP08K – UVH6RP08K

240 VAC Left Factory Fit Only UVH1LP11K UVH2LP11K UVH3LP11K UVH4LP11K UVH5LP11K –

Right – UVH1RP11K UVH2RP11K UVH3RP11K UVH4RP11R – UVH6RP11K

24 VDC Left – UVH1LP21K UVH2LP21K UVH3LP21K UVH4LP21K UVH5LP21K –

Right – UVH1RP21K UVH2RP21K UVH3RP21K UVH4RP21K – UVH6RP21K

48 VDC Left – UVH1LP23K UVH2LP23K UVH3LP23K UVH4LP23K UVH5LP23K –

Right – UVH1RP23K UVH2RP23K UVH3RP23K UVH4RP23K – UVH6RP23K

a

b

UV

Make

Break

Selection Guide and Ordering Information

➀ Shunt trip and undervoltage release can only be mounted in left pole of K- and L-Frame breakers equipped with electronic trip units.

ST

c

Series C Frame Sizes G through R

UK PG.29B.01.T.U A4 23-33 Page 33 Friday, March 12, 1999 3:57 PM

PG.29B.01.T.U

Cutler-Hammer

34

July 1998

Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

Selection Guide and Ordering Information

The Cutler-Hammer general purpose rotary handle mechanisms are suita-ble for use with NEMA 1, 3R, 4 and 12 fabricated enclosures. They are designed for use with Series C Circuit Breakers, Moulded Case Switches, and Motor Circuit Protec-tors (MCP).

Required for a standard application are the operating handle, shaft, and mechanism.

It may be mounted in either the hori-zontal or the vertical direction. The handle was ergonomically designed with extra clearance for “gloved hand” to operate. It may be pad-locked in the OFF position utilizing three padlocks. The handle is cast metal only.

The standard label on the operating handle indicates ON/Tripped/OFF/Reset.

The Flex Shaft type handle mecha-nism is an extra heavy-duty handle mechanism designed for mounting in flange-type enclosures. An oper-ating handle, flexible shaft, and mechanism are required for stand-ard application.

The handle can be locked in the RESET position with up to three padlocks. The handle is suitable for NEMA 1, 3R, 4, 4X, and 12 fabricated enclosures. It is supplied for mount-ing in right-hand flange enclosures. The handle fits the industry standard cutout.

Eight lengths of shafts are available for use with the wide range of depths of various enclosures (3-feet through 10-feet). These choices ena-ble this mechanism to be mounted in various depth, width, and height enclosures. Note: when selecting the length of shaft, ensure minimum bending radius of 4-inches is main-tained to operate properly.

Series C Rotary Handle Mechanism

Series C Frame Sizes F through N

Flex Shaft™ Handle Mechanism

Series C Rotary Handle Mechanisms

Breaker Frame Shaft Length (mm) Complete Catalog Number

IEC IP65

➀➁

IEC IP66

➀➁

Series C F-Frame 152.4304.8406.4609.6

WHM1R06WHM1R12WHM1R16WHM1R24

WHM1R06XWHM1R12XWHM1R16XWHM1R24X

Series C J-Frame 152.4304.8406.4609.6

WHM2R06WHM2R12WHM2R16WHM2R24

WHM2R06XWHM2R12XWHM2R16XWHM2R24X

Series C K-Frame 152.4304.8406.4609.6

WHM3R06WHM3R12WHM3R16WHM3R24

WHM3R06XWHM3R12XWHM3R16XWHM3R24X

Series C L-Frame 152.4304.8406.4609.6

WHM4R06WHM4R12WHM4R16WHM4R24

WHM4R06XWHM4R12XWHM4R16XWHM4R24X

Series C N-Frame 152.4304.8406.4609.6

WHM5R06WHM5R12WHM5R16WHM5R24

WHM5R06XWHM5R12XWHM5R16XWHM5R24X

The standard method of shipment includes the mechanism preset at the factory; however, minor field adjustments may be required.

Refer to Cutler-Hammer for availability.

Standard Label on the IEC operating handle indicates (I)/Tripped/(O)/Reset.

IEC Handle Mechanism supplied with Metric thread mounting hardware.

Complete Catalog Number includes a handle, mechanism and shaft.

UK PG.29B.01.T.U A4 34-42 Page 34 Friday, March 12, 1999 3:58 PM

July 1998

PG.29B.01.T.U

Cutler-Hammer

35Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

2 AS

2 AS

1 AS

F-Frame for Motor Protection

4 AUX 4 AUX 4 AUX 4 AUX 4 AUX 4 AUX

U< DI

U< DI

U< DI

U< DI

U< DI

U< DI

U< DI

U< DI

U< DI

1 AUX

2 AUX

1 AS

1 AS + 1 AUX

2 AS

U< 2AS 2AS 2AS U< 2AS 2AS 2AS

2 AS

2 AS

1 AS

U< DI

1 AUX

2 AUX

1 AS

1 AS + 1 AUX

1 AUX

2 AUX

2 AUX

1 AUX

2 AUX

1 AUX

1 AUX

2 AUX

2 AUX

3-PoleCircuitBreakers

4-PoleCircuitBreakersleft right left right

1 AS

1 AS

AUX

= Shunt Trip or Undervoltage Release or DI Module (if Built-In)

= Auxiliary Switch

AS = Alarm Switch

= For R-Frame Circuit Breakers Only

Remote Controlled Operating

Mechanisms

Series C Circuit Breakers (sizes 160 to 2000 amperes) can be equipped with motorized operating mecha-nisms for remote in-service closing and opening.

For normal remote opening, sole-noid operating mechanisms F- and K-Frames are available for circuit breakers and motorized operating mechanisms for J to R (sizes 250 to 2500 amperes) solenoid operating mechanisms and motor operators are always supplied with a locking device for padlocks. This device can be used for electrical and mechanical blocking of the operating mecha-nism. All remote operating mecha-nisms are equipped with a manual actuator for local operation.

Alarm Lockout

The alarm switches operate when the circuit breaker is tripped by a short circuit or overcurrent, but also when it is tripped by a shunt trip or undervoltage release.

Auxiliary Switches

Auxiliary switches are used for sig-nalling and control purposes. The various functions of the auxiliary switches (changeover) are shown in the top table to the right.

Shunt Trips

The shunt trip is used for remote tripping.

The coil of the shunt trip is rated only for short-time operation.

It is not permissible with the circuit breaker open to apply a continuous opening command to the shunt trip in order to prevent the breaker from closing.

This means that interlocking circuits with continuous commands may not be set up with shunt trips.

Undervoltage Releases

The circuit breaker cannot be closed until the undervoltage release is energized. If the release is not ener-gized, the circuit breaker can only perform an idle switching operation.

Frequent idle switching actions should be avoided as they shorten the endurance of the circuit breaker.

Possible Equipment of F- and L-Frame Circuit Breakers with Auxiliary and Alarm Switches

Selection Guide and Ordering Information

Contact making by the auxiliary and alarm switches as a function of the switching position of the circuit breaker

OFFRESET

ON

Tripped

Position of theToggle Handle Drive(EquivalentlyApplicable forRotary Drives)

Position of the AuxiliarySwitch

Position of the AlarmSwitch

Series C Frame Sizes G through R

UK PG.29B.01.T.U A4 34-42 Page 35 Friday, March 12, 1999 3:58 PM

PG.29B.01.T.U

Cutler-Hammer

36

July 1998

Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

100 2 4 6 8 101 2 4 6 8 102 2 4 6 8 103

10000

500030002000

1000

500300200

100

503020

10

532

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIM

E I

N S

EC

ON

DS

CURRENT IN MULTIPLES OF In

(660/690V)

(n)

10XIn

(a)

(380/415V)

(220/240V)

5XIn

Notes:

“a” thermal overload release

“n” instantaneous (electromagnetic) short circuit release

100 2 4 6 8 101 2 4 6 8 102 2 4 6 8 103

10000

500030002000

1000

500300200

100

503020

10

532

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIM

E I

N S

EC

ON

DS

CURRENT IN MULTIPLES OF In

(660/690V)

(n)

10XIn

(a)

(380/415V)

(220/240V)

5XIn

Notes:

“a” thermal overload release

“n” instantaneous (electromagnetic) short circuit release

100 2 4 6 8 101 2 4 6 8 102 2 4 6 8 103

10000

500030002000

1000

500300200

100

503020

10

532

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIM

E I

N S

EC

ON

DS

CURRENT IN MULTIPLES OF In

(660/690V)

(n)

10XIn

(a)

(380/415V)

(220/240V)

5XIn

Notes:

“a” thermal overload release

“n” instantaneous (electromagnetic) short circuit release

102 2 4 6 8 103 2 4 6 8 10 4 2 4 6 8 10 5

10000

500030002000

1000

500300200

100

503020

10

532

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIM

E I

N S

EC

ON

DS

CURRENT IN MULTIPLES OF In

Two Poles in SeriesFor IEC Use Only

MinimumTripTime

MaximumTripTime

(n)

(a)

Notes:

“a” thermal overload release

“n” instantaneous (electromagnetic) short circuit release

Time-Current Curves

Tripping Characteristics

The operating values specified for the inverse time overcurrent releases (thermal overload releases, “a” releases) are mean values of the scatter bands of all setting ranges from the cold state and with uniform current loading of the conducting paths.

The tripping characteristics of the instantaneous (electromagnetic) short circuit releases (“n” releases) are based on the rated phase current I

n

which in the case of circuit break-ers with adjustable thermal overload releases is also the upper value of the setting range. With a lower set-ting current, a correspondingly higher multiple is obtained for the operating current of the “n” release.

Individual time-current curves K- and L-Frame Digitrip 310 Elec-tronic Trip Curves are available upon request.

Type GWF

Tripping characteristics of GWF circuit breakers for plant protection, I

cu

= 25 kA, “n” release fixed settingn = 500-1300 for breaker 16-63A; 1300-1800 for breaker 70-100A

Type FWF

Tripping characteristics of FWFcircuit breakers for plant protection, I

cu

= 40/70 kA, “n” release fixed setting

Type JW

Tripping characteristics of JW circuit breakers for plant protection, I

cu

= 40/70 kA, “n” release adjustable

Type FW

Tripping characteristics of FW circuit breakers for plant protection, I

cu

= 40/70 kA, “n” release adjustable

Type KW

Tripping characteristics of KW circuit breakers for plant protection, I

cu

= 45/70 kA, “n” release adjustable

(660/690V)

(n)

8XIn➀

(a)

100 2 4 6 8 101 2 4 6 8 102 2 4 6 8 103

10000

500030002000

1000

500300200

100

503020

10

532

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIM

E I

N S

EC

ON

DS

CURRENT IN MULTIPLES OF In

(380/415V)

(220/240V)

Notes:

“a” thermal overload release

“n” instantaneous (electromagnetic) short circuit release

Series C Frame Sizes G through K

Tripping time characteristics (Thermal Memory)

Cold Cold

Warm

Warm

0 1 5 min 10

2/3

1

1/3

Cooling Down

Heating Up

UK PG.29B.01.T.U A4 34-42 Page 36 Friday, March 12, 1999 3:58 PM

July 1998

PG.29B.01.T.U

Cutler-Hammer

37Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

100 2 4 6 8 101 2 4 6 8 102 2 4 6 8 103

10000

500030002000

1000

500300200

100

503020

10

532

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIM

E I

N S

EC

ON

DS

CURRENT IN MULTIPLES OF In

(660/690V)

(a)

(380/415V)

(220/240V)

(n)

10XIn5XIn

Notes:

“a” thermal overload release

“n” instantaneous (electromagnetic) short circuit release

100 2 4 6 8 101 2 4 6 8 102 2 4 6 8 103

10000

500030002000

1000

500300200

100

503020

10

532

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIM

E I

N S

EC

ON

DS

CURRENT IN MULTIPLES OF In

(660/690V)

(n)

10XIn

(a)

(380/415V)

(220/240V)

5XIn

Notes:

“a” thermal overload release

“n” instantaneous (electromagnetic) short circuit release

100 2 4 6 8 101 2 4 6 8 102 2 4 6 8 103

10000

500030002000

1000

500300200

100

503020

10

532

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIM

E I

N S

EC

ON

DS

CURRENT IN MULTIPLES OF In

(660/690V)

8XIn

(a)

(380/415V)

(220/240V)

(n)

Notes:

“a” thermal overload release

“n” instantaneous (electromagnetic) short circuit release

100 2 4 6 8 101 2 4 6 8 102 2 4 6 8 103

10000

500030002000

1000

500300200

100

503020

10

532

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIM

E I

N S

EC

ON

DS

CURRENT IN MULTIPLES OF In

(660/690V)

(n)

10XIn

(a)

(380/415V)

(220/240V)

5XIn

Notes:

“a” thermal overload release

“n” instantaneous (electromagnetic) short circuit release

100 2 4 6 8 101 2 4 6 8 102 2 4 6 8 103

10000

500030002000

1000

500300200

100

503020

10

532

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIM

E I

N S

EC

ON

DS

CURRENT IN MULTIPLES OF In

(660/690V)

(n)

10XIn

(a)

(380/415V)

(220/240V)

5XIn

Notes:

“a” thermal overload release

“n” instantaneous (electromagnetic) short circuit release

100 2 4 6 8 101 2 4 6 8 102 2 4 6 8 103

10000

500030002000

1000

500300200

100

503020

10

532

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

TIM

E I

N S

EC

ON

DS

CURRENT IN MULTIPLES OF In

(660/690V)

(n)

10XIn

(a)

(380/415V)

(220/240V)

5XIn

Notes:

“a” thermal overload release

“n” instantaneous (electromagnetic) short circuit release

Time-Current Curves

Tripping Characteristics

The operating values specified for the inverse time overcurrent releases (thermal overload releases, “a” releases) are mean values of the scatter bands of all setting ranges from the cold state and with uniform current loading of the conducting paths.

The tripping characteristics of the instantaneous (electromagnetic) short circuit releases (“n” releases) are based on the rated phase current I

n

which in the case of circuit break-ers with adjustable thermal overload releases is also the upper value of the setting range. With a lower set-ting current, a correspondingly higher multiple is obtained for the operating current of the “n” release.

Type LW

Tripping characteristics of LW circuit breakers for plant protection, I

cu

= 45/70 kA, “n” release adjustable

Type JW

Tripping characteristics of JW circuit breakers for plant protection, I

cu

= 100 kA, “n” release adjustable

Type FWF

Tripping characteristics of FWF circuit breakers for plant protection, I

cu

= 100 kA, “n” release fixed setting

Type KW

Tripping characteristics of KW circuit breakers for plant protection, I

cu

= 100 kA, “n” release adjustable

Type FW

Tripping characteristics of FW circuit breakers for plant protection, I

cu

= 100 kA, “n” release adjustable

Type LW

Tripping characteristics of LW circuit breakers for plant protection, I

cu

= 100 kA, “n” release adjustable

Series C Frame Sizes F through L

UK PG.29B.01.T.U A4 34-42 Page 37 Friday, March 12, 1999 3:58 PM

PG.29B.01.T.U

Cutler-Hammer

38

July 1998

Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

1 2 3 4 5 6 8 10 15Xlr

7200

1000

500

200

100

50

20

10

5

2

1

.5

.2

.1

.05

.02

.01

.005

TIM

E I

N S

EC

ON

DS

CURRENT IN MULTIPLES OF In

1.5 10 15 20 30 40 60 80 100 200kA

Setting for ldas Multiples of lr(7X lr Not Shown)

2X

3X

4X

5X

6X

8X

7 X

td

300 ms

200 ms

100 ms

n

s

a

Notes:

Inverse-time overload release “a”lr Set current (adjustable)

Short time delayed short circuit releaseld Tripping current (adjustable)td Delay time (adjustable)

Instantaneous short circuit release “n”li Tripping current (fixed setting)

1 2 3 4 5 6 8 10 15Xlr

7200

1000

500

200

100

50

20

10

5

2

1

.5

.2

.1

.05

.02

.01

.005

TIM

E I

N S

EC

ON

DS

CURRENT IN MULTIPLES OF In

1.5 10 15 20 30 40 60 80 100 200kA

Setting for ldas Multiples of lr(7x lr Not Shown)

2X

3X

4X

5X

6X

8X

7 X

Notes:

Inverse-time overload release “a”lr Set current (adjustable)

Short time delayed short circuit releaseld Tripping current (adjustable)td Delay time (adjustable)

Instantaneous short circuit release “n”li Tripping current (fixed setting)

td

300 ms

200 ms

100 ms

n

s

a

Time-Current Curves

Type NW

Tripping characteristics for NW circuit breakers, I

cu

50/70/100 kA, with solid state overcurrent release

Working Temperature Range

The tolerance bands shown are applicable to an ambient tempera-ture range of -5 to +60

°

C at the circuit breaker.

Working Temperature Range

The tolerance bands shown are applicable to an ambient tempera-ture range of -5 to +60

°

C at the circuit breaker.

Type RW

Tripping characteristics for RW circuit breakers, I

cu

70/100 kA, with solid state overcurrent release

Series C Frame Sizes N and R

UK PG.29B.01.T.U A4 34-42 Page 38 Friday, March 12, 1999 3:58 PM

July 1998

PG.29B.01.T.U

Cutler-Hammer

39Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

1 10 100Xle

7200

1000

100

10

1

.1

.01

TIM

E I

N S

EC

ON

DS

CURRENT IN MULTIPLES OF In

s

Class 30

20

15

10

5

Time-Current Curves

Type FWMP, KWMP, and LWMP

Tripping characteristics for FWMP, KWMP, and LWMP circuit breakers for motor protection with solid state overcurrent releases

Characteristics of the FWMP,

KWMP, and LWMP Circuit Breakers

for Motor Protection with Solid

State Overcurrent Releases

The tripping times of the inverse-time delayed overcurrent releases are only valid for the not preloaded (cold) state. At operating tempera-ture (after load with rated current), the tripping times are reduced to approximately 33%. After an over-current trip, the tripping times are reduced according to the tripping time characteristics (see figure below) so that cooling down for some minutes is required before restarting the motor. During the first minute after tripping, reclosing of the circuit breaker is blocked.

Series C Frame Sizes F through L

UK PG.29B.01.T.U A4 34-42 Page 39 Friday, March 12, 1999 3:58 PM

PG.29B.01.T.U

Cutler-Hammer

40

July 1998

Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

5 7 10 20 30 50 kA 100

100

80

60

40

20

10

6

4

2

1

I2 t

VA

LUE

X10

5

SHORT CIRCUIT CURRENT ISrms

L

8

A2s

K

J

F

5 7 10 20 30 50 kA 100

100

80

60

40

20

10

6

4

2

1

I2 t

VA

LUE

X10

6

SHORT CIRCUIT CURRENT ISrms

8

A2s

N➁

R➁

R➀

N➀

Notes:➀ 50/60 Hz 380/415 VAC➁ 50/60 Hz 660/690 VAC

5 7 10 20 30 50 kA 100

200

kA

100

80

60

40

20

10

8

6

4

2

CU

T-O

FF

CU

RR

EN

T I

D

SHORT CIRCUIT CURRENT ISrms

0.3

0.2

R

N

0.5

cos =0.25

5 7 10 20 30 50 kA 100

100

80

60

40

20

10

6

4

2

1

I2 t

VA

LUE

X10

5

SHORT CIRCUIT CURRENT ISrms

L

8

K

J

F

5 7 10 20 30 50 kA 100

200

kA

100

80

60

40

20

10

8

6

4

2

CU

T-O

FF

CU

RR

EN

T I

D

SHORT CIRCUIT CURRENT ISrms

0.3

0.2

F

J

KL

cos =0.25

0.3

5 7 10 20 30 50 kA 100

200

kA

100

80

60

40

20

10

8

6

4

2

CU

T-O

FF

CU

RR

EN

T I

D

SHORT CIRCUIT CURRENT ISrms

0.2

F

J

K

Lcos =0.25

Current Limiting Curves

Current Limiting Characteristics and

Maximum I

2

t Values

Type FW/LW

Current limiting characteristics for FW to LW, 50/60 Hz 380/415 VAC

Type FW/LW

Current limiting characteristics for FW to LW, 50/60 Hz 660/690 VAC

Type NW/RW

Current limiting characteristics for NW to RW, 50/60 Hz 380/415 VAC

Type FW/LW

Maximum I

2

t values for FW to LW, 50/60 Hz 380/415 VAC

Type FW/LW

Maximum I

2

t values for FW to LW, 50/60 Hz 660/695 VAC

Type NW/RW

Maximum I

2

t values for NW to RW

Series C Frame Sizes F through R

UK PG.29B.01.T.U A4 34-42 Page 40 Friday, March 12, 1999 3:58 PM

July 1998

PG.29B.01.T.U

Cutler-Hammer

41Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

Front View 3-PoleFront Cover Cutout Side View

104.77(4.125)

39.67 (1.444)19.83

(0.781) 8.74 (0.344) R

103.17(4.062)

254.00(10.000)

147.24(5.797)

88.90(3.500)

100.02(3.938)

74.22 (2.922)

C LBreaker

22.22 (0.875)18.24

(0.718)

CLHandle

Front View 3-PoleFront Cover Cutout Side View

86.00(3.386)

101.60(4.000)

152.40(6.000)

6.35 (0.250) R

73.81(2.906)

4.78 Dia.(0.188) 30.20 (1.189)

33.65(1.325)

15.07 (0.593)

CL

104.77(4.125)

Handle

C LBreaker

Front View 3-PoleFront Cover Cutout Side View

76.20(3.000)

76.20(3.000)

56.34(2.218)

66.67(2.625)

81.74(3.218)

123.82(4.875)

Front View 3-PoleFront Cover Cutout Side View

139.45(5.490)

104.00(4.094)

257.17(10.125)

151.55(5.967)

33.35 (1.313)4.77 (0.188) R

41.66 (1.640)

21.03 (3.750)95.25 (3.750)

60.73(2.391)

66.67 (2.625)121.46(4.782)

31.75 (1.250)

8.74 (0.344) R

C LBreaker

CLHandle

Dimensions,

mm (inches)

F-Frame

J-Frame

K-Frame

Series C Frame Sizes G through K

G-Frame

Dimensions in parentheses in inches.

UK PG.29B.01.T.U A4 34-42 Page 41 Friday, March 12, 1999 3:58 PM

PG.29B.01.T.U

Cutler-Hammer

42

July 1998

Moulded Case Circuit Breakers16-2500 Amperes for IEC 947-2 Applications

Front View 3-PoleFront Cover Cutout Side View

43.66 (1.719)

63.50 (2.500) R

4.77 (0.188) R

209.60(8.252)

139.70(5.500)

184.94(7.281)

87.32(3.438)

58.22(2.292)

33.65(1.325)

92.48(3.641)

83.34(3.281)

44.50(1.752)

142.60(5.614)

273.10(10.752)

406.40(16.00)

10.00(0.394)

111.10(4.374)

CL Breaker

38.10(1.500)

CLHandle

CL Breaker

406.4(16.000)

330.2(13.000)

2.250 (0.089)

TeeConnectors

May BeRotated 90°

209.55(8.250)

393.7(15.500)

171.45(6.750)

228.6(9.000)

327.81(12.906)

368.3(14.500)

166.70(6.563)

184.15(7.250)

129.38(5.094)

246.07(9.688)

196.85(7.750)

381.0(15.000)

3.96 R(0.156)

4 Holes11.12 Dia.(0.438)

CLHandle

CLHandle

234.95(9.250)

406.40(16.000)

139.68(5.499)

209.55(8.250)

CL Breaker

43.63 (1.718)

96.77(3.810)

38.1 (1.500)

87.32 (3.438)

4.77 (0.188) R161.92(6.375)

80.94 (3.187)

6.35 (0.250) R

Front View 3-PoleFront Cover Cutout Side View

Front View 3-PoleFront Cover Cutout Side View

L-Frame 630

(Bus extensions not included)

L-Frame 800

N-Frame

R-Frame

Dimensions,

mm (inches)

Series C Frame Sizes L through R

Dimensions in parentheses in inches.

UK PG.29B.01.T.U A4 34-42 Page 42 Friday, March 12, 1999 3:58 PM

The circuit breakers shall meet or exceed all standards as defined in IEC 947-2. Electrical circuits shall be protected by Series C World Moulded Case Circuit Breakers asmanufactured by Cutler-Hammer.

Each pole of the one-, two-, and three-pole circuit breakers shall provide complete circuit overcurrrent protection by having inverse time and instantaneous tripping character-istics and, where applicable, be current limiting.

The circuit breaker shall be available in interruptingfamilies that provide 35-65-100 kA at 380-415 volts AC.

The circuit breakers shall be operated by a toggle-type handle and have a quick-make, quick-break, over-centre switching mechanism that is mechanically trip-free from the handle so that the contacts cannot be closed against short circuit currents. Tripping due to overload or short cir-cuits shall be clearly indicated by the position of the han-dle. The ON and OFF positions shall be clearly marked on the cover of the circuit breaker along with the international symbols I for ON and O for OFF on the handle, providing positive indication of the circuit breaker contact position. Additionally, a colour-coded indication of the circuit break-er contact position shall be provided: red for ON, green for OFF, and white for TRIPPED. An easily accessible Push-To-Trip button for mechanically exercising the trip unit shall be provided on the cover of each circuit breaker. All poles of a multi-pole circuit breaker shall be so constructed as to ensure simultaneous open, close, and trip operations.

Circuit breakers shall be completely enclosed in a high strength glass-polyester case.

Noninterchangeable trip circuit breakers shall be factory sealed; interchangeable trip circuit breakers shall have the trip unit sealed to prevent tampering. Ampere ratings shall be clearly visible from the front of the circuit breaker. Con-tacts shall be nonwelding silver alloy. Arc extinction shall

be accomplished by means of DE-ION

®

arc extinguishers consisting of metal grids mounted in an insulating support.

The minimum interrupting ratings of the circuit breakers shall be at least equal to the available short circuit current at the line terminals.

The circuit breakers can be applied in series rated applica-tions and subject to test data verification.

Circuit breakers in frame sizes 100 amperes through 250 amperes shall be equipped with thermal-magnetic trip units. Circuit breakers 400 amperes through 2500 ampere frame sizes shall be equipped with electronic trip units that are insensitive to changes in ambient temperature within the normal operating temperature range of the circuit breaker. The 400 ampere and 630 ampere frame sizes shall be designed to accept either thermal-magnetic or electronic interchangeable trip units.

Electronic trip units shall be rms sensing type and have unpowered thermal memory.

Circuit breaker ratings and modifications shall beindicated on the drawings.

Circuit breakers shall be of the inverse time and instan-taneous trip type as provided by thermal-magnetic orelectronic trip elements with either standard interrupting, high interrupting, or current limiting characteristics as required.

Moulded case circuit interrupters (motor circuit protec-tors) shall be of the instantaneous (magnetic) only type, providing instantaneous short circuit protection by means of a front adjustable trip unit.

Moulded case switches shall be of the same construction as the related listed circuit breaker and equipped with a factory sealed, nonadjustable, high instantaneous only short circuit protection.

Moulded case switches shall have no overload or low level fault protection provided and shall be marked with amaximum withstand rating denoting the type and level of upstream protection required. Moulded case switchesshall be listed per IEC 947-2.

Internally mounted accessories including alarm (signal)/lockout switches, auxiliary switches, shunt trips, andundervoltage released mechanisms shall be of the plug-in type and shall be listed for field fitting in circuit breakers which are not factory sealed.

Electrical operators for circuit breakers of the 400 ampere frame size and below shall be of the solenoid type with maximum five-cycle closing characteristics. Electricaloperators for circuit breaker frame sizes 630 amperes through 2500 amperes shall be of the motor driven type. All electrical operators shall be cover mounted. Allelectrical operators shall be listed for field installationper IEC 947-2.

Electrical characteristics of accessories shall be asindicated on the drawings.

Circuit breakers in the 160 amperes rating shall be sup-plied in one-, two-, three-, and four-pole models, as speci-fied on the drawings. Circuit breakers in ratings of 225 amperes through 1250 amperes shall be supplied in two-, three-, or four-pole models. The 2500 ampere circuit breaker is available in three- and four-pole models as specified on the drawings.

Accessory wiring shall be brought out through the side or rear of the circuit breaker, or be connected to a terminal block mounted on the side of the circuit breaker, as speci-fied. The ability to route accessory wiring to the opposite side of the circuit breaker through a trough in the base shall be provided.

Circuit breakers shall be provided with uniformly designed nameplates to clearly indicate the type, rating, listing/recognition/certification marks, accessory details, andother information defined in IEC 947-2.

Typical Specifications

for Series C

T

Moulded Case Circuit Breakers