C Fireproof(ing) F.P. W.PT. Top of Steel Top of Slab Refrigerator Refrigerator Square Yard(s) System Symmetrical Structure Structural Structure Sheer Wall Suspend(ed) Storage Sound Transmission Coefficient Standard Steel Service Sink Station Speaker Specification See Plumbing Drawings Sanitary Napkin Receptacle Sanitary Napkin Dispenser Sheet Note See Mechanical Drawings Stanchion Module See Landscape Drawings Sliding Sink Similar Sheet Shower Shelf Sprinkler Head Square Foot (Feet) See Finish Drawings See Fire Protection Drawings See Electrical Drawings Section Soap Dispenser Schedule Seat Cover Dispenser Self Adhesive Sheet Membrane Sanitary South See Structural Drawings Stainless Steel Square S.Y. SYS. SYM. STRL. S.W. SUSP. STR. STOR. STC STD. STRUCT. STL. S.SK. STA. SPKR. SPEC. S.P.D. S.N.R. S.N.D. S.N. S.M.D. S.M. S.L.D. SL. SK. SIM. SHT. SHR. SHLF. S.H. S.F. S.F.D. S.F.P.D. S.E.D. SECT. S.D. SCHED. S.C.D. S.C. SAN. S. S.S. SQ. S.S.D. Radius Point R.P. Rain Water Leader RWL. Rough Opening Round Room Register Reflected Remaining Reinforced Reference Recessed Roof Drain Reflected Ceiling Plan Resilient Base Radius Return Air Riser Revised / Revision Retaining Resilient Required Quarry Tile R.O. RND. RM. RFG. RGTR. RFL. REM. REINF. REF. REC. R.D. R.C.P. R.B. RAD. R.A. REF. REV. RET. RES. REQ. Q.T. Paper Towel Dispenser & Receptacle Painted Paper Towel Dispenser Partition Paper Towel Receptacle PTN. P.T.D. / R. PTD. P.T.D. P.T.R. Welded Wire Fabric WWF Waterproof Work Point WP. Weight WT. W.R. Water Resistant Window WDW W/ W. W.F. W.H. W/O Without Water Heater Wood Flooring White Board W.B. West OR Width With W.C. WD. Water Closet Wall Covering Wood WC Veneer Plaster V.P. VOL. Volume V.I.F. Verify in Field VERT. Vestibule Veneer Vertical VEN. VEST. Vapor Barrier VB. Varies VAR. Underwriters Laboratory U.L. Top of Wall T.W. T.O.STL. T.O.S. T.O.P. Top of Parapet Top of Concrete Top of Curb Top Of T.O.CONC. T.O.C. T.O. T.V. T.P.H. Toilet Paper Dispenser Top of Wall Top of Plate T.P.D. T.O.W. T.O.PL. Toilet Paper Holder Television U.B.C. U.C. Under Counter TYP. Typical Uniform Building Code Urinal Unless Otherwise Noted UNF. U.O.N. UR. Unfinished Thick TH. T. & G. Tongue and Groove Top of Deck(ing) T.D. Top of Concrete Towel Bar T.B. T.B.D. T.C. To Be Determined Tempered Telephone TEMP. TEL. Tread T-24 Title 24 T. R. Precast Polished Plumbing Pair Panel Panel Module Plywood Plaster Plastic Laminate PRCST. POL. PLBG. PR. PNL. P.M. P.LAM. PLYWD. PLAS. Point PT. Heating, Ventilation, Air Conditioning Owner Furnished Contractor Installed Perpendicular Precast Concrete Paving Paint Plate Paint Grade Ounce Overhead Oriented Strand Board Opposite Hand Opposite Overflow Drain Outside Diameter On Center Overall Not To Scale Nominal Number Not In Contract New North Opening Masonry Opening Middle Mullion Mounted Miscellaneous Mirror Minimum Microwave Manhole Owner Furnished Owner Installed Overflow Leader Overhead Manufacturer Metal Mechanical, Electrical, Plumbing Membrane Mechanical Medium Density Fiber Board Maximum Masonry Material Maintenance Machine Millimeter Meter Low Point Locker Light Fixture Light Long Linear Foot Laboratory Lavatory Laminate Length Kick Plate Knockout Joint Joist Junction Box Janitor Include(d) (ing) Inside Diameter / Dimension Invert Inch Intermediate Interior Insulation Information Incandescent Hot water Hour Handrail MET./MTL. PERP. P.C. PAV. P. PL. P.G. OZ. OVHD. OSB OPP. HD. OPP. OPNG. O.H. O.F.O.I. OFL. OFD. O.F.C.I. O.D. O.C. O.A. N.T.S. NOM. NO. N.I.C. N. (N) M.O. MID. MUL. MTD. MISC. MIRR. MIN. MIC. M.H. MFR. MEP MEMB. MECH. M.D.F. MAX. MAS. MAT. MAINT. MACH. MM M. LT.FIXT. LT. L.PT. LKR. LG. L.F. LAB. LAV. LAM. L. K.P. KO. J-BOX JT. JST. JAN. INV. INCL. IN. INTER. INT. INSUL. INFO. INCAN. I.D. H.W. H.V.A.C. HR. H.R. Ground Fault Circuit Interruption High Point Handrail Horizontal Height Hollow Metal Hardwood Hardboard Hardware Header Handicapped Hollow Core Hose Bib Hand Ground Glass Reinforced Gypsum Glass Fiber Reinforced Concrete Grade Guard Rail Gypsum Board General Note Glass Galvanized Gauge General Garbage Disposal General Contractor Grab Bar Future Furring Footing Foot OR Feet Fire Treated Full Size Fire Retardant H.PT. HNDRL. HOR. HT. H.M. HDWD. HDBD. HDW. HDR. HCP. H.C. H.B. HD. GR. G.R. GYP. G.N. GND. GL. GRG. GFRC GFCI GALV. GA. GEN. G.D. G.C. G.B. FUT. FURR. FTG. FT. F.T. F.S. F.R. Corridor Face of Building Face of Stud Face of Finish Face of Concrete F.O.B. F.O.S. F.O.F. F.O.C. Factory Mutual Fluorescent Flashing Floor Fixture Finish Flat Head OR Full Height Floor Drain OR Fire Damper Foundation Fire Extinguisher Cabinet Fire Extinguisher Fire Alarm Fabric Electro-static Dissipative Electrical Water Cooler Expansion Exposed Existing Exterior (elastic plastic flashing) Ethylene Polypropylene Electrical Panelboard Engineer Enclosure Emergency Elevator Electrical Elevation Expansion Joint Exterior Insulation Finish System Equipment Equal Each Existing East Drawer Dimension Point Door Demountable Double Dispenser Dimension Diameter Drinking Fountain Detail Department Door Opening Down Door Note Counter Control Joint Cast in Place Cast Iron Corner Guard Category Clear Closet Caulking Ceiling Ceramic Cement Cabinet Carpet Basement Built-up Roofing Brick Bearing Bracket Bottom Downspout Drain Drawings Drawing Dishwasher Below Board Bottom Of Brick Module Beam Block Building Asphalt Anchor Access Panel Aluminum Aggregate Architectural Above finished floor Adjacent Adjustable Additional Americans W/ Disabilities Act Approximate Area Drain Countersunk Center Curtain wall Ceramic Tile Cold Rolled Concrete Masonry Unit Carpet Contractor Continuous Construction Concrete Column Cased Opening Acoustical Air Condition Above Automatic FM. FLUOR. FLASH. FL./FLR. FIXT. FIN. F.H. F.E.C. F.E. FND. F.D. F.A. F. EXST. EXT. EXP. EXPO. E.W.C. ESD EPDM E.P. ENGR. ENCL. EMER. ELEV. ELEC. EL. E.J. E.I.F.S. EQPT. EQ. EA. (E) E. DS. DRN. DWR. D.P. DR. DMT. DBL. DIM. DISP. DIA. D.F. DET./DTL. DEPT. D.O. DN. D.N. CNTR. C.M.U. CLO. CLR. CLKG. CLG. C.J. C.I.P. C.I. C.G. CER. CEM. CBC CAT. CAB. C. BSMT. B.U.R. BRK. BRG. BRKT. BOT. DWGS. DWG. D.W. BEL. BD. B.O. B.M. BM. BLK. BLDG. AUTO ASPH. ANCH. A.P. AL. AGGR. ARCH. ADJA. A.F.F. ADJ. ADDL. ADA APPROX. A.D. CTSK. CTR. CW. C.T. C.R. CPT. CORR. COL. C.O. CONTR. CONT. CONSTR. CONC. ACOUS. A/C. ABV. Property Line P Square Feet S.F. # Number or Pound » « Perpendicular Parallel Plus or Minus ± ¬ ABBREVIATIONS Diameter Degrees Copyright Centerline At Angle And Ø º & © @ L Solid Core SASM Cross-Laminated Timber CLT California Building Code Above Sea Level A.S.L. L Midpoint M.P. Glazed Aluminum Wall System GAWS Environmental ENV. Cold-Formed Metal Framing CFF Module MOD. A B INDICATES ROOM NAME INDICATES PARTITION TYPE INDICATES SHEET NUMBER INDICATES DRAWING NUMBER INDICATES DRAWING NUMBER SUBGROUP INTERIOR ELEVATION ROOM NAME & NUMBER WALL TAG INDICATES SHEET NUMBER INDICATES DRAWING NUMBER INDICATES SHEET NUMBER INDICATES DRAWING NUMBER ELEVATION BUILDING SECTION SYMBOLS INDICATES ROOM AREA 1 A101 SIM INDICATES SHEET NUMBER INDICATES DRAWING NUMBER Room name 150 SF A B INDICATES DRAWING NUMBER SUBGROUP INDICATES PARTITION FIRE RATING STUD SIZE 1 A101 SIM 1 A101 1 A101 ADDITIONAL NOTE DETAIL KEY 1 1 A B 2 2C6.A 100 CR AA DOOR TAG DOOR NUMBER DOOR TYPE SECURITY NOTES HARDWARE GROUP GENERAL NOTES ALL WORK SHALL COMPLY WITH THE APPLICABLE CODES, AMENDMENTS, RULES, REGULATIONS, ORDINANCES, LAWS, ORDERS, APPROVALS, ETC., THAT ARE REQUIRED BY PUBLIC AUTHORITIES. IN THE EVENT OF CONFLICT, THE MOST STRINGENT REQUIREMENTS SHALL COMPLY. CONTRACTOR TO FOLLOW MANUFACTURER’S RECOMMENDED SPECIFICATIONS AND INSTALLATION PROCEDURES. IF THESE ARE CONTRARY TO THE CONTRACT DOCUMENTS, CONTRACTOR SHALL NOTIFY THE ARCHITECT, IN WRITING IMMEDIATELY, TO RESOLVE DISCREPANCIES PRIOR TO PROCEEDING. “FURNISH” MEANS SUPPLY ONLY, FOR OWNER TO PUT IN PLACE. “INSTALL” MEANS SUPPLIED BY OWNER, TO BE INSTALLED BY CONTRACTOR. “PROVIDE” MEANS FURNISH AND INSTALL, COMPLETE AND IN PLACE. “SIMILAR” MEANS COMPARABLE CHARACTERISTICS FOR CONDITIONS NOTED. CONTRACTOR TO VERIFY DIMENSIONS AND ORIENTATION. “TYPICAL” MEANS IDENTICAL FOR CONDITIONS NOTED. DO NOT SCALE DRAWINGS, DIMENSIONS GOVERN. VERIFY DIMENSIONS WITH FIELD CONDITIONS, IF DISCREPANCIES ARE DISCOVERED BETWEEN FIELD CONDITIONS AND DRAWINGS OR BETWEEN INDIVIDUAL DRAWINGS, CONTACT THE ARCHITECT FOR RESOLUTION BEFORE PROCEEDING. HORIZONTAL DIMENSIONS INDICATED ARE TO/FROM FINISHED FACE OF CONSTRUCTION, EXCEPT AS NOTED. VERTICAL DIMENSIONS ARE FROM TOP OF FINISHED FLOOR, (A.F.F.), UNLESS OTHERWISE NOTED. IN THE EVENT OF CONFLICT BETWEEN DATA SHOWN ON DRAWINGS AND DATA SHOWN IN THE SPECIFICATIONS, THE SPECIFICATIONS SHALL GOVERN. DIMENSIONS NOTED ON DRAWINGS SHALL TAKE PRECEDENCE OVER SCALED DIMENSIONS. DETAIL DRAWINGS TAKE PRECEDENCE OVER DRAWINGS OF SMALLER SCALE. SHOULD THE CONTRACTOR AT ANY TIME DISCOVER AN ERROR IN A DRAWING OR SPECIFICATIONS, OR A DISCREPANCY OR VARIATION BETWEEN DIMENSIONS ON DRAWINGS AND MEASUREMENTS AT SITE, OR LACK OF DIMENSIONS OR OTHER INFORMATION, HE/SHE SHALL REPORT AT ONCE TO THE ARCHITECT FOR CLARIFICATION AND SHALL NOT PROCEED WITH THE WORK AFFECTED UNTIL CLARIFICATION HAS BEEN MADE. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING THE DIMENSIONS AND ELEVATIONS AT THE SITE. THE CONTRACTOR AND SUB-CONTRACTORS SHALL COORDINATE THE LAYOUT AND EXACT LOCATION OF ALL PARTITIONING, DOORS, ELECTRICAL/TELEPHONE OUTLETS, LIGHT SWITCHES AND THERMOSTATS WITH THE ARCHITECT IN THE FIELD BEFORE PROCEEDING WITH CONSTRUCTION. THE CONTRACTOR SHALL CONTINUOUSLY CHECK ARCHITECTURAL AND STRUCTURAL CLEARANCES FOR ACCESSIBILITY OF EQUIPMENT AND MECHANICAL AND ELECTRICAL SYSTEMS. CONTRACTOR SHALL VERIFY THAT NO CONFLICTS EXIST IN LOCATIONS OF ANY AND ALL MECHANICAL, TELEPHONE, ELECTRICAL, LIGHTING, PLUMBING, AND SPRINKLER EQUIPMENT (TO INCLUDE ALL PIPING, DUCT WORK AND CONDUIT) AND THAT ALL REQUIRED CLEARANCES FOR INSTALLATION AND MAINTENANCE OF ABOVE EQUIPMENT ARE PROVIDED. NO ALLOWANCE OF ANY KIND WILL BE MADE FOR THE CONTRACTOR’S NEGLIGENCE TO NOTE UNFORESEEN MEANS OF INSTALLING EQUIPMENT INTO POSITION INSIDE STRUCTURE. ALL WORK SHALL BE ERECTED AND INSTALLED PLUMB, LEVEL, SQUARE AND TRUE, AND IN PROPER ALIGNMENT. COORDINATE AND PROVIDE APPROPRIATE STRUCTURAL BLOCKING/BACKING AND REINFORCING IN PARTITIONS BEHIND ALL WALL MOUNTED ITEMS. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR CHECKING CONTRACT DOCUMENTS, FIELD CONDITIONS AND DIMENSIONS FOR ACCURACY AND CONFIRMING THAT WORK IS AS SHOWN BEFORE PROCEEDING WITH CONSTRUCTION. CLARIFICATIONS REGARDING ANY CONFLICTS SHALL BE ACHIEVED PRIOR TO RELATED WORK BEING STARTED. GENERAL CONTRACTOR SHALL VERIFY THAT NO CONFLICTS EXIST IN LOCATIONS OF ANY AND ALL MECHANICAL, TELEPHONE, ELECTRICAL, PLUMBING AND SPRINKLER EQUIPMENT (TO INCLUDE ALL PRICING, DUCT WORK AND CONDUIT) AND THAT ALL REQUIRED CLEARANCES FOR INSTALLATION AND MAINTENANCE OF ALL ABOVE EQUIPMENT ARE PROVIDED. WHAT ELEMENTS ARE TO BE EXPOSED OR CONCEALED SHALL BE DETERMINED AND REVIEWED WITH ARCHITECT PRIOR TO CONSTRUCTION PROCEEDING. IF AT ANY TIME BEFORE COMMENCEMENT OF WORK, OR DURING PROCESS THEREOF, CONTRACTOR'S METHODS, EQUIPMENT OR APPLIANCES ARE INEFFICIENT OR INAPPROPRIATE FOR SECURING QUALITY OF WORK, OR RATE OF PROGRESS INTENDED BY CONTRACT DOCUMENTS, CITY MAY ORDER CONTRACTOR TO IMPROVE THEIR QUALITY OR INCREASE THEIR EFFICIENCY. THIS WILL NOT RELIEVE CONTRACTOR OR HIS SURETIES FROM THEIR OBLIGATIONS TO SECURE QUALITY OF WORK AND RATE OF PROGRESS SPECIFIED IN CONTRACT. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. T L I C D E C H N S E A R I T E C S T A T E O F C A L I F O R N I A N0. C33665 REN. A R H L L A B R N D O N M S A 03-31-19 SCALE PROJECT NO. DATE 8106 TERRACE DRIVE, EL CERRITO, CA 94530 707.297.6185 www.fogprojects.com STAMP CONSULTANT LOGO RESTROOM RENOVATION As indicated 10/20/2017 10:14:35 AM 16.25 10/20/17 PROJECT INFORMATION G0.01 A1.00 SITE PLAN A2.00 EXISTING PLAN A2.01 PROPOSED PLAN A3.01 REFLECTED CEILING PLAN A9.10 ENLARGED PLANS AND ELEVATIONS - TOILET A11.01 PARTITION TYPES & ACCESSIBILITY DETAILS SHEET NUMBER SHEET NAME G0.01 PROJECT INFORMATION VICINITY MAP PROJECT LOCATION PROJECT ADDRESS: 3102 DELTA FAIR BLVD, ANTIOCH CA 94509 APN: 076-431-010 ZONING: C-3 PARCEL AREA: 85,378 SF GROSS BUILDING AREA: 13,000 SF PROJECT AREA: 6,500 SF NUMBER OF STORIES: 1 SPRINKLERS: NONE PROPERTY INFORMATION PROJECT IS AN INTERIOR RENOVATION OF APPROXIMATELY 340 SF TO THE RESTROOM AREA OF A 6,500 SF TENANT SPACE IN A MULTI-TENANT BUILDING. - REMOVAL OF (E) PLUMBING FIXTURES - NEW PLUMBING FIXTURES AND ACCESSORIES - NEW FLOOR, WALL AND CEILING FINISHES AS NEEDED - NEW LIGHTING AND EXHAUST FANS AT RESTROOMS SCOPE OF WORK DESCRIPTION PROJECT DIRECTORY OWNER: OPPORTUNITY JUNCTION Alissa Friedman 3102 Delta Fair Blvd., Antioch, CA 94509 Phone: 925-776-1133 [email protected] ARCHITECT: FOG STUDIO Brandon Marshall, C-33665 8106 Terrace Dr., El Cerrito, CA 94530 Phone: 707-297-6185 [email protected] SHEET INDEX No. Description Date ISSUE FOR PERMIT 10/20/17

Upload: vothien

Post on 20-Aug-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

C

Fireproof(ing)F.P.

W.PT.

Top of SteelTop of Slab

Refrigerator

Refrigerator

Square Yard(s)

SystemSymmetrical

StructureStructural

Structure

Sheer WallSuspend(ed)

Storage

Sound Transmission CoefficientStandardSteel

Service SinkStation

SpeakerSpecificationSee Plumbing DrawingsSanitary Napkin ReceptacleSanitary Napkin DispenserSheet NoteSee Mechanical DrawingsStanchion ModuleSee Landscape DrawingsSlidingSinkSimilarSheetShowerShelfSprinkler HeadSquare Foot (Feet)See Finish DrawingsSee Fire Protection DrawingsSee Electrical DrawingsSectionSoap DispenserScheduleSeat Cover Dispenser

Self Adhesive Sheet MembraneSanitarySouth

See Structural DrawingsStainless SteelSquare

S.Y.

SYS.SYM.

STRL.

S.W.SUSP.

STR.STOR.

STCSTD.

STRUCT.

STL.

S.SK.STA.

SPKR.SPEC.S.P.D.S.N.R.S.N.D.S.N.S.M.D.S.M.S.L.D.SL.SK.SIM.SHT.SHR.SHLF.S.H.S.F.S.F.D.S.F.P.D.S.E.D.SECT.S.D.SCHED.S.C.D.S.C.

SAN.S.

S.S.SQ.

S.S.D.

Radius PointR.P.Rain Water LeaderRWL.

Rough OpeningRoundRoomRegisterReflected

RemainingReinforced

ReferenceRecessedRoof DrainReflected Ceiling PlanResilient BaseRadiusReturn AirRiser

Revised / RevisionRetainingResilientRequired

Quarry Tile

R.O.RND.RM.

RFG.

RGTR.RFL.

REM.REINF.

REF.REC.R.D.R.C.P.R.B.RAD.R.A.

REF.

REV.RET.RES.REQ.

Q.T.

Paper Towel Dispenser & Receptacle

PaintedPaper Towel Dispenser

PartitionPaper Towel Receptacle

PTN.

P.T.D. / R.

PTD.P.T.D.

P.T.R.

Welded Wire FabricWWF

WaterproofWork Point

WP.

WeightWT.W.R. Water Resistant

WindowWDW

W/W.

W.F.W.H.W/O Without

Water HeaterWood Flooring

White BoardW.B.

West OR WidthWith

W.C.WD.

Water ClosetWall CoveringWood

WC

Veneer PlasterV.P.VOL. VolumeV.I.F. Verify in Field

VERT.Vestibule

VeneerVertical

VEN.

VEST.

Vapor BarrierVB.VariesVAR.

Underwriters LaboratoryU.L.

Top of WallT.W.

T.O.STL.T.O.S.

T.O.P. Top of ParapetTop of ConcreteTop of CurbTop Of

T.O.CONC.T.O.C.T.O.

T.V.T.P.H.

Toilet Paper DispenserTop of Wall

Top of Plate

T.P.D.T.O.W.

T.O.PL.

Toilet Paper HolderTelevision

U.B.C.U.C. Under Counter

TYP. Typical

Uniform Building Code

UrinalUnless Otherwise Noted

UNF.U.O.N.UR.

Unfinished

ThickTH.

T. & G. Tongue and Groove

Top of Deck(ing)T.D.Top of Concrete

Towel BarT.B.T.B.D.T.C.

To Be Determined

TemperedTelephone

TEMP.TEL.

TreadT-24 Title 24T.

R.

Precast

PolishedPlumbing

PairPanelPanel Module

PlywoodPlasterPlastic Laminate

PRCST.

POL.PLBG.

PR.PNL.P.M.

P.LAM.

PLYWD.PLAS.

PointPT.

Heating, Ventilation, Air Conditioning

Owner Furnished Contractor Installed

PerpendicularPrecast ConcretePavingPaint

PlatePaint Grade

OunceOverheadOriented Strand BoardOpposite HandOpposite

Overflow Drain

Outside DiameterOn CenterOverall

Not To ScaleNominalNumberNot In ContractNewNorth

Opening

Masonry Opening

Middle

MullionMounted

MiscellaneousMirrorMinimum

MicrowaveManhole

Owner Furnished Owner InstalledOverflow Leader

Overhead

ManufacturerMetalMechanical, Electrical, PlumbingMembraneMechanicalMedium Density Fiber BoardMaximumMasonryMaterialMaintenanceMachineMillimeterMeter

Low PointLocker

Light FixtureLight

LongLinear Foot

LaboratoryLavatoryLaminate

Length

Kick PlateKnockout

JointJoist

Junction BoxJanitor

Include(d) (ing)

Inside Diameter / Dimension

Invert

Inch

IntermediateInteriorInsulationInformation

Incandescent

Hot water

HourHandrail

MET./MTL.

PERP.P.C.PAV.P.

PL.P.G.

OZ.OVHD.OSBOPP. HD.OPP.OPNG.O.H.O.F.O.I.OFL.OFD.O.F.C.I.O.D.O.C.O.A.

N.T.S.NOM.NO.N.I.C.

N.(N)

M.O.

MID.

MUL.MTD.

MISC.MIRR.MIN.

MIC.M.H.MFR.

MEPMEMB.MECH.M.D.F.MAX.MAS.MAT.MAINT.MACH.MMM.

LT.FIXT.LT.L.PT.LKR.

LG.L.F.

LAB.

LAV.LAM.

L.

K.P.KO.

J-BOX

JT.JST.JAN.

INV.

INCL.

IN.

INTER.INT.INSUL.INFO.

INCAN.

I.D.

H.W.H.V.A.C.HR.H.R.

Ground Fault Circuit Interruption

High Point

HandrailHorizontal

HeightHollow Metal

Hardwood

Hardboard

HardwareHeader

HandicappedHollow CoreHose Bib

Hand

Ground

Glass Reinforced GypsumGlass Fiber Reinforced Concrete

GradeGuard Rail

Gypsum Board

General NoteGlass

GalvanizedGauge

GeneralGarbage DisposalGeneral ContractorGrab Bar

FutureFurringFootingFoot OR FeetFire TreatedFull SizeFire Retardant

H.PT.

HNDRL.HOR.

HT.H.M.

HDWD.

HDBD.

HDW.HDR.

HCP.H.C.H.B.

HD.

GR.G.R.

GYP.

G.N.GND.

GL.GRG.GFRCGFCI

GALV.GA.

GEN.G.D.G.C.G.B.

FUT.FURR.FTG.FT.F.T.F.S.F.R.

Corridor

Face of Building

Face of StudFace of FinishFace of Concrete

F.O.B.

F.O.S.F.O.F.F.O.C.

Factory MutualFluorescentFlashingFloorFixtureFinishFlat Head OR Full Height

Floor Drain OR Fire DamperFoundation

Fire Extinguisher CabinetFire Extinguisher

Fire AlarmFabric

Electro-static DissipativeElectrical Water CoolerExpansionExposedExistingExterior

(elastic plastic flashing)Ethylene PolypropyleneElectrical Panelboard

EngineerEnclosureEmergencyElevatorElectricalElevationExpansion JointExterior Insulation Finish System

EquipmentEqual

EachExistingEast

Drawer

Dimension PointDoor

Demountable

Double

DispenserDimensionDiameterDrinking FountainDetailDepartment

Door OpeningDownDoor Note

Counter

Control JointCast in PlaceCast IronCorner Guard

Category

ClearClosetCaulkingCeiling

CeramicCement

CabinetCarpet

BasementBuilt-up RoofingBrickBearingBracketBottom

DownspoutDrain

DrawingsDrawingDishwasher

BelowBoard

Bottom OfBrick ModuleBeamBlockBuilding

Asphalt

Anchor

Access PanelAluminumAggregate

Architectural

Above finished floorAdjacentAdjustableAdditionalAmericans W/ Disabilities Act

Approximate

Area Drain

CountersunkCenter

Curtain wall

Ceramic TileCold Rolled

Concrete Masonry Unit

Carpet

ContractorContinuousConstructionConcreteColumnCased Opening

AcousticalAir ConditionAbove

Automatic

FM.FLUOR.FLASH.FL./FLR.FIXT.FIN.F.H.F.E.C.F.E.FND.F.D.F.A.F.

EXST.EXT.

EXP.EXPO.

E.W.C.ESD

EPDME.P.

ENGR.ENCL.EMER.ELEV.ELEC.EL.E.J.E.I.F.S.

EQPT.EQ.

EA.(E)E.

DS.DRN.

DWR.

D.P.DR.

DMT.

DBL.

DIM.DISP.

DIA.D.F.DET./DTL.DEPT.

D.O.DN.D.N.

CNTR.

C.M.U.

CLO.CLR.

CLKG.CLG.C.J.C.I.P.C.I.C.G.

CER.CEM.CBCCAT.CAB.C.

BSMT.B.U.R.BRK.BRG.BRKT.BOT.

DWGS.DWG.D.W.

BEL.BD.

B.O.B.M.BM.BLK.BLDG.

AUTOASPH.

ANCH.

A.P.AL.AGGR.

ARCH.

ADJA.A.F.F.

ADJ.ADDL.ADA

APPROX.

A.D.

CTSK.CTR.

CW.

C.T.C.R.CPT.CORR.

COL.C.O.

CONTR.CONT.CONSTR.CONC.

ACOUS.A/C.ABV.

Property LineP

Square FeetS.F.# Number or Pound

»«

PerpendicularParallel

Plus or Minus±

¬

ABBREVIATIONS

DiameterDegreesCopyrightCenterlineAtAngleAnd

غ

&

©

@L

Solid CoreSASM

Cross-Laminated TimberCLT

California Building Code

Above Sea LevelA.S.L.

L

MidpointM.P.

Glazed Aluminum Wall SystemGAWS

EnvironmentalENV.

Cold-Formed Metal FramingCFF

ModuleMOD.

A

B

INDICATES ROOM NAME

INDICATES PARTITION TYPE

INDICATES SHEET NUMBER

INDICATES DRAWING NUMBERINDICATES DRAWING NUMBER SUBGROUP

INTERIOR ELEVATION

ROOM NAME & NUMBER

WALL TAG

INDICATES SHEET NUMBER

INDICATES DRAWING NUMBER

INDICATES SHEET NUMBER

INDICATES DRAWING NUMBER

ELEVATION

BUILDING SECTION

SYMBOLS

INDICATES ROOM AREA

1A101

SIM

INDICATES SHEET NUMBER

INDICATES DRAWING NUMBER

Room name150 SF

A

B INDICATES DRAWING NUMBER SUBGROUP

INDICATES PARTITION FIRE RATINGSTUD SIZE

1

A101

SIM

1A101

1A101

ADDITIONAL NOTE

DETAIL KEY

1 1AB

2

2C6.A100

CRAA

DOOR TAG DOOR NUMBER

DOOR TYPE

SECURITY NOTESHARDWARE GROUP

GENERAL NOTESALL WORK SHALL COMPLY WITH THE APPLICABLE CODES, AMENDMENTS, RULES, REGULATIONS, ORDINANCES, LAWS, ORDERS, APPROVALS, ETC., THAT ARE REQUIRED BY PUBLIC AUTHORITIES. IN THE EVENT OF CONFLICT, THE MOST STRINGENT REQUIREMENTS SHALL COMPLY.

CONTRACTOR TO FOLLOW MANUFACTURER’S RECOMMENDED SPECIFICATIONS AND INSTALLATION PROCEDURES. IF THESE ARE CONTRARY TO THE CONTRACT DOCUMENTS, CONTRACTOR SHALL NOTIFY THE ARCHITECT, IN WRITING IMMEDIATELY, TO RESOLVE DISCREPANCIES PRIOR TO PROCEEDING.

“FURNISH” MEANS SUPPLY ONLY, FOR OWNER TO PUT IN PLACE.

“INSTALL” MEANS SUPPLIED BY OWNER, TO BE INSTALLED BY CONTRACTOR.

“PROVIDE” MEANS FURNISH AND INSTALL, COMPLETE AND IN PLACE.

“SIMILAR” MEANS COMPARABLE CHARACTERISTICS FOR CONDITIONS NOTED. CONTRACTOR TO VERIFY DIMENSIONS AND ORIENTATION.

“TYPICAL” MEANS IDENTICAL FOR CONDITIONS NOTED.

DO NOT SCALE DRAWINGS, DIMENSIONS GOVERN. VERIFY DIMENSIONS WITH FIELD CONDITIONS, IF DISCREPANCIES ARE DISCOVERED BETWEEN FIELD CONDITIONS AND DRAWINGS OR BETWEEN INDIVIDUAL DRAWINGS, CONTACT THE ARCHITECT FOR RESOLUTION BEFORE PROCEEDING.

HORIZONTAL DIMENSIONS INDICATED ARE TO/FROM FINISHED FACE OF CONSTRUCTION, EXCEPT AS NOTED.

VERTICAL DIMENSIONS ARE FROM TOP OF FINISHED FLOOR, (A.F.F.), UNLESS OTHERWISE NOTED.

IN THE EVENT OF CONFLICT BETWEEN DATA SHOWN ON DRAWINGS AND DATA SHOWN IN THE SPECIFICATIONS, THE SPECIFICATIONS SHALL GOVERN. DIMENSIONS NOTED ON DRAWINGS SHALL TAKE PRECEDENCE OVER SCALED DIMENSIONS. DETAIL DRAWINGS TAKE PRECEDENCE OVER DRAWINGS OF SMALLER SCALE. SHOULD THE CONTRACTOR AT ANY TIME DISCOVER AN ERROR IN A DRAWING OR SPECIFICATIONS, OR A DISCREPANCY OR VARIATION BETWEEN DIMENSIONS ON DRAWINGS AND MEASUREMENTS AT SITE, OR LACK OF DIMENSIONS OR OTHER INFORMATION, HE/SHE SHALL REPORT AT ONCE TO THE ARCHITECT FOR CLARIFICATION AND SHALL NOT PROCEED WITH THE WORK AFFECTED UNTIL CLARIFICATION HAS BEEN MADE.

THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING THE DIMENSIONS AND ELEVATIONS AT THE SITE. THE CONTRACTOR AND SUB-CONTRACTORS SHALL COORDINATE THE LAYOUT AND EXACT LOCATION OF ALL PARTITIONING, DOORS, ELECTRICAL/TELEPHONE OUTLETS, LIGHT SWITCHES AND THERMOSTATS WITH THE ARCHITECT IN THE FIELD BEFORE PROCEEDING WITH CONSTRUCTION.

THE CONTRACTOR SHALL CONTINUOUSLY CHECK ARCHITECTURAL AND STRUCTURAL CLEARANCES FOR ACCESSIBILITY OF EQUIPMENT AND MECHANICAL AND ELECTRICAL SYSTEMS. CONTRACTOR SHALL VERIFY THAT NO CONFLICTS EXIST IN LOCATIONS OF ANY AND ALL MECHANICAL, TELEPHONE, ELECTRICAL, LIGHTING, PLUMBING, AND SPRINKLER EQUIPMENT (TO INCLUDE ALL PIPING, DUCT WORK AND CONDUIT) AND THAT ALL REQUIRED CLEARANCES FOR INSTALLATION AND MAINTENANCE OF ABOVE EQUIPMENT ARE PROVIDED. NO ALLOWANCE OF ANY KIND WILL BE MADE FOR THE CONTRACTOR’S NEGLIGENCE TO NOTE UNFORESEEN MEANS OF INSTALLING EQUIPMENT INTO POSITION INSIDE STRUCTURE.

ALL WORK SHALL BE ERECTED AND INSTALLED PLUMB, LEVEL, SQUARE AND TRUE, AND IN PROPER ALIGNMENT.

COORDINATE AND PROVIDE APPROPRIATE STRUCTURAL BLOCKING/BACKING AND REINFORCING IN PARTITIONS BEHIND ALL WALL MOUNTED ITEMS.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR CHECKING CONTRACT DOCUMENTS, FIELD CONDITIONS AND DIMENSIONS FOR ACCURACY AND CONFIRMING THAT WORK IS AS SHOWN BEFORE PROCEEDING WITH CONSTRUCTION. CLARIFICATIONS REGARDING ANY CONFLICTS SHALL BE ACHIEVED PRIOR TO RELATED WORK BEING STARTED.

GENERAL CONTRACTOR SHALL VERIFY THAT NO CONFLICTS EXIST IN LOCATIONS OF ANY AND ALL MECHANICAL, TELEPHONE, ELECTRICAL, PLUMBING AND SPRINKLER EQUIPMENT (TO INCLUDE ALL PRICING, DUCT WORK AND CONDUIT) AND THAT ALL REQUIRED CLEARANCES FOR INSTALLATION AND MAINTENANCE OF ALL ABOVE EQUIPMENT ARE PROVIDED. WHAT ELEMENTS ARE TO BE EXPOSED OR CONCEALED SHALL BE DETERMINED AND REVIEWED WITH ARCHITECT PRIOR TO CONSTRUCTION PROCEEDING.

IF AT ANY TIME BEFORE COMMENCEMENT OF WORK, OR DURING PROCESS THEREOF, CONTRACTOR'S METHODS, EQUIPMENT OR APPLIANCES ARE INEFFICIENT OR INAPPROPRIATE FOR SECURING QUALITY OF WORK, OR RATE OF PROGRESS INTENDED BY CONTRACT DOCUMENTS, CITY MAY ORDER CONTRACTOR TO IMPROVE THEIR QUALITY OR INCREASE THEIR EFFICIENCY. THIS WILL NOT RELIEVE CONTRACTOR OR HIS SURETIES FROM THEIR OBLIGATIONS TO SECURE QUALITY OF WORK AND RATE OF PROGRESS SPECIFIED IN CONTRACT.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

TLIC

D

E

CHNSE AR ITEC

STAT EO F C ALIF O R NIA

N0. C33665

REN.

AR HLLA

BRNDO

N M S A

03-31-19

SCALE

PROJECT NO.

DATE

8106 TERRACE DRIVE, EL CERRITO, CA 94530707.297.6185 www.fogprojects.com

STAMP

CONSULTANT LOGO

RESTROOM RENOVATION

As indicated

10/2

0/20

17 1

0:14

:35

AM

16.2510/20/17

PROJECTINFORMATION

G0.01

A1.00 SITE PLANA2.00 EXISTING PLANA2.01 PROPOSED PLANA3.01 REFLECTED CEILING PLANA9.10 ENLARGED PLANS AND ELEVATIONS - TOILETA11.01 PARTITION TYPES & ACCESSIBILITY DETAILS

SHEETNUMBER SHEET NAME

G0.01 PROJECT INFORMATION

VICINITY MAP PROJECT LOCATION

PROJECT ADDRESS: 3102 DELTA FAIR BLVD, ANTIOCH CA 94509APN: 076-431-010ZONING: C-3PARCEL AREA: 85,378 SFGROSS BUILDING AREA: 13,000 SFPROJECT AREA: 6,500 SFNUMBER OF STORIES: 1SPRINKLERS: NONE

PROPERTY INFORMATION

PROJECT IS AN INTERIOR RENOVATION OF APPROXIMATELY 340 SF TO THE RESTROOM AREA OF A 6,500 SF TENANT SPACE IN A MULTI-TENANT BUILDING.- REMOVAL OF (E) PLUMBING FIXTURES- NEW PLUMBING FIXTURES AND ACCESSORIES- NEW FLOOR, WALL AND CEILING FINISHES AS NEEDED- NEW LIGHTING AND EXHAUST FANS AT RESTROOMS

SCOPE OF WORK DESCRIPTION

PROJECT DIRECTORYOWNER: OPPORTUNITY JUNCTION

Alissa Friedman3102 Delta Fair Blvd., Antioch, CA 94509Phone: [email protected]

ARCHITECT: FOG STUDIOBrandon Marshall, C-336658106 Terrace Dr., El Cerrito, CA 94530Phone: [email protected]

SHEET INDEX

No. Description DateISSUE FOR PERMIT 10/20/17

2402 SAN JOSE

2009 SOMERSVILLE RD

3102 DELTA FAIRDELTA FAIR BLVD

SAN JOSE DR

ACCESSIBLE PATH OF TRAVEL

SEPARATE TENANT (NOT IN SCOPE)

9' - 0

" 8' -

0"

18' - 0"

EXISTING ADA PARKING (NO WORK)

TLIC

D

E

CHNSE AR ITEC

STAT EO F C ALIF O R NIA

N0. C33665

REN.

AR HLLA

BRNDO

N M S A

03-31-19

SCALE

PROJECT NO.

DATE

8106 TERRACE DRIVE, EL CERRITO, CA 94530707.297.6185 www.fogprojects.com

STAMP

CONSULTANT LOGO

RESTROOM RENOVATION

1" = 20'-0"

10/2

0/20

17 1

0:14

:21

AM

16.2510/20/17

SITE PLAN

A1.00SCALE:

1" = 20'-0"1 SITE PLAN

No. Description DateISSUE FOR PERMIT 10/20/17

SEPARATE TENANT(NOT IN SCOPE)

150 SFOFFICE

145 SFOFFICE

145 SFOFFICE

145 SFOFFICE

145 SFOFFICE

585 SFHALL

93 SFOFFICE

89 SFOFFICE

396 SF

INTERNAREA

71 SFOFFICE

159 SFOFFICE

301 SFRECEPTION

706 SFKITCHEN

428 SFCLASSROOM

70 SFOFFICE

69 SFOFFICE

427 SFCLASSROOM

402 SFCLASSROOM

90 SFSTORAGE

163 SFSTORAGE

OFFICE191 SF

WOMEN'S126 SF

WOMEN'S54 SF

MEN'S71 SF

MEN'S72 SF 30 SF

JANITOR

REMOVE ALL (E) TOILET FIXTURES, PARTITIONS, LAVATORIES AND URINAL

REMOVE (E) DOORS, PATCH & FINISH WALLS TO MATCH (E) AS REQUIRED

LIMIT OF WORK18 S

FSE

RVER

TLIC

D

E

CHNSE AR ITEC

STAT EO F C ALIF O R NIA

N0. C33665

REN.

AR HLLA

BRNDO

N M S A

03-31-19

SCALE

PROJECT NO.

DATE

8106 TERRACE DRIVE, EL CERRITO, CA 94530707.297.6185 www.fogprojects.com

STAMP

CONSULTANT LOGO

RESTROOM RENOVATION

1/8" = 1'-0"

10/2

0/20

17 1

0:14

:22

AM

16.2510/20/17

EXISTING PLAN

A2.00SCALE:

1/8" = 1'-0"1 EXISTING PLAN

No. Description DateISSUE FOR PERMIT 10/20/17

70 SFOFFICE

69 SFOFFICE

427 SFCLASSROOM

402 SFCLASSROOM

428 SFCLASSROOM

163 SFSTORAGE

90 SFSTORAGE

706 SFKITCHEN

30 SFJANITOR

93 SFOFFICE

89 SFOFFICE

159 SFOFFICE

71 SFOFFICE

145 SFOFFICE

145 SFOFFICE

145 SFOFFICE

145 SFOFFICE

150 SFOFFICE

585 SFHALL

301 SFRECEPTION

53 SFUNISEX 1

54 SFUNISEX 2

71 SFUNISEX 3

72 SFUNISEX 4

18 S

FSE

RVER

396 SF

INTERNAREA

A9.101

2A

1A

3A

4A

1 NA4

171 SFOFFICE

145 SFOFFICE

150 SFOFFICE

145 SFOFFICE

145 SFOFFICE

145 SFOFFICE

585 SFHALL

396 SF

INTERNAREA

93 SFOFFICE

89 SFOFFICE

71 SFOFFICE

159 SFOFFICE

70 SFOFFICE

69 SFOFFICE

427 SFCLASSROOM

402 SFCLASSROOM

428 SFCLASSROOM

706 SFKITCHEN

90 SFSTORAGE

163 SFSTORAGE

53 SFUNISEX 1

18 S

FSE

RVER

30 S

FJA

NITO

R

72 SFUNISEX 4

71 SFUNISEX 354 SF

UNISEX 2

344 SFHALL

450 SFCLASSROOM

OCCUPANCY GROUP: BOCCUPANCY LOAD FACTOR: 20 SFOCCUPANT LOAD: 23

410 SFCLASSROOM

OCCUPANCY GROUP: BOCCUPANCY LOAD FACTOR: 20 SFOCCUPANT LOAD: 21

450 SFCLASSROOM

OCCUPANCY GROUP: BOCCUPANCY LOAD FACTOR: 20 SFOCCUPANT LOAD: 23

4376 SFOFFICE

OCCUPANCY GROUP: BOCCUPANCY LOAD FACTOR: 100 SFOCCUPANT LOAD: 44

330 SFRESTROOMS

OCCUPANCY GROUP: ACCESSORY

261 SFSTORAGE

OCCUPANCY GROUP: SOCCUPANCY LOAD FACTOR: 300 SFOCCUPANT LOAD: 1

145' - 4 5/8" MAX. DIAGONAL

= GREATER THAN 1/3 DIAGONAL

69' - 9 7/8" EXIT SEPARATION

MAX TRAVEL DISTANC = 58FT

OCCUPANT LOAD = 38DOOR CAPACITY = 160

OCCUPANT LOAD = 38DOOR CAPACITY = 320

OCCUPANT LOAD = 38DOOR CAPACITY = 320

71 SFSTORAGE

171 SFOFFICE

MIN. PLUMBING FIXTURES REQUIRED PER CPC TABLE 422.1 - B OCCUPANCY

MALE WC 1-50 = 1MALE URINAL 1-75 = 1MALE LAVATORY 1-75 = 1

MINIMUM PLUMBING FIXTURES REQURED FOR B OCCUPANCYLOAD FACTORS USED:

GROUP B (CLASSROOM) 30 SF 44 OCCUPANTSGROUP B 200 SF 22 OCCUPANTSGROUP S 5,000 SF 1 OCCUPANTTOTAL 67 OCCUPANTS (34 MALE, 34 FEMALE)

REQUIRED MALE WC 1MALE URINAL 1MALE LAVATORY 1FEMALE WC 3FEMALE LAVATORY 1

TOTAL WC 4TOTAL LAVATORY 2TOTAL URINAL 1

PROVIDED4 TOTAL UNISEX RESTROOMS:

4 WC4 LAVATORY1 URINAL

PLUMBING CALCULATIONS

FEMALE WC 31-50 = 3FEMALE LAVATORY 1-50 = 1

SOLID CORE DOORA

SEE DOOR SCHED.

DOOR TYPES GENERAL NOTESSEE PARTITION SCHEDULE FOR DEPTH OF ALL DOORS & WINDOWS IN GYP. BOARD WALLS.

INTERIOR DOORS - MAXIMUM EFFORT TO OPERATE DOORS SHALL NOT EXCEED 5 POUNDS.

FIRE DOORS - THE AUTHORITY HAVING JURISDICTION MAY INCREASE THE MAXIMUM EFFORT TO OPERATE FIRE DOORS TO ACHIEVE POSITIVE LATCHING, BUT NOT TO EXCEED 15 POUNDS.

TYPICAL JAMB DIMENSION IS 4" FROM ADJACENT PARTITION U.O.N.

WIDTH / HEIGHT DIMENSIONS ARE LEAF OPENING SIZE

1.

2.

3.

4.

5.

LEGENDMATERIALS:ALUM = ALUMINUMCLR = CLEARGL = GLASSPTD = PAINTEDSC = SOLID CORE WOODSTL = STEELST STL = STAINLESS STEELWD = WOOD

TLIC

D

E

CHNSE AR ITEC

STAT EO F C ALIF O R NIA

N0. C33665

REN.

AR HLLA

BRNDO

N M S A

03-31-19

SCALE

PROJECT NO.

DATE

8106 TERRACE DRIVE, EL CERRITO, CA 94530707.297.6185 www.fogprojects.com

STAMP

CONSULTANT LOGO

RESTROOM RENOVATION

As indicated

10/2

0/20

17 1

0:14

:28

AM

16.2510/20/17

PROPOSED PLAN

A2.01SCALE:

1/8" = 1'-0"1 PROPOSED PLAN

SCALE:

1/8" = 1'-0"2 OCCUPANCY & EXITING PLAN

OCCUPANCY - CODE ANALYSIS

NAME AREAOCCUPANCY LOAD

FACTOROCCUPANT

LOADCALCULATED

OCCUPANT LOADOCCUPANCY

GROUPRESTROOMS 330 SF ACCESSORYCLASSROOM 450 SF 20 SF 23 22.497476 BCLASSROOM 410 SF 20 SF 21 20.520217 BCLASSROOM 450 SF 20 SF 23 22.482487 BOFFICE 4376 SF 100 SF 44 43.76137 BSTORAGE 261 SF 300 SF 1 0.87101 S

112

PLUMBING ANALYSIS

NAME AREAOCCUPANCY

GROUPPlumbing Load

FactorPlumbing

Occupant LoadCalculated

Load FactorACCESSORYRESTROOMS 330 SF ACCESSORY 0 SF 0

330 SF 0BCLASSROOM 450 SF B 30 SF 15 14.998317CLASSROOM 410 SF B 30 SF 14 13.680145CLASSROOM 450 SF B 30 SF 15 14.988324OFFICE 4376 SF B 200 SF 22 21.880685

5686 SF 66SSTORAGE 261 SF S 5000 SF 1 0.052261

261 SF 16277 SF 67

DOOR SCHEDULE

1 UNISEX 4 A SC PTD 3' - 0" 7' - 0" 0' - 1 3/4" HM PTD SEE A11.01 FOR SIGNAGE2 UNISEX 3 A SC PTD 3' - 0" 7' - 0" 0' - 1 3/4" HM PTD SEE A11.01 FOR SIGNAGE3 UNISEX 2 A SC PTD 3' - 0" 7' - 0" 0' - 1 3/4" HM PTD SEE A11.01 FOR SIGNAGE4 UNISEX 1 A SC PTD 3' - 0" 7' - 0" 0' - 1 3/4" HM PTD SEE A11.01 FOR SIGNAGE5 STORAGE A SC PTD 3' - 0" 7' - 0" 0' - 1 3/4" HM PTD SEE A11.01 FOR SIGNAGE

No. Description DateISSUE FOR PERMIT 10/20/17

18 SFSERVER

53 SFUNISEX 1

54 SFUNISEX 2

71 SFUNISEX 3

72 SFUNISEX 4

30 SFJANITOR

344 SFHALL

585 SFHALL

301 SFRECEPTION

71 SFOFFICE 427 SF

CLASSROOM

70 SFOFFICE 69 SF

OFFICE

402 SFCLASSROOM

428 SFCLASSROOM

9' - 0" 9' - 0" 9' - 0" 9' - 0"

F1 F1F1

F1 F1

F1

CL1 CL1 CL1 CL1

(EXPOSED CEILING)

F2

706 SFKITCHEN

LIMIT OF WORK

71 SFSTORAGE

NEW PARTITION

EXISTING PARTITION

NOT IN SCOPE - ADJACENT TENANT

DUPLEX

GROUND FAULT INTERCEPT DUPLEX

S SWITCH

(E) EMERGENCY EXIT SIGN V.I.F.

EXHAUST FAN

LEGEND

GFI

F2

F1 RECESSED LED DOWNLIGHT - WET-LISTED

4FT LED UTILITY LIGHT

S DIMMABLE SWITCHD

DEDICATED CIRCUIT, THEATER LIGHTING

GYP BD CEILINGCL1

CL2 (E) 2X2 ACOUSTIC CEILING

TLIC

D

E

CHNSE AR ITEC

STAT EO F C ALIF O R NIA

N0. C33665

REN.

AR HLLA

BRNDO

N M S A

03-31-19

SCALE

PROJECT NO.

DATE

8106 TERRACE DRIVE, EL CERRITO, CA 94530707.297.6185 www.fogprojects.com

STAMP

CONSULTANT LOGO

RESTROOM RENOVATION

As indicated

10/2

0/20

17 1

0:14

:29

AM

16.2510/20/17

REFLECTED CEILINGPLAN

A3.01SCALE:

1/4" = 1'-0"1 REFLECTED CEILING PLAN

No. Description DateISSUE FOR PERMIT 10/20/17

7' - 10 3/4"7' - 1 3/4"7' - 6 1/2"

9' - 1

1/2"

9' - 1

1"

7' - 1

1/2"

1' - 6" 1' - 6"

30 SFJANITOR

53 SFUNISEX 1

54 SFUNISEX 2

71 SFUNISEX 3

72 SFUNISEX 4

7' - 6"

18 SFSERVER

REMOVE (E) PARTITIONS

RELOCATE (E) ELEC PANEL AS REQ'D

1' - 6"

12" MIN.

2A

1A

3A

4A

1 1 1

1

2

3 33

3

2 2

24 4

4

477

7

7

55

5

5

5' - 0"

59"

5' - 0" 5' - 0" 5' - 0"

A9.102

3

4

1' - 6" 1' - 6"1' - 6" 1' - 6"

A9.10 2SIM

3

4

11

11

1111

2' - 0

"

A9.106

8

7

1' - 6

"

12

A9.10

8

4SIM

5

18

18

18

5A

71 SFSTORAGE

1919

19 19

19

42"12" MAX.

24" MIN.

54" MIN.

7" - 9"

19" M

IN.34

"

1

3 2

16

15

14

1

3 2

34"

24" MIN.12" MIN.

36" MIN.10

4

0"

30"

40"

18"

17

16

TO O

PERA

BLE

PART

40" M

AX. H

T.

13

15

1

SHEET NOTES

2

3

4

5

6

7

8

ACCESSIBLE WATER CLOSET: MFR: KOHLER HIGHLINE K-3979 RIGHT HAND TRIP LEVER (AWAY FROM WALL)36" GRAB BAR42" GRAB BARACCESSIBLE LAVATORY: MFR: AMERICAN STANDARD LUCERNE WALL-HUNG

30"x48" REQUIRED CLEAR FLOOR SPACE AT LAVATORY OR ACCESSIBLE FIXTURE60"x59" REQUIRED CLEAR FLOOR SPACE AT WATER CLOSET60" DIAMETER WHEEL CHAIR TURNING CIRCLEGFI DUPLEX TO BE MIN 15" A.F.F. AND MAX 44" A.F.F.

9

10

11

SURFACE MOUNTED TOILET TISSUE DISPENSER

MIRROR3'-0" WIDE x 6'-8" HIGH DOOR WITH LEVER HANDLES, SEE 1/G1.10 & ACCESSIBILITY NOTES 4,5 & 6 ON G1.10.

WALL MOUNTED SOAP DISPENSER: MANUFACTURER: GOJO, MODEL: NXT SPACE SAVER. 40" MAX HT TO OPERABLE PARTS

URINAL - KOHLER BARDON HIGH EFFICIENCY, .125 GPF12

13

WALL MOUNTED SINGLE PAPER TOWEL DISPENSER: MANUFACTURER: BOBRICK, MODEL: B-2620

14

15

16

GENERAL NOTES1. SEE G0.01 FOR , SYMBOLS & ABBREVIATIONS AND PROJECT

GENERAL NOTES.

FLOOR TILE WITH COVED BASE, SEE ACCESSIBILITY NOTE 1 ON G2.10WATER-RESISTANT GYP BD

17 ACCESSIBLE PIPE WRAP18 SIGN TYPE 2, SEE 8/A11.01

2. SEE A11.01 FOR TYPICAL ACCESSIBILITY NOTES, SIGNAGE AND DOOR CLEARANCES.

19 SIGN TYPE 1, SEE 7/A11.01

16

CLR. KNEE & TOE SPACE9"

MIN

.MIN.

11"

27" M

IN.

29" M

IN.

34" M

AX.

MIN.

8"14

TO O

PERA

BLE

PART

S

40" M

AX. H

T.174

15

34"

42" 12" MAX.

1

3 2

15

14

19" M

IN. 7"-9"

54" MIN.10

4

17

16

13

40"

30"

18"

34" M

AX.

TO O

PERA

BLE

PART

S

40" M

AX.

CLR. KNEE & TOE SPACE

14

17

13MIN.

8"

29" M

IN.

34" M

AX. 7"

MIN

.

MIN.25"

TO O

PERA

BLE

PART

S

40" M

AX. H

T.

MIN.

11"

15

1611

34"

1

32

24" MIN.12" MIN.

36" MIN.

16

15

1

A9.102 FOR TYP

DIMENSIONS12

17" M

AX.

16

15

TLIC

D

E

CHNSE AR ITEC

STAT EO F C ALIF O R NIA

N0. C33665

REN.

AR HLLA

BRNDO

N M S A

03-31-19

SCALE

PROJECT NO.

DATE

8106 TERRACE DRIVE, EL CERRITO, CA 94530707.297.6185 www.fogprojects.com

STAMP

CONSULTANT LOGO

RESTROOM RENOVATION

As indicated

10/2

0/20

17 1

0:14

:32

AM

16.2510/20/17

ENLARGED PLANSAND ELEVATIONS -

TOILET

A9.10SCALE:

1/2" = 1'-0"1 ENLARGED RESTROOM PLAN

SCALE:

1/2" = 1'-0"2 INTERIOR ELEVATION - UNISEX 1 - WEST

SCALE:

1/2" = 1'-0"3 INTERIOR ELEVATION - UNISEX 1 - NORTH

SCALE:

1/2" = 1'-0"4 INTERIOR ELEVATION - UNISEX 1 - EAST

SCALE:

1/2" = 1'-0"6 INTERIOR ELEVATION - UNISEX 3 - WEST

SCALE:

1/2" = 1'-0"7 INTERIOR ELEVATION - UNISEX 3 - SOUTH

SCALE:

1/2" = 1'-0"8 INTERIOR ELEVATION - UNISEX 3 - NORTH

SCALE:

1/2" = 1'-0"5 INTERIOR ELEVATION - UNISEX 4 - WEST

No. Description DateISSUE FOR PERMIT 10/20/17

SECTION

PLAN

SECTION

1 LAYER 5/8" TYPE "X" GYPSUM BOARD EACH SIDE, TYP. U.O.N.

WD STUDS

ACOUSTIC BATT INSULATION AS SCHEDULED

T.O. SLAB

B.O. STR. ABV.

1 = 7/8" FURRING CHANNEL2 = 1 5/8" METAL STUD3 = 2 1/2" METAL STUD4 = 2X4 STUD6 = 2X6 STUD8 = 2X8 STUD

STUD SIZE DESIGNATION :

PARTITION TYPE TAG :

RATING: HOUR RATING AS INDICATED (N = NOT RATED)ADDITIONAL NOTES

STUD SIZE - GAUGE & SPACING PERSPAN TABLE ABOVE

ADDITIONAL NOTES

11

4A

PARTITION, SEE PLANS

PARTITION TYPE

A

A - PROVIDE ACOUSTIC BATT INSULATION & ACOUSTIC SEALANTB - GYPSUM BOARD 6" ABOVE CEILINGC - DEFLECTION CRITERIA OF L/360 REQUIREDD - MOISTURE-RESISTANT GYPSUM BOARD REQUIREDF - THERMAL INSULATION

ADDITIONAL NOTES :2-1/2" x 16 GA. TRACK CHANNEL STIFFENERS WELDED TO CONT. PL. AS SHOWN

CONT. 6" x 14 GA. PL. - MIN. TWO STUD BAYS#10 FLAT HEAD SHT. MTL. SCREWS @ MID HT. OF PL.MIN. 2-1/2" x 16 GA. STUDS OR AS SCHED.

F.T. WD. BLK. 12" MIN. LENGTH - SECURE TO STUDS W/ 2-1/2" x #14 WD. SCREWS

6" x 20 GA. BACKING PL. SECURED TO STUDS & BLK. W/ #14 WD. SCREWS

MIN. 2-1/2" x 20 GA. SCREW STUDS

TYPE A

TYPE B

1" LONG1/8"

PLAN-SECTION

1" LONG1/8"

TYPE 'B' BACKING PL. FOR ALL UPPER WALL HUNG CAB. (OVER TWO SHELVES) - WALL MTD. EQPT. UP TO MAX. WEIGHT OF 200 POUNDS/FOOT, HANDRAILS, GRAB BARS AT 250 POUNDS/POINT LOAD

TYPE 'A' BACKING PL. FOR UPPER WALL HUNG CAB. (UP TO TWO SHELVES), BASE CAB., FULL HT. CAB., FILM VIEWING CNTR., WALL HUNG EQPT., ETC. - MAX. WEIGHT = 80 POUNDS/FOOT.

1/4" MAX.1/4" MAX.

2 7/8"

60" M

IN.

2"

PROVIDE THIS ADDITIONAL SPACE WHEN DOOR IS EQUIPPED WITH BOTH A LATCH AND A CLOSER

3 5/8"

4"

24" MIN. CLR. AT EXTERIOR18" MIN. CLR. AT INTERIOR

DOOR CLEARANCES

LEVE

L ARE

A-MA

X SL

OPE

1:48

32" MIN.CLR.

PULL

SID

E

12"

8" MIN. PUSH SIDE48" MIN. WHEN NO LATCH AND CLOSER

OF HARDWAREHARDWARE NOTES:1. OPERABLE WITHOUT GRASPING.2. MAX. EFFORT FOR INTERIOR AND EXTERIOR DOORS - 5 LBS3. REQUIRED FIRE DOORS, MAX. EFFORT = 15 LBS.

THRESHOLD: 1/2" MAX. HEIGHT. CHANGE IN LEVEL BETWEEN 1/4" TO 1/2" SHALL BE BEVELED WITH A SLOPE NOT GREATER THAN 1:2

10" KICKPLATE OR SMOOTH FULL WIDTH OF DOOR

HARD

WAR

E HE

IGHT

34" M

IN - 4

4" M

AX

12

DOOR HEIGHT IS TO BE 7'-0"MIN. HIGH

SECTION AT DOOR/THRESHOLD

PUSH SIDE:

NOTES:

1. PER CBC 11B-404.2.8: IF A DOOR HAS A CLOSER THEN THE SWEEP PERIOD OF THE CLOSER SHALL BE ADJUSTED SO THAT FROM AN OPEN POSITION OF 90-DEGRESS, THE TIME REQUIRED TO MOVE THE DOOR TO A POSITION 12 DEGREES FROM THE LATCH IS 5 SECONDS MINIMUM.

2. ALL DOORS SHALL BE EQUIPPED WITH SINGLE-EFFORT, NON-GRASP HARDWARE (I.E., LEVER) CENTERED BETWEEN 34" AND 44" A.F.F..

NOTE: EXISTING ENTRANCE DOOR DOES NOT PROVIDE PUSH/PULL CLEARANCES

1. ALL FLOOR TILE TO HAVE MIN. STATIC COEFFICIENT OF FRICTION OF .6 AS DETERMINED BY ASTM C1028.

3. ALL NEW SWITCHES AND UPPER DUPLEXES TO BE MIN. 44" AND MAX. 48" ABOVE FINISH FLOOR.

2. ALL NEW DUPLEX OUTLETS TO BE MIN. 15" ABOVE FINISH FLOOR.

ACCESSIBILITY NOTES

4. DOOR HANDLES, PULLS, LATCHES, LOCKS AND OTHER PARTS OF DOORS SHALL COMPLY WITH CBC SECTION 11B-309.4. OPERABLE PARTS OF SUCH HARDWARE SHALL BE MIN 34" AND MAX 44" ABOVE FINISH FLOOR.

5. DOOR CLOSING SPEED SHALL COMPLY WITH CBC SECTION 11B-404.2.8. DOOR CLOSERS SHALL BE ADJUSTED SO THAT FROM AN OPEN POSITION OF 90 DEGREES, THE TIME REQUIRED TO MOVE THE DOOR TO A POSITION OF 12 DEGREES FROM THE LATCH IS 5 SECONDS MINIMUM.

6. THE FORCE FOR PUSHING OR PULLING OPEN A DOOR SHALL BE 5 POUNDS MAXIMUM.

ACCESSIBLE WC NOTES:A. FLUSH CONTROL 44" MAX FROM F.F. @ WIDE SIDEB. FLUSH CONTROL FORCE 5 POUND MAXC. FLUSH CONTROL SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, PINCHING OR TWISTING.D. TOILET SEAT SHALL BE A MAX. OF 2" HIGH.E. ADEQUATE GRAB BAR BACKING WILL BE INSTALLED IN THE WALLS TO RESIST

A FORCE OF 250 POUNDS IN ANY DIRECTION.

7.

8. ELECTRICAL DEVICE BOXES INSTALLED FOR ENVIRONMENTAL CONTROLS FOR USE BY OCCUPANTS (IF INSTALLED) MUST BE PLACED AT 48”, MAXIMUM, ABOVE THE FLOOR, TO THE TOP. THOSE DEVICES REQUIRING REACH OVER AN OBSTRUCTION MUST BE PLACED AT 44” OR LESS.

9. ELECTRICAL DEVICE BOXES FOR OUTLETS AND SWITCHES WILL BE PLACED NOT MORE THAN 48” TO TOP OF BOX AND NOT LESS THAN 15” TO BOTTOM OF BOX. THOSE DEVICES REQUIRING REACH OVER AN OBSTRUCTION MUST BE LOWERED TO 44” TO TOP OF BOX.

PHENOLIC PLASTIC PLAQUE, CHARCOAL COLOR

48" MIN AFF

TEXT RAISED 1/32" FROM SURFACE, WHITE PAINT -FONT: GILL SANS

60" MAX AFF

CONTRACTED GRADE 2 BRAILLE

RESTROOM

0' - 0

3/8"0'

- 0 5/

8"

RESTROOM

4"

7"

0' - 1

1/8"

18" X 18" SPACE CLEAR OF DOOR SWING, CENTERED ON TACTILE CHARACTERS

45°

DOOR OR OPENING

10"

10"

6"2 3/4"

6"

E.Q.

(3' -

0" M

AX)

E.Q.

(3' -

0" M

AX)

F.E.C.

5"

HINGE

STROBE LIGHT

DEADLOCK/BOLTTHERMOSTAT

LIGHT SWITCH

HARDWARE PER SCHEDULE

TELEPHONE OR DATA OUTLETPOWER OUTLET

FINISH FLOOR10" MIN. BOT. RAILAT GLAZED DOORS

LOCATE ADJACENT TO STRIKEOR SIDELIGHT WHERE OCCURS

6' - 8

"

4' - 0

"

SIGNAGE, WHERE OCCURS

58" M

IN., 6

0" M

AX.

15" M

IN

18" M

AX

15" M

IN48

" MAX

FIRE EXTINGUISHER TO BE LOCATED AT OR BELOW 48" ACCESSIBLE HEIGHT W/IN CABINET

PHENOLIC PLASTIC PLAQUE, 12" DIAMETER, CHARCOAL COLOR, 1/4" THICK

58" MIN -60" MAX AFF

OF SIGN

FONT: GILL SANS5/8" H, WHITE PAINT, TYP

EQUILATERAL TRIANGLE, 1/4" THICK, OVER CIRCLE: WHITE PAINT TO CONTRAST WITH CHARCOAL COLOR CIRCLE

RESTROOM

OF DOOR, SIGN AND BAR

3" HIGH PICTOGRAM, CHARCOAL COLOR, TYP

NOTES: 1. GEOMETRIC SYMBOLS ON TOILET ROOM

DOORS SHALL NOT CONTAIN RAISEDCHARACTERS, RAISED PICTOGRAMS OR BRAILLE

2. GEOMETRIC SYMBOLS ON TOILET ROOM DOORS SHALL CONTRAST 70% WITH THE DOOR COLOR

3. EDGES AND CORNERS OF THE GEOMETRIC SYMBOLS ON TOILET ROOM DOORS SHALL BE ROUNDED, CHAMFERED OR EASED.

TLIC

D

E

CHNSE AR ITEC

STAT EO F C ALIF O R NIA

N0. C33665

REN.

AR HLLA

BRNDO

N M S A

03-31-19

SCALE

PROJECT NO.

DATE

8106 TERRACE DRIVE, EL CERRITO, CA 94530707.297.6185 www.fogprojects.com

STAMP

CONSULTANT LOGO

RESTROOM RENOVATION

As indicated

10/2

0/20

17 1

0:14

:34

AM

16.2510/20/17

PARTITION TYPES &ACCESSIBILITY

DETAILS

A11.01

SCALE:

1 1/2" = 1'-0"1 PTN. TYPE 1 - NON-RATED FULL HT. PTN.

SCALE:

1 : 1- PTN. TYPES - PARTITION TYPES DESCRIPTION

SCALE:

1" = 1'-0"4 BACKING PLATE DETAIL, TYP.

SCALE:

3" = 1'-0"5 DOOR DISABLED ACCESS REQUIREMENTS

SCALE:

6" = 1'-0"7 TACTILE ROOM ID SIGN - TYPE 1

SCALE:

1/4" = 1'-0"10 TACTILE SIGNAGE MOUNTING DIAGRAM

SCALE:

1/2" = 1'-0"6 TYPICAL MOUNTING HEIGHTS AND LOCATIONS

SCALE:

6" = 1'-0"8 UNISEX RESTROOM DOOR SIGN - TYPE 2

No. Description DateISSUE FOR PERMIT 10/20/17