C1250 D5A
50
Diesel
Our energy working for you.™
1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
20.9 36.2 51.8 67.6 N.A. N.A. N.A. N.A.
79 137 196 256 N.A. N.A. N.A. N.A.
Standby rating
Combustion air, m3/min
2296
Prime
kW (kVA)
900 (1125)
Standby
kW (kVA)
1000 (1250)
N.A.
13.9:1
159
1500
Overspeed limit, rpm
Regenerative power, kWm
Cummins
Prime rating
159
KTA38G9
4-Cycle; 60° Vee; 12-Cylinder Diesel
Turbocharged and Aftercooled
N.A.
1089
Governor type
Starting voltage
Maximum fuel inlet temperature (°C)
Maximum fuel inlet restriction, mm Hg
Maximum air cleaner restriction, mm H2O
78.5
Lube oil capacity, L
Maximum fuel flow, L/hr
Engine manufacturer
Engine model
Piston speed, m/s
Compression ratio
Configuration
BMEP at set rated load, kPa
Aspiration
Bore, mm
L/hr
Engine
Gross engine power output, kWm
60
203
428
Fuel consumption
7.9
Ratings
Stroke, mm
Rated speed, rpm
Load
US gph
Fuel flow
114
Electronic
24 Volts DC
1800±50
86
Air
N.A.
©2007 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are
registered trademarks of Cummins Inc. “Our energy working for you.” is a trademark of Cummins Power
Generation.
APSB-1154-07 (9/07)
635
Model:
Frequency:
Fuel Type:
1250 kVA Standby
» Generator set data sheet
8/12/2019 Cummins c1250 d5a
http://slidepdf.com/reader/full/cummins-c1250-d5a 2/3
Open Enclosed
Dimensions
Our energy working for you.
TM
1128
Total heat rejection, BTU/min N.A.
Length "A"
76
Genset outline
212.4
Standby rating
Fan load, KWm 24
Exhaust
40
8990
Enclosed set standard dimensions, mm
www.cumminspower.com
©2007 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are
registered trademarks of Cummins Inc. “Our energy working for you.” is a trademark of Cummins Power Generation.
APSB-1154-07 (9/07)
4387
20' container
Enclosed set
Open set
Height "C"
Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.
N.A.
N.A.
Coolant capacity (with radiator), L
Cooling system air flow, m3/min @ 12.7mmH2O
37960
8615
Width "B"
* Weights represent a set with standard features. See outline drawing for weights of other configurations
Unit wet weight kgs
Unit dry weight kgs
336
Exhaust gas flow at set rated load, m3/min
Exhaust gas temperature,°C
Ambient design,°
C
Standard set-mounted radiator cooling
Maximum cooling air flow static restriction mmH2O 12.7
Prime rating
Maximum exhaust back pressure, mmHg
529
Weights
N.A.
N.A.
22282083
- -
Standard open set dimensions, mm
8/12/2019 Cummins c1250 d5a
http://slidepdf.com/reader/full/cummins-c1250-d5a 3/3
Feature code
-
0
0
Notes:
Single phase output
kW x 1000
Voltage
Our energy working for you.TM
2. Standby (S) and Prime (P) ratings.
1. Limited single phase capability is available from some three phase rated configurations. To obtain single phase
rating, multiply the three phase kW rating by the single phase factor. All single phase ratings are at unity power factor.
Prime (unlimited running time):
Applicable for supplying power
to varying electrical load for
unlimited hours. Prime Power is
in accordance with ISO 8528.
Ten percent overload capability
is available in accordance with
ISO 3046, AS 2789, DIN 6271
and BS 5514.
Voltage
E-Mail: [email protected]
kW x 1000Voltage x 1.732 x 0.8
TT International Tradepark
10 Toh Guan Road #07-01
See your distributor for more information.
Asia Pacific
Cummins Power Generation
Fax: (65) 6417 2399
Tel: (65) 6417 2388
www.cumminspower.com
©2007 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are
registered trademarks of Cummins Inc. “Our energy working for you.” is a trademark of Cummins Power Generation.
APSB-1154-07 (9/07)
0
Formulas for calculating full load currents:
Three phase output
Alternator data
0
0 0
Ratings definitions
0
Duty2
P7A
Temp rise
125/105Wye, 3 Phase 380-415VS/P
Alternator
00
Connection1
0 0
Standby:
Applicable for supplying power to
varying electrical load for the
duration of power interruption of a
reliable utility source. Emergency
Standby Power (ESP) is in
accordance with ISO 8528. Fuel
Stop power in accordance with ISO
3046, AS 2789, DIN 6271 and BS
5514.
Limited Time Running:
Applicable for supplying
power to a constant electrical
load for limited hours.
Limited Time Running Power
is in accordance with ISO
8528.
Base Load (Continuous):
Applicable for supplying power
continuously to a constant
electrical load for unlimited
hours. Continuous power in
accordance with ISO 8528, ISO
3046, AS 2789, DIN 6271 and
BS 5514.
0