CTR-Transformer Explosion Prevention and Fire Extinguishing System

TRANSCRIPT

  • INCREDIBLE SOLUTIONS

    CTR MANUFACTURING INDUSTRIES LTD

    CTR

    TRANSFORMER EXPLOSION PREVENTION AND FIRE EXTINGUISHING SYSTEM

  • FOR TRANSFORMER TANK PROTECTION

    FOR HIGHER RATING TRANSFORMER TANK PROTECTION WITH PLC, MIMIC AND SCADA

    FOR TRANSFORMER TANK, OLTC / CABLE BOX PROTECTION

  • l Reliable Dedicated system Saved over 4000 MVA of transformers from explosion

    System can be installed on existing transformers at site with minimal outage period.

    System can be tested on energised transformers, unlike the other systems.

    Multi signal activation, eliminates possibility of mal-operation Patented in over 80 countries.

    Low investment compared to other systems. Minimal post-fire and no secondary damage.

    Low maintenance and running cost compared to other systems.

    Fool proof design to avoid ingress of nitrogen due to climatic changes into energised transformer.

    Suitable for indoor,outdoor and unmanned substations. Models available to protect OLTC and cable box. Extinguishes external fire in bushing and/or radiator also.

    Back up provision ensures nitrogen injection for fail safe operation.

    Suitable for oil filled generator / furnace / rectifier / power transformers and reactors.

    Approved by leading transformer manufacturers and utilities worldwide.

    On receipt of required activating signals, depressurizing commences by draining of a predetermined quantity of oil. Simultaneously Nitrogen is injected under pressure at a pre-detemined flow rate to create a stirring action thereby bringing the temperature of top oil surface below ignition point. Additionally in case of fire, extinguishes within 30 seconds maximum. Nitrogen gas occupies the space created by oil drain and acts as an insulating layer between the top layer of oil in the transformer tank and oxygen in the atmosphere. Transformer Conservator Isolation Valve blocks the passage of oil and isolates conservator oil thereby preventing escalation of fire.

    l l

    l

    l

    l l

    l l

    l

    l

    l l

    l

    l

    l

    l

    TYPICAL INSTALLATION

  • Iecomposition of oil due to arcing

    oil surge / turbulance in Rapid

    pressure rise relay

    is achieved

    nternal arcing results in insulation failure and consequent imbalance of input and output currents

    leading to operation of differential relay. D results in generation

    of gases and consequent transformer tank leading to operation of

    and/or buchholz relay and / or pressure release valve (PRV). Immediate

    reduction of pressure by partially draining oil from the top side of transformer tank.

    Conservator oil is isolated simultaneously due to operation of TCIV. The drained oil is collected in

    TRANSFORMER CONSERVATOR ISOLATION VALVE (TCIV)

    BUCHHOLZ RELAY

    FIRE DETECTOR

    OIL DRAIN

    TRANSFORMER

    OPERATINGSIGNALSFROMCONTROLROOM /RELAYPANEL

    CUBICLE

    CONTROLBOX

    N2

    N2 RELEASEDEVICE

    PRESSURE RELIEF VALVE(PRV)

    CIVIL WORK

    DIFFERENTIAL RELAY

    BUCHHOLZ / OIL SURGE RELAY

    PRESSURE RELIEF VALVE

    RAPID PRESSURE RISE RELAY

    CONSERVATOR OIL ISOLATION BY TRANSFORMER CONSERVATOR

    ISOLATION VALVE (TCIV)OIL DRAIN

    MASTER TRIP / HV+LV CB TRIP

    NITROGEN INJECTION

    NITROGENINJECTION

    RAPIDPRESSURERISE RELAY

    (RPRR)

    COVEREDOIL PIT/TANK

    QUICK DEPRESSURISATION VALVE ASSEMBLY

    EXHIBIT 1A

    AUTO EXPLOSION PREVENTION MODE

  • AUTO EXTINCTION MODE

    5

    FIRE DETECTOR

    BUCHHOLZ /OIL SURGE RELAY

    OIL DRAIN

    MASTER TRIP / HV+LV CB TRIP

    NITROGEN INJECTION

    CONSERVATOR OIL ISOLATION BY TRANSFORMER CONSERVATOR

    ISOLATION VALVE (TCIV)

    PRESSURE RELIEF VALVE

    RAPID PRESSURE RISE RELAY

    Simultaneous with oil drain injection of nitrogen gas at a predetermined flow rate and pressure

    from the bottom side valves of the transformer tank. Stirring action by the nitrogen gas of the

    transformer oil reduces the temperature of the top layer of the oil eliminating the possibility of fire

    on the top surface of the oil. Continuous nitrogen injection for upto 45 minutes cools the oil to

    ambient temperature. Refer to exhibit 1B.

    BUCHHOLZ RELAY

    FIRE DETECTOR

    OIL DRAIN

    OPERATINGSIGNALSFROMCONTROLROOM /RELAYPANEL

    CUBICLE

    CONTROLBOX

    N2

    N2 RELEASEDEVICE

    PRESSURE RELIEF VALVE(PRV)

    TRANSFORMER

    NITROGENINJECTION

    RAPIDPRESSURERISE RELAY

    (RPRR)

    COVEREDOIL PIT/TANK

    CIVIL WORK

    QUICK DEPRESSURISATION VALVE ASSEMBLY

    EXHIBIT 1B

    TRANSFORMER CONSERVATOR ISOLATION VALVE (TCIV)

  • EXHIBIT 2A

    TYPICAL LOGIC 1

    Upon receipt of system activation signals, immediate draining of top layer of oil in the transformer tank commences reducing any p ressure in the transformer tank, the t op layer of oil being drained and collected in a covered oil pit / tank . Refer to exhibit 2B.

    TRANSFORMER CONSERVATOR ISOLATION VALVE (TCIV)

    BUCHHOLZ RELAY

    FIRE DETECTOR

    OIL DRAIN

    TRANSFORMER

    OPERATINGSIGNALSFROMCONTROLROOM /RELAYPANEL

    CUBICLE

    CONTROLBOX

    N2

    N2 RELEASEDEVICE

    PRESSURE RELIEF VALVE(PRV)

    NITROGENINJECTION

    COVEREDOIL PIT/TANK

    TRANSFORMER CONSERVATOR ISOLATION VALVE (TCIV)

    BUCHHOLZ RELAY

    FIRE DETECTOR

    OIL DRAIN

    TRANSFORMER

    OPERATINGSIGNALSFROMCONTROLROOM /RELAYPANEL

    CUBICLE

    CONTROLBOX

    N2

    N2 RELEASEDEVICE

    PRESSURE RELIEF VALVE(PRV)

    NITROGENINJECTION

    System will also operate in case of bushing failure or transformer tank rupture, since oil from conservator will flow at an abnormal rate resulting in operation of TCIV, which isolates the conservator oil preventing aggravation and spread of fire. Consequently buchholz relay operates due to non availability of oil in the relay. Refer to exhibit 2A.

    RAPIDPRESSURERISE RELAY

    (RPRR)

    COVEREDOIL PIT/TANK

    CIVIL WORK

    CIVIL WORK

    RAPIDPRESSURERISE RELAY

    (RPRR)

    QUICK DEPRESSURISATION VALVE ASSEMBLY

    QUICK DEPRESSURISATION VALVE ASSEMBLY

    EXHIBIT 2B

  • EXHIBIT 2C

    TRANSFORMER CONSERVATOR ISOLATION VALVE (TCIV)

    BUCHHOLZ RELAY

    FIRE DETECTOR

    OIL DRAIN

    OPERATINGSIGNALSFROMCONTROLROOM /RELAYPANEL

    CUBICLE

    CONTROLBOX

    N2

    N2 RELEASEDEVICE

    PRESSURE RELIEF VALVE(PRV)

    NITROGENINJECTION

    TRANSFORMER

    Simultaneous with oil drain, nitrogen gas is injected at a predetermined flow rate and pressure

    from the bottom side valves of the transformer tank. Stirring action by the nitrogen gas of the

    transformer oil reduces the temperature of the top layer of the oil extinguishing any fire on the top

    surface of the oil. Continuous nitrogen injection for upto 45 minutes cools the oil to ambient

    temperature. Refer to exhibit 2C.

    COVEREDOIL PIT/TANK

    RAPIDPRESSURERISE RELAY

    (RPRR)

    REMOTE MANUAL MODE

    EXTINGUISHING RELEASE SWITCH ON

    CONSERVATOR OIL ISOLATION BY TRANSFORMER CONSERVATOR ISOLATION

    VALVE (TCIV)

    OIL DRAIN

    MASTER TRIP / HV+LV CB TRIP

    NITROGEN INJECTION

    QUICK DEPRESSURISATION VALVE ASSEMBLY

    In case of an emergency, the system can also be operated in remote manual mode by breaking the

    glass window provided on the control box and by turning on extinguishing release switch to 'ON'

    position.

    CIVIL WORK

  • LOCAL MANUAL MODE

    In case of an unlikely event of failure of power source, the system can be still be operated manually from the cubicle.

    OPERATE ANOTHER LEVER FOR NITROGEN INJECTION

    CONSERVATOR OIL ISOLATION BY TRANSFORMER CONSERVATOR ISOLATION

    VALVE (TCIV)

    OPERATE FIRST LEVER FOR OIL DRAIN

    FIRE DETECTORBUCHHOLZ RELAY

    TRANSFORMER CONSERVATOR ISOLATION VALVE (TCIV)

    OIL DRAIN

    NITROGENINJECTION

    RAPIDPRESSURERISE RELAY

    (RPRR)TRANSFORMER

    OPERATINGSIGNALSFROMCONTROLROOM /RELAYPANEL

    CUBICLE

    CONTROLBOX

    N2

    N2 RELEASEDEVICE

    COVEREDOIL PIT/TANK

    PRESSURE RELIEF VALVE(PRV)

    OLTC

    TYPICAL LAYOUT OPTIONAL FOR OLTC PROTECTION

    QUICK DEPRESSURISATION VALVE ASSEMBLY

    CIVIL WORK

  • TYPICAL LAYOUT FOR OPTIONAL CABLE BOX

    FIRE DETECTORBUCHHOLZ RELAY

    TRANSFORMER CONSERVATOR ISOLATION VALVE (TCIV)

    OIL DRAIN

    NITROGENINJECTION

    RAPIDPRESSURERISE RELAY

    (RPRR) TRANSFORMER

    OPERATINGSIGNALSFROMCONTROLROOM /RELAYPANEL

    CUBICLE

    CONTROLBOX

    N2N2

    N2 RELEASEDEVICE

    COVEREDOIL PIT/TANK

    PRESSURE RELIEF VALVE(PRV)

    QUICK DEPRESSURISATIONVALVE ASSEMBLY

    Service engineers are available for supervision of system installation, commissioning and

    training. CTR warranty is valid, if system is commissioned by CTR representative

    authorised in writing. Worldwide representatives are available for spares and service.

    Marketing enquiry questionnaire form PTFS 1005 should be entered completely for

    prompt response and offering of most appropriate model. Operation and maintenance

    manual is supplied in English language, unless specifically requested for otherwise.

    Please also specify number of copies required both in digital and hard format and to

    whom these should be delivered.

    INSTALLATION AND COMMISSIONING

    CIVIL WORK

  • TESTIMONIALS

  • SOME INTERNATIONAL PATENTS

  • Depressurisation : Commences before pressure build up and

    consequent explosion

    Fire Extinguishing period : Maximum 30 seconds from commencement of

    N2 injection

    Fire detector heat : 141 C

    sensing temperature

    Transformer conservator : Settable between 60 and 100 litre per minute,

    isolation valve depending upon transformer and conservator size.

    Control Box : 110 V DC / 125V DC/220 V DC and 110 V AC/230 V AC

    Cubicle : 110 V AC / 230 V AC

    Cubicle :

    Dimensions in mm

    L B H

    250 MVA and above 1600 600 1900 600

    10 MVA to 249 MVA 1200 500 1900 500 2 MVA to 10 MVA 1200 500 1700 450

    Below 2 MVA 1200 500 1200 350

    Height includes 100 mm for Base

    Control Box : Dimensions in mm

    L B H

    0

    TECHNICAL HIGHLIGHTS

    Transformer rating

    Types Weight in Kgs

    Weight in Kgs

  • DMJ:fpPTFS.1005.D.0412.R2 TURNOVER

    Conservator pipe angle :mmConservator pipe dia :

    dg

    d=0g=0

    No

    Type DType C

    Yes

    Dimension :

    If yes : Arrangement

    Builtin onload Tapchanger :

    ca

    Type B

    Type A

    B =

    Main Dimensions of tank :

    Oil temp.indicator trip1 Nr. NOpotential free

    HV circuit breakers &LV circuit breakertrip, 1 Nr Each, NCpotential free

    Restricted Earthfault relay trip1 Nr. Nopotential free

    1 Nr. NO potential free

    Buchholz TripPRV Trip

    125 V 110 V 48 V 24 V

    230 V230 V

    110 V 50 Hz 60 Hz110 V 50 Hz 60 Hz

    Lts Oil Qty in Cable box : Lts

    Trs. Sr. Nr. :

    Voltage Ratio :Top cover Drg Nr.:(Enclosed)

    Enquiry Ref :

    Quantity :

    Oil Qty in tank :

    (Enclosed)

    Rating : MVA/MVARG.A. Drg Nr. :

    D.C. Supply available in Control Room :

    A.C. Supply available near Transformer :A.C. Supply available in Control Room :

    Customer :

    Work Order Nr/Tender Nr :

    End User :

    Manufacturer :

    MK ENQUIRY QUESTIONAIRE FORMSR.NR.

    POONACTR FIRE SYSTEMS DIVISION

    Oil Qty in Conservator :

    Confirm availability of spare contacts in relay panel :Differentialrelay trip1 Nr. NOpotential free

    1 Nr. NOpotential free

    Winding temp.indicator trip1 Nr. NOpotential free

    Master relay(86) Trip1 Nr. NOpotential free

    If numeric relay for Differential relay :Remarks :

    Self reset Manual reset

    H =

    a =

    c =

    mm

    mm

    mm

    mm

    B L

    H

    H

    B L

    d =

    g =

    mm

    mm

    Degree

    L = mm

    OLTC oil surgerelay trip1 Nr. NOpotential free

    Rapid Pressurerise relay trip1 Nr. NOpotential free

    Lts

    Tank

    Cable box

    Tank

    Cable box

    Tank

    Cable box

    Tank

    Cable box

    Tank

    Cable box

    Tank Cable box Tank Cable box

    220 V

  • Arrangement of Bushing :

    a) HV

    LV

    TV

    others

    HV

    LV

    TV

    others

    HV

    LV

    TV

    others

    p p

    b) c)

    p = mm p = mm

    d)

    p

    HV

    LV

    TV

    others

    e)

    p

    HV

    LV

    TV

    othersp = mm p = mm

    f)

    p

    p = mm

    HV

    LV

    TV

    others

    g) HV

    LV

    TV

    others

    HV

    LV

    TV

    others

    h)

    Cooling details :if OF type, NR. OF PUMPS :

    KW/HP :HEAD :FLOW :

    Installation : New Post

    Dist. from Trs. to Control Room through Cable Trench :Dist. from Relay panel to Control Room through Cable Trench : mtrs

    Valve Schedule Drawing to be attached : Drg. Nr :

    Availability of valves :Between Conservator and Buchholz Relay :Between Buchhloz Relay and Transformer :

    ** If valve not available enclose detailed pipe drawing for Tank and conservator along with buchholzvalve flange details.

    Available

    Available

    Not Available

    Not Available**

    **

    Oil pit/tank :Available Not Available Dist from Trs : mtrs

    Capacity : LtsDimensions ( L X B X D ) mm :

    mmSize of pipe connecting Trs. to Oil pit :

    Site Details :Sub-station layout drawing to be attachedSub-station foundation drawing to be attachedSub-station cable trence drawing to be attached

    Drg. Nr.Drg. Nr.Drg. Nr.

    Manuals : Nrs. Language : English Other ............

    Packing : Export DomesticInstructions required for packing :

    NAME :

    DESIGNATION :

    FOR CTR USE Quotation Nr. :

    SIGNATURE :

    DATE :

    STAMPORSEAL

    PTFS.1005.D.0412.R2DMJ:fp

    mtrs

    Tank Cable box

    Tank Cable box

    Tank Cable box

    Tank Cable box**

    **

    Qty

  • CTR : System : Cubicle /

    Depressurisation Equipment

    : Control box

    : Transformer conservator

    isolation valve (TCIV)

    : Required number of fire

    detectors

    : Signal box

    Other : Fire survival cable

    : Fire resistant low smoke

    (FRLS) cables

    : Pipe connections between

    Transformer and Cubicle

    : Pipe connections between

    cubicle and oil pit

    TRANSFORMER On transformer : Oil drain opening.

    MANUFACTURER / : Nitrogen injection openings

    BUYER : : Brackets for Fire detector

    fixing

    : TCIV fixing arrangement.

    : Signal box fixing

    arrangement.

    USER : Other : Civil work for plinth for

    Cubicle and supports. Oil pit/OGST

    : Potential free contacts in relay

    panel.

    : Power supply.

    : Topping up of transformer oil if

    SCOPE OF SUPPLY / WORK

  • FIRE SYSTEMS DIVISION CTR MANUFACTURING INDUSTRIES LTD

    NAGAR ROAD, PUNE 411014, INDIA.

    PHONE : 91 20 26633402/3/4/5. FAX : 91 20 [email protected] / [email protected]

    CTR Pune

    PM FS.1005APRIL 2012