csb400 series commercial / industrial pressure reducing ... descargas/csb400.pdf · d103123x012...
TRANSCRIPT
D10
3123
X01
2
CSB400 SeriesInstruction ManualForm 5836
June 2014
www.fisherregulators.com
CSB400 Series Commercial / IndustrialPressure Reducing Regulators
Table of Contents
Introduction .....................................................................1Specifi cations .................................................................2Principle of Operation .....................................................8Installation and Overpressure Protection ..................... 11Commissioning .............................................................15Adjustment....................................................................15Shutdown......................................................................17Maintenance and Inspection.........................................19Parts Ordering ..............................................................20Parts List.......................................................................21
Introduction
Scope of the Manual
This Instruction Manual provides installation, maintenance and parts ordering information for the CSB400 Series regulators. Instructions and parts lists for other equipment mentioned in this instruction manual are found in separate manuals.
Figure 1. Typical CSB400 Series Pressure Reducing Regulators
P1424
P1426 P1425
TYPICAL TYPE CSB400 REGULATOR
TYPICAL TYPE CSB403 REGULATOR WITH INTEGRAL TRUE-MONITOR™ REGULATOR
TYPICAL TYPE CSB404 REGULATOR WITH INTEGRAL TYPE VSX4 SLAM-SHUT MODULE
CSB400 Series
2
SpecificationsThe Specifications section lists the specifications for the CSB400 Series Regulators. The following information is stamped on the nameplate of CSB400 Series: Type and Class, Maximum Outlet Pressure and Spring Range.
Pressure RegistrationInternal, External or Dual (Internal and External)
Operating Temperature (TS)(1)(2)
According to PED Standards:All Types: -20 to 66°C / -4 to 150°FNon-PED with standard construction:Types CSB400/CSB404, CSB420/CSB424:-20 to 66°C / -4 to 150°F Types CSB450/CSB454(3):-30 to 66°C / -20 to 150°FNon-PED with low temperature construction:Types CSB400F/CSB404F(3), CSB420F/CB424F(3): -30 to 66°C / -20 to 150°F
Approximate WeightsWith Threaded body Type CSB400: 4.1 kg / 9 pounds Type CSB403: 9.1 kg / 20 pounds Type CSB404: 5.0 kg / 11 poundsWith Flanged Body: Add 4.1 kg / 9 pounds to threaded weights listed above
PED Conformity Statement and InformationThe CSB400 Product Series is in conformity with the Pressure Equipment Directive PED 97/23/EC. The exceptions to this previous statement are the Types CSB403 and CSB423. Both of these types are not yet certified to conform with the PED Directive.Pressure regulator does not require any supplementary upstream safety accessory for protection against overpressure compared with its design pressure PS, when upstream reducing station is sized for a max downstream incidental MIPd <= 1.1 PS.
PED Related InformationSee Table 2
Available ConfigurationsSee Table 1
Regulator Type: Differential Strength (DS)
Accuracy Class: Up to AC5 (depending on Outlet Pressure)
Lock-up Class: Up to SG10 (depending on Outlet Pressure)
Failure Mode: Fail Open (FO)
Body Sizes and End Connection StylesSee Table 5
Integral Strength (IS) Pressure Ratings(1)
See Table 3
Differential Strength (DS) Pressure Ratings and Flow and Sizing Coefficients(1)
See Table 4
Operating Pressure Ranges(1)
Regulator: See Table 6Integral True-Monitor™ Module: See Table 7Slam-Shut Module: See Table 8
Maximum Outlet Pressures(1)
Emergency: 4.0 bar / 58 psigTo Avoid Internal Parts Damage: Type CSB450: 1 bar / 14.5 psig above outlet pressure setting All other Types: 0.34 bar / 5 psig above outlet pressure settingOperating: 3.0 bar / 43.5 psig
Spring Case Vent Connection1 NPT
Orifice Size17.5 mm / 11/16 inch
1. The pressure/temperature limits in this Instruction Manual or any applicable standard limitation should not be exceeded. 2. Standard token relief set values listed in Table 8 are based on -20 to 60°C / -4 to 140°F. 3. Product has passed Emerson Process Management Regulator Technologies, Inc. (Regulator Technologies) testing for lockup, relief start-to-discharge and reseal down to -40°.
CSB400 Series
3
TYPE NUMBEROPTIONS
C S B 4PRESSURE CONSTRUCTION AND UPSTREAM MONITOR APPLICATIONS
0 Low Pressure Applications (Outlet Pressure: 17 to 100 mbar / 7 to 40 inches w.c.)
1 Low Pressure, Upstream Monitoring Applications(1)(3) (Outlet Pressure: 17 to 100 mbar / 7 to 40 inches w.c.)
2 Medium Pressure Applications (Outlet Pressure: 100 to 517 mbar / 40 to 208 inches w.c.)
3 Medium Pressure, Upstream Monitoring Applications(1)(3) (Outlet Pressure: 100 to 517 mbar / 40 to 208 inches w.c.)
5 High Pressure Applications(2) (Outlet Pressure: 0.50 to 3.0 bar / 7 to 43.5 psig)
OVERPRESSURE PROTECTION0 Without Overpressure Protection Module
0F Low Temperature Capability, Without Overpressure Protection Module
3 With Integral True-Monitor™ Module(4)
3F Low Temperature Capability, With Integral True-Monitor Module(4)
4 With Type VSX4 Slam-shut Module(5)
4F Low Temperature Capability, With Type VSX4 Slam-shut Module(5)
PRESSURE REGISTRATIOND Dual Registration (Best solution for quick changing loads)
E External Registration
I Internal Registration
RELIEFN No Relief
T Internal Token Relief
Example: Type number CSB424DT: Type CSB400 regulator constructed for medium pressure applications, with Type VSX4 slam-shut module, Dual pressure registration and Internal Token relief.1. Not available with Integral True-Monitor option.2. Not available with Integral True-Monitor or Token Relief option.3. Available with External Pressure Registration only.4. Reference Instruction Manual D103126X012 for information regarding the Type TM600 Integral True-Monitor module.5. Reference Instruction Manual D103127X012 for information regarding the Type VSX4 Slam-Shut module.
Table 1. Available Configurations
! WARNING
Failure to follow these instructions or to properly install and maintain this equipment could result in an explosion and/or fire causing property damage and personal injury or death.Fisher® regulators must be installed, operated, and maintained in accordance with federal, state, and local codes, rules and regulations and Regulator Technologies instructions. If the regulator vents gas or a leak develops in the system, service to the unit may be required. Failure to correct trouble could result in a hazardous condition.Call a gas service person to service the unit. Only a qualified person must install or service the regulator.
DescriptionCSB400 Series regulators are typically installed on industrial and commercial applications. See Table 1 for Available Configurations. Low, Medium and High outlet pressure constructions are available via Types CSB400, CSB420 and CSB450, respectively, that provide outlet setpoints ranging from 17 mbar to 3.0 bar / 7 inches w.c. to 43.5 psig. Also available are upstream monitoring configurations such as Types CSB410 and CSB430, which are installed upstream of the primary regulator to provide overpressure protection.
Types that include an “F” refer to the cold temperature construction of the base Type number. For example, the Type CSB404F provides a cold temperature construction of the Type CSB404. Refer to the Operating Temperature section found on the following page for additional information regarding temperature capabilities and refer to Table 7 for inlet pressure limitations. For types that include an “F”, refer to the base type number for general information such as Principles of Operation, Maintenance instructions, Warnings and Cautionary notes.
CSB400 Series
4
TYPE
MAXIMUM ALLOWABLE PRESSURE(1) / MAXIMUM EMERGENCY INLET PRESSURE MAXIMUM OPERATING INLET PRESSURE(1)
PS Pumax
bar psig bar psigCSB400, CSB400F, CSB404 and CSB404F
4.0 58 4.0 58
CSB420, CSB420F, CSB424 and CSB424F CSB450 and CSB454CSB410 and CSB414
CSB403, CSB403F, CSB423 and CSB423F CSB403 and CSB423
1. For the Integral Strength (IS) version, the maximum value of PS and Pumax should be similar to the PSD used for the Differential Strength (DS) version.
Table 3. Integral Strength (IS) Pressure Ratings
Table 4. Differential Strength (DS) Pressure Ratings and Flow and Sizing Coefficients
TYPE
SPECIFIC MAXIMUM ALLOWABLE
PRESSURE / MAXIMUM EMERGENCY OUTLET
PRESSURE
MAXIMUM OPERATING INLET
PRESSURE
MAXIMUM EMERGENCY
INLET PRESSURE(1)ORIFICE
SIZE
FLOW COEFFICIENTS
WIDE OPEN
IEC SIZING COEFFICIENTS
PSD Pumax PS
bar psig bar psig bar psig mm Inch Cg Cv C1 XT FD FL
CSB400F and CSB404F
4.0 58
6.0 87 12.0 174
17.5 11/16 428 11 43 1.16 0.84 0.90
CSB403F and CSB423F 6.0 87 10.0 145CSB403 and CSB423
10.0 145 10.0 145CSB410 and CSB414CSB430 and CSB434CSB400 and CSB404
10.0 145 12.0 174CSB420F and CSB424F
CSB420 and CSB42416.0 232 20.0 290
CSB450 and CSB4541. If ordered with a PN 16 flanged connection, PS rating is a maximum of 16.0 bar / 232 psig. PS rating may be lower than 16.0 bar / 232 psig as indicated by this table.
Figure 2. CSB400 Series Regulator, Slam-shut and Integral True-Monitor™ Nameplates and Labels
PATENTPENDING TS
REGULATOR SLAM SHUT SERIAL NO.
TEMP CLASS DOM
PS FLUID GROUP CAT LOC Std:
EN
334
TYPE PSD
Pumax PmaxMatl
Wds Case
Failure Mode
REG
ULA
TOR
Std:
EN
1438
2SL
AM
SH
UT
RELAIS Pu MaxRELAY Max IN
TYPE PSD CLASS
Wdso WdsuOP range UP range
MATL P maxCASE Max OUT
DN SEAT BODY
TYPE NO.
PATENT PENDING DOMLOC
MAX EMEROUT OUT
MAX OP
MAX IN ORIFICE SPG RANGERELIEF
SERIAL NO.
PN MATL0062 PED
mfg
: Cha
rtre
s,
Fra
nce
PED
mfg
: Cha
rtre
s,
Fra
nce
REGULATOR NAMEPLATES
SLAM-SHUT NAMEPLATE INTEGRAL TRUE-MONITOR NAMEPLATE
PATENTPENDING TS
REGULATOR SLAM SHUT SERIAL NO.
TEMP CLASS DOM
PS FLUID GROUP CAT LOC Std:
EN
334
TYPE PSD
Pumax PmaxMatl
Wds Case
Failure Mode
REG
ULA
TOR
Std:
EN
1438
2SL
AM
SH
UT
RELAIS Pu MaxRELAY Max IN
TYPE PSD CLASS
Wdso WdsuOP range UP range
MATL P maxCASE Max OUT
DN SEAT BODY
TYPE NO.
PATENT PENDING DOMLOC
MAX EMEROUT OUT
MAX OP
MAX IN ORIFICE SPG RANGERELIEF
SERIAL NO.
PN MATL0062 PED
mfg
: Cha
rtre
s,
Fra
nce
PED
mfg
: Cha
rtre
s,
Fra
nce
Table 2. PED Information
TYPE DESCRIPTION PED CATEGORY FLUID GROUPCSB400, CSB400F, CSB410, CSB420,
CSB420F, CSB430 and CSB450 Base regulator I Groups 1 and 2 according to PED 97/23/EC, 1st and 2nd family gas according to EN 437 or other
gases (compressed air, nitrogen). The gas must be non-corrosive, clean
(filtration on inlet side necessary) and dry.
CSB404, CSB404F, CSB414, CSB424, CSB424F, CSB434 and CSB454 Regulator with Slam-Shut Module IV
European EN Reference Standards EN 334, EN 14382
CSB400 Series
5
Table 6. CSB400 Series Primary Regulator Outlet Pressure Ranges
Table 7. Primary Regulator and Integral True-Monitor™ Outlet Pressure Ranges
TYPEOPERATING PRESSURE
RANGES, WdPART
NUMBERSPRINGCOLOR
SPRING WIRE DIAMETER SPRING FREE LENGTH
mbar Inch w.c. mm Inch mm Inch
CSB400, CSB400F, CSB403, CSB403F, CSB404, CSB404F,
CSB410 and CSB414
17 to 24 6.8 to 9.6 GE30191X012 Pink 2.03 0.080 152 6.0024 to 35 9.6 to 14 GE43955X012 Orange Stripe 2.19 0.086 110 4.3535 to 60 14 to 24.1 GE30201X012 Dark Green 3.23 0.127 110 4.35
54 to 100 21.7 to 40 GE30202X012 Tan 2.85 0.112 127 5.00CSB420, CSB420F, CSB423, CSB423F,CSB424, CSB424F,
CSB430 and CSB434
100 to 160 1.45 to 2.3 psig GE35081X012 Purple Stripe 3.86 0.152 124 4.90
138 to 300 2.0 to 4.4 psig GE30192X012 Dark Blue 4.27 0.168 118 4.65276 to 517 4 to 7.5 psig GE33121X012 Red 4.93 0.194 118 4.65
CSB450 and CSB454500 mbar to 1 bar 7.3 to 14.5 psig GE30203X012 Light Blue 5.59 0.220 102 4.00
1 to 3 bar 14.5 to 43.5 psig GE30204X012 Light Green 6.73 0.265 100 3.95
TYPE
PRIMARY REGULATOR INTEGRAL TRUE-MONITOR
Factory Setpoint Set Pressure RangeColor P/N
Factory Token Relief Set(1) Factory Setpoint(1) Spring RangeColor P/N
mbar psig mbar psig % of REG. Set mbar psig mbar psig mbar psig
CSB403 and
CB403F
20 8 in w.c. 17 to 24 6.8 to 9.6 in w.c. Pink GE30191X012
No Token Relief 37 15 in w.c. 30 to 52 12 to 21 in w.c. Blue GE30189X012
170% 35 14 in w.c.52 21 in w.c. 45 to 75 18 to
30 in w.c. Green GE30196X012
30 12 in w.c. 24 to 35 9.6 to 14 in w.c.
Orange Stripe GE43955X012
No Token Relief
150% 45 18 in w.c.70 1 65 to 99 26 to
40 in w.c. Orange GE30225X012
50 20 in w.c. 35 to 60 14 to 24 in w.c.
Dark Green GE30201X012
No Token Relief
140% 70 1103 1.5 97 to 200
1.4 to 2.9 Black GE30190X01269 1 54 to 100 0.78 to 1.45 Tan GE30202X012
No Token Relief
130% 90 1.3 138 2 97 to 200
CSB423 and
CB423F
138 2 100 to 160 1.45 to 2.3 Purple Stripe GE35081X012
No Token Relief 172 2.5 97 to 200
130% 180 2.6 241 3.5 197 to 255 2.6 to 3.7 Purple GE35081X012
207 3 138 to 300 2.0 to 4.4 Dark Blue GE30192X012
No Token Relief 276 4248 to 414 3.6 to 6 Dark
Blue GE30192X012125% 260 3.8 345 5
345 5 276 to 517 4 to 7.5 Red GE33121X012No Token Relief 414 6
352 to 517 5.1 to 7.5 Red GE33121X012125% 430 6.25 448 6.5
1. Recommended minimum Integral True-Monitor setpoints shown.
Table 5. Body Sizes, Material, End Connections and Pressure Ratings
BODY MATERIAL INLET SIZE, NPS OUTLET SIZE, NPS END CONNECTION FACE-TO-FACE DIMENSION BODY PRESSURE RATINGmm Inch bar psig
Ductile Iron
1 1
NPT
100 4
20.0 290
1-1/4 1-1/4 114 4.51-1/2 1-1/2 114 4.5
2 2 127 51 1
Rp
100 41 1-1/4 114 4.5
1-1/4 1-1/4 114 4.51-1/2 1-1/2 114 4.5
2 2 127 5
DN 50 / 2 DN 50 / 2CL150 FF 254 10PN 10/16 254 10
16.0 232DN 40 / 1-1/2(1) DN 40 / 1-1/2(1) PN 16 Slip-On 184 7.24
1 2-1/4 Rp x GAZ 105 4.1
20.0 290WCC Steel
1 1NPT
100 41-1/4 1-1/4 114 4.51-1/2 1-1/2 114 4.5
1 1Rp
100 41-1/4 1-1/4 114 4.51-1/2 1-1/2 114 4.5
1. Uses Rp 1-1/2 x 1-1/2 threaded body with PN 16 slip-on flanges.
CSB400 Series
6
Table 8. Regulator and Slam-shut OPSO and UPSO Pressure Ranges
Example: If a non-standard setpoint is needed, see the following example for the proper use of Table 8. Non-standard setpoint = 140 mbar / 2 psig, using the value presented above, the factory set of the token relief will be 1.3 x 140 = 182 mbar / 2.6 psig. The factory OPSO and UPSO set pressures are 165% and 50% of the non-standard setpoint, respectively. The resulting settings are: OPSO = 231 mbar / 3.4 psig and UPSO = 70 mbar / 1 psig.
TYPE
REGULATOR SLAM-SHUT MODULE
Set Pressure Range
Standard Setpoints
Token Relief Set(1)(2)
Available Token Relief
Range Shown as a % of Regulator Setpoint
Overpressure Shutoff (OPSO) Underpressure Shutoff (UPSO)
Minimum Required
Difference between Token
Relief and OPSO Set
Standard OPSO Set
Values(1) Pdso
OPSO Set Range as a % of Regulator
Setpoint
Standard UPSO Set
Values(1) Pdsu
UPSO Set Range as a % of Regulator
Setpoint
mbar psig mbar psig mbar psig Min(2) Max mbar psig mbar psig Min Max mbar psig Min Max
CSB404, CSB404F
and CSB414
17 to 24
0.25 to 0.35
20 0.29 34 0.49170% 215% 8 0.12
43 0.62215% 270%
10 0.1550% 56%
21 0.30 36 0.52 45 0.65 11 0.16
24 to 35
0.35 to 0.51
27 0.39 41 0.59
150% 160% 10 0.14
51 0.74
190% 200%
14 0.20
50% 60%30 0.44 45 0.65 57 0.83 15 0.22
35 0.50 53 0.76 67 0.96 18 0.26
35 to 60
0.51 to 0.87
50 0.70 70 1.0140% 158% 16 0.23
90 1.3180% 200%
25 0.3650% 70%
60 0.87 84 1.2 108 1.57 30 0.44
54 to 100
0.8 to 1.5
75 1.10 98 1.4130% 140% 20 0.29
128 1.85170% 190%
38 0.5450% 70%
100 1.5 130 1.9 170 2.47 50 0.73
CSB424, CSB424F
and CSB434
100 to 160
1.5 to 2.3
150 2.2 195 2.8130% 140% 40 0.58
248 3.59165% 175%
75 1.150% 70%
160 2.3 208 3.0 264 3.83 80 1.2
138 to 300
2.0 to 4.4 300 4.4 375 5.4 125% 140% 50 0.73 450 6.53 150% 165% 150 2.2 50% 70%
276 to 517
4.0 to 7.5 500 7.3 625 9.1 125% 140% 60 0.87 700 10.2 140% 180% 250 3.6 50% 70%
CSB454(3)
500 to 1000
7.3 to 14.5 1000 14.5 - - - - - - - - - - - - - - - - - - - - - - - - 1320 19.2 112% 140% 500 7.3 50% 70%
1000 to 3000
14.5 to 43.5
1200 17.4 - - - - - - - - - - - - - - - - - - - - - - - - 1600 23.2 112% 133% 600 8.7
50% 70%1500 21.6 - - - - - - - - - - - - - - - - - - - - - - - - 1900 27.6 112% 127% 750 10.9
2000 29.0 - - - - - - - - - - - - - - - - - - - - - - - - 2400 34.8 112% 120% 1000 14.5
3000 43.5 - - - - - - - - - - - - - - - - - - - - - - - - 3400 49.3 112% 113% 1500 21.8
1. Standard factory set shown. Factory set is at the Minimum value of the range indicated. Range indicated is a percentage of Setpoint. Percentage indicated is based on the Set Pressure Range in which that setpoint resides. If non-standard sets are required, adherence must be made to constraints shown in Table 7, including Token Relief Set Range, OPSO and UPSO set range and Minimum Required difference between Token Relief and OPSO Set.
2. Minimum Token Relief values apply to -20 to 60°C / -4 to 140°F service temperatures. For service below -20°C / -4°F, add 8 mbar / 0.12 psig to the minimum Token Relief value listed.3. Token Relief is not available for the Type CSB454.
CSB400 Series
7
Table 9. CSB400 Series Dimensions
BODY SIZE, NPS BODY END CONNECTION STYLE
FACE-TO-FACE DIAMETER (A) PITOT TUBE (B)
mm Inch mm Inch
1
NPT or Rp
100 4
97 3.8
1-1/4 114 4.5
1-1/2 114 4.5
2 127 5
DN 50 / 2 CL150 FF or PN 10/16 254 10
1 x 1-1/4 Rp 114 4.5
1 x 2-1/4 Rp x GAZ 105 4.1 20 0.8
DN 40 / 1-1/2 PN 16 Slip-On 184 7.2 97 3.8
Figure 3. CSB400 Series Dimensions
1. MAXIMUM SPRING REMOVAL CLEARANCE FOR BOTH THE PRIMARY REGULATOR AND INTEGRAL TRUE-MONITOR IS 158 mm / 6.2 inches.2. MAXIMUM SPRING REMOVAL CLEARANCE FOR THE SLAM SHUT IS 80 mm / 3.1 inches.
B SLAM-SHUTMODULE
TRUE-MONITOR™MODULE
249 /9.81
171 /6.72
275 /10.81
291 /11.46
205 /8.09
208 /8.18
146 /5.77
54 /2.13
45 /1.79
307 /12.08
SPRING REMOVAL(2)
151 /5.95
A/2
A
SPRINGREMOVAL(1)
A
A/2
A
A/2 A/2
A A
A/2
1 NPTSCREENED
VENT
mm / INCHGE34270
152 /5.97
CSB400 Series
8
Figure 4. Type CSB400DT Dual Registered Regulator Operational Schematic
Principle of Operation
Type CSB400 Base Regulator Operation
Refer to Figure 4. When downstream demand decreases, the pressure under the regulator diaphragm increases. This pressure overcomes the regulator setting (which is set by the regulator control spring). Through the action of the pusher post assembly, lever and valve stem, the valve disk moves closer to the orifice and reduces gas flow. If demand downstream increases, pressure under the regulator diaphragm decreases. Spring force pushes the pusher post assembly downward, the valve disk moves away from the orifice, and the gas flow increases downstream as the regulator opens in response to the decreased pressure underneath the regulator diaphragm.
Type numbers with a “T”, for example, Type CSB400IT, provide a token or low-capacity relief. The Token relief provides relief from minor overpressure caused by nicks or dents on the orifice or by thermal expansion of gas in the downstream line. Token relief also provides a token or signal, in the form of odor, that an overpressure situation is occurring.
Additional overpressure protection options include Types CSB403 and CSB423, which offer True-Monitor™ protection provided by an integral monitor module installed on the inlet side of the valve body. This Integral True-Monitor assumes control of the pressure to the downstream system should the primary regulator fail to regulate. The Types CSB404, CSB424 and CSB454 are examples of CSB400 Series configurations that offer a slam-shut module that shuts off the flow of gas to the downstream system in the event of outlet pressure rising above or falling below the predefined levels due to a failure.
Optional token relief is available, which acts as a low-capacity internal relief valve to relieve minor overpressure situations due to nicks or other minor damage to the orifice or disk, or due to thermal expansion of the downstream system.
Internal, external or dual outlet pressure registration is available. Constructions with dual or external registration require an external control line / sense line. For quick changing loads, dual sense is recommended as it provides the quickest response time.
TOKEN RELIEF SPRING
EXTERNAL CONTROL LINE(SENSE LINE)
PUSHER POST
REGULATOR CONTROL SPRING
LEVER
VALVE STEM
BALANCED PORT ASSEMBLY
REGULATOR ORIFICE
REGULATOR DISK
REGULATORADJUSTING SCREW
M1143
INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE
CSB400 Series
9
Figure 6. Type CSB404ET Externally Registered Regulator and Slam-shut Operational Schematic
INLET PRESSUREOUTLET PRESSURE
ATMOSPHERIC PRESSURE
M1146
Figure 5. Type CSB403IT Internally Registered Primary Regulator with Externally Registered Integral True-Monitor™ Operational Schematic
M1145
INLET PRESSURE
OUTLET PRESSURE
ATMOSPHERIC PRESSURE
WIDE-OPEN INTEGRAL TRUE-MONITOR REGULATOR PRIMARY REGULATOR
TYPE VSX4 SLAM-SHUT MODULE PRIMARY REGULATOR
EXTERNAL CONTROLLINE (SENSE LINE)
PRESSURE RETAINING PLUG (DO NOTREMOVE WHILE UNIT IS PRESSURIZED)
MONITOR ADJUSTING SCREW
REGULATOR ORIFICE
REGULATOR ADJUSTING SCREW
REGULATOR CONTROL SPRING
MONITOR CONTROL SPRING
MONITOR DISK
MONITOR LEVER
MONITOR VALVE STEM
MONITOR OPENING SPRING
BALANCED PORT ASSEMBLY
REGULATORVALVE STEM
REGULATORLEVER REGULATOR
PUSHER POST
TOKEN RELIEF SPRING
MONITOR ORIFICE
OPSO ADJUSTING SCREWUPSO ADJUSTING SCREW
UPSO SPRING
SENSE BLOCKING SCREW
SLAM-SHUTORIFICE
OPSO SET SPRING
RESET KNOBSLAM-SHUT DISK
VENT
REGULATOR CONTROL SPRING
REGULATOR ADJUSTING SCREW
REGULATOR ORIFICE
VALVE STEM
LEVER
EXTERNAL CONTROLLINE (SENSE LINE)
TOKEN RELIEF SPRING
PROXIMITY SWITCH PLUG
CSB400 Series
10
Figure 7. CSB400 Series Regulator Installed with the Vent Pointed Downward and with a Type 289H Relief Valve for High Capacity Relief
Type CSB403 Integral True-Monitor™ OperationType CSB403 combines the operation of a conventional two-regulator wide-open monitor set into one body, see Figure 5. The Integral True-Monitor is installed on the inlet side of the body and serves to throttle flow and maintain an acceptable downstream pressure in the case where the primary regulator ceases to regulate downstream pressure. During normal operation the Integral True-Monitor is in a wide-open state as its setpoint is set higher than the primary regulator. See Table 7 for guidance regarding the setpoints of the regulator and associated Integral True-Monitor sets. If the downstream pressure should rise to the setpoint of the Internal Monitor due to a loss of pressure control by the primary regulator, the Integral True-Monitor will assume control and regulate the flow to the downstream system. If token relief is present, it will relieve a small amount of gas to the atmosphere as an indication that the Integral True-Monitor is controlling the downstream pressure. The Type CSB403 provides the option of internal or external downstream pressure registration. External registration requires a downstream sensing line. See Figure 9 for guidance regarding installation of the downstream control line. Refer to the Type TM600 Instruction Manual for additional details of Integral True-Monitor operation.
Type CSB404 Slam-shut OperationThe Type VSX4 slam-shut module on the Type CSB404 regulator is a fast acting shut-off device that provides overpressure (OPSO) or over and underpressure (OPSO / UPSO) protection by completely shutting off the flow of gas to the downstream system. See Table 8 for guidance regarding the typical setpoints of the regulator and associated slam-shut OPSO and also the combined OPSO and UPSO setpoints. The Type VSX4’s actions are independent of the Type CSB404 regulator and of variations to the inlet pressure. The Type VSX4 comes standard with external downstream pressure registration, with the option for internal registration only on the Rp 1 x 2-1/4 GAZ body. External registration requires a downstream sensing line. See Figure 10 for guidance regarding installation of the downstream control line.
The Type VSX4 shut-off disk is normally in the open (reset) position, see Figure 6. If the downstream pressure below the slam-shut diaphragm increases (or decreases) until it reaches the slam-shut setpoint, this diaphragm moves upward (or downward) to release the trip mechanism which allows the spring force on the stem to push the disk against the seat, shutting off all gas flow. To reset the slam shut after gas has been shut off, refer to the Type VSX4 Instruction Manual for additional details.
CSB400 SERIES REGULATOR
REGULATOR VENT POINTED DOWNWARD
PROTECT VENT PIPE WITH RAIN CAP
NPS 2 TYPE 289H RELIEF VALVE
GE27692
CSB400 Series
11
In order for the Underpressure Shutoff (UPSO) of any slam shut to be triggered, the downstream pipe pressure must drop below the UPSO setpoint. In the case of a downstream line break, numerous factors can prevent the downstream pipe pressure from decreasing below the slam-shut UPSO setpoint. These factors include the distance of pipe to the break, the diameter of the pipe, size of the break and the number of restrictions, such as valves, elbows and bends, downstream of the regulator and/or slam-shut device. Due to these factors additional protections should be installed to stop flow in the event of a line break.
Installation and Overpressure ProtectionInstall in accordance with provisions of EN 12186 / EN 12279.
! WARNING
Personal injury or system damage may result if this regulator is installed, without appropriate overpressure protection, where service conditions could exceed the limits given in the Specifications section and/or regulator nameplate. Regulator and equipment installation should be adequately protected from physical damage.
All vents should be kept open to permit free flow of gas to the atmosphere. Protect openings against entrance of rain, snow, insects or any other foreign material that may plug the vent or vent line. On outdoor installations, point the spring case vent downward to allow condensate to drain, see Figures 7 through 10. This minimizes the possibility of freezing and of water or other foreign materials entering the vent and interfering with proper operation.
For the Type CSB403 with Integral True-Monitor™ or the Type CSB404 with Slam shut, point the vents of both the primary regulator and Integral True-Monitor or slam shut downward to allow condensate to drain. From the factory, the Integral True-Monitor or slam shut will always point in the same direction as that of the primary regulator.
Under enclosed conditions or indoors, escaping gas may accumulate and be an explosion hazard. In these cases, the vent should be piped away from the regulator to the outdoors.
In case of complete disassembly of the equipment (body included) from the pipeline, care must be taken not to bend, hit or otherwise damage the pitot tube (key 83 Figure 15) that protrudes beyond the body outlet. Damage to the pitot tube could result in inaccurate internal pressure registration and loss of regulation quality.
CAUTION
CSB400 Series regulators have an outlet pressure rating lower than their inlet pressure rating. If actual inlet pressure can exceed the outlet pressure rating, outlet overpressure protection is necessary. However, overpressuring any portion of the regulators beyond the limits in the Specifications section may cause leakage, damage to regulator parts or personal injury due to bursting of pressure-containing parts.
Some type of external overpressure protection should be provided to the CSB400 Series if inlet pressure will be high enough to damage downstream equipment. Common methods of external overpressure protection include relief valves, monitoring regulators, shut-off devices, and series regulation.
If the regulator is exposed to an overpressure condition, it should be inspected for any damage that may have occurred. Regulator operation below the limits specified in the Specifications section and regulator nameplate does not preclude the possibility of damage from external sources or from debris in the pipeline.
CSB400 Series
12
Figure 8. Type CSB400 “Series Monitor” Regulator Downstream Control Line Installation
Before installing the regulator, check for damage which might have occurred in shipment. Also check for dirt or foreign matter which may have accumulated in the regulator body or in the pipeline. Apply pipe compound to the external threads of the pipeline and install the regulator so that flow is in the direction of the arrow cast on the body. The diaphragm casing assembly can be rotated to any position relative to the body. Loosen the two cap screws (key 71, Figure 11) in order to rotate the diaphragm casing assembly.
General Installation InstructionsBefore installing the regulator,
• Check for damage, which might have occurred during shipment.
• Check for and remove any dirt or foreign material, which may have accumulated in the regulator body.
• Blow out any debris, dirt or copper sulfate in the copper tubing and the pipeline.
• Apply pipe compound to the external threads of the pipe before installing the regulator.
• Make sure gas flow through the regulator is in the same direction as the arrow on the body. “Inlet” and “Outlet” connections are clearly marked.
• Verify that:- Equipment limits of utilization (PS, TS) corresponds
to the desired operating conditions.- The inlet is protected by an appropriate device(s) to
avoid exceeding the allowable limits (PS, TS).• When designing a pressure reducing station using
a CSB regulator, make an analysis if it is necessary to take into account the effects of wind, snow and temperature to avoid unnecessary load and movement to the flanges of the equipment.
• If needed, a support may be used under the piping and regulator/slam-shut body to avoid excessive pressure force on the regulator/slam shut.
WIDE-OPEN MONITORING REGULATOR PRIMARY WORKING REGULATOR
INLET PRESSUREOUTLET PRESSUREATMOSPHERIC PRESSUREINTERMEDIATE PRESSURE
Type CSB400ET with External Pressure Registration and Token Relief Wide-Open Upstream Monitor Regulator
INLET PRESSUREOUTLET PRESSURE
UPSTREAM BLOCK VALVE DOWNSTREAM
BLOCK VALVE
MINIMUM OF 4 X OUTLET PIPING DIAMETER
CSB400 Series
13
Figure 10. Type CSB404 Downstream Control Line Installation
Figure 9. Type CSB403 Downstream Control Line Installation
SLAM SHUT
PRIMARY REGULATOR
INTEGRAL TRUE-MONITOR™
UPSTREAM BLOCK VALVE
DOWNSTREAM BLOCK VALVE
MINIMUM OF 4 X OUTLET PIPING DIAMETER
M1062
PRIMARY REGULATOR
UPSTREAM BLOCK VALVE
DOWNSTREAM BLOCK VALVE
MINIMUM OF 4 X OUTLET PIPING DIAMETER
M1063
INLET PRESSUREOUTLET PRESSURE
ATMOSPHERIC PRESSURE
CSB400 Series
14
Installation Location • The installed regulator should be adequately
protected from vehicular traffic and damage from other external sources.
• Install the regulator with the vent pointed vertically down, see Figures 7 through 10. If the vent cannot be installed in a vertically down position, the regulator must be installed under a separate protective cover. Installing the regulator with the vent down allows condensation to drain, minimizes the entry of water or other debris from entering the vent, and minimizes vent blockage from freezing precipitation.
• Do not install the regulator in a location where there can be excessive water accumulation or ice formation, such as directly beneath a downspout, gutter or roof line of building. Even a protective hood may not provide adequate protection in these instances.
• Install the regulator so that any gas discharge through the vent or vent assembly is over 0.91 m / 3 feet away from any building opening.
Regulators Subjected to Heavy Snow ConditionsSome installations, such as in areas with heavy snowfall, may require a hood or enclosure to protect the regulator from snow load and vent freeze over.
Downstream Control Line Installation
! WARNING
Failure to install a downstream control line could result in a hazardous condition. Install downstream control line(s) to the slam-shut device when construction uses external pressure registration.
The regulator and slam-shut device will not control pressure or shutoff if a downstream control line is not installed on those constructions where external pressure registration is required.
CSB400 Series regulators with an “ET” or “EN” in the type number use external pressure registration. To communicate the downstream pressure to the regulator, connect a downstream control line tubing to the 3/4 NPT control line tapping in the lower diaphragm casing and connect the other end of the tubing downstream of the regulator outlet with a minimum distance of 4 times the outlet pipe diameter.
For Types CSB400 and CSB404 with external control lines, use tubing with an outer diameter of 9.5 mm / 0.375 inch or larger. For Types CSB420, CSB424, CSB450 and CSB454 with external control lines, use tubing with an outer diameter of 13 mm / 0.5 inch or larger.
The Types CSB410, CSB414, CSB430 and CSB434 are dedicated wide-open monitoring regulators and are installed upstream of a primary working regulator. Refer to Figure 8 for installation of the downstream control line. To communicate the downstream pressure to the wide-open monitor regulator, connect a downstream control line tubing to the 3/4 NPT control line tapping in the lower diaphragm casing of the monitor regulator and connect the other end of the tubing downstream of the regulator outlet with a minimum distance of 4 times the outlet pipe diameter.
For Types CSB410 and CSB414, use tubing with an outer diameter of 9.5 mm / 0.375 inch or larger.
For Types CSB430 and CSB434, use tubing with an outer diameter of 13 mm / 0.5 inch or larger.
Downstream Control Line Installation with Integral True-Monitor™
Refer to Figure 9. When installing the Types CSB403 and CSB423 regulators, connect downstream control line tubing to the lower casing of the primary regulator, and run the tubing downstream of the regulator outlet with a minimum distance of 4 times the outlet pipe diameter. Connect a second, separate downstream control line tubing to the lower casing of the Integral True-Monitor, and run the tubing downstream of the regulator outlet with a minimum distance of 4 times the outlet pipe diameter. For Type CSB403 with external control lines, use tubing with an outer diameter of 9.5 mm / 0.375 inch or larger for both the primary regulator and Integral True-Monitor.
CSB400 Series
15
For Type CSB423 with external control lines, use tubing with an outer diameter of 13 mm / 0.5 inch or larger for both the primary regulator and Integral True-Monitor™.
Downstream Control Line Installation with Slam shutRefer to Figure 10. When installing the Types CS404ET, CS404EN, CSB424ET, CSB424EN and CSB454EN regulators, connect downstream control line tubing to the lower casing of the regulator and run the tubing downstream of the regulator outlet with a minimum distance of 4 times the outlet pipe diameter. Connect a second, separate downstream control line tubing to the lower casing of the slam shut and run the tubing downstream of the regulator outlet a minimum distance of 4 times the outlet pipe diameter.
For Type CSB404 with external control lines, use tubing with an outer diameter of 9.5 mm / 0.375 inch or larger for the primary regulator and 6.4 mm / 0.25 inch or larger for the slam shut.
For Types CSB424 and CSB454 with external control lines, use tubing with an outer diameter of 13 mm / 0.5 inch or larger for the primary regulator and 6.4 mm / 0.25 inch or larger for the slam shut.
Installation with External Overpressure ProtectionIf the regulator is used in conjunction with a Type 289H relief valve, it should be installed as shown in Figure 7. The outside end of the vent line should be protected with a rainproof assembly. The Type 289H is typically set 25 mbar / 10 inches w.c. higher than the outlet pressure setting of the regulator, up to 75 mbar / 30 inches w.c. outlet pressure. For pressure greater than this, set the Type 289H 0.05 bar / 0.75 psi higher than the outlet pressure setting of the regulator.
Vent Line InstallationThe CSB400 Series regulators have a 1 NPT screened vent opening in the spring case. If necessary to vent escaping gas away from the regulator, install a remote vent line in the spring case tapping. Vent piping should be as short and direct as possible with a minimum number of bends and elbows. The remote vent line should have the largest practical diameter. Vent piping on regulators with token relief must be large enough
to vent all relief valve discharge to atmosphere without excessive backpressure and resulting excessive pressure in the regulator.
For types with optional Token relief, this low capacity relief is located in the spring case of the primary regulator. If necessary to vent escaping gas away, install a remote vent line in the spring case tapping of the primary regulator as described above. Periodically check all vent openings to be sure that they are not plugged or obstructed.
CSB400 Series outlet pressure ranges are shown in Table 6. Outlet pressure higher than 0.34 bar / 5 psig above the setpoint may damage internal parts such as the diaphragm head and valve disk. The maximum emergency (casing) outlet pressure is 4.0 bar / 58 psig.
Commissioning
CAUTION
Pressure gauges must always be used to monitor downstream pressure during Startup.
With the downstream system depressurized, use the following procedure to start up the regulator.1. Check to see that all appliances are turned off.2. Slowly open the upstream shut-off valve. 3. Check inlet and outlet pressure for correct values. 4. Check all connections for leaks. 5. Turn on utilization equipment and recheck
the pressures.
AdjustmentNote
For types that include the Integral True-Monitor module, refer to the Instruction Manual for Type TM600 Integral True-Monitor for adjustment and maintenance of the Integral True-Monitor. For the types that include the slam-shut module, refer to the Instruction Manual for Type VSX4 slam shut for adjustment and maintenance of the slam shut.
CSB400 Series
16
The range of allowable pressure settings for the primary regulator is stamped on the nameplate. If the required setting is not within this range, substitute the correct spring (as shown in Table 6). If the spring is changed, re-stamp the nameplate to indicate the new pressure range.
A pressure gauge must always be used to monitor downstream pressure while adjustments are being made.
For Types CSB400 and CSB4201. Remove the closing cap (key 60, Figure 16). 2. To increase the outlet setting, turn the adjusting
screw (key 65) clockwise. To decrease the outlet setting, turn the adjusting screw counterclockwise.
3. Replace the closing cap.
For Type CSB4501. Loosen the hex nut (key 58, Figure 16). 2. To increase the outlet setting, turn the adjusting screw
(key 65, Figure 16) clockwise. To decrease the outlet setting, turn the adjusting screw counterclockwise.
3. Tighten the hex nut.
CSB400 Series with Integral True-Monitor™When adjusting the primary regulator and Integral True-Monitor for operation, ensure that the pressure differences between the primary regulator and the integral monitor shown in Table 7 are observed. For example, if the primary regulator setpoint is set at 20 mbar / 8 inches w.c., then the Integral True-Monitor should be set at a minimum of 35 mbar / 14 inches w.c. or higher.
To test the Integral True-Monitor operation, the primary regulator setpoint must be adjusted above the Integral True-Monitor’s setpoint to simulate a failure of the primary regulator. If the spring range of the primary regulator is sufficiently high, it can simply be adjusted above the Integral True-Monitor’s setpoint by following step 2 above. Otherwise, a different spring with a setpoint higher than the Integral True-Monitor’s setpoint must be installed to check the operation of the Integral True-Monitor.
CSB400 Series with Slam shutWhen adjusting the primary regulator and slam shut for operation, refer to Table 8 for the OPSO setpoints and also the combined OPSO and UPSO setpoints of the slam shut for a given regulator spring ranges.
CAUTION
Equipment installed downstream the Type VSX slam shut device can be damaged if the following procedure for resetting the Type VSX slam shut device is not followed. This equipment includes the integral Type VSX or regulator configurations.
Step 1: • To properly reset the Type VSX slam shut after it
has been tripped to the closed position, a flat-head screwdriver must be inserted into the position shown in Figure 8 on the backside of the reset button (refer to Type VSX4 Instruction Manual, key 30, Figure 8).
Step 2: • The screwdriver should be slowly rotated to gradually
pull the reset button (refer to Type VSX4 Instruction Manual, key 30) away from the Type VSX device. This slow movement allows for a slow bleed of the pressure across the Type VSX slam shut’s disk and seat area. The operator should be able to hear the pressure bleeding through the system.
Step 3: • When the pressure has equalized and the air
bleeding sound has dissipated, the reset button (refer to Type VSX4 Instruction Manual, key 30) should be pulled completely away from the Type VSX slam shut device by hand until the internal shut-off mechanism has been re-latched.
Step 4: • Once the operator feels the click of the re-latch
occurring, the reset button (refer to Type VSX4 Instruction Manual, key 30) should be pushed completely back into its original position.
CSB400 Series
17
! WARNING
In the case of a downstream line break, numerous factors affect the capability to evacuate gas from the pipeline. These factors include the distance of pipe to the break, the diameter of the pipe, size of the break and the number of restrictions, such as valves, elbows and bends, downstream of the regulator and/or slam-shut device. Due to these factors additional protections should be installed to stop flow in the event of a line break.
ShutdownInstallation arrangements may vary, but in any installation it is important that the valves be opened or closed slowly and that the outlet pressure be vented before venting inlet pressure to prevent damage caused by reverse pressurization of the regulator. The following steps apply to the typical installation as indicated.
1. Open valves downstream of the regulator.2. Slowly close the upstream shut-off valve.3. Inlet pressure should automatically be released
downstream as the regulator opens in response to the lowered pressure underside of the diaphragm.
4. Close outlet shut-off valve.
Dow Corning® is a mark owned by Dow Corning Corporation.
Figure 11. CSB400 Series Regulator Assembly
APPLY LUBRICANTS (L) / SEALANT (S)(1):
L1 = DOW CORNING® 33 OR COMPARABLE EXTREME LOW TEMPERATURE LUBRICANTL2 = ANTI-SEIZE LUBRICANTS1 = MULTI-PURPOSE POLYTETRAFLUOROETHYLENE (PTFE) THREAD SEALANT
1. Lubricants and sealant must be selected such that they meet the temperature requirements.
ERAA04154
S1
L1L1 22
L1
21L1 27
35
74
L2 25
L1 75
L1 77
L1 19
20
19 55
10141318 11
L2
96100
L2
65
L2
60
L1
62
L2
L238
95
51
8
7
5
64
TORQUE: 1.7 TO 3.4 N•m /15 TO 30 INCH-POUNDS
TORQUE: 1.7 TO 3.4 N•m /15 TO 30 INCH-POUNDS
TORQUE: 1.7 TO 3.4 N•m /15 TO 30 INCH-POUNDS
TORQUE: 47 TO 61 N•m /35 TO 45 FOOT-POUNDS
CSB400 Series
18
Figure 11. CSB400 Series Regulator Assembly (continued)
TORQUE: 14 TO 18 N•m /10 TO 13 FOOT-POUNDS
TORQUE: 14 TO 18 N•m /10 TO 13 FOOT-POUNDS
TORQUE: 7.1 TO 10.1 N•m /63 TO 90 INCH-POUNDS
ERAA04154
APPLY SEALANT (S)(1):
S1 = MULTI-PURPOSE POLYTETRAFLUOROETHYLENE (PTFE) THREAD SEALANT
1. Sealant must be selected such that it meets the temperature requirements.2. The torque range as specified is initial assembly torque. Due to elastomeric compression, the torque values indicated may decrease. Minimum inspection torque is 4 N•m / 35 inch-pounds.
2
16
15
3
1
9
80
72
76
70
71
17
S1
CSB400 Series
19
Maintenance and Inspection
! WARNING
To avoid personal injury or equipment damage, do not attempt any maintenance or disassembly without first isolating the regulator from system pressure and relieving all internal pressure as described in “Shutdown”.
Regulators that have been disassembled for repair must be tested for proper operation before being returned to service. Only parts manufactured by Regulator Technologies should be used for repairing Fisher® regulators. Restart gas utilization equipment according to normal startup procedures.
Due to normal wear or damage that may occur from external sources, this regulator should be inspected and maintained periodically. The frequency of inspection and replacement depends on the severity of service conditions, test results found during the annual test, and on applicable codes and regulations. In accordance with applicable National or Industry codes, standards and regulations/recommendations, all hazards covered by specific tests after final assembly, before applying the CE marking, shall also be covered after every subsequent reassembly at installation site in order to ensure that the equipment will be safe throughout its intended life.
Periodic inspection must be performed on the CSB400 Series that include the Integral True-Monitor™ or slam-shut overpressure protection modules to ensure that they protect the downstream system in the event the primary regulator losses pressure control. This inspection must test that the Integral True-Monitor or slam-shut functions as intended.
NoteFor adjusting setpoints above 100 mbar / 1.5 psig, use a 13 mm / 1/2-inch hex driver, a 13 mm / 1/2-inch socket or a 27 mm / 1-1/16-inch socket to turn the adjusting screw (key 65).
Disassembly to Replace the Regulator Main Diaphragm1. Remove the closing cap (key 60, Figure 11) or loosen
hex locknut (key 58, Figure 16). Turn the adjusting screw (key 65) or nut (key 58) counterclockwise to ease spring (key 38) compression.
2. Remove the adjusting screw (key 65) and spring (key 38).
3. Remove hex nuts (key 16, Figure 11) and cap screws (key 15, Figure 11). Separate the upper spring case (key 1) from the lower casing assembly (key 9).
Note
When disassembling a CSB400 Series regulator, lift the upper spring case (key 1) straight up in order to avoid hitting the stem (key 44).
4. Slide the diaphragm assembly (key 55) away from the body (key 70) to unhook the pusher post (key 51) from the lever (key 10). Lift off the diaphragm assembly (key 55).
5. a. For none relieving units such as the Types CSB400IN and CSB400EN, unscrew the cap (key 45), see Figure 12, high-pressure Non-Relief and low-pressure Non-Relief assemblies. The cap fastens the R.V. spring seat (key 43) to the pusher post (key 51). Unscrew the cap to separate the R.V. spring seat (key 43), diaphragm assembly (key 55) and pusher post (key 51).
b. For units with internal token relief such as Type CSB400IT, refer to Figure 12, unscrew the adjusting upper seat (key 47). This will allow for removal of the relief spring (key 41), R.V. spring seat (key 43), diaphragm assembly (key 55) and pusher post (key 51).
CSB400 Series
20
6. Reassemble the spring case (key 1) unit in the reverse order of the above steps. Before tightening the cap screws (key 15) or stem (key 44) into the pusher post (key 51), place the loosely-assembled diaphragm assembly (key 55) into position in the lower casing (key 9), being sure that the pusher post (key 51) is hooked on the lever (key 10). Rotate the diaphragm (key 55A) so that the diaphragm and lower casing (key 9) holes are aligned. Tighten the stem (key 44) or diaphragm retainer (key 45) for HP and LP non-relief assemblies.
Disassembly to Replace Valve Disk, Balanced Port Assembly Diaphragm and Regulator Orifice
1. Remove the bolts (key 71, Figure 11) which hold the lower spring casing (key 9) to the body (key 70). Separate the lower spring casing (key 9) from the body (key 70).
2. Check the body O-ring (key 21) for wear. 3. Remove the balanced port assembly (key 35,
Figures 11 and 13) from the body, make sure to rotate the assembly toward the outlet of the body as it is being removed to clear the sense tube from the body.
4. Examine the valve disk (key 35K) for nicks, cuts and other damage. If damage is present, it is recommended to replace both the disk and also the balanced port diaphragm (key 35F) and associated diaphragm O-ring (key 35M), that comes into direct contact with the inner flange of the balanced port diaphragm. Start the process of replacing the disk by disassembling the balanced port assembly. Remove the four cap screws (key 35R) and then the cap (key 35G).
5. Grasp the spring retainer (key 35C) and slide the brazed housing (key 35A) away to expose the diaphragm (key 35F) and disk (key 35K). Still grasping the spring retainer (key 35C) insert a 5 mm Allen wrench into the disk screw (key 35E) and unscrew.
6. Remove the disk (key 35K) and discard if damaged Slide the diaphragm O-ring (key 35M) off the stem (key 35B) along with the diaphragm (key 35F). Slide the new diaphragm over the stem in the same manner that it was removed, make sure that it completely contacts the surface of the inner retainer (key 35J).
7. Reassemble the Balanced Port assembly in reverse order of the above. Ensure Dow Corning® 33 or comparable extreme low temperature lubricant completely coats the O-ring (key 35M), stem (key 35B) and the center bore of the outer retainer (key 35H).
8. Examine the seating edge of the orifice (key 25). If it is nicked or rough, replace the orifice and O-ring (key 27). If a slam shut or monitor is installed on the backside of the body, refer to the applicable Instruction Manual for inspection and removal of the overpressure protection orifice (key 26) and O-ring (key 27).
9. Reassemble the regulator in reverse order of the above steps.
Regulator ReassemblyAs indicated by the square callouts in Figures 11 to 17, it is recommended that a good quality pipe thread sealant be applied to pressure connections and fittings and a good quality extreme low temperature lubricant, such as Dow Corning® 33, be applied to O-rings. Also apply an anti-seize compound to the adjusting screw threads, orifice threads and other noted areas as needed.
Parts OrderingThe type number, orifice size, spring range and date of manufacture are stamped on the nameplate. Always provide this information in any correspondence with your local Sales Office regarding replacement parts or technical assistance.When ordering replacement parts, reference the key number of each needed part as found in the following parts list. Separate kit containing all recommended spare parts is available.
Dow Corning® is a mark owned by Dow Corning Corporation.
CSB400 Series
21
*Recommended spare part.
Parts List
Key Description Part Number
Spare Parts (Repair Parts Kit include keys 12, 19, 21, 27, 35K, 55, 62, 75 and 77) Type CSB400 RCSB400X012 Type CSB403 RCSB403X012 Type CSB404 RCSB404X0121 Spring Case, Aluminum GE24555X0122 Vent Screen, 18-8 Stainless steel T11213389823 Retaining Ring, Steel T11209250724 Stabilizer Guide, 304 Stainless steel GE27061X0125 Stabilizer, Acrylonitrile Butadiene Styrene (ABS) GE27063X0126 Stabilizer Spring, Stainless steel GE35010X0127 Retainer Ring, Zinc-plated steel GE27024X0128 Stabilizer Screw, Zinc-plated steel (3 required) GE29724X0129 Lower Casing, Aluminum GE24289X01210 Lever, Steel Types CSB400, CSB403, CSB404, CSB410 and CSB414 GE28773X012 Types CSB420, CSB423, CSB424, CSB430, CSB434, CSB450 and CSB454 GE28772X01211 Valve Stem, Aluminum GE27812X01212* O-ring, Nitrile (NBR) External Registration Only 1E47270699213 Lever Pin, 18-8 Stainless steel Types CSB400, CSB403, CSB404, CSB410 and CSB414 T14397T0012 Types CSB420, CSB423, CSB424, CSB430, CSB434, CSB450 and CSB454 (2 required) T14397T001214 Lever Screw, Steel Types CSB400, CSB403, CSB404, CSB410 and CSB414 (2 required) GE34243X012 Types CSB420, CSB423, CSB424, CSB430, CSB434, CSB450 and CSB454 (4 required) GE34243X01215 Cap Screw, Steel (8 required) GE32059X01216 Nut, Steel (8 required) GE32060X01217 Union Ring, Aluminum GE26590X01218 Snap Ring, 302 Stainless steel T112063702219* O-ring, Nitrile (NBR) (2 required) 1K59490656220 Stem Guide, Aluminum GE26027X01221* O-ring, Nitrile (NBR) GE45216X01222 Pipe plug, 3/4 NPT, Steel Internal Registration Only GE34199X01223 Screw (For external registration only), Steel (2 required) 1E17582898224* O-ring (For external registration only), Nitrile (NBR) (2 required) 17A0960X01225 Orifice Types CSB400F and CSB404F, Aluminum GG08494X012 All other Types, Brass GE31321X01226 OPP Orifice 18 mm / 0.69 inch With Integral True-Monitor™ Orifice, Aluminum GE30003X012 With Slam-shut Orifice, Brass GE28684X01227* O-ring, Nitrile (NBR) Type CSB400 (1 required) 10A3802X022 Type CSB403 (2 required) 10A3802X022 Type CSB404 (2 required) 10A3802X02235 Balanced Port Assembly for all bodies except GAZ Standard GE31196X012 Low temperature “F” version GE31196X02235A Brazed Housing GE31261X01235B Stem, Stainless steel GE31191X01235C Spring Retainer, Zinc-plated steel GE31189X01235D Spring, Stainless steel GE30193X01235E Disk Screw, Zinc-plated steel GE31190X01235F* Diaphragm, Nitrile (NBR) / Fabric GE30439X01235G Cap, Brass GE31195X012
Key Description Part Number
35H Outer Retainer, Brass GE31187X01235J Inner Retainer, Brass GE31186X01235K* Disk Assembly, Brass / Nitrile (NBR)
Standard version ERSA00457A0 Low Temperature “F” version GE31185X012
35M O-ring, Nitrile (NBR) (2 required) 1E472706992 35N* O-ring, Nitrile (NBR) 1U879006562 35R Screw, Steel (4 required) GE25968X012 35S Pin, Zinc-plated steel GE31232X012 35 Balanced port assembly for Rp 1 x 2-1/4, GAZ Body
Standard GE33822X012 Low temperature “F” version GE33822X022
35A Brazed Housing GE32505X012 35B Stem, Stainless steel GE31191X012 35C Spring Retainer, Zinc-plated steel GE31189X012 35D Spring, Stainless steel GE30193X012 35E Disk Screw, Zinc-plated steel GE31190X012 35F* Diaphragm, Nitrile (NBR) / Fabric GE30439X012 35G Cap, Brass GE31195X01235H Outer Retainer, Brass GE31187X012 35J Inner Retainer, Brass GE31186X01235K* Disk Assembly, Brass / Nitrile (NBR)
Standard version ERSA00457A0 Low-temperature “F” version GE31185X012
35M O-ring, Nitrile (NBR) (2 required) 1E47270699235N* O-ring, Nitrile (NBR) 1U879006562 35R Screw, Cap, Hex Socket, Steel (4 required) GE25968X012 38 Spring
17 to 24 mbar / 6.8 to 9.6 inches w.c., Pink GE30191X012 24 to 35 mbar / 9.6 to 14 inches w.c., Orange Stripe GE43955X012 35 to 60 mbar / 14 to 24 inches w.c., Dark Green GE30201X012 54 to 100 mbar / 0.78 to 1.5 psig, Tan GE30202X012 100 to 160 mbar / 1.45 to 2.3 psig, Purple Stripe GE35081X012 138 to 300 mbar / 2.0 to 4.4 psig, Dark Blue GE30192X012 276 to 517 mbar / 4 to 7.5 psig, Red GE33121X012 500 mbar to 1 bar / 7.3 to 14.5 psig, Light Blue GE30203X012 1 to 3 bar / 14.5 to 43.5 psig, Light Green GE30204X012
40 Upper Spring Seat, Steel High Pressure, Zinc-plated steel GE32501X012
41 Relief Valve Spring, 302 Stainless steel Types CSB400, CSB403 and CSB404, Token GE30194X012 Types CSB420, CSB423 and CSB424, Token GE42225X012
43 Relief Valve Spring Seat, Zinc-plated steel Types CSB400 and CSB420, Non-Relief GE27327X012 Type CSB450, Non-Relief GE31677X012 Types CSB400 and CSB420, Token GE28947X012
44 Stem, Aluminum Types CSB400 and CSB420, Token GE30895X012
45 Diaphragm Retainer, Zinc-plated steel Types CSB400 and CSB420, Non-Relief GE30887X012 Type CSB450, Non-Relief GE33850X012
47 Upper Spring Seat, Aluminum Types CSB400 and CSB420, Token GE33332X012
48 Restrictor Plate, Zinc-plated steel Token GE28948X012
51 Pusher Post, Aluminum Token ERAA00876A0 Non-Relief ERAA00875A0
53 Solid Rivet, 18-8 Stainless steel GE29761X01254 Roller Pin, Brass GE27060X01255* Diaphragm Assembly, Steel / Nitrile (NBR)
Without Diaphragm Head Limiter GE31248X012 With Diaphragm Head Limiter GE32140X012
55A Diaphragm - - - - - - - - - - -55B Diaphragm Head - - - - - - - - - - -
CSB400 Series
22
Figure 12. CSB400 Series Diaphragm and Relief Assemblies
ERAA04154
APPLY ADHESIVE (A)(1):A = ADHESIVE
NOTE: APPLY ADHESIVE ON THE FLAT SURFACE OF THE DIAPHRAGM PLATE THAT CONTACTS THE DIAPHRAGM, TOWARD THE OUTER PERIMETER, AND AWAY FROM THE CENTER HOLE.
43
43
51
53
54
54
56
56
4745
45
41
43
53
54
51
44
48
56
56
53
51
55B
55A 107
108
109
A55B
55A
55A
A
55B
A
TORQUE: 6 TO 8 N•m / 50 TO 70 INCH-POUNDS
HIGH-PRESSURE NON-RELIEF
TORQUE: 6 TO 8 N•m / 50 TO 70 INCH-POUNDS
LOW-PRESSURE NON-RELIEF
TOKEN RELIEF
TORQUE: 6 TO 8 N•m / 50 TO 70 INCH-POUNDS
NOTE DIRECTION OF RETAINER RING INSTALLATION
NOTE DIRECTION OF RETAINER RING INSTALLATION
NOTE DIRECTION OF RETAINER RING INSTALLATION
NOTE DIRECTION OF RETAINER RING INSTALLATION
1. Adhesive must be selected such that it meets the temperature requirements.
CSB400 Series
23
35S 35N 35H 35M 35B
S2
35C
35D
35R
35G35A
L1 L1
35F 35J
35M
L1
35E
35K
L1
35M
35E
35K
35A 35G
35R
35D
35C
S2
35B35M
L1L1
35N35J35F 35H
Figure 13. Balance Trim Assemblies
STANDARD BALANCED PORT ASSEMBLY
BALANCED PORT ASSEMBLY FOR Rp 1 X 2-1/4 GAZ BODY
ERAA04154
APPLY LUBRICANT (L) / SEALANT (S)(1):
L1 = DOW CORNING® 33 OR COMPARABLE EXTREME LOW TEMPERATURE LUBRICANTS2 = PERMANENT THREAD SEALANT
TORQUE: 2.3 TO 2.8 N•m /
20 TO 25 INCH-POUNDS
TORQUE: 2.3 TO 2.8 N•m /20 TO 25 INCH-POUNDS
TORQUE: 0.9 TO 1.4 N•m / 8 TO 12 INCH-POUNDS
TORQUE: 2.3 TO 2.8 N•m /
20 TO 25 INCH-POUNDS
TORQUE: 2.3 TO 2.8 N•m / 20 TO 25 INCH-POUNDS
TORQUE: 0.9 TO 1.4 N•m /8 TO 12 INCH-POUNDS
Dow Corning® is a mark owned by Dow Corning Corporation.
1. Lubricant and sealant must be selected such that they meet the temperature requirements.
CSB400 Series
24
20 11
B
B
23
24 L1
L1
L1
L1
L1
L1
L1
12
1120
L1
Figure 14. CSB400 Series Stem Guides
GE27692
APPLY LUBRICANT (L)(1):L1 = DOW CORNING® 33 OR COMPARABLE EXTREME LOW TEMPERATURE LUBRICANT
Dow Corning® is a mark owned by Dow Corning Corporation.
1. Lubricant must be selected such that it meets the temperature requirements.
INTERNAL OR DUAL REGISTRATION(NO SCREWS)
EXTERNAL REGISTRATION
REF HOLES “B”
TORQUE: 1.7 TO 3.4 N•m /15 TO 30 INCH-POUNDSINSTALL IN “B” HOLES(THROUGH HOLES)
CSB400 Series
25
80
74
76 77 75 101 70
L1
L1
75
77
80
74
76
S2 83 82 81
L1 L1
Figure 15. Standard Body Assembly and Rp 1 x 2-1/4 GAZ Body Assembly
ERAA04154
APPLY LUBRICANT (L) / SEALANT (S)(1):L1 = DOW CORNING® 33 OR COMPARABLE EXTREME LOW TEMPERATURE LUBRICANTS2 = PERMANENT THREAD SEALANT
DUCTILE / STEEL BODY GAZ BODY
TORQUE: 14 TO 18 N•m /10 TO 13 FOOT-POUNDS
TORQUE: 14 TO 18 N•m /10 TO 13 FOOT-POUNDS
TORQUE: 1.7 TO 3.4 N•m /15 TO 30 INCH-POUNDS
Figure 16. CSB400 Series Control Spring Adjustment Assemblies
CSB450 SERIES HIGH PRESSURE ERAA04154
APPLY LUBRICANT (L)(1): L1 = DOW CORNING® 33 OR COMPARABLE EXTREME LOW TEMPERATURE LUBRICANTL2 = ANTI-SEIZE LUBRICANT
CSB400 / CSB420 SERIES STANDARD
Dow Corning® is a mark owned by Dow Corning Corporation.
1. Lubricant and sealant must be selected such that they meet the temperature requirements.
1. Lubricant and sealant must be selected such that they meet the temperature requirements.
65 62 38 60 10038 40 62 58 65 61 57
L2
L2 L1
L1 L2 L2
96
CSB400 Series
26
L2 L2
26
L1 L1
70 27 25 101 L2 27
L1
2770 25 101
L2L1
26
27
L2 L2
26
L1 L1
70 27 25 101 L2 27
L1
2770 25 101
L2L1
26
27
Figure 17. CSB400 Series Slam-shut and Integral True-Monitor Modules
ERAA04154
APPLY LUBRICANTS (L)(1):L1 = DOW CORNING® 33 OR COMPARABLE EXTREME LOW TEMPERATURE LUBRICANTL2 = ANTI-SEIZE LUBRICANT
INTEGRAL TRUE-MONITOR™ ASSEMBLY
SLAM-SHUT ASSEMBLY
TORQUE: 47 TO 61 N•m /35 TO 45 FOOT-POUNDS
TORQUE: 47 TO 61 N•m /
35 TO 45 FOOT-POUNDS
TORQUE: 14 TO 18 N•m /
10 TO 13 FOOT-POUNDS
TORQUE: 47 TO 61 N•m /
35 TO 45 FOOT-POUNDS
TORQUE: 14 TO 18 N•m /
10 TO 13 FOOT-POUNDS
TORQUE: 47 TO 61 N•m /35 TO 45 FOOT-POUNDS
Dow Corning® is a mark owned by Dow Corning Corporation.
1. Lubricants must be selected such that they meet the temperature requirements.
CSB400 Series
27
56 Retaining Ring, Pusher Post Pin GE33772X01257 Bearing ball GE33131X01258 Hex Nut, High-Pressure, (CSB450 Series only) Steel GE33132X01260 Closing Cap, Low-Pressure, Aluminum GE29244X01261 Bonnet, High-Pressure, (CSB450 Series only) Zinc-plated steel GE32499X01262* O-ring, Nitrile (NBR) T10275X001265 Adjust Screw
Low-Pressure, Aluminum GE27828X012 High-Pressure, Steel GE32500X012
70 Body Ductile Cast Iron NPT: 1 GE26463X012 1-1/4 GE26465X012 1-1/2 GE26466X012 2 GE26467X012 Rp: Rp 1 GE26468X012 Rp 1-1/4 GE26469X012 Rp 1-1/2 GE26470X012 Rp 1 x 1-1/4 GE42505X012 Rp 1 x 2-1/4, GAZ GE26482X012 Rp 2 GE26471X012 Flange: DN 50 / NPS 2, CL150 FF GE26480X012 DN 40 / NPS 1-1/2, PN 10/16 Slip-Flange GE44902X012 DN 50 / NPS 2, PN 10/16 GE26481X012 WCC Steel NPT: 1 GE26463X022 1-1/4 GE26465X022 1-1/2 GE26466X022 Rp Rp 1 GE26468X022 Rp 1-1/4 GE26469X022 Rp 1-1/2 GE26470X022
71 Bolt, Steel (2 required) GE32061X012 72 Pipe Plug, 1/4 NPT
Steel 1C333528992 316 Stainless steel 1C3335X0012
74 Blanking Plug, Aluminum GE31255X01275* O-ring, Metric, Nitrile (NBR) GF03442X01276 Half Flange, Steel (2 required) GF01942X012 77* Metric O-ring, Nitrile (NBR) GF03443X012 80 Cap Screw, Steel (4 required) GE38176X01281 Slotted Spring Pin GE32503X01282 Tube Gasket, Nitrile (NBR) GE32502X01283 Pitot Tube, Aluminum GE31988X01290 Nameplate - - - - - - - - - - -91 Warning Label - - - - - - - - - - -93 Information Label - - - - - - - - - - -94 Overlay Label - - - - - - - - - - -95 Grommet, Nitrile (NBR) GE35358X01296 Slip Disk, Stainless steel GG05787X012100 Wire and Seal T14088T0012101 Spring Pin, Steel GE32724X012104 Hub, Zinc-plated steel (2 required) not shown GG02505X012105 Flange Slip, Zinc-plated steel (2 required) not shown GG02508X012106 O-ring, Nitrile (NBR) (2 required) not shown GE41121X012107 Diaphragm Head Limiter, Zinc-plated steel GE28761X012108 Diaphragm Protector, Zinc-plated steel GE42747X012109 Pad, (CSB450 Series only) T13830T0012
Parts List (continued)Key Description Part Number Key Description Part Number
CSB400 Series
©Emerson Process Management Regulator Technologies, Inc., 2009, 2014; All Rights Reserved
Industrial Regulators
Emerson Process Management Regulator Technologies, Inc.
USA - HeadquartersMcKinney, Texas 75070 USATel: +1 800 558 5853Outside U.S. +1 972 548 3574
Asia-Pacifi cShanghai 201206, ChinaTel: +86 21 2892 9000
EuropeBologna 40013, ItalyTel: +39 051 419 0611
Middle East and AfricaDubai, United Arab EmiratesTel: +011 971 4811 8100
Natural Gas Technologies
Emerson Process ManagementRegulator Technologies, Inc.
USA - HeadquartersMcKinney, Texas 75070 USATel: +1 800 558 5853Outside U.S. +1 972 548 3574
Asia-Pacifi cSingapore 128461, SingaporeTel: +65 6770 8337
EuropeBologna 40013, ItalyTel: +39 051 419 0611Chartres 28008, FranceTel: +33 2 37 33 47 00
Middle East and AfricaDubai, United Arab EmiratesTel: +011 971 4811 8100
TESCOM
Emerson Process ManagementTescom Corporation
USA - HeadquartersElk River, Minnesota 55330-2445, USATels: +1 763 241 3238 +1 800 447 1250
EuropeSelmsdorf 23923, GermanyTel: +49 38823 31 287
Asia-Pacifi cShanghai 201206, ChinaTel: +86 21 2892 9499
The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher is a mark owned by Fisher Controls International LLC,a business of Emerson Process Management.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifi cations of such products at any time without notice.
Emerson Process Management Regulator Technologies, Inc. does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson Process Management Regulator Technologies, Inc. product remains solely with the purchaser.
For further information visit www.emersonprocess.com/regulators
The distinctive swirl pattern cast into every actuator casing uniquely identifi es the regulator as part of the Fisher® brand Commercial Service Regulator family and assures you of the highest-quality engineering, performance, and support traditionally associated with Fisher®, Francel™ and Tartarini™ regulators. Visit www.fishercommercialservice.com to access interactive applications.