crTY OF HALLANDALE BEACH I FLORIDA MEMORANDUM
DATE July 8 2013
TO Charles Wu Director Development Services
FROM Danie l Sullivan Di rector Department of Fire Rescue
SUBJECT RENEWAL OF NIGHTCLUB LICENSES fOR FY 20 132014
rite staff conducted fire saf e t y inspec t ions of the nightclubs referenced in your memo of June 3 2013 The inspections were satisfactory with no significant t hreat to life safety and Fire staf f s uppor ts l icensure renewal s for the coming fiscal year
If you need further informat ion please contact DivisionI 1
sect~ Department Signature __-o~_~~~~~-~~~~~c-~~~~~c--shy
Division ~f Gregg Pagliarul o
I 0h0I0kgtn CIWII G PaQ ~~ (964) 4amp7411 IHALLANDALE BEACH FIRE RESCUE iIPIQIi~org
~-Matllll M Alom iS4j457-14111Division of Fire Prevention and Public Education mJltmarllZcohb(gtg f121 Sw 3rd Street Firt IMPIICH L M1IIm (~5) ~ 57middot1 7 8
Hallandale Beach Florida 33009 wIi -Ccob Oro
FAX (954) 457middot1472 F~ 11lIpeclJr Y FeI)o~ Yfl1oo~ootobcx-g
FIRE IHSPECllON REPORT
ANNUAL - Commercial (0-5000) Aslgned To AlEMAN Miguel on 31sno13
DlIte 31512013 120000AM
Location Number 835062
Business Name CHUPULTEPEC
Addu 019-023 NW 2 AVE
CitylStatelZip HALLAN DAlE BEACH FL 33009 Volatioo StjixlardlRe(i[ebull
GENERAL
ADDRESS MISSING ON BUILDING IS) NFPA 1 - 2006101212
MUST BE VISIBLE FROM THE STREET AND IN CONTRASTING COLOR TO THE BUILDING NUMERALS NO lESS THAN 3 INCHES IN HEIGHT FOR RESIDENTIAL 6 INCHES FOR COMMERCIAL
EGREss EXIT
I
EMERGENCY LIGHTS SHAll BE PROVIDED
ErtERGEIICY LIGHTS SHAlL BE PROVIDED TO ILLUMINATE MEANS OF EGRESS CHECK LIGHT eULBS AND BATTERY BACKUP
eXIT SIGNS MUST BE UT AT ALL TIMES bull lt
EVERY EXIT SIGN SHALL BE ILLUMINATED DURING NORMAL AND EMERGENCY OPERA110N NOTIFY INSPECTOR IF LIGHTING SYSTEMS ARE ON TIMERS FROM DUSK TO DAWN OPERATION
CHECK LIGHT BULBS AND BATTERY BACKUP
EXITS OBSTRUCTED LOCKED OR DAMAGED
DOORS SHALL BE ARRANGED TO BE OPENED REAOIl Y FROM THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED PENAlTY APPLIED FOR BLOCKED EXITS UNDER PI
REAR EXIT
MAXIMUM CAPACITY
POST OCCUPANT LOAD SIGN IN CONSPICUOUS PLACE NEAR MAIN EXIT DO NOT EXCEED POSTEa NUMBER
Reclplltnt Sillnatur
ALL LIFE SAFETY CODE V10LATIONS SHAU BE CORRECTED IW(EOIATELY
HALLANDALE BEACH FIRE RESCUE Division of Fire Prevention and Public Education
121 SW 3rd Sireet Hallandale Beach Florida 33009
FAA (954) 457-1472
FIRE INSPECTION REPORT
ANNUAL - Occupational License A$9lgned To ALEMAN Miguel on 71812013
Date 61512013 12OO53AM
Location Nllmblr 94023S
6ulneu Name CLUB FATE
Addr 601 SILKS RUN Unit No 2499
SPRINKLER
SPRINKIER I STANDPIPE - ANNUAL SERVICe
FIRE SPRINKLERS SHAll BE INSPECTED ANNUALLY AND A SERVIcE TAG PLACED IN CLEAR VIEW FIRE SPRINKLER HAS NO TAG
FIRE ALARM
ALARM PANEL NEEDS ANNUAL SERVICE
FIRE ALARM SYSTEM MUST HAVE ANNUAL CERTIFICATION TAG
FA LAST INSPECTION TAG NOVmiddot20
Recipient Signawrt
Recipint
ALL LIFE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDIATELY
HALLANDALE BEACH FIRE RESCUE Division of Fire Prevention and Public Education
121 sw3rd Street Halandala Beach Florida JJ009
FAX ~954) 457-1412
FIRe INSPECTlON REPORT
ANNUAL - Commercial (5000-10000) Assigned To WILLIAMS Lori on 611712013
Date 61312013 12OO00AM
l oeali ll n Number 838954
Business Name CLUB TATlANAS
Addrebullbull 17 10 E HALLANDALE BEACH BLVa
CltylStateJZip HALLANDALE BEACH FL 33009
GENERAL SPECIAL HAZARD
PROVIDE PERMIT FOR REAR RAMP AT EXIT DOOR ON vEST SlOE fIOODEN RAJlP BUlLT W THOUT PERMIT
Reclplnt Signaiurl
~clplnl
Pag~ 1 All UFE SAFETY CooE VlOLAnONS SHALL BE CORRECTED INMEOIATELY
OMtion Ct G p~g (954)$7-1~nHALLANDALE BEACH FIRE RESCUE ~~bV
Fn IBhaI M Ailmln tfS4)S1-1Division of Fire Prevention and Public Education nOoohbOI9
121 SW 3td Street npecllgtf I h (i$ltll nltl Halandale Beltlch Florida 33009 ~ 0c0hbV
F ~Y E~ ~$4)4$7~1 ~OOOCOhbot1l
FAX (954) 457-1472
FIRE INSPECl10N REPORT
ANNUAL - Commercial (0-5000) Assigned To ALEMAN Miguecl on 81272012
Oatt 812712012 120000Ait
Location Numbtr 836786
Busin Nama FLANIGANS
Add 10 N FEDERAL HVIY
CltylStateZip HALLANDALE BEACHF~ 33009 StIndardlB ftrtncbull V10latiOD L~~_~tl=li~i~ii~==~~1I _A
EGRESS EXIT KEY BOX REQUIRED [S) NFPA 1 _ 200618221
FIRE DEPT ACCESS SOX MUST BE INSTALLED MAINTAINED AND KEYS PROVIDED VERIFY WITH INSPECTOR NHICH KEYS NEEDED
GENERAL PRIOR VIOLAnONS NOT CORRECTED
ELECTRICAL
EXPOSED WIRING
BY MAIN ENTRANCE KITCKEN
GE NERAL PRIOR VIOLAliONS NOT CORRECTED
Reelplent Signature
Recipient
Page1 ALL UFE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDIATELY
C91tec Us (9~~)457middot1417
HALLANDALE BEACH FIRE RESCUE (95-)4571479Division of Fire Prevention and Public Education
121 Sw 3rd SIrH1 (5~) 457middot1~78
Hallanc1ale Beach Florida 33009 fAX (954) 457middot1472 19S4) 457-3Cgt51
FIRE INSPECTION REPORT
CERTIFICATE OF OCCUPANCY Assigned To WILLlAMS Lori on 7812013
Date 11121201 2 120000AM
Locllon Numbr 94041 8
Business Name MARTINI BAR
AddlU$ 601 SILKS RUN Unit No 2497
CitylStatelZip HALLANDALE BEACH fL 33009
GENERAL
NO FIRE CODE VIOLA liONS NOTED
NO FIRE CODE VIOLATIONS WERE NOTED DURING THE LISTED INSPECTION INSPECTION WAS SATISFACTORY
PERMIT CLOSEDmiddot CO ISSUED
Recipient Signature
Reciplenl
I Page ALL LIFE SAFETY PODE VIOLATIONS SHALL BE CO RRECTED IMMEDIATEL
CgjCI U DMaIooI Cl~ G PIIJIO I~ ) 457middot ~n _ HALLANDALE BEACH FIRE RESCUE F LIvI W AiIoman (9 So14S141VOivision of Fire Prevention and Public EducaUon
121 S W 3rd Street n1n_l MILo (S SltI ) 4n_4re Halandale Blach Florida 33009 OgchOoro--
FN Iru~cb Y F-too (950t) S7-)()61FAX (954) 4157 472 - FIRE ~sp~cnON REPORT
ANNUAL - Commercial gt25000 Aulgned To ALEMAN Miguel on 102212012
Daw 1012212012 120000AM
loelion Number 838802
Buso HI m GULFSTREAM PARK CLUBHOUSE
Addrn 901 S FEDERAll-fNf
CltyStJtlZlp Hdnnd~ ~each ~l33009
Yiolation
HAlMAT HAZMAT PERMIT NEEDED
FIRST LETTER UAlLED
HAZMAT PERMIT NEEDED
SECOND LETTER MAILED
GENERAl
EMERGENCY OPERATlOHS PlAN REQUIREO III CrTYORDINANCE 18-1131()
lSI FS 553 509 (2Xd)
EMERGENCY OPERATIONS PLAN REQUIRED TO BE WRlITEN MAINTAINED AND ON FILE WITli FIRE RESCUE
LETTE R MAllED
EGRESS I EXIT
EMERGENCY U GHTS SHALL BE PROVIDED
EMERGENCY LIGHTS SHAll BE PROVIDED TO IUUMINATE MEANS OF EGRESS
CHECK LIGHT BULBS AND BATTERY BACKUP
EXIT SIGNS MUST BE LIT AT ALL TIMES
EVERY EXIT SIGN SHALL BE ILLUMINATED DURING NORMALANO EMERGENCY OPERATION NOTIFY INSPECTOR IF LIGHTING SYSTEMS ARE ON TIMERS FROM DUSK TO DAWN OPERATION
CHECK LIGHT BULBS AND BATTERY BACKUP
FIRE ALARM
ALARM PANel NEEDS ANNUAL SERVICE
FIRE ALARM SYSTEM MUST HAVE ANNUAL CERTIFICATlON TAG
SPRINKLER
SPRINKLER I STANDPIPE - ANNUAl SERVICE
FIRE SPRINKLERS SHALL BE INSPECTED ANNUAUY AND A SERV1CE TAG PlACED IN CLEAR VIEW
GENERAL
PRIOR VIOLATIONS NOT CORRECTED
EGRESS I EXIT
EXITS OBSTRUCTED LOCKED OR DAMAGED
DOORS SHAU BE ARRANGED TO BE OPENE D REAPllY FROM THE f GRESSSIDE WHENEVER THE BUILDING IS OCCUPIED PENALTY APPUEO FOR BLOCKED EXITS UNDER Pl
HAUVoIAY 1ST FLOOR MAIN KlTCHEN IS OBSTRUCTED
Page1 ALL UFE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDIATELY
I
I
fANNUAL - Commercial gt25000 Assigned To ALEMAN Miguel on 102212012 Date 1012212012 120000AM
location NumMr 838802
Buln Name GULFSTREAM PARKmiddot CLUBHOUSE
Addrt 901 S FEDERAL HWY
CItyStattZlp Hallandale Beach FL 33009
Reclplnt Signature
RI( lpl nt
Page2 ALL LIFE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDIATELY
HALLANDALE BEACH FIRE RESCUE Oioilio Chief G PIaNio paglilruloOcotlbOI9
(oI)4S7- In
Division of Fire Prevention and Pubfic Education n MvaIIol AWnt~ (9544S7-419
121 Sw 3rd Street Hallandale Beacn Florida 33009
~ n Imfgteltgtr if i liampIT ~~CIQ
~J ~i7middot 16
FAX (954) 457middot1472 F1r6IIl~CIO y FelJoo (~~) ~57-3051
eilooGco~bQIQ
FIRE INSPECTION REPORT
ANNUALmiddot Commercial gt25000 Assigned To ALEMAN Miguel on 71812013
Date 10012012 1200S2AM
location Number 836756
Bulne Name MARDI GRAS CASINO
Add 831 N FEDERAL HWf
CltyIStJtJZip HAllANDALE BEACH FL 33009- shyVoltdon StandrslfRtftrtdegCl
GENERAL PRIOR VIOLAnONS NOT CORRECTED
FIRE AlARM ANNUNCIATOR AND NOTIFICATION DEVICES ARE MISSING THROUGHOlfT 4TH FLOOR
SPRINKLER
ESCUTCHEON PLATES MISSING
ESCUTCHEONS (COVERS) useD NITH RECESSED FLUSH-TYPE OR CONCEALED SPRINKLERS SHAll BE PART OF THE LISTED SPRINKLER ASSEMBLY AND REPlACED MiEN MISSING
5TH FLQOR PRESS ANNUNCIATOR ROOM
ELECTRICAl
EXPOSED WIRING
THROUGHOUT 4TH FLOOR REFER TO ELECTRICAL BUILDING DEPARTMENT
FlRE HOSE
FIRE HOSE NEEDS ANNUAL SERVICE
FIRE HOSE MUST BE VISUALLY INSPECTED FOR DAMAGE AND REmiddotROUEQ(RACKED ON AN ANNUAL BASIS WITH THE SERVICE TAG MARKED AND KEPT VIIITH HOSE
THROUGHOUT BUSINESS WAITING FOR LETIER TO BE ABLE TO REMOVE HOSE
ELECTRICAL
NO STORAGE IN MElfR ROOM
rAETER ROOM 5TH FLOOR CAlWALK
GENERAL
CEJUNG TIlES MISSING
5TH FLOOR PHOTO FINISH ROOM AND JUDGE ROOM
REPAIR HOLES IN WAlLS I CEIUNG
3RD FLOOR ELECTRICAL ROOM 3AAND WIRING ROOM
HAZMAT NEED APPROveD FLA_A8LE STORAGE CABIHET
FIRE PUMP ROOM
EGRESS I EXIT MAXIMUM CAPACITY
POST OCCUPANT LOAD SIGN IN CONSPICUOUS P~CE NEAR MAIN EXIT DO NOT EXCEED POSTED NUMBER
2NO FLOOR NORTH SIDE
Page l ALL LIFE SAFETY CODE VIOLA l IONS SHAll BE CORRECTED IMMEDIA TEL Y
ANNUAL - Commerclal gt2$000 Assigned To ALE~N Migllel on 782013
Oete 1013112012 120052AM
Lonlion Ntlmbr 630756
BUI5inU Nal MARDI GRAS CASINO
Addr 831 N FEDERAL HWY
CItyStatelZlp HALLANDALE BEACH FL 33009
Reclpllnt Signature
Rtcipllnt
Page2 ALL L1FE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDlATELY
HALLANDALE BEACH FIRE RESCUE Division of Fire Prevention and Public Education
121 SW 3rd Street Hallandale Bead Florida 33009
FAX (954) 457-1472 1
FIRE INSPECTION REPORT
ANNUALmiddot Commercial (0-5000) Assigned To ALEMAN Miguel on 91612012
Date 9f612012 120000AM
Location Number 188160
SustOItSS Name OCEANS 11 LOUNGE
Addrs 800 N FEDERAL HW
CityStaleJZip HALLANDALE BEACH FL 33009 _-- V IOlation
EGRESS I EXIT
MAXIMUM CAPACITY [S] NFPA 1 - 2006 2014103
POST OCCUPANT lOAD SIGN IN CONSPICUOUS PLACE NEAR MAIN EXIT DO NOT EXCEED POSTED NUMBER
KEY BOX REQUIRED [S] NFPAmiddot 2006116221
FlRE DEPT ACCESS BOX MUST BE INSTALLED MAINTAINED AND KEYS PROVIDED VERIFY rVlTH INSPECTOR WHICH KEYS NEEDED
GENERAL PRIOR VIOlA lIONS NOT CORRECTED
OTHER
PROVIDE INTERIOR FINISH CLASSIFICATION FOR CURTAINS INSIDE BAR AREA
HOoo SYSTEMS
HOOD SYSTEM MUST BE CLEANED (SI NFPA 1 2006 f SO53 TABLEv
ENTIRE EXHAUST SYSTEM MUST BE INSPECTED FOR GREASE BUILDUP BY A CERTIFIED COMPANY AND CLEANED IF NECESSARY AT LEAST SEMImiddotANNUAlLY QUARTERLY IF EXCESSIVE GREASE
FILTERS FOR KITCHEN HOOD SYSTEM MUST BE ClEAN
ELECTRICAL
REMOVE ALL EXTENSION CORDS
EXTENSION CORDS SHALL NOT BE USED AS A SUBSTITUTE FOR PERMANENT WIRING EXTENSION CORDS SHAll NOT EXTEND THROUGH WALLS CEILINGS OR FlOORS OR UNDER DOORS OR FLOOR COVERINGS
HOOD SYSTEMS
HOoo SYSTEM MUST SE CLEANED
ENTIRE EXHAUST SYSTEM MUST BE INSPECTED FOR GREASE BUILDUP BY A CERnFIED COMPANY AND CLEANED IF NECESSARY AT LEAST SEMImiddotANNUALLY QUARTERLY IF eXCESSIVe GREASE
09f0612012
GENERAl
OTHER
090612012 PROVIDE INTERIOR FINISH CLASSIFYCATION FOR CURTAINS IN BAR AREA
PRIOR VIOLATIONS NOT CORRECTED
Page1 AU LIFE SAFElY CODE VOLATtONS SHAlL BE CORRECTED INMEDIA1ElY
ANNUAL - Commercial (0-5000) ASsigned To ALEMAN Mlguamp1 on 91612012 I Date 916120 12 120000AM
ILocatiOtl Number 188160
BulnfJ Name OCEANS 11 LOUNGE
AddrI8$ 800 N FEDERAL rNVV
CltyfStatelZlp HALLANOALE BEACH FL 33009
Rlclplent Signature I Recipient
Page2 All LIFE SAFETY CODE vlouoom SHALl BE CORRECTED IMMEDIATELY
ConlJCjt ua 0i1I101on ChIeI G Pa(llLtllJ1oHALLANDALE BEACH FIRE RESCUE ~ruloregeohborg ~Mmt M Alom Oivision of Fire Prevention and Public Education mII~rtAII4IIcolll9fQ
121 Sw 3rd Street n ~r L W~Im HaRandale Beach Florida 33009 ~~mlCrxgthbOII
FAX (954) 457-1472 L-InpocIGrv Fij~ tOj~~OQ
FIRE INSP~CTION REPORT
ANNUAL - Commercial (0-5000) Assigned To ALEMAN Miguel on 5212013
Oat 512112013 120000AM
Location Numb 838798
BuslrWlU Nam UPPER OECK SPORTS GRILL
AddtelS 906 E HALLANDALE BEACH BLVD
CltylSlafDIZlp HALLANDALE BEACH fL 33009
Voftion
HOOD SYSTEMS
FRVER SEPARATION MISSING (NI NFPA 96 2()0412 124
(NI NFPA 96 200412124
IN] NFPA 96 ~0Olti 1 12125
IN] NFPA 96 200412125 MUST HAVe 16 IN HORIZONTAL OR 81NCH VERTICAL SEPARATION BETWEEN FRYER AND OPEN FLAME APPLIANCES
ELECTRICAL
ELECTRICAL OUTLET pLATE COVER MISSING
ELECTRICAL PANEL OBSTRUCTED
REMOVE ALL EXTENSION CORDS (SI NfPA 1 _ 2006111 15
EXTENSION CORDS SHALL NOT BE USED AS A SUBSTITUTE FOR PERMANENT WIRING EXTENSiON COROS SHALL NOT EXTEND THROUGH WALLS CEIUNGS OR fLOORS OR UNDER DOORS OR FLOOR COVERINGS
KITCHEN AND HOST AREA
EGRESS I EXIT
EMERGENCY LIGITS SHALL BE PROVIDED
EMERGENCY LIGHTS SHALL BE PROVIDED TO ILLUMINATE MEANS OF EGRESS
GENERAL
PRIOR VIOLAnONS NOT CORRECTED
Recipient Signarurt
RecipIent
I Page1 ALL LIFE SAFETY bODE VIOLATIONS SHALL BE CORRECTEO IMMEDIATELY
I 0h0I0kgtn CIWII G PaQ ~~ (964) 4amp7411 IHALLANDALE BEACH FIRE RESCUE iIPIQIi~org
~-Matllll M Alom iS4j457-14111Division of Fire Prevention and Public Education mJltmarllZcohb(gtg f121 Sw 3rd Street Firt IMPIICH L M1IIm (~5) ~ 57middot1 7 8
Hallandale Beach Florida 33009 wIi -Ccob Oro
FAX (954) 457middot1472 F~ 11lIpeclJr Y FeI)o~ Yfl1oo~ootobcx-g
FIRE IHSPECllON REPORT
ANNUAL - Commercial (0-5000) Aslgned To AlEMAN Miguel on 31sno13
DlIte 31512013 120000AM
Location Number 835062
Business Name CHUPULTEPEC
Addu 019-023 NW 2 AVE
CitylStatelZip HALLAN DAlE BEACH FL 33009 Volatioo StjixlardlRe(i[ebull
GENERAL
ADDRESS MISSING ON BUILDING IS) NFPA 1 - 2006101212
MUST BE VISIBLE FROM THE STREET AND IN CONTRASTING COLOR TO THE BUILDING NUMERALS NO lESS THAN 3 INCHES IN HEIGHT FOR RESIDENTIAL 6 INCHES FOR COMMERCIAL
EGREss EXIT
I
EMERGENCY LIGHTS SHAll BE PROVIDED
ErtERGEIICY LIGHTS SHAlL BE PROVIDED TO ILLUMINATE MEANS OF EGRESS CHECK LIGHT eULBS AND BATTERY BACKUP
eXIT SIGNS MUST BE UT AT ALL TIMES bull lt
EVERY EXIT SIGN SHALL BE ILLUMINATED DURING NORMAL AND EMERGENCY OPERA110N NOTIFY INSPECTOR IF LIGHTING SYSTEMS ARE ON TIMERS FROM DUSK TO DAWN OPERATION
CHECK LIGHT BULBS AND BATTERY BACKUP
EXITS OBSTRUCTED LOCKED OR DAMAGED
DOORS SHALL BE ARRANGED TO BE OPENED REAOIl Y FROM THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED PENAlTY APPLIED FOR BLOCKED EXITS UNDER PI
REAR EXIT
MAXIMUM CAPACITY
POST OCCUPANT LOAD SIGN IN CONSPICUOUS PLACE NEAR MAIN EXIT DO NOT EXCEED POSTEa NUMBER
Reclplltnt Sillnatur
ALL LIFE SAFETY CODE V10LATIONS SHAU BE CORRECTED IW(EOIATELY
HALLANDALE BEACH FIRE RESCUE Division of Fire Prevention and Public Education
121 SW 3rd Sireet Hallandale Beach Florida 33009
FAA (954) 457-1472
FIRE INSPECTION REPORT
ANNUAL - Occupational License A$9lgned To ALEMAN Miguel on 71812013
Date 61512013 12OO53AM
Location Nllmblr 94023S
6ulneu Name CLUB FATE
Addr 601 SILKS RUN Unit No 2499
SPRINKLER
SPRINKIER I STANDPIPE - ANNUAL SERVICe
FIRE SPRINKLERS SHAll BE INSPECTED ANNUALLY AND A SERVIcE TAG PLACED IN CLEAR VIEW FIRE SPRINKLER HAS NO TAG
FIRE ALARM
ALARM PANEL NEEDS ANNUAL SERVICE
FIRE ALARM SYSTEM MUST HAVE ANNUAL CERTIFICATION TAG
FA LAST INSPECTION TAG NOVmiddot20
Recipient Signawrt
Recipint
ALL LIFE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDIATELY
HALLANDALE BEACH FIRE RESCUE Division of Fire Prevention and Public Education
121 sw3rd Street Halandala Beach Florida JJ009
FAX ~954) 457-1412
FIRe INSPECTlON REPORT
ANNUAL - Commercial (5000-10000) Assigned To WILLIAMS Lori on 611712013
Date 61312013 12OO00AM
l oeali ll n Number 838954
Business Name CLUB TATlANAS
Addrebullbull 17 10 E HALLANDALE BEACH BLVa
CltylStateJZip HALLANDALE BEACH FL 33009
GENERAL SPECIAL HAZARD
PROVIDE PERMIT FOR REAR RAMP AT EXIT DOOR ON vEST SlOE fIOODEN RAJlP BUlLT W THOUT PERMIT
Reclplnt Signaiurl
~clplnl
Pag~ 1 All UFE SAFETY CooE VlOLAnONS SHALL BE CORRECTED INMEOIATELY
OMtion Ct G p~g (954)$7-1~nHALLANDALE BEACH FIRE RESCUE ~~bV
Fn IBhaI M Ailmln tfS4)S1-1Division of Fire Prevention and Public Education nOoohbOI9
121 SW 3td Street npecllgtf I h (i$ltll nltl Halandale Beltlch Florida 33009 ~ 0c0hbV
F ~Y E~ ~$4)4$7~1 ~OOOCOhbot1l
FAX (954) 457-1472
FIRE INSPECl10N REPORT
ANNUAL - Commercial (0-5000) Assigned To ALEMAN Miguecl on 81272012
Oatt 812712012 120000Ait
Location Numbtr 836786
Busin Nama FLANIGANS
Add 10 N FEDERAL HVIY
CltylStateZip HALLANDALE BEACHF~ 33009 StIndardlB ftrtncbull V10latiOD L~~_~tl=li~i~ii~==~~1I _A
EGRESS EXIT KEY BOX REQUIRED [S) NFPA 1 _ 200618221
FIRE DEPT ACCESS SOX MUST BE INSTALLED MAINTAINED AND KEYS PROVIDED VERIFY WITH INSPECTOR NHICH KEYS NEEDED
GENERAL PRIOR VIOLAnONS NOT CORRECTED
ELECTRICAL
EXPOSED WIRING
BY MAIN ENTRANCE KITCKEN
GE NERAL PRIOR VIOLAliONS NOT CORRECTED
Reelplent Signature
Recipient
Page1 ALL UFE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDIATELY
C91tec Us (9~~)457middot1417
HALLANDALE BEACH FIRE RESCUE (95-)4571479Division of Fire Prevention and Public Education
121 Sw 3rd SIrH1 (5~) 457middot1~78
Hallanc1ale Beach Florida 33009 fAX (954) 457middot1472 19S4) 457-3Cgt51
FIRE INSPECTION REPORT
CERTIFICATE OF OCCUPANCY Assigned To WILLlAMS Lori on 7812013
Date 11121201 2 120000AM
Locllon Numbr 94041 8
Business Name MARTINI BAR
AddlU$ 601 SILKS RUN Unit No 2497
CitylStatelZip HALLANDALE BEACH fL 33009
GENERAL
NO FIRE CODE VIOLA liONS NOTED
NO FIRE CODE VIOLATIONS WERE NOTED DURING THE LISTED INSPECTION INSPECTION WAS SATISFACTORY
PERMIT CLOSEDmiddot CO ISSUED
Recipient Signature
Reciplenl
I Page ALL LIFE SAFETY PODE VIOLATIONS SHALL BE CO RRECTED IMMEDIATEL
CgjCI U DMaIooI Cl~ G PIIJIO I~ ) 457middot ~n _ HALLANDALE BEACH FIRE RESCUE F LIvI W AiIoman (9 So14S141VOivision of Fire Prevention and Public EducaUon
121 S W 3rd Street n1n_l MILo (S SltI ) 4n_4re Halandale Blach Florida 33009 OgchOoro--
FN Iru~cb Y F-too (950t) S7-)()61FAX (954) 4157 472 - FIRE ~sp~cnON REPORT
ANNUAL - Commercial gt25000 Aulgned To ALEMAN Miguel on 102212012
Daw 1012212012 120000AM
loelion Number 838802
Buso HI m GULFSTREAM PARK CLUBHOUSE
Addrn 901 S FEDERAll-fNf
CltyStJtlZlp Hdnnd~ ~each ~l33009
Yiolation
HAlMAT HAZMAT PERMIT NEEDED
FIRST LETTER UAlLED
HAZMAT PERMIT NEEDED
SECOND LETTER MAILED
GENERAl
EMERGENCY OPERATlOHS PlAN REQUIREO III CrTYORDINANCE 18-1131()
lSI FS 553 509 (2Xd)
EMERGENCY OPERATIONS PLAN REQUIRED TO BE WRlITEN MAINTAINED AND ON FILE WITli FIRE RESCUE
LETTE R MAllED
EGRESS I EXIT
EMERGENCY U GHTS SHALL BE PROVIDED
EMERGENCY LIGHTS SHAll BE PROVIDED TO IUUMINATE MEANS OF EGRESS
CHECK LIGHT BULBS AND BATTERY BACKUP
EXIT SIGNS MUST BE LIT AT ALL TIMES
EVERY EXIT SIGN SHALL BE ILLUMINATED DURING NORMALANO EMERGENCY OPERATION NOTIFY INSPECTOR IF LIGHTING SYSTEMS ARE ON TIMERS FROM DUSK TO DAWN OPERATION
CHECK LIGHT BULBS AND BATTERY BACKUP
FIRE ALARM
ALARM PANel NEEDS ANNUAL SERVICE
FIRE ALARM SYSTEM MUST HAVE ANNUAL CERTIFICATlON TAG
SPRINKLER
SPRINKLER I STANDPIPE - ANNUAl SERVICE
FIRE SPRINKLERS SHALL BE INSPECTED ANNUAUY AND A SERV1CE TAG PlACED IN CLEAR VIEW
GENERAL
PRIOR VIOLATIONS NOT CORRECTED
EGRESS I EXIT
EXITS OBSTRUCTED LOCKED OR DAMAGED
DOORS SHAU BE ARRANGED TO BE OPENE D REAPllY FROM THE f GRESSSIDE WHENEVER THE BUILDING IS OCCUPIED PENALTY APPUEO FOR BLOCKED EXITS UNDER Pl
HAUVoIAY 1ST FLOOR MAIN KlTCHEN IS OBSTRUCTED
Page1 ALL UFE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDIATELY
I
I
fANNUAL - Commercial gt25000 Assigned To ALEMAN Miguel on 102212012 Date 1012212012 120000AM
location NumMr 838802
Buln Name GULFSTREAM PARKmiddot CLUBHOUSE
Addrt 901 S FEDERAL HWY
CItyStattZlp Hallandale Beach FL 33009
Reclplnt Signature
RI( lpl nt
Page2 ALL LIFE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDIATELY
HALLANDALE BEACH FIRE RESCUE Oioilio Chief G PIaNio paglilruloOcotlbOI9
(oI)4S7- In
Division of Fire Prevention and Pubfic Education n MvaIIol AWnt~ (9544S7-419
121 Sw 3rd Street Hallandale Beacn Florida 33009
~ n Imfgteltgtr if i liampIT ~~CIQ
~J ~i7middot 16
FAX (954) 457middot1472 F1r6IIl~CIO y FelJoo (~~) ~57-3051
eilooGco~bQIQ
FIRE INSPECTION REPORT
ANNUALmiddot Commercial gt25000 Assigned To ALEMAN Miguel on 71812013
Date 10012012 1200S2AM
location Number 836756
Bulne Name MARDI GRAS CASINO
Add 831 N FEDERAL HWf
CltyIStJtJZip HAllANDALE BEACH FL 33009- shyVoltdon StandrslfRtftrtdegCl
GENERAL PRIOR VIOLAnONS NOT CORRECTED
FIRE AlARM ANNUNCIATOR AND NOTIFICATION DEVICES ARE MISSING THROUGHOlfT 4TH FLOOR
SPRINKLER
ESCUTCHEON PLATES MISSING
ESCUTCHEONS (COVERS) useD NITH RECESSED FLUSH-TYPE OR CONCEALED SPRINKLERS SHAll BE PART OF THE LISTED SPRINKLER ASSEMBLY AND REPlACED MiEN MISSING
5TH FLQOR PRESS ANNUNCIATOR ROOM
ELECTRICAl
EXPOSED WIRING
THROUGHOUT 4TH FLOOR REFER TO ELECTRICAL BUILDING DEPARTMENT
FlRE HOSE
FIRE HOSE NEEDS ANNUAL SERVICE
FIRE HOSE MUST BE VISUALLY INSPECTED FOR DAMAGE AND REmiddotROUEQ(RACKED ON AN ANNUAL BASIS WITH THE SERVICE TAG MARKED AND KEPT VIIITH HOSE
THROUGHOUT BUSINESS WAITING FOR LETIER TO BE ABLE TO REMOVE HOSE
ELECTRICAL
NO STORAGE IN MElfR ROOM
rAETER ROOM 5TH FLOOR CAlWALK
GENERAL
CEJUNG TIlES MISSING
5TH FLOOR PHOTO FINISH ROOM AND JUDGE ROOM
REPAIR HOLES IN WAlLS I CEIUNG
3RD FLOOR ELECTRICAL ROOM 3AAND WIRING ROOM
HAZMAT NEED APPROveD FLA_A8LE STORAGE CABIHET
FIRE PUMP ROOM
EGRESS I EXIT MAXIMUM CAPACITY
POST OCCUPANT LOAD SIGN IN CONSPICUOUS P~CE NEAR MAIN EXIT DO NOT EXCEED POSTED NUMBER
2NO FLOOR NORTH SIDE
Page l ALL LIFE SAFETY CODE VIOLA l IONS SHAll BE CORRECTED IMMEDIA TEL Y
ANNUAL - Commerclal gt2$000 Assigned To ALE~N Migllel on 782013
Oete 1013112012 120052AM
Lonlion Ntlmbr 630756
BUI5inU Nal MARDI GRAS CASINO
Addr 831 N FEDERAL HWY
CItyStatelZlp HALLANDALE BEACH FL 33009
Reclpllnt Signature
Rtcipllnt
Page2 ALL L1FE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDlATELY
HALLANDALE BEACH FIRE RESCUE Division of Fire Prevention and Public Education
121 SW 3rd Street Hallandale Bead Florida 33009
FAX (954) 457-1472 1
FIRE INSPECTION REPORT
ANNUALmiddot Commercial (0-5000) Assigned To ALEMAN Miguel on 91612012
Date 9f612012 120000AM
Location Number 188160
SustOItSS Name OCEANS 11 LOUNGE
Addrs 800 N FEDERAL HW
CityStaleJZip HALLANDALE BEACH FL 33009 _-- V IOlation
EGRESS I EXIT
MAXIMUM CAPACITY [S] NFPA 1 - 2006 2014103
POST OCCUPANT lOAD SIGN IN CONSPICUOUS PLACE NEAR MAIN EXIT DO NOT EXCEED POSTED NUMBER
KEY BOX REQUIRED [S] NFPAmiddot 2006116221
FlRE DEPT ACCESS BOX MUST BE INSTALLED MAINTAINED AND KEYS PROVIDED VERIFY rVlTH INSPECTOR WHICH KEYS NEEDED
GENERAL PRIOR VIOlA lIONS NOT CORRECTED
OTHER
PROVIDE INTERIOR FINISH CLASSIFICATION FOR CURTAINS INSIDE BAR AREA
HOoo SYSTEMS
HOOD SYSTEM MUST BE CLEANED (SI NFPA 1 2006 f SO53 TABLEv
ENTIRE EXHAUST SYSTEM MUST BE INSPECTED FOR GREASE BUILDUP BY A CERTIFIED COMPANY AND CLEANED IF NECESSARY AT LEAST SEMImiddotANNUAlLY QUARTERLY IF EXCESSIVE GREASE
FILTERS FOR KITCHEN HOOD SYSTEM MUST BE ClEAN
ELECTRICAL
REMOVE ALL EXTENSION CORDS
EXTENSION CORDS SHALL NOT BE USED AS A SUBSTITUTE FOR PERMANENT WIRING EXTENSION CORDS SHAll NOT EXTEND THROUGH WALLS CEILINGS OR FlOORS OR UNDER DOORS OR FLOOR COVERINGS
HOOD SYSTEMS
HOoo SYSTEM MUST SE CLEANED
ENTIRE EXHAUST SYSTEM MUST BE INSPECTED FOR GREASE BUILDUP BY A CERnFIED COMPANY AND CLEANED IF NECESSARY AT LEAST SEMImiddotANNUALLY QUARTERLY IF eXCESSIVe GREASE
09f0612012
GENERAl
OTHER
090612012 PROVIDE INTERIOR FINISH CLASSIFYCATION FOR CURTAINS IN BAR AREA
PRIOR VIOLATIONS NOT CORRECTED
Page1 AU LIFE SAFElY CODE VOLATtONS SHAlL BE CORRECTED INMEDIA1ElY
ANNUAL - Commercial (0-5000) ASsigned To ALEMAN Mlguamp1 on 91612012 I Date 916120 12 120000AM
ILocatiOtl Number 188160
BulnfJ Name OCEANS 11 LOUNGE
AddrI8$ 800 N FEDERAL rNVV
CltyfStatelZlp HALLANOALE BEACH FL 33009
Rlclplent Signature I Recipient
Page2 All LIFE SAFETY CODE vlouoom SHALl BE CORRECTED IMMEDIATELY
ConlJCjt ua 0i1I101on ChIeI G Pa(llLtllJ1oHALLANDALE BEACH FIRE RESCUE ~ruloregeohborg ~Mmt M Alom Oivision of Fire Prevention and Public Education mII~rtAII4IIcolll9fQ
121 Sw 3rd Street n ~r L W~Im HaRandale Beach Florida 33009 ~~mlCrxgthbOII
FAX (954) 457-1472 L-InpocIGrv Fij~ tOj~~OQ
FIRE INSP~CTION REPORT
ANNUAL - Commercial (0-5000) Assigned To ALEMAN Miguel on 5212013
Oat 512112013 120000AM
Location Numb 838798
BuslrWlU Nam UPPER OECK SPORTS GRILL
AddtelS 906 E HALLANDALE BEACH BLVD
CltylSlafDIZlp HALLANDALE BEACH fL 33009
Voftion
HOOD SYSTEMS
FRVER SEPARATION MISSING (NI NFPA 96 2()0412 124
(NI NFPA 96 200412124
IN] NFPA 96 ~0Olti 1 12125
IN] NFPA 96 200412125 MUST HAVe 16 IN HORIZONTAL OR 81NCH VERTICAL SEPARATION BETWEEN FRYER AND OPEN FLAME APPLIANCES
ELECTRICAL
ELECTRICAL OUTLET pLATE COVER MISSING
ELECTRICAL PANEL OBSTRUCTED
REMOVE ALL EXTENSION CORDS (SI NfPA 1 _ 2006111 15
EXTENSION CORDS SHALL NOT BE USED AS A SUBSTITUTE FOR PERMANENT WIRING EXTENSiON COROS SHALL NOT EXTEND THROUGH WALLS CEIUNGS OR fLOORS OR UNDER DOORS OR FLOOR COVERINGS
KITCHEN AND HOST AREA
EGRESS I EXIT
EMERGENCY LIGITS SHALL BE PROVIDED
EMERGENCY LIGHTS SHALL BE PROVIDED TO ILLUMINATE MEANS OF EGRESS
GENERAL
PRIOR VIOLAnONS NOT CORRECTED
Recipient Signarurt
RecipIent
I Page1 ALL LIFE SAFETY bODE VIOLATIONS SHALL BE CORRECTEO IMMEDIATELY
HALLANDALE BEACH FIRE RESCUE Division of Fire Prevention and Public Education
121 SW 3rd Sireet Hallandale Beach Florida 33009
FAA (954) 457-1472
FIRE INSPECTION REPORT
ANNUAL - Occupational License A$9lgned To ALEMAN Miguel on 71812013
Date 61512013 12OO53AM
Location Nllmblr 94023S
6ulneu Name CLUB FATE
Addr 601 SILKS RUN Unit No 2499
SPRINKLER
SPRINKIER I STANDPIPE - ANNUAL SERVICe
FIRE SPRINKLERS SHAll BE INSPECTED ANNUALLY AND A SERVIcE TAG PLACED IN CLEAR VIEW FIRE SPRINKLER HAS NO TAG
FIRE ALARM
ALARM PANEL NEEDS ANNUAL SERVICE
FIRE ALARM SYSTEM MUST HAVE ANNUAL CERTIFICATION TAG
FA LAST INSPECTION TAG NOVmiddot20
Recipient Signawrt
Recipint
ALL LIFE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDIATELY
HALLANDALE BEACH FIRE RESCUE Division of Fire Prevention and Public Education
121 sw3rd Street Halandala Beach Florida JJ009
FAX ~954) 457-1412
FIRe INSPECTlON REPORT
ANNUAL - Commercial (5000-10000) Assigned To WILLIAMS Lori on 611712013
Date 61312013 12OO00AM
l oeali ll n Number 838954
Business Name CLUB TATlANAS
Addrebullbull 17 10 E HALLANDALE BEACH BLVa
CltylStateJZip HALLANDALE BEACH FL 33009
GENERAL SPECIAL HAZARD
PROVIDE PERMIT FOR REAR RAMP AT EXIT DOOR ON vEST SlOE fIOODEN RAJlP BUlLT W THOUT PERMIT
Reclplnt Signaiurl
~clplnl
Pag~ 1 All UFE SAFETY CooE VlOLAnONS SHALL BE CORRECTED INMEOIATELY
OMtion Ct G p~g (954)$7-1~nHALLANDALE BEACH FIRE RESCUE ~~bV
Fn IBhaI M Ailmln tfS4)S1-1Division of Fire Prevention and Public Education nOoohbOI9
121 SW 3td Street npecllgtf I h (i$ltll nltl Halandale Beltlch Florida 33009 ~ 0c0hbV
F ~Y E~ ~$4)4$7~1 ~OOOCOhbot1l
FAX (954) 457-1472
FIRE INSPECl10N REPORT
ANNUAL - Commercial (0-5000) Assigned To ALEMAN Miguecl on 81272012
Oatt 812712012 120000Ait
Location Numbtr 836786
Busin Nama FLANIGANS
Add 10 N FEDERAL HVIY
CltylStateZip HALLANDALE BEACHF~ 33009 StIndardlB ftrtncbull V10latiOD L~~_~tl=li~i~ii~==~~1I _A
EGRESS EXIT KEY BOX REQUIRED [S) NFPA 1 _ 200618221
FIRE DEPT ACCESS SOX MUST BE INSTALLED MAINTAINED AND KEYS PROVIDED VERIFY WITH INSPECTOR NHICH KEYS NEEDED
GENERAL PRIOR VIOLAnONS NOT CORRECTED
ELECTRICAL
EXPOSED WIRING
BY MAIN ENTRANCE KITCKEN
GE NERAL PRIOR VIOLAliONS NOT CORRECTED
Reelplent Signature
Recipient
Page1 ALL UFE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDIATELY
C91tec Us (9~~)457middot1417
HALLANDALE BEACH FIRE RESCUE (95-)4571479Division of Fire Prevention and Public Education
121 Sw 3rd SIrH1 (5~) 457middot1~78
Hallanc1ale Beach Florida 33009 fAX (954) 457middot1472 19S4) 457-3Cgt51
FIRE INSPECTION REPORT
CERTIFICATE OF OCCUPANCY Assigned To WILLlAMS Lori on 7812013
Date 11121201 2 120000AM
Locllon Numbr 94041 8
Business Name MARTINI BAR
AddlU$ 601 SILKS RUN Unit No 2497
CitylStatelZip HALLANDALE BEACH fL 33009
GENERAL
NO FIRE CODE VIOLA liONS NOTED
NO FIRE CODE VIOLATIONS WERE NOTED DURING THE LISTED INSPECTION INSPECTION WAS SATISFACTORY
PERMIT CLOSEDmiddot CO ISSUED
Recipient Signature
Reciplenl
I Page ALL LIFE SAFETY PODE VIOLATIONS SHALL BE CO RRECTED IMMEDIATEL
CgjCI U DMaIooI Cl~ G PIIJIO I~ ) 457middot ~n _ HALLANDALE BEACH FIRE RESCUE F LIvI W AiIoman (9 So14S141VOivision of Fire Prevention and Public EducaUon
121 S W 3rd Street n1n_l MILo (S SltI ) 4n_4re Halandale Blach Florida 33009 OgchOoro--
FN Iru~cb Y F-too (950t) S7-)()61FAX (954) 4157 472 - FIRE ~sp~cnON REPORT
ANNUAL - Commercial gt25000 Aulgned To ALEMAN Miguel on 102212012
Daw 1012212012 120000AM
loelion Number 838802
Buso HI m GULFSTREAM PARK CLUBHOUSE
Addrn 901 S FEDERAll-fNf
CltyStJtlZlp Hdnnd~ ~each ~l33009
Yiolation
HAlMAT HAZMAT PERMIT NEEDED
FIRST LETTER UAlLED
HAZMAT PERMIT NEEDED
SECOND LETTER MAILED
GENERAl
EMERGENCY OPERATlOHS PlAN REQUIREO III CrTYORDINANCE 18-1131()
lSI FS 553 509 (2Xd)
EMERGENCY OPERATIONS PLAN REQUIRED TO BE WRlITEN MAINTAINED AND ON FILE WITli FIRE RESCUE
LETTE R MAllED
EGRESS I EXIT
EMERGENCY U GHTS SHALL BE PROVIDED
EMERGENCY LIGHTS SHAll BE PROVIDED TO IUUMINATE MEANS OF EGRESS
CHECK LIGHT BULBS AND BATTERY BACKUP
EXIT SIGNS MUST BE LIT AT ALL TIMES
EVERY EXIT SIGN SHALL BE ILLUMINATED DURING NORMALANO EMERGENCY OPERATION NOTIFY INSPECTOR IF LIGHTING SYSTEMS ARE ON TIMERS FROM DUSK TO DAWN OPERATION
CHECK LIGHT BULBS AND BATTERY BACKUP
FIRE ALARM
ALARM PANel NEEDS ANNUAL SERVICE
FIRE ALARM SYSTEM MUST HAVE ANNUAL CERTIFICATlON TAG
SPRINKLER
SPRINKLER I STANDPIPE - ANNUAl SERVICE
FIRE SPRINKLERS SHALL BE INSPECTED ANNUAUY AND A SERV1CE TAG PlACED IN CLEAR VIEW
GENERAL
PRIOR VIOLATIONS NOT CORRECTED
EGRESS I EXIT
EXITS OBSTRUCTED LOCKED OR DAMAGED
DOORS SHAU BE ARRANGED TO BE OPENE D REAPllY FROM THE f GRESSSIDE WHENEVER THE BUILDING IS OCCUPIED PENALTY APPUEO FOR BLOCKED EXITS UNDER Pl
HAUVoIAY 1ST FLOOR MAIN KlTCHEN IS OBSTRUCTED
Page1 ALL UFE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDIATELY
I
I
fANNUAL - Commercial gt25000 Assigned To ALEMAN Miguel on 102212012 Date 1012212012 120000AM
location NumMr 838802
Buln Name GULFSTREAM PARKmiddot CLUBHOUSE
Addrt 901 S FEDERAL HWY
CItyStattZlp Hallandale Beach FL 33009
Reclplnt Signature
RI( lpl nt
Page2 ALL LIFE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDIATELY
HALLANDALE BEACH FIRE RESCUE Oioilio Chief G PIaNio paglilruloOcotlbOI9
(oI)4S7- In
Division of Fire Prevention and Pubfic Education n MvaIIol AWnt~ (9544S7-419
121 Sw 3rd Street Hallandale Beacn Florida 33009
~ n Imfgteltgtr if i liampIT ~~CIQ
~J ~i7middot 16
FAX (954) 457middot1472 F1r6IIl~CIO y FelJoo (~~) ~57-3051
eilooGco~bQIQ
FIRE INSPECTION REPORT
ANNUALmiddot Commercial gt25000 Assigned To ALEMAN Miguel on 71812013
Date 10012012 1200S2AM
location Number 836756
Bulne Name MARDI GRAS CASINO
Add 831 N FEDERAL HWf
CltyIStJtJZip HAllANDALE BEACH FL 33009- shyVoltdon StandrslfRtftrtdegCl
GENERAL PRIOR VIOLAnONS NOT CORRECTED
FIRE AlARM ANNUNCIATOR AND NOTIFICATION DEVICES ARE MISSING THROUGHOlfT 4TH FLOOR
SPRINKLER
ESCUTCHEON PLATES MISSING
ESCUTCHEONS (COVERS) useD NITH RECESSED FLUSH-TYPE OR CONCEALED SPRINKLERS SHAll BE PART OF THE LISTED SPRINKLER ASSEMBLY AND REPlACED MiEN MISSING
5TH FLQOR PRESS ANNUNCIATOR ROOM
ELECTRICAl
EXPOSED WIRING
THROUGHOUT 4TH FLOOR REFER TO ELECTRICAL BUILDING DEPARTMENT
FlRE HOSE
FIRE HOSE NEEDS ANNUAL SERVICE
FIRE HOSE MUST BE VISUALLY INSPECTED FOR DAMAGE AND REmiddotROUEQ(RACKED ON AN ANNUAL BASIS WITH THE SERVICE TAG MARKED AND KEPT VIIITH HOSE
THROUGHOUT BUSINESS WAITING FOR LETIER TO BE ABLE TO REMOVE HOSE
ELECTRICAL
NO STORAGE IN MElfR ROOM
rAETER ROOM 5TH FLOOR CAlWALK
GENERAL
CEJUNG TIlES MISSING
5TH FLOOR PHOTO FINISH ROOM AND JUDGE ROOM
REPAIR HOLES IN WAlLS I CEIUNG
3RD FLOOR ELECTRICAL ROOM 3AAND WIRING ROOM
HAZMAT NEED APPROveD FLA_A8LE STORAGE CABIHET
FIRE PUMP ROOM
EGRESS I EXIT MAXIMUM CAPACITY
POST OCCUPANT LOAD SIGN IN CONSPICUOUS P~CE NEAR MAIN EXIT DO NOT EXCEED POSTED NUMBER
2NO FLOOR NORTH SIDE
Page l ALL LIFE SAFETY CODE VIOLA l IONS SHAll BE CORRECTED IMMEDIA TEL Y
ANNUAL - Commerclal gt2$000 Assigned To ALE~N Migllel on 782013
Oete 1013112012 120052AM
Lonlion Ntlmbr 630756
BUI5inU Nal MARDI GRAS CASINO
Addr 831 N FEDERAL HWY
CItyStatelZlp HALLANDALE BEACH FL 33009
Reclpllnt Signature
Rtcipllnt
Page2 ALL L1FE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDlATELY
HALLANDALE BEACH FIRE RESCUE Division of Fire Prevention and Public Education
121 SW 3rd Street Hallandale Bead Florida 33009
FAX (954) 457-1472 1
FIRE INSPECTION REPORT
ANNUALmiddot Commercial (0-5000) Assigned To ALEMAN Miguel on 91612012
Date 9f612012 120000AM
Location Number 188160
SustOItSS Name OCEANS 11 LOUNGE
Addrs 800 N FEDERAL HW
CityStaleJZip HALLANDALE BEACH FL 33009 _-- V IOlation
EGRESS I EXIT
MAXIMUM CAPACITY [S] NFPA 1 - 2006 2014103
POST OCCUPANT lOAD SIGN IN CONSPICUOUS PLACE NEAR MAIN EXIT DO NOT EXCEED POSTED NUMBER
KEY BOX REQUIRED [S] NFPAmiddot 2006116221
FlRE DEPT ACCESS BOX MUST BE INSTALLED MAINTAINED AND KEYS PROVIDED VERIFY rVlTH INSPECTOR WHICH KEYS NEEDED
GENERAL PRIOR VIOlA lIONS NOT CORRECTED
OTHER
PROVIDE INTERIOR FINISH CLASSIFICATION FOR CURTAINS INSIDE BAR AREA
HOoo SYSTEMS
HOOD SYSTEM MUST BE CLEANED (SI NFPA 1 2006 f SO53 TABLEv
ENTIRE EXHAUST SYSTEM MUST BE INSPECTED FOR GREASE BUILDUP BY A CERTIFIED COMPANY AND CLEANED IF NECESSARY AT LEAST SEMImiddotANNUAlLY QUARTERLY IF EXCESSIVE GREASE
FILTERS FOR KITCHEN HOOD SYSTEM MUST BE ClEAN
ELECTRICAL
REMOVE ALL EXTENSION CORDS
EXTENSION CORDS SHALL NOT BE USED AS A SUBSTITUTE FOR PERMANENT WIRING EXTENSION CORDS SHAll NOT EXTEND THROUGH WALLS CEILINGS OR FlOORS OR UNDER DOORS OR FLOOR COVERINGS
HOOD SYSTEMS
HOoo SYSTEM MUST SE CLEANED
ENTIRE EXHAUST SYSTEM MUST BE INSPECTED FOR GREASE BUILDUP BY A CERnFIED COMPANY AND CLEANED IF NECESSARY AT LEAST SEMImiddotANNUALLY QUARTERLY IF eXCESSIVe GREASE
09f0612012
GENERAl
OTHER
090612012 PROVIDE INTERIOR FINISH CLASSIFYCATION FOR CURTAINS IN BAR AREA
PRIOR VIOLATIONS NOT CORRECTED
Page1 AU LIFE SAFElY CODE VOLATtONS SHAlL BE CORRECTED INMEDIA1ElY
ANNUAL - Commercial (0-5000) ASsigned To ALEMAN Mlguamp1 on 91612012 I Date 916120 12 120000AM
ILocatiOtl Number 188160
BulnfJ Name OCEANS 11 LOUNGE
AddrI8$ 800 N FEDERAL rNVV
CltyfStatelZlp HALLANOALE BEACH FL 33009
Rlclplent Signature I Recipient
Page2 All LIFE SAFETY CODE vlouoom SHALl BE CORRECTED IMMEDIATELY
ConlJCjt ua 0i1I101on ChIeI G Pa(llLtllJ1oHALLANDALE BEACH FIRE RESCUE ~ruloregeohborg ~Mmt M Alom Oivision of Fire Prevention and Public Education mII~rtAII4IIcolll9fQ
121 Sw 3rd Street n ~r L W~Im HaRandale Beach Florida 33009 ~~mlCrxgthbOII
FAX (954) 457-1472 L-InpocIGrv Fij~ tOj~~OQ
FIRE INSP~CTION REPORT
ANNUAL - Commercial (0-5000) Assigned To ALEMAN Miguel on 5212013
Oat 512112013 120000AM
Location Numb 838798
BuslrWlU Nam UPPER OECK SPORTS GRILL
AddtelS 906 E HALLANDALE BEACH BLVD
CltylSlafDIZlp HALLANDALE BEACH fL 33009
Voftion
HOOD SYSTEMS
FRVER SEPARATION MISSING (NI NFPA 96 2()0412 124
(NI NFPA 96 200412124
IN] NFPA 96 ~0Olti 1 12125
IN] NFPA 96 200412125 MUST HAVe 16 IN HORIZONTAL OR 81NCH VERTICAL SEPARATION BETWEEN FRYER AND OPEN FLAME APPLIANCES
ELECTRICAL
ELECTRICAL OUTLET pLATE COVER MISSING
ELECTRICAL PANEL OBSTRUCTED
REMOVE ALL EXTENSION CORDS (SI NfPA 1 _ 2006111 15
EXTENSION CORDS SHALL NOT BE USED AS A SUBSTITUTE FOR PERMANENT WIRING EXTENSiON COROS SHALL NOT EXTEND THROUGH WALLS CEIUNGS OR fLOORS OR UNDER DOORS OR FLOOR COVERINGS
KITCHEN AND HOST AREA
EGRESS I EXIT
EMERGENCY LIGITS SHALL BE PROVIDED
EMERGENCY LIGHTS SHALL BE PROVIDED TO ILLUMINATE MEANS OF EGRESS
GENERAL
PRIOR VIOLAnONS NOT CORRECTED
Recipient Signarurt
RecipIent
I Page1 ALL LIFE SAFETY bODE VIOLATIONS SHALL BE CORRECTEO IMMEDIATELY
HALLANDALE BEACH FIRE RESCUE Division of Fire Prevention and Public Education
121 sw3rd Street Halandala Beach Florida JJ009
FAX ~954) 457-1412
FIRe INSPECTlON REPORT
ANNUAL - Commercial (5000-10000) Assigned To WILLIAMS Lori on 611712013
Date 61312013 12OO00AM
l oeali ll n Number 838954
Business Name CLUB TATlANAS
Addrebullbull 17 10 E HALLANDALE BEACH BLVa
CltylStateJZip HALLANDALE BEACH FL 33009
GENERAL SPECIAL HAZARD
PROVIDE PERMIT FOR REAR RAMP AT EXIT DOOR ON vEST SlOE fIOODEN RAJlP BUlLT W THOUT PERMIT
Reclplnt Signaiurl
~clplnl
Pag~ 1 All UFE SAFETY CooE VlOLAnONS SHALL BE CORRECTED INMEOIATELY
OMtion Ct G p~g (954)$7-1~nHALLANDALE BEACH FIRE RESCUE ~~bV
Fn IBhaI M Ailmln tfS4)S1-1Division of Fire Prevention and Public Education nOoohbOI9
121 SW 3td Street npecllgtf I h (i$ltll nltl Halandale Beltlch Florida 33009 ~ 0c0hbV
F ~Y E~ ~$4)4$7~1 ~OOOCOhbot1l
FAX (954) 457-1472
FIRE INSPECl10N REPORT
ANNUAL - Commercial (0-5000) Assigned To ALEMAN Miguecl on 81272012
Oatt 812712012 120000Ait
Location Numbtr 836786
Busin Nama FLANIGANS
Add 10 N FEDERAL HVIY
CltylStateZip HALLANDALE BEACHF~ 33009 StIndardlB ftrtncbull V10latiOD L~~_~tl=li~i~ii~==~~1I _A
EGRESS EXIT KEY BOX REQUIRED [S) NFPA 1 _ 200618221
FIRE DEPT ACCESS SOX MUST BE INSTALLED MAINTAINED AND KEYS PROVIDED VERIFY WITH INSPECTOR NHICH KEYS NEEDED
GENERAL PRIOR VIOLAnONS NOT CORRECTED
ELECTRICAL
EXPOSED WIRING
BY MAIN ENTRANCE KITCKEN
GE NERAL PRIOR VIOLAliONS NOT CORRECTED
Reelplent Signature
Recipient
Page1 ALL UFE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDIATELY
C91tec Us (9~~)457middot1417
HALLANDALE BEACH FIRE RESCUE (95-)4571479Division of Fire Prevention and Public Education
121 Sw 3rd SIrH1 (5~) 457middot1~78
Hallanc1ale Beach Florida 33009 fAX (954) 457middot1472 19S4) 457-3Cgt51
FIRE INSPECTION REPORT
CERTIFICATE OF OCCUPANCY Assigned To WILLlAMS Lori on 7812013
Date 11121201 2 120000AM
Locllon Numbr 94041 8
Business Name MARTINI BAR
AddlU$ 601 SILKS RUN Unit No 2497
CitylStatelZip HALLANDALE BEACH fL 33009
GENERAL
NO FIRE CODE VIOLA liONS NOTED
NO FIRE CODE VIOLATIONS WERE NOTED DURING THE LISTED INSPECTION INSPECTION WAS SATISFACTORY
PERMIT CLOSEDmiddot CO ISSUED
Recipient Signature
Reciplenl
I Page ALL LIFE SAFETY PODE VIOLATIONS SHALL BE CO RRECTED IMMEDIATEL
CgjCI U DMaIooI Cl~ G PIIJIO I~ ) 457middot ~n _ HALLANDALE BEACH FIRE RESCUE F LIvI W AiIoman (9 So14S141VOivision of Fire Prevention and Public EducaUon
121 S W 3rd Street n1n_l MILo (S SltI ) 4n_4re Halandale Blach Florida 33009 OgchOoro--
FN Iru~cb Y F-too (950t) S7-)()61FAX (954) 4157 472 - FIRE ~sp~cnON REPORT
ANNUAL - Commercial gt25000 Aulgned To ALEMAN Miguel on 102212012
Daw 1012212012 120000AM
loelion Number 838802
Buso HI m GULFSTREAM PARK CLUBHOUSE
Addrn 901 S FEDERAll-fNf
CltyStJtlZlp Hdnnd~ ~each ~l33009
Yiolation
HAlMAT HAZMAT PERMIT NEEDED
FIRST LETTER UAlLED
HAZMAT PERMIT NEEDED
SECOND LETTER MAILED
GENERAl
EMERGENCY OPERATlOHS PlAN REQUIREO III CrTYORDINANCE 18-1131()
lSI FS 553 509 (2Xd)
EMERGENCY OPERATIONS PLAN REQUIRED TO BE WRlITEN MAINTAINED AND ON FILE WITli FIRE RESCUE
LETTE R MAllED
EGRESS I EXIT
EMERGENCY U GHTS SHALL BE PROVIDED
EMERGENCY LIGHTS SHAll BE PROVIDED TO IUUMINATE MEANS OF EGRESS
CHECK LIGHT BULBS AND BATTERY BACKUP
EXIT SIGNS MUST BE LIT AT ALL TIMES
EVERY EXIT SIGN SHALL BE ILLUMINATED DURING NORMALANO EMERGENCY OPERATION NOTIFY INSPECTOR IF LIGHTING SYSTEMS ARE ON TIMERS FROM DUSK TO DAWN OPERATION
CHECK LIGHT BULBS AND BATTERY BACKUP
FIRE ALARM
ALARM PANel NEEDS ANNUAL SERVICE
FIRE ALARM SYSTEM MUST HAVE ANNUAL CERTIFICATlON TAG
SPRINKLER
SPRINKLER I STANDPIPE - ANNUAl SERVICE
FIRE SPRINKLERS SHALL BE INSPECTED ANNUAUY AND A SERV1CE TAG PlACED IN CLEAR VIEW
GENERAL
PRIOR VIOLATIONS NOT CORRECTED
EGRESS I EXIT
EXITS OBSTRUCTED LOCKED OR DAMAGED
DOORS SHAU BE ARRANGED TO BE OPENE D REAPllY FROM THE f GRESSSIDE WHENEVER THE BUILDING IS OCCUPIED PENALTY APPUEO FOR BLOCKED EXITS UNDER Pl
HAUVoIAY 1ST FLOOR MAIN KlTCHEN IS OBSTRUCTED
Page1 ALL UFE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDIATELY
I
I
fANNUAL - Commercial gt25000 Assigned To ALEMAN Miguel on 102212012 Date 1012212012 120000AM
location NumMr 838802
Buln Name GULFSTREAM PARKmiddot CLUBHOUSE
Addrt 901 S FEDERAL HWY
CItyStattZlp Hallandale Beach FL 33009
Reclplnt Signature
RI( lpl nt
Page2 ALL LIFE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDIATELY
HALLANDALE BEACH FIRE RESCUE Oioilio Chief G PIaNio paglilruloOcotlbOI9
(oI)4S7- In
Division of Fire Prevention and Pubfic Education n MvaIIol AWnt~ (9544S7-419
121 Sw 3rd Street Hallandale Beacn Florida 33009
~ n Imfgteltgtr if i liampIT ~~CIQ
~J ~i7middot 16
FAX (954) 457middot1472 F1r6IIl~CIO y FelJoo (~~) ~57-3051
eilooGco~bQIQ
FIRE INSPECTION REPORT
ANNUALmiddot Commercial gt25000 Assigned To ALEMAN Miguel on 71812013
Date 10012012 1200S2AM
location Number 836756
Bulne Name MARDI GRAS CASINO
Add 831 N FEDERAL HWf
CltyIStJtJZip HAllANDALE BEACH FL 33009- shyVoltdon StandrslfRtftrtdegCl
GENERAL PRIOR VIOLAnONS NOT CORRECTED
FIRE AlARM ANNUNCIATOR AND NOTIFICATION DEVICES ARE MISSING THROUGHOlfT 4TH FLOOR
SPRINKLER
ESCUTCHEON PLATES MISSING
ESCUTCHEONS (COVERS) useD NITH RECESSED FLUSH-TYPE OR CONCEALED SPRINKLERS SHAll BE PART OF THE LISTED SPRINKLER ASSEMBLY AND REPlACED MiEN MISSING
5TH FLQOR PRESS ANNUNCIATOR ROOM
ELECTRICAl
EXPOSED WIRING
THROUGHOUT 4TH FLOOR REFER TO ELECTRICAL BUILDING DEPARTMENT
FlRE HOSE
FIRE HOSE NEEDS ANNUAL SERVICE
FIRE HOSE MUST BE VISUALLY INSPECTED FOR DAMAGE AND REmiddotROUEQ(RACKED ON AN ANNUAL BASIS WITH THE SERVICE TAG MARKED AND KEPT VIIITH HOSE
THROUGHOUT BUSINESS WAITING FOR LETIER TO BE ABLE TO REMOVE HOSE
ELECTRICAL
NO STORAGE IN MElfR ROOM
rAETER ROOM 5TH FLOOR CAlWALK
GENERAL
CEJUNG TIlES MISSING
5TH FLOOR PHOTO FINISH ROOM AND JUDGE ROOM
REPAIR HOLES IN WAlLS I CEIUNG
3RD FLOOR ELECTRICAL ROOM 3AAND WIRING ROOM
HAZMAT NEED APPROveD FLA_A8LE STORAGE CABIHET
FIRE PUMP ROOM
EGRESS I EXIT MAXIMUM CAPACITY
POST OCCUPANT LOAD SIGN IN CONSPICUOUS P~CE NEAR MAIN EXIT DO NOT EXCEED POSTED NUMBER
2NO FLOOR NORTH SIDE
Page l ALL LIFE SAFETY CODE VIOLA l IONS SHAll BE CORRECTED IMMEDIA TEL Y
ANNUAL - Commerclal gt2$000 Assigned To ALE~N Migllel on 782013
Oete 1013112012 120052AM
Lonlion Ntlmbr 630756
BUI5inU Nal MARDI GRAS CASINO
Addr 831 N FEDERAL HWY
CItyStatelZlp HALLANDALE BEACH FL 33009
Reclpllnt Signature
Rtcipllnt
Page2 ALL L1FE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDlATELY
HALLANDALE BEACH FIRE RESCUE Division of Fire Prevention and Public Education
121 SW 3rd Street Hallandale Bead Florida 33009
FAX (954) 457-1472 1
FIRE INSPECTION REPORT
ANNUALmiddot Commercial (0-5000) Assigned To ALEMAN Miguel on 91612012
Date 9f612012 120000AM
Location Number 188160
SustOItSS Name OCEANS 11 LOUNGE
Addrs 800 N FEDERAL HW
CityStaleJZip HALLANDALE BEACH FL 33009 _-- V IOlation
EGRESS I EXIT
MAXIMUM CAPACITY [S] NFPA 1 - 2006 2014103
POST OCCUPANT lOAD SIGN IN CONSPICUOUS PLACE NEAR MAIN EXIT DO NOT EXCEED POSTED NUMBER
KEY BOX REQUIRED [S] NFPAmiddot 2006116221
FlRE DEPT ACCESS BOX MUST BE INSTALLED MAINTAINED AND KEYS PROVIDED VERIFY rVlTH INSPECTOR WHICH KEYS NEEDED
GENERAL PRIOR VIOlA lIONS NOT CORRECTED
OTHER
PROVIDE INTERIOR FINISH CLASSIFICATION FOR CURTAINS INSIDE BAR AREA
HOoo SYSTEMS
HOOD SYSTEM MUST BE CLEANED (SI NFPA 1 2006 f SO53 TABLEv
ENTIRE EXHAUST SYSTEM MUST BE INSPECTED FOR GREASE BUILDUP BY A CERTIFIED COMPANY AND CLEANED IF NECESSARY AT LEAST SEMImiddotANNUAlLY QUARTERLY IF EXCESSIVE GREASE
FILTERS FOR KITCHEN HOOD SYSTEM MUST BE ClEAN
ELECTRICAL
REMOVE ALL EXTENSION CORDS
EXTENSION CORDS SHALL NOT BE USED AS A SUBSTITUTE FOR PERMANENT WIRING EXTENSION CORDS SHAll NOT EXTEND THROUGH WALLS CEILINGS OR FlOORS OR UNDER DOORS OR FLOOR COVERINGS
HOOD SYSTEMS
HOoo SYSTEM MUST SE CLEANED
ENTIRE EXHAUST SYSTEM MUST BE INSPECTED FOR GREASE BUILDUP BY A CERnFIED COMPANY AND CLEANED IF NECESSARY AT LEAST SEMImiddotANNUALLY QUARTERLY IF eXCESSIVe GREASE
09f0612012
GENERAl
OTHER
090612012 PROVIDE INTERIOR FINISH CLASSIFYCATION FOR CURTAINS IN BAR AREA
PRIOR VIOLATIONS NOT CORRECTED
Page1 AU LIFE SAFElY CODE VOLATtONS SHAlL BE CORRECTED INMEDIA1ElY
ANNUAL - Commercial (0-5000) ASsigned To ALEMAN Mlguamp1 on 91612012 I Date 916120 12 120000AM
ILocatiOtl Number 188160
BulnfJ Name OCEANS 11 LOUNGE
AddrI8$ 800 N FEDERAL rNVV
CltyfStatelZlp HALLANOALE BEACH FL 33009
Rlclplent Signature I Recipient
Page2 All LIFE SAFETY CODE vlouoom SHALl BE CORRECTED IMMEDIATELY
ConlJCjt ua 0i1I101on ChIeI G Pa(llLtllJ1oHALLANDALE BEACH FIRE RESCUE ~ruloregeohborg ~Mmt M Alom Oivision of Fire Prevention and Public Education mII~rtAII4IIcolll9fQ
121 Sw 3rd Street n ~r L W~Im HaRandale Beach Florida 33009 ~~mlCrxgthbOII
FAX (954) 457-1472 L-InpocIGrv Fij~ tOj~~OQ
FIRE INSP~CTION REPORT
ANNUAL - Commercial (0-5000) Assigned To ALEMAN Miguel on 5212013
Oat 512112013 120000AM
Location Numb 838798
BuslrWlU Nam UPPER OECK SPORTS GRILL
AddtelS 906 E HALLANDALE BEACH BLVD
CltylSlafDIZlp HALLANDALE BEACH fL 33009
Voftion
HOOD SYSTEMS
FRVER SEPARATION MISSING (NI NFPA 96 2()0412 124
(NI NFPA 96 200412124
IN] NFPA 96 ~0Olti 1 12125
IN] NFPA 96 200412125 MUST HAVe 16 IN HORIZONTAL OR 81NCH VERTICAL SEPARATION BETWEEN FRYER AND OPEN FLAME APPLIANCES
ELECTRICAL
ELECTRICAL OUTLET pLATE COVER MISSING
ELECTRICAL PANEL OBSTRUCTED
REMOVE ALL EXTENSION CORDS (SI NfPA 1 _ 2006111 15
EXTENSION CORDS SHALL NOT BE USED AS A SUBSTITUTE FOR PERMANENT WIRING EXTENSiON COROS SHALL NOT EXTEND THROUGH WALLS CEIUNGS OR fLOORS OR UNDER DOORS OR FLOOR COVERINGS
KITCHEN AND HOST AREA
EGRESS I EXIT
EMERGENCY LIGITS SHALL BE PROVIDED
EMERGENCY LIGHTS SHALL BE PROVIDED TO ILLUMINATE MEANS OF EGRESS
GENERAL
PRIOR VIOLAnONS NOT CORRECTED
Recipient Signarurt
RecipIent
I Page1 ALL LIFE SAFETY bODE VIOLATIONS SHALL BE CORRECTEO IMMEDIATELY
OMtion Ct G p~g (954)$7-1~nHALLANDALE BEACH FIRE RESCUE ~~bV
Fn IBhaI M Ailmln tfS4)S1-1Division of Fire Prevention and Public Education nOoohbOI9
121 SW 3td Street npecllgtf I h (i$ltll nltl Halandale Beltlch Florida 33009 ~ 0c0hbV
F ~Y E~ ~$4)4$7~1 ~OOOCOhbot1l
FAX (954) 457-1472
FIRE INSPECl10N REPORT
ANNUAL - Commercial (0-5000) Assigned To ALEMAN Miguecl on 81272012
Oatt 812712012 120000Ait
Location Numbtr 836786
Busin Nama FLANIGANS
Add 10 N FEDERAL HVIY
CltylStateZip HALLANDALE BEACHF~ 33009 StIndardlB ftrtncbull V10latiOD L~~_~tl=li~i~ii~==~~1I _A
EGRESS EXIT KEY BOX REQUIRED [S) NFPA 1 _ 200618221
FIRE DEPT ACCESS SOX MUST BE INSTALLED MAINTAINED AND KEYS PROVIDED VERIFY WITH INSPECTOR NHICH KEYS NEEDED
GENERAL PRIOR VIOLAnONS NOT CORRECTED
ELECTRICAL
EXPOSED WIRING
BY MAIN ENTRANCE KITCKEN
GE NERAL PRIOR VIOLAliONS NOT CORRECTED
Reelplent Signature
Recipient
Page1 ALL UFE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDIATELY
C91tec Us (9~~)457middot1417
HALLANDALE BEACH FIRE RESCUE (95-)4571479Division of Fire Prevention and Public Education
121 Sw 3rd SIrH1 (5~) 457middot1~78
Hallanc1ale Beach Florida 33009 fAX (954) 457middot1472 19S4) 457-3Cgt51
FIRE INSPECTION REPORT
CERTIFICATE OF OCCUPANCY Assigned To WILLlAMS Lori on 7812013
Date 11121201 2 120000AM
Locllon Numbr 94041 8
Business Name MARTINI BAR
AddlU$ 601 SILKS RUN Unit No 2497
CitylStatelZip HALLANDALE BEACH fL 33009
GENERAL
NO FIRE CODE VIOLA liONS NOTED
NO FIRE CODE VIOLATIONS WERE NOTED DURING THE LISTED INSPECTION INSPECTION WAS SATISFACTORY
PERMIT CLOSEDmiddot CO ISSUED
Recipient Signature
Reciplenl
I Page ALL LIFE SAFETY PODE VIOLATIONS SHALL BE CO RRECTED IMMEDIATEL
CgjCI U DMaIooI Cl~ G PIIJIO I~ ) 457middot ~n _ HALLANDALE BEACH FIRE RESCUE F LIvI W AiIoman (9 So14S141VOivision of Fire Prevention and Public EducaUon
121 S W 3rd Street n1n_l MILo (S SltI ) 4n_4re Halandale Blach Florida 33009 OgchOoro--
FN Iru~cb Y F-too (950t) S7-)()61FAX (954) 4157 472 - FIRE ~sp~cnON REPORT
ANNUAL - Commercial gt25000 Aulgned To ALEMAN Miguel on 102212012
Daw 1012212012 120000AM
loelion Number 838802
Buso HI m GULFSTREAM PARK CLUBHOUSE
Addrn 901 S FEDERAll-fNf
CltyStJtlZlp Hdnnd~ ~each ~l33009
Yiolation
HAlMAT HAZMAT PERMIT NEEDED
FIRST LETTER UAlLED
HAZMAT PERMIT NEEDED
SECOND LETTER MAILED
GENERAl
EMERGENCY OPERATlOHS PlAN REQUIREO III CrTYORDINANCE 18-1131()
lSI FS 553 509 (2Xd)
EMERGENCY OPERATIONS PLAN REQUIRED TO BE WRlITEN MAINTAINED AND ON FILE WITli FIRE RESCUE
LETTE R MAllED
EGRESS I EXIT
EMERGENCY U GHTS SHALL BE PROVIDED
EMERGENCY LIGHTS SHAll BE PROVIDED TO IUUMINATE MEANS OF EGRESS
CHECK LIGHT BULBS AND BATTERY BACKUP
EXIT SIGNS MUST BE LIT AT ALL TIMES
EVERY EXIT SIGN SHALL BE ILLUMINATED DURING NORMALANO EMERGENCY OPERATION NOTIFY INSPECTOR IF LIGHTING SYSTEMS ARE ON TIMERS FROM DUSK TO DAWN OPERATION
CHECK LIGHT BULBS AND BATTERY BACKUP
FIRE ALARM
ALARM PANel NEEDS ANNUAL SERVICE
FIRE ALARM SYSTEM MUST HAVE ANNUAL CERTIFICATlON TAG
SPRINKLER
SPRINKLER I STANDPIPE - ANNUAl SERVICE
FIRE SPRINKLERS SHALL BE INSPECTED ANNUAUY AND A SERV1CE TAG PlACED IN CLEAR VIEW
GENERAL
PRIOR VIOLATIONS NOT CORRECTED
EGRESS I EXIT
EXITS OBSTRUCTED LOCKED OR DAMAGED
DOORS SHAU BE ARRANGED TO BE OPENE D REAPllY FROM THE f GRESSSIDE WHENEVER THE BUILDING IS OCCUPIED PENALTY APPUEO FOR BLOCKED EXITS UNDER Pl
HAUVoIAY 1ST FLOOR MAIN KlTCHEN IS OBSTRUCTED
Page1 ALL UFE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDIATELY
I
I
fANNUAL - Commercial gt25000 Assigned To ALEMAN Miguel on 102212012 Date 1012212012 120000AM
location NumMr 838802
Buln Name GULFSTREAM PARKmiddot CLUBHOUSE
Addrt 901 S FEDERAL HWY
CItyStattZlp Hallandale Beach FL 33009
Reclplnt Signature
RI( lpl nt
Page2 ALL LIFE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDIATELY
HALLANDALE BEACH FIRE RESCUE Oioilio Chief G PIaNio paglilruloOcotlbOI9
(oI)4S7- In
Division of Fire Prevention and Pubfic Education n MvaIIol AWnt~ (9544S7-419
121 Sw 3rd Street Hallandale Beacn Florida 33009
~ n Imfgteltgtr if i liampIT ~~CIQ
~J ~i7middot 16
FAX (954) 457middot1472 F1r6IIl~CIO y FelJoo (~~) ~57-3051
eilooGco~bQIQ
FIRE INSPECTION REPORT
ANNUALmiddot Commercial gt25000 Assigned To ALEMAN Miguel on 71812013
Date 10012012 1200S2AM
location Number 836756
Bulne Name MARDI GRAS CASINO
Add 831 N FEDERAL HWf
CltyIStJtJZip HAllANDALE BEACH FL 33009- shyVoltdon StandrslfRtftrtdegCl
GENERAL PRIOR VIOLAnONS NOT CORRECTED
FIRE AlARM ANNUNCIATOR AND NOTIFICATION DEVICES ARE MISSING THROUGHOlfT 4TH FLOOR
SPRINKLER
ESCUTCHEON PLATES MISSING
ESCUTCHEONS (COVERS) useD NITH RECESSED FLUSH-TYPE OR CONCEALED SPRINKLERS SHAll BE PART OF THE LISTED SPRINKLER ASSEMBLY AND REPlACED MiEN MISSING
5TH FLQOR PRESS ANNUNCIATOR ROOM
ELECTRICAl
EXPOSED WIRING
THROUGHOUT 4TH FLOOR REFER TO ELECTRICAL BUILDING DEPARTMENT
FlRE HOSE
FIRE HOSE NEEDS ANNUAL SERVICE
FIRE HOSE MUST BE VISUALLY INSPECTED FOR DAMAGE AND REmiddotROUEQ(RACKED ON AN ANNUAL BASIS WITH THE SERVICE TAG MARKED AND KEPT VIIITH HOSE
THROUGHOUT BUSINESS WAITING FOR LETIER TO BE ABLE TO REMOVE HOSE
ELECTRICAL
NO STORAGE IN MElfR ROOM
rAETER ROOM 5TH FLOOR CAlWALK
GENERAL
CEJUNG TIlES MISSING
5TH FLOOR PHOTO FINISH ROOM AND JUDGE ROOM
REPAIR HOLES IN WAlLS I CEIUNG
3RD FLOOR ELECTRICAL ROOM 3AAND WIRING ROOM
HAZMAT NEED APPROveD FLA_A8LE STORAGE CABIHET
FIRE PUMP ROOM
EGRESS I EXIT MAXIMUM CAPACITY
POST OCCUPANT LOAD SIGN IN CONSPICUOUS P~CE NEAR MAIN EXIT DO NOT EXCEED POSTED NUMBER
2NO FLOOR NORTH SIDE
Page l ALL LIFE SAFETY CODE VIOLA l IONS SHAll BE CORRECTED IMMEDIA TEL Y
ANNUAL - Commerclal gt2$000 Assigned To ALE~N Migllel on 782013
Oete 1013112012 120052AM
Lonlion Ntlmbr 630756
BUI5inU Nal MARDI GRAS CASINO
Addr 831 N FEDERAL HWY
CItyStatelZlp HALLANDALE BEACH FL 33009
Reclpllnt Signature
Rtcipllnt
Page2 ALL L1FE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDlATELY
HALLANDALE BEACH FIRE RESCUE Division of Fire Prevention and Public Education
121 SW 3rd Street Hallandale Bead Florida 33009
FAX (954) 457-1472 1
FIRE INSPECTION REPORT
ANNUALmiddot Commercial (0-5000) Assigned To ALEMAN Miguel on 91612012
Date 9f612012 120000AM
Location Number 188160
SustOItSS Name OCEANS 11 LOUNGE
Addrs 800 N FEDERAL HW
CityStaleJZip HALLANDALE BEACH FL 33009 _-- V IOlation
EGRESS I EXIT
MAXIMUM CAPACITY [S] NFPA 1 - 2006 2014103
POST OCCUPANT lOAD SIGN IN CONSPICUOUS PLACE NEAR MAIN EXIT DO NOT EXCEED POSTED NUMBER
KEY BOX REQUIRED [S] NFPAmiddot 2006116221
FlRE DEPT ACCESS BOX MUST BE INSTALLED MAINTAINED AND KEYS PROVIDED VERIFY rVlTH INSPECTOR WHICH KEYS NEEDED
GENERAL PRIOR VIOlA lIONS NOT CORRECTED
OTHER
PROVIDE INTERIOR FINISH CLASSIFICATION FOR CURTAINS INSIDE BAR AREA
HOoo SYSTEMS
HOOD SYSTEM MUST BE CLEANED (SI NFPA 1 2006 f SO53 TABLEv
ENTIRE EXHAUST SYSTEM MUST BE INSPECTED FOR GREASE BUILDUP BY A CERTIFIED COMPANY AND CLEANED IF NECESSARY AT LEAST SEMImiddotANNUAlLY QUARTERLY IF EXCESSIVE GREASE
FILTERS FOR KITCHEN HOOD SYSTEM MUST BE ClEAN
ELECTRICAL
REMOVE ALL EXTENSION CORDS
EXTENSION CORDS SHALL NOT BE USED AS A SUBSTITUTE FOR PERMANENT WIRING EXTENSION CORDS SHAll NOT EXTEND THROUGH WALLS CEILINGS OR FlOORS OR UNDER DOORS OR FLOOR COVERINGS
HOOD SYSTEMS
HOoo SYSTEM MUST SE CLEANED
ENTIRE EXHAUST SYSTEM MUST BE INSPECTED FOR GREASE BUILDUP BY A CERnFIED COMPANY AND CLEANED IF NECESSARY AT LEAST SEMImiddotANNUALLY QUARTERLY IF eXCESSIVe GREASE
09f0612012
GENERAl
OTHER
090612012 PROVIDE INTERIOR FINISH CLASSIFYCATION FOR CURTAINS IN BAR AREA
PRIOR VIOLATIONS NOT CORRECTED
Page1 AU LIFE SAFElY CODE VOLATtONS SHAlL BE CORRECTED INMEDIA1ElY
ANNUAL - Commercial (0-5000) ASsigned To ALEMAN Mlguamp1 on 91612012 I Date 916120 12 120000AM
ILocatiOtl Number 188160
BulnfJ Name OCEANS 11 LOUNGE
AddrI8$ 800 N FEDERAL rNVV
CltyfStatelZlp HALLANOALE BEACH FL 33009
Rlclplent Signature I Recipient
Page2 All LIFE SAFETY CODE vlouoom SHALl BE CORRECTED IMMEDIATELY
ConlJCjt ua 0i1I101on ChIeI G Pa(llLtllJ1oHALLANDALE BEACH FIRE RESCUE ~ruloregeohborg ~Mmt M Alom Oivision of Fire Prevention and Public Education mII~rtAII4IIcolll9fQ
121 Sw 3rd Street n ~r L W~Im HaRandale Beach Florida 33009 ~~mlCrxgthbOII
FAX (954) 457-1472 L-InpocIGrv Fij~ tOj~~OQ
FIRE INSP~CTION REPORT
ANNUAL - Commercial (0-5000) Assigned To ALEMAN Miguel on 5212013
Oat 512112013 120000AM
Location Numb 838798
BuslrWlU Nam UPPER OECK SPORTS GRILL
AddtelS 906 E HALLANDALE BEACH BLVD
CltylSlafDIZlp HALLANDALE BEACH fL 33009
Voftion
HOOD SYSTEMS
FRVER SEPARATION MISSING (NI NFPA 96 2()0412 124
(NI NFPA 96 200412124
IN] NFPA 96 ~0Olti 1 12125
IN] NFPA 96 200412125 MUST HAVe 16 IN HORIZONTAL OR 81NCH VERTICAL SEPARATION BETWEEN FRYER AND OPEN FLAME APPLIANCES
ELECTRICAL
ELECTRICAL OUTLET pLATE COVER MISSING
ELECTRICAL PANEL OBSTRUCTED
REMOVE ALL EXTENSION CORDS (SI NfPA 1 _ 2006111 15
EXTENSION CORDS SHALL NOT BE USED AS A SUBSTITUTE FOR PERMANENT WIRING EXTENSiON COROS SHALL NOT EXTEND THROUGH WALLS CEIUNGS OR fLOORS OR UNDER DOORS OR FLOOR COVERINGS
KITCHEN AND HOST AREA
EGRESS I EXIT
EMERGENCY LIGITS SHALL BE PROVIDED
EMERGENCY LIGHTS SHALL BE PROVIDED TO ILLUMINATE MEANS OF EGRESS
GENERAL
PRIOR VIOLAnONS NOT CORRECTED
Recipient Signarurt
RecipIent
I Page1 ALL LIFE SAFETY bODE VIOLATIONS SHALL BE CORRECTEO IMMEDIATELY
C91tec Us (9~~)457middot1417
HALLANDALE BEACH FIRE RESCUE (95-)4571479Division of Fire Prevention and Public Education
121 Sw 3rd SIrH1 (5~) 457middot1~78
Hallanc1ale Beach Florida 33009 fAX (954) 457middot1472 19S4) 457-3Cgt51
FIRE INSPECTION REPORT
CERTIFICATE OF OCCUPANCY Assigned To WILLlAMS Lori on 7812013
Date 11121201 2 120000AM
Locllon Numbr 94041 8
Business Name MARTINI BAR
AddlU$ 601 SILKS RUN Unit No 2497
CitylStatelZip HALLANDALE BEACH fL 33009
GENERAL
NO FIRE CODE VIOLA liONS NOTED
NO FIRE CODE VIOLATIONS WERE NOTED DURING THE LISTED INSPECTION INSPECTION WAS SATISFACTORY
PERMIT CLOSEDmiddot CO ISSUED
Recipient Signature
Reciplenl
I Page ALL LIFE SAFETY PODE VIOLATIONS SHALL BE CO RRECTED IMMEDIATEL
CgjCI U DMaIooI Cl~ G PIIJIO I~ ) 457middot ~n _ HALLANDALE BEACH FIRE RESCUE F LIvI W AiIoman (9 So14S141VOivision of Fire Prevention and Public EducaUon
121 S W 3rd Street n1n_l MILo (S SltI ) 4n_4re Halandale Blach Florida 33009 OgchOoro--
FN Iru~cb Y F-too (950t) S7-)()61FAX (954) 4157 472 - FIRE ~sp~cnON REPORT
ANNUAL - Commercial gt25000 Aulgned To ALEMAN Miguel on 102212012
Daw 1012212012 120000AM
loelion Number 838802
Buso HI m GULFSTREAM PARK CLUBHOUSE
Addrn 901 S FEDERAll-fNf
CltyStJtlZlp Hdnnd~ ~each ~l33009
Yiolation
HAlMAT HAZMAT PERMIT NEEDED
FIRST LETTER UAlLED
HAZMAT PERMIT NEEDED
SECOND LETTER MAILED
GENERAl
EMERGENCY OPERATlOHS PlAN REQUIREO III CrTYORDINANCE 18-1131()
lSI FS 553 509 (2Xd)
EMERGENCY OPERATIONS PLAN REQUIRED TO BE WRlITEN MAINTAINED AND ON FILE WITli FIRE RESCUE
LETTE R MAllED
EGRESS I EXIT
EMERGENCY U GHTS SHALL BE PROVIDED
EMERGENCY LIGHTS SHAll BE PROVIDED TO IUUMINATE MEANS OF EGRESS
CHECK LIGHT BULBS AND BATTERY BACKUP
EXIT SIGNS MUST BE LIT AT ALL TIMES
EVERY EXIT SIGN SHALL BE ILLUMINATED DURING NORMALANO EMERGENCY OPERATION NOTIFY INSPECTOR IF LIGHTING SYSTEMS ARE ON TIMERS FROM DUSK TO DAWN OPERATION
CHECK LIGHT BULBS AND BATTERY BACKUP
FIRE ALARM
ALARM PANel NEEDS ANNUAL SERVICE
FIRE ALARM SYSTEM MUST HAVE ANNUAL CERTIFICATlON TAG
SPRINKLER
SPRINKLER I STANDPIPE - ANNUAl SERVICE
FIRE SPRINKLERS SHALL BE INSPECTED ANNUAUY AND A SERV1CE TAG PlACED IN CLEAR VIEW
GENERAL
PRIOR VIOLATIONS NOT CORRECTED
EGRESS I EXIT
EXITS OBSTRUCTED LOCKED OR DAMAGED
DOORS SHAU BE ARRANGED TO BE OPENE D REAPllY FROM THE f GRESSSIDE WHENEVER THE BUILDING IS OCCUPIED PENALTY APPUEO FOR BLOCKED EXITS UNDER Pl
HAUVoIAY 1ST FLOOR MAIN KlTCHEN IS OBSTRUCTED
Page1 ALL UFE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDIATELY
I
I
fANNUAL - Commercial gt25000 Assigned To ALEMAN Miguel on 102212012 Date 1012212012 120000AM
location NumMr 838802
Buln Name GULFSTREAM PARKmiddot CLUBHOUSE
Addrt 901 S FEDERAL HWY
CItyStattZlp Hallandale Beach FL 33009
Reclplnt Signature
RI( lpl nt
Page2 ALL LIFE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDIATELY
HALLANDALE BEACH FIRE RESCUE Oioilio Chief G PIaNio paglilruloOcotlbOI9
(oI)4S7- In
Division of Fire Prevention and Pubfic Education n MvaIIol AWnt~ (9544S7-419
121 Sw 3rd Street Hallandale Beacn Florida 33009
~ n Imfgteltgtr if i liampIT ~~CIQ
~J ~i7middot 16
FAX (954) 457middot1472 F1r6IIl~CIO y FelJoo (~~) ~57-3051
eilooGco~bQIQ
FIRE INSPECTION REPORT
ANNUALmiddot Commercial gt25000 Assigned To ALEMAN Miguel on 71812013
Date 10012012 1200S2AM
location Number 836756
Bulne Name MARDI GRAS CASINO
Add 831 N FEDERAL HWf
CltyIStJtJZip HAllANDALE BEACH FL 33009- shyVoltdon StandrslfRtftrtdegCl
GENERAL PRIOR VIOLAnONS NOT CORRECTED
FIRE AlARM ANNUNCIATOR AND NOTIFICATION DEVICES ARE MISSING THROUGHOlfT 4TH FLOOR
SPRINKLER
ESCUTCHEON PLATES MISSING
ESCUTCHEONS (COVERS) useD NITH RECESSED FLUSH-TYPE OR CONCEALED SPRINKLERS SHAll BE PART OF THE LISTED SPRINKLER ASSEMBLY AND REPlACED MiEN MISSING
5TH FLQOR PRESS ANNUNCIATOR ROOM
ELECTRICAl
EXPOSED WIRING
THROUGHOUT 4TH FLOOR REFER TO ELECTRICAL BUILDING DEPARTMENT
FlRE HOSE
FIRE HOSE NEEDS ANNUAL SERVICE
FIRE HOSE MUST BE VISUALLY INSPECTED FOR DAMAGE AND REmiddotROUEQ(RACKED ON AN ANNUAL BASIS WITH THE SERVICE TAG MARKED AND KEPT VIIITH HOSE
THROUGHOUT BUSINESS WAITING FOR LETIER TO BE ABLE TO REMOVE HOSE
ELECTRICAL
NO STORAGE IN MElfR ROOM
rAETER ROOM 5TH FLOOR CAlWALK
GENERAL
CEJUNG TIlES MISSING
5TH FLOOR PHOTO FINISH ROOM AND JUDGE ROOM
REPAIR HOLES IN WAlLS I CEIUNG
3RD FLOOR ELECTRICAL ROOM 3AAND WIRING ROOM
HAZMAT NEED APPROveD FLA_A8LE STORAGE CABIHET
FIRE PUMP ROOM
EGRESS I EXIT MAXIMUM CAPACITY
POST OCCUPANT LOAD SIGN IN CONSPICUOUS P~CE NEAR MAIN EXIT DO NOT EXCEED POSTED NUMBER
2NO FLOOR NORTH SIDE
Page l ALL LIFE SAFETY CODE VIOLA l IONS SHAll BE CORRECTED IMMEDIA TEL Y
ANNUAL - Commerclal gt2$000 Assigned To ALE~N Migllel on 782013
Oete 1013112012 120052AM
Lonlion Ntlmbr 630756
BUI5inU Nal MARDI GRAS CASINO
Addr 831 N FEDERAL HWY
CItyStatelZlp HALLANDALE BEACH FL 33009
Reclpllnt Signature
Rtcipllnt
Page2 ALL L1FE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDlATELY
HALLANDALE BEACH FIRE RESCUE Division of Fire Prevention and Public Education
121 SW 3rd Street Hallandale Bead Florida 33009
FAX (954) 457-1472 1
FIRE INSPECTION REPORT
ANNUALmiddot Commercial (0-5000) Assigned To ALEMAN Miguel on 91612012
Date 9f612012 120000AM
Location Number 188160
SustOItSS Name OCEANS 11 LOUNGE
Addrs 800 N FEDERAL HW
CityStaleJZip HALLANDALE BEACH FL 33009 _-- V IOlation
EGRESS I EXIT
MAXIMUM CAPACITY [S] NFPA 1 - 2006 2014103
POST OCCUPANT lOAD SIGN IN CONSPICUOUS PLACE NEAR MAIN EXIT DO NOT EXCEED POSTED NUMBER
KEY BOX REQUIRED [S] NFPAmiddot 2006116221
FlRE DEPT ACCESS BOX MUST BE INSTALLED MAINTAINED AND KEYS PROVIDED VERIFY rVlTH INSPECTOR WHICH KEYS NEEDED
GENERAL PRIOR VIOlA lIONS NOT CORRECTED
OTHER
PROVIDE INTERIOR FINISH CLASSIFICATION FOR CURTAINS INSIDE BAR AREA
HOoo SYSTEMS
HOOD SYSTEM MUST BE CLEANED (SI NFPA 1 2006 f SO53 TABLEv
ENTIRE EXHAUST SYSTEM MUST BE INSPECTED FOR GREASE BUILDUP BY A CERTIFIED COMPANY AND CLEANED IF NECESSARY AT LEAST SEMImiddotANNUAlLY QUARTERLY IF EXCESSIVE GREASE
FILTERS FOR KITCHEN HOOD SYSTEM MUST BE ClEAN
ELECTRICAL
REMOVE ALL EXTENSION CORDS
EXTENSION CORDS SHALL NOT BE USED AS A SUBSTITUTE FOR PERMANENT WIRING EXTENSION CORDS SHAll NOT EXTEND THROUGH WALLS CEILINGS OR FlOORS OR UNDER DOORS OR FLOOR COVERINGS
HOOD SYSTEMS
HOoo SYSTEM MUST SE CLEANED
ENTIRE EXHAUST SYSTEM MUST BE INSPECTED FOR GREASE BUILDUP BY A CERnFIED COMPANY AND CLEANED IF NECESSARY AT LEAST SEMImiddotANNUALLY QUARTERLY IF eXCESSIVe GREASE
09f0612012
GENERAl
OTHER
090612012 PROVIDE INTERIOR FINISH CLASSIFYCATION FOR CURTAINS IN BAR AREA
PRIOR VIOLATIONS NOT CORRECTED
Page1 AU LIFE SAFElY CODE VOLATtONS SHAlL BE CORRECTED INMEDIA1ElY
ANNUAL - Commercial (0-5000) ASsigned To ALEMAN Mlguamp1 on 91612012 I Date 916120 12 120000AM
ILocatiOtl Number 188160
BulnfJ Name OCEANS 11 LOUNGE
AddrI8$ 800 N FEDERAL rNVV
CltyfStatelZlp HALLANOALE BEACH FL 33009
Rlclplent Signature I Recipient
Page2 All LIFE SAFETY CODE vlouoom SHALl BE CORRECTED IMMEDIATELY
ConlJCjt ua 0i1I101on ChIeI G Pa(llLtllJ1oHALLANDALE BEACH FIRE RESCUE ~ruloregeohborg ~Mmt M Alom Oivision of Fire Prevention and Public Education mII~rtAII4IIcolll9fQ
121 Sw 3rd Street n ~r L W~Im HaRandale Beach Florida 33009 ~~mlCrxgthbOII
FAX (954) 457-1472 L-InpocIGrv Fij~ tOj~~OQ
FIRE INSP~CTION REPORT
ANNUAL - Commercial (0-5000) Assigned To ALEMAN Miguel on 5212013
Oat 512112013 120000AM
Location Numb 838798
BuslrWlU Nam UPPER OECK SPORTS GRILL
AddtelS 906 E HALLANDALE BEACH BLVD
CltylSlafDIZlp HALLANDALE BEACH fL 33009
Voftion
HOOD SYSTEMS
FRVER SEPARATION MISSING (NI NFPA 96 2()0412 124
(NI NFPA 96 200412124
IN] NFPA 96 ~0Olti 1 12125
IN] NFPA 96 200412125 MUST HAVe 16 IN HORIZONTAL OR 81NCH VERTICAL SEPARATION BETWEEN FRYER AND OPEN FLAME APPLIANCES
ELECTRICAL
ELECTRICAL OUTLET pLATE COVER MISSING
ELECTRICAL PANEL OBSTRUCTED
REMOVE ALL EXTENSION CORDS (SI NfPA 1 _ 2006111 15
EXTENSION CORDS SHALL NOT BE USED AS A SUBSTITUTE FOR PERMANENT WIRING EXTENSiON COROS SHALL NOT EXTEND THROUGH WALLS CEIUNGS OR fLOORS OR UNDER DOORS OR FLOOR COVERINGS
KITCHEN AND HOST AREA
EGRESS I EXIT
EMERGENCY LIGITS SHALL BE PROVIDED
EMERGENCY LIGHTS SHALL BE PROVIDED TO ILLUMINATE MEANS OF EGRESS
GENERAL
PRIOR VIOLAnONS NOT CORRECTED
Recipient Signarurt
RecipIent
I Page1 ALL LIFE SAFETY bODE VIOLATIONS SHALL BE CORRECTEO IMMEDIATELY
CgjCI U DMaIooI Cl~ G PIIJIO I~ ) 457middot ~n _ HALLANDALE BEACH FIRE RESCUE F LIvI W AiIoman (9 So14S141VOivision of Fire Prevention and Public EducaUon
121 S W 3rd Street n1n_l MILo (S SltI ) 4n_4re Halandale Blach Florida 33009 OgchOoro--
FN Iru~cb Y F-too (950t) S7-)()61FAX (954) 4157 472 - FIRE ~sp~cnON REPORT
ANNUAL - Commercial gt25000 Aulgned To ALEMAN Miguel on 102212012
Daw 1012212012 120000AM
loelion Number 838802
Buso HI m GULFSTREAM PARK CLUBHOUSE
Addrn 901 S FEDERAll-fNf
CltyStJtlZlp Hdnnd~ ~each ~l33009
Yiolation
HAlMAT HAZMAT PERMIT NEEDED
FIRST LETTER UAlLED
HAZMAT PERMIT NEEDED
SECOND LETTER MAILED
GENERAl
EMERGENCY OPERATlOHS PlAN REQUIREO III CrTYORDINANCE 18-1131()
lSI FS 553 509 (2Xd)
EMERGENCY OPERATIONS PLAN REQUIRED TO BE WRlITEN MAINTAINED AND ON FILE WITli FIRE RESCUE
LETTE R MAllED
EGRESS I EXIT
EMERGENCY U GHTS SHALL BE PROVIDED
EMERGENCY LIGHTS SHAll BE PROVIDED TO IUUMINATE MEANS OF EGRESS
CHECK LIGHT BULBS AND BATTERY BACKUP
EXIT SIGNS MUST BE LIT AT ALL TIMES
EVERY EXIT SIGN SHALL BE ILLUMINATED DURING NORMALANO EMERGENCY OPERATION NOTIFY INSPECTOR IF LIGHTING SYSTEMS ARE ON TIMERS FROM DUSK TO DAWN OPERATION
CHECK LIGHT BULBS AND BATTERY BACKUP
FIRE ALARM
ALARM PANel NEEDS ANNUAL SERVICE
FIRE ALARM SYSTEM MUST HAVE ANNUAL CERTIFICATlON TAG
SPRINKLER
SPRINKLER I STANDPIPE - ANNUAl SERVICE
FIRE SPRINKLERS SHALL BE INSPECTED ANNUAUY AND A SERV1CE TAG PlACED IN CLEAR VIEW
GENERAL
PRIOR VIOLATIONS NOT CORRECTED
EGRESS I EXIT
EXITS OBSTRUCTED LOCKED OR DAMAGED
DOORS SHAU BE ARRANGED TO BE OPENE D REAPllY FROM THE f GRESSSIDE WHENEVER THE BUILDING IS OCCUPIED PENALTY APPUEO FOR BLOCKED EXITS UNDER Pl
HAUVoIAY 1ST FLOOR MAIN KlTCHEN IS OBSTRUCTED
Page1 ALL UFE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDIATELY
I
I
fANNUAL - Commercial gt25000 Assigned To ALEMAN Miguel on 102212012 Date 1012212012 120000AM
location NumMr 838802
Buln Name GULFSTREAM PARKmiddot CLUBHOUSE
Addrt 901 S FEDERAL HWY
CItyStattZlp Hallandale Beach FL 33009
Reclplnt Signature
RI( lpl nt
Page2 ALL LIFE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDIATELY
HALLANDALE BEACH FIRE RESCUE Oioilio Chief G PIaNio paglilruloOcotlbOI9
(oI)4S7- In
Division of Fire Prevention and Pubfic Education n MvaIIol AWnt~ (9544S7-419
121 Sw 3rd Street Hallandale Beacn Florida 33009
~ n Imfgteltgtr if i liampIT ~~CIQ
~J ~i7middot 16
FAX (954) 457middot1472 F1r6IIl~CIO y FelJoo (~~) ~57-3051
eilooGco~bQIQ
FIRE INSPECTION REPORT
ANNUALmiddot Commercial gt25000 Assigned To ALEMAN Miguel on 71812013
Date 10012012 1200S2AM
location Number 836756
Bulne Name MARDI GRAS CASINO
Add 831 N FEDERAL HWf
CltyIStJtJZip HAllANDALE BEACH FL 33009- shyVoltdon StandrslfRtftrtdegCl
GENERAL PRIOR VIOLAnONS NOT CORRECTED
FIRE AlARM ANNUNCIATOR AND NOTIFICATION DEVICES ARE MISSING THROUGHOlfT 4TH FLOOR
SPRINKLER
ESCUTCHEON PLATES MISSING
ESCUTCHEONS (COVERS) useD NITH RECESSED FLUSH-TYPE OR CONCEALED SPRINKLERS SHAll BE PART OF THE LISTED SPRINKLER ASSEMBLY AND REPlACED MiEN MISSING
5TH FLQOR PRESS ANNUNCIATOR ROOM
ELECTRICAl
EXPOSED WIRING
THROUGHOUT 4TH FLOOR REFER TO ELECTRICAL BUILDING DEPARTMENT
FlRE HOSE
FIRE HOSE NEEDS ANNUAL SERVICE
FIRE HOSE MUST BE VISUALLY INSPECTED FOR DAMAGE AND REmiddotROUEQ(RACKED ON AN ANNUAL BASIS WITH THE SERVICE TAG MARKED AND KEPT VIIITH HOSE
THROUGHOUT BUSINESS WAITING FOR LETIER TO BE ABLE TO REMOVE HOSE
ELECTRICAL
NO STORAGE IN MElfR ROOM
rAETER ROOM 5TH FLOOR CAlWALK
GENERAL
CEJUNG TIlES MISSING
5TH FLOOR PHOTO FINISH ROOM AND JUDGE ROOM
REPAIR HOLES IN WAlLS I CEIUNG
3RD FLOOR ELECTRICAL ROOM 3AAND WIRING ROOM
HAZMAT NEED APPROveD FLA_A8LE STORAGE CABIHET
FIRE PUMP ROOM
EGRESS I EXIT MAXIMUM CAPACITY
POST OCCUPANT LOAD SIGN IN CONSPICUOUS P~CE NEAR MAIN EXIT DO NOT EXCEED POSTED NUMBER
2NO FLOOR NORTH SIDE
Page l ALL LIFE SAFETY CODE VIOLA l IONS SHAll BE CORRECTED IMMEDIA TEL Y
ANNUAL - Commerclal gt2$000 Assigned To ALE~N Migllel on 782013
Oete 1013112012 120052AM
Lonlion Ntlmbr 630756
BUI5inU Nal MARDI GRAS CASINO
Addr 831 N FEDERAL HWY
CItyStatelZlp HALLANDALE BEACH FL 33009
Reclpllnt Signature
Rtcipllnt
Page2 ALL L1FE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDlATELY
HALLANDALE BEACH FIRE RESCUE Division of Fire Prevention and Public Education
121 SW 3rd Street Hallandale Bead Florida 33009
FAX (954) 457-1472 1
FIRE INSPECTION REPORT
ANNUALmiddot Commercial (0-5000) Assigned To ALEMAN Miguel on 91612012
Date 9f612012 120000AM
Location Number 188160
SustOItSS Name OCEANS 11 LOUNGE
Addrs 800 N FEDERAL HW
CityStaleJZip HALLANDALE BEACH FL 33009 _-- V IOlation
EGRESS I EXIT
MAXIMUM CAPACITY [S] NFPA 1 - 2006 2014103
POST OCCUPANT lOAD SIGN IN CONSPICUOUS PLACE NEAR MAIN EXIT DO NOT EXCEED POSTED NUMBER
KEY BOX REQUIRED [S] NFPAmiddot 2006116221
FlRE DEPT ACCESS BOX MUST BE INSTALLED MAINTAINED AND KEYS PROVIDED VERIFY rVlTH INSPECTOR WHICH KEYS NEEDED
GENERAL PRIOR VIOlA lIONS NOT CORRECTED
OTHER
PROVIDE INTERIOR FINISH CLASSIFICATION FOR CURTAINS INSIDE BAR AREA
HOoo SYSTEMS
HOOD SYSTEM MUST BE CLEANED (SI NFPA 1 2006 f SO53 TABLEv
ENTIRE EXHAUST SYSTEM MUST BE INSPECTED FOR GREASE BUILDUP BY A CERTIFIED COMPANY AND CLEANED IF NECESSARY AT LEAST SEMImiddotANNUAlLY QUARTERLY IF EXCESSIVE GREASE
FILTERS FOR KITCHEN HOOD SYSTEM MUST BE ClEAN
ELECTRICAL
REMOVE ALL EXTENSION CORDS
EXTENSION CORDS SHALL NOT BE USED AS A SUBSTITUTE FOR PERMANENT WIRING EXTENSION CORDS SHAll NOT EXTEND THROUGH WALLS CEILINGS OR FlOORS OR UNDER DOORS OR FLOOR COVERINGS
HOOD SYSTEMS
HOoo SYSTEM MUST SE CLEANED
ENTIRE EXHAUST SYSTEM MUST BE INSPECTED FOR GREASE BUILDUP BY A CERnFIED COMPANY AND CLEANED IF NECESSARY AT LEAST SEMImiddotANNUALLY QUARTERLY IF eXCESSIVe GREASE
09f0612012
GENERAl
OTHER
090612012 PROVIDE INTERIOR FINISH CLASSIFYCATION FOR CURTAINS IN BAR AREA
PRIOR VIOLATIONS NOT CORRECTED
Page1 AU LIFE SAFElY CODE VOLATtONS SHAlL BE CORRECTED INMEDIA1ElY
ANNUAL - Commercial (0-5000) ASsigned To ALEMAN Mlguamp1 on 91612012 I Date 916120 12 120000AM
ILocatiOtl Number 188160
BulnfJ Name OCEANS 11 LOUNGE
AddrI8$ 800 N FEDERAL rNVV
CltyfStatelZlp HALLANOALE BEACH FL 33009
Rlclplent Signature I Recipient
Page2 All LIFE SAFETY CODE vlouoom SHALl BE CORRECTED IMMEDIATELY
ConlJCjt ua 0i1I101on ChIeI G Pa(llLtllJ1oHALLANDALE BEACH FIRE RESCUE ~ruloregeohborg ~Mmt M Alom Oivision of Fire Prevention and Public Education mII~rtAII4IIcolll9fQ
121 Sw 3rd Street n ~r L W~Im HaRandale Beach Florida 33009 ~~mlCrxgthbOII
FAX (954) 457-1472 L-InpocIGrv Fij~ tOj~~OQ
FIRE INSP~CTION REPORT
ANNUAL - Commercial (0-5000) Assigned To ALEMAN Miguel on 5212013
Oat 512112013 120000AM
Location Numb 838798
BuslrWlU Nam UPPER OECK SPORTS GRILL
AddtelS 906 E HALLANDALE BEACH BLVD
CltylSlafDIZlp HALLANDALE BEACH fL 33009
Voftion
HOOD SYSTEMS
FRVER SEPARATION MISSING (NI NFPA 96 2()0412 124
(NI NFPA 96 200412124
IN] NFPA 96 ~0Olti 1 12125
IN] NFPA 96 200412125 MUST HAVe 16 IN HORIZONTAL OR 81NCH VERTICAL SEPARATION BETWEEN FRYER AND OPEN FLAME APPLIANCES
ELECTRICAL
ELECTRICAL OUTLET pLATE COVER MISSING
ELECTRICAL PANEL OBSTRUCTED
REMOVE ALL EXTENSION CORDS (SI NfPA 1 _ 2006111 15
EXTENSION CORDS SHALL NOT BE USED AS A SUBSTITUTE FOR PERMANENT WIRING EXTENSiON COROS SHALL NOT EXTEND THROUGH WALLS CEIUNGS OR fLOORS OR UNDER DOORS OR FLOOR COVERINGS
KITCHEN AND HOST AREA
EGRESS I EXIT
EMERGENCY LIGITS SHALL BE PROVIDED
EMERGENCY LIGHTS SHALL BE PROVIDED TO ILLUMINATE MEANS OF EGRESS
GENERAL
PRIOR VIOLAnONS NOT CORRECTED
Recipient Signarurt
RecipIent
I Page1 ALL LIFE SAFETY bODE VIOLATIONS SHALL BE CORRECTEO IMMEDIATELY
I
I
fANNUAL - Commercial gt25000 Assigned To ALEMAN Miguel on 102212012 Date 1012212012 120000AM
location NumMr 838802
Buln Name GULFSTREAM PARKmiddot CLUBHOUSE
Addrt 901 S FEDERAL HWY
CItyStattZlp Hallandale Beach FL 33009
Reclplnt Signature
RI( lpl nt
Page2 ALL LIFE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDIATELY
HALLANDALE BEACH FIRE RESCUE Oioilio Chief G PIaNio paglilruloOcotlbOI9
(oI)4S7- In
Division of Fire Prevention and Pubfic Education n MvaIIol AWnt~ (9544S7-419
121 Sw 3rd Street Hallandale Beacn Florida 33009
~ n Imfgteltgtr if i liampIT ~~CIQ
~J ~i7middot 16
FAX (954) 457middot1472 F1r6IIl~CIO y FelJoo (~~) ~57-3051
eilooGco~bQIQ
FIRE INSPECTION REPORT
ANNUALmiddot Commercial gt25000 Assigned To ALEMAN Miguel on 71812013
Date 10012012 1200S2AM
location Number 836756
Bulne Name MARDI GRAS CASINO
Add 831 N FEDERAL HWf
CltyIStJtJZip HAllANDALE BEACH FL 33009- shyVoltdon StandrslfRtftrtdegCl
GENERAL PRIOR VIOLAnONS NOT CORRECTED
FIRE AlARM ANNUNCIATOR AND NOTIFICATION DEVICES ARE MISSING THROUGHOlfT 4TH FLOOR
SPRINKLER
ESCUTCHEON PLATES MISSING
ESCUTCHEONS (COVERS) useD NITH RECESSED FLUSH-TYPE OR CONCEALED SPRINKLERS SHAll BE PART OF THE LISTED SPRINKLER ASSEMBLY AND REPlACED MiEN MISSING
5TH FLQOR PRESS ANNUNCIATOR ROOM
ELECTRICAl
EXPOSED WIRING
THROUGHOUT 4TH FLOOR REFER TO ELECTRICAL BUILDING DEPARTMENT
FlRE HOSE
FIRE HOSE NEEDS ANNUAL SERVICE
FIRE HOSE MUST BE VISUALLY INSPECTED FOR DAMAGE AND REmiddotROUEQ(RACKED ON AN ANNUAL BASIS WITH THE SERVICE TAG MARKED AND KEPT VIIITH HOSE
THROUGHOUT BUSINESS WAITING FOR LETIER TO BE ABLE TO REMOVE HOSE
ELECTRICAL
NO STORAGE IN MElfR ROOM
rAETER ROOM 5TH FLOOR CAlWALK
GENERAL
CEJUNG TIlES MISSING
5TH FLOOR PHOTO FINISH ROOM AND JUDGE ROOM
REPAIR HOLES IN WAlLS I CEIUNG
3RD FLOOR ELECTRICAL ROOM 3AAND WIRING ROOM
HAZMAT NEED APPROveD FLA_A8LE STORAGE CABIHET
FIRE PUMP ROOM
EGRESS I EXIT MAXIMUM CAPACITY
POST OCCUPANT LOAD SIGN IN CONSPICUOUS P~CE NEAR MAIN EXIT DO NOT EXCEED POSTED NUMBER
2NO FLOOR NORTH SIDE
Page l ALL LIFE SAFETY CODE VIOLA l IONS SHAll BE CORRECTED IMMEDIA TEL Y
ANNUAL - Commerclal gt2$000 Assigned To ALE~N Migllel on 782013
Oete 1013112012 120052AM
Lonlion Ntlmbr 630756
BUI5inU Nal MARDI GRAS CASINO
Addr 831 N FEDERAL HWY
CItyStatelZlp HALLANDALE BEACH FL 33009
Reclpllnt Signature
Rtcipllnt
Page2 ALL L1FE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDlATELY
HALLANDALE BEACH FIRE RESCUE Division of Fire Prevention and Public Education
121 SW 3rd Street Hallandale Bead Florida 33009
FAX (954) 457-1472 1
FIRE INSPECTION REPORT
ANNUALmiddot Commercial (0-5000) Assigned To ALEMAN Miguel on 91612012
Date 9f612012 120000AM
Location Number 188160
SustOItSS Name OCEANS 11 LOUNGE
Addrs 800 N FEDERAL HW
CityStaleJZip HALLANDALE BEACH FL 33009 _-- V IOlation
EGRESS I EXIT
MAXIMUM CAPACITY [S] NFPA 1 - 2006 2014103
POST OCCUPANT lOAD SIGN IN CONSPICUOUS PLACE NEAR MAIN EXIT DO NOT EXCEED POSTED NUMBER
KEY BOX REQUIRED [S] NFPAmiddot 2006116221
FlRE DEPT ACCESS BOX MUST BE INSTALLED MAINTAINED AND KEYS PROVIDED VERIFY rVlTH INSPECTOR WHICH KEYS NEEDED
GENERAL PRIOR VIOlA lIONS NOT CORRECTED
OTHER
PROVIDE INTERIOR FINISH CLASSIFICATION FOR CURTAINS INSIDE BAR AREA
HOoo SYSTEMS
HOOD SYSTEM MUST BE CLEANED (SI NFPA 1 2006 f SO53 TABLEv
ENTIRE EXHAUST SYSTEM MUST BE INSPECTED FOR GREASE BUILDUP BY A CERTIFIED COMPANY AND CLEANED IF NECESSARY AT LEAST SEMImiddotANNUAlLY QUARTERLY IF EXCESSIVE GREASE
FILTERS FOR KITCHEN HOOD SYSTEM MUST BE ClEAN
ELECTRICAL
REMOVE ALL EXTENSION CORDS
EXTENSION CORDS SHALL NOT BE USED AS A SUBSTITUTE FOR PERMANENT WIRING EXTENSION CORDS SHAll NOT EXTEND THROUGH WALLS CEILINGS OR FlOORS OR UNDER DOORS OR FLOOR COVERINGS
HOOD SYSTEMS
HOoo SYSTEM MUST SE CLEANED
ENTIRE EXHAUST SYSTEM MUST BE INSPECTED FOR GREASE BUILDUP BY A CERnFIED COMPANY AND CLEANED IF NECESSARY AT LEAST SEMImiddotANNUALLY QUARTERLY IF eXCESSIVe GREASE
09f0612012
GENERAl
OTHER
090612012 PROVIDE INTERIOR FINISH CLASSIFYCATION FOR CURTAINS IN BAR AREA
PRIOR VIOLATIONS NOT CORRECTED
Page1 AU LIFE SAFElY CODE VOLATtONS SHAlL BE CORRECTED INMEDIA1ElY
ANNUAL - Commercial (0-5000) ASsigned To ALEMAN Mlguamp1 on 91612012 I Date 916120 12 120000AM
ILocatiOtl Number 188160
BulnfJ Name OCEANS 11 LOUNGE
AddrI8$ 800 N FEDERAL rNVV
CltyfStatelZlp HALLANOALE BEACH FL 33009
Rlclplent Signature I Recipient
Page2 All LIFE SAFETY CODE vlouoom SHALl BE CORRECTED IMMEDIATELY
ConlJCjt ua 0i1I101on ChIeI G Pa(llLtllJ1oHALLANDALE BEACH FIRE RESCUE ~ruloregeohborg ~Mmt M Alom Oivision of Fire Prevention and Public Education mII~rtAII4IIcolll9fQ
121 Sw 3rd Street n ~r L W~Im HaRandale Beach Florida 33009 ~~mlCrxgthbOII
FAX (954) 457-1472 L-InpocIGrv Fij~ tOj~~OQ
FIRE INSP~CTION REPORT
ANNUAL - Commercial (0-5000) Assigned To ALEMAN Miguel on 5212013
Oat 512112013 120000AM
Location Numb 838798
BuslrWlU Nam UPPER OECK SPORTS GRILL
AddtelS 906 E HALLANDALE BEACH BLVD
CltylSlafDIZlp HALLANDALE BEACH fL 33009
Voftion
HOOD SYSTEMS
FRVER SEPARATION MISSING (NI NFPA 96 2()0412 124
(NI NFPA 96 200412124
IN] NFPA 96 ~0Olti 1 12125
IN] NFPA 96 200412125 MUST HAVe 16 IN HORIZONTAL OR 81NCH VERTICAL SEPARATION BETWEEN FRYER AND OPEN FLAME APPLIANCES
ELECTRICAL
ELECTRICAL OUTLET pLATE COVER MISSING
ELECTRICAL PANEL OBSTRUCTED
REMOVE ALL EXTENSION CORDS (SI NfPA 1 _ 2006111 15
EXTENSION CORDS SHALL NOT BE USED AS A SUBSTITUTE FOR PERMANENT WIRING EXTENSiON COROS SHALL NOT EXTEND THROUGH WALLS CEIUNGS OR fLOORS OR UNDER DOORS OR FLOOR COVERINGS
KITCHEN AND HOST AREA
EGRESS I EXIT
EMERGENCY LIGITS SHALL BE PROVIDED
EMERGENCY LIGHTS SHALL BE PROVIDED TO ILLUMINATE MEANS OF EGRESS
GENERAL
PRIOR VIOLAnONS NOT CORRECTED
Recipient Signarurt
RecipIent
I Page1 ALL LIFE SAFETY bODE VIOLATIONS SHALL BE CORRECTEO IMMEDIATELY
HALLANDALE BEACH FIRE RESCUE Oioilio Chief G PIaNio paglilruloOcotlbOI9
(oI)4S7- In
Division of Fire Prevention and Pubfic Education n MvaIIol AWnt~ (9544S7-419
121 Sw 3rd Street Hallandale Beacn Florida 33009
~ n Imfgteltgtr if i liampIT ~~CIQ
~J ~i7middot 16
FAX (954) 457middot1472 F1r6IIl~CIO y FelJoo (~~) ~57-3051
eilooGco~bQIQ
FIRE INSPECTION REPORT
ANNUALmiddot Commercial gt25000 Assigned To ALEMAN Miguel on 71812013
Date 10012012 1200S2AM
location Number 836756
Bulne Name MARDI GRAS CASINO
Add 831 N FEDERAL HWf
CltyIStJtJZip HAllANDALE BEACH FL 33009- shyVoltdon StandrslfRtftrtdegCl
GENERAL PRIOR VIOLAnONS NOT CORRECTED
FIRE AlARM ANNUNCIATOR AND NOTIFICATION DEVICES ARE MISSING THROUGHOlfT 4TH FLOOR
SPRINKLER
ESCUTCHEON PLATES MISSING
ESCUTCHEONS (COVERS) useD NITH RECESSED FLUSH-TYPE OR CONCEALED SPRINKLERS SHAll BE PART OF THE LISTED SPRINKLER ASSEMBLY AND REPlACED MiEN MISSING
5TH FLQOR PRESS ANNUNCIATOR ROOM
ELECTRICAl
EXPOSED WIRING
THROUGHOUT 4TH FLOOR REFER TO ELECTRICAL BUILDING DEPARTMENT
FlRE HOSE
FIRE HOSE NEEDS ANNUAL SERVICE
FIRE HOSE MUST BE VISUALLY INSPECTED FOR DAMAGE AND REmiddotROUEQ(RACKED ON AN ANNUAL BASIS WITH THE SERVICE TAG MARKED AND KEPT VIIITH HOSE
THROUGHOUT BUSINESS WAITING FOR LETIER TO BE ABLE TO REMOVE HOSE
ELECTRICAL
NO STORAGE IN MElfR ROOM
rAETER ROOM 5TH FLOOR CAlWALK
GENERAL
CEJUNG TIlES MISSING
5TH FLOOR PHOTO FINISH ROOM AND JUDGE ROOM
REPAIR HOLES IN WAlLS I CEIUNG
3RD FLOOR ELECTRICAL ROOM 3AAND WIRING ROOM
HAZMAT NEED APPROveD FLA_A8LE STORAGE CABIHET
FIRE PUMP ROOM
EGRESS I EXIT MAXIMUM CAPACITY
POST OCCUPANT LOAD SIGN IN CONSPICUOUS P~CE NEAR MAIN EXIT DO NOT EXCEED POSTED NUMBER
2NO FLOOR NORTH SIDE
Page l ALL LIFE SAFETY CODE VIOLA l IONS SHAll BE CORRECTED IMMEDIA TEL Y
ANNUAL - Commerclal gt2$000 Assigned To ALE~N Migllel on 782013
Oete 1013112012 120052AM
Lonlion Ntlmbr 630756
BUI5inU Nal MARDI GRAS CASINO
Addr 831 N FEDERAL HWY
CItyStatelZlp HALLANDALE BEACH FL 33009
Reclpllnt Signature
Rtcipllnt
Page2 ALL L1FE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDlATELY
HALLANDALE BEACH FIRE RESCUE Division of Fire Prevention and Public Education
121 SW 3rd Street Hallandale Bead Florida 33009
FAX (954) 457-1472 1
FIRE INSPECTION REPORT
ANNUALmiddot Commercial (0-5000) Assigned To ALEMAN Miguel on 91612012
Date 9f612012 120000AM
Location Number 188160
SustOItSS Name OCEANS 11 LOUNGE
Addrs 800 N FEDERAL HW
CityStaleJZip HALLANDALE BEACH FL 33009 _-- V IOlation
EGRESS I EXIT
MAXIMUM CAPACITY [S] NFPA 1 - 2006 2014103
POST OCCUPANT lOAD SIGN IN CONSPICUOUS PLACE NEAR MAIN EXIT DO NOT EXCEED POSTED NUMBER
KEY BOX REQUIRED [S] NFPAmiddot 2006116221
FlRE DEPT ACCESS BOX MUST BE INSTALLED MAINTAINED AND KEYS PROVIDED VERIFY rVlTH INSPECTOR WHICH KEYS NEEDED
GENERAL PRIOR VIOlA lIONS NOT CORRECTED
OTHER
PROVIDE INTERIOR FINISH CLASSIFICATION FOR CURTAINS INSIDE BAR AREA
HOoo SYSTEMS
HOOD SYSTEM MUST BE CLEANED (SI NFPA 1 2006 f SO53 TABLEv
ENTIRE EXHAUST SYSTEM MUST BE INSPECTED FOR GREASE BUILDUP BY A CERTIFIED COMPANY AND CLEANED IF NECESSARY AT LEAST SEMImiddotANNUAlLY QUARTERLY IF EXCESSIVE GREASE
FILTERS FOR KITCHEN HOOD SYSTEM MUST BE ClEAN
ELECTRICAL
REMOVE ALL EXTENSION CORDS
EXTENSION CORDS SHALL NOT BE USED AS A SUBSTITUTE FOR PERMANENT WIRING EXTENSION CORDS SHAll NOT EXTEND THROUGH WALLS CEILINGS OR FlOORS OR UNDER DOORS OR FLOOR COVERINGS
HOOD SYSTEMS
HOoo SYSTEM MUST SE CLEANED
ENTIRE EXHAUST SYSTEM MUST BE INSPECTED FOR GREASE BUILDUP BY A CERnFIED COMPANY AND CLEANED IF NECESSARY AT LEAST SEMImiddotANNUALLY QUARTERLY IF eXCESSIVe GREASE
09f0612012
GENERAl
OTHER
090612012 PROVIDE INTERIOR FINISH CLASSIFYCATION FOR CURTAINS IN BAR AREA
PRIOR VIOLATIONS NOT CORRECTED
Page1 AU LIFE SAFElY CODE VOLATtONS SHAlL BE CORRECTED INMEDIA1ElY
ANNUAL - Commercial (0-5000) ASsigned To ALEMAN Mlguamp1 on 91612012 I Date 916120 12 120000AM
ILocatiOtl Number 188160
BulnfJ Name OCEANS 11 LOUNGE
AddrI8$ 800 N FEDERAL rNVV
CltyfStatelZlp HALLANOALE BEACH FL 33009
Rlclplent Signature I Recipient
Page2 All LIFE SAFETY CODE vlouoom SHALl BE CORRECTED IMMEDIATELY
ConlJCjt ua 0i1I101on ChIeI G Pa(llLtllJ1oHALLANDALE BEACH FIRE RESCUE ~ruloregeohborg ~Mmt M Alom Oivision of Fire Prevention and Public Education mII~rtAII4IIcolll9fQ
121 Sw 3rd Street n ~r L W~Im HaRandale Beach Florida 33009 ~~mlCrxgthbOII
FAX (954) 457-1472 L-InpocIGrv Fij~ tOj~~OQ
FIRE INSP~CTION REPORT
ANNUAL - Commercial (0-5000) Assigned To ALEMAN Miguel on 5212013
Oat 512112013 120000AM
Location Numb 838798
BuslrWlU Nam UPPER OECK SPORTS GRILL
AddtelS 906 E HALLANDALE BEACH BLVD
CltylSlafDIZlp HALLANDALE BEACH fL 33009
Voftion
HOOD SYSTEMS
FRVER SEPARATION MISSING (NI NFPA 96 2()0412 124
(NI NFPA 96 200412124
IN] NFPA 96 ~0Olti 1 12125
IN] NFPA 96 200412125 MUST HAVe 16 IN HORIZONTAL OR 81NCH VERTICAL SEPARATION BETWEEN FRYER AND OPEN FLAME APPLIANCES
ELECTRICAL
ELECTRICAL OUTLET pLATE COVER MISSING
ELECTRICAL PANEL OBSTRUCTED
REMOVE ALL EXTENSION CORDS (SI NfPA 1 _ 2006111 15
EXTENSION CORDS SHALL NOT BE USED AS A SUBSTITUTE FOR PERMANENT WIRING EXTENSiON COROS SHALL NOT EXTEND THROUGH WALLS CEIUNGS OR fLOORS OR UNDER DOORS OR FLOOR COVERINGS
KITCHEN AND HOST AREA
EGRESS I EXIT
EMERGENCY LIGITS SHALL BE PROVIDED
EMERGENCY LIGHTS SHALL BE PROVIDED TO ILLUMINATE MEANS OF EGRESS
GENERAL
PRIOR VIOLAnONS NOT CORRECTED
Recipient Signarurt
RecipIent
I Page1 ALL LIFE SAFETY bODE VIOLATIONS SHALL BE CORRECTEO IMMEDIATELY
ANNUAL - Commerclal gt2$000 Assigned To ALE~N Migllel on 782013
Oete 1013112012 120052AM
Lonlion Ntlmbr 630756
BUI5inU Nal MARDI GRAS CASINO
Addr 831 N FEDERAL HWY
CItyStatelZlp HALLANDALE BEACH FL 33009
Reclpllnt Signature
Rtcipllnt
Page2 ALL L1FE SAFETY CODE VIOLATIONS SHALL BE CORRECTED IMMEDlATELY
HALLANDALE BEACH FIRE RESCUE Division of Fire Prevention and Public Education
121 SW 3rd Street Hallandale Bead Florida 33009
FAX (954) 457-1472 1
FIRE INSPECTION REPORT
ANNUALmiddot Commercial (0-5000) Assigned To ALEMAN Miguel on 91612012
Date 9f612012 120000AM
Location Number 188160
SustOItSS Name OCEANS 11 LOUNGE
Addrs 800 N FEDERAL HW
CityStaleJZip HALLANDALE BEACH FL 33009 _-- V IOlation
EGRESS I EXIT
MAXIMUM CAPACITY [S] NFPA 1 - 2006 2014103
POST OCCUPANT lOAD SIGN IN CONSPICUOUS PLACE NEAR MAIN EXIT DO NOT EXCEED POSTED NUMBER
KEY BOX REQUIRED [S] NFPAmiddot 2006116221
FlRE DEPT ACCESS BOX MUST BE INSTALLED MAINTAINED AND KEYS PROVIDED VERIFY rVlTH INSPECTOR WHICH KEYS NEEDED
GENERAL PRIOR VIOlA lIONS NOT CORRECTED
OTHER
PROVIDE INTERIOR FINISH CLASSIFICATION FOR CURTAINS INSIDE BAR AREA
HOoo SYSTEMS
HOOD SYSTEM MUST BE CLEANED (SI NFPA 1 2006 f SO53 TABLEv
ENTIRE EXHAUST SYSTEM MUST BE INSPECTED FOR GREASE BUILDUP BY A CERTIFIED COMPANY AND CLEANED IF NECESSARY AT LEAST SEMImiddotANNUAlLY QUARTERLY IF EXCESSIVE GREASE
FILTERS FOR KITCHEN HOOD SYSTEM MUST BE ClEAN
ELECTRICAL
REMOVE ALL EXTENSION CORDS
EXTENSION CORDS SHALL NOT BE USED AS A SUBSTITUTE FOR PERMANENT WIRING EXTENSION CORDS SHAll NOT EXTEND THROUGH WALLS CEILINGS OR FlOORS OR UNDER DOORS OR FLOOR COVERINGS
HOOD SYSTEMS
HOoo SYSTEM MUST SE CLEANED
ENTIRE EXHAUST SYSTEM MUST BE INSPECTED FOR GREASE BUILDUP BY A CERnFIED COMPANY AND CLEANED IF NECESSARY AT LEAST SEMImiddotANNUALLY QUARTERLY IF eXCESSIVe GREASE
09f0612012
GENERAl
OTHER
090612012 PROVIDE INTERIOR FINISH CLASSIFYCATION FOR CURTAINS IN BAR AREA
PRIOR VIOLATIONS NOT CORRECTED
Page1 AU LIFE SAFElY CODE VOLATtONS SHAlL BE CORRECTED INMEDIA1ElY
ANNUAL - Commercial (0-5000) ASsigned To ALEMAN Mlguamp1 on 91612012 I Date 916120 12 120000AM
ILocatiOtl Number 188160
BulnfJ Name OCEANS 11 LOUNGE
AddrI8$ 800 N FEDERAL rNVV
CltyfStatelZlp HALLANOALE BEACH FL 33009
Rlclplent Signature I Recipient
Page2 All LIFE SAFETY CODE vlouoom SHALl BE CORRECTED IMMEDIATELY
ConlJCjt ua 0i1I101on ChIeI G Pa(llLtllJ1oHALLANDALE BEACH FIRE RESCUE ~ruloregeohborg ~Mmt M Alom Oivision of Fire Prevention and Public Education mII~rtAII4IIcolll9fQ
121 Sw 3rd Street n ~r L W~Im HaRandale Beach Florida 33009 ~~mlCrxgthbOII
FAX (954) 457-1472 L-InpocIGrv Fij~ tOj~~OQ
FIRE INSP~CTION REPORT
ANNUAL - Commercial (0-5000) Assigned To ALEMAN Miguel on 5212013
Oat 512112013 120000AM
Location Numb 838798
BuslrWlU Nam UPPER OECK SPORTS GRILL
AddtelS 906 E HALLANDALE BEACH BLVD
CltylSlafDIZlp HALLANDALE BEACH fL 33009
Voftion
HOOD SYSTEMS
FRVER SEPARATION MISSING (NI NFPA 96 2()0412 124
(NI NFPA 96 200412124
IN] NFPA 96 ~0Olti 1 12125
IN] NFPA 96 200412125 MUST HAVe 16 IN HORIZONTAL OR 81NCH VERTICAL SEPARATION BETWEEN FRYER AND OPEN FLAME APPLIANCES
ELECTRICAL
ELECTRICAL OUTLET pLATE COVER MISSING
ELECTRICAL PANEL OBSTRUCTED
REMOVE ALL EXTENSION CORDS (SI NfPA 1 _ 2006111 15
EXTENSION CORDS SHALL NOT BE USED AS A SUBSTITUTE FOR PERMANENT WIRING EXTENSiON COROS SHALL NOT EXTEND THROUGH WALLS CEIUNGS OR fLOORS OR UNDER DOORS OR FLOOR COVERINGS
KITCHEN AND HOST AREA
EGRESS I EXIT
EMERGENCY LIGITS SHALL BE PROVIDED
EMERGENCY LIGHTS SHALL BE PROVIDED TO ILLUMINATE MEANS OF EGRESS
GENERAL
PRIOR VIOLAnONS NOT CORRECTED
Recipient Signarurt
RecipIent
I Page1 ALL LIFE SAFETY bODE VIOLATIONS SHALL BE CORRECTEO IMMEDIATELY
HALLANDALE BEACH FIRE RESCUE Division of Fire Prevention and Public Education
121 SW 3rd Street Hallandale Bead Florida 33009
FAX (954) 457-1472 1
FIRE INSPECTION REPORT
ANNUALmiddot Commercial (0-5000) Assigned To ALEMAN Miguel on 91612012
Date 9f612012 120000AM
Location Number 188160
SustOItSS Name OCEANS 11 LOUNGE
Addrs 800 N FEDERAL HW
CityStaleJZip HALLANDALE BEACH FL 33009 _-- V IOlation
EGRESS I EXIT
MAXIMUM CAPACITY [S] NFPA 1 - 2006 2014103
POST OCCUPANT lOAD SIGN IN CONSPICUOUS PLACE NEAR MAIN EXIT DO NOT EXCEED POSTED NUMBER
KEY BOX REQUIRED [S] NFPAmiddot 2006116221
FlRE DEPT ACCESS BOX MUST BE INSTALLED MAINTAINED AND KEYS PROVIDED VERIFY rVlTH INSPECTOR WHICH KEYS NEEDED
GENERAL PRIOR VIOlA lIONS NOT CORRECTED
OTHER
PROVIDE INTERIOR FINISH CLASSIFICATION FOR CURTAINS INSIDE BAR AREA
HOoo SYSTEMS
HOOD SYSTEM MUST BE CLEANED (SI NFPA 1 2006 f SO53 TABLEv
ENTIRE EXHAUST SYSTEM MUST BE INSPECTED FOR GREASE BUILDUP BY A CERTIFIED COMPANY AND CLEANED IF NECESSARY AT LEAST SEMImiddotANNUAlLY QUARTERLY IF EXCESSIVE GREASE
FILTERS FOR KITCHEN HOOD SYSTEM MUST BE ClEAN
ELECTRICAL
REMOVE ALL EXTENSION CORDS
EXTENSION CORDS SHALL NOT BE USED AS A SUBSTITUTE FOR PERMANENT WIRING EXTENSION CORDS SHAll NOT EXTEND THROUGH WALLS CEILINGS OR FlOORS OR UNDER DOORS OR FLOOR COVERINGS
HOOD SYSTEMS
HOoo SYSTEM MUST SE CLEANED
ENTIRE EXHAUST SYSTEM MUST BE INSPECTED FOR GREASE BUILDUP BY A CERnFIED COMPANY AND CLEANED IF NECESSARY AT LEAST SEMImiddotANNUALLY QUARTERLY IF eXCESSIVe GREASE
09f0612012
GENERAl
OTHER
090612012 PROVIDE INTERIOR FINISH CLASSIFYCATION FOR CURTAINS IN BAR AREA
PRIOR VIOLATIONS NOT CORRECTED
Page1 AU LIFE SAFElY CODE VOLATtONS SHAlL BE CORRECTED INMEDIA1ElY
ANNUAL - Commercial (0-5000) ASsigned To ALEMAN Mlguamp1 on 91612012 I Date 916120 12 120000AM
ILocatiOtl Number 188160
BulnfJ Name OCEANS 11 LOUNGE
AddrI8$ 800 N FEDERAL rNVV
CltyfStatelZlp HALLANOALE BEACH FL 33009
Rlclplent Signature I Recipient
Page2 All LIFE SAFETY CODE vlouoom SHALl BE CORRECTED IMMEDIATELY
ConlJCjt ua 0i1I101on ChIeI G Pa(llLtllJ1oHALLANDALE BEACH FIRE RESCUE ~ruloregeohborg ~Mmt M Alom Oivision of Fire Prevention and Public Education mII~rtAII4IIcolll9fQ
121 Sw 3rd Street n ~r L W~Im HaRandale Beach Florida 33009 ~~mlCrxgthbOII
FAX (954) 457-1472 L-InpocIGrv Fij~ tOj~~OQ
FIRE INSP~CTION REPORT
ANNUAL - Commercial (0-5000) Assigned To ALEMAN Miguel on 5212013
Oat 512112013 120000AM
Location Numb 838798
BuslrWlU Nam UPPER OECK SPORTS GRILL
AddtelS 906 E HALLANDALE BEACH BLVD
CltylSlafDIZlp HALLANDALE BEACH fL 33009
Voftion
HOOD SYSTEMS
FRVER SEPARATION MISSING (NI NFPA 96 2()0412 124
(NI NFPA 96 200412124
IN] NFPA 96 ~0Olti 1 12125
IN] NFPA 96 200412125 MUST HAVe 16 IN HORIZONTAL OR 81NCH VERTICAL SEPARATION BETWEEN FRYER AND OPEN FLAME APPLIANCES
ELECTRICAL
ELECTRICAL OUTLET pLATE COVER MISSING
ELECTRICAL PANEL OBSTRUCTED
REMOVE ALL EXTENSION CORDS (SI NfPA 1 _ 2006111 15
EXTENSION CORDS SHALL NOT BE USED AS A SUBSTITUTE FOR PERMANENT WIRING EXTENSiON COROS SHALL NOT EXTEND THROUGH WALLS CEIUNGS OR fLOORS OR UNDER DOORS OR FLOOR COVERINGS
KITCHEN AND HOST AREA
EGRESS I EXIT
EMERGENCY LIGITS SHALL BE PROVIDED
EMERGENCY LIGHTS SHALL BE PROVIDED TO ILLUMINATE MEANS OF EGRESS
GENERAL
PRIOR VIOLAnONS NOT CORRECTED
Recipient Signarurt
RecipIent
I Page1 ALL LIFE SAFETY bODE VIOLATIONS SHALL BE CORRECTEO IMMEDIATELY
ANNUAL - Commercial (0-5000) ASsigned To ALEMAN Mlguamp1 on 91612012 I Date 916120 12 120000AM
ILocatiOtl Number 188160
BulnfJ Name OCEANS 11 LOUNGE
AddrI8$ 800 N FEDERAL rNVV
CltyfStatelZlp HALLANOALE BEACH FL 33009
Rlclplent Signature I Recipient
Page2 All LIFE SAFETY CODE vlouoom SHALl BE CORRECTED IMMEDIATELY
ConlJCjt ua 0i1I101on ChIeI G Pa(llLtllJ1oHALLANDALE BEACH FIRE RESCUE ~ruloregeohborg ~Mmt M Alom Oivision of Fire Prevention and Public Education mII~rtAII4IIcolll9fQ
121 Sw 3rd Street n ~r L W~Im HaRandale Beach Florida 33009 ~~mlCrxgthbOII
FAX (954) 457-1472 L-InpocIGrv Fij~ tOj~~OQ
FIRE INSP~CTION REPORT
ANNUAL - Commercial (0-5000) Assigned To ALEMAN Miguel on 5212013
Oat 512112013 120000AM
Location Numb 838798
BuslrWlU Nam UPPER OECK SPORTS GRILL
AddtelS 906 E HALLANDALE BEACH BLVD
CltylSlafDIZlp HALLANDALE BEACH fL 33009
Voftion
HOOD SYSTEMS
FRVER SEPARATION MISSING (NI NFPA 96 2()0412 124
(NI NFPA 96 200412124
IN] NFPA 96 ~0Olti 1 12125
IN] NFPA 96 200412125 MUST HAVe 16 IN HORIZONTAL OR 81NCH VERTICAL SEPARATION BETWEEN FRYER AND OPEN FLAME APPLIANCES
ELECTRICAL
ELECTRICAL OUTLET pLATE COVER MISSING
ELECTRICAL PANEL OBSTRUCTED
REMOVE ALL EXTENSION CORDS (SI NfPA 1 _ 2006111 15
EXTENSION CORDS SHALL NOT BE USED AS A SUBSTITUTE FOR PERMANENT WIRING EXTENSiON COROS SHALL NOT EXTEND THROUGH WALLS CEIUNGS OR fLOORS OR UNDER DOORS OR FLOOR COVERINGS
KITCHEN AND HOST AREA
EGRESS I EXIT
EMERGENCY LIGITS SHALL BE PROVIDED
EMERGENCY LIGHTS SHALL BE PROVIDED TO ILLUMINATE MEANS OF EGRESS
GENERAL
PRIOR VIOLAnONS NOT CORRECTED
Recipient Signarurt
RecipIent
I Page1 ALL LIFE SAFETY bODE VIOLATIONS SHALL BE CORRECTEO IMMEDIATELY
ConlJCjt ua 0i1I101on ChIeI G Pa(llLtllJ1oHALLANDALE BEACH FIRE RESCUE ~ruloregeohborg ~Mmt M Alom Oivision of Fire Prevention and Public Education mII~rtAII4IIcolll9fQ
121 Sw 3rd Street n ~r L W~Im HaRandale Beach Florida 33009 ~~mlCrxgthbOII
FAX (954) 457-1472 L-InpocIGrv Fij~ tOj~~OQ
FIRE INSP~CTION REPORT
ANNUAL - Commercial (0-5000) Assigned To ALEMAN Miguel on 5212013
Oat 512112013 120000AM
Location Numb 838798
BuslrWlU Nam UPPER OECK SPORTS GRILL
AddtelS 906 E HALLANDALE BEACH BLVD
CltylSlafDIZlp HALLANDALE BEACH fL 33009
Voftion
HOOD SYSTEMS
FRVER SEPARATION MISSING (NI NFPA 96 2()0412 124
(NI NFPA 96 200412124
IN] NFPA 96 ~0Olti 1 12125
IN] NFPA 96 200412125 MUST HAVe 16 IN HORIZONTAL OR 81NCH VERTICAL SEPARATION BETWEEN FRYER AND OPEN FLAME APPLIANCES
ELECTRICAL
ELECTRICAL OUTLET pLATE COVER MISSING
ELECTRICAL PANEL OBSTRUCTED
REMOVE ALL EXTENSION CORDS (SI NfPA 1 _ 2006111 15
EXTENSION CORDS SHALL NOT BE USED AS A SUBSTITUTE FOR PERMANENT WIRING EXTENSiON COROS SHALL NOT EXTEND THROUGH WALLS CEIUNGS OR fLOORS OR UNDER DOORS OR FLOOR COVERINGS
KITCHEN AND HOST AREA
EGRESS I EXIT
EMERGENCY LIGITS SHALL BE PROVIDED
EMERGENCY LIGHTS SHALL BE PROVIDED TO ILLUMINATE MEANS OF EGRESS
GENERAL
PRIOR VIOLAnONS NOT CORRECTED
Recipient Signarurt
RecipIent
I Page1 ALL LIFE SAFETY bODE VIOLATIONS SHALL BE CORRECTEO IMMEDIATELY