crowcon sensores
DESCRIPTION
Sensores para detecção de gases toxicos e inflamaveis do fabricante CrowconTRANSCRIPT
CO2
H2S
CI2
NH3
O3
CO
O2
CH4
SO2
CO2
H2S
Fixed detectors for flammable, toxic or oxygen gases
Xgard Type 1: Intrinsically safe toxic and oxygen gas detector
Xgard Type 2: Flameproof toxic and oxygen gas detector
Xgard Type 3: Flameproof flammable gas detector
Xgard Type 4: Flameproof high temperature flammable gas detector
Xgard Type 5: Flameproof flammable gas detector with 4-20mA output
Xgard Type 6: Flameproof thermal conductivity type gas detector
Xsafe: Safe area flammable gas detector
Xgard
XgardThe Xgard range of gas detectors has been specifically designed to meet your requirements. The dangers presented by toxic and flammable gases as well as oxygen deficiency vary with each application.
Xgard offers three different sensor concepts so you can choose exactly what you need for your site. Xgard is available in flameproof, intrinsically safe or safe area formats for use in all environments, whatever the classification.
Low cost of ownership• Xgard detectors are designed for easy installation and
maintenance to keep costs down.
• The three junction box options are all designed to make
replacement of sensors and sinters extremely simple.
Spare sensors simply plug-in.
• Many spare parts are common to all Xgard models, which
keeps spares holding requirements to a minimum.
Flexible installation options• Xgard is designed for either wall or ceiling mounting
without the need for additional brackets.
• Xgard can accommodate M20, 1/2” NPT or
3/4” NPT cable glands to suit all site requirements.
• High temperature models are available for hot
environments (up to 150oC).
• Accessories are available for duct mounting and sampling
applications as well as remote gassing for simple sensor
checking.
Wide range of sensorsXgard offers an extremely wide range of sensors for all
applications:
• Poison resistant pellistors, for all flammable detection
needs including hydrocarbons, hydrogen, ammonia, jet
fuel, leaded petrol and vapours containing halogens.
• Electrochemical sensors are used to detect a vast range
of toxic gases and oxygen.
• Thermal conductivity sensors are available to monitor
volume concentrations of gases.
Rugged and reliable• Xgard is manufactured using a choice of three
materials: glass reinforced nylon, highly durable
aluminium with a tough polyester coating, or 316
stainless steel for ultimate corrosion resistance. All
versions are designed to operate even in the harshest
conditions.
• Spray deflectors and weatherproof caps are available
for use in areas subject to regular wash-downs, or
offshore environments.
• All models have been validated to the functional
safety standard IEC 61508 (SIL 1 to SIL 3).
Accessories(all accessories require an Accessory Adaptor to be fitted to the Xgard junction box)
For outdoor use and protection against wash-down operations.
Spray Deflector
For use where a
detector is installed
in direct sunlight
Sun Shield
For use in very wet
conditions, such as
offshore installations
and ships.
Weatherproof Cap
For aiding detection
of gases which are
lighter than air, such
as hydrogen and
methane.
Collector Cone
For use in sampling
applications.
Flow Adaptor
For fitting accessories
to Xgard.
Accessory Adaptor
Xgard label
Amplifier PCB
Universal junction box
‘O’ ring
Plug-in sensor moduleWall mounting lugs
PCB cover
Screw-on lid
Sensor retainer with sinter on
flameproof models
M20, 1/2” or 3/
4”
cable entry
Ceiling mounting lugs
The Xgard range offers a comprehensive selection of fixed point gas detectors that meet the diverse requirements for flammable and toxic gas detection and oxygen monitoring in industries throughout the world.
This diagram is designed to help you choose the correct Xgard detector to suit your needs.
Detector Selector
Ordering RequirementsThe following code is designed to help in the selection of the correct detector. The product reference number should be compiled by inserting the appropriate integer in each box.
*1: Xgard Type 1 ATEX certified detectors will be supplied in a glass-reinforced nylon enclosure as standard, or in a 316 stainless steel enclosure as an option. Xgard Type 1 UL certified detectors and all other Xgard Types will be supplied in aluminium as standard, or in a 316 stainless steel enclosure as an option.
*2: The stainless steel option is not available for Xsafe and Xgard type 4. Example product reference for an I.S. 0-25ppm H2S detector with ATEX certification and M20 cable entry in a standard (nylon) junction box:
XGARD/1/A/M20/AT/H2S/25.
Gas Hazard
TOXI
C O
R O
XY
GEN FLAMM
ABLE
% VolumeGas Concentrations
CO2, CH
4, He, Ar
ZONE 1 OR 2, D
IV 1 OR 2
ZONE 0,1 OR
2, D
IV 1
OR
2
ZO
NE 1
OR 2, DIV 1 OR 2
ZONE 1 OR 2, DIV 1 OR 2
SAFE AREA
Xgard Type 6
Xsa
fe
Xgar
d Ty
pe 1
Xgar
d Type 2
Xgard Type 4 Xgard Type 5 Xgard Type 3
Flameproof electrochemical type detector with 2-wire 4-20mA output.
Intrinsically Safe electrochemical type detector with 2-wire 4-20mA output. Wide range of sensor options. A zener barrier or galvanic isolator is required for I.S. operation.
Flameproof thermal conductivity type detector with 3-wire 4-20mA output.
Flameproof high temperature (up to 150oC) catalytic bead type detector with mV bridge output.
Flameproof catalytic bead type detector with 3-wire 4-20mA output.
Non-certified low cost catalytic bead type detector with 3-wire 4-20mA or mV bridge output.
Flameproof catalytic bead type detector with 3-wire mV bridge output.
Detector Type No. Code Output Junction Box Code Cable Entry Code Certification Code Gas Type Range
XGARD Type 1 1 Standard*1 A M20 M20 ATEX AT Abbreviated up From selection
XSAFE Type 2 2 Stainless Steel*2 S 1/ 2”NPT 1/ 2 UL UL to 8 characters shown on table
Type 3 3 3/ 4”NPT 3/ 4
Type 4 4
Type 5 5
Type 6 6
XSAFE XS mV or mA
Notes: Other sensors and ranges may be available, please contact Crowcon. *Ranges not available for Xsafe or Xgard Type 4 †Contact Crowcon for availability LTEL & STEL figures are derived from the UK HSE document: EH40 Oct 07. Alternative thresholds may apply in countries outside of the UK LEL figures derived from EN61779-1: 2000 *1 Current limits advised in the UK *2 Nominal 0-100ppm range with Carbon Monoxide (CO). Contact Crowcon for a full list of gases that can be detected using this sensor
Xgard Gases and Ranges:
Gas type LTEL(ppm) STEL(ppm) Ranges Available: Ranges Available: Ranges Available: Ranges Available: LEL(%vol) UEL(%vol) Type 1 Type 2 Type 3,4,5 & Xsafe Type 6
Acetylene (C2H
2) 2.3 (2.4) 100 0-100% lel*
Ammonia (NH3) 25 35 50, 100, 250, 0-25%lel*
15 (15) 33.6 (28) 500, 1000 ppm
Argon (Ar) - - Contact Crowcon
Arsine (AsH3) 0.05 - 1 ppm
Bromine (Br2) 0.1 0.2 3 ppm
Butane (C4H
10) 1.4 (1.8) 9.3 (9) 0-100% lel*
Carbon Dioxide 5000 15000 Contact Crowcon (CO
2) (0.5%Vol) (1.5%Vol)
Carbon Monoxide 30 200 50, 100, 200, 250, 50, 100, 250, 500, (CO) 500, 1000, 2000 ppm 1000, 2000 ppm
Chlorine (Cl2) - 0.5 3,5,10,20,50,100 ppm
Chlorine Dioxide 0.1 0.3 1 ppm (ClO
2)
Diborane (B2H
6) 0.1 - 1 ppm
Ethane (C2H
6) 2.5 (3) 15.5 0-100% lel*
Ethylene (C2H
4) 2.3 (2.7) 36 0-100% lel*
Ethylene Oxide 5 - 10, 50, 100 ppm (C
2H
4O)
Fluorine (F2) 1 1 1 ppm
Germane (GeH4) 0.2 0.6 2 ppm
Helium (He) - - Contact Crowcon
Hydrogen (H2) 4 77 (80) 200, 2000 ppm 200, 2000 ppm 0-100% lel* 0-5%, 10%, 50% vv (in air)
0-20%, 25%, 30%, 50% vv (H
2 in N
2)
Hydrogen Chloride 1 5 10, 25 ppm (HCl)
Hydrogen Cyanide - 10 25ppm (HCN)
Hydrogen Fluoride 1.8 3 10 ppm(HF)
Hydrogen Sulphide 5 10 5, 10, 20, 25, 50, 5, 10, 20, 25, 50 (H
2S) 100, 200, 250, 300, 100, 200 ppm
1000 ppm
LPG 2 10 0-100% lel
Methane (CH4) 4.4 (5) 17 (15) 0-100% lel
Nitric Oxide (NO) 5*1 15*1 25, 50, 100 ppm
Nitrogen Dioxide 1 1 10, 50, 100 ppm (NO
2)
Ozone (O3) - 0.2 1 ppm
Oxygen (O2) - - 25% Vol 25% Vol
Pentane (C5H
12) 1.4 (1.5) 7.8 (7.8) 0-100% lel*
600ppm 1800ppm
Petrol Vapour 1.3 6 0-100% lel*
Phosgene (COCl2) 0.02 0.06 1 ppm
Phosphine (PH3) 0.1 0.2 1 ppm
Propane (C3H
8) 1.7 (2.2) 10.9 (10) 0-100% lel
Silane (SiH4) 0.5 1 1 ppm
Sulphur Dioxide (SO2) 1 1 10, 20, 50, 100, 250 ppm
Vinyl Chloride 3.6 33 0-100% lel*(VCM) (CH
2=CHCl) 3 -
Volatile Organics - - 0 - 100 ppm*2
(VO)*2
* 3/4" cable entry only available on aluminium junction boxes
* 3/4" cable entry only available on aluminium junction boxes
P03018GB Issue 7 January 2010
UK: 2 Blacklands Way, Abingdon Business Park, Abingdon, OXON, OX14 1DY +44 (0) 1235 557700 [email protected]
US: 21 Kenton Lands Road, Erlanger, Kentucky 41018-1845 +1 859 957 1039 [email protected]
NL: Vlambloem 129, 3068JG, Rotterdam +31 10 421 1232 [email protected]
SG: Block 194 Pandan Loop, #06-20 Pantech Industrial Complex, Singapore, 128383 +65 6745 2936 [email protected]
www.crowcon.com
Area reserved for distributor stamp
Xgard Specification:
Xgard Model Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 Xsafe
Junction box ATEX Certified: Glass- Aluminium Aluminium Aluminium Aluminium Aluminium Aluminium material reinforced nylon or or 316 Stainless or 316 Stainless or 316 Stainless or 316 Stainless 316 S/S UL Certified: Steel Steel Steel Steel Aluminium or 316 S/S.
Dimensions 156 x 166 x 156 x 166 x 156 x 166 x 195 x 166 x 156 x 166 x 156 x 166 x 156 x 166 x 111mm (6.1 x 6.5 111mm (6.1 x 6.5 111mm (6.1 x 6.5 111mm (7.6 x 6.5 111mm (6.1 x 6.5 111mm (6.1 x 6.5 111mm (6.1 x 6.5 x 4.3 inches) x 4.3 inches) x 4.3 inches) x 4.3 inches) x 4.3 inches) x 4.3 inches) x 4.3 inches)
Weight Nylon 0.5Kg (1.1lbs) AL 1Kg (2.2 lbs) AL 1Kg (2.2 lbs) 1.5Kg (3.3 lbs) AL 1Kg (2.2 lbs) AL 1Kg (2.2 lbs) 1Kg (2.2 lbs) Alloy 1Kg (2.2 lbs) 316 S/S: 3.1kg (6.8 lbs) 316 S/S: 3.1kg (6.8 lbs) 316 S/S: 3.1kg (6.8 lbs) 316 S/S: 3.1kg (6.8 lbs) 316 S/S: 3.1kg (6.8 lbs)
Ingress IP65 IP65 IP65 IP54 IP65 IP65 IP65 protection
Cable entries 1 x M20 or 1 x M20, 1 x M20, 1 x M20, 1 x M20, 1 x M20, 1 x M20, or 1 /
2” NPT 1 /
2” NPT or 3 /
4” NPT* 1 /
2” NPT or 3 /
4” NPT* 1 /
2” NPT or 3 /
4” NPT* 1 /
2” NPT or 3 /
4” NPT* 1 /
2” NPT or 3 /
4” NPT* 1 /
2” NPT
on right-side on right-side on right-side on right-side on right-side on right-side on right-side
Terminations 0.5 to 2.5mm2 0.5 to 2.5mm2 0.5 to 2.5mm2 0.5 to 2.5mm2 0.5 to 2.5mm2 0.5 to 2.5mm2 0.5 to 2.5mm2
(20 to 13awg) (20 to 13awg) (20 to 13awg) (20 to 13awg) (20 to 13awg) (20 to 13awg) (20 to 13awg)
Sensor type Electrochemical Electrochemical Catalytic bead 316 s/s Catalytic bead Thermal Catalytic bead sensor housing conductivity with catalytic beads
Operating -20 to +50oC -20 to +50oC -40 to +80oC -20 to +150oC -40 to +55oC +10 to +55oC -40 to +80oCtemperature (-4 to 122oF) (-4 to 122oF) (-40 to 176oF) (-4 to 302oF) (-40 to 131oF) (50 to 131oF) (-40 to 176oF) (sensor dependant) (sensor dependant) (mV version) -40 to +55oC (-40 to 131oF) (mA version)
Humidity 15-90% RH 15-90% RH 0-99% RH 0-99% RH 0-99% RH 0-90% RH 0-99% RH non-condensing non-condensing non-condensing non-condensing non-condensing non-condensing non-condensing
Repeatability <2% FSD (Typ.) <2% FSD (Typ.) <2% FSD (Typ.) <2% FSD (Typ.) <2% FSD (Typ.) <2% FSD (Typ.) <2% FSD (Typ.)Zero drift <2% FSD / month <2% FSD / month <2% FSD / month <2% FSD / month <2% FSD / month <2% FSD / month <2% FSD / month (Typ.) (Typ.) (Typ.) (Typ.) (Typ.) (Typ.) (Typ.)
Response time T90 <10s Oxygen T90 <10s Oxygen T90 <15s (Typ) T90 <15s (Typ) T90 <15s (Typ) T90 <15s (Typ) T90 <15s (Typ) T90 <30s to 120s T90 <30s to 120s Toxic (sensor Toxic (sensor dependant) dependant)
Operating 8 – 30V dc 8 – 30V dc 2.0V dc +/- 0.1V 2.0V dc +/- 0.1V 10 – 30V dc 10 – 30V dc 10 – 30V dc voltage (Typ) (Typ) (mA version) 2.0V dc (mV version)
Power 24mA max. 24mA max. 300mA (Typical) 300mA (Typical) 50mA @ 24V 50mA @ 24V mA version: requirements dc 1.2W dc 1.2W 50mA @ 24V dc 1.2W. mV version: 300mA (Typ.)
Electrical 2-wire 4-20mA 2-wire 4-20mA 3-wire mV bridge 3-wire mV bridge 3-wire 4-20mA 3-wire 4-20mA mA version: output (current sink) (current sink) Typical signal Typical signal (current sink or (current sink or 3-wire 4-20mA 12-15mV / %lel >10mV / %lel source) source) (current sink or CH4 CH4 source) mV version: 3-wire mV bridge Typical signal 12-15mV / %lel CH4
Approvals ATEX: II 1 G ATEX: II 2 GD ATEX: II 2 GD ATEX: II 2 G ATEX: II 2 GD ATEX: II 2 GD Not certified Exia IIC T4 Exd IIC T6 Exd IIC T4 Exd IIC T3 Exd IIC T6 Exd IIC T6 for use in a (Tamb –40 to (Tamb –40 to (Tamb –40 to (Tamb –20 to (Tamb –40 to (Tamb –40 to hazardous +55oC) +50oC) +80oC) +150oC) +50oC) +50oC) environment. UL/cUL: Cl I, Div 1 UL: Class 1, Div. 1 Exd IIC T6 Exd IIC T4 Exd IIC T4 Groups A,B,C,D Groups B,C,D Tamb (-40 to +50oC) (Tamb –40 to +80oC) (Tamb -40 to +80oC) IECEx IECEx UL: Class 1, Div. 1 UL: Class 1, Div. 1 UL: Class 1, Div. 1 MED Marine MED Marine Groups B,C,D Groups B,C,D Groups B,C,D (Oxygen Only) (Oxygen Only) IECEx IECEx IECEx GOST-R GOST-R GOST-R GOST-R GOST-R
EMC EN 50270 EN 50270 EN 50270 EN 50270 EN 50270 EN 50270 EN 50270 compliance FCC Part 15 FCC Part 15 FCC Part 15 FCC Part 15 FCC Part 15 FCC Part 15 FCC Part 15 ICES-003 ICES-003 ICES-003 ICES-003 ICES-003 ICES-003 ICES-003
CH4
C2 H4
C3H8
C4H10
C2H50H
C6H14
LPG
C5H12
CO2
Detector Infravermelho de Gases
Xgard IR
O Xgard IR é um detector de gases à prova de explosões que usa um sensor infravermelho de duplo comprimento de onda para proporcionar detecção confiável de gases e vapores perigosos. O Xgard IR oferece muitas vantagens da tecnologia de raios infravermelhos em um pacote de preço acessível:
Baixo custo
• Sensor com mais de 5 anos de vida útil
• Necessária pouca manutenção • Substituição de peças simples • Mais baixo consumo de energia
da categoria (metade do consumo dos de esferas catalíticas)
Altamente versátil
• Saída de 4-20 mA padrão da indústria
• Compatível virtualmente com qualquer sistema de controle
• Aprovado segundo ATEX, IECEx, UL e equipamento marítimo MED**
Robusto e confiável
• Fabricado de alumínio resistente à corrosão ou aço inoxidável 316
• Proteção contra líquidos e poeira IP65
• Lâmpada IR de tungstênio de longa duração
• Total compensação de temperatura • Acessórios para ambientes úmidos • 2 anos de garantia
Opção de sensores
• Hidrocarboneto para detecção de gases de HC em concentrações inflamáveis
• Dióxido de Carbono para detecção de CO2 em concentrações tóxicas
• Tecnologia de sensor à prova de falhas • Imune a envenenamento • Nenhum dano devido a excesso de gases • Resposta rápida • Não precisa de oxigênio para funcionar
P03020BR 7ª edição setembro de 2010
UK: 2 Blacklands Way, Abingdon Business Park, Abingdon, OXON, OX14 1DY +44 (0) 1235 557700 [email protected]
US: 21 Kenton Lands Road, Erlanger, Kentucky 41018-1845 +1 859 957 1039 [email protected]
NL: Vlambloem 129, 3068JG, Rotterdam +31 10 421 1232 [email protected]
SG: Block 194 Pandan Loop, #06-20 Pantech Industrial Complex, Singapore, 128383 +65 6745 2936 [email protected]
www.crowcon.com
Area reserved for distributor stamp
Especificação do Xgard IR:
• Model
Acessórios do Xgard IR
Proteção contra o sol
A Crowcon reserva o direito de mudar o desenho ou as especificações do produto sem aviso prévio.
Material da caixa Alumínio resistente à corrosão ou aço inoxidável 316
Dimensões 156 mm x 166 mm x 111 mm (alt x larg x prof )
Peso 1 kg – Alumínio, 3,1 kg – Aço Inoxidável
Proteção contra líquidos e poeira
IP65
Entradas de cabos 1 x M20 ou ½" NPT do lado direito
Energia 10-30 VCC – 50 mA a 24 VCC, 67 mA a 10 VCC
Temperatura de funcionamento
-20°C a +55°C.
Umidade relativa 0 a 95% sem condensação
Potência elétrica 3 fios 4-20 mA (coletor ou fonte de corrente)
Terminais Adequados para cabo de até 2,5 mm2
Tipo de sensor Infravermelho
Repetibilidade +/- 2% FSD*
Desvio do zero +/- 2% FSD/mês*
Tempo de resposta T90 <30 seg.*
Zonas de área perigosa Zona 1 ou Zona 2, Zona 21/22
Aprovações II 2 GD Exd IIC T6 (Temp amb até +50°C) II 2 GD Exd IIC T4 (Temp amb até +80°C) UL Classe 1 Div. 1 Grupos B, C, D IECEx Diretiva de Equipamento Marítimo (MED, 96/98/EC conforme alteração)**
Conformidade com EMC EN50270, EN60945, FCC parte 15, ICES-003
Desempenho EN60079-29-1
* Segundo testes nos laboratórios da Crowcon ** Aprovação da Diretiva de Equipamento Marítimo MED disponível somente
para versões de hidrocarbonetos (não CO2)
Cone coletor Para auxiliar a detecção de gases
que são mais leves do que o ar (ex: metano)
Defletor de borrifos Para uso no exterior e proteção contra
operações de lavagem
Tampa à prova de intempéries Para uso em condições muito
úmidas, como instalações offshore e navios
Adaptador de fluxo Para uso em operações
de amostragem
Tipo de gás LTELLEL (% vol)
STELUEL (% vol)
Intervalos disponíveis
Dióxido de carbono (CO2) 0,5% vol. 1,5% vol. 0-2 ou 0-5%
Etileno (C2H4) 2,7 (2,3) 36 (36) 0-100% lel
Metano (CH4) 5 (4,4) 15 (17) 0-100% lel
Propano (C3H8) 2,2 (1,7) 10 (10,9) 0-100% lel
Butano (C4H10) 1,8 (1,4) 9 (9,3) 0-100% lel
Etanol (C2H5OH) 3,3 (3,1) 19 (19) 0-100% lel
Hexano (C6H14) 1,2 (1) 7,4 (8,4) 0-100% lel
GLP 2 10 0-100% lel
Pentano (C5H12) 1,5 (1,4) 8 (7,8) 0-100% lel
Os valores LEL indicados entre parênteses são tirados da norma EN 61779 Parte 1:2000
IEC 61508Validated
SIL
CO2
H2S
CI2
NH3
O3
CO
O2
CH4
SO2
HF
H2
TXgard &Flamgard Plus
The Flamgard and TXgard ‘Plus’ range of detectors offer reliable detection of flammable, toxic or oxygen gases with a local display and optional relays.
Three models are available to suit all requirements:
Flamgard Plus: ‘Exd - Flameproof’ flammable gas detector with local display and optional relays
TXgard Plus : ‘Exd - Flameproof’ toxic or oxygen gas detector with local display and optional relays
TXgard-IS+: ‘I.S. - Intrinsically Safe’ toxic or oxygen gas detector with local display
Low cost of ownership
• Non-intrusive one man calibration
• Long life sensors
• Simple parts replacement
Wide range of sensors
• Choice of catalytic beads for a wide selection of flammable gases and vapours
• Extensive range of electrochemical sensors for toxic gases and oxygen
Rugged and reliable
• TXgard Plus and Flamgard Plus are constructed using marine grade aluminium with a stainless steel sensor housing
• TXgard-IS+ is made from tough carbon loaded nylon
• Proven track record for operation in the harshest environments
Flexible output options
• 4-20mA current sink or source
• 2 or 3 wire formats
• Optional relays for alarm and fault
STEL & LTEL figures are derived from the UK HSE document: EH40. Other thresholds may apply in countries outside the UK.
Crowcon reserves the right to change the design or specification of the product without notice.
UK: 2 Blacklands Way, Abingdon Business Park, Abingdon, OXON, OX14 1DY +44 (0) 1235 557700 [email protected]
US: 21 Kenton Lands Road, Erlanger, Kentucky 41018-1845 +1 859 957 1039 [email protected]
NL: Vlambloem 129, 3068JG, Rotterdam +31 10 421 1232 [email protected]
SG: Block 194 Pandan Loop, #06-20 Pantech Industrial Complex, Singapore, 128383 +65 6745 2936 [email protected]
www.crowcon.com
Area reserved for distributor stamp
TXgard & Flamgard Plus Specification:
Model Flamgard Plus TXgard Plus TXgard-IS+
Size 200h x 115w x 115d (mm) 200h x 115w x 115d (mm) 160h x 123w x 92d (mm)
Weight 2.2kg 2.2kg 0.7kg
Enclosure material Junction box: Marine grade alloy Sensor housing: 316 stainless steel
Junction box: Marine grade alloySensor housing: 316 stainless steel
Junction box: Carbon loaded nylonSensor housing: ABS plastic
Ingress Protection IP65 IP65 IP65
Cable entries 2 x M20 or 1/2” NPT 2 x M20 or 1/2” NPT 1 x M20 or 1/2” NPT with adaptor
Power 10-30Vdc, 210mA max (relay version)160mA max (non relay)
10-30Vdc, 100mA max (relay version)50mA max (non relay)
8-32Vdc, 4-20mA loop-powered
Operation temperatures -10OC to +55OC (14OF to 131OF) -10oC to +55oC (14oF to 131oF)Figures shown exclude the sensors - Please contact Crowcon for a full list of sensor operating temperatures
-20oC to +55oC (-4oF to 131oF)Figures shown exclude the sensors -Please contact Crowcon for a full list of sensor operating temperatures
Humidity 0-99% RH non-condensing 15 to 90% RH non-condensing 15 to 90% RH non-condensing
Relays (optional) SPNO or SPNC contacts rated30Vdc 1A (non-inductive load) for Alarm 1, Alarm 2, Fault
SPNO or SPNC contacts rated30Vdc 1A (non-inductive load) for Alarm 1, Alarm 2, Fault
N/A
Display 3-digit LCD back-lit display, LED status indicator
3-digit LCD back-lit display, LED status indicator
2-Line, 16 character LCD
Calibration method Via magnetically operated buttons Via magnetically operated buttons Via push-buttons
Electrical output 3 wire 4-20mA (current sink or source) 3 wire 4-20mA (current sink or source) 2 wire 4-20mA (current sink)
Terminals Suitable for up to 1.5mm2 cable Suitable for up to 1.5mm2 cable Suitable for up to 2.5mm2 cable
Sensor type Catalytic bead Electrochemical Electrochemical
Repeatability +/- 2% FSD typically +/- 2% FSD typically +/- 2% FSD typically
Zero drift +/-2% FSD, 6 months typically +/-2% FSD, 6 months typically +/-2% FSD, 6 months typically
Response time T90 <15 seconds typically Contact Crowcon for a full list of sensor response times
Contact Crowcon for a full list of sensor response times
Hazardous area zones Zone 1 or 2 Zone 1 or 2 Zone 0, 1 or 2Division 1 or 2(when connected via an isolation device)
Approvals ATEX II 2 G Exd IIC T6UL Class I Zone 1
ATEX II 2 G Exd IIC T6UL Class I Zone 1
ATEX, IECEx II 1 G Exia IIC T4 GaUL & cUL Class I Groups A,B,C,D.
EMC compliance EN50270, FCC, ICES-003 EN50270, FCC, ICES-003 EN50270, FCC, ICES-003
Gas Type LEL (%vol) Ranges Available: Flamgard Plus
Acetylene (C2H2)* 2.3 (2.4) 0-100% LEL
Ammonia (NH3) 15 0-100% LEL
Butane (C4H10) 1.4 (1.8) 0-100% LEL
Ethanol (C2H5OH) 3.1 (4.3) 0-100% LEL
Ethane (C2H6) 2.5 (3) 0-100% LEL
Ethylene (C2H4) 2.3 (2.7) 0-100% LEL
Hexane (C6H14) 1.0 (1.1) 0-100% LEL
Hydrogen (H2) 4 0-100% LEL
LPG 2 0-100% LEL
Methane (CH4) 4.4 (5) 0-100% LEL
Methanol (CH3OH) 5.5 (7.3) 0-100% LEL
Pentane (C5H12) 1.4 (1.5) 0-100% LEL
Petrol vapour 1.3 0-100% LEL
Propane (C3H8) 1.7 (2.2) 0-100% LEL
Propanol (C3H8O) 2.2 (2.1) 0-100% LEL
LEL figures derived from EN61779-1:2000*Acetylene option not available on UL certified version.
Gas Type LTEL (ppm) STEL (ppm) Range Available:TXgard-IS+
Range Available:TXgard Plus
Ammonia (NH3) 25 35 50, 100 ,1000 ppm -
Carbon Monoxide (CO) 30 200 250, 500 ppm 100, 250, 500, 1000 ppm
Chlorine (Cl2) - 0.5 5, 10, 20 ppm -
Chlorine Dioxide (ClO2) 0.1 0.3 1 ppm -
Hydrogen (H2) N/A N/A 2000ppm, 50%LEL, 100%LEL -
Hydrogen Cyanide (HCN) 10 (MEL) 25 ppm -
Hydrogen Fluoride (HF) 1.8 3 10 ppm -
Hydrogen Sulphide (H2S) 5 10 5, 25, 50, 100, 200 ppm 15, 20, 25, 50, 100, 200 ppm
Nitrogen Dioxide (NO2) 1 1 10 ppm -
Ozone (O3) - 0.2 1 ppm -
Oxygen (O2) - - 25% Vol 25% Vol
Phosgene (COCl2) 0.02 0.06 1 ppm -
Phosphine (PH3) 0.1 0.2 2 ppm -
Sulphur Dioxide (SO2) 1 1 10, 20 ,30 ppm -
P03019GB Issue 4 April 2010
CH4
C2H
6
C3H
8
C4H
10
C5H
12
C6H
14
C7H
16
C2H
4
C2H
5OH
C3H
6
LPG
Detector Infravermelho de Gases de Hidrocarbonetos
IRmax
IRmax• Detector de gases infravermelho robusto, compacto e de baixo consumo para o monitoramento de concentrações potencialmente inflamáveis de metano, butano, propano entre muitos outros vapores e gases hidrocarbonetos.
IR Display• Acessório com Visor disponível para conexão direta com o IRmax ou por conexão remota com até 30 metros de distância do detector.
• O IR Display exibe níveis de obscurecimento óptico e de gás e permite uma calibração não invasiva do detector.
IRmaxO IRmax é um detector de gases IV de qualidade premium projetado para proteger instalações contra perigos de gases inflamáveis. IRmax é a escolha perfeita para proteger instalações novas ou para aprimorar a segurança de localidades existentes.
Robusto e confiável •Resposta rápida: com um tempo de resposta de somente
4 segundos, o IRmax fornece uma rápida detecção contra perigos de gases de hidrocarbonetos.
•Excelente segurança: projetado e aprovado em conformidade com o IEC61508 SIL 2, o IRmax foi testado rigorosamente em ambientes offshore.
•Ampla gama de temperaturas operacionais: o IRmax possui temperatura totalmente compensada para a operação em ambientes de -40°C a +75°C.
•Detecção confiável: O IRmax continua a detectar gases mesmo com o sistema óptico obstruído em até 90% por sal ou outros contaminantes. O nível de obscurecimento (contaminação) pode ser facilmente verificado pelo IR Display e um sinal de falha é gerado quando os ópticos estiverem 90% obstruídos.
•Folha de serviço comprovada: o IRmax passou por testes intensos de longa duração realizados por empresas terceirizadas para comprovar confiabilidade em ambientes quentes, frios, úmidos e salinos.
Manutenção simples •Baixa manutenção: o IRmax emprega sistemas sofisticados
e algoritmos para garantir uma operação confiável em todos os momentos.
•Calibração não invasiva remota: o IR Display permite verificação de status simples, além da capacidade de zerar e calibrar o detector. O IR Display pode ser instalado com até 30 metros de distância do IRmax e gases teste podem ser aplicados sem a necessidade de acessar o detector diretamente.
•Calibrador I.S. portátil: quando um visor local não for requerido, os detectores IRmax instalados com um módulo de barreira I.S. podem ser verificados e calibrados com uso de um acessório de calibração Intrinsecamente Seguro (I.S.).
•Ópticos STAY-CLIR: os componentes ópticos são tratados com um revestimento patenteado para evitar um obscurecimento em potencial em atmosferas com condensação. O revestimento STAY-CLIR reduz significantemente o acúmulo de poeira, sujeira ou outros contaminantes na janela e espelho.
Fácil de instalar •Tamanho compacto: o IRmax é bem menor do que os
detectores de gases IV convencionais e, por este motivo, requer menos espaço, esforços e tempo de instalação.
•Opções de instalação: o IRmax pode ser instalado em paredes, fixo em um tubo de 2” (50 mm) ou conectado a uma caixa de derivação auxiliar com uso de uma série de acessórios de montagem.
•Conectividade versátil: com padrão de indústria de sinal de saída 4–20 mA, opções para RS-485 Modbus e comunicações HART, o IRmax é compatível virtualmente com qualquer sistema de controle.
Baixo custo •Baixo consumo de energia: ao contrário dos detectores
de gases IV convencionais, o IRmax não requer janelas ou espelhos aquecidos. O IRmax consome somente 1 Watt de energia, permitindo um fornecimento de energia inferior e o uso de sistemas de backup de bateria.
• IR Display Remoto: a versão remota do IR Display permite verificação, ajuste e calibração do detector IRmax sem a necessidade de um acesso direto a ele. Este recurso elimina a necessidade do uso de escadas, andaimes, entre outros meios, para a realização de tarefas de manutenção de rotina em detectores instalados em áreas inacessíveis.
•Manutenção mínima de rotina: possui uma monitoração automática de obscurecimento óptico e somente requer testes de gases ocasionais, mantendo os custos de engenharia de manutenção ao mínimo.
O IRmax está disponível como uma unidade básica sem o visor ou com três opções de visor. O IR Display fixo é anexado permanentemente a um detector IRmax a fim de permitir verificações de status simples e calibração não invasiva. O IR Display remoto pode ser instalado com até 30 metros de distância de um detector IRmax, facilitando a verificação e manutenção dos detectores instalados em áreas inacessíveis. O calibrador I.S. portátil está disponível para conexão temporária em detectores IRmax instalados com um módulo de barreira I.S.
Opções do IRmax
IRmax•Resposta rápida
• Em conformidade com
IEC61508 SIL 2
• Vasta gama de gases
IR Display Remoto •Pode ser instalado em uma distância de até 30 metros
do IRmax
• Elimina a necessidade de acessar o detector IRmax diretamente
•Opções de comprimento de condutores de conexão
Comunicações HART•Comunicadores portáteis HART podem ser conectados ao IR Display
para diagnósticos locais e calibração
•Os dados HART são superimpostos no sinal 4-20 mA para
comunicação com sistemas de controle ativados por HART
• Compatível com topologias ponto a ponto ou HART endereçável
IR Display Fixo •Visor amplo e nítido exibe os níveis de gases
e outras informações de status
• Calibração não invasiva simples
• Permite a conexão de comunicadores HART
portáteis
• Pode ser girado para cima e para baixo a fim
de fornecer um ângulo de visão aprimorado
RS-485-Modbus•Permite interrogação remota do IRmax
• Permite que até 32 detectores possuam conexão
multiponto em uma rede endereçável
• Plataforma física RS-485 para transmissão de dados
com até 1 Km
Calibrador portátil I.S. •Permite calibração e interrogação de detectores IRmax
sem um IR Display fixo ou remoto
• Somente um calibrador I.S. portátil
requerido por conjunto de detectores IRmax
• Intrinsecamente Seguro; adequado para
uso em áreas perigosas
Módulo de IR Display Fixo
Módulo de IR Display Fixo Permite conexão de IR Display Remoto
ou Calibrador I.S. para IRmax
* 3/4" cable entry only available on aluminium junction boxes
P03024BR Edição 3 Outubro de 2010
UK: 2 Blacklands Way, Abingdon Business Park, Abingdon, OXON, OX14 1DY
+44 (0) 1235 557700 [email protected]
US: 21 Kenton Lands Road, Erlanger, Kentucky 41018-1845
+1 859 957 1039 [email protected]
NL: Vlambloem 129, 3068JG, Rotterdam
+31 10 421 1232 [email protected]
SG: Block 194 Pandan Loop, #06-20 Pantech Industrial Complex, Singapore, 128383
+65 6745 2936 [email protected]
A Crowcon se reserva o direito de alterar o design ou as especificações do produto sem aviso prévio.
www.crowcon.com
Area reserved for distributor stamp
Especificação IRmax:
Acessórios
Linearização Faixa
Acetona (C3H
6O) 0-100% LIE
Butano (C4H
10) 0-100% LIE
Etanol (C2H
5OH) 0-100% LIE
Etileno (C2H
4) 0-100% LIE
Acetato de etilo (CH3COOC
2H
5) 0-100% LIE
Heptano (C7H
16) 0-100% LIE
Hexano (C6H
14) 0-100% LIE
GPL 0-100% LIE
Metano (CH4) 0-100% LIE
Metanol (CH3OH) 0-100% LIE
Pentano (C5H
12) 0-100% LIE
Propano (C3H
3) 0-100% LIE
THF (Tetrahydrofuran) 0-100% LIE
Tolueno (C7H
8) 0-100% LIE
Outras faixas podem estar disponíveis, entre em contato com a Crowcon.
Kit suporte de montagem
Cobertura de calibração
Adaptador de fluxo Prensaestompa
Protetor solarCaixa de derivação auxiliar
Condutores de conexão para visor remoto I.S.
Kit de montagem de duto
Descrição Detector Infravermelho de gases de hidrocarbonetos de feixe duplo com visor opcional.
Material do invólucro Aço inoxidável 316
Tamanho IRmax: 158 C x 75 A x 57 P mm (6,2 x 2,9 x 2,6 pol.) IRmax com IR Display Fixo: 230 C x 75 A x 57 P mm (9 x 2,9 x 2,6 pol.) IRmax com módulo de barreira IS: 261 C x 75 A x 57 P mm (10,2 x 2,9 x 2,6 pol.) IR Display Remoto: 60 C x 54 A x 48 P (2,3 x 2,1 x 1,9 pol.)
Peso IRmax: 1,58 Kg (3,5 lbs) IRmax com IR Display Fixo: 2 kg (4,4 lbs) IRmax com módulo de barreira IS: 2,4 kg (5,3 lbs) IR Display Remoto: 0,2kg (0,4 lbs)
Proteção contra líquidos e poeira
IP66
Conexão Uma entrada de prensa de cabo ½”NPT ou M20
Alimentação 12-30 Vdc. <1W
Saída elétrica Dreno ou fonte atual de 4-20 mA Alerta de ópticos sujos 2 mA (configurável) Sinal de falha de detector 0 mA (configurável) RS-485 Modbus (opcional) HART 7 (opcional)
IR Display LCD de 4 dígitos com luz de fundo Os botões de funções podem ser desativados se necessário Sinalizador sonoro com pressionamento de tecla Terminais para conexão de comunicadores HART (função opcional) LED vermelha: Gás detectado LED laranja: Falha do IRmax LED verde: Saudável Funções de visor: nível de gás, nível de obscurecimento, tensão de alimentação, corrente de sinal Funções protegidas por senha: ação de zerar, calibração, saída de ramp, ajuste zero mA, ajuste span mA
Temperatura operacional
-40°C a +75°C (-40°F a 167°F)
Umidade Umidade relativa de 0 a 100% sem condensação
Faixa de pressão Atmosférica +/-10%
Repetibilidade +/- 2% FSD
Desvio de zero Máximo de +/- 2% FSD por ano
Tempo de resposta T90 <4 seg.
Desempenho Em conformidade com EN60079-29-1
Segurança funcional IEC61508 SIL 2
Aprovações ATEX & IECEx IRmax: Ex II 2 G Exd IIC T6 Gb (Tamb -40 a +50°C), T4 (Tamb -40 a +75°C) IRmax (IR Display compatível): Ex II 2 G Exd ia IIC T4 Gb (Tamb -40 a +75°C)
Zonas Certificado para uso em áreas de perigo Zona 1 ou Zona 2
Conformidade com EMC
EN50270:2006 FCC CFR47 Parte 15B ICES-003
CH4
C2H6
C3H8
C4H10
C5H12
C6H14
C7H16
C2H4
C2H5OH
C3H6
LPG
Pellistor Replacement IR Gas Detector
• Pellistors do not fail safe: sensors can be ‘poisoned’ and rendered insensitive to gas by silicones, lead, sulphurs and chlorinated compounds.
• Pellistors must be operated behind a sinter (flame arrestor): which may become blocked, thus preventing gas from reaching the sensor. • Pellistors may burn-out: if exposed to gas concentrations in excess of 110%LEL.
• Pellistors are high-maintenance: sensors must be regularly tested with gas to ensure they are still operational. Sensors typically last 3-5 years, after which they must be exchanged.
• Pellistors need oxygen: their ability to detect gas reduces significantly in oxygen deficient atmospheres.
IREX is an innovative infrared (IR) flammable gas detector designed specifically to directly replace pellistor (catalytic bead) type flammable gas detectors. IREX operates from control systems designed solely for use with pellistor-based gas detectors: it produces a mV Wheatsone Bridge type signal (as per a pellistor) and operates from as little as 2.9Vdc. IREX is supplied with an M20 type fixing enabling originally installed detector junction boxes and cables to be retained.
IR Technology versus Pellistor Gas SensorsPellistor sensor technology has provided effective flammable gas detection at low cost for many years. Pellistors do however have several disadvantages:
IREX
All of these issues are overcome using IREX.
Area reserved for distributor stamp
The IREX concept enables pellistor-based gas detection systems to be upgraded to dual-wavelength IR gas detector technology without incurring the very significant costs associated with upgrading the control system and re-installation.
UK: 2 Blacklands Way, Abingdon Business Park, Abingdon, OXON, OX14 1DY +44 (0) 1235 557700 [email protected]
US: 21 Kenton Lands Road, Erlanger, Kentucky 41018-1845 +1 859 957 1039 [email protected]
NL: Vlambloem 129, 3068JG, Rotterdam +31 10 421 1232 [email protected]
SG: Block 194 Pandan Loop, #06-20 Pantech Industrial Complex, Singapore, 128383 +65 6745 2936 [email protected]
www.crowcon.com
STAY-CLIR optics: optical components are treated with a patented
coating to prevent potential obscuration in condensing atmospheres.
Unlike conventional IR gas detectors, IREX does not require heated
windows or mirrors. As a result IREX consumes only 1 Watt of power
which ensures compatibility with a wide range of control systems.
Sinter-free operation: pellistor based detectors and other IR type
gas detectors are fitted with sinters (flame arrestors) to achieve Exd
Flameproof certification. Sinters slow response time significantly and can
become blocked by contaminants: a dangerous un-revealed failure.
Fast response: with a T90 response time of less than 4 seconds, IREX
competes with even the most expensive conventional IR gas detectors.
Minimal maintenance: IREX employs sophisticated systems and
algorithms to ensure reliable operation at all times. No adjustments are
necessary at the detector, zero and span adjustments (if required) are
performed at the control panel only.
Remote gassing: gas response tests and calibration can be performed
without accessing the detector. Test gas can be applied remotely via a
tube to the standard weather cover, saving significant time and cost.
3rd party validation: IREX has been independently tested for reliability
and performance in harsh offshore conditions by Micropack Engineering
Ltd a highly respected test authority. This, along with 3rd-party approval
to the performance standard EN60079-29-1, demonstrates IREX will
operate dependably in any application.
Description Dual-beam infrared pellistor replacement
hydrocarbon gas detector
Gases 0-100%LEL methane, propane, butane and other
hydrocarbons
Enclosure material 316 stainless steel
Size 120h x 55w x 130d mm (with spigot gland)
Weight 1.5Kg
Ingress protection IP66
Connection Supplied either with M20 spigot gland for
installation into existing junction boxes or with
one M20 cable gland entry
Power <1W
Operating voltage
and current
2.9 - 3.2Vdc, 330 - 400mA Over-voltage and
reverse polarity protected
Electrical output 3-wire mV (Wheatstone) Bridge. Typically 10-
20mV per % volume Methane
Operating
temperature
-40°C to +75°C
Humidity 0 to 100% RH non-condensing
Repeatability +/- 2% FSD
Zero drift +/- 2% FSD per year maximum
Response time T90 <4 secs.
Performance Tested in accordance with EN60079 - 29 - 1
Functional safety Validation to IEC61508 SIL 2*
Approvals II 2 G Exd IIB + H2 T6 (-40 to +50°C) T4 (-40 to +75°C)ATEX & IECEx
EMC compliance EN 50270, FCC, ICES-003
IREX Accessories:
• Spigot gland: for mounting IREX to existing M20 junction boxes
(supplied)
• Mounting bracket: suitable for wall or pipe mounting (not required
if spigot gland is used)
• Sun Shade/Collector Cone
• Duct sampling unit
• Calibration cap (required if ambient air speed exceeds 2m/s)
*Feature currently pending, contact Crowcon for more information
P03023 GB Issue 3 Jan 10
Specifications:
Crowcon reserves the right to change the design or specification of the product without notice.
Nimbus
DetectorsInfrared flammable gas detector you can trust
Nimbus
Rugged & reliable
One man calibration
Simple maintenance
Flexible installation
Nimbus is compact and lightweight but rugged.Maintenance is simple, and because it is compatible withhandheld and laptop computers, units can be checkedby a single engineer.
It can be integrated into existing systems with ease.Nimbus protects staff and property without makingyour life complicated.
Nimbus has been designed to be lightweightbut tough.
Even in the dirtiest conditions Nimbusstill functions. The optics operate at up to90% obscuration. While still detecting gas, at75% obscuration a dirty optics warning flashesso you know when to clean Nimbus.
Dust and water ingress are not a problem eitheras Nimbus is rated IP66 and IP67. Alliedto this Nimbus has full approvals from bothEUROPE and North America.
Nimbus has a MTBF of 10 years. This figurehas been independently assessed using the MILHandbook 217F/2/12/91
In short you can rely on Nimbus to protect you.
Nimbus has a local external status lightwhich shows, at a glance, if the unit is in normalfunction or fault. When a hazard is detected itindicates both rising gas and alarm levels.
The status light clearly indicates 22 furtherconditions for instant diagnosis.
Nimbus is simple to use even ininaccessible areas. A duct mounting plate is available, which incorporates a remote gassing port to allow calibration checking without requiring entry into the duct.
Nimbus is compatible with Windows software,which means that a Windows compatible portable PC can be used to check gas levels, find faults and change configurations in the field. Only one person is required to do this.
Nimbus is fitted with an optical Communications Interface Module, to allow connection of a PC without opening the detector.
For detectors installed in a hazardous area, the configuration and status can be checked remotely using the Modbus serial link.
Nimbus can be integrated into existingsituations with ease. It has a RS485 output and dual redundant 4-20mA outputs, compatible with metric and imperial armoured cable and conduit.
The Modbus serial link allows addressabledetectors to be looped providing a remotecontrol and interrogation facility.
For facilities where Nimbus is replacing apellistor based detector the pellistor mimicmeans that existing cabling can beretained to reduce upgrade costs.
Nimbus, the total system solution
It can interface with any standard control system,or combination of systems, new or old.
Safe area
Mounting Options
Hazardous area
Existing pellistorinstallations
Laptop/PC Configuration
New Installations
DC supply
SIDE VIEW
BOTTOM VIEW
NIMBUS DUCT MOUNTING PLATEWITH HINGE FOR EASY ACCESS
Interior Duct Mounting Exterior
PLC-DCS-BMS
MODBUS (RS485) Serial Link
Simultaneous 4-20 mA outputs sink or source
Optional pellistor mimic
3 or 4 wire mV bridge
3 wire 4-20 mA sink or source
P03005 Issue 6 08/05
NimbusInfrared flammable gas detector
UK OfficeCrowcon Detection Instruments Ltd2 Blacklands WayAbingdon Business ParkAbingdonOxfordshire OX14 1DYUnited KingdomTel: +44 (0) 1235 557700Fax: +44 (0) 1235 557749Email: [email protected] Site: www.crowcon.com
USA OfficeCrowcon Detection Instruments Ltd21 Kenton Lands RoadEarlangerKentucky 41018-1845USATel: +1 859 957 1039 or 1-800-5-CROWCONFax: +1 859 957 1044Email: [email protected] Site: www.crowcon.com
Rotterdam OfficeCrowcon Detection Instruments LtdVlambloem 1293068JG, RotterdamNetherlandsTel: +31 10 421 1232Fax: +31 10 421 0542Email: [email protected] Site: www.crowcon.net
Singapore OfficeCrowcon Detection Instruments LtdBlock 194 Pandan Loop#06-20 Pantech Industrial ComplexSingapore 128383Tel: +65 6745 2936Fax: +65 6745 0467Email: [email protected] Site: www.crowcon.com
Model Nimbus
Function The detection of hydrocarbon gases C 1 to C 6 + ethanol, ethylene and LPG in the LEL range by means of infrared absorption. Contact Crowcon for a full list of available gases and ranges.Dimensions 125 x 170 x 210 mm (5 x 6.8 x 8.3 ins)Weight 2.5 kg, (5.5 lbs)Construction LM25 marine grade alloy, polyester powder coatedOptical system Dual wavelength, dual detectorOptical performance Correct operation with up to 90% obscuration Dirty optics warning above 75% (configurable) Heated optics to avoid condensation.Power consumption Operating voltage: 10 to 32 V dc (nominal 24 V) – LK2 fitted (Anti Condensation Heater) Operating current: 300 mA max (7.2 W @ 24 V, 3 W @ 10 V) – LK2 not fitted Operating current: 180 mA max (4.3 W @ 24 V, 1.8 W @ 10 V)Typical output signals All levels configurable - simultaneous sink and source output 0 mA: fault 2 mA: dirty optics 4-20 mA: 0-100% LEL 24 mA: over rangeStatus light Green - normal function Orange - fault Red - detecting gas 22 other conditions indicated by flash rateCommunications Modbus RS485 serial linkFunctional testing Flow adaptor for gassingAccuracy ±2% of gas reading @ ≤ 50% LEL ±5% of gas reading @ > 50% to 100% LELResponse time <7 seconds - T90 <3 seconds – instantaneous high levels of gasTemperature range -40ºC to 65ºC (-40ºF to 149ºF)Humidity range 0 to 99% RH non-condensingEuropean Approvals ATEX II 2G EEx d IIB+Hydrogen T6and Standards Safety Cert. No: DEMKO01ATEX130838 Tamb = -40°C to 65°C EN50014, EN50018UL Approval and Class 1, Div 1, Groups B, C & DStandards Tamb = -20°C to 65°C UL 1203 (When connected to a class 2 Power Supply)Ingress protection IP66 (jets of water) IP67 (temporary submersion), NEMA 4XLight immunity Totally immune to all external light, both constant and modulated (including sunlight, white light, flashing beacons etc.)General immunity Totally immune to all catalyst poisonsElectromagnetic compatibility Gas detection standard EN50270 RF emissions EN50081-2 RF immunity EN50082-2
Suitable for use in Zone 1 or Zone 2Hazardous Areas
C h i h h h d i ifi i f hi d i h i