crm-91h, crm-93h, crm-9s multifunction time relay crm …€¦ · crm-91h crm-93h crm-9s crm-9s ......
TRANSCRIPT
16 17
CRM-93HCRM-91H CRM-9S
CRM-9S
A1 /B1
S A2
18 18 CCA
110ON
OFF
11 10
110
10m
S
hd 1
10ON
OFF
11 10
110
10m
S
hd 1
10ON
OFF
11 10
110
10m
S
hd 1
10ON
OFF
11 10
110
10m
S
hd 1
10ON
OFF
11 10
110
10m
S
hd1
10ON
OFF
11 10
110
10m
S
hd 1
10ON
OFF
11 10
110
10m
S
hd 1
10ON
OFF
11 10
110
10m
S
hd 1
10ON
OFF
11 10
110
10m
S
hd 1
10ON
OFF
11 10
110
10m
S
hd
8595188112444
8595188112420
8595188112789
8595188112468
8595188116008
t t
U
t t
U
t tt tt t
U
t t
S
a
b
d
e
c
i
t t t t t t
U
f
g
j
h
t t
U
S
t t t t
S
t t
S
t t
S
CRM-91 /230 V:
CRM-91 /UNI:
CRM-93H /230 V:
CRM-93H /UNI:
CRM-9S /UNI:
CRM-91H CRM-93H CRM-9S
t
t
U
15-18
LED
U
S
15-18
LED
+ -
Un
15 16 18
A1 S A2
16 18
15
S A2
A1
Un
+ -
Un
15 16 18
25 26 28
35 36 38
A1 S A2
Un
A1 S A2
B1 18 18
CRM-93HCRM-91H
15
16 18A1
S A2
16 26 3618 28 38A1
S A2 15 25 35
CRM-91H, CRM-93H, CRM-9S | CRM-91H, CRM-93H, CRM-9S |
+
• Multifunction time relay can be used for electrical appliances, control
of lights, heating, motors, pumps and fans (10 functions, 10 time
ranges, multi-voltage, 16 A or 3x 8 A contacts)
• Fulfi lls all requirements for time relays
• 10 functions:
- 5 time functions controlled by supply voltage
- 4 time functions controlled by control input
- 1 function of latching relay
• Comfortable and well-arranged function and time-range setting by
rotary switches
• Time scale 0.1 s - 10 days divided into 10 ranges: (0.1 s - 1 s / 1 s - 10 s /
0.1 min - 1 min / 1 min - 10 min / 0.1 hrs - 1 hrs / 1 hrs - 10 hrs /
0.1 day - 1 day / 1 day - 10 days / only ON / only OFF)
• CRM-91H, CRM-93H:
- universal supply voltage AC/DC 12 - 240 V or AC 230 V,
- Output contact: CRM-91H: 1x changeover/SPDT 16 A;
CRM-93H: 3 x changeover/SPDT 8 A
• CRM-9S:
- universal supply voltage AC 12 - 240 V AC 12 - 240 V, absolutely
noise-less switching
- 1x static contactless output (triac) 0.7 A (60 A / < 10 ms), switches
potential A1
• Multifunction red LED output indicator fl ashes or shines depending
on the status of output
• 1-MODULE, DIN rail mounting
Multifunction time relay
Technical parameters
load
Number of functions:
Supply terminals:
Voltage range:
Burden:
Voltage range:
Consumption (apparent / loss):
Supply voltage tolerance:
Supply indication:
Time ranges:
Time setting:
Time deviation:
Repeat accuracy:
Temperature coeffi cient:
Output
Number of contacts:
Current rating:
Breaking capacity:
Inrush current:
Switching voltage:
Voltage drop on switch:
Load on B1 terminal:
Output indication:
Mechanical life:
Electrical life (AC1):
Controlling
Power on control input:
Load between S-A2:
Control. terminals:
Glow tubes connections:
Max. amount of glow lamps
connected to controlling input:
Impulse length:
Reset time:
Other information
Operating temperature:
Storage temperature:
Electrical strength:
Operating position:
Mounting:
Protection degree:
Overvoltage category:
Pollution degree:
Max. cable size (mm2):
Dimensions:
Weight:
Standards:
10
A1 - A2
-15 %; +10 %
green LED
0.1 s - 10 days
rotary switch and potentiometer
5 % - mechanical setting
0.2 % - set value stability
0.01 % / °C, at = 20 °C (0.01 % / °F, at = 68 °F)
multifunction red LED
AC 0.025 - 0.2 VA / DC 0.1 - 0.7 W (UNI), AC 0.53 VA (AC 230 V),
AC 0.025 - 0.2 VA (AC 12 - 240 V)
Yes
A1-S
min. 25 ms / max. unlimited
-20 °C to +55 °C (-4 °F to 131 °F)
-30 °C to +70 °C (-22 °F to 158 °F)
any
DIN rail EN 60715
IP40 from front panel / IP20 terminals
III.
2
solid wire max. 1x 2.5 or 2x 1.5 /
with sleeve max. 1x 2.5 (AWG 12)
90 x 17.6 x 64 mm (3.5˝ x 0.7˝ x 2.5˝)
(UNI)-64 g (2.26 oz.); (UNI)-89 g (3.1 oz.);
(230)-62 g (2.2 oz.) (230)-87 g (3 oz.) 51 g (1.8 oz.)
EN 61812-1, EN 61010-1
AC/DC 12 - 240 V (AC 50 - 60 Hz)
AC 0.7 - 3 VA / DC 0.5 - 1.7 W
AC 230 V / 50 - 60 Hz
250 V AC1 / 24 V DC
x
x
3x107
0.7x105
230 V - Yes / UNI - No
UNI - glow lamps cannot connected/NO
230 V - max.20 pcs (measured with
glow lamp 0.68 mA / 230 V AC)
max. 150 ms
4kV (supply-output)
AC max. 12VA / 1.3W
1x changeover/ SPDT
(AgNi / Silver Alloy)
16 A / AC1
4000 VA / AC1,
384 W / DC
30 A / < 3 s
AC max. 12VA / 1.9W
3x changeover/ SPDT
(AgNi / Silver Alloy)
8 A / AC1
2000 VA / AC1,
192 W / DC
10 A / < 3 s
AC 12-240 V (50-
60 Hz)
AC max. 0.35VA
x
x
1x static contactless
output (triac)
0.7 A
x
60 A / < 10 ms
x
max. 0.9 V at I max.
Yes / I max. 0.7 A
> 108
>108
x
glow lamps cannot
connected/NO
max. 250 ms
x
EAN code
Possibility to connect load onto
controlling input
It is possible to connect the load
(e.g.: contactor) between terminals
S-A2, without any interruption of
correct relay function.
Examples of signaling
Supply terminals
1) Output contacts of CRM-93H do not allow switching of diff erent phases or 3-phase voltages (voltage > 250 V).
2) When mounting into steal-plated switchboards, it is necessary to keep a safety distance of min. 3 mm from terminal’s screws 35-36-38 and 25-26-28
towards the shutter of a switchboard.
Function
Control input “S”
Supply indication
Rought time setting
Fine time setting
Function setting
Output indication-multifunction LED
Output contactTime ranges
0.1 - 1s 1 - 10 s 0.1 - 1 min 1 - 10 min 0.1 - 1 h 1 - 10 hrs 0.1 - 1 day 1 - 10 days only ON only OFF
Description
Notes
Multifunction time relay
On Delay (Power On)
When the input voltage U is applied, timing delay t
begins. Relay contacts R change state after time de-
lay is complete. Contacts R return to their shelf state
when input voltage U is removed. Trigger switch is
not used in this function.
Off Delay
When input voltage U is applied, relay contacts
R change state immediately and timing cycle be-
gins. When time delay is complete, contacts return
to shelf state. When input voltage U is removed,
contacts will also return to their shelfstate. Trigger
switch is not used in this function.
Repeat Cycle (Starting Off )
When input voltage U is applied, time delay t be-
gins. When time delay t is complete, relay contacts
R change state for time delay t. This cycle will repeat
until input voltage U is removed. Trigger switch is
not used in this function.
Repeat Cycle (Starting On)
When input voltage U is applied, relay contacts R
change state immediately and time delay t begins.
When time delay t is complete, contacts return to
their shelf state for time delay t. This cycle will repe-
at until input voltage U is removed. Trigger switch is
not used in this function.
Off Delay (S Break) Input voltage U must be applied continuously. When trigger
switch S is closed, relay contacts R change state. When trigger
switch S is opened, delay t begins. When delay t is complete,
contacts R return to their shelf state. If trigger switch S is clo-
sed before time delay t is complete, then time is reset. When
trigger switch S is opened, the delay begins again, and relay
contacts R remain in their energized state. If input voltage U is
removed, relay contacts R return to their shelf state.
Single Shot Upon application of input voltage U, the relay is ready to
accept trigger signal S. Upon application of the trigger signal S,
the relay contacts R transfer and the preset time t begins. Du-
ring time-out, the trigger signal S is ignored. The relay resets by
applying the trigger switch S when the relay is not energized.
Single Shot Trailing Edge (Non-Retriggerable) Upon application of input voltage U, the relay is ready to
accept trigger signal S. Upon application of the trigger signal
S, the relay contacts R transfer and the preset time t begins.
At the end of the preset time t, the relay contacts R return to
their normal condition unless the trigger switch S is opened
and closed prior to time out t (before preset time elapses).
Continuous cycling of the trigger switch S at a rate faster than
the preset time will cause the relay contacts R to remain clo-
sed. If input voltage U is removed, relay contacts R return to
their shelf state.
On/Off Delay Input voltage U must be applied continuously. When trigger
switch S is closed, time delay t begins. When time delay t is
complete, relay contacts R change state and remain transfe-
rred until trigger switch S is opened. If input voltage U is remo-
ved, relay contacts R return to their shelf state.
Latching relay
Input voltage U must be applied continuously. Out-
put changes state with every trigger switch S clo-
sure. If input voltage U is removed, relay contacts R
return to their shelf state.
Pulse generator
Upon application of input voltage U, a single output
pulse of 0.5 seconds is delivered to relay after time
delay t. Power must be removed and reapplied to
repeat pulse. Trigger switch is not used in this func-
tion.
Function a
Function e pulse = 0.5 s
pulse pulse
Connection
Symbol