Brief description
CPV valve terminalwith AS-Interfacetype CPV..-GE-ASI-4E4A-...
– English
8076574
2017-11e
[8076576]
Compact performance
Festo CPV..-GE-ASI-4E4A-... 2017-11e 2
Translation of the original instructions
Documentation on the product
For all available product documentation
� www.festo.com/pk
AS-Interface® is a registered trademark of the AS-InterfaceAssociation.
Copyright:
Festo SE & Co.Ruiter Straße 8273734 Esslingen Germany
Internet: �http://www.festo.comE-Mail: �[email protected]
Reproduction, distribution or sale of this document or communication ofits contents to others without express authorization is prohibited. Offenders will be liable for damages. All rights reserved in the event thata patent, utility model or design patent is registered.
English 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Festo CPV..-GE-ASI-4E4A-... 2017-11e English 3
1 User instructionsEnglish
Valve terminal type CPV..-GE-ASI-4E4A-... has been designed exclusively for controlling pneumatic actuators andis only suitable for use in bus systems in accordance withthe AS-Interface specifications. If additional commercially-available components such as sensors and actuators areconnected, the specifiedlimits for pressures, temperatures, electrical data, torques, etc. must not be exceeded.
AS-Interface bus systems and valve terminals may only beinstalled by personnel especially trained for this purpose.Detailed information on the design and addressing of yourbus system can be found in the manual for your AS-Interface master.
Information on the pneumatic components of the valve terminal can be found in the Pneumatics manual P.BE-CPV-... .
Warning� Switch off the power supply before connecting or
disconnecting plugs (otherwise this could lead tofunctional damage).
� Connect the earth connection on the left end platewith low impedance (short cable with large cross-sectional area) to the earth potential.
� Commission only a valve terminal which has beenfitted and wired completely.
Festo CPV..-GE-ASI-4E4A-... 2017-11e English4
2 Connecting and display elements
1 2 3 4
5
6
789
1 AS-Interface bus connection
2 Earth connection
3 Type plate
4 LED status display for inputs(green)
5 Sensor connections (PNP)
6 Inscription field for AS-Interface address
7 LED status display forvalves (yellow)
8 Load voltage connection for valves *)
9 PWR LED (Power, green),Fault LED (red)
*) Only with type CPV..-GE-ASI-4E4A-Z: Valves can be switched off during EMERGENCY STOP, no voltage supply to valves via AS-Interface bus
PWR LED Fault LED Meaning
onoffflasheson
on
offoffonflashes
on
AS-Interface voltage applied, no faultNo AS-Interface voltage on the busAS-Interface address not set ( = 0)Short circuit / overload at the inputs or address selector switch actuatedBus communication failed (watchdog expired)
Festo CPV..-GE-ASI-4E4A-... 2017-11e English 5
3 Installation instructions
3.1 Assigning the AS-Interface address
Please noteThe AS-Interface address of the valve terminal typeCPV..-GE-ASI-4E4A-... is stored electronically (no battery) after every modification and can be modified atleast 10 times. After that the valve terminal maintainsthe last set AS-Interface address.
We recommend that you use the Festo addresser type ASI-PRG-ADR with adapter cable type KASI-ADR.
Before connecting to the AS-Interface bus: assign an unused address to each slave. Set the desired address withthe AS-Interface addresser. The permitted address range is1 ... 31.The factory setting of the terminal is address 0. It is notnecessary to parametrize the AS-Interface slaves.
Example of address assignment (Siemens S7)
IO-Code 7H: D3 D2 D1 D0I/O I/O I/O I/O
Input Output‹7 6 5 4 3 2 1 0› ‹7 6 5 4 3 2 1 0›
���res.�������#1 ���res.�������#1����#2��������#3 ����#2��������#3����#4��������#5 ����#4��������#5����#6��������#7 ����#6��������#7�...
PLC
...
...
36
...
...
= Assigned addresseswith IO code 7H
AS-Interface adress #5, PLC byte #36
Festo CPV..-GE-ASI-4E4A-... 2017-11e English6
3.2 Address assignment of the solenoid coils (top view)
Fitting valve locations 1 to 4
2 double-solenoid valves
4 single-solenoid valves
1 double-solenoid valve,2 single-solenoid valves
12
34
5 6 5 6
1 2 3 4
7 7 7 7
12
3 4
5 6 7 7
1 234
7 7 5 6
DIP switch setting (see 3.6)
1: ON2: OFF3: ON4: OFF
1: OFF2: ON3: OFF4: ON
1: ON2: OFF3: OFF4: ON
1: OFF2: ON3: ON4: OFF
1 ... 4 Addresses of the solenoid coils5 Valve plates with 2 valve solenoid coils, like 2 single-sole
noid valves, 5/2-way double-solenoid valves or 5/3-wayvalves (e.g. code J, N, C, H, G, D, I, E) or blanking or separatorplate
6 Blanking or separator plate (e.g. code L, S, T)7 Valve plates with 1 valve solenoid coil (e.g. code M, F, A) or
blanking or separator plate
Festo CPV..-GE-ASI-4E4A-... 2017-11e English 7
Example (Siemens S7)
– 1 double-solenoid valve, 2 single-solenoid valves
– PLC byte #36 and AS-Interface address #5
This results in the following address assignment of thevalve terminal:
Adresses of the Inputs:
Adresses of the outputs:
J = Double-solenoid valve M = Single-solenoid valve L = Blanking plate
I36.0 ... 3
0 1 2 3
1J L M M
O36.0 ... 3
0 – 2 3
1 – – –12
14
1 Identifications for valve plates (example: J, M, L)
Festo CPV..-GE-ASI-4E4A-... 2017-11e English8
3.3 Connecting sensors (PNP inputs)
For connecting sensors use cable type KM8-M8-GSGD-...and plugs with union nut, M8x1 thread.
Fasten the plugs with the aid of the union nut in order toprevent unintentional loosening, e.g. due to shock. Sealunused sensor connections with the protective caps typeISK-M8. Only in this way can you comply with protectionclass IP65.
Please note‒ The inputs have been based on the IEC1131-2 type
02.‒ The inputs are protected against short circuits. If a
short circuit occurs, the slave will be switched off.The AS-Interface master regards this slave as missing. When the short circuit has been eliminated, theslave responds immediately as being operative.
1 Pin assignment:1: 24 V3: 0 V4: Input Ix+3
1
1
4
3
Festo CPV..-GE-ASI-4E4A-... 2017-11e English 9
3.4 Connecting the AS-interface bus and the load voltage
Please noteThe sensor power supply for the inputs is provided viathe AS-interface bus. Voltage suppply of the outputsvia the AS-Interface bus is only possible with typeCPV...-GE-ASI-4E4A.Type CPV...-...-Z must always besupplied with 24 V via the load voltage connection. The AS-Interface has an integrated watchdog functionwhich resets the outputs if there is a bus communication failure.
WarningUse power supplies which guarantee reliable electricalisolation of the operating voltage as per IEC/DIN EN60204-1. Consider also the general requirements forPELV circuits in accordance with IEC/DIN EN 60204-1.
By the use of PELV circuits, protection against electricshock (protection against direct and indirect contact) isguaranteed in accordance with IEC/EN 60204-1 (Electrical equipment for machines, General requirements).
Festo CPV..-GE-ASI-4E4A-... 2017-11e English10
Please note with branch lines:
– the total maximum length of the AS-Interface bus: 100 m (without repeater/extender).
– the cable length of the load voltage connection (depends on the ccurrent consumption of the valveterminal and the fluctuations in the load voltage).
– seal unused cable ends with the Festo cable cap ASI-KK-FK or the cable sleeve ASI-KT-FK. In this way youwill avoid leakage currents and comply with protectionclass IP65.
1 Pin 2: AS-Interface�+(brown)
2 Pin 1: AS-Interface - (light blue)
3 Pin 2: + 24 V *)
4 Pin 1: 0 V *)
1
2
3
4
*) Only with CPV...-GE-ASI-4E4A-Z
Recommendation: For connecting the valve terminal usethe Festo cable sockets ASI-SD-FK... . You will then complywith protection class IP65.
Festo CPV..-GE-ASI-4E4A-... 2017-11e English 11
Proceed as follows:
1. Press the AS-Interface cable into the upper part of thecable socket.
2. Make sure that the AS-Interface cable is free of tension.
3. Place the cable socket in position and screw it tight(max. 0.3 Nm).
1 AS-Interface cable
2 Cable cap type ASI-KK-FK
3 Cable socket typeASI-SD-FK (or ASI-SD-FK180)
1 2
3
3.5 Connection example – valve terminal type 10
1 AS-Interface master
2 Combination powersupply from Festo(electronically safeguarded/short-circuit proof )
3 Load voltage can be switched off
1
2
3
Festo CPV..-GE-ASI-4E4A-... 2017-11e English12
3.6 Converting the valve terminal
The CPV valve terminal can be fitted with double-solenoidand/or single-solenoid valves. During conversion, the newvalve terminal configuration must be set on the DIPswitches on the bottom of the electric sub-base.
1 DIP switch on thebottom of the sub-base 1
Instructions on removign the electric sub-base can befound in the Pneumatics Manual. The permitted valve combinations as well as the relevant DIP switch settings can befound in the table in section 3.2.
Festo CPV..-GE-ASI-4E4A-... 2017-11e English 13
4 Technical specifications
Type CPV...-GE-ASI-4E4A... M8
General technical specifications See Pneumatics manualP.BE-CPV-...
Protection class according to EN�60529plug connector inserted or provided withprotective cap
IP65
Electromagnetic compatibility– EMC interference emission– EMC resistance to interference
See declaration ofconformity� www.festo.com
AS-Interface bus connection– voltage range
(protected against incorrect polarity)– residual ripple– max. current consumption
a) Type CPV...-GE-ASI-4E4A-Z M8– all inputs in 0-status– all inputs in 1-status, no current
consumption by sensors 1)
– all inputs in 1-status, max. current consumption by sensors
b) Type CPV...-GE-ASI-4E4A M8 (max. two coils energized simultaneously)
– all inputs in 0-status– all inputs in 1-status, no current
consumption by sensors 1)
– all inputs in 1-status, max. current consumption by sensors
DC 26.5 ... 31.6 V
≤ 20 mVss
CPV10-... CPV14-...7mA 7mA35mA 35mA
137mA 137mA
CPV10-... CPV14-...61mA 95mA89mA 123mA
191mA 225mA
1) e.g. switches
Festo CPV..-GE-ASI-4E4A-... 2017-11e English14
Type CPV...-GE-ASI-4E4A... M8
Load voltage connection (only type ...-4E4A-Z)– rated value
(protected against incorrect polarity)– residual ripple– Current consumption for 4 valves
(at 24 V)– when switching on– after current drop (stationary)
DC 21.6 ... 26.4 V
4 Vss
CPV10-... CPV14-...108 mA 176 mA42 mA 72 mA
Valves (see pneumatics manual) Watchdog function activeafter 50 ms (see 3.4)
Digital inputs
– design
– logic level
– reference potential– response delay
4 inputs based on IEC1131-2 type 2DC 24 V, PNP, Status display (LED)ON: 11 ... 30 VOFF: -30 ...-5 V0Vtyp. 3 ms (at 24V)
AS-Interface data– Profile
ID-Code=FH;IO-Code=7HS-7.F