Medium Voltage SwitchgearPrimary Distribution
CPG.0Gas insulated, single busbar cubicle rangeUp to 24 kV / 2500 A / 25 kAUp to 36 kV / 1250 A / 25 kACPG System
Thequalityoftheproductsdesigned,manufacturedandinstalledbyOrmazabalisbackedbytheimplementationandcertificationofaqualitymanagementsystem,basedontheinternationalstandardISO9001:2000.Our commitment to the environment is reaffirmed withtheimplementationandcertificationofanenvironmentalmanagementsystemaslaiddownininternationalstandardISO14001.
Inviewoftheconstantevolutioninstandardsanddesign,thecharacteristicsoftheelementscontainedinthiscataloguearesubjecttochangewithoutpriornotification.Thesecharacteristics,aswellastheavailabilityofcomponents,are subject to confirmation by Ormazabal's Technical-Commercialdepartment.
FocusonMediumVoltage3
Gas insulated, single busbar cubicle rangeUp to 24 kV / Up to 36 kV
CPG SystemMedium Voltage Switchgear Primary Distribution
Contents
Generaldescription 4Presentation 4
Areasofimplementation 4
Applicablestandards 5
Constructioncharacteristics 5
Safety 6
Qualityoftheelectricalsupply 7
Typesofcubicles 8CPG.0-V 9
CPG.0-S 10
CPG.0-F 11
CPG.0-C 12
CPG.0-RB 13
Mainfunctionalelements 14Safeoperation 14
ekorSYSfamily 16
Auxiliaryelements 17
Protection 18
Installation 18Characteristics 18
Civilwork 19
Connectionbetweencubicles 19
FocusonMediumVoltage4
Gas insulated, simple busbar cubicle rangeUp to 24 kV / Up to 36 kV CPG System Medium Voltage Switchgear
Primary Distribution
TheCPG.0rangeofOrmazabal'sCPGsystemismadeupofafullassemblyofmodularcubiclesofupto24kV/2500 Aandupto36kV/1250A,GIStype,withSF6insulation,fortheconfigurationofdifferentprimarydistributionelectricaldiagrams.
Typesoffunctionalunits:
•Circuit-breakerCPG.0-V
•BusbarcouplingCPG.0-C
•DisconnectorCPG.0-S
•FuseprotectionCPG.0-F
•BusbarriseCPG.0-RB
TheinstallationofelementsthatallowtowithstandaninternalarcinalltheirMediumVoltagecompartments,togetherwithanadvanceddesignthatprovidestotalresistanceagainstexternalagents,makestheCPG.0cubiclestheidealsolutionforusinginsubstations,bothpublicandprivate,providingasafeandreliabledistribution.
Thefinalqualityoftheproductsuppliedisbackedbyanautomatedmanufactureprocesswhereroutinetestsarecarriedoutinthedifferentassemblystages.
AReASOFIMPLeMenTATIOn
Designedforuseinawiderangeofinstallations,bothpublicandprivate.Theirmainapplicationsare:
General description
STAnDARDS
IEC 62271-001Commonspecificationsforhighvoltageswitchgearandcontrolgearstandards.
IEC 62271-200Alternatingcurrentmetal-enclosedswitchgearandcontrolgearforratedvoltagesabove1kVandupto52kV.
IEC 62271-100Highvoltagealternatingcurrentcircuit-breakers.
IEC 62271-102Alternatingcurrentdisconnectorsandearthingswitches.
IEC 62271-105Highvoltagealternatingcurrentswitch-fusecombination.
•Utilities • Industrial sector
• Primarydistributionsubstations •Cementindustry •Miningindustry
•Mobilesubstations • Switchingsubstations • Textileindustry • Foodindustry
•Electrical power stations •Chemicalandpetrochemicalindustry
• Substation • Steelindustry
•Large infrastructures • Automotiveindustry
• Airportsandrailways •Windfarms
FocusonMediumVoltage5
Gas insulated, single busbar cubicle rangeUp to 24 kV / Up to 36 kV
CPG SystemMedium Voltage Switchgear Primary Distribution
COnSTRuCTIOnCHARACTeRISTICS
TheCPG.0cubiclespresentanarchitecturedividedintoindependentcompartments:
• (A)Switchcompartment.
• (B)Busbarcompartment.
• (C)Cablecompartment.
• (D)Controlcompartment.
• (e)Operationinterface
Itsstructureismadeupofametalframewithamechanicalrigiditythatpreservestheshapeoftheassemblyundernormalserviceconditions.
Theframe,togetherwiththerestofnon-livemetalpartsofthecubicle,isconnectedtothegeneralearthingbusbar,reinforcingthesafetyoftheinstallation.
Thecubiclesareconnectedusingabusbarinstalledintheupperpartofthecubiclesinacompartmentoutsidetheswitchcompartment.
Theswitch compartment,sealedforlife,housestheswitchingandbreakingswitchgear,wheretheinsulatingmediumisSF6gas.Builtinstainlesssteel,itisdesignedtowithstandaninternalarcofupto25kA/1s.Thegasgeneratedasaresultofaninternalarciscooleddownandcanbechannelledthroughareliefductlocatedontherearside.
Thefollowingelementsarelocatedinside,dependingonthefunctionality:
•Disconnectorandearthingswitch.
•Vacuumcircuit-breaker.
•Fuseholders(modelCPG.0-F).
Itcanbeconnectedtothebusbarandthemediumvoltagecablesrespectivelybymeansofcablebushingsatthetopandbottom.
Thegaspressureistestedbymeansofatemperature-compensatedpressuregauge,withapotential-freecontact,allowingittobeusedasaremotealarm.
Thebusbar compartment,locatedintheupperpartofthecubicle,isusedtohousethebusbar(electricalconnectionbetweenthemediumvoltagecubicles).*
eachoneofthephasesthatmakeupthebusbarhassolidandshieldedinsulation,earthedbymeansofthecompartment'sspecificearthingbar.Becauseofthissingle-phasearrangement,thecubicleoffersexcellentreliabilityintermsofservicecontinuity.
Theinstallationofaphasesegregationassemblyusingearthedmetalplatesallowstowithstandaninternalarcof25kA/1s.
Optionally,toroidal-corecurrenttransformersand/orplug-involtagetransformerscanbeinstalledinthiscompartment,withoutneedingmeteringcubicles.
Î *SeesectionCOnneCTIOnBeTWeenCuBICLeSonpage19.
A
BD
e
C
Busbarcompartment
FocusonMediumVoltage6
Gas insulated, simple busbar cubicle rangeUp to 24 kV / Up to 36 kV CPG System Medium Voltage Switchgear
Primary Distribution
Thecable compartment,whichallowsfrontalaccesstothemediumvoltagecables,islocatedinthelowerpartofthecubicleandhasacoverthatisinterlockedwiththeearthingcircuit.
Theexternalcone-typebushingsallowtheinstallationoftoroidal-corecurrenttransformersonthem.
Thiscompartmentcanbesuppliedreadytowithstandaninternalarcinterminalsof25kA/1s,incompliancewiththecriteriaofstandardIeC62271-200.
Thebasecanhousethefollowingcomponents:
•upto4reinforcedshieldedconnectionterminals(screw-in)perphase.
•Cabletieforthemediumvoltagecables
•earthingbars.
•Toroidal-corecurrenttransformers.
•Plug-involtagetransformers.
•Surgearresters.
Alltheelementsmakinguptheenclosureareearthedbymeansofaconductorconsistingofacopperbardesignedtowithstandtheratedshort-timecurrent,allowingtoinsertorextractmediumvoltagecableswiththeircorrespondingterminationswithouthavingtoremoveit.
Thecontrol compartment,locatedintheupperpartofthecubicleandindependentofthemediumvoltagearea,ispreparedforinstallingmeteringequipmentandprotectionrelays,andcontainstheterminalblockwiththecontrolsignalsproperlyidentified.
Theconnectionswiththeoperationinterfacearemadeviaconnectors,makingtheassemblymoreflexible,andallowingthecontrolcompartmenttobeassembledandconnectedonsiteinasimpledirectway.
Theoperation interface,locatedinthecentralpart,alsoincludesacustomisedmimicdiagramforeachtypeofcubicle,theaccessesformanualoperationofthedisconnectordrivingmechanism,circuit-breaker,springloading,indicationelements,etc.
SAFeTY
Internal arc
Inbothitsassemblyandinitsdifferentcompartments,theinstallationofdifferentelementsallowsthecubicletowithstandaninternalarcof25kA/1s,incompliancewiththe5criteriaofAnnexAofstandardIeC62271-200(classIAC-AFL).
Environmental resistance
Againstaggressiveenvironmentalagents(dust,pollution,humidity,salinity,etc.),protectionagainstindirectcontactandlongservicelifeprovidedbyitsgasinsulation,withthebreakingandmakingcomponentshousedinindependentstainlesssteeltanks,sealedforlife.
Controlcompartment
Cablecompartment
Operationinterface
FocusonMediumVoltage7
Gas insulated, single busbar cubicle rangeUp to 24 kV / Up to 36 kV
CPG SystemMedium Voltage Switchgear Primary Distribution
IP rating
IPratingofIP65forthetankandIP3Xforthecubicleassembly.
Monitoring
Monitoring compensatedby thegaspressure temperature inside thetank,includingpotential-freecontact.
Voltage presence/absence indicator
Permanentindication(multi-LeD)andoptionalcontactsforremoteindicationand/oruseofelectromagneticinterlocks.
Full insulation of the entire power circuit
Includingthecableterminations,allofwhichisshielded,earthedandinstalledinsideametalenclosure.
Ergonomic design
Safeaccesstothecontrolandindicationarea,locatedoutsidetheswitchcompartment.
Standard internal interlocks
Theypreventtheexecutionofincorrectoperations.Optionofadditionalinterlocks.
Safe and simple operation
QuALITYOFTHeeLeCTRICALSuPPLY
TheCPGsystemcontributestoimprovingtheelectricaldistributioninMediumVoltagenetworks:
•Routine testsperformedatthefactoryonallequipment.
•Sealed assembly:on-siteinstallationandassembly,withoutgasmanipulation.
•Circuit-breakerwithvacuumbreakingtechnology,compactandhighlyreliable,certifiedaccordingtostandardIeC62271-100,includingextendedelectricalendurance(classe2)withfastreclosingcycle,andthereforemaintenance-freeduringitsentireservicelife.
•Visual indication ofthepositionoftheswitchgearinthemimicdiagram.
•No maintenance ofthelivepartsofthecubicles,whichincreasestheavailabilityandcontinuityofservice.
•Easy and reliable connectionofthecontrolandindicationcircuits,usingconnectors.
•Loss of service continuity categoryaccordingtoIeC62271-200:LSC2B.
•Ormazabal'sprotection,meteringandcontrolelectronic units:ekorRPSandekorRPG.
Controlcompartment
Operationinterface
FocusonMediumVoltage8
Gas insulated, simple busbar cubicle rangeUp to 24 kV / Up to 36 kV CPG System Medium Voltage Switchgear
Primary Distribution
Types of cubicles
CPG.0-V Circuit-breakercubicle
CPG.0-F Fuseprotectioncubicle
CPG.0-S Disconnectorcubicle
CPG.0-C Busbarcouplingcubicle
CPG.0-RB Busbarrisecubicle
TeCHnICALCHARACTeRISTICS
Rated voltage Ur [kV] 24 36
Frequency fr [Hz] 50/60 50/60
Rated current
inbusbars Ir [A] upto2500 upto1250
outgoingline Ir [A] upto2500* upto1250*
Short-time power frequency withstand voltage (1 min)
betweenphasesandphase-to-earth Ud [kV] 50 70
isolatingdistance Ud [kV] 60 80
Lightning impulse withstand voltage
betweenphasesandphase-to-earth Up [kV] 125 170
isolatingdistance Up [kV] 145 195
Rated short-time withstand current Ik / tk [kA / 1 s - 3 s] 25 25
Rated peak value withstand current Ip [kA] 65 65
Rated short-circuit breaking capacity Isc [kA] 25 25
Rated short-circuit making capacity Ima [kA] 65 65
Internal arc classification IAC AFL25kA-1s AFL25kA-1s
IP rating IP3X IP3X
*Forfuseprotectioncubicle=200A
CPG.0-V 2500 A
FocusonMediumVoltage9
Gas insulated, single busbar cubicle rangeUp to 24 kV / Up to 36 kV
CPG SystemMedium Voltage Switchgear Primary Distribution
CPG.0-V
Circuit-breaker cubicle
Includesavacuumcircuit-breakerandathreepositiondisconnectorinserieswithit.Bothcomponentsarelocatedinsidetheswitchcompartment.
eLeCTRICALCHARACTeRISTICS
Rated voltage Ur [kV] 24 36
Rated busbar current Ir [A]1250/1600/2000/2500
1250
Rated outgoing line current Ir [A]630/1250/1600/2000/2500*
630/1250
Rated short-time withstand current Ik / tk [kA / 1 s - 3 s] 25 25
*Withforcedventilation
COnFIGuRATIOn
SF6 pressure gauge with potential-free contact YeS
Busbar
Currenttransformers Optional
Voltagetransformers Optional
Three-position disconnector
Motordrivingmechanism(disconnector) Optional
Interlocks** Optional
Vacuum circuit-breaker
Motordrivingmechanism YeS
Trippingcoil YeS
2ndtrippingcoil Optional
Closingcoil YeS
undervoltagecoil Optional
Opening/closingpush-buttonblocking YeS
Voltage presence detector YeS
Auxiliarycontact Optional
Cable compartment
Maximumno.ofcablesperphase 4
Toroidal-corecurrenttransformers Optional
Plug-involtagetransformers Optional
**Seesection“Interlocks”
Applications:
•Maintransformerprotection
•Feederprotection
•Busbarcouplingprotection
•Capacitorbankprotection
•Auxiliaryservicestransformerprotection
DIMenSIOnS
Cubicle 24 kV - 630 A 36 kV - 630 A 24/36 kV - 1250/1600 A 24 kV - 2000 A 24 kV - 2500 A
Control
compartmentLow High Low High Low High Low High
Width [mm] 600 600 800 1000
Depth [mm] 1365 1365 1545 1545
Height [mm] 2225 2425 2225 2425 2225 2425 2225 2425
Weight [kg] <300 <750 <1100 <1200
FocusonMediumVoltage10
Gas insulated, simple busbar cubicle rangeUp to 24 kV / Up to 36 kV CPG System Medium Voltage Switchgear
Primary Distribution
CPG.0-S
Disconnector cubicle
Includesathree-positiondisconnectorwithoutloadbreakingcapacity.
eLeCTRICALCHARACTeRISTICS
Rated voltage Ur [kV] 24 36
Rated busbar current Ir [A]1250/1600/2000/2500
1250
Rated outgoing line current Ir [A] 1250/1600 1250
Rated short-time withstand current Ik / tk [kA / 1 s - 3 s] 25 25
COnFIGuRATIOn
SF6 pressure gauge with potential-free contact YeS
Busbar
Currenttransformers Optional
Voltagetransformers Optional
Three-position disconnector
Motordrivingmechanism(disconnector) Optional
Interlocks* Optional
Voltage presence detector YeS
Auxiliarycontact Optional
Cable compartment
Maximumno.ofcablesperphase 4
Toroidal-corecurrenttransformers Optional
Plug-involtagetransformers Optional
*Seesection“Interlocks”.
DIMenSIOnS
Cubicle 24 kV / 36 kV
Control
compartmentLow High
Width [mm] 600
Depth [mm] 1365
Height [mm] 2225 2425
Weight [kg] <550
Applications:
•Feeder/transformerdisconnection.
•Busbarcouplingrise.
•Busbarvoltagemetering.
FocusonMediumVoltage11
Gas insulated, single busbar cubicle rangeUp to 24 kV / Up to 36 kV
CPG SystemMedium Voltage Switchgear Primary Distribution
CPG.0-F
Fuse protection cubicle
Ithasathree-positionswitch-disconnector(closed/open/earthing),includingfuseprotection.Thefusesarehousedinsealedfuseholders,whichinturnareinsidetheswitchcompartment,reinforcingthelevelofinsulation.
Thethree-poleopeningswitchwithcombinedactuationbyfuseblowisoptionallymotorisable.
eLeCTRICALCHARACTeRISTICS
Rated voltage Ur [kV] 24 36
Rated busbar current Ir [A]1250/1600/2000/2500
1250
Rated outgoing line current Ir [A] 200 200
Rated short-time withstand current Ik / tk [kA / 1 s - 3 s] 25 25
Rated short-circuit breaking current (switch-fuse combination)
[kA] 25 25
Transfer current Itransfer [A] >800 >800
COnFIGuRATIOn
SF6 pressure gauge with potential-free contact YeS
Busbar
Currenttransformers Optional
Voltagetransformers Optional
Three-position disconnector
Motordrivingmechanism(disconnector) Optional
Interlocks* Optional
Fuses combined with the switch-disconnector YeS
Voltage presence detector YeS
Auxiliarycontact Optional
*Seesection“Interlocks”.Applications:
•Auxiliaryservicestransformerprotection.
DIMenSIOnS
Cubicle 24 kV / 36 kV
Control
compartmentLow High
Width [mm] 600
Depth [mm] 1403
Height [mm] 2225 2425
Weight [kg] <550
FocusonMediumVoltage12
Gas insulated, simple busbar cubicle rangeUp to 24 kV / Up to 36 kV CPG System Medium Voltage Switchgear
Primary Distribution
CPG.0-C
Busbar coupling cubicle
Itincludesavacuumcircuit-breakerwithtwothree-positiondisconnectorsinserieswithit,oneupstreamandtheotherdownstreamfromthecircuit-breaker.
Theseelementsarelocatedinsidetheswitchcompartments.
eLeCTRICALCHARACTeRISTICS
Rated voltage Ur [kV] 24 36
Rated busbar current Ir [A]1250/1600/2000/2500
1250
Rated outgoing line current Ir [A]1250/1600/2000/2500
1250
Rated short-time withstand current Ik / tk [kA / 1 s - 3 s] 25 25
COnFIGuRATIOnSF6 pressure gauge with potential-free contact YeS
Busbar
Currenttransformers Optional
Voltagetransformers Optional
Three-position disconnector
Motordrivingmechanism(disconnector) Optional
Interlocks* Optional
Vacuum circuit-breaker
Motordrivingmechanism YeS
Trippingcoil YeS
2ndtrippingcoil Optional
Closingcoil YeS
undervoltagecoil Optional
Opening/closingpush-buttonblocking YeS
Cable compartment
Lowerbusbar YeS
Toroidal-corecurrenttransformers Optional
*Seesection“Interlocks”.
Applications:
•Longitudinalbusbarcoupling
DIMenSIOnS
Cubicle 24/36 kV - 1250/1600 A 24 kV - 2000 A 24 kV - 2500 A
Control
compartmentLow High Low High Low High
Width [mm] 1200 1600 2000
Depth [mm] 1365 1545 1545
Height [mm] 2225 2425 2225 2425 2225 2425
Weight [kg] <1300 <2200 <2400
FocusonMediumVoltage13
Gas insulated, single busbar cubicle rangeUp to 24 kV / Up to 36 kV
CPG SystemMedium Voltage Switchgear Primary Distribution
CPG.0-RB
Busbar rise cubicle
Allowsthelateralcablefeederincomingoroutgoingforcommunicationwiththebusbarofthegeneralcubicleassemblyanditsearthing.
eLeCTRICALCHARACTeRISTICS
Rated voltage Ur [kV] 24 36
Rated busbar current Ir [A] 1250/1600 1250
Rated outgoing line current Ir [A] 1250 1250
Rated short-time withstand current Ik / tk [kA / 1 s - 3 s] 25 25
COnFIGuRATIOnSF6 pressure gauge with potential-free contact YeS
Busbar
Currenttransformers Optional
Voltagetransformers Optional
Cable compartment
Lowerbusbar YeS
Toroidal-corecurrenttransformers Optional
*Seesection“Interlocks”.
Applications:
•Busbarlateralfeeder.
DIMenSIOnS
Cubicle 24 kV / 36 kV
Control
compartmentLow High
Width [mm] 600
Depth [mm] 1400
Height [mm] 2225 2425
Weight [kg] <500
FocusonMediumVoltage14
Gas insulated, simple busbar cubicle rangeUp to 24 kV / Up to 36 kV CPG System Medium Voltage Switchgear
Primary Distribution
Main functional elements
SAFeOPeRATIOn
DISCOnneCTORAnDeARTHInGSWITCH
24/36 kV
Disconnector
Mechanicalendurance M0(1000operations)
Earthing switch
Short-circuitmakingcapacity [kA] 63(50Hz)/65(60Hz)
Electrical endurance e2*
Rated current [A]630/1250/1600**/2000**/2500**
Rated short-time withstand current [kA / 1 s - 3 s]
25
*Theearthingswitchdoesnothavemakingcapacitybyitself,asthisistransferredtothecircuit-breaker.Theelectricalenduranceofthecompleteearthingcircuitise2(5short-circuitmakingoperations).**Validupto24kV.
Characteristics:
•3positions(connection-disconnection-earthing)
• Independentactuationandleversfortheoperations:•Connection-disconnection(motordrivingmechanismoption)•Disconnection-earthing(motordrivingmechanismoption)
CIRCuIT-BReAKeR
24 kV 36 kV
Breaking capacity
Short-circuit(asymmetry) [kA] 25
DC 34% 38%
no-loadcable-chargingbreakingcapacity [A] 31.5 50
Capacitorbankbreakingcapacity [A] 400
Electrical endurance e2
Reclosing sequence O-0.3”-CO-15”-CO
Mechanical endurance M2(10000operations)
Rated current [A]630/
1250/1600/2000/2500
630/1250
Rated short-time withstand current [kA / 1 s - 3 s]
25
Opening time [kA] <45ms
Characteristics:
•Vacuumbreaking• Manualoperationthroughpush-button(lockablewithapadlock)
•Motordrivingmechanism• Springloadingtime<15seconds
• Operatingcoils:• 1shunttripopeningcoil.2ndoptionalcoil.• 1closingcoil• 1undervoltagecoil(optional)
FocusonMediumVoltage15
Gas insulated, single busbar cubicle rangeUp to 24 kV / Up to 36 kV
CPG SystemMedium Voltage Switchgear Primary Distribution
SWITCH-DISCOnneCTOR(combinedwithfuses)
24/36 kV
Switch
Ratedcurrent [A] 200
Mainswitchmakingcapacity [kA] 63
electricalendurance e3
Ciclesofoperations(activecurrent) 100
Ciclesofoperations(Short-circuitmakingcurrent) 5
Mechanicalendurance(manual) M1(1000)
Earthing switch
Short-circuitmakingcapacity [kA] 7.5
electricalendurance e2
Short-circuitmakingoperations 5
Ratedshort-timewithstandcurrent*
[kA / 1 s - 3 s]
25
[kA / 3 s] 3(earthing)
Rated short-circuit breaking current (switch-fuse combination) [kA] 25
*Fuselimitation.
Characteristics:
•3positions(connection-disconnection-earthing)
• Independentactuationandleversfortheoperations:• Connection-disconnection• Disconnection-earthing
•Switchdrivingmechanism:• Manualwithretention(BR)withtrippingcoil•Option:switch-disconnectormotorisation
Î Note: for other values, please consult Ormazabal's Technical-Commercial Department
FocusonMediumVoltage16
Gas insulated, simple busbar cubicle rangeUp to 24 kV / Up to 36 kV CPG System Medium Voltage Switchgear
Primary Distribution
ekorSYSFAMILY
ThisfamilygroupsaseriesofunitsthatintegratedintheCPG.0cubiclesprovideprotection,metering,controlandindicationintheMediumVoltageelectricaldistributionnetworks:
ekorRPS
SubstationProtectionunitdesignedspecificallytocovertheapplicationsrequiredinthePrimaryDistributionsector.ItsimplementationinCPG.0cubiclesgivesthemthenecessarycharacteristicsforbeingincludedinIntegratedControlsystems.
FeATuReSOFTHeekorRPSunIT
Protection Control
Overcurrent 50n/51n-50n/51n Switchstatusandcontrol Oscillograph
Sensitiveneutral 50ns/51ns Disconnectorstatusandcontrol Chronology
Directionalovercurrent 67n/67n Switchmonitoring Self-monitoring
Overvoltage 59 Localpanel Coldload
Minimumvoltage 27 eventlog Impedance/faultdistance
Frequency 81 Faultreport Automation
Imbalance 46-47 Communications
Reclosing 79 IeC870-5-103 DnP3.0.
Metering IeC870-5-101 PROCOMe
30electricalparameters:voltage,current,power,energy,etc. ModBusRTu
ekorRPG
General Protectionunit designed forovercurrentprotection in electricalinstallationswithConventionalControl.Itisdesignedspecificallytoprotectawiderangeofpowers.
FeATuReSOFTHeekorRPGunIT
Protection Control
Overcurrent 50n/51n-50n/51n Switchmonitoring
Sensitiveneutral 50ns/51ns Fault report
Reclosing 79n Self-monitoring
Overvoltage 59 Communications
Frequency 81 ModBusRTuPROCOMe
Imbalance 46-47
Reclosing 79
ekorIVDS
eachcubiclehasavoltagepresence/absencedetectorwithpermanentlightindicationandanoptionalfreeauxiliarycontactforremotedisplayofthecorrespondingindication.
The indicator, with fixed installation, has been designed according tostandardIeC61243-5andVDe0682Part415.
FocusonMediumVoltage17
Gas insulated, single busbar cubicle rangeUp to 24 kV / Up to 36 kV
CPG SystemMedium Voltage Switchgear Primary Distribution
AuXILIARYeLeMenTS
Current transformers
TransformersdesignedbyOrmazabalwhosemaincharacteristicsare:
•Toroidaltype•encapsulated• Installedoutsidetheswitchcompartment,upstreamofthemediumvoltageconnectors
•Protectedagainstenvironmentalconditions•Simpleassemblyandfreeoferrorsduringinstallation(earths)
Installation:•Busbarcompartmentand/orcablecompartment
eLeCTRICALCHARACTeRISTICS
Insulationlevel 0.72kV
Ratedwithstandalternatingvoltage 3kV/1min
Ratedfrequency 50Hz/60Hz
Permanentthermalcurrent 1.2IrAccuracyclass e
RATIO MeTeRInG PROTeCTIOn
Primary Secondary
150A*200A250A300A*400A500A600A*
800A1000A1200A1600A2000A2500A
1A5A
CL0.2CL0.5
5P105P20
*Preferredratios.note:Burdenaccordingtotheratios.
Voltage transformers
Characteristics:•Plug-intype•Single-phase• Insulated•Shieled• Inductiveoperation• Installedoutsidetheswitchcompartment•Protectedagainstenvironmentalconditions•Anti-explosive
Installation:•Busbarcompartmentand/orcablecompartment
eLeCTRICALCHARACTeRISTICS
Ratedvoltage 3.6-36kV
Continuousvoltagefactor 1.2ur
Ratedvoltagefactorur/8h 1.9Hz
Voltageinsecondary100/√3V-110/√3V100/3V-110/3V
Burden 25-50VA
Accuracyclass0.2-0.5-1(metering)3P-6P(protection)
note:Characteristicsconfigurabledependingontypeofinstallation
FocusonMediumVoltage18
Gas insulated, simple busbar cubicle rangeUp to 24 kV / Up to 36 kV CPG System Medium Voltage Switchgear
Primary Distribution
PROTeCTIOn
Interlocks
•Thedisconnector,circuit-breakerandearthingswitchareinterlockedinaccordancewiththecriteriadefinedinsection5.11ofstandardIeC62271-200.
•Thedisconnectorlevercanonlybeinsertedifthecircuit-breakerisinopenposition.
•Operationonthecircuit-breakerisonlypossibleifthedisconnector/earthingswitchoperationleverhasbeenremoved.Also,allelectricaloperationsareoverriddenifthedisconnectorleverisintheactuationshaft.
•Thecircuit-breakercanonlybeconnectedintheendpositionsofthedisconnector/earthingswitch.
• Intheeffectiveearthingpositiontheelectricalopeningcommandsofthecircuit-breakerareoverridden.
•Theaccesstothefusecompartmentisinterlockedwiththeearthingswitch.
•Thecablecompartmentisonlyaccessiblewiththeearthingswitchinclosedposition.
•Optionally:
• electromagneticinterlockoftheearthingswitch.
• Lockingwithinterlocks:-earthingswitchinclosedposition
-earthingswitchinopenposition
-Disconnectorinopenposition
Installation
CHARACTeRISTICS
•Reduceddimensionsandminimumspacerequiredforitslocation,duetoitscarefuldesignanduseofSF6gasasinsulatingmedium.
•Modularityandextensibilityonbothsides,allowingafastandeconomicinstallationprocess,inreducedspaceandwithoutusinggasonsite,nothavingtomoveadjacentcubiclestoremoveacentralcubicle.
•Reductionofthecubicleroomdimension,duetoitsfrontalaccessanddesignwithoutremovableswitchgear,andnotrequiringarearaccessspace.
•Optimisationofinstallationandcivilworkcostsduetoitsreduceddimensionsandlittleneedofoperationspace.
•Simplehousingofvoltagetransformersandtoroidalcurrenttransformers.
FocusonMediumVoltage19
Gas insulated, single busbar cubicle rangeUp to 24 kV / Up to 36 kV
CPG SystemMedium Voltage Switchgear Primary Distribution
CIVILWORK
Theminimumdistances[mm]recommendedforacorrectinstallation,onceplacedintheirfinallocation,are:
Î * Not required with pressure relief duct.Î ** According to Annex A of standard IEC 62271-220Î For other dimensions, please consult Ormazabal's Technical-
Commercial Department.
COnneCTIOnBeTWeenCuBICLeS
Theconnectionbetweencubiclesisexternaltotheswitchcompartmentandismadewithbusbarswithsolidandshieldedinsulation,designedtoallowuninstallingafunctionalunitwithouthavingtomovetheadjacentunitsandwithout gas manipulation.
Thecopperbusbarsarepreparedtowithstandthermalanddynamicforcesofratedshort-timecurrents(25kA/1or3s)andratedcontinuouscurrents,the2typesofexistingbusbarsare:
•Option1:busbarsupto1600A/24kVorupto1250A/36kV
•Option2:busbarsupto2000Aand2500A/24kV
Î In the version up to 24 kV, the two busbar options are incompatible between each other.
Products, applications, solutions:
• Primarydistributionswitchgear
• Secondarydistributionswitchgear
• Automation,protection,remotecontrolandcommunicationsinelectricalnetworks
• Distributiontransformers
• LowVoltageboards
• Transformersubstations