corrosion of buried lpg pipe work... an agency of the health and safety executive an agency of the...

35
www.hsl.gov.uk www.hsl.gov.uk An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried LPG pipe work By Louise Robinson, BEng, ProfgradIMMM Email: [email protected]

Upload: others

Post on 18-Apr-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

www.hsl.gov.ukAn Agency of the Health and Safety Executive

www.hsl.gov.ukAn Agency of the Health and Safety Executive

Industrial and domestic installations

Corrosion of buried LPG pipe work By Louise Robinson, BEng, ProfgradIMMM

Email: [email protected]

Page 2: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

Main points

• About LPG• Explosions from fractured mains• Industrial installation – ICL Plastics Explosion• Domestic installation – house explosion• Calor Survey• Typical installations• Metallic and non-metallic pipe work• Fittings• Mechanisms of deterioration• Corrosion risk factors• Duty of care

Page 3: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

About LPG• Primarily supplied as propane, butane or a

mixture of the two• Heavier than air so can settle and accumulate

in low spots such as basements• Can cause a suffocation hazard as well as fire

and explosion hazard• Pressures typically low (<75 mbar) or medium

(75 mbar - 2 bar)

Page 4: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

Explosions from fractured mains

• 1999 Larkhall, Scotland –– residential property destroyed, 3 fatalities– Ductile cast iron main leaking– plug corrosion

• 2001 Cavendish Mill, Oldham– old cotton mill converted to apartments, 1

fatality– 14” grey cast iron main found to be leaking– Fissure corrosion-crack due to bending

moment on pipe and wet corrosive soil

Page 5: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

ICL Plastics

Page 6: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

ICL Plastics

Page 7: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

ICL Plastics

GAS PIPELINE

BASEMENT WALL

INTERIOR EXTERIOR

CONCRETE SLAB

Poorly consolidated soil

Rubble and voids

Page 8: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

ICL Plastics

Page 9: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

ICL Plastics

Bridge of corrosion products across opening

Mirror placed underneath bend

Page 10: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

Width of opening 1.5mm minimum

Approx. 50

ICL Plastics

Page 11: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

ICL Plastics

Outline of threaded end of pipe

Outer surface of bend – soil side

Inner surface of bend – LPG side

Main opening

Second opening

Six impressions from Vickers

hardness testing

Page 12: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

ICL Plastics

Widest point of opening

Bright reflective fracture

Fracture through wall of bend

Original surface of thread

Brown/orange fracture

~29%

~71%

Page 13: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

ICL Plastics

Page 14: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

Findings• Failure at the bend had characteristics of two

forms of environmentally assisted cracking: fissure or graphitic corrosion and corrosion fatigue

• Downwards force was due to concrete slabs in contact with the bend, and possible periodic higher loads caused by vehicle movements

• Corrosion at the bend as a result of direct contact of the uncoated malleable cast iron with aggressive soil

• The remainder of the pipe was very corroded with significant thinning

Page 15: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

Domestic pipework

Page 16: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

Radiography of domestic pipework

Page 17: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

Calor survey

Page 18: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

Calor survey

Page 19: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

Calor survey

Page 20: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

Typical installation

Page 21: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

Typical installation

Page 22: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

Typical installation

Page 23: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

• Carbon steelUsually rolled strip, formed into a tube and continuously welded. Plain (red oxide primer or black lacquer) or galvanised.

• BS 1387 : three weights – light, medium and heavy. Medium and heavy are most commonly used.

• Commonly used for mains gas and lpg

Steel pipe for buried gas services

Page 24: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

4.003.202.60251

3.202.602.30203/4

Wall thickness, in mm Light Medium Heavy

Nominal size, in mm

* NB Galvanising produces a zinc layer 0.05mm to 0.1mm thick.

Steel pipe for buried gas services

Page 25: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

Steel pipe – plain and coated

Page 26: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

Steel pipe connections

• Usually malleable cast iron to BS1256• Female parallel threads / male taper

threads• Similar wall thickness to pipe

Page 27: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

• GIS/PL2-2:2008- Specification forPolyethylene pipes and fittings for natural gas and suitable manufactured gasPart 2: Pipes for use at pressures up to 5.5 bar

• PE80 or possibly PE100

• OD 16mm, 20mm, or 25mm with 2.5mm thick wall

PE pipe for gas services

Page 28: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

• Anode and cathode can be some distance apart.

• Movement of electrons, ions and molecules between the two.

Corrosion basics

Fe+ ions OH- ions

electronsAnode Cathode

Oxygen

Page 29: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

• Corrosion of steel and cast iron in soil normally needs oxygen and moisture.

• Other key factors are:Soil type (gravel, sand, loam, clay, peat)pH, chloride and sulphateOrganic matter

Corrosion of ferrous pipes in soil

Page 30: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

Typical corrosion rates

• Average rates for uniform corrosion would range from 0.01mm/year to 0.1mm/year.

• Corrosion is not usually uniform, most leaks will result from pitting.

• Pitting rates can be several times higher than uniform rates.

• Worst case pitting could perforate steel pipe with a wall thickness of 3.2mm in 10 years to 20 years.

Page 31: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

• Type of ground• Moisture content and variations• Air – soil interface and depth of soil cover• Temperature• Protective coating• Electric currents

Corrosion risk factors

Page 32: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

Buried metallic lpg pipes –what to look out for (1)

• Age

• Pipe material and current condition

• Protective coating and condition

• Cathodic protection

Page 33: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

Stages of deterioration

Page 34: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

• Externally applied loading • Knowledge of pipe route and ground type• Position / layout relative to surface water• Depth of pipe

Buried metallic lpg pipes –what to look out for (2)

Page 35: Corrosion of buried LPG pipe work... An Agency of the Health and Safety Executive An Agency of the Health and Safety Executive Industrial and domestic installations Corrosion of buried

An Agency of the Health and Safety Executive

Duty of care• Issues arising from survey – who owns

the pipes? – Industrial: LPG supplier owns the tank,

pipework and valves usually responsibility of the company, even if installed by supplier.

– Domestic: LPG supplier has responsibility for tank and pipe up to valve at the property.

BUT- differs according to contracthttp://www.hse.gov.uk/gas/lpg/index.htmhttp://www.hse.gov.uk/pubns/indg428.pdf