CORRinSiTE™ Corrosion MonitorAGF’s CORRinSITE™ Corrosion Monitors provide an inexpensive method to detect inner pipe corrosion in wet and dry fire sprinkler systems. CORRinSITE™ Corrosion Monitors are designed to monitor actual wall loss under normal operating conditions because they install directly into the piping system and not into an isolated loop.
Under normal conditions the CORRinSITE™ viewing window is white. Should wall loss occur past 0.040” the sight glass will display a bright orange color signifying a corrosive condition.
FeaturesLow Cost•
Easy Installation and Maintenance•
Continuous Monitoring•
Easy-to-Read Visual Notification•
No Power Needed•
Direct Installation in to the System•
For Black and Galvanized Pipe•
Specifications
Service Pressure .............. 300 PSI
Operating Temp ............... -40° to 200° F
Material ............................ Mild Carbon Steel
Wear Dimension .............. 0.040”
Corrosion MonitorWWW.CORRINSITE.COM
SS-CORRinSITE · 6/18
Reliability, Versatility, Code Compatibility
Corrosion Monitor1.
Mechanical Tee Configuration2.
Inline Pipe Configuration3.
Configuration Sizes
2” 2½” 3” 4” 6” 8”
1
2
3
Custom Label Option
![Page 2: Corrosion Monitor - content.agfmfg.com](https://reader031.vdocuments.us/reader031/viewer/2022012019/61687ef1d394e9041f6ff1d8/html5/thumbnails/2.jpg)
Floor Control
Wet SystemOffice Building
Dry SystemParking Garage
Branch Line
End of Line
Water Main
0.040” Corrosion Limit1.
Hollow Chamber2.
Job Name:__________________________________
Architect: ___________________________________
Engineer: ___________________________________
Contractor: _________________________________
Patent Pending
AGF Manufacturing Inc.100 Quaker Lane, Malvern, PA 19355
Phone: 610-240-4900 Fax: 610-240-4906www.agfmanufacturing.com
CORRinSiTE™ Corrosion Monitor
The CORRinSITE™ Corrosion Monitor can be installed virtually anywhere on a wet or dry fire system. AGF recommends near water mains, at the end of branch lines, or in areas where corrosion has been a problem. When installing horizontally on a wet system, the monitor’s sight glass should be facing up (dark blue area), and on a dry system the sight glass should face down (light blue area).
1