Raszczuk and Karolak Herit Sci (2021) 9:43 https://doi.org/10.1186/s40494-021-00516-1 RESEARCH ARTICLE Correlation between the cracking pattern of historical structure and soil properties: the case of the church in Kożuchów Krzysztof Raszczuk and Anna Karolak * Abstract The paper presents a diagnosis of damage to heritage structures based on the case of the historic church in Kożuchów. The Church of the Purification of the Blessed Virgin Mary dates back to the thirteenth century and is an important sacral building in south-west Poland. Renovation and strengthening works have been conducted in recent years with the goal of structurally stabilizing the heritage building. The paper includes a short history of the building, as well as a review of contemporary diagnostic methods used in heritage buildings with emphasis on the methods used in the diagnosis of the discussed object. Correct diagnosis of the heritage building is the key to selecting an optimal design solution for supporting and strengthening the building structure. Pre-design analysis was based on a geotechnical assessment of ground conditions, identifying cracking patterns of walls and vaults, preparing a digital model using Heritage—Building Information Modeling technology and performing structural analysis. The main cause of cracking of the walls and vaults of the church is related to uneven subsidence and localized stability loss of the building’s foundations, resulting from differentiated soil and water conditions beneath the building. Based on the research and analysis, final conclusions and proposals for strengthening the structure were presented, including jet- grouting columns, tie rods and Fibre Reinforced Cementitious Matrix systems. Keywords: Historical buildings, Diagnosis of historical structures, Diagnostic methods, Cracking pattern analysis, Geotechnical investigation, Strengthening © The Author(s) 2021. This article is licensed under a Creative Commons Attribution 4.0 International License, which permits use, sharing, adaptation, distribution and reproduction in any medium or format, as long as you give appropriate credit to the original author(s) and the source, provide a link to the Creative Commons licence, and indicate if changes were made. The images or other third party material in this article are included in the article’s Creative Commons licence, unless indicated otherwise in a credit line to the material. If material is not included in the article’s Creative Commons licence and your intended use is not permitted by statutory regulation or exceeds the permitted use, you will need to obtain permission directly from the copyright holder. To view a copy of this licence, visit http://creativeco mmons.org/licenses/by/4.0/. The Creative Commons Public Domain Dedication waiver (http://creativecommons.org/publicdomain/ zero/1.0/) applies to the data made available in this article, unless otherwise stated in a credit line to the data. Introduction Various causes of damage of heritage buildings Historical structures are important elements of culture and a source of knowledge for shaping social conscious- ness. Increased degradation of heritage buildings, which has been observed in recent years, demands develop- ment of effective diagnostic methods as a basis for select- ing the most appropriate conservation interventions to strengthen the historical structures. Problems relating to securing stability of historical structures are of growing interest to researchers and engineers (i.a. in [1]). Heritage buildings were built dozens or hundreds of years ago. ey were built over long periods of time. Over the years, they experienced damage and breakdown, and were as a result subjected to repairs. ese interventions impacted also the static status of the structure, often cur- tailing degradation processes. But at the same time, this prevented a return to the original state of the structure in later years. Where documentation is incomplete, which is very common with historical structures, restoration to the original state is difficult and most often impossible. In addition, documented historical structures are charac- terized by high material heterogeneity [1, 2]. In conse- quence, determining mechanical parameters in different places may be difficult. is relates to, for example the foundations. For this reason, every historical building Open Access *Correspondence: [email protected] Faculty of Civil Engineering, Wroclaw University of Science and Technology, Wybrzeże Wyspiańskiego 27, 50-370 Wrocław, Poland

Upload: others

Post on 04-Jun-2022

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Correlation between the cracking pattern of historical

Raszczuk and Karolak Herit Sci (2021) 9:43 https://doi.org/10.1186/s40494-021-00516-1

RESEARCH ARTICLE

Correlation between the cracking pattern of historical structure and soil properties: the case of the church in KożuchówKrzysztof Raszczuk and Anna Karolak*

Abstract

The paper presents a diagnosis of damage to heritage structures based on the case of the historic church in Kożuchów. The Church of the Purification of the Blessed Virgin Mary dates back to the thirteenth century and is an important sacral building in south-west Poland. Renovation and strengthening works have been conducted in recent years with the goal of structurally stabilizing the heritage building. The paper includes a short history of the building, as well as a review of contemporary diagnostic methods used in heritage buildings with emphasis on the methods used in the diagnosis of the discussed object. Correct diagnosis of the heritage building is the key to selecting an optimal design solution for supporting and strengthening the building structure. Pre-design analysis was based on a geotechnical assessment of ground conditions, identifying cracking patterns of walls and vaults, preparing a digital model using Heritage—Building Information Modeling technology and performing structural analysis. The main cause of cracking of the walls and vaults of the church is related to uneven subsidence and localized stability loss of the building’s foundations, resulting from differentiated soil and water conditions beneath the building. Based on the research and analysis, final conclusions and proposals for strengthening the structure were presented, including jet-grouting columns, tie rods and Fibre Reinforced Cementitious Matrix systems.

Keywords: Historical buildings, Diagnosis of historical structures, Diagnostic methods, Cracking pattern analysis, Geotechnical investigation, Strengthening

© The Author(s) 2021. This article is licensed under a Creative Commons Attribution 4.0 International License, which permits use, sharing, adaptation, distribution and reproduction in any medium or format, as long as you give appropriate credit to the original author(s) and the source, provide a link to the Creative Commons licence, and indicate if changes were made. The images or other third party material in this article are included in the article’s Creative Commons licence, unless indicated otherwise in a credit line to the material. If material is not included in the article’s Creative Commons licence and your intended use is not permitted by statutory regulation or exceeds the permitted use, you will need to obtain permission directly from the copyright holder. To view a copy of this licence, visit http:// creat iveco mmons. org/ licen ses/ by/4. 0/. The Creative Commons Public Domain Dedication waiver (http:// creat iveco mmons. org/ publi cdoma in/ zero/1. 0/) applies to the data made available in this article, unless otherwise stated in a credit line to the data.

IntroductionVarious causes of damage of heritage buildingsHistorical structures are important elements of culture and a source of knowledge for shaping social conscious-ness. Increased degradation of heritage buildings, which has been observed in recent years, demands develop-ment of effective diagnostic methods as a basis for select-ing the most appropriate conservation interventions to strengthen the historical structures. Problems relating to securing stability of historical structures are of growing interest to researchers and engineers (i.a. in [1]).

Heritage buildings were built dozens or hundreds of years ago. They were built over long periods of time. Over the years, they experienced damage and breakdown, and were as a result subjected to repairs. These interventions impacted also the static status of the structure, often cur-tailing degradation processes. But at the same time, this prevented a return to the original state of the structure in later years.

Where documentation is incomplete, which is very common with historical structures, restoration to the original state is difficult and most often impossible. In addition, documented historical structures are charac-terized by high material heterogeneity [1, 2]. In conse-quence, determining mechanical parameters in different places may be difficult. This relates to, for example the foundations. For this reason, every historical building

Open Access

*Correspondence: [email protected] of Civil Engineering, Wroclaw University of Science and Technology, Wybrzeże Wyspiańskiego 27, 50-370 Wrocław, Poland

Page 2: Correlation between the cracking pattern of historical

Page 2 of 16Raszczuk and Karolak Herit Sci (2021) 9:43

requires its own individualized methodology for diag-nosis and selection of interventions [3]. Despite this, the recognizing of the common features relating to identify-ing the causes of damage and the most significant threats is possible. The main causes of damage and significant threats faced by historical structures are as follows:

• subsidence of the ground substrate (e.g. in the case of the Leaning Tower in Pisa [4], the cathedral in Mex-ico City [5], or the Church of St. John in Gdansk [6]),

• errors in design and implementation of construction solutions during the building process (e.g. expansion of the Church of St. John in Gdansk involved plac-ing the building on foundations designed for a much smaller structure [6]),

• additional, unforeseen loading (incl. fires, explosions, seismic movements etc.),

• reduction of material strength resulting from deg-radation caused by external environmental condi-tions (e.g. impact of water, wind, frost, temperature changes, pollution etc.).

All of these causes may affect the technical state of structural elements or entire building structures of his-torical objects. Consequently, they can lead to a dan-gerous threat to the safety of the structure, what is even more adverse as the issue often refers to historic build-ings that should be protected by all means. This paper focus on the correlation between cracking pattern on masonry structure and heterogenous soil conditions.

Geometrical survey and H‑BIM modeling as a basis for diagnostic activitiesRapid development and proliferation of new diagnos-tic technologies for historical buildings means that they can be applied in building maintenance and use, as well as during design and implementation of conservation

interventions. Diagnostics based on modern meth-ods allows for material identification and restoration of the internal structure of individual elements, which is extremely important when documentation is lacking for existing structures. Based on diagnostic test results, it may be possible to plan appropriately and carry out con-servation and strengthening interventions in historical buildings [7].

Non-destructive testing methods are the most impor-tant among the available modern diagnostic methods for historic buildings [2, 3], due to the fact that they offer the maximum protection of the historic substance result-ing from their character. The most commonly used test-ing methods include: visual assessment [8], geotechnical investigations [5, 6, 9], geometrical survey and H-BIM [10–16], core sampling [17, 18], ultrasound testing [19–24], geo-radar (GPR) testing [25–30], operational modal analysis (OMA) [31–34]. One of the most important phases in the diagnostic process is the selection of the appropriate methods for investigation including pros and cons for each of them.

A listing of the testing methods used in case of church Kożuchów with characteristic, advantages and disadvan-tages is presented in Table 1.

Due to the complex nature of non-destructive test-ing like core sampling, GPR scanning, ultrasonic inves-tigations and difficulties in interpreting the resulting data, these tests may sometimes result in unsatisfactory results. This may be the result of applying an incorrect test method or a lack of precision. Visual assessment appears to be one of the easiest methods to apply. The conclusion is that the best results can be obtained by applying several methods, allowing for verification of results. Modern monitoring systems combined with advanced computer analysis have been deployed in many important historic buildings, including St. Mark’s Basil-ica in Venice [35], city cathedrals in Florence [36], Padua

Table 1 Diagnostic methods used in the case study

Method Method characteristics Advantages/disadvantages

Visual assessment Assessment of external surfaces and cracking patterns + Low cost+ Does not require specialized equipment− Results are qualitative

Geotechnical investigations Geological cores + Assessment of differentiated subsidence rates of building foundations

− High costs, especially with respect to deep bore holes

Geometrical survey including H-BIM Interactive model built by the use of the historical architectural and construction documentation, photogrammetric techniques, laser scanning, and other data obtained from the physical analysis of the building

+ The possibility to understand, analyze, document, advertise and virtually reconstruct the whole structure

+ Enables also energy simulations, time, and cost calculations, and other functions that may improve the way to manage the maintenance and restoration processes

− Complex and time consuming method

Page 3: Correlation between the cracking pattern of historical

Page 3 of 16Raszczuk and Karolak Herit Sci (2021) 9:43

and Mexico [37], and towers [38]. In turn, in the case of e.g. the Milan Cathedral, the dynamic assessment was applied [33]. Proper assessment and identification of the problem allows for diagnostics and appropriate interven-tion. Currently, the problem of damage diagnosis is often treated too generally. Researchers and designers use inte-grated methods to assess the safety or hazard status of a structure, especially when it comes to historically sig-nificant buildings [39–43]. When visual assessment sug-gests that the cause of damage to a structure (cracks) is in the ground substrate, the case may require to carry out geotechnical tests to verify the foundation conditions of the building. The H-BIM (Heritage BIM) is an inno-vative concept, increasingly applied by researchers and engineers in the recent years [10]. It consists in creating a three-dimensional model of an existing historical or his-toric object in an appropriate degree of detail. The model applies not only to architecture, but also to the building structure. H-BIM is a complex method allowing to obtain a detailed building and structure models with its history documented In principle, in the first step, the H-BIM library is created by the use of technologies laser scan-ning, photogrammetry, and other data obtained from the physical analysis and historical architectural documen-tation and manuscripts [14]. Particularly, the use of his-torical data for modelling the H-BIM library components introduces the possibility to elaborate the details stored behind the surface of the parametric objects, in regard to their material, structural elements, historical or cultural characteristics and also conservation status and mainte-nance program [15, 16]. What it more, is the opportu-nity to enter temporal parametric data that represent the incidents occurring through the life cycle of the building [44]. In the third step, that is parametric modeling in 3-D, the integrated point cloud is segmented, according to the rules and historical patterns, in order to identify objects to be modeled. What is worth emphasizing, is the fact that thanks to H-BIM, it is possible, not only to conduct the complex analysis of the heritage structure, but also to understand issues related to materials and construction techniques, as well as to help in the conservation, man-agement, renovation or reconstruction processes of her-itage buildings, including those that no longer exist or are not well documented [10].

Cracking of masonry structure in relation to soil propertiesCracking of walls is often a consequence of uneven ground subsidence (differential soil settlement) [45], especially when there are heterogeneous soil conditions. Uneven soil subsidence results in uneven settlement of building foundations. The most common causes of sub-sidence are [46]:

• ground movements caused by differing soil structure underneath the building foundations and by differing physical and mechanical soil parameters,

• building structures on ground of low load bearing character, e.g. clay or organic,

• inadequate compaction (or lack of it) of soil during the construction work or faulty foundation work,

• decrease of groundwater level, causing in conse-quence changes in the volume and strength of the supporting ground substrate,

• changes in environmental conditions, changes in humidity caused by cyclical weather conditions (rain, frost, drought, etc.), causing changes in soil structure and its mechanical properties,

• growing vegetation drawing water from the ground and natural soil degradation processes,

• vibrations and ground movement associated with nearby earthworks, traffic or natural seismic phe-nomena.

The problem of soil and foundation subsidence is a complex engineering issue [47], especially in the case of historic or heritage buildings, built tens or hundreds of years ago, often upon soil that is heterogeneous, pos-sesses poor loading capabilities and is poorly compacted.

As a result of uneven subsidence, tensile stresses are created in the building structure, causing cracking of walls and degradation of the structure as a whole [43]. Analysis of the cracking pattern should provide a basis for assessing structural safety [48] and for planning rein-forcements or repairs. Many authors conclude that analy-sis of wall cracking patterns and determination of cause may be a good method for assessing threats to structural safety, e.g. in relation to historic towers [49]. In Fig.  1 typical wall cracking patterns associated with foundation subsidence as determined in [50–52].

Introduction summary and objectives of the researchThe appearance of cracking patterns and their mor-phology has been the subject of many research papers describing damage in masonry structures (inter alia [39, 53–56]). At this point, what is worth noting is the fact, that the most common cause of masonry damage is movements of ground substrate, which is the case in 60–70% damage incidents [46]. In recent times, heritage building collapses have occurred in Poland, the causes of which can be attributed indirectly to soil and water con-ditions. One such example was the collapse of the church tower in Otyń in 2012 [9]. The most recent spectacular building failure was the collapse of columns and vaults in the Castle of the Pomeranian Princes in Szczecin.

The main goal of the conducted diagnostic works and structural analysis of the historic building is to prevent

Page 4: Correlation between the cracking pattern of historical

Page 4 of 16Raszczuk and Karolak Herit Sci (2021) 9:43

further damage and, in the extreme cases, to prevent a construction disaster. In the case of objects with numer-ous masonry cracks, one of the probable causes are changes in physical and mechanical soil properties. Proper analysis of the structure is possible if, for diag-nostics purposes, appropriate geometrical survey is conducted in order to recreate the technical documen-tation of the building. The implementation of the model in H-BIM technology allows to perform 3-D analysis of the structure. Only the combination of many diagnostic methods enables the correct assessment of the technical condition of the structure along with the selection of the optimal strengthening methods.

Moreover, the aim of the paper is to demonstrate the correlation between the image of historic object damages and groundwater conditions.

MethodsCase study—church in Kożuchów: architectural characteristic and historical descriptionKożuchów is one of the oldest towns in Lower Sile-sia (the first records date back to 1273 [57]). The medi-eval town was located at the crossroads of trade routes.

Consequently, it quickly grew in importance and archi-tectural sophistication. Significant fragments of for-tification walls, a castle and the parish church of the Purification of the Blessed Virgin Mary, so named in the mid-thirteenth century, have survived to this day [58–60]. The present corpus of the church is the result of several construction phases. The early Gothic church had a two-part corpus, consisting of a nave and presbytery. The building was damaged in the great fire of 1339, which destroyed most of the buildings in Kożuchów. Most probably only the stone walls survived. The church was rebuilt between 1340 and 1369. In the fourteenth century, a high tower was added to the north. At the beginning of the fifteenth century, extension work was carried out. This involved widening of the nave by 12.5  m. The side walls, pillars and gable walls were also demolished. New masonry side walls were built. A porch was added on the west side and the nave was extended to the south and connected to the chancel through space made by break-ing through the arcades in the wall. In the second half of the fifteenth century, the church was enlarged with addi-tion of another three chapels and a porch to the south-ern nave. Over the centuries the church was damaged by

Fig. 1 Images of typical cracking patterns arising from irregular subsidence of building foundations: a subsidence of the corner of a building, b small scale subsidence of the central part of foundations, c large scale subsidence of the central part of foundations, d localized subsidence of a foundation in the case of weak foundations, e localized subsidence of foundations in the case of strong foundations (own drawing in accordance with [50–52])

Page 5: Correlation between the cracking pattern of historical

Page 5 of 16Raszczuk and Karolak Herit Sci (2021) 9:43

fire several more times (1488, 1554, 1637, 1764). Inter-ventions were needed to repair the vaults (1554) and to rebuild the roofing (1764). In the first reconstruction, the roof of the church was rebuilt as a gable roof over the main body, and a gable and pulpit roof over the sac-risty and chapels. The church was covered with three parallel roof covers, one for each nave. The tower was covered with a helmet in the form of an octagonal bro-ken pyramid. The war damage suffered by Kożuchów in 1945 spared the church. At its core, the building is a late Gothic structure with added Renaissance elements (the vaults of the nave and the presbytery) and Baroque ele-ments (the Ogrójcowa chapel, the helmet of the tower).

Research methodologyAnalysis of the resulting cracks may be an indication of uneven foundation subsidence, which in turn may indi-cate heterogeneous ground conditions upon which the building rests. The lithographic structure may comprise many layers and may be characterized by differing physi-cal and mechanical parameters. The issue described above concerns the situation in many historic objects built centuries ago in medieval towns, where soil lay-ers accumulated in succeeding years. Due to the fact, that design cross-sections of analyzed historic buildings (cathedrals, palaces) were of considerable size, the situ-ation is more than likely that they extended over a diver-sity of soil and water conditions. For this reason, analysis of the cracking pattern of a heritage structure, usually requires geological surveying at points surrounding the historic building in order to ascertain a full picture of the geotechnical status of the underlying substrate. The key challenge lies in locating the bore holes and in determin-ing the depth of the boreholes which can extend to tens of meters.

The most appropriate procedural algorithm for select-ing design solutions for the repair and strengthening of a historic building must be based on a wider assessment of the structure of the building and its technical condition. A multi-level correlation of available data enables solv-ing technical issues as a basis for selecting appropriate structural solutions. In the first step the H-BIM model preparation is needed. Then the identification of crack-ing pattern and geotechnical investigation were carried out. Finally the structural analysis was performed and strengthening solutions were designed the procedure used in the case of the church in Kożuchów is presented in Fig. 2.

Results and discussionGeometrical survey and H‑BIM modelThe contemporary devices and software allow to prepare 3-D model of historical object in H-BIM technology, aiming to carry out—in the next step—an appropriate numerical simulations and structural analysis. In case of the church in Kożuchów, tachometric technique was used to determine the global localization of each point for the vaults, arches and walls (Fig. 3). The measure pro-cedure was carried out from outside and from inside.

After the preliminary visual inspections, the range of geometrical survey was defined. All of the points were uploaded to the H-BIM software (Autodesk Revit) using additional software (Autodesk ReCap), that allows this transfer. Figure  4 presents an axonometric view of the church building.

Based on the visual inspections and preliminary analysis of the cracking pattern a hypothesis was for-mulated concerning the influence of soil and water conditions on the uneven settlement of the building structure, and in consequence on structural cracking. The cracking pattern indicates that it occurs something

Fig. 2 Flow chart of the methodology used in the church in Kożuchów

Page 6: Correlation between the cracking pattern of historical

Page 6 of 16Raszczuk and Karolak Herit Sci (2021) 9:43

separate from cracking of the vaults resulting from the gable wall displacement in external direction. The cracking pattern points to global deformation of the gable wall, which leans out into Kościelna Street. The horizontal displacement of the gable wall has been con-firmed through tacheometric testing (Fig. 5).

Geotechnical investigation of the ground substrateInvestigation of the cracking pattern and assessment of the displacement of the gable wall, prompted formula-tion of the hypothesis that damage had been caused by variations in soil and water conditions. Geotechnical tests were carried to test the hypothesis based on bore-holes in the ground in conjunction with core sampling of

Fig. 3 Geometrical survey in the church: a measurement device, b points definition for laser scanner measurement

Fig. 4 View of the digital model of the church in Kożuchów prepared in Revit

Page 7: Correlation between the cracking pattern of historical

Page 7 of 16Raszczuk and Karolak Herit Sci (2021) 9:43

the foundation walls [61]. Six geological boreholes were drilled to a depth of about 4 to 12 m below ground level (total depth of approx. 50 running metres) and 5 core samples were taken from the foundation wall in the east, where damage was greatest. The locations of the bore-holes and core samples from the foundation wall are pre-sented in Fig. 6.

A dry drilling method without pipe casing was used for preparing the geological boreholes. During the testing process, macroscopic description of soils (type, admix-tures, layers, colour, moisture content) was recorded on an ongoing basis and samples were collected for labora-tory testing, ensuring that the natural moisture content or natural granulation was assured. Soil samples were taken to enable laboratory analysis to determine the physical–mechanical parameters of the ground substrate (on average, 3 or 4 samples were taken from each bore-hole). Laboratory testing involved a sieve analysis of the

collected loose soil samples, whereas the condition of compacted soils was determined by testing the consist-ency limit and determining the moisture content.

The results of geological borehole and laboratory test-ing served to separate out geo-technical layers in the ground substrate, and so, to determine geological and engineering conditions. The ground conditions support-ing building foundations were also determined. In all, 7 geo-technical soil layers were separated out in terms of their physical–mechanical properties (degree of plasticity and compaction), (Table 2).

Geological surveying identified the soil-types appear-ing in the area of the building’s foundations. A sub-surface earthworks layer was identified (which includes uncontrolled deposits of clay, sand and brick rub-ble) and also deeper layers of indigenous compacted soils (including mainly sandy clays, phyllosilicate clays and fine clays) and non-compacted soils (sands). The

Fig. 5 Assessing displacement of the gable wall into Kościelna Street

Page 8: Correlation between the cracking pattern of historical

Page 8 of 16Raszczuk and Karolak Herit Sci (2021) 9:43

research also accurately determined the morphology and hydrography of the ground substrate. The depth of the ground water table was determined to be located 4.50–5.80  m below ground level and 7.80  m below ground level (in the O-3 geological borehole). Ground-water resources change under the influence of pre-cipitation, evaporation and may be subject to seasonal fluctuations of ± 1.0  m. The diversity of ground layers appearing in the geological borehole locations indicates

complex ground conditions underlying the foundations of the building (Fig. 7).

The analysis the influence of soil and water conditions on the building foundation is possible on the basis of geo-logical cross-sections obtained for different directions in relation to the ground-level floor plan of the building (Fig. 8).

As a result of the core samples (vertical relative to the wall), the condition of the building’s foundation was

Fig. 6 Ground-level plan of the church (with vaults) showing locations of geological sections, geological boreholes (O), drillings through the foundation walls (P)

Table 2 Listing of ground substrate geo-technical layer properties

Symbol Description Density index (ID) for noncohesive soils/liquidity index (IL) for cohesive soils

I Uncontrolled anthropogenic soils (brick rubble, clay, sand), appearing in a plastic state IL = 0.50

IIa Fine grain, moist sand appearing in semi-compacted state ID = 0.45

IIb Medium grain sands, coarse, moist sand, appearing in a semi-compacted state ID = 0.40

IIIa Hydrated sand-gravel, appearing in a semi-compacted state ID = 0.50

B1 Phyllosilicate clays, sandy clays, dust with phyllosilicate sand layers, moist, appearing in a plastic state IL = 0.43

B2 Phyllosilicate clays, sandy loams, dust with phyllosilicate sand layers, moist, appearing in a hard-plastic state

IL = 0.18

D clays, sandy clays, silts, wet, damp, appearing in a compacted or semi-compacted state IL < 0.00

Page 9: Correlation between the cracking pattern of historical

Page 9 of 16Raszczuk and Karolak Herit Sci (2021) 9:43

determined for the eastern wall area. The church struc-ture was built on stone foundations placed at a depth of 0.60 to 0.70  m below ground level. The south-eastern chapel was built at a depth ranging from 2.10 to 1.40 m below ground level. The frost depth for the village of Kożuchów is 0.80  m, which means that part of the foundations on the eastern side do not meet minimum

requirements. Existing foundations are set partly in substrate subject to displacement (fine grained dust and phyllosilicate clays), and sensitive to freezing and ground water level changes. In the event of even slight water absorption, they can plasticize rapidly under even a small load and reduce their load-bearing capacity. The foundation wall of the church on the east side and the

Fig. 7 Soil characteristics in specified geological boreholes

Fig. 8 Schematic geological section

Page 10: Correlation between the cracking pattern of historical

Page 10 of 16Raszczuk and Karolak Herit Sci (2021) 9:43

chapel is built with pebbles, sandstone and brick on clay and lime mortar. The content of clay in the mortar determines the mechanical properties of the wall (espe-cially the modulus of elasticity) are variable for differ-ent moisture levels. Taking into account the cracking pattern on the walls and vaults of the building and soil substrate that is sensitive to ground water level changes beneath the foundations, it can be concluded that the foundations have sustained a loss of stability (related to both rotation and displacement) in the eastern wall of the church and the chapel in the south-eastern part of the building. These foundations are displacing in both horizontal (outside) and vertical (settling) directions.

It was determined that the observed damage (crack-ing) was caused by uneven horizontal and vertical movements of the foundations arising from variations in geological substrate. The cracking has been caused by: foundations that are too shallow, periodic fluctua-tions in water level in weak load-bearing soils and soil loosening due to excavation.

It was necessary to strengthen the foundations of the church in the eastern part and in the south-eastern chapel to avert the threat of building collapse.

Analysis of cracking patterns of walls and vaultsObservation of numerous cracks on the walls and vaults of the church prompted structural assessment of the building. The cracks were inventoried and presented on floorplans of the church. Cracking on the vault surfaces and vertical cracks in the walls were noted. Special atten-tion was paid to the numerous longitudinal cracks in the eastern part of the heritage building (Fig. 9).

Cracking appeared on both walls and vaults mainly in the eastern part of the building, but also in the main nave. The most significant crack was identified in the inter-nave arch in axis 3, between axes F and G. In this case, the damage to the arch also manifested itself by shifting a wall fragment in a vertical direction. The crack size measured approx. 15–20 mm, posing a serious threat to structural safety. The direct cause of the crack and the formation of a hinge in the interval arch in axis 3 was the significant vertical load of the structure in the area of the roof truss above the arch. Measured from the church floor, the height of the nave at its highest point is 11.52 m. The vaults are supported by external walls (southern and eastern), by the rood arch in the E axis and by the pillar located at the intersection of axes 3 and F. Examples of the cracking are shown in the photographs in Fig. 10.

Fig. 9 Church plan including cracks appearing on the walls and vaults

Page 11: Correlation between the cracking pattern of historical

Page 11 of 16Raszczuk and Karolak Herit Sci (2021) 9:43

Cracking penetrating the entire thickness of the cross-section was observed in the area of the southern nave and the adjoining chapels. The cracking is con-centrated especially in the area of the keystones of the window lintel arches in the upper part of the southern facade. Diagonal cracking was observed in the rood arch, which separates the southern nave from its exten-sion towards the presbytery. Moreover, a deformation (twisting) of the rood arch from the vertical plane was observed. With a maximum height of 13.95 m, the main nave consists of 4 bays covered by cross vaults. Crack-ing was observed in line with the direction of compres-sive stress.

In the eastern part of the building, the cracking pat-tern of vaults indicates the occurrence of tensile stress along the external wall of the building. A typical vault cracking pattern resulting from exceeding tensile capacity in specific places in relation to the situation in the church in Kożuchów is presented in Fig. 11.

The analysis of the influence of the load from the roof into church wallsDuring the diagnosis process, the influence of the load from the roof into church walls was checked. For this purpose, the 3-D roof data were uploaded from H-BIM model to structural software (Fig.  12). Various live load (wind) cases were considered to determine the predicted vertical reaction on the external walls.

As a result of structural analysis, the values for reac-tions from the roof to the wall was determined (Fig. 13).

It was estimated that the internal stresses in the walls caused by horizontal forces from the roof are on the low level and do not have crucial meaning for the cracking appearance in the vaults, but there was a need to add tie rod to ensure the stability of high top walls.

Structural strengthening of the churchThe scope of strengthening work focused on the east-ern part of the church foundations and the chapel

Fig. 10 Examples of cracks appearing on walls and vaults of the church

Page 12: Correlation between the cracking pattern of historical

Page 12 of 16Raszczuk and Karolak Herit Sci (2021) 9:43

foundations in the south-east side (Fig.  14). The inter-vention that was made in this case, should have pre-ventive aims and ensure a passive counteracting for the settlements. Otherwise, such a deep intervention may

cause some unexpected reaction for the global structural behaviour in the future. The strenghtening project was prepared on the basis of results of structural analysis.

Fig. 11 Cracking patterns for cross-vaults: a typical, b vaults in the eastern part of the church in Kożuchów

Fig. 12 3-D numerical model for structural analysis of the roof: a static scheme, b various live load cases (wind)

Page 13: Correlation between the cracking pattern of historical

Page 13 of 16Raszczuk and Karolak Herit Sci (2021) 9:43

When it comes to strengthening existing historic build-ings built using traditional technologies, non-vibrating technologies and technologies that are insensitive to changing ground water levels should be considered [61]. In the case of the church in Kożuchów, the strengthening

measures applied involved constructing cement and ground columns using jet—grouting technology. Rein-forcement involved replacing low-load bearing soils with a concrete substrate of a strength of 3.0 to 7.0 MPa. Fig-ure  15 shows models of the church, indicating a design

Fig. 13 The values of reaction forces from the roof which act on the external walls

Fig. 14 Plan of the church (with reference to the vaults) showing the foundation area proposed for strengthening

Page 14: Correlation between the cracking pattern of historical

Page 14 of 16Raszczuk and Karolak Herit Sci (2021) 9:43

for reinforcement of the foundations based on using piles.

First, tie rods were introduced in order to stabilize the structure and take over the forces from the roof,

and then the vaults should be strengthened due to dam-age occurring in them. In addition, the strengthening of the upper sections of the building through introducing

Fig. 15 Axonometric view of the church showing design for strengthening with jet-grouting columns and zones for tie-rod anchoring (left). Diagonal cross-section through the foundation zone (right)

Fig. 16 Axonometry of the vaults with strengthening introduced in the form of: a C-FRCM carbon fibre nets (marked green), b 40 mm diameter tie rods (marked blue)

Page 15: Correlation between the cracking pattern of historical

Page 15 of 16Raszczuk and Karolak Herit Sci (2021) 9:43

steel cables and strengthening the vaults on the roof side using FRCM technology was necessary (Fig. 16).

Conclusions

1. H-BIM method is an advanced approach that allows to obtain detailed building and structural model and gives the opportunity to conduct a global analysis of the technical state and state of stresses. It is strongly recommended to prepare the H-BIM model for her-itage objects before any structural interventions, especially in the case where the building structure is complex. Furthermore, the contemporary H-BIM models allow to collect information about the previ-ous and current interventions in one digital file, what should be the principle in contemporary design pro-cesses.

2. Based on the structural roof analysis, it was esti-mated that the internal stresses in the walls caused by horizontal forces from the roof are on the low level and do not have significant meaning for the cracking pattern in the vaults, however, there was a need to add tie rods to ensure the stability of high top walls.

3. Geotechnical research conducted at large scale (espe-cially geological boreholes drilled to considerable depths), enabled the determination of soil proper-ties in the area of the building’s foundations, and as a consequence, indication of the causes of cracking of the church structure.

4. The main cause of cracking of the walls and vaults of the church was related to uneven subsidence and localized stability loss of the building’s foundations, resulting from differentiated soil properties beneath the building.

5. Every historical building requires its own individual-ized approach for diagnosis and selection of design interventions.

6. Based on diagnostic results including modern tech-niques, it may be possible to plan appropriately and conduct conservation and strengthening interven-tions in historical buildings.

AcknowledgementsNot applicable.

Authors’ contributionsConceptualization: KR; analysis: AK, KR; resources and data: AK, KR; writing—original draft preparation: AK, KR; writing—review and editing: AK, KR; supervi-sion: KR. All authors have agreed to the published version of the manuscript. All authors read and approved the final manuscript.

FundingNot applicable.

Availability of data and materialsNot applicable.

Declarations

Competing interestsThe authors declare no conflict of interest.

Received: 4 November 2020 Accepted: 31 March 2021

References 1. Dialer CP. Typical masonry failures and repairs: a German Engineer’s view.

Prog Struct Mater Eng. 2002;4(3):332–9. 2. Pérez-Gracia V, Caselles JO, Clapés J, Martinez G, Osorio R. Non-destruc-

tive analysis in cultural heritage buildings: evaluating the Mallorca cathedral supporting structures. NDT E Int. 2013;59:40–7.

3. Saisi A, Cantini L, Binda L. Investigation strategies for the diagnosis of historic structures. In: Emerging technologies in non-destructive testing V. CRC Press; 2012. p. 43.

4. Burland JB, Jamiolkowski M, Viggiani C. The stabilisation of the Leaning Tower of Pisa. Soils Found. 2003;43(5):63–80.

5. Guerra SZ. Severe soil deformations, leveling and protection at the Metropolitan Cathedral in Mexico City. APT Bull J Preserv Technol. 1992;24(1/2):28–35.

6. Topolnicki M. Strengthening and underpinning of stone foundations of St. John Church in Gdansk. In: Proc. international conference on soil mechanics and geotechnical engineering, Istambul, Turkey; 2001. p. 1863–6.

7. Roca P. Restoration of historic buildings: conservation principles and structural assessment. Int J Mater Struct Integr. 2011;5(2–3):151–67.

8. Binda L, Saisi A, Tiraboschi C. Investigation procedures for the diagnosis of historic masonries. Constr Build Mater. 2000;14(4):199–233.

9. Jasieńko J, di Tommasso A, Bednarz Ł, Casacci S, Raszczuk K. Comparative analysis of collapsing towers in Poland and Italy: different causes, similar problems. J Herit Conserv. 2015;43:38–50.

10. López FJ, Lerones PM, Llamas J, Gómez-García-Bermejo J, Zalama E. A review of heritage building information modeling (H-BIM). Multimodal Technol Interact. 2018;2(2):21.

11. Calì A, de Moraes PD, Do VÂ. Understanding the structural behavior of historical buildings through its constructive phase evolution using H-BIM workflow. J Civ Eng Manag. 2020;26(5):421–34.

12. Calì A, do Valle Â, de Moraes PD. Building information modeling and structural analysis in the knowledge path of a historical construction. In: Structural analysis of historical constructions. Cham: Springer; 2019. p. 2071–9.

13. Bruno S, De Fino M, Fatiguso F. Historic building information modelling: performance assessment for diagnosis-aided information modelling and management. Autom Constr. 2018;86:256–76.

14. Dore C, Murphy M, McCarthy S, Brechin F, Casidy C, Dirix E. Structural sim-ulations and conservation analysis-historic building information model (HBIM). Int Arch Photogramm Remote Sens Spat Inf Sci. 2015;40(5):351–7.

15. Quattrini R, Baleani E. Theoretical background and historical analy-sis for 3D reconstruction model. Villa Thiene at Cicogna. J Cult Herit. 2015;16(1):119–25.

16. Quattrini R, Pierdicca R, Morbidoni C. Knowledge-based data enrichment for HBIM: exploring high-quality models using the semantic-web. J Cult Herit. 2017;28:129–39.

17. Dagrain F, Descamps T, Poot B. Less-destructive testing of masonry mate-rials: a comparison between scratching and drilling approaches. In: Proc. 8th international masonry conference, July, Dresden, Germany; 2010.

18. Pelà L, Roca P, Benedetti A. Mechanical characterization of historical masonry by core drilling and testing of cylindrical samples. Int J Archit Herit. 2016;10(2–3):360–74.

19. Binda L, Saisi A, Tiraboschi C, Valle S, Colla C, Forde M. Application of sonic and radar tests on the piers and walls of the Cathedral of Noto. Constr Build Mater. 2003;17(8):613–27.

20. Carpinteri A, Lacidogna G, Pugno N. A fractal approach for damage detection in concrete and masonry structures by the acoustic emission technique. Acoust Tech. 2004;38(3):31–7.

Page 16: Correlation between the cracking pattern of historical

Page 16 of 16Raszczuk and Karolak Herit Sci (2021) 9:43

21. Carpinteri A, Lacidogna G. Damage monitoring of an historical masonry building by the acoustic emission technique. Mater Struct. 2006;39(2):161–7.

22. Carpinteri A, Lacidogna G. Damage evaluation of three masonry towers by acoustic emission. Eng Struct. 2007;29(7):1569–79.

23. Da Porto F, Valluzzi MR, Modena C. Use of sonic tomography for the diag-nosis and the control of intervention in historic masonry buildings. In: Proc. international symposium non-destructive testing in civil engineer-ing 2003 (NDT-CE 2003), Berlin, Germany; 2003. p. 16–9.

24. Schuller M, Berra M, Atkinson R, Binda L. Acoustic tomography for evalua-tion of unreinforced masonry. Constr Build Mater. 1997;11(3):199–204.

25. Binda L, Zanzi L, Lualdi M, Condoleo P. The use of georadar to assess damage to a masonry Bell Tower in Cremona, Italy. NDT E Int. 2005;38(3):171–9.

26. García FG, Blanco MR, Abad IR, Sala RM, Ausina IT, Marco JB, Conesa JLM. GPR technique as a tool for cultural heritage restoration: San Miguel de los Reyes Hieronymite Monastery, 16th century (Valencia, Spain). J Cult Herit. 2007;8(1):87–92.

27. Leucci G, Negri S, Carrozzo MT. Ground penetrating radar (GPR): an appli-cation for evaluating the state of maintenance of the building coating. Ann Geophys. 2003;46(3):481–9.

28. Orlando L, Slob E. Using multicomponent GPR to monitor cracks in a historical building. J Appl Geophys. 2009;67(4):327–34.

29. Ranalli D, Scozzafava M, Tallini M. Ground penetrating radar investigations for the restoration of historic buildings: the case study of the Collemag-gio Basilica (L’Aquila, Italy). J Cult Herit. 2004;5(1):91–9.

30. Soldovieri F, Orlando L. Novel tomographic based approach and process-ing strategies for GPR measurements using multifrequency antennas. J Cult Herit. 2009;10:83–92.

31. Gentile C, Saisi A, Cabboi A. Structural identification of a masonry tower based on operational modal analysis. Int J Archit Herit. 2015;9(2):98–110.

32. Zonno G, Aguilar R, Boroschek R, Lourenço PB. Environmental and ambi-ent vibration monitoring of historical adobe buildings: applications in emblematic andean churches. Int J Archit Herit. 2019. https:// doi. org/ 10. 1080/ 15583 058. 2019. 16534 02.

33. Gentile C, Poggi C, Ruccolo A, Vasic M. Vibration-based assessment of the tensile force in the tie-rods of the Milan Cathedral. Int J Archit Herit. 2019;13(3):411–24.

34. Aras F, Krstevska L, Altay G, Tashkov L. Experimental and numerical modal analyses of a historical masonry palace. Constr Build Mater. 2011;25(1):81–91.

35. Rossi PP, Rossi C. Monitoring of two great venetian cathedrals: San Marco and Santa Maria Gloriosa dei Frari. Int J Archit Herit. 2015;9(1):58–81.

36. Bartoli G, Blasi C, De Robertis N, Foraboschi P. Monitoring system of the Brunelleschi’s dome in Florence: intrepretations of the recorded data. In: Structural repair and maintenance of historical buildings II. Vol. 1: general studies, materials and analysis; 1991. p. 209–21.

37. Sánchez AR, Meli R, Chávez MM. Structural monitoring of the Mexico City Cathedral (1990–2014). Int J Archit Herit. 2016;10(2–3):254–68.

38. Carpinteri A, Lacidogna G. Structural monitoring and integrity assess-ment of medieval towers. J Struct Eng. 2006;132(11):1681–90.

39. Bosiljkov V, Uranjek M, Žarnić R, Bokan-Bosiljkov V. An integrated diag-nostic approach for the assessment of historic masonry structures. J Cult Herit. 2010;11(3):239–49.

40. Cataldo R, De Donno A, De Nunzio G, Leucci G, Nuzzo L, Siviero S. Integrated methods for analysis of deterioration of cultural heritage: the Crypt of “Cattedrale di Otranto.” J Cult Herit. 2005;6(1):29–38.

41. Guadagnuolo M, Faella G, Donadio A, Ferri L. Integrated evaluation of the Church of S. Nicola di Mira: Conservation versus safety. NDT E Int. 2014;68:53–65.

42. Lignola GP, Manfredi G. A combination of NDT methods for the restora-tion of monumental façades: the case study of Monte di Pietà (Naples, Italy). J Cult Herit. 2010;11(3):360–4.

43. Tokimatsu K, Mizuno H, Kakurai M. Building damage associated with geotechnical problems. Soils Found. 1996;36(Special):219–34.

44. Fai S, Graham K, Duckworth T, Wood N, Attar R. Building information modelling and heritage documentation. In: Proc. 23rd international

symposium, international scientific committee for documentation of cultural heritage (CIPA), Prague, Czech Republic; 2011. p. 12–6.

45. Pronozin YA, Epifantseva LR, Kajgorodov MD. Structural safety of buildings in excess values of differential settlements. In: Proc. IOP conference series: materials science and engineering, vol. 481, no. 1. IOP Publishing; 2019. p. 012013.

46. Drobiec Ł. Przyczyny uszkodzeń murów. In: Proc. XXII Ogólnopolska Konferencja Warsztat Pracy Projektanta Konstrukcji, Szczyrk [The causes of masonry damages]. 2007. p. 7–10. (in Polish).

47. Casalegno C, Cecchi A, Reccia E, Russo S. Heterogeneous and continuous models: comparative analysis of masonry wall subjected to differential settlements. Compos Mech Comput Appl Int J. 2013;4(3):187–207.

48. Alessandri C, Garutti M, Mallardo V, Milani G. Crack patterns induced by foundation settlements: integrated analysis on a renaissance masonry palace in Italy. Int J Archit Herit. 2015;9(2):111–29.

49. Anzani A, Binda L, Carpinteri A, Invernizzi S, Lacidogna G. A multilevel approach for the damage assessment of historic masonry towers. J Cult Herit. 2010;11(4):459–70.

50. Drobiec Ł. Przyczyny uszkodzeń murów (cz. 1) Uszkodzenia spowodow-ane błędami projektowymi [Causes of damage to walls (part 1). Damage caused by design errors]. Izolacje. 2017;22:44–56 (in Polish).

51. Mastrodicasa S. Dissesti statici delle strutture edilizie: diagnosi, consoli-damento, istituzioni teoriche [Static instability of building structures: diagnosis, consolidation, theoretical institutions]. Milano: Ulrico Hoepli; 1978. (in Italian).

52. Burland JB, Broms BB, De Mello VF. Behaviour of foundations and struc-tures, Geo-Report; 1978. p. 495–46.

53. Binda L, Saisi A, Tedeschi C. Masonry. In: Fracture and failure of natural building stones. Dordrecht: Springer; 2006. p. 167–82.

54. Fathy AM, Planas J, Sancho JM. A numerical study of masonry cracks. Eng Fail Anal. 2009;16(2):675–89.

55. Schubert P. Beitragsserie: Schadenfreies Bauen mit Mauerwerk. Thema 1: Zweischalige Außenwende - Risse durch zu große Verformungsunter-schiede in horizontaler Richtung [Article series: damage-free masonry buildings. Topic 1: two-shell exterior turn—cracks due to excessive deformation differences in the horizontal direction]. Mauerwerk. 2001;5(1):35–8 (in German).

56. Schubert P. Beitragsserie: Schadenfreies Bauen mit Mauerwerk. Innen/Außenwende - Risse durch zu große Verformungsunterschiede in ver-tikaler Richtung [Article series: damage-free masonry buildings. Inside/outside turn—cracks due to excessive deformation differences in the vertical direction]. Mauerwerk. 2001;5(4):141–4 (in German).

57. Eckert W. Kożuchów–historyczne miasto z przyszłością [Kożuchów—historical town with the future]. Budownictwo i Architektura. 2018;17(2):065–80 (in Polish).

58. Andrzejewski T. Szlaki kulturowe w Gminie Kożuchów, Towarzystwo Przyjaciół Ziemi Kożuchowskiej, Kożuchów [Cultural routes in Kożuchów commune]. 2012. (in Polish).

59. Kowalski S, Karczewska J, Podolan E, Gerlic H, Górski A, Kozieł A, Kłoda E, Brylla WJ. Kościół farny w Kożuchowie w świetle najnowszych badań, Towarzystwo Przyjaciół Ziemi Kożuchowskiej, Kożuchów [The church in Kożuchów in accordance to the latest research]. 2011. (in Polish).

60. Stachura W. Parafia katolicka. In: Kożuchów. Zarys dziejów, red. T. Andrzejewski, Kożuchowski Ośrodek Kultury i Sportu “Zamek”, Kożuchów [Catholic parish. In: Kożuchów—outline of the history]. 2003. p. 217–20. (in Polish).

61. Budzińska-Koźlik, Tutaj W, Adamowicz-Palma A. Badania geotechniczne określające warunki gruntowo – wodne wokół kościoła pw. Matki Bożej Gromniczej w Kożuchowie, GeoProject Sp. z o.o [Geotechnical investiga-tions determining the soil and water conditions around the church in Kożuchów]. 2016. (in Polish).

Publisher’s NoteSpringer Nature remains neutral with regard to jurisdictional claims in pub-lished maps and institutional affiliations.