Page 1: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

Copyright MaterialsThis presentation is protected by US and

International Copyright laws. Reproduction, distribution, display and use of the presentation

without written permission of the speaker is prohibited.

© The Epsten Group, Inc. 2014

Page 2: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

About Us

Epsten Group Services:

Commissioning

Retro-Commissioning

Building Envelope Services

Roofing & Waterproofing Consulting

Architecture & Interior Design

LEED Consulting

Energy Modeling

• Established in 1991

• Multi-Disciplinary

• 6,000 LEED Reviews in 50+ Countries

• Small Disadvantaged Business; 8(m) WOSB

Page 3: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

Guide to ASHRAE 90.1 Changes

P r e s e n t a t i o n f o r C x E n e r g y 2 0 1 4A A B C C o m m i s s i o n i n g G r o u p

L a s Ve g a s , N e v a d aA p r i l 2 3 , 2 0 1 4

Page 4: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

At the end of this course, participants will be able to:

1. Participants will learn how the ASHRAE 90.1 energy standard has evolved in recent years up to the current version that has been adopted.

2. Participants will be able to distinguish the major amendments to the standard that have led to substantial energy improvements from the last version.

3. Participants will learn how the changes to 90.1 and its Appendix G will affect the latest version of LEED and consequentially building energy models.

4. Participants will learn how the changes to the standard will impact the building industry and particularly how it will impact commissioning providers.

Learning Objectives

Page 5: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

1.0 Evolution

First drafted in 1975

Major re-write of the standard in 1999

Continuous maintenance began in 2001 (every 3 years)

ASHRAE 90.1-2007 updated from 2004 via 44 addenda

ASHRAE 90.1-2010 updated from 2007 with more than 100 addenda

Page 6: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

1.1 ASHRAE 90.1-2010 Goal

Set out to achieve a 30% energy savings when compared to ASHRAE 90.1-2004.

Goal achievement proven by Pacific Northwest National Laboratory (PNNL)

Substantial energy efficiency improvement when compared to earlier iterations

Sidenote: Significant implications for LEED pursuit in LEED v4

Page 7: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

1.2 Major Sections

5.X Envelope

6.X Mechanical

7.X Service Water Heating

8.X Power

9.X Lighting

Appendix G (Performance Rating Method)

Page 8: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

1.3 Compliance

5.X Envelope

6.X Mechanical

7.X Service Water Heating

8.X Power

9.X Lighting

Appendix G (Performance Rating Method)

Page 9: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

1.4 Climate Zones

Page 10: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

1.5 Building Prototypes

Small/Medium/Large Offices Retail/Strip Mall Primary/Secondary Schools Outpatient Healthcare Hospital Small/Large Hotels Warehouse Quick/Full-Service Restaurants Mid-Rise/High-Rise Apartments

Page 11: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

2.0 Envelope Changes

Continuous air barrier

Cool roofs

Constraints on glazing

Page 12: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

2.0.1 Air Barriers

A properly functioning air barrier system provides a barrier against both the air leakage and the diffusion of air caused by wind, stack, and mechanical equipment pressures.– According to the ABAA, air leakage

can result in increased energy costs of up to 30-40% in heating climates and 10-15% in cooling climates

– The additional benefit to air barriers is that they keep unconditioned, moist air out of the building and reduce the possibility of mold growth

Page 13: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

2.1.1Continuous Air Barrier

Permeance ≤ 0.004 cfm/sf– Individual materials: plywood, insulation

board, metal

Permeance ≤ 0.04 cfm/sf– Assemblies or materials

All air barrier components must be clear on documents

All joints, penetrations must be detailed Barrier must extend over all envelope

surfaces Barrier must be design to resist

positive AND negative pressures

Page 14: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

2.1.2 Continuous Air Barrier

Construction of barrier must include sealing, caulking, gasketing, or weather-stripping:– Joints (windows and doors)– Junctions of walls to foundation or roofs– Openings– Any penetrations through vapor retarders

Exceptions:– Semi-heated spaces in Climate Zone 1

through Zone 6

Page 15: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

2.2 Cool Roofs

Required in Climate Zone 1 through Zone 3

Certified by ASTM– 3 year aged solar reflectance ≥ 0.55 and

emmittance ≥ 0.75 OR– 3 year aged SRI ≥ 64 OR– Increased insulation of Table 5.5.3.1.2

Numerous exceptions are noted

Page 16: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

2.3 Glazing

Window Wall Ratio ≤ 40% of gross wall area (prescriptive path)

Skylight roof ratio ≤ 5% of roof area

Major changes for SHGCs over 90.1-2004 which apply to all orientations

SHGC reductions through use of overhangs

Page 17: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

3.0 HVAC Changes

Efficiency ratings on equipment

Energy recovery

Economizers

Duct sealing/leakage

Fan power

Reheat

Page 18: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

3.1 Simplified Approach Option

Only applies to HVAC section

Acceptable for buildings that are 1 to 2 stories and < 25,000 sf

Must also meet 17 separate criteria

Page 19: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

3.2 Efficiency Updates

Unitary AC and heat pumps Single zone VAV Water-cooled units Packaged units and heat pumps Water-to-water heat pumps CRAC units VRF Chillers Cooling towers Heat exchangers Heat pump pool heaters Furnaces and water heating

Page 20: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

3.3 Economizers

Comfort cooling– Not required for 1A and 1B– Required for all other zones where the cooling

capacity is ≥ 54,000 Btu/h

Computer rooms– Not required in 1A, 1B, 2A, 3A, 4A– Required in other zones dependent on tonnage

Exempt:– If able to prove efficiency improvement for the

climate zone

Page 21: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

3.4 Waterside

Two-position valves in water-cooled units (i.e. SWUD units)

Variable flow/pumping Pump pressure optimization No regulation downstream of booster pumps Maximum flows in nominal pipe sizes Significant insulation upgrades, particularly for

steam and hot water systems

Page 22: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

3.5.1 Airside

Ventilation optimization Supply air temp reset Limitation on damper leakage Dual maximum for VAV terminal units Overhead heating temp limit Lab VAV exhaust air Demand control ventilation Fan power limitation

Page 23: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

3.5.2 Airside

Exhaust air energy recovery

Page 24: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

4.0 Lighting Changes

Lighting power density improvements

Exterior building lighting updates

Grounds lighting

Page 25: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

4.1 Lighting Power Density

Most spaces defined in standard have lower LPDs than 2007 and reductions are substantial

Important to keep in mind impact of these requirements on cooling and heating load calculations

Average reduction of 16.2% in LPDs versus 90.1-2007

Page 26: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

4.2 Auto Shutoff/Dimming

Time clock with separate shutoff for each floor or building > 25,000 sf OR

Occupancy sensors set to 30 minutes OR

Separate signal from controls indicated the space is unoccupied

Daylight switching for daylit areas > 250 sf

Page 27: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

4.3 Exterior Lighting

Turn off when adequate daylight available

Façade and landscape lighting off between closing or midnight and 6 am or opening

Reduced lighting of advertising overnight

Reduction in lighting power densities, depending on zone

Page 28: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

5.0 LEED EAp2 Impact

LEED v2009 requires a 10% energy cost savings when compared to the baseline building as defined by ASHRAE 90.1-2007

LEED v4 requires a 5% energy cost savings when compared to the baseline building as defined by ASHRAE 90.1-2010

Page 29: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

5.1 LEED EAc1 Impact

0 2 4 6 8 10 12 14 16 18 200%

10%

20%

30%

40%

50%

60%

6%8%

10%12%

14%16%

18%20%

22%24%

26%

29%

32%

35%

38%

42%

46%

50%

54%

14%16%

18%20%

22%24%

26%28%

30%32%

34%36%

38%40%

42%44%

46%48%

50%

EAc1 Point Comparison

v2009

v4

Page 30: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

6.0.1 Energy Modeling Impact

Appendix G– Section G1.4 has been revised to include a more

detailed list of required documentation to be submitted to the rating authority.

– Section G2.5 has been revised to more clearly explain the Exceptional Calculation Method procedure and what documentation is required to justify the results.

– Section G3.1.1 includes new exceptions for additional system types for kitchens and heated only spaces (new Baseline system types 9 and 10).

– Section G3.1.1.1 through Section G3.1.1.3 provide new guidance for modeling district heating and cooling systems.

Page 31: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

6.0.2 Energy Modeling Impact

Appendix G (continued)– Table G3.1(14) includes new guidance regarding

“exterior conditions” (adjacent structures and terrain, ground temperatures, and water main temperatures).

– Section G3.1.2.6 has been revised to more clearly explain how to take credit for improved ventilation systems (i.e. demand control ventilation)

– Section G3.1.2.9 includes new provision for sizing supply air volumes in the Baseline model for laboratories.

– Section G3.1.3.13 includes additional requirements for VAV minimum setpoints in the Baseline model for laboratories.

Page 32: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

7.0 Impact on Building Industry

Jump in energy performance requirements to drive vendors to be more aggressive

Architects, engineers and contractors will have a learning curve on new requirements

Initially expect increased cost of construction while industry catches up

Even more importance now on technical competence across all trades, but specific focus on controls technicians that are required to implement more complex strategies

Page 33: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

7.1 Impact on Commissioning

Elevated performance requirements leading to more complex building systems– HVAC and Controls– Lighting controls– Integration of other systems

Commissioning providers required to be knowledgeable on optimization requirements stipulated in energy code

Opportunity for commissioning professionals to provide guidance and lessons learned on success of optimization strategies to design engineers

Page 35: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

Knowledge acquired:

1. Participants learned how the ASHRAE 90.1 energy standard has evolved in recent years up to the current version that has been adopted.

2. Participants are able to distinguish the major amendments to the standard that have led to substantial energy improvements from the last version.

3. Participants learned how the changes to 90.1 and its Appendix G will affect the latest version of LEED and consequentially building energy models.

4. Participants learned how the changes to the standard will impact the building industry and particularly how it will impact commissioning providers.

Conclusion

Page 36: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

Please feel free to ask any questions you may have for today’s course presenters.

Questions

Page 37: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

Thank You For Your Time

Page 38: Copyright Materials This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation

About Us

Epsten Group Services:

Commissioning

Retro-Commissioning

Building Envelope Services

Roofing & Waterproofing Consulting

Architecture & Interior Design

LEED Consulting

Energy Modeling

• Established in 1991

• Multi-Disciplinary

• 5,500 LEED Reviews in 50+ Countries

• 8(a) Certified; Small Disadvantaged Business; 8(m) WOSB