controller 4

Upload: adel-suker

Post on 03-Apr-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 Controller 4

    1/52

    ATC-300 Transfer SwitchController Standard Features

    Time Delay Normal to Emergency (0-1800 sec) (Default 5 sec)

    Time Delay Engine Start (0-120 sec) (Default 8 sec)

    Time Delay Emergency to Normal (0-1800 sec) (Default 5 min)

    Time Delay Engine Cooldown

    (0-1800 sec) (Default 0 sec) Time Delay in Neutral

    (Default 5 sec)

  • 7/28/2019 Controller 4

    2/52

    ATC-300 Transfer SwitchController Standard Features (continued)

    Source #1 Undervoltage Source #2 Undervoltage & Under Frequency LED Indicator Lights

    Display Status Normal Available Normal Connected

    Emergency Available Emergency Connected

  • 7/28/2019 Controller 4

    3/52

    ATC-300 Transfer SwitchController Standard Features (continued)

    Engine Test Button Alarm Relay

    Improper Circuit Breaker Operation Motor Operator Failure Lockout Failsafe Condition

    Aborted Engine Test Aborted Plant Exerciser Unsuccessful in-phase Transition

  • 7/28/2019 Controller 4

    4/52

    Step / EnterPressing the Step/Enterpushbutton advances theinformation through theprogramming or display cycle.

    HelpPressing the Help pushbuttonin any function mode willbring up display messages,explanations and prompts toassist the operator.

    Engine TestPressing the Engine Testpushbutton twice initiates theengine test cycle.

    Lamp TestPressing the Lamp Testpushbutton lights all LEDsand then displays ATC-300controller information. Bypass TDNE/TDEN

    Pressing Step and Help/Lamp Testpushbuttons simultaneously reducesprogrammed time delays to zero to simplifytest procedures.

    ATC-300 Main Display

  • 7/28/2019 Controller 4

    5/52

    Unit StatusThe Unit Status LED isa blinking indicator forself and systemdiagnostics.

    LCD-BasedDisplayThe LCD based displayis a backlit, 2-line, 16character display.Displayed informationincludes:

    Source Voltages andfrequency

    Time/date stamp

    Historical data Programming and setpoint information

    Password entryIncrease & DecreasePressing the increase or Decreasepushbuttons affect the value of thefunction presently active on the LCDbased display.

    ATC-300 Main Display

  • 7/28/2019 Controller 4

    6/52

    PASSWORD0300

    ATC-300 Programming Mode Password:

    Key in the numericalpassword: 0300

  • 7/28/2019 Controller 4

    7/52

    2002 Eaton Corporation. All rights reserved.

    Diesel Fire Pump Controllers

  • 7/28/2019 Controller 4

    8/52

    Operation Diesel controllers monitor the fire sprinkler

    system pressure by means of a pressuretransducer or pressure switch.

    Upon detecting a drop in system pressure, astart signal is sent to the engine, initiating itscrank cycle.

  • 7/28/2019 Controller 4

    9/52

    Starting The starting process can be initiated by causes

    other than a pressure drop, such as a signal froma Deluge Valve opening or a Remote Startpushbutton being activated.

  • 7/28/2019 Controller 4

    10/52

    Number & Capacity of Batteries NFPA 20, Section 11.2.5.2.1

    Each engine shall be provided with two storagebattery units.

    At 4.5 degrees C (45 deg. F) - each battery unit shall

    have twice the capacity sufficient to maintain thecranking speed recommended by the enginemanufacturer.

  • 7/28/2019 Controller 4

    11/52

    Crank Cycle NFPA 20, Section 11.2.5.2.1

    The attempt to start cycle shall be of a 3 minuteduration - consisting of 15 seconds of crankingfollowed by 15 seconds of rest, in six consecutive

    cycles.

  • 7/28/2019 Controller 4

    12/52

    Stopping There are 2 approved methods of stopping a diesel

    controller. Manual Electric Shutdown Manual shutdown shall be accomplished by either of the

    following: Operation of the main switch inside the controller. Operation of a stop button on the outside of the controller enclosure.

    (The stop button shall cause the engine to shutdown through theautomatic circuits only if all starting causes have been returned

    to normal - ie: pressure rises above the start point.) The controller then returns to the full automatic position.

  • 7/28/2019 Controller 4

    13/52

    Stopping Automatic Shutdown after Automatic Start.

    There are several conditions that must be met for thismethod to be used.

    All starting causes must have returned to normal for a

    minimum of 30 minutes.

  • 7/28/2019 Controller 4

    14/52

    Stopping Automatic Shutdown after Automatic Start.

    The engine cannot shut down automatically on highwater temp. or low oil pressure when any startingcause exists.

    If no other starting cause exists during engine test,shutdown is permitted.

  • 7/28/2019 Controller 4

    15/52

    Battery Chargers NFPA 20, Section 8-2.5.2.4

    There are several stringent requirements that BatteryChargers must meet under this section of the NFPACode.

    This is an extensive section of the code - withoutproperly charged batteries, there is no way to start theengine - hence . NO FIRE PROTECTION

  • 7/28/2019 Controller 4

    16/52

    Battery Chargers NFPA 20, Section 11.2.5.2.4

    Chargers shall be specifically listed for fire pumpservice.

    The rectifier shall be a semiconductor type.

  • 7/28/2019 Controller 4

    17/52

    Battery Chargers NFPA 20, Section 11.2.5.2.4

    When the battery (lead-acid type) reaches a fullycharged condition, the charger must reduce thecharging rate to less than 500mA.

    The charger must charge the battery withoutdamaging it - and must restore the battery to 100% ofreserve capacity within 24 hours.

  • 7/28/2019 Controller 4

    18/52

    Overpressure Requirements NFPA 20, Section 12.4.1.3

    Due to the introduction of pressure limiting drivers there is a requirement for the controller to monitoroverpressure.

    For engines equipped with pressure limiting controls,the controllers are required to provide visual andaudible indication when system overpressure

    reaches 115 % of total rated head pressure.

  • 7/28/2019 Controller 4

    19/52

    Electronic Engine Requirements NFPA 20, Section 12.4.1.3

    Due to the introduction of electronic engines into themarket, a visible indicator and audible alarm must beprovided for the conditions ECM Selector Switch in

    Alternate and Fuel Injection Malfunction. In order to meet the requirements, two pilot lights

    and relay contacts are added to the controller.

  • 7/28/2019 Controller 4

    20/52

    Electronic Engine Requirements NFPA 20, Section 12.4.1.3

    Controller terminal strips have two additional terminalsfor connecting to the engine control panel.

    They are as follows: Terminal Number: 301 - ECM Selector Switch in Alternate Terminal Number: 302 - Fuel Injection Malfunction

  • 7/28/2019 Controller 4

    21/52

    Microprocessor -vs- Relays Microprocessor based controllers provide several

    advantages over relay-based controllers .. Advanced diagnostics and troubleshooting Communication Memory for storage of alarm conditions On site changes performed easily Digital accuracy of parameters

  • 7/28/2019 Controller 4

    22/52

    2002 Eaton Corporation. All rights reserved.

    FD100 Diesel

  • 7/28/2019 Controller 4

    23/52

    FD100 Standard Features Microprocessor Based 12VDC or 24VDC Battery Voltage NEMA 2 Enclosure

    Dual 10 Amp Battery Chargers Pressure Transducer (0-600 psi) Weekly Test Timer Run Period Timer

  • 7/28/2019 Controller 4

    24/52

    FD100 Standard Features contd Manual Stop Printer Recorder AC Power Failure Start

    Sequential Start Timer Relay Energized Indicator Remote Start Deluge Valve Start

  • 7/28/2019 Controller 4

    25/52

    Weekly Program Timer To ensure dependable operation of the diesel

    engine, NFPA 20 code requires automaticweekly starting and running of the engine.

    The weekly test period is for at least 30minutes.

  • 7/28/2019 Controller 4

    26/52

    FD100 Visual/Audible Alarms

  • 7/28/2019 Controller 4

    27/52

    FD100 Main Display Voltmeter for each Battery Ammeter for each Battery Current System Pressure

  • 7/28/2019 Controller 4

    28/52

    FD100 Diesel Controller Standard Alarms

    All alarms are pre-wired to the Terminal Block Can be connected now, or in the future, without the addition of

    any auxiliary components

    Extra sets of contacts supplied as standard for:Manual Mode Off Mode

    Engine Trouble Pump Room Trouble

    Engine Run Crank Battery #1 & #2

    Fuel Solenoid Valve Drain Valve Solenoid

    Common Alarm

  • 7/28/2019 Controller 4

    29/52

    FD100 Programmable Features Pressure Start & Stop Points Weekly Test Timer Run Period Timer

    Sequential Start Timer Pressure Deviation (paperless chart recorder) Low Suction Alarm and/or Shutdown

    Auto/Manual Reset on Shutdown

  • 7/28/2019 Controller 4

    30/52

    FD100 Programmable Features(2) Stop Mode

    Manual or Automatic Programmable Future Relays

    Battery Failure Input = Output

    Test Mode High Engine Temp.

    Auto Mode Low Fuel

    AC Power Fail Engine Overspeed

    Fail to Start Low Oil Pressure

    Low Pressure Start Battery Charger FailFuel Spill

  • 7/28/2019 Controller 4

    31/52

    FD100 Programmable Features(3) Language

    English French Spanish

    Print Routine Automatic (testing) vs Manual (operational)

  • 7/28/2019 Controller 4

    32/52

    FD100 Options Space Heater / Thermostat / Humidistat Enclosure Type

    NEMA 12/3R/4/4X

    Fuel Level Switches (16 or 45) Low Suction Pressure Switch

  • 7/28/2019 Controller 4

    33/52

    Electronic Control Module (ECM)

    The FD100 diesel engine fire pump controllers arecompatible with NFPA20 - Section 12.4.1.3 for engineswith ECM controls.

    Separate visible indicators and audible alarms areprovided for the conditions - ECM Selector Switch inAlternate and Fuel Injection Malfunction.

    FD100 Options

  • 7/28/2019 Controller 4

    34/52

    FD100 Options Electronic Control Module (ECM)

    When the ECM option is requested, two pilot lightsand relay contacts are added to the controller in order tomeet the requirements.

  • 7/28/2019 Controller 4

    35/52

    Electronic Control Module (ECM)

    As well, the terminal strip now has two additionalterminals for connecting to the engine control panel. Theyare as follows:

    Terminal Number: 301 - ECM Selector Switch in Alternate Terminal Number: 302 - Fuel Injection

    FD100 Options

  • 7/28/2019 Controller 4

    36/52

    FD100 Options System Over Pressure

    In order to meet the requirements of NFPA 20; whenthe PLD option is requested, a visible alarm light and anadditional pressure switch are added to the controller.

    As well, the diesel controller horn will sound if systemover pressure is present.

  • 7/28/2019 Controller 4

    37/52

    Printer / Recorder

    Battery Chargers

    Solenoid Valve

    Pressure Transducer

    Relay Output Board

    Microprocessor

    Crank Push ButtonsStop Push Button

    LCD Display

    Alarm / Function LEDs

    Audible Horn

    Input Terminals

    Inside Look at the FD100

  • 7/28/2019 Controller 4

    38/52

    FD100 Upgrades on the horizon Upgraded firmware will perform System Overpressure

    function by utilizing pressure transducer input eliminates the need for a second input from a pressureswitch.

    New battery chargers with enhanced features. Voltage Input: 90 - 130VAC / 180 - 240VAC Auto detect Voltage Output: 12-24VDC DIP switch selectable

    Hertz: Operates on 50 / 60 Hz

    Temperature Monitoring

    Dead Battery Cell Alarm Battery Temperature Probe

    Reduced overall size

  • 7/28/2019 Controller 4

    39/52

    2002 Eaton Corporation. All rights reserved.

    Jockey Pump Controllers

  • 7/28/2019 Controller 4

    40/52

    Purpose Plumbing systems can encounter leaks for

    various reasons. Leaks = drop in pressure - (usually minor - only a

    few psi) The pressure must be kept at a level that will

    enable the system to react correctly in case of acall to start.

  • 7/28/2019 Controller 4

    41/52

    Purpose Since the pressure drop is minor - the fire pump

    should not be called upon to keep the pressureat a minimum level.

    A smaller Jockey Pump is used to keep thesystem pressure at the desired constant.

    A separate Jockey Pump Controller is used tocontrol the jockey pump.

  • 7/28/2019 Controller 4

    42/52

    NEMA 2 Rated Enclosure

    120V Control Transformer

    Circuit Breaker Disconnect

    Pressure Switch

    15-260 psi

    Internal Components

  • 7/28/2019 Controller 4

    43/52

    Operation The Jockey Pump controller is essentially an

    Across-The-Line combination starter with apressure switch.

    The pressure switch is set to operate at aspecific set-point - set on site.

  • 7/28/2019 Controller 4

    44/52

    Operation Typically the jockey pump starting set point is

    10psi above the set point of the fire pumpcontroller.

    This allows the jockey pump to cycle on and off,as needed, to keep the pressure at the desiredpsi - without excessively cycling the fire pump.

  • 7/28/2019 Controller 4

    45/52

    Breakers -vs- Fuses Typically two styles of jockey pump controllers

    can be found in the market. For turning power on and off to the controller -

    either a fusible disconnect or a breaker with amechanical operating handle are utilized.

  • 7/28/2019 Controller 4

    46/52

    Breakers -vs- Fuses One of the most common reasons breakers are

    used over fuses, are on-site disappearances offuses.

    However, breaker style controllers may be moreexpensive depending on which manufacturerchosen.

  • 7/28/2019 Controller 4

    47/52

    Circuit Transformers The control voltage in the jockey pump controller

    is typically line voltage or 120V, 3 phase. The controllers can have a transformer in the

    circuit which operates on full line voltage andsteps down the voltage to 120V.

  • 7/28/2019 Controller 4

    48/52

    Overload Protection Thermal overload protection is allowed by code. Overloads are sized according to the namplate

    Full Load Amps (FLA) on the motor. Most jockey pump manufacturers size the

    controller for the appropriate Hp and supply theproper size overload.

  • 7/28/2019 Controller 4

    49/52

    Options Enclosure Type - NEMA 12/3R/4/4X Single Phase Service (120V or 220V) Low Suction Shutdown c/w Pressure Switch Space Heater / Thermostat / Humidistat Power On Light Extra Contacts

  • 7/28/2019 Controller 4

    50/52

    Run Period Timers (RPTs) A Run Period Timer can be added - as an option

    - to a standard jockey pump controller. The purpose is to ensure that the jockey pump

    runs for a minimum period of time, when there isa call to start due to low pressure.

  • 7/28/2019 Controller 4

    51/52

    http://www.chfire.com

    VISIT OUR WEBSITE !

  • 7/28/2019 Controller 4

    52/52

    FIRE PUMP CONTROLLERS