control panel mcc3 symbol legend
TRANSCRIPT
KEY TO COIL/CONTACT GRID REFERENCE
2
2122
CONTACT No.2
REFERENCE TO CONTACTOR/RELAY
1
R34No. OF CONTACTS
CONTROL PANEL MCC3
2 POLECONTACT
TERMINAL
NORMALLY OPENCONTACT
NORMALLY CLOSEDCONTACT
RELAYCOIL
CONTACTORCOIL
GRIDREFERENCE
CURRENTTRANSFORMER
SYMBOL LEGENDPUSHBUTTON
MCB
NEUTRALLINK
PUSHBUTTON
HANDOFF
AUTO
3 POSITIONSELECTOR SWITCH
No.1 No.2
2 POSITIONSELECTOR SWITCH
D.PSWITCH
4A FUSEDSPUR
GRID REFERENCE1ST DIGIT INDICATES SHEET No.2ND DIGIT INDICATED GRID 0-9
FUSEF11A
B1
4A
25
BUZZER
PANEL COLOUR KEYBLACK - PANEL WIRINGBLUE - PANEL COMPONENTSGREEN - FIELD WIRING & EQUIPMENT
R12
R112
22222
C12
LAMP
LAMP COLOURR
INDEX
INCOMING MAINS & CONTROL CIRCUITS
DESCRIPTION
01
02
SHEET No.
INDEX & LEGEND OF SYMBOLSISSUE
REVISION/
KITCHEN GAS VALVE03
-
-
3
04
14 -
-MEETING ROOMS 1-7 AHU1
SHEET
DATE
ISSUE
SCALE
DRG No.
DRAWN
CHECKED
DATEISSUE No. ISSUE DETAILS
Job-No
1 of 22
3
15/06/2011
NTS
J.STONEMAN
JS
1 FOR APPROVAL 17/06/20112 FOR MANUFACTURE 21/06/20113 AS BUILT 15/08/2011
19
20
-
-
OUTSTATION WIRING
GENERAL ARRANGEMENT
LABELING DETAILS
05 -MEETING ROOMS 1-7 AHU1
15 -OUTSTATION WIRING
16 -
17 -
18 -
MEETING ROOMS 8-9 / DAYTIME RESTAURANT / SYNDICATE ROOMS AHU206
MEETING ROOMS 8-9 / DAYTIME RESTAURANT / SYNDICATE ROOMS AHU207
-
-
08 -NEW RESTAURANT AHU3
09 -NEW RESTAURANT AHU3
10 -KITCHEN AHU4 SUPPLY
21 -
LABELING DETAILS
22 -
LABELING DETAILS
LABELING DETAILS
LABELING DETAILS
11 KITCHEN EXTRACT & GROUND FLOOR TOILET EXTRACT UNIT
12 -
13 -
-
OUTSTATION WIRING
OUTSTATION WIRING
OUTSTATION WIRING
L1
400V INCOMING MAINSUPPLY
FED FROM MCC1
N E
E
L1 L2 L3 N
T1 T2 T3 N
160 AMPMAIN DOORINTERLOCKEDISOLATOR
230V
24V
200VATX
502
1
N
L1407
24V0
CB16A
CB26A
24V~1
503
407
24V CCT
FR/1
24V~
24V SUPPLIES TOBMS SECTION
124V CCT
NL1
CONTROLCIRCUIT
LIVE
W
0
24V
FIRE ALARM INTERLOCK(REMOVE LINK IF REQUIRED)
1 2
501
L2 L3
L3
L2
L2 L3
230V SUPPLY TOSERVICE SOCKET
MCB26A
230V SUPPLYTO TREND
OUTSTATION
MCB32A
FR4
FR1
425
2 253 26
R
504
FIREALARM
FR/2
3 4 5
NORMAL OFFEXT. ONLY
FIREMANSSWITCH
FN1 14
262 42
FE1 1 274 4
FN1 FE1 4
2 463 474 62
3 484 66
FE2 1 684
FE2 4
2 86FN2 1
467
2 824
FN2
3 874 02
FN3 11
1111
FN3
401 402 403 404
405 406 407
FS1
FN/1
FIREMANS SWITCHNORMAL
409
FE/1
FIREMANS SWITCHEXTRACT ONLY
410
FR/3
FIREALARM
408MCB16A
230V CCTFEED TODAMPERS
411230V CCT
TODAMPERS
4 33
412
3 884 110
19
0
20 21 22 23 24 25 26 27 28 29
DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN
DRG No.
SCALEREVISIONDATE
SHEET
INTERNAL/EXTERNAL WIRING DIAGRAMOF
BOILER ROOM CONTROL PANEL MCC3
Job-No2 of 22NTS
J.STONEMANJS15/06/2011
N
L1407
24V0
24V~124V CCT
L3
L2
407
1
0
N
24V
24V CCT
24V~
L3
L2
L1
ES1
ES1
133
10
KITCHENEMERGENCY STOP
KNOCK OFF BUTTON No.1
KITCHENGAS SOLENOID VALVE
L N
14 15
507
R2/2
EP-SW11
R1/2
508
GV/2
GAS VALVECLOSED
R
GAS VALVECLOSED
5
AUX
6 7
VS-PS6684
16 17
415
GV2
GV1
234
2 34
509
GV/1
KITCHENEMERGENCY STOP
KNOCK OFF BUTTON No.2
EP-SW11
6 7
AHU4 KITCHENSUPPLY FAN DPS(Make On Flow)
PA-604-90-IP65
8 9
KITCHENEXTRACT FAN DPS(Make On Flow)
PA-604-90-IP65
11 12 13
R12
R11
231
2 33
R1/1
AHU4 KITCHEN SUPPLYFAN AIR FLOW
413
R22
R21
232
2 33
R2/1
KITCHEN EXTRACT FANAIR FLOW
414
505
ES/1
MCB42A
FR/4
506
30 31 32 33 34 35 36 37 38 39
DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN
DRG No.
SCALEREVISIONDATE
SHEET
INTERNAL/EXTERNAL WIRING DIAGRAMOF
BOILER ROOM CONTROL PANEL MCC3
Job-No3 of 22NTS
J.STONEMANJS15/06/2011
N
24V0
407
1
0
N
24V
24V CCT
24V~
24V CCT
24V~
407
1
L3L3
L2
L1
L2
L1
G R
HOFF
AUTO
O/L95
96
97
98
C11
C11
143
517516
TRIPRUN
C1/1
515
5 - 8A
513
SUPPLY FANENABLE
MEETING ROOMS 1-7 AHU1SUPPLY FAN
LOCALISOLATOR
23 24 25
C1
MSB1
FLC11.4 A5.5kW
418
R53
R51
342
26 27
AHU1 FROSTTHERMOSTAT
ST-FRE1-IP65
4
1
2
R
518
FROST
R5/3
2 44
514
R3/2 R5/2
FROST419
3 44
DamperAux.
R4/1
AHU1 FRESH AIRINLET DAMPER
18 19 20 21
1 2 3
R32
R31
241
2 43
S3S1NM240A
22
HANDOFF
A
510
F/A DAMPERENABLE
417
R5/1
512
FN1/2
R41
R41
141
FrostStat
511
R3/1
F/A DAMPEROPENED
416
19230V CCT
G R
HOFF
AUTO
O/L95
96
97
98
C21
C21
148
525524
TRIPRUN
C2/1
523
5 - 8A
521
EXTRACT FANENABLE
MEETING ROOMS 1-7 AHU1EXTRACT FAN
LOCALISOLATOR
33 34 35
C2
MSB2
FLC11.4 A5.5kW
422
R6/2DamperAux.
R7/1
AHU1 EXHAUST AIRDAMPER
28 29 30 31
1 2 3
R62
R61
246
2 48
S3S1
32
HANDOFF
A
EXH. DAMPERENABLE
421
520
FN1/3
R71
R71
145
519
R6/1
EXH. DAMPEROPENED
420
230V CCT
/S1A NM240A /S1A
FE1/2
522
FE1/3
19
40 41 42 43 44 45 46 47 48 49
DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN
DRG No.
SCALEREVISIONDATE
SHEET
INTERNAL/EXTERNAL WIRING DIAGRAMOF
BOILER ROOM CONTROL PANEL MCC3
Job-No4 of 22NTS
J.STONEMANJS15/06/2011
N
24V0
407
1
0
N
24V
24V CCT
24V~
24V CCT
24V~
407
1
L3L3
L2
L1
L2
L1
INTERFACE
L N 12 13SUPPLY
36 37
R8/1
6 7
40
R92
R91
252
G
CONDENSER 1ENABLE
AUTO
R81
R81
151
526
RUN
MEETING ROOMS 1-7 AHU1 CONDENSER 1
START/STOP FAULT4 5
38 39
RUN
R
527
FAULT
R9/2
OFF
LOCALISOLATOR
R9/1
CONDENSER 1FAULT
2 53
CONTROL CABLE
CONDENSER
423 424
FEED FROM ELSEWHERE
INTERFACE
L N 12 13SUPPLY
41 42
R10/1
6 7
45
R112
R111
255
G
CONDENSER 2ENABLE
AUTO
R101
R101
154
528
RUN
MEETING ROOMS 1-7 AHU1 CONDENSER 2
START/STOP FAULT4 5
43 44
RUN
R
529
FAULT
R11/2
OFF
LOCALISOLATOR
R11/1
CONDENSER 2FAULT
2 55
CONTROL CABLE
CONDENSER
425 426
50 51 52 53 54 55 56 57 58 59
DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN
DRG No.
SCALEREVISIONDATE
SHEET
INTERNAL/EXTERNAL WIRING DIAGRAMOF
BOILER ROOM CONTROL PANEL MCC3
Job-No5 of 22NTS
J.STONEMANJS15/06/2011
N
24V0
407
1
0
N
24V
24V CCT
24V~
24V CCT
24V~
407
1
L3L3
L2
L1
L2
L1
G R
HOFF
AUTO
O/L95
96
97
98
C31
C31
163
537536
TRIPRUN
C3/1
535
5 - 8A
533
SUPPLY FANENABLE
MEETING ROOMS 8-9 / DAYTIME RESTAURANT / SYNDICATE ROOMS AHU2SUPPLY FAN
LOCALISOLATOR
51 52 53
C3
MSB3
FLC11.4 A5.5kW
429
R143
R141
362
54 55
AHU2 FROSTTHERMOSTAT
ST-FRE1-IP65
4
1
2
R
538
FROST
R14/3
2 64
534
R12/2 R14/2
FROST430
3 64
DamperAux.
R13/1
AHU2 FRESH AIRINLET DAMPER
46 47 48 49
1 2 3
R122
R121
261
2 63
S3S1NM240A
50
HANDOFF
A
530
F/A DAMPERENABLE
428
R14/1
532
FN1/4
R131
R131
161
FrostStat
531
R12/1
F/A DAMPEROPENED
427
19230V CCT
G R
HOFF
AUTO
O/L95
96
97
98
C41
C41
168
545544
TRIPRUN
C4/1
543
5 - 8A
541
EXTRACT FANENABLE
MEETING ROOMS 8-9 / DAYTIME RESTAURANT / SYNDICATE ROOMS AHU2EXTRACT FAN
LOCALISOLATOR
61 62 63
C4
MSB4
FLC11.4 A5.5kW
433
R15/2DamperAux.
R16/1
AHU2 EXHAUST AIRDAMPER
56 57 58 59
1 2 3
R152
R151
266
2 68
S3S1
60
HANDOFF
A
EXH. DAMPERENABLE
432
540
FN2/1
R161
R161
165
539
R15/1
EXH. DAMPEROPENED
431
230V CCT
/S1A NM240A /S1A
FE1/4
542
FE2/1
19
60 61 62 63 64 65 66 67 68 69
DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN
DRG No.
SCALEREVISIONDATE
SHEET
INTERNAL/EXTERNAL WIRING DIAGRAMOF
BOILER ROOM CONTROL PANEL MCC3
Job-No6 of 22NTS
J.STONEMANJS15/06/2011
N
24V0
407
1
0
N
24V
24V CCT
24V~
24V CCT
24V~
407
1
L3L3
L2
L1
L2
L1
INTERFACE
L N 12 13SUPPLY
64 65
R17/1
6 7
68
R182
R181
272
G
CONDENSER 1ENABLE
AUTO
R171
R171
171
546
RUN
MEETING ROOMS 8-9 / DAYTIME RESTAURANT / SYNDICATE ROOMSAHU2 CONDENSER 1
START/STOP FAULT4 5
66 67
RUN
R
547
FAULT
R18/2
OFF
LOCALISOLATOR
R18/1
CONDENSER 1FAULT
2 73
CONTROL CABLE
CONDENSER
434 435
FEED FROM ELSEWHERE
INTERFACE
L N 12 13SUPPLY
69 70
R19/1
6 7
73
R202
R201
275
G
CONDENSER 2ENABLE
AUTO
R191
R191
174
548
RUN
START/STOP FAULT4 5
71 72
RUN
R
549
FAULT
R20/2
OFF
LOCALISOLATOR
R20/1
CONDENSER 2FAULT
2 75
CONTROL CABLE
CONDENSER
436 437
FEED FROM ELSEWHERE
MEETING ROOMS 8-9 / DAYTIME RESTAURANT / SYNDICATE ROOMSAHU2 CONDENSER 2
70 71 72 73 74 75 76 77 78 79
DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN
DRG No.
SCALEREVISIONDATE
SHEET
INTERNAL/EXTERNAL WIRING DIAGRAMOF
BOILER ROOM CONTROL PANEL MCC3
Job-No7 of 22NTS
J.STONEMANJS15/06/2011
N
24V0
407
1
0
N
24V
24V CCT
24V~
24V CCT
24V~
407
1
L3L3
L2
L1
L2
L1
G R
HOFF
AUTO
O/L95
96
97
98
C51
C51
183
557556
TRIPRUN
C5/1
555
5 - 8A
553
SUPPLY FANENABLE
NEW RESTAURANT AHU3SUPPLY FAN
LOCALISOLATOR
79 80 81
C5
MSB5
FLC11.4 A5.5kW
440
R233
R231
382
82 83
AHU3 FROSTTHERMOSTAT
ST-FRE1-IP65
4
1
2
R
558
FROST
R23/3
2 84
554
R21/2 R23/2
FROST441
3 84
DamperAux.
R22/1
AHU3 FRESH AIRINLET DAMPER
74 75 76 77
1 2 3
R212
R211
281
2 83
S3S1NM240A
78
HANDOFF
A
550
F/A DAMPERENABLE
439
R23/1
552
FN2/2
R221
R221
181
FrostStat
551
R21/1
F/A DAMPEROPENED
438
19230V CCT
G R
HOFF
AUTO
O/L95
96
97
98
C61
C61
188
565564
TRIPRUN
C6/1
563
5 - 8A
561
EXTRACT FANENABLE
NEW RESTAURANT AHU3EXTRACT FAN
LOCALISOLATOR
89 90 91
C6
MSB6
FLC11.4 A5.5kW
444
R24/2DamperAux.
R25/1
AHU3 EXHAUST AIRDAMPER
84 85 86 87
1 2 3
R242
R241
286
2 88
S3S1
88
HANDOFF
A
EXH. DAMPERENABLE
443
560
FN2/3
R251
R251
185
559
R24/1
EXH. DAMPEROPENED
442
230V CCT
/S1A NM240A /S1A
FE2/2
562
FE2/3
19
80 81 82 83 84 85 86 87 88 89
DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN
DRG No.
SCALEREVISIONDATE
SHEET
INTERNAL/EXTERNAL WIRING DIAGRAMOF
BOILER ROOM CONTROL PANEL MCC3
Job-No8 of 22NTS
J.STONEMANJS15/06/2011
N
24V0
407
1
0
N
24V
24V CCT
24V~
24V CCT
24V~
407
1
L3L3
L2
L1
L2
L1
INTERFACE
L N 12 13SUPPLY
92 93
R26/1
6 7
96
R272
R271
292
G
CONDENSER 1ENABLE
AUTO
R261
R261
191
566
RUN
NEW RESTAURANT AHU3 CONDENSER 1
START/STOP FAULT4 5
94 95
RUN
R
567
FAULT
R27/2
OFF
LOCALISOLATOR
R27/1
CONDENSER 1FAULT
2 93
CONTROL CABLE
CONDENSER
445 446
FEED FROM ELSEWHERE
INTERFACE
L N 12 13SUPPLY
97 98
R28/1
6 7
101
R292
R291
295
G
CONDENSER 2ENABLE
AUTO
R281
R281
194
568
RUN
START/STOP FAULT4 5
99 100
RUN
R
569
FAULT
R29/2
OFF
LOCALISOLATOR
R29/1
CONDENSER 2FAULT
2 95
CONTROL CABLE
CONDENSER
447 448
FEED FROM ELSEWHERE
NEW RESTAURANT AHU3 CONDENSER 2
90 91 92 93 94 95 96 97 98 99
DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN
DRG No.
SCALEREVISIONDATE
SHEET
INTERNAL/EXTERNAL WIRING DIAGRAMOF
BOILER ROOM CONTROL PANEL MCC3
Job-No9 of 22NTS
J.STONEMANJS15/06/2011
N
24V0
407
1
0
N
24V
24V CCT
24V~
24V CCT
24V~
407
1
L3L3
L2
L1
L2
L1
107 108 109 110 111
LOCALISOLATOR
U2 V2 W2 W1 U1 V1
LOW SPEED FLC 1.9kW 5.54AHIGH SPEED FLC 7.5kW 16A
KITCHEN AHU4SUPPLY FAN
112 113 114
T11
T11
1106
Delay On0-30 Sec
C82
C81
2105
T1/1
C7/2
HIGH LOWT1 = HIGH SPEED CHANGE DOWN TO LOW SPEED
SUPPLY FAN ENABLE
452 453451L HCOM
579
R31/1
AHU4 FRESH AIRINLET DAMPER
102 103 104 105
1 2 3
R302
R301
2101
2 103
S3S1NM240A
106
R32/1
572
FN2/4
R311
R311
1101
FrostStat
571
R30/1
F/A DAMPEROPENED
449
/S1A
19230V CCT
R323
R321
3102
115 116
AHU4 FROSTTHERMOSTAT
ST-FRE1-IP65
4
1
2
R
583
FROST
R32/3
2 107
R32/2
FROST454
3 107
573
R30/2DamperAux.
HANDOFF
A
570
F/A DAMPERENABLE
450
HANDOFF
A
G R
O/L95
96
97
98
C72
C71
2104
577
HIGHTRIP
C7/1
574
11 - 17A
HIGHRUN
2 106
581
G R
O/L95
96
97
98
582
LOWTRIP
C8/1
578
4 - 6.3A
LOWRUN
580
Sht-06
C7
MSB7HIGH
C8
MSB8LOW
HIGH LOW
576
575C8/2
2 104
100 101 102 103 104 105 106 107 108 109
DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN
DRG No.
SCALEREVISIONDATE
SHEET
INTERNAL/EXTERNAL WIRING DIAGRAMOF
BOILER ROOM CONTROL PANEL MCC3
Job-No10 of 22NTS
J.STONEMANJS15/06/2011
N
24V0
407
1
0
N
24V
24V CCT
24V~
24V CCT
24V~
407
1
L3L3
L2
L1
L2
L1
117 118 119 120 121
LOCALISOLATOR
U2 V2 W2 W1 U1 V1
KITCHEN EXTRACT FAN
122 123 124
T21
T21
1113
Delay On0-30 Sec
C102
C101
2113
T2/1
C9/2
HIGH LOWT2 = HIGH SPEED CHANGE DOWN TO LOW SPEED
EXTRACT FAN ENABLEL HCOM
590
HANDOFF
A
G R
O/L95
96
97
98
C92
C91
2111
588587HIGHTRIP
C9/1
585HIGHRUN
2 113
592
G R
O/L95
96
97
98
593
LOWTRIP
C10/1
589LOWRUN
591
FN3/1584
FE2/4
586
2 111
C10/2
LOW SPEED FLC 1.9kW 5.54AHIGH SPEED FLC 7.5kW 16A
456 457455
HANDOFF
AUTO
EXTRACT UNITENABLE
125 126
LOCALISOLATOR
22 21
GROUND FLOOR TOILET EXTRACT UNITAF500 CONTROL PANEL
R331
R331
1116
594
25
130
15 16
COMMONRUN
129
G
RUN
132
19 20
COMMONFAULT
131
R342
R341
2117
R
595
R34/1
FAULT
128
R33/1
127
L N
3 6
3 6
1 5
1 5
FLAP B FLAP A2 7
2 7
4 8
4 8
FAN A FAN B
MCB56A
FLO226-WH TWIN FAN1.31kW 5.7A
458
11 - 17A 4 - 6.3A
R34/2
EXTRACT UNITFAULT
459
2 117
Sht-03
C9
MSB9HIGH
C10
MSB10LOW
133 - 200 SPARE Nos ONLY
460 - 500 SPARE Nos. ONLY
110 111 112 113 114 115 116 117 118 119
DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN
DRG No.
SCALEREVISIONDATE
SHEET
INTERNAL/EXTERNAL WIRING DIAGRAMOF
BOILER ROOM CONTROL PANEL MCC3
Job-No11 of 22NTS
J.STONEMANJS15/06/2011
16
4846
1
1 32
+ 0
E E
2
4 65
+ 0
E E
3
7 98
+ 0 4
10 1211
+ 0
E E
5
13 1514
+ 0 6
16 1817
+ 0
E E
7
19 2120
+ 0 8
22 2423
+ 0
E E
9
25 2726
+ 0 10
28 3029
+ 0
E E
47P 015
4543 44P 014
4240 41P 013
3937 38P 012
3634 35P 011
3331 32P 0
P24 240
A100-240V
~ TRS232
IQ 3XCITE/96/LAN/100-24024VDC AUXSUPPLY
MUST BEEARTHED
DIN RAILMUST BEEARTHED
230V OSSUPPLY
RCDSOCKET
230V RCDSUPPLY
T T T
D I T V
DIGITALCURRENT
VOLTAGETHERMISTOR
T
EARTHLINK
TTT T T T T
24V
24V~1
0
1
0
24V SUPPLIES FROMPOWER SECTION
I.T. NETWORKFROM ETHERNET
SWITCH'POSSIBLE FUTURE'
201 202 203 204 205 206 207 208 209 210 211 212
AHU1HEATING
VALVE
5 1LR24A-SR
2
221 222 223 224 225 226
R322
24V~24V
12345
213 214
* *
AHU4SUPPLY
AIRTEMP
215 216
* *
AHU4OFF FROST
COILTEMP
TT522/A TT522/A
217 218
* *
219 220
KITCHENEXTRACT
AIRTEMP
TT522/A
AHU3HEATING
VALVE
5 1LR24A-SR
2
227 228 229
R322
401 402 403 404 406 405
SPARE
AHU4HEATING
VALVE
5 1LR24A-SR
2
230 231 232
R322
AHU2HEATING
VALVE
5 1LR24A-SR
2
R322
* *
AHU2SUPPLY
AIRTEMP
* *
AHU2EXTRACT
AIRTEMP
TT522/A TT522/A* *
AHU3SUPPLY
AIRTEMP
* *
AHU3EXTRACT
AIRTEMP
TT522/A TT522/A* *
AHU1SUPPLY
AIRTEMP
* *
AHU1EXTRACT
AIRTEMP
TT522/A TT522/A
AHU4FROST COIL
VALVE
5 1LR24A-SR
2
233 234 235
R322
SPARE
236 237 238
DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN
DRG No.
SCALEREVISIONDATE
SHEET
INTERNAL/EXTERNAL WIRING DIAGRAMOF
BOILER ROOM CONTROL PANEL MCC3
Job-No12 of 22NTS
J.STONEMANJS15/06/2011
~ T
1 2
~ T
3 4
~ T
5 6
~ T
7 8
~ T
9 10
~ T
11 12
~ T
13 14
~ T
15 16
1 2 3 4 5 6 7 8
XCITE/IO/16DI (MODULE 2)12345
54321
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
9 10 11 12 13 14 15 16~ T ~ T ~ T ~ T ~ T ~ T ~ T ~ T
~ T
1 2
~ T
3 4
~ T
5 6
~ T
7 8
~ T
9 10
~ T
11 12
~ T
13 14
~ T
15 16
1 2 3 4 5 6 7 8
FIREALARM
FIREMANSSWITCHNORMAL
FIREMANSSWITCH
EXTRACTONLY
KITCHENGAS
VALVECLOSED
XCITE/IO/16DI (MODULE 1)12345
54321
408 409 410 415
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
9 10 11 12 13 14 15 16~ T ~ T ~ T ~ T ~ T ~ T ~ T ~ T
247 248
AHU1EXTRACT
FILTERPA-604-90
AHU1F/A
DAMPEROPENED
AHU1FROST
AHU1EXHAUSTDAMPEROPENED
AHU1CONDENSER
1FAULT
416 419 420 424
239 240
AHU1SUPPLY FAN
DPSPA-604-90
241 242
AHU1EXT.FAN
DPSPA-604-90
243 244
AHU1PANELFILTER
PA-604-90
245 246
AHU1BAG
FILTERPA-604-90
AHU2F/A
DAMPEROPENED
427AHU2
FROST
430
AHU2EXHAUSTDAMPEROPENED
431
AHU3F/A
DAMPEROPENED
438AHU1
CONDENSER2
FAULT
426
249 250
AHU2SUPPLY FAN
DPSPA-604-90
251 252 253 254
AHU2EXTRACTFAN DPSPA-604-90
AHU2PANELFILTER
PA-604-90
AHU2CONDENSR
1FAULT
435
AHU2CONDENSR
2FAULT
437
255 256
AHU2BAG
FILTERPA-604-90
257 258
AHU2EXTRACT
FILTERPA-604-90
AHU3FROST
441AHU3
EXHAUSTDAMPEROPENED
442AHU3
CONDENSR1
FAULT
446AHU3
CONDENSR2
FAULT
448
259 260
AHU3SUPPLY FAN
DPSPA-604-90
261 262
AHU3EXT.FAN
DPSPA-604-90
263 264
AHU3PANELFILTER
PA-604-90
DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN
DRG No.
SCALEREVISIONDATE
SHEET
INTERNAL/EXTERNAL WIRING DIAGRAMOF
BOILER ROOM CONTROL PANEL MCC3
Job-No13 of 22NTS
J.STONEMANJS15/06/2011
~ T
1 2
~ T
3 4
~ T
5 6
~ T
7 8
~ T
9 10
~ T
11 12
~ T
13 14
~ T
15 16
1 2 3 4 5 6 7 8
XCITE/IO/16DI (MODULE 3)12345
54321
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
9 10 11 12 13 14 15 16~ T ~ T ~ T ~ T ~ T ~ T ~ T ~ T
277 278 279
XCITE/IO/8UI (MODULE 4)12345
54321
MUST BEEARTHED
1
1 32
+ 0 2
4 65
+ 0
E E
3
7 98
+ 0 4
10 1211
+ 0
E E
T T T T
FLOWTEMP
* *
RETURNTEMP
TT541/A
POOL AHU HEAT METER
280 281
TT541/A* *
282 283 284 285
GASMETER
CPT50* *
KITCHEN
AHU4F/A
DAMPEROPENED
AHU4FROST
449 454
AHU4PANELFILTER
PA-604-90
AHU4BAG
FILTERPA-604-90
269 270 271 272
GROUNDFLOORTOILET
EXTRACTUNIT
FAULT
459
POOL AHUHEATING
HOT WATERMETER
* * MW-HF-50
273 274
KITCHENEXTRACT
FILTERPA-604-90
275 276
KITCHENCHEFS SWITCH
265 266
AHU3BAG
FILTERPA-604-90
267 268
AHU3EXTRACT
FILTERPA-604-90
AHU4SUPPLYFAN AIRFLOW
KITCHENEXTRACTFAN AIRFLOW
413 414
10
2
DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN
DRG No.
SCALEREVISIONDATE
SHEET
INTERNAL/EXTERNAL WIRING DIAGRAMOF
BOILER ROOM CONTROL PANEL MCC3
Job-No14 of 22NTS
J.STONEMANJS15/06/2011
1
1 32NC C 2
4 65
3
7 98
4
10 1211NC C NC C NC C
XCITE/IO/8DO (MODULE 5)
AHU1F/A DAMPER
ENABLE417
AHU1SUPPLY FAN
ENABLE418
423AHU1
CONDENSER1
ENABLE
425
12345
54321
24V CCT
1
1 32NC C 2
4 65
3
7 98
4
10 1211NC C NC C NC C
XCITE/IO/8DO (MODULE 6)12345
54321
8
2422 23
7
2119 20
6
1816 17
5
1513 14C NC C NC C NC C NC
286 287 288
1 2 3NM240A
AHU1 HEAT EXCHANGERBYPASS DAMPER
411
230V CCTTO
DAMPERS412
L N
434
AHU2CONDENSER
1ENABLE
1
1 32NC C 2
4 65
3
7 98
4
10 1211NC C NC C NC C
XCITE/IO/8DO (MODULE 7)12345
54321
289 290 291
1 2 3NM240A
AHU2 HEAT EXCHANGERBYPASS DAMPER
8
2422 23
7
2119 20
6
1816 17
5
1513 14C NC C NC C NC C NC 8
2422 23
7
2119 20
6
1816 17
5
1513 14C NC C NC C NC C NC
292 293 294
1 2 3NM240A
AHU3 HEAT EXCHANGERBYPASS DAMPER
24V CCT
N
L
407
407407
407
19 19
421
AHU1EXHAUSTDAMPERENABLE
AHU1EXTRACT
FANENABLE
422
AHU1CONDENSER
2ENABLE
24V CCT407
428AHU2
F/A DAMPERENABLE
AHU2SUPPLY FAN
ENABLE429 432
AHU2EXHAUSTDAMPERENABLE
AHU2EXTRACT
FANENABLE
433
436AHU2
CONDENSER2
ENABLE
439AHU3
F/A DAMPERENABLE
440AHU3
SUPPLY FANENABLE
445
AHU3CONDENSER
1ENABLE
443
AHU3EXHAUSTDAMPERENABLE
AHU3EXTRACT
FANENABLE
444 447
AHU3CONDENSER
2ENABLE
450AHU4
F/A DAMPERENABLE
AHU4SUPPLY FANLOW SPEED
ENABLE
AHU4SUPPLY FANHIGH SPEED
ENABLE
452 453451Com
295 - 400 SPARE Nos. ONLY
DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN
DRG No.
SCALEREVISIONDATE
SHEET
INTERNAL/EXTERNAL WIRING DIAGRAMOF
BOILER ROOM CONTROL PANEL MCC3
Job-No15 of 22NTS
J.STONEMANJS15/06/2011
T-R+ T+R-
COMMS OUT
T-R+ T+R-
COMMS IN
R-R+
LAN CARD
T+E T- R-R+ T+ T- E
COMMSCOMMS
TERMINATOR
KITCHENEXTRACT FANLOW SPEED
ENABLE
KITCHENEXTRACT FANHIGH SPEED
ENABLE456 457455
Com
1
1 32NC C 2
4 65
3
7 98
4
10 1211NC C NC C NC C
XCITE/IO/8DO (MODULE 8)12345
54321
24V CCT 407
458
GROUNDFLOORTOILET
EXTRACTUNIT
ENABLE
LAST IDENT USED - 595
DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN
DRG No.
SCALEREVISIONDATE
SHEET
INTERNAL/EXTERNAL WIRING DIAGRAMOF
BOILER ROOM CONTROL PANEL MCC3
Job-No16 of 22NTS
J.STONEMANJS15/06/2011
1200
300
1400
TX
OUTGOING TERMINALS
ISO
C2C1 C3 C4
CONSTRUCTION1NOTES
ETTAMOUNTING PLATEFINISH COLOUR
5
GALVANISED STEELRAL 7032
PROTECTION
6ACCESS
7INCOMING CABLES
8
IP65FRONTTOP
2
4
PROTECTIVE EARTH1CABLE COLOURS
L1 PHASEGREEN/YELLOWBROWN
L2 PHASEL3 PHASE5NEUTRAL6
BLACKGREYBLUE
24VAC ~724VAC 8DC +9
WHITEWHITEWHITE
24
T
DC -10 WHITE
3
TRUNKING 60mm & 40mmSPACING BETWEEN LABELS 10mm
MB4
MB3
MB2
MB1
DIST.
INTERNAL ARRANGEMENT
IQ 3XCITE I/O I/O
OUTGOING TERMINALS
I/O I/O
I/O I/O I/O I/O
400V
800
1
EXTERNAL ARRANGEMENT
2000
230V
C5 C6
MB6
MB5
T1
T2
9R
10
1R
11R
21R
41R
51R
61R
71R
82R
NF
RF
NF
NF
OE
ROE
R4R
5R
6R
7R
8R
VG
SE
1R
3R R
13
R2R
12R
22R
32R
42R
62R
71R
920
R25
R2R
82R
93R
13R
230
RINTERCONNECTING TERMINALS
5
2
6 7 8
9 10 11 12
13 14 15 16
17 18 19 20
3
C7 C8
MB8
MB7
C9 C10
MB10
MB9
3R
33R
4
DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN
DRG No.
SCALEREVISIONDATE
SHEET
GENERAL ARRANGEMENTOF
BOILER ROOM CONTROL PANEL MCC3
Job-No17 of 221:12.5 @ A3
J.STONEMANJS15/06/2011
135
20
105
BLACK TEXT ON WHITE TRAFFOLYTE LABELMAIN TEXT - 4mm (IF APPLICABLE)SUB-TEXT - 3mm
5
5
3
AS ABOVE1LABEL No. LAMP(S) TEXTMAIN TEXT DESCRIPTION (IF APPLICABLE)
AS ABOVE
3535
18 18
23 23
CONTROL
CIRCUIT
LIVE
FIRE
ALARM
135
20
105
BLACK TEXT ON WHITE TRAFFOLYTE LABELMAIN TEXT - 4mm (IF APPLICABLE)SUB-TEXT - 3mm
5
5
3
AS ABOVE2LABEL No. LAMP(S) TEXTMAIN TEXT DESCRIPTION (IF APPLICABLE)
AS ABOVE
3535
23
CLOSED
KITCHEN GAS VALVE
CL
DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN
DRG No.
SCALEREVISIONDATE
SHEET
LABELLING DETAILOF
BOILER ROOM CONTROL PANEL MCC3
Job-No18 of 221:1 @ A3
J.STONEMANJS15/06/2011
135
35
AUTO
105
23
RUN
23
TRIP
MEETING ROOMS 1-7
AHU1 EXTRACT FAN
3
23
NEW RESTAURANT AHU3 EXTRACT FAN 14
LABEL No. LAMP(S) TEXTMAIN TEXT DESCRIPTION
AS ABOVE
HAND
OFF
BLACK TEXT ON WHITE TRAFFOLYTE LABELMAIN TEXT - 4mm (IF APPLICABLE)SUB-TEXT - 3mm
20
3 RUN - FAULTGROUND FLOOR TOILET EXTRACT UNIT
AS ABOVE6 AS ABOVEMEETING ROOMS 8-9 / DAYTIME RESTAURANT / SYNDICATE ROOMS AHU2 EXTRACT FAN 10 AS ABOVE
135
18
35
AUTO
18
105
23
RUN
23
TRIP
MEETING ROOMS 1-7
AHU1 SUPPLY FAN
3
23
LABEL No. LAMP(S) TEXTMAIN TEXT DESCRIPTION
HAND
OFF
BLACK TEXT ON WHITE TRAFFOLYTE LABELMAIN TEXT - 4mm (IF APPLICABLE)SUB-TEXT - 3mm
20
9 AS ABOVEMEETING ROOMS 8-9 / DAYTIME RESTAURANT / SYNDICATE ROOMS AHU2 SUPPLY FAN 13 AS ABOVENEW RESTAURANT AHU3 SUPPLY FAN
AS ABOVE5 AS ABOVE
23
FROST
52.552.5CL
DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN
DRG No.
SCALEREVISIONDATE
SHEET
LABELLING DETAILOF
BOILER ROOM CONTROL PANEL MCC3
Job-No19 of 221:1 @ A3
J.STONEMANJS15/06/2011
135
35
105
MEETING ROOMS 1-7
AHU1 CONDENSER 1
3
23
AS ABOVE7LABEL No. LAMP(S) TEXTMAIN TEXT DESCRIPTION
AS ABOVE
BLACK TEXT ON WHITE TRAFFOLYTE LABELMAIN TEXT - 4mm (IF APPLICABLE)SUB-TEXT - 3mm
MEETING ROOMS 1-7 AHU1 CONDENSER 28 AS ABOVE
20
18 18
23 23
RUN FAULT
MEETING ROOMS 8-9 / DAYTIME RESTAURANT / SYNDICATE ROOMS AHU2 CONDENSER 111 AS ABOVE
OFF
AUTO
135
105
LABEL No. LAMP(S) TEXTMAIN TEXT DESCRIPTION
BLACK TEXT ON WHITE TRAFFOLYTE LABELMAIN TEXT - 4mm (IF APPLICABLE)SUB-TEXT - 3mm
AS ABOVE4 AS ABOVE
MEETING ROOMS 8-9 / DAYTIME RESTAURANT / SYNDICATE ROOMS AHU2 CONDENSER 212 AS ABOVENEW RESTAURANT AHU3 CONDENSER 115 AS ABOVENEW RESTAURANT AHU3 CONDENSER 216 AS ABOVE
DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN
DRG No.
SCALEREVISIONDATE
SHEET
LABELLING DETAILOF
BOILER ROOM CONTROL PANEL MCC3
Job-No20 of 221:1 @ A3
J.STONEMANJS15/06/2011
135
18
35
AUTO
18
105
23
HIGH SPEED
RUN
23
HIGH SPEED
TRIP
KITCHEN AHU4 SUPPLY FAN
3
23
LABEL No. LAMP(S) TEXTMAIN TEXT DESCRIPTION
HAND
OFF
BLACK TEXT ON WHITE TRAFFOLYTE LABELMAIN TEXT - 4mm (IF APPLICABLE)SUB-TEXT - 3mm
20
AS ABOVE17 AS ABOVE
23
FROST
135
35
105
KITCHEN AHU4 SUPPLY FAN
3
AS ABOVE18LABEL No. LAMP(S) TEXTMAIN TEXT DESCRIPTION
AS ABOVE
BLACK TEXT ON WHITE TRAFFOLYTE LABELMAIN TEXT - 4mm (IF APPLICABLE)SUB-TEXT - 3mm
20
18 18
23 23
LOW SPEED
RUN
LOW SPEED
TRIP
CL
DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN
DRG No.
SCALEREVISIONDATE
SHEET
LABELLING DETAILOF
BOILER ROOM CONTROL PANEL MCC3
Job-No21 of 221:1 @ A3
J.STONEMANJS15/06/2011
135
18
35
AUTO
18
105
23
HIGH SPEED
RUN
23
HIGH SPEED
TRIP
KITCHEN EXTRACT FAN
3
23
LABEL No. LAMP(S) TEXTMAIN TEXT DESCRIPTION
HAND
OFF
BLACK TEXT ON WHITE TRAFFOLYTE LABELMAIN TEXT - 4mm (IF APPLICABLE)SUB-TEXT - 3mm
20
AS ABOVE19 AS ABOVE
135
35
105
KITCHEN EXTRACT FAN
3
AS ABOVE20LABEL No. LAMP(S) TEXTMAIN TEXT DESCRIPTION
AS ABOVE
BLACK TEXT ON WHITE TRAFFOLYTE LABELMAIN TEXT - 4mm (IF APPLICABLE)SUB-TEXT - 3mm
20
18 18
23 23
LOW SPEED
RUN
LOW SPEED
TRIP
DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN
DRG No.
SCALEREVISIONDATE
SHEET
LABELLING DETAILOF
BOILER ROOM CONTROL PANEL MCC3
Job-No22 of 221:1 @ A3
J.STONEMANJS15/06/2011