control panel mcc3 symbol legend

22
KEY TO COIL/CONTACT GRID REFERENCE 2 21 22 CONTACT No. 2 REFERENCE TO CONTACTOR/RELAY 1 R34 No. OF CONTACTS CONTROL PANEL MCC3 2 POLE CONTACT TERMINAL NORMALLY OPEN CONTACT NORMALLY CLOSED CONTACT RELAY COIL CONTACTOR COIL GRID REFERENCE CURRENT TRANSFORMER SYMBOL LEGEND PUSHBUTTON MCB NEUTRAL LINK PUSHBUTTON HAND OFF AUTO 3 POSITION SELECTOR SWITCH No.1 No.2 2 POSITION SELECTOR SWITCH D.P SWITCH 4A FUSED SPUR GRID REFERENCE 1ST DIGIT INDICATES SHEET No. 2ND DIGIT INDICATED GRID 0-9 FUSE F1 1A B1 4A 25 BUZZER PANEL COLOUR KEY BLACK - PANEL WIRING BLUE - PANEL COMPONENTS GREEN - FIELD WIRING & EQUIPMENT R1 2 R1 1 2 2 22 22 C1 2 LAMP LAMP COLOUR R INDEX INCOMING MAINS & CONTROL CIRCUITS DESCRIPTION 01 02 SHEET No. INDEX & LEGEND OF SYMBOLS ISSUE REVISION/ KITCHEN GAS VALVE 03 - - 3 04 14 - - MEETING ROOMS 1-7 AHU1 SHEET DATE ISSUE SCALE DRG No. DRAWN CHECKED DATE ISSUE No. ISSUE DETAILS Job-No 1 of 22 3 15/06/2011 NTS J.STONEMAN JS 1 FOR APPROVAL 17/06/2011 2 FOR MANUFACTURE 21/06/2011 3 AS BUILT 15/08/2011 19 20 - - OUTSTATION WIRING GENERAL ARRANGEMENT LABELING DETAILS 05 - MEETING ROOMS 1-7 AHU1 15 - OUTSTATION WIRING 16 - 17 - 18 - MEETING ROOMS 8-9 / DAYTIME RESTAURANT / SYNDICATE ROOMS AHU2 06 MEETING ROOMS 8-9 / DAYTIME RESTAURANT / SYNDICATE ROOMS AHU2 07 - - 08 - NEW RESTAURANT AHU3 09 - NEW RESTAURANT AHU3 10 - KITCHEN AHU4 SUPPLY 21 - LABELING DETAILS 22 - LABELING DETAILS LABELING DETAILS LABELING DETAILS 11 KITCHEN EXTRACT & GROUND FLOOR TOILET EXTRACT UNIT 12 - 13 - - OUTSTATION WIRING OUTSTATION WIRING OUTSTATION WIRING

Upload: others

Post on 10-Nov-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

KEY TO COIL/CONTACT GRID REFERENCE

2

2122

CONTACT No.2

REFERENCE TO CONTACTOR/RELAY

1

R34No. OF CONTACTS

CONTROL PANEL MCC3

2 POLECONTACT

TERMINAL

NORMALLY OPENCONTACT

NORMALLY CLOSEDCONTACT

RELAYCOIL

CONTACTORCOIL

GRIDREFERENCE

CURRENTTRANSFORMER

SYMBOL LEGENDPUSHBUTTON

MCB

NEUTRALLINK

PUSHBUTTON

HANDOFF

AUTO

3 POSITIONSELECTOR SWITCH

No.1 No.2

2 POSITIONSELECTOR SWITCH

D.PSWITCH

4A FUSEDSPUR

GRID REFERENCE1ST DIGIT INDICATES SHEET No.2ND DIGIT INDICATED GRID 0-9

FUSEF11A

B1

4A

25

BUZZER

PANEL COLOUR KEYBLACK - PANEL WIRINGBLUE - PANEL COMPONENTSGREEN - FIELD WIRING & EQUIPMENT

R12

R112

22222

C12

LAMP

LAMP COLOURR

INDEX

INCOMING MAINS & CONTROL CIRCUITS

DESCRIPTION

01

02

SHEET No.

INDEX & LEGEND OF SYMBOLSISSUE

REVISION/

KITCHEN GAS VALVE03

-

-

3

04

14 -

-MEETING ROOMS 1-7 AHU1

SHEET

DATE

ISSUE

SCALE

DRG No.

DRAWN

CHECKED

DATEISSUE No. ISSUE DETAILS

Job-No

1 of 22

3

15/06/2011

NTS

J.STONEMAN

JS

1 FOR APPROVAL 17/06/20112 FOR MANUFACTURE 21/06/20113 AS BUILT 15/08/2011

19

20

-

-

OUTSTATION WIRING

GENERAL ARRANGEMENT

LABELING DETAILS

05 -MEETING ROOMS 1-7 AHU1

15 -OUTSTATION WIRING

16 -

17 -

18 -

MEETING ROOMS 8-9 / DAYTIME RESTAURANT / SYNDICATE ROOMS AHU206

MEETING ROOMS 8-9 / DAYTIME RESTAURANT / SYNDICATE ROOMS AHU207

-

-

08 -NEW RESTAURANT AHU3

09 -NEW RESTAURANT AHU3

10 -KITCHEN AHU4 SUPPLY

21 -

LABELING DETAILS

22 -

LABELING DETAILS

LABELING DETAILS

LABELING DETAILS

11 KITCHEN EXTRACT & GROUND FLOOR TOILET EXTRACT UNIT

12 -

13 -

-

OUTSTATION WIRING

OUTSTATION WIRING

OUTSTATION WIRING

L1

400V INCOMING MAINSUPPLY

FED FROM MCC1

N E

E

L1 L2 L3 N

T1 T2 T3 N

160 AMPMAIN DOORINTERLOCKEDISOLATOR

230V

24V

200VATX

502

1

N

L1407

24V0

CB16A

CB26A

24V~1

503

407

24V CCT

FR/1

24V~

24V SUPPLIES TOBMS SECTION

124V CCT

NL1

CONTROLCIRCUIT

LIVE

W

0

24V

FIRE ALARM INTERLOCK(REMOVE LINK IF REQUIRED)

1 2

501

L2 L3

L3

L2

L2 L3

230V SUPPLY TOSERVICE SOCKET

MCB26A

230V SUPPLYTO TREND

OUTSTATION

MCB32A

FR4

FR1

425

2 253 26

R

504

FIREALARM

FR/2

3 4 5

NORMAL OFFEXT. ONLY

FIREMANSSWITCH

FN1 14

262 42

FE1 1 274 4

FN1 FE1 4

2 463 474 62

3 484 66

FE2 1 684

FE2 4

2 86FN2 1

467

2 824

FN2

3 874 02

FN3 11

1111

FN3

401 402 403 404

405 406 407

FS1

FN/1

FIREMANS SWITCHNORMAL

409

FE/1

FIREMANS SWITCHEXTRACT ONLY

410

FR/3

FIREALARM

408MCB16A

230V CCTFEED TODAMPERS

411230V CCT

TODAMPERS

4 33

412

3 884 110

19

0

20 21 22 23 24 25 26 27 28 29

DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN

DRG No.

SCALEREVISIONDATE

SHEET

INTERNAL/EXTERNAL WIRING DIAGRAMOF

BOILER ROOM CONTROL PANEL MCC3

Job-No2 of 22NTS

J.STONEMANJS15/06/2011

N

L1407

24V0

24V~124V CCT

L3

L2

407

1

0

N

24V

24V CCT

24V~

L3

L2

L1

ES1

ES1

133

10

KITCHENEMERGENCY STOP

KNOCK OFF BUTTON No.1

KITCHENGAS SOLENOID VALVE

L N

14 15

507

R2/2

EP-SW11

R1/2

508

GV/2

GAS VALVECLOSED

R

GAS VALVECLOSED

5

AUX

6 7

VS-PS6684

16 17

415

GV2

GV1

234

2 34

509

GV/1

KITCHENEMERGENCY STOP

KNOCK OFF BUTTON No.2

EP-SW11

6 7

AHU4 KITCHENSUPPLY FAN DPS(Make On Flow)

PA-604-90-IP65

8 9

KITCHENEXTRACT FAN DPS(Make On Flow)

PA-604-90-IP65

11 12 13

R12

R11

231

2 33

R1/1

AHU4 KITCHEN SUPPLYFAN AIR FLOW

413

R22

R21

232

2 33

R2/1

KITCHEN EXTRACT FANAIR FLOW

414

505

ES/1

MCB42A

FR/4

506

30 31 32 33 34 35 36 37 38 39

DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN

DRG No.

SCALEREVISIONDATE

SHEET

INTERNAL/EXTERNAL WIRING DIAGRAMOF

BOILER ROOM CONTROL PANEL MCC3

Job-No3 of 22NTS

J.STONEMANJS15/06/2011

N

24V0

407

1

0

N

24V

24V CCT

24V~

24V CCT

24V~

407

1

L3L3

L2

L1

L2

L1

G R

HOFF

AUTO

O/L95

96

97

98

C11

C11

143

517516

TRIPRUN

C1/1

515

5 - 8A

513

SUPPLY FANENABLE

MEETING ROOMS 1-7 AHU1SUPPLY FAN

LOCALISOLATOR

23 24 25

C1

MSB1

FLC11.4 A5.5kW

418

R53

R51

342

26 27

AHU1 FROSTTHERMOSTAT

ST-FRE1-IP65

4

1

2

R

518

FROST

R5/3

2 44

514

R3/2 R5/2

FROST419

3 44

DamperAux.

R4/1

AHU1 FRESH AIRINLET DAMPER

18 19 20 21

1 2 3

R32

R31

241

2 43

S3S1NM240A

22

HANDOFF

A

510

F/A DAMPERENABLE

417

R5/1

512

FN1/2

R41

R41

141

FrostStat

511

R3/1

F/A DAMPEROPENED

416

19230V CCT

G R

HOFF

AUTO

O/L95

96

97

98

C21

C21

148

525524

TRIPRUN

C2/1

523

5 - 8A

521

EXTRACT FANENABLE

MEETING ROOMS 1-7 AHU1EXTRACT FAN

LOCALISOLATOR

33 34 35

C2

MSB2

FLC11.4 A5.5kW

422

R6/2DamperAux.

R7/1

AHU1 EXHAUST AIRDAMPER

28 29 30 31

1 2 3

R62

R61

246

2 48

S3S1

32

HANDOFF

A

EXH. DAMPERENABLE

421

520

FN1/3

R71

R71

145

519

R6/1

EXH. DAMPEROPENED

420

230V CCT

/S1A NM240A /S1A

FE1/2

522

FE1/3

19

40 41 42 43 44 45 46 47 48 49

DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN

DRG No.

SCALEREVISIONDATE

SHEET

INTERNAL/EXTERNAL WIRING DIAGRAMOF

BOILER ROOM CONTROL PANEL MCC3

Job-No4 of 22NTS

J.STONEMANJS15/06/2011

N

24V0

407

1

0

N

24V

24V CCT

24V~

24V CCT

24V~

407

1

L3L3

L2

L1

L2

L1

INTERFACE

L N 12 13SUPPLY

36 37

R8/1

6 7

40

R92

R91

252

G

CONDENSER 1ENABLE

AUTO

R81

R81

151

526

RUN

MEETING ROOMS 1-7 AHU1 CONDENSER 1

START/STOP FAULT4 5

38 39

RUN

R

527

FAULT

R9/2

OFF

LOCALISOLATOR

R9/1

CONDENSER 1FAULT

2 53

CONTROL CABLE

CONDENSER

423 424

FEED FROM ELSEWHERE

INTERFACE

L N 12 13SUPPLY

41 42

R10/1

6 7

45

R112

R111

255

G

CONDENSER 2ENABLE

AUTO

R101

R101

154

528

RUN

MEETING ROOMS 1-7 AHU1 CONDENSER 2

START/STOP FAULT4 5

43 44

RUN

R

529

FAULT

R11/2

OFF

LOCALISOLATOR

R11/1

CONDENSER 2FAULT

2 55

CONTROL CABLE

CONDENSER

425 426

50 51 52 53 54 55 56 57 58 59

DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN

DRG No.

SCALEREVISIONDATE

SHEET

INTERNAL/EXTERNAL WIRING DIAGRAMOF

BOILER ROOM CONTROL PANEL MCC3

Job-No5 of 22NTS

J.STONEMANJS15/06/2011

N

24V0

407

1

0

N

24V

24V CCT

24V~

24V CCT

24V~

407

1

L3L3

L2

L1

L2

L1

G R

HOFF

AUTO

O/L95

96

97

98

C31

C31

163

537536

TRIPRUN

C3/1

535

5 - 8A

533

SUPPLY FANENABLE

MEETING ROOMS 8-9 / DAYTIME RESTAURANT / SYNDICATE ROOMS AHU2SUPPLY FAN

LOCALISOLATOR

51 52 53

C3

MSB3

FLC11.4 A5.5kW

429

R143

R141

362

54 55

AHU2 FROSTTHERMOSTAT

ST-FRE1-IP65

4

1

2

R

538

FROST

R14/3

2 64

534

R12/2 R14/2

FROST430

3 64

DamperAux.

R13/1

AHU2 FRESH AIRINLET DAMPER

46 47 48 49

1 2 3

R122

R121

261

2 63

S3S1NM240A

50

HANDOFF

A

530

F/A DAMPERENABLE

428

R14/1

532

FN1/4

R131

R131

161

FrostStat

531

R12/1

F/A DAMPEROPENED

427

19230V CCT

G R

HOFF

AUTO

O/L95

96

97

98

C41

C41

168

545544

TRIPRUN

C4/1

543

5 - 8A

541

EXTRACT FANENABLE

MEETING ROOMS 8-9 / DAYTIME RESTAURANT / SYNDICATE ROOMS AHU2EXTRACT FAN

LOCALISOLATOR

61 62 63

C4

MSB4

FLC11.4 A5.5kW

433

R15/2DamperAux.

R16/1

AHU2 EXHAUST AIRDAMPER

56 57 58 59

1 2 3

R152

R151

266

2 68

S3S1

60

HANDOFF

A

EXH. DAMPERENABLE

432

540

FN2/1

R161

R161

165

539

R15/1

EXH. DAMPEROPENED

431

230V CCT

/S1A NM240A /S1A

FE1/4

542

FE2/1

19

60 61 62 63 64 65 66 67 68 69

DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN

DRG No.

SCALEREVISIONDATE

SHEET

INTERNAL/EXTERNAL WIRING DIAGRAMOF

BOILER ROOM CONTROL PANEL MCC3

Job-No6 of 22NTS

J.STONEMANJS15/06/2011

N

24V0

407

1

0

N

24V

24V CCT

24V~

24V CCT

24V~

407

1

L3L3

L2

L1

L2

L1

INTERFACE

L N 12 13SUPPLY

64 65

R17/1

6 7

68

R182

R181

272

G

CONDENSER 1ENABLE

AUTO

R171

R171

171

546

RUN

MEETING ROOMS 8-9 / DAYTIME RESTAURANT / SYNDICATE ROOMSAHU2 CONDENSER 1

START/STOP FAULT4 5

66 67

RUN

R

547

FAULT

R18/2

OFF

LOCALISOLATOR

R18/1

CONDENSER 1FAULT

2 73

CONTROL CABLE

CONDENSER

434 435

FEED FROM ELSEWHERE

INTERFACE

L N 12 13SUPPLY

69 70

R19/1

6 7

73

R202

R201

275

G

CONDENSER 2ENABLE

AUTO

R191

R191

174

548

RUN

START/STOP FAULT4 5

71 72

RUN

R

549

FAULT

R20/2

OFF

LOCALISOLATOR

R20/1

CONDENSER 2FAULT

2 75

CONTROL CABLE

CONDENSER

436 437

FEED FROM ELSEWHERE

MEETING ROOMS 8-9 / DAYTIME RESTAURANT / SYNDICATE ROOMSAHU2 CONDENSER 2

70 71 72 73 74 75 76 77 78 79

DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN

DRG No.

SCALEREVISIONDATE

SHEET

INTERNAL/EXTERNAL WIRING DIAGRAMOF

BOILER ROOM CONTROL PANEL MCC3

Job-No7 of 22NTS

J.STONEMANJS15/06/2011

N

24V0

407

1

0

N

24V

24V CCT

24V~

24V CCT

24V~

407

1

L3L3

L2

L1

L2

L1

G R

HOFF

AUTO

O/L95

96

97

98

C51

C51

183

557556

TRIPRUN

C5/1

555

5 - 8A

553

SUPPLY FANENABLE

NEW RESTAURANT AHU3SUPPLY FAN

LOCALISOLATOR

79 80 81

C5

MSB5

FLC11.4 A5.5kW

440

R233

R231

382

82 83

AHU3 FROSTTHERMOSTAT

ST-FRE1-IP65

4

1

2

R

558

FROST

R23/3

2 84

554

R21/2 R23/2

FROST441

3 84

DamperAux.

R22/1

AHU3 FRESH AIRINLET DAMPER

74 75 76 77

1 2 3

R212

R211

281

2 83

S3S1NM240A

78

HANDOFF

A

550

F/A DAMPERENABLE

439

R23/1

552

FN2/2

R221

R221

181

FrostStat

551

R21/1

F/A DAMPEROPENED

438

19230V CCT

G R

HOFF

AUTO

O/L95

96

97

98

C61

C61

188

565564

TRIPRUN

C6/1

563

5 - 8A

561

EXTRACT FANENABLE

NEW RESTAURANT AHU3EXTRACT FAN

LOCALISOLATOR

89 90 91

C6

MSB6

FLC11.4 A5.5kW

444

R24/2DamperAux.

R25/1

AHU3 EXHAUST AIRDAMPER

84 85 86 87

1 2 3

R242

R241

286

2 88

S3S1

88

HANDOFF

A

EXH. DAMPERENABLE

443

560

FN2/3

R251

R251

185

559

R24/1

EXH. DAMPEROPENED

442

230V CCT

/S1A NM240A /S1A

FE2/2

562

FE2/3

19

80 81 82 83 84 85 86 87 88 89

DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN

DRG No.

SCALEREVISIONDATE

SHEET

INTERNAL/EXTERNAL WIRING DIAGRAMOF

BOILER ROOM CONTROL PANEL MCC3

Job-No8 of 22NTS

J.STONEMANJS15/06/2011

N

24V0

407

1

0

N

24V

24V CCT

24V~

24V CCT

24V~

407

1

L3L3

L2

L1

L2

L1

INTERFACE

L N 12 13SUPPLY

92 93

R26/1

6 7

96

R272

R271

292

G

CONDENSER 1ENABLE

AUTO

R261

R261

191

566

RUN

NEW RESTAURANT AHU3 CONDENSER 1

START/STOP FAULT4 5

94 95

RUN

R

567

FAULT

R27/2

OFF

LOCALISOLATOR

R27/1

CONDENSER 1FAULT

2 93

CONTROL CABLE

CONDENSER

445 446

FEED FROM ELSEWHERE

INTERFACE

L N 12 13SUPPLY

97 98

R28/1

6 7

101

R292

R291

295

G

CONDENSER 2ENABLE

AUTO

R281

R281

194

568

RUN

START/STOP FAULT4 5

99 100

RUN

R

569

FAULT

R29/2

OFF

LOCALISOLATOR

R29/1

CONDENSER 2FAULT

2 95

CONTROL CABLE

CONDENSER

447 448

FEED FROM ELSEWHERE

NEW RESTAURANT AHU3 CONDENSER 2

90 91 92 93 94 95 96 97 98 99

DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN

DRG No.

SCALEREVISIONDATE

SHEET

INTERNAL/EXTERNAL WIRING DIAGRAMOF

BOILER ROOM CONTROL PANEL MCC3

Job-No9 of 22NTS

J.STONEMANJS15/06/2011

N

24V0

407

1

0

N

24V

24V CCT

24V~

24V CCT

24V~

407

1

L3L3

L2

L1

L2

L1

107 108 109 110 111

LOCALISOLATOR

U2 V2 W2 W1 U1 V1

LOW SPEED FLC 1.9kW 5.54AHIGH SPEED FLC 7.5kW 16A

KITCHEN AHU4SUPPLY FAN

112 113 114

T11

T11

1106

Delay On0-30 Sec

C82

C81

2105

T1/1

C7/2

HIGH LOWT1 = HIGH SPEED CHANGE DOWN TO LOW SPEED

SUPPLY FAN ENABLE

452 453451L HCOM

579

R31/1

AHU4 FRESH AIRINLET DAMPER

102 103 104 105

1 2 3

R302

R301

2101

2 103

S3S1NM240A

106

R32/1

572

FN2/4

R311

R311

1101

FrostStat

571

R30/1

F/A DAMPEROPENED

449

/S1A

19230V CCT

R323

R321

3102

115 116

AHU4 FROSTTHERMOSTAT

ST-FRE1-IP65

4

1

2

R

583

FROST

R32/3

2 107

R32/2

FROST454

3 107

573

R30/2DamperAux.

HANDOFF

A

570

F/A DAMPERENABLE

450

HANDOFF

A

G R

O/L95

96

97

98

C72

C71

2104

577

HIGHTRIP

C7/1

574

11 - 17A

HIGHRUN

2 106

581

G R

O/L95

96

97

98

582

LOWTRIP

C8/1

578

4 - 6.3A

LOWRUN

580

Sht-06

C7

MSB7HIGH

C8

MSB8LOW

HIGH LOW

576

575C8/2

2 104

100 101 102 103 104 105 106 107 108 109

DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN

DRG No.

SCALEREVISIONDATE

SHEET

INTERNAL/EXTERNAL WIRING DIAGRAMOF

BOILER ROOM CONTROL PANEL MCC3

Job-No10 of 22NTS

J.STONEMANJS15/06/2011

N

24V0

407

1

0

N

24V

24V CCT

24V~

24V CCT

24V~

407

1

L3L3

L2

L1

L2

L1

117 118 119 120 121

LOCALISOLATOR

U2 V2 W2 W1 U1 V1

KITCHEN EXTRACT FAN

122 123 124

T21

T21

1113

Delay On0-30 Sec

C102

C101

2113

T2/1

C9/2

HIGH LOWT2 = HIGH SPEED CHANGE DOWN TO LOW SPEED

EXTRACT FAN ENABLEL HCOM

590

HANDOFF

A

G R

O/L95

96

97

98

C92

C91

2111

588587HIGHTRIP

C9/1

585HIGHRUN

2 113

592

G R

O/L95

96

97

98

593

LOWTRIP

C10/1

589LOWRUN

591

FN3/1584

FE2/4

586

2 111

C10/2

LOW SPEED FLC 1.9kW 5.54AHIGH SPEED FLC 7.5kW 16A

456 457455

HANDOFF

AUTO

EXTRACT UNITENABLE

125 126

LOCALISOLATOR

22 21

GROUND FLOOR TOILET EXTRACT UNITAF500 CONTROL PANEL

R331

R331

1116

594

25

130

15 16

COMMONRUN

129

G

RUN

132

19 20

COMMONFAULT

131

R342

R341

2117

R

595

R34/1

FAULT

128

R33/1

127

L N

3 6

3 6

1 5

1 5

FLAP B FLAP A2 7

2 7

4 8

4 8

FAN A FAN B

MCB56A

FLO226-WH TWIN FAN1.31kW 5.7A

458

11 - 17A 4 - 6.3A

R34/2

EXTRACT UNITFAULT

459

2 117

Sht-03

C9

MSB9HIGH

C10

MSB10LOW

133 - 200 SPARE Nos ONLY

460 - 500 SPARE Nos. ONLY

110 111 112 113 114 115 116 117 118 119

DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN

DRG No.

SCALEREVISIONDATE

SHEET

INTERNAL/EXTERNAL WIRING DIAGRAMOF

BOILER ROOM CONTROL PANEL MCC3

Job-No11 of 22NTS

J.STONEMANJS15/06/2011

16

4846

1

1 32

+ 0

E E

2

4 65

+ 0

E E

3

7 98

+ 0 4

10 1211

+ 0

E E

5

13 1514

+ 0 6

16 1817

+ 0

E E

7

19 2120

+ 0 8

22 2423

+ 0

E E

9

25 2726

+ 0 10

28 3029

+ 0

E E

47P 015

4543 44P 014

4240 41P 013

3937 38P 012

3634 35P 011

3331 32P 0

P24 240

A100-240V

~ TRS232

IQ 3XCITE/96/LAN/100-24024VDC AUXSUPPLY

MUST BEEARTHED

DIN RAILMUST BEEARTHED

230V OSSUPPLY

RCDSOCKET

230V RCDSUPPLY

T T T

D I T V

DIGITALCURRENT

VOLTAGETHERMISTOR

T

EARTHLINK

TTT T T T T

24V

24V~1

0

1

0

24V SUPPLIES FROMPOWER SECTION

I.T. NETWORKFROM ETHERNET

SWITCH'POSSIBLE FUTURE'

201 202 203 204 205 206 207 208 209 210 211 212

AHU1HEATING

VALVE

5 1LR24A-SR

2

221 222 223 224 225 226

R322

24V~24V

12345

213 214

* *

AHU4SUPPLY

AIRTEMP

215 216

* *

AHU4OFF FROST

COILTEMP

TT522/A TT522/A

217 218

* *

219 220

KITCHENEXTRACT

AIRTEMP

TT522/A

AHU3HEATING

VALVE

5 1LR24A-SR

2

227 228 229

R322

401 402 403 404 406 405

SPARE

AHU4HEATING

VALVE

5 1LR24A-SR

2

230 231 232

R322

AHU2HEATING

VALVE

5 1LR24A-SR

2

R322

* *

AHU2SUPPLY

AIRTEMP

* *

AHU2EXTRACT

AIRTEMP

TT522/A TT522/A* *

AHU3SUPPLY

AIRTEMP

* *

AHU3EXTRACT

AIRTEMP

TT522/A TT522/A* *

AHU1SUPPLY

AIRTEMP

* *

AHU1EXTRACT

AIRTEMP

TT522/A TT522/A

AHU4FROST COIL

VALVE

5 1LR24A-SR

2

233 234 235

R322

SPARE

236 237 238

DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN

DRG No.

SCALEREVISIONDATE

SHEET

INTERNAL/EXTERNAL WIRING DIAGRAMOF

BOILER ROOM CONTROL PANEL MCC3

Job-No12 of 22NTS

J.STONEMANJS15/06/2011

~ T

1 2

~ T

3 4

~ T

5 6

~ T

7 8

~ T

9 10

~ T

11 12

~ T

13 14

~ T

15 16

1 2 3 4 5 6 7 8

XCITE/IO/16DI (MODULE 2)12345

54321

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

9 10 11 12 13 14 15 16~ T ~ T ~ T ~ T ~ T ~ T ~ T ~ T

~ T

1 2

~ T

3 4

~ T

5 6

~ T

7 8

~ T

9 10

~ T

11 12

~ T

13 14

~ T

15 16

1 2 3 4 5 6 7 8

FIREALARM

FIREMANSSWITCHNORMAL

FIREMANSSWITCH

EXTRACTONLY

KITCHENGAS

VALVECLOSED

XCITE/IO/16DI (MODULE 1)12345

54321

408 409 410 415

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

9 10 11 12 13 14 15 16~ T ~ T ~ T ~ T ~ T ~ T ~ T ~ T

247 248

AHU1EXTRACT

FILTERPA-604-90

AHU1F/A

DAMPEROPENED

AHU1FROST

AHU1EXHAUSTDAMPEROPENED

AHU1CONDENSER

1FAULT

416 419 420 424

239 240

AHU1SUPPLY FAN

DPSPA-604-90

241 242

AHU1EXT.FAN

DPSPA-604-90

243 244

AHU1PANELFILTER

PA-604-90

245 246

AHU1BAG

FILTERPA-604-90

AHU2F/A

DAMPEROPENED

427AHU2

FROST

430

AHU2EXHAUSTDAMPEROPENED

431

AHU3F/A

DAMPEROPENED

438AHU1

CONDENSER2

FAULT

426

249 250

AHU2SUPPLY FAN

DPSPA-604-90

251 252 253 254

AHU2EXTRACTFAN DPSPA-604-90

AHU2PANELFILTER

PA-604-90

AHU2CONDENSR

1FAULT

435

AHU2CONDENSR

2FAULT

437

255 256

AHU2BAG

FILTERPA-604-90

257 258

AHU2EXTRACT

FILTERPA-604-90

AHU3FROST

441AHU3

EXHAUSTDAMPEROPENED

442AHU3

CONDENSR1

FAULT

446AHU3

CONDENSR2

FAULT

448

259 260

AHU3SUPPLY FAN

DPSPA-604-90

261 262

AHU3EXT.FAN

DPSPA-604-90

263 264

AHU3PANELFILTER

PA-604-90

DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN

DRG No.

SCALEREVISIONDATE

SHEET

INTERNAL/EXTERNAL WIRING DIAGRAMOF

BOILER ROOM CONTROL PANEL MCC3

Job-No13 of 22NTS

J.STONEMANJS15/06/2011

~ T

1 2

~ T

3 4

~ T

5 6

~ T

7 8

~ T

9 10

~ T

11 12

~ T

13 14

~ T

15 16

1 2 3 4 5 6 7 8

XCITE/IO/16DI (MODULE 3)12345

54321

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

9 10 11 12 13 14 15 16~ T ~ T ~ T ~ T ~ T ~ T ~ T ~ T

277 278 279

XCITE/IO/8UI (MODULE 4)12345

54321

MUST BEEARTHED

1

1 32

+ 0 2

4 65

+ 0

E E

3

7 98

+ 0 4

10 1211

+ 0

E E

T T T T

FLOWTEMP

* *

RETURNTEMP

TT541/A

POOL AHU HEAT METER

280 281

TT541/A* *

282 283 284 285

GASMETER

CPT50* *

KITCHEN

AHU4F/A

DAMPEROPENED

AHU4FROST

449 454

AHU4PANELFILTER

PA-604-90

AHU4BAG

FILTERPA-604-90

269 270 271 272

GROUNDFLOORTOILET

EXTRACTUNIT

FAULT

459

POOL AHUHEATING

HOT WATERMETER

* * MW-HF-50

273 274

KITCHENEXTRACT

FILTERPA-604-90

275 276

KITCHENCHEFS SWITCH

265 266

AHU3BAG

FILTERPA-604-90

267 268

AHU3EXTRACT

FILTERPA-604-90

AHU4SUPPLYFAN AIRFLOW

KITCHENEXTRACTFAN AIRFLOW

413 414

10

2

DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN

DRG No.

SCALEREVISIONDATE

SHEET

INTERNAL/EXTERNAL WIRING DIAGRAMOF

BOILER ROOM CONTROL PANEL MCC3

Job-No14 of 22NTS

J.STONEMANJS15/06/2011

1

1 32NC C 2

4 65

3

7 98

4

10 1211NC C NC C NC C

XCITE/IO/8DO (MODULE 5)

AHU1F/A DAMPER

ENABLE417

AHU1SUPPLY FAN

ENABLE418

423AHU1

CONDENSER1

ENABLE

425

12345

54321

24V CCT

1

1 32NC C 2

4 65

3

7 98

4

10 1211NC C NC C NC C

XCITE/IO/8DO (MODULE 6)12345

54321

8

2422 23

7

2119 20

6

1816 17

5

1513 14C NC C NC C NC C NC

286 287 288

1 2 3NM240A

AHU1 HEAT EXCHANGERBYPASS DAMPER

411

230V CCTTO

DAMPERS412

L N

434

AHU2CONDENSER

1ENABLE

1

1 32NC C 2

4 65

3

7 98

4

10 1211NC C NC C NC C

XCITE/IO/8DO (MODULE 7)12345

54321

289 290 291

1 2 3NM240A

AHU2 HEAT EXCHANGERBYPASS DAMPER

8

2422 23

7

2119 20

6

1816 17

5

1513 14C NC C NC C NC C NC 8

2422 23

7

2119 20

6

1816 17

5

1513 14C NC C NC C NC C NC

292 293 294

1 2 3NM240A

AHU3 HEAT EXCHANGERBYPASS DAMPER

24V CCT

N

L

407

407407

407

19 19

421

AHU1EXHAUSTDAMPERENABLE

AHU1EXTRACT

FANENABLE

422

AHU1CONDENSER

2ENABLE

24V CCT407

428AHU2

F/A DAMPERENABLE

AHU2SUPPLY FAN

ENABLE429 432

AHU2EXHAUSTDAMPERENABLE

AHU2EXTRACT

FANENABLE

433

436AHU2

CONDENSER2

ENABLE

439AHU3

F/A DAMPERENABLE

440AHU3

SUPPLY FANENABLE

445

AHU3CONDENSER

1ENABLE

443

AHU3EXHAUSTDAMPERENABLE

AHU3EXTRACT

FANENABLE

444 447

AHU3CONDENSER

2ENABLE

450AHU4

F/A DAMPERENABLE

AHU4SUPPLY FANLOW SPEED

ENABLE

AHU4SUPPLY FANHIGH SPEED

ENABLE

452 453451Com

295 - 400 SPARE Nos. ONLY

DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN

DRG No.

SCALEREVISIONDATE

SHEET

INTERNAL/EXTERNAL WIRING DIAGRAMOF

BOILER ROOM CONTROL PANEL MCC3

Job-No15 of 22NTS

J.STONEMANJS15/06/2011

T-R+ T+R-

COMMS OUT

T-R+ T+R-

COMMS IN

R-R+

LAN CARD

T+E T- R-R+ T+ T- E

COMMSCOMMS

TERMINATOR

KITCHENEXTRACT FANLOW SPEED

ENABLE

KITCHENEXTRACT FANHIGH SPEED

ENABLE456 457455

Com

1

1 32NC C 2

4 65

3

7 98

4

10 1211NC C NC C NC C

XCITE/IO/8DO (MODULE 8)12345

54321

24V CCT 407

458

GROUNDFLOORTOILET

EXTRACTUNIT

ENABLE

LAST IDENT USED - 595

DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN

DRG No.

SCALEREVISIONDATE

SHEET

INTERNAL/EXTERNAL WIRING DIAGRAMOF

BOILER ROOM CONTROL PANEL MCC3

Job-No16 of 22NTS

J.STONEMANJS15/06/2011

1200

300

1400

TX

OUTGOING TERMINALS

ISO

C2C1 C3 C4

CONSTRUCTION1NOTES

ETTAMOUNTING PLATEFINISH COLOUR

5

GALVANISED STEELRAL 7032

PROTECTION

6ACCESS

7INCOMING CABLES

8

IP65FRONTTOP

2

4

PROTECTIVE EARTH1CABLE COLOURS

L1 PHASEGREEN/YELLOWBROWN

L2 PHASEL3 PHASE5NEUTRAL6

BLACKGREYBLUE

24VAC ~724VAC 8DC +9

WHITEWHITEWHITE

24

T

DC -10 WHITE

3

TRUNKING 60mm & 40mmSPACING BETWEEN LABELS 10mm

MB4

MB3

MB2

MB1

DIST.

INTERNAL ARRANGEMENT

IQ 3XCITE I/O I/O

OUTGOING TERMINALS

I/O I/O

I/O I/O I/O I/O

400V

800

1

EXTERNAL ARRANGEMENT

2000

230V

C5 C6

MB6

MB5

T1

T2

9R

10

1R

11R

21R

41R

51R

61R

71R

82R

NF

RF

NF

NF

OE

ROE

R4R

5R

6R

7R

8R

VG

SE

1R

3R R

13

R2R

12R

22R

32R

42R

62R

71R

920

R25

R2R

82R

93R

13R

230

RINTERCONNECTING TERMINALS

5

2

6 7 8

9 10 11 12

13 14 15 16

17 18 19 20

3

C7 C8

MB8

MB7

C9 C10

MB10

MB9

3R

33R

4

DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN

DRG No.

SCALEREVISIONDATE

SHEET

GENERAL ARRANGEMENTOF

BOILER ROOM CONTROL PANEL MCC3

Job-No17 of 221:12.5 @ A3

J.STONEMANJS15/06/2011

135

20

105

BLACK TEXT ON WHITE TRAFFOLYTE LABELMAIN TEXT - 4mm (IF APPLICABLE)SUB-TEXT - 3mm

5

5

3

AS ABOVE1LABEL No. LAMP(S) TEXTMAIN TEXT DESCRIPTION (IF APPLICABLE)

AS ABOVE

3535

18 18

23 23

CONTROL

CIRCUIT

LIVE

FIRE

ALARM

135

20

105

BLACK TEXT ON WHITE TRAFFOLYTE LABELMAIN TEXT - 4mm (IF APPLICABLE)SUB-TEXT - 3mm

5

5

3

AS ABOVE2LABEL No. LAMP(S) TEXTMAIN TEXT DESCRIPTION (IF APPLICABLE)

AS ABOVE

3535

23

CLOSED

KITCHEN GAS VALVE

CL

DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN

DRG No.

SCALEREVISIONDATE

SHEET

LABELLING DETAILOF

BOILER ROOM CONTROL PANEL MCC3

Job-No18 of 221:1 @ A3

J.STONEMANJS15/06/2011

135

35

AUTO

105

23

RUN

23

TRIP

MEETING ROOMS 1-7

AHU1 EXTRACT FAN

3

23

NEW RESTAURANT AHU3 EXTRACT FAN 14

LABEL No. LAMP(S) TEXTMAIN TEXT DESCRIPTION

AS ABOVE

HAND

OFF

BLACK TEXT ON WHITE TRAFFOLYTE LABELMAIN TEXT - 4mm (IF APPLICABLE)SUB-TEXT - 3mm

20

3 RUN - FAULTGROUND FLOOR TOILET EXTRACT UNIT

AS ABOVE6 AS ABOVEMEETING ROOMS 8-9 / DAYTIME RESTAURANT / SYNDICATE ROOMS AHU2 EXTRACT FAN 10 AS ABOVE

135

18

35

AUTO

18

105

23

RUN

23

TRIP

MEETING ROOMS 1-7

AHU1 SUPPLY FAN

3

23

LABEL No. LAMP(S) TEXTMAIN TEXT DESCRIPTION

HAND

OFF

BLACK TEXT ON WHITE TRAFFOLYTE LABELMAIN TEXT - 4mm (IF APPLICABLE)SUB-TEXT - 3mm

20

9 AS ABOVEMEETING ROOMS 8-9 / DAYTIME RESTAURANT / SYNDICATE ROOMS AHU2 SUPPLY FAN 13 AS ABOVENEW RESTAURANT AHU3 SUPPLY FAN

AS ABOVE5 AS ABOVE

23

FROST

52.552.5CL

DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN

DRG No.

SCALEREVISIONDATE

SHEET

LABELLING DETAILOF

BOILER ROOM CONTROL PANEL MCC3

Job-No19 of 221:1 @ A3

J.STONEMANJS15/06/2011

135

35

105

MEETING ROOMS 1-7

AHU1 CONDENSER 1

3

23

AS ABOVE7LABEL No. LAMP(S) TEXTMAIN TEXT DESCRIPTION

AS ABOVE

BLACK TEXT ON WHITE TRAFFOLYTE LABELMAIN TEXT - 4mm (IF APPLICABLE)SUB-TEXT - 3mm

MEETING ROOMS 1-7 AHU1 CONDENSER 28 AS ABOVE

20

18 18

23 23

RUN FAULT

MEETING ROOMS 8-9 / DAYTIME RESTAURANT / SYNDICATE ROOMS AHU2 CONDENSER 111 AS ABOVE

OFF

AUTO

135

105

LABEL No. LAMP(S) TEXTMAIN TEXT DESCRIPTION

BLACK TEXT ON WHITE TRAFFOLYTE LABELMAIN TEXT - 4mm (IF APPLICABLE)SUB-TEXT - 3mm

AS ABOVE4 AS ABOVE

MEETING ROOMS 8-9 / DAYTIME RESTAURANT / SYNDICATE ROOMS AHU2 CONDENSER 212 AS ABOVENEW RESTAURANT AHU3 CONDENSER 115 AS ABOVENEW RESTAURANT AHU3 CONDENSER 216 AS ABOVE

DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN

DRG No.

SCALEREVISIONDATE

SHEET

LABELLING DETAILOF

BOILER ROOM CONTROL PANEL MCC3

Job-No20 of 221:1 @ A3

J.STONEMANJS15/06/2011

135

18

35

AUTO

18

105

23

HIGH SPEED

RUN

23

HIGH SPEED

TRIP

KITCHEN AHU4 SUPPLY FAN

3

23

LABEL No. LAMP(S) TEXTMAIN TEXT DESCRIPTION

HAND

OFF

BLACK TEXT ON WHITE TRAFFOLYTE LABELMAIN TEXT - 4mm (IF APPLICABLE)SUB-TEXT - 3mm

20

AS ABOVE17 AS ABOVE

23

FROST

135

35

105

KITCHEN AHU4 SUPPLY FAN

3

AS ABOVE18LABEL No. LAMP(S) TEXTMAIN TEXT DESCRIPTION

AS ABOVE

BLACK TEXT ON WHITE TRAFFOLYTE LABELMAIN TEXT - 4mm (IF APPLICABLE)SUB-TEXT - 3mm

20

18 18

23 23

LOW SPEED

RUN

LOW SPEED

TRIP

CL

DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN

DRG No.

SCALEREVISIONDATE

SHEET

LABELLING DETAILOF

BOILER ROOM CONTROL PANEL MCC3

Job-No21 of 221:1 @ A3

J.STONEMANJS15/06/2011

135

18

35

AUTO

18

105

23

HIGH SPEED

RUN

23

HIGH SPEED

TRIP

KITCHEN EXTRACT FAN

3

23

LABEL No. LAMP(S) TEXTMAIN TEXT DESCRIPTION

HAND

OFF

BLACK TEXT ON WHITE TRAFFOLYTE LABELMAIN TEXT - 4mm (IF APPLICABLE)SUB-TEXT - 3mm

20

AS ABOVE19 AS ABOVE

135

35

105

KITCHEN EXTRACT FAN

3

AS ABOVE20LABEL No. LAMP(S) TEXTMAIN TEXT DESCRIPTION

AS ABOVE

BLACK TEXT ON WHITE TRAFFOLYTE LABELMAIN TEXT - 4mm (IF APPLICABLE)SUB-TEXT - 3mm

20

18 18

23 23

LOW SPEED

RUN

LOW SPEED

TRIP

DESCRIPTIONREVISION APPROVEDDATECHECKEDDRAWN

DRG No.

SCALEREVISIONDATE

SHEET

LABELLING DETAILOF

BOILER ROOM CONTROL PANEL MCC3

Job-No22 of 221:1 @ A3

J.STONEMANJS15/06/2011