control of hybrid (high voltage) ac/dc grids

33
This project has received funding from the European Union's Horizon 2020 research and innovation programme under Marie Sklodowska-Curie grant agreement No 675318 Control of Hybrid (High Voltage) AC/DC Grids Adedotun J. Agbemuko INCITE Fellow 1 Main Location: IREC, Barcelona, Spain Supervisors: José Luis Domínguez-García (IREC) Oriol Gomis-Bellmunt (UPC)

Upload: others

Post on 05-Oct-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Control of Hybrid (High Voltage) AC/DC Grids

This project has received funding from the EuropeanUnion's Horizon 2020 research and innovationprogramme under Marie Sklodowska-Curie grantagreement No 675318

Control of Hybrid (High Voltage) AC/DC Grids

Adedotun J. AgbemukoINCITE Fellow

1

Main Location: IREC, Barcelona, Spain

Supervisors:

José Luis Domínguez-García (IREC)

Oriol Gomis-Bellmunt (UPC)

Page 2: Control of Hybrid (High Voltage) AC/DC Grids

Direction of this Work (1)

2

Models to capture both AC/DCside dynamics without sacrificingtoo much computational time

Further research onidentification of AC-DC interactions

New phenomenaand mitigation orcontrol strategies

Controller design andsynthesis (Extensionto MTDC)

Coordination and control

Influence of physical propertiesof grid on interactions andphenomena

Page 3: Control of Hybrid (High Voltage) AC/DC Grids

Direction of this Work (2)

3

Grid level integration ofstorage technologies andposible interactions

Distributedcontribution from RES(WPPs)

Advanced strategies forancillary support

Stability assessment

FACTS and SynchronousCondensers for InertiaImprovement

Harmonics and Mitigationstrategies

Page 4: Control of Hybrid (High Voltage) AC/DC Grids

Harmonic Stability and Interaction

4

• Expected pervasiveness of PE converters and devices.

• Transmission system as an interconnection of devices.

• Global stability becomes the fundamental issue.

• Complicated when two distinct grids are involved.

• Understanding and insight into harmonic interaction and

stability of combined Meshed AC and MTDC grids.

Page 5: Control of Hybrid (High Voltage) AC/DC Grids

Methodology for Analysis

5

• Impedance modelling.

• Classical frequency domain analysis.

• State space + frequency domain (large systems).

Page 6: Control of Hybrid (High Voltage) AC/DC Grids

HVDC Control Basics

6

• Multi-loop control system

Page 7: Control of Hybrid (High Voltage) AC/DC Grids

HVDC Control Basics

7

• Current controller as the fundamental control system.

• Interacts directly with the converter and AC grid.

Page 8: Control of Hybrid (High Voltage) AC/DC Grids

HVDC Control Basics (2)

8

• AC, DC voltage, power controller as an outer-loop.

• Controls the either the voltage of the AC bus, DC bus, or

power injected.

Page 9: Control of Hybrid (High Voltage) AC/DC Grids

HVDC Control Basics (3)

9

• Reduced control system

Page 10: Control of Hybrid (High Voltage) AC/DC Grids

Rationale for Impedance Model

10

• Current controller can be viewed as dynamic impedance.

• Voltage controller can be viewed as dynamic admittance.

• Note: Admittance and Impedance are used

interchangeably.

• Why not model the entire system as an impedance?

• Impedance plots are a good predictor of stability.

Page 11: Control of Hybrid (High Voltage) AC/DC Grids

Why Investigate Harmonics/Resonance?

11

• Global impedance (control inclusive) changes with any

change at all.

• Changes affect the harmonic/resonance points.

• Control parameter particularly affect resonances.

• Shape of impedance functions over frequency.

• Possibility of resonance points moving to the LF region.

• Control system as a means to manipulate impedance.

Page 12: Control of Hybrid (High Voltage) AC/DC Grids

Impedance Modelling

12

• Inner-loop and AC grid dynamics:

𝑖𝑐,𝑑𝑞 = 𝐻𝑐𝑙𝑖 𝑖𝑐,𝑑𝑞

∗ − 𝑌𝑜𝑐𝑈𝑠,𝑑𝑞

𝑌𝑜𝑐 =𝑌𝑎𝑐

1 + 𝐻𝑜𝑙𝑖

Page 13: Control of Hybrid (High Voltage) AC/DC Grids

Impedance Modelling (2)

13

• Outer-loop, inner-loop, AC grid dynamics, DC grid dynamics:

– 𝑈𝑑𝑐1 = 𝐻𝑐𝑙𝑣𝑈𝑑𝑐1

∗ −𝐾𝑌𝑜𝑐𝐻1 𝑠

1+𝐻𝑜𝑙𝑣 𝑈𝑠,𝑑𝑞 + 𝑍𝑖𝑐𝐼𝑑𝑐2

𝑍𝑖𝑐 =𝑍𝑑𝑐,𝑝

1 + 𝐻𝑜𝑙𝑣

𝑌𝑜𝑐𝑣 =

𝑌𝑜𝑐1 + 𝐻𝑜𝑙

𝑣

• Notice we can actually construct the impedance of a system ifwe know the eigenvalues of the system.

Page 14: Control of Hybrid (High Voltage) AC/DC Grids

Extension to Meshed Grid

14

a. DC side current source bus circuit

b. DC side voltage source equivalent

Page 15: Control of Hybrid (High Voltage) AC/DC Grids

To have a matrix that describes the DC Side

15

a. DC side Z-bus circuit

𝑍𝑏𝑢𝑠,𝑑𝑐 =𝑍11 𝑍12𝑍21 𝑍22

𝑍11 =𝑍1𝑍2 + 𝑍1𝑍3𝑍1 + 𝑍2 + 𝑍3

• All variables are in s-Domain

Page 16: Control of Hybrid (High Voltage) AC/DC Grids

Then…

16

• The same is done for the AC grid.

• Thus, we can have a whole matrix that describes the network

dynamics and control of an MTDC as a single matrix,

• And that of control and AC grid as a single matrix.

• Then, we select the buses that we are interested in with

respect to the corresponding AC bus OR analyse the DC bus

matrix distinctly for DC side analysis.

• Same applies for AC bus.

Page 17: Control of Hybrid (High Voltage) AC/DC Grids

Analysis

17

• Bode plot of open loop gains and influence of parameter

sensitivity on frequency response.

• Bode plot of closed loop charateristic equations.

• Nyquist stability criterion.

• Routh-Hurwitz stability criterion

Page 18: Control of Hybrid (High Voltage) AC/DC Grids

Results

18

• AC output admittance with base control data (Inner-loop)

Page 19: Control of Hybrid (High Voltage) AC/DC Grids

Results

19

• AC output admittance with base control data

Page 20: Control of Hybrid (High Voltage) AC/DC Grids

Results

20

• AC output admittance with base control data (outer-loop)

Page 21: Control of Hybrid (High Voltage) AC/DC Grids

Results

21

• Impedance change from inner-loop to outer-loop

Page 22: Control of Hybrid (High Voltage) AC/DC Grids

Results

22

• Sensitivity analysis to parameter variation (inner-loop)

Page 23: Control of Hybrid (High Voltage) AC/DC Grids

Results

23

• Sensitivity analysis to parameter variation (Multi-loop)

Page 24: Control of Hybrid (High Voltage) AC/DC Grids

Results

24

• Stability based on Nyquist’s criterion

Page 25: Control of Hybrid (High Voltage) AC/DC Grids

Results

25

• Stability based on Nyquist’s criterion

Page 26: Control of Hybrid (High Voltage) AC/DC Grids

Results

26

• Stability based on Nyquist’s criterion

Page 27: Control of Hybrid (High Voltage) AC/DC Grids

Results

27

• Stability based on Nyquist’s criterion (Outer-loop before tuning)

Page 28: Control of Hybrid (High Voltage) AC/DC Grids

Results

28

• Stability based on Nyquist’s criterion (Outer-loop before tuning)

Page 29: Control of Hybrid (High Voltage) AC/DC Grids

Results

29

• Stability based on Nyquist’s criterion (Outer-loop after tuning)

Page 30: Control of Hybrid (High Voltage) AC/DC Grids

Results

30

• Stability based on Nyquist’s criterion (Outer-loop after tuning)

Page 31: Control of Hybrid (High Voltage) AC/DC Grids

Results

31

• Stability based on Nyquist’s criterion (Outer-loop after tuning)

Page 32: Control of Hybrid (High Voltage) AC/DC Grids

Publications (Expected)

6

• Two conferences accepted – awaiting review.

• One journal on parametric sensitivity due in August.

• One journal on DC stability analysis with impedance

models expected.

• One journal on AC stability analysis considering

synchronous generator and converter controls.

Page 33: Control of Hybrid (High Voltage) AC/DC Grids

Thank you!

6

Questions/Feedback