continuum netcontroller reference

Upload: pujfierros

Post on 07-Aug-2018

226 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/20/2019 Continuum NetController Reference

    1/76

     

    Andover Cont inuum  NetController Reference 

  • 8/20/2019 Continuum NetController Reference

    2/76

     © 2005, TAC

     All Rights Reserved

    No part of this publication may be reproduced, read or stored in a retrieval system, ortransmitted, in any form or by any means, electronic, mechanical, photocopying,

    recording, or otherwise, without prior written permission of TAC.This document is produced in the United States of America.

    Infinity  is a trademark of TAC. All other trademarks are the property of their respectiveowners.

    And over Continuum NetControl ler Reference

    Rev. F October , 2005 

    TAC part number: 30-3001-703

    Controller Firmware Version: 1.53 

    Related Documents:

    Continuum Power Supply Reference, 30-3001-702

    Continuum I/O System Reference, 30-3001-499

    Continuum Display Module Reference, 30-3001-711

    Continuum Command Terminal Configuration Guide, 30-3001-743

    Continuum CyberStation Configurator’s Guide, 30-3001-781

    Plain English Language Reference, 30-3001-872

    Continuum Online Help

    The information in this document is furnished for informational purposes only, is subjectto change without notice, and should not be construed as a commitment by TAC. TACassumes no liability for any errors or inaccuracies that may appear in this document.

    TACOne High StreetNorth Andover, MA 01845(978) 470-0555Fax: (978) 975-9782http://www.tac.com

    TACii

  • 8/20/2019 Continuum NetController Reference

    3/76

    Regulatory Notices

    Radio Interference – Federal Communications Commission

    This equipment has been tested, and it complies with the limits for a Class A digital device,

     pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection

    against harmful interference when the equipment is operated in a commercial environment. Thisequipment generates, uses, and can radiate radio frequency energy and, if not installed and used in

    accordance with the instructions in this manual, may cause harmful interference to radio

    communications. Operation of this equipment in a residential area is likely to cause harmful

    interference, in which case you will be required to correct the interference at your own expense.

    Radio Interference – Canadian Department of Communications

    This digital apparatus does not exceed the Class A limits for radio noise emissions from digital

    apparatus set out in the Radio Interference Regulations of the Canadian Department of

    Communications.

    Brouillage Radioélectrique – Ministère des Communicationsdu Canada

    Le présent appareil numérique n’émet pas de bruits radioélectriques dépassant les limites

    applicables aux appareils numériques de la Classe A prescrites dans le Règlement sur le brouillage

    radioélectrique édicté par le ministère des Communications du Canada.

    CE – Compliance to European Union (EU)

    This equipment complies with the European Union (EU) standards specified in the EU

    EMC directive 89/336/EEC and/or the product-safety low voltage directive 73/23/EEC,

    governing the European community.

    C-Tick – Australian Communications Authority (ACA)

    This equipment carries the C-Tick label and complies with EMC and radiocommunications regulations of the Australian Communications Authority (ACA),

    governing the Australian and New Zealand communities.

    WEEE – Directive of the European Union (EU)

    This equipment and its packaging carry the waste electrical and electronic equipment

    (WEEE) label, in compliance with European Union (EU) Directive 2002/96/EC,governing the disposal and recycling of electrical and electronic equipment in the

    European community.

    iii

  • 8/20/2019 Continuum NetController Reference

    4/76

    FCC Compliance Information for the Continuum Modem

    Manufactured by:

    TACOne High StreetNorth Andover, MA 01845

    Phone Line Connector: RJ-11 Connector

    This equipment complies with FCC CFR47 rules, Part 68. Behind the upper (hinged) cable-trough

    door is a label that contains, among other information, the FCC Registration Number and Ringer

    Equivalence Number (REN) for this equipment (to open the cable-trough door, pull outward at the

    lower or non-hinged side of the door). If requested, provide this information to your telephone

    company.

    The REN is useful to determine the quantity of devices you may connect to your telephone line

    and still have all of these devices ring when your number is called. In most—but not all—areas,

    the sum of the RENs of all devices should not exceed five (5.0). To be certain of the number of

    devices you may connect to your line, as determined by the REN, you should call your local

    telephone company to determine the maximum REN for your calling area.

    If this equipment causes harm to the telephone network, the telephone company may discontinue

    your service temporarily. If possible, they will notify you in advance. But if advance notice isn’t

    practical, you will be notified as soon as possible. You will be advised of your right to file a

    complaint with the FCC.

    Your telephone company may make changes in its facilities, equipment, operations, or procedures

    that could affect the proper operation of your equipment. If they do, you will be given advance

    notice so as to give you an opportunity to maintain uninterrupted service.

    If you experience trouble with this equipment, please contact the manufacturer for warranty/repair

    information. The telephone company may ask that you disconnect this equipment from the

    network until the problem has been corrected or until you are sure that the equipment is not

    malfunctioning.

    TACiv

  • 8/20/2019 Continuum NetController Reference

    5/76

     

    DOC Compliance Information for the Continuum Modem

    If you order your controller module with the Continuum modem option—the following

    requirements of the Canadian Department of Communications apply.

    The Canadian Department of Communications label identifies certified equipment. This

    certification means that the equipment meets certain telecommunications network protective,

    operational and safety requirements. The Department does not guarantee the equipment will

    operate to the user’s satisfaction.

    Before installing this equipment, users should ensure that it is permissible to be connected to the

    facilities of the local telecommunications company. The equipment must also be installed using an

    acceptable method of connection. In some cases, the company’s inside wiring associated with a

    single line individual service may be extended by means of a certified connector assembly

    (telephone extension cord). The customer should be aware that compliance with the aboveconditions may not prevent degradation of service in some situations.

    Repairs to certified equipment should be made by an authorized Canadian maintenance facility

    designated by the supplier. Any repairs or alterations made by the user to this equipment, or

    equipment malfunctions, may give the telecommunications company cause to request the user to

    disconnect the equipment.

    Users should ensure for their own protection that the electrical ground connections of the power

    utility, telephone lines and internal metallic water pipe system, if present, are connected together.

    This precaution may be particularly important in rural areas.

    Caution: Users should not attempt to make such connections themselves, but should contact the

    appropriate electric inspection authority, or electrician, as appropriate. 

    Note:  The Load Number (LN) assigned to each terminal device denotes the percentage of the

    total load to be connected to a telephone loop which is used by the device, to prevent overloading.

    The termination on a loop may consist of any combination of devices subject only to the

    requirement that the total of the Load Numbers of all the devices does not exceed 100.

    v

  • 8/20/2019 Continuum NetController Reference

    6/76

    Limitations DDC de Fixation de Dispositifs Auxiliaires

    L’étiquette du Département de Communications Canadien identifie un équipement certifié. Cette

    certification veut dire que l’équipement satisfait à certaines exigences de sûreté, d’exploitation, et

    de protection de réseau de télécommunications. Le Département ne garantit pas que l’équipement

    fonctionnera à la satisfaction de l’utilisateur.

    Avant d’installer cet équipement, les utilisateurs doivent s’assurer qu’il est admissible d’être

    connecté aux installations de la société de télécommunications locale. L’équipement doit

    également être installé en utilisant une méthode de connexion admissible. Dans certains cas, le

    câblage intérieur d’une société associé avec une ligne unique de service individuel peut être

    étendu par un ensemble connecteur certifié (prolongateur téléphonique). Le client doit être

    conscient du fait que la conformité aux conditions ci-dessus n’empêcherait pas la dégradation de

    service dans certaines situations.

    Les réparations à l’équipement certifié devraient être effectuées par un établissement d’entretien

    canadien autorisé qui est désigné par le fournisseur. Toutes réparations ou modifications faites par

    l’utilisateur à cet équipement ou aux mauvais fonctionnements de l’équipement, peut donner à la

    société de télécommunications un sujet de demander que l’utilisateur déconnecte l’équipement.

    Les utilisateurs devraient s’assurer, pour leur propre protection, que les connexions électriques

    mises à la masse du service électrique, des lignes téléphoniques et du système de tuyaux d’eau

    métallique, si présent, sont interconnectées. Cette précaution pourrait être très significative à la

    campagne.

    Avertissement:

    Les utilisateurs devraient ne pas tenter de faire de telles connexions eux-même, mais devraient

    prendre contact avec l’autorité d’inspections électriques ou un(e) électricien(ne) convenable.

    Note—Le numéro de chargement (load number / LN) assigné à chaque dispositif terminal indique

    le pourcentage du chargement total à être connecté à une boucle téléphonique qui est utilisé par le

    dispositif, pour empêcher une surcharge. Le raccordement sur une boucle peut consister de

    quelque combinaison de dispositifs, assujettis uniquement à l’exigence que le total des numéros de

    chargement ne peut pas dépasser 100.

    TACvi

  • 8/20/2019 Continuum NetController Reference

    7/76

    Contents

    Introduction .................................................1

    NetController Module Characteristics .........3

    Special System Characteristics ..................4Smoke Control Operation (UL 864) ..........................................4

    Access Control Operation (UL 294) .........................................4

    Mechanical Installation................................5

    DC Power Connection ................................8

    Third-Party DC Power Connection............10

    Output Power-I/O Connections.................12Connection of I/O Modules.........................................................13Maximum Number of I/O Modules .............................................14Maximum Length of I/O Bus....................................................... 15Cable Recommendations ...........................................................15Power Wiring Guideline Table ................................................... 17Connecting Remote I/O Modules with ACC-LON (RS-485) ..... 18Connecting Remote I/O Modules with FFT-10A....................... 22

    vii

  • 8/20/2019 Continuum NetController Reference

    8/76

    Communications Ports............................. 28RS-232 ..........................................................................................29

    Lbus Port Configuration......................................................................31

    RS-485 ..........................................................................................32Infinet Cable Specifications ................................................................ 32Infinet Connections..............................................................................33

    Ethernet........................................................................................34Token Ring ...................................................................................38Modem..........................................................................................40

    Status/Control Panel .................................41

    Operation ..................................................45

    Commissioning..........................................47

    UPS Programming ....................................55

    Appendix A: Command TerminalInterface ....................................................57

    Appendix B: NetModemRemoval/Replacement..............................61

    Appendix C: Network Interface Circuit BoardRemoval/Replacement..............................65

    TACviii

  • 8/20/2019 Continuum NetController Reference

    9/76

     

    TCX 865

    NetController 

    This manual describes the installation, care and use of the Andover Continuum

    NetController CPU module.

    The Continuum NetController CPU module is part of the Continuum network-based

    intelligent building system. The Continuum system allows you to cost-effectively mix andmatch DIN rail-mounted CPU, power supply, and various combinations of I/O modulesand user interfaces to meet your control and monitoring needs. This CPU includes animpressive array of features.

    The Continuum NetController with FLASH EPROM is the high-powered CentralProcessing Unit (CPU) module and network manager for the Continuum intelligentbuilding system.

    High-Speed Communications

    The NetController acts as the system coordinator for the Continuum I/O modules,providing integrated global control and monitoring, history logging, local and remotealarming. It communicates with the I/O modules via LON communications and a choice ofRS-485 or free topology bus media. In addition, an optional network support interfaceallows the NetController to communicate with other NetControllers and Continuum Workstations over a high-speed 10Mb/s Ethernet Local Area Network (LAN) or a4/16Mb/s Token Ring Network using the TCP/IP protocol. Several different Ethernet

    physical interface modules are available ⎯ you can choose either a 10BASE-T (twistedpair), or a10BASE-FL (fiber optic connection).

    Flash MemoryNetController’s flash EPROM allows you to download software revisions over network orstandard telephone lines using a Continuum workstation. This flash memory featureeliminates the need to perform EPROM change-outs in the field.

    Andover Continuum NetController Reference 1 

  • 8/20/2019 Continuum NetController Reference

    10/76

    2 TAC

    Serial Communications

    NetController’s programmable communications ports can be configured as either anRS-232 or an RS-485 interface to modems, printers, third-party devices, and the Infinity  Infinet field bus network. TAC has developed an extensive library of third-party softwareinterfaces, including tie-ins to chiller control panels, fire alarm systems, emergencygenerator systems, bar code readers, elevator controls, and video switchers.

    Plain Englis h  ® 

     Programming

    The Continuum NetController can be configured to meet the exact requirements of yourapplication using the powerful Plain English programming language. Programs areentered into NetController using the Continuum Workstation. The program is then storedin, and executed by, the NetController. (See also the Plain English Language Reference,30-3001-872.)

    Software Capabilities

    The dynamic memory of the Continuum NetController can be allocated for anycombination of programs, scheduling, alarming, reporting and data logging. Our object-oriented Plain English language with intuitive keywords provides easy operation and

    programming. In addition, Plain English ‘s pre-defined and customized functions andpowerful math capabilities reduce programming time for repetitive applications.

    Optional Auto-Baud Modem

    The optional Continuum modem allows NetController to communicate and exchange dataover standard voice grade telephone lines with speeds up to 33.6K baud. The modemhas built-in data compression and error-correction protocols, auto-dial/auto-answercapabilities, and is UPS-supported.

    UPS Operation

    The Continuum NetController incorporates software programmable battery backup thatreduces or eliminates the impact of power failure. On UPS, the NetController CPU can turnoff I/O power to extend battery life and support modem and network operation for up to fourhours. In addition, NetController can go into a low-power mode in which only the DRAM andreal-time clock are powered for up to 72 hours.

    In smoke and access control installations (UL 864 and UL 294) the listing specifies thatbattery backup is provided for the retention of program memory only.

    Modular Design for Snap-Together Connection

    NetController features a sleek, lightweight casing designed for natural convection cooling.

    Built-in connectors on either side of the NetController module allow power transmissionfrom the power supply module and communication signals to the Continuum I/O modulesto feed through easy snap-together connections. Built-in quick-release fasteners at the

    back of the module are provided for DIN rail mounting ⎯ no tools required. Thesefasteners also snap into a locked position for panel mounting.

  • 8/20/2019 Continuum NetController Reference

    11/76

    Andover Continuum NetController Reference 3 

    NetController Module Characteristics

    The following lists the features included in the Continuum NetController module:

    •  Real Time Clock

    •  Watchdog timer

    •  Scan, CPU, Error and Communications status LEDs•  Reset Button on the front panel

    •  4MB EEPROM

    •  Optional Network interface with several options:

    10BASE-T Unshielded twisted pair cable

    10BASE-FL Fiber optic cable

    Token Ring

    •  4MB and 8MB models

    •  2MB Flash

    •  4K bits serial EEPROM

    •  Optional on-board 33.6 KBPS modem

    •  Controls I/O modules on “I/O BUS” via 5-position male connector located on theright side of the case. Supports either RS-485 (ACC-LON) @ 39k baud orFTT-10A @ 78k baud communication interfaces.

    •  4 Communications ports (excluding I/O BUS):

    COMM1 – RS-232 / RS-485 Infinet , L-bus (with appropriate converter),

    Xdriver, TankNet or Printer (RS-232)

    COMM2 – RS-485 Printer, Infinet, Xdriver or TankNet

    COMM3 – RS-232 / Modem Printer, Xdriver, TankNet orInternal 33.6 Kbps Modem

    COMM4 – RS-485 Printer, Xdriver or TankNet

    •  During UPS operation, the CPU can turn off the I/O power to extend battery life. Also, the CPU can go into low-power mode in which only the DRAM and RealTime Clock are powered.

    * The firmware that runs the NetController is upgradeable (called FLASH updates). Updatesare performed through a CyberStation. Refer to the CyberStation Configuration manual forinstructions to perform updates.

  • 8/20/2019 Continuum NetController Reference

    12/76

    4 TAC

    Special System Characteristics

    Smoke Control Operation (UL 864)

    Continuum Main Controllers (NetControllers) available through TAC that are listed withUL for Smoke Control applications and the options pertaining to smoke control operationare the following:

    CX 9900 -S (8MB Ram)Options: 1.) 10 Base FL Fiber optic Ethernet network option

    CX 9940 -S  (4MB Ram)Options: 1.) 10 Base FL Fiber optic Ethernet network option

    The Optional on-board 33.6 KBPS modem and the FTT-10A Network Option are not

    listed for UL 864 applications.

    Access Control Operation (UL 294)

    NetControllers and their options that are listed with UL for Access Control applicationsare the following:

    Controllers:

    CX 99XX All models of the NetController are listed for use in Access Control applications.

    Options 

    10BASE-T Ethernet LANACC LON RS485 I/O Bus

    The Optional on-board 33.6 KBPS modem and the FTT-10A Network Option are notlisted for UL 294 applications.

  • 8/20/2019 Continuum NetController Reference

    13/76

     

    Mechanical Installation

    Note to the installer:This device must be properly installed to suit its intended application.

    European Installations:The NetController is listed as a Class 1 device intended for installation in anIP2 enclosure. The Continuum Enclosure is an IP2 enclosure.

    When installing I/O modules it is imperative that the installer supply a solid Earthground connection to the module. Refer to the Earth Ground Connection subsectionfound later in this manual.

    The NetController module can be mounted to a standard DIN rail or be directlymounted to a panel using screws. Hardware facilitating both mounting methods isincluded as an integral part of the case design.

    On the back of each module are molded DIN rail guide fingers. The design allows themodule to easily hook onto and slide along a standard DIN rail.

    Andover Continuum NetController Reference 5 

  • 8/20/2019 Continuum NetController Reference

    14/76

     

    Special clamps are provided on the case that allow you to lock the module in place,once it is in position.

    These clamps, when extended, provide an alternative method of mounting to the DINrail. You can mount the module directly to a panel using the reinforced mountingholes provided on each of the clamps.

    Once the module is in the desired position, it is locked to the rail by pushing thebottom clamps inward. After the bottom is secure, press the top clamp inward tocomplete the operation.

    6 TAC

  • 8/20/2019 Continuum NetController Reference

    15/76

     

    Overall Dimensions

    The overall dimensions of the CPU unit are as shown:

    9.0 ''(228.7 mm)

    6.7(170.2

      2.50 ''(63.5 mm)

    Andover Continuum NetController Reference 7 

  • 8/20/2019 Continuum NetController Reference

    16/76

     

    DC Power Connection

    PowerConnector

    The CPU module is powered by an external 24 VDC source. This source isnormally supplied by one of the Continuum Power Supply Modules, however you can

    attach a third-party supply to the NetController if you follow the information provided in

    the next few pages. The input power connector is located on the left side of the CPU

    module case and consists of five pins.

    The power input connector is a five-pin male assembly that is designed to easilyinsert directly into the right side (output) connector of any Continuum Power Supplymodule. The signals within that connector are as follows:

    PIN Function5 +24 VDC

    4 24 VDC Return

    3 Ground

    2 Low Battery Signal*

    1 AC Power Present Signal*

    * Only supplied from Continuum UPS version Power Supplies

    It is assumed that the CPU is directly connected to a power supply module as shownbelow:

    Power Supply CPU

     

    8 TAC

  • 8/20/2019 Continuum NetController Reference

    17/76

     The power supply generates a +24 VDC source for the CPU and all othermodules in the system. This power source is located on pins 4 and 5.Pin 3 (Ground) is intended as an Earth ground connection.

    The NetController consumes a maximum of 10 Watts of 24VDC power.

    The Continuum UPS version power supplies provide the CPU with two power statussignals on pins 1 and 2. Their function is as follows:

    AC Power  is a logic signal that is intended to communicate that AC power isavailable. When AC is interrupted and the power supply has switched to UPSbattery mode, this signal presents a logic low. The CPU can use this signal tostart an orderly system shutdown. For more information on the use of this signal,refer to the section titled UPS Programming .

    Low Battery is a logic signal that is intended to communicate that the voltage ofthe battery has dropped below 22 Volts. When the power supply has switched toUPS battery mode, this signal presents a logic high. Should the battery voltagedrop, this signal switches to a logic low. The CPU can use this signal to start an

    orderly system shutdown. For more information on the use of this signal refer tothe section titled UPS Programming .

    WarningMake sure that AC power is not   applied (switch is off) to the power

    supply while you are connecting the CPU module. The module could be

    damaged or you could receive an electrical shock that is life threatening.

    ESD WarningTo avoid damaging electronic components because of the discharge of

    static electricity, always ground yourself before touching any boards or

    other internal components of Andover Continuum devices.

    •  At the very least, discharge yourself by touching metal first.

    •  If possible, use a grounding strap or heel plate.

    Andover Continuum NetController Reference 9 

  • 8/20/2019 Continuum NetController Reference

    18/76

     

    Third-Party DC Power Connection

    In situations where a large number of I/O modules are used, the power available fromthe standard Continuum power supply module may not be sufficient. In thesescenarios you can either use an auxiliary power supply for the extended I/O group oryou can replace the main power supply with one that can handle the entire job.

    When using a third-party power source to supply a Continuum system it is necessarythat you connect the power as shown below. Normally all power flows from thesupply and through the NetController. Third party supplies should connect directly tothe I/O module power bus. That way the internal current limitations of theNetController do not detract from your system design.

    Third-PartyPower Supply

    2-ConductorShielded Power Cable

    from Power Supply

    2-Conductor Shieldeddata cable from

    NetController.

    CPU2-ConductorShielded

    Power Cable

    54321

    10 TAC

    54321

    +24VDC

    24V RETURN

    EARTH GROUND . NetController

    54321

    From Third-party supplypower supply

    I/O Module(s)

    Specific information regarding cable preparation and overall system layout may befound in the Continuum I/O System Reference, 30-3001-499.

  • 8/20/2019 Continuum NetController Reference

    19/76

    Earth Ground Connection

    To insure reliable operation under all adverse conditions, the CPU module must

    have a wire connected to it and Earth ground. The wire should be as short as

    possible, ideally 6” or less, and the wire gauge should be a minimum of 18 AWG. Pin

    4 of the COMM 2 connector located on the bottom of the CPU module case as shown

    below.

    COMM 2RS-485 Connector

    Earth Ground

     

    Continuum Enclosure Grounding

    If you are installing the CPU into the Continuum enclosure, there is an Earth ground

    stud pressed into the backplate in the lower right of the case. Connect the ground

    wire from pin 4 of the connector to this stud provided. 

    Andover Continuum NetController Reference 11 

  • 8/20/2019 Continuum NetController Reference

    20/76

     

    Output Power-I/O Connections

    The Continuum NetController CPU module includes a connector on the upper rightside of its case for further distribution of the 24 VDC input power and special I/Ocommunications signals to all I/O modules. Continuum I/O modules use these signals

    for power and communications.

    The power-I/O connector is a five pin male assembly that is designed to easily insertdirectly into the left side connector of any I/O module. The signals within thisconnector is as follows:

    54321

     PIN Function

    5 +24 VDC

    4 24 VDC Return

    3 Shield

    2 Comm B

    1 Comm A

    The main system power supply generates a +24 VDC source for the CPU. Thispower source is received through the input power connector on the left side of theCPU module and sent through to pins 4 and 5 of this connector.

     All the Continuum I/O modules can operate at 24V. Some have extended ranges to allowoperation at lower voltages. Refer to the individual specifications for each module.

    Communications between the CPU and I/O modules is through a two-signal serialinterface that is factory configured as either RS 485 ACC-LON or FTT-10A.

    Pins 1 and 2 (Comm A and Comm B) provide the electrical connection for this interface.Pin 3 (Shield) is the communications signal shield connection. This is not an Earthground connection. Proper shielding requires that the installer connect all shieldstogether. The CPU (if grounded properly) provides the single Earth ground point for

    all modules. Each I/O also has its own Earth ground connection.

    12 TAC

  • 8/20/2019 Continuum NetController Reference

    21/76

     

    Connection of I/O Modules

    The CPU can directly connect to I/O without the use of cables through a system of built-inplugs and jacks. All I/O modules include two complementary module inter-connectors.

    Creating a system is as simple as physically plugging the modules together.

    CPUPower SupplyI/O I/O

    Power Supply CPU I/O I/O

    In vertical extended systems, I/O modules may be located above or below other modules.In this case, cable assemblies bridge the I/O modules together.

    CPUPower Supply

    I/O

    The cables necessary to connect the CPU and external I/O modules are attached using aplug-in screw terminal connector. Connection between the modules is one-to-onestraightforward wiring as shown below:

    5

    4321

    5

    4321

    Connectors are available from TAC under part number 01-0010-840.

    Andover Continuum NetController Reference 13 

  • 8/20/2019 Continuum NetController Reference

    22/76

     Maximum Number of I/O Modules

    The Continuum system allows for a maximum of 32 I/O modules per CPU. There is alsoa limit based upon the capacity of the power supply feeding the modules.

    Note:  It is possible to insert auxiliary power supplies into the I/O bus to increase thenumber of modules supported up to the maximum of 32. The Power Supply Reference,30-3001-702, includes information on auxiliary supply installation.

    •  PS 120/240 AC 50 U, UPS power supply: 35 Watts of power available

    •  PS 120/240 AC 65 U, UPS power supply: 50 Watts of power available

    •  PS 120/240 AC 85 U, UPS power supply: 70 Watts of power available

    •  PS 120/240 AC 50, non-UPS power supply: 50 Watts of power available

    •  PS 120/240 AC 65, non-UPS power supply: 65 Watts of power available

    •  PS 120/240 AC 85, non-UPS power supply: 85 Watts of power available

    • PS –48 DC 50, Battery operated power supply: 50 Watts of power available

    •  PS –48 DC 50 U, UPS Battery operated supply: 50 Watts of power available

    UPS power supplies (except the –48 DC 50 U) include battery charging circuitry that

    consume 15 Watts of the total power available. This is why the UPS supplies are listedwith less available Wattage.

    To determine the maximum number of I/O modules each power supply can support, subtractthe power requirements for each module from the maximum available per supply.

    If the supply also powers the NetController CPU be sure to subtract the 10 Watts itconsumes.

    The power requirements for the NetController and each I/O module* is listed below:

    Module Power (Watts) Current (mA)

    NetController 10 417

    UI-8-10 & UI-8-10-10V; Universal Input Modules 0.7  29

    DI-6 AC & DI-6 AC HV; AC Digital Input Modules 0.7  29

    DI-8; Digital Input Module 0.8  33

    MI-6; MilliAmp Input Module 3.8 158

    DM-20; Digital Input/Output Module 0.5 **  20 **

     AO-4-8 & AO-4-8-O; Analog Output Modules 3.8  158

    DO-4(A)-R & DO-4(A)-R-O; Relay Output Modules 2.8  116

    DO-6-TR; Triac Output Module 1.1  45

    LO-2 & LO-2-O; Lighting Output Modules 0.4  16

     AC-1; Door, Access Control, Module 2.6 200

     AC-1A; Door, Access Control, Module 2.0 83 AC-1 Plus; Door, Access Control, Module 2.2 105

    VS-8 & VS-8-T; Video Switch Module 2.0 83

    VT-1; Voice Telecom Module 1.5  63

    * Power requirements for Display Modules can be found in the Display Module Reference (30-3001-711)** Listed power value does not include any devices attached and powered by the module (i.e. DIO-20)

    14 TAC

  • 8/20/2019 Continuum NetController Reference

    23/76

    Andover Continuum NetController Reference 15 

    Maximum Length of I/O Bus

    The I/O Bus is a network. Networks are limited by cable lengths because electricalsignals lose power and distort as they travel along wire. The longer the wire, the lowerthe signal strength. The following are the maximum cable length specifications:

    RS-485 2000 ft. (610 m)

    FTT-10A 8858 ft. (2700 m) double termination

    1640 ft. (500 m) free topology

    Cable Recommendations

    Data Cable (Pins 1, 2 and 3)You must use shielded cable for the data lines (pins 1, 2 and 3) to provide reliablecommunications and to ensure compliance with the Class A FCC limits (USA).

    ACC-LON (RS-485)The data cable should be 24-gauge (0.25 mm), single-twisted-pair, tinned, shielded

    copper wire with an impedance of 100-120 Ohms and a nominal velocity ofpropagation of 78%.

    Capacitance of the cable should be below 12.5 pF/ft (41 pF/m) between conductorsand below 22 pF/ft (72 pF/m) between the conductor connected to ground and thenext conductor.

    The following cable meets all of the data cable specifications:

    Belden 9729, double twisted pair, shielded

    ACC LON FTT-10A

    The installer may choose a variety of cables, depending on cost, availability, andperformance. Performance may vary with cable type. The transmission specificationdepends on such factors as resistance, mutual capacitance, and the velocity ofpropagation. System performance on the cable types is shown below. They arelisted in order of performance.

    Cable Type Wire dia./AWG 

    Belden 85102, single twisted pair, stranded 19/29,unshielded

    28 

    Belden 8471, single twisted pair, stranded 19/29,

    unshielded, 600C

    28

    Level IV, twisted pair, typically solid & unshielded 22

    24 TIA568A Category 5, twisted pairIf a shielded cable is used, the shield should be connected to earth ground via a 470 k ,1/4 W 10%, metal film resistor to prevent static charge build-up.

  • 8/20/2019 Continuum NetController Reference

    24/76

    16 TAC

    Power Cable (Pins 4 and 5)

    You should use shielded cable for the power lines as well (pins 4 and 5) to ensure noiseimmunity and therefore more reliable operation. The shield would be connected to pin 3like that of the data cable.

    The gauge of the power cable is determined by the power it carries. As indicatedpreviously, the longer the wire the more voltage drop. Do not allow the power supplyvoltage measured at the furthest remote module to drop more than the allowable amount:

    24 VDC modules: 2V (1V for the power run and 1V for the return run)10-28 VDC modules: 12V (6V for the power run and 6V for the return run)

    Voltage drop can be calculated by using Ohms Law:

    Voltage=Current x Resistance

     A table providing some guidelines for choosing wire gauge is included on the next page.

  • 8/20/2019 Continuum NetController Reference

    25/76

    Andover Continuum NetController Reference 17 

    Power Wiring Guideline TableThe following is a conservative estimate of typical power consumptions and their relatedwire gauge and number of feet:

    24 VDC Modules 

    Total I/O Power Draw (Watts)

    10 20 30 40 50

    AWG Resistance

    per 1000 ft(305 m)

    Distance in Feet (meters)

    14 2.5 585 (178) 255 (78) 145 (44) 90 (27) 57 (17)

    16 4 366 (111) 159 (48) 91 (28) 56 (17) 36 (11)

    18 6 244 (74) 106 (32) 60 (18) 38 (12) 24 (7)

    20 10 146 (44) 64 (20) 36 (11) 23 (7) 14 (4)

    22 15 98 (30) 43 (13) 24 (7) 15 (6) 10 (3)

    24 24 61 (19) 27 (8) 15 (5) 9 (3) 6 (2)

    10 - 28 VDC Modules 

    Total I/O Power Draw (Watts)10 20 30 40 50

    AWG Resistanceper 1000 ft

    (305 m)Distance in Feet (meters)

    14 2.5 3885 (1184) 1905 (581) 1245 (379) 915 (279) 717 (219)

    16 4 2428 (740) 1191 (363) 778 (237) 572 (174) 448 (137)

    18 6 1619 (493) 794 (242) 519 (158) 381 (116) 299 (91)

    20 10 971 (296) 476 (145) 311 (95) 229 (70) 179 (55)

    22 15 648 (198) 318 (97) 208 (63) 153 (47) 120 (37)

    24 24 405 (123) 198 (60) 130 (40) 95 (29) 75 (23)

    These tables are intended as a guide. There is no way to account for every Continuum I/Opermutation. External noise suppression may be required if the power wiring is run in a noisyenvironment. 

  • 8/20/2019 Continuum NetController Reference

    26/76

     Connecting Remote I/O Modules with ACC-LON (RS-485)

    The Continuum system allows I/O modules to be placed in a remote location from theCPU (NetController). Long cable lengths in ACC-LON (RS 485)-based networks cancause signal communications problems on the I/O bus.

    When locating an I/O module remotely on an RS 485-based bus, it is necessary to add

    an external 120Ω

     terminator resistor to the bus to compensate for the distance. Theterminator must be connected at both ends of the bus for proper operation.

    The following diagrams are typical installations that indicate the correct placement of theterminator:

    Simp le CPU and 1 ACC-LON Remote I/O Modu le:

    The I/O Bus that needs to be terminated is the one formed by the cable attaching theremote module to the CPU. In this case, a terminator resistor is connected across the

    communications lines (pins 1 & 2) directly at the NetController and again at the remoteI/O module.

    CPU 54

    3

    2

    1

    5

    4

    3

    2

    1

    120 ΩResistor

    120 ΩResistor

    RemoteI/O

    Module

     

    18 TAC

  • 8/20/2019 Continuum NetController Reference

    27/76

     

    CPU with L ocal and 1 ACC-LON Remote I/O Modu le:

    The I/O Bus that needs to be terminated is the one formed by the cable that starts atthe NetController and ends at the remote module. The bus that extends from theNetController through the local I/O stack does not need termination. In this case, theterminator resistor is connected directly across the communications lines (pins 1 & 2) at

    the NetController and again at the remote I/O module.

    CPU

    5

    4

    3

    2

    1

    RemoteI/O

    Module

    LocalI/O

    LocalI/O

    5

    4

    3

    2

    1

    120 ΩResistor

    120 ΩResistor

     

    Andover Continuum NetController Reference 19 

  • 8/20/2019 Continuum NetController Reference

    28/76

     

    CPU with L ocal and Several Remote ACC-LON I/O Modu les:

    The I/O Bus that needs to be terminated is the one formed by the cable that starts atthe NetController and ends at the first remote module. The bus that extends from theNetController through the local I/O stack and the one that starts at the first remotemodule and extends through subsequent modules do not need termination. In this

    case, the terminator resistor is connected directly across the communications lines(pins 1 & 2) at the NetController and again at the first remote I/O module.

    CPU

    5

    4

    3

    2

    1

    RemoteI/O

    Module

    LocalI/O

    5

    4

    3

    2

    1

    120 ΩResistor

    RemoteI/O

    Module120 ΩResistor

    20 TAC

  • 8/20/2019 Continuum NetController Reference

    29/76

     

    CPU with Two Remo te ACC-LON Modules Separated b y Distance:

    The I/O Bus that needs to be terminated is the one formed by both cables on eitherend of the first remote I/O module. In this case, the bus begins at the NetController,flows by the first remote module and ends at the second. The terminator resistor isconnected directly across the communications lines (pins 1 & 2) at the NetController

    and again at the last remote I/O module. If the last module is actually a stack ofdirectly connected I/O modules, the terminator is placed at the first module of thestack as indicated in the scenario described on the previous page.

    CPU 54

    3

    2

    1

    5

    4

    3

    2

    1

    120 ΩResistor

    RemoteI/O

    Module

    RemoteI/O

    Module

    5

    4

    3

    2

    1

    120 ΩResistor

     

    Andover Continuum NetController Reference 21 

  • 8/20/2019 Continuum NetController Reference

    30/76

    22 TAC

    Connecting Remote I/O Modules with FTT-10A

    The ACC LON bus topology wiring (RS-485) consists of a network of I/O modules thatare interconnected using a shielded twisted wire pair. In accordance with RS-485guidelines, all of the devices must be wired in a bus topology to limit electrical reflectionsand ensure reliable communications. There is a high cost associated with installing and

    maintaining the cable plant that links together the many elements of an RS-485 basedcontrol system. Bus topology wiring is more time consuming and expensive to installbecause the installer is unable to branch or star the wiring where convenient: all devicesmust be connected directly to the main bus.

    The best solution for reducing installation and maintenance costs and simplifying systemmodifications is a flexible topology communication system. Echelon Corporation’s freetopology transceiver (FTT) technology offers just such a solution, and provides anelegant and inexpensive method of interconnecting the different elements of a distributedcontrol system.

    The FTT-10A free topology architecture allows you to wire Continuum I/O modules withvirtually no topology restrictions.

    Unlike ACC-LON, the FTT-10A system uses a free topology wiring scheme that supportsstar, loop, and/or bus wiring. This design has many advantages. First, the installer is freeto select the method of wiring that best suits the installation, reducing the need foradvanced planning and allowing last minute changes at the installation site. Second,retrofit installations with existing wiring plants can be accommodated with minimal, if any,rewiring. This capability ensures that FTT-10A technology can be adapted to both old andnew projects. Finally, free topology permits Continuum systems to be expanded in thefuture by simply tapping into the existing wiring where it is most convenient to do so. This

    reduces the time and expense of system expansion, and from the customer'sperspective, keeps down the life cycle cost of the free topology network.

    IMPORTANT FTT-10A NETWORK INSTALLATION NOTICEThe termination and wiring information provided in this guide is a small subset of thecomplete technical information presented by Echelon Corporation in their FTT-10A

    installation documentation. It is highly recommended that you obtain their document andread the sections pertaining to network installation. As a courtesy, the Echelon FTT-10A

    documentation has been included on the TSD web site.

    The document filename is Echelon FTT-10A.pdf  

  • 8/20/2019 Continuum NetController Reference

    31/76

     FTT-10A Cable Termination (see important notice on the previous page)When locating an I/O module remotely on a LON FTT-10A-based system, it is necessaryto add an external terminator to the wiring to compensate for the distance. The terminatorcan be connected at both ends or at one central point.

    * The TAC implementat ion o f the Lon FTT-10A network can co nnect to a Link-Power

    network; how ever, i t does not use the Link Power.

    Free Topology Segment

    In a free topology segment, only one termination is required and may be placedanywhere on the free topology segment. Using 24 AWG cable the maximum loopimpedance is 75 ohms.

    Terminat ion Terminat ion

    Non-Link Power network Link Power network

    Resistor = 52.30±1%, 1/8W Resistor = 52.30±1%, 1/8W

    Capacitors = 100 μF 50V min.

    Andover Continuum NetController Reference 23 

    R1 52.3 Ω ± 1% 

    Doubly Terminated Bus Topology Segment

    In a doubly terminated bus topology, two terminations are required, one at each end ofthe bus. Using 24 AWG cable the maximum loop impedance is 150 ohms.

    Terminat ion Terminat ion

    Non-Link Power network Link Power network

    Resistor = 105 ohm±1%, 1/8W Resistor = 105 ohm±1%, 1/8W

    Capacitors = 100 μF 50V min.

    R1 105 Ω ± 1%

     

  • 8/20/2019 Continuum NetController Reference

    32/76

    24 TAC

    The following characteristics apply when using doubly terminated or free topology wiringschemes:

    1. Network lengths vary for doubly terminated vs. free topology.

    2. Network lengths vary based on cable type.

    3. FTT-I/O has two specifications for a free topology network: total wirelength and node-to-node wire length (which also applies to termination).

     A doubly terminated bus may have stubs of up to 3 meters from a bus to each node.

    Doubly Terminated Bus Topology Specifications

    Maximum bus length (meters)

    Belden 85102 2700

    Belden 8471 2700

    Level IV, 22AWG 1400

    JY (St) Y 2x2x0.8 900

    TIA Category 5 900

    The free topology transmission specification includes two components that must be metfor proper system operation. The distance from each tranceiver to all other transceiversand to the termination (including the LPI-10 termination, if used) must not exceed themaximum node-to-node distance. If multiple paths exist, e.g., a loop topology, then thelongest path should be used for calculations. The maximum total wire length  is the totalamount of wire connected per segment.

    Free Topology Specifications

    Maximum node-to-node distance(meters)

    Maximum totalwire length(meters)

    Belden 85102 500 500

    Belden 8471 400 500

    Level IV, 22AWG 400 500

    JY (St) Y 2x2x0.8 320 500

    TIA Category 5 250 450

    The following pages contain diagrams of typical installations that indicate the correctplacement of the terminator:

  • 8/20/2019 Continuum NetController Reference

    33/76

     

    Example of Maximum Total and Node-to-Node Lengths

    Andover Continuum NetController Reference 25 

    CPUPower Supply

    I/O

    I/O

    I/O

    I/O

    I/O

    Node-to-NodeLength

    Maximum WireLength

     

  • 8/20/2019 Continuum NetController Reference

    34/76

     

    CPU with Local and a CPU with Several Remote FTT-10A I/O Modules *:

    CPUPower Supply

    I/O

    I/O

    I/O

    I/O

    I/O

    CPUPower Supply I/O I/O I/O I/O I/O

    1

    2

    3

    52.3 Ω

    1

    2

    3

    52.3 Ω

    * See Im ortant Installation Notice on a e 22

    26 TAC

  • 8/20/2019 Continuum NetController Reference

    35/76

     

    CPU with Several Remote FTT-10A I/O Modu les and Doub ly Terminated Bus*:

    CPUPower Supply

    I/O

    I/O

    I/O

    I/O

    I/O

    1

    2

    3

    105 Ω

    1

    2

    3

    105 Ω

     

    * See Im ortant Installation Notice on a e 22

     Andover Continuum NetController Reference 27 

  • 8/20/2019 Continuum NetController Reference

    36/76

     

    Communications Ports

    The Continuum NetController module includes connections for communications withexternal devices such as printers, Infinet  controllers and others. These connectionsare called Comm Ports. It also optionally includes network connections.

    The NetController includes four Comm Ports called COMM1 through COMM4 withthe following possible configurations:

    COMM1 – RS-232 / RS-485 Infinet , Autoset, Command, L-bus, Xdriver,TankNet or Printer (RS-232), Not Configured

    COMM2 – RS-485 Autoset, Command, Printer, Infinet, Xdriver orTankNet, Not Configured

    COMM3* – RS-232 / Modem Autoset, Command, Printer, Xdriver orInternal 33.6 Kbps Modem

    COMM4 – RS-485 Autoset, Command, Printer, Xdriver or TankNet,Not Configured

    * Comm3 is the only port intended for an internal modem connection.

    Network interface connectors are available in 10BASE-T, 10BASE-FL and TokenRing styles. The physical locations of these ports on the NetController module caseare illustrated below:

    28 TAC

  • 8/20/2019 Continuum NetController Reference

    37/76

     

    RS-232

    The NetController can be connected to other support devices such as printers forreports and other PCs used as command terminals. These connections areaccomplished using either of the two RS-232 ports.

    I/OI/ONetControllerPowerSupply

    I/O

    Printer

    PC

     

    Both COMM 1 and COMM 3 include general-purpose RS-232 connections. An

    industry standard 8-pin shielded insulation displacement RJ-45 termination connectoris provided for the RS-232 interconnection. Although the official specification defines25 signals, typically most devices use only eight of these. A full compliment of thesesignals are included in both COMM ports.

    The following lists the signals provided and their description:

    Signal Abbreviation Description 

    Signal Ground Ground Return for all data signals

    Transmitted Data TD Serial data originating at the NetController

    Received Data RD Serial data originating at the connecteddevice

    Data Terminal Ready DTR NetController signals it is operating

    Data Set Ready DSR External device signals it is operating

    Clear to Send CTS External device signals it is ready for atransmission from NetController

    Request to Send RTS NetController signals it wants data fromexternal device

    Data Carrier Detect DCD External device (usually a modem) signals

    that it is communicating with another deviceand is ready for operation

    Andover Continuum NetController Reference 29 

  • 8/20/2019 Continuum NetController Reference

    38/76

     

    RS-232 Connections

     A standard 8-pin shielded insulation displacement RJ-45 termination connector isprovided for the RS-232 interconnection. Protective ground is connected to the outershield of the connector that is connected to the shield of the cable. Both COMM 1and COMM 3 provide the same connector.

    COMM 3 can be configured as an internal modem or an RS-232 connection. Whenthe internal modem option is installed, the RS-232 connection is no longer available.

    The RS-232 pin connections are shown below:

    30 TAC

  • 8/20/2019 Continuum NetController Reference

    39/76

     

    Connection to a standard RS-232 device using a cable terminated with an RJ-45 and 25-pin or 9-pin D-type connector is shown below: 

    Use a cable of this type to connect to printers and other devices. Depending on thedevice, it may be necessary to reverse some or all of the connections. In mostcases, this is easily accomplished using an adapter called a “null modem.”

    RS-232 COMM Port Configuration

     After physical connection, the COMM Port must be configured as an RS-232 deviceproperly through the Command Terminal interface or the Continuum workstation.

    Configuration requires selecting the type of device to be connected (i.e., Printer,Command, etc.) and setting various communications-related parameters. Refer to theCommand Terminal User Guide, the Continuum CyberStation Configurator’s Guide or the Continuum online help system for detailed information regarding configurationissues.

    L-bus Port Configuration

    COMM 1 can support L-bus devices only when used with an RS-232 to RS-422 levelconverter. The LA-1 converter may be used for this purpose.

    For installation and configuration information refer to the LA-1 Installation Guide, 30-

    3001-813.

    Note: L-bus and TankNet are mu tual ly exclusive. When L-bus is c onfigu red on

    this port, TankNet is not supp orted on any other port.

    Andover Continuum NetController Reference 31 

  • 8/20/2019 Continuum NetController Reference

    40/76

    32 TAC

    RS-485

    The NetController can be connected to other standalone Andover Continuumcontrollers such as local VAV controllers and touch screen displays. Communicationprotocol and interface to these devices is called the Infinet network. Theseconnections are accomplished using any of the three RS-485 ports.

    COMM 1, COMM 2 and COMM 4 include RS-485 connections. A removable screwterminal type connector is provided for the interconnection.

    The Infinet is a high-performance, token-passing protocol designed for Infinetcontrollers where more than one controller can be the network master at a time.

    Infinet is physically wired using two conductor shielded twisted pair cable thattransmits data at a rate of up to 19.2 Kb/sec. Although Infinet has a token-passingdata access system, it can have a combination of daisy-chained bus and startopology.

    Cable lengths of up to 4,000-ft (1,220 m) daisy chained from Infinet controller to

    Infinet controller for every 31 Infinet controllers on one arm of a star are supported. After 31 nodes or 4,000 ft (1,220 m), an InfiLink 200 or InfiLink 210 signal repeater isrequired to add more nodes to the network or further extend the cabling. Using anInfiLink 210 allows you to extend the length of Infinet with fiber optic cable,recommended for running cable between buildings and through noisy environments.You can have a maximum of 127 nodes on one Infinet with InfiLink 200 or 210 .

    Only two Infinet  connections are supported. Therefore, the following Infinet  combinations are valid:

    COMM 1 & COMM 2

     Although COMM 4 is an RS-485 port, it does not support Infinet .

    For more detailed information on the Infinet network, consult the Infinet NetworkConfiguration Guide, 30-3001-169.

    Infinet Cable SpecificationsCables used to form the Infinet should conform to the following specifications:

    Wire Size: 22-24 AWGCable Type: Twisted-pair, copper wire, tinnedShield: Braid

    Nominal Impedance: 100 Ω 

    Velocity of propagation: 78%Capacitance:

  • 8/20/2019 Continuum NetController Reference

    41/76

     Infinet ConnectionsCOMM Port 1 provides both Infinet and RS-232 connections. However, only one typemay be connected at any one time. For example, COMM 1 can be used as an Infinetconnection or an RS-232 connection BUT NOT BOTH!

    The Infinet pin connections are shown below:

    COMM 1Infinet Connector

    +

    Shield

    COMM 2Infinet Connector

    +

    Shield

    Earth

    Ground

     

    The connector for COMM 2 includes an extra connection for Earth ground.

    Connection to the cable is done by inserting a stripped conductorinto the opening on a screw terminal position and tightening theassociated screw to secure it in place.

    When the network is connected to more than one device, it is done so in a daisychain manner as shown below:

    + - SHLD

    White

    BlackBlack

    White

    ShieldShield

    Infinet CableInfinet Cable

     

    The NetController does not internally connect the Shield pins to Earth ground. Theinstaller must connect the Shield to Earth ground at ONE point somewhere in thesystem.

    * Wire colors are included for clarity. The colors of your cable may vary. However, make sure that all

    Infinet connections are consistent on their connections.

    Andover Continuum NetController Reference 33 

  • 8/20/2019 Continuum NetController Reference

    42/76

    34 TAC

    Ethernet

    The NetController can be connected to workstations and other NetControllers via anEthernet interface. These connections are accomplished via one of several physicalmethods. 10BASE-T (RJ-45) and 10BASE-FL (fiber optic) connection options areavailable. Only one of the methods is installed depending upon your configuration.

    The Ethernet is a high-speed CSMA/CD local area network (LAN) that includes allTAC network-level controllers and workstations and the network software that makesthem communicate.

    Ethernet consists of a minimum of two NetControllers or a NetController and aworkstation. Data transmits over the Ethernet at a rate of 10 Mb/sec. Depending onyour particular installation, you may want to use unshielded twisted-pair (10BASE-T),fiber optic cable (10BASE-FL) or all in a variety of combinations.

    Ethernet can be constructed as a bus or daisy chain or in a combination bus/daisychain and star topology called “distributed star” topology.

     Andover Continuum’s Ethernet implementation is a baseband network, connected byup to 1,635-ft (500 m) of twisted pair cabling. The number of nodes on the networkdepends on the type of cable you use. For each applicable segment of coaxial cable,you can have 30 nodes. Each segment of twisted pair cable connects two nodes inan arrangement called a “point-to-point” configuration.

     As with any baseband network, Ethernet is easy to install. It requires only cabling andinterface modules. Depending on cable length, you may need an electronic repeaterand/or cable switching box, to extend the amount of cabling to its maximum, to form adistributed star topology, and to utilize every type of cable available.

    Ethernet NodesThe two types of nodes on the Andover Continuum Ethernet are Network Controllers(e.g., NetControllers) and workstations. Each controller requires two types of IDs: oneyou assign strictly for use by the local network, called the EnergyNet ID, and anotherthat allows the unit to be used on not only your Ethernet, but on a world-wide Internet(called the IP Address).

    Configuration of both these identifiers is done through the Command Terminalinterface or through the Continuum workstation and locally at the controller throughthe use of an externally connected terminal attached to COMM Port 3.

     A complete procedure for setting up the Ethernet addresses in the NetController canbe found in the Commissioning  section of this document.

  • 8/20/2019 Continuum NetController Reference

    43/76

    Andover Continuum NetController Reference 35 

    Ethernet Connections

    The controller module is equipped with an on-board Ethernet interface—completewith connector(s)—corresponding to one of the following Ethernet media types:

    10BASE-T

    10BASE-FL

    Different connectors, cable limitations, and network termination requirements apply tothe Ethernet, depending on which type of option your NetController uses.

    10BASE-T Ethernet

    Cable Limitations:

    This option provides a standard RJ-45 connector for Ethernet. Unshielded twistedpair cable is used to form this type of network (you actually use a cable with dualtwisted pairs—one for the transmit signal, and one for the receive signal). Themaximum cable length you can use between two nodes is 327 feet (100 meters). Themaximum length for the network segment is 1,635 feet (500 meters). If you need touse a cable that exceeds the recommended maximum length, use a networkrepeater.

    10BASE-T Cable Specifications

    Cables used to form the 10BASE-T Ethernet should be twisted pair wire, (Category 3(CAT-3) or Category (CAT-5) with CAT-5 preferred). The cable should have anominal impedance of 100 Ω  (85 –111 Ω).

    Example:

    Twisted Pair Belden 9562

    Twisted Pair Plenum Belden 88102

  • 8/20/2019 Continuum NetController Reference

    44/76

    Instal lation

    Plug the connector of the Ethernet cable into the RJ-45 connector on theNetController module. You must connect the other end of the cable to an EthernetHub or to another NetController.

    NetController to NetController

    Or

    PC to NetController

    TD+ 1 

    TD- 

    RD+ 

    Not Used 

    Not Used 

    RD- 

    Not Used 

    Not Used 

    The TD and RD pairs on the unshielded  

    twisted pair cable should be crossed if two 

     

    controllers are attached at each end of  

    the unshielded pair link segment.

    1

    2

    4

    5

    6

    7

    8

    3

    TD+

    TD-

    RD+

    Not Used

    Not Used

    RD-

    Not Used

    Not Used

    TD+1

    2

    4

    5

    6

    7

    8

    3

    1

    2

    4

    5

    6

    7

    8

    3

    TD-

    RD+

    Not Used

    Not Used

    RD-

    Not Used

    Not Used

    TD+

    TD-

    RD+

    Not Used

    Not Used

    RD-

    Not Used

    Not Used

    NetController to Bridge, HubUse a straight-through cable to 

    attach to a bridge or hub 

    36 TAC

  • 8/20/2019 Continuum NetController Reference

    45/76

     

    10BASE-FL Ethernet

    Cable Limitations:

    This option outfits the NetController module with standard ST fiber optic cable

    connectors for Ethernet. Fiber optic cable is used to form this type of network. The

    specific type of cable is called graded index, multimode fiber optic cable. This type of

    cable is ideally suited to the 850 nm wavelength signal used by the 10BASE-FL

    Ethernet interface. The maximum cable length you can use between two nodes is

    6,561 feet (2,000 meters). The maximum length for the network segment is 19,683

    feet (6,000 meters). If you need to use a cable that exceeds the recommended

    maximum length, use a TAC EnergyLink E2500 as a network repeater.

    10BASE-FL Cable Specific ations

    Use the following table to select your fiber optic cable. If your application has more

    specific requirements, please telephone:

    Siecor: 

    (704) 327-5000 (USA) (306) 683-5500 (Canada) 1 800 743-2671 (Internationa

    Cable Type Siecor Number Belden Number

    Indoor, PVCJacket, Riser-Rated

    002K81-31141-24 (1 pair)004K81-31141-24 (2 pair)

    225182 (1 pair)225364 (2 pair)

    Indoor,

    Smoke/Plenum-Rated

    002K88-31141-29 (1 pair)

    004K88-31141-29 (2 pair)

    225812 (1 pair)

    225864 (2 pair)

    Outdoor 002K14-14110-20 (1 pair)004K14-14110-20 (2 pair)

    225432 (1 pair)225414 (2 pair)

    Instal lation

    Connect one end of the fiber cable (two color coded connectors) to the

    corresponding ST Ethernet connectors on the NetController module. You must

    connect the other end of the cable to an Ethernet hub or to another controller. The

    figure (below) illustrates a point-to-point fiber optic cable connection.

    Receive 

    Transmit 

    Receive 

    Transmit 

    Andover Continuum NetController Reference 37 

  • 8/20/2019 Continuum NetController Reference

    46/76

    38 TAC

    Token Ring

    The NetController can be connected to workstations and other NetControllers via astandard Token Ring interface. This connection is accomplished via one RJ45 jack.

    Token ring connects workstations and controllers together in a closed ring. Deviceson the ring cannot transmit data until permission is received from the network in theform of an electronic 'token'.

    The NetController connects to the Multistation Access Unit (MAU or MSAU) throughan RJ45 terminated lobe cable consisting of four wires; two for transmit and two forreceive. The cable can be Shielded Twisted Pair or Unshielded Twisted Pair. Although the token ring stations are attached to the MAU in a physical starconfiguration, a true ring is maintained inside the MAU.

    The NetController Token Ring RJ-45 connector is an eight conductor unit of whichfour pins are used:

    Pin 3 - Transmit -

    Pin 4 - Receive +Pin 5 - Receive -Pin 6 - Transmit +

    Distance Between Controllers, Workstations and Other Nodes

    In token ring networking, distance requirements differ from vendor to vendor. In

    general terms, the recommended standard distance between stations for two-pair

    shielded cable is approximately 300 meters, and the recommended standard

    distance between stations for unshielded cabling is about 150 meters.

    Token ring distances are computed as the distance between repeaters. In a tokenring network, each workstation with a Network Interface Card (NIC) and eachNetController is a repeater. Therefore, the length between stations cannot exceed thecable lengths listed above.

    Some manufacturers use 'active' MAUs that can regenerate the token ring signal andact as a repeater. In these cases, the distances between the token ring workstationsand the MAUs can be much larger than many 'passive' MAUs. Many active MAUshave other network management features such as SNMP capabilities and auto-station removal for stations inserting at the incorrect speeds.

  • 8/20/2019 Continuum NetController Reference

    47/76

     

    Token Ring Speed Selection

    The NetController supports Token ring speeds of 4 megabits per second (500,000 bytesper second) and 16 megabits per second (2,000,000 bytes per second). Selection isdone via a small switch located inside the NetController case.

    Token RingRate Switch

    SW1

    SW1

    16 M/s 4 M/s

     

    The default position of the switch is for a 16Mb/s network. For older networks (4Mb/s),slide both switches to the right.

     A complete procedure for setting up the network addresses in the NetController can befound in the Commissioning  section of this document.

    Andover Continuum NetController Reference 39 

  • 8/20/2019 Continuum NetController Reference

    48/76

    Modem

    When you order the modem option for your NetController, COMM Port 3 includes aninternally connected data modem. All you need to do is connect a telephone line tothe modem using the Modem port. The Modem port accepts a standard RJ-11telephone jack connector.

    Having a modem built into the CPU facilitates connection to remote sites and allowsremote data acquisition.

    You can switch from using the modem to using the standard RS-232 connection ofCOMM 3 simply by pressing the Modem/RS-232 Override button on the front statuspanel.

    COMM 3Modem Connector

    TIP

    RING

     

    Before the modem can be operated, it must be configured from the CommandTerminal interface or through the Continuum workstation.

    The communications data rate, handshaking options, etc. are set up when definingCOMM 3 as a Modem. Consult the Command Terminal User Guide, the Continuum CyberStation Configurator’s Guide or the Continuum online help for specificinformation.

    40 TAC

  • 8/20/2019 Continuum NetController Reference

    49/76

     

    Status/Control Panel

    Status IndicatorsThe NetController includes a complete indicator status panel on the front of the module.

    Status Panel

    Indicators provide status information on communications port use, network traffic andNetController internal operation.

    The following page lists the various indicators and describes their operation.

    Control Push Buttons

    There are two control push buttons along with the status indicators located on the frontpanel. These buttons provide a hardware reset to the module as well as a way todisengage the modem from COMM Port 3. The following describes the action of each:

    CLEAR MEMORY

    The CLEAR MEMORY button erases al l  the memory in the NetController, includingconfiguration details, point information, and Plain English programming— this action isoften referred to as a “hard reset.” Clearly, this is not a button you want to press unlessyou really  mean it—Be careful!

    MODEM-RS-232 OVERRIDEThis button alternately engages and disengages the optional internal modem fromoperating on COMM Port 3. This allows Modem users to use the COMM Port 3 as ageneral purpose RS-232 port. Pressing the button disengages the modem. Anotherpress engages the modem, etc.

    If the internal modem is connected, upon reset, the controller defaults to having Modemselected.

    Andover Continuum NetController Reference 41 

  • 8/20/2019 Continuum NetController Reference

    50/76

    42 TAC

    Indicator Descriptions

    The following describes the functions of each of the status indicators on the front panel:

    CPU Status Indicators

    POWER

    The power status indicator is ON if the NetController module is receiving power from

    the power supply.

    CPU

    The CPU (for Central Processing Unit ) indicator flashes constantly (may appear as

    if it is steady on) if the NetController module is active—many refer to this indicator as

    the NetController’s “heartbeat.”

    SCAN

    The scan indicator flashes once for every scan executed by NetController.

    ERRORThe ERROR indicator remains OFF until an error occurs.

    If the NetController fails an internal system test, the ERROR indicator blinks a preset

    number of times, then pauses, and repeats the blinking and pausing sequence—this

    blinking pattern will persist until you reset the controller. The number of blinks

    between pauses identifies the specific problem (as shown in the table below).

    ERROR Ind icator B link Rates (before a paus e)

    # Blinks Type of Failure

    17 CX Firmware is corrupt (Bad Flash/ROM or bad update)

    18 LAN Card's memory is faulty - Try replacing the LAN Card.

    19 Problem creating certain System Tasks - Maybe due to lack of memory.

    20 Problem with the NIC - Try replacing the LAN Card

    21 reserved

    22 RTC Failed - Possible Hardware issue

    23 reserved

    24 Problem with the PIT chip - H/W related

    25 Problem creating Timer Tasks - Maybe due to lack of memory

    26 to 27 reserved

    28 The RAM memory is faulty or bad. Try replacing the RAM module(s).

    29 to 62 Problem creating certain System Tasks - Maybe due to lack of memory.

    63 Copy protection - Flash Upgrade file is invalid for this Controller (UPD file is Serial #protected)

    64 Problem creating the Uprev task - Maybe due to lack of memory.

    Note: If a Plain English program disables due to an error, the ERROR indicator illuminates and staysON (without blinking)—if this occurs, you can turn the indicator off by setting the ERRORS systemvariable to zero.

  • 8/20/2019 Continuum NetController Reference

    51/76

    Andover Continuum NetController Reference 43 

    CommPort Act iv i ty Ind icators

    There are four sets of CommPort activity indicators—one for each CommPort. The

    indicators in this group report on the following:

    TD

    The TD (for Transmit Data) indicator flashes quickly as data is being transmitted outthrough the CommPort.

    RD

    The RD (for Receive Data) indicator flashes quickly as data is being received through

    the CommPort.

    Modem Activi ty Indicators

    These indicators are applicable only if your NetController module is equipped with an

    internal modem option. The indicators in this group report on the following:

    DCD

    The DCD (for Data Carrier Detected) indicator is ON if the modem has detected and

    synchronized with an external carrier signal from another modem.

    DTR

    The DTR (for Data Terminal Ready) indicator is ON if the controller has asserted

    DTR.

    SELECTED

    This indicator is ON if the modem has been enabled via the MODEM-RS-232

    OVERRIDE push button. When it is ON, it indicates COMM Port 3 is in Modem

    mode. When OFF, COMM Port 3 is a general RS-232 port.

    I /O Bus Activi ty Indicator

    This indicator reports on the following:

    STATUS

    The STATUS indicator flashes rapidly as data is being transmitted out across the I/O

    Bus.

  • 8/20/2019 Continuum NetController Reference

    52/76

    44 TAC

    Ethernet A ctivi ty Indicators (for Ethernet-equipped m odels)

    The indicators in this group report on the following:

    TD

    The TD (for Transmit Data) indicator flashes rapidly as data is being transmitted out

    across the Ethernet.

    RD

    The RD (for Receive Data) indicator flashes rapidly as data is being received from

    the Ethernet.

    COL

    The COL (for Collision) indicator is ON whenever the controller detects data collisions

    on the Ethernet.

    LINK (Note: this indicator applies only to 10BASE-T Ethernet.)The LINK indicator is ON whenever the controller detects a valid 10BASE-T Ethernet

    link.

    POL (Note: this indicator applies only to 10BASE-T Ethernet.)

    The POL (for Polarity) indicator is ON if a cable polarity reversal has been detected

    on the 10BASE-T Ethernet.

    Token Ring Ac tivi ty Indicators (for Token Ring-equipped models)

    The indicators in this group report on the following:

    ACTIVITY

    This indicator flashes rapidly as data is being transmitted/received across the

    network.

    16MBPS

    This indicator is ON whenever the communications rate switch is in the 16 Mb/s

    position indicating the high speed network communication rate.

    4MBPS

    This indicator is ON whenever the communications rate switch is in the 4 Mb/s

    position indicating the low speed network communication rate.

  • 8/20/2019 Continuum NetController Reference

    53/76

    Andover Continuum NetController Reference 45 

    Operation

    Power OnIMPORTANT

    Before applying power to the NetController make sure all connections are secure.

    The NetController has no power switch. It is assumed that it is connected to anappropriate Continuum power supply module. To apply power to the system, the powerswitch located on the left side of the power supply module case must be depressed.

    The switch is a rocker type with each side marked according to function. Pressing the sidemarked with the I turns the power on. The POWER status indicator illuminates.

    To remove power, press the side marked O.

    Once power is applied, any pre-loaded Plain English programs residing in theNetController begin operating. Otherwise, the power-on system tests run and thecontroller awaits instructions.

  • 8/20/2019 Continuum NetController Reference

    54/76

    46 TAC

    Commissioning

    Once the NetController has been mechanically installed and electrically connected, thecontroller’s network address information must be entered so the Continuum software cancommunicate with the controller. This operation is called “commissioning”.

    What You’ll NeedCommissioning a NetController requires a laptop or other computer that is running an ASCII terminal emulator. Terminal emulators are common programs that allow you tocommunicate simply with RS-232 devices. One emulator program, HyperTerminal, is builtinto Windows and is available from the Accessories menu off of the Start menu.

    ConnectionsYou can connect to the NetController either directly or through a modem, using a devicewith a keyboard and display. These devices are often referred to as ASCII terminals, TTYreplacements, or terminals. We call them command terminals.

    Your command terminal must be DEC VT100 or VT220 compatible, or your computermust be running a terminal emulation program for one of these terminals.

    Communications between the NetController and the command terminal is through theRS-232 interface. Connect the NetController Comm Port and the command terminal’sSerial or Comm port.

    Connections made through a modem are straightforward; however, refer to the modemmanufacturer’s guidelines before making the connection.

    Direct connection requires an RS-232 Null Modem cable. The NetController’s defaultstate is for connection to the CyberStation via a modem. If you are connecting directly tothe controller via a network, select “MODEM RS-232 OVERRIDE” on the NetController’sdisplay panel.

    RS-232 communications operates at a number of speeds called the Baud Rate. Both theNetController and the command terminal must be set to the same baud rate tocommunicate. Use Comm3 on the NetController. The following table shows the correctsettings:

    RS-232 Settings

    Baud rate 9600

    Data Length 8 bits

    Parity None

    Stop bits One

  • 8/20/2019 Continuum NetController Reference

    55/76

    Example NetController Commissioning using HyperTerminal

    The following is an example procedure for connecting the CyberStation to theNetController using the emulator program, HyperTerminal, built into Windows 95. OpenHyperTerminal from the Accessories menu off the Start menu.

    •  For modem connection, enter a name for your connection, select an icon, andclick OK.

    •  For direct connection, enter a name for your connection and click OK.

    The Connect To dialog box appears.

    •  For modem use, fill in the appropriate dial-up information, select the desired portand click OK.

    •  For direct connection, select the desired port and click OK.

    Andover Continuum NetController Reference 47 

  • 8/20/2019 Continuum NetController Reference

    56/76

    When the Port Settings box appears configure your command terminal Port Settings asfollows and click OK:

    48 TAC

  • 8/20/2019 Continuum NetController Reference

    57/76

    Logging on to the NetController

     After connection, power up the terminal and the NetController. In the blank screen at thecommand terminal type:

    WINDOW 

    The characters do not echo to your display. If they were received properly, the commandterminal interface window appears:

    For security reasons, access to the NetController internal setup program is limited topeople who need to use it, so you must log on the system. Your System Administratorshould have been given a User ID and Password. The default User ID and Password areboth ACC. These defaults should be changed as soon as possible to preventunauthorized users from entering Continuum.

    Type your user name and press the TAB key, then type your password and click Enter tolog into the controller.

    Andover Continuum NetController Reference 49 

  • 8/20/2019 Continuum NetController Reference

    58/76

     

    The Command Terminal Main Window appears containing the following features:

    Menu Bar   There are four menus (View, Edit, Connect, and Logout),with the current menu highlighted. In the figure above, Viewis the current menu.

    Command Prompt  Issue commands to the system at the R> prompt in theCommand Window. (The R indicates “Ready.”)

    Status Bar   The status line displays information on the status of the

    Infinity control system.

    Controller Path Shows what controller the command terminal is currentlyconnected to.

    To enter commands at the Command Prompt, pres the F4 key. To toggle between theCommand Prompt and the Menu Bar, press the F4 key again.

    50 TAC

  • 8/20/2019 Continuum NetController Reference

    59/76

    Setting the NetController Network Address InformationSelect Edit from the Menu Bar. Using the arrow keys, move the curser down to highlightthe Controller and press Enter

     After the ‘Open a Controller’ window appears, type in the name of your NetController andpress the Enter key. Pressing F2 will reveal a list of any known NetControllers availableto connect to, just use the arrow keys to select the controller to connect to and pressEnter.

    Andover Continuum NetController Reference 51 

  • 8/20/2019 Continuum NetController Reference

    60/76

    The Network setup form contains all the address information. Enter the requestednumbers supplied by your Network Administrator.

    Name:  Displays the default name for the controller. You can change thisthrough the Command Terminal interface or through the CyberStationworkstation. Do not enter anything here.

    Description:  The description is also displayed as described above (Name).

    Serial Number:  Automatically displays the serial number of the controller. You do notenter it.

    Model:  Automatically displays the controller model number. You do not enterit.

    Status:  Displays Offline or Online depending on whether or not the controller ison the network.

    EnergyNet Id:  Enter the ID of this controller on your network.

    ProbeTime: Displays the rate per second that the controller probes the network forother devices.

    Version: Displays the version of the controller

    Ethernet ID:  Automatically displays the controller Ethernet ID or Token Ring IDnumber. You do not enter anything here.

    To set the IP address, press TAB until the TCP/IP button is highlighted and press Enter.

    52 TAC

  • 8/20/2019 Continuum NetController Reference

    61/76

    Setting the NetController IP Address

    Enter the appropriate information when the TCP/IP window appears. Use the arrow keysto move around in the window.

    IP Address:  Displays the Internet Address of the controller.Subnet Mask:  Displays the Subnet Address of the controller.

    Default Router:  Displays the Router ID number on your LAN.

    PPP IP Address: Displays the Point-to-Point Protocol Address of the controller.

    Web Server Port Web server port number (defaults to 80).

    Max Response Time:  Displays the Number of seconds the system is to wait for aresponse to a command before it is determined thatcommunications are lost.

    When the “Send ACC Modem Initialization String Upon Reset” is set, the followingdefault command strings are sent to initialize the ACC modem:

     AT&F\015 ATE\015 ATV&C1&D2&S1S0=1\\N3\\A3%%E1%%C1X3&W\015

     After entering the particulars, press the TAB key until the Save button is highlighted andpress Enter.

    Back at the main form, TAB to the Save button and press Enter.

    Commissioning is now complete from the controller end. Power down the controller to

    write the new settings into EEPROM. Log onto the controller once again and verify yournew settings.

    You will still have to create a new controller object and fill in much of the sameinformation at the Continuum workstation or Command Terminal to complete the process.

    Andover Continuum NetController Reference 53 

  • 8/20/2019 Continuum NetController Reference

    62/76

    54 TAC

    UPS Programming

    The NetController acts as the intelligence in your system. Plain English programs arecreated and then downloaded from the Command Terminal or from the Continuum workstation and are executed by the CPU within this module. There are several PlainEnglish commands that, when inserted into your programs, allow the NetController tosense when the system is operating on battery backup power (UPS operation) and toremove power from critical areas before the available power is depleted.

    The following Plain English keywords and system variables pertain to this UPS operation:

    •  PowerFail

    •  CPUPower

    •  ModemPower

    •  PowerUpTime

    Detecting a Power FailureWhen the main AC power fails, the UPS versions of the Continuum power supply signalthe NetController that they have lost AC power. You can add a routine to your program totest for this occurrence using the PowerFail system variable:

    If PowerFail is ON then …..

    Turning Off Various SubsystemsWhen a loss of power is detected, it signals that the system is operating using backupbatteries. In order to conserve power during this operation, you have the ability to remove

    power from the optional modem and or the CPU itself. The following commands would beused in both of these scenarios:

    If PowerFail is ON then SET ModemPower to OFF ‘ turns off power to the modem

    If PowerFail is ON then SET CPUPower to OFF ‘ turns off power to the CPU and allsubsystems including the modem

    How Long Was I Down?The PowerUpTime system variable can be used to keep track of how long it has been

    since the last power failure.

    More Information For more comprehensive examples, refer to the descriptions of each of these keywordsor system variables in the Plain English Language Reference, 30-3001-872, or theContinuum online help.

  • 8/20/2019 Continuum NetController Reference

    63/76

     

     Appendix ACommand Terminal

     Interface

    Andover Continuum NetController Reference 55 

  • 8/20/2019 Continuum NetController Reference

    64/76

    56 TAC

  • 8/20/2019 Continuum NetController Reference

    65/76

    Andover Continuum NetController Reference 57 

    Command Terminal Interface

    What is the Command Terminal Interface?

    Continuum NetControllers include a firmware-based user interface through whichcommands may be passed to configure and control its actions. This interface requires aseparate personal computer running a terminal emulator program or a dedicated ASCIIterminal. Communications with the Command Terminal firmware are carried out over an

    RS232 link through any CX Comm port configured as AutoSet.

    The typical and recommended path for programming a NetController is through the useof a separate personal computer (Continuum workstation running the CyberStationapplication). However, if a CyberStation is not present, it is possible to program theNetController directly through the Command Terminal interface. The Command Terminalinterface has the same capabilities of a Continuum CyberStation except for the followingitems:

    •  Configuring Alarms

    •  Schedules

    •  Area Objects

    •  Personnel Objects

    Particularly valuable as a site troubleshooting aid, using the Command Terminal interfacemakes it possible to write programs, create and access system points and configurationof networks and SNMP alarms.

    The Command Terminal Configuration Guide, 30-3001-843, provides you with detailedinformation about using the Command Terminal mode, including procedures to:

    •  Commission the NetController

    •  Create and configure object types

    •  Create and configure points

    •  Save and reload controllers

    •  Use the program editors to create controller-resident Plain English programs

  • 8/20/2019 Continuum NetController Reference

    66/76

    58 TAC

  • 8/20/2019 Continuum NetController Reference

    67/76

     

     Appendix B NetModem

     Removal/Replacement

    Andover Continuum NetController Reference 59 

  • 8/20/2019 Continuum NetController Reference

    68/76

    60 TAC

  • 8/20/2019 Continuum NetController Reference

    69/76

    NetModem Removal/Replacement

    Disconnect the PowerBefore performing removal or installation of the NetModem board, the NetControllermust be disconnected from any power source. Although it is possible to perform theinstallation with the controller mounted to a DIN rail, it is much easier to do with the unitplaced on a table or workbench.

    Open the NetController CaseThe to