SPLIT TYPE AIR CONDITIONER CEILING TYPE (50Hz) Indoor unit Outdoor unit ABYA45LCT AOYA45LBTL CONTENTS SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . 1 DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . 2 REFRIGERANT SYSTEM DIAGRAM . . . . . 4 CIRCUIT DIAGRAM . . . . . . . . . . . . . . . . . . . 5 ERROR DETECTION . . . . . . . . . . . . . . . . . 6 INDOOR PCB CIRCUIT DIAGRAM . . . . . . . . . . 10 OUTDOOR PCB CIRCUIT DIAGRAM 13 PARTS (INDOOR UNIT) . . . . . . . . . . . . . . 17 PARTS (OUTDOOR UNIT) . . . . . . . . . . . . 22 ACCESSORIES . . . . . . . . . . . . . . . . . . . . . 26

Upload: others

Post on 27-Jul-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CONTENTSaircon-info.com/wp-content/uploads/Fujitsu/Ceiling...W3 W6 W7 W1 W2 TM102 TM 10 RED U W305 V W304 W W 30 CN407 W12 W13 W21 W22 W16 W17 CN37 CN30 CN8 0 CN801 CN27 W200 FUSE

SPLIT TYPEAIR CONDITIONERCEILING TYPE (50Hz)

Indoor unit Outdoor unit

ABYA45LCT AOYA45LBTL

CONTENTSSPECIFICATIONS . . . . . . . . . . . . . . . . . . . . 1DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . 2REFRIGERANT SYSTEM DIAGRAM. . . . . 4CIRCUIT DIAGRAM. . . . . . . . . . . . . . . . . . .5

ERROR DETECTION. . . . . . . . . . . . . . . . .

6INDOOR PCB CIRCUIT DIAGRAM . . . . . .. . . .10OUTDOOR PCB CIRCUIT DIAGRAM

13PARTS (INDOOR UNIT) . . . . . . . . . . . . . . 17PARTS (OUTDOOR UNIT) . . . . . . . . . . . . 22ACCESSORIES. . . . . . . . . . . . . . . . . . . . . 26

Page 2: CONTENTSaircon-info.com/wp-content/uploads/Fujitsu/Ceiling...W3 W6 W7 W1 W2 TM102 TM 10 RED U W305 V W304 W W 30 CN407 W12 W13 W21 W22 W16 W17 CN37 CN30 CN8 0 CN801 CN27 W200 FUSE

H x W x DOUTDOOR UNIT

DIMENSIONS

Gross / NetOUTDOOR UNIT

WEIGHT

POWER SOURCECoolingRUNNING

CURRENT Heating

INPUT WATTSCooling

Heating

E.E.R.CoolingHeating

CoolingHeating

STARTING CURRENTMOISTURE REMOVAL

AIRCIRCULATIONOUTDOOR

FAN MOTORDiscriminationHigh speed

INDOORUNIT

Middle speedLow speed

Upper fanLower fan

DiscriminationOUTDOORUNIT(cool / heat)

TYPE Cooling & Heating

INDOOR UNIT ABYA45LCT

OUTDOOR UNIT

COOLING CAPACITYHEATING CAPACITY

INDOOR UNIT H x W x D 240 x 1,660 x 700 mm

INDOOR UNIT Gross / Net 58 kg / 46 kg

17.0 A

16.5 A

3.89 kW3.77 kW

3.21 kW/kW3.71 kW/kW

15.0 A4.5 L/hr

6,200 m3/hMAXIMUM CURRENT 20.0 A

AIRCIRCULATION INDOOR 2,100 m3/h6,900 m3/h

MFH-45RV1,200 r.p.m.

1,000 r.p.m.830 r.p.m.

Quiet 680 r.p.m.

12.5 kW14.0 kW

ELECTRICAL DATA

TYPE

DISCRIMINATIONWEIGHT (with oil)REFRIGERANT TYPE R410A

Hermetic type, Inverter,4 poles, 3 phase,

DC motor, Twin Rotary

PRECHARGED REFRIGERANT

COMPRESSOR AND REFRIGERANT

2009.02.25 1

SPECIFICATIONS

MAX PIPE LENGTHMAX PIPE HEIGHT 30 m

Pipe length

FULL CHARGE

ADDITIONAL CHARGE 50 g/m

NOISE LEVELHigh speed

INDOORUNIT

Middle speed

Low speed

Cooling

Heating

49 dB45 dB

39 dB

Quiet 34 dB

OUTDOORUNIT

107 kg / 98 kg

1,290 x 900 x 330 mm

MFE-60TVT

AOYA45LBTL

55 dB56 dB

750 r.p.m.850 r.p.m.

230 V 50 Hz

DA420A3F-21ZA23.7 kg

3,350 g50 m

20 m 3,350 g30 m 3,850 g40 m 4,350 g50 m 4,850 g

Page 3: CONTENTSaircon-info.com/wp-content/uploads/Fujitsu/Ceiling...W3 W6 W7 W1 W2 TM102 TM 10 RED U W305 V W304 W W 30 CN407 W12 W13 W21 W22 W16 W17 CN37 CN30 CN8 0 CN801 CN27 W200 FUSE

DIMENSIONS

1,660 240

700

1,600 130

300

(Unit : mm)

INDOOR UNIT

2098.02.10 2

Page 4: CONTENTSaircon-info.com/wp-content/uploads/Fujitsu/Ceiling...W3 W6 W7 W1 W2 TM102 TM 10 RED U W305 V W304 W W 30 CN407 W12 W13 W21 W22 W16 W17 CN37 CN30 CN8 0 CN801 CN27 W200 FUSE

(Unit : mm)

OUTDOOR UNIT

2009.02.10 3

31900 330 12

921

1,29

0

400

650

370

Air Flow

77

Page 5: CONTENTSaircon-info.com/wp-content/uploads/Fujitsu/Ceiling...W3 W6 W7 W1 W2 TM102 TM 10 RED U W305 V W304 W W 30 CN407 W12 W13 W21 W22 W16 W17 CN37 CN30 CN8 0 CN801 CN27 W200 FUSE

REFRIGERANTSYSTEM DIAGRAM

OUTDOOR UNIT INDOOR UNIT

Refrigerant Pipe 15.88mm (5/8")

: Cool

Refrigerant direction

: Heat

Evaporator

Refrigerant Pipe9.52mm (3/8")

Charging Valve

ChargingValve

Accumulator

Strainer

Compressor

ExpansionValve

Strainer

Condenser

Strainer

4-wayValve

Muf

fler

x 2

PressureCheck Valve

HighPressureSwitch

2009.02.10 4

Page 6: CONTENTSaircon-info.com/wp-content/uploads/Fujitsu/Ceiling...W3 W6 W7 W1 W2 TM102 TM 10 RED U W305 V W304 W W 30 CN407 W12 W13 W21 W22 W16 W17 CN37 CN30 CN8 0 CN801 CN27 W200 FUSE

TERMINAL

2009.02.25 5

INDOOR UNIT

OUTDOOR UNITCIRCUIT DIAGRAM

ORANGEREDBROWN

WHITEBLUEPURPLEGRAY

REDWHITEBLACK

REDWHITEBLACK

YELLOWWHITEBLACK

RED

BROWN

GR

EE

N

GR

EE

N

GR

EE

N /

YE

LLO

W

GR

AYG

RAY

GR

AYG

RAY

GR

AYG

RAY

GR

AYG

RAY

GR

AYG

RAY

GR

AY

WHITEYELLOWORANGE

REDBROWN

WHITEYELLOWORANGE

REDBROWN

BLACKBLACK

BLACK

BLACK

GRAYGRAY

12345678

12345678

12345678

1234567

123

1234567

123

123

12

12345

12345

12345

12345

12345

12345

12345

12345

123

12

1 2 3 4 5 6 7 8

1 2 1 2 1 2

1 2 3 4 5 6 7 81 2 3 4 5 6 7 8

1 2 31 2 3

1 2 31 2 31 2 3 4 5 6 7 8

1 2 3 1 2 1 2

12345678

12345678

123456

123456

12

12

1 2 1 2

12

CN5 CN7 CN8

CN4 CN1

CN104 CN101W105W102W101

CN102 CN103 CN108

CN

106

CN

105

E101 E102

CN

6C

N14

CN

13

CN

10C

N9

CN

11C

N12

CN

3

F101

FUSE3.15A 250VF M

FAN MOTOR

M

M

STEP MOTOR

STEP MOTOR

THERMISTOR ( ROOM TEMP. )

THERMISTOR ( PIPE TEMP. )

INDICATOR PCB ASSY

TERMINAL

COIL

1 2 3

1 2 3

TO REMOTE CONTROL UNIT( OPTION PART )

POWERSUPPLY

PCB ASSY

CONTROLLERPCB ASSY

WH

ITE

WH

ITE

YELLOWBROWN

WHITEBLACK

RED

YELLOWBROWN

WHITEBLACK

RED

YELLOW

BROWN

WHITE

BLA

CK

RED

BLUEORANGE

WH

ITE

BLA

CK

BR

OW

NR

ED

BLA

CK

BLA

CK

WH

ITE

WH

ITE

GR

EE

N

BLACK

WHITE

ORANGE

ORANGE

RED

BLACK

BLUE

YELLOW

YELLOW

ORANGEREDBROWN

BLACK

WHITE

RED

BLACK

BLACK

BROWN

BLACK

BROWN

BLUE

BLACK

BLACK

REDRED

BROWN

WHITE

123456

123456

12345

123456

123456

1234567

1234567

123456

123456

7 7

123

123

12

12

1 2 3 4

1 2 31 2 3

1 2 31 2 3

1 21 2

1 21 2 1 2

1 2 1 21 2 1 2 1 2

1 2 1 2

CN24 CN21 CN22 CN23 CN26 CN25

CN1 CN34

CN1 W9 W8

W3 W6 W7 W1 W2

TM102

TM101

RED

UW305

VW304

WW303

CN407

W12W13

W21W22

W16

W17

CN37

CN30

CN800

CN801

CN27

W200

FUSEF2 T 3.15A - 250V

FUSEF4 T 5A - 250V

+ -

L1

L2

PN

W10

W11

C ( T )

R ( R )

S ( S )

COMPRESSOR

TERMINAL

CHOKECOIL

POSISTOR

EARTH

FUSE10A

FUSE25A

EARTH321 L N

E V

F M

F M

EXPANSIONVALVE COIL

FAN MOTOR 2

FAN MOTOR 1

4WV

SOLENOID COIL

HIGH PRESSURE SWITCH

THERMISTOR ( OUTDOOR TEMP. )

THERMISTOR ( COMPRESSOR TEMP. )

THERMISTOR ( HEAT SINK TEMP. )

THERMISTOR ( PIPE TEMP. )

THERMISTOR ( DISCHARGE TEMP. )

THERMISTOR ( PIPE MID. TEMP. )

C M

ACTPMINVERTER PCB ASSY

POWER SUPPLY PCB ASSY

POWER SOURCE

TERMINAL

Page 7: CONTENTSaircon-info.com/wp-content/uploads/Fujitsu/Ceiling...W3 W6 W7 W1 W2 TM102 TM 10 RED U W305 V W304 W W 30 CN407 W12 W13 W21 W22 W16 W17 CN37 CN30 CN8 0 CN801 CN27 W200 FUSE

PCB Circuit Diagrams not available at time of publication

Page 8: CONTENTSaircon-info.com/wp-content/uploads/Fujitsu/Ceiling...W3 W6 W7 W1 W2 TM102 TM 10 RED U W305 V W304 W W 30 CN407 W12 W13 W21 W22 W16 W17 CN37 CN30 CN8 0 CN801 CN27 W200 FUSE

2009.02.10 13

Troubleshooting with the indoor displayINDOOR UNIT

ERROR DETECTION

Error is displayed on the wired andwireless remote control.

FILTER Lamp (Red)

TIMER Lamp (Orange)

OPERATION Lamp(Green)

Lamps show error contents by flashing as follows.OPERATION

LampTIMERLamp

FILTERLamp Error contents

2 times

Indoor signal error3 times4 times5 times8 times Wired remote controller abnormal

2 times 2 times Indoor room temperature sensor error

2 times 3 times Indoor heat exchanger temperature

Indoor heat exchanger temperaturesensor (middle) error

2 times 4 times sensor (inlet) error2 times 6 times Float switch operated

3 times 2 times Outdoor discharge pipe temperaturesensor error

3 times 3 times Outdoor heat exchanger temperature

Outdoor heat exchanger temperature

sensor (outlet) error3 times 4 times Outdoor temperature sensor error3 times 7 times Heat sink thermistor (Inverter) error3 times 8 times Compressor temperature sensor error3 times 2 times 2-way valve temperature sensor error3 times 3 times 3-way valve temperature sensor error

3 times 4 times sensor (middle) error3 times 5 times Heat sink thermistor (P.F.C) error4 times 2 times Indoor manual auto switch abnormal4 times 4 times Power supply frequency detection error5 times 2 times IPM protection5 times 3 times CT error5 times 5 times Compressor location error5 times 6 times Outdoor fan error5 times 7 times Connected indoor unit abnormal

5 times 8 times Outdoor unit computer communicationerror

5 times 2 times Inverter error6 times 2 or 3 times Indoor fan abnormal7 times 2 times Discharge temperature error

7 times 3 times Excessive high pressure protectionon cooling

7 times 4 times 4-way valve abnormal

7 times 5 times Pressure switch abnormal,Pressure sensor abnormal

7 times 6 times Compressor temperature error7 times 7 times Low pressure error8 times 2 or 3 times Active filter abnormal8 times 4 times P.F.C. circuit error

9 times 2 times Refrigerant circuit address set-up error9 times 3 times Master unit, Slave unit set-up error9 times 4 times Connected indoor number set-up error

Flash means "0.5 second on / 0.5 second off".offoffoff

off8 times 6 times P.F.C. PCB erroroff

off

off

off

off

off

offoff

off

off

offoffoffoffoffoffoff

offoff

off

off

off

off

off

off

off

off

off

off

offoffoffoffoffoff

offoffoffoffoff

off

Page 9: CONTENTSaircon-info.com/wp-content/uploads/Fujitsu/Ceiling...W3 W6 W7 W1 W2 TM102 TM 10 RED U W305 V W304 W W 30 CN407 W12 W13 W21 W22 W16 W17 CN37 CN30 CN8 0 CN801 CN27 W200 FUSE

Troubleshooting at the remote control LCDREMOTE CONTROL (option)

This is possible only on the wired remote control.

Self-diagnosisIf an error occurs, the following display will be shown.

If "CO" appears in the unit number display,there is a remote control error.Refer to the installation instruction sheetincluded with the remote control.

(“EE” will appear in the set room temperature display.)

Unit number Error code

Ex. Self-diagnosis

SU MO TU WE TH FR SA

Errorcode Error contents

01132627

Indoor signal error

00 Wired remote controller abnormal02 Indoor room temperature sensor error

04 Indoor heat exchanger temperature sensor(middle) error

28 Indoor heat exchanger temperature sensor (inlet)error

09 Float switch operated0c Outdoor discharge pipe temperature sensor error

06 Outdoor heat exchanger temperature sensor(outlet) error

0A Outdoor temperature sensor error0E Heat sink thermistor (Inverter) error15 Compressor temperature sensor error1d 2-way valve temperature sensor error1E 3-way valve temperature sensor error

29 Outdoor heat exchanger temperature sensor(middle) error

2d Heat sink thermistor (P.F.C.) error20 Indoor manual auto switch abnormal2A Power supply frequency detection error17 IPM protection18 CT error1A Compressor location error1b Outdoor fan error1F Connected indoor unit abnormal1c Outdoor unit computer communication error2E Inverter error12 Indoor fan abnormal0F Discharge temperature error24 Excessive high pressure protection on cooling2c 4-way valve abnormal16 Pressure switch abnormal, Pressure sensor abnormal2b Compressor temperature error2F Low pressure error19 Active filter abnormal

2009.02.10 14

25 P.F.C. circuit error30 Refrigerant circuit address set-up error31 Master unit, Slave unit set-up error

33 P.F.C. PCB error32 Connected the indoor number set-up error

Page 10: CONTENTSaircon-info.com/wp-content/uploads/Fujitsu/Ceiling...W3 W6 W7 W1 W2 TM102 TM 10 RED U W305 V W304 W W 30 CN407 W12 W13 W21 W22 W16 W17 CN37 CN30 CN8 0 CN801 CN27 W200 FUSE

2009.02.10 15

Make a TEST RUN in accordance with theinstallation instruction sheet for the indoor unit.

OUTDOOR UNIT LED

When a malfunction occurs in the outdoor unit,the LED on the circuit board lights to indicate the error.Refer to the following table for the description of eacherror according to the LED.

Error contentsCommunication error(Indoor unit - Outdoor unit)

Discharg pipe temperature sensor

Outdoor heat exchanger temperature (outlet) sensor

Outdoor heat exchanger temperature (mid) sensor

Outdoor temperature sensor

Compressor temperature sensor

Heat sink temperature sensor

Pressure switch abnormal

IPM error

Compressor rotor position cannot detect

Compressor cannot operate

Outdoor fan abnormal (upper fan)

Outdoor fan abnormal (lower fan)

Pump down operation

No error

LED

1 flash

2 flash

3 flash

4 flash

5 flash

Discharge pipe temperature abnormal6 flash

7 flash

8 flash

9 flash

Compressor temperature abnormal10 flash

12 flash

13 flash

14 flash

15 flash

16 flash

1 sec. on/1 sec. offrepeat

Protect operation5 sec. on/1 sec. offrepeat

off

Page 11: CONTENTSaircon-info.com/wp-content/uploads/Fujitsu/Ceiling...W3 W6 W7 W1 W2 TM102 TM 10 RED U W305 V W304 W W 30 CN407 W12 W13 W21 W22 W16 W17 CN37 CN30 CN8 0 CN801 CN27 W200 FUSE

2009.02.10 16

SPECIAL INSTALLATION SETTING

PUMP DOWN (Refrigerant collecting operation)

1. When the product is stopped:

Perform the following procedures to collect the refrigerantwhen moving the indoor unit or outdoor unit

1

2

3

4

Press the PUMP DOWN switch on the outdoor unit.(The LED on the outdoor unit circuit board starts flashing.)(1 sec. on / 1 sec. off repeated)

The pump down operation (cooling operation) beginsright away. After oparation starts, close the three-wayvalve (liquid).

After 2 - 3 minutes, operation stops. Close the three-wayvalve (gas) within one minute after operations stops.

The LED will go out three minutes after it stops.Disconnect the power supply after confirming that theLED has gone out.

2. When the product is operating:

1

2

3

4

Press the PUMP DOWN switch on the outdoor unit.The LED on the outdoor unit circuit board starts flashing( 1 sec. on / 1 sec. off repeated), and operation stops.At this point, recovery has not been completed, so do notclose the three-way valves. (liquid and gas)

The pump down operation (cooling operation) be-gins after three minutes. Close the three-way valve(liquid) after operation starts.

After 2 - 3 minutes, operation stops. Close the three-wayvalve (gas) within one minute after operations stops.

The LED will go out three minutes after it stops. Dis-connect the power supply after confirming that the LEDhas gone out.

3-way valve(Liquid)

3-way valve(Gas)

DANGER

This part (Choke coil) generates high voltages.Never touch this part.

PUMP DOWN SW (SW2)

20 to 25 N-m (200 to 250 kgf-cm)

20 to 25 N-m (200 to 250 kgf-cm)

25 to 30 N-m (250 to 300 kgf-cm)30 to 35 N-m (300 to 350 kgf-cm)

35 to 40 N-m (350 to 400 kgf-cm)

6 to 7 N-m (60 to 70 kgf-cm)

Tightening torque

Connecting pipeBlank cap

Hexagon wrench

3-way valveCharging port

Cap

Outdoor unit

Use a 4 mmhexagon wrench.

Blankcap

6.35 mm (1/4 in.)

9.52 mm (3/8 in.)

12.70 mm (1/2 in.)15.88 mm (5/8 in.)

19.05 mm (3/4 in.)

Spindle (Hexagon wrench)

10 to 12 N-m (100 to 120 kgf-cm)Charging port cap

*When the pump down operation is repeated, temporarilydisconnect the power supply after opening the closed valves(both liquid and gas).Reconnect the power supply after 2 - 3 minutes and performthe pump down operation.

*When the start of the operation after pump down operationhas been completed, temporarily disconnect the power supplyafter opening the closed valves (both liquid and gas).Reconnect the power supply after 2-3 minutes and be sure toperform a test operation for cooling.

Page 12: CONTENTSaircon-info.com/wp-content/uploads/Fujitsu/Ceiling...W3 W6 W7 W1 W2 TM102 TM 10 RED U W305 V W304 W W 30 CN407 W12 W13 W21 W22 W16 W17 CN37 CN30 CN8 0 CN801 CN27 W200 FUSE

615

2

4

9

11

17

19

5

7

8

1318

15

3

1

16

14

14

INDOOR UNIT

2009.02.10 17

PARTS

10

11

12

20

9

6 Air Filter 9359739005

1 Kit (Base Sub Assy) 9371360010

9 Front Panel 9359734000

5 Intake Grille 9359738008

15 Hanger Bracket 9359742005

13 Hole Cover 9359691006

20 Badge 9359735083

14 Hinge Plate (Grille) 9359694007

7 Filter Guide R 93596920038 Filter Guide L 9359693000

16 Cover (Decoration) R 935974400917 Cover (Decoration) L 9359745006

10 Indicator PCB Assy 9705891043

2 Panel Left Sub Assy 93604270143 Kit (Panel Right Assy) 93713610174 Cover (Top) 9359737001

18 Kit (Side Cover R) 937136401819 Kit (Side Cover L) 9371365015

12 Receiver Cover 935971400211 PCB Holder 9359736004

Ref. Description Part number

Page 13: CONTENTSaircon-info.com/wp-content/uploads/Fujitsu/Ceiling...W3 W6 W7 W1 W2 TM102 TM 10 RED U W305 V W304 W W 30 CN407 W12 W13 W21 W22 W16 W17 CN37 CN30 CN8 0 CN801 CN27 W200 FUSE

35

36 22

23

28

33

2624

25

27

21

INDOOR UNITDrain pan, Flap

2009.02.10 18

3

27

28

29

2

32

333130

328

34

35 Kit (Separate Wall Sub Assy) 9371366029

21 Evaporator Assy 9372585078

Drain Pan Sub Assy 936042901827

24 Kit (Panel pipe L) Sub Assy 937136201425 Kit (Panel pipe R) Sub Assy 9371363011

28 Flap Assy 935973100929 Bushing 9359733003

-- Drain Cap 9358746004

23 Coupling Pipe Assy 9373038405

2 Panel Left Sub Assy 93604270143 Kit (Panel Right Assy) 9371361017

26 Reinforcement Metal 9359697008

31 Sector Gear 935972900630 Flap Spring 9359730002

32 Pinion Gear 935972800933 Motor Base 9359727002

22 Distributor Assy 9371325378

36 Pipe Fixture Metal 9359688006

-- Thermistor Spring A 313728262708-- Pipe Thermistor 9900022020

34 Step Motor V 9900362010

Ref. Description Part number

Page 14: CONTENTSaircon-info.com/wp-content/uploads/Fujitsu/Ceiling...W3 W6 W7 W1 W2 TM102 TM 10 RED U W305 V W304 W W 30 CN407 W12 W13 W21 W22 W16 W17 CN37 CN30 CN8 0 CN801 CN27 W200 FUSE

INDOOR UNITLouver Base Sub Assy

2009.02.10 19

48

43

47

44

46

45

42

41

50

49

51

42 Louver 935971900741 Louver Base Sub Assy 9360432025

43 Rod (Motor) 935972300444 Louver Link 935972600545 Louver Base 935971800046 Louver Spring 935972000347 Louver Stopper 935972400148 Louver Rod 935972500849 Step Motor H 990029701550 Louver Insulation R 935972100051 Louver Insulation L 9359722007

Ref. Description Part number

Page 15: CONTENTSaircon-info.com/wp-content/uploads/Fujitsu/Ceiling...W3 W6 W7 W1 W2 TM102 TM 10 RED U W305 V W304 W W 30 CN407 W12 W13 W21 W22 W16 W17 CN37 CN30 CN8 0 CN801 CN27 W200 FUSE

74

7372

68

69

70

62

62

64 64

65

6363

66

74

67

61

61

73

7271

INDOOR UNITFan motor

2009.02.10 20

69 Sirocco Fan Assy 9359701002

67 Casing 9359704003

73 Bearing B Assy 9357921006

61 Motor Mount 937799901662 Fan Motor Assy 960238901863 Motor Band A assy 937464701964 Motor Band B 937464802365 Reinforcement Motor Band 937800001866 Rubber 9385102002

72 Shaft Holder Bracket 935968600271 Shaft 935970700470 Joint Assy 9378038011

74 Shaft Holder Fixture 9359687009

68 Kit (Cover Casing) Sub Assy 9371367019

Ref. Description Part number

Page 16: CONTENTSaircon-info.com/wp-content/uploads/Fujitsu/Ceiling...W3 W6 W7 W1 W2 TM102 TM 10 RED U W305 V W304 W W 30 CN407 W12 W13 W21 W22 W16 W17 CN37 CN30 CN8 0 CN801 CN27 W200 FUSE

INDOOR UNITControl unit

2009.02.10 21

93

99

94

82

83

98

89

8895

81

87

92

91

86

97

96

84

85

Ref. Description Part number

89 Rubber Bushing 9357376004

81 Control Box Assy 9377912015

93 Room Thermistor 9703299025

84 Controller PCB Assy 9707393453

94 Wire Assy (Connector) 9707442021

95 Wire Assy (Connector) 9703339028

96 Wire Assy (Connector) 9702319014

97 Wire Assy (Connector) 9702318017

98 Remote Control 9315885012

99 Remote Control Holder 9305642045

83 Control Box B 9359713005

82 Control Box A 9359712008

86 Terminal 3P 9703345012

87 Terminal 3P 9306489045

88 Reactor Assy 9707457018

85 Power Supply PCB Assy 9707398168

91 Cord Clamp A 9359820017

92 Cord Clamp B 9359821014

Page 17: CONTENTSaircon-info.com/wp-content/uploads/Fujitsu/Ceiling...W3 W6 W7 W1 W2 TM102 TM 10 RED U W305 V W304 W W 30 CN407 W12 W13 W21 W22 W16 W17 CN37 CN30 CN8 0 CN801 CN27 W200 FUSE

1 6

75

23

4

3

OUTDOOR UNIT

PARTS

2009.02.10 22

1 Top Panel Sub Assy2 Front Panel3 Fan Guard4 Grip Side5 Service Panel Sub Assy6 Right Panel Sub Assy7 Valve Cover

9374417025937409402893743300109374173013937441506993744161419374174010

-- Emblem Rear 9351355005

Description Parts numberRef.

Page 18: CONTENTSaircon-info.com/wp-content/uploads/Fujitsu/Ceiling...W3 W6 W7 W1 W2 TM102 TM 10 RED U W305 V W304 W W 30 CN407 W12 W13 W21 W22 W16 W17 CN37 CN30 CN8 0 CN801 CN27 W200 FUSE

10

2007.02.06 19

1312

11

10

915

14

OUTDOOR UNIT

2009.02.02 23

9 Propeller Fan Assy10 Motor DC Brushless11 Condenser A Assy12 Condenser B Assy13 Separate Wall14 Cap Foot15 Base Assy

9366378020960284301593744330189374434015937462901593743450149374166046

Description Parts numberRef.

16

16 Coil Choke 9703458019

Page 19: CONTENTSaircon-info.com/wp-content/uploads/Fujitsu/Ceiling...W3 W6 W7 W1 W2 TM102 TM 10 RED U W305 V W304 W W 30 CN407 W12 W13 W21 W22 W16 W17 CN37 CN30 CN8 0 CN801 CN27 W200 FUSE

OUTDOOR UNIT

2008.11.13 24

56

55

54

57

18

17

26

42

25

19

24

23

21

22

20

17 3-Way Valve Assy18 3-Way Valve Assy19 Compressor Assy20 Accumulator Assy21 Solenoid22 Pressure Switch23 4-Way Valve24 Check Valve Assy25 Coil (Expansion Valve)26 Strainer Assy

55 Compressor Cover B56 Compressor Cover C57 Compressor Cover D

42 Expansion Valve Assy54 Compressor Cover A

9377958013937795901093780350109375250034990016505599001860129970035029937427401799001970259372524039

937443110693720670869375382025

93709471759374430109

Description Parts numberRef.

58 Solenoid 9900165055

58

Page 20: CONTENTSaircon-info.com/wp-content/uploads/Fujitsu/Ceiling...W3 W6 W7 W1 W2 TM102 TM 10 RED U W305 V W304 W W 30 CN407 W12 W13 W21 W22 W16 W17 CN37 CN30 CN8 0 CN801 CN27 W200 FUSE

31

38

27

36

28

29

33

37

OUTDOOR UNIT

2009.11.25 25

(Connector : Black)

3230

40

51

39

48

52

5341

504344

4546

47

(Green)(Blue)

(Red)(Yellow)

(White)

(Connector: Red)

47 Heatsink Thermistor

52 Fuse Holder (Large)

48 Wire (Pressure Switch)50 Thermistor (Heat Exchanger)

9900311018

050145401251 Fuse Holder (Small) 0501456016

93675950519900403010

27 Inverter Box A28 Inverter Box B29 Inverter Box C30 Inverter Box Duct

36 Posistor

38 Power PCB Assy39 Clamp (Cord)40 Terminal41 Fuse (Small)43 Thermistor (Dischage)44 Thermistor (Heat Exchanger)45 Thermistor (Outdoor)46 Compressor Thermistor

31 Inverter Box Cover32 Heat Sink B33 ACTPM

9374603015937462501793746050269374609017

970426501237 Inverter PCB Assy 9708013183

97056470229356857009990020302306003761169704219084990037403799003780359900156060

937460801093746070209707592016

Description Parts numberRef.

53 Fuse (Large) 0600086039

Page 21: CONTENTSaircon-info.com/wp-content/uploads/Fujitsu/Ceiling...W3 W6 W7 W1 W2 TM102 TM 10 RED U W305 V W304 W W 30 CN407 W12 W13 W21 W22 W16 W17 CN37 CN30 CN8 0 CN801 CN27 W200 FUSE

Name and Shape Q'ty Part numberApplication

INDOOR UNIT

Special nut A(large flange)

Special nut B(small flange)

Installationtemplate

Adhesive type 70 x 2301Drain hoseinsulation

For fixing the drain hoseL 280 mm

1VT wire

For indoor side pipe joint(large pipe)2

1

Coupler heatinsulator(large)

For indoor side pipe joint(small pipe)

4

Coupler heatinsulator(small)

For fixing the coupler heatinsulator

Large4

Small4

Nylon fastener

For installing indoor unit

For positioning the indoor unit

4

For installing indoor unit

1

312300787605

9360464002

313806350303

9378173569

9374714025

9378173521

9301501001

313005446653

313005446759

9360022004

For connecting the piping1Auxiliarypipe assembly

ACCESSORIES

2009.02.25 26

0700019036

0600185541

9305642045

93158850121

1

2

2

For air conditioner operation

For installing remote controlon the wall

For remote control

For mounting the remotecontrol holder

Remotecontrolholder

Remotecontrol

Battery

Tapping screw

Name and Shape Q'ty Part numberApplication

Installation(seal)

1

2

1

OUTDOOR UNIT

For outdoor unit drain pipingwork

For filling in a gap at theentrance of connection cords

Drain pipe

Drain cap

9303029015

313166024302

9374756018

Page 22: CONTENTSaircon-info.com/wp-content/uploads/Fujitsu/Ceiling...W3 W6 W7 W1 W2 TM102 TM 10 RED U W305 V W304 W W 30 CN407 W12 W13 W21 W22 W16 W17 CN37 CN30 CN8 0 CN801 CN27 W200 FUSE

OPTIONAL PARTS

Exterior

2009.02.25 27

Parts name Model No. Summary

Wired remote control

UTB-YUD UTB-GUD (geNE)UTB-XUD (fuJI Hiya)

Unit control is performedby wired remote control

Round duct UTD-RF204 For Ceiling type

Drain pumpunit UTR-DPB241 For Ceiling type