contents power outlet panels - amazon s3 · contents power outlet panels 6-1 6 power outlet panels...
TRANSCRIPT
February 2007
CA08101001E For more information visit:
www.eaton.com
Contents
Power Outlet Panels 6-1
6
Po
wer
Ou
tlet
Pan
els
Description Page
Power Outlet Panels
Surface Units
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-3
Pedestal Units
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-3
Product Selection
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-5
Catalog Numbering System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-5
Power Outlet Panel Receptacle Configuration Rules . . . . . . . . . . . . . . . .
6-6
Unmetered Surface Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-7
Metered Surface Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-7
Unmetered Pedestal Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-8
Metered Pedestal Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-8
Unmetered Back-to-Back Pedestal Type. . . . . . . . . . . . . . . . . . . . . . . . . . .
6-8
Metered Back-to-Back Pedestal Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-8
Dimensional Drawings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-9
Accessories and Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-15
Mobile Home Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-16
Receptacle Deadfront Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-16
Don’t Give Up!
If you don’t find the product you want in this catalog, try the Flex Center at
1-800-330-6479
.
Power Outlet Panel Family
February 2007
6-2
For more information visit:
www.eaton.com
CA08101001E
Power Outlet Panels
6
Product Description
Product Description
A Power Outlet Panel (or POP) is a device designed for outdoor service to meet temporary power requirements at construction sites and recreation vehicle (RV) parks. Construction sites and RV parks need to provide a safe and reliable means for users to access electricity and POPs provide the outlets for electrical access.
Application Description
Power Outlet Panels or POPs are also sometimes called Temporary Power Panels, Temporary Site Service Equipment or RV Panels.
Construction Site Application
When POPs are used at a construction site, they are installed on a temporary basis until electrical power is available at the building. The most common rea-son for needing a POP at a construc-tion site is to provide a power source for the contractor’s tools.
Construction Site Application
RV Park Application
When POPs are used at an RV park, they are installed for more permanent use and serve the purpose of provid-ing power to the vehicle’s appliances. Many RV parks now supply users with lighted POPs with TV and telephone jacks. A move towards offering more amenities at RV parks.
RV Park Application
Standards and Certifications
■
UL
�
Standard 231.
■
UL File Number E163588.
■
Receptacles conform to NEMA
�
and/or ANSI configurations as specified by the National Electrical Code
�
.
Product Specifications
The power outlet panels shall be designed for outdoor service to meet temporary power outlet requirements at construction sites and provide high quality, economical power to individual sites at recreational vehicle (RV) parks. Construction site panels shall be pro-vided with means to bond the neutral for service entrance applications. RV panels shall have a factory-installed insulated neutral bar.
Receptacles and Circuit Protection
The circuit protection shall be Eaton’s Cutler-Hammer
�
UL listed full-size Type BR or half-size Type BD circuit breakers. The receptacles shall be NEMA commercial/industrial grade and come in a wide variety of configurations. Ground fault protec-tion (GFCB) shall be provided at the 20 ampere duplex NEMA 5-20R recep-tacle or 20 ampere single-pole circuit breaker when required. Ground fault protection shall be provided at the circuit breaker for receptacles above 20 amperes when required.
Construction
The power outlet panel pedestal shall be of deadfront design and constructed of heavy gauge, 100 percent galvanized steel. Baked-on polyester powder coating shall be used for excellent mechanical strength, plus resistance to chalking caused by the sun’s ultraviolet rays. The power outlet panel surface and pedestal units shall have NEMA Type 3R rainproof enclosures.
Ease of Installation
Panels shall ship from the factory completely assembled, prewired with 100 percent copper wire, and tested in accordance with UL Standard 231. Door shall swing up and open for user convenience and ease of access to breakers and receptacles. When required, a means for securing the door in the open position shall be provided. Panels shall be bottom fed through knockouts in endwall or top fed using a bolt-on raintight hub. Knockouts shall range from 1/2-inch (12.7 mm) to 1-1/2 inches (38.1 mm). #4 – 14 Cu/Al grounding provisions shall be provided on all panels.
Standard Compliance
All power outlet panels for temporary construction site power and RV (recre-ational vehicle) application shall be UL listed for the U.S. per UL Standard 231, File E163588. Receptacles shall conform to NEMA and/or ANSI config-urations as specified by the National Electrical Code (NEC).
February 2007
CA08101001E For more information visit:
www.eaton.com
6-3Power Outlet Panels
6
Surface and Pedestal Units
Eaton’s Cutler-Hammer Power Outlet Panels
Power Where You Need It, When You Need It
Features
■
Designed for outdoor service to meet power outlet requirements.
■
Receptacles conform to NEMA and/or ANSI configurations as specified by NEC.
■
Suitable for use as service entrance equipment.
■
Includes a factory installed insulated neutral bar with provisions for bonding when used for service entrance applications.
■
125 ampere rated meter socket.
Designed for Easy Installation and Protection
■
Panels come from the factory completely assembled, prewired with 100 percent copper wire and tested...ready for easy installation.
■
Door swings up and open for user convenience and ease of access to breakers and receptacles.
■
Panels can be bottom fed through knockouts in endwall or top fed using a bolt-on raintight hub.
■
Two-piece deadfront cover allows field wiring without interfering with factory wiring.
■
Lower deadfront cover permits easy field wiring to circuit protective devices.
■
GFI (ground fault interrupter) 1- and 2-pole protection through 50 amperes.
Two Styles to Meet Your Power Outlet Needs
Surface Mount:
User mounts unit to a post.
Pedestal Mount:
User mounts with an underground pedestal extension or pad-mounting bracket. (Underground pedestal extension and pad-mounting bracket are sold separately. See acces-sories
Page 6-15
for part numbers and options.)
Surface Units
Pedestal Units
Lighted option for site location and nighttime panel operations.
Three-point mounting.
100 percent galvanized steel with baked-on polyester powder coating.
GFI circuit breakers available through 50 amperes.
One-piece case back for metered and unmetered panels.
Unique steel barrier prevents unauthorized operation of breakers when door is closed and padlocked.
Lower deadfront cover rotates 90 degrees or can be removed for easy routing of incoming wires or receptacle changeouts.
Padlock provisions to prevent unauthorized entry.
Utility grade metering available for construction site RV park applications.
Removable upper deadfront cover for easy incoming wire connections to breaker terminals.
• Units are factory wired and assembled.
NEMA 3R construction for rainproof installation.
Door swings up and pushes in to lock into open position. Pull out and push down to close door.
• Metered units available with meter on top or on bottom.
• Units are factory wired and assembled.
100 percent galvanized steel with baked-on polyester powder coating.
GFI circuit breakers (1- and 2-pole) available through 50 amperes.
One-piece case back for metered and unmetered panels.
Removable upper deadfront cover for easy incoming wire connections to breaker terminals.
Door swings up and pushes in to lock into open position. Pull out and push down to close door.
Unique steel barrier prevents unauthorized operation of breakers when door is closed and padlocked.
Lower deadfront cover rotates 90 degrees or can be removed for easy routing of incoming wires or receptacle changeouts.
Padlock provisions to prevent unauthorized entry.
Loop feed lug assembly with 350 kcmil lugs as standard.
Pad-mounted bracket option also available.
Pedestal extension available for underground services.
Utility grade metering available for construction site RV park applications.
NEMA 3R construction forrainproof installation.
February 2007
6-4
For more information visit:
www.eaton.com
CA08101001E
Power Outlet Panels
6
Surface and Pedestal Units
Cutler-Hammer Power Outlet Panels
Surface Units
Pedestal Units
Unmetered Type
Metered Ring or Ringless Type Back-to-Back Type
Unmetered Type Metered Ring or Ringless Type Metered Ring or Ringless Type Bottom Feed
Single Receptacle
February 2007
CA08101001E For more information visit:
www.eaton.com
6-5Power Outlet Panels
6
Product Selection
Product Selection
When quoting or selecting a Power Outlet Panel, the following questions should be answered:
■
Unmetered, Ring or Ringless Style.
■
Number and types of receptacles (7 standard and 8 twist-lock options).
■
Standard or Ground Fault Breakers.
■
Surface, Pedestal or Back-to-Back Mounting.
■
Are any factory or field options required?
Table 6-1. Catalog Numbering System
�
For receptacle configurations, see
Table 6-2
.
�
Only available with metered surface mount units.
Note:
Twist-lock receptacles are not listed in the above chart as not all receptacle combinations are valid even though one can create a catalog number above.
Contact Eaton for a quote on twist-lock and custom receptacle/breaker combinations.
Table 6-2. Receptacle Configuration
1
50 ampere, 125/250 volt3-pole, 4-wire,
NEMA 14-50R
2-pole 50 ampere breaker
5
20 ampere, 250 volt,2-pole, 3-wire,
NEMA 6-20R2
2-pole 20 ampere breaker
2
50 ampere, 125/250 volt2-pole, 3-wire, NEMA 10-50R
2-pole 50 ampere breaker
6 20 ampere, 125 volt,2-pole, 3-wire, NEMA 5-20R2
1-pole 20 ampere breaker
3 30 ampere, 125/250 volt3-pole, 4-wire, NEMA 14-30R
2-pole 30 ampere breaker
7 20 ampere, 125 volt,2-pole, 3-wire, NEMA 5-20R2GFI
1-pole 20 ampere breaker
4 30 ampere, 125 volt2-pole, 3-wire,
NEMA TT-30R
1-pole 30 ampere breaker
Cutler-Hammer
Metering Type
U = UnmeteredM = Metered-RingR = Metered-Ringless
Receptacle Type
Left Position �
1 = NEMA 14-50R2 = NEMA 10-50R3 = NEMA 14-30R4 = NEMA TT-30R5 = NEMA 6-20R26 = NEMA 5-20R27 = NEMA 5-20R2GFI
Blank = No Receptacle
Receptacle Type
Center Position �
1 = NEMA 14-50R2 = NEMA 10-50R3 = NEMA 14-30R4 = NEMA TT-30R5 = NEMA 6-20R26 = NEMA 5-20R27 = NEMA 5-20R2GFI
Blank = No Receptacle
Mounting
S = SurfaceP = PedestalB = Back-to-Back
Pedestal
Interior
X = Six CircuitBlank = Standard
Four Circuit
L = Lighted
TZ = Factory InstalledPedestal Extensionwith Lay-inGround Lug
C H M 1 N 7 N 4 N P X L T Z U
Receptacle Type
Right Position �
1 = NEMA 14-50R2 = NEMA 10-50R3 = NEMA 14-30R4 = NEMA TT-30R5 = NEMA 6-20R26 = NEMA 5-20R27 = NEMA 5-20R2GFI
Circuit Breaker TypePosition 2
N = Non-Ground FaultG = Ground Fault
Feed
U = Bottom Fed �Blank = Top Fed
Circuit Breaker TypePosition 3
N = Non-Ground FaultG = Ground Fault
Circuit Breaker TypePosition 1
N = Non-Ground FaultG = Ground Fault
February 2007
6-6
For more information visit: www.eaton.com CA08101001E
Power Outlet Panels
6
Product Selection
Product Selection
Built to Order■ Configure catalog number.■ Calculate list price.■ Lead-time:
❑ 3 days up to 15 units❑ 10 days up to 50 units
Power Outlet Panel ReceptacleConfiguration Rules
Four Receptacles/UnitAll receptacles must be NEMA 5-20R and/or NEMA 5-20R2, surfacemount only.
Three Receptacles/Unit
■ One or more of the receptacles must be NEMA 6-20R2, NEMA 5-20R2 or NEMA 5-20R2GFI.
■ NEMA 6-20R2, NEMA 5-20R2, or NEMA 5-20R2GFI must go in the second position.
■ If two receptacles consist of types NEMA 14-50R, NEMA 10-50R, NEMA 14-30R or NEMA 6-20R2 a six-circuit interior must be added.❑ Example: CHUIN5N2NSX
Note: Configuration 1 and 2 werechosen so a six-circuit interior needsto be added (suffix X) to the end ofthe catalog number. Also, configura-tion 5 is in the second position.
Two, One and Zero Receptacles/Unit■ Any configuration.
Power Outlet Panel List Price ConfiguratorTable 6-3. Base Price
Note: Contact your local Eaton sales office for current pricing.
Table 6-4. Receptacle/Breaker Adders
Note: Contact your local Eaton sales office for current pricing.
Table 6-5. Options
Note: Contact your local Eaton sales office for current pricing.
Description PriceU.S. $
Unmetered SurfaceMetered Surface
Unmetered PedestalMetered Pedestal
Unmetered Back-to-BackMetered Back-to-Back
Configuration Description PriceU.S. $
1N1G
NEMA 14-50R with 2-Pole 50 Ampere Breakerwith 2-Pole 50 Ampere GFI Breaker
2N2G
NEMA 10-50R with 2-Pole 50 Ampere Breakerwith 2-Pole 50 Ampere GFI Breaker
3N3G
NEMA 14-30R with 2-Pole 30 Ampere Breakerwith 2-Pole 30 Ampere GFI Breaker
4N4G
NEMA TT-30R with 1-Pole 30 Ampere Breakerwith 1-Pole 30 Ampere GFI Breaker
5N5G
NEMA 6-20R2 with 2-Pole 20 Ampere Breakerwith 2-Pole 20 Ampere GFI Breaker
6N6G
NEMA 5-20R2 with 1-Pole 20 Ampere Breakerwith 1-Pole 20 Ampere GFI Breaker
7N NEMA 5-20R2GFI with 1-Pole 20 Ampere Breaker
Option PriceU.S. $
Six Circuit InteriorFactory-Mounted Pedestal ExtensionLightedBottom Fed
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 22CD
February 2007
CA08101001E For more information visit: www.eaton.com
6-7Power Outlet Panels
6
Product Selection
Product Selection (Continued)Table 6-6. Surface Type
� Consult Power Outlet Estimator on Eaton’s intranet for additional combinations. Contact your local Eaton salesperson.� The “X” suffix indicates that a six circuit interior is provided, instead of the standard four circuit interior.� Includes 60 ampere 2-pole main breaker for service disconnect ratings.Note: For receptacle and circuit breaker configurations, please contact your local Eaton salesperson.Note: Contact your local Eaton sales office for configurations not listed.
AmpereSeries
Receptacle Description Breaker Description UPC Number78211
CatalogNumber �
PriceU.S. $Position 1st 2nd 3rd
Left Center Right
Unmetered Single Receptacle50503030
————
14-50R10-50R14-30 RTT-30R
————
No BreakerNo BreakerNo BreakerNo Breaker
No BreakerNo BreakerNo BreakerNo Breaker
No BreakerNo BreakerNo BreakerNo Breaker
6128174612818161281986128204
CHU1SCHU2SCHU3SCHU4S
202020
———
6-20R25-20R25-20R2GFI
———
No BreakerNo BreakerNo Breaker
No BreakerNo BreakerNo Breaker
No BreakerNo BreakerNo Breaker
612821161282286128235
CHU5SCHU6SCHU7S
Unmetered20/20/2020/20/2020/20/20
5-20R25-20R2GFI5-20R2GFI
5-20R25-20R2GFI5-20R2GFI
6-20R26-20R26-20R2
GFINon-GFINon-GFI
GFINon-GFINon-GFI
GFINon-GFIGFI
42039 242039 4—
CHU6G6G5GSCHU7N7N5NSCHU7N7N5GS
50/20/3050/20/3030/20
5-20R2GFI14-50RTT-30R
5-20R2GFI5-20R2GFI5-20R2GFI
TT-30R6-20R—
Non-GFIGFINon-GFI
Non-GFINon-GFINon-GFI
Non-GFINon-GFI—
——42037 4
CHU1N7N4NSCHU1G7N7NSCHU4N7NS
20/2050/2050/20
5-20R2GFI14-50R14-50R
5-20R2GFI5-20RGFI5-20RGFI
———
Non-GFIGFINon-GFI
Non-GFINon-GFINon-GFI
———
42037 742156 842037 0
CHU7N7NSCHU1G7NSCHU1N7NS
50/20/505050/20
14-50R14-50R10-50R
5-20R2GFI—5-20R2GFI
14-50R——
Non-GFINon-GFIGFI
Non-GFI—Non-GFI
Non-GFI——
——42156 9
CHU1N7N1NSX �
CHU1NSCHU2G7NS
30/30/2050/2030
TT-30R10-50RTT-30R5-20R2
5-20R2GFI5-20R2GFI—5-20R2
TT-30R——5-20R2
Non-GFINon-GFINon-GFIGFI
Non-GFINon-GFI—GFI
Non-GFI——GFI
42039 042037 242036 7
CHU4N7N4NSCHU2N7NSCHU4NSCHU6G6G5GS6OM �
Metered — Ring50/20/2020/2020/20/20
14-50R5-20R2GFI5-20R2GFI
5-20R2GFI5-20R2GFI5-20R2GFI
5-20R2GFI—6-20R2
GFINon-GFINon-GFI
Non-GFINon-GFINon-GFI
Non-GFI—GFI
42028 642028 342156 1
CHM1G7N7NSCHM7N7NSCHM7N7N5GS
20/20/2050/30/2050/2020/20
5-20R2GFI14-50R14-50R6-20R2
5-20R2GFI5-20R2GFI5-20R2GFI5-20R2GFI
6-20R2TT-30R——
Non-GFINon-GFINon-GFINon-GFI
Non-GFINon-GFINon-GFINon-GFI
Non-GFINon-GFI——
42030 042028 842027 742156 3
CHM7N7N5NSCHM1N7N4NSCHM1N7NSCHM5N7NS
Metered — Ringless50/2020/2050/20/20
14-50R5-20R2GFI14-50R
5-20R2GFI5-20R2GFI5-20R2GFI
——5-20R2GFI
GFINon-GFIGFI
Non-GFINon-GFINon-GFI
——Non-GFI
42190 742032 942398 3
CHR1G7NSCHR7N7NSCHR1G7N7NS
50/2050/2020/20/20
10-50R14-50R5-20R2GFI
5-20R2GFI5-20R2GFI5-20R2GFI
——5-20R2GFI
GFINon-GFINon-GFI
Non-GFINon-GFINon-GFI
——Non-GFI
42398 242032 442034 7
CHR2G7NSCHR1N7NSCHR7N7N7NS
30/20/2050/30/20
14-30R14-50R
5-20R2GFI5-20R2GFI
5-20R2GFITT-30R
Non-GFINon-GFI
Non-GFINon-GFI
Non-GFINon-GFI
42034 142033 4
CHR3N7N7NSCHR1N7N4NS
Metered — Ring — Bottom Fed20/2020/20/2050/20/20
5-20R2GFI5-20R2GFI14-50R
5-20R2GFI5-20R2GFI5-20R2GFI
—6-20R25-20R2GFI
Non-GFINon-GFIGFI
Non-GFINon-GFINon-GFI
—GFINon-GFI
615327 5615330 5615329 9
CHM7N7NSUCHM7N7N5GSUCHM1G7N7NSU
Metered — Ringless — Bottom Fed20/2050/2050/20
5-20R2GFI14-50R10-50R
5-20R2GFI5-20R2GFI5-20R2GFI
———
Non-GFIGFIGFI
Non-GFINon-GFINon-GFI
———
615326 8615328 2615338 1
CHR7N7NSUCHR1G7NSUCHR2G7NSU
20/20/2020/20/2020/20/20
5-20R2GFI5-20R2GFI5-20R2GFI
5-20R2GFI5-20R2GFI5-20R2GFI
6-20R26-20R25-20R2GFI
Non-GFINon-GFINon-GFI
Non-GFINon-GFINon-GFI
GFINon-GFINon-GFI
615331 2615332 9615337 4
CHR7N7N5GSUCHR7N7N5NSUCHR7N7N7NSU
30/20/2030/20/2050/20/2050/20/30
14-30R14-30R14-50R14-50R
5-20R2GFI5-20R2GFI5-20R2GFI5-20R2GFI
5-20R2GFI5-20R2GFI5-20R2GFITT-30R
Non-GFIGFIGFINon-GFI
Non-GFINon-GFINon-GFINon-GFI
Non-GFINon-GFINon-GFINon-GFI
615333 6615334 3615336 7615335 0
CHR3N7N7NSUCHR3G7N7NSUCHR1G7N7NSUCHR1N7N4NSU
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . 22CD
February 2007
6-8
For more information visit: www.eaton.com CA08101001E
Power Outlet Panels
6
Product Selection
Table 6-7. Pedestal Type
� Consult Power Outlet Estimator on Eaton’s intranet for additional combinations. Contact your local Eaton salesperson.Note: For receptacle and circuit breaker configurations, please contact your local Eaton salesperson.Note: Contact your local Eaton sales office for configurations not listed.
Table 6-8. Back-to-Back Pedestal Type
� Consult Power Outlet Estimator on Eaton’s intranet for additional combinations. Contact your local Eaton salesperson.� The pedestal back-to-back units have receptacles and circuit breakers as shown for each panel and share one common pedestal with loop feed lugs.Note: For receptacle and circuit breaker configurations, please contact your local Eaton salesperson.Note: Contact your local Eaton sales office for configurations not listed.
AmpereSeries
Receptacle Description Breaker Description UPCNumber78211
CatalogNumber �
PriceU.S. $Position 1st 2nd 3rd
Left Center Right
Unmetered50/30/2030/20
14-50RTT-30R
5-20R2GFI5-20R2GFI
TT-30R—
Non-GFINon-GFI
Non-GFINon-GFI
Non-GFI—
42038 242031 7
CHU1N7N4NPCHU4N7NP
50/30/2030/30/20
14-50RTT-30R
5-20R2GFI5-20R2GFI
TT-30RTT-30R
Non-GFINon-GFI
Non-GFINon-GFI
Non-GFINon-GFI
42038 342032 1
CHU1N7N4NPTZCHU4N7N4NP
Metered — Ring50/30/2050/20
14-50R14-50R
5-20R2GFI5-20R2GFI
TT-30R—
Non-GFINon-GFI
Non-GFINon-GFI
Non-GFI—
42030 442231 5
CHM1N7N4NPCHM1N7NP
Metered — Ringless50/30/20 14-50R 5-20R2GFI TT-30R Non-GFI Non-GFI Non-GFI 42031 0 CHR1N7N4NP
AmpereSeries
Receptacle Description Breaker Description UPCNumber78211
CatalogNumber �
PriceU.S. $Position 1st 2nd 3rd
Left Center Right
Unmetered �
30/30/20 TT-30R 5-20R2GFI TT-30R Non-GFI Non-GFI Non-GFI 42036 4 CHU4N7N4NB
Metered — Ring �
30/2050/30/20
TT-30R14-50R
5-20R2GFI5-20R2GFI
—TT-30R
Non-GFINon-GFI
Non-GFINon-GFI
—Non-GFI
42034 842035 0
CHM4N7NBCHM1N7N4NB
Metered — Ringless �
50/30/20 14-50R 5-20R2GFI TT-30R Non-GFI Non-GFI Non-GFI 42035 7 CHR1N7N4NBTZ
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 22CD
February 2007
CA08101001E For more information visit: www.eaton.com
6-9Power Outlet Panels
6
Product Selection
Dimensional Drawings
Figure 6-1. Single Receptacle
6.58 (167.1)
2.63 (66.8)
0.24 (6.1)
7.10 (108.3)
4.50 (114.3)
1.30 (33.0)
6.23 (158.2)
2.50 (63.5)
1.87 (47.5 )
3.18 (80.8)
4.79 (121.7)
4.27 (108.5)
0.13 (3.3)
February 2007
6-10
For more information visit: www.eaton.com CA08101001E
Power Outlet Panels
6
Product Selection
Figure 6-2. 100 Amperes Back-to-Back
RinglessU.G. Feed Pedestal-Mount B/B
33.00(838.2)
8.25
18.02(457.7)
Hit ExitHoleB/B Only
33.00(838.2)
February 2007
CA08101001E For more information visit: www.eaton.com
6-11Power Outlet Panels
6
Product Selection
Figure 6-3. 100 Ampere Pedestal
Gasket
RinglessU.G. Feed Pedestal-Mount.
6.10(154.9)
33.00(838.2)
18.02
Hit ExitHole B/BOnly
0.24260.0)
4.00
10.78(273.7)
wer Barrier
.79(20.1)
.92 (23.4)
33.00(838.2)
February 2007
6-12
For more information visit: www.eaton.com CA08101001E
Power Outlet Panels
6
Product Selection
Dimensions in Inches (mm) — Metered Units (Ring and Ringless)
Figure 6-4. Metered Surface Type
Figure 6-5. Metered Pedestal Type
SealingProvision
LockingProvision
9.50
22.50(571.5)
30.00(762.0)
4.50(114.3)
.074.30
(170.1)
SealingProvision
LockingProvision
9.50(241.3)
52.00(1320.8)
25.80(655.3)
16.90(429.3)
44.50(1130.3)
22.00(558.8)
6.80(172.7)
5.00(127.0) 4.30
(109.2)
February 2007
CA08101001E For more information visit: www.eaton.com
6-13Power Outlet Panels
6
Product Selection
Dimensions in Inches (mm) — Metered Units (Ring and Ringless)
Figure 6-6. Metered Back-to-Back Pedestal Type
Figure 6-7. Bottom Fed Type
9.49(241.1)
30.10(764.6)
SealingProvision
6.15(156.2)
17.11(434.7)
12.97(329.4)
4.93(125.2)
LockingProvision
6.80(172.8)
4.31
.06(1.6)
February 2007
6-14
For more information visit: www.eaton.com CA08101001E
Power Outlet Panels
6
Product Selection
Figure 6-8. Unmetered Surface Type
Figure 6-9. Unmetered Pedestal Type
Dimensions in Inches (mm) — Unmetered Units
LockingProvision
9.50(241.3)
17.10(434.3)
6.70(170.2)
1.30(33.0)
14.50(368.3)
4.30(109.2)
.07(1.7)
9.50(241.3)
39.90(1013.5)
39.10(993.1)
9.40(238.8)
9.20(233.7)
Figure 6-10. Unmetered Back-to-Back Pedestal Type
LockingProvision
17.10(434.3)
13.60(345.4)
8.60(218.4)
19.20(487.7)
3.30(83.8).75
(19.1)
9.50
CA08101001E For more information visit: www.eaton.com
6-15Power Outlet Panels
February 2007
6
Accessories and Replacement Parts
Accessories and Replacement PartsTable 6-9. Accessories and Replacement Parts
� For Power Outlet Panels manufactured before 12/1/02.� For Power Outlet Panels manufactured after 12/1/02.� For Power Outlet Panels with a date code ending in L.� For Power Outlet Panels with a date code not ending in L.
Description UPCNumber78211
CatalogNumber
PriceU.S. $
AccessoriesUnderground Pedestal ExtensionStainless Steel Underground Pedestal ExtensionPad-Mount Bracket
420273422130420274
CHPEDEXTCHPEDEXTSSCHPADEXT
Cable TV and Telephone Bracket 420275 CHTELTV
Rainproof Conduit Hub 0.75 inch (19.1 mm)Rainproof Conduit Hub 1.00 inch (25.4 mm)Rainproof Conduit Hub 1.25 inch (31.8 mm)Rainproof Conduit Hub 1.50 inch (38.1 mm)
310991310992310993310994
DS075H1DS100H1DS125H1DS150H1
Fluorescent Light Kit — Converts power outlet panel to lighted unit, must also order CHOUTCVRL. 463424 CHFLGTKIT
Replacement PartsReplacement Meter Socket �Replacement Meter Socket �Replacement Meter Socket (1 Block Assembly Per Kit) �
481999612728603686
CHPOPMSCHPOPMSNARP00039CH
5th Jaw Kit �5th Jaw Kit �Bonding Strap and Mounting HardwareHorn Bypass (1 Lug Cap Per Kit; 4 Kits Required Per Device) �Horn Bypass (1 Kit Required Per Device) �
600788400413421926612840438033
1MM5JKOPARP00035CHJCHBONDSTARP00777CH1MMBPH
Inner Lens for Lighted Power Outlet Panels Loop Feed Lug Assembly for Single PedestalLoop Feed Lug Assembly for Back-to-Back Pedestal
421927421928421929
CHINLENSCHLOOPFDPCHLOOPFDB
Blank Lower Deadfront CoverLower Deadfront Cover with Duplex Receptacle OpeningLower Deadfront Cover with Duplex, Duplex Receptacle Opening
421930421931421932
CHLDFCVRCHLDFCVR1CHLDFCVR2
Lower Deadfront Cover with Duplex, Duplex, Duplex Receptacle Opening
Lower Deadfront Cover with Rectangle Receptacle OpeningLower Deadfront Cover with Rectangle, Rectangle
Receptacle Opening
421933421934
421935
CHLDFCVR3CHLDFCVR4
CHLDFCVR5
Lower Deadfront Cover with Rectangle, Rectangle, Rectangle Receptacle Opening
Lower Deadfront Cover with Duplex, Rectangle Receptacle OpeningLower Deadfront Cover with Duplex, Rectangle, Duplex
Receptacle Opening
421936421937
421938
CHLDFCVR6CHLDFCVR7
CHLDFCVR8
Lower Deadfront Cover with Rectangle, Rectangle, Duplex Receptacle Opening
Lower Deadfront Cover with Round Receptacle OpeningLower Deadfront Cover with Round, Round Receptacle Opening
421939421940422128
CHLDFCVR9CHLDFCVR10CHLDFCVR11
Lower Deadfront Cover with Round, Duplex Receptacle OpeningLower Deadfront Cover with Round, Duplex, Duplex
Receptacle OpeningLower Deadfront Cover with Round, Duplex, Round
Receptacle Opening
422129
421942
421943
CHLDFCVR12
CHLDFCVR13
CHLDFCVR14
Lower Deadfront Cover with Round, Rectangle Receptacle OpeningLower Deadfront Cover with Round, Rectangle, Rectangle
Receptacle OpeningLower Deadfront Cover with Round, Rectangle, Round
Receptacle Opening
421944
421945
421946
CHLDFCVR15
CHLDFCVR16
CHLDFCVR17
Lower Deadfront Cover with Round, Rectangle, Duplex Receptacle Opening
Upper Deadfront Cover with Six Breaker TwistoutsUpper Deadfront Cover with Provisions for Lighted Option
422079421947421948
CHLDFCVR18CHUDFCVRCHUDFCVRL
Power Head Outer CoverPower Head Outer Cover with Lens
421949421950
CHOUTCVRCHOUTCVRL
6-Hole Neutral Assembly with 2/0 Lug7-Hole Neutral Assembly with 2/0 Lug5-Hole Ground Bar Kit10-Hole Ground Bar Kit
421951422180309906401456
CHNEUTCHNEUT1GBK5GBK10
Replacement Meter Cover — Ring Type Replacement Meter Cover — Ringless �Replacement Meter Cover — Ringless �Replacement Meter Cover — Ringless �
483847483848612729641914
CHPOPRMCCHPOPRLMCCHPOPRLMCNCHPOPRLMCN2
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . 22CD
Underground Pedestal Extension
Pad-Mount Bracket
DS Hub
Cable TV/TelephoneBracket
Neutral Assemblies
Power Head Outer Cover with Lens
Power Head Outer Cover
Inner Lens
Meter Socket
Loop Feed Lug Assembly
Lower Deadfront Cover
Upper Deadfront Cover
Circuit Breaker(BR/GFCB)
Bonding Strap and Mounting Hardware
February 2007
6-16
For more information visit: www.eaton.com CA08101001E
Power Outlet Panels
6
Product Selection
Mobile Home PanelsThe versatile Cutler-Hammer Mobile Home Panels have a user-friendly design that allows for a faster, cleaner installation — letting you move on to your next job sooner.
100 and 200 ampere panels come complete with the main breaker and a 4/8 or 8/16 interior, respectively. The 200 ampere units are designed about 5 inches wider than other manufacturer’s panels to ensure plenty of room for wire bending and an easier wiring job.
Receptacle Deadfront Kits200 ampere units include a new door. Optional receptacle deadfront kits can supply power for a variety of applica-tions including:
■ Visiting RVs.■ Pool filters.■ Weed whackers.■ Air compressors.■ Anything else that requires power
(receptacles and breakers supplied by contractor).
Fastenerless Socket Design■ Makes failure a non-issue.■ No socket connections that
overheat.
Pedestal Unit■ Convenient and sturdy ground
mounting.■ Loop feed feature allows several
units to be connected in series.
Easier, Better and Faster Installation■ More wire bending and viewing
room.■ Additional circuits mean more
flexibility.
Table 6-10. Mobile Home Panels �
� Pedestal Extension included with Mobile Home Panels.
Amperes Security Interior Main BranchBreakers
Mounting Receptacles UPC Number78211
CatalogNumber
PriceU.S. $
100100100100
RingRingRinglessRingless
4/84/84/84/8
BR2100BR2100BR2100BR2100
BRBRBRBR
PedestalBack-to-BackPedestalBack-to-Back
NoneNoneNoneNone
498168 9498169 6498170 2498171 9
MHM100PMHM100BMHR100PMHR100B
150150150150
RingRingRinglessRingless
8/168/168/168/16
BWH2150BWH2150BWH2150BWH2150
BRBRBRBR
PedestalBack-to-BackPedestalBack-to-Back
NoneNoneNoneNone
617535 2617534 5616475 2616474 5
MHM150PMHM150BMHR150PMHR150B
200200200200
RingRingRinglessRingless
8/168/168/168/16
BWH2200BWH2200BWH2200BWH2200
BRBRBRBR
PedestalBack-to-BackPedestalBack-to-Back
NoneNoneNoneNone
498172 6498173 3498174 0498175 7
MHM200PMHM200BMHR200PMHR200B
200 Ringless 8/16 BWH2200 BR Pedestal Qty 1 14-50RQty 2 TT-30R
498176 4 MHM200P1N4N4N
February 2007
CA08101001E For more information visit: www.eaton.com
6-17Power Outlet Panels
6
Product Selection
Product Selection
Figure 6-11. Mobile Home Panel — Ringless Security — Pedestal Mounting
Figure 6-12. Mobile Home Panel — Ringless Security — Back-to-Back Mounting
Grade Level
5.31
27.87(708.0)28.01
(711.5)23.69
(601.8)
50.08(1272.1)
RinglessSocket
Rated 200 AContinuous
200A57.81
(1468.3)
Sealin
1-1/4, 1-1/2,2, 2-1/2
(31.8, 38.1,50.8, 63.5)Knockout
1, 1-1/4, 1-1/2, 2(25.4, 31.8, 38.1, 50.8)
Knockout
5/16 (7.9)Diameter KO
OppositeSide Only
43.20(1097.4)
28.70(729.0)
1.212.00
(50.8)
24.65(626.1)
Optional DirectFeed Kit
Shown Installed(Cover Not Shown)
1/2, 3/4,1(12.7, 19.1, 25.4)KO (2 Required)
1, 1-1/4, 1-1/2, 2(25.4, 31.8, 38.1,50.8) KO
1/2, 3/4, 1, 1-1/4,1-1/2 (12.7, 19.1,25.4, 31.8, 38.1) KOSealing Provision
SealingProvision
DoorNotShown
12.09(307.2) 10
27.87(708.0)
22.01(711.5) 18.69
(474.6)
25.00(635.0)
Front View
Feed Kit Shown Installed
(Cover NotShown)
200AMain
SealingProvision
1-1/4, 1-1/2,
(31.8, 38.1,50.8, 63.5)Knockout
5/16 (7.9) Diameter
Side Only
DiameterKO
Side Only1,1-1/4,1-1/2, 2
Grade Level
Door NotShown
23.69(601.8)
50.08(1272.1)
57.81(1468.3)
(1097.4)
28.70(729.0)
1.212.00
14.45
Bottom Endwall Direct Feed Kit
1/2, 3/4, 1 (12.7,19.1, 25.4) KO(2) Required
1/2, 3/4, 1, 1-1/4, 1-1/2(12.7, 19.1, 25.4, 31.8, 38.1) KO
1, 1-1/4, 1-1/2, 2(25.4, 31.8, 38.1, 50.8) KO
Bottom Endwall Back Unit
1-1/2, 2, 2-1/2, 3 (38.1, 50.8, 63.5, 76.2) KO
KO (3) Required
1/2 (12.7) KO(3) Required
3/4, 1 (19.1, 25.4) KO
1-1/4, 1-1/2, 2, 2-1/2(31.8, 38.1, 50.8, 63.5) KO(2) Required
KO (2) Required
RinglessSocket
Rated 200 AContinuous
Back View
February 2007
6-18
For more information visit: www.eaton.com CA08101001E
Power Outlet Panels
6
Product Selection
Figure 6-13. Mobile Home Panel — Ring Security — Pedestal Mounting
Figure 6-14. Mobile Home Panel — Ring Security — Back-to-Back Mounting
ON
OFFO
N
OFF
Ring Type SocketRated 200 A Continuous
200A MainBreaker
DoorNotShown
5/16 (7.9) Diameter
KOOpposite
Side Only
1-1/4,1-1/2, 2,
2-1/2(31.8, 38.1,
Knockout
SealingProvision
24.64(626.0)
Optional Direct Feed KitShown Installed
(Cover Not Shown)
28.01(711.5)
1, 1-1/4,1-1/2, 2
(25.4,
50.8) KO
1/2, 3/4, 1 (12.7, 19.1, 25.4) KO(2 Required)
Direct Feed Kit
1/2, 3/4, 1, 1-1/4,1-1/2 (12.7, 19.1,25.4, 31.8, 38.1) KO
1, 1-1/4, 1-1/2, 2 (25.4, 31.8, 38.1, 50.8) KO
Grade Level
27.87(708.0)
23.69(601.8)
50.08(1272.1)
57.81(1468.3)
28.70(729.0)
1.21(30.7)
2.00(50.8)
5.56(141.3) 5.31
(134.8)
43.20(1097.4)
14.45
Grade Level
1-1/4,1-1/2, 2,
2-1/2(31.8,
38.1, 50.8,63.5)
Knockout
Sealing Provision
5/16 (7.9)Diameter KO
Back View Front View
1-1/4, 1-1/2, 2, 2-1/2
KO (2) Required
Bottom EndwallBack Unit
Direct Feed Kit
1/2, 3/4, 119.1, 25.4) K(2) Required
1/2, 3/4, 1, 1-1/4,1-1/2 (12.7, 19.1, 25.4, 31.8, 38.1) KO
1, 1-1/4, 1-1/2, 2 (25.4, 31.8, 38.1, 50.8) KO
, 2, 2-1/2, 3 (38.1,50.8, 63.5, 76.2) KO
3/4, 1 (19.1, 25.4) KO
Feed KitShown Installed
(Cover NotShown)
200AMain
Breaker
DoorNotShown
23.69(601.8)
50.0(1272
57.81(1468.3)
43.20(1097.4)
28.70(729.0)
11.25(285.8) 10 75 14.45
(367.0) Ring Type SocketRated 200 A Continuous
27.87(708.0)
18.69(474.6)
25.00(635.0)
22.01(711.5)
5/16 (7.9) Diameter 1/2 (12.7) KO(3) Required
KO (2) Required
February 2007
CA08101001E For more information visit: www.eaton.com
6-19Power Outlet Panels
6
Product Selection
Mobile Home Panel Deadfronts for 200 Ampere Units �
Figure 6-15. Available Receptacle Deadfront Kits — Receptacles and Breakers Not Included� For 100 ampere units, the accessory Catalog Number would be MHD1___. For example, to order
a deadfront to accept one 30 ampere receptacle (round) in a 100 ampere device, the Catalog Number would be MHD1X.
Cutler-Hammer is am federally registered trademark of Eaton Corporation. National Electrical Code and NEC are registered trademarks of the National Fire Protection Association, Quincy, Mass. NEMA is the registered trademark and service mark of the National Electrical Manufacturers Association. UL is a federally registered trademark of Underwriters Laboratories Inc.