Content

1 Installation ........................................................................................................................................ 3

1.1 Mervis IDE ............................................................................................................................... 3

1.2 Card ......................................................................................................................................... 3

1.2.1 MicroSD card preparation ................................................................................................ 3

1.2.2 Deploying image .............................................................................................................. 3

1.3 Connecting UniPi ..................................................................................................................... 3

1.3.1 Router mode .................................................................................................................... 3

1.3.2 Direct mode ..................................................................................................................... 4

2 Basic IDE ......................................................................................................................................... 5

2.1 Simple vs Full mode ................................................................................................................ 5

2.1.1 Simple mode .................................................................................................................... 5

2.1.2 Full mode ......................................................................................................................... 5

2.2 New project .............................................................................................................................. 5

2.3 Mervis IDE environment .......................................................................................................... 5

2.4 Attaching PLC .......................................................................................................................... 6

2.5 Uploading/Updating RunTime ................................................................................................. 6

2.6 Controller properties ................................................................................................................ 7

2.7 Attaching UniPi 1.x .................................................................................................................. 9

2.7.1 Analog inputs ................................................................................................................... 9

2.7.2 Relays ............................................................................................................................ 12

2.7.3 Digital inputs and Analog Output ................................................................................... 12

2.8 Attaching Neuron ................................................................................................................... 15

2.8.1 All IOs except 1-Wire ..................................................................................................... 15

2.8.2 Analog outputs ............................................................................................................... 16

2.8.3 Analog Inputs ................................................................................................................. 18

2.8.4 RS485 ............................................................................................................................ 19

2.8.5 Extension modules ........................................................................................................ 21

2.8.6 Configure the software configuration of the connection ................................................ 22

2.9 Example of attaching Modbus serial device (Electricity meter Inepro) .................................. 24

2.10 Attaching OneWire devices (Thermometer) .......................................................................... 26

2.11 PWM (Pulse width modulation) ............................................................................................. 27

2.12 Simple program ..................................................................................................................... 28

2.13 Debugging ............................................................................................................................. 30

3 HMI (Human Machine Interface) ................................................................................................... 32

3.1 Creating a web....................................................................................................................... 32

3.2 Connecting variables ............................................................................................................. 32

3.3 Gadgets ................................................................................................................................. 32

3.4 New panel .............................................................................................................................. 34

Page 3: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

Page 2 of 46

3.5 Uploading web ....................................................................................................................... 34

4 Advanced IDE ................................................................................................................................ 37

4.1 Manual mapping of HW prototypes to variables .................................................................... 37

4.2 Creating function blocks ........................................................................................................ 38

4.3 Creating a new program ........................................................................................................ 39

4.4 SSCP communication ............................................................................................................ 40

4.5 UniPi database access .......................................................................................................... 41

4.5.1 Setup ............................................................................................................................. 41

4.5.2 Online access ................................................................................................................ 43

4.6 Proxy connection ................................................................................................................... 44

4.6.1 Configuration ................................................................................................................. 44

SECTIONS OF THIS MANUAL

Common for UniPi 1, UniPi Lite and UniPi Neuron

For UniPi 1 & UniPi Lite only

For UniPi Neuron only

Page 4: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1, UniPi Lite and UniPi Neuron

Page 3 of 46 UniPi 1, UniPi Lite and UniPi Neuron

1 Installation

1.1 Mervis IDE

The first step is to download the installation package from http://downloads.unipi.technology

Run the installation package and make sure to include the following components:

• IDE – developing environment for control programs

• HMI –developing environment for human machine interfaces

• WindowsRT – tool for running RunTime under Windows (we will not be using that, so the installation of this

package is optional)

IDE requires Microsoft .NET framework version 4+ to be installed. If the framework is not installed in your computer,

download the installer from the following link:

http://www.microsoft.com/en-us/download/details.aspx?id=17851

1.2 Card

1.2.1 MicroSD card preparation

At least 4GB Micro SD card will be needed (An adapter might be necessary to connect the Micro SD card to your PC).

The SD card has to be formatted:

• The file system needs to be set to FAT32 and the allocation unit can be left to the default value

• It's recommended to use the SD Formatter, which is designed for formatting various SD cards.

• It can be downloaded from: https://www.sdcard.org/downloads/formatter_4/

• In the link, we can find a simple user manual

ATTENTION! You need to be extra careful which drive you select. Choosing wrong drive can cause losing all your data.

1.2.2 Deploying image

Prerequisites:

• Mervis OS image – http://downloads.unipi.technology/

• Win32DiskImager - http://sourceforge.net/projects/win32diskimager/

• WinRar, WinZip,…

Download the compressed image file and extract it using your favorite program (WinRar, WinZip,…)

Open the Win32DiskImager

• Set the Device representing your Micro SD card

• Image File needs to contain the path to the unpacked file

• Press the Write button. The image will be written onto the MicroSD card

Once the process is completed, close the utility, eject the microSD card, insert it into your UniPi and power it on.

1.3 Connecting UniPi

In order to be able to program the UniPi, you need to connect it with your PC. The connection should be done using an

Ethernet connection. This can be done either using a router that will assign the UniPi an IP address or directly without

a router.

1.3.1 Router mode

This scenario expect presence of a DHCP server (basically a router) in your network which will assign an IP address to

the UniPi. This process is done automatically. But make sure that you are connected to the same physical network as

your UniPi. If not, please contact your IT administrator.

Page 5: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1, UniPi Lite and UniPi Neuron

Page 4 of 46 UniPi 1, UniPi Lite and UniPi Neuron

1.3.2 Direct mode

If there is no DHCP server on the network (e.g. when the UniPi is connected directly to your PC using an Ethernet cable)

the UniPi will assign itself an IP address from the same range as Microsoft Windows, e.g. 169.254.xxx.xxx. This

supposes that your Windows is set to use DHCP as well, if not please make sure it is so.

Page 6: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1, UniPi Lite and UniPi Neuron

Page 5 of 46 UniPi 1, UniPi Lite and UniPi Neuron

2 Basic IDE

2.1 Simple vs Full mode

2.1.1 Simple mode

Simple Mode is designed to help beginners with the Mervis IDE environment. It automatically generates the “backbone”

of the project. So, all the user needs to do, is to make some basic configuration.

If a device is added to a channel in simple mode (will be described later), autogen automatically generates and maps

all the variables to device’s inputs and outputs.

2.1.2 Full mode

Full Mode is designed for advanced users who already know what needs to be done and are capable of creating the

whole project from “scratch”, which includes adding Profiles, Devices, Executable and Library projects, History, etc.

Full Mode will be explained more extensively in Advanced IDE chapter.

2.2 New project

• Launch the Mervis IDE

• Create a new solution: File -> New Solution

• In the new window choose your Project Name and a folder where the project files will be saved

• Select your working mode – simple / full

• This scenario will be using Simple mode

2.3 Mervis IDE environment

See the upper part of the screen with buttons for file management, project build and deploy, debugging tool, help (very

useful), etc.

Note the left side of the screen with Solution Explorer where the structure of whole project is shown. Structure consists

of:

• Profiles

• PLCs(+ its channels and devices)

Page 7: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1, UniPi Lite and UniPi Neuron

Page 6 of 46 UniPi 1, UniPi Lite and UniPi Neuron

• Executable projects

• Histories (available only in full mode)

In the central area is by default used for programming behavior of your application (either FUPLA or ST), debugging,

variable management, etc.

On the right side, there is a window called Properties, where properties of PLC, channels, devices, function blocks, etc.,

are set

2.4 Attaching PLC

In order to attach UniPi to a new or already existing solution, we must first right click on PLC in Solution Explorer and

choose Attach PLC.

New window will appear with possible options of detection of the PLC → choose UDP broadcast.

Once done, you should see a list of all detected PLCs(UniPi/Neuron with Mervis) in your local network. Select the one

you wish to attach to this project.

• By default, the UniPi/Neuron tries to request IP address from a DHCP server in your LAN

• If it fails requesting IP from DHCP, it will automatically assign a random address from the same network as

Windows default IP address (e.g. 169.254.xxx.xxx)

• Make sure to have IP address from the same network as the UniPi

A new window will pop asking whether to download the configuration from the PLC or not. This is useful when attaching

already configured PLC (network settings, etc.).

The UniPi is now attached to your solution.

2.5 Uploading/Updating RunTime

If you notice a yellow or red triangle next to Runtime Version number while selecting our UniPi from the PLC detection

dialog, it means that runtime (RT) is outdated or does not match with the version of the Mervis IDE you are using. In

that case, we need to update the runtime to compatible RT:

• Right click on the PLC icon → PLC Operation → Upload RT

• When the upload is finished, right click on the PLC icon → PLC Operation → Reboot PLC

A new menu appears which will show us two options of a reboot:

o Warm Restart – reboot the device and use the most recent values of variables

o Cold Restart – reboot the device and use initial values as set in the project defaults

Page 8: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1, UniPi Lite and UniPi Neuron

Page 7 of 46 UniPi 1, UniPi Lite and UniPi Neuron

This step is also necessary when deploying project fails due to an old version of RT.

In case you see a skull, it means you have to deploy your image to SD card because it is incompatible. How to deploy

your Image jump back to Chapter 1.2.2

2.6 Controller properties

This panel is used to configure specific parameters of the UniPi (e.g. IP address, date and time or a NTP server, name

of the PLC, etc.)

After any change in this section, it is required to upload the settings to the PLC which consists of two steps:

• Right click on the PLC icon (in solution explorer) and choose: PLC Operation → PLC Setup → Upload

configuration. After a while the progress bar should display “Upload successful”.

Page 9: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1, UniPi Lite and UniPi Neuron

Page 8 of 46 UniPi 1, UniPi Lite and UniPi Neuron

• After a successful upload, it is necessary to reboot the PLC. Right click on the PLC icon (in Solution Explorer)

and choose PLC Operation → Reboot PLC.

• After the device reboots, the progress bar should display “Device reboot successful”

Page 10: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1 & UniPi Lite

Page 9 of 46 UniPi 1 & UniPi Lite

2.7 Attaching UniPi 1.x

(If you want attach Neuron device, jump to chapter 2.7)

2.7.1 Analog inputs

Right click on the PLC icon in Solution Explorer and choose Add channel

In solution explorer, under the PLC icon, you will find a newly created channel. Select that channel by left clicking on it

and in the right part of the screen you will see its properties. Set is as following:

• Protocol – PlatformIO

• Link protocol – for analog inputs choose I2C

• Name – it is recommended to use a descriptive name (for example we can use the Link Protocol name - „I2C“)

Page 11: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1 & UniPi Lite

Page 10 of 46 UniPi 1 & UniPi Lite

Once the channel is configured proceed with adding devices.

There are two ways how to add a device:

• Manual – you must create the device and set all necessary parameters like address, reading and writing groups

etc.

• From Library - you can choose a device that is already in the library

For analog inputs, you can use a predefined device. Right click on the created channel and select Add library device →

UniPi (v1.1) → I2C → Analog-Inputs (version 1) from the menu. After these steps, we will see a new device under our

I2C channel which represents analog inputs.

Because of being in Simple Mode, the Autogen feature automatically generates and maps variables to physical inputs

and outputs.

Page 12: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1 & UniPi Lite

Page 11 of 46 UniPi 1 & UniPi Lite

Double left click on the PLC icon in Solution Explorer. This should show you a new PLC tab in the main window. Select

IO Mapping tab (in the bottom section of the window). In this tab, you should see all input/output ports which have been

added to your device.

For analog inputs, you need to locate ports with names AI1 and AI2. Choose the AI1 input by left clicking on it. This

allows you to access the properties of the current port, where we can set the following parameters:

• Transform – this parameter allows to select a transformation of the physical value (linear, defined by two points,

…) to a value represented in the program, e.g. that is more suitable for your purposes

• Mapping – the auto-generated and mapped variable. When in advanced IDE, you will see map your self-created

variables to physical ports

Transformations Available transformations:

• Identity – transform type 1:1 (input = output)

• ResistanceToTemperature – transforms the value to a temperature based on the value of the resistance by

setting all the necessary parameters

• Linear – transforms the value based on a line defined by parameters q and k

• Threshold – transforms the value in a digital true – false value based on threshold value

• Window – a window (low and high parameters) which allows transforming discrete input value into Boolean

true/false value

• Negate – negates the digital input value

• LinearByTwoPoints – this type will return a value that lies on a linear line between the two predefined points

• LinearByTable – almost identical to LinearByTwoPoints transformation, but it allows us to define up to 8 points

When using transformations, make sure to set the parameters in the right order based on the fact if of using inputs or

outputs or you might end up with values that won’t be representing the real value.

In this case, it is predefined with LinearByTwoPoints transformation for our analog inputs. The set up values are in a

range 0 – 10 000 mV.

Page 13: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1 & UniPi Lite

Page 12 of 46 UniPi 1 & UniPi Lite

2.7.2 Relays

Relays are connected via the I2C channel as well so you only need to add another device to the I2C channel. Otherwise

you will need to add I2C channel, which is descripted in the beginning of Analog Inputs chapter.

Once the channel is set up then right click on the channel (in Solution Explorer) and from the menu select Add library

device → UniPi (v1.1) → I2C → Relays (version 1)

See the auto-generated variables in Variable Browser.

2.7.3 Digital inputs and Analog Output

Digital inputs require a new channel – right click on the PLC in Solution Explorer → Add new channel.

After the new channel is created under the PLC icon, left click on it and set the Properties on the right side of the screen:

• Protocol – set this to Modbus

• Link Protocol – set this to TCP

• Name – use a descriptive name (e.g. „Modbus“)

Page 14: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1 & UniPi Lite

Page 13 of 46 UniPi 1 & UniPi Lite

After that add a new device by right clicking on the channel and select: Add library device → UniPi Technology → Unipi

(1.1) AO/DI/CNT (version 1).

Page 15: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1 & UniPi Lite

Page 14 of 46 UniPi 1 & UniPi Lite

Digital inputs, analog output and counters has been added to the variables as (DIx, DI_CNT_x…).

The last step is to set a proper physical connection e.g.:

Analog Output (UniAODICounters_AO01)

This variable can take values from 0 to 10 000. When value 0 represents 10V and value 10 000 represents 0V.

Page 16: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi Neuron

Page 15 of 46 UniPi Neuron

2.8 Attaching Neuron

(If you want attach UniPi 1.x device, go back to chapter 2.6)

2.8.1 All IOs except 1-Wire

Adding most of the peripherals of all Neuron devices (except extensions) is simplified to a TCP Modbus channel. So,

start by creating a TCP Modbus Channel:

Right click on the PLC in Solution Explorer → Add new channel

After the new channel is created under the PLC icon, left click on it and set the Properties on the right side of the screen:

• Protocol – set this to Modbus

• Link Protocol – set this to TCP

• Name – again, use a descriptive name (e.g. „TCP Modbus“)

Page 17: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi Neuron

Page 16 of 46 UniPi Neuron

After the channel setup is completed add a new device by right clicking on the channel and choosing Add library device

→ UniPi Technology → and select the Neuron device you are using.

All the peripherals of the Neuron are now available in a Variable browser (if using Simple mode).

This step is required in order to let Mervis know, what device you are using so it know what serial lines and

other peripherals can be used!

2.8.2 Analog outputs

Working with analog output of group 1 is different than analog output of other groups – group 2 and 3 and analog output

of extension modules.

2.8.2.1 Analog Output of group 1 (Alternatively Resistance Analog Input – Pt1000) UniPi Neuron have one special functionality. It’s capable measuring of Analog Output level. Analog Output can work in

3 (4) modes:

1. Voltage Output

2. Current Output

3. Resistance Input

a. Pt1000 temperature

For all of this you can use AOI function module.

You can choose which mode you want use in function block Properties → mode (Voltage, Current, Resistance, Pt1000)

Page 18: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi Neuron

Page 17 of 46 UniPi Neuron

Input Variables:

target_value – used only while in AO mode(Volts/Amperes) to set the output value Mode – it is necessary to select the appropriate option

All remaining input variables must be connected to the variables created by Autogen with the same name. This will ensure proper working of the function block.

Output Variables:

AO_1 – must be appended to a variable with the same name when using autogen

Page 19: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi Neuron

Page 18 of 46 UniPi Neuron

AO_mode – must be appended to a variable with the same name when using autogen All remain output variables can be connected to your custom variables. The following table describes the options of AO_mode variable. After changing the value, it is recommended to save the configuration using the appropriate NV_save variable of that group to True.

2.8.2.2 Analog outputs of extension modules and groups other than 1 (AO2.1) Analog outputs of these is only provide 0 – 10 V output. To set the voltage on this output it is only needed to write the requested value to the appropriate AO variable. Remember that in WH prototypes with version 1.0 it is needed to set Linear transformation for these outputs (k=4, q=0) and then set the values in millivolts. In prototypes with version 1.1 this transformation is already included.

2.8.3 Analog Inputs

The similar way as analog outputs, working with analog input of group 1 is also different than working with analog inputs

of other groups (groups 2 and 3) and extensions.

2.8.3.1 Analog Input of group 1 UniPi Neuron can work in 2 modes:

1. Voltage Intput

2. Current Input

For all of this you can use AI_measure function module.

You can choose which mode you want use in function block Properties → mode (Voltage, Current)

Settings Output type Note

0 Voltage 0 – 10 V

1 Current 0 – 20 mA

3 Resistance measurement Since Firmware 5.0

Page 20: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi Neuron

Page 19 of 46 UniPi Neuron

Input Variables:

Mode – it is necessary to select the appropriate option All remaining input variables must be connected to the variables created by Autogen with the same name. This will ensure proper working of the function block.

Output Variables:

AI_1 – must be appended to a variable with the same name when using Autogen All remain output variables can be connected to your custom variables.

2.8.3.2 Analog inputs of extension modules and groups other than 1 (AI2.1,…) Analog inputs other than group 1 and extensions are capable of measuring voltage, current and resistance. The type of

measurement has to be set using variable AI_mode according to the following table. Than the value read from the AI

variable is the value measure on the AI according to the settings.

Again, after configuration to the AI_mode variable, it is recommended to set appropriate NV_save variable to True to and than back to False so that the configuration is saved.

2.8.4 RS485

If you want to attach any Neuron Extension module, you must attach Neuron controller first to the TCP Modbus channel!

You can do this by the procedure given in chapter 2.7.1.

Settings Type of measurement

0 Off

1 Voltage 0 – 10 V

2 Voltage 0 – 2.5 V

3 Current 0 – 20 mA

4 Resistance (two conductors) 0 – 1 960 Ω

5 Resistance (three conductors) 0 – 100 kΩ

Page 21: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi Neuron

Page 20 of 46 UniPi Neuron

In solution explorer, under the PLC icon, you will create a new channel. Select that channel by left clicking on it and in

the right part of the screen you will see its Properties. Set is as following:

• Protocol – Modbus

• Link protocol – Serial

• Name – it is recommended to use a descriptive name (for example we can use the Link Protocol name -

„RS485“)

RS485 serial communication and have these parameters:

Speed (Baud Rate)

Software setting – ONLY speed can be set via Channel Properties → Serial Line Parameters. This is the ONLY option

that can be set from Properties frame.

It is HIGHLY recommended to set all parameters via variable named UART_config. Data Bits

This option is factory set to 8 and cannot be changed.

Parity

Software setting – parity can be set via variable named UART_config_1.01.

Stop Bits

This option is factory set to 1 and cannot be changed.

UART config variable

This variable contains physical configuration of the serial line. The value must be filled in decimal format.

Bits 0 – 12 represents speed. Bit 13 represents parity status (0 = None, 1 = Even/Odd).

Bit 14

represents

parity type (0 =

Even, 1 = Odd)

Value Speed [bps]

11 2 400

12 4 800

13 9 600

14 19 200

15 38 400

4097 57 600

4098 115 200

Page 22: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi Neuron

Page 21 of 46 UniPi Neuron

Example: odd

parity and

57 600bps

speed:

Parity Odd Speed 57 600bps Result (UART_config)

Binary 0000 0000 0000 0110 0001 0000 0000 0001 0001 0000 0000 0111

Decimal 24 576 4 097 28 673

Example: even parity and 38 400bps speed:

!!You must save the changes by overwriting _NV_save_2 (e.g. for Neuron second group) to 1.

2.8.5 Extension modules

If you want to attach any Neuron Extension module, you must attach Neuron controller first! You can do this by the

procedure given in 2.8

It is possible to configure communication parameters in two ways. Either directly via integrated DIP switch (hardware

settings) or through software configuration in the corresponding registers (software settings). Hardware configuration

always supersedes the software configuration. To enable software configuration the hardware configuration must be set

to 0. The configuration is deeply described in the Neuron technical documentation.

In solution explorer, under the PLC icon, you will create a new channel. Select that channel by left clicking on it and in

the right part of the screen you will see its properties. Set is as following:

• Protocol – Modbus

• Link protocol – Serial

• Name – it is recommended to use a descriptive name (for example we can use the Link Protocol name - „Modbus

Serial“)

In the Serial Line Parameters set:

If you want set speed or parity via manual DIP switch, you must set address on DIP first.

• Port Number – choose your Modbus TCP attached (master) Neuron device

• Baud Rate [19 200] – 2 400 to 115 200bps; 9 600bps/19 200bps can set by DIP switch

• Data Bits [8] – fixed

• Parity [no parity] – no parity, even, odd; no parity/even can set by DIP switch

• Stop Bits [1] – fixed

Value Parity

24 576 Odd

8 192 Even

Parity Even Speed 38 400bps Result (UART_config)

Binary 0000 0000 0000 0010 1111 1111 0000 0000 0010

Decimal 8 192 15 8 207

Page 23: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi Neuron

Page 22 of 46 UniPi Neuron

After that add a new device by right clicking on the channel and select Add library device → UniPi Technology → Neuron

xS10 [xS30, xS40] (Device/Prototype ver. x.x/x.x).

2.8.6 Configure the software configuration of the connection

It serves for wider communication between PLC and Extension. At Extension can be set: only 19200bps (default) or

9200bps, no parity (default) or even and address of a maximum of 15 devices (default 15). The software configuration

allows you to select from multiple parity, speed and up to 255 addresses. To enable software configuration, the DIP

switch must be in the default position (address 0).

2.8.6.1 Setting the RS-485 parameters To set up your own configuration, you need to calculate the value of variable _UART_config_ as described in Chapter

2.8.4 (e.g. 8206). First write this value in debug mode to the _UART_config_ Extension variable and save it by

overwriting _NV_save_ (Extension) to true. It is then necessary to restart the Extension and override the _Reboot_

Extension value to true or disconnect and connect the power terminals. Then do the same with the PLC variables

(otherwise, we would break the communication). Subsequently, the field with the given Extension variable is coloured

Page 24: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi Neuron

Page 23 of 46 UniPi Neuron

in red in the Value PLC column. Now turn off the debug mode and left-click on your Modbus-serial channel in its

properties to the right to set your parameters (e.g., baud rate: 19200 and parity: even).

!! You need to communicate with your device (preferably by default) to make the change.

Then click to deploy solution and upload these changes to the PLC and make a cold restart.

2.8.6.2 Address settings To modify the Modbus address, perform a similar procedure. In the variable browser, enter the new address value (1-

255) (e.g. 20) into the _Modbus_Address_config_ variable. Then save it by overwriting the _NV_save_ (Extension)

variable to true and restart the Extension by overwriting the _Reboot_ of Extension to true or disconnecting and

connecting the power terminals. Then turn off the debug mode and left-click on your Extension device in the report

explorer in the properties to the right again to enter your new address (e.g. 20). Then deploy solution and the device will

communicate with each other at a new address.

NOTE: Make both changes. The first concerns an extension device that only communicates with the PLC and the other

concerns the connection that the PLC creates.

Page 25: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi Neuron

Page 24 of 46 UniPi Neuron

2.9 Example of attaching Modbus serial device (Electricity meter Inepro)

This is description in Simple mode.

In order to set up the Modbus serial devices you need to add a new channel which will represent the Modbus serial

channel.

Right click on the PLC in Solution Explorer → Add new channel

After the new channel is created under the PLC icon, left click on it and set the Properties on the right side of the screen:

• Protocol – set this to Modbus

• Link Protocol – set this to Serial

• Name – again, use a descriptive name (e.g. „Modbus_serial“)

• Port Number – set this to your UniPi device

After the channel setup is completed add a new device by right clicking on the channel and choosing → Add Device.

After the new device is created under the PLC icon, left click on it and set the Properties on the right side of the screen:

• Name – again, use a descriptive name (e.g. electricity_meter.)

• Is suggest to fill in Device Info for better description (in our case: Model – „PRO 380” a Manufacturer – „Inepro”)

At first we will be defined groups.

Double click on device will appear New working place. Right click somewhere in working place and choose Add Group.

After the new Group is created, left click on it and set the Properties on the right side of the screen:

• Name – use a descriptive name with type of group (e.g. „PowerRead“)

• Group Type – choose what you want, if only read or only write (e.g. ReadOnly)

• Starting element – Here is the number of the initial element of the register to be read

(e.g. „8321“)

• Qantity of elements - how many registers to read in the group (e.g. 24)

NOTE: The registry number you want to read, you can find in table of registers in HEX, but IDE request for DEC number

and don’t forget to add one.

The table of registers for electricity meter Inepro you can find

Page 26: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi Neuron

Page 25 of 46 UniPi Neuron

After that by right click somewhere in working place choose Add Data Point.

After the new Data Point is created left click on it and set the Properties on the right side of the screen:

• Name – use a descriptive name (e.g. „L1_Apparent_Power“)

• Group – select a group the data point belongs to (e.g. „PowerRead‘)

• Comm. Value Mapped Type - select from BuiltIn, Bit and Array (e.g. „BuiltIn“)

• ST type – select the data point type (e.g. „real“)

• Data Offset (Parser) – specifies on which byte the data of a data point start (e.g. „36“)

• MultiByte Lenght (Parser) – number of bytes to be read into a data point (e.g. „4-byte”)

Connect the electricity meter to UniPi, compile and deploy the project to UniPi.

After a successful upload click the Start Debugging button and in Variable Browser you can see the value of apparent

power from electricity meter.

In a case of red colouring check the parameter UART_config, by the procedure given in chapter 2.8.4

Page 27: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1, UniPi Lite and UniPi Neuron

Page 26 of 46 UniPi 1, UniPi Lite and UniPi Neuron

2.10 Attaching OneWire devices (Thermometer)

In order to set up the 1Wire devices you need to add a new channel which will represent the 1Wire channel.

Right click on the PLC in Solution Explorer → Add new channel

After the new channel is created under the PLC icon, left click on it and set the Properties on the right side of the screen:

• Protocol – set this to PlatformIO

• Link Protocol – set this to OneWire

• Name – again, use a descriptive name (e.g. „1Wire“)

After the channel setup is completed add a new device by right clicking on the channel and choosing Add library device

→ UniPi (v1.1) → OneWire → 1W-Thermometer (version 1).

Because each 1Wire device uses a special address for identification, you need to set the find out the address, CRC and

family code of the sensor.

In order to do that, connect the thermometer to UniPi, compile and deploy the project to UniPi (Ctrl+Shift+D).

Optimal settings are:

Now proceed with setting the address, CRC, and family code:

• Set the PLC to Commissioning mode – Right click on the PLC icon in Solution Explorer and choose PLC

Operation→ Commissioning mode

Page 28: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1, UniPi Lite and UniPi Neuron

Page 27 of 46 UniPi 1, UniPi Lite and UniPi Neuron

• After that, right click on the added One Wire device (in Solution Explorer) and from the menu choose Assign

One Wire Sensor

• After a short detection a table will show up with all detected One Wire Devices connected to UniPi. Select the

device you wish to add.

• Now you have a fully functional 1Wire device which should include the assigned address, family and CRC code.

As before Autogen created and mapped variables of the device

2.11 PWM (Pulse width modulation)

PWM can be activated for each digital output separately, but frequency settings are shared among all output of that

particular group. If DO is switched on, PWM value is ignored.

The following formula can be used to calculate the values of PWM_prescale from the given PWM_cycle and frequency (f). The PWM_cycle is the precision of PWM (e.g. if PWM_cycle is 100 the range of PWM variable is 0-100)

𝑃𝑊𝑀𝑝𝑟𝑒𝑠𝑐𝑎𝑙𝑒 =48𝑀𝐻𝑧

𝑓 ∗ (𝑃𝑊𝑀𝑐𝑦𝑐𝑙𝑒 + 1)− 1

EXAMPLE:

PWM_prescale will be 4751 when PWM_cycle is set to 100, frequency is 100Hz. Furthermore, setting of PWM value to

50 duty cycle will equal 50% on frequency 100Hz.

Page 29: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi Neuron

Page 28 of 46 UniPi Neuron

2.12 Simple program

This chapter will guide you through a process of making a simple program.

The program will switch a relay based on a status of digital inputs and results of some function blocks.

If you haven’t done all the previous steps, start from the beginning of this manual – create a new solution → attach

UniPi → configure inputs and outputs

Once done with the initial project setup, double click on “main” in Solution Explorer (under the tab Executable projects).

In the middle of main window, you will see the main control program including:

• Column showing inputs - read (left side)

• Area for placing and connecting Fupla blocks (center)

• Column showing outputs - write (right side)

First add global variables – right click into the column for inputs and choose: Global variables → Insert Existing Variable.

Gradually find and add variables _DI_1.01 - Neuron _DI_1.03

Then repeat the same process, but instead of adding a variable into the inputs column, add _RO_2.05 into the outputs

column.

Then right click to the area for placing Fupla blocks, choose Add Library Box → Add Library Box. Gradually find and

add blocks AND and OR.

Page 30: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi Neuron

Page 29 of 46 UniPi Neuron

Make connections as in the picture below.

After finishing all the steps above, Build solution (Ctrl+Shift+B) and check for any errors or warnings, which can be seen

in the Results tab at the bottom of the screen

• Error – critical mistake, which needs to be resolved, in order the program to work

• Warning – just a reminder that something might be wrong and should be addressed, but it doesn’t have any

impact on the functionality

If the compilation is successful Deploy solution (Ctrl+Shift+D) to UniPi. A new window with Device run settings shows

up where you can set how the UniPi runs.

Program description:

• Digital input 1 is ON AND on Digital input 2 is ON

• OR on digital input 3

• Relay 5 switches ON else is OFF

Page 31: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1, UniPi Lite and UniPi Neuron

Page 30 of 45 UniPi 1, UniPi Lite and UniPi Neuron

2.13 Debugging

After a successful upload click the Start Debugging button.

When in debugging mode, you can see the values of all variables either in program, or in Variable Browser. You can

also manually change the value of variables. Go to Variable Browser find the variable UniRelaysRelay_2 and change

the value in PLC Value column to True. The relay 2 will switch ON.

Page 32: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1, UniPi Lite and UniPi Neuron

Page 31 of 45 UniPi 1, UniPi Lite and UniPi Neuron

In debugging mode, a new tab in the central window opens – System Status.

It is useful to monitor used memory, sent or received packets, communication status with DB or Proxy server, etc.

Detailed explanation is in IDE’s Help (search for System Status).

Page 33: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1, UniPi Lite and UniPi Neuron

Page 32 of 45 UniPi 1, UniPi Lite and UniPi Neuron

3 HMI (Human Machine Interface)

For simple and user, friendly control interface of program running on UniPi, users can utilize the ability to create and

deploy a web interface which can be accessed on a LAN by any device which has a compatible web browser.

First step is to make sure that project on UniPi is configured and deployed properly.

To create web HMI use the Mervis HMI (see installation in the first part of this tutorial).

3.1 Creating a web

First step is to create a new project.

• On the top toolbar you need to select File → New → Project

• A new window will appear. Set the basic project configuration:

• AlarmsConfigFilePath – path for the file with Alarms configuration (leave it on the default path)

• Name – name of the project

• Path –path, where the whole web will be saved and stored and from there, it will be uploaded to the UniPi later

on

• Size – used for changing parameters of height and width of the web panel

A new window will appear where you can change the color of the panel or set a background image

3.2 Connecting variables

Next step is to make a connection between HMI and variables from IDE project.

• Select File → Variable Manager...

• Click on the Select File and go to the project folder and open the bin folder, choose the *.exs file and confirm.

After that, press Retrieve which retrieves all the variables used in the project

3.3 Gadgets

On the left side of the Mervis HMI environment see all gadgets which we can be added to the HMI. Gadgets include

indicators, setters, progress bar, graph, etc.

In this tutorial, will use the digital setter and analog indicator. Other gadgets can be set and utilized similarly.

Page 34: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1, UniPi Lite and UniPi Neuron

Page 33 of 45 UniPi 1, UniPi Lite and UniPi Neuron

• Left click on Analog indicator in Gadgets Panel, hold, drag and drop it into the HMI Panel. Properties of the

gadget will show up on the right side of the screen. Attach desired variable (E.g. temperature) by left clicking

on the button with three dots and choosing the required variable.

• Next, drag and drop the Digital setter. In the properties, attach a variable again, and then go to

DigitalSetterValues. Here add states of the setter for setting the value by clicking on Add. Every state can be

set with: text, picture, background color, or defined with value which will be inserted into our variable

Page 35: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1, UniPi Lite and UniPi Neuron

Page 34 of 45 UniPi 1, UniPi Lite and UniPi Neuron

These two simple gadgets can be used e.g. for indicating temperature (analog indicator) or switching relays (digital

setter).

3.4 New panel

If you need more panels in web interface, e.g. first panel for setting values (control) and second panel for displaying

values (overview), just create a new panel, and then switch between them in the web page

• Choose File → New → Panel.

• Fill in the same properties as when creating a new HMI project

3.5 Uploading web

Once the design of HMI is complete, proceed with uploading the HMI to UniPi.

• First save the HMI project. File → Save. Then export the project to a folder, from where it will be uploaded to

the UniPi. File → Export To WebPanel.... Choose the same folder as the one, where the project is saved or

create a new subfolder (e.g. www) for better organization

Page 36: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1, UniPi Lite and UniPi Neuron

Page 35 of 45 UniPi 1, UniPi Lite and UniPi Neuron

• Now go to Mervis IDE and open the project. You have to add the exported project to the device configuration.

In Controller properties locate Web files directory column, and add the path to the exported folder. You can

also set up Web user and Web password, if you need restrict access to control of the web panel. To deploy

the user and the password into the PLC is necessary to perform Cold restart.

Page 37: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1, UniPi Lite and UniPi Neuron

Page 36 of 45 UniPi 1, UniPi Lite and UniPi Neuron

• Now left click on the PLC in Solution Explorer, and then click on Upload web. After the upload is done, you can

open web browser and type the IP address of the UniPi as an URL address. You should see the web panel. If

not, try refreshing the page or rebooting the UniPi.

Page 38: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1, UniPi Lite and UniPi Neuron

Page 37 of 45 UniPi 1, UniPi Lite and UniPi Neuron

4 Advanced IDE

This chapter describes configuration and usage of advanced features of Mervis IDE, such as Mervis DB logging or

remote access to the UniPi via Mervis Proxy. This features are available only in full mode of the project.

To switch to full mode right click on name of your project in the Solution Explorer and select Switch to full mode. If you

do this, you cannot switch back to simple mode further.

4.1 Manual mapping of HW prototypes to variables • First create a new global variable

• Go to main and right click into the column for inputs and choose Global variables → Create New Variable. Name

it Digital_Input_4 and as a type choose bool (can also be done in ST language)

• Now create an output global variable. Name it Relay_2 with bool

• Go to IO Mapping, locate the variable DI04, and make sure the Autogen is disabled for the variable (uncheck

Enable SWAutogen in Properties) and in the IO => ST column type our newly created variable Digital_Input_4

• Note: column IO => ST is for reading from inputs, column ST => IO is for writing to outputs

• Do the same for the second variable: Relay_2 to Relay2 (ST =>IO)

• Try changing the new global variables instead of the generated variables in the project program

Page 39: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1, UniPi Lite and UniPi Neuron

Page 38 of 45 UniPi 1, UniPi Lite and UniPi Neuron

4.2 Creating function blocks

If the basic function blocks are not enough, or some of the blocks (or code) is repeating in the program, users can

create their own function blocks

This is very useful in more cases, for example: If you use some operation more times in a program, create the

operation in a function block and then use only the one function block. Then the program is simpler, shorter and more

elegant and changes to the behavior is done only in one place.

• Before creating a function block, first switch to Full Mode. The function block will be created in ST (structured

text) language, and it is only supported in full mode.

• Up to now, all examples were shown using FBD (function block diagram) language. These two program

description (or languages) are equal and can be combined

• To create a new Function Block right click on project icon in Solution Explorer and choose Add → Add Function

Block. Fill in the name (e.g. conversion) and choose ST as a language

• A new program appears in the Solution Explorer, double click on it to see the function block’s structure. Type

the following code to the editor:

Page 40: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1, UniPi Lite and UniPi Neuron

Page 39 of 45 UniPi 1, UniPi Lite and UniPi Neuron

• It should be clear, that the function block will convert temperature in Celsius degrees °C to Fahrenheit degrees

°F

• Save the project and go to main. Insert an existing global variable 1W-Thermometer-Temperature to inputs

column, which represents temperature from OneWire sensor. Create a new local variable Temperature_F in

outputs column, which will represent temperature in °F – as a type choose real

• Now right click to the area for placing Fupla blocks, choose Add Library Box → Add Library Box. Find our

function block conversion and confirm

• Left click on the added box and uncheck en and eno in properties

• Make connections as in the picture:

• After deploying solution to the UniPi, the data from 1W-Thermometer-Temperature (temperature in °C) will be

converted to temperature in °F by function block conversion, and stored to the local variable Temperature_F.

• Check the correct working in debugging mode

4.3 Creating a new program

• For better and clear division of behavior of the PLC, the UniPi can run multiple programs at once (e.g. one

program switching lights, second for controlling room temperature, …)

• To create a Program right click on project icon in Solution Explorer, choose Add → Add Program, fill in the name

(e.g. lights) and choose type st/fdb

Page 41: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1, UniPi Lite and UniPi Neuron

Page 40 of 45 UniPi 1, UniPi Lite and UniPi Neuron

• In order tell the UniPi to include also the new program, set active the base to the Profile by right click on the

Profile and Set Active

• Then double click on PLC icon in Solution Explorer and go to Tasks tab. Now it is possible to change the

program assigned to the task. After going to Program mapping, users can assign which programs will run and

which not.

• Note: Never add more tasks! The whole program will fail.

4.4 SSCP communication

SSCP communication is used for reading/setting values from one UniPi to another or even to Proxy (e.g. for

communication of two UniPis that do not reside in the same IP network).

The problem will be explained on a project SSCP_multiple_plcs, which we can download from

http://downloads.unipi.technology.

• First, attach a UniPi normally as we did before and set all the necessary properties. Name this UniPi e.g. Master.

Then add a channel I2C and UniRelays device. Map a variable to Relay1 (use Autogen or manual mapping)

• Next add a second UniPi (right click on System → Add new Controller) and name it e.g. Slave. Then add

a channel Modbus (Tcp) and UniAODICounters device. Map a variable to DI1

Page 42: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1, UniPi Lite and UniPi Neuron

Page 41 of 45 UniPi 1, UniPi Lite and UniPi Neuron

• Now select the Master UniPi again and add a new channel with SSCP protocol and TCP Link protocol, name it

e.g. sscp. Then right click on the new channel and select Add device

• Go to Master UniPi’s properties, and remember parameters Username, Password and SSCP adress(default is

admin:rw). Go back to the created device for SSCP communication and set parameters Name (e.g.

to_slave_unipi), Device IP Address (same as the Slave’s IP address) and Device address, User Name,

Password (remembered parameters)

• Double click on the new device, and in the new opened window right click anywhere and choose Add Group.

Left click on the first line (Group) and edit properties: Name (read_group), Group Type (ReadOnly)

• Go to main, and create a new global variable slave_unipi_di1 (input column)

• Double click on the new device, right click anywhere to the group and select Add Data Point. In properties of

the new data point, map the variable slave_unipi_di1 to the column IO => ST. As a Source Variable, choose the

variable mapped to DI1 of Slave UniPi

• The communication should be now set. As a last step, go to main, and make a connection between

slave_unipi_di1 and Relay1 (output column)

• The master reads boolean value of variable DI1 from the slave, store it in slave_unipi_di and sets relay on/off

depending on its value

• ATTENTION: The maximum number of data points per channel is 12!

4.5 UniPi database access

Mervis database (DB) can store historical data from various data points to the cloud database. This is extremely useful

when dealing with correct behavior of the system.

The data can be viewed from either from the online viewer Web or online Scada system.

4.5.1 Setup

Make sure to be in advanced mode.

• Left click the PLC icon in Solution Explorer and look to the properties tab located on the right side of the screen

• First step is to set a unique history name identification in the History runtime Identification

• In order to save values fill in the necessary parameters in MervisDB Parameters

o Enabling database – parameter Enable set on True

o URL – URL address of database (MervisDB URL - http://db.unipi.technology/plc/save)

o Communication Period – represents how often will the data be written into the DB

Page 43: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1, UniPi Lite and UniPi Neuron

Page 42 of 45 UniPi 1, UniPi Lite and UniPi Neuron

o Access authentication – parameter User name (DB username) and Password (DB password)

• The final step is uploading the configuration into the device and performing a device reboot

• In order save variables from the UniPi to the database create a history, where the variables will be stored

• See a tab named History in Solution Explorer. Right click on it and choose Add new history. A new history

instance will appear and configure it with the following parameters:

o History Name

o History Saved on PLC → True - the data will be stored in your UniPi memory and later they will be

uploaded to your DB

o Save period – defines how often the data will be saved in History (either synchronously or

asynchronously to an event)

Page 44: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1, UniPi Lite and UniPi Neuron

Page 43 of 45 UniPi 1, UniPi Lite and UniPi Neuron

• First select which variables will be stored in the History

• UniPi has a part of its memory reserved for storing the history. Thanks to this, even in a case of a connection

error, the values will be buffered in the memory and once the connection is restored, uploaded to the DB

• Variables can be assigned to the History from Variable browser. In browser locate the variable and right click

om it and from the menu choose Add to history and select the desired history

• Deploy the project to UniPi and start debugging mode

• After the configured time you should see an increasing count and time of last request of Records saved to DB

in the System status under Services

4.5.2 Online access

• If the previous steps are completed, go to https://db.unipi.technology/viewer

• Fill in your User name and Password and confirm by clicking on Set

• It is possible to choose between showing a graph or text log, change the showed time interval, change the style

of drawing the graph etc.

• Note: If no data have been uploaded to DB, you will not be able to log in to the viewer

Page 45: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1, UniPi Lite and UniPi Neuron

Page 44 of 45 UniPi 1, UniPi Lite and UniPi Neuron

4.6 Proxy connection

Proxy connection allows accessing UniPi remotely. This allows users to change anything in the program (e.g. value of

variables) or even completely reprogram the UniPi.

Some settings cannot be changed (such as IP address) to prevent users from losing the remote connection with

UniPi.

4.6.1 Configuration

• Left click the PLC in Solution Explorer → in properties locate the Proxy Parameters and set:

o Enable proxy connection – parameter Enable must be set on „true“

o Proxy ID - a unique ID string (Proxy ID)

o Parameter URL must contain the URL + port address for the Proxy server which will be used (Proxy

URL - http://proxy.unipi.technology:6677)

o Parameter Keep-alive period can be optionally set to a different value

• Upload the configuration to UniPi and perform a device reboot

• After a successful device reboot change the connection parameters from TCP to Proxy:

o In device properties we locate PLC Connection Parameters:

Parameter Connection type must be set to proxy

o In device properties we locate Connection Parameters:

Parameter URI must contain Controller connection URI address

(proxy.unipi.technology:12348)

• Parameter Proxy ID must be identical with the one assigned in previous step

• Try to connect to your UniPi using proxy (no other configuration uploads or reboot is required) - just go to

Debugging mode

Page 46: Contentsoftware:mervis:mervis_step... · 2.8.1 All IOs except 1-Wire ... 2.13 Debugging ... If there is no DHCP server on the network (e.g. when the UniPi is connected directly to

UniPi 1, UniPi Lite and UniPi Neuron

Page 45 of 45 UniPi 1, UniPi Lite and UniPi Neuron

• You can also test the connection by downloading device log, rebooting the device, uploading the main control

program etc. When in debug mode and look into System Status, you should see that number of free proxy slots

is one lower then number of all slots

It is good idea to set up one profile for TCP connection and one profile for Proxy connection. Example:

• First do all the programming and setting the device properties in „mother’s profile” (profile dev – This

profile will communicate with UniPi on LAN). Then we add a new child profile proxy (right click on

profile dev and choose Add Child Profile). This profile will be used for remote management.

• Remember that the changes you make in the „child’s profile” are not transferred to the upper profile

and not all parameters are inherited from the upper layer profile