WARMUP TECTORA JOISTED BATTEN FLOOR SYSTEM. Concrete subfloor. Generic template 11_ Floor finish and intermediate layer 02_ DPM 03_ Timber battens [400 mm centres] 01_ Subfloor 04_ ≥20 mm Rigid insulation [finishing 16 mm below top of battens] 05_ Warmup Tectora diffusion plates 08_ 1 mm Polyethylene foam or equivalent 06_ Warmup16 mm pipework 09_ Timber floor deck 07_ Warmup 40/60 Clypso Clip* [between plates and on turns] 10_ Floor sensor (conduit recommended)** * Pipes need to be clipped to the insulation on turns ** Channel a groove in the floor deck to allow for floor sensor installation REV DATE DESCRIPTION DR CH DRAWING ISSUE STATUS PROJECT PROJECT MANAGER DRAWN CHECKED DATE SCALE REVISION © This drawing is confidential and may not be used, copied or disclosed to anyone without permission of Warmup Plc. The Copyright of these drawings remain the property of Warmup Plc. Do not scale from drawings, all dimensions to be checked on site. The Warmup word and associated logos are trade marks. © Warmup Plc. 2010 - Regd. TM Nos. 1257757, 4409926, 5265707. E & OE. Registered in England No. 2955213. DRAWING NO CAD FILE WARMUP PLC, 704 Tudor Estate, Abbey Road, London,NW10 7UW Tel 0845 034 8270 Fax 0208 453 6869 [email protected] [email protected] www.warmup.co.uk TITLE DETAILED SECTION CONSTRUCTION 01 TECTORA JOISTED BATTEN FLOOR SYSTEM CONCRETE SUBFLOOR GENERIC TEMPLATE 01.03.2017 20170228-H-TECTORA-DET SECTIONS.DWG AA 1:50@A3 AW

Upload: others

Post on 30-Sep-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CONSTRUCTION WARMUP TECTORA JOISTED BATTEN FLOOR …es.warmup.co.uk/wp-content/uploads/20170228-H-TECTORA-DET-SE… · WARMUP TECTORA JOISTED BATTEN FLOOR SYSTEM. Concrete subfloor

WARMUP TECTORA JOISTED BATTEN FLOOR SYSTEM. Concrete subfloor. Generic template

11_ Floor finish and intermediate layer

02_ DPM

03_ Timber battens [400 mm centres]

01_ Subfloor

04_ ≥20 mm Rigid insulation [finishing 16 mm below top of battens]

05_ Warmup Tectora diffusion plates

08_ 1 mm Polyethylene foam or equivalent

06_ Warmup16 mm pipework

09_ Timber floor deck

07_ Warmup 40/60 Clypso Clip* [between plates and on turns]

10_ Floor sensor (conduit recommended)**

* Pipes need to be clipped to the insulation on turns

** Channel a groove in the floor deck to allow for floor sensor installation

REV DATE DESCRIPTION DR CH

DRAWING ISSUE STATUS

PROJECT

PROJECT MANAGER DRAWN CHECKED

DATE SCALE REVISION

© This drawing is confidential and may not be used, copied ordisclosed to anyone without permission of Warmup Plc. The Copyrightof these drawings remain the property of Warmup Plc.

Do not scale from drawings, all dimensions to be checked on site.

The Warmup word and associated logos are trade marks. © WarmupPlc. 2010 - Regd. TM Nos. 1257757, 4409926, 5265707. E & OE. Registeredin England No. 2955213.

DRAWING NO

CAD FILE

WARMUP PLC, 704 Tudor Estate, Abbey Road, London,NW10 7UW Tel 0845 034 8270 Fax 0208 453 6869

[email protected] [email protected] www.warmup.co.uk

TITLE

DETAILED SECTION

CONSTRUCTION 01

TECTORA JOISTED BATTEN FLOOR SYSTEMCONCRETE SUBFLOOR

GENERIC TEMPLATE

01.03.2017

20170228-H-TECTORA-DET SECTIONS.DWG

AA

1:50@A3

AW

Page 2: CONSTRUCTION WARMUP TECTORA JOISTED BATTEN FLOOR …es.warmup.co.uk/wp-content/uploads/20170228-H-TECTORA-DET-SE… · WARMUP TECTORA JOISTED BATTEN FLOOR SYSTEM. Concrete subfloor

WARMUP TECTORA JOISTED BATTEN FLOOR SYSTEM. Concrete subfloor. Tiled floor

11_ Flexible tile adhesive

12_ Tiled floor finish

* Pipes need to be clipped to the insulation on turns

** Channel a groove in the floor deck to allow for floor sensor installation

02_ DPM

03_ Timber battens [400 mm centres]

01_ Subfloor

04_ ≥20 mm Rigid insulation [finishing 16 mm below top of battens]

05_ Warmup Tectora diffusion plates

08_ 1 mm Polyethylene foam or equivalent

06_ Warmup16 mm pipework

09_ Timber floor deck

07_ Warmup 40/60 Clypso Clip* [between plates and on turns]

10_ Floor sensor (conduit recommended)**

REV DATE DESCRIPTION DR CH

DRAWING ISSUE STATUS

PROJECT

PROJECT MANAGER DRAWN CHECKED

DATE SCALE REVISION

© This drawing is confidential and may not be used, copied ordisclosed to anyone without permission of Warmup Plc. The Copyrightof these drawings remain the property of Warmup Plc.

Do not scale from drawings, all dimensions to be checked on site.

The Warmup word and associated logos are trade marks. © WarmupPlc. 2010 - Regd. TM Nos. 1257757, 4409926, 5265707. E & OE. Registeredin England No. 2955213.

DRAWING NO

CAD FILE

WARMUP PLC, 704 Tudor Estate, Abbey Road, London,NW10 7UW Tel 0845 034 8270 Fax 0208 453 6869

[email protected] [email protected] www.warmup.co.uk

TITLE

DETAILED SECTION

CONSTRUCTION 02

TECTORA JOISTED BATTEN FLOOR SYSTEMCONCRETE SUBFLOOR

TILED FLOOR

01.03.2017

20170228-H-TECTORA-DET SECTIONS.DWG

AA

1:50@A3

AW

Page 3: CONSTRUCTION WARMUP TECTORA JOISTED BATTEN FLOOR …es.warmup.co.uk/wp-content/uploads/20170228-H-TECTORA-DET-SE… · WARMUP TECTORA JOISTED BATTEN FLOOR SYSTEM. Concrete subfloor

WARMUP TECTORA JOISTED BATTEN FLOOR SYSTEM. Concrete subfloor. Wood / Laminate floor - floating

11_ UFH compatible underlay

12_ Floating timber floor finish

* Pipes need to be clipped to the insulation on turns

** Channel a groove in the floor deck to allow for floor sensor installation

02_ DPM

03_ Timber battens [400 mm centres]

01_ Subfloor

04_ ≥20 mm Rigid insulation [finishing 16 mm below top of battens]

05_ Warmup Tectora diffusion plates

08_ 1 mm Polyethylene foam or equivalent

06_ Warmup16 mm pipework

09_ Timber floor deck

07_ Warmup 40/60 Clypso Clip* [between plates and on turns]

10_ Floor sensor (conduit recommended)**

REV DATE DESCRIPTION DR CH

DRAWING ISSUE STATUS

PROJECT

PROJECT MANAGER DRAWN CHECKED

DATE SCALE REVISION

© This drawing is confidential and may not be used, copied ordisclosed to anyone without permission of Warmup Plc. The Copyrightof these drawings remain the property of Warmup Plc.

Do not scale from drawings, all dimensions to be checked on site.

The Warmup word and associated logos are trade marks. © WarmupPlc. 2010 - Regd. TM Nos. 1257757, 4409926, 5265707. E & OE. Registeredin England No. 2955213.

DRAWING NO

CAD FILE

WARMUP PLC, 704 Tudor Estate, Abbey Road, London,NW10 7UW Tel 0845 034 8270 Fax 0208 453 6869

[email protected] [email protected] www.warmup.co.uk

TITLE

DETAILED SECTION

CONSTRUCTION 03

TECTORA JOISTED BATTEN FLOOR SYSTEMCONCRETE SUBFLOOR

WOOD / LAMINATE FLOOR - FLOATING

01.03.2017

20170228-H-TECTORA-DET SECTIONS.DWG

AA

1:50@A3

AW

Page 4: CONSTRUCTION WARMUP TECTORA JOISTED BATTEN FLOOR …es.warmup.co.uk/wp-content/uploads/20170228-H-TECTORA-DET-SE… · WARMUP TECTORA JOISTED BATTEN FLOOR SYSTEM. Concrete subfloor

WARMUP TECTORA JOISTED BATTEN FLOOR SYSTEM. Concrete subfloor. Wood / Laminate floor - glued

04_ ≥20 mm Rigid insulation [finishing 16 mm below top of battens]

11_ UFH compatible floor adhesive

12_ Timber floor finish

* Pipes need to be clipped to the insulation on turns

** Channel a groove in the floor deck to allow for floor sensor installation

02_ DPM

03_ Timber battens [400 mm centres]

01_ Subfloor

04_ ≥20 mm Rigid insulation [finishing 16 mm below top of battens]

05_ Warmup Tectora diffusion plates

08_ 1 mm Polyethylene foam or equivalent

06_ Warmup16 mm pipework

09_ Timber floor deck

07_ Warmup 40/60 Clypso Clip* [between plates and on turns]

10_ Floor sensor (conduit recommended)**

REV DATE DESCRIPTION DR CH

DRAWING ISSUE STATUS

PROJECT

PROJECT MANAGER DRAWN CHECKED

DATE SCALE REVISION

© This drawing is confidential and may not be used, copied ordisclosed to anyone without permission of Warmup Plc. The Copyrightof these drawings remain the property of Warmup Plc.

Do not scale from drawings, all dimensions to be checked on site.

The Warmup word and associated logos are trade marks. © WarmupPlc. 2010 - Regd. TM Nos. 1257757, 4409926, 5265707. E & OE. Registeredin England No. 2955213.

DRAWING NO

CAD FILE

WARMUP PLC, 704 Tudor Estate, Abbey Road, London,NW10 7UW Tel 0845 034 8270 Fax 0208 453 6869

[email protected] [email protected] www.warmup.co.uk

TITLE

DETAILED SECTION

CONSTRUCTION 04

TECTORA JOISTED BATTEN FLOOR SYSTEMCONCRETE SUBFLOOR

WOOD / LAMINATE FLOOR - GLUED

01.03.2017

20170228-H-TECTORA-DET SECTIONS.DWG

AA

1:50@A3

AW

Page 5: CONSTRUCTION WARMUP TECTORA JOISTED BATTEN FLOOR …es.warmup.co.uk/wp-content/uploads/20170228-H-TECTORA-DET-SE… · WARMUP TECTORA JOISTED BATTEN FLOOR SYSTEM. Concrete subfloor

WARMUP TECTORA JOISTED BATTEN FLOOR SYSTEM. Concrete subfloor. Wood / Laminate floor -screwed / nailed

02_ DPM

03_ Timber battens [400 mm centres]

01_ Subfloor

04_ ≥20 mm Rigid insulation [finishing 16 mm below top of battens]

05_ Warmup Tectora diffusion plates

09_ 1 mm Polyethylene foam or equivalent

06_ Warmup16 mm pipework

10_ Timber floor finish

* Pipes need to be clipped to the insulation on turns

** Floor sensor should be placed in a notch, filled with caulk/adhesive, in the batten with the diffuser plate trimmed back 10-15mm.

08_ Floor sensor (conduit recommended)**

07_ Warmup 40/60 Clypso Clip* [between plates and on turns]

REV DATE DESCRIPTION DR CH

DRAWING ISSUE STATUS

PROJECT

PROJECT MANAGER DRAWN CHECKED

DATE SCALE REVISION

© This drawing is confidential and may not be used, copied ordisclosed to anyone without permission of Warmup Plc. The Copyrightof these drawings remain the property of Warmup Plc.

Do not scale from drawings, all dimensions to be checked on site.

The Warmup word and associated logos are trade marks. © WarmupPlc. 2010 - Regd. TM Nos. 1257757, 4409926, 5265707. E & OE. Registeredin England No. 2955213.

DRAWING NO

CAD FILE

WARMUP PLC, 704 Tudor Estate, Abbey Road, London,NW10 7UW Tel 0845 034 8270 Fax 0208 453 6869

[email protected] [email protected] www.warmup.co.uk

TITLE

DETAILED SECTION

CONSTRUCTION 05

TECTORA JOISTED BATTEN FLOOR SYSTEMCONCRETE SUBFLOOR

WOOD/LAMINATE FLOOR-SCREWED/NAILED

01.03.2017

20170228-H-TECTORA-DET SECTIONS.DWG

AA

1:50@A3

AW

Page 6: CONSTRUCTION WARMUP TECTORA JOISTED BATTEN FLOOR …es.warmup.co.uk/wp-content/uploads/20170228-H-TECTORA-DET-SE… · WARMUP TECTORA JOISTED BATTEN FLOOR SYSTEM. Concrete subfloor

WARMUP TECTORA JOISTED BATTEN FLOOR SYSTEM. Concrete subfloor. Vinyl floor - floating

12_ UFH compatible underlay

13_ Floating vinyl floor finish

11_ 2-3 mm smoothing compound

* Pipes need to be clipped to the insulation on turns

** Channel a groove in the floor deck to allow for floor sensor installation

02_ DPM

03_ Timber battens [400 mm centres]

01_ Subfloor

04_ ≥20 mm Rigid insulation [finishing 16 mm below top of battens]

05_ Warmup Tectora diffusion plates

08_ 1 mm Polyethylene foam or equivalent

06_ Warmup16 mm pipework

09_ Timber floor deck

07_ Warmup 40/60 Clypso Clip* [between plates and on turns]

10_ Floor sensor (conduit recommended)**

REV DATE DESCRIPTION DR CH

DRAWING ISSUE STATUS

PROJECT

PROJECT MANAGER DRAWN CHECKED

DATE SCALE REVISION

© This drawing is confidential and may not be used, copied ordisclosed to anyone without permission of Warmup Plc. The Copyrightof these drawings remain the property of Warmup Plc.

Do not scale from drawings, all dimensions to be checked on site.

The Warmup word and associated logos are trade marks. © WarmupPlc. 2010 - Regd. TM Nos. 1257757, 4409926, 5265707. E & OE. Registeredin England No. 2955213.

DRAWING NO

CAD FILE

WARMUP PLC, 704 Tudor Estate, Abbey Road, London,NW10 7UW Tel 0845 034 8270 Fax 0208 453 6869

[email protected] [email protected] www.warmup.co.uk

TITLE

DETAILED SECTION

CONSTRUCTION 06

TECTORA JOISTED BATTEN FLOOR SYSTEMCONCRETE SUBFLOOR

VINYL FLOOR - FLOATING

01.03.2017

20170228-H-TECTORA-DET SECTIONS.DWG

AA

1:50@A3

AW

Page 7: CONSTRUCTION WARMUP TECTORA JOISTED BATTEN FLOOR …es.warmup.co.uk/wp-content/uploads/20170228-H-TECTORA-DET-SE… · WARMUP TECTORA JOISTED BATTEN FLOOR SYSTEM. Concrete subfloor

12_ UFH compatible vinyl floor adhesive

13_ Vinyl floor finish

11_ 2-3 mm smoothing compound

WARMUP TECTORA JOISTED BATTEN FLOOR SYSTEM. Concrete subfloor. Vinyl floor - glued* Pipes need to be clipped to the insulation on turns

** Channel a groove in the floor deck to allow for floor sensor installation

02_ DPM

03_ Timber battens [400 mm centres]

01_ Subfloor

04_ ≥20 mm Rigid insulation [finishing 16 mm below top of battens]

05_ Warmup Tectora diffusion plates

08_ 1 mm Polyethylene foam or equivalent

06_ Warmup16 mm pipework

09_ Timber floor deck

07_ Warmup 40/60 Clypso Clip* [between plates and on turns]

10_ Floor sensor (conduit recommended)**

REV DATE DESCRIPTION DR CH

DRAWING ISSUE STATUS

PROJECT

PROJECT MANAGER DRAWN CHECKED

DATE SCALE REVISION

© This drawing is confidential and may not be used, copied ordisclosed to anyone without permission of Warmup Plc. The Copyrightof these drawings remain the property of Warmup Plc.

Do not scale from drawings, all dimensions to be checked on site.

The Warmup word and associated logos are trade marks. © WarmupPlc. 2010 - Regd. TM Nos. 1257757, 4409926, 5265707. E & OE. Registeredin England No. 2955213.

DRAWING NO

CAD FILE

WARMUP PLC, 704 Tudor Estate, Abbey Road, London,NW10 7UW Tel 0845 034 8270 Fax 0208 453 6869

[email protected] [email protected] www.warmup.co.uk

TITLE

DETAILED SECTION

CONSTRUCTION 07

TECTORA JOISTED BATTEN FLOOR SYSTEMCONCRETE SUBFLOOR

VINYL FLOOR - GLUED

01.03.2017

20170228-H-TECTORA-DET SECTIONS.DWG

AA

1:50@A3

AW

Page 8: CONSTRUCTION WARMUP TECTORA JOISTED BATTEN FLOOR …es.warmup.co.uk/wp-content/uploads/20170228-H-TECTORA-DET-SE… · WARMUP TECTORA JOISTED BATTEN FLOOR SYSTEM. Concrete subfloor

11_ UFH compatible underlay

12_ Carpet floor finish

WARMUP TECTORA JOISTED BATTEN FLOOR SYSTEM. Concrete subfloor. Carpet floor* Pipes need to be clipped to the insulation on turns

** Channel a groove in the floor deck to allow for floor sensor installation

02_ DPM

03_ Timber battens [400 mm centres]

01_ Subfloor

04_ ≥20 mm Rigid insulation [finishing 16 mm below top of battens]

05_ Warmup Tectora diffusion plates

08_ 1 mm Polyethylene foam or equivalent

06_ Warmup16 mm pipework

09_ Timber floor deck

07_ Warmup 40/60 Clypso Clip* [between plates and on turns]

10_ Floor sensor (conduit recommended)**

REV DATE DESCRIPTION DR CH

DRAWING ISSUE STATUS

PROJECT

PROJECT MANAGER DRAWN CHECKED

DATE SCALE REVISION

© This drawing is confidential and may not be used, copied ordisclosed to anyone without permission of Warmup Plc. The Copyrightof these drawings remain the property of Warmup Plc.

Do not scale from drawings, all dimensions to be checked on site.

The Warmup word and associated logos are trade marks. © WarmupPlc. 2010 - Regd. TM Nos. 1257757, 4409926, 5265707. E & OE. Registeredin England No. 2955213.

DRAWING NO

CAD FILE

WARMUP PLC, 704 Tudor Estate, Abbey Road, London,NW10 7UW Tel 0845 034 8270 Fax 0208 453 6869

[email protected] [email protected] www.warmup.co.uk

TITLE

DETAILED SECTION

CONSTRUCTION 08

TECTORA JOISTED BATTEN FLOOR SYSTEMCONCRETE SUBFLOOR

CARPET FLOOR

01.03.2017

20170228-H-TECTORA-DET SECTIONS.DWG

AA

1:50@A3

AW