WARMUP TECTORA JOISTED BATTEN FLOOR SYSTEM. Concrete subfloor. Generic template
11_ Floor finish and intermediate layer
02_ DPM
03_ Timber battens [400 mm centres]
01_ Subfloor
04_ ≥20 mm Rigid insulation [finishing 16 mm below top of battens]
05_ Warmup Tectora diffusion plates
08_ 1 mm Polyethylene foam or equivalent
06_ Warmup16 mm pipework
09_ Timber floor deck
07_ Warmup 40/60 Clypso Clip* [between plates and on turns]
10_ Floor sensor (conduit recommended)**
* Pipes need to be clipped to the insulation on turns
** Channel a groove in the floor deck to allow for floor sensor installation
REV DATE DESCRIPTION DR CH
DRAWING ISSUE STATUS
PROJECT
PROJECT MANAGER DRAWN CHECKED
DATE SCALE REVISION
© This drawing is confidential and may not be used, copied ordisclosed to anyone without permission of Warmup Plc. The Copyrightof these drawings remain the property of Warmup Plc.
Do not scale from drawings, all dimensions to be checked on site.
The Warmup word and associated logos are trade marks. © WarmupPlc. 2010 - Regd. TM Nos. 1257757, 4409926, 5265707. E & OE. Registeredin England No. 2955213.
DRAWING NO
CAD FILE
WARMUP PLC, 704 Tudor Estate, Abbey Road, London,NW10 7UW Tel 0845 034 8270 Fax 0208 453 6869
[email protected] [email protected] www.warmup.co.uk
TITLE
DETAILED SECTION
CONSTRUCTION 01
TECTORA JOISTED BATTEN FLOOR SYSTEMCONCRETE SUBFLOOR
GENERIC TEMPLATE
01.03.2017
20170228-H-TECTORA-DET SECTIONS.DWG
AA
1:50@A3
AW
WARMUP TECTORA JOISTED BATTEN FLOOR SYSTEM. Concrete subfloor. Tiled floor
11_ Flexible tile adhesive
12_ Tiled floor finish
* Pipes need to be clipped to the insulation on turns
** Channel a groove in the floor deck to allow for floor sensor installation
02_ DPM
03_ Timber battens [400 mm centres]
01_ Subfloor
04_ ≥20 mm Rigid insulation [finishing 16 mm below top of battens]
05_ Warmup Tectora diffusion plates
08_ 1 mm Polyethylene foam or equivalent
06_ Warmup16 mm pipework
09_ Timber floor deck
07_ Warmup 40/60 Clypso Clip* [between plates and on turns]
10_ Floor sensor (conduit recommended)**
REV DATE DESCRIPTION DR CH
DRAWING ISSUE STATUS
PROJECT
PROJECT MANAGER DRAWN CHECKED
DATE SCALE REVISION
© This drawing is confidential and may not be used, copied ordisclosed to anyone without permission of Warmup Plc. The Copyrightof these drawings remain the property of Warmup Plc.
Do not scale from drawings, all dimensions to be checked on site.
The Warmup word and associated logos are trade marks. © WarmupPlc. 2010 - Regd. TM Nos. 1257757, 4409926, 5265707. E & OE. Registeredin England No. 2955213.
DRAWING NO
CAD FILE
WARMUP PLC, 704 Tudor Estate, Abbey Road, London,NW10 7UW Tel 0845 034 8270 Fax 0208 453 6869
[email protected] [email protected] www.warmup.co.uk
TITLE
DETAILED SECTION
CONSTRUCTION 02
TECTORA JOISTED BATTEN FLOOR SYSTEMCONCRETE SUBFLOOR
TILED FLOOR
01.03.2017
20170228-H-TECTORA-DET SECTIONS.DWG
AA
1:50@A3
AW
WARMUP TECTORA JOISTED BATTEN FLOOR SYSTEM. Concrete subfloor. Wood / Laminate floor - floating
11_ UFH compatible underlay
12_ Floating timber floor finish
* Pipes need to be clipped to the insulation on turns
** Channel a groove in the floor deck to allow for floor sensor installation
02_ DPM
03_ Timber battens [400 mm centres]
01_ Subfloor
04_ ≥20 mm Rigid insulation [finishing 16 mm below top of battens]
05_ Warmup Tectora diffusion plates
08_ 1 mm Polyethylene foam or equivalent
06_ Warmup16 mm pipework
09_ Timber floor deck
07_ Warmup 40/60 Clypso Clip* [between plates and on turns]
10_ Floor sensor (conduit recommended)**
REV DATE DESCRIPTION DR CH
DRAWING ISSUE STATUS
PROJECT
PROJECT MANAGER DRAWN CHECKED
DATE SCALE REVISION
© This drawing is confidential and may not be used, copied ordisclosed to anyone without permission of Warmup Plc. The Copyrightof these drawings remain the property of Warmup Plc.
Do not scale from drawings, all dimensions to be checked on site.
The Warmup word and associated logos are trade marks. © WarmupPlc. 2010 - Regd. TM Nos. 1257757, 4409926, 5265707. E & OE. Registeredin England No. 2955213.
DRAWING NO
CAD FILE
WARMUP PLC, 704 Tudor Estate, Abbey Road, London,NW10 7UW Tel 0845 034 8270 Fax 0208 453 6869
[email protected] [email protected] www.warmup.co.uk
TITLE
DETAILED SECTION
CONSTRUCTION 03
TECTORA JOISTED BATTEN FLOOR SYSTEMCONCRETE SUBFLOOR
WOOD / LAMINATE FLOOR - FLOATING
01.03.2017
20170228-H-TECTORA-DET SECTIONS.DWG
AA
1:50@A3
AW
WARMUP TECTORA JOISTED BATTEN FLOOR SYSTEM. Concrete subfloor. Wood / Laminate floor - glued
04_ ≥20 mm Rigid insulation [finishing 16 mm below top of battens]
11_ UFH compatible floor adhesive
12_ Timber floor finish
* Pipes need to be clipped to the insulation on turns
** Channel a groove in the floor deck to allow for floor sensor installation
02_ DPM
03_ Timber battens [400 mm centres]
01_ Subfloor
04_ ≥20 mm Rigid insulation [finishing 16 mm below top of battens]
05_ Warmup Tectora diffusion plates
08_ 1 mm Polyethylene foam or equivalent
06_ Warmup16 mm pipework
09_ Timber floor deck
07_ Warmup 40/60 Clypso Clip* [between plates and on turns]
10_ Floor sensor (conduit recommended)**
REV DATE DESCRIPTION DR CH
DRAWING ISSUE STATUS
PROJECT
PROJECT MANAGER DRAWN CHECKED
DATE SCALE REVISION
© This drawing is confidential and may not be used, copied ordisclosed to anyone without permission of Warmup Plc. The Copyrightof these drawings remain the property of Warmup Plc.
Do not scale from drawings, all dimensions to be checked on site.
The Warmup word and associated logos are trade marks. © WarmupPlc. 2010 - Regd. TM Nos. 1257757, 4409926, 5265707. E & OE. Registeredin England No. 2955213.
DRAWING NO
CAD FILE
WARMUP PLC, 704 Tudor Estate, Abbey Road, London,NW10 7UW Tel 0845 034 8270 Fax 0208 453 6869
[email protected] [email protected] www.warmup.co.uk
TITLE
DETAILED SECTION
CONSTRUCTION 04
TECTORA JOISTED BATTEN FLOOR SYSTEMCONCRETE SUBFLOOR
WOOD / LAMINATE FLOOR - GLUED
01.03.2017
20170228-H-TECTORA-DET SECTIONS.DWG
AA
1:50@A3
AW
WARMUP TECTORA JOISTED BATTEN FLOOR SYSTEM. Concrete subfloor. Wood / Laminate floor -screwed / nailed
02_ DPM
03_ Timber battens [400 mm centres]
01_ Subfloor
04_ ≥20 mm Rigid insulation [finishing 16 mm below top of battens]
05_ Warmup Tectora diffusion plates
09_ 1 mm Polyethylene foam or equivalent
06_ Warmup16 mm pipework
10_ Timber floor finish
* Pipes need to be clipped to the insulation on turns
** Floor sensor should be placed in a notch, filled with caulk/adhesive, in the batten with the diffuser plate trimmed back 10-15mm.
08_ Floor sensor (conduit recommended)**
07_ Warmup 40/60 Clypso Clip* [between plates and on turns]
REV DATE DESCRIPTION DR CH
DRAWING ISSUE STATUS
PROJECT
PROJECT MANAGER DRAWN CHECKED
DATE SCALE REVISION
© This drawing is confidential and may not be used, copied ordisclosed to anyone without permission of Warmup Plc. The Copyrightof these drawings remain the property of Warmup Plc.
Do not scale from drawings, all dimensions to be checked on site.
The Warmup word and associated logos are trade marks. © WarmupPlc. 2010 - Regd. TM Nos. 1257757, 4409926, 5265707. E & OE. Registeredin England No. 2955213.
DRAWING NO
CAD FILE
WARMUP PLC, 704 Tudor Estate, Abbey Road, London,NW10 7UW Tel 0845 034 8270 Fax 0208 453 6869
[email protected] [email protected] www.warmup.co.uk
TITLE
DETAILED SECTION
CONSTRUCTION 05
TECTORA JOISTED BATTEN FLOOR SYSTEMCONCRETE SUBFLOOR
WOOD/LAMINATE FLOOR-SCREWED/NAILED
01.03.2017
20170228-H-TECTORA-DET SECTIONS.DWG
AA
1:50@A3
AW
WARMUP TECTORA JOISTED BATTEN FLOOR SYSTEM. Concrete subfloor. Vinyl floor - floating
12_ UFH compatible underlay
13_ Floating vinyl floor finish
11_ 2-3 mm smoothing compound
* Pipes need to be clipped to the insulation on turns
** Channel a groove in the floor deck to allow for floor sensor installation
02_ DPM
03_ Timber battens [400 mm centres]
01_ Subfloor
04_ ≥20 mm Rigid insulation [finishing 16 mm below top of battens]
05_ Warmup Tectora diffusion plates
08_ 1 mm Polyethylene foam or equivalent
06_ Warmup16 mm pipework
09_ Timber floor deck
07_ Warmup 40/60 Clypso Clip* [between plates and on turns]
10_ Floor sensor (conduit recommended)**
REV DATE DESCRIPTION DR CH
DRAWING ISSUE STATUS
PROJECT
PROJECT MANAGER DRAWN CHECKED
DATE SCALE REVISION
© This drawing is confidential and may not be used, copied ordisclosed to anyone without permission of Warmup Plc. The Copyrightof these drawings remain the property of Warmup Plc.
Do not scale from drawings, all dimensions to be checked on site.
The Warmup word and associated logos are trade marks. © WarmupPlc. 2010 - Regd. TM Nos. 1257757, 4409926, 5265707. E & OE. Registeredin England No. 2955213.
DRAWING NO
CAD FILE
WARMUP PLC, 704 Tudor Estate, Abbey Road, London,NW10 7UW Tel 0845 034 8270 Fax 0208 453 6869
[email protected] [email protected] www.warmup.co.uk
TITLE
DETAILED SECTION
CONSTRUCTION 06
TECTORA JOISTED BATTEN FLOOR SYSTEMCONCRETE SUBFLOOR
VINYL FLOOR - FLOATING
01.03.2017
20170228-H-TECTORA-DET SECTIONS.DWG
AA
1:50@A3
AW
12_ UFH compatible vinyl floor adhesive
13_ Vinyl floor finish
11_ 2-3 mm smoothing compound
WARMUP TECTORA JOISTED BATTEN FLOOR SYSTEM. Concrete subfloor. Vinyl floor - glued* Pipes need to be clipped to the insulation on turns
** Channel a groove in the floor deck to allow for floor sensor installation
02_ DPM
03_ Timber battens [400 mm centres]
01_ Subfloor
04_ ≥20 mm Rigid insulation [finishing 16 mm below top of battens]
05_ Warmup Tectora diffusion plates
08_ 1 mm Polyethylene foam or equivalent
06_ Warmup16 mm pipework
09_ Timber floor deck
07_ Warmup 40/60 Clypso Clip* [between plates and on turns]
10_ Floor sensor (conduit recommended)**
REV DATE DESCRIPTION DR CH
DRAWING ISSUE STATUS
PROJECT
PROJECT MANAGER DRAWN CHECKED
DATE SCALE REVISION
© This drawing is confidential and may not be used, copied ordisclosed to anyone without permission of Warmup Plc. The Copyrightof these drawings remain the property of Warmup Plc.
Do not scale from drawings, all dimensions to be checked on site.
The Warmup word and associated logos are trade marks. © WarmupPlc. 2010 - Regd. TM Nos. 1257757, 4409926, 5265707. E & OE. Registeredin England No. 2955213.
DRAWING NO
CAD FILE
WARMUP PLC, 704 Tudor Estate, Abbey Road, London,NW10 7UW Tel 0845 034 8270 Fax 0208 453 6869
[email protected] [email protected] www.warmup.co.uk
TITLE
DETAILED SECTION
CONSTRUCTION 07
TECTORA JOISTED BATTEN FLOOR SYSTEMCONCRETE SUBFLOOR
VINYL FLOOR - GLUED
01.03.2017
20170228-H-TECTORA-DET SECTIONS.DWG
AA
1:50@A3
AW
11_ UFH compatible underlay
12_ Carpet floor finish
WARMUP TECTORA JOISTED BATTEN FLOOR SYSTEM. Concrete subfloor. Carpet floor* Pipes need to be clipped to the insulation on turns
** Channel a groove in the floor deck to allow for floor sensor installation
02_ DPM
03_ Timber battens [400 mm centres]
01_ Subfloor
04_ ≥20 mm Rigid insulation [finishing 16 mm below top of battens]
05_ Warmup Tectora diffusion plates
08_ 1 mm Polyethylene foam or equivalent
06_ Warmup16 mm pipework
09_ Timber floor deck
07_ Warmup 40/60 Clypso Clip* [between plates and on turns]
10_ Floor sensor (conduit recommended)**
REV DATE DESCRIPTION DR CH
DRAWING ISSUE STATUS
PROJECT
PROJECT MANAGER DRAWN CHECKED
DATE SCALE REVISION
© This drawing is confidential and may not be used, copied ordisclosed to anyone without permission of Warmup Plc. The Copyrightof these drawings remain the property of Warmup Plc.
Do not scale from drawings, all dimensions to be checked on site.
The Warmup word and associated logos are trade marks. © WarmupPlc. 2010 - Regd. TM Nos. 1257757, 4409926, 5265707. E & OE. Registeredin England No. 2955213.
DRAWING NO
CAD FILE
WARMUP PLC, 704 Tudor Estate, Abbey Road, London,NW10 7UW Tel 0845 034 8270 Fax 0208 453 6869
[email protected] [email protected] www.warmup.co.uk
TITLE
DETAILED SECTION
CONSTRUCTION 08
TECTORA JOISTED BATTEN FLOOR SYSTEMCONCRETE SUBFLOOR
CARPET FLOOR
01.03.2017
20170228-H-TECTORA-DET SECTIONS.DWG
AA
1:50@A3
AW