construction specifications - gcccd 019... · 2020. 11. 27. · d. visual requirements: do not cut...

78
CONSTRUCTION SPECIFICATIONS B14.019 Grossmont College Trophy Cases 8800 Grossmont College Dr, El Cajon, CA 92020 June 09, 2014 Prepared by: Di Donato Associates 3939 First Avenue, Suite 100 San Diego, CA 92103 09 June 2014 Grossmont College B14.019 Trophy Cases

Upload: others

Post on 24-Jan-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

CONSTRUCTION SPECIFICATIONS

B14.019 Grossmont College

Trophy Cases

8800 Grossmont College Dr, El Cajon, CA 92020

June 09, 2014

Prepared by:

Di Donato Associates 3939 First Avenue, Suite 100

San Diego, CA 92103

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 2: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

TABLE OF CONTENTS

TABLE OF CONTENTS

DIVISION 1 - GENERAL REQUIREMENTS

01731 Cutting and Patching

[Additional sections by GAFCON]

DIVISION 2 - SITE CONSTRUCTION

02221 Building Demolition and Site Preparation

DIVISION 3 - CONCRETE

NOT USED

DIVISION 4 - MASONRY

NOT USED

DIVISION 5 - METALS

NOT USED

DIVISION 6 - WOOD AND PLASTICS

06100 Rough Carpentry

DIVISION 7 - THERMAL AND MOISTURE PROTECTION

NOT USED

DIVISION 8 - DOORS AND WINDOWS

NOT USED

DIVISION 9 - FINISHES

09250 Gypsum Board

09900 Paints

DIVISION 10 - SPECIALTIES

NOT USED

DIVISION 11 - EQUIPMENT

NOT USED

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 3: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

TABLE OF CONTENTS

DIVISION 12 - FURNISHINGS

NOT USED

DIVISION 13 - SPECIAL CONSTRUCTION

NOT USED

DIVISION 14 - CONVEYING SYSTEMS

NOT USED

DIVISION 15 – MECHANICAL

NOT USED

DIVISION 16 - ELECTRICAL

16100 General Provisions

16300 Basic Materials and Methods

16400 Wiring Methods, Raceways, and Conductors

END OF TABLE OF CONTENTS

***

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 4: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

CUTTING AND PATCHING 01731-1

SECTION 01731 - CUTTING AND PATCHING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes procedural requirements for cutting and patching.

B. Related Sections include the following: 1. Divisions 2 through 16 Sections for specific requirements and limitations

applicable to cutting and patching individual parts of the Work. 2. Division 7 Section "Through-Penetration Firestop Systems" for patching fire-rated

construction.

1.3 DEFINITIONS

A. Cutting: Removal of in-place construction necessary to permit installation or performance of other Work.

B. Patching: Fitting and repair work required to restore surfaces to original conditions after installation of other Work.

1.4 SUBMITTALS

A. Cutting and Patching Proposal: Submit a proposal describing procedures at least 10 days before the time cutting and patching will be performed, requesting approval to proceed. Include the following information: 1. Extent: Describe cutting and patching, show how they will be performed, and

indicate why they cannot be avoided. 2. Changes to In-Place Construction: Describe anticipated results. Include

changes to structural elements and operating components as well as changes in building's appearance and other significant visual elements.

3. Products: List products to be used and firms or entities that will perform the Work.

4. Dates: Indicate when cutting and patching will be performed. 5. Utility Services and Mechanical/Electrical Systems: List services/systems that

cutting and patching procedures will disturb or affect. List services/systems that will be relocated and those that will be temporarily out of service. Indicate how long services/systems will be disrupted.

6. Structural Elements: Where cutting and patching involve adding reinforcement to structural elements, submit details and engineering calculations showing integration of reinforcement with original structure.

7. Architect's and Construction Manager's Approval: Obtain approval of cutting and patching proposal before cutting and patching. Approval does not waive right to later require removal and replacement of unsatisfactory work.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 5: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

CUTTING AND PATCHING 01731-2

1.5 QUALITY ASSURANCE

A. Structural Elements: Do not cut and patch structural elements in a manner that could change their load-carrying capacity or load-deflection ratio.

B. Operational Elements: Do not cut and patch operating elements and related components in a manner that results in reducing their capacity to perform as intended or that results in increased maintenance or decreased operational life or safety. Operating elements include the following: 1. Primary operational systems and equipment. 2. Air or smoke barriers. 3. Fire-suppression systems. 4. Mechanical systems piping and ducts. 5. Control systems. 6. Communication systems. 7. Conveying systems. 8. Electrical wiring systems. 9. Operating systems of special construction in Division 13 Sections.

C. Miscellaneous Elements: Do not cut and patch miscellaneous elements or related components in a manner that could change their load-carrying capacity, that results in reducing their capacity to perform as intended, or that results in increased maintenance or decreased operational life or safety. Miscellaneous elements include the following: 1. Water, moisture, or vapor barriers. 2. Membranes and flashings. 3. Equipment supports. 4. Piping, ductwork, vessels, and equipment. 5. Noise- and vibration-control elements and systems.

D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and patching. Do not cut and patch construction exposed on the exterior or in occupied spaces in a manner that would, in Architect's opinion, reduce the building's aesthetic qualities. Remove and replace construction that has been cut and patched in a visually unsatisfactory manner.

E. Cutting and Patching Conference: Before proceeding, meet at Project site with parties involved in cutting and patching, including mechanical and electrical trades. Review areas of potential interference and conflict. Coordinate procedures and resolve potential conflicts before proceeding.

1.6 WARRANTY

A. Existing Warranties: Remove, replace, patch, and repair materials and surfaces cut or damaged during cutting and patching operations, by methods and with materials so as not to void existing warranties.

PART 2 - PRODUCTS

2.1 MATERIALS

A. General: Comply with requirements specified in other Sections.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 6: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

CUTTING AND PATCHING 01731-3

B. In-Place Materials: Use materials identical to in-place materials. For exposed surfaces, use materials that visually match in-place adjacent surfaces to the fullest extent possible. 1. If identical materials are unavailable or cannot be used, use materials that, when

installed, will match the visual and functional performance of in-place materials.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine surfaces to be cut and patched and conditions under which cutting and patching are to be performed. 1. Compatibility: Before patching, verify compatibility with and suitability of

substrates, including compatibility with in-place finishes or primers. 2. Proceed with installation only after unsafe or unsatisfactory conditions have been

corrected.

3.2 PREPARATION

A. Temporary Support: Provide temporary support of Work to be cut.

B. Protection: Protect in-place construction during cutting and patching to prevent damage. Provide protection from adverse weather conditions for portions of Project that might be exposed during cutting and patching operations.

C. Adjoining Areas: Avoid interference with use of adjoining areas or interruption of free passage to adjoining areas.

3.3 PERFORMANCE

A. General: Employ skilled workers to perform cutting and patching. Proceed with cutting and patching at the earliest feasible time, and complete without delay. 1. Cut in-place construction to provide for installation of other components or

performance of other construction, and subsequently patch as required to restore surfaces to their original condition.

B. Cutting: Cut in-place construction by sawing, drilling, breaking, chipping, grinding, and similar operations, including excavation, using methods least likely to damage elements retained or adjoining construction. If possible, review proposed procedures with original Installer; comply with original Installer's written recommendations. 1. In general, use hand or small power tools designed for sawing and grinding, not

hammering and chopping. Cut holes and slots as small as possible, neatly to size required, and with minimum disturbance of adjacent surfaces. Temporarily cover openings when not in use.

2. Finished Surfaces: Cut or drill from the exposed or finished side into concealed surfaces.

3. Concrete and Masonry: Cut using a cutting machine, such as an abrasive saw or a diamond-core drill.

4. Excavating and Backfilling: Comply with requirements in applicable Division 2 Sections where required by cutting and patching operations.

5. Mechanical and Electrical Services: Cut off pipe or conduit in walls or partitions to be removed. Cap, valve, or plug and seal remaining portion of pipe or conduit to prevent entrance of moisture or other foreign matter after cutting.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 7: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

CUTTING AND PATCHING 01731-4

6. Proceed with patching after construction operations requiring cutting are complete.

C. Patching: Patch construction by filling, repairing, refinishing, closing up, and similar operations following performance of other Work. Patch with durable seams that are as invisible as possible. Provide materials and comply with installation requirements specified in other Sections. 1. Inspection: Where feasible, test and inspect patched areas after completion to

demonstrate integrity of installation. 2. Exposed Finishes: Restore exposed finishes of patched areas and extend finish

restoration into retained adjoining construction in a manner that will eliminate evidence of patching and refinishing. a. Clean piping, conduit, and similar features before applying paint or other

finishing materials. b. Restore damaged pipe covering to its original condition.

3. Floors and Walls: Where walls or partitions that are removed extend one finished area into another, patch and repair floor and wall surfaces in the new space. Provide an even surface of uniform finish, color, texture, and appearance. Remove in-place floor and wall coverings and replace with new materials, if necessary, to achieve uniform color and appearance. a. Where patching occurs in a painted surface, apply primer and intermediate

paint coats over the patch and apply final paint coat over entire unbroken surface containing the patch. Provide additional coats until patch blends with adjacent surfaces.

4. Ceilings: Patch, repair, or rehang in-place ceilings as necessary to provide an even-plane surface of uniform appearance.

5. Exterior Building Enclosure: Patch components in a manner that restores enclosure to a weathertight condition.

D. Cleaning: Clean areas and spaces where cutting and patching are performed. Completely remove paint, mortar, oils, putty, and similar materials.

END OF SECTION 01731

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 8: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

CUTTING AND PATCHING 01731-1

SECTION 01731 - CUTTING AND PATCHING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes procedural requirements for cutting and patching.

B. Related Sections include the following: 1. Divisions 2 through 16 Sections for specific requirements and limitations

applicable to cutting and patching individual parts of the Work. 2. Division 7 Section "Through-Penetration Firestop Systems" for patching fire-rated

construction.

1.3 DEFINITIONS

A. Cutting: Removal of in-place construction necessary to permit installation or performance of other Work.

B. Patching: Fitting and repair work required to restore surfaces to original conditions after installation of other Work.

1.4 SUBMITTALS

A. Cutting and Patching Proposal: Submit a proposal describing procedures at least 10 days before the time cutting and patching will be performed, requesting approval to proceed. Include the following information: 1. Extent: Describe cutting and patching, show how they will be performed, and

indicate why they cannot be avoided. 2. Changes to In-Place Construction: Describe anticipated results. Include

changes to structural elements and operating components as well as changes in building's appearance and other significant visual elements.

3. Products: List products to be used and firms or entities that will perform the Work.

4. Dates: Indicate when cutting and patching will be performed. 5. Utility Services and Mechanical/Electrical Systems: List services/systems that

cutting and patching procedures will disturb or affect. List services/systems that will be relocated and those that will be temporarily out of service. Indicate how long services/systems will be disrupted.

6. Structural Elements: Where cutting and patching involve adding reinforcement to structural elements, submit details and engineering calculations showing integration of reinforcement with original structure.

7. Architect's and Construction Manager's Approval: Obtain approval of cutting and patching proposal before cutting and patching. Approval does not waive right to later require removal and replacement of unsatisfactory work.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 9: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

CUTTING AND PATCHING 01731-2

1.5 QUALITY ASSURANCE

A. Structural Elements: Do not cut and patch structural elements in a manner that could change their load-carrying capacity or load-deflection ratio.

B. Operational Elements: Do not cut and patch operating elements and related components in a manner that results in reducing their capacity to perform as intended or that results in increased maintenance or decreased operational life or safety. Operating elements include the following: 1. Primary operational systems and equipment. 2. Air or smoke barriers. 3. Fire-suppression systems. 4. Mechanical systems piping and ducts. 5. Control systems. 6. Communication systems. 7. Conveying systems. 8. Electrical wiring systems. 9. Operating systems of special construction in Division 13 Sections.

C. Miscellaneous Elements: Do not cut and patch miscellaneous elements or related components in a manner that could change their load-carrying capacity, that results in reducing their capacity to perform as intended, or that results in increased maintenance or decreased operational life or safety. Miscellaneous elements include the following: 1. Water, moisture, or vapor barriers. 2. Membranes and flashings. 3. Equipment supports. 4. Piping, ductwork, vessels, and equipment. 5. Noise- and vibration-control elements and systems.

D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and patching. Do not cut and patch construction exposed on the exterior or in occupied spaces in a manner that would, in Architect's opinion, reduce the building's aesthetic qualities. Remove and replace construction that has been cut and patched in a visually unsatisfactory manner.

E. Cutting and Patching Conference: Before proceeding, meet at Project site with parties involved in cutting and patching, including mechanical and electrical trades. Review areas of potential interference and conflict. Coordinate procedures and resolve potential conflicts before proceeding.

1.6 WARRANTY

A. Existing Warranties: Remove, replace, patch, and repair materials and surfaces cut or damaged during cutting and patching operations, by methods and with materials so as not to void existing warranties.

PART 2 - PRODUCTS

2.1 MATERIALS

A. General: Comply with requirements specified in other Sections.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 10: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

CUTTING AND PATCHING 01731-3

B. In-Place Materials: Use materials identical to in-place materials. For exposed surfaces, use materials that visually match in-place adjacent surfaces to the fullest extent possible. 1. If identical materials are unavailable or cannot be used, use materials that, when

installed, will match the visual and functional performance of in-place materials.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine surfaces to be cut and patched and conditions under which cutting and patching are to be performed. 1. Compatibility: Before patching, verify compatibility with and suitability of

substrates, including compatibility with in-place finishes or primers. 2. Proceed with installation only after unsafe or unsatisfactory conditions have been

corrected.

3.2 PREPARATION

A. Temporary Support: Provide temporary support of Work to be cut.

B. Protection: Protect in-place construction during cutting and patching to prevent damage. Provide protection from adverse weather conditions for portions of Project that might be exposed during cutting and patching operations.

C. Adjoining Areas: Avoid interference with use of adjoining areas or interruption of free passage to adjoining areas.

3.3 PERFORMANCE

A. General: Employ skilled workers to perform cutting and patching. Proceed with cutting and patching at the earliest feasible time, and complete without delay. 1. Cut in-place construction to provide for installation of other components or

performance of other construction, and subsequently patch as required to restore surfaces to their original condition.

B. Cutting: Cut in-place construction by sawing, drilling, breaking, chipping, grinding, and similar operations, including excavation, using methods least likely to damage elements retained or adjoining construction. If possible, review proposed procedures with original Installer; comply with original Installer's written recommendations. 1. In general, use hand or small power tools designed for sawing and grinding, not

hammering and chopping. Cut holes and slots as small as possible, neatly to size required, and with minimum disturbance of adjacent surfaces. Temporarily cover openings when not in use.

2. Finished Surfaces: Cut or drill from the exposed or finished side into concealed surfaces.

3. Concrete and Masonry: Cut using a cutting machine, such as an abrasive saw or a diamond-core drill.

4. Excavating and Backfilling: Comply with requirements in applicable Division 2 Sections where required by cutting and patching operations.

5. Mechanical and Electrical Services: Cut off pipe or conduit in walls or partitions to be removed. Cap, valve, or plug and seal remaining portion of pipe or conduit to prevent entrance of moisture or other foreign matter after cutting.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 11: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

CUTTING AND PATCHING 01731-4

6. Proceed with patching after construction operations requiring cutting are complete.

C. Patching: Patch construction by filling, repairing, refinishing, closing up, and similar operations following performance of other Work. Patch with durable seams that are as invisible as possible. Provide materials and comply with installation requirements specified in other Sections. 1. Inspection: Where feasible, test and inspect patched areas after completion to

demonstrate integrity of installation. 2. Exposed Finishes: Restore exposed finishes of patched areas and extend finish

restoration into retained adjoining construction in a manner that will eliminate evidence of patching and refinishing. a. Clean piping, conduit, and similar features before applying paint or other

finishing materials. b. Restore damaged pipe covering to its original condition.

3. Floors and Walls: Where walls or partitions that are removed extend one finished area into another, patch and repair floor and wall surfaces in the new space. Provide an even surface of uniform finish, color, texture, and appearance. Remove in-place floor and wall coverings and replace with new materials, if necessary, to achieve uniform color and appearance. a. Where patching occurs in a painted surface, apply primer and intermediate

paint coats over the patch and apply final paint coat over entire unbroken surface containing the patch. Provide additional coats until patch blends with adjacent surfaces.

4. Ceilings: Patch, repair, or rehang in-place ceilings as necessary to provide an even-plane surface of uniform appearance.

5. Exterior Building Enclosure: Patch components in a manner that restores enclosure to a weathertight condition.

D. Cleaning: Clean areas and spaces where cutting and patching are performed. Completely remove paint, mortar, oils, putty, and similar materials.

END OF SECTION 01731

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 12: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

BUILDING DEMOLITION & SITE PREP 02221-1

SECTION 02221 – BUILDING DEMOLITION AND SITE PREPARATION

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes the following: 1. Demolition and removal of portions of buildings and structures. 2. Demolition and removal of site improvements adjacent to a building or structure

to be demolished. 3. Disconnecting, capping or sealing, and removing site utilities. 4. Protecting existing vegetation to remain. 5. Clearing and grubbing. 6. Temporary erosion and sedimentation control.

B. Related Sections include the following: 1. Division 1, Sections for Summary, Work Restrictions, Construction Progress

Documentation, Photographic Documentation, Temporary Facilities and Controls, and Execution Requirements, for all pertinent requirements.

2. Division 2, for all pertinent requirements. 3. Division 15 Sections for demolishing or relocating site mechanical items. 4. Division 16 Sections for demolishing or relocating site electrical items.

1.3 DEFINITIONS

A. Remove: Detach items from existing construction and legally dispose of them off-site unless indicated to be removed and salvaged or recycled.

B. Remove and Salvage: Detach items from existing construction and deliver them to Owner.

C. Existing to Remain: Existing items of construction that are not to be removed and that are not otherwise indicated to be removed, removed and salvaged, or recycled.

D. Topsoil: Natural or cultivated surface-soil layer containing organic matter and sand, silt, and clay particles; friable, pervious, and black or a darker shade of brown, gray, or red than underlying subsoil; reasonably free of subsoil, clay lumps, gravel, and other objects more than 2 inches in diameter; and free of subsoil and weeds, roots, toxic materials, or other nonsoil materials.

E. Tree Protection Zone: Area surrounding individual trees or groups of trees to be protected during construction, and defined by the drip line of individual trees or the perimeter drip line of groups of trees, unless otherwise indicated.

1.4 MATERIAL OWNERSHIP

A. Except for stripped topsoil or other materials indicated to remain Owner's property, cleared materials shall become Contractor's property and shall be removed from Project site.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 13: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

BUILDING DEMOLITION & SITE PREP 02221-2

1.5 SUBMITTALS

A. Proposed Environmental-Protection, Dust-Control, and Noise-Control Measures: Submit statement or drawing that indicates the measures proposed for use, proposed locations, and proposed time frame for their operation for District review and approval. Identify options if proposed measures are later determined to be inadequate.

B. Schedule of Building Demolition Activities: Indicate the following: 1. Detailed sequence of demolition and removal work, with starting and ending

dates for each activity. 2. Interruption of utility services. 3. Coordination for shutoff, capping, and continuation of utility services. 4. Locations of temporary protection and means of egress. 5. Coordination of Owner's continuing occupancy of adjacent buildings and partial

use of premises.

C. Inventory: After demolition is complete, submit a list of items that have been removed and salvaged.

D. Pre-demolition Photographs: Show existing trees and conditions of adjoining construction and site improvements, including finish surfaces, which might be misconstrued as damage caused by building demolition operations. Submit to Inspector of Record before Work begins.

E. Post-demolition Photographs: Sufficiently detailed, of existing conditions of trees and plantings, adjoining construction, and site improvements that might be misconstrued as damage caused by site clearing.

1.6 QUALITY ASSURANCE

A. Demolition Firm Qualifications: An experienced firm that has specialized in demolition work similar in material and extent to that indicated for this Project.

B. Regulatory Requirements: Comply with governing EPA notification regulations before beginning demolition. Comply with hauling and disposal regulations of authorities having jurisdiction.

C. Standards: Comply with ANSI A10.6 and NFPA 241.

D. Pre-demolition and Pre-installation Conference: Conduct conference at Project site to comply with requirements in Division 1 Section "Project Management and Coordination."

1.7 PROJECT CONDITIONS

A. Buildings to be demolished will be vacated and their use discontinued before start of Work.

B. Owner will occupy another building immediately adjacent to demolition area. Conduct building demolition so Owner's operations will not be disrupted. 1. Provide not less than 72 hours' notice to Owner of activities that will affect

Owner's operations. 2. Maintain access to existing walkways, exits, and other adjacent occupied or used

facilities.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 14: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

BUILDING DEMOLITION & SITE PREP 02221-3

a. Do not close or obstruct walkways, exits, or other occupied or used facilities without written permission from authorities having jurisdiction.

C. Owner assumes no responsibility for buildings and structures to be demolished. 1. Conditions existing at time of inspection for bidding purpose will be maintained by

Owner as far as practical. 2. Before building demolition, Owner will remove all salvaged items.

D. Storage or sale of removed items or materials on-site is not permitted.

E. Traffic: Minimize interference with adjoining roads, streets, walks, and other adjacent occupied or used facilities during site-clearing operations. 1. Do not close or obstruct streets, walks, or other adjacent occupied or used

facilities without permission from Owner and authorities having jurisdiction. 2. Provide alternate routes around closed or obstructed traffic ways if required by

authorities having jurisdiction.

F. Salvable Improvements: Carefully remove items indicated to be salvaged and store on Owner's premises where indicated.

G. Utility Locator Service: Notify utility locator service for area where Project is located before site clearing.

H. Do not commence site clearing operations until temporary erosion and sedimentation control measures are in place.

1.8 COORDINATION

A. Arrange demolition schedule so as not to interfere with Owner's on-site operations.

B. Coordinate utility outages to not disrupt campus operations. Shut downs and cross-overs are to take place on weekends as arranged with campus representatives.

PART 2 - PRODUCTS

2.1 SOIL MATERIALS

A. Satisfactory Soils: Comply with requirements in Division 2 Section "Earthwork." 1. Obtain approved borrow soil materials off-site when satisfactory soil materials are

not available on-site.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Survey existing conditions and correlate with requirements indicated to determine extent of building demolition required.

B. When unanticipated mechanical, electrical, or structural elements are encountered, investigate and measure the nature and extent of the element. Promptly submit a written report to Inspector of Record.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 15: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

BUILDING DEMOLITION & SITE PREP 02221-4

3.2 PREPARATION

A. Existing Utilities: Locate, identify, disconnect, and seal or cap off indicated utilities serving buildings and structures to be demolished. 1. Owner will arrange to shut off indicated utilities when requested by Contractor. 2. Arrange to shut off indicated utilities with utility companies. 3. If utility services are required to be removed, relocated, or abandoned, before

proceeding with building demolition provide temporary utilities that bypass buildings and structures to be demolished and that maintain continuity of service to other buildings and structures.

4. Cut off pipe or conduit a minimum of 24 inches below grade. Cap, valve, or plug and seal remaining portion of pipe or conduit after bypassing.

B. Do not start demolition work until utility disconnecting and sealing have been completed and verified in writing.

C. Removed and Salvaged Items: Comply with the following: 1. Clean salvaged items of dirt and demolition debris. 2. Pack or crate items after cleaning. Identify contents of containers. 3. Store items in a secure area until delivery to Owner. 4. Transport items to Owner's storage area designated by Owner. 5. Protect items from damage during transport and storage.

D. Protect and maintain benchmarks and survey control points from disturbance during construction.

E. Temporary Partitions: 1. Provide substantial construction designed by the contractor to provide effective

protection as required. a. Exterior closures: Weatherproof, constructed to prevent water leakage,

insulated to prevent excessive heat loss or gain to occupied areas, and sealed to prevent excessive air filtration.

2. Construct Temporary partitions in a manner at least equal to the following (or superior, if necessary to provide effective protection specified): a. Wood studs covered with plywood sheathing. b. Gypsum-board surfaces adjacent to occupied areas, with joints taped.

3. Equip partitions with doors where access is required.

F. Structural Support: 1. Construct and maintain shoring bracing, and supports as necessary to ensure

the stability of structures. 2. Increase or add new supports as required by the progress of the work.

G. Damages: Without cost to the owner and without delay, repair any damages caused to facilities to remain.

H. Locate and clearly flag trees and vegetation to remain or to be relocated.

I. Protect existing site improvements to remain from damage during construction. 1. Restore damaged improvements to their original condition, as acceptable to

Owner.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 16: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

BUILDING DEMOLITION & SITE PREP 02221-5

3.3 TEMPORARY EROSION AND SEDIMENTATION CONTROL

A. Provide temporary erosion and sedimentation control measures to prevent soil erosion and discharge of soil-bearing water runoff or airborne dust to adjacent properties and walkways, according to requirements of authorities having jurisdiction.

B. Inspect, repair, and maintain erosion and sedimentation control measures during construction until permanent vegetation has been established.

C. Remove erosion and sedimentation controls and restore and stabilize areas disturbed during removal.

3.4 PROTECTION

A. Existing Facilities: Protect adjacent walkways, loading docks, building entries, and other building facilities during demolition operations.

B. Existing Items to Remain: Protect construction indicated to remain against damage and soiling during demolition.

C. Existing Utilities: Maintain utility services indicated to remain and protect them against damage during demolition operations. 1. Do not interrupt existing utilities serving adjacent occupied or operating facilities

unless authorized in writing by Owner and authorities having jurisdiction. 2. Provide temporary services during interruptions to existing utilities, as acceptable

to Owner and to authorities having jurisdiction. a. Provide at least 72 hours' notice to Owner if shutdown of service is required

during changeover.

D. Temporary Protection: Erect temporary protection, such as walks, fences, railings, canopies, and covered passageways, where required by authorities having jurisdiction and as required for pedestrian safety. Comply with requirements in Division 1 Section "Temporary Facilities and Controls." 1. Protect existing site improvements, appurtenances, and landscaping to remain. 2. Erect a plainly visible fence around drip line of individual trees or around

perimeter drip line of groups of trees to remain. 3. Provide temporary barricades and other protection required to prevent injury to

people and damage to adjacent buildings and facilities to remain. 4. Provide protection to ensure safe passage of people around building demolition

area and to and from occupied portions of adjacent buildings and structures. 5. Erect and maintain dustproof partitions and temporary enclosures to limit dust

and dirt migration and to separate areas from fumes and noise from occupied portions of adjacent buildings.

3.5 TREE PROTECTION

A. Erect and maintain temporary fencing around tree protection zones before starting site clearing. Remove fence when construction is complete. 1. Do not store construction materials, debris, or excavated material within fenced

area. 2. Do not permit vehicles, equipment, or foot traffic within fenced area. 3. Maintain fenced area free of weeds and trash.

B. Do not excavate within tree protection zones, unless otherwise indicated.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 17: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

BUILDING DEMOLITION & SITE PREP 02221-6

C. Where excavation for new construction is required within tree protection zones, hand clear and excavate to minimize damage to root systems. Use narrow-tine spading forks, comb soil to expose roots, and cleanly cut roots as close to excavation as possible. 1. Cover exposed roots with burlap and water regularly. 2. Temporarily support and protect roots from damage until they are permanently

redirected and covered with soil. 3. Coat cut faces of roots more than 1-1/2 inches in diameter with an emulsified

asphalt or other approved coating formulated for use on damaged plant tissues. 4. Backfill with soil as soon as possible.

3.6 UTILITIES

A. Owner will arrange for disconnecting and sealing indicated utilities that serve existing structures before site clearing, when requested by Contractor. 1. Verify that utilities have been disconnected and capped before proceeding with

site clearing.

B. Locate, identify, disconnect, and seal or cap off utilities indicated to be removed. 1. Arrange with utility companies to shut off indicated utilities. 2. Owner will arrange to shut off indicated utilities when requested by Contractor. 3. Removal of underground utilities is included in Division 2 Sections covering site

utilities

C. Existing Utilities: Do not interrupt utilities serving facilities occupied by Owner or others unless permitted under the following conditions and then only after arranging to provide temporary utility services according to requirements indicated: 1. Notify Architect not less than two days in advance of proposed utility

interruptions. 2. Do not proceed with utility interruptions without Architect's written permission.

D. Remove obstructions, trees, shrubs, grass, and other vegetation to permit installation of new construction. 1. Do not remove trees, shrubs, and other vegetation indicated to remain or to be

relocated. 2. Cut minor roots and branches of trees indicated to remain in a clean and careful

manner where such roots and branches obstruct installation of new construction. 3. Grind stumps and remove roots, obstructions, and debris extending to a depth of

18 inches below exposed sub-grade. 4. Use only hand methods for grubbing within tree protection zone. 5. Chip removed tree branches and dispose of off-site.

E. Fill depressions caused by clearing and grubbing operations with satisfactory soil material unless further excavation or earthwork is indicated. 1. Place fill material in horizontal layers not exceeding a loose depth of 8 inches,

and compact each layer to a density equal to adjacent original ground.

3.7 TOPSOIL STRIPPING

A. Remove sod and grass before stripping topsoil.

B. Strip topsoil to whatever depths are encountered in a manner to prevent intermingling with underlying subsoil or other waste materials.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 18: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

BUILDING DEMOLITION & SITE PREP 02221-7

1. Remove subsoil and non-soil materials from topsoil, including trash, debris, weeds, roots, and other waste materials.

C. Stockpile topsoil materials away from edge of excavations without intermixing with subsoil. Grade and shape stockpiles to drain surface water. Cover to prevent windblown dust. 1. Limit height of topsoil stockpiles to 72 inches. 2. Do not stockpile topsoil within tree protection zones. 3. Dispose of excess topsoil as specified for waste material disposal. 4. Stockpile surplus topsoil to allow for re-spreading deeper topsoil.

3.8 DEMOLITION, GENERAL

A. General: Demolish indicated portions of existing buildings and structures, and site improvements completely. Use methods required to complete the Work within limitations of governing regulations and as follows:

B. Remove: Unless items are otherwise indicated to be reinstalled or salvaged, remove and scrap.

C. Remove and Reinstall: Remove items indicated; clean, service, and otherwise prepare for service; reinstall in the same location (or in the location indicated).

D. Remove and Install New: Remove and dispose of items indicated and install new items in the same location (or in the location indicated).

E. Remove and Salvage: Items indicated to be salvaged will remain the owner's property. Carefully remove and clean items indicated to be salvaged; pack or crate to protect against damage; identify contents of containers; deliver to the locations indicated.

F. Remove and Scrap: Remove and dispose of items indicated. 1. All demolished or removed items and materials shall be considered scrap except

for those indicated to remain, those indicated to be reinstalled, and those indicated to be salvaged.

2. Items of value to the contractor: a. Do not store-removed items on site.

G. Existing to Remain: Construction or items indicated to remain shall be protected against damage during demolition operations. Where practicable, and with the architect's permission, the contractor may elect to remove items to a suitable storage location during demolition and then properly clean and reinstall the items.

H. Perform work in a systematic manner.

I. Demolish and remove existing construction only to the extent required by new construction and as indicated in the contract documents.

J. Perform selective demolition using methods, which are least likely to damage work to remain, and which will provide proper surfaces for patching. At edge of existing concrete or other permanent construction, saw cut the material for a smooth joint.

K. Remove debris daily.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 19: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

BUILDING DEMOLITION & SITE PREP 02221-8

L. Site Access and Temporary Controls: Conduct building demolition and debris-removal operations to ensure minimum interference with roads, streets, walks, walkways, and other adjacent occupied and used facilities. 1. Do not close or obstruct streets, walks, walkways, or other adjacent occupied or

used facilities without permission from Owner and authorities having jurisdiction. Provide alternate routes around closed or obstructed traffic ways if required by authorities having jurisdiction.

2. Use water mist and other suitable methods to limit spread of dust and dirt. Comply with governing environmental-protection regulations. Do not use water when it may damage adjacent construction or create hazardous or objectionable conditions, such as ice, flooding, and pollution.

3.9 DEMOLITION

A. Proceed with demolition of structure systematically, from higher to lower level. Demolish entire structure including foundations as needed.

B. Remove debris from elevated portions by device that will convey debris to grade level in a controlled descent. 1. Remove structural framing members and lower to ground by method suitable to

minimize ground impact or dust generation.

C. Concrete: Cut concrete slabs and walks at junctures with construction indicated to remain, using power-driven saw, then remove concrete between saw cuts.

D. Building Components: Remove doors, windows, door hardware, cabinets, mirrors, chalkboards and marker boards, tackboards, toilet accessories, plumbing fixtures and light fixtures, as whole units, intact and undamaged.

E. Existing Utilities: Demolish and remove existing utilities.

3.10 SITE IMPROVEMENTS

A. Remove existing above- and below-grade improvements as indicated and as necessary to facilitate new construction. 1. Remove existing site walls entirely including foundations.

B. Remove slabs, paving, curbs, gutters, and aggregate base as indicated. 1. Unless existing full-depth joints coincide with line of demolition, neatly saw-cut

length of existing pavement to remain before removing existing pavement. Saw-cut faces vertically.

2. Paint cut ends of steel reinforcement in concrete to remain to prevent corrosion.

3.11 SITE RESTORATION

A. Site Grading: Uniformly rough grade area of demolished construction to a smooth surface, free from irregular surface changes. Provide a smooth transition between adjacent existing grades and new grades.

3.12 REPAIRS

A. General: Promptly repair damage to adjacent construction caused by building demolition operations.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 20: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

BUILDING DEMOLITION & SITE PREP 02221-9

B. Where repairs to existing surfaces are required, patch to produce surfaces suitable for new materials.

C. Where similar new work is not included in the project, perform repairs using approved materials that are appropriate to the repair and, where practicable, are identical to the existing materials being repaired.

D. Restore exposed finishes of patched areas in a manner, which eliminates evidence of repairs. 1. Continuous surfaces: Extend refinish to nearest intersection, with a neat transition

to adjacent surfaces. 2. Assemblies: Refinish entire unit. 3. Painted piping, conduit, and duct: Clean and repaint.

3.13 RECYCLING DEMOLISHED MATERIALS

A. General: Separate recyclable demolished materials from other demolished materials to the maximum extent possible. Separate recyclable materials by type. 1. Provide containers or other storage method approved by District for controlling

recyclable materials until they are removed from Project site. 2. Stockpile materials away from demolition area. Do not store within drip line of

remaining trees. 3. Store components off the ground and protect from the weather. 4. Transport recyclable materials off Owner's property and legally dispose of them.

B. Recycling Incentives: Revenues, savings, rebates, tax credits, and other incentives received for recycling building demolition materials shall accrue to Contractor.

C. Asphalt: Break up and transport asphalt to asphalt recycling facility.

D. Concrete: Remove reinforcement and other metals from concrete and sort with other metals. Pulverize concrete to maximum 1-1/2-inch size.

E. Wood Materials: Sort and stack members according to size, type, and length. Separate dimensional and engineered lumber, panel products, and treated wood materials.

F. Roofing: Separate organic and glass-fiber shingles and felts. Remove nails, staples, and accessories.

G. Doors and Hardware: Brace open end of door frames. Except for removing door closers, leave door hardware attached to doors.

H. Carpet: Store clean, dry carpet in a closed container or trailer provided by Carpet Reclamation Agency.

I. Equipment: Drain tanks, piping, and fixtures. Seal openings with caps or plugs.

J. Piping: Reduce piping to straight lengths and store by type and size. Separate supports, hangers, valves, sprinkler heads, and other components by type and size.

K. Lighting Fixtures: Separate lamps by type and protect from breakage.

L. Electrical Devices: Separate switches, receptacles, switchgear, transformers, meters, panel boards, circuit breakers, and other devices by type.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 21: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

BUILDING DEMOLITION & SITE PREP 02221-10

M. Conduit: Reduce conduit to straight lengths and store by type and size.

3.14 DISPOSAL OF DEMOLISHED MATERIALS

A. General: Except for items or materials indicated to be recycled, reused, salvaged, reinstalled, or otherwise indicated to remain Owner's property, remove demolished materials from Project site and legally dispose of them in an EPA-approved landfill. 1. Do not allow demolished materials to accumulate on-site. 2. Remove and transport debris in a manner that will prevent spillage on adjacent

surfaces and areas.

B. Burning: Do not burn demolished materials.

C. Disposal: Remove surplus soil material, unsuitable topsoil, obstructions, demolished materials, and waste materials including trash and debris, and legally dispose of them off Owner's property. 1. Separate recyclable materials produced during site clearing from other

nonrecyclable materials. Store or stockpile without intermixing with other materials and transport them to recycling facilities.

3.15 CLEANING

A. Remove tools and equipment. Dispose of scrap.

B. Broom clean interior areas.

C. Leave exterior areas free of debris.

D. Clean soil, smudges, and dust from surfaces to remain.

E. Return structures and surfaces to remain to condition existing prior to commencement of demolition.

3.16 SCHEDULES

A. Remove and Scrap: 1. All items shown as demolished and not otherwise noted.

B. Existing Items to Remain: 1. Existing building shell including exterior CMU and concrete Walls, roof structure,

plaster soffits and asphalt shingles unless other noted. 2. Items shown to remain or not identified as demolished. Piping and conduit shown

to remain, or as required to maintain services to the other portions of the building.

C. Remove and Re-install: 1. Items noted on the drawings.

D. Remove and Salvage

END OF SECTION 02221

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 22: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

ROUGH CARPENTRY 06100-1

SECTION 06100 - ROUGH CARPENTRY

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes the following: 1. Framing with dimension lumber. 2. Framing with engineered wood products. 3. Rooftop equipment bases and support curbs. 4. Wood blocking and nailers. 5. Wood furring. 6. Sheathing. 7. Plywood backing panels.

1.3 DEFINITIONS

A. Rough Carpentry: Carpentry work not specified in other Sections and not exposed, unless otherwise indicated.

B. Exposed Framing: Dimension lumber not concealed by other construction.

C. Lumber grading agencies, and the abbreviations used to reference them, include the following:

1. WCLIB - West Coast Lumber Inspection Bureau. 2. WWPA - Western Wood Products Association.

1.4 SUBMITTALS

A. Product Data: For each type of process and factory-fabricated product. Indicate component materials and dimensions and include construction and application details.

1. Include data for wood-preservative treatment from chemical treatment manufacturer and certification by treating plant that treated materials comply with requirements. Indicate type of preservative used, net amount of preservative retained, and chemical treatment manufacturer's written instructions for handling, storing, installing, and finishing treated material.

2. For products receiving a waterborne treatment, include statement that moisture content of treated materials was reduced to levels specified before shipment to Project site.

3. Include copies of warranties from chemical treatment manufacturers for each type of treatment.

B. Material Certificates: For dimension lumber specified to comply with minimum allowable unit stresses. Indicate species and grade selected for each use and design values approved by the American Lumber Standards Committee Board of Review.

C. Research/Evaluation Reports: For the following, showing compliance with building code in effect for Project:

1. Preservative-treated wood.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 23: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

ROUGH CARPENTRY 06100-2

2. Power-driven fasteners.

1.5 QUALITY ASSURANCE

A. Comply with applicable provisions of the California Code of Regulations (CCR) Title 24, Part 2, 2001 California Building Code. Timber connectors shall comply with CBC Section 2337A.2.

B. Testing Agency Qualifications: An independent testing agency, acceptable to authorities having jurisdiction, with the experience and capability to conduct the testing indicated, as documented according to ASTM E 548.

1.6 DELIVERY, STORAGE, AND HANDLING

A. Keep materials under cover and dry. Protect from weather and contact with damp or wet surfaces. Stack lumber, plywood, and other panels; place spacers between each bundle to provide air circulation. Provide for air circulation around stacks and under coverings.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

2.2 WOOD PRODUCTS, GENERAL

A. Lumber: DOC PS 20 and applicable rules of lumber grading agencies certified by the American Lumber Standards Committee Board of Review.

1. Factory mark each piece of lumber with grade stamp of grading agency. 2. Where nominal sizes are indicated, provide actual sizes required by DOC PS 20

for moisture content specified. Where actual sizes are indicated, they are minimum dressed sizes for dry lumber.

3. Provide dressed lumber, S4S, unless otherwise indicated. 4. Provide dry lumber with 19 percent maximum moisture content at time of dressing

for 2-inch nominal thickness or less, unless otherwise indicated.

2.3 WOOD-PRESERVATIVE-TREATED MATERIALS

A. Preservative Treatment by Pressure Process: AWPA C2 lumber except that lumber that is not in contact with the ground and is continuously protected from liquid water may be treated according to AWPA C31 with inorganic boron (SBX).

1. Preservative Chemicals: Acceptable to authorities having jurisdiction and one of the following: a. Ammoniacal copper zinc arsenate (ACZA). b. Ammoniacal, or amine, copper quat (ACZA). c. Copper bits (dimethyldithiocarbamate) (CDDC). d. Ammoniacal copper citrate (CC). e. Copper azole, Type A (CBA-A). f. Oxine copper (copper-8-quinolinolate) in a light petroleum solvent.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 24: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

ROUGH CARPENTRY 06100-3

2. For exposed items indicated to receive a stained or natural finish, use chemical formulations that do not require incising, contain colorants, bleed through, or otherwise adversely affect finishes.

B. Kiln-dry material after treatment to a maximum moisture content of 19 percent for lumber. Do not use material that is warped or does not comply with requirements for untreated material.

C. Mark each treated item with the treatment quality mark of an inspection agency approved by the American Lumber Standards Committee Board of Review.

1. For exposed lumber indicated to receive a stained or natural finish, mark end or back of each piece or omit marking and provide certificates of treatment compliance issued by inspection agency.

D. Application: Treat items indicated on Drawings, and the following: 1. Wood cants, nailers, curbs, equipment support bases, blocking, stripping, and

similar members in connection with roofing, flashing, vapor barriers, and waterproofing.

2. Wood sills, sleepers, blocking, furring, stripping, and similar concealed members in contact with masonry or concrete.

3. Wood framing members less than 18 inches above grade. 4. Wood floor plates that are installed over concrete slabs directly in contact with

earth.

2.4 DIMENSION LUMBER

A. General: Provide dimension lumber of grades indicated according to the American Lumber Standards Committee National Grading Rule provisions of the grading agency indicated.

2.5 MISCELLANEOUS LUMBER

A. General: Provide lumber for support or attachment of other construction, including the following:

1. Rooftop equipment bases and support curbs. 2. Blocking. 3. Cants. 4. Nailers. 5. Furring.

B. For items of dimension lumber size, provide Construction, Stud, or No. 2 grade lumber with 19 percent maximum moisture content and the following species:

1. Douglas Fir; WCLIB or WWPA.

C. For concealed boards, provide lumber with 19 percent maximum moisture content and the following species and grades:

1. Douglas Fir, Construction or 2 Common, WCLIB, or WWPA.

D. For furring strips for installing plywood or hardboard paneling, select boards with no knots capable of producing bent-over nails and damage to paneling.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 25: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

ROUGH CARPENTRY 06100-4

2.6 FASTENERS

A. General: Provide fasteners of size and type indicated that comply with requirements specified in this Article for material and manufacture.

1. Where rough carpentry is exposed to weather or in ground contact, provide fasteners with hot-dip zinc coatings complying with ASTM A153/A 153M.

B. Nails, Brads, and Staples: ASTM F 1667.

C. Power-Driven Fasteners: CABO NER-272.

D. Wood Screws: ASME B18.6.1.

E. Screws for Fastening to Cold-Formed Metal Framing: ASTM C 954, except with wafer heads and reamer wings, length as recommended by screw manufacturer for material being fastened.

F. Lag Bolts: ASME B18.2.1.

G. Bolts: Steel bolts complying with ASTM A 307, Grade A; with ASTM A 563 hex nuts and, where indicated, flat washers.

2.7 INSTALLATION, GENERAL

A. Set rough carpentry to required levels and lines, with members plumb, true to line, cut, and fitted. Fit rough carpentry to other construction; scribe and cope as needed for accurate fit. Locate nailers, blocking and similar supports to comply with requirements for attaching other construction.

B. Do not use materials with defects that impair quality of rough carpentry or pieces that are too small to use with minimum number of joints or optimum joint arrangement.

C. Apply field treatment complying with AWPA M4 to cut surfaces of preservative-treated lumber and plywood.

D. Securely attach rough carpentry work to substrate by anchoring and fastening as indicated, complying with the following:

1. CABO NER-272 for power-driven fasteners. 2. Published requirements of metal framing anchor manufacturer. 3. Table 23A-II-B-1, "Nailing Schedule," and Table 23A-II-B-2, "Wood Structural

Panel Roof Sheathing Nailing Schedule," in the California Building Code.

E. Use common wire nails, unless otherwise indicated. Select fasteners of size that will not fully penetrate members where opposite side will be exposed to view or will receive finish materials. Make tight connections between members. Install fasteners without splitting wood; predrill as required.

2.8 WOOD SLEEPER, BLOCKING, AND NAILER INSTALLATION

A. Install where indicated and where required for attaching other work. Form to shapes indicated and cut as required for true line and level of attached work. Coordinate locations with other work involved.

B. Attach items to substrates to support applied loading. Recess bolts and nuts flush with surfaces, unless otherwise indicated. Build anchor bolts into masonry during

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 26: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

ROUGH CARPENTRY 06100-5

installation of masonry work. Where possible, secure anchor bolts to formwork before concrete placement.

C. Provide permanent grounds of dressed, pressure-preservative-treated, key-beveled lumber not less than 1-1/2 inches wide and of thickness required to bring face of ground to exact thickness of finish material. Remove temporary grounds when no longer required.

END OF SECTION 06100

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 27: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

GYPSUM BOARD 09250-1

SECTION 09250 - GYPSUM BOARD PART 1 - GENERAL 1.1 RELATED DOCUMENTS

A. Documents affecting work of this Section include, but are not necessarily limited

to, General Conditions, Supplementary Conditions, and Sections in Division 1 of these Specifications.

1.2 DESCRIPTION/SUMMARY

A. Work Included: The work includes, but is not necessarily limited to furnishing all materials, labor, equipment and transportation to provide all gypsum wallboard, backer board, exterior sheathing, shaftwall work, taping and preparation for finishes, including fasteners, accessories, etc., complete as indicated and as specified herein.

B. Related Work Specified Elsewhere

Note: Coordinate work of this section with work of other sections to properly execute the work and maintain satisfactory progress of work of other sections including:

Section 07210 – “Building Insulation” Section 07920 – “Sealants”

Section 09900 – “Paints” Section 09310 – “Ceramic Tile” 1.3 REFERENCES A. Reference standard: The applicable provisions of GA-201, GA-216 and GA-600

latest editions, published by the Gypsum Association govern the work of this Section. Install per ASTM C840 and ASTM C1280. In case of conflict between the Drawings, these Specifications, Code requirements and the reference standard, the more restrictive requirement shall govern.

B. Applicable portions of the reference specifications for Lathing, Plastering and

Drywall, 1988 edition, published in the Plaster and Drywall Systems Manual, 3rd Edition, hereinafter referred to as "Reference Specification", is made a part of this specification to the same extent as if bound herein.

C. UBC - Chapters 7 and 25. D. Gypsum Construction Handbook (by United States Gypsum Co.) 5th Edition.

The current edition of the handbook applicable reference specifications and details for installation now shown elsewhere.

E. The listed American Society for Testing and Materials (ASTM) specifications and

standards referenced herein, apply to the work only to the extent specified by the reference. Refer to Division 1, Section: REFERENCE STANDARDS for information concerning availability and use of references.

1.4 SUBMITTALS A. Product Data: In accordance with the provisions of Section 01330 – “Submittal

Procedures”, submit complete manufacturer's descriptive literature and specifications.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 28: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

GYPSUM BOARD 09250-2

B. Architectural samples: 1. Submit color and finish samples to determine range of texture and

consistency of color and finish to be expected in the finished work. Standard sample size to be 6” x 6.”

C. Fire-Test-Response Reports: From a qualified independent testing and

inspection agency substantiating each gypsum board shaft-wall assembly’s required fire-resistance rating. 1. Include data substantiating that elevator entrances and other items that

penetrate each gypsum board shaft-wall assembly do not negate fire-resistance rating.

D. Research/Evaluation Reports: Evidence of compliance with building code in

effect for Project, from a model code organization acceptable to authorities having jurisdiction that substantiate required fire-resistance rating for each gypsum board shaft-wall assembly.

1.5 QUALITY ASSURANCE A. Regulatory Requirements: Gypsum board construction shall conform with UBC

Chapter 25. Fire resistive walls, partitions and ceilings shall conform to UBC Chapter 7.

B. Provide fire-rated assemblies as listed in the following:

1. GA-600, “Fire Resistance Design Manual.” 2. Underwriters Laboratories Inc.’s (UL) “Fire Resistance Directory.”

C. General Performance Requirements, Gypsum Board Shaftwall: Provide pre-

engineered system produced and distributed by a single manufacturer and tested for compliance with specified performance requirements.

D. Vibration isolation hardware must not be concealed until approval is obtained

from the owner’s field representative.

E. Verify clearances at sound-rated walls (e.g. no contact is permitted between gypsum board, framing and ceiling wires, conduit, ducts or piping).

1.6 DELIVERY, STORAGE AND HANDLING

A. Deliver components in clearly marked containers and packages suitable for shipment of specified products so as to minimize finish damage in transit. Provide protective wrapping or film to provide protection.

B. Store components in locations that will avoid damage from job-site traffic moisture,

stacking or other job-site contamination.

C. Handle components to avoid racking, twisting, denting or scratching of finished surfaces.

PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Pabco Gypsum,Georgia Pacific Gysum Corp. (G-P), Centex American Gypsum,

National Gypsum Co. (Gold Bond), U.S. Gypsum Corp. or approved equal. 2.2 MATERIALS

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 29: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

GYPSUM BOARD 09250-3

A. Gypsum wallboard shall be tapered or T&G/square edge (where required for fire rating); U.L. labeled Type X fire-rated where required; thickness: walls 5/8-inch (15.7 mm) unless otherwise indicated; ceilings ½-inch (12.7 mm) U.O.I.; exterior wall sheathing ½-inch (12.7 mm) U.O.I.

B. Liner Panels: Gypsum coreboard as required for specific fire-resistant-rated

assemblies indicated: 1. Framing profile and gage: As required to comply with structural

performance requirements. 2. Maximum deflection: L/2140. 3. Design air pressure load: uniform load of 5 pounds-force per square foot.

C. Materials shall conform to the following ASTM and ANSI Specifications and

requirements: 1. Gypsum Wallboard: Standard Specification for Gypsum Wallboard,

ASTM C36, Type ‘X’, fire code ‘C.’ 2. Gypsum Backing Board and Coreboard: Standard Specification for

Gypsum Backing Board and Coreboard, ASTM C442 and ASTM C630. 3. Shaft Wall Fire Resistant Gypsum Wallboard: G-P "Dens-Glass" “Ultra

Shaftliner”, use in shaft walls, meeting ASTM E 84, ASTM C442; tested in accordance with ASTM C473 and ASTM D 3273-94, no known equal.

4. Exterior Sheathing: G-P “Dens-Glass Gold” use at walls, soffits and parapets as backer board for plaster, meets ASTM E84, ASTM C79 and ASTM C1278 (Type X); meets ASTM C630, water resistant (Type WR).

5. Roof Sheathing: G-P ½” “DensDeck” to be used at where noted, meeting ASTM E84, ASTM C442; tested in accordance with ASTM C473 and ASTM D 3273-94, no known equal.

6. Water Resistant: meeting ASTM C1178, U.L. classified, Application Std. FM 4450, G-P “Dens-Shield”, no known equal.

7. Cementitious Backer Units (CBU): Standard Specification for CBU, ANSI 118.9 (90).

8. Abuse Resistant Gypsum Board - Fiber Rock VHI: Proprietary product of US Gypsum Company 5/8” thickness, Type”X.”

9. Joint Reinforcing Tape and Joint Compound: Standard Specification for Joint Compound and Joint Tape for Finishing Gypsum Board, ASTM C475.

10. Laminating Adhesive: Either joint compound, adhesive, or laminating compound, all as recommended by the manufacturer of gypsum board.

11. Water: Should be clean, fresh and suitable for domestic consumption. D. Screws: 1. Standard Specification for Steel Drill Screws for the Application of

Gypsum Board, ASTM C1002, C954 and C1002. 2. Type G: For the fastening of gypsum board to gypsum board. 3. Type S: For the fastening of gypsum board to light gage steel framing and

furring. 4. Type W: For the fastening of gypsum board to wood framing. 5. Standard Specification for Steel Drill Screws for the Application of

Gypsum Board to Steel Studs from 0.033 in. to 0.112 in. thickness, ASTM C954.

6. Type S-12: For the fastening of gypsum board to heavier gage steel framing (not over 12 gauge).

7. Use galvanized screws at exterior sheathing CBU and WR Board. E. Adhesives 1. Standard Specification for Adhesives for Fastening Gypsum Board to

Wood Framing, ASTM C557. 2. Adhesives for fastening gypsum board to metal framing should be as

recommended by gypsum board manufacturer.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 30: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

GYPSUM BOARD 09250-4

3. Adhesives for fastening gypsum board to gypsum board should be as recommended by gypsum board manufacturer.

4. Bonding agents for exterior plastering per ASTM C932. 2.3 TRIM, CASINGS AND ACCESSORIES

A. General: Except as otherwise specifically indicated, provide trim and accessories by manufacturer of gypsum board materials, made of galvanized steel or zinc alloy and configured for concealment in joint compound.

B. Galvanized steel of approved design per ASTM C1047. Use 1-inch flange at all

corners C Exposed Trim: Provide manufacturer’s standard metal trim units designed to be

left exposed or semi-exposed. D. Insulation per Section 07210 – “Building Insulation”. E. Acoustical Sealant per Section 07920 – “Sealants” and as recommended by

shaft-wall assembly manufacturer for application indicated. F. Steel Drill Screws: ASTM C1002, unless otherwise indicated.

1. Use screws complying with ASTM C954 for fastening panels to steel members from 0.033 to 0.112 inch thick.

G. Screws: ASTM C954, C893 and C1002 size and spacing as recommended by

the gypsum wallboard manufacturer for the applications shown.

H. Metal trim: Galvanized steel of the following GA types: 1. At external corners: Type CB with metal flanges. 2. At exposed edges: Type L. 3. Where gypsum wallboard abuts dissimilar materials: Type L. 4. Control joint: Type V.

2.4 METAL STUDS AND FURRING A. See Section 05400 – “Cold-formed Metal Framing and Section 09110 – “Metal

Support Assemblies”. 2.5 MISCELLANEOUS MATERIALS

A. General: Provide miscellaneous materials, including joint tape and sealant, as

produced or recommended by manufacturers of shaftwall system components. 2.6 ARCHITECTURAL SHAPES

A. Fry Reglet Corporation, as distributed by Expo Builders Supply (858) 566-4343, or equal. 1. “F” gypsum board reveal, both radius and straight. 2. Soffit vents as indicated.

B. Material:

1. Aluminum sheet: a. Type: 3003 H-14 or 5052 H-32 alloy aluminum sheet complying

with ASTM A789. b. Thickness: 0.125.

2. Finish: Primed for field finishing. Primer shall be compatible with common interior drywall tapes, spackles, caulks and paint finishes.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 31: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

GYPSUM BOARD 09250-5

PART 3 - EXECUTION 3.1 EXAMINATION A. Before applying gypsum board ensure that corners and framing are plumb, true

and solid and that framing members are properly spaced. Edges and ends of board shall have solid bearing. Do not start work until deficiencies have been corrected. Start of work of this section constitutes acceptance of the surfaces.

B. Examine substrates to which gypsum board shaft-wall assemblies attach or abut,

with Installer present including hollow-metal frames, elevator hoistway doorframes, cast-in anchors, and structural framing. Examine for compliance with requirements for installation tolerances and other conditions affecting performance. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 APPLICATION A. Installation of gypsum board shall conform to ASTM C840 and C1280 for

sheathing. Apply wallboard first to ceiling then to walls with long dimension at right angles to framing members. Use boards of maximum practical length so absolute minimum number of end joints occur. Bring boards into contact with each other, but do not force into place. Locate so no end joint aligns with edges of openings. Finish all exposed joints with reinforcing tape and joint cement. Locate boards in fire rated assemblies as required for individual tested assemblies. For deflection absorbing installations follow manufacturer’s recommendations and code requirements. Use screw attachment throughout.

B. Installation of all wallboard shall be done with extreme care to assure that sound

separation is complete and maintained in all partitions where indicated.

C. Water resistant gypsum board is to be used at all toilet room walls and on all walls that have sinks.

D. Abuse Resistant Board – Use USG Fiberock VHI at all walls in the locker and

toilet rooms that are not covered by the lockers, and in the weight and exercise rooms from the floor to 4 feet above the floor.

E. Double Lay Application:

1. Joints: Stagger 24 inches between layers. 2. Sound-rated construction: Tape all layers.

F. Sound-rated Condition: Gypsum board layers shall be stagger where they

intersect. A ¼ inch maximum gap shall be provided at all gypsum board face layer perimeter intersection conditions. The ¼ inch gap shall be fully caulked with acoustical sealant around the entire gypsum board surface perimeter.

G. Application on Resilient Channel:

1. Gypsum board and attaching screws shall not directly contact the structure at any point.

2. Use the appropriate length screws as recommended by the manufacturer. Screws shall not contact studs or framing.

3. Resilient channel only to bear load of gypsum board. All fixtures shall be surface mounted and attached using molly type fasteners. The fasteners shall not contact resilient channels or structure.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 32: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

GYPSUM BOARD 09250-6

H. Multilayer Application on Partitions/Walls: Apply gypsum board indicated for base layers and face layers vertically (parallel to framing) with joints of base layers located over stud or furring member and face-layer joints offset at least one stud or furring member with base-layer joints, unless otherwise indicated or required by fire-resistance-rated assembly. Stagger joints on opposite sides of partitions.

3.3 PENETRATIONS THROUGH SOUND-RATED CONSTRUCTION

A. Cut-outs are to be regular, will not fracture core or tear covering of gypsum board, and with accuracy to meet the following requirements.

B. Penetrations of insulated wall and ceiling constructions shall be made only where necessary and are to be fully sealed airtight at the perimeter using acoustical sealant.

C. Where ducts and piping greater than 3 inches in diameter penetrate insulated wall or ceiling construction, provide a clearance of 1 inch± ¼ inch at the perimeter of the penetration.

D. Where piping 3 inches in diameter or less (including mechanical, hydraulic, plumbing, etc.) pass through insulated wall or ceiling construction, provide a clearance of ¼ inch± 1/8 inch between the conduit or piping and the structure, unless otherwise shown.

E. After the ductwork, conduit or piping has been installed, repair the perimeter clearance to the specified tolerance as required. Where the clearance exceeds ¾ inch, provide a sheet metal sleeve within the partition and fill by packing with safing insulation batts and caulk both sides airtight with an acoustical sealant. Where the perimeter clearance exceeds ½ inch, a flexible backing rod shall be used to caulk against.

F. Where penetration clearances are 3/8 inch or less, caulk airtight with acoustical sealant at gypsum board.

G. Conduit and sprinkler piping penetrations through concrete and masonry units shall be grouted solid and airtight. Caulk airtight with acoustical sealant at gypsum board.

H. Gypsum board penetrations resulting from telephone and communication system wiring, cables, and electrical junction boxes are to be sealed airtight with acoustical sealant.

I. The back of junction boxes in acoustically-rated construction must be sealed airtight with sheet caulking. Caulk perimeter face at gypsum board with acoustical sealant.

J. Recessed panel boards, equipment, boxes, etc. with penetration area greater than 32 sq. in. (4 gang box) at double framing are to be fully boxed in gypsum board.

3.4 GYPSUM SHEATHING

A. General: Fasten gypsum sheathing to supports with galvanized roofing nails; comply with GA-253 and manufacturer's recommended spacing and referenced

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 33: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

GYPSUM BOARD 09250-7

fastening schedule. Keep perimeter fasteners 3/8 inch from edges and ends of units.

B. Install 24-by-96-inch sheathing horizontally with long edges at right angles to studs with V-grooved edge down and tongue edge up. Interlock tongue with groove to bring long edges in contact with edges of adjacent board without forcing. Abut ends of boards over centers of studs and stagger end joints of adjacent boards not less than one stud spacing, two where possible.

C. Install 48-by-96-inch and longer sheathing vertically with long edges parallel to, and centered over, studs. Install solid wood blocking where end joints do not occur over framing. Fit units tightly against each other.

D. Apply sheathing tape to joints between sheathing panels and at items penetrating sheathing. Apply at upstanding flashing to overlap both flashing and sheathing.

3.5 METAL EDGE TRIM CORNER BEADS AND CASINGS A. Use metal edge trim against wood, metal, concrete, and concrete masonry

throughout. Use corner beads and casing at all corners or exposed edges. Fasten trims with screws; clinching shall only be used with tape reinforcing.

3.6 EXPANSION CONTROL JOINTS

A. Adhere to recommendations as specified in the ‘Gypsum Construction Handbook; by U.S.G. Co., the Fifth Edition.

B. If expansion joints are not specifically called out on the drawings, consult

Architect for exact spacing and type of expansion joint to utilize. Install per “The Gypsum Construction Handbook”, Centennial Edition, by USG.

3.7 ARCHITECTURAL SHAPES AND REVEALS

A. Install components in accordance with manufacturer’s product data and approve

shop drawings. B. Anchor components to related structures such as walls and beams as indicated

on approved shop drawings. Use anchors with sufficient holding strength to provide solid installation. Use only plated, galvanized or stainless steel fasteners.

3.8 FINISH A. Finish tape all gypsum wallboard ready to receive paint or vinyl wallcovering as

scheduled. Taping for fire rating shall be as indicated. B. At exposed ceilings and soffits and at all walls with painted finish provide a

smooth Level 5 finish. 3.9 ACOUSTIC SEALANT A. Refer to Section 07920 – “Sealants”. Install acoustic sealant at all joints and

cracks between G.P.D.W. and dissimilar materials to provide at sealed sound separated space where indicated. Install per ASTM C919.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 34: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

GYPSUM BOARD 09250-8

3.10 CLEAN UP A. After completion clean all windows, metal and adjacent surfaces from joint taping

compound, over sprays, etc. and remove all debris from the jobsite.

B. Architectural Shapes 1. Remove protective coverings (if any) and clean components to remove

adhesives and tape residue. a. Test all solvents on non-exposed surfaces prior to use. b. For painted surfaces use a mild detergent solution on a soft cloth.

2. Visually inspect exposed surfaces for scratches or blemishes. 3. Protect components from damage during remainder of construction period.

END OF SECTION 09250

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 35: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

CUTTING AND PATCHING 09900-1

SECTION 09900 - PAINTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS

A. Documents affecting work of this Section include, but are not necessarily limited

to, General Conditions, Supplementary Conditions, and Sections in Division 1 of these Specifications.

1.2 DESCRIPTION/SUMMARY A. Work Included

1. The work includes, but is not necessarily limited to, the furnishing of all labor, materials and equipment for the completion of all painting and painter's finishes on all exposed exterior and interior surfaces, piping, etc. as required to complete the finish of the project as shown and noted on the drawings and specified herein.

2. Surface preparation, priming and coats of paint specified are in addition to shop priming and surface treatment specified in other Sections.

3. Paint all exposed surfaces whether or not colors are designated, except where the natural finish of the material is obviously intended or specifically noted as a surface not to be painted. Where items or surfaces are not specifically mentioned, paint these the same as adjacent similar materials or areas.

4. Exposed metal flashing and ductwork where exposed are to be painted.

B. Painting not included: The following surfaces are not to be painted or their painting is included in other Sections of these Specifications. 1. Shop priming of ferrous metal items included under structural steel, metal

fabrications, steel doors and frames, and similar Sections. 2. Concrete, except where scheduled or designated to be painted. 3. 4” high colored concrete masonry units receive water repellant per

Section 07190 and graffiti coating per this section. 4. Factory-finished or installer-finished items such as (but not limited to)

curtainwall, toilet partitions, pre-finished exterior wall louvers, finished (not primed) mechanical and electrical equipment including light fixtures, switchgear and distribution cabinets unless specifically so indicated.

6. Prefinished metal surfaces such as aluminum, alloys and steel with special coatings, anodized aluminum, stainless steel, chromium plating, copper, bronze, brass and similar finished materials will not require finish painting.

7. Piping identification. 8. Painting is not required on walls or ceilings in concealed and inaccessible

areas, such as furred areas, pipe spaces, duct shafts and elevator shafts. 9. Operating parts and labels:

a. Do not paint moving parts of operating units, mechanical and electrical parts, such as valve and damper operator linkages, sinkages, sensing devices, motor and fan shafts.

b. Do not paint over any Code required labels, such as UL and FM, or any equipment identification, performance rating; name, or nomenclature plates.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 36: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

CUTTING AND PATCHING 09900-2

C. Related Work Specified Elsewhere: Note - Coordinate work of this section with work of other sections to properly execute the work and maintain satisfactory progress of work of other sections including: 1. WATER REPELLANT, Division 7 2. PREFINISHED METAL COPING AND FLASHINGS, Division 7 3. SHEET METAL FLASHING AND TRIM, Division 7 4. FLUID APPLIED WATERPROOFING, Division 7

1.3 REFERENCES A. References made herein to published specifications, standards, methods of

testing and recommended methods of trade, industry and governmental organizations shall apply to the work of this section only to the extent specified by reference. All ASTM references refer to the year of original adoption or the year of the latest revision or reapprovals. Refer to Division 1, Section: REFERENCE STANDARDS.

B. "Manual" referenced this Section: Architectural Specifications Manual, Painting;

edition current as of date of this Specification, published by Specification Services, P.O. Box 6225, Federal Way, Washington 98063-6225, Telephone (206) 941-8823.

C. American Society for Testing and Materials (ASTM): D 2200-67 (1980) Pictorial

Surface Preparation Standards for Painting Steel Surfaces. D. Steel Structures Painting Manual, Volume 2, Systems and Specifications (5th

edition). 1.4 DEFINITION

A. Paint as used herein, is defined as all finishes required such as priming,

undercoats, finish coats of paint, enamels, stains, emulsions, lacquers, varnish, sealer, and other similar finishes whether used as prime, intermediate or finish coats.

1.5 SUBMITTALS A. Product Data: Submit complete manufacturer's descriptive literature and

specifications in accordance with the provisions of Division 1, Section: SUBMITTAL PROCEDURES.

1. Materials List: Submit complete lists of materials proposed for use, giving the manufacturer's name, catalog number, and catalog cut for each item when applicable. When required, provide a list of paint and coating materials proposed for use which equates such materials with the design-basis products specified.

B. Samples: Submit, on 4 x 8 inch cardboard, samples of each color, gloss, texture

and material selected by the Architect from standard colors available for the coatings required.

1. For natural and stained finishes, provide sample on each type and quality of wood used on the project.

C. Manufacturer's Instructions: Submit the manufacturer's current recommended

methods of installation, including relevant limitations, safety and environmental

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 37: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

CUTTING AND PATCHING 09900-3

cautions, and application rates. D. Field Sample: When and as directed by the Architect, apply one complete

coating system for each color, gloss and texture required. When approved, the sample panel areas will be deemed incorporated into the Work and will serve as the standards by which the subsequent Work of this Section will be judged.

E. Certification: The manufacturer and the contractor shall jointly provide

certification that all materials used on the job site are the manufacturer's best line materials as specified and that the approved paint materials have been used.

F. When other paint or coating types are proposed by a manufacturer as a

substitution for products by the specified manufacturer(s), the manufacturer, at his own expense, shall furnish a test report by an independent testing laboratory for any one or all of the substitution paints or coatings when requested by the Architect. The test report(s) shall indicate all of the following properties: 1. Physical Properties: 1) Percent non-volatile (weight); 2) Percent non-

volatile (volume); 3) Weight per gallon (pound/gallon); 4) Viscosity (Krebbs/ICI/Zahn/Ford); 5) Opacity as Supplied; 6) Whiteness Scale; 7) Spread Rate as Supplied, 1.5 DFT.

2. Working Properties: 1) Brushability; 2) Flow and Leveling/Leveling Index; 3) Sag Resistance/Sag Index.

3. Dry film Properties: 1) Specular Gloss (60/85 degrees); 2) Stain Resistance; 3) Abrasion Resistance 1,000 cycles.

1.6 QUALITY ASSURANCE

A. Conditions for Application: Temperatures and relative humidity conditions at time of painting shall be as recommended by the paint manufacturer. Paint for exterior surfaces shall not be applied in rainy, damp, dusty, misty or excessively windy weather. Neither exterior nor interior painting shall be done before the structure has sufficiently dried out and is in acceptable condition for painting.

B. Material Coordination:

1. Contractor shall be responsible for providing primer and finish coats which are compatible with each other and with prime coats provided under other sections. Verify compatibility with factory applied primers on all pre-primed items specified elsewhere.

2. Use adequate numbers of skilled workmen who are thoroughly trained and experienced in the necessary crafts and who are completely familiar with the specified requirements and the methods needed for proper performance of the work of this Section.

3. Paint coordination: a. In general the specifications will require primers for materials and

equipment to be compatible with the specified paint or coating system and have manufacturer’s printed data showing compatibility.

b. Review other Sections of these Specifications as required, verifying the prime coats to be used and assuring compatibility of the total coating system for the various substrates.

c. Upon request, furnish information on the characteristics of the specific finish materials to assure that compatible prime coats are used.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 38: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

CUTTING AND PATCHING 09900-4

d. Provide barrier coats over non-compatible primers, or remove the primer and reprime as required. Reprime ferrous metals to receive finish coats.

e. Notify the Architect in writing of anticipated problems in using the specified coating systems over prime coatings supplied under other Sections.

C. Protection:

1. Protect unpainted surfaces, lawns, shrubbery and adjacent surfaces against paint and damage. Repair damage resulting from inadequate protection.

2. Furnish sufficient drop cloths, shields, and protective equipment to prevent spray or splatter from fouling surfaces not being painted.

3. Remove electrical plate 5, surface hardware and related fittings prior to commencement of work. Carefully store, clean and replace these items on completion of work in each area.

4. Protect all surfaces, equipment and fixtures from damage resulting from use of fixed, movable and hanging scaffolding, planking and staging. Repair damage resulting from inadequate protection.

D. All painting work shall conform to all the applicable provisions of the latest edition

of the specification manual by the Painting and Decorating Contractors of America (PDCA) and the Steel Structures Painting Manual, Volume 2, by Steel Structures Painting Council (SSPC).

E. Certification: The general contractor and the Painting Contractor shall jointly

provide a notarized certification at the closeout of the job stating that the specified submitted and approved materials have been furnished all installed in the quantities specified by the manufacturer and installed per the manufacturer's recommendations.

1.7 ENVIRONMENTAL PROTECTION

A. Use no methods or materials that will in any way contribute pollutants to the

project's immediate environment. Special attention is brought to all current regulations by Federal, State, County and other local codes and ordinances for the volatile organic compound (VOC) or toxic contents of paints and coatings (excluding water) where in every case the more restrictive requirements shall apply. If a specified coating or coating component(s) have been changed, altered or discontinued, submit and use equal quality coating(s) and submit request for substitution.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 39: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

CUTTING AND PATCHING 09900-5

1.8 COLOR SCHEDULE A. Architect shall provide five copies of the color schedule, unless shown on

drawings. Allow for custom colors and conditions involving cutting of one color against another. Allow for About four different basic exterior colors and maximum of two different wall and ceiling colors in any given interior room or area.

1.9 EXTRA PAINT

A. At completion of work, Contractor shall furnish Owner with at least one gallon of

each color and type of paint used. All extra paint shall be drawn from first lot shipment and be in unopened containers.

PART 2 - PRODUCTS 2.1 PAINT MATERIALS

A. Manufacturer: Paint and finishing materials, unless otherwise specified, shall be products of the manufacturer's best quality line as stated in the manufacturer’s Architectural Products Specifications. Materials shall be manufactured by Frazee or approved equal. Coatings specified but not manufactured by the proposed paint system manufacturer shall be furnished as specified. Paint manufacturers numbers and names have been used on schedule for convenience purposes only.

B. Tinting: Each undercoat shall be a lighter shade than finish coat so that number

of coats can be easily discerned. Colors shall be incorporated into materials by paint manufacturer at the plant; no color mixing will be allowed at the job site unless specifically approved or directed by Architect.

C. Thinner: Paint thinner, type and usage, shall be as recommended by the paint

manufacturer.

D. Primer: All primers, except metal primers, shall be white or divergent color from finish coats for inspection purposes.

2.2 PAINT SCHEDULE

A. Surfaces shall be finished in accordance with the following procedure for the

surface and finish desired thereon for the following headings: B. Exterior

Cast-in-place Concrete and Smooth finish plaster (Stucco) where designated Pretreatment As recommended by manufacturer.

1st Coat Primer recommended by manufacturer. 2nd Coat Custom colors of Thorlastic by Thoro System Products.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 40: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

CUTTING AND PATCHING 09900-6

Metal Ferrous - Flat Finish 1st Coat Rust inhibitive primer 2nd Coat Intermediate metal undercoat 3rd Coat 100% acrylic flat

Metal - Galvanized - Enamel Finish –Typical unless noted otherwise.

1st Coat Corrosion inhibitive primer 2nd &

3rd Coats 100% acrylic semi - gloss non-blocking enamel

Metal – Galvanized – Handrails Pretreatment Wire brushed and cleaned per manufacturer's

specifications. 1st Coat Epoxy primer (two component) 2nd & 3rd Coats Polyurethane base enamel (two component)

Metal - Galvanized - Flat Finish (Roof Flashings and where noted)

Pretreatment Vinyl wash primer (etching solution) 1st Coat Corrosion inhibitive primer 2nd Coat Acrylic co-polymer

3rd Coat Acrylic co-polymer C. Interior Concrete Masonry - Eggshell Finish –Typical unless noted otherwise.

1st Coat Masonry primer 2nd Coat or 3rd Coat Acrylic co-polymer Gypsum Wallboard - Flat Finish

1st Coat Pigmented Sealer (PVA emulsion type) 2nd Coat & 3rd Coat Acrylic-vinyl latex wall paint

Wood or Masonite - Flat Finish

1st Coat Interior undercoat 2nd Coat & 3rd Coat Acrylic-vinyl wall paint

Gypsum Wallboard - Eggshell Finish–Typical unless noted otherwise 1st Coat Pigmented Sealer (PVA emulsion type) 2nd Coat & 3rd Coat Acrylic eggshell enamel

Wood or Masonite - Eggshell Finish –Typical unless noted otherwise.

1st Coat Interior pigmented wood primer 2nd Coat or 3rd Coat Acrylic eggshell enamel

Metal - Eggshell Finish

1st Coat Rust inhibitive primer (Ferrous) 1st Coat Galvanized metal primer (Galvanized) 2nd Coat Intermediate metal undercoat 3rd Coat Acrylic eggshell enamel

Gypsum Wallboard - Semi-gloss Finish

1st Coat Pigmented Sealer (PVA emulsion type) 2nd Coat Undercoater

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 41: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

CUTTING AND PATCHING 09900-7

3rd Coat 100% acrylic non-yellowing semi-gloss enamel. Gypsum Wallboard – Epoxy - Designated Areas

1st Coat Pigmented Sealer (manufacturer’s recommendation)

2nd Coat and 3rd Coat 2 part epoxy gloss.

Wood - Semi-gloss Finish

1st Coat Interior undercoat 2nd & 3rd Coat Semi-gloss enamel Acrylic/Non-Blocking

Metal - Semi-gloss Finish

1st Coat Rust inhibitive primer (Ferrous) 1st Coat Galvanized metal primer (Galvanized) 2nd Coat Intermediate metal undercoat 3rd Coat Semi-gloss enamel Acrylic-Non Blocking

2.4 SPECIAL COATING/PRIMERS

A. Galvanized surfaces damaged due to welding, threading, etc., shall be treated

with Galvicon, Galvalloy, or Drygalv or equal. 2.5 MECHANICAL AND ELECTRICAL EQUIPMENT

A. Exposed interior and exterior piping, ducts, conduit boxes, panels, terminal

cabinets, and similar related items of mechanical or electrical nature. In general, paint one coat, in addition to primer to match adjoining work, except as modified herein: 1. Copper piping: One coat primer and one finish coat. 2. Chrome plated piping: Do not paint. 3. Black steel pipe: Paint same as specified for other metalwork, exterior

and interior. 4. Insulated piping: One coat of glue sizing and one finish coat to match

adjacent surfaces. 5. Plastic piping: Shall be painted with an enamel-type paint compatible

with the plastic material. 6. Registers, connectors, air-diffusers, similar related items: Heat-resisting

enamel off-white factory finish. 7. Interior of ducts, visible from habitable rooms thru grills, registers: One

coat of primer and one coat flat black duct paint. 8. All exposed ductwork, exterior mechanical and plumbing equipment

prefinished or not, shall be etched and painted with 2 prime coats and 2 finish coats.

2.6 APPLICATION EQUIPMENT

A. For application of the approved paint, use only such equipment as is recommended for application of the particular paint by the manufacturer of the particular paint, and as approved by the Architect.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 42: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

CUTTING AND PATCHING 09900-8

B. Prior to use of application equipment, verify that the proposed equipment is actually compatible with the material to be applied, and that integrity of the finish will not be jeopardized by use of the proposed equipment.

2.7 OTHER MATERIALS

A. Provide other materials, not specifically described but required for a complete

and proper installation, as selected by the Contractor subject to the approval of the Architect.

PART 3 - EXECUTION 3.1 SURFACE PREPARATION A. All surface preparation and cleaning procedures shall be in strict accordance with

the paint manufacturer's instructions and as specified herein. All interior joints in walls and ceilings, back bedding, control joints, bedding of mullions panels and frames shall be caulked and/or sealed as required to provide smooth finish-painted surfaces. Use materials as specified elsewhere and as approved and required by the paint system manufacturer for the included use.

B. Where nothing else is specified the surface preparation(s) shall be per Chapter 3

and 3R of the referenced "Architectural Specifications Manual". C. Quality: All surface preparations and cleaning procedures shall be in strict

accordance with the paint manufacturer's instructions and as specified herein. D. Preparation: Remove dust and loose deleterious material from all surfaces

before beginning painting operations. If a surface to be painted cannot be put in proper condition by methods specified herein, notify Architect in writing before applying paint or assume responsibility for any resulting unsatisfactory finish. Touch up all damaged preprinted materials or products. Fill cracks, depressions, voids, etc., to be painted as required.

E. Cleaning: Exercise care so that dust and dirt from cleaning operations does not

come into contact with newly painted surfaces. F. Steel: Ferrous metal to be painted, provided it is not galvanized or factory

finished, shall be cleaned to accept a sound prime coat. Remove grease, oil, dirt, etc, minor cracks or open joints, with color of putty matching finish coat. Reprime all ferrous metal factory primed to be finish painted. Follow requirements of SSPC.

G. Galvanized Steel: Galvanized metal to be painted shall be washed with specified

vinyl wash pretreatment or as specified. Rinse surfaces treated with solution using clear water. Clean galvanized metal the same day to be painted. Failure of paint due to peeling, chipping or cracking shall be guaranteed for a period of 2 years from initial coating. Damaged areas shall be repainted for that period of time.

H. Wood: Wood to be painted shall be sanded to sound surfaces and cleaned off.

Backprime all exterior wood. Putty or spackle nail holes, minor cracks or open joints, with color of putty matching finish coat.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 43: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

CUTTING AND PATCHING 09900-9

I. Plaster/Stucco: Smooth finish plaster is to be painted: Fill minor cracks, holes or

other imperfections with patching plaster or other approved materials, bring flush to adjoining surfaces and sand smooth when dry. Treat excessive alkaline conditions by cleaning affected surfaces with solution of 3-lbs. zinc sulphate to each gallon of water. After application, allow solution to dry, clean off resulting crystalization with stiff dry brushes. Do not paint over surfaces where the moisture content exceeds 8%, unless otherwise allowed by paint manufacturer.

J. Concrete/Concrete Masonry: Concrete surfaces designated to be painted.

Remove miscellaneous residue and foreign material. Concrete shall have laitance, form oil or bond breaker removed by sanding and/or blasting if necessary. Alkali or efflorescence shall be neutralized with mild acid wash (18% muratic acid to water by volume). Remove all traces of acid solution with clear water, under pressure. Allow surfaces to dry thoroughly. 1. All concrete masonry walls exposed to weather shall be treated with

water repellant coating coats as specified elsewhere prior to painting, where so indicated.

K. Gypsum Wallboard: Drywall and other like materials to be painted: Dust down

with brush or with fine sandpaper. Repair minor holes with patching material and sand to smooth finish.

3.2 APPLICATION A. Apply paint by brush or roller in accordance with paint manufacturer's directions.

Use paint of proper consistency for each coat, well brushed-out or flowed-on to obtain a uniform finish free from holidays, brush marks, sags crawls, or other defects. Do not apply succeeding coats until the previous coat has completely dried. Spray painting of paint material shall only be allowed if followed immediately with brush or roller for uniform coverage.

1. Provide 2” contrasting color warning stripe 1” maximum from edge of nosing of each exterior.

B. Coats: Apply each paint material to a dry mil thickness of not less than that

specified or as recommended by the manufacturer for particular material used, but in no case less than one mil dry film thickness per coat. It is the intent of these specifications to obtain painted finishes of uniform color and textures, free from cloudy or mottled appearance on surfaces and evident thinness of coatings on surfaces; all spot coating and undercoating shall be done to produce such results.

C. Sanding: Sand lightly between coats of enamel, lacquer, or varnish applied to

wood or metal surfaces so as to produce an even smooth finish free of brush marks.

D. Back-Priming: Back-prime all frames, trim, and all galvanized sheet metal to be

painted with the specified first coat material prior to installation. 3.3 HARDWARE

Hardware plates and other items in place prior to painting shall be removed and replaced upon completion of each space.

Equipment that is adjacent to walls prior to painting shall be disconnected to permit

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 44: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

CUTTING AND PATCHING 09900-10

hidden wall surfaces to be painted. Replace and reconnect equipment upon completion of the painting.

3.4 CLEAN UP

Upon completion of painting work, remove all paint from surfaces adjacent to those painted. Remove rubbish, paint cans, and accumulated materials resulting from work.

END OF SECTION 09900

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 45: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

GENERAL REQUIREMENTS 16100 - 1

SECTION 16100 - GENERAL PROVISIONS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the contract, including General and Supplementary Conditions and Division 1 Specification sections, apply to this section.

1.2 GENERAL REQUIREMENTS

A. This Division is an integrated whole comprising interrelated and interdependent Sections and shall be considered in its entirety in determining requirements. Refer to other sections of this Division for additional requirements or information regarding the topics of this Section.

1.3 SUBMITTALS

A. Comply with requirements of Section 01300 - SUBMITTALS.

B. Material Lists and Manufacturers Literature.

C. Shop Drawings.

D. Electrical Room/Closet Layout Plans.

1.4 DEFINITIONS (as used on Division 16 drawings and herein)

A. "Provide" means furnish, install and connect unless otherwise described in specific instances.

B. "Extend", "Submit", "Repair" and similar words mean that the Contractor shall accomplish the action described.

C. "Codes" or "Code" means all codes, laws, statutes, rules, regulations, ordinances, orders, decrees, and other requirements of all legally constituted authorities having jurisdiction.

D. "Verify Location" when noted for an item, such as a receptacle, outlet, light fixture, stubouts/stubup/stubdowns, etc., means that the location of the item within the room is tentative and not necessarily as shown on the drawings. Contractor shall request the exact location of the item from the Architect during construction. The item may be located anywhere in the room by the Architect at no additional cost to the Owner.

E. "Products", "materials" and "equipment" are used interchangeably and mean materials, fixtures, equipment, accessories, etc.

F. "Utility areas" are defined as mechanical, electrical, telephone, janitorial and similar rooms or spaces which are normally used or occupied only by custodial or maintenance personnel. "Public areas" are defined as the rooms or spaces

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 46: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

GENERAL REQUIREMENTS 16100 - 2

which are not included in the utility areas definition.

1.5 DESCRIPTION

A. Provide a complete and operable installation, including all labor, supervision, materials, equipment, tools, apparatus, transportation, warehousing, rigging, scaffolding and other equipment and services necessary to accomplish the work in accordance with the intent and meaning of these contract documents.

1.6 INTERRELATED WORK

A. Contractor shall coordinate the installation layout of the HVAC-plumbing-fire sprinkler-electrical systems to ensure that the work will be installed in the available space without modification to the architectural and structural work. Where space for these systems is limited or restricted, the system installers shall jointly prepare mechanical-plumbing-fire sprinkler-electrical coordination layout drawings at appropriate scale and degree of detail.

B. Examine the drawings and specifications of all other Divisions of this specification for work /related to the work of this Division. Order the work of this Division so that progress will harmonize with that of other Divisions and all work will proceed expeditiously.

1.7 EXISTING CONDITIONS

A. Visit the site prior to bidding and investigate the existing conditions which affect or will be affected by work of this Division. Become thoroughly familiar with the working conditions and take into account any special or unusual features peculiar to this job. By the act of submitting a Bid, the Contractor will be deemed to have complied with the foregoing, to have accepted such conditions, and to have made allowance therefore in preparing his Bid.

B. The Contractor shall verify all existing conditions prior to bid and include all costs in bid.

C. The Contractor shall match the finish and appearance of all existing conditions where constructing new work adjacent to existing surfaces or equipment.

D. Coordinate with the District’s Representative for all ongoing projects or the work

of other trades which may affect the Contractor’s work. Verify District schedule requirements for special or standard events which may impact the Contractor’s

work.

E. Coordinate work to be performed in occupied areas and comply with the District’s requirements such that the District’s work is not disrupted by the

Contractor. Verify the need for work to be performed during premium hours, evenings, weekends, or holidays prior to bid and include all costs in bid. Bring to the District’s attention the need for all disruptive work prior to commencement of

work.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 47: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

GENERAL REQUIREMENTS 16100 - 3

1.8 DRAWINGS AND SPECIFICATIONS

A. Drawings and specifications are intended to complement each other. Where a conflict exists between the requirements of the drawings and/or the specifications, request clarification.

B. The Architect shall interpret the drawings and the specifications, and his decision as to the true intent and meaning thereof and the quality, quantity, and sufficiency of the materials and workmanship furnished thereunder shall be accepted as final and conclusive.

C. In case of conflicts not clarified prior to Bidding deadline, use the most costly alternative (better quality, greater quantity, or larger size) in preparing the Bid. A clarification will be issued to the successful Bidder as soon as feasible after the Award and if appropriate a deductive change order will be issued.

D. All provisions shall be deemed mandatory except as expressly indicated as optional by the word "may" or "option".

1.9 CHANGE ORDERS

A. Contractor shall clearly understand that the electrical work shown on the drawings and described in these specifications is subject to revision. Furnish backup data segregated by each electrical drawing involved in the Change Order and further broken down into credits (deletions) and costs (additions) per drawing. This is required to facilitate review by the Architect.

1.10 DISTRICT – PROVIDED UTILITY REQUIREMENTS

A. Contractor shall contact the District for all utility systems requirements prior to commencement of work. Utility work shall include electric power, telephone, data, fiber optic cable, cable television or other utilities as may be require connections as a part of this contract. Coordinate and comply with all District requirements.

B. The utility information depicted on the contract documents is for bidding purposes only and shall not be used for construction purposes. All construction shall be performed according to engineered documents from the district. The contractor shall obtain and coordinate with District requirements as a part of this contract and furnish and install all work as a part of this contract.

C. Verify all connections points, routing and requirements with the District prior to commencement of work and coordinate final requirement with other trades.

D. The contractor shall be responsible fro all costs associated with his failure to contract of coordinate with District requirements.

1.11 CONSTRUCTION UTILITY REQUIREMENTS

A. Power, telephone or other temporary construction utility services required by the contractor shall be the responsibility of the contractor.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 48: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

GENERAL REQUIREMENTS 16100 - 4

B. Arrangements for construction utility services shall be made by the contractor in coordination with the Districts Representative.

1.12 SEQUENCING (PHASING) OF CONSTRUCTION

A. Contractor shall consult with the General Contractor regarding this topic prior to bid and shall make allowance therefore in preparing his bid.

1.13 OBSERVATION OF CONSTRUCTION

A. Afford the Architect every facility for evaluating the skill and competence of the mechanics and to examine the products. Concealed work shall be reopened when so directed during his periodic visits.

1.14 CODES AND REGULATIONS

A. By submitting a Bid, Contractor is deemed to represent himself as competent to accomplish the work of this Division in conformance with applicable Codes. In case of conflict between the Contract Documents and Code requirements, the Codes shall take precedence. Should such conflicts appear, cease work on the parts of the contract affected and immediately notify the Architect in writing. It shall be the Contractor's responsibility to correct, at no cost to the Owner, any work he executes in violation of Code requirements. Specific references to Codes elsewhere in this Division are either to aid the Contractor in locating applicable information or to deny him permission to use options which are permitted by Codes.

B. Applicable Codes: (Current editions unless otherwise noted): 1998 CBC CH 3503 for adopted standards. 1. California Electrical Code (CEC) 2. California Building Code (CBC) 3. CCR Titles (as applicable) 4. Fire Marshal Regulations 5. State of California Public Utilities Commission General Orders #95 and

#128 (G095 and G0128). 6. Division of State Architect (DSA). 7. Regulations of all other applicable codes and authorities having

jurisdiction.

C. Where conflict or variation exists among Codes, the most stringent shall govern.

1.15 CONTINUITY OF SERVICE

A. The Contractor shall coordinate all shutdowns with the District’s Representative.

Electrical shutdowns shall be kept to the minimum number necessary to complete the work.

B. The Contractor shall coordinate all work done on overtime or premium time with District’s Representative prior to commencement of work.

C. All work performed in or through occupied spaces, or other work disruptive to existing occupants shall be considered as performed during premium time or as overtime for the purposes of the bid; include all costs in bid.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 49: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

GENERAL REQUIREMENTS 16100 - 5

D. The Contractor shall notify District’s Representative of all shutdowns or

disruptive work minimum of 72 hours prior to commencement of work. The Contractor shall obtain approval from the District’s Representative prior to

commencement of work.

E. The Contractor shall provide all necessary temporary power, including temporary power generation, to accommodate shutdowns and minimize disruption of work.

F. The District reserves the right to provide emergency repairs or temporary power to maintain service continuity at the Contractor’s cost in the event Contractor fails to provide adequate service continuity.

1.16 RECORDS AND DOCUMENTATION

A. Accumulate the following and deliver to the Architect prior to final acceptance of the work.

B. Record Drawings:

1. Maintain in good order in the field office a complete set of "as-built" electrical prints. Update the drawings daily with neat and legible annotations in red ink showing the work as actually installed.

2. The actual size, location and elevation of all buried lines, boxes, monuments, and stubouts shall be accurately located and dimensioned from building walls or other permanent landmarks.

3. Furnish the originals.

C. O&M Manuals: Furnish 3 copies of an operating and maintenance manual. Each manual shall be bound and indexed and shall include the following:

D. Operating and service instructions for systems and equipment as required by other sections of this Division. A spare parts list recommended for purchase by Owner shall be included.

E. Updated approved materials list, shop drawings, and catalog information as required by Submittals subsections.

F. List of material and equipment manufacturers (with names, addresses and phone numbers of local suppliers) in order to expedite ordering of replacement parts by the Owner. This list may be integrated with the material list.

G. Permits and Certificates of Inspection: Furnish the originals.

H. Testing procedures and test results required in this and other sections: Furnish 2 copies.

I. Other data required by other sections of this Division: Furnish 2 copies.

1.17 TOOLS

A. Provide all special tools needed for proper operation and routine adjustment and maintenance of systems and equipment. Deliver tools to Architect and request a receipt for same.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 50: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

GENERAL REQUIREMENTS 16100 - 6

1.18 GUARANTEE

A. All work shall be guaranteed in conformance with General Conditions of Contract and Division 1 for a minimum period of one year from either the official date of completion or from the official notice of acceptance, whichever is the later date.

B. The guarantee period for certain items shall be longer, as indicated in the specification for those items.

C. Should any trouble or fault develop during the guarantee period due to defective material, faulty workmanship, or non-compliance with plans, specifications, codes or directions of the Owner, Architect, Engineer, or Inspector, the Contractor shall furnish all necessary labor and materials to correct the trouble without additional charges.

D. The guarantee period shall be extended by any period of time the guaranteed item is defective or out of service due to trouble or fault.

PART 2 - PRODUCTS

2.1 MATERIALS

A. Materials shall be new, in accordance with the specifications of the Institute of Electrical and Electronic Engineers (IEEE), National Electrical Manufacturer's Association (NEMA), National Fire Production Association (NFPA), and the National Electrical Code (NEC), and shall have an Underwriter's Laboratories (UL) listing and bear their label where such services are available.

B. Where applicable, listing or labeling shall apply to the complete assembled equipment and not to the components alone. Where listing or labeling service is not available for an assembly, the components shall be listed or labeled and applied within their tested rating.

C. Materials for the same purpose shall be of the same make and shall be the manufacturer's latest standard design that complies with the specification requirements.

2.2 SUBSTITUTIONS

A. Substitutions will be allowed only in strict conformance with the General Conditions of the Contract and Division 1.

B. Whenever in specifications any materials, process, or article is indicated or specified by grade, patent, or proprietary name or by name of manufacturer such specification shall be deemed to be used for the purpose of facilitating description of material, process, or article desired and shall be substantially equal or better in every respect to that so indicated or specified. If material, process, or article offered by Contractor is not, in opinion of architect, substantially equal or better in every respect to that specified, then Contractor shall furnish material, process, or article specified. Burden of proof as to equality of any material, process, or article shall rest with Contractor. Contractor shall submit request together with substantiating data for substitution of an "or equal" item within thirty-five (35) days after award of contract. Provision authorizing

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 51: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

GENERAL REQUIREMENTS 16100 - 7

submission of "or-equal" justification data shall not in any way authorize an extension of time for performance of this contract.

C. When no specific make of material, apparatus or equipment is mentioned, a first-class specification grade product made by a well established manufacturer shall be used that conforms to the requirements of the contract documents and is acceptable to the Architect.

D. The Contractor shall assume any extra costs to other work or trades resulting from the use of substitutions. All substitutions accepted shall be provided at no extra charge.

2.3 SUBMITTALS

A. General: 1. Architect review of the submittal is only for general conformance with

design concept of the project and general compliance with the information given in the contract documents. The submittal procedure is required in an effort to minimize the problems which occur due to the discovery of Contractor non compliance at the construction site. The Contractor is responsible for confirmation and correlation of the dimensions, quantities and sizes, for information that pertains to fabrication methods or construction techniques, and for coordination of work of all Divisions of the work. Deviations, if any, from Contract Documents shall be clearly and completely indicated (by a separate letter if deviations are extensive) in the submittals, and the lack of such is deemed complete compliance with Contract Documents without any deviations. Submittals favorably processed will not relieve the Contractor of responsibility for deviations not so reported nor for errors in the submittal.

2. Contractor Stamp: All submittals shall be stamped with the following text and signed by the Contractors representative.

3. "IT IS HEREBY CERTIFIED THAT THE PRODUCTS SHOWN AND MARKED IN THIS SUBMITTAL ARE IN COMPLIANCE WITH THE CONTRACT DOCUMENTS AND CAN BE INSTALLED IN THE ALLOCATED SPACES EXCEPT WHERE DEVIATIONS ARE NOTED. CERTIFIED BY: DATE: "

4. All submittals shall be complete and with catalog data and information properly marked to show, among other things, equivalency of product (where substitution is requested), adequacy in capacity and performance to meet minimum capacities or performance as specified or indicated. Arrange the submittals in the same sequence as these specifications, and reference (at the upper right-hand corner) the particular specification provision for which each submittal is intended. Incomplete submittals will be rejected.

5. Late, incorrect, improper or rejected submittals will not be acceptable reasons for delaying the work or substituting non-specified material or equipment. The Contractor is responsible for providing proper submittals and allowing adequate time for their processing.

6. Refer to the other sections of this Division for specific requirements. 7. Material List: Submit for approval a complete list of materials proposed

for use. Furnish names and addresses of manufacturers, catalog numbers (where applicable) types and trade names. For purposes of

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 52: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

GENERAL REQUIREMENTS 16100 - 8

uniformity, only one manufacturer will be accepted for each class or type of material. This list is in addition to Shop Drawings.

8. Equipment Shop Drawings: Shop drawings and data sheets for devices, fixtures, equipment and systems shall be submitted as required in the specifications for those items. Include information on each component, wiring diagrams, layouts, finish, dimensions, and sufficient other data to establish compliance with the specifications and acceptability of the device, equipment, or system. Do not authorize fabrication of the equip-ment until approved drawings are received.

9. Electrical Room/Closet Layouts: Furnish a scale drawing of all electrical rooms and closets where power distribution equipment is provided. Indicate location and size of equipment to be provided, and the routing of feeder conduits within the space. Do not begin installation until the Architect has approved the layouts.

10. Samples: Samples of any item may be required, whether listed here or not, at the discretion of the Owners representative. The Architect or the owner shall not be charged for the sample. All costs including freight or postage shall be at the Contractor's expense. Samples shall be returned to the Contractor when review has been completed.

11. Other Submittals: As required by other sections of this Division.

PART 3 - EXECUTION

3.1 WORKMANSHIP AND INSTALLATION METHODS

A. Workmanship shall be in conformance with the "NECA (National Electrical Contractors Association) Standards of Installation" and the best standard practice of the trade except where specifically indicated otherwise.

B. Execute the work so as to contribute to ease of operation and maintenance, maximum accessibility and best appearance. Execute it so that the installation will conform and adjust itself to the building structure, its equipment and its usage. The work shall be symmetrical, plumb, uniform, properly aligned and firmly secured in place.

C. Install equipment in accordance with the manufacturer's instructions and recommendations unless otherwise noted or specified.

3.2 SCHEDULING OF WORK AND INTERRUPTIONS TO ELECTRICAL SYSTEMS

A. All existing electrical systems shall be maintained in operation at all times unless an interruption is necessary to the prosecution of the work.

B. Interruption of electrical systems shall be scheduled by request to the Architect at least 15 days in advance of the proposed date. The day of the outage shall be any day of the week (including Saturday or Sunday), and anytime of the day or night selected by the Architect. Prior to the outage, all possible work shall have been completed which will minimize the length of the required outage. During the outage, all feasible portions of the system requiring an outage shall be worked on simultaneously, and the work shall be prosecuted with diligence by an adequate number of skilled personnel.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 53: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

GENERAL REQUIREMENTS 16100 - 9

3.3 COORDINATION WITH STRUCTURAL REQUIREMENTS

A. The placement of conduits, etc., and the location, size and reinforcement of holes in the building structure shall conform to the structural drawings and specifications. When the requirements of the Electrical Division of the specifications or drawings are in conflict with the structural requirements, the structural requirements shall take precedence. Where the safety of the building structure is threatened, due to electrical work or holes required for such work, modifications shall be made as directed by the Architect.

3.4 LOCATIONS, SIZES, ROUTINGS AND CLEARANCES

A. For the purpose of clearness and legibility, the drawings are essentially diagrammatic. The size and location of equipment is shown to scale wherever possible, but the Contractor shall make use of all the data in the Contract Documents, and shall verify such information. Contractor is responsible for fitting the equipment provided by him in the spaces available while maintaining required working, ventilation, and equipment maintenance access space. Exercise particular care that such space is not infringed by the work of other Divisions.

B. Conduit Routing: The drawings show the points of termination of the conduits, and may suggest a route for the conduit. However, it shall be the responsibility of the Contractor to install the conduits with a minimum number of bends in such a manner as to conform to the structure, avoid obstructions, preserve headroom, keep openings and passageways clear, and meet all Code requirements with such offsets and special fittings as may be required.

C. Existing Conditions: The exact locations of borings, trenches, excavations, manholes, pullboxes, ground rods and all new sub-surface work shall be adjusted to avoid damaging or disturbing any existing-to-remain underground structure, pipe, or cable. The Contractor shall make every reasonable effort to determine their existing correct locations, including: obtaining record drawings that show location of existing utilities and having existing utilities located and marked for both routing and depth prior to commencing trenching operations.

D. Mounting Heights: Mounting heights shown are from finished floor, pavement or grade to middle of wall mounted outlet boxes, and from finished floor to highest point of suspended fixtures unless otherwise indicated.

3.5 TESTS

A. Demonstrate that all components of the work of this Division have been provided and that they operate in accordance with the Contract Documents.

B. Provide instruments and personnel for tests and demonstrations. Submit signed test results.

C. Notify the Architect in writing, seven (7) days in advance of tests to allow presence of Architect.

D. Refer to the other sections of this Division for test requirements.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 54: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

GENERAL REQUIREMENTS 16100 - 10

3.6 DELIVERY, HANDLING, STORAGE OF MATERIALS AND PROTECTION OF WORK

A. Protect materials against dirt, water, chemical and mechanical damage both while in storage and during construction.

B. Cover materials in such a manner that no finished surfaces will be damaged, marred or splattered with plaster or paint, and all moving parts will be kept clean and dry.

C. Replace or refinish all damaged materials including fronts of panels and switchboard sections as directed by Architect.

D. Keep raceways, boxes, cabinets, and other openings closed to prevent entry of foreign matter.

3.7 TEMPORARY LIGHTING AND POWER

A. Contractor shall provide on-site generation, labor, materials and/or any required utility fees associated with the installation and maintenance of a temporary power source for Contractor's equipment or field offices during the period of construction.

B. Building and site shall be sufficiently illuminated so that construction work can be safely performed. Lights shall be controlled by switches located with consideration for safety, security, and convenience.

3.8 CLEANUP AND HOUSEKEEPING

A. Cleaning shall be done as the work proceeds. Remove waste and debris to keep the site as clean as is practical.

B. Vacuum clean dirt and debris from interiors of switchboards, panelboards, transformers, and similar items. Leave exposed parts of the electrical work in a neat, clean and usable condition (including the tops of equipment which are higher than normal eye level), with painted surfaces unblemished and plated metal surfaces polished. Clean lighting fixtures and wipe lamps clean.

C. Clean and vacuum floors, ceilings and walls, and wet mop the floors of electrical rooms and closets.

3.9 JOB VISITS

A. Periodic visits to the project construction site by the Architect are for the purpose of observing the progress of construction and generally verifying that work is proceeding in accordance with the intent of the Construction Documents.

B. Such visits shall not be construed to be construction supervision nor the assumption of responsibility for construction means, methods, sequences, and safety by the Engineer.

C. The Contractor shall be present during scheduled job visits and shall, upon request open boxes, panels, switchboards, or other equipment and shall operate equipment, apparatus, or systems to demonstrate compliance with contract

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 55: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

GENERAL REQUIREMENTS 16100 - 11

documents.

D. Observation reports will be forwarded to the Contractor for prompt correction of unsatisfactory work and completion of incomplete work. Failure to note improper or incomplete work in an observation report does not relieve the Contractor of the responsibility for complete and correct work conforming to the contract documents.

3.10 ACOUSTICAL CONTROL WORK

A. Fixture ballasts shall have a class "A" sound rating throughout. Contractor will be required to replace any noisy ballasts at his expense.

B. All electrical conduit connected to vibrating equipment or transformers shall be flexible type at least 3 feet or 20 diameters, whichever is longer, installed very slack in such a manner as to prevent sound or vibration transmission from the equipment.

C. Contractor shall take any further measures necessary to prevent sound being caused or transmitted by or through electrical equipment and material.

END OF SECTION 16100

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 56: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

BASIC MATERIALS AND METHODS 16300 - 1

SECTION 16300 - BASIC MATERIALS AND METHODS PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the contract, including General and Supplementary Conditions and Division 1 Specification sections, apply to this section.

1.2 SUBMITTALS

A. Comply with requirements of Section 01300 - SUBMITTALS.

B. Material List and Manufacturer's Literature.

1.3 CUTTING AND PATCHING

A. Perform drilling, cutting, and patching of the general construction work whether existing or new, which may be required for the installation. Patch with the same materials, workmanship and finish as the original work and accurately match all surrounding work. Such work shall be done by a craftsman accredited in the applicable trade and be acceptable to the Architect. Refer to other sections of work under this specification for additional information.

PART 2 - PRODUCTS

2.1 IDENTIFICATION SYSTEMS

A. Nameplates: 1. Provide nameplates for safety switches, breakers mounted in

switchboards, relay cabinets, signal terminal cabinets, individually mounted enclosed breakers, panelboards, timeclocks, remote control switches and similar items. Nameplates shall be laminated black-white-black backlite or phenolic plastic with 1/4-inch high lettering engraved through the outer covering except where specifically described otherwise. Affix with self-tapping machine screws (no rivets or glue). The screws shall not project beyond the backside face of enclosure doors, or panels.

2. Labels for switchboards shall be minimum 3” wide and 1” tall with ½”

letters. 3. Labels for device plates shall be preasure sensitive, machine printed tape

with black characters on a clear background. Kroy, Brother, or equal. 4. Inscribe as indicated on drawings or herein. If not indicated, the

inscription should describe the equipment served. 5. Refer to DEVICE PLATES for engraving and labeling requirements. 6. Refer to WIRE AND CABLE for tagging and color coding requirements.

2.2 CONDUIT PAINT

A. All conduit paint shall be non-toxic, permanent and colored per the attached schedule. Provide a minimum of one 6” wide painted conduit section every 10’ of

lineal conduit run.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 57: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

BASIC MATERIALS AND METHODS 16300 - 2

1. Emergency power conduit Green 2. Security, access conduit Blue 3. Fire alarm conduits Red 4. Tele/data conduit yellow 5. BMS conduit Orange

2.3 PAINT, FINISHES AND COLORS

A. General: Painting requirements of this Subsection are supplementary to the Painting Sections of these specifications.

B. Switchboards, panels, terminal cabinets, equipment enclosures, wireways, boxes, conduit etc.: Standard manufacturers finish unless otherwise noted hereinafter.

C. Surface and Flush Boxes: Paint to match adjacent surfaces.

D. Exposed conduit: Paint to match adjacent surfaces.

E. Ferrous metal miscellaneous parts (except stainless steel): Galvanized in accordance with ASTM A123 or A153.

F. Wiring devices, device plates and floor boxes in public areas: As specified in WIRING DEVICES and DEVICE PLATES Subsections.

2.4 WIRING DEVICES

A. Acceptable Manufacturers: Arrow Heart, Pass & Seymour, Hubbell, Leviton, or equal.

B. Switches: 1. AC general use snap switches shall be toggle handle, quiet operating,

premium specification grade, UL listed and verified to meet Federal Specification W-S-896 and NEMA WD-1 heavy duty tests.

2. Switches shall be rated 120/277 volts 20 amps. Switches shall have HP ratings as follows:

3. 20 amp rating - 1 HP @ 120V, 2 HP @ 240V. 4. Toggle handle color shall be selected by Architect. 5. Switches shall be constructed with oversized silver-cadmium alloy

contacts, permanent lubrication, and binding head screws suitable for #10 AWG wire. Connection shall be made by wrapping the wire around the screw or tightening a screw clamp. Push-in type connections are not acceptable. Switches may have built-in pigtail connection in lieu of screw connection. Switches shall have means for grounding.

6. Switches shall be Pass & Seymour #20AC1, or equal. 7. Keyed and momentary contact switches, required but not listed, shall be

of the same manufacturers and identical quality as those listed above.

C. Receptacles: 1. Receptacle outlets shall be “Extra Hard Use” Specification Grade of

standard NEMA configuration. 2. General receptacle outlets shall be 20 amp, 125 volt, 2 pole, 3 wire. The

attachment screw shall have an automatic grounding clip. A green

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 58: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

BASIC MATERIALS AND METHODS 16300 - 3

grounding screw shall be mounted on the bridge which shall run around the back of a break and impact resistant nylon body. The bridge shall be securely locked to the body. Outlets shall be UL listed and verified to meet Federal Specification WC 596 and NEMA WD 1 heavy duty performance tests. Contacts shall be extra heavy duty copper alloy or bronze double wipe type. Outlets shall have binding head screws suitable for #10 AWG wire. Connection shall be made by wrapping the wire around the screw or tightening a clamp. Push-in type connections are not acceptable. Outlets may have built-in pigtail connection in lieu of screw connection.

3. Color of receptacle outlet fronts shall be ivory. 4. Receptacles connected to emergency circuits shall be red.

D. Outlets shall be Pass & Seymour 5362 series, Hubbell HBL5362 series, or equal.

E. Ground fault circuit interrupter (GFCI) outlets shall be specification grade 20 amp duplex grounding receptacle suitable for mounting in a standard outlet box. A ground current of 5 milliamps + shall trip the circuit open in less than 1/30 second. There shall be a test button and a reset button on the front. Each GFCI outlet shall be tested after installation and results of the test submitted in writing. GFI receptacles shall be Pass & Seymour 2091 series, Hubbell GFR5352 series, or equal.

F. Industrial type outlets shall be by Crouse-Hinds Appleton, or Russellstoll, and shall be rated for the amps, volts, poles, and wires indicated on the drawings.

G. Special power outlets, not listed above, shall be standard NEMA configuration as noted on drawings and shall be of at least equal grade and quality to those listed above.

2.5 DEVICE PLATES

A. Acceptable Manufacturers: Pass & Seymour, Hubbell, Leviton or equal.

B. Plates for flush wiring devices, including telephone outlets, in all office areas shall be smooth, high impact unbreakable thermoplastic, Pass & Seymour “SRP”

Series, or equal. Plates for flush wiring devices, including telephone outlets in all other areas shall be stainless steel. Wiring devices and device plates shall be the same manufacturer. Color shall be ivory.

C. Provide switch and device plates with engraved designations wherever called for by words, set off in quotation marks near a switch location, or by symbol. If inscription is not detailed on drawings request it from the Architect. Engraving shall be in 3/16-inch high block type letters filled with black enamel.

D. Finish plates for all surface mounted devices shall be pressed steel galvanized. Coverplates for flush mounted junction boxes in finished areas shall be selected by Architect.

E. For surface interior outlet and junction boxes of the pressed steel knockout type, use 1/2-inch raised galvanized steel plates for devices and flat galvanized steel for blank plates.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 59: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

BASIC MATERIALS AND METHODS 16300 - 4

F. Provide a plate for each outlet, receptacle, switch, device and box.

G. Each switch, receptacle device, etc. which is installed in a outlet box with coverplate shall have the panel and circuit number labeled with 3/16" high black lettering at top of coverplate. I.E.: “3A-6”

H. Plates for exterior roof locations shall be metallic with gaskets and shall have non-lockable weatherproof spring loaded covers for devices, Pass & Seymour #WPH-26, or equal.

I. Plates for exterior wall locations shall be key lockable, heavy duty hinged type. Pass & Seymour #4600-26, or equal by Cole.

J. Ganged devices shall have gang plates exactly matching the arrangement and quantity of devices. All plates shall fit the box perfectly with no field modification necessary. Plates on surface mounted boxes shall not overhang the box. All plates shall be manufactured specifically for the type of outlet, device and box to which they are applied.

2.6 SURFACE MULTI-OUTLET RACEWAY SYSTEM

A. Provide ISODUCT Series AL 4400 multioutlet raceway system where indicated on drawings. Raceways shall be decorative, low profile extruded #6063-T5 aluminum alloy with a minimum wall thickness meeting U.L. requirements of .078". Finish of raceway shall be 204R1 class 2 anodize. Minimum anodize coating shall be .004" thick. Raceways' cross section shall be 2-1/4" deep by 4-3/4" high without partition.

B. Multioutlet systems shall consist of a factory assembled product including body, covers, end caps, fittings, receptacles and wire. Manufacturer shall cut each length of raceway to the exact job requirements, which will be in 12" increments, no one section exceeding 23'. Contractor shall verify length prior to placing order. Field cutting of raceways will not be permitted. Raceway shall set plumb, square level, and in alignment with casework or furniture as required. Secure raceway to structural surface in accordance with manufacturer's directions.

C. Each multioutlet assembly shall contain the quantity and type of receptacles specified and as shown on the plans. Each receptacle shall be installed in a 12" extruded cover to match the blank cover of the raceway. Blank section shall also be complete with 12" blank covers. Under normal usage, the cover of the raceway shall be securely held in place by extruded protrusions. All cover plates shall be removable by use of a standard flat screwdriver without marring the extrusion finish. Cover sections containing receptacles shall have devices factory installed so that cover plate and receptacle are removable as a single integral unit. Each receptacle shall be identified by means of taped on lettering (Weber, Kroy, Brother or equal) noting the panel number and circuit number from which it is fed. Locations of conduit only entries shall also be identified by taped on lettering. Receptacles other than NEMA 5-20R configuration shall also be provided with voltage (120V, 208V, etc.), amperage and phase identified in the same method. All receptacle circuits shall be factory pre-wired, leaving a pigtail at each receptacle for field connection within the raceway.

D. Receptacles shall be connected to the circuit wiring within the raceway by means

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 60: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

BASIC MATERIALS AND METHODS 16300 - 5

of Scotchlok #562 tap connectors. Special wiring arrangement shall be as detailed on drawings. Ground continuity shall be maintained throughout each individual raceway length by means of factory installed code sized grounding conductors. Ground stud shall be accessible from the front by removing the cover and shall be mounted in the bottom plate. Wiring entry to raceway shall be via a 2" diameter grommeted nipple.

2.7 BACKBOARD

A. Type AC, Interior grade, 3/4-inch thick fire-rated plywood with exterior waterproof glue. Mount with "A" side out. Prime and then paint with 2 coats of semi-gloss oil base enamel to match color of adjacent surface. Paint shall not cover fire rating label. Backboards shall be used only in interior locations.

B. Securely mount backboard to wall structure. Use expansion anchors in masonry and concrete, sheet metal screws supplemented with toggle bolts in drywall with metal studs, and wood screws supplemented with toggle bolts in drywall with wood studs.

C. Neatly arrange equipment on board and attach to board with round head wood screws.

PART 3 - EXECUTION

3.1 EQUIPMENT DISCONNECTS

A. Provide equipment disconnect switches as indicated on drawings and as required to conform to Code. Safety switches shall be horsepower rated when used with motors. Toggle switches and toggle type manual motor starters without overload protection shall be used, within their ratings, in lieu of safety switches for motor disconnects where shown on the drawings.

3.2 INSTALLATION OF OUTLETS AND EQUIPMENT

A. All outlets, wall switches or wiring devices may be located within a radius of twelve feet from original location shown on plans at no additional charge to the Owner if such request is made prior to installation of the rough-in for the item.

B. Accurately place outlet boxes independently and securely fasten to the structure and, in concealed work, provide with plaster rings and set flush with finished surface of walls or ceilings.

C. Coordinate the location and mounting heights of wall-mounted receptacles, fire alarm and signal devices switches with casework, shelving, furniture, and other equipment shown on Architectural and Interiors drawings and Americans with Disabilities Act (ADA), UBC, ANSI, and all other applicable codes governing the project. Conflict between electrical and architectural drawings shall immediately be brought to the attention of the Architect for resolution before the installation of the devices.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 61: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

BASIC MATERIALS AND METHODS 16300 - 6

D. Outlet and junction boxes for interior use shall be galvanized, one-piece pressed or welded steel, knockout type, except where other types of boxes are indicated or specified. In masonry or concrete construction waterproof boxes manufactured for that purpose shall be used. Plastic, fiber or composition boxes will not be permitted.

E. Protectively cover all devices, outlet boxes, cabinets, etc., before plastering and painting.

3.3 CONCRETE HOUSEKEEPING BASES FOR EQUIPMENT

A. Floor standing switchboards, transformers, and similar equipment shall be mounted on housekeeping concrete bases.

B. Bases shall be minimum 3-1/2 inch high above finish grade and shall extend 1-inch beyond edge of equipment unless specifically indicated otherwise. Verify size of equipment before fabrication of base.

3.4 FIRE RATED SEPARATIONS

A. Where electrical equipment or materials of this Division penetrate fire separations, maintain the integrity of the separation by providing Code approved fire rated penetrations or by providing an enclosure around the penetration which effectively continues the separation. Refer to other sections of this Division for supplementary requirements to these basic requirements.

3.5 SEISMIC RESTRAINTS

A. Provide the work in compliance with the most stringent seismic requirements for Zone 4, of applicable Codes including the Title 24 and California Code of Regulations (CCR) Uniform Building Code, but with the requirements herein as minimum standards. Provide seismic restraints for materials and equipment of this Division, including (but not limited to) the items listed below. The attachments shall resist forces applied to the center of gravity of the components. Criteria shall be the operating weight of the item times .5g for horizontal forces and .33g for vertical forces. Design for the horizontal force to be applied in any direction. Wall mounted or suspended components shall, in addition, resist a downward force of 200 pounds minimum added to the operating weight.

B. Switchboards, transformers, and all free-standing panels or cabinets and similar equipment.

C. Suspended lighting fixtures.

D. Lighting fixtures integral with ceiling or directly mounted to ceiling.

E. Suspended conduit hangers and trapezes.

F. Cable tray.

G. Suspended electrical conduit, 2-1/2" nominal size and larger, shall have individual hangers not longer than 12" from the top of the pipe to the bottom of the support for the hanger. If a longer hanger is used, Contractor shall apply

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 62: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

BASIC MATERIALS AND METHODS 16300 - 7

seismic restraints. Supporting calculations and details shall be submitted for Title 24 compliance review.

H. Four #9-12 gauge hanger wires shall be provided to each recessed troffer one located at each diagonal corner. In addition troffers shall be fastened with two self tapping screws at each end of fixture through housing to main runners of the T-bar grid. Installation of these screws shall in no way deform the fixture housing. Provide spacers between the fixture housing and the T-bar grid where required.

I. Provide bracing and anchorage of conduit hangers and trapezes in accordance with SMACNA published "Guidelines for Seismic Restraints of Mechanical Systems".

J. Pendant, suspended, or stem mounted lighting fixtures shall have approved earthquake resistant hangers if code required and have movable joints at ceiling and fixture when more than one stem is used per fixture. In addition, fixtures shall have steel stranded aircraft cable attached to the structure and to the fixture at each point of support, in addition to the fixture hanger. Cables shall be installed without slack and shall be capable of supporting four times the vertical

or other means of bracing shall be added to prevent the fixture from swinging against the other object.

K. Carefully review the space available to insure that the restraint systems proposed will not impair the required equipment clearance, working space or access.

L. Submit details of the seismic anchorages and receive approval of the Architect prior to installation. Details shown on the drawings are for reference only and may not be suitable for the actual equipment to be installed. Exception: Details for seismic anchorage may be omitted for equipment installed on a floor or roof and weighing less than 500 lbs, but the installation shall be subject to the approval of the Architect.

3.6 CHECKING AND TESTING OF EQUIPMENT AND SYSTEMS

A. Switchgear, panels, disconnects, contactors, transformers, and other equipment installed under this section shall be inspected for defects, and tested for proper operation.

B. Enclosures and cabinets shall be checked for cleanliness inside and out and for defective or damaged finish.

C. Systems shall be tested for short circuits, open circuits and wrong connections and shall be free from mechanical and electrical defects. Circuits shall be tested for proper neutral, phase rotation, and ground connections. Ground rods shall be tested for resistance and a report submitted listing each rod by location and its resistance to ground.

D. GFCI outlets shall be tested by applying a ground current of 5 milliamps, + 1 ma, which shall trip the unit off in less than 1/40 second. Each test shall be recorded

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 63: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

BASIC MATERIALS AND METHODS 16300 - 8

and the record shall include the type of test equipment used, results of test, location of device tested, date of test, and name of test technician. "Test" button operation shall be successfully demonstrated but will not be acceptable as a substitute for the trip test described

E. Where required or directed, systems shall be tested in the presence of the Architect to demonstrate that equipment furnished, installed or connected functions in the manner intended.

F. The Contractor shall furnish all necessary instruments and equipment and all power sources and connections required for making required tests, and shall immediately correct any defective work at no additional charge.

G. Bolted connections shall be torque tightened to manufacturer's specifications.

H. For additional checking and testing of systems see the Sections where those systems are specified.

END OF SECTION 16300

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 64: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

WIRING METHODS, RACEWAYS

AND CONDUCTORS 16400 - 1

SECTION 16400 - WIRING METHODS, RACEWAYS AND CONDUCTORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the contract, including General and Supplementary Conditions and Division 1 Specification sections, apply to this section.

1.2 SUBMITTALS

A. Comply with requirements of Section 01300 - SUBMITTALS.

B. Material List and manufacturer’s literature. 1.3 ACCEPTABLE MANUFACTURERS

A. Metallic conduit Triangle, PWC, Wheeling Steel, Youngstown Sheet & Tube Co., Allied Tube & Conduit Co., Wheatland, or equal.

B. Non-metallic conduit Carlon, CertainTeed, Pacific Western, or equal. C. Liquidtight flexible American Brass Co., Colum bia Cable and

conduit Electric Corp., International Metal Hose, Appleton, or equal.

D. Conduit bodies and Appleton Electric, Crouse Hinds,

Fittings Thomas & Betts, Steel City, Gedney Electric Mfg. Co., or equal.

E. Floor boxes Walker, Lew, Steel City, Hubbell, Thomas & Betts, Russell and Stoll, or equal. F. Wireways Square D, Hoffman, Nepco., or equal. G. Wire and cable (600V) Cablex, Anaconda, Okonite, Paranite, Circle,

Phelps-Dodge, Simplex, General Cable, Cyprus-Rome, Pirelli, Triangle, or equal.

H. Wire pulling compound Minerallac, Wyrease, Ideal, or equal. I. Solderless connectors Burndy, OZ, T&B, Dossert, or equal.

and lugs

J. Underground Pullboxes, Newbasis, Jensen Precast, Utility Vault Co., and Handholes or equal.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 65: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

WIRING METHODS, RACEWAYS

AND CONDUCTORS 16400 - 2

K. Cable Tray Chaufaut, Cope, Huskey, P-W Western, Square D, or equal.

PART 2 - PRODUCTS 2.1 UNDERGROUND PULLBOXES

A. Pullboxes (less than 24" X 36") for exterior underground use shall be reinforced, precast, concrete electrical type.

B. Boxes shall consist of a body, cover, with clear interior dimensions as shown on the drawings.

C. Covers shall be concrete with finger hole bolt down type. All exposed steel shall be galvanized. Concrete covers shall fit flush and without rocking. Chipped, cracked, or badly fitting covers will not be acceptable.

D. Mark all covers with permanent raised or depressed letters reading “Lighting", or

applicable designation. No abbreviations.

2.2 UNDERGROUND HANDHOLES

A. Pullboxes (24" x 36" or larger) for exterior underground use shall be reinforced, precast, concrete electrical type.

B. Boxes shall consist of a body, cover, extensions and base, with clear interior dimensions as shown on the drawings.

C. Covers for 24" X 36" pull boxes shall be 1 piece, bolt-down type. Covers for 48" X 48" or larger pull boxes shall be two piece torsion hinged type. Covers shall be traffic as called for on drawings with galvanized steel checkered plate with angle frame. All exposed steel shall be galvanized. All bolts shall be stainless steel. Mark all covers with permanent raised or depressed letters reading "Electrical", "Communications", or applicable designation. No abbreviations.

2.3 CONDUITS

A. General:

1. Types and applications shall be in conformance with Codes and with this specification.

2. Minimum sizes: 3/4-inch underground or in concrete except that 1/2-inch is permissible where such a run terminates in a box containing a single wiring device. 3/4-inch minimum for homeruns.

3. Rigid aluminum conduit is not acceptable.

B. Types: 1. Rigid steel conduit (RSC) and fittings: Hot-dip galvanized or sherardized. 2. Electrical Metallic Tubing (EMT) and fittings: Same finish requirements

as for rigid steel. Use permitted only in dry, concealed locations (above suspended ceilings and inside stud walls) and interior exposed locations (10 feet minimum above floor) where not subject to mechanical damage.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 66: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

WIRING METHODS, RACEWAYS

AND CONDUCTORS 16400 - 3

Fittings: Liquid tight compression gland type, Steel City #TC715 or T & B #5123 series or set screw type, T&B or "ETP", or equal.

3. Flexible steel conduit and fittings: Flexible conduit shall be galvanized steel and shall be used where shown on the plans and to connect conduit systems to motors, direct wired and vibrating equipment, and as a final connection to lighting fixtures in accessible dropped grid type ceilings. Flex shall not be used as a wiring system instead of EMT. Flex shall be used instead of EMT only where EMT would be impossible to use in interior dry frame or stud construction in conformance with codes and ordinances and where permission is granted upon request, by the Architect. Flexible conduit shall have a code sized grounding conductor run with it and shall have approved grounding fittings. Where used in damp or wet locations flexible conduit shall be of the liquid tight type with outer neoprene jacket and suitable liquid-tight fittings. Fittings: "Jake" or malleable iron squeeze type.

4. Liquidtight flexible steel conduit and fittings: Same finish requirements as for flexible steel conduit except PVC jacketed. Use in lieu of standard flexible conduit in damp or wet locations and for connections to motors. Fittings: Appleton ST series or American Brass Sealtite type U.A., or equal.

5. Rigid plastic conduit (RPC) and fittings: Shall be used for underground work. Plastic conduit for direct burial and concrete encasement installations shall conform to NEMA TC-2 and shall be PVC equal to Carlon Type EPC-40 (Schedule 40). EB duct shall not be allowed. Types named are minimum acceptable for the applications indicated. Conduit, fittings and solvent cement shall be produced by the same manufacturer and shall be chemically and mechanically compatible.

C. Installation - General: 1. Continuously check the work of the other Divisions to prevent any

interference between the various installations. Should structural difficulties or work of other Divisions prevent the routing of conduit as indicated on the drawings, make necessary deviations therefrom as directed by the Architect.

2. Route conduit so as to clear beams, plates, footings and structural members, whether or not indicated on the plans. Do not run conduit through any structural member of the building, except as specifically directed by the Architect. Under no circumstances run conduits through column footings or grade beams.

3. Conduit installed in concrete work shall be carefully laid and rigidly supported in the forms in such a manner as to provide proper clearance so that all boxes and outlets will be in exact locations after concrete has set and forms have been removed.

4. Concrete slabs on grade: Conduit shall not be installed in slab on grade. 5. Where conduit penetrates a fire rated separation, any of the following

packing methods may be used to restore the integrity of the separation if Code approved: cement, mineral fiber sprayed with a flame retardant coating, or Dow Corning 3-6548 RTV silicon foam, 3M caulk #CP25, 3M putty #303, or equal. Seal shall be water tight and shall be accomplished prior to wire pulling.

6. Where a conduit enters building through the concrete foundation wall or

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 67: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

WIRING METHODS, RACEWAYS

AND CONDUCTORS 16400 - 4

floor below ground water level, a watertight entrance seal shall be used. These seals shall be 0.Z. Type "FSK" or "WSK", or as equal.

7. Do not run conduit closer than 6-inch to any uninsulated hot water or steam pipe, heater flue or vent. If pipe is insulated, the clearance may be reduced to 2-inch. Provide condulets for exposed runs of conduit where junction, bends or offset are required, whether such condulets are indicated on the plans or not. No bends are permitted around corners, beams, wall or equipment. No running threads are permitted. Run a die over factory threads to ensure that they are clean and free from all coating material and that good metallic contact with the fittings is obtained. Paint the exposed portion of field cut threads with a suitable zinc rich paint.

8. Upon completion of each run of conduit, test the run and clear it of all obstructions. Plug each conduit end with conduit pennies and bushings or manufacturers seals until ready for pulling wire. Provide a 200 pound test nylon or polypropylene pull rope in each empty conduit, tie off rope at each end, and provide an identification tag on rope at each end.

9. Where panelboards and cabinets are installed flush in walls, extend empty conduits from panel to an accessible space above or as indicated on plans. Provide a minimum of one 3/4-inch conduit for each three single pole spare circuit breakers or spaces, or equivalent, but not less than three conduits.

10. All Fire Alarm system conduits shall have a 2" wide band of red paint every 10 feet along the length.

D. Installation - Above Grade: 1. All conduit above grade or inside of a structure shall be metallic, except in

masonry and concrete walls schedule 40 may be used. 2. Run conduit concealed, except as otherwise indicated. 3. Run exposed conduit parallel with or at right angles to walls or as directed

by the Architect. 4. Where conduits are placed in partitions necessitating cutting of any

structural member, provide supports as directed by Architect in accordance with applicable structural requirements.

5. Locate conduit so as not to obstruct access or service to equipment. 6. Conduit passing through the roof: Flash and counterflash and/or provide

a pitch pocket. Method shall be compatible with roofing system and acceptable to the Architect.

7. Conduit 1-inch and smaller over metal channel for lath and plaster or acoustical ceilings shall be tied to the supporting channels with 12 gauge galvanized tie wire spaced at a maximum of 10-feet intervals. Conduits shall not obstruct accessibility of ceiling or removal of panels. Do not use ceiling wires for support. Support exposed conduit 1-inch and smaller from building with T & B, or equal, pipe straps spaced at a maximum of 10-feet intervals. Attach supports with machine screws, nuts and lock washers in metal; wood screws in wood; and expansion shields or inserts in masonry or concrete. Perforated strap iron shall not be used. Conduits larger than 1-inch shall be suspended on pipe racks with Grinnell No. 107B, or equal, split-ring hangers and rods from concrete inserts.

8. Rigid steel conduit (RSC) shall be installed in interior wet locations,

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 68: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

WIRING METHODS, RACEWAYS

AND CONDUCTORS 16400 - 5

exposed exterior locations, and wherever specifically shown. Where installed in exterior locations, RSC and fittings shall be encased in PVC coated for corrosion protection. Conduit, from slab to bottom of surface mounted panelboards, distribution panels, device outlet boxes, terminal cabinets, where exposed, shall be RSC. Conduit concealed in wall from slab to flush mounted panels, distribution panels, terminal cabinets, and all device outlet boxes for all systems shall be EMT except to devices mounted at 18" or less in which case flexible conduit may be used. Contractor shall be allowed a dimension of 3 inches above slab to make transition from PVC to EMT, flex or RSC. All conduit on the roof shall be rigid steel.

9. Conduits which cross building expansion joints or seismic joints shall be provided with expansion/deflection couplings, Crouse Hinds “XD” Series,

or equal where building movement exceeds the rating of expansion/deflection couplings, provide suitable flexible metallic conduit installation across joint.

E. Installation - Underground: 1. Bury underground conduit (except under buildings) to a 24-inch minimum

depth below finish grade to top of concrete envelope. Deeper burial depths shall be as indicated on drawings, or as required to meet minimum spacing from other utilities lines and obstructions.

2. Concrete: All underground conduits shall be concrete encased. Provide a 3-inch thick (minimum) concrete cover around conduits below grade. Provide not less than 2-inch of concrete between adjacent conduits in the same encasement except that power conduits shall be separated 6-inch minimum from signal (control/instrumentation/communications/ public telephone) conduits. Concrete shall be minimum of 2000 psi. Slurry backfill is not acceptable.

3. Provide non-metallic spacers and chairs to prevent deflection of the conduits. For concrete encased duct banks, tie conduits to spacers and anchor to prevent floating or displacement during pouring of concrete.

4. Exception: Provide utility service conduits in accordance with this Section and with serving utility requirements except that the portion underground beyond 5-feet from the building need only meet serving utility and Code Requirements.

5. Exposed exterior risers above grade shall be PVC coated rigid galvanized steel unless otherwise noted. Risers that are concealed above grade or slab that terminate in equipment or structure shall be EMT.

6. The ends of all underground conduits entering buildings shall be capped or sealed with acceptable compound, such as Crouse Hinds "Chico A", or equal, after installation of wire. Cap empty conduit stubouts at both ends.

2.4 WARNING TAPE

A. Provide a plastic warning tape in the backfill over the ductlines approximately 12 inches below grade. Tape shall be run continuously along the entire length of the underground utility lines. Tape shall be polyethylene plastic manufactured specifically for warning and identification of all buried utility lines. Tape shall be of the type provided in rolls, 6-inches minimum width, color coded for electric lines (red), and communications (orange) with warning and identification imprinted in

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 69: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

WIRING METHODS, RACEWAYS

AND CONDUCTORS 16400 - 6

bold black letters continuously and repeatedly over entire tape length. Tape shall consist of top and bottom layers of B-721 polyethylene or polyester with a center metallic foil core suitable for locating by a conventional detector at the specified depth. Tape shall be by Thor Enterprises, Brady, Seton, or equal. Submit data sheets as specified under "SUBMITTALS".

B. Conduit Location Markers: Conduits stubbed or capped-off underground shall have their location identified with a concrete marker 6" x 6" x 12" high with a flush brass plate set in the 6" face. Identification of the conduit shall be stamped or engraved into the plate and the marker set flush with finished grade. Show exact location of markers and identification markings on as-built drawings. Submit data sheets as specified under "SUBMITTALS".

C. Excavated materials not required or unsuitable for backfill shall be removed from the project site. Provide sheeting and shoring as necessary for protection of work and safety of personnel. Remove water from excavations by pumping or other approved method.

D. Backfill shall be placed in layers not more than 6" thick and each layer shall be compacted. Backfilling shall progress as rapidly as the construction, testing and acceptance of the work permits. Backfill shall be free from roots, wood, scrap material, and other vegetable matter and refuse. Compaction of backfill shall be to 95 percent of maximum density.

E. Backfill around underground structures such as handholes shall consist of earth, loam, sand, clay, or sand and gravel, free from large clods of earth or stones over one inch size. Backfill materials shall be placed symmetrically on all sides in loose layers not more than nine inches deep. Each layer shall be moistened, if necessary, and compacted with mechanical or hand tampers to 90 percent compaction.

2.5 UNDERFLOOR TRENCH AND DUCT SYSTEMS

A. Provide a complete underfloor trench and duct system for power, telephone, and data located, constructed, and arranged as shown on the plans.

B. The system shall consist of steel trenches with covers, raceways, junction boxes, and outlets complete with all couplings, supports, inserts, elbows, and caps, adapters and other fittings, devices and hardware necessary for a complete integrated system.

C. Manufacturer shall be Walker, Square D, or equal. All components shall be by the same manufacturer and shall be designed for assembly as a system.

D. Power duct shall be Walker #2, Square D "standard", or equal. Telephone and data duct shall be Walker #4, Square D "super", or equal. Ducts shall be blank or have inserts as shown on the plans. Inserts shall be 24" on centers. Inserts shall be capped and plaster-of-paris poured and set in each cap before concrete is poured. The first and last insert on each run shall have a marker screw set flush with the finished floor surface.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 70: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

WIRING METHODS, RACEWAYS

AND CONDUCTORS 16400 - 7

E. Junction boxes shall be arranged for duct entries as shown on the plans. Covers shall be adjusted flush and shall have linoleum, tile, or carpet pans where applicable. Provide blank-off plugs for unused duct entries.

F. Trenches shall consist of base sections with barriers as shown, and an adjustable upper assembly. Base section and barriers shall be minimum 14 gauge galvanized steel. Upper adjustable assembly shall consist of minimum 15 gauge galvanized steel telescoping side panels, side screen strips, and flat coverplates. Upper assembly shall be designed to be continuously supported independent of adjusting screws, side screens, and telescoping side panels shall be mechanically locked into concrete fill to allow no movement or vertical adjustment of coverplate after concrete has set. Coverplates shall be fabricated from 1/4" thick steel plate, hot dip galvanized after fabrication and roller leveled again after galvanizing. Plates shall be true and level, in easily handled sections, and gasketed along the supporting members. Plates shall be held in place during concrete placement with flat head, countersunk machine screws. Replace stock screws with special stainless steel flathead screws for finished installation. Provide a tapped hole at each corner of each plate for insertion of lifting screws. Provide an adjustable double trim at edges of plate and along each side of trench. Trim shall be aluminum or stainless steel of a proper height to finish flush with floor covering. Verify type of floor covering to be used. Trim strips shall be attached to upper assembly independent of coverplates.

G. Trench and duct systems shall be accurately aligned and securely braced before concrete pour. Top of duct inserts shall be set by transit 1/8" below finished floor level. Duct and trench supports shall be set on brick or concrete pads and staked in place. All joints in the system shall be sealed with approved tape or waterproof compound so that no foreign material or moisture can enter the system trenches and ducts. Ducts shall be set with clearance for a minimum of a 2" concrete envelope around sides and bottom. Concrete shall be carefully placed to assure that the components remain in exact position and that a complete envelope is formed with no voids.

H. Insert markers and hold-down screws shall be set in escutcheons and shall be pulled down tight to the floor covering so that the edges cannot be felt.

I. Provide service fittings as shown on the plans. Electrical floor outlets shall be Walker #513 AL-DPS-G, Square D #G2-CA, or equal. Telephone outlets shall be Walker #507-AL, Square D #G5-100, or equal.

J. Receptacles shall comply with the specification for "RECEPTACLE OUTLETS".

K. Submit shop drawings as required under "SUBMITTALS".

2.6 WIREWAYS AND WIRING GUTTERS

A. Construct of galvanized sheet steel which has been primed and given a final coat of grey enamel. Covers shall be hinged and fastened with brass machine screws spaced not more than 12-inch apart. When covers are on the bottom, provide removable wire supports not more than 3-ft. apart. Sections shall be securely attached to each other and to cabinets, boxes, or duct to insure ground

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 71: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

WIRING METHODS, RACEWAYS

AND CONDUCTORS 16400 - 8

continuity. Provide copper equipment grounding conductors throughout the wireway system. Securely attached or support the wireway or gutter from the building structure at points no more than 4-feet apart. Size shall be as indicated on drawings unless larger is required to conform to NEC standards. When suspended from roof or ceiling, the support spacing shall be not more than 4-feet and 3/8-inch diameter rods shall be used. When attached to wall, use expansion anchors in masonry and concrete, sheet metal screws supplemented with toggle bolts in drywall with metal studs, and wood screws supplemented with toggle bolts in drywall with wood studs.

B. Power gutter assemblies: Mount gutter to a 3/4-inch plywood backboard unless otherwise noted. Gutter and backboard shall be sized to accommodate the equipment. Arrange equipment neatly and symmetrically on backboard.

C. Surface raceway shall be extruded aluminum with anodized finish. Where shown attached to curved surfaces a template of the radius of the surface shall be provided to the manufacturer. The curve of the raceway shall perfectly match the radius of the surface it is to be mounted on. Bending of the raceway shall be done at the factory. Raceway shall be Wiremold.

2.7 CABLE TRAY

A. Ladder type, hot dipped galvanized steel cable tray with nominal 4-inch sides and 9-inch rung spacing, UL listed, and conforming to NEMA VE-1. NEMA Class 12B span/load designation (12 foot support span/75 lbs. per foot load). Width of tray shall be 18 inches except where otherwise indicated on drawings. Tray system shall be complete with splice plates, end plates, dropouts, and miscellaneous hardware. Change-of-direction fittings shall have the manufacturer standard radius. All edges, fittings, and hardware shall be finished free from both sides of smoke and fire partitions. Cables run through smoke and fire separations shall be installed in 4-inch rigid steel conduits with grounding bushing, extending 12 inches beyond each side of the partitions. Connect the grounding bushing on the conduit to a grounding terminal on the tray, with #2 bare soft drawn copper wire. The installation shall be sealed to preserve the smoke and fire ratings of the partitions penetrated.

B. Basket type cable tray may be used. EZ-Tray by CABLOFIL or approved equal.

C. Support the tray system at not more than 6-ft. intervals, at each end, within 2-ft. of each change-of-direction fitting, and at the center of arc of each fitting. Supports shall be by hanger rods or wall brackets attached to concrete inserts or bolted to structural members. Each support assembly shall support 400 lbs. minimum. Runs longer than 20-feet shall be side braced at the end of run and at approximately equal spacings (not to exceed 20 feet) along the run. Refer to Section 16300, Seismic Restraints subsection.

2.8 OUTLET, JUNCTION AND PULL BOXES

A. Outlet boxes, junction boxes and covers shall be galvanized one-piece pressed steel knockout type. Exceptions: Exposed conduit boxes shall be cast metal if connected to rigid or intermediate conduit, 4-11/16 inch square by 2-1/8 deep

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 72: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

WIRING METHODS, RACEWAYS

AND CONDUCTORS 16400 - 9

boxes may be of welded construction.

B. The size of each box for light outlets shall be determined by the number of wires or conduits, or size of conduits, entering the box but shall be not less than 4-11/16-inch square and 2-1/8 inch deep, unless prohibited by structural conditions.

C. All junction boxes on the drawings shall be minimum 4-11/16-inch square by 2-1/8-inch deep.

D. Provide pull boxes and junction boxes where indicated on plans or where required by Code. Size to properly accommodate conductors with Code requirements as minimum. When necessary pull and junction boxes are not indicated on drawings and are to be placed in a public space, coordinate the location with the Architect. Boxes of outlet box size which are in public spaces shall be flush mounted and shall have single gang ring and blank device plate painted to match adjacent surface.

E. Equip outlet boxes with plaster rings and extension as may be required. Provide manufactured "far side box supports", which shall be in contact with the gypboard surface behind the box.

F. For local switch outlets, provide 4-inch and 1 1/2" deep pressed steel boxes with switch plaster rings for one or two gangs. Where 2 gang, 20-ampere or larger switches occur, provide 4-11/16-inch square boxes with switch plaster rings.

G. For convenience outlets, etc., provide 4-inch square pressed steel boxes, or larger if necessary, with single gang plaster rings.

H. Use approved factory-made knockout seals in all boxes where knockouts are not intact.

I. Use offset bar hangers fitted with fixture studs to support outlet boxes in stud partitions and in furred or plastered ceilings.

J. Outlets for wall mounted telephones shall be in outlet box which is securely fastened to structure.

K. Ganged boxes shall be used whenever possible where drawings show outlets grouped at single location.

L. Boxes for in-floor flush outlets shall be cast iron, concrete tight Hubbell #B2436, or equal. Multi-gang floor box shall be used where indicated on the drawings. There shall be minimum of 1-1/4" external height adjustment and minimum 3/8" internal final adjustment. Top flange shall be rectangular and adjusted flush with the finished floor. Provide brass tile flanges. Cover shall be brass duplex flap type, equal to Hubbell #S3825, or equal for power, and brass 2-1/8" single type, equal to Hubbell #S2825, or equal, for telephone, signal and data systems, and Soundolier MRB, or equal series for projector and microphone jacks. Single and ganged floor boxes in carpeted areas shall be provided with clear polycarbonate carpet flange. Outlets shall be as specified in "RECEPTACLE OUTLETS".

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 73: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

WIRING METHODS, RACEWAYS

AND CONDUCTORS 16400 - 10

2.9 WIRE AND CABLE (under 600 volts)

A. General: Deliver wire and cable to the site in their original unbroken packages, plainly marked or tagged with UL label, size and insulation type, and manufacturers name.

B. Conductors: Soft drawn copper, solid or stranded for No. 10 AWG and smaller, stranded for No. 8 AWG and larger or for connections to vibrating equipment or control wiring. Minimum size No. 12 except as noted. Aluminum cable will not be permitted.

C. Insulation: Thermoplastic type THHN, THWN. Insulation for conductors #2 and larger shall be type XHHW. Provide high temperature insulations in abnormally high ambient temperatures as applicable. Equipment and electrode ground wires may be uninsulated in conformance with codes, and where indicated.

D. Connections and Terminations:

E. Use Pressure indentor type or self-threading spring wire connectors for sizes up to the catalog capacity of the connector. 3M Scotchlok, Ideal Supernut, Buchanan B-Cap, or equal.

F. Use clamp type pressure connectors complete with clip held insulating cover for large sizes or capacities. As manufactured by Burndy, O.Z., T & B or equal.

G. Wrap joints with two layers of plastic tape, half lapped, Scotch No. 33. Underground (below grade) splices shall be epoxy encapsulated.

H. Wiring in underground pullboxes shall be spliced using compression connectors and resin encapsulation kits, 3M Scotch-cast, or equal; or shrink tubing kits. Splices shall be completely waterproof.

I. Bolted connections to equipment or busbars shall be made with approved solderless compression type or set screw type lugs for wires No. 8 AWG and larger. Special connections shall be as shown on the plans. Binding screws may be used for size No. 10 solid and smaller.

J. Installation Under 600 Volts:

K. Install wiring in conduit unless noted otherwise. Type AC, MC and NM cable is not acceptable. Raceways shall be clean and dry before cable installation.

L. Do not use mechanical devices for pulling No. 2 AWG and smaller wire. Torque limiting types may be used for No. 1 and larger sizes but tensions shall not exceed cable manufacturer's recommendations.

M. Pulling compound: Minerallac #100, Wyrease, Ideal 77 Yellow, or equal.

N. Form wire into pigtail splices with 8-inch leads for connections to wiring devices and fixtures.

O. Any wire damaged as a result of installation or removal of wire under this

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 74: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

WIRING METHODS, RACEWAYS

AND CONDUCTORS 16400 - 11

Section, shall be pulled out and replaced with new at no additional charge.

P. Color Coding:

Q. General: Insulation for wires No. 6 and smaller shall be factory color coded and for larger sizes where available from the factory. When factory color is not available provide 1-inch band of colored pressure sensitive tape at each splice and termination point. Colors shall be consistent throughout the respective system and shall be identified as follows:

Equipment System A Phase B Phase C Phase Neutral Ground 120/208V 3Ø 4W Black Red Blue White Green 277/480v 3Ø 4W Brown Orange Yellow Gray Green w/stripe

R. Control, low voltage, and other systems shall have distinctive coloring different

from above.

S. All branch circuit conductors shall have their circuit numbers identified with tape labels on each phase conductor. Identification shall be provided at each outlet box, junction box, panelboard, contactor cabinet, or similar location.

T. Engraved nameplates shall be provided on all power and communications system feeders in underground pull boxes. Nameplates shall be fastened to feeders with plastic tie wrap. Description shall indicate origin voltage and destination of feeder, i.e: "From MSB to Panel HZA voltage, 208/120 volts".

U. Any conductors or signal cables left unconnected shall be identified by labeling with their intended use, circuit number, or other suitable information. All power and communications conductors or cables shall tape identified denoting circuit or zone numbers with tape type labels on each conductor of circuit or cable.

PART 3 - EXECUTION

3.1 INSTALLATION OF UNDERGROUND PULLBOXES, AND HANDHOLES

A. Pullboxes, and handholes ducts shall be assembled and installed in strict conformance with the manufacturer's instructions.

B. Pullboxes with open bottoms shall be set on a minimum of 12" deep sand base to allow for drainage. Handhole base sections shall be set on a minimum of 12" compacted and leveled rock or sand to ensure even distribution of soil pressure on base. Top of covers shall be flush with final grade or paving and shall be perfectly level.

C. A preformed joint sealing compound of non-hardening mastic furnished by the handhole manufacturer shall be placed in the grooves of the base and body sections to seal the sections together watertight. Joints shall be carefully cleaned before sealing.

D. Concrete encased duct lines connecting to handholes shall be constructed to

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 75: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

WIRING METHODS, RACEWAYS

AND CONDUCTORS 16400 - 12

have a tapered section adjacent to the manhole to provide shear strength.

E. Provide end bells for all duct terminations in handholes.

F. Backfilling around structures shall consist of earth, loam, sand-clay, or sand and gravel, free from large clods of earth or stones over one inch in size. Backfill materials shall be placed symmetrically on all sides in loose layers not more than nine inches deep. Each layer shall be moistened, if necessary, and compacted with mechanical or hand tampers to 90 percent compaction. Surfaces disturbed during the installation of pullboxes, and handholes shall be replaced as described under paragraph "RESTORATION OF SURFACES".

G. After installation, handholes, and pullboxes, shall be cleaned of dirt, sand, and debris and the covers sets in place. Pullropes leaving ducts shall be suitably tagged to allow future identification and use. Location of duct entry shall be marked clearly on as-built plans for pullboxes and handholes. All tags shall be engraved plastic plates.

3.2 GROUNDING AND BONDING

A. Ground and bond the electrical system and equipment in accordance with the most stringent of applicable codes but with the requirements herein and on drawings to be the minimum standards.

B. System Grounding Electrode:

C. Provide a "UFER" made electrode. The electrode shall be comprised of a 50 foot #3/0 bare copper cable imbedded in the concrete foundation footing. Locate the cable three inches up from the bottom and a three-inch clearance from the sides of the concrete footing and supported by a Reinforcing Bar #4 or larger completely encased in concrete. When below ground, the grounding electrode conductor shall be encased in concrete or in rigid nonmetallic conduit from six inches inside the concrete footing to the service equipment. The electrode conductor shall be continuous and unbroken to its termination at the service connection. Installation shall also be in accordance with CEC 250-81.

D. Where available on the premises and in accordance with Code requirements, the water piping system and metal building frame shall be bonded together to form a grounding system as described in CEC 250-80 and 250-81.

E. Test: Resistance to ground of the electrode shall be a maximum of 10 ohms. If the resistance is in excess of 10 ohms, provide one or more ground rods bonded to the electrode described herein before until the required resistance is obtained. Space rods a minimum of 6-feet apart. Bond wire shall be the same size as the grounding electrode connector. Test the electrode using the "fall of potential" method (described in IEEE No. 142) using a Biddle Earth Megger. Perform test not less than 48 hours after rainfall. No. conductive agents, chemicals, water, etc., shall be applied to improve grounding.

F. Equipment grounding conductors:

G. Provide copper THWN insulated equipment grounding conductors throughout all

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 76: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

WIRING METHODS, RACEWAYS

AND CONDUCTORS 16400 - 13

raceways.

H. The grounding conductors shall be provided whether scheduled or shown on the drawings or not, and if necessary the conduit size shall be increased to accommodate them. These grounding conductors shall be connected to the ground terminals on the device or enclosure at each end of the installation and shall be interconnected with the other ground terminals and conductors to form a continuous wired grounding system throughout the electrical wiring system.

I. Ground rods: 3/4-inch diameter X 10-feet copper clad steel. Drive full length into earth with the top 3-inch minimum below grade or underside of slab. Where ground rods cannot be driven vertically to the desired depth below grade, they shall be driven at an angle away from or parallel to the exterior wall. When

penetrate to a depth of permanent ground moisture. When ground rods cannot be driven because of bedrock at less than 4 feet below grade level, a counterpoise ground electrode shall be used in place of rods. The counterpoise system shall consist of not less than 50 feet of No. 2 AWG bare tinned copper wire, buried to a depth of at least 18 inches below grade, for each ground rod shown. The wires shall be run in a straight line.

J. Connections: Connection to ground rods below ground shall be made using exothermic welding devices. Above ground and accessible connections may be made using ground rod clamps, or exothermic devices. Multiple bolt silicon bronze connectors, Burndy or O.Z. Electric; or exothermic welded, Burndy, Erico Cadweld products, or equal.

K. Grounding electrode conductors shall be provided for service equipment and transformers by the Contractor. Utility Company transformer grounding shall be installed per Utility Company requirements. Final ground conductor connections to transformer shall be by Utility Company.

L. Flush wall outlets and switches shall have a bonding wire from device ground terminal, or approved mounting screw from strap, to metal box.

3.3 CABLE TRAY - ABOVE CEILING

A. Ladder type, hot dipped galvanized steel cable tray with nominal 4” sides and 9”

rung spacing, UL listed, and conforming to NEMA VE-1. NEMA Class 12B span/load designation (12’ support span/75 lbs. per foot load). Width of tray as

indicated on drawings. Tray system shall be complete with splice plates, end plates, dropouts, and miscellaneous hardware. Change-of-direction fittings shall have the manufacturer standard radius. All edges, fittings, and hardware shall be finished free from both sides of smoke and fire partitions. Cables run through smoke and fire separations shall be installed in 4” rigid steel conduits with

grounding bushing, extending 12” beyond each side of the partitions. Connect

the grounding bushing on the conduit to a grounding terminal on the tray, with #2 bare soft drawn copper wire. The installation shall be sealed to preserve the smoke and fire ratings of the partitions penetrated.

B. Support the tray system at not more than 8-ft. intervals, at each end, within 2-ft.

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 77: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

WIRING METHODS, RACEWAYS

AND CONDUCTORS 16400 - 14

of each change-of-direction fitting, and at the center of arc of each fitting. Supports shall be by hanger rods or wall brackets attached to concrete inserts or bolted to structural members. Each support assembly shall support 400 lbs. minimum. Runs longer than 20-feet shall be side braced at the end of run and at approximately equal spacings (not to exceed 20’) along the run. Refer to

Section 16300, Seismic Restraints subsection.

3.4 DEMOLITION WORK AND SALVAGE

A. Where an outlet, device or item of electrical equipment is shown to be removed, the entire installation, including boxes and conduit, shall be removed unless otherwise indicated.

B. Where the structure, finish, fixture, outlet, circuit or equipment is damaged or left incomplete or unworkable due to demolition work, it shall be patched, repaired, replaced, rerouted or relocated as conditions require and as directed by the Architect.

C. All existing wiring not being reused shall be removed back to the switchboard, panel or first active outlet box. Vacated conduit shall be removed unless removal would damage the structure. Place blank plates on all vacated boxes left in place.

D. Electrical material which the Contractor is directed to remove that is not specified for reuse on this project shall be removed from the site. Material released shall become the property of, and shall be removed from the site by, the Contractor. Material to be delivered to the District shall be carefully removed and transported so as to remain in reusable condition. Materials to be delivered to the District will include circuit breakers from the existing switchboard.

3.5 RESTORATION OF SURFACES

A. Unpaved surfaces disturbed during the installation of ducts or electrical structures shall be restored to specified elevation and condition. Sod or topsoil shall be preserved carefully and replaced after the backfilling is completed. All damaged irrigation lines, sprinkler heads or controller wiring shall be replaced.

B. The Contractor shall patch pavement, sidewalks, curbs and gutters where existing surfaces are removed or disturbed. Where necessary to cut, pavement edges shall be sawn.

C. Concrete work shall be as specified elsewhere.

3.6 MISCELLANEOUS WORK

A. Do all miscellaneous metal and concrete work required; all core drilling required; all cutting and patching required; all trenching and backfill required; and provide all hangers, anchors, chases, supports, and material required for the installation of the electrical systems.

B. Touch up or refinish damaged surfaces of panels, switchboards, and equipment, worked under this section, to the satisfaction of the Architect. Use paint provided

09 June 2014

Grossmont College B14.019 Trophy Cases

Page 78: CONSTRUCTION SPECIFICATIONS - GCCCD 019... · 2020. 11. 27. · D. Visual Requirements: Do not cut and patch construction in a manner that results in visual evidence of cutting and

WIRING METHODS, RACEWAYS

AND CONDUCTORS 16400 - 15

for that purpose by the equipment manufacturer.

C. All work shall be in accordance with applicable sections of the specifications.

3.7 CONCRETE WORK

A. Reinforcement of concrete shall be as specified elsewhere.

B. Concrete involving a serving Utility's equipment or systems shall conform to the requirements of the Utility.

C. Unless otherwise indicated, concrete shall be 3000 psi with maximum of 1" aggregate conforming to ASTM C-33, and reinforcing steel shall conform to ASTM A615.

END OF SECTION 16400

09 June 2014

Grossmont College B14.019 Trophy Cases