construction of the village arts factory – dormitory phase 2

142
CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2 SPECIFICATION MANUAL OCTOBER 2016

Upload: others

Post on 11-Apr-2022

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

CONSTRUCTION OF THE

VILLAGE ARTS FACTORY – DORMITORY PHASE 2

SPECIFICATION MANUAL

OCTOBER 2016

Page 2: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2
Page 3: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

PARTNERSHIP FOR THE ARTS & HUMANITIES CANTON TOWNSHIP COMMUNITY DEVELOPMENT BLOCK GRANT

INVITATION TO BID NOTICE IS HEREBY GIVEN that the Partnership for the Arts & Humanities, P.O. Box 871722, Canton, Michigan will accept sealed bids at Canton’s Office of the Clerk up to 3:00 p.m. Thursday, November 3, 2016 for the following:

CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2 Bids may be picked up at Canton’s Finance and Budget Department, on Canton’s website at www.canton-mi.org, or you may contact Mike Sheppard at: 734/394-5225. All bids must be submitted in a sealed envelope clearly marked with the proposal name, company name, address and telephone number and date and time of bid opening. The Partnership reserves the right to accept or reject any or all proposals. The Partnership does not discriminate on the basis of race, color, national origin, sex, religion, age or disability in employment or the provision of services. Publish 10/20/2016

Page 4: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2
Page 5: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY – DORMITORY TOC-1

TABLE OF CONTENTS 00 – PROCUREMENT AND CONTRACTING REQUIREMENTS 00 11 13 ADVERTISEMENT FOR BIDS 00 11 15 ADVERTISEMENT FOR PREQUALIFICATION OF BIDDERS 00 11 53 REQUEST FOR QUALIFICATIONS 00 41 13 BID FORM 14 - CONVEYING EQUIPMENT 14 26 00 LIMITED-USE-LIMITED-APPLICATION ELEVATORS 21 - FIRE SUPPRESSION 21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION 21 10 00 WATER BASED FIRE SUPPRESSION SYSTEMS 22 – PLUMBING 22 05 00 COMMON WORK RESULTS FOR PLUMBING 22 11 00 FACILITY WATER DISTRIBUTION 22 13 00 FACILITY SANITARY SEWER 26 – ELECTRICAL 26 05 00 COMMON WORK RESULTS FOR ELECTRICAL 26 05 19 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLE 26 05 33 RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS 26 24 16 PANELBOARDS 26 27 26 WIRING DEVICES 26 43 13 SURGE PROTECTIVE DEVICES FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS 28 – ELECTRICAL SAFETY AND SECURITY 28 31 00 FIRE DETECTION AND ALARM SUPPLEMENT INFORMATION AND FORMS FEDERAL LABOR STANDARDS PROVISIONS DAVIS BACON RATES FOR WAYNE COUNTY MICHIGAN CERTIFIED PAYROLL FORM AIA 305

Page 6: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2
Page 7: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 001113 - 1

DOCUMENT 001113 - ADVERTISEMENT FOR BIDS

1.1 PROJECT INFORMATION

A. Notice to Bidders: Qualifiedbidders may submit bids for project as described in this Document. Submit bids according to the Instructions to Bidders.

1. Regulatory Requirements: State of Michigan and Canton Township shall govern submittal, opening, and award of bids.

B. Project Identification: Construction of the Village Arts Factory – Dormitory Phase 2.

1. Project Location: 50625 Cherry Hill Road, Canton, MI, 48188

C. Owner: Partnership for the Arts & Humanities

1. Owner's Representative: Tom Yack

D. Architect: Cambridge Design & Architecture

E. Project Description: This project is a renovation of a historic structure to be adapted as a modern office use. This project will be completed in multiple phases. Scope of work may extend into different phases. The scope of work identified in this phase relates to the installation of a limited use elevator, installation of a new electrical system, installation of a new plumbing system, and installation of a new fire protection and alarm system.

F. Construction Contract: Bids will be received for the following Work: 1. Multiple Contract Project consisting of the following prime contracts:

a. Elevator Construction. b. Plumbing Construction. c. Electrical Construction. d. Fire Protection Construction.

1.2 BID SUBMITTAL AND OPENING

A. Owner will receive sealed lump sum bids until the bid time and date at the location given below. Owner will consider bids prepared in compliance with the Instructions to Bidders issued by Owner, and delivered as follows:

1. Bid Date: November 3, 2016 2. Bid Time: 3:00 p.m. >, local time. 3. Location: Clerks Office, Canton Township Administration Building, Attn: Village Arts

Factory – Dormitory Phase 2, 1150 South Canton Center Road, Canton, Michigan, 48188.

B. Bids will be thereafter publicly opened and read aloud.

Page 8: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 001113 - 2

1.3 BID SECURITY

A. Bid security shall be submitted with each bid in the amount of 5 percent of the bid amount. No bids may be withdrawn for a period of 60 days after opening of bids. Owner reserves the right to reject any and all bids and to waive informalities and irregularities.

1.4 PREBID QUESTIONS

A. Any prebid questions must be submitted in writing for a formal response provided to all potential bidders. No individual contact or questions will be responded to by the Owner, Canton Township, or the design team. Questions should be submitted in the following way 1. Deadline for questions shall be 5:00pm EST on October 26, 2016 2. Email all questions to [email protected] 3. Put in Subject header “Dormitory Phase 2 Bid Questions

B. Responses to the bid questions will be posted to the Canton Township website by close of business day October 28, 2016.

1.5 DOCUMENTS

A.

B. Online Procurement and Contracting Documents: Obtain access on or after Thursday October 20, 2016. Online access will be provided to all interested bidders. Bidders can go to Canton Township website to download documents. www.canton-mi.org.

C.

D. Viewing Procurement and Contracting Documents: Examine on or after <Thursday October 20, 2016 at the locations below:

1. Canton Finance and Budget Department, Canton Township Administrative Building, 1150 South Canton Center Road, Canton, Michigan, 48188.

1.6 TIME OF COMPLETION

A. Successful bidder shall begin the Work on receipt of the Notice to Proceed and shall complete the Work within the Contract Time.

1.7 BIDDER'S QUALIFICATIONS

A. Bidders must be qualified by Owner. Qualification will occur as part of the bidding process. Refer to Request for Qualifications section 001153.

B. Bidders must be properly licensed under the laws governing their respective trades and be able to obtain insurance and bonds required for the Work

Page 9: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 001113 - 3

C. Selected bidder does not mean lowest bid. Winning bidder will be selected from a combination of qualifications, price, services provided, and overall value added to the project.

1.8 NOTIFICATION

A. This Advertisement for Bids document is issued by Canton Township, Canton Michigan.

END OF DOCUMENT 001113

Page 10: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2
Page 11: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 001115 - 1

DOCUMENT 001115 - ADVERTISEMENT FOR PREQUALIFICATION OF BIDDERS

1.1 NOTIFICATION

A. Notice to Prospective Bidders: Owner will receive sealed Submittal of Qualifications from contractors interested in submitting construction bids on Project(s) described in this Advertisement, until the time and date given below.

1. Regulatory Requirements: State of Michigan and Canton Township > shall govern submittal and evaluation of qualifications.

B. Owner: Partnership for the Arts & Humanities

1. Owner's Representative: Tom Yack

1.2 PROJECT INFORMATION

A. See Document 001113 "Advertisement for Bids" for Project information.

1.3 SUBMITTAL OF PROSPECTIVE BIDDERS' QUALIFICATIONS

A. Owner will receive sealed Submittal of Qualifications until the time and date at the location given below. Owner will consider submittals prepared in compliance with the Request for Qualifications issued by Owner, and delivered as follows:

1. Date: November 3, 2016 2. Time: 3:00 p.m., local time. 3. Location: Clerks Office, Canton Township Administration Building, Attn: Village Arts

Factory – Dormitory Phase 2, 1150 South Canton Center Road, Canton, Michigan, 48188

B. Submittals of Qualifications will thereafter be evaluated by Owner and the names of the prequalified bidders will thereafter be published. Prospective Bidders' qualification information shall be considered privileged and confidential.

1.4 DOCUMENTS

A. Online Prequalification Documents: Obtain access on or after Thursday October 20, 2016, by contacting Owner. Submittal will be in the form of printed AIA Document A305, "Contractor's Qualification Statement," with supplemental attachments described in the documents. Document is incorporated with the bid documents.

1.5 QUALIFICATIONS OF PROSPECTIVE BIDDERS

A. Bidders must be properly licensed under the laws governing their respective trades and be able to obtain insurance and bonds required for the Work. The completed Prequalification Submittal

Page 12: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 001115 - 2

for each Prospective Bidder will be evaluated by Owner according to the following criteria, described in greater detail in the documents:

1. Proper license under the laws governing their respective trade(s). 2. Capacity to provide adequate Performance Bond, Labor and Material Payment Bond, and

Insurance in a form acceptable to Owner. 3. Adequate financial resources, work-in-hand capacity, adequate organization, and

acceptable past performance. 4. Applicable experience of firm, including experience of Project and field management

staff to be assigned to the Work. 5. Applicant must be able to meet insurance requirements set by Canton Township and

provide the appropriate certificates of insurance prior to award of bid. Canton requires the following proof of Liability Insurance and Endorsements a. Commercial General Liability of $3,000,000.00 b. Commercial Auto Liability of $3,000,000.00 c. Umbrella Liability of $3,000,000.00 d. Workers Comp Statutory of $500,000.00 e. Cancellation Endorsement for Canton Township

6.

1.6 NOTIFICATION

A. This Advertisement for Prequalification of Bidders document is issued by Canton Township, Canton, Michigan.

END OF DOCUMENT 001115

Page 13: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 001153 - 1

DOCUMENT 001153 - REQUEST FOR QUALIFICATIONS

1.1 PURPOSE, LAWS, AND REGULATIONS

A. The purpose of the Prequalification Procedure described in this Document is to provide Owner with a mechanism to evaluate and determine whether Prospective Bidders are qualified to participate in the construction of Project. Evaluation will be limited to that office of the Prospective Bidder that is proposed to perform the Work.

B. Applicable provisions of The State of Michigan and Canton Township shall be observed in the soliciting, receiving, and evaluating of Prospective Bidders' qualifications.

C. Applicable provisions of The State of Michigan and Canton Township shall be observed in bidding, letting, and execution of the Work.

D. Prospective Bidders are required to comply with these Requirements for Prequalification. Only those Prospective Bidders who have complied with the Requirements for Prequalification and have been determined to be qualified will be eligible to submit construction bids on Project.

1.2 DEFINITIONS

A. Financial Statement: The requirement for submitting a financial statement as an attachment to AIA Document A305, "Contractor's Qualification Statement" shall be understood to mean a certified annual audit, prepared according to generally acceptable accounting practices and signed by an independent certified public accountant. A Reviewed Statement of Assets and Liabilities, prepared and signed by an independent certified public accountant, is also acceptable. A self-prepared annual compiled financial statement or balance sheet is unacceptable.

B. Prospective Bidder: A Prospective Bidder is a person or entity who submits a Submittal of Qualifications to Owner.

C. Project: Generally described in the Invitation to Bid.

1.3 PREQUALIFICATION DOCUMENTS

A. Prequalification Documents: Consist of the Advertisement for Prequalification of Bidders; this Request for Qualifications document; AIA Document A305, "Contractor's Qualification Statement"; and additional documents issued by Owner.

B. Obtaining Prequalification Documents: Prospective Bidders may obtain complete sets of the Prequalification Documents from the issuing office designated in the Advertisement for Prequalification of Bidders. Prospective Bidders shall use complete sets of Prequalification Documents in preparing their submittal. Owner assumes no responsibility for errors or misinterpretations resulting from the use of incomplete sets of Prequalification Documents.

C. Interpretation or Correction of Prequalification Documents: If the Prospective Bidder is in doubt as to the interpretation of any part of the Prequalification Documents, or finds discrepancies in

Page 14: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 001153 - 2

or omissions from any part of the Prequalification Documents, it must submit a written Request for Interpretation thereof no later than [seven] <Insert number> days prior to acceptance of Submittals of Qualifications. Address all communications to Owner.

1.4 PREQUALIFICATION PROCEDURES

A. Form of Prequalification Submittal:

1. Submittals of Prequalification must be submitted in duplicate on AIA Document A305, "Contractor's Qualification Statement," properly executed and with all items filled out in ink or typed, and all additional data, attachments, and forms provided. Do not change or add words to the Qualification Statement or forms. All signatures must be original (and sealed if a corporation) and must be notarized and sealed by a Notary Public.

B. Modification to Requirements for Prequalification:

1. Clarifications, alterations, or changes made by Owner to the Requirements for Prequalification shall be in writing only. Verbal information is not valid or binding.

2. Modifications will be mailed or delivered to those Prospective Bidders having obtained Prequalification Documents from the issuing office.

C. Submission of Prequalification Documents:

1. Each Submittal of Prequalification shall be delivered to the location indicated in the Invitation for Bid on or before the day and hour set for receipt of Submittals. Each Submittal of Prequalification shall be submitted in an opaque, sealed envelope marked in the lower left-hand corner as follows:

a. Bidder's Qualification Statement for Construction of the Village Arts Factory – Dormitory Phase 2

b. Prospective Bidder's Name. c. Prospective Bidder's Address. d. Prospective Bidder’s Phone Number e. Date and Time for Submittal.

2. If not delivered in person, this envelope shall be enclosed in a second envelope for posting to the location indicated for receipt of bids.

3. Include a completed copy of the Prequalification Checklist attached to the cover of the Submittal.

4. It is the sole responsibility of the Prospective Bidder to ensure that its submittal is received by the submittal date and time. No faxed or e-mail submittal or modification of a submittal will be considered. No submittal submitted after the time fixed for receiving submittals will be considered; late submittals will be returned to the Prospective Bidder unopened.

5. Owner reserves the right to waive any informality and to request additional information from Prospective Bidders, at Owner's discretion.

D. Attachments:

Page 15: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 001153 - 3

1. Prospective Bidders shall complete all required forms and attachments described in the Prequalification Documents, entering "Not Applicable" where information does not apply. Absence of any of the forms included in the Prequalification Documents will be reason for possible disqualification.

E. Status of Prospective Bidders:

1. Proprietors submitting bids shall indicate their status as proprietors. 2. Prospective Bidders submitting qualifications for partnerships shall indicate their status

as partners and shall submit a certified copy of the power of attorney authorizing the executor of the submittal to bind the partnership.

3. Prospective Bidders submitting qualifications for corporations shall indicate their status as corporations and shall submit a certified copy of the board of directors' authorization for the Prospective Bidder to bind the corporation and shall affix the corporate seal on the submittal.

4. Prospective Bidders shall provide the following:

a. Names and addresses of proprietors, of all members of a partnership, or of the corporation's officers.

b. Name of jurisdiction where the partnership is registered or where the corporation is incorporated. Corporations must be licensed to do business in Project state at the time of executing the Contract.

1.5 WITHDRAWAL

A. A Qualification Statement may be withdrawn on personal request received from the Prospective Bidder.

1.6 QUALIFICATION CRITERIA

A. Prospective Bidders must demonstrate the following to the satisfaction of Owner:

1. Proper license under the laws and regulations governing their respective trade(s).

2. Capacity to provide Performance Bond, Labor and Material Payment Bond, and Insurance in a form acceptable to Owner in amounts adequate to bond the Work based on the scope indicated in the Invitation to Bid.

3. Applicable experience of firm as described in the Contractor's Qualification Statement, including the following:

a. Experience of Firm: The firm in its current organization shall have successfully completed minimum of five projects of similar type, quality, and scope, including a minimum of two within the last three years. The firm shall have a record of project completion, credit record, record of judgment claims, arbitration proceedings, and suits pending or outstanding acceptable to Owner.

b. Experience of Firm Officers: The firm officers shall have personal record of project completion acceptable to Owner.

c. Experience of Project and Field Management Staff to Be Committed by the Prospective Bidder to Carry Out the Work: The assigned project manager and field

Page 16: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 001153 - 4

superintendent must have successfully completed minimum of three projects of similar type, quality, and scope.

d. For purposes of this submittal, reference to "key individuals" as described in the Contractor's Qualification Statement shall be understood to mean the principal in charge, the project manager(s), and the project field superintendent(s) committed by the Prospective Bidder to carry out the Work of this Project. Prospective Bidder by submitting qualifications of key individuals agrees that Owner reserves the right to approve or reject subsequent reassignment of key individuals.

e. For purposes of this submittal, "successful completion" shall be understood to mean completion of project within project schedule and budget. Provide additional information indicating reasons why any referenced project did not meet project schedule or project budget.

f. For purposes of this Qualification, "similar project" shall be understood to include the following project elements:

1) Installation of elevators 2) Design and sizing of plumbing systems. 3) Design and sizing of electrical systems. 4) Design and sizing of fire protection systems 5) Automated building systems (controls, fire detection and alarm, technology

wiring infrastructure, intercommunications). 6) Renovation work.

4. Ability to provide necessary engineering services to work with the local jurisdiction to provide all necessary documentation necessary to acquire required building permits.

5. Adequate financial resources, including ability to secure materials and labor necessary for completion of the Work and other work in hand, within the anticipated contract times, and reflecting the anticipated retainage from progress payments.

6. Work-in-hand capacity, such that the Prospective Bidder demonstrates adequate work under contract to continue its business operations at least at their current level, at the same time indicating the capability to carry out Owner's proposed work.

7. Adequate organization to complete work of the scope anticipated, including firm management, project management, field superintendence, and field engineering and quality control.

8. Acceptable past performance as indicated by firm's references, including ability to meet contract time and to monitor, manage, and communicate interim scheduling requirements, to carry out required quality-control activities, to properly prepare interim and final payment requests, and to successfully complete project closeout requirements.

9. Acceptable documentation of firm's ability to comply with Owner's Minority-owned business enterprise/woman-owned business enterprise (MBE/WBE) requirements. Prospective Bidders shall contact Owner to obtain copies of requirements.

10. Acceptable documentation of firm's employee screening practices as indicating by affidavit describing background check procedures for firm's employees and requirements for same incorporated in firm's subcontracts.

B. Consideration of qualifications may be withheld if the Qualification Statement shows any unexplained erasures, omissions, alterations of form, additions not called for, added restrictions or qualifying conditions, or other irregularities of any kind.

Page 17: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 001153 - 5

C. Owner may make such investigations as it deems necessary to determine the ability of the Prospective Bidder to perform the Work, and the Prospective Bidder shall furnish to Owner all such information for this purpose as Owner may request. Owner reserves the right to withhold qualification if the evidence submitted by or investigation of such Prospective Bidder fails to satisfy Owner that such Prospective Bidder is properly qualified to carry out the obligations of the proposed Project. The determination of which bidders are prequalified is not protestable, except as allowed by law.

D. Qualification Submittal and data contained therein is considered privileged and confidential and will not be disclosed to any outside party except as required by law.

1.7 BONDS AND INSURANCE

A. The Prospective Bidder shall provide as part of the Submittal of Qualifications evidence of its ability to furnish below:

1. Performance Bond, a Payment Bond, and a Labor and Material Bond, each in the amount of 100 percent of the Contract Sum, with a corporate surety authorized to transact business in Project's jurisdiction.

2. Satisfactory certificates of insurance in the amount and types required by statute, but not less than the following:

a. Professional design errors and omissions insurance endorsement for delegated design by Contractor's professional engineer.

b. Workers' Compensation insurance provisions: statutory limits. c. Commercial General Liability insurance provisions: at limits established by Owner

in Project Contract Documents and including below:

1.8 ACCEPTANCE OF QUALIFICATIONS

A. Evaluations will be confidential. Notifications will be publicly available information.

B. Owner may deny qualification if it finds one or more of the following:

1. The Prospective Bidder does not have sufficient financial capacity to perform the Work. 2. The Prospective Bidder does not have the appropriate experience to perform the Work,

including, but not limited to, having met the experience criteria set forth herein. 3. The Prospective Bidder or any officer, director, or owner thereof has had judgments

entered against him within the past five years for the breach of contracts for governmental or nongovernmental construction work including, but not limited to, design-build or construction management contracts.

4. The Prospective Bidder has been in substantial noncompliance with the terms and conditions of prior construction with Owner, or in documented substantial noncompliance with the terms and conditions of prior construction with another public body without good cause.

5. The Prospective Bidder or any officer, director, owner, or chief financial official thereof has been convicted within the past 10 years of a crime related to governmental or nongovernmental construction or contracting.

Page 18: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 001153 - 6

6. The Prospective Bidder or any officer, director, or owner thereof is currently debarred pursuant to an established debarment procedure from bidding or contracting by any public body, agency of another state, or agency of the Federal Government.

7. The Prospective Bidder failed to provide to the public body in a timely manner any information required by the public body relevant to the six preceding subparagraphs.

8. The Prospective Bidder provides false, nonresponsive, misleading, or incomplete information for items required herein.

END OF DOCUMENT 001153

Page 19: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

004113 - 1

DOCUMENT 004113 - BID FORM - STIPULATED SUM (SINGLE-PRIME CONTRACT)

1.1 BID INFORMATION

A. Bidder: ____________________________________________________.

B. Project Name: VILLAGE ARTS FACTORY – DORMITORY PHASE 2.

C. Project Location: 50625 CHERRY HILL ROAD, CANTON, MI 48188.

D. Owner: PARTNERSHIP FOR THE ARTS & HUMANITIES.

E. Architect: CAMBRIDGE DESIGN & ARCHITECTURE.

1.2 CERTIFICATIONS AND BASE BID

A. Base Bid, Single-Prime (All Trades) Contract: The undersigned Bidder, having carefully examined the Procurement and Contracting Requirements, Conditions of the Contract, Drawings, Specifications, and all subsequent Addenda, as prepared by Cambridge Design & Architecture and Architect's consultants, having visited the site, and being familiar with all conditions and requirements of the Work, hereby agrees to furnish all material, labor, equipment and services, including all scheduled allowances, necessary to complete the construction of the above-named project, according to the requirements of the Procurement and Contracting Documents, for the stipulated sum of:

1. ________________________________________________ Dollars ($______________).

1.3 BID GUARANTEE

A. The undersigned Bidder agrees to execute a contract for this Work in the above amount and to furnish surety as specified within 10 days after a written Notice of Award, if offered within 60 days after receipt of bids, and on failure to do so agrees to forfeit to Owner the attached cash, cashier's check, certified check, U.S. money order, or bid bond, as liquidated damages for such failure, in the following amount constituting five percent (5%) of the Base Bid amount above:

1. ________________________________________________ Dollars ($______________).

B. In the event Owner does not offer Notice of Award within the time limits stated above, Owner will return to the undersigned the cash, cashier's check, certified check, U.S. money order, or bid bond.

1.4 SUBCONTRACTORS AND SUPPLIERS

A. Provide a list of all subcontractors and major suppliers that shall be used to execute portions of the Work indicated:

1. ________________________________________________________.

Page 20: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

004113 - 2

2. ________________________________________________________. 3. _________________________________________________________. 4. ________________________________________________________. 5. __________________________________________________________.

1.5 TIME OF COMPLETION

A. The undersigned Bidder proposes and agrees hereby to commence the Work of the Contract Documents on a date specified in a written Notice to Proceed to be issued by Architect, and shall fully complete the Work within a negotiated number of calendar days,.

1.6 ACKNOWLEDGEMENT OF ADDENDA

A. The undersigned Bidder acknowledges receipt of and use of the following Addenda in the preparation of this Bid:

1. Addendum No. 1, dated ____________________. 2. Addendum No. 2, dated ____________________. 3. Addendum No. 3, dated ____________________. 4. Addendum No. 4, dated ____________________.

1.7 CONTRACTOR ACKNOWLEDGEMENTS

A. By officially signing and submitting the bid the contractor confirms acknowledgements and accepts the following: 1. The rules and requirements to provide Davis Bacon prevailing wages as set forth in the

attached document for all contractors doing work on the project. 2. Insurance requirements set for by Canton Townships for all contractors doing work on

the project.

1.8 CONTRACTOR'S LICENSE

A. The undersigned further states that it is a duly licensed contractor, for the type of work proposed, in the State of Michigan, and that all fees, permits, etc., pursuant to submitting this proposal have been paid in full.

1.9 SUBMISSION OF BID

A. Respectfully submitted this ____ day of ____________, 2016.

B. Submitted By______________________________(Name of bidding firm or corporation).

C. Authorized Signature:____________________________________(Handwritten signature).

D. Signed By:______________________________________________(Type or print name).

E. Title:___________________________________(Owner/Partner/President/Vice President).

Page 21: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

004113 - 3

F. Witness By:___________________________________________(Handwritten signature).

G. Attest:_______________________________________________(Handwritten signature).

H. By:____________________________________________________(Type or print name).

I. Title:_________________________________(Corporate Secretary or Assistant Secretary).

J. Street Address:___________________________________________________________.

K. City, State, Zip___________________________________________________________.

L. Phone:__________________________________________________________________.

M. License No.:_____________________________________________________________.

N. Federal ID No.:_____________________________________(Affix Corporate Seal Here).

END OF DOCUMENT 004113

Page 22: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2
Page 23: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 142600 - 1

SECTION 142600 - LIMITED-USE/LIMITED-APPLICATION ELEVATORS

PART 1 - GENERAL

1.1 SUMMARY

A. Section includes limited-use/limited-application (LU/LA) elevators.

1.2 ACTION SUBMITTALS

A. Product Data: Include capacities, sizes, performances, operations, safety features, finishes, and similar information. Include Product Data for car enclosures, hoistway entrances, and operation, control, and signal equipment.

B. Shop Drawings:

1. Include plans, elevations, sections, and large-scale details indicating service at each landing, machine room layout, coordination with building structure, relationships with other construction, and locations of equipment.

2. Indicate loads imposed on building structure at points of support and power requirements.

C. Samples: For finishes involving color selection.

1.3 INFORMATIONAL SUBMITTALS

A. Qualification Data: For Installer.

B. Seismic Qualification Certificates: For elevator equipment, accessories, and components, from manufacturer.

C. Manufacturer Certificates: Signed by elevator manufacturer certifying that hoistway, pit, and machine room layout and dimensions, as shown on Drawings, and electrical service, as shown and specified, are adequate for elevator being provided.

D. Sample warranty.

1.4 CLOSEOUT SUBMITTALS

A. Operation and maintenance data.

B. Inspection and Acceptance Certificates and Operating Permits: As required by authorities having jurisdiction, for normal, unrestricted elevator use.

C. Continuing Maintenance Proposal: Provide a continuing maintenance proposal from Installer to Owner, in the form of a standard five-year maintenance agreement, starting on date initial maintenance service is concluded.

Page 24: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 142600 - 2

1.5 WARRANTY

A. Manufacturer's Special Warranty: Manufacturer agrees to repair or replace elevator work that fails in materials or workmanship within specified warranty period.

1. Warranty Period: one year(s) from date of Substantial Completion.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Basis-of-Design: RAM Manufacturing, Ltd. Model CR-1400. www.trustram.com

B. Other manufacturers are acceptable provided they meet all the required specifications and size requirements in this specification and on the drawings.

2.2 PERFORMANCE REQUIREMENTS

A. Regulatory Requirements: Comply with ASME A17.1/CSA B44.

B. Accessibility Requirements: Comply with requirements for LU/LA elevators in the United States Access Board's ADA-ABA Accessibility Guidelines and with ICC A117.1.

C. Seismic Performance: Elevator system shall withstand the effects of earthquake motions determined according to ASCE/SEI 7and shall comply with elevator seismic requirements in ASME A17.1/CSA B44.

1. Project Seismic Design Category: B. 2. Elevator Component Importance Factor:1.0. 3. Design earthquake spectral response acceleration short period (Sds) for Project is 0.1.1 g,

Category A.

2.3 SYSTEMS AND COMPONENTS

A. Elevator System, General: Manufacturer's standard LU/LA elevator. Unless otherwise indicated, manufacturers' standard components shall be used, as included in standard LU/LA elevators and as required for complete system.

1. Rated Load: 1400 lb (635 kg). 2. Rated Speed: 25 to 30 fpm (0.13 to 0.15 m/s).

B. Machine Type: Hydraulic, holeless, beside the car; direct-acting hydraulic or roped hydraulic.

C. Pump Units: Positive-displacement type with a maximum of 10 percent variation between no load and full load and with minimum pulsations.

1. Pump shall be submersible type, suspended inside oil tank from vibration isolation mounts.

Page 25: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 142600 - 3

2. Motor shall have solid-state starting. 3. System shall have hydraulic silencer and flexible piping connectors at pump unit.

D. Hydraulic Fluid: Elevator manufacturer's standard fire-resistant fluid with additives as needed to prevent oxidation of fluid, corrosion of cylinder and other components, and other adverse effects.

2.4 OPERATION SYSTEMS

A. General: Provide manufacturer's standard operation system for single automatic operation.

B. Battery-Powered Lowering: When power fails, car is lowered to the lowest floor, opens its car and hoistway doors, and shuts down. System includes rechargeable battery and automatic recharging system.

C. Provide automatic operation of lights and ventilation fans.

D. Emergency Operation: None required.

2.5 CAR ENCLOSURES

A. General: Provide steel-framed car enclosures with wall panels, car roof, access doors, power door operators, and ventilation. Provide finished car including materials and finishes specified below.

B. Clear Inside Dimensions:

1. Inside Width: 46” from sidewall to sidewall. 2. Inside Depth: 61” from back wall to front wall (return panels). 3. Inside Height: 81” to underside of ceiling.

C. Materials and Finishes: Manufacturer's standards, but not less than the following:

1. Floor Finish: Elevator manufacturer's standard level-loop nylon carpet; color as selected by Architect from manufacturer's full range.

2. Plastic-Laminate Wall Panels: Plastic laminate adhesively applied to manufacturer's standard core with plastic-laminate panel backing and manufacturer's standard protective edge trim. Panels shall have a flame-spread index of 25 or less, when tested according to ASTM E 84. Plastic-laminate color, texture, and pattern as selected by Architect from elevator manufacturer's full range.

3. Metal Ceiling: Flush panels, fabricated from cold-rolled steel sheet. Provide panels with factory-applied enamel or powder-coat finish; colors as selected by Architect from manufacturer's full range.

4. Lighting: Not less than two downlights. Provide battery backup power source with automatic charging.

a. Light Fixture Efficiency: Not less than 35 lumens/watt.

5. Handrail: Manufacturer's standard.

Page 26: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 142600 - 4

D. Car Doors: Manufacturer's standard units complete with track systems, hardware, sills, and accessories.

1. Operation: Power-operated, automatic. 2. Type: Horizontal sliding. 3. Clear Opening Width: 32 inches (815 mm). 4. Door Height: 80 inches (2032 mm). 5. Enameled or Powder-Coated Steel Doors: Flush, hollow-metal construction; fabricated

from cold-rolled steel sheet. Provide with factory-applied enamel or powder-coat finish; colors as selected by Architect from manufacturer's full range.

2.6 HOISTWAY ENTRANCES

A. General: Provide manufacturer's standard door-and-frame hoistway entrances, same size as car doors, complete with track systems, hardware, sills, and accessories.

1. Operation: Power-operated, automatic. 2. Type: Horizontal sliding.

B. Coordinate frame size and profile with hoistway wall construction.

1. Where gypsum board wall construction is indicated, provide self-supporting frames with reinforced head sections.

C. Materials and Fabrication: Manufacturer's standards, but not less than the following:

1. Enameled or Powder-Coated Steel Frames: Formed from cold- or hot-rolled steel sheet. Provide with factory-applied enamel or powder-coat finish; colors as selected by Architect from manufacturer's full range.

2. Enameled or Powder-Coated Steel Doors: Flush, hollow-metal construction; fabricated from cold-rolled steel sheet. Provide with factory-applied enamel or powder-coat finish; colors as selected by Architect from manufacturer's full range.

2.7 SIGNAL EQUIPMENT

A. General: Provide hall-call and car-call buttons that light when activated and remain lit until call has been fulfilled. Provide buttons and lighted elements illuminated with light-emitting diodes.

1. Finish: Satin stainless steel, No. 4 finish.

B. Car-Control Stations: Provide manufacturer's standard car-control stations. Mount in side panel adjacent to car door unless otherwise indicated.

1. Mark buttons and switches for function. Use both tactile symbols and Braille. 2. Provide "No Smoking" sign matching car-control station, either integral with car-control

station or mounted adjacent to it, with text and graphics as required by authorities having jurisdiction.

C. Emergency Communication System: Two-way voice communication system, with visible signal, which dials preprogrammed number of monitoring station and does not require handset

Page 27: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 142600 - 5

use. System is contained in flush-mounted cabinet, with identification, instructions for use, and battery backup power supply.

D. Car Position Indicator: Provide digital-type position indicator in elevator car. Also, provide audible signal to indicate to passengers that car is either stopping at or passing each of the floors served. Include travel direction arrows if not provided in car-control station.

E. Hall Push-Button Stations: Wall-mounted or jamb-mounted units equipped with buttons for calling elevator and for indicating desired direction of travel where applicable.

F. Hall Lanterns: Wall-mounted or jamb-mounted units with illuminated arrows; but provide single arrow at terminal landings.

G. Hall Annunciator: Provide audible signals indicating car arrival and direction of travel.

H. Emergency Pictorial Signs: Fabricate from materials matching hall push-button stations, with text and graphics as required by authorities having jurisdiction, indicating that in case of fire, elevators are out of service and exits should be used instead. Provide one sign at each hall push-button station unless otherwise indicated.

2.8 FINISH MATERIALS

A. Cold-Rolled Steel Sheet: ASTM A 1008/A 1008M, commercial steel, Type B, exposed, matte finish.

B. Hot-Rolled Steel Sheet: ASTM A 1011/A 1011M, commercial steel, Type B, pickled.

C. Stainless-Steel Sheet: ASTM A 240/A 240M, Type 304.

D. Aluminum Extrusions: ASTM B 221 (ASTM B 221M), Alloy 6063.

E. Plastic Laminate: High-pressure type complying with NEMA LD 3, Type HGS for flat applications.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Install cylinder plumb and accurately located for elevator car position and travel. Anchor securely in place, supported at pit floor and braced at intervals as needed to maintain alignment. Anchor cylinder guides at spacing needed to maintain alignment and avoid overstressing guides.

B. Sound Isolation: Mount rotating and vibrating equipment on vibration-isolating mounts to minimize vibration transmission to structure and structure-borne noise from elevator system.

C. Lubricate operating parts of systems as recommended by manufacturers.

Page 28: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 142600 - 6

D. Alignment: Coordinate installation of hoistway entrances with installation of elevator guide rails for accurate alignment of entrances with car. Reduce clearances to minimum, safe, workable dimension at each landing.

E. Leveling Tolerance: 1/4 inch (6 mm), up or down, regardless of load and direction of travel.

F. Set sills flush with finished floor surface at landing.

G. Locate hall lanterns either above or beside hoistway entrance at a minimum of 72 inches (1829 mm) above finished floor unless hall lanterns are built into entrance frames.

3.2 FIELD QUALITY CONTROL

A. Acceptance Testing: On completion of elevator installation and before permitting elevator use, perform acceptance tests as required and recommended by ASME A17.1/CSA B44 and by authorities having jurisdiction.

3.3 MAINTENANCE SERVICE

A. Initial Maintenance Service: Beginning at Substantial Completion, maintenance service shall include 12 months' full maintenance by skilled employees of elevator Installer. Include monthly preventive maintenance, repair or replacement of worn or defective components, lubrication, cleaning, and adjusting as required for proper elevator operation. Parts and supplies shall be manufacturer's authorized replacement parts and supplies.

END OF SECTION 142600

Page 29: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

21 05 00-1

SECTION 21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION

P A R T 1 - G E N E R A L

SCOPE This section includes information common to two or more technical fire protection specification sections or items that are of a general nature, not conveniently fitting into other technical sections. RELATED WORK This section applies to all Division 21 sections of fire suppression. REFERENCE Applicable provisions of Division 1 govern work under this section. REFERENCE STANDARDS Abbreviations of standards organizations referenced in this and other sections are as follows: AGA American Gas Association ANSI American National Standards Institute ASME American Society of Mechanical Engineers ASPE American society of Plumbing Engineers ASTM American Society for Testing and Materials AWWA American Water Works Association AWS American Welding Society CGA Compressed Gas Association CS Commercial Standards, Products Standards Sections, Office of Engineering Standards Service, NBS EPA Environmental Protection Agency FM FM Global FS Federal Specifications, Superintendent of Documents, U.S. Government Printing Office IAPMO International Association of Plumbing & Mechanical Officials IEEE Institute of Electrical and Electronics Engineers ISA Instrument Society of America MCA Mechanical Contractors Association MSS Manufacturer's Standardization Society of the Valve & Fitting Industry, Inc. NBS National Bureau of Standards NEC National Electric Code NEMA National Electrical Manufacturers Association NFPA National Fire Protection Association STI Steel Tank Institute UL Underwriters Laboratories Inc. QUALITY ASSURANCE Substitution of Materials: Refer to Section GC - General Conditions of the Contract, Equals and Substitutions. All products and materials used are to be new, undamaged, clean and in good condition. Existing products and materials are not to be reused unless specifically indicated. Where equipment or accessories are used which differ in arrangement, configuration, dimensions, ratings, or engineering parameters from those indicated on the contract documents, the contractor is responsible for

Page 30: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

21 05 00-2

all costs involved in integrating the equipment or accessories into the system and for obtaining the intended performance from the system into which these items are placed. SEALING AND FIRESTOPPING Sealing and firestopping of sleeves/openings between piping, etc. and the sleeve or structural opening shall be the responsibility of the contractor whose work penetrates the opening. The contractor responsible shall hire individuals skilled in such work to do the sealing and fireproofing. Provide all fire stopping of fire rated penetrations and sealing of smoke rated penetrations in compliance with section 07 84 00 Fire Stopping. OFF SITE STORAGE Prior approval by the A/E will be needed. Generally, sleeves, pipe/pipe fittings and similar rough-in material will not be accepted for off site storage. No material will be accepted for off site storage unless shop drawings for the material have been approved. CODES Comply with requirements of Michigan Building Code, Dept. of Safety and Professional Services, NFPA Standards and local Fire Chief or Fire Marshal (AHJ, Authority Having Jurisdiction) regarding design, materials and installation. DESIGN CRITERIA Design fire protection systems in accordance with codes, standards and regulations noted above. Available water supply data for system design is as follows: Test Date and Time: Performed By: Outlet Flow Static Residual

Hydrant Location Elevation GPM PSI PSI

Water test data is preliminary for bidding purposes. Verify and obtain any additional test data required for design. Tests to be representative of high water use periods. CERTIFICATES AND INSPECTIONS Obtain and pay for all required State or local installation Include copies of the certificates and reports in the Operating and Maintenance Instructions. SUBMITTALS Refer to Section GC - General Conditions of the Contract, Submittals. Shop drawing submittals are to be bound, labeled, contain the project manual cover page and a material index list page showing item designation, manufacturer and additional items supplied with the installation. Submit for all equipment and systems as indicated in the respective specification sections, marking each submittal with that specification section number. Mark general catalog sheets and drawings to indicate specific items being submitted and proper identification of equipment by name and/or number, as indicated in the contract documents. Include wiring diagrams of electrically powered equipment.

Page 31: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

21 05 00-3

The specific items that will be required for submittals shall be coordinated with the A/E, and the General Prime Contractor for inclusion in the project submittal log. Submittals shall be sent to the local Fire Chief or Fire Marshal for review prior to the Architect/Engineer. Include copy of all review/approval letters in submission to Architect/Engineer. Submit plans indicating water supply location and size, piping layout and size, sprinkler locations and type, hanger locations and type, equipment locations and type, valve locations and type, occupancy classes, hydraulic reference points, design areas and discharge densities. Submit hydraulic calculations for water supply and sprinkler systems. Include summary sheet and detailed work sheets. Describe characteristics of water supply and location of effective point used in calculations. Include graph illustration of water supply, hose demand, sprinkler demand and in-rack sprinkler demand. Where a fire pump is used, graph primary rating point, secondary rating point and churn pressure of pump and combined water supply. Submit sufficient quantities of data sheets and shop drawings to allow the following distribution:

• Operating and Maintenance Manuals 2 copies • User Agency 1 copy • Architect/Engineer 1 copy • Local Fire Chief or Marshal 1 copy

OPERATING AND MAINTENANCE INSTRUCTIONS All operations and maintenance data shall comply with the submission and content requirements specified under section GENERAL REQUIREMENTS. In addition to the general content specified under GENERAL REQUIREMENTS supply the following additional documentation:

• Copies of all approved submittals along with approval letters. • Manufacturer's wiring diagrams for electrically powered equipment. • Records of tests performed to certify compliance with system requirements. • Certificates of inspection by regulatory agencies. • Parts lists for equipment and specialties. • Manufacturers installation, operation and maintenance recommendations for equipment and

specialties. • Valve schedules • Lubrication instructions, including list/frequency of lubrication • Warranties • Additional information as indicated in the technical specification sections

TRAINING OF OWNER PERSONNEL Instruct Owner's personnel in the proper operation, maintenance and testing of systems and equipment provided as part of this project. Demonstrate testing, startup and shutdown procedures for all equipment. All training to be during normal working hours. Video record all instructions and provide Owner with copy. RECORD DOCUMENTS Refer to Division 1, General Requirements, Record Documents. In addition to the data indicated in the General Requirements, maintain fire protection layout record drawings and hydraulic calculations on originals prepared by the installing contractor/subcontractor. Include copies of these record drawings and calculations with the Operating and Maintenance manuals.

P A R T 2 - P R O D U C T S

Page 32: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

21 05 00-4

ACCESS PANELS AND DOORS PLASTER WALLS AND CEILINGS: 16 gauge frame with not less than a 20 gauge hinged door panel, prime coated steel for general applications, stainless steel for use in toilets, showers, and similar wet areas, concealed hinges, screwdriver operated cam latch for general applications, key lock for use in public areas, UL listed for use in fire rated partitions if required by the application. Use the largest size access opening possible, consistent with the space and the equipment needing service; minimum size is 12" by 12". IDENTIFICATION STENCILS: Not less than1/2" high letters for pipe sizes 1" through 2-1/2" and 1 inch high letters/numbers for pipe sizes 3" and above for marking pipe and equipment. Apply flow arrows to piping. ADHESIVE LABELS: Pressure-sensitive, adhesive backed, vinyl pipe markers with applicable labeling, ¾” min. size for lettering and surrounding tape on both ends. With flow arrows on piping. Conforming to ANSI, ANSI and NFPA standards. Seton Opti-Code, MSI, Brady or approved equal. Clean piping before application. SNAP-AROUND MARKERS: One-piece, pre-formed, vinyl construction, snap-around or strap-around pipe markers with applicable labeling, ¾” min. size for lettering. Provide nylon ties on each end of pipe marker. Seton Setmark or approved equal. SIGNS: Metal construction, baked porcelain enamel finish signs, sizes conforming to NFPA no. 13 and 7-1.2, with holes and s-hooks/chains for hanging or securing. With applicable labeling. MSI, Seton, W.H. Brady or equal. ENGRAVED NAME PLATES: White letters on a black background, 1/16 inch thick plastic laminate, beveled edges, screw mounting, Setonply Style 2060 by Seton Name Plate Company or Emedolite Style EIP by EMED Co., or equal by W. H. Brady. VALVE TAGS: Round brass tags with 1/2 inch numbers, 1/4 inch system identification abbreviation, 1-1/4 inch minimum diameter, with brass jack chains with brass "S" hooks or one piece nylon ties around the valve stem, available from EMED Co., Seton Name Plate Company, MSI or W. H. Brady. SEALING AND FIRE STOPPING NON-RATED PENETRATIONS: Pipe Penetrations Through Below Grade Walls: In exterior wall openings below grade, use a modular mechanical type seal consisting of interlocking synthetic rubber links shaped to continuously fill the annular space between the uninsulated pipe and the cored opening or a water-stop type wall sleeve. The operating bolts of the mechanical type seal shall be accessible from the building interior. Pipe Penetrations: At pipe penetrations of non-rated interior partitions, floors and exterior walls above grade, use urethane caulk in annular space between pipe insulation and sleeve. For non-rated drywall, plaster or wood partitions where sleeve is not required, use urethane caulk in annular space between pipe insulation and wall material.

P A R T 3 - E X E C U T I O N

Page 33: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

21 05 00-5

BUILDING ACCESS Arrange for the necessary openings in the building to allow for admittance of all apparatus. When the building access was not previously arranged and must be provided by this contractor, restore any opening to its original condition after the apparatus has been brought into the building. EQUIPMENT ACCESS Install all piping, conduit and accessories to permit access to equipment for maintenance and service. Coordinate the exact location of wall and ceiling access panels and doors with the General Prime Contractor, making sure that access is available for all equipment and specialties. Access doors in general construction are to be furnished by the Fire Protection Contractor and installed by the General Prime Contractor. Provide color coded thumb tacks or screws, depending on the surface, for use in accessible ceilings which do not require access panels. COORDINATION Coordinate all work with other contractors prior to installation. Any work that is not coordinated and that interferes with other contractor's work shall be removed or relocated at the installing contractor's expense. Verify that all devices are compatible for the type of construction and surfaces on which they will be used. IDENTIFICATION Identify equipment in mechanical equipment rooms by stenciling equipment number and service with one coat of black enamel against a light background or white enamel against a dark background. Use a primer where necessary for proper paint adhesion. Where stenciling is not appropriate for equipment identification, engraved name plates may be used. Identify interior piping mains not less than once every 25 feet, not less than once in each room, adjacent to each access door or panel, and on both sides of the partition where exposed piping passes through walls or floors. Place flow directional arrows at each pipe identification location. Use one coat of black enamel against a light background or white enamel against a dark background, or approved pipe marking label systems, or provide snap-around type pipe markers as specified in Part 2 – Products. Identify valves with signs per NFPA rulings. Provide hydraulic design information sign of permanently marked weatherproof metal or engraved nameplate material. Secure to alarm valve with brass chain. Information to include location of the design areas, discharge densities, required flow and residual pressure at the base of riser, hose stream demand and sprinkler demand. LUBRICATION Lubricate all bearings with lubricant as recommended by the manufacturer before the equipment is operated for any reason. Once the equipment has been run, maintain lubrication in accordance with the manufacturer's instructions until the work is accepted by the Owner. Maintain a log of all lubricants used and frequency of lubrication; include this information in the Operating and Maintenance Manuals at the completion of the project. SLEEVES AND OPENINGS Pipe penetrations through existing floors located in food service areas that do not require a T rating: Core drill sleeve opening large enough to insert schedule 40 sleeve, extend sleeve 2 inches above the floor and grout area around sleeve with hydraulic setting, non-shrink grout. Size sleeve to allow insulated pipe to run through sleeve and paint the sleeve.

Page 34: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

21 05 00-6

Where penetrating pipe or conduit weight is supported by floor, provide manufactured product or structural bearing collar designed to carry load. SEALING AND FIRE STOPPING NON-RATED PARTITIONS: In exterior wall openings below grade, assemble rubber links of mechanical seal to the proper size for the pipe and tighten in place, in accordance with manufacturer's instructions. The bolt heads for the mechanical seal shall face the inside of the building to facilitate repair or replacement of the seal. At all interior partitions and exterior walls, pipe penetrations are required to be sealed. Apply sealant to both sides of the penetration in such a manner that the annular space between the pipe sleeve or cored opening and the pipe or insulation is completely blocked. PENETRATIONS SUBJECT TO WATER INTRUSION: For penetrations (both rated and non-rated) in floors subject to water intrusion or in rooms housing electrical equipment (but not within walls) provide one of the following:

• Pipe penetration where steel pipe sleeve is used extend steel sleeve 2” above the floor. • Pipe penetration where cast in place fire stopping device/sleeve is used, extend device/sleeve 2”

above the floor (provided it meets the device’s UL listing). • Pipe penetration where there is no steel sleeve or cast in place fire stopping device/sleeve, provide

2”x 2” x 1/8” galvanized steel angles fastened to floor surrounding the penetration or group of penetrations to prevent water from getting to penetration. Provide urethane caulk between angles and floor and fasten angles to floor minimum 8”on center. Seal corners water tight with urethane caulk.

• Duct penetrations. Provide 2”x 2” x 1/8” galvanized steel angles fastened to floor surrounding the penetration or group of penetrations to prevent water from getting to penetration. Provide urethane caulk between angles and floor and fasten angles to floor minimum 8”on center. Seal corners water tight with urethane caulk.

Floors subject to water intrusion or rooms housing electrical equipment include the following locations:

• Food Service/Kitchen Areas • Restrooms • Mechanical/Plumbing Equipment Rooms • Data/Telecommunications Rooms • Electrical Equipment Rooms

Provide waterproof caulk sealant top coating on fire stopping system (or other approved means to protect the fire stopping system from water) in areas subject to wash down such as Food Service and Dish Washing Areas.

END OF SECTION

Page 35: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ATS FACTORY - DORMITORY

21 10 00-1

SECTION 21 10 00 WATER BASED FIRE SUPPRESSION SYSTEMS

P A R T 1 - G E N E R A L

SCOPE This section contains specifications for fire suppression pipe and pipe fittings for this project. RELATED WORK Section 21 05 00 – Common Work Results for Fire Suppression REFERENCE Applicable provisions of Division 1 govern work under this section. REFERENCE STANDARDS ANSI A21.4 ANSI A21.11 ANSI A21.51 ANSI B16.1 Cast Iron Pipe Flanges and Flanged Fittings ANSI B16.3 Malleable and Ductile Iron Threaded Fittings ANSI B16.4 Cast Iron Threaded Fittings ANSI B16.5 Pipe Flanges and Flanged Fittings ANSI B16.9 Factory Made Wrought Steel Buttweld Fittings ANSI B16.11 Forged Steel Fittings, Socket Welded and Threaded ANSI B16.18 Cast Bronze Solder Joint Pressure Fittings ANSI B16.22 Wrought Copper and Wrought Copper Alloy Solder Joint Pressure Fittings ANSI B16.29 Wrought Copper and Wrought Copper Alloy Solder Joint Drainage Fittings - DWV ASTM A53 Pipe, Steel, Black and Hot-Dipped, Zinc Coated Welded and Seamless ASTM A105 Forgings, Carbon Steel, for Piping Components ASTM A126 Gray Cast Iron Castings for Valves, Flanges, and Pipe Fittings ASTM A135 Electric Resistance Welded Steel Pipe ASTM A181 Forgings, Carbon Steel for General Purpose Piping ASTM A234 Pipe Fittings of Wrought Carbon Steel and Alloy Steel for Moderate and Elevated

Temperatures ASTM A536 Ductile Iron Castings ASTM A795 Black and Hot Dipped Zinc Coated (Galvanized) Welded and Seamless Steel Pipe for

Fire Protection Use ASTM B88 Seamless Copper Water Tube AWS A5.8 Brazing Filler Metal AWS D10.9 Qualification of Welding Procedures and Welders for Piping and Tubing, Level AR3 NFPA 13 Installation of Sprinkler Systems. (Latest prevailing edition) NFPA 14 Installation of Standpipe and Hose Systems. (Latest prevailing edition) UL Underwriters' Laboratories Listing FM Factory Mutual Approval SHOP DRAWINGS Schedule from the contractor indicating the ANSI/ASTM specification number of the pipe being proposed along with its type and grade, if known at the time of submittal, and sufficient information to indicate the type and rating of fittings for each service. QUALITY ASSURANCE

Page 36: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ATS FACTORY - DORMITORY

21 10 00-2

Substitution of Materials: Refer to Section GC – General Conditions of the Contract, Equals and Substitutions. Order all copper and steel pipe with each length marked with the name or trademark of the manufacturer and type of pipe; with each shipping unit marked with the purchase order number, metal or alloy designation, temper, size, and name of supplier. Any installed material not meeting the specification requirements must be replaced with material that meets these specifications without additional cost to the Owner. DELIVERY, STORAGE, AND HANDLING Promptly inspect shipments to insure that the material is undamaged and complies with specifications. Cover pipe to prevent corrosion or deterioration while allowing sufficient ventilation to avoid condensation. Do not store materials directly on grade. Protect pipe, tube, and fitting ends so they are not damaged. Where end caps are provided or specified, take precautions so the caps remain in place. Protect fittings, flanges, and unions by storage inside or by durable, waterproof, above ground packaging. Offsite storage agreements will not relieve the contractor from using proper storage techniques. Storage and protection methods must allow inspection to verify products. DESIGN CRITERIA Use only new material, free of defects, rust and scale, and meeting the latest revision of ASTM specifications as listed in this specification. Construct all piping systems for the highest pressures and temperatures in the respective system but not less than 175 psig. Where weld fittings are used, use only long radius elbows having a centerline radius of 1.5 pipe diameters. Where mechanical grooved fittings are used, use only ASTM standard radius fittings, short radius grooved fittings are not allowed. Where ASTM A53 or A795 type F pipe is specified, grade A type E or S, or grade B type E or S may be substituted at Contractor's option. Where ASTM A135 grade A pipe is specified, grade B pipe may be substituted at Contractor's option. Where the grade or type is not specified, Contractor may choose from those commercially available. Where ASTM B88, type L H (drawn) temper copper tubing is specified, ASTM B88, type K H (drawn) temper copper tubing may be substituted at Contractor's option. WELDER QUALIFICATIONS Welding procedures, welders, and welding operators for all building service piping to be in accordance with certified welding procedures of the National Certified Pipe Welding Bureau and Section 927.5 of ASME B31.9 Building Services Piping or AWS 10.9 Qualification of Welding Procedures and Welders for Piping and Tubing. Before any metallic welding is performed, Contractor to submit his Standard Welding Procedure Specification together with the Procedure Qualification Record as required by Section 927.6 of ASME B31.9 Building Services Piping. The Architect or Engineer reserves the right to test the work of any welder employed on the project, at the Owner's expense. If the work of the welder is found to be unsatisfactory, the welder shall be prevented from doing further welding on the project and all defective welds replaced.

Page 37: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ATS FACTORY - DORMITORY

21 10 00-3

P A R T 2 - P R O D U C T S FIRE SUPPRESSION PIPING STEEL PIPE: Black steel pipe welded and seamless, Type F, Grade A, ASTM A53; black welded and seamless steel pipe for fire protection use, Type F, ASTM A795; electric resistance welded steel pipe, Grade A, ASTM A135. Pipe wall Thickness: Threaded pipe shall have a minimum wall thickness of schedule 40. All other pipe shall have a minimum wall thickness of schedule 10. Piping 2” and under shall be minimum schedule 40 unless stated otherwise herein. Fittings: Cast iron threaded fittings, Class 125 or 250, ASTM A126/ANSI B16.4. Malleable and ductile iron threaded fittings, Class 150 or 300, ASTM A197/ANSI B16.3. Standard weight seamless carbon steel weld fittings, ASTM A234 grade, ANSI B16.9. Mechanical grooved fittings with EPDM gaskets, ASTM A536 ductile iron, ASTM A47 malleable iron or ASTM A53 fabricated steel. For wet pipe systems mechanical tee fittings with full iron back equal to Grinnell Figure 730 will be allowed only as needed for connection to existing systems. Outlets for drypipe and preaction systems shall be mechanical tees. Mechanical tees with U-bolt back or other fastening means are not allowed. Welding Materials: Comply with Section II, Part C, ASME Boiler and Pressure Vessel Code for welding materials. UNIONS AND FLANGES 2" AND SMALLER STEEL: ASTM A197/ANSI B16.3 malleable iron unions with brass seats. Use black malleable iron on black steel piping and galvanized malleable iron on galvanized steel piping. Grooved couplings may be used in lieu of unions. 2-1/2" AND LARGER: ASTM A181 or A105, Class 150, grade 1 hot forged steel flanges of threaded, welding neck, or slip-on pattern on black steel and threaded only on galvanized steel. ANSI B16.1 or ANSI B16.5, Class 150 cast iron threaded flanges. Use raised face flanges ANSI B16.5 for mating with other raised face flanges or equipment with flat ring or full face gaskets. Use ANSI B16.1 flat face flanges with full face gaskets for mating with other flat face flanges on equipment. SPRINKLER HEADS Manufacturer: Sprinkler head model numbers establish type and style of head. Products of the following manufacturers determined to be equal by the Architect/Engineer will be accepted: Tyco, Reliable, Victaulic and Viking. Standard coverage sprinkler heads are to be the basis for design unless noted otherwise on the plans or within these specifications. Fusible link or glass bulb type, cast brass or bronze construction. Provide heads with nominal 1/2" or 17/32” discharge orifice except where greater than normal density requires large orifice.

Page 38: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ATS FACTORY - DORMITORY

21 10 00-4

Select fusible link or glass bulb temperature rating to not exceed maximum ambient temperature rating allowed under normal conditions at installed location. Provide ordinary temperature (155 to 165 degree) fusible link or glass bulb type except at skylights, sealed display windows, unventilated attics and roof spaces, over cooking equipment, adjacent to diffusers, unit heaters, uninsulated heating pipes or ducts, mechanical rooms, storage rooms, or where otherwise indicated. Provide quantity of spare heads as noted below and 1 wrench for each type of head and each temperature range installed. Provide 6 spare heads per 300 or less installed heads, 12 per 1000 or less and 24 for more than 1000. Provide steel cabinet for storage of heads and wrenches. Provide an equal number of concealed cover plates and/or sprinkler escutcheons for each spare sprinkler head. FLOW SWITCHES Vane type waterflow switch with metal enclosure, adjustable pneumatic retard and electrical characteristics compatible with alarm system. LOCAL ALARM Weatherproof electric horn/strobe with red painted metal housing, mounting base and weatherproof gasket seal, and electrical characteristics compatible with alarm system. The horn strobe should be mounted above or as close as possible to the fire department connection.

PRESSURE GAUGES Manufacturer: Ametek/U. S. Gauge Division, Ashcroft, Marsh, Taylor, H. O. Trerice, Weiss, Weksler. Cast aluminum, stainless steel, brass, polycarbonate or ABS case of not less than 3.5 inches in diameter, double strength glass window, black lettering on a white background, phosphor bronze bourdon tube with bronze bushings, recalibration from the front of the dial, 99% accuracy over the middle half of the scale, 98.5% accuracy over the remainder of the scale. Include bronze 3-way globe valve with plugged outlet for Fire Inspector's test gauge. VALVES Manufacturers: Kennedy, Milwaukee, Nibco, Stockham, Victaulic, or Watts. BALL VALVES: 2" and smaller: Bronze, 2-piece, threaded or sweat ends, standard port, blowout proof stem, chrome plated ball, glass reinforced seats, UL approved @ 250 psi. Watts No. B-6000 UL. GATE VALVES: 2" and smaller: Outside screw and yoke gate valves, 175 psig, bronze body, bronze mounted, screwed bonnet, rising stem, solid wedge, with normally open tamper switch with double wire leads. 2-1/2" and larger: Outside screw and yoke gate valves, 175 psig, cast iron body, bronze mounted, bolted bonnet, rising stem, solid wedge, with normally open tamper switch with double wire leads. BUTTERFLY VALVES: 2" and smaller: Bronze body butterfly valve, 175 psig, geared operator, visible position indicator, normally open tamper switch with double wire leads, Buna or Viton seat, stainless steel disc and stem. 2" and larger: Cast or ductile iron body butterfly valve, lug style or grooved, 175 psig, geared operator, visible position indicator, normally open tamper switch with double wire leads, EPDM resilient seat,

Page 39: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ATS FACTORY - DORMITORY

21 10 00-5

EPDM seals, nickel plated ductile iron disc. Valve assembly to be bubble tight to 175 psig with no downstream flange/pipe attached. Use cap screws for removal of downstream piping while using the valve for system shutoff. SUPERVISORY/TAMPER SWITCHES: For O S & Y valve or butterfly valve installations, UL/FM listed/approved, to monitor position of valve, tamper resistant cover screws, single or double SPDT switch contacts, corrosion resistant, for indoor or outdoor use, NEMA 4 & 6P enclosures. CHECK VALVES: 3" and smaller: Bronze body, threaded end, Y-pattern, regrindable bronze seat, renewable bronze disc, 175 psig, suitable for installation in a horizontal or vertical line with flow upward. 2-1/2" and larger: Cast or ductile iron body, flanged or grooved ends, bronze trim, bolted cap, renewable bronze seat and disc, 175 psig, suitable for installation in a horizontal or vertical line with flow upward. Provide 1/2" automatic drip drain on inlet of fire dept. connection check valve. DRAIN VALVES: 3/4" minimum two piece bronze body ball valve; threaded ends, chrome plated bronze ball; glass filled teflon seat; teflon packing and threaded packing nut; blowout-proof stem; 400 psig WOG, with hose thread outlet and cap. DOUBLE CHECK VALVES: Manufacturers: Ames, Conbraco, Febco, Watts, or Wilkins. ASSE 1015 _" double check backflow preventer with 2 independent spring loaded check valves, 2 isolation ball or gate valves with normally open tamper switch with double wire leads, 4 valved test ports. Size for maximum pressure drop of __ psig at __ GPM. Constructed of bronze or epoxy coated cast iron or stainless steel body with bronze and plastic internal parts, stainless steel springs, silicone rubber valve discs, bronze seats, rated for 175 psig. SPECIALTY VALVES Manufacturer: Tyco, Reliable, Victaulic and Viking.

P A R T 3 - E X E C U T I O N GENERAL Install pipe fittings, and other fire suppression system components in accordance with reference standards, manufacturers recommendations and recognized industry practices. PREPARATION Cut pipe ends square. Ream ends of piping to remove burrs. Clean scale and dirt from interior and exterior of each section of pipe and fitting prior to assembly. ERECTION Install all piping parallel to building walls and ceilings and at heights which do not obstruct any portion of a window, doorway, stairway, or passageway. Where interferences develop in the field, offset or reroute piping as required to clear such interferences. Coordinate locations of fire protection piping with piping,

Page 40: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ATS FACTORY - DORMITORY

21 10 00-6

ductwork, conduit and equipment of other trades to allow sufficient clearances. In all cases, consult drawings for exact location of pipe spaces, ceiling heights, ceiling grid layout, light fixtures and grilles before installing piping. Where copper or steel piping is embedded in masonry or concrete, provide protective sleeve covering of elastomeric pipe insulation. Provide 3/32" min. thickness steel nailing plates behind or on either side of piping where the possibility of penetration from nails or drywall screws exists. Maintain piping in clean condition internally during construction. Provide clearance for access to valves and piping specialties. Provide anchors, expansion joints, swing joints and/or expansion loops so that piping may expand and contract without damage to itself, equipment, or building. Install piping so that system can be drained. Where possible, slope to main drain valve. Slope dry pipe and pre-action systems subject to freezing at minimum 1/4"/10' on mains and 1/2"/10' on branches. Where piping not susceptible to freezing cannot be fully drained, install nipple and cap for drainage of less than 5 gallons or ball valve with hose thread outlet and cap for drainage over 5 gallons. Pipe main drain valve to grade or to air gap sewer receptor. Mitered ells, notched tees, and orange peel reducers are not acceptable. On threaded piping, bushings are not acceptable. Do not route piping within exterior walls. Do not route piping through transformer vaults or above transformers, panelboards, or switchboards, including the required service space for this equipment, unless the piping is serving this equipment.

Install all valves and piping specialties, including items furnished by others, as specified and/or detailed. Provide access to valves and specialties for maintenance. Make connections to all equipment, fixtures and systems installed by others where same requires the piping services indicated in this section. WELDED PIPE JOINTS Make all welded joints by fusion welding in accordance with ASME Codes, ANSI B31, and State Codes where applicable. "Weldolets" and "Threadolets" may be used up to following sizes:

Maximum Weldolet/ Main Threadolet Pipe

¾” 1¼” Diameter Diameter

1” 1½” 1¼” 2” 1½” 2½” 2” 3” 3” 4” 4” 6” 6” 8”

Page 41: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ATS FACTORY - DORMITORY

21 10 00-7

THREADED PIPE JOINTS Use a thread lubricant or teflon tape when making joints; no hard setting pipe thread cement or caulking will be allowed. UNIONS AND FLANGES Install a union, flange or grooved coupling combination at each connection to each piece of equipment and at other items which may require removal for maintenance, repair, or replacement. Where a valve is located at a piece of equipment, locate the flange or union or grooved coupling combination connections on the equipment side of the valve. Concealed unions, flanges or couplings are not acceptable. PIPING SYSTEM LEAK TESTS Conduct pressure test with test medium of water. If leaks are found, repair the area with new materials and repeat the test; caulking will not be acceptable. Test piping in sections or entire system as required by sequence of construction. Do not conceal pipe until it has been successfully tested. If required for the additional pressure load under test, provide temporary restraints at fittings or expansion joints. Entire test must be witnessed by the Division's representative. Use clean water and remove air from the piping being tested where possible. Measure and record test pressure at the high point in the system. Test system at 200 psi for 2 hours showing no leakage. Where system design is in excess of 150 psig, test at a pressure 50 psig above system design pressure. All pressure tests are to be documented on NFPA Contractor's Material and Test Certificate forms. UNDERGROUND WATER MAIN FLUSHING Conduct flushing of the underground water/fire main service as required by NFPA 13. The 200 PSI pressure test of the main shall be conducted by the installer of the main. The flushing operation is to be documented on NFPA Underground Contractor's Material and Test Certificate forms. INSTALLATION Install fire protection system components in accordance with NFPA rulings, listings and manufacturers recommendations. Locate where accessible for servicing and replacement. Sprinkler Heads: Locate sprinkler heads as indicated on fire protection plan and reflected ceiling plan maintaining minimum clearances from obstructions, ceilings and walls. Install sprinkler heads level in locations not subject to spray pattern interference. Provide fire sprinkler head installations below ductwork, soffits, etc. Switches: Locate flow and pressure switches where indicated and where required to obtain specified zoning to isolate floors and major areas of floors. Provide valved test connection for flow switch adjacent to flow switch. Pipe to floor drain. Test flow switch to verify proper operation.

Gauges: Provide a valved pressure gauge in main fire protection riser, at the top of each piping riser, at inlet and outlet of pump and elsewhere as indicated.

Page 42: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ATS FACTORY - DORMITORY

21 10 00-8

Valves: Properly align piping before installation of valves. Do not support weight of piping system on valve ends. Mount valves in locations which allow access for operation, servicing and replacement. Install all valves with the stem in the upright or horizontal position. Valves installed with the stems down will not be accepted. Provide a riser shutoff valve and a capped hose thread drain valve at the bottom of each riser. Provide capped hose thread drain valves to allow draining of each portion of piping. Specialty Valves: Install in vertical position fire protection riser. Install trim recommended by manufacturer including drain and test valves. Pipe drains to hub or floor drains. Test and adjust operation of valves, alarms, pressure maintenance devices, emergency pull boxes and deluge/preaction controls.

END OF SECTION

Page 43: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

22 05 00-1

SECTION 22 05 00 COMMON WORK RESULTS FOR PLUMBING

P A R T 1 - G E N E R A L SCOPE This section includes information common to two or more technical plumbing specification sections or items that are of a general nature, not conveniently fitting into other technical sections. REFERENCE Applicable provisions of Division 1 govern work under this section. This section applies to all Division 22 00 00 sections of plumbing. REFERENCE STANDARDS Abbreviations of standards organizations referenced in this and other sections are as follows: ABMA American Boiler Manufacturers Association ACPA American Concrete Pipe Association AGA American Gas Association AMCA Air Movement and Control Association ANSI American National Standards Institute ARI Air Conditioning and Refrigeration Institute ASME American Society of Mechanical Engineers ASPE American society of Plumbing Engineers ASSE American Society of Sanitary Engineering ASTM American Society for Testing and Materials AWWA American Water Works Association AWS American Welding Society CISPI Cast Iron Soil Pipe Institute CGA Compressed Gas Association CS Commercial Standards, Products Standards Sections, Office of Eng. Standards Service, NBS DSPS State of Wisconsin Dept. of Safety and Professional Services, State Plumbing Code EPA Environmental Protection Agency FS Federal Specifications, Superintendent of Documents, U.S. Government Printing Office GAMA Gas Appliance Manufacturers Association IAPMO International Association of Plumbing & Mechanical Officials IEEE Institute of Electrical and Electronics Engineers ISA Instrument Society of America MCA Mechanical Contractors Association MICA Midwest Insulation Contractors Association MSS Manufacturer's Standardization Society of the Valve & Fitting Industry, Inc. NBS National Bureau of Standards NEC National Electric Code NEMA National Electrical Manufacturers Association NFPA National Fire Protection Association NSF National Sanitation Foundation PDI Plumbing and Drainage Institute SMACNA Sheet Metal and Air Conditioning Contractors' National Association. Inc. STI Steel Tank Institute UL Underwriters Laboratories Inc.

Page 44: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

22 05 00-2

Standards referenced in this section: ACI 614 Recommended Practice for Measuring, Mixing and Placing of Concrete ASTM D1557 Standard Test Method for Moisture-Density Relations of Soils ASTM E814 Standard Test Method for Fire Tests of Through-Penetration Fire Stops ASTM E84 Standard Test Method for Surface Burning Characteristics of Building Materials UL1479 Fire Tests of Through-Penetration Firestops UL723 Surface Burning Characteristics of Building Materials LEAD FREE REQUIREMENTS All materials that contact potable water shall be lead free. Lead free refers to the wetted surface of pipe, fittings and fixtures in potable water systems that have a weighted average lead content ≤0.25% per the Federal Safe Drinking Water Act as amended January 4th 2011 Section1417. This requirement applies to all of the subsequent Plumbing Specification Sections and Plumbing Drawings and supersedes any part or model number that may conflict with this requirement. QUALITY ASSURANCE Substitution of Materials: Refer to Section GC - General Conditions of the Contract, Equals and Substitutions. All products and materials used are to be new, undamaged, clean and in good condition. Existing products and materials are not to be reused unless specifically indicated. Where equipment or accessories are used which differ in arrangement, configuration, dimensions, ratings, or engineering parameters from those indicated on the contract documents, the contractor is responsible for all costs involved in integrating the equipment or accessories into the system and for obtaining the intended performance from the system into which these items are placed. SLEEVES AND OPENINGS Refer to Division 1, General Requirements, Sleeves and Openings. SEALING AND FIRESTOPPING Sealing and firestopping of sleeves/openings between piping, etc. and the sleeve or structural opening shall be the responsibility of the contractor whose work penetrates the opening. The contractor responsible shall hire individuals skilled in such work to do the sealing and fireproofing. PROVISIONS FOR FUTURE

All pipes must be closed off and secure until finish elements such as fixtures or sprinkler heads can be installed.

OFF SITE STORAGE Prior approval the A/E will be needed. The contractor shall submit Storage Agreement Form AD-BDC-74 to DFD for consideration of off site materials storage. Generally, sleeves, pipe/pipe fittings and similar rough-in material will not be accepted for off site storage. No material will be accepted for off site storage unless shop drawings for the material have been approved. CODES Comply with requirements of Michigan Plumbing Code. CERTIFICATES AND INSPECTIONS

Page 45: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

22 05 00-3

Refer also to Division 1, General Conditions, Permits, Regulations, Utilities and Taxes. Obtain and pay for all required State installation inspections except those provided by the Architect/Engineer. Deliver the originals of inspection certificates and test records to the Owner's Project Representative. Include copies of the certificates and test records in the Operating and Maintenance Instructions. SUBMITTALS Refer to Division 1, General Conditions, Submittals. Shop drawing submittals are to be bound, labeled, contain the project manual cover page and a material index list page showing item designation, manufacturer and additional items supplied with the installation. Submit for all equipment and systems as indicated in the respective specification sections, marking each submittal with that specification section number. Mark general catalog sheets and drawings to indicate specific items being submitted and proper identification of equipment by name and/or number, as indicated in the contract documents. Include wiring diagrams of electrically powered equipment. The specific items that will be required for submittals shall be coordinated with the the A/E, and the General Prime Contractor for inclusion in the project submittal log. Submit sufficient quantities of data sheets and shop drawings to allow the following distribution:

• Operating and Maintenance Manuals 1 copies • User Agency 1 copy • Architect/Engineer 1 copy

OPERATION AND MAINTENANCE DATA All operations and maintenance data shall comply with the submission and content requirements specified under section GENERAL REQUIREMENTS. In addition to the general content specified under GENERAL REQUIREMENTS supply the following additional documentation:

1. Records of tests performed a to certify compliance with system requirements 2. Manufacturer's wiring diagrams for electrically powered equipment 3. Certificates of inspection by regulatory agencies 4. Valve schedules 5. Lubrication instructions, including list/frequency of lubrication 6. Parts lists for fixtures, equipment, valves and specialties. 7. Manufacturers installation, operation and maintenance recommendations for fixtures, equipment,

valves and specialties. 8. Additional information as indicated in the technical specification sections

TRAINING OF OWNER PERSONNEL Instruct user agency personnel in the proper operation and maintenance of systems and equipment provided as part of this project. Demonstrate startup, operation and shutdown procedures for all equipment. All training to be during normal working hours. Video record all instructions and provide Owner with copy. RECORD DRAWINGS Refer to Division 1, General Requirements, Record Drawings.

P A R T 2 - P R O D U C T S

ACCESS PANELS AND DOORS PLASTER WALLS AND CEILINGS: 16 gauge frame with not less than a 20 gauge hinged door panel, prime coated steel for general applications, stainless steel for use in toilets, showers, and similar wet areas, concealed hinges, screwdriver

Page 46: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

22 05 00-4

operated cam latch for general applications, key lock for use in public or secured areas, UL listed for use in fire rated partitions if required by the application. Use the largest size access opening possible, consistent with the space and the item needing service; minimum size is 12" by 12".

The plumbing engineer must coordinate this item with the architect so installation responsibilities, quantities, sizes and locations are defined on the bidding documents.

IDENTIFICATION STENCILS: Not less than 1 inch high letters/numbers for marking pipe and equipment. ENGRAVED NAME PLATES: White letters on a black background, 1/16 inch thick plastic laminate, beveled edges, screw mounting, Setonply Style 2060 by Seton Name Plate Company or Emedolite Style EIP by EMED Co., or equal by W. H. Brady. ADHESIVE LABELS: Pressure-sensitive, adhesive backed, vinyl pipe markers with applicable labeling, ¾” min. size for lettering and surrounding tape on both ends. With flow arrows on piping. Conforming to ANSI, ANSI and NFPA standards. Seton Opti-Code, MSI, Brady or approved equal. Clean piping before application. SNAP-AROUND PIPE MARKERS: One-piece, preformed, vinyl construction, snap-around or strap-around pipe markers with applicable labeling and flow direction arrows, ¾" min. size for lettering. Provide nylon ties on each end of pipe markers. Equal to Seton Setmark. VALVE TAGS: Round brass tags with 1/2 inch numbers, 1/4 inch system identification abbreviation, 1-1/4 inch minimum diameter, with brass jack chains, brass "S" hooks or one piece nylon ties around the valve stem, available from EMED Co., Seton Name Plate Company, or W. H. Brady. UNDERGROUND WARNING TAPE: Detectable underground warning tape, 5.0 mil overall thickness, 6" width, .0035" thick aluminum foil core with polyethylene jacket bonded to both sides. Color code tape and print caution along with name of buried service in bold letters on face of tape. Thor Enterprises Magnatec or equal by Carlton, MSI Marking Services, Seton. UNDERGROUND TRACER WIRE: All underground non-metallic sewers/mains and water services/mains shall be provided with tracer wire installations. Tracer wire installations shall conform with Section 182.0715(2r) of Wisconsin Statutes and prevailing Department of Safety and Professional Services Chapter 384 requirements. Tracer wire shall be continuous solid copper or steel plastic coated with split bolt or compression-type connectors. BEDDING AND BACKFILL Bedding up to a point 12" inches above the top of the pipe shall be thoroughly compacted sand or crushed stone chips meeting the following gradations: Gradation for Bedding Sand

Gradation for Crushed Stone Chip Bedding

Sieve Size % Passing (by Wt) 1 inch 100 1/2 inch 100

Sieve Size % Passing (by Wt)

No. 16 45 - 80 No. 4 75 - 100 No. 200 2 - 10 No. 100 10 - 25

Page 47: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

22 05 00-5

Backfill above the bedding in lawn areas shall be thoroughly compacted excavated material free of large stones, organic, perishable, and frozen materials. Backfill above the bedding under existing and future utilities, paving, sidewalks, curbs, roads and buildings shall be granular materials, pit run sand, gravel, or crushed stone, free from large stones, organic, perishable, and frozen materials. SEALING AND FIRE STOPPING NON-RATED PENETRATIONS: In exterior wall openings below grade, use a modular mechanical type seal consisting of interlocking synthetic rubber links shaped to continuously fill the annular space between the uninsulated pipe and the cored opening or a water-stop type wall sleeve. The operating bolts of the mechanical type seal shall be accessible from the interior of the building. At pipe penetrations of non-rated interior partitions, floors and exterior walls, use urethane caulk in annular space between pipe insulation and sleeve. For non-rated drywall, plaster or wood partitions where sleeve is not required use urethane caulk in annular space between pipe insulation and wall material

P A R T 3 - E X E C U T I O N

EXCAVATION AND BACKFILL Perform all excavation and backfill work necessary to accomplish indicated plumbing systems installation. Excavate to bottom of pipe and structure bedding, 4" in stable soils, 6" in rock or wet trenches and 8" in unstable soil. Finish bottoms of excavations to true, level surface. Tunnel or remove sidewalk and curb in areas of excavation to the nearest joint. Remove pavements, curbs and gutters to neat and straight lines to the limits of removal. Make sawcut lines parallel to existing joints, or parallel or perpendicular to pavement edges to form a neat patch. Carefully remove remaining pavement within the sawcut area. Leave existing base materials between the area disturbed by the work and the sawcut line undisturbed by the sawcutting, pavement removal, or pavement replacement processes. Strip topsoil from area to be excavated, free from subsoil and debris, and store for later respreading. At no time place excavated materials where they will impede surface drainage unless such drainage is being safely rerouted away from the excavation. Excavate whatever materials are encountered as required to place at the elevations shown, all pipe, manholes, and other work. Remove debris and rubbish from excavations before placing bedding and backfill material. Remove surplus excavated materials from site. Verify the locations of any water, drainage, gas, sewer, electric, telephone or steam lines which may be encountered in the excavation. Underpin and support all lines. Cut off service connections encountered which are to be removed at the limits of the excavation and cap.

Page 48: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

22 05 00-6

Provide and maintain all fencing, barricades, signs, warning lights, and/or other equipment necessary to keep all excavation pits and trenches and the entire subgrade area safe under all circumstances and at all times. No excavation shall be left unattended without adequate protection. Elevations shown on the plans are subject to such revisions as may be necessary to fit field conditions. No adjustment in compensation will be made for adjustments up to two (2) feet above or below the grades indicated on the plans. Install lines passing under foundations with minimum of 1-1/2 inch clearance to concrete and insure there is no disturbance of bearing soil. Bed pipe up to a point 12" above the top of the pipe. Take care during bedding, compaction and backfill not to disturb or damage piping. Mechanically compact bedding and backfill to prevent settlement. The initial compacted lift to not exceed 24" compacted to 95% density per Modified Proctor Test (ASTM D-1557). Subsequent lifts under pavements, curbs, walks and structures are not to exceed 12" and be compacted to 95% density per Modified Proctor Test. In all other areas where construction above the excavation is not anticipated within 2 years, mechanically compact backfill in lifts not exceeding 24" to 90% density per Modified Proctor Test. Route the equipment over each lift of the material so that the compaction equipment contacts all areas of the surface of the lift. SHEETING, SHORING AND BRACING Provide shoring, sheet piling and bracing in conformance with the Wisconsin Administrative Code to prevent earth from caving or washing into the excavation. Shore and underpin to properly support adjacent or adjoining structures. Abandon in place shoring, sheet piling and underpinning below the top of the pipe, or, if approved in advance by the engineer, maintained in place until other permanent support approved by the engineer is provided. DEWATERING Provide, operate and maintain all pumps and other equipment necessary to drain and keep all excavation pits, trenches and the entire subgrade area free from water under all circumstances. Obtain general permit from the Wisconsin Department of Natural Resources district office for discharge of construction dewatering effluent. Obtain well permit from the Wisconsin Department of Natural Resources district office for dewatering wells discharging more than 70 GPM. Comply with permit requirements. ROCK EXCAVATION Remove rock encountered in the excavation to a minimum dimension of six (6) inches outside the pipe. Rock excavation includes all hard, solid rock in ledges, bedded deposits and unstratified masses, all natural conglomerate deposits so firmly cemented as to present all the characteristics of solid rock; which material is so hard or so firmly cemented that in the opinion of the Engineer it is not practical to excavate and remove same with a power shovel except after thorough and continuous drilling and blasting. Rock excavation includes rock boulders of 1/2 cubic yard or more in volume. Rock excavation will be computed on the basis of the depth of rock removed and a trench width two (2) feet larger than the outside diameter of the pipe where one (1) pipe is laid in the trench and three (3) feet larger than the combined outside diameter where two (2) pipes are laid in the trench. Include 6" pipe and structure bedding in rock excavation. Include rock excavation shown on the plans in the Base Bid. SURFACE RESTORATION Completely restore the surface of all disturbed areas to a like condition of the surface prior to the work. Level off all waste disposal areas and clean up all areas used for the storage of materials or the temporary deposit of excavated earth. Remove all surplus material, tools and equipment.

Page 49: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

22 05 00-7

Lawns: Topsoil with 4" of clean, friable, fertile topsoil conforming to D.O.T. Section 625, free from debris, lumps, rocks, roots, plants and seeds. Grade surfaces to match adjacent elevations. Rake smooth, free of lumps and debris. Sod with good quality nursery sod conforming to D.O.T. Section 631, be uniform, dense, free from weeds and consist of approximately 60% Kentucky blue grass and the balance perennial rye, fescue and white clover. Place sod with joints staggered and abutting. Maintain lawn areas for one month after installation. Contractor (user agency) will be responsible for necessary watering and mowing. Do necessary weeding, repair, reseeding or resodding until uniform catch is obtained. BUILDING ACCESS Arrange for the necessary openings in the building to allow for admittance or removal of all apparatus. When the building access was not previously arranged and must be provided by this contractor, restore any opening to its original condition after the apparatus has been brought into the building. EQUIPMENT ACCESS Install all piping, conduit and accessories to permit access to equipment for maintenance and service. Coordinate the exact location of wall and ceiling access panels and doors with the General Prime Contractor, making sure that access is available for all equipment and specialties. Access doors in general construction are to be furnished by the Plumbing Contractor and installed by the General Prime Contractor. Provide color coded thumb tacks or screws, depending on the surface, for use in accessible ceilings which do not require access panels. COORDINATION Coordinate all work with other contractors prior to installation. Any work that is not coordinated and that interferes with other contractor's work shall be removed or relocated at the installing contractor's expense. Verify that all devices are compatible for the type of construction and surfaces on which they will be used. IDENTIFICATION Identify equipment in mechanical equipment rooms by stenciling equipment number and service with one coat of black enamel against a light background or white enamel against a dark background. Use a primer where necessary for proper paint adhesion. Where stenciling is not appropriate for equipment identification, engraved name plates may be used. Identify interior piping not less than once every 30 feet, not less than once in each room, adjacent to each access door or panel, and on both side of the partition where accessible piping passes through walls or floors. Place flow directional arrows at each pipe identification location. Use one coat of black enamel against a light background or white enamel against a dark background. Identify all exterior buried piping for entire length with underground warning tape except for sewer piping which is routed in straight lines between manholes or cleanouts. Place tape 6"-12" below finished grade along entire length of pipe. Extend tape to surface at building entrances, meters, hydrants and valves. Where existing underground warning tape is broken during excavation, replace with new tape identifying appropriate service and securely spliced to ends of existing tape. Identify valves with brass tags bearing a system identification and a valve sequence number. Identify medical gas and vacuum valves with brass tags and wall or cabinet mounted color coded engraved nameplate with the following "(Type of Gas) Shutoff Valve for (Location or Zone)". Valve tags are not required at a terminal device unless the valves are greater than ten feet from the device, located in another room or not visible from device. Provide a typewritten valve schedule and pipe identification schedule indicating the valve number and the equipment or areas supplied by each valve and the symbols used for pipe identification; locate schedules in mechanical room and in each Operating and Maintenance manual. Schedule in mechanical room to be framed under clear plastic.

Page 50: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

22 05 00-8

LUBRICATION Lubricate all bearings with lubricant as recommended by the manufacturer before the equipment is operated for any reason. Once the equipment has been run, maintain lubrication in accordance with the manufacturer's instructions until the work is accepted by the Owner. Maintain a log of all lubricants used and frequency of lubrication; include this information in the Operating and Maintenance Manuals at the completion of the project. SLEEVES AND OPENINGS Pipe penetrations in new poured concrete horizontal construction requiring F and T rating: Form opening using hole form or core drill opening. Alternatively provide cast in place fire stopping devices/sleeves. Pipe penetrations in new poured concrete horizontal construction requiring F rating but no T rating: Same as pipe penetrations in new poured concrete construction requiring F and T ratings except that schedule 40 steel sleeves may also be used. Pipe penetrations in new poured concrete horizontal construction that do not require F or T ratings: Provide schedule 40 steel pipe sleeve, form opening using hole form or core drill opening. Pipe penetrations in existing concrete floors: Core drill openings. Pipe penetrations through existing floors located in food service areas that do not require a T rating: Core drill sleeve opening large enough to insert schedule 40 sleeve, extend sleeve 2 inches above the floor and grout area around sleeve with hydraulic setting, non-shrink grout. Size sleeve to allow insulated pipe to run through sleeve and paint the sleeve. Where penetrating pipe or conduit weight is supported by floor, provide manufactured product or structural bearing collar designed to carry load. SEALING AND FIRE STOPPING NON-RATED PARTITIONS: In exterior wall openings below grade, assemble rubber links of mechanical seal to the proper size for the pipe and tighten in place, in accordance with manufacturer's instructions. . The bolt heads for the mechanical seal shall face the inside of the building to facilitate repair or replacement of the seal. At all interior partitions and exterior walls, pipe penetrations are required to be sealed. Apply sealant to both sides of the penetration in such a manner that the annular space between the pipe sleeve or cored opening and the pipe or insulation is completely blocked. PENETRATIONS SUBJECT TO WATER INTRUSION: For penetrations (both rated and non-rated) in floors subject to water intrusion or in rooms housing electrical equipment (but not within walls) provide one of the following:

• Pipe penetration where steel pipe sleeve is used extend steel sleeve 2” above the floor. • Pipe penetration where cast in place fire stopping device/sleeve is used, extend device/sleeve 2”

above the floor (provided it meets the device’s UL listing). • Pipe penetration where there is no steel sleeve or cast in place fire stopping device/sleeve, provide

2”x 2” x 1/8” galvanized steel angles fastened to floor surrounding the penetration or group of penetrations to prevent water from getting to penetration. Provide urethane caulk between angles and floor and fasten angles to floor minimum 8”on center. Seal corners water tight with urethane caulk.

• Duct penetrations. Provide 2”x 2” x 1/8” galvanized steel angles fastened to floor surrounding the penetration or group of penetrations to prevent water from getting to penetration. Provide urethane caulk between angles and floor and fasten angles to floor minimum 8”on center. Seal corners water tight with urethane caulk.

Page 51: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

22 05 00-9

Floors subject to water intrusion or rooms housing electrical equipment include the following locations: • Food Service/Kitchen Areas • Restrooms • Mechanical/Plumbing Equipment Rooms • Electrical Equipment Rooms

Provide waterproof caulk sealant top coating on fire stopping system (or other approved means to protect the fire stopping system from water) in areas subject to wash down such as Food Service and Dish Washing Areas. AGENCY TRAINING All training provided for agency shall comply with the format, general content requirements and submission guidelines specified under Section 01 91 01 or 01 91 02. Contractor to provide factory authorized representative and/or field personnel knowledgeable with the operations, maintenance and troubleshooting of the system and/or components defined within this section.

END OF SECTION

Page 52: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2
Page 53: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

22 11 00-1

SECTION 22 11 00 FACILITY WATER DISTRIBUTION

P A R T 1 - G E N E R A L

SCOPE This section contains specifications for plumbing pipe and pipe fittings for this project. Included are the following topics: REFERENCE STANDARDS ANSI A21.4 ANSI A21.11 ANSI A21.51 ANSI B16.3 Malleable Iron Threaded Fittings ANSI B16.4 Cast Iron Threaded Fittings ANSI B16.5 Pipe Flanges and Flanged Fittings ANSI B16.22 Wrought Copper and Wrought Copper Alloy Solder Joint Pressure Fittings ANSI B16.29 Wrought Copper and Wrought Copper Alloy Solder Joint Drainage Fittings - DWV ASTM A53 Pipe, Steel, Black and Hot-Dipped, Zinc Coated Welded and Seamless ASTM A105 Forgings, Carbon Steel, for Piping Components ASTM A126 Gray Cast Iron Castings for Valves, Flanges, and Pipe Fittings ASTM A234 Pipe Fittings of Wrought Carbon Steel and Alloy Steel for Moderate and Elevated

Temperatures ASTM B32 Solder Metal ASTM B88 Seamless Copper Water Tube ASTM B280 Seamless Copper Tube for Air Conditioning and Refrigeration Field Service ASTM B813 Liquid and Paste Fluxes for Soldering Applications of Copper and Copper Alloy Tube ASTM D1785 Poly Vinyl Chloride (PVC) Plastic Pipe ASTM D2241 Poly Vinyl Chloride (PVC) Pressure-Rated Pipe (SDR Series) ASTM D2464 Threaded Poly Vinyl Chloride (PVC) Plastic Pipe Fittings, Schedule 80 ASTM D2466 Poly Vinyl Chloride (PVC) Plastic Pipe Fittings, Schedule 40 ASTM D2513 Thermoplastic Gas Pressure Pipe, Tubing, and Fittings ASTM D2564 Solvent Cements for Poly Vinyl Chloride (PVC) Plastic Pipe and Fittings ASTM D2657 Heat Fusion Joining of Polyolefin Pipe and Fittings ASTM D2774 Recommended Practice for Underground Installation of Thermoplastic Pressure Piping ASTM D2855 Making Solvent Cemented Joints with Poly Vinyl Chloride (PVC) Pipe and Fittings ASTM D3139 Joints for Plastic Pressure Pipes Using Flexible Elastomeric Seals ASTM D3222 Unmodified Poly Vinylidene Fluoride (PVDF) Molding Extrusion and Coating Materials ASTM D4101 Propylene Plastic Injection and Extrusion Materials ASTM F437 Threaded Chlorinated Poly Vinyl Chloride (CPVC) Plastic Pipe Fittings, Schedule 80 ASTM F438 Socket Type Chlorinated Poly Vinyl Chloride (CPVC) Plastic Pipe Fittings, Schedule 40 ASTM F441 Chlorinated Poly Vinyl Chloride (CPVC Plastic Pipe, Schedules 40 and 80 ASTM F493 Solvent Cements for Chlorinated Poly Vinyl Chloride (CPVC) Plastic Pipe and Fittings ASTM F656 Primers for Use in Solvent Cement Joints of Poly Vinyl Chloride (PVC) Plastic Pipe and

Fittings AWS A5.8 Brazing Filler Metal AWWA C104 Cement Mortar Lining for Ductile Iron Pipe and Fittings for Water AWWA C105 Polyethylene Encasement for Ductile Iron Piping for Water

Page 54: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

22 11 00-2

AWWA C110 Ductile Iron and Gray Iron Fittings, 3 In. Through 48 In., for Water and Other Liquids AWWA C111 Rubber Gasket Joints for Ductile Iron and Gray Iron Pressure Pipe and Fittings AWWA C151 Ductile Iron Pipe, Centrifugally Cast in Metal Molds or Sand-Lined Molds for Water or

Other Liquids AWWA C153 Ductile Iron Compact Fittings, 3 In. Through 48 In., for Water and Other Liquids AWWA C600 Installation of Ductile Iron Water Mains and Their Appurtenances AWWA C651 Disinfecting Water Mains AWWA C900 Polyvinyl Chloride (PVC) Pressure Pipe, 4 In. Through 12 In., for Water Distribution SHOP DRAWINGS Schedule from the contractor indicating the ASTM, AWWA or CISPI specification number of the pipe being proposed along with its type and grade if known at the time of submittal, and sufficient information to indicate the type and rating of fittings for each service. Statement from manufacturer on his letterhead that pipe furnished meets the ASTM, AWWA or CISPI specification contained in this section.

QUALITY ASSURANCE Order all copper, cast iron, steel, PVC and polyethylene pipe with each length marked with the name or trademark of the manufacturer and type of pipe; with each shipping unit marked with the purchase order number, metal or alloy designation, temper, size, and name of supplier. Any installed material not meeting the specification requirements must be replaced with material that meets these specifications without additional cost to the Owner. DELIVERY, STORAGE, AND HANDLING Promptly inspect shipments to insure that the material is undamaged and complies with specifications. Cover pipe to prevent corrosion or deterioration while allowing sufficient ventilation to avoid condensation. Do not store materials directly on grade. Protect pipe, tube, and fitting ends so they are not damaged. Where end caps are provided or specified, take precautions so the caps remain in place. Protect fittings, flanges, and unions by storage inside or by durable, waterproof, above ground packaging. Offsite storage agreements will not relieve the contractor from using proper storage techniques. Storage and protection methods must allow inspection to verify products. DESIGN CRITERIA Use only new material, free of defects, rust and scale, and meeting the latest revision of ASTM, AWWA or CISPI specifications as listed in this specification. Construct all piping for the highest pressures and temperatures in the respective system. Non-metallic piping will be acceptable only for the services indicated. It will not be acceptable in ventilation plenum spaces, including plenum ceilings. Where weld fittings or mechanical grooved fittings are used, use only long radius elbows having a centerline radius of 1.5 pipe diameters.

Page 55: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

22 11 00-3

Where ASTM B88, type L H (drawn) temper copper tubing is specified, ASTM B88, type K H (drawn) temper copper tubing may be substituted at Contractor's option. WELDER QUALIFICATIONS Welding procedures, welders, and welding operators for all building service piping to be in accordance with certified welding procedures of the National Certified Pipe Welding Bureau and Section 927.5 of ASME B31.9 Building Services Piping or AWS 10.9 Qualification of Welding Procedures and Welders for Piping and Tubing. Before any metallic welding is performed, Contractor to submit his Standard Welding Procedure Specification together with the Procedure Qualification Record as required by Section 927.6 of ASME B31.9 Building Services Piping. Before any polyethylene fusion welding is performed, Contractor to submit certification that the welders to be used on this project have successfully demonstrated proper welding procedures in accordance with the Code of Federal Regulations, Title 49, Part 192, Section 192.285. The Architect or Engineer reserves the right to test the work of any welder employed on the project. If the work of the welder is found to be unsatisfactory, the welder shall be prevented from doing further welding on the project and all defective welds replaced.

P A R T 2 - P R O D U C T S DOMESTIC WATER ABOVE GROUND: Type L copper water tube, H (drawn) temper, ASTM B88; wrought copper pressure fittings, ANSI B16.22; lead free (<.2%) solder, ASTM B32; flux, ASTM B813; copper phosporous brazing alloy, AWS A5.8 BCuP. Copper mechanical grooved fittings and couplings on roll grooved pipe may be used in lieu of soldered fittings. Mechanically formed brazed tee connections may be used in lieu of specified tee fittings for branch takeoffs up to one-half (1/2) the diameter of the main. Ductile iron pipe, thickness Class 53, AWWA C151/C115; with standard thickness cement mortar lining, AWWA C104; ductile iron mechanical grooved cement mortar lined fittings and couplings on cut grooved pipe, Class 350 12" and below, Class 250 above 12", AWWA C606; ductile iron or gray iron flanged cement mortar lined fittings, Class 250, AWWA C110; rubber gasket joints with non-toxic gasket lubricant, AWWA C111. BELOW GROUND 2-1/2" AND SMALLER: Type K copper water tube, O (annealed) temper, ASTM B88; with cast copper pressure fittings, ANSI B16.18; wrought copper pressure fittings, ANSI B16.22; lead free (<.2%) solder, ASTM B32; flux, ASTM B813; or cast copper flared pressure fittings, ANSI B16.26. BELOW GROUND 3" AND LARGER: Ductile iron pipe, mechanical or push on joint, thickness Class 52, AWWA C151; with standard thickness cement mortar lining, AWWA C104; ductile iron or gray iron mechanical joint cement mortar lined fittings, Class 250, AWWA C110; ductile iron mechanical joint compact fittings, Class 350, AWWA C153; rubber gasket joints with non-toxic gasket lubricant, AWWA C111. Provide 8 mil tube or sheet polyethylene encasement of iron pipe and pipe fittings, AWWA C105. UNDERGROUND TO INTERIOR BUILDING ENTRANCE PIPING 3” AND LARGER: Ductile iron as specified above with factory threaded and machined flanges.

Page 56: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

22 11 00-4

THRUST RESTRAINTS FOR UNDERGROUND PIPING: Asphaltic or epoxy coated ductile iron follower gland mechanical joint restraint with gripping wedge restraints and torque limiting twist-off nuts around the pipe circumference, low alloy steel T-bolts and UL listing or Factory Mutual approval. For PVC pipe joint bells, use epoxy or primer coated ductile iron bell and serrated ring restraints or gripping wedge restraints and torque limiting twist-off nuts around the pipe circumference with low alloy steel tie bolts. Restraint to have minimum pressure rating and safety factor equal to or greater than pressure rating and safety factor of pipe and be designed specifically for the pipe material it’s applied on.

DIELECTRIC UNIONS AND FLANGES Watts Regulator Company, Lochinvar, Wilkins or EPCO Sales, Inc., dielectric unions 2" and smaller; dielectric flanges 2" and larger; with iron female pipe thread to copper solder joint or brass female pipe thread end connections, non-asbestos gaskets, having a pressure rating of not less than 175 psig at 180 degrees. UNIONS AND FLANGES Unions, flanges and gasket materials to have a pressure rating of not less than 150 psig at 180 degrees. Gasket material for flanges and flanged fittings shall be teflon type. Treated paper gaskets are not acceptable. 2" AND SMALLER STEEL: ASTM A197/ANSI B16.3 malleable iron unions with brass seats. Use black malleable iron on black steel piping and galvanized malleable iron on galvanized steel piping. 2" AND SMALLER COPPER: ANSI B16.18 cast bronze union coupling or ANSI B15.24 Class 150 cast bronze flanges. 2-1/2" AND LARGER STEEL: ASTM A181 or A105, grade 1 hot forged steel flanges of threaded, welding neck, or slip-on pattern on black steel and threaded only on galvanized steel. Use raised face flanges ANSI B16.5 for mating with other raised face flanges or equipment with flat ring or full face gaskets. Use ANSI B16.1 flat face flanges with full face teflon gaskets for mating with other flat face flanges on equipment. Gaskets shall be teflon type. 2-1/2" AND LARGER COPPER: ANSI B15.24 Class 150 cast bronze flanges with full face teflon gaskets.

P A R T 3 - E X E C U T I O N GENERAL Install pipe and fittings in accordance with reference standards, manufacturers recommendations and recognized industry practices. PREPARATION Cut pipe ends square. Ream ends of piping to remove burrs. Clean scale and dirt from interior and exterior of each section of pipe and fitting prior to assembly. ERECTION

Page 57: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

22 11 00-5

Install all piping parallel to building walls and ceilings and at heights which do not obstruct any portion of a window, doorway, stairway, or passageway. Where interferences develop in the field, offset or reroute piping as required to clear such interferences. Coordinate locations of plumbing piping with piping, ductwork, conduit and equipment of other trades to allow sufficient clearances. In all cases, consult drawings for exact location of pipe spaces, ceiling heights, door and window openings, or other architectural details before installing piping. Where copper or steel piping is embedded in masonry or concrete, provide protective sleeve covering of elastomeric pipe insulation. Install underground warning tape 6"-12" below finished grade above all exterior below ground piping. Where existing underground warning tape is encountered, repair and replace. Maintain piping in clean condition internally during construction. Provide clearance for installation of insulation, access to valves and piping specialties. Provide anchors, expansion joints, swing joints and/or expansion loops so that piping may expand and contract without damage to itself, equipment, or building. Do not route piping through transformer vaults or above transformers, panelboards, or switchboards, including the required service space for this equipment, unless the piping is serving this equipment Install all valves and piping specialties, including items furnished by others, as specified and/or detailed. Provide access to valves and specialties for maintenance. Make connections to all equipment, fixtures and systems installed by others where same requires the piping services indicated in this section. COPPER PIPE JOINTS Remove all slivers and burrs remaining from the cutting operation by reaming and filing both pipe surfaces. Clean fitting and tube with metal brush, emery cloth or sandpaper. Remove residue from the cleaning operation, apply flux and assemble joint to socket stop. Apply flame to fitting until solder melts when placed at joint. Remove flame and feed solder into joint until full penetration of cup and ring of solder appears. Wipe excess solder and flux from joint. WELDED PIPE JOINTS Make all welded joints by fusion welding in accordance with ASME Codes, ANSI B31, and State Codes where applicable. "Weldolets" and "Threadolets" may be used for branch takeoffs up to one-half (1/2) the diameter of the main. THREADED PIPE JOINTS Use a thread lubricant or teflon tape when making joints; no hard setting pipe thread cement or caulking will be allowed. DOMESTIC WATER Maintain piping system in clean condition during installation. Remove dirt and debris from assembly of piping as work progresses. Cap open pipe ends where left unattended or subject to contamination. Install exterior water piping below predicted frost level in accordance with COMM Table 82.30-6, but in no case less than 6' bury depth to top of pipe. Maintain minimum of 8' horizontal distance between 2-1/2" and larger water piping and sanitary sewer piping. Maintain minimum of 30" horizontal and 12" vertical

Page 58: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

22 11 00-6

distance, water on top, between 2" and smaller water piping and sanitary sewer piping. Where water piping crosses a sanitary sewer, provide minimum 18" vertical clearance and waterproof PVC water pipe sleeve (reference sanitary sewer materials) sealed at both ends for distance of 10' from sewer in both directions. Provide thrust restraints for 3" and larger exterior water piping joints, hydrants, caps, plugs, fittings and bends of 22-1/2 degrees or more. Field apply continuous anti-corrosion coating to rodded restraint components. Protect mechanical joints, nuts and bolts from concrete cover. Cover with 8 mil sheet or tube polyethylene material sleeve. Install interior water piping with drain valves where indicated and at low points of system to allow complete drainage. Install shutoff valves where indicated and at the base of risers to allow isolation of portions of system for repair. Do not install water piping within exterior walls. Prior to use, isolate and fill system with potable water. Allow to stand 24 hours. Flush each outlet proceeding from the service entrance to the furthest outlet for minimum of 1 minute and until water appears clear. Fill system with a solution of water and chlorine containing at least 50 parts per million of chlorine and allow to stand for 24 hours. Alternately a solution containing at least 200 parts per million of chlorine may be used and allowed to stand for 3 hours. Flush system with potable water until chlorine concentration is no higher than source water level. Wait 24 hours after final flushing. Take samples of water for lab testing. The number and location of samples shall be representative of the system size and configuration and are subject to approval by Engineer. Test shall show the absence of coliform bacteria. If test fails, repeat disinfection and testing procedures until no coliform bacteria are detected. Submit test report indicating date and time of test along with test results. UNDERGROUND PIPE WRAP Use for steel piping encased in concrete or underground which is not in a conduit. Remove all dirt and other foreign material from exterior of pipe. Apply primer as recommended by the manufacturer. Use a spiral wrap process for applying tape to the pipe. Repair any breaks in the tape coating caused by the installation process. DIELECTRIC UNIONS AND FLANGES Install dielectric unions or flanges at each point where a copper-to-steel pipe connection is required in domestic water systems. UNIONS AND FLANGES Install a union or flange at each connection to each piece of equipment and at other items which may require removal for maintenance, repair, or replacement. Where a valve is located at a piece of equipment, locate the flange or union connection on the equipment side of the valve. Concealed unions or flanges are not acceptable. PIPING SYSTEM LEAK TESTS Isolate or remove components from system which are not rated for test pressure. Test piping in sections or entire system as required by sequence of construction. Do not insulate or conceal pipe until it has been successfully tested. If required for the additional pressure load under test, provide temporary restraints at fittings or expansion joints. Backfill underground water mains prior to testing with the exception of thrust restrained valves which may be exposed to isolate potential leaks.

Page 59: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

22 11 00-7

For hydrostatic tests, use clean water and remove all air from the piping being tested by means of air vents or loosening of flanges/unions. Measure and record test pressure at the high point in the system. Inspect system for leaks. Where leaks occur, repair the area with new materials and repeat the test; caulking will not be acceptable. Test Initial Test Final Test

*Below Ground Domestic Water Water N/A 200 psig 2 hr System Medium Pressure Duration Pressure Duration

Above Ground Domestic Water Water N/A 100 psig 8 hr Above Ground Non-potable Water Water N/A 100 psig 8 hr Below Ground Non-potable Water Water N/A 100 psig 8 hr

* Leakage on exterior mains 3" and larger may not exceed leakage calculated as follows: GPH Allowable Leakage = 133,200

(Feet of Pipe) (Inches Dia. of Pipe) (Test Pressure).5

CONSTRUCTION VERIFICATION ITEMS Contractor is responsible for utilizing the construction verification checklists supplied under specification Section 22 08 00 in accordance with the procedures defined for construction verification in Section 01 91 01 or 01 91 02.

END OF SECTION

Page 60: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

22 11 00-8

PIPING SYSTEM TEST REPORT Date Submitted: Project Name: Location: Contractor: □ Plumbing □ Fire Sprinkler

Test Medium: □ Air □ Water □ Other Test performed per specification section No. Specified Test Duration ______ Hours Specified Test Pressure PSIG System Identification: Describe Location:

Test Date:

Start Test Time: Initial Pressure: PSIG Stop Test Time: Final Pressure: PSIG

Tested By: Witnessed By: Title: Title: Signed: Signed: Date: Date: Comments:

Page 61: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

22 13 00-1

SECTION 22 13 00 FACILITY SANITARY SEWERAGE

P A R T 1 - G E N E R A L

SCOPE This section contains specifications for plumbing pipe and pipe fittings for this project. Included are the following topics: . REFERENCE STANDARDS ANSI A21.4 ANSI A21.11 ANSI A21.51 ANSI B16.5 Pipe Flanges and Flanged Fittings ASTM D1785 Poly Vinyl Chloride (PVC) Plastic Pipe ASTM D2241 Poly Vinyl Chloride (PVC) Pressure-Rated Pipe (SDR Series) ASTM D2466 Poly Vinyl Chloride (PVC) Plastic Pipe Fittings, Schedule 40 ASTM D2564 Solvent Cements for Poly Vinyl Chloride (PVC) Plastic Pipe and Fittings ASTM D2665 Poly Vinyl Chloride (PVC) Plastic Drain, Waste and Vent Pipe and Fittings ASTM D2729 Poly Vinyl Chloride (PVC) Sewer Pipe and Fittings ASTM D2774 Recommended Practice for Underground Installation of Thermoplastic Pressure Piping ASTM D2855 Making Solvent Cemented Joints with Poly Vinyl Chloride (PVC) Pipe and Fittings ASTM D3034 Type PSM Poly Vinyl Chloride (PVC) Sewer Pipe and Fittings ASTM D3139 Joints for Plastic Pressure Pipes Using Flexible Elastomeric Seals ASTM D3212 Joints for Drain and Sewer Plastic Pipes Using Flexible Elastomeric Seals ASTM D3222 Unmodified Poly Vinylidene Fluoride (PVDF) Molding Extrusion and Coating Materials ASTM D3311 Drain, Waste and Vent (DWV) Plastic Fitting Patterns SHOP DRAWINGS Schedule from the contractor indicating the ASTM, or CISPI specification number of the pipe being proposed along with its type and grade if known at the time of submittal, and sufficient information to indicate the type and rating of fittings for each service. QUALITY ASSURANCE Substitution of Materials: Refer to Section GC – General Conditions of the Contract, Equals and Substitutions. Order all copper, cast iron, steel, PVC and polyethylene pipe with each length marked with the name or trademark of the manufacturer and type of pipe; with each shipping unit marked with the purchase order number, metal or alloy designation, temper, size, and name of supplier. Any installed material not meeting the specification requirements must be replaced with material that meets these specifications without additional cost to the State. DELIVERY, STORAGE, AND HANDLING Promptly inspect shipments to insure that the material is undamaged and complies with specifications.

Page 62: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

22 13 00-2

Cover pipe to prevent corrosion or deterioration while allowing sufficient ventilation to avoid condensation. Do not store materials directly on grade. Protect pipe, tube, and fitting ends so they are not damaged. Where end caps are provided or specified, take precautions so the caps remain in place. Protect fittings, flanges, and unions by storage inside or by durable, waterproof, above ground packaging. Offsite storage agreements will not relieve the contractor from using proper storage techniques. Storage and protection methods must allow inspection to verify products. DESIGN CRITERIA Use only new material, free of defects, rust and scale, and meeting the latest revision of ASTM, or CISPI specifications as listed in this specification. Construct all piping for the highest pressures and temperatures in the respective system. Non-metallic piping will be acceptable only for the services indicated. It will not be acceptable in ventilation plenum spaces, including plenum ceilings. Where weld fittings or mechanical grooved fittings are used, use only long radius elbows having a centerline radius of 1.5 pipe diameters. WELDER QUALIFICATIONS Before any polyethylene fusion welding is performed, Contractor to submit certification that the welders to be used on this project have successfully demonstrated proper welding procedures in accordance with the Code of Federal Regulations, Title 49, Part 192, Section 192.285. The Architect or Engineer reserves the right to test the work of any welder employed on the project, at the State's expense. If the work of the welder is found to be unsatisfactory, the welder shall be prevented from doing further welding on the project and all defective welds replaced.

P A R T 2 - P R O D U C T S SANITARY WASTE AND VENT INTERIOR ABOVE GROUND: PVC plastic pipe, Schedule 40, Class 12454-B (PVC 1120), ASTM D1785; PVC plastic drain, waste and vent pipe and fittings, ASTM D2665; socket fitting patterns, ASTM D3311; primer, ASTM F656; solvent cement, ASTM D2564. INTERIOR BELOW GROUND:

PVC plastic pipe, Schedule 40, Class 12454-B (PVC 1120), ASTM D1785; PVC plastic drain, waste and vent pipe and fittings, ASTM D2665; socket fitting patterns, ASTM D3311; primer, ASTM F656; solvent cement, ASTM D2564. EXTERIOR BELOW GROUND 15" AND SMALLER:

Page 63: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

22 13 00-3

Type PSM PVC sewer pipe and socket fittings, SDR 35, Class 12454-B (PVC 1120), ASTM D3034; primer, ASTM F656; solvent cement, ASTM 2564; or integral bell and flexible elastomeric seal, ASTM D3212.

P A R T 3 - E X E C U T I O N GENERAL Install pipe and fittings in accordance with reference standards, manufacturers recommendations and recognized industry practices. PREPARATION Cut pipe ends square. Ream ends of piping to remove burrs. Clean scale and dirt from interior and exterior of each section of pipe and fitting prior to assembly. ERECTION Install all piping parallel to building walls and ceilings and at heights which do not obstruct any portion of a window, doorway, stairway, or passageway. Where interferences develop in the field, offset or reroute piping as required to clear such interferences. Coordinate locations of plumbing piping with piping, ductwork, conduit and equipment of other trades to allow sufficient clearances. In all cases, consult drawings for exact location of pipe spaces, ceiling heights, door and window openings, or other architectural details before installing piping. Where piping is embedded in masonry or concrete, provide protective sleeve covering of elastomeric pipe insulation. Install underground warning tape 6"-12" below finished grade above all exterior below ground piping. Where existing underground warning tape is encountered, repair and replace. Maintain piping in clean condition internally during construction. Provide clearance for installation of insulation, access to valves and piping specialties. Provide anchors, expansion joints, swing joints and/or expansion loops so that piping may expand and contract without damage to itself, equipment, or building. Do not route piping through transformer vaults or above transformers, panelboards, or switchboards, including the required service space for this equipment, unless the piping is serving this equipment Install all valves and piping specialties, including items furnished by others, as specified and/or detailed. Provide access to valves and specialties for maintenance. Make connections to all equipment, fixtures and systems installed by others where same requires the piping services indicated in this section. SOLVENT WELDED PIPE JOINTS Install in accordance with ASTM D2855 "Making Solvent Cemented Joints With PVC Pipe and Fittings". Saw cut piping square and smooth. Tube cutters may be used if they are fitted with wheels designed for use with PVC/CPVC pipe that do not leave a raised bead on pipe exterior. Support and restrain pipe during cutting to prevent nicks and scratches. Bevel ends 10-15 degrees and deburr interior. Remove dust, drips, moisture, grease and other superfluous materials from pipe interior and exterior. Check dry fit of pipe and

Page 64: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

22 13 00-4

fittings. Reject materials which are out of round or do not fit within close tolerance. Use heavy body solvent cement for large diameter fittings. Maintain pipe, fittings, primer and cement between 40 and 100 degrees during application and curing. Apply primer and solvent using separate daubers (3" and smaller piping only) or clean natural bristle brushes about 1/2 the size of the pipe diameter. Apply primer to the fitting socket and pipe surface with a scrubbing motion. Check for penetration and reapply as needed to dissolve surface to a depth of 4-5 thousandths. Apply solvent cement to the fitting socket and pipe in an amount greater than needed to fill any gap. While both surfaces are wet, insert pipe into socket fitting with a quarter turn to the bottom of the socket. Solvent cement application and insertion must be completed in less than 1 minute. Minimum of 2 installers is required on piping 4" and larger. Hold joint for 30 seconds or until set. Reference manufacturer recommendations for initial set time before handling and for full curing time before pressure testing. Cold weather solvent/cement may be utilized only under unusual circumstances and when specifically approved by the architect. SANITARY WASTE AND VENT Verify invert elevations and building elevations prior to installation. Install exterior piping pitched to drain at indicated elevations and slope. Install interior piping pitched to drain at minimum slope of 1/4" per foot where possible and in no case less than 1/8" per foot for piping 3" and larger. Install exterior piping below predicted frost level and not less than 5' bury depth to top of pipe wherever possible. Where piping is located above predicted frost level, provide frost protection in accordance with SPS 382.30(11)(c). Flush piping inlets (floor drains, hub drains, mop basins, fixtures, etc.) with high flow of water at completion of project to demonstrate full flow capacity. Remove blockages and make necessary repairs where flow is found to be impeded. PIPING SYSTEM LEAK TESTS Isolate or remove components from system which are not rated for test pressure. Perform final testing for medical and lab gas with all system components in place. Test piping in sections or entire system as required by sequence of construction. Do not insulate or conceal pipe until it has been successfully tested. If required for the additional pressure load under test, provide temporary restraints at fittings or expansion joints. Backfill underground water mains prior to testing with the exception of thrust restrained valves which may be exposed to isolate potential leaks. For hydrostatic tests, use clean water and remove all air from the piping being tested by means of air vents or loosening of flanges/unions. Measure and record test pressure at the high point in the system. For air or nitrogen tests, gradually increase the pressure to not more than one half of the test pressure; then increase the pressure in steps of approximately one-tenth of the test pressure until the required test pressure is reached. Examine all joints and connections with a soap bubble solution or equivalent method. System will not be approved until it can be demonstrated that there is no measurable loss of test pressure during the test period. Inspect system for leaks. Where leaks occur, repair the area with new materials and repeat the test; caulking will not be acceptable.

Page 65: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY

22 13 00-5

Test Initial Test Final Test

Sanitary Waste and Vent Water N/A 10' water 2 hr System Medium Pressure Duration Pressure Duration

Pressurized Sanitary Waste & Vent Water N/A 100 psig 2 hr Acid Waste and Vent Water N/A 10' water 2 hr

END OF SECTION

Page 66: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2
Page 67: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 26 05 00 - 1

SECTION 26 05 00 COMMON WORK RESULTS FOR ELECTRICAL

PART 1 - GENERAL

The electrical work included in all other divisions is the responsibility of the contractor performing the division 26 work unless noted otherwise. PROJECT OVERVIEW

SCOPE The work under this section includes basic electrical requirements, which are applicable to all Division 26 sections. This section includes information common to two or more technical specification sections or items that are of a general nature, not conveniently fitting into other technical sections. Included are the following topics: RELATED WORK Applicable provisions of Division 1 govern work under this Section. NFPA 70 - National Electrical Code. REFERENCE STANDARDS Abbreviations of standards organizations referenced in this and other sections are as follows: ANSI American National Standards Institute ASTM American Society for Testing and Materials EPA Environmental Protection Agency ETL Electrical Testing Laboratories, Inc. IEEE Institute of Electrical and Electronics Engineers IES Illuminating Engineering Society ISA Instrument Society of America NBS National Bureau of Standards NEC National Electric Code NEMA National Electrical Manufacturers Association NESC National Electrical Safety Code NFPA National Fire Protection Association UL Underwriters Laboratories Inc. REGULATORY REQUIREMENTS All work and materials are to conform in every detail to applicable rules and requirements of the National Electrical Code (NFPA 70), other applicable National Fire Protection Association codes, the National Electrical Safety Code, and present manufacturing standards (including NEMA). All Division 26 work shall be done under the direction of a currently licensed State of Michigan Electrician. QUALITY ASSURANCE Where equipment or accessories are used which differ in arrangement, configuration, dimensions, ratings, or engineering parameters from those indicated on the contract documents, the contractor is responsible for all costs involved in integrating the equipment or accessories into the system and the assigned space, and for obtaining the performance from the system into which these items are placed. Manufacturer references used herein are intended to establish a level of quality and performance requirements unless more explicit restrictions are stated to apply. All materials, except medium voltage equipment and components, shall be listed by and shall bear the label of an approved electrical testing laboratory. If none of the approved electrical testing laboratories has published standards for a particular item, then other national independent testing standards, if available, applicable, shall apply and such items shall bear those labels. Where one of the approved electrical testing

Page 68: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 26 05 00 - 2

laboratories has an applicable system listing and label, the entire system, except for medium voltage equipment and components, shall be so labeled. PROTECTION OF FINISHED SURFACES Furnish one can of touch-up paint for each different color factory finish furnished by the Contractor. Deliver touch-up paint with other "loose and detachable parts" as covered in the General Requirements. APPROVED ELECTRICAL TESTING LABORATORIES The following laboratories are approved for providing electrical product safety testing and listing services as required in these specifications: Underwriters Laboratories Inc. Electrical Testing Laboratories, Inc. PROVISIONS FOR FUTURE WORK

INTENT The Contractor shall furnish and install all the necessary materials, apparatus, and devices to complete the electrical equipment and systems installation herein specified, except such parts as are specifically exempted herein. If an item is either called for in the specifications or shown on the plans, it shall be considered sufficient for the inclusion of said item in this contract. If a conflict exists within the Specifications or exists within the Drawings, the Contractor shall furnish the item, system, or workmanship, which is the highest quality, largest, or most closely fits the intent (as determined by the Architect). It must be understood that the details and drawings are diagrammatic. The Contractor shall verify all dimensions at the site and be responsible for their accuracy. All sizes as given are minimum except as noted. Materials and labor shall be new (unless noted or stated otherwise), first class, and workmanlike, and shall be subject at all times to the A/E's inspections, tests and approval from the commencement until the acceptance of the completed work. Whenever a particular manufacturer's product is named, it is intended to establish a level of quality and performance requirements unless more explicit restrictions are stated to apply. OMISSIONS No later than ten (10) days before bid opening, the Contractor shall call the attention of the Architect to any materials or apparatus the Contractor believes to be inadequate and to any necessary items of work omitted. SUBMITTALS Submit for all equipment and systems as indicated in the respective specification sections, marking each submittal with that specification section number. Mark general catalog sheets and drawings to indicate specific items being submitted and proper identification of equipment by name and/or number, as indicated in the contract documents. Failure to do this may result in the submittal(s) being returned to the Contractor for correction and resubmission. Failing to follow these instructions does not relieve the Contractor from the requirement of meeting the project schedule. On request, the successful bidder shall furnish additional drawings, illustrations, catalog data, performance characteristics, etc. Submittals shall be grouped to include complete submittals of related systems, products, and accessories in a single submittal. Mark dimensions and values in units to match those specified. Include wiring diagrams of electrically powered equipment. The submittals must be approved before fabrication is authorized. Submit sufficient quantities of submittals to allow the following distribution:

Page 69: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 26 05 00 - 3

Operating and Maintenance Manuals 1 copies User agency 1 copy A/E 1 copy PROJECT/SITE CONDITIONS

Install Work in locations shown on drawings, unless prevented by project conditions. Prepare drawings showing proposed rearrangement of work to meet project conditions, including changes to work specified in other sections. Obtain permission of Architect before proceeding. Tools, materials and equipment shall be confined to areas designated by the Architect. WORK SEQUENCE AND SCHEDULING Install work in phases to accommodate user agency's occupancy requirements. During the construction period coordinate electrical schedule and operations with Owners Construction Representative. WORK BY OTHER TRADES Every attempt has been made to indicate in this trade's specifications and drawings all work required of this Contractor. However, there may be additional specific paragraphs in other trade specifications and addenda, and additional notes on drawings for other trades which pertain to this trade's work, and thus those additional requirements are hereby made a part of these specifications and drawings. Electrical details on drawings for equipment to be provided by others are based on preliminary design data only. This Contractor shall lay out the electrical work and shall be responsible for its correctness to match equipment actually provided by others. OFFSITE STORAGE Prior approval by the A/E will be needed. The contractor shall submit Storage Agreement Form DOA-4528 to Owner for consideration of off-site materials storage. In general, building wire, conduit, fittings and similar rough-in material will not be accepted for off-site storage. No material will be accepted for off-site storage unless shop drawings for the material have been approved. SALVAGE MATERIALS No materials removed from this project shall be reused. All materials removed shall become the property of and shall be disposed of by the Contractor. CERTIFICATES AND INSPECTIONS Obtain and pay for all required State installation inspections, in accordance with the Michigan Building Code. Deliver originals of these certificates to the Architect. This contractor is responsible for coordination of electrical inspection. OPERATION AND MAINTENANCE DATA All operations and maintenance data shall comply with the submission and content requirements specified under section GENERAL REQUIREMENTS. In addition to the general content specified under GENERAL REQUIREMENTS supply the following additional documentation:

1. Manufacturer’s wiring diagrams for electrically powered equipment. RECORD DRAWINGS The Contractor shall maintain at least one copy each of the specifications and drawings on the job site at all times.

Page 70: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 26 05 00 - 4

Contractor to provide a suitable set of contract drawings on which daily records of changes and deviations from contract shall be recorded. Dimensions and elevations on the record drawings shall locate all buried or concealed piping, conduit, or similar items. The daily record of changes shall be the responsibility of Contractor's field superintendent. No arbitrary mark-ups will be permitted. At completion of the project, the Contractor shall submit the marked-up record drawings to the Architect/Engineer prior to final payment.

PART 2 - PRODUCTS ACCESS PANELS AND DOORS

Plaster Walls and Ceilings: 16 gauge frame with not less than a 20 gauge hinged door panel, prime coated steel for general applications, stainless steel for use in toilets, showers and similar wet areas, concealed hinges, screwdriver operated cam latch for general application, key lock for use in public areas, UL listed for use in fire rated partitions if required by the application. Use the largest size access opening possible, consistent with the space and the equipment needing service; minimum size is 12" by 12".

IDENTIFICATION See Electrical section 26 05 53 – Identification for Electrical Systems. SEALING AND FIRE STOPPING NON-RATED PENETRATIONS: Conduit Penetrations Through Below Grade Walls: In exterior wall openings below grade, use a modular mechanical type seal consisting of interlocking synthetic rubber links shaped to continuously fill the annular space between the uninsulated conduit and the cored opening or water-stop type wall sleeve. Conduit and Cable Tray Penetrations: At conduit and cable tray penetrations of non-rated interior partitions, floors and exterior walls above grade, use urethane caulk in annular space between conduit and sleeve, or the core drilled opening.

PART 3 - EXECUTION EXCAVATION AND BACKFILL Perform all excavation and backfill work to accomplish indicated electrical systems installation in accordance with section 31 23 16.13 - Trenching. Blasting will not be allowed. BUILDING ACCESS Arrange for the necessary openings in the building to allow for admittance of all apparatus. When the building access was not previously arranged and must be provided by this contractor, restore any opening to its original condition after the apparatus has been brought into the building. EQUIPMENT ACCESS Install all piping, conduit, ductwork, and accessories to permit access to equipment for maintenance. Coordinate the exact location of wall and ceiling access panels and doors with the General Contractor, making sure that access is available for all equipment and specialties. Where access is required in plaster or drywall walls or ceilings, furnish the access doors to the General Contractor and reimburse the General Contractor for installation of those access doors. COORDINATION

Page 71: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 26 05 00 - 5

The Contractor shall cooperate with other trades and DFD in locating work in a proper manner. Should it be necessary to raise or lower or move longitudinally any part of the electrical work to better fit the general installation, such work shall be done at no extra cost to the DFD, provided such decision is reached prior to actual installation. The Contractor shall check location of electrical outlets with respect to other installations before installing. The Contractor shall verify that all devices are compatible for the surfaces on which they will be used. This includes, but is not limited to light fixtures, panelboards, devices, etc. and recessed or semi-recessed heating units installed in/on architectural surfaces. Coordinate all work with other contractors prior to installation. Any installed work that is not coordinated and that interferes with other contractor's work shall be removed or relocated at the installing contractor's expense. Cooperate with the testing consultant in ensuring specification Section 26 05 04 compliance. Verify system completion to the testing consultant. Demonstrate the starting, interlocking and control features of each system so the testing contractor can perform their work. SLEEVES AND OPENINGS Conduit penetrations in new poured concrete horizontal construction requiring F and T rating: Form opening using hole form or core drill opening. Alternatively provide cast in place fire stopping devices/sleeves. Conduit penetrations in new poured concrete horizontal construction requiring F rating but no T rating: Same as conduit penetrations in new poured concrete construction requiring F and T ratings except that schedule 40 steel pipe sleeves may also be used. Conduit penetrations in new poured concrete horizontal construction that do not require F or T ratings: Provide schedule 40 steel pipe sleeve, form opening using hole form or core drill opening. Conduit penetrations in existing concrete floors: Core drill openings. Conduit penetrations through existing floors located in food service areas that do not require a T rating: Core drill sleeve opening large enough to insert schedule 40 sleeve, extend sleeve 2 inches above the floor and grout area around sleeve with hydraulic setting, non-shrink grout. Where penetrating conduit weight is supported by floor, provide manufactured product or structural bearing collar designed to carry load. SEALING AND FIRE STOPPING NON-RATED PENETRATIONS: In exterior wall openings below grade, assemble rubber links of mechanical seal to the proper size for the conduit and tighten in place, in accordance with the manufacturer's instructions. Install so that the bolts used to tighten the seal are accessible from the interior of the building or vault. At all interior walls and exterior walls, conduit penetrations are required to be sealed. Apply sealant to both sides of the penetration in such a manner that the annular space between the sleeve or cored opening and the conduit is completely blocked. PENETRATIONS SUBJECT TO WATER INTRUSION: For penetrations (both rated and non-rated) in floors subject to water intrusion or in rooms housing electrical equipment (but not within walls) provide one of the following:

• Conduit penetration where steel pipe sleeve is used extend steel sleeve 2” above the floor. • Conduit penetration where cast in place fire stopping device/sleeve is used, extend device/sleeve

2” above the floor (provided it meets the device’s UL listing).

Page 72: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 26 05 00 - 6

• Conduit penetration where there is no steel sleeve or cast in place fire stopping device/sleeve, provide 2”x 2” x 1/8” galvanized steel angles fastened to floor surrounding the penetration or group of penetrations to prevent water from getting to penetration. Provide urethane caulk between angles and floor and fasten angles to floor minimum 8”on center. Seal corners water tight with urethane caulk.

Floors subject to water intrusion or rooms housing electrical equipment include the following locations:

• Food Service/Kitchen Areas • Restrooms • Mechanical/Plumbing Equipment Rooms • Electrical Equipment Rooms

Provide waterproof caulk sealant top coating on fire stopping system (or other approved means to protect the fire stopping system from water) in areas subject to wash down such as Food Service and Dish Washing Areas. HOUSEKEEPING AND CLEAN UP The Contractor shall clean up and remove from the premises, on a daily basis, all debris and rubbish resulting from its work and shall repair all damage to new and existing equipment resulting from its work. When job is complete, this Contractor shall remove all tools, excess material and equipment, etc., from the site. AGENCY TRAINING Contractor to provide factory authorized representative and/or field personnel knowledgeable with the operations, maintenance and troubleshooting of the system and/or components defined within this section.

END OF SECTION

Page 73: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 26 05 19 - 1

SECTION 26 05 19 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLE

PART 1 - GENERAL

SCOPE The work under this section includes furnishing and installing required wiring and cabling systems including pulling, terminating and splicing. Included are the following topics: RELATED WORK Applicable provisions of Division 1 govern work under this Section. Section 26 05 33 – Raceway and Boxes for Electrical Systems. SUBMITTALS Submit product data: Provide for each cable assembly type. Submit factory test reports: Indicate procedures and values obtained. Submit shop drawings for modular wiring system including layout of distribution devices, branch circuit conduit and cables, circuiting arrangement, and outlet devices. Submit manufacturer's installation instructions. Indicate application conditions and limitations of use stipulated by product testing agency specified under Regulatory Requirements. PROJECT CONDITIONS Verify that field measurements are as shown on Drawings. Conductor sizes are based on copper. Wire and cable routing shown on Drawings is approximate unless dimensioned. Route wire and cable as required to meet project conditions. Where wire and cable routing is not shown, and destination only is indicated, determine exact routing and lengths required.

PART 2 - PRODUCTS

GENERAL All wire shall be new, delivered to the site in unbroken cartons and shall be less than one year old out of manufacturer's stock. All conductors shall be copper. Aluminum conductors size #1/0 and larger may be substituted for copper and used for phase and neutral conductors for transformer feeders, switchboard feeders, and panelboard feeders. All ground conductors shall be copper. Aluminum conductors shall not be used for serving individual motors, chillers, VFD’s and motor controllers. The following requirements shall be met when aluminum conductors are used:

Aluminum alloy conductors shall be compact stranded conductors of a recognized Aluminum Association 8000 Series aluminum alloy conductor material (AA-8000 series alloy). It is the responsibility of the contractor to increase the size of the conduit, wire gutter, or enclosure, if necessary, to accommodate the aluminum conductors and meet allowable code requirements. It is the responsibility of the contractor to increase the size of the aluminum conductor and associated termination lugs to match the ampacity of the copper conductor circuit shown on the Drawings.

Page 74: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 26 05 19 - 2

The contractor shall submit a feeder schedule to the Engineer for all conductor substitutions indicating the aluminum conductor wire size and the conduit size. The contractor shall not begin the installation until written approval is granted by the Engineer. All aluminum conductors shall terminate on a mechanical screw-type connector or mechanical compression-type connector. Connector shall be dual rated (AL7CU or AL9CU) and Listed by UL for use with aluminum and copper conductors, and sized to accept aluminum conductors of the required ampacity. When using compression-type connectors, the lugs shall be marked with wire size, die index, number and location of crimps and shall be suitably color-coded. Using a suitable stripping tool, remove insulation from the required length of the conductor. Wire brush the conductor and apply a Listed joint compound. Tighten or crimp the connection per the connector manufacturer’s recommendation. Wipe off any excess joint compound. When terminating aluminum conductors to aluminum bus, prepare a mechanical screw-type or compression-type connection. Bolts shall be anodized alloy and conform to current ANSI and ASTM chemical and mechanical property limits. Nuts shall be aluminum alloy and conform to current ANSI standards. Washers shall be flat aluminum alloy, Type A plain, standard wide series conforming to current ANSI standards. Lubricate and tighten the hardware per manufacturer’s recommendations. When terminating aluminum conductors to copper bus, prepare a mechanical screw-type or compression-type connection. Bolts shall be plated or galvanized medium carbon steel; heat treated, quenched and tempered equal to current ASTM standard or SAE grade 5. Nuts shall conform to current ANSI standards. Washers shall be steel, Type A plain, standard wide series conforming to current ANSI standards. Belleville conical spring washers shall be of hardened steel, cadmium plated or silicone bronze. Lubricate and tighten the hardware per manufacturer’s recommendations. The final tightening torque shall be recorded for all aluminum conductor mechanical screw-type connections and provided in report form, in the completed O&M manuals. The contractor shall perform an infrared survey of all aluminum conductor connections after the installation is complete and in normal service. Infrared surveys shall be performed during periods of maximum possible loading with at least 30% of rated load of the equipment being inspected. All connections with elevated temperatures shall be corrected by the contractor. The infrared survey results shall be provided in report form, in the completed O&M manuals.

No copper-to-aluminum transitions permitted when splicing onto existing copper feeders. Insulation shall have a 600 volt rating. All conductors shall be stranded.

Stranded conductors may only be terminated with UL OR ETL Listed type terminations or methods: e.g. stranded conductors may not be wrapped around a terminal screw but must be terminated with a crimp type device or must be terminated in an approved back wired method.

BUILDING WIRE Description: Single conductor insulated wire 90 degree C. Insulation: Type THHN/THWN-2, XHHW-2 insulation. SERVICE ENTRANCE CONDUCTORS Description: Single conductor or multi-conductor insulated wire. 90 degree C sized at the 75 degree C table. Insulation: Type USE-2, XHHW-2 insulation for service entrance conductors routed from exterior source

to exterior termination location. Type XHHW-2 insulation for services entrance conductors routed from exterior source to interior termination location.

VARIABLE FREQUENCY DRIVE (VFD) WIRE

Page 75: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 26 05 19 - 3

All power wiring from the VFD output to the motor shall be type XHHW-2 insulation, single conductor wire. ABOVE GROUND WIRE FOR EXTERIOR WORK Description: Single conductor insulated wire, 90 degree C. Insulation: Type THHN/THWN-2, XHHW-2 insulation. UNDERGROUND WIRE FOR EXTERIOR WORK Description: Stranded single or multiple conductor insulated wire, 90 degree C. Insulation: Type USE-2, XHHW-2, RHW-2 insulation. This wiring shall be used in all underground feeder and branch circuit applications, except THHN/THWN-2 is permitted when run in a concrete-encased ductbank. EMERGENCY CIRCUITS (2-HOUR RATED) Description: Power cable assembly for fire pump circuits and emergency circuits requiring a minimum 2-hour rating. Insulation: Type MI mineral insulated cable installed as a listed electrical circuit protective system with a minimum 2-hour fire-resistive cable rating per Factory Mutual testing. UL 2196 and ULC-S139-00 approved. Install and support cabling system per manufacturer’s requirements. WIRING CONNECTORS Split Bolt Connectors: Not acceptable. Solderless Pressure Connectors: High copper alloy terminal. May be used only for cable termination to equipment terminals. Not approved for splicing. Twist Type Wire Connectors: Solderless twist type spring connector (wire-nut) with insulating cover for copper wire splices and taps. Use for conductor sizes 10 AWG and smaller. The manufacturer’s wire fill capacity must be followed.

All wire connectors used in underground or exterior pull boxes or hand holes shall be gel filled twist connectors or a connector designed for damp and wet locations. Gel filled twist type connectors can be used for copper conductor sizes 6 AWG and smaller for site lighting applications. The manufacturer’s wire fill capacity must be followed.

Mechanical Connectors: Bolted type tin-plated; high conductivity copper alloy; spacer between conductors; beveled cable entrances. Compression (crimp) Connectors: Long barrel; seamless, tin-plated electrolytic copper tubing; internally beveled barrel ends. Connector shall be clearly marked with the wire size and type and proper number and location of crimps. Connector must be installed with a crimper tool listed for use with the manufacturer and type of compression connector. Insulation Piercing Connectors: Molded insulated body, copper teeth, wrench tightened, UL 486B Listed. May be used only for connection of a tap conductor in run and tap type applications when main conductor is 8 AWG and larger.

PART 3 - EXECUTION GENERAL WIRING METHODS All wire and cable shall be installed in conduit. Do not use wire smaller than 12 AWG for power and lighting circuits. All phase, neutral and ground conductors shall be sized to prevent excessive voltage drop at rated circuit ampacity. As a minimum use 10 AWG conductors for 20 ampere, 120 volt branch circuit home runs longer than 100 feet (30 m), and for 20 ampere, 277 volt branch circuit home runs longer than 200 feet (61 m).

Page 76: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 26 05 19 - 4

Make conductor lengths for parallel conductors equal. Splice only in junction or outlet boxes. No conductor less than 10 AWG shall be installed in exterior underground conduit. Identify ALL low voltage wire, 600V and lower. Neatly train and lace wiring inside boxes, equipment, and panelboards. WIRING INSTALLATION IN RACEWAYS Pull all conductors into a raceway at the same time. Use Listed water or silicone based wire pulling lubricant for pulling 4 AWG and larger wires and for other conditions when necessary. Wax based lubricants are not allowed. Pulling lubricant is not required for low friction type products where the cable manufacturer recommends that cables be pulled without lube. Install wire in raceway after interior of building has been physically protected from the weather and all mechanical work likely to injure conductors has been completed. Completely and thoroughly swab raceway system before installing conductors. Place all conductors of a given circuit (this includes phase wires, neutral (if any), and ground conductor) in the same raceway. If parallel phase and/or neutral wires are used, then place an equal number of phase and neutral conductors in same raceway or cable. VFD Installations: Install VFD input wiring and output wiring in separate conduit systems. Do not mix VFD input power and output power, or control wiring in a common raceway. In high ambient spaces, mechanical rooms, utility rooms and exterior exposed conduit, 90 degree C conductors shall be utilized. WIRING CONNECTIONS AND TERMINATIONS Splice only in accessible junction boxes. Wire splices and taps shall be made firm, and adequate to carry the full current rating of the respective wire without soldering and without perceptible temperature rise. All splices shall be so made that they have an electrical resistance not in excess of two feet (600 mm) of the conductor. Use solderless twist type spring connectors (wire nuts) with insulating covers for wire splices and taps, 10 AWG and smaller. Use mechanical or compression connectors for wire splices and taps, 8 AWG and larger. Tape uninsulated conductors and connectors with electrical tape to 150 percent of the insulation value of the wiring. Thoroughly clean wires before installing lugs and connectors. At all splices and terminations, leave tails long enough to cut splice out and completely re-splice. FIELD QUALITY CONTROL Field inspection and testing will be performed under provisions of Section 26 05 04.

Additional testing as follows shall be performed if aluminum conductors are used: Feeders terminated with aluminum conductors shall be tested with a thermal imager and recorded. Conductors shall be closely checked for loose or poor connections, and for signs of overheating or corrosion. Test procedures shall meet NETA guidelines. Test results and report shall be provided to the engineer and included in O&M manual under AL conductors/ tests.

Page 77: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 26 05 19 - 5

Contractor shall correct all deficiencies reported in the test report.

WIRE COLOR General:

Solid colored insulation is required for all THHN/THWN-2 wire. For other wire types use colored wire or identify wire with colored tape at all terminals, splices and boxes. Wire shall be colored as indicated below. Use black and red for single phase circuits at 120/240 volts, use Phase A black, Phase B red and Phase C blue for circuits at 120/208 volts single or three phase, and use Phase A brown, Phase B orange and Phase C yellow for circuits at 277/480 volts single or three phase. Note: This includes fixture whips except for Listed whips mounted by the fixture manufacturer on the fixture and Listed as a System. Switch legs shall be the same color as their associated circuit, except for the second switch leg used for dual-level switching. The second switch leg shall be the next phase color, e.g. if the first switch leg is brown (277/480V phase A), the second switch leg shall be orange (277/480V phase B). Traveler conductors run between 3 and 4 way switches shall be colored pink or purple.

Neutral Conductors: White for 120/208V and 120/240V systems, Gray for 277/480V systems. Where there are two or more neutrals in one conduit, each shall be individually identified with a different stripe. Branch Circuit Conductors: Three or four wire home runs shall have each phase uniquely color coded. Feeder Circuit Conductors: Each phase shall be uniquely color coded. Ground Conductors: Green colored insulation for THHN/THWN-2 wire. For other wire types use green colored wire or identify wire with green tape at both ends and at all access points, such as panelboards, motor starters, disconnects and junction boxes. When isolated grounds are required, contractor shall provide green with yellow tracer. BRANCH CIRCUITS The use of single-phase, multi-wire branch circuits with a common neutral is not permitted. All single-phase branch circuits shall be furnished and installed with an individual accompanying neutral, sized the same as the phase conductors. EMERGENCY CIRCUITS All Emergency, Legally Required Standby and Optional Standby system wiring shall be installed in separate raceways after their associated transfer switches. The wiring shall be separate from each other and from all normal system wiring. All emergency wiring serving fire pumps, requiring minimum 2 hour fire rating shall comply with NEC 695.6(B). All emergency wiring serving NEC 700 loads, requiring minimum 2 hour fire rating shall comply with NEC 700.10(D)(1). All generator control conductors installed between transfer equipment and the emergency generator serving Emergency, Legally Required Standby and Optional Standby systems shall be kept entirely independent of all other wiring. This shall require a dedicated conduit system between each transfer switch and the emergency generator. If a Fire Pump is served off the emergency generator, a separate conduit shall be provided between fire pump controller and generator.

END OF SECTION

Page 78: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2
Page 79: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 26 05 33 - 1

SECTION 26 05 33 RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS

PART 1 - GENERAL

SCOPE This section describes the products and execution requirements relating to furnishing and installing raceways and boxes and related systems as part of a raceway system for electrical, communications, and other low-voltage systems for the project. Included are the following topics: RELATED WORK Applicable provisions of Division 1 govern work under this section. Section 27 10 00 - Structured Cabling Section 28 31 00 – Fire Detection and Alarm. REFERENCES NFPA 70 - National Electrical Code. SUBMITTALS Surface Raceway System - submit product data and catalog sheets for all components. Boxes - provide product data showing configurations, finishes, dimensions, and manufacturer's instructions. Conduits in Concrete Slabs Above Grade - provide proposed conduit routing and sizing to Structural Engineer prior to approval of installation to verify structural integrity and fire rating of concrete slab.

PART 2 - PRODUCTS GENERAL All steel fittings and conduit bodies shall be galvanized. No cast metal or split-gland type fittings permitted. Mogul-type condulets larger than 2 inch (50 mm) not permitted except as approved or detailed. All condulet covers must be fastened to the condulet body with screws and be of the same manufacture. C-condulets shall not be used in lieu of pull boxes. All boxes shall be of sufficient size to provide free space for all conductors enclosed in the box and shall comply with NEC requirements. RIGID METAL CONDUIT (RMC) AND FITTINGS Conduit: Heavy wall threaded, galvanized steel, schedule 40. Fittings and Conduit Bodies: Use all steel threaded fittings and conduit bodies. Expansion Fittings/Expansion Joints: Expansion Fittings shall be Internal Grounding type and shall not rely on external bonding jumpers to maintain grounding continuity between raceway components. ELECTRICAL METALLIC TUBING (EMT) AND FITTINGS Conduit: Steel, galvanized tubing. Fittings: All steel, set screw type. No push-on or indenter types permitted. Conduit Bodies: All steel threaded conduit bodies. ELECTRICAL NONMETALLIC TUBING (ENT) AND FITTINGS Conduit: ENT (smurf tube), UL listed and NEC recognized.

Page 80: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 26 05 33 - 2

Fittings: One piece quick connect fittings for 1/2 inch to 1 inch size and schedule 40 cemented fittings for larger size. When installed in concrete, fittings shall be suitable for damp locations and shall be concrete–tight, stub-ups and stub-downs kits shall meet manufacturer’s recommendations. RIGID POLYVINYL CHLORIDE CONDUIT (PVC) AND FITTINGS Conduit: Rigid non-metallic conduit, Schedule 40 PVC minimum, Listed, sunlight resistant, rated for 900 C conductors. Schedule 80 for locations exposed to physical damage or as required. Fittings and Conduit Bodies: NEMA TC 2, Listed. FIBERGLASS RESIN CONDUIT (RTRC) AND FITTINGS: Conduit: Reinforced Thermosetting Resin Conduit RTRC, Type AG (Above Ground) and XW (Exposed), and UL 2515 AG (Above Ground) or UL 2420 BG (Below Ground) listed. Fittings, Factory Elbows and Conduit Bodies: Match Conduit. HIGH DENSITY POLYETHYLENE CONDUIT (HDPE) AND FITTINGS Conduit: Continuous length smooth-wall HDPE conduit for electrical applications produced to ASTM F2160. Conduit shall be listed by a Nationally Recognized Testing Laboratory to UL Standard 651-A for smooth-wall duct to be used as electrical conduit for the installation of Listed electrical cables underground. The recommended HDPE color is black or black with red stripes. Red identifies the conduit as electrical and black provides UV protection for storage and at points where the conduit may exit the ground. Fittings: Threaded Mechanical Fittings: Aluminum reverse-threaded conduit couplers designed for use with HDPE conduit. Compression Fittings and Socket Couplings designed for use with HDPE conduit may also be used. CONDUIT WATER SEALANT Description: Conduit sealant used to prevent water from entering buildings via conduits. Sealant shall seal conduits against water and gas intrusion, such as Polywater® FST™-250 Foam Duct Sealant, Raychem RDSS Rayflate Duct Sealing System, or approved alternate. Sealant shall be re-enterable, shall be compatible with the conduit and conductor types being used, and shall comply with NEC 225.27, 230.8, and 300.5(G). Manufacturer names and catalog numbers are used to develop quality and performance requirements only. Products manufactured by others may be acceptable provided they meet or exceed the specifications. PULL AND JUNCTION BOXES Interior Sheet Metal Boxes: code gauge galvanized steel, screw covers, flanged and spot welded joints and corners. Interior Sheet Metal Boxes larger than 12 inches (300 mm) in any dimension shall have a hinged cover or a chain installed between box and cover. Exterior Boxes and Wet Location Installations: Type 4 and Type 6, flat-flanged, surface-mounted junction box, UL listed as rain-tight. [Galvanized cast iron][Aluminum][PVC] box and cover with ground flange, neoprene gasket, and stainless steel cover screws. Box extensions and adjacent boxes within 48 inches of each other are not allowed for the purpose of creating more wire capacity. Junction boxes 6 inch-by-6 inch or larger size shall be without stamped knock-outs. Wireways shall not be used in lieu of junction boxes. OUTLET BOXES Sheet Metal Outlet Boxes: galvanized steel, with stamped knockouts.

Page 81: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 26 05 33 - 3

Luminaire and Equipment Supporting Boxes: Rated for weight of equipment supported; include 3/8 inch male fixture studs where required. Cast Boxes: Cast ferroalloy or aluminum, deep type, gasketed cover, threaded hubs.

BOXES FOR FIRE ALARM AUDIO-VISUAL NOTIFICATION APPLIANCES Recessed boxes for Fire Alarm audio, visual, and audio-visual notification appliances shall be galvanized steel sheet metal with stamped knockouts. Boxes shall be 4 inches square (100 mm) by 2 1/8 inches (54 mm) deep, and shall be painted red. For surface mounting, use manufacturer supplied back boxes and trim plates

, painted red or off white, and shall contain no visible conduit knock-outs. Mark each device with its circuit number.

PART 3 - EXECUTION CONDUIT SIZING, ARRANGEMENT, AND SUPPORT EMT is permitted to be used in sizes 4 inch (100 mm) and smaller for power and low-voltage systems. See CONDUIT INSTALLATION SCHEDULE below for other limitations for EMT and other types of conduit. Size power conductor raceways for conductor type installed. Conduit size shall be 1/2 inch (16 mm) minimum except all homerun conduits shall be 3/4 inch (21 mm), or as specified elsewhere. Caution: Per the NEC, the allowable conductor ampacity is reduced when more than three current-carrying conductors are installed in a raceway. Contractor must take the NEC ampacity adjustment factors into account when sizing the raceway and wiring system.

Size communications and other low-voltage systems raceways as follows:

Communications, including Outlet Box: [1] [1 1/4] inch minimum. Conduit used for single device locations (e.g. Wireless Access Point, Video Surveillance Camera, and Wall mounted telephone) may be 3/4 inch minimum. Fire Alarm: 1/2 inch minimum.

Provide one raceway from each communications outlet box to above accessible ceiling. Arrange conduit to maintain 6’-8” clear headroom and present a neat appearance. Route exposed conduit and conduit above accessible ceilings parallel and perpendicular to walls and adjacent piping. Maintain minimum 6 inch (150 mm) clearance between conduit and piping. Maintain 12 inch (300 mm) clearance between conduit and heat sources such as flues, steam pipes, and heating appliances. Arrange conduit supports to prevent distortion of alignment by wire pulling operations. Fasten conduit using galvanized pipe straps, conduit racks (lay-in adjustable hangers), clevis hangers, or bolted split stamped galvanized hangers. Group conduit in parallel runs where practical and use conduit rack (lay-in adjustable hangers) constructed of steel channel with conduit straps or clamps. Provide space for 25 percent additional conduit. Do not fasten conduit with wire or perforated pipe straps. Before conductors are pulled, remove all wire used for temporary conduit support during construction. Support and fasten metal conduit at a maximum of 8 feet (2.4 m) on center. Supports shall be independent of the installations of other trades, e.g. ceiling support wires, HVAC pipes, other conduits, etc., unless so approved or detailed.

Page 82: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 26 05 33 - 4

Conceal all conduits except where noted on the drawings or approved by the Architect/Engineer. Contractor shall verify with Architect/Engineer all surface conduit installations except in mechanical rooms. Changes in direction shall be made with symmetrical bends, cast steel boxes, stamped metal boxes or cast steel conduit bodies. For indoor conduits, no continuous conduit run shall exceed 100 feet (30 meters) without a junction box. All conduits installed in exposed areas shall be installed with a box offset before entering box. CONDUIT INSTALLATION Cut conduit square; de-burr cut ends. Conduit shall not be fastened to the corrugated metal roof deck. Bring conduit to the shoulder of fittings and couplings and fasten securely. Use conduit hubs for fastening conduit to cast boxes. Use sealing locknuts or conduit hubs for fastening conduit to sheet metal boxes in damp or wet locations. Terminate all conduit (except for terminations into conduit bodies) using conduit hubs, or connectors with one locknut, or utilize double locknuts (one each side of box wall). Provide bushings for the ends of all conduit not terminated in box walls. Refer to Section 26 05 26 – Grounding and Bonding for Electrical Systems for grounding bushing requirements. Provide insulated bushings where raceways contain 4 AWG or larger conductors. Install no more than the equivalent of: Three 90 degree bends between boxes for electrical systems.

Two 90 degree bends between boxes for communications and other low voltage systems. No single bend may exceed 90 degrees.

Use hydraulic one-shot conduit bender or factory elbows for bends in conduit larger than 2 inch (50 mm) size unless sweep elbows are required. Bend conduit according to manufacturer’s recommendations. Torches or open flame shall not be used to aid in bending of PVC conduit. Use suitable conduit caps or other approved seals to protect installed conduit against entrance of dirt and moisture. Provide 1/8 inch (3 mm) nylon pull string in empty conduit, except sleeves and nipples. Install expansion-deflection joints where conduit crosses building expansion joints. Note: expansion-deflection joints are not required where conduit crosses building control joints if the control joint does not act as an expansion joint. Install expansion joints where direct-buried conduit is subject to Earth Movement by settlement or frost per NEC 300.5(J), especially where conduit exits the ground exposed and enters a box, cabinet, or enclosure attached to a building or structure. Install expansion fitting in exterior PVC conduit runs per NEC table 352.44 utilizing a minimum temperature change of 120 degree F. Avoid moisture traps where possible. Where moisture traps are unavoidable, provide junction boxes with drain fittings at conduit low points. Where conduit passes between areas of differing temperatures such as into or out of cool rooms, freezers, unheated and heated spaces, buildings, etc., provide condulet or box with duct seal or other means to prevent the passage of moisture and water vapor through the conduit.

Page 83: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 26 05 33 - 5

Route conduit through roof openings for piping and ductwork where possible. Where communication cabling is to be installed in conduit to the wiring hub (e.g. Telecom Room), multiple conduits may be consolidated into fewer, larger conduits. Capacity of shared conduits shall equal the capacity of the individual conduits unless otherwise noted. Use NRTL listed metallic grounding clamps when terminating conduit to cable tray. Ground and bond conduit under provisions of Section 26 05 26. Conduit is not permitted in any slab topping of two inches (50 mm) or less. Identify conduit under provisions of Section 26 05 53. All conduit installed underground (exterior to building) shall be buried a minimum of 24 inches below finished grade, whether or not the conduit is concrete encased. Install warning tape 12" below finish grade over all buried conduits. Underground warning tape shall be detectable, 2” wide minimum, 5 mil thickness, containing a foil core. Tape color shall be red and labeled with the words "CAUTION-BURIED ELECTRIC LINE BELOW" as manufactured by Presco or similar. Conduits penetrating underground foundation walls: Individual conduits or each conduit as part of a ductbank penetrating underground foundation walls (excluding manholes) shall be sealed against water intrusion into the building. CONDUIT INSTALLATION SCHEDULE

Edit this article carefully; restrict material application as need to match project needs. This conduit installation schedule may be included on Contract Drawings. Consultant: In prisons or similar applications, a separate rigid steel conduit system shall be specified for all security systems in locations potentially accessible to inmates, including door and lock controls, intercom paging, monitoring and video systems. Consultant shall edit the specification accordingly.

Conduit other than that specified below for specific applications shall not be used.

• Underground Installations That Penetrate Foundation Walls: Rigid metal conduit within five feet (1.5 m) of the foundation wall. Conduit may transition to PVC conduit five feet (1.5 m) from the foundation walls.

• Underground Installations That Do Not Penetrate Foundation Walls: Rigid metal conduit, or PVC

conduit.

• Underground Installations Emerging from Grade: Buried conduit emerging from grade shall be Rigid metal conduit extending from the minimum cover distance of 24 inches below grade to the conduit termination point above grade.

• Underground Installations Under Concrete Slab: Rigid metal conduit or Schedule 40 PVC conduit.

• Underground Installations Emerging through Concrete Slab: Rigid metal conduit.

• Concealed Dry Interior Locations: Electrical metallic tubing, and PVC conduit (Ground conductor).

• Interior Building Grounding Electrode Conductor: Schedule 80 PVC.

• • •

Page 84: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 26 05 33 - 6

COORDINATION OF BOX LOCATIONS Provide electrical boxes as shown on Drawings, and as required for splices, taps, wire pulling, equipment connections, and code compliance. Electrical box locations shown on Contract Drawings are approximate unless dimensioned. Verify location of floor boxes and outlets in offices and work areas prior to rough-in. No outlet, junction, or pull boxes shall be located where it will be obstructed by other equipment, piping, lockers, benches, counters, etc. Conduit and boxes shall not be fastened to the metal roof deck. If conduit and boxes are required to be located and installed on roof decks, the conduit and boxes are required to be spaced minimum 1-5/8 inch off the lowest part of the metal roof decking material, per NEC 300.4 (E). It shall be the Contractor's responsibility to study drawings pertaining to other trades, to discuss location of outlets with workmen installing other piping and equipment and to fit all electrical outlets to job conditions. In case of any question or argument over the location of an outlet, the Contractor shall refer the matter to the Architect/Engineer and install outlet as instructed by the Architect/Engineer. The proper location of each outlet is considered a part of this contract and no additional compensation will be paid to the Contractor for moving outlets which were improperly located. Locate and install boxes to allow access to them. Where installation is inaccessible, coordinate locations and provide 18 inch (450 mm) by 24 inch (600 mm) access doors. Boxes must be installed within 12” from edge of the access door. Locate and install to maintain headroom and to present a neat appearance. Install boxes to preserve fire resistance rating of partitions and other elements, using approved materials and methods. PULL AND JUNCTION BOX INSTALLATION Pull boxes and junction boxes shall be minimum 4 inches square (100 mm) by 2 1/8 inches (54 mm) deep for use with 1 inch (25 mm) conduit and smaller. On conduit systems using 1 1/4 inch (31.75 mm) conduit, minimum junction box size shall be 4 11/16 inches square by 2 1/8 inches deep. Where used with raceway(s) containing conductors of 4 AWG or larger, pull box shall be sized as required unless otherwise noted on the drawings. Where used with raceway(s) containing conductors on systems over 600V, pull box shall be sized per NEC 314 Part IV unless otherwise noted as larger on the drawings. Locate pull boxes and junction boxes above accessible ceilings, in unfinished areas or furnish and install access panels in non-accessible ceilings where boxes are installed. All boxes are to be readily-accessible. Provide Pull and Junction boxes for communications and other low voltage applications (a) in any section of conduit longer than 100 feet, (b) where there are bends totaling more than 180 degrees between pull points or pull boxes and (c) wherever there is a reverse bend in run. Locate boxes on straight section of raceway (e.g. do not use boxes in place of raceway bends). Support pull and junction boxes independent of conduit. OUTLET BOX INSTALLATION Do not install boxes back-to-back in walls. Provide minimum 6 inch (150 mm) separation, except provide minimum 24 inch (600 mm) separation in acoustic-rated walls. Power:

Recessed (1/4 inch maximum) outlet boxes in masonry, concrete, tile construction, or drywall shall be minimum 4 inch square, with device rings. Device covers shall be square-cut except rounded corner plaster rings are allowed in drywall applications. Angle cut plaster rings are not permitted. Coordinate masonry cutting to achieve neat openings for boxes. A single gang box can be used in drywall and masonry, for a single device location, when a single conduit enters box.

Page 85: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 26 05 33 - 7

Shallow 4 inch square by 1 1/2 inch deep boxes can be used as device boxes for power provided the box and plaster ring is sized for installed device and conductors.

Low Voltage:

Recessed (1/4 inch maximum) outlet boxes in masonry, concrete, tile construction or drywall shall be minimum 4 11/16 inch square by 2 1/8 inch deep with single gang device ring (unless noted otherwise on drawings). Device covers shall be square-cut except rounded corner plaster rings are allowed in drywall applications. Angle cut plaster rings are not permitted. Coordinate masonry cutting to achieve neat openings for boxes. Provide one conduit from each communications outlet box. Conduit runs between outlet boxes for communications are not allowed. Terminate conduit above accessible ceiling.

Provide knockout closures for unused openings. Support boxes independently of conduit except for cast boxes that are connected to two rigid metal conduits, both supported within 12 inches (300 mm) of box. Use multiple-gang boxes where more than one device are mounted together; do not use sectional boxes. Provide non-metallic barriers to separate wiring of different voltage systems. Install boxes in walls without damaging wall insulation. Coordinate mounting heights and locations of outlets mounted above counters, benches, and backsplashes. Ceiling outlets shall be 4 inch square, minimum 2 1/8 inch (54 mm) deep except that concrete boxes and plates will be approved where applicable. Position outlets to locate luminaires as shown on reflected ceiling plans. In inaccessible ceiling areas, position outlets and junction boxes within 6 inches (150 mm) of recessed luminaire, to be accessible through luminaire ceiling opening. Provide recessed outlet boxes in finished areas; secure boxes to interior wall and partition studs, accurately positioning to allow for surface finish thickness. Use stamped steel stud bridges for flush outlets in hollow stud wall, and adjustable steel channel fasteners for flush ceiling outlet boxes. Align wall-mounted outlet boxes for switches, thermostats, and similar devices. Provide cast ferroalloy or aluminum outlet boxes in exterior and wet locations. Surface wall outlets shall be 4 inch (100 mm) square with raised covers for one and two gang requirements. For three gang or larger requirements, use gang boxes with non-overlapping covers.

END OF SECTION

Page 86: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2
Page 87: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 26 24 16 - 1

SECTION 26 24 16 PANELBOARDS

PART 1 - GENERAL

SCOPE The work under this section includes main, distribution and branch circuit panelboards. Included are the following topics: RELATED WORK Applicable provisions of Division 1 govern work under this Section. REFERENCES ANSI C57.13 – Instrument Transformers NEMA AB 1 - Molded Case Circuit Breakers NEMA KS 1 - Enclosed Switches UL-891 - Dead Front Switchboards SUBMITTALS Include outline and support point dimensions, voltage, main bus ampacity, circuit breaker arrangement and sizes, and interrupting ratings confirming a fully-rated system for all equipment and components. Submit required short circuit coordination study per specification section 26 05 73 to the consulting engineer for review and approval. Submittal shall be on or before date of panelboard equipment submittal. OPERATION AND MAINTENANCE DATA All operations and maintenance data shall comply with the submission and content requirements specified under section GENERAL REQUIREMENTS. SPARE PARTS Keys: Furnish 2 keys for each panelboard to Owner. Handle lock-off: Furnish (2) 20/1 circuit breaker handle lock-off devices for each panelboard to Owner. One set of three spare fuses of each size and type utilized

PART 2 - PRODUCTS POWER DISTRIBUTION PANELBOARDS Panelboards: Circuit breaker or fusible switch type. The panelboard and overcurrent devices contained within shall be fully-rated. Enclosure: NEMA Type 1. Minimum cabinet size: 6.5 inches (165 mm) deep; 26 inches (660 mm) wide. Constructed of galvanized code gauge steel. Cabinet front cover and cabinet shall be Type 4X, 304 stainless steel in wet and damp locations including kitchen, foodservice and therapeutic/pool applications. Power distribution panelboards installed in electrical rooms and mechanical rooms shall utilize a standard dead front cover. In all other areas provide cabinet front with hinged door, flush lock and hinged trim (door-in-door) to allow access to wiring gutters without removal of panel front. Hinged trim shall be held in place with screw fasteners. Finish in manufacturer's standard gray enamel. Provide metal directory holders with clear plastic covers. Provide panelboards with copper bus (phase buses, bus fingers, etc.). Provide ground bars in all panelboards. Neutral and ground bars can be dual rated ALCU9. All spaces shall have bus fully extended and drilled for the future installation of breakers.

Page 88: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 26 24 16 - 2

Minimum System (i.e. individual component) Short Circuit Rating: As shown on the Drawings and as required by short circuit/coordination study. Main breakers shall be individually mounted. Back feed mains shall NOT be utilized. The circuit breakers are to be totally front accessible and mounted in the panelboard to permit installation, maintenance and testing without reaching over line side bussing. The circuit breakers are to be removable by the disconnection of only the load side terminations and line and load side connections are to be individual to each circuit breaker. Common mounting brackets or electrical bus connectors are not acceptable. Circuit breakers shall be provided with provisions for mounting handle padlock attachments. Breaker feeder lugs shall be dual rated for use with either aluminum or copper conductors. Each circuit breaker is to be furnished with an externally operable mechanical means to trip the circuit breaker, enabling maintenance personnel to verify the ability of the circuit breaker trip mechanism to operate, as well as exercise the circuit breaker operating mechanisms. A minimum of 20% future circuit breaker spaces shall be included. Spaces for future circuit breakers shall be “prepared” spaces. These spaces shall be provided with the necessary mounting hardware and bus extensions so that when future breakers are added, only the breaker itself needs to be purchased by the installer. Circuit breakers serving single motor loads shall be magnetic only, instantaneous trip. Overload protection shall be shall be part of the motor combination controller. Circuit breakers in 480V power distribution panelboards shall be fully adjustable LSI circuit breakers with electronic trip for frame sizes 400A and greater. Circuit Breakers:

Electronic Trip Circuit Breakers: Electronic circuit breakers shall have, at a minimum, adjustments for long time, short time and instantaneous trip. Provide integral ground fault sensing with adjustable ground fault trip where indicated on the drawings. Molded Case Circuit Breakers:Integral thermal and instantaneous magnetic trip elements in each pole.

Fusible Distribution Switches:

Fusible switches shall be quick make, quick break and shall be group mounted in panel type construction. Switches of 30 amperes to 200 amperes shall have plug-on line side connections. Each switch is to be contained in a separate steel enclosure. The enclosure shall employ a hinged cover for access to the fuses which shall be interlocked with the operating handle to prevent opening the cover when the switch is in the "ON" position. This interlock shall be constructed so that it can be released with a standard electrician's tool for testing fuses without interrupting service. Units shall have padlocking provisions in "OFF" position and operating handle position shall give positive switch position indication, i.e. red for "ON" and black for "OFF". Switches shall pass industry standard I2t with-stand tests and fuse tests. A minimum of 20% future fusible switch spaces shall be included. Spaces for future fusible switches shall be “prepared” spaces. These spaces shall be provided with the necessary mounting hardware and bus extensions so that when future fusible switches are added, only the fusible switch itself needs to be purchased by the installer.

Meter: Provide an electronic meter (with meter test switch and instrument transformers) for Owner’s use in the distribution panelboard. Meter and related equipment shall meet the requirements of specification section 26 27 13. Surge Protective Device: Provide a surge protective device meeting the requirements of specification section 26 43 13. Surge protective devices shall be served from an overcurrent protective device within the

Page 89: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 26 24 16 - 3

power distribution panelboard. Surge protective device shall be installed external to the distribution panelboard. BRANCH CIRCUIT PANELBOARDS Lighting and Appliance Branch Circuit Panelboards: Circuit breaker type. The panelboard and overcurrent devices contained within shall be fully-rated. Enclosure: Type 1. Minimum cabinet size: 5-3/4 inches (144 mm) deep; 20 inches (508 mm) wide with 5" minimum gutter space top and bottom. Constructed of galvanized code gauge steel. Panel enclosure (back box) shall be of non-stamped type (without KO's) to avoid concentric break out problem. Cabinet front cover and cabinet shall be Type 4X, 304 stainless steel in wet and damp locations including kitchen, food service and therapeutic/pool applications. Provide flush cabinet front with concealed trim clamps, concealed hinge and flush cylinder lock all keyed alike. Front cover shall be hinged to allow access to wiring gutters without removal of panel trim. Hinged trim shall be held in place with screw fasteners. Finish in manufacturer's standard gray enamel. Provide metal directory holders with clear plastic covers. Provide panelboards with copper bus (phase buses, bus fingers, etc.). Provide ground bars in all panelboards. Phase, neutral and ground bar terminations can be dual rated ALCU9. All spaces shall have bus fully extended and drilled for the future installation of breakers. Incoming conductors shall terminate at lug landing pads rated for the panelboard. Provide compression type lugs to accommodate the conductor shown on drawings. Minimum System (i.e. individual component) Short Circuit Rating: As shown on the Drawings and as required by short circuit/ coordination study. Molded Case Circuit Breakers: Bolt-on type thermal magnetic trip circuit breakers. Provide UL Class A ground fault interrupter circuit breakers where shown on Drawings. Provide circuit breakers UL listed as Type HACR for air conditioning equipment branch circuits. Do not use tandem circuit breakers. Circuit breakers shall be bolt-on type with common trip handle for all poles. No handle ties of any sort will be approved. Provide a minimum of 10% spare circuit breakers in branch panelboards. All of the panelboards provided under this section shall be by the same manufacturer. All sub-feed panelboards installed side by side shall utilize same enclosure height. COORDINATION BRANCH PANELBOARDS Branch Circuit Panelboards: Fusible switch type with current limiting Class J time delay protection. The panelboard and overcurrent devices contained within shall be fully-rated. Enclosure: Type 1. Minimum cabinet size: 5-3/4 inches (144 mm) deep; 20 inches (508 mm) wide with 5" minimum gutter space top and bottom. Constructed of galvanized code gauge steel. Panel enclosure (back box) shall be of non-stamped type (without KO's) to avoid concentric break out problem. Provide flush cabinet front with concealed trim clamps, concealed hinge and flush cylinder lock all keyed alike. Front cover shall be hinged to allow access to wiring gutters without removal of panel trim. Hinged trim shall be held in place with screw fasteners. Finish in manufacturer's standard gray enamel. Provide metal directory holders with clear plastic covers.

Page 90: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 26 24 16 - 4

Provide panelboards with copper bus (phase buses, bus fingers, etc.). Provide ground bars in all panelboards. Phase, neutral and ground bar terminations can be dual rated ALCU9. All spaces shall have bus fully extended and drilled for the future installation of devices. Overcurrent devices shall be fused branch disconnects including compact base and cube fuses with the following features:

Current limiting Class J time delay protection. Single handle common trip, two and three phase. Bolt on type. Local open fuse indication. UL listed for type and temperature rating of wire specified. Permanently installed integrated lockout/tag out provisions. 600V AC rated.

COORDINATION OF OVERCURRENT PROTECTIVE DEVICES Provide a coordination study of the electrical system and recommend set points for all of the overcurrent and ground fault trip adjustments on the equipment provided. The coordination study and set point recommendations shall be submitted to the consulting engineer for approval. Submittal shall be on or before date of switchboard and panelboard equipment submittal.

PART 3 - EXECUTION INSTALLATION Install panelboards plumb with wall finishes. Height:

Power Distribution panelboards: Minimum 12” above finished floor and maximum of 6’-7” to center of the grip of the operating handle of the top most mounted switch or circuit breaker, when at its highest position. Branch panelboards: 6’-0” to top of panelboard.

Install a crimp type stud termination to stranded conductor when terminating on circuit breakers without a captive assembly rated for terminating stranded conductors. Provide filler plates for unused spaces in panelboards. Provide typed circuit directory for each branch circuit panelboard. Revise directory to reflect circuiting changes required to balance phase loads. Stub three (3) empty ¾” conduits to accessible location above ceiling or below floor out of each recessed panelboard. Cap these conduits to prevent material from entering them. FIELD QUALITY CONTROL If aluminum conductors size #1/0 and larger (per Section 26 05 19) are to be used as panelboard feeders, it is the responsibility of the contractor to provide panelboards with adequate wire bending space to accommodate the aluminum conductors and terminators to meet allowable code requirements. The Contractor shall circuit the panelboards as shown on the drawings. Measure steady state load currents at each panelboard feeder. Should the difference at any panelboard between phases exceed 10 percent, rearrange circuits in the panelboard to balance the phase loads within 10 percent. Visual and Mechanical Inspection: Inspect for physical damage, proper alignment, anchorage, and grounding. Check proper installation and tightness of connections.

END OF SECTION

Page 91: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 26 27 26 - 1

SECTION 26 27 26 WIRING DEVICES

PART 1 - GENERAL SCOPE This section describes the products and execution requirements relating to furnishing and installing wiring devices and related systems for the project. Included are the following topics: SUBMITTALS Provide product data showing model numbers, configurations, finishes, dimensions, and manufacturer's instructions. For occupancy sensor shop drawings, the manufacturer’s actual layout of occupancy sensors and the wiring diagrams shall be provided. OPERATION AND MAINTENANCE DATA All operations and maintenance data shall comply with the submission and content requirements specified under section GENERAL REQUIREMENTS.

PART 2 - PRODUCTS

MODULARLY CONNECTED (MODULAR) DEVICES: Modularly connected devices are allowed, but not required. Modular Pigtailed Connector: Polarized connector with minimum six-inch stranded copper wire leads, polycarbonate right-angle housing, UL498 listed, with finger-safe connector housing which provides insulation from conductive surfaces. Contacts shall be brass. Connector shall be manufactured so that it provides a secure connection such that it will maintain contact with the device until the device is removed for replacement. Modular connectors shall be provided with covers which protect the contacts from paint, drywall mud, and construction dust and debris. Connectors shall be Hubbell SNAPConnect, Leviton Lev-Lok, Pass & Seymour PlugTail, or approved equal. WALL SWITCHES General: Heavy duty use toggle switch, rated 20 amperes and 120/277 volts AC. Switches shall be UL20 Listed and meet Federal Specification WS-896. All switches shall be heavy duty Specification Grade. Handle: White made of nylon or high impact resistant material. Wall Switches for Lighting Circuits and Motor Loads Under 1/2 HP: All switches shall be back and side wired, screw clamp type, suitable for solid or stranded wire up to #10 AWG, with separate green ground screw. Switches shall be as follows:

Hubbell 1221*, Leviton 1221-S*, Pass & Seymour CSB20AC1-*, or approved equal. (* indicates color selection).

Modular Wall Switches for Lighting Circuits and Motor Loads Under 1/2 HP: Switches shall be as follows:

Hubbell SNAP1221*NA, Leviton M1221-*, Pass & Seymour PT20AC1-*, or approved equal. (* indicates color selection).

RECEPTACLES General Requirements: NEMA Type 5-20R, white nylon or high impact resistant face. Receptacles shall be UL498 Listed and meet Federal Specification WC-596. All duplex receptacles shall be heavy duty Specification Grade, 20 amp rated.

Page 92: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 26 27 26 - 2

Generally, all receptacles shall be duplex convenience type unless otherwise noted. All receptacles designated as isolated ground shall have an isolated ground triangle imprint on the face of the receptacle. All receptacles installed in bathrooms, kitchens, and within 6 feet of the outside edge of sinks shall be GFCI type. All receptacles installed in outdoor locations, garages, rooftops, and in other damp or wet locations shall be GFCI type with a weather-resistant (WR) rating. Convenience and Straight-blade Receptacles: All receptacles shall be back and side wired, screw clamp type, suitable for solid or stranded wire up to #10 AWG, with a separate green ground screw. Receptacles shall be as follows:

Hubbell 5362*, Leviton 5362-*, Pass & Seymour PS5362*, or approved equal. (* indicates color selection).

GFCI Receptacles: Duplex convenience receptacle with integral ground fault current interrupter meeting the requirements of UL standard 943 Class A, including self-test functionality and reverse line-load misfire function repeatability. GFCI receptacles shall be as follows:

Hubbell GFR5362SG*, Leviton GFNT2-*, Pass & Seymour 2097*, or approved equal. (* indicates color selection).

GFCI Receptacles with a weather-resistant (WR) rating: Weather-Resistant duplex convenience receptacle with integral ground fault current interrupter meeting the requirements of UL standard 943 Class-A, including self-test functionality and reverse line-load misfire function repeatability. WR GFCI receptacles shall be as follows:

Hubbell GFR5362SG*, Leviton GFWR2-*, Pass & Seymour 2097TRWR*, or approved equal. (* indicates color selection).

Modular Convenience and Straight-blade Receptacles: Receptacles shall be as follows:

Hubbell SNAP5362*A, Leviton M5362-*, Pass & Seymour PT5362*, or approved equal. (* indicates color selection).

Modular GFCI Receptacles: Duplex convenience receptacle with integral ground fault current interrupter meeting the requirements of UL standard 943 Class A, including self-test functionality and reverse line-load misfire function repeatability. GFCI receptacles shall be as follows:

Hubbell GFRST83SNAP*, Leviton MGFN2-*, Pass & Seymour PT2097*, or approved equal. (* indicates color selection).

Modular GFCI Receptacles with a weather-resistant (WR) rating: Use back and side wired devices in lieu of modular weather-resistant rated GFCI receptacles. DEVICE PLATES AND BOX COVERS Decorative Cover Plate: Whitesmooth thermoplastic nylon. Note requirement for red plates on emergency outlets and switches. Weatherproof Cover: All receptacles installed in wet locations shall have an enclosure that is weatherproof whether or not the attachment plug is inserted. Covers shall be gasketed metal with hinged

Page 93: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 26 27 26 - 3

“in-use” device covers, powder coat painted. Non-metallic covers are not allowed. Covers shall be latching type and shall be lockable. Covers shall be identified as “extra-duty” type per NEC 406.9(B)(1).

Damp Location Cover: All receptacles installed outdoors in a location protected from the weather or in other damp locations shall have an enclosure that is weatherproof when the receptacle is covered (attachment plug not inserted and receptacle covers closed). Covers shall be gasketed metal with hinged device covers, powder coat painted. Non-metallic covers are not allowed.

PART 3 - EXECUTION

INSTALLATION See plans for device mounting heights.

Install wall switches with OFF position down.

Wall dimmers: de-rate ganged dimmers as instructed by manufacturer; do not use common neutral.

Install convenience receptacles with grounding pole on bottom.

Install box for information outlet at the same height as adjacent convenience receptacles. Locate boxes for information outlet as close as practical to duplex power outlet, approximately 2-inches apart.

Install box for telephone jack for wall telephone at 46-inches to center above finished floor.

Install specific-use receptacles at heights shown on Contract Drawings. Install decorative plates on switch, receptacle, and blank outlets in finished areas.

Install galvanized steel plates on outlet boxes and junction boxes in unfinished areas, above accessible ceilings, and on surface-mounted outlets.

Install devices and wall plates flush and level.

Receptacles shall have a bonding conductor from grounding terminal to the metal conduit system. Self-grounding receptacles using mounting screws as bonding means are not approved.

FIELD QUALITY CONTROL Inspect each wiring device for defects.

Operate each wall switch and sensor with circuit energized, and verify proper operation.

Verify operation of each ELCU by turning off the normal power circuit breaker at the panelboard.

Verify that each receptacle device is energized.

Test each receptacle device for proper polarity.

Test each GFCI receptacle device for proper operation.

The user agency and DFD personnel reserve the right to be present at all tests.

ADJUSTING Adjust devices and wall plates to be flush and level.

Mark all conductors with the panel and circuit number serving the device with a machine generated label, at the device, and on the back of the device cover.

END OF SECTION

Page 94: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2
Page 95: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 26 43 13 - 1

SECTION 26 43 13 SURGE PROTECTIVE DEVICES FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS

PART 1 - GENERAL

SCOPE The work under this section includes Surge Protective Devices (SPDs) as indicated on the project drawings and electrical diagrams. Included are the following topics: REFERENCE STANDARDS ANSI/UL 1449, Fourth Edition – Standard For Surge Protective Devices. ANSI/IEEE C62.41.1 Guide on the Surge Environment in Low-Voltage AC Power Circuits. ANSI/IEEE C62.41.2 Recommended Practice on Surge Voltages in Low-Voltage AC Power Circuits. ANSI/IEEE C62.45 Recommended Practice on Surge Testing for Equipment Connected to Low Voltage AC Power Circuits. IEEE C62.62 Standard Test Specification for Surge Protective Devices For Low-Voltage AC Power Circuits. NFPA 70, NEC Article 285 QUALITY ASSURANCE The manufacturer shall have been in the Surge Protective Device industry for a minimum of 5 years. WARRANTY The manufacturer shall provide a minimum 5 year warranty from the date of shipment of the SPD. SUBMITTALS Include all SPD data necessary to show device is in compliance with all product specifications. Include product data sheets showing the device performance, dimensions, weight, connections, and mounting requirements, along with installation instructions. OPERATION AND MAINTENANCE DATA All operations and maintenance data shall comply with the submission and content requirements specified under section GENERAL REQUIREMENTS.

PART 2 - PRODUCTS SURGE PROTECTIVE DEVICES The SPD shall be Listed in accordance with UL 1449, Fourth Edition. The product and ratings shall be included in the database of the UL.com web site. The surge protective device (SPD) shall be designated a location Type 1 or Type 2 device intended for installation on the load side of the service equipment overcurrent device, including SPDs located at the branch panel. The SPD shall be connected in parallel with the facility’s electrical system. The SPD shall be made up of metal oxide varistors (MOV's), or a combination of MOV’s with selenium cells or silicon avalanche diodes, ensuring that all of the performance requirements are met. Gas tubes shall not be used. The entire SPD shall be enclosed in a metal or ABS enclosure, NEMA rated for the location. SPDs at main service equipment shall be mounted outside the switchboard or panelboard (not integral to, or installed within the switchboard or panelboard). SPDs for branch panelboard (2nd tier) locations may be mounted outside of, or integral to, the branch panelboard. SPDs installed internal to the distribution equipment shall be of the same manufacturer as the equipment. The SPD shall have a maximum continuous operating voltage (MCOV) rating not less than 115% of nominal voltage of the system it is protecting.

Protection Modes:

The SPD shall have line to neutral (L-N), line to ground (L-G), line to line (L-L) and neutral to ground (N-G) protection modes for three-phase grounded wye configured systems. For a three-

Page 96: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 26 43 13 - 2

phase delta configured system, the device shall have line to line (L-L) and line to ground (L-G) protection modes.

Voltage Protection Rating (VPR):

The UL 1449 Voltage Protection Rating (VPR) for the device shall not exceed the following: 208Y/120 volt applications: 800V L-N, L-G, N-G; 1200V L-L 480Y/277 volt applications: 1200V L-N, L-G, N-G; 2000V L-L 480 volt delta applications: 2000V L-G, 2000V L-L

Nominal Discharge Current (In):

The UL 1449 Nominal Discharge Current Rating (In) shall not be less than the following:

20kA for service entrance, switchboard, and main distribution panel locations 10kA for branch panelboard (2nd tier) locations

Short Circuit Current Rating (SCCR):

The SPD shall have a UL 1449 Short Circuit Current Rating (SCCR) of not less than 200kA. Surge Current Rating:

The single-pulse (8 X 20 microsecond waveform as specified in ANSI/IEEE Standard C62.41) surge current capacity shall not be less than the following:

100kA per mode (200kA per phase) for service entrance, switchboard, and main distribution panel locations

50kA per mode (100kA per phase) for branch panelboard (2nd tier) locations Each SPD shall include externally-mounted LED visual status indicators that indicate the on-line status of the unit, for each phase. At service entrance, switchboard, and main distribution panel locations each SPD shall include the following features:

• audible diagnostic monitoring by way of an audible alarm function • one set of NO/NC dry contracts for alarm conditions

PART 3 - EXECUTION

INSTALLATION Install SPD units in accordance with manufacturer's written instructions, applicable requirements of NEC and NEMA standards, and recognized industry practices. The SPD units shall be installed at the locations shown on the drawings, or as indicated in the one-line diagram. They shall be parallel-connected to, and located adjacent to the switchboard or panelboard being protected. Locate as close as practical to the bus, keeping lead length as short as possible (less than 3 feet preferred to ensure optimum performance). SPDs shall be connected through a multi-pole circuit breaker or fused disconnect switch, not into main lugs. Circuit breaker or fused disconnect switch shall be 60A for main service device, 30A for branch panelboard device or as recommended by the manufacturer. Use schedule 40 PVC conduit or metallic conduit between the SPD and the switchboard or panelboard as recommended by the manufacturer. Avoid sharp bends, excess length, and splices in the wires. Where possible, use a close-nippled connection with wires going directly to a circuit breaker within the switchboard or panelboard. Setup and test per the manufacturer's recommendations.

END OF SECTION

Page 97: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 28 31 00 - 1

SECTION 28 31 00 FIRE DETECTION AND ALARM

PART 1 - GENERAL

SCOPE The work covered by this section of the specifications includes the furnishing of all labor, equipment, materials, and performance of all operations associated with the installation of the new Fire Alarm System as herein specified. RELATED WORK The work covered by this section of the specifications shall be coordinated with the related work as specified elsewhere under the following project sections: Section 26 05 00 - Common Work Results for Electrical Section 26 05 26 – Grounding and Bonding for Electrical Systems Section 26 05 33 – Raceway and Boxes for Electrical Systems DESCRIPTION OF WORK Complete installation of a fire alarm system including visual and audio alarms and pull stations. The complete installation shall be done in a neat, workmanlike manner in accordance with the applicable requirements of NFPA 70 - Article 760 and the manufacturer's recommendations. The New Fire Alarm System shall consist of a single Main Fire Alarm Control Panel (FACP unless a different design is submitted and approved. The New Fire Alarm System shall be configured as a local protective signaling system, as defined in NFPA-72, and shall use/incorporate the following features, as a minimum:

The latest intelligent analog, addressable technology (detectors/sensors and modular panel equipment) currently available from the manufacturer Non-Coded, Speaker-type Audible Notification Appliances

Initiating Device Circuits (IDCs) shall be limited to short runs from Monitor Modules to the connected device, unless specifically stated otherwise herein, and shall be configured as NFPA Style B (Class B), with individual zone supervision. Notification Appliance Circuits (NACs) shall be configured as NFPA Style Y (Class “B”). Audible NACs serving Speakers shall be installed using shielded cable, such that the speakers do not generate unwanted noises, due to cross-talk with other circuits.

The system shall be an intelligent/analog type, and shall consist of the following panels: PANEL NAME:

PANEL TYPE:

PANEL LOCATION:

FACP Main Fire Alarm Control Unit REGULATORY REQUIREMENTS The complete installation shall conform to the applicable sections of the latest edition of the following Codes and Standards: NATIONAL FIRE PROTECTION ASSOCIATION (NFPA):

NFPA-70 National Electrical Code (NEC) Generally, and Article 760 in particular NFPA-72 National Fire Alarm Code NFPA 101 Life Safety Code IBC International Building Code IFC International Fire Code IMC International Mechanical Code

Page 98: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 28 31 00 - 2

NATIONAL ELECTRICAL MANUFACTURER’S ASSOCIATION (NEMA) UNDERWRITERS’ LABORATORIES, INC. (UL)

UL-864 Control Units for Fire Protective Signaling Systems UL-268 Smoke Detector for Fire Protective Signaling Systems UL-217 Smoke Detectors for Single and Multiple Station UL-521 Heat Detectors for Fire Protective Signaling Systems UL-464 Audible Signaling Appliances UL-1971 Visual Signaling Appliances UL-38 Manually Actuated Signaling Boxes UL-1481 Power Supplies for Fire Protective Signaling Systems

MANUFACTURER PROVIDED SERVICES A manufacturer-trained service technician shall provide the following installation supervision. This Techni-cian shall be certified by the equipment manufacturer, and shall have had a minimum of two (2) years of service experience in the fire alarm industry. The technician's name shall appear on equipment submittals and a letter of certification from the fire alarm manufacturer shall be sent to the project engineer. The manufacturer's service technician shall be responsible for the following items:

Pre-installation visit to the job site to review equipment submittals and verify method by which the system should be wired. Periodic job site visits to verify installation and wiring of system, and to perform any partial system programming – required to permit portions of the existing system to be removed. Upon completion of wiring, final connections shall be made under the supervision of this technician, and final checkout and certification of the system. At the time of final checkout, technician shall give operational instructions to the Owner and/or his representative on the system. All job site visits shall be dated and documented in writing and signed by the Electrical Contractor. Any discrepancy shall be noted on this document and a copy kept in the system job folder that shall be available to the Project Engineer any time during the project.

QUALITY ASSURANCE Unless specifically stated otherwise, each and all items of the fire alarm system shall be listed as a product of a SINGLE fire alarm system manufacturer under the appropriate category by Underwriters' Laboratories, Inc. (UL), and shall bear the UL label. Notification Appliances may be products of a single, different manufacturer – provided that the Primary Equipment Provider or Manufacturer provides written documentation of compatibility, and agrees to assume any and all responsibility for compatibility with the Control Equipment. In addition to previously listed UL standards, all control equipment shall be listed under the following UL Standards: UOJZ UL category UOJZ as a single control unit. Partial listing shall NOT be acceptable. UL 864 Transient protection UL 497B Isolated Loop Circuit Protectors. Where fire alarm circuits leave the building, additional

Transient protection must be provided for each circuit. UL 1481 Power Limited Applications. QUALIFICATIONS All equipment shall be supplied by a firm, which specializes in fire alarm and smoke detection systems with a minimum of five (5) years-documented experience. The company shall be an authorized distributor of the proposed equipment All work shall be performed by a licensed contractor, who is regularly engaged in the installation and servicing of fire alarm systems. Proof of five (5) years documented experience and of factory authorization to furnish and install the equipment proposed shall be furnished prior to contract award, if required by Division of State Facilities. Contractor shall be located within three (3) hours of travel time or less from the site of this project.

Page 99: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 28 31 00 - 3

SUBMITTALS Under the provisions of Section 26 05 00 and Division 1, submit the following for approval prior to ordering any equipment in accordance with requirements of Division 1, General Conditions. Submit a total of 5 (5) sets. Copies of CAD Files (AutoCAD, latest version) for the Fire Alarm floor plans will be made available to the successful bidder for preparation of the required shop drawings and as-builts REQUIRED SUBMITTAL MATERIALS The following items, and any additional items required per Section 26 05 00, shall be included within the submittal package:

Although they may be submitted under separate cover, Submittal Brochures / Booklets / Binders and Shop Drawings shall be submitted together, and shall be treated as a complete set.

COVER SHEET: The submittals shall contain a cover sheet, which shall include the following information:

Submittal Date Specification Section(s) Electrical Contractor (Contact Name, name, address, and telephone number) Project Name, Project City, Project State, and Project Address.

TABS AND TABLE OF CONTENTS: The Table of Contents shall appear immediately behind the Cover Sheet, and shall contain a complete listing of all of the tabs contained within the binder / booklet.

Tabbed index sheets shall be inserted into each of the binders, such that each binder is clearly sub-divided into sections. Tabbed sections shall be provided, at minimum, for the following:

One section for each building – ALL submittal data, which applies to any particular building, shall be located within the tabbed section for the corresponding building. All submittal data within each “building” section shall appear in the same order. One section for manufacturer’s data sheets – divided into sub-sections for the following:

Panel Equipment (Panels, Panel Components / Modules, Printers, Annunciators, etc.) Addressable Field Devices (Initiating and Control / Monitoring / Isolation) Non-Addressable Field Devices (Initiating Devices, relays, etc.) Notification Appliances Fire-Fighter Communications Equipment if applicable

EQUIPMENT LIST: A complete equipment list of all components, including the following: Quantity, Manufacturer, Part Number, and Description. If the supplier uses different part numbers from those of the actual manufacturer, the actual manufacturer and part numbers as they appear – marked on the shipping box / packages

, shall also be identified on this list.

Each Equipment List shall include a complete listing of the modules, components, and software included for each modular FIRE Alarm Control Panel, Network Panel, Transponder, Outboard Gear Panel or Annunciator. Such items shall be listed in a manner that clearly indicates that such items are parts of / components of a larger unit. Simply stating a single part number and description for such panels shall be unacceptable. A separate list shall be included for each section, with items grouped by system. For projects involving multiple systems, separate equipment lists shall be provided - one for each system. Spare Parts shall also be listed separately, and shall be identified clearly as “Spare Equipment”.

Page 100: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 28 31 00 - 4

PRODUCT DATA: Manufacturer's product data sheets, and equipment description of all system components. These data sheets shall be highlighted or suitably marked, so that included items and options are indicated. On data sheets that include multiple products, products that are not used shall be crossed out.

Product Data Sheets shall be organized, in order, corresponding to the FIRST occurrence of the corresponding item on the equipment list

SEQUENCE OF OPERATION: Complete sequence of operations of all functions of the system. This sequence of operation shall be custom-created for this particular job.

In order to satisfy this submittal requirement, it shall be acceptable to include copies of the “Operation” portions of the specifications, including any applicable schedules / other supplementary information. Copied specification pages shall be marked and highlighted, where the programmed operation will differ from the specified operation. Copied specification pages shall be marked “no changes”, where no significant deviation will occur. Other acceptable alternatives shall include written narratives, organized in a logical manner, and Matrix Charts. Where Matrix Charts are provided, such charts shall be organized and labeled clearly, and shall incorporate suitable levels of detail (refer to NFPA-72 (2007) A.10.6.2.3(9) for an example of an acceptable matrix chart). The Leftmost column of the Matrix Chart shall include groupings of initiating devices and other function switches. The Topmost Row shall include groupings of notification appliances and output devices.

BATTERY CALCULATIONS: These calculations shall clearly illustrate both the Standby and Alarm loads, due to the various field devices and panel components / modules. It is generally recommended to submit such calculations in a “spreadsheet” format. These calculations shall include any reserve / additional capacity, as required elsewhere within these specifications. Final results shall indicate both the minimum battery capacity required and the capacity actually provided. AMPLIFIER CAPACITY CALCULATIONS For all speakers plus all required spare capacity.

NAC WIRE DROP CALCULATIONS: Calculations shall be provided for all Notification Appliance Circuits (NAC) in the building . It is recommended that this calculation should follow a “spreadsheet” format, and should clearly indicate the following:

The name of the circuit Point of origin of the circuit Complete list of all devices served by the circuit, including location and type of each device Alarm Current Draw for each device, at the applied voltage Applied Voltage (Based on anticipated battery voltage after specified stand-by & alarm operation) Acceptable Operating Voltage for each type of device on circuit Calculated Voltage at each device on circuit These calculations should mathematically prove that all Notification Appliances on the circuit will receive acceptable power for proper operation, under “worst-case-scenario” conditions.

SHOP DRAWINGS: All submitted drawings shall be created using CAD, and shall be coordinated so that terminal numbering, circuit designation and equipment or device designations are the same on all drawings. All drawings must be submitted and approved by the engineer before ordering or fabrication starts, but such approval will not waive any specification requirements unless specifically stated. Each and every sheet of the Shop Drawings shall be clearly and prominently identified as “SHOP DRAWINGS – PREPARED BY: (insert name of contractor firm preparing the shop drawings)”, and shall be clearly and visibly different from the Contract Documents / Bidding Drawings. As a minimum, the name and company logo for the Electrical Contractor and the FIRE Alarm Equipment Vendor should be added to each sheet, and a revision date shall be inserted on each sheet.

Page 101: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 28 31 00 - 5

The submitted Shop Drawings shall include the following types of drawings:

PROJECT-SPECIFIC DRAWINGS: Project-Specific Drawings. These drawings shall include the following:

SYSTEM RISER DRAWING: A separate riser drawing shall be furnished for each system. Each System Riser shall illustrate all fire alarm circuits, which serve the facility, and shall incorporate the following information, in a clear, concise format:

Point of origin of each circuit (usually a Panel, or a Module within a panel) Circuit type and labeling Area served by each circuit Wire / cable type and size Locations of Panelboards where primary system power is obtained The following information for each Field Device:

Device Type Circuit(s) to which device is connected Locations of any End-Of-Line Resistor (EOLR) (and the circuit terminated by any such EOLR)

BLOCK DIAGRAMS: Showing layout and operation of the entire system. FLOOR PLANS: These drawings shall consist of edited versions of the Contract Documents, which shall include the following information:

Fire Department Response Location(s) Annunciator Location(s) Panel Location(s) Device Addresses - The addresses shown on these drawings shall directly correspond to the chart or printout, as specified previously, which spells out specific information about each device, including the field programmable “custom label”.

TYPICAL DEVICE / MODULE WIRING DETAILS: Component and module wiring diagrams – intended to illustrate terminations and wiring connections to each typical Field Device (Detectors, Notification Appliances, etc.), and each typical panel component / module utilized within the system. This set of drawings shall only include diagrams for modules and components, which are actually used in the provided system(s).

These drawings shall incorporate clear labeling / nomenclature, which shall clearly indicate the corresponding field device or module, to which it corresponds.

OMISSION OF ANY OF THE ABOVE MATERIALS FROM THE SUBMITTALS SHALL RESULT IN AN IMMEDIATE REJECTION OF THE SUBMITTALS FOR THIS PROJECT. If the EC / FAC has any questions concerning the preparation of these materials, please contact the Engineer. PROJECT RECORD DRAWINGS Installing Electrical Contractor shall submit to the Construction Superintendent the as-built drawings for the entire work done under this project prior to final payment. Work shall be done on Auto CAD using the contract drawings provided to the Contractor in the form of Auto CAD files. A hard copy of same shall also be submitted. These drawings shall show:

Locations and addresses of Initiation Devices, Notification Appliances, isolation devices, status-monitoring devices, supervised signaling devices, and auxiliary control devices. Circuit and Address information for each field device listed above. Conduit layout. Number/size/type of conductors in each conduit run Riser diagrams

Page 102: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 28 31 00 - 6

Location of end-of-line devices

Riser diagrams shall be specific for this project, and shall include location of emergency 120VAC panel, panel designation and circuit number used to feed each fire alarm panel. Also, indicate if panel is backed up by an emergency generator. Riser diagrams shall include locations (room or area number) of notification, initiating, end-of-line devices and addresses for all addressable field devices. Also see requirements in Division 1, General Conditions. OPERATION AND MAINTENANCE DATA All operations and maintenance data shall comply with the submission and content requirements specified under section GENERAL REQUIREMENTS. In addition to the general content specified under GENERAL REQUIREMENTS supply the following additional documentation:

1. A material guide, which shall contain the replacement part numbers and description of all components used. If this information is included in an instruction section for any of the equipment, it will not be necessary to duplicate the list. In either case, the parts list shall be associated with its respective chassis, modules or kit wherein it is found. A total listing of parts without such grouping will not be acceptable.

2. Catalog data or literature 3. Manufacturer's operating instructions. 4. Manufacturer's maintenance instructions 5. Installation instructions 6. Name, address and telephone number of source for parts (i.e. keys, guards, etc) not supplied by the

Fire Alarm Manufacturer 7. Copies of all approved shop drawings 8. An updated copy of the submitted sequence of operation, revised to reflect any implemented

changes PRODUCT DELIVERY, STORAGE AND HANDLING Receive equipment at job site; verify applicable components and quantity delivered. Handle equipment to prevent internal components' damage and breakage, as well as denting and scoring of enclosure finish. Do not install damaged equipment. Store equipment in a clean, dry space and protect from dirt, fumes, water, and construction debris and physical damage. Make arrangements with the Owner at the pre-construction meeting for storage of equipment on the premises SPARE PARTS Contractor shall provide the following spare parts in quantities shown: {A/E INSERT NUMBERS IN PLACE OF ?} Quantity : (?) Photoelectric smoke detectors

Type of Device

(?) Heat detectors (?) Smoke and heat detector bases – “standard” 2-Wire Type (?) Monitor Module (of each type utilized in this project) (?) Control Modules (?) Duct detectors with housing, head, remote test station, and sample tubes (?) Ceiling-Mount multi-candela Speaker/strobe Units. (?) Wall mounted multi-candela Speaker/strobe Units (?) Multi-candela Strobe-Only Units (?) Pull Stations (?) 120 Vac smoke detectors (?) 120 Vac smoke detectors with ADA strobe (?) System Detector base with sounder SUPERVISION

Page 103: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 28 31 00 - 7

The system shall report a TROUBLE condition when any supervised circuit becomes disarranged, disconnected, or is manually disabled or overridden. Each supervised circuit shall be independently protected for short-circuit conditions, and shall be arranged so that faults on any one circuit do not prevent the proper operation of any other circuit in the system. The following devices/circuits shall be supervised, as a minimum:

ALL communications links. ALL Signaling Line Circuits ALL Initiating Device Circuits. All sprinkler flow and tamper switches.. ALL Notification Appliance Circuits. Auxiliary manual control circuits. Manual control switches for off normal position Remote Control Relays / Control Modules. Primary, AC Incoming power to the system. The system's batteries. System Expansion Modules Auxiliary module LED's.

The system shall have provisions for disabling and enabling all circuits individually for maintenance or testing purposes. Each independently supervised circuit shall include a discrete LCD readout, to indicate disarrangement conditions per circuit. POWER REQUIREMENTS Primary 120 VAC power, to all Fire Alarm equipment shall consist of dedicated branch circuits. These circuits shall be of a 3-conductor type, including a suitably sized green ground wire – SHARED NEUTRALS AND CONDUIT GROUNDS SHALL BE UNACCEPTABLE. Each control panel shall receive 120 VAC power via a branch circuit in one of the building's emergency load panels. Each such branch circuit shall have a "breaker lock" to prevent accidentally de-energizing of the power to the fire alarm panel. Circuit breakers shall be painted red and labeled "FIRE ALARM". If more than one power circuit is used, each circuit shall be properly labeled as “FIRE ALARM”

, and shall also be labeled with additional information – in order to indicate which fire alarm equipment is powered from each such circuit.

All fire alarm power supplies, as well as any other supplemental power supplies, shall be installed in compliance with NFPA-70 – National Electrical Code (Latest Edition). The panel shall include a disconnect switch for the AC power inside a locked enclosure near the panel or within the panel itself. This switch shall be labeled “Fire Alarm Power Disconnect”. Where the new control panel is to remain at same location as the existing panel, the contractor may re-use the existing branch circuit, if it meets the previously stated requirements stated above. The control panel shall include 120 VAC electrical power surge and transient protection. If problems are anticipated, due to electrical transients associated with periodic generator testing, then the fire alarm equipment supplier shall provide suitable power filtering / suppression equipment, as recommended by the equipment manufacturer. The system shall include sufficient back-up battery capacity to operate the entire system as follows, upon loss of normal 120 VAC power:

For panels, which are not connected to Dedicated Emergency Power (no Generator) Branch Circuits:

The Panel and associated devices shall operate in a normal (non-Alarm) mode for a period of 24 Hours. After the 24-Hour normal period has expired, sufficient capacity shall remain, such that the panel and associated devices shall operate in an Alarm mode (All Speakers EVAC) for a period of 15 minutes.

The panel shall include a power-limited, filtered and regulated battery charger. The charger shall charge a fully discharged battery to 70% in 12 hours. The panel shall monitor for AC fail / disconnect, low/no battery and high battery and shall distinctly display or annunciator any abnormality. The main panel power

Page 104: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 28 31 00 - 8

supply shall include sufficient power to power all connected field devices and an additional 25% spare power for future additions without the need to add additional boards or booster power supplies. The charger shall be designed specifically for, or shall be properly configured for the provided batteries, which shall be of one of the following types:

Sealed, Immobilized Electrolyte Lead-Acid type (“Gel-Cells”) – Types which require fluid level maintenance, or which vent significant amounts of Hydrogen shall be unacceptable. Nickel-Cadmium (Ni-Cad) batteries.

All batteries used in conjunction with the fire alarm system shall be installed in accordance with NFPA-70 – National Electrical Code (Latest Edition). If these batteries are not located within or immediately adjacent to the fire alarm equipment, the location of such batteries shall be clearly indicated within the fire alarm equipment served by them, and the batteries and their enclosure shall be clearly marked as “FIRE ALARM” All external circuits requiring system-operating power shall be 24VDC and shall be individually supervised and fused at the control panel.

PART 2 - PRODUCTS ENCLOSURES All panels and peripheral devices shall be the standard product of a single manufacturer and shall display the manufacturer's name on each component. Cabinet shall be equipped with locks and transparent door panel providing tamper proof enclosure yet allowing full view of the various lights and controls as required above. MULTIPLEX/INTELLIGENT FIRE ALARM CONTROL PANEL (FACP): A Multiplex intelligent fire alarm system shall be installed within the [This building shall be provided with a minimum of one fire Alarm Control Panel (FACP), as shown on the project drawings. The control Panel shall be modular, expandable with solid state, microprocessor based electronics. It shall display through the front viewing window only those primary controls and displays essential to operation during a fire alarm condition. The fire alarm system shall allow for loading and editing special instructions and operating sequences as required. Software programming shall allow for full flexibility for selective input/output control functions based on the Boolean programming functions AND, OR, NOT, as well as, timing, and special coded operations. The system shall be able to use all of the above programming functions in combination with any number of inputs and outputs. The systems shall be capable of on-site programming to accommodate system expansion and facilitate changes in operation. All software operations shall be stored in a non-volatile programmable memory within the fire alarm control panel. Loss of primary and secondary power shall not erase the instructions stored in memory. Simple Addressable systems, which do not support Analog Addressable or Intelligent Addressable detection technology, shall be unacceptable. The control panel shall provide the following as standards:

Analog Addressable or Intelligent Addressable Detection, supporting the following: Drift compensation Sensitivity display in % Sensitivity adjustment Day/night sensitivity adjustment Auto Detector test to meet NFPA 72 Alarm verification with tally counter Maintenance alerts

The number of Signaling Line Circuits (SLCs) required for the specified quantity of addressable field devices and peripherals, plus one (1) spare loop (SLC) for each five (5) active loops. Each active loop shall include 10% spare capacity or a minimum of 10 additional devices.

Page 105: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 28 31 00 - 9

The number of Audible Notification Appliance Circuits (Speaker NACs) required for the specified quantity of speakers plus one (1) spare circuit for each ten (10) active circuits. Each active circuit shall include 25% spare capacity The number of Visual Notification Appliance Circuits (Strobe NACs) required for the specified quantity of strobes plus one (1) spare circuit for each ten (10) active circuits. Each active circuit shall include 25% spare capacity or a minimum of (4) 110 cd devices that can be added in the future. 80-character liquid crystal display. Printer interface History log file with a minimum of 800 events Field programmability Silent walk test

The multiplex/intelligent system shall provide the ability to recall alarms and trouble conditions in chronological order for the purpose of recreating an event history. The LCD shall display the following information relative to the abnormal condition of a point in the system prior to acknowledgement: 40 characters for: Point address and loop number (i.e. 555-L5) Type of device (i.e. smoke sensor, pull station, water-flow) Point status (i.e. alarm, trouble) 40 characters for: Custom location label (i.e. 4th Floor - Room 444) Keyboards or keypads shall not be required to operate the system during fire alarm conditions. The following software functions shall be provided, from the built-in system keyboard / display:

Setting of time and date LED testing Alarm, trouble, and abnormal condition listing Enabling and disabling of each monitor point separately Activation and deactivation of each control point separately Changing operator access levels Walk Test enable / disable Running diagnostic functions Displaying historical logs Point listing

The following hardware control switches/functions shall be provided within the main panel enclosure: Acknowledge alarm or trouble Silence alarm or trouble Reset system after alarm Connect/disconnect Central Monitoring tie Provide manual evacuation (drill) Provide manual ALERT message(s) activation Provide manual audio selection switches (if select voice is specified) Provide manual selection of indoor or outdoor speakers Bypass elevator interface Bypass AHU / Fan Interface Bypass door holders (2) Future programmable switches Switches mentioned above but not applicable to this building shall still be provided in the stated quantity. These unused switches shall not be initially programmed and would be label unused

STATUS INDICATORS AND DISPLAYS A local audible device shall sound during Alarm, Trouble or Supervisory conditions. This audible device shall also sound during each key-press to provide an audible feedback to ensure that the key has been pressed properly.

Page 106: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 28 31 00 - 10

The 2-line by 40-character liquid crystal display shall be backlit for enhanced readability. A cursor shall be visible on the LCD when entering information.

Scrolling through menu options or lists shall be accomplished in a self-directing manner in which prompting messages shall direct the user

LED SUPERVISION All slave modules LEDs shall be supervised for burnout or disarrangement. ACKNOWLEDGMENT Two methods of acknowledgment for each abnormal condition shall be provided. One may be chosen depending on the NFPA requirements. First method

- Acknowledge one event at a time from an unacknowledged list of events:

Pressing the appropriate acknowledge button shall display the first unacknowledged condition in the appropriate list (either alarm, supervisory or trouble), and require another acknowledge button. Press to acknowledge only the displayed point. After all points have been acknowledged, the LEDs shall glow steadily and the Sonalert will be silenced. The total number of alarms, supervisory and trouble conditions shall be displayed along with a prompt to review each list chronologically. The end of the list shall be indicated by an end of list message "END of LIST". Second method

- Pressing the appropriate acknowledge button shall globally acknowledge all points.

SILENCING If an alarm condition exists and the "Alarm Silence" button is pressed, all alarm audio and visual notifications appliances shall cease operation. If trouble conditions exist in the system and the "Trouble Silence" button has been pressed, the aural trouble signal shall cease, but shall resound at time intervals to act as a reminder that the fire alarm system is not in a normal operating mode. Both the time interval and the trouble reminder signal shall be programmable to suit the Owner's application. RESET The SYSTEM RESET button shall be used to return the system to its normal state after an alarm condition has been remedied. Should the Alarm Silence Inhibit function be active, the system shall ignore all key presses. An indication of enabling and disabling the inhibit state shall be provided as a feedback to the operator. BYPASS FUNCTIONS Provide a switch for each item as shown below. Switches not applicable to this building would be provided, but left non programmed and labeled and unused. Bypass Switches shall be configured such that whenever any bypass function is active, a Trouble status condition shall be reported by the system, per the Trouble Sequence. The trouble message shall indicate the active function(s). Bypass LEDs shall be configured such that LEDs corresponding to the active function(s) shall illuminate, and shall remain lit until the associated bypass function is de-activated (until the system is restored to normal operating status). Switches and LEDs shall be provided for the following functions

Central Monitoring Bypass

- When this bypass function is active; reporting of various status conditions to the reporting system shall be disabled.

Elevator Interface bypass

- When this bypass function is active; actuation of the Control Modules or Supervised Relays, which interface to the Elevator Controls and to the Shunt-Trip Circuit Breaker(s) shall be prevented.

HVAC / Fan Interface bypass - When this bypass function is active; actuation of the Control Modules or Supervised Relays, which interface to the AHU / Fan starters / Temperature Controls, and to any Smoke Dampers shall be prevented. (Smoke Control System bypass shall be accomplished via the separate, previously specified manual controls).

Page 107: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 28 31 00 - 11

Door holder release bypass

- When this bypass function is active; actuation of the Control Modules or Relays, which cause release of the Door Holders shall be prevented.

ACCESS TO OPERATOR FUNCTIONS: The following Operator Function Access Restrictions shall be adhered to as closely as possible. Where system limitations do not allow for the restrictions to be configured exactly as listed, alternate methods will be considered, and shall be brought to the attention of the Engineer prior to bidding:

ACCESS LEVEL 1 - BASIC OPERATOR FUNCTIONS: ACKNOWLEDGE

– allows Basic Operators to acknowledge ALARM, TROUBLE, and SUPERVISORY conditions, and to view the lists / logs associated with these functions.

SIGNAL SILENCE

– allows Basic Operators to silence the audible and visual signals. The system shall not permit signals to be silenced during “alarm silence inhibit mode” (if “Inhibit Mode” is utilized).

SYSTEM RESET

– allows Basic Operators to Reset the Fire Alarm System. The "System Reset" button shall be used to return the system to its normal state after an alarm condition has been remedied. The LCD display shall step the user through the reset process with simple English language messages.

POINT LISTING

All points list by address Monitor point list Signal/speaker list Auxiliary control list Feedback point list

HISTORY LOGGING The system shall be capable of logging and storing the last 800 events (alarm & trouble) in a history log. These events shall be stored in a battery protected random access memory. The following historical alarm/trouble log events shall be stored:

Alarms Alarm Acknowledgment Alarm Silence System Reset Alarm Historical log cleared Trouble conditions Supervisory alarms Trouble acknowledgment Supervisory acknowledgment Alarm Verification tallies Walk Test results Trouble Historical log cleared

SILENT WALK TEST WITH HISTORY LOGGING The system shall be capable of being tested by one person. While in testing mode the alarm activation of an alarm-initiating device shall be silently logged as an alarm condition in the historical data file. The panel shall automatically reset itself after the logging of the alarm. The momentary disconnection of an initiating or indicating device circuit shall be silently logged as a trouble condition in the historical data file. The panel shall automatically reset itself after logging of the trouble condition. Should the silent walk-test feature be on for an inappropriate amount of time (30 minutes max.) it shall revert to the normal mode automatically. The panel shall have the capability of dividing the system into distinctive walk test groups, a minimum of (8) groups.

Page 108: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 28 31 00 - 12

Should an alarm condition occur from an active point, not in walk test mode, it shall perform operations described above. After testing is considered complete, testing data may be retrieved from the system in chronological order to ensure device/circuit activation. WATCH-DOG TIMERS The system shall include independent "Watch-Dog" timers to detect and report failure of any microprocessor circuit, memory, or software. FIELD PROGRAMMING The system shall be fully programmable, configurable, and expandable in the field without the need for special tools or PROM programmers and shall not require replacement of memory IC's. All programming may be accomplished through the standard control panel keyboard or a keyboard at the printer, or the use of a PC. All programs shall be stored in non-volatile memory. All programming or reprogramming shall be done by the supplier at no charge until the owner accepts the system. SOFTWARE MODIFICATIONS The system shall be capable of being programmed by means of a Field Configuration Program (FCP) allowing programming to be downloaded via portable computer from any node on the network. Provide the services of a factory trained and authorized Technician to perform all system software modifications, upgrades, or changes. Response time of the Technician to the site shall not exceed 4 hours. Should the Owner have a factory trained and authorized technician on staff, provide all hardware, software, programming tools, access codes, and documentation necessary to modify the fire alarm system on site. Modification includes addition and deletion of devices, circuits, zones, and changes to system operation and custom label changes for devices or zones. The system structure and software shall place no limit on the type or extent of software modifications on-site. Modification of software shall not require power-down of the system or loss of system fire protection while modifications are being made. If the system access code is either a hardware key or a software key, the Contractor/Vendor shall provide the proper key to meet the above requirements." SIGNALING LINE CIRCUITS: The system must provide communications with intelligent addressable initiating and control devices individually. These devices shall be individually annunciated at the control panel [and FAAP] [and RFCC]. Annunciation shall include the following conditions for each point:

Alarm Trouble Open Short Device missing/failed

All intelligent addressable initiation and control devices shall have the capability of being disabled or enabled individually. Systems that require factory pre-programming or EPROMs to add or delete devices shall be unacceptable. The communication format must be a completely digital poll/response protocol to allow t-tapping of the Signaling Line Circuit wiring. Systems that do not utilize full digital transmission protocol are not acceptable. Special-purpose Isolator devices shall be used to provide further isolation / protection of sections of the Signaling Line Circuits. Areas served by Signaling Line Circuits shall be isolated as specified within the “scope” portion of this specification. The following Isolation devices shall be acceptable for use in performing this function:

Isolator Modules – Field Mounted. OPERATION: MULTIPLEX/INTELLIGENT FIRE ALARM SYSTEM PRIORITY: Manual ALERT voice messages (prerecorded or live) shall have the highest priority.

Page 109: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 28 31 00 - 13

FIRE alarm status conditions shall have second highest priority. Supervisory status conditions shall have the third highest priority. Trouble status conditions shall have the lowest priority. STAND-BY MODE: Under normal condition the front panel shall display a "System is Normal" message and the current time and date SYSTEM RESPONSE The time delay between the FIRE alarm activation of an initiating device and the automatic activation of the Notification Appliances and the annunciation of the alarm status condition at the FACP and annunciators shall not exceed 5 seconds. For response-time purposes, the manual actuation of an Audio Control Switch - associated with the one-way voice communications system - shall be instantaneous and shall be treated as if it were manual alarm activation. ALARM SEQUENCE: The following events are not required to occur in the stated order. However, ALL automatic responses must be initiated within the time interval allotted by UL and NFPA codes and standards. This “FIRE alarm sequence” shall be initiated upon receipt of one of the following, valid FIRE alarm status conditions:

Actuation of any Manual Pull Station, any Fire Protective Sprinkler System, any other Automatic Fire Suppression System, from any Smoke Detector, any Heat Detector, and any Beam-type Smoke or Flame Detectors.

The system alarm operation, subsequent to the activation of any of the conditions listed above, shall be as follows:

The EVAC System shall automatically initiate “EVAC” Mode. All audible notification appliances (Speakers) [within the building] [within the affected Notification Area(s)] shall sound, using a sequence that is compliant with NFPA-72 – including an Alert Tone and a Digital Voice Message. The Alert Tone and Digital Message shall be repeated a minimum of three times, and shall continue to be repeated until the Audible Notification Appliances are Silenced, or until a Manual Announcement is Made, or until the system is Reset. All visual notification appliances [within the building] [or within the affected Notification Area(s)] shall flash continuously until the system is [acknowledged] [reset]. Any subsequent alarm shall reactivate the alarm audible [and visual] notification appliances [within the building] [within the affected Notification Area(s)]. All doors normally held open by door control devices [within the building] [within the affected Notification Area(s)] shall release. [Alarm outputs connected to the facility reporting system shall be activated.] The system Alarm LED shall flash on the FACP, until the alarm has been acknowledged. Once acknowledged, this same LED shall latch on. A subsequent alarm received from another device shall flash the system alarm LED on the FACP . The LCD display shall show the new alarm information. A pulsing alarm tone shall occur within the FACP until the event has been acknowledged. The system shall have a single key that will allow the operator to display all alarms, troubles, and supervisory service conditions including the time and date of each occurrence. A programmed Alarm Message shall appear on the FACP LCD displays. These field programmable messages shall be revised, as directed by the Owner, during shop drawing review. The alarm shall be displayed on an 80-character LCD display as follows:

Page 110: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 28 31 00 - 14

40 characters for: Point address and loop number Type of device Point status 40 characters for: Custom location label

AUTOMATIC ALARM VERIFICATION: The initial Alarm activation of any system smoke detector shall initiate an alarm verification operation whereby the panel will reset the activated detector and wait for a second alarm activation. If, after (20) seconds and within (30) seconds after resetting, a second alarm is reported from the same or any other smoke detector, the system shall process the alarm as described previously. If no second alarm occurs within (30) seconds, the system shall resume normal operation. The alarm verification shall operate only on single smoke detector alarm. Other activated initiating devices or multiple smoke detector alarms shall be processed and reported immediately. The alarm verification operation shall be selectable by device or by group for addressable detectors and by IDC for non-addressable smoke detectors. Automatic Alarm Verification shall be enabled for all smoke detectors [including resident room smoke detectors if they are connected to the fire alarm system]. SELF-TEST AND AUTOMATIC DRIFT COMPENSATION: The control panel shall continuously perform an automatic self-test routine on each Smoke Detector, which will functionally check detector electronics and ensure the accuracy of the values being transmitted to the control panel. Any detector that fails this test shall indicate a "SELF TEST FAILED" trouble condition with the detector location at the control panel. All Intelligent Addressable Smoke Detectors used on this project shall incorporate automatic drift compensation / automatic sensitivity monitoring and adjustment, as described within the “definitions” portion of this specification section. OPERATOR INTERFACE / MAINTENANCE FEATURES FOR AUTOMATIC SMOKE DETECTION: An operator at the control panel shall have the capability to manually access the following information for each detector:

Primary status Device type Present average value Present sensitivity value selected Peak detection values Detector range (normal, dirty, etc.)

Values shall be in "percent of smoke obscuration" format so that no interpretation is required by the operator. An operator at the control panel shall have the capability to manually control the following for each detector:

Clear peak detection values Enable or disable the detector Clear verification tally Establish alarm sensitivity Control a detector's relay driver output

It shall be possible to program the control panel to automatically change the sensitivity settings of each detector based on time-of-day and day-of-week. The control panel shall clear a “Detector dirty” trouble after a detector has been removed from its base cleaned and replaced. ELEVATOR RECALL After any elevator lobby, machine room, or shaft smoke detector alarm is verified, it shall, in addition to the operations listed in the “FIRE alarm sequence”, cause Phase I Emergency Recall Operation according to the following sequence:

Page 111: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 28 31 00 - 15

If the alarmed detector is located on any floor other than the designated level of egress, an Addressable Control Module or a supervised remote relay shall be actuated. This Control Module / Relay shall be located within three feet of the elevator controls, and shall cause the associated cabs to be recalled to the designated recall floor. If the alarmed detector is located on the designated level of egress, an Addressable Control Module or a supervised remote relay shall be actuated. This Control Module / Relay shall be located within three feet of the elevator controls, and shall cause the associated cabs to be recalled to the alternate recall floor. If the alarmed detector is located within the shaft, or within the machine room, an Addressable Control Module or a supervised remote relay shall be actuated. This Control Module / Relay shall be located within three feet of the elevator controls, and shall cause the “Fire Hat Lamp” at the associated Fire Service Control Station provided by Elevator Contractor / Owner to Flash. This lamp illuminates steadily, in response to elevator lobby recall conditions.

ELEVATOR SHUNT TRIP The intended function of elevator Shunt-Trip operation is to disable power to the Elevator prior to Elevator Shaft or Machine Room Sprinkler Actuation. Elevator shaft and Machine Room Heat Detectors shall be configured as follows:

Detectors shall be configured for FIXED TEMPERATURE-ONLY OPERATION. Detectors shall have a lower actuation temperature than the sprinkler heads within the shaft and machine room. The EC shall coordinate this information with the Fire Protection Contractor. Detector shall be installed within 2 feet from the sprinkler head. Detectors shall have a lower response-time index than the sprinkler heads within the shaft and machine room. The EC shall coordinate this information with the Fire Protection Contractor.

If the alarmed heat detector is located within the elevator shaft, or within the machine room, an Addressable Control Module or a supervised remote relay shall be actuated. This Control Module / Relay shall be located within three feet of the shunt-trip circuit breaker, and shall interrupt power to the elevator. If the elevator is hydraulic, a second Control Module Contract shall allow elevator auxiliary power to lower the elevator to the proper level. Aux. power, if needed, shall be furnished by the elevator contractor. The Power Source, which is used to actuate each elevator shunt-trip circuit breaker, shall be individually supervised by the FACP. AHU SYSTEM INTERFACE Duct Smoke Detectors and Addressable Control Modules, or Supervised Remote Relays shall be provided as specified below. Duct Smoke Detectors shall be installed in compliance with the manufacturer’s recommendations. Each Addressable Control Module or Supervised Remote Relay for AHU and / or Fan shutdown shall be installed within 3 feet of the Temperature Control Panel to which it is connected. The Division 26 EC shall provide all wiring and terminations required for shutdown of the specified AHUs / Fans. The Addressable Control Modules or Supervised Remote Relays provided for this purpose shall be provided with DPDT output contacts. One SPDT set of the DPDT contacts shall be utilized for the specified shutdown function. The second SPDT set of the DPDT contacts shall be available for connection to the temperature controls, to indicate that unit shutdown – due to Duct Smoke – has occurred. The control panel shall provide an output alarm interface to the air handling/energy management system controllers, which in turns shall perform automatic function as specified in the applicable sections of Division 23. An override feature / control switch shall be provided which shall prevent shutdown of AHUs when this function is active. On this project, Air Handling Equipment Interface shall be configured as follows:

AHU-#: LOCATION: SIZE: CFM SERVES: DUCT SMOKE DETECTORS: # in supply air duct & # in return air duct

Page 112: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 28 31 00 - 16

FAN-#: LOCATION:

SIZE: CFM SERVES: DUCT SMOKE DETECTORS: # in supply air duct & # in return air duct

PROGRAMMING: (This shall apply to All AHUs / Fans listed above):

The associated Fan shall be shut down only upon actuation of the Duct Smoke Detector associated with the particular unit. All such AHUs / Fans shall remain shut down, until a valid System Reset occurs.

SPRINKLER SYSTEM SUPERVISORY SERVICE The control panel shall have a dedicated supervisory service LED and a dedicated supervisory service acknowledge switch. The activation of any standpipe or sprinkler valve supervisory (tamper) switch shall activate the system supervisory service audible signal and illuminate the LED at the control panel [and FAAP] [and the RFCC]. The panel shall provide differentiation between valve tamper activation and opens and/or grounds on the initiation circuit wiring.

The Fire Pump shall be monitored for presence of power, lose of power and phase reversal

Pressing the supervisory service acknowledge key will silence the supervisory audible signal while maintaining the supervisory service LED "on" indicating the off-normal condition. Restoring the valve to the normal position shall automatically reset the tamper indication. TROUBLE SEQUENCE: Disarrangement, disconnection, Power Failure, or malfunction of any supervised feature(s) / components of the System shall cause actuation of the following sequence of events:

A SYSTEM TROUBLE or POINT TROUBLE status condition shall be both audibly and visually indicated at the fire Alarm Control Panel (FACP) [and FAAP] [and the RFCC] in a way which differentiates the TROUBLE status clearly from an ALARM. Audible indication shall cease, once the TROUBLE has been acknowledged. In addition, a programmed message, similar in nature to the ALARM “Custom Labels”, shall appear on the FACP [and FAAP] [and the RFCC]. (Default messages, if TROUBLE Detector / Sensor / Module Point Messages are associated with ALARM messages, shall be acceptable.) A “Trouble Reminder” Feature, which causes the FACP to re-sound the TROUBLE indicators when System / Point TROUBLE conditions remain on the system, shall be enabled, and shall be set to re-sound every twelve (12) hours. Subsequent Troubles shall cause the FACP [and FAAP] [and the RFCC] TROUBLE LEDs and sounders to re-sound, along with the “Custom Label” and other information related to the “new” TROUBLE condition.

MANUAL DRILL A manual evacuation (drill) switch shall be provided to operate the FIRE alarm indicating appliances without causing other control circuits to be activated. MANUAL ALERT A manual ALERT switch shall be provided to operate the prerecorded voice message and amber ALERT indicating appliances without causing other control circuits to be activated. LED AND LCD TEST Activation of the Lamp Test switch shall turn on all LED indicators, LCD display, and the local sounder and then return to the previous condition. SYSTEM DIAGNOSIS

Page 113: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 28 31 00 - 17

The system shall include special software to detect, diagnose and report failures and isolate such failures to a printed circuit board level. SILENT WALK TEST WITH HISTORY LOGGING The actuation of the "Walk Test" switch/program at the control panel shall activate the "Walk Test" mode of the system, which shall cause the following to occur:

The Output Contacts, which provide the interface to the Fire Alarm System Reporting shall be bypassed. Control relay functions shall be bypassed, such as door holders, elevator capture, fan shut down, etc. The audio and visual circuits shall be bypassed. The control panel shall show a trouble condition. The alarm activation of any initiation device shall be silently logged as an alarm condition in the historical data file. The panel shall automatically reset itself after the logging of the alarm. Any momentary opening of an initiating or indicating appliance circuit shall be silently logged as a trouble condition in the historical data file. The panel shall automatically reset itself after logging of the trouble condition. If the system becomes inactive for a period of longer than 10 minutes the panel shall default to normal fire alarm functions.

It shall not

be required to manually restart or reboot the fire alarm panel after a silent walk test is completed.

MULTIPLEX/INTELLIGENT PERIPHERAL DEVICES All devices shall be supervised for trouble conditions. The system control panel shall be capable of displaying the type of trouble condition (open, short, device missing/failed). Failure of a device shall not hinder the operation of other system devices. DEVICE IDENTIFICATION Each intelligent device must be uniquely identified by an address code entered on each device at time of installation. The use of jumpers to set address shall not be acceptable. Device addressing schemes which use permanently-imbedded, electronically-identifiable “serial number” which is similar to the address imbedded within Personal Computer Network Interface Cards shall be acceptable. Fire Alarm Systems utilizing hand-held or briefcase-style programming tools, which are used to electronically assign addresses and/or programming parameters to devices shall be acceptable. However one such programmer tool shall be provided to the Owner at no additional cost. The address along with the loop number and end-of-line device if present shall be indicated, and be visible from the ground, on the device in the field using machine generated marking. Contractor shall provide a sample of such labeling scheme before using it. End-of Line devices shall also be identified by means of permanent, machine generated label, affixed to the device. Device identification schemes that do not use uniquely set addresses but rely on electrical position along the communication channel are unacceptable. These systems cannot accommodate t tapping and the addition of an intelligent device between existing devices requires re-programming all existing devices beyond added device. The system must verify that proper type device is in place and matches the desired software configuration. INTELLIGENT DETECTORS - GENERAL Smoke and heat detectors must be approved by the State Engineer prior to installation. Each detector shall incorporate the following features:

LED(s), which shall flash to indicate communication with the Fire Alarm System, and which also illuminate in a steady mannerA means to allow field function testing of the detector

when the detector is in an alarm status

A low-profile design / shape

Page 114: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 28 31 00 - 18

An insect screen Voltage and RF transient suppression techniques, in order to minimize false alarms

Smoke detectors shall communicate the actual smoke chamber values to the system control panel. Smoke detectors shall be listed for sensitivity testing from the control panel. Sensitivity test results shall be logged and downloaded to a printer. The detectors shall be plug-in units, which mount to a common base, and shall be UL 268 approved. Each detector shall be compatible with the fire alarm panel and shall obtain its operating power from the SLC, to which it is connected. (Where relay or sounder-equipped bases are used, it shall be acceptable to require a separate 24 VDC or NAC connection.) Each detector shall be reset by actuating the control panel reset switch. If field conditions so require the smoke detection devices shall not be installed until the construction is completed. INTELLIGENT DETECTOR BASES Bases shall be suitable for either smoke or heat detector mounting. Either the base or the head shall contain electronic circuits that communicate the detector's status (normal, alarm, sensitivity status, trouble, etc.) to the control panel over two wires. The same two wires shall also provide power to the base and detector. Contacts between the base and head shall be of the bifurcated type using spring-type, self-wiping contacts. The base shall be lockable. The locking feature must be field-removable when not required. Upon removal of the detector's head, a trouble signal shall be transmitted to the control panel. The detector base shall be sealed against rear airflow entry. Each detector's base or head shall contain LED(s), which shall flash when the detector is being scanned by the control panel. The LED(s) shall turn on steady

when the detector is in an alarm condition.

INTELLIGENT PHOTOELECTRIC SMOKE DETECTORS The detectors shall contain no radioactive material. Detectors shall be of the solid state photoelectric type and shall operate on the light scattering photodiode principle using a pulsed infrared LED light. INTELLIGENT THERMAL DETECTORS The detectors shall be a combination rate-of-rise and fixed temperature 135 F unless noted. Detectors shall sense within a temperature range of 32 F to 158 F. The control panel shall be capable of sensing either a set point of 135 F, or a rate-of-rise of 15 degrees F per minute for fire sensing. MULTI-CRITERIA DETECTORS The Intelligent multi-criteria detector shall have advanced software to continuously sample the air in an environment and adjust its detection parameters and alarm threshold accordingly. It shall do this automatically, without user intervention. Detector shall incorporate either thermal and photoelectric technologies or thermal, photoelectric and carbon monoxide technologies. Detector shall have on-board microprocessor and advanced software that focuses on rejecting nuisance alarms. INTELLIGENT DUCT SMOKE DETECTORS Duct detectors shall be of the photoelectric type specified above. It shall be possible to alarm the duct detector by using a remote or local test switch.

Page 115: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 28 31 00 - 19

For maintenance purposes, it shall be possible to clean the duct housing sampling tubes by accessing them through the duct housings front cover. Detector shall include remote keyed test switch and alarm LED indicator. In mechanical rooms, alarm LED indicators and test switches for duct detectors shall be grouped on a stainless steel cover plate mounted adjacent to the main mechanical room door. Each LED/switch shall be labeled with the detectors loop and address. A floor plan of the room showing the detectors and addresses shall be located adjacent to the cover plate. Provide Plexiglas cover over the plan. CARBON MONOXIDE DETECTORS Carbon monoxide detector shall be listed to Underwriters Laboratories UL 2075 for Gas and Vapor Detectors and Sensors. The detector shall be equipped with a sounder and a trouble relay. The detector’s base shall be mountable to a single-gang electrical box. Wiring connections shall be made by means screws. The detector shall provide dual color LED indication that blinks to indicate normal standby, alarm, or end-of-life. When the sensor supervision is in a trouble condition, the detector shall send a trouble signal to the panel. The detector shall provide a means to test CO gas entry into the CO sensing cell. The detector shall provide this with a test mode that accepts CO gas from a test agent and alarms immediately upon sensing CO entry. Carbon monoxide alarm signals shall be displayed as SUPERVISORY signals on the fire alarm system displays. ADDRESSABLE PULL STATIONS Pull stations shall contain circuits that communicate the station's status (alarm, normal or trouble) to the control panel over two wires, which also provide power to the pull station. The address shall be field programmable on the station. Manual stations shall be [single-action] [double-action] type, constructed of metal or of high impact, red Lexan with raised white lettering and a smooth high gloss finish. Station shall mechanically latch upon operation and remain so until manually reset by means of a key common to all system locks. Stations that require Allen wrenches or special tools to reset them shall not be accepted

.

Manual stations shall be fitted with screw terminals or wire leads for field wire attachment. INTERFACE MODULES - GENERAL If external power to Addressable Interface Modules is required, such power shall be 24VDC, and shall be derived from a supervised fire alarm power supply. Addressable Interface Modules may be provided in either a Class B or Class A supervision version. In the Class B version the wiring shall be supervised by an end-of-line device. In the Class A version the wiring shall be looped back through a separate conduit/route and connected to the module to allow continual operation of the controlled devices even if the wiring sustains a single break. The interface modules shall be supervised and uniquely identified by the control panel. Device identification shall be transmitted to the control panel for processing according to the program instructions. INTERFACE MODULES - SUPERVISED CONTROL Supervised Control Modules shall be utilized where needed, for control of Notification Appliances. For Notification Appliances, speakers, and other device control with Class B or Class A wiring supervision, the interface module shall provide a double-pole/double-throw relay output, with supervision. These interface modules shall communicate the supervised wiring status (normal, trouble) to the fire alarm control panel and shall receive from the fire alarm control panel a command to transfer the relay. INTERFACE MODULES - SUPERVISED MONITORING

Page 116: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 28 31 00 - 20

Addressable Monitor Modules shall be suited for monitoring of water-flow, valve tamper, fire Suppression Control Panels, and other non-intelligent detectors and systems. Addressable Monitor Modules shall be provided in any needed configuration, and may be used to interface any of the following initiation devices to a Signaling Line Circuit, as follows:

Conventional 2-wire smoke detectors, including providing suitable power to the IDC. Normally Open, dry contact type devices - with class B or class A wiring supervision:

These interface modules shall communicate the Initiating Device Circuit status (normal, alarm, trouble) to the control panel.

INTERFACE MODULES - NON-SUPERVISED CONTROL

This interface module shall provide double-pole/double-throw relay switching for loads up to 120VAC. It shall contain easily replaceable 2 amp fuses, one on each common leg of the relay.

FAULT ISOLATOR MODULE (FIM) The system shall employ Fault Isolator Modules (FIM) on the Signaling Line Circuits. These FIM units shall be utilized in order to isolate portions of SLCs, in the event of short circuit conditions. The SLC segment protected by each FIM shall be separated from the SLC in a manner such that a single short-circuit condition may not affect more than 25 Addressable Field Devices / Detectors, which are served by the isolated SLC segment. The FIM shall be located as close as practical to the point where the isolated SLC sub-circuit branches, and shall also be located at an accessible location. CONVENTIONAL PERIPHERAL DEVICES NON-ADDRESSABLE HEAT DETECTORS Non-Addressable Heat Detectors shall of the fixed temp type and only to be used at locations where the ambient conditions are unsuitable for Analog Addressable units, or where the required operation (set point / response index, etc.) cannot be achieved with Analog Addressable units. Where used, these devices shall be UL listed for their intended purpose. These heat detectors do not have to be made by the same manufacturer supplying the other fire alarm equipment for the project. PROJECTED BEAM TYPE SMOKE DETECTORS The Projected Beam Type Smoke Detectors shall be listed per UL 268 and shall functionally interface to the FACP as a standard, 4-wire type smoke detector. The Projected Beam Type Smoke Detectors shall incorporate built-in "aiming-aid" features, such as optical sights or indicator LEDs. Where additional wiring or particular configurations are recommended by the manufacturer, in order to take advantage of built-in aiming features, such wiring or configurations shall be provided. Installation methods utilized with these units shall be in strict compliance with the manufacturer’s instructions. A Remote Test Station shall be supplied for each TX / RX pair. Power to each TX / RX pair shall be supervised, by means of either built-in Trouble relay outputs at each detector, or by means of end-of-line relays at each detector. Such Trouble Relay outputs and / or end-of line relays shall be connected to the IDC which monitors each TX / RX pair in a manner, such that Trouble conditions indicated by such relays / outputs do not prevent the transmission of an Alarm over the IDC. Each TX / RX pair shall be individually monitored for Alarm status conditions, via addressable Monitor Modules, or via dedicated IDC circuits. Each TX / RX pair shall be individually monitored for Trouble status conditions. SPRINKLER WATERFLOW SWITCHES – WET SYSTEMS Waterflow switches shall be individually monitored, via individual IDCs, Monitor Modules, or Mini Monitor Modules. The point corresponding to each Waterflow switch shall be programmed such that when activated, the suitable FIRE Alarm sequence shall be initiated.

Page 117: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 28 31 00 - 21

If the flow switch incorporates an internal “cover tamper switch”, which actuates whenever the flow switch assembly cover is removed, the Trouble sequence shall be initiated in response to the removal of this cover. AUDIO VISUAL NOTIFICATION APPLIANCES SPEAKERS Speakers shall have vandal resistant metal or Lexan white housing or grills with field adjustable output taps ranging from 1/4 watt to 2 watts. Speakers selected for this project shall produce a Sound Pressure Level, at the 1 watt tap of at least 86 dBA

at 10 feet – as tested per UL Standard 1480. Speakers shall have sealed backs to protect the phenolic impregnated cone.

SUPERVISED HORN LOUDSPEAKERS Supervised horn loudspeakers shall be equipped with a compression driver providing up to 15 Watt RMS power handling capability. Horn loudspeakers when installed outdoors, shall be of the weather-resistant metal construction to provide protection against water, humidity, vermin, and corrosion.. The mounting bracket allows directional sound dispersion via the vertical and the horizontal positioning. Provisions shall include for surface or strap mounting for the installation to pillars and I-beams. Horn loudspeakers shall include 25/70/100V transformer with adjustable 7-position Watt/ impedance selection switch. STROBES ALL strobes, and the strobe portion of audible/strobe combination units, shall be of the Xenon type. FIRE alarm strobes shall have clear lenses and labeled “FIRE”. ALERT strobes shall have amber lenses and labeled “ALERT”. When mounted on the same box or when dual strobe expander plate is used, the ALERT strobe shall be on the bottom. ALL strobes shall be designed for synchronized flash operation at one flash per second (1 Hz) minimum over the device's listed input voltage range. Strobes shall be synchronized such that all strobe units within the building shall flash simultaneously (As a minimum, all devices on each floor shall flash simultaneously, with flash timing within the limits established by current UL standards.). SPECIAL DEVICES TOOLS/KEYS Contractor shall provide two (2) keys per pull station. Keys shall be identical and usable in all keyways associated with this project – including, but not limited to Manual Pull Stations, the FACP Panel(s). Provide one device programmer tool and case for fire alarm systems utilizing hand-held or briefcase-style programming tools used to electronically assign addressees and/or programming parameters.

PART 3 - EXECUTION GENERAL The complete installation shall be done in a neat, workmanlike manner in accordance with the applicable requirements of NFPA 70 - Article 760 and the manufacturer's recommendations. Smoke detectors shall not be mounted until the construction is completed, unless they are covered with plastic bags or fitted covers immediately after installation to maintain cleanliness. RACEWAYS All wiring shall be in a conduit system separate from other building wiring. See Section 26 05 33 – Raceway and Boxes for Electrical Systems for specifications. All wiring shall be in minimum ½" steel raceway, unless free-air wiring is approved.

Page 118: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 28 31 00 - 22

40% fill factor shall be applied to all conduit sizes. The contractor shall size conduit and boxes by circular mil size of each cable in each conduit or box. The circular mil sizing can be found on the manufacture's spec sheet, then use the NEC codebook to make calculation to follow NEC Chapter 9 Tables and Annex C for box and conduit fill. There shall be no sharp edges with installed materials. Use only identified conduit entries or request approval for other penetrations in cabinets; (certain areas require clear space for interior components / batteries). Cabinet shall be grounded to either a cold water pipe or grounding rod. Existing conduit and surface metal raceway that is ½” in size or larger may be reused if found to have adequate space provided that it only serves the fire Alarm system and doesn’t contain any AC wiring. All existing conduit that is reused MUST be brought up to the current State of Wisconsin Electrical Code and Approved for usage by the Engineer prior to work being done. FREE AIR WIRING: All wiring shall be run “free-air”, in conduit or in surface raceway. "Free-air" wiring for horizontal cable runs of Power Limited FIRE Alarm (PLFA) DC circuits as approved by the Engineer shall be the method of installation only

Finished accessible ceiling in the following areas:

Rooms designated as ‘mechanical’ rooms

All other

wiring shall be installed in conduit.

Where installed “free-air”, installation shall consider the following:

Cable shall run at right angles and be kept clear of other trades work. All cable run as “Free-Air” shall be Tray Cable rated. All splices shall be done in approved junction boxes. Junction boxes or at minimum the cover shall be red with FA inscribed on it. Cables shall be supported according to code utilizing "Bridal-type" mounting rings or J hooks anchored to ceiling concrete, piping supports or structural steel beams. Rings shall be designed to maintain cables bend to larger than the minimum bend radius (typically 4 x cable diameter). Supports should be spaced at a maximum 4-foot interval unless limited by building construction. If cable "sag" at mid-span exceeds 12-inches, another support shall be used. Cable shall never be laid directly on the ceiling grid.

Cables shall not be attached to or supported by, existing cabling, plumbing or steam piping, ductwork, ceiling supports or electrical or communications conduit.

A coil of 4 feet in each cable shall be placed in the ceiling at each “free-air” wired fire alarm device. These "service loops" shall be secured at the last cable support before the cable reaches the device and shall be coiled from 100% to 200% of the cable recommended minimum bend radius. Devices wired with conduit shall be provided with an 8-inch wire tail at each device box and 36-inch wire tails at the FACP and FAAP. To reduce or eliminate EMI, the following minimum separation distances from ≤480V Power lines shall be adhered to:

Twelve (12) inches from power lines of <5-kVa. Eighteen (18) inches from high voltage lighting (including fluorescent). Thirty-nine (39) inches from power lines of 5-kVa or greater. Thirty-nine (39) inches from transformers and motors.

Page 119: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 28 31 00 - 23

All cable shall be free of tension at both ends. In cases where the cable must bear some stress, Kellom grips may be used to spread the strain over a longer length of cable. Manufacturers minimum bend radius specifications shall be observed in all instances. Care should be taken in the use of cable ties to secure and anchor the fire alarm cabling. Ties should not be over tightened as to compress the cable jacket. No sharp burrs should remain where excess length of the cable tie has been cut. All vertical cable extensions to fire alarm devices located below the finished ceiling shall be in conduit. It is the contractors' responsibility to survey the site and include all necessary costs to perform the installation as specified. This includes any modifications required to route and conceal horizontal distribution wiring. Beginning installation means contractor accepts existing conditions. Contractor shall furnish all required installation tools to facilitate cable pulling without damage to the cable jacket. Such equipment is to include, but not limited to, sheaves, winches, cable reels, cable reel jacks, duct entrance tunnels, pulling tension gauge and similar devices. All equipment shall be of substantial construction to allow steady progress once pulling has begun. Makeshift devices, which may move or wear in a manner to pose a hazard to the cable, shall not be used. All cable shall be pulled by hand unless installation conditions require mechanical assistance. Where mechanical assistance is used, care shall be taken to insure that the maximum tensile load for the cable as defined by the manufacturer is not exceeded. This may be in the form of continuous monitoring of pulling tension, use of a “break-away” or other approved method. The contractor will be responsible for identifying and reporting to the Site Coordinator(s) any existing damage to walls, flooring, tiles and furnishings in the work area prior to start of work. The Contractor must repair all damage to interior spaces caused by the installation of cable; raceway or other hardware. Repairs must match preexisting color and finish of walls, floors and ceilings. Any contractor-damaged ceiling tiles are to be replaced to match color, size, style and texture. Where unacceptable conditions are found, the Contractor shall bring this to the attention of the construction supervisor immediately. A written resolution will follow to determine the appropriate action to be taken. Qualified personnel utilizing state-of-the-art equipment and techniques shall complete all installation work. During pulling operation an adequate number of workers shall be present to allow cable observation at all points of duct entry and exit as well as the feed cable and operate pulling machinery. Cable pulling shall be done in accordance with cable manufacturer’s recommendations and ANSI/IEEE C2 standards. Manufacturer’s recommendations shall be a part of the cable submittal. Recommended pulling tensions and pulling bending radius shall not be exceeded. Any cable bent or kinked to radius less than recommended dimension shall not be installed. Avoid abrasion and other damage to cables during installation. Pulling Lubricant may be used to ease pulling tensions. Lubricant shall be of a type that is non-injurious to the cable jacket and other materials used. Lubricant shall not harden or become adhesive with age. CONDUCTORS All wire and cable associated with this system shall be as required by the equipment manufacturer. The following information is intended for estimating purposes only. However, the minimum wire gauges and colors specified shall be strictly adhered to. All cable shall be installed as per NEC Article 760. Type FPL wiring is required if the system is run in conduit or 'free-air. All initiation and notification circuit cabling shall be listed Type FPL (300V) in accordance with NEC article 760." All cables and wires #14 AWG and larger shall be stranded. fire alarm wiring shall be held in place at the device box, by means of a two-screw connector, (do not use squeeze or crimp type connectors).

Page 120: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 28 31 00 - 24

All wiring shall be completely supervised. In the event of a primary power failure, disconnected standby battery, disarrangement of any components, any open circuits or grounds in the system, an audible and visual trouble signal shall be activated until the system is restored to normal. All conductors shall be color-coded. Coding shall be consistent throughout the facility. Green wire shall be used only for equipment ground. Each FIRE Alarm Control Panel shall be connected to separate dedicated branch circuit from the building emergency panel, maximum 20 amperes. Circuit shall be labeled as "FIRE ALARM". The breaker shall be painted red and cap-locked. Power wiring for FIRE Alarm Control Panelshall be #12 AWG. FIRE Alarm Control Panel shall have #6 AWG green equipment ground wire. fire alarm risers, notification appliance circuits and interconnections to remote panels (per NFPA 72) shall have a minimum 2Hr fire alarm rating. All notification appliance circuits shall be protected from the fire alarm panel of origination to the signaling zone they serve. Where fire alarm circuits enter or leave a building, additional transient 75 to 90 volt gas tube protection shall be provided for each conductor. Leave 8-inch wire tails at each device box and 36-inch wire tails at the fire Alarm Control Panel [and Remote Annunciator Panel(s)], [and Remote FIRE Command Center]. Cable for Intelligent detector Loops shall be 18 to 12 AWG twisted pair with a shield jacket or per manufacturers recommendations installed in ½" conduit. Shield continuity must be maintained and connected to earth ground only at the control panel. SLC wiring must not be in the same conduit with AC power wiring or other high current circuits. T-taps or branch circuit connections are allowed for all class B SLCs. Cable for RS 232-c devices (CRT, PRINTER) shall be dual pair twisted- shielded. Cable for RS 485 devices (Remote Annunciators) shall be twisted-shielded pair (Belden 9841 or equivalent) for the data signal. Power wiring shall be 12 AWG. All splices or connections shall be made within approved junction boxes and with approved fittings. Boxes shall be red and labeled "FIRE ALARM SYSTEM" or “FA” by decal or other approved markings. Speaker and strobe circuits shall have separate conductors, and shall operate independently of each other. Speaker wiring shall be #18 AWG twisted-shielded cable or per manufacturers recommendations. Strobe wiring shall be #14 AWG minimum. Tray cable is not acceptable for use as fire alarm system wiring installed in conduit. DEVICE MOUNTING Unless otherwise noted on the drawings, plans, specifications or by the Architect or Engineer; the recommended mounting heights, and requirements are as follows: FIRE ALARM CONTROL PANELS Mount control panels such that all visual indicators and controls are located at 60 inches above floor level. VISUAL AND AUDIO / VISUAL NOTIFICATION APPLIANCES In Public-Mode Areas, as defined within NFPA-72, install flush, semi-flush or surface between 80 inches and 96 inches or 6 inches below finished ceiling or at 80 inches from the bottom of the device to the highest level of the finished floor. No devices protruding 4 inches or more shall be installed lower than 80 inches. If these requirements are not achievable, consult with the Engineer before installation.

Page 121: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 28 31 00 - 25

Audio/visual devices may be installed on the ceilings only where indicated, or where approved in writing by the Engineer. (In such cases, these devices shall be installed in accordance with current NFPA 72 standards). Audio/visual devices installed on ceilings shall have white grills Except as noted in the previous paragraph, all audio/visual devices shall be wall-mounted at the same height throughout the facility. Spacing of speakers shall not exceed 25 feet on center. Strobes spacing shall be in accordance with NFPA 72. For surface mounting, use manufacture-supplied back boxes and trim plates

, which shall be painted Red or off White, and shall contain no visible conduit knock-outs. Mark each device with its circuit number.

MANUAL STATIONS The operable part of the manual stations shall be installed not less than 3 ½ ft. (42") and not more than 4 ft. (48”) above finished floor. All Manual Stations shall be in unobstructed locations. Mark the unit’s address on the inside and outside of housing. All manual pull stations shall be installed at the same height throughout the facility. For surface mounting, use manufacture-supplied back boxes and trim plates

. Back boxes shall be painted Red or off White, and shall contain no visible conduit knock-outs. Mark each device with its loop and address.

During the installation of the new fire alarm systems, new pull stations should be covered or identified as not being operable so building occupants will not be confused as to which fire alarm pull station should be pulled during an alarm condition. Likewise, after the new system is installed, tested and accepted, the existing pull stations should be identified as not being operable (or permanently removed as soon as possible). HEAT AND SMOKE DETECTORS The location of detectors shown on the plans is schematic only. The detectors must be located according to code requirements. Surface mounted detectors shall be installed using back boxes equal to the base’s size. Standard octagon and square boxes are not acceptable. Detectors should be located on the highest part of a smooth ceiling so that the edge of the detector is no closer than 4 inches from a sidewall. Ceilings with beams, joists or soffits that exceed 8 inches in depth require special planning and closer spacing. If it is necessary to mount a detector upon a sidewall, the top of the detector (the sensing chamber portion of the device) shall be located no closer than 4 inches from the ceiling and no further away than 12 inches. Smoke detectors should be installed to favor the air flow towards return openings and not located closer than 3 feet from air supply diffusers which could dilute smoke before it reaches the detector. No detectors shall be installed in direct airflow. Duct smoke detector installation to be by this contractor and should be installed in the locations shown on the mechanical and electrical plans. Ensure that the duct smoke detectors are in serviceable locations. Consult with the mechanical designer for alternate locations if these are shown in non-serviceable locations. When locations on mechanical plans are not available, install in locations called for that provide accessibility for service. Do not install within four feet of a fan discharge Heat and smoke detectors should be located near the center of the open area which they are protecting, thus providing coverage generally for 15-foot radius for heat and smoke detectors. Questionable locations shall be verified with Architect or Engineer before installation takes place. Heat and smoke detectors / Sensors – both Intelligent and non-addressable, shall be installed in accordance with their UL Listed Spacing. The quantity of Heat and smoke detectors / Sensors depicted on the drawings is based on the 900 square foot per detector rule. If detectors with significantly different spacing requirements are selected by the fire Alarm equipment provider / EC, then additional detectors / sensors, if required, shall be provided at no additional cost to the project.

Page 122: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 28 31 00 - 26

IDENTIFICATION Attach the label containing the address and SLC designation to:

Each addressable detector. Label shall be visible and readable from the floor, 3/16” minimum character size (¼” is recommended). Each manual pull station. Label shall be placed on the top part Each Addressable Module. Label shall be attached to the faceplate

Label shall consist of black writing on white or clear background. All junction boxes shall be painted red and labeled "Fire Alarm" or “FA”. All circuits must be labeled with the name of circuit and the area being served by the circuit. Wire/cable splices in junction boxes shall be labeled indicating where the wire/cable is coming from and where it is going. All conductors terminated in control panels, annunciator panels and extension panels shall be labeled. All audio visual devices shall be labeled by each circuit and the order of the device on that circuit such as “Circuit No. 2, strobe No. 05 of 10”. All labels shall be permanent, and be machine generated. NO HANDWRITTEN OR NON-PERMANENT LABELS SHALL BE ALLOWED. Submit a sample for approval before using any labeling schemes. Label size shall be appropriate for the conductor or cable size(s) and design. All labels to be used shall be self-laminating, white/transparent vinyl and be wrapped around the cable (sheath). Flag type labels are not allowed

. The labels shall be of adequate size to accommodate the circumference of the cable being labeled and properly self-laminate over the full extent of the printed area of the label.

Adhesive type labels not permitted except for phase and wire identification. TESTING Before proceeding with any testing, all persons, facilities and building occupants whom receive alarms or trouble signals shall be notified by the contractor to prevent unnecessary response or building occupant distress. At the conclusion of testing, those previously notified shall be notified that testing has been concluded. The manufacturer's authorized representative shall provide on-site supervision of installation of the complete fire alarm system installation, perform a complete functional test of the system, and submit a written report to the Contractor attesting to the proper operation of the completed system prior to final inspection. Contractor shall pre-test each and every device in the system before the system is considered ready for final inspection. The completed and pre-tested fire alarm system shall be fully tested in accordance with NFPA-72 by the Contractor in the presence of the Engineer, Owner's representative and the local Fire Marshal. The Engineer or his authorized representative may suspend or discontinue the tests at any time performance is considered unsatisfactory. Resumption of testing will cover untested elements and any replaced elements. The contractor shall furnish all test personnel, test instruments and equipment of the accuracy necessary to perform the test. Arrangements for testing must be made at least two weeks before the proposed testing date. Upon the completion of a successful test, and prior to the final request for payment the Contractor shall:

Certify the system to the Owner in writing Complete the NFPA 72 record of completion form Provide as builts and O&M manuals. Provide a signed statement that the Owner had received the specified system operation and maintenance training

The final payment will not be processed unless these documents are complete and are on hand. WARRANTY

Page 123: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 28 31 00 - 27

The Contractor shall warrant the completed fire alarm system wiring and equipment to be free from inherent mechanical and electrical defects for a period of two (2) years from the date of substantial completion of the project. At the end of the project, the Contractor shall post the warranty period along with the company’s name and telephone number inside the fire alarm panel. Any occupied facility shall not be without a UL and an NFPA approved and fully operational fire alarm system for a period longer than two (2) hours. Emergency response shall be provided within two (2) hours of the notification, to the contractor, of the failure of the system to perform operationally per UL and NFPA standards. Non-emergency service calls shall be responded to within twenty-four (24) hours of the notification to the contractor. Emergency situations may include, but not limited to

System can’t be acknowledged or reset System is non-responsive to commands System in non-responsive to actuated alarm devices Malfunction of notification/initiating circuit(s) System going into alarm/trouble without indicating the source System is dead (no power), etc.

Repairs and/or replacement arising from emergency situations shall be completed within twenty-four (24) hours of the time of notification. Other than emergency, actual repairs and /or replacement shall be provided within seventy two (72) hours of the time of notification during normal working hours, Monday through Friday, excluding holidays. If the repairs involve parts that are not shelve items and require lead time, the contractor shall inform the Owner within twenty-four (24) hours from the time of notification of the exact time when the repairs will be completed. If repair and/or replacement cannot be made within the prescribed time, then other means and methods of protection shall be provided to insure the safety of the building’s occupants during which time the system is not in compliance with the standards. This may involve up to and include hiring Owner approved qualified personnel to stand a fire watch, all at the contractor's expense. Warranty service for the equipment shall be provided by the system supplier's factory trained representative. Further, Warranty shall include all parts, labor and necessary travel. TRAINING The Contractor through his/her supplier shall provide, as part of this contract, operation training for owner, the Architect/Engineer, and fire department personnel. The training session shall consist of the following sessions:

Sessions for the purpose of training personnel who will need to operate the system – primarily, Level 1 and Level 2 system operators / users. Session for the purpose of training personnel who will need to administrate and maintain the system. This training session shall familiarize these “power-users” with High-Level functions, and shall also familiarize Electrical Department personnel with an overview of the as-built drawings and equipment configuration / basic troubleshooting.

All training sessions shall be coordinated and scheduled by the EC, and shall be conducted at a time to be stipulated by the owner. All training and other indoctrination shall be completed prior to final inspection. The contractor shall record all training and instructional sessions on DVD. Provide a separate DVD for each system and label for the system demonstrated and turnover to the Owner. Training shall not take place until all systems are 100% operational as determined by the Owner. The purpose of training is to fully prepare the facility maintenance staff for complete operational responsibility of the fire alarm system. The facility maintenance staff shall be fully trained and be given the capability by the product Vendor and installing Contractor to modify, to program, to fully repair, to service, and to maintain the system after (and if desired, during) the warranty period. The above training shall include, but not be limited to, providing and reviewing all programming software, access codes, and licenses that allow the Owner to add or to delete any points (i.e.: The mapping of

Page 124: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

VILLAGE ARTS FACTORY - DORMITORY 28 31 00 - 28

devices), and to change a heat detector to a smoke detector. To meet this requirement, provide the necessary configuration and/or access code (hardware and/or software key). If the Vendor can not meet this requirement, the product is not acceptable

END OF SECTION

Page 125: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

Federal Labor Standards Provisions U.S. Department of Housing and Urban Development Office of Labor Relations

Previous editions are obsolete

Page 1 of 5

form HUD-4010 (06/2009) ref. Handbook 1344.1

Applicabil ity

The Project or Program to which the construct ion work covered by this contract pertains is being assisted by the United States of America and the fol lowing Federal Labor Standards Provisions are included in this Contract pursuant to the provisions appl icable to such Federal assistance.

A. 1. (i ) Minimum Wages. All laborers and mechanics employed or working upon the site of the work, wi l l be paid uncondit ional ly and not less often than once a week, and without subsequent deduct ion or rebate on any account (except such payrol l deduct ions as are permit ted by regulat ions issued by the Secretary of Labor under the Copeland Act (29 CFR Part 3), the fu l l amount of wages and bona f ide fr inge benefi ts (or cash equivalents thereof) due at t ime of payment computed at rates not less than those contained in the wage determinat ion of the Secretary of Labor which is attached hereto and made a part hereof, regardless of any contractual relat ionship which may be al leged to exist between the contractor and such laborers and mechanics. Contribut ions made or costs reasonably ant ic ipated for bona f ide fr inge benef i ts under Sect ion l(b)(2) of the Davis-Bacon Act on behalf of laborers or mechanics are considered wages paid to such laborers or mechanics, subject to the provisions of 29 CFR 5.5(a)(1)(iv); also, regular contribut ions made or costs incurred for more than a weekly period (but not less often than quarterly) under plans, funds, or programs, which cover the part icular weekly period, are deemed to be construct ively made or incurred during such weekly period.

Such laborers and mechanics shal l be paid the appropriate wage rate and fr inge benefi ts on the wage determinat ion for the classif icat ion of work actual ly performed, without regard to ski l l , except as provided in 29 CFR 5.5(a)(4). Laborers or mechanics performing work in more than one classif icat ion may be compensated at the rate specif ied for each classif icat ion for the t ime actual ly worked therein: Provided, That the employer’s payrol l records accurately set forth the t ime spent in each classif icat ion in which work is performed. The wage determinat ion (including any addit ional c lassif icat ion and wage rates conformed under 29 CFR 5.5(a)(1)(i i ) and the Davis-Bacon poster (WH-1321) shal l be posted at al l t imes by the contractor and i ts subcontractors at the site of the work in a prominent and accessible, place where i t can be easi ly seen by the workers.

(i i ) (a) Any class of laborers or mechanics which is not l isted in the wage determinat ion and which is to be employed under the contract shal l be classif ied in conformance with the wage determinat ion. HUD shal l approve an addit ional c lassif icat ion and wage rate and fr inge benefi ts therefor only when the fol lowing cri ter ia have been met:

(1) The work to be performed by the classif icat ion requested is not performed by a classif icat ion in the wage determinat ion; and

(2) The classif icat ion is ut i l ized in the area by the construct ion industry; and

(3) The proposed wage rate, including any bona f ide fr inge benefi ts, bears a reasonable relat ionship to the wage rates contained in the wage determinat ion.

(b) I f the contractor and the laborers and mechanics to be employed in the classif icat ion (i f known), or their representat ives, and HUD or i ts designee agree on the classif icat ion and wage rate (including the amount designated for fr inge benefi ts where appropriate), a report of the act ion taken shal l be sent by HUD or i ts designee to the Administrator of the Wage and Hour Divis ion, Employment Standards Administrat ion, U.S. Department of Labor, Washington, D.C. 20210. The Administrator, or an authorized representat ive, wi l l approve, modify, or disapprove every addit ional c lassif icat ion act ion within 30 days of receipt and so advise HUD or i ts designee or wi l l not i fy HUD or i ts designee within the 30-day period that addit ional t ime is necessary. (Approved by the Off ice of Management and Budget under OMB control number 1215-0140.)

(c) In the event the contractor, the laborers or mechanics to be employed in the classif icat ion or their representat ives, and HUD or i ts designee do not agree on the proposed classif icat ion and wage rate (including the amount designated for f r inge benefi ts, where appropriate), HUD or i ts designee shal l refer the quest ions, including the views of al l interested part ies and the recommendation of HUD or i ts designee, to the Administrator for determinat ion. The Administrator, or an authorized representat ive, wi l l issue a determinat ion within 30 days of receipt and so advise HUD or i ts designee or wi l l not i fy HUD or i ts designee within the 30-day period that addit ional t ime is necessary. (Approved by the Off ice of Management and Budget under OMB Control Number 1215-0140.)

(d) The wage rate (including fr inge benefi ts where appropriate) determined pursuant to subparagraphs (1)(i i ) (b) or (c) of this paragraph, shal l be paid to al l workers performing work in the classif icat ion under th is contract from the f irst day on which work is performed in the classif icat ion.

(i i i ) Whenever the minimum wage rate prescribed in the contract for a class of laborers or mechanics includes a fr inge benefi t which is not expressed as an hourly rate, the contractor shal l ei ther pay the benefi t as stated in the wage determinat ion or shal l pay another bona f ide fr inge benefi t or an hourly cash equivalent thereof.

(iv) I f the contractor does not make payments to a trustee or other third person, the contractor may consider as part

Page 126: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

Previous editions are obsolete Page 2 of 5

form HUD-4010 (06/2009) ref. Handbook 1344.1

of the wages of any laborer or mechanic the amount of any costs reasonably ant ic ipated in providing bona f ide fr inge benefi ts under a plan or program, Provided, That the Secretary of Labor has found, upon the writ ten request of the contractor, that the appl icable standards of the Davis-Bacon Act have been met. The Secretary of Labor may require the contractor to set aside in a separate account assets for the meeting of obl igat ions under the plan or program. (Approved by the Off ice of Management and Budget under OMB Control Number 1215-0140.)

2. Withholding. HUD or i ts designee shal l upon i ts own act ion or upon writ ten request of an authorized representat ive of the Department of Labor withhold or cause to be withheld from the contractor under this contract or any other Federal contract with the same prime contractor, or any other Federal ly-assisted contract subject to Davis-Bacon prevai l ing wage requirements, which is held by the same prime contractor so much of the accrued payments or advances as may be considered necessary to pay laborers and mechanics, including apprent ices, trainees and helpers, employed by the contractor or any subcontractor the ful l amount of wages required by the contract In the event of fai lure to pay any laborer or mechanic, including any apprent ice, trainee or helper, employed or working on the site of the work, al l or part of the wages required by the contract, HUD or i ts designee may, after wr i t ten not ice to the contractor, sponsor, appl icant, or owner, take such act ion as may be necessary to cause the suspension of any further payment, advance, or guarantee of funds unt i l such violat ions have ceased. HUD or i ts designee may, after wri t ten not ice to the contractor, disburse such amounts withheld for and on account of the contractor or subcontractor to the respect ive employees to whom they are due. The Comptrol ler General shal l make such disbursements in the case of direct Davis-Bacon Act contracts.

3. (i) Payrolls and basic records. Payrol ls and basic records relat ing thereto shal l be maintained by the contractor during the course of the work preserved for a period of three years thereafter for al l laborers and mechanics working at the si te of the work. Such records shal l contain the name, address, and social secur i ty number of each such worker, his or her correct c lassif icat ion, hourly rates of wages paid (including rates of contribut ions or costs ant ic ipated for bona f ide fr inge benefi ts or cash equivalents thereof of the types described in Sect ion l (b)(2)(B) of the Davis-bacon Act), dai ly and weekly number of hours worked, deduct ions made and actual wages paid. Whenever the Secretary of Labor has found under 29 CFR 5.5 (a)(1)(iv) that the wages of any laborer or mechanic include the amount of any costs reasonably ant ic ipated in providing benefi ts under a plan or program described in Sect ion l(b)(2)(B) of the Davis-Bacon Act, the contractor shal l maintain records which show that the commitment to provide such benefi ts is enforceable, that the plan or program is f inancial ly responsible, and that the plan or program has been

communicated in writ ing to the laborers or mechanics affected, and records which show the costs ant ic ipated or the actual cost incurred in providing such benefi ts. Contractors employing apprent ices or trainees under approved programs shal l maintain wr it ten evidence of the registrat ion of apprent iceship programs and cert i f icat ion of trainee programs, the registrat ion of the apprent ices and trainees, and the rat ios and wage rates prescribed in the appl icable programs. (Approved by the Off ice of Management and Budget under OMB Control Numbers 1215-0140 and 1215-0017.)

(i i ) (a) The contractor shal l submit weekly for each week in which any contract work is performed a copy of al l payrol ls to HUD or i ts designee i f the agency is a party to the contract, but i f the agency is not such a party, the contractor wi l l submit the payrol ls to the appl icant sponsor, or owner, as the case may be, for transmission to HUD or i ts designee. The payrol ls submitted shal l set out accurately and completely al l of the information required to be maintained under 29 CFR 5.5(a)(3)(i) except that ful l social securi ty numbers and home addresses shal l not be included on weekly transmittals. Instead the payrol ls shal l only need to include an individual ly ident i fying number for each employee (e.g., the last four digits of the employee’s social securi ty number). The required weekly payrol l information may be submitted in any form desired. Optional Form WH-347 is avai lable for th is purpose from the Wage and Hour Divis ion Web site at http:/ /www.dol.gov/esa/whd/forms/wh347instr.htm or i ts successor site. The prime contractor is responsible for the submission of copies of payrol ls by al l subcontractors. Contractors and subcontractors shal l maintain the ful l social securi ty number and current address of each covered worker, and shal l provide them upon request to HUD or i ts designee i f the agency is a party to the contract, but i f the agency is not such a party, the contractor wi l l submit the payrol ls to the appl icant sponsor, or owner, as the case may be, for transmission to HUD or i ts designee, the contractor, or the Wage and Hour Divis ion of the Department of Labor for purposes of an invest igat ion or audit of compliance with prevai l ing wage requirements. I t is not a violat ion of this subparagraph for a prime contractor to require a subcontractor to provide addresses and social securi ty numbers to the prime contractor for i ts own records, without weekly submission to HUD or i ts designee. (Approved by the Off ice of Management and Budget under OMB Control Number 1215-0149.)

(b) Each payrol l submitted shal l be accompanied by a “Statement of Compliance,” s igned by the contractor or subcontractor or his or her agent who pays or supervises the payment of the persons employed under the contract and shal l cert i fy the fol lowing:

(1) That the payrol l for the payrol l period contains the information required to be provided under 29 CFR 5.5 (a)(3)(i i ), the appropriate information is being maintained under 29 CFR 5.5(a)(3)(i), and that such information is correct and complete;

Page 127: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

Previous editions are obsolete Page 3 of 5

form HUD-4010 (06/2009) ref. Handbook 1344.1

(2) That each laborer or mechanic (including each helper, apprent ice, and trainee) employed on the contract during the payrol l period has been paid the ful l weekly wages earned, without rebate, either di rect ly or indi rect ly, and that no deduct ions have been made either di rect ly or indirect ly from the ful l wages earned, other than permissible deduct ions as set forth in 29 CFR Part 3;

(3) That each laborer or mechanic has been paid not less than the appl icable wage rates and fr inge benefi ts or cash equivalents for the classif icat ion of work performed, as specif ied in the appl icable wage determinat ion incorporated into the contract.

(c) The weekly submission of a properly executed cert i f icat ion set forth on the reverse side of Optional Form WH-347 shal l sat isfy the requirement for submission of the “Statement of Compliance” required by subparagraph A.3.(i i )(b).

(d) The fals i f icat ion of any of the above cert i f icat ions may subject the contractor or subcontractor to civi l or c riminal prosecut ion under Sect ion 1001 of Tit le 18 and Sect ion 231 of Tit le 31 of the United States Code.

(i i i ) The contractor or subcontractor shal l make the records required under subparagraph A.3.(i) avai lable for inspect ion, copying, or transcript ion by authorized representat ives of HUD or i ts designee or the Department of Labor, and shal l permit such representat ives to interview employees during working hours on the job. I f the contractor or subcontractor fai ls to submit the required records or to make them avai lable, HUD or i ts designee may, after wri t ten not ice to the contractor, sponsor, appl icant or owner, take such act ion as may be necessary to cause the suspension of any further payment, advance, or guarantee of funds. Furthermore, fai lure to submit the required records upon request or to make such records avai lable may be grounds for debarment act ion pursuant to 29 CFR 5.12.

4. Apprentices and Trainees.

(i ) Apprentices. Apprent ices wil l be permit ted to work at less than the predetermined rate for the work they performed when they are employed pursuant to and individual ly registered in a bona f ide apprent iceship program registered with the U.S. Department of Labor, Employment and Training Administrat ion, Off ice of Apprent iceship Training, Employer and Labor Services, or with a State Apprent iceship Agency recognized by the Off ice, or i f a person is employed in his or her f i rst 90 days of probat ionary employment as an apprent ice in such an apprent iceship program, who is not individual ly registered in the program, but who has been cert i f ied by the Off ice of Apprent iceship Training, Employer and Labor Services or a State Apprent iceship Agency (where appropriate) to be el igible for probat ionary employment as an apprent ice. The al lowable rat io of apprent ices to journeymen on the job site in any craft c lassif icat ion shal l not be greater than the rat io permit ted to the contractor as to the ent ire work force under the registered program. Any worker l isted on a payrol l at an apprent ice wage rate, who

is not registered or otherwise employed as stated above, shal l be paid not less than the appl icable wage rate on the wage determinat ion for the classif icat ion of work actual ly performed. In addit ion, any apprent ice performing work on the job site in excess of the rat io permit ted under the registered program shal l be paid not less than the appl icable wage rate on the wage determinat ion for the work actual ly performed. Where a contractor is performing construct ion on a project in a local i ty other than that in which i ts program is registered, the rat ios and wage rates (expressed in percentages of the journeyman’s hourly rate) specif ied in the contractor’s or subcontractor’s registered program shal l be observed. Every apprent ice must be paid at not less than the rate specif ied in the registered program for the apprent ice’s level of progress, expressed as a percentage of the journeymen hourly rate specif ied in the appl icable wage determinat ion. Apprent ices shal l be paid fr inge benefi ts in accordance with the provisions of the apprent iceship program. I f the apprent iceship program does not specify fr inge benefi ts, apprent ices must be paid the ful l amount of f r inge benefi ts l isted on the wage determinat ion for the appl icable classif icat ion. I f the Administrator determines that a dif ferent pract ice prevai ls for the appl icable apprent ice classif icat ion, fr inges shal l be paid in accordance with that determinat ion. In the event the Off ice of Apprent iceship Training, Employer and Labor Services, or a State Apprent iceship Agency recognized by the Off ice, withdraws approval of an apprent iceship program, the contractor wi l l no longer be permit ted to ut i l ize apprent ices at less than the appl icable predetermined rate for the work performed unt i l an acceptable program is approved.

(i i ) Trainees. Except as provided in 29 CFR 5.16, trainees wil l not be permitted to work at less than the predetermined rate for the work performed unless they are employed pursuant ‘ , to and individual ly registered in a program which has received prior approval, evidenced by formal cert i f icat ion by the U.S. Department of Labor, Employment and Training Administrat ion. The rat io of t rainees to journeymen on the job site shal l not be greater than permit ted under the plan approved by the Employment and Training Administrat ion. Every trainee must be paid at not less than the rate specif ied in the approved program for the trainee’s level of progress, expressed as a percentage of the journeyman hourly rate specif ied in the appl icable wage determinat ion. Trainees shal l be paid fr inge benefi ts in accordance with the provisions of the trainee program. I f the trainee program does not mention fr inge benefi ts, t rainees shal l be paid the ful l amount of f r inge benefi ts l isted on the wage determinat ion unless the Administrator of the Wage and Hour Divis ion determines that there is an apprent iceship program associated with the corresponding journeyman wage rate on the wage determinat ion which provides for less than ful l f r inge benefi ts for apprent ices. Any employee l isted on the payrol l at a trainee rate who is not registered and part ic ipat ing in a training plan approved by

Page 128: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

Previous editions are obsolete Page 4 of 5

form HUD-4010 (06/2009) ref. Handbook 1344.1

the Employment and Training Administrat ion shal l be paid not less than the appl icable wage rate on the wage determinat ion for the work actual ly performed. In addit ion, any trainee performing work on the job site in excess of the rat io permit ted under the registered program shal l be paid not less than the appl icable wage rate on the wage determinat ion for the work actual ly performed. In the event the Employment and Training Administrat ion withdraws approval of a tra ining program, the contractor wi l l no longer be permit ted to ut i l ize trainees at less than the appl icable predetermined rate for the work performed unt i l an acceptable program is approved.

(i i i ) Equal employment opportunity. The ut i l izat ion of apprent ices, trainees and journeymen under 29 CFR Part 5 shal l be in conformity with the equal employment opportunity requirements of Execut ive Order 11246, as amended, and 29 CFR Part 30.

5. Compliance with Copeland Act requirements. The contractor shal l comply with the requirements of 29 CFR Part 3 which are incorporated by reference in this contract

6. Subcontracts. The contractor or subcontractor wi l l insert in any subcontracts the clauses contained in subparagraphs 1 through 11 in th is paragraph A and such other clauses as HUD or i ts designee may by appropr iate instruct ions require, and a copy of the appl icable prevai l ing wage decision, and also a clause requiring the subcontractors to include these clauses in any lower t ier subcontracts. The prime contractor shal l be responsible for the compliance by any subcontractor or lower t ier subcontractor with al l the contract c lauses in this paragraph.

7. Contract termination; debarment. A breach of the contract c lauses in 29 CFR 5.5 may be grounds for terminat ion of the contract and for debarment as a contractor and a subcontractor as provided in 29 CFR 5.12.

8. Compliance with Davis-Bacon and Related Act Requirements. All rul ings and interpretat ions of the Davis-Bacon and Related Acts contained in 29 CFR Parts 1, 3, and 5 are herein incorporated by reference in this contract

9. Disputes concerning labor standards. Disputes aris ing out of the labor standards provisions of this contract shal l not be subject to the general disputes clause of this contract. Such disputes shal l be resolved in accordance with the procedures of the Department of Labor set forth in 29 CFR Parts 5, 6, and 7. Disputes within the meaning of this c lause include disputes between the contractor (or any of i ts subcontractors) and HUD or i ts designee, the U.S. Department of Labor, or the employees or their representat ives.

10. (i) Certification of Eligibil ity. By entering into th is contract the contractor cert i f ies that neither i t (nor he or she) nor any person or f i rm who has an interest in the contractor’s f i rm is a person or f i rm inel igible to be awarded Government contracts by virtue of Sect ion 3(a) of the Davis-Bacon Act or 29 CFR 5.12(a)(1) or to be

awarded HUD contracts or part ic ipate in HUD programs pursuant to 24 CFR Part 24.

(i i ) No part of this contract shal l be subcontracted to any person or f i rm inel igible for award of a Government contract by virtue of Sect ion 3(a) of the Davis-Bacon Act or 29 CFR 5.12(a)(1) or to be awarded HUD contracts or part ic ipate in HUD programs pursuant to 24 CFR Part 24.

(i i i ) The penalty for making false statements is prescribed in the U.S. Criminal Code, 18 U.S.C. 1001. Addit ional ly, U.S. Criminal Code, Sect ion 1 01 0, Tit le 18, U.S.C., “Federal Housing Administrat ion transact ions”, provides in part : “Whoever, for the purpose of . . . inf luencing in any way the act ion of such Administrat ion.. . . . makes, utters or publ ishes any statement knowing the same to be false. . . . . shal l be f ined not more than $5,000 or imprisoned not more than two years, or both.”

11. Complaints, Proceedings, or Testimony by Employees. No laborer or mechanic to whom the wage, salary, or other labor standards provisions of this Contract are appl icable shal l be discharged or in any other manner discriminated against by the Contractor or any subcontractor because such employee has f i led any complaint or inst i tuted or caused to be inst i tuted any proceeding or has test i f ied or is about to test i fy in any proceeding under or relat ing to the labor standards appl icable under this Contract to his employer.

B. Contract Work Hours and Safety Standards Act. The provisions of this paragraph B are applicable where the amount of the prime contract exceeds $100,000. As used in this paragraph, the terms “laborers” and “mechanics” include watchmen and guards.

(1) Overtime requirements. No contractor or subcontractor contracting for any part of the contract work which may require or involve the employment of laborers or mechanics shall require or permit any such laborer or mechanic in any workweek in which the individual is employed on such work to work in excess of 40 hours in such workweek unless such laborer or mechanic receives compensation at a rate not less than one and one-half times the basic rate of pay for all hours worked in excess of 40 hours in such workweek.

(2) Violation; l iabil ity for unpaid wages; l iquidated damages. In the event of any violat ion of the clause set forth in subparagraph (1) of this paragraph, the contractor and any subcontractor responsible therefor shal l be l iable for the unpaid wages. In addit ion, such contractor and subcontractor shal l be l iable to the United States (in the case of work done under contract for the District of Columbia or a terri tory, to such District or to such terri tory), for l iquidated damages. Such l iquidated damages shal l be computed with respect to each individual laborer or mechanic, including watchmen and guards, employed in violat ion of the clause set forth in subparagraph (1) of this paragraph, in the sum of $10 for each calendar day on which such individual was required or permitted to work in excess of the standard workweek of 40 hours without payment of the overtime wages required by the clause set forth in sub paragraph (1) of this paragraph.

Page 129: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

Previous editions are obsolete Page 5 of 5

form HUD-4010 (06/2009) ref. Handbook 1344.1

(3) Withholding for unpaid wages and l iquidated damages. HUD or i ts designee shal l upon i ts own act ion or upon writ ten request of an authorized representat ive of the Department of Labor withhold or cause to be withheld, from any moneys payable on account of work performed by the contractor or subcontractor under any such contract or any other Federal contract with the same prime contract, or any other Federal ly-assisted contract subject to the Contract Work Hours and Safety Standards Act which is held by the same prime contractor such sums as may be determined to be necessary to sat isfy any l iabi l i t ies of such contractor or subcontractor for unpaid wages and l iquidated damages as provided in the clause set forth in subparagraph (2) of this paragraph.

(4) Subcontracts. The contractor or subcontractor shal l insert in any subcontracts the clauses set forth in subparagraph (1) through (4) of this paragraph and also a clause requiring the subcontractors to include these clauses in any lower t ier subcontracts. The prime contractor shal l be responsible for compliance by any subcontractor or lower t ier subcontractor with the clauses set forth in subparagraphs (1) through (4) of this paragraph.

C. Health and Safety. The provisions of this paragraph C are applicable where the amount of the prime contract exceeds $100,000.

(1) No laborer or mechanic shal l be required to work in surroundings or under working condit ions which are unsanitary, hazardous, or dangerous to his health and safety as determined under construct ion safety and heal th standards promulgated by the Secretary of Labor by regulat ion.

(2) The Contractor shal l comply with al l regulat ions issued by the Secretary of Labor pursuant to Tit le 29 Part 1926 and fa i lure to comply may result in imposit ion of sanct ions pursuant to the Contract Work Hours and Safety Standards Act, (Publ ic Law 91-54, 83 Stat 96). 40 USC 3701 et seq.

(3) The contractor shal l include the provisions of this paragraph in every subcontract so that such provisions wi l l be binding on each subcontractor. The contractor shal l take such act ion with respect to any subcontractor as the Secretary of Housing and Urban Development or the Secretary of Labor shal l di rect as a means of enforcing such provisions.

Page 130: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2
Page 131: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

General Decision Number: MI160101 09/09/2016  MI101

Superseded General Decision Number: MI20150101

State: Michigan

Construction Type: Building

County: Wayne County in Michigan.

BUILDING CONSTRUCTION PROJECTS (does not include single familyhomes or apartments up to and including 4 stories).

Note: Under Executive Order (EO) 13658, an hourly minimum wageof $10.15 for calendar year 2016 applies to all contractssubject to the Davis‐Bacon Act for which the solicitation wasissued on or after January 1, 2015. If this contract is coveredby the EO, the contractor must pay all workers in anyclassification listed on this wage determination at least$10.15 (or the applicable wage rate listed on this wagedetermination, if it is higher) for all hours spent performingon the contract in calendar year 2016. The EO minimum wage ratewill be adjusted annually. Additional information on contractorrequirements and worker protections under the EO is availableat www.dol.gov/whd/govcontracts.

Modification Number     Publication Date          0              01/08/2016          1              01/15/2016          2              01/22/2016          3              02/26/2016          4              06/24/2016          5              07/22/2016          6              07/29/2016          7              08/19/2016          8              08/26/2016          9              09/02/2016          10             09/09/2016

 ASBE0025‐002 06/01/2016

                                  Rates          Fringes

ASBESTOS WORKER/HEAT & FROST   INSULATOR........................$ 31.51            31.04‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐ BOIL0169‐001 01/01/2014

Page 132: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

                                  Rates          Fringes

BOILERMAKER......................$ 32.78            28.39‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐ BRMI0001‐001 06/01/2013

                                  Rates          Fringes

BRICKLAYER.......................$ 32.67            18.40TILE FINISHER....................$ 26.15            16.22TILE SETTER......................$ 32.25            16.22‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐ CARP0687‐003 06/01/2016

                                  Rates          Fringes

CARPENTER (Including   Acoustical Ceiling   Installation, Drywall   Hanging, Form Work, Metal   Stud Installation & Scaffold   Building)........................$ 31.16            26.56‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐ CARP1045‐001 06/01/2016

                                  Rates          Fringes

CARPENTER (Floor Layer ‐   Carpet, Resilient, & Vinyl   Flooring)........................$ 28.00            23.02‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐ CARP1102‐002 06/01/2013

                                  Rates          Fringes

MILLWRIGHT.......................$ 31.11            28.64‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐* ELEC0058‐001 07/03/2016

                                  Rates          Fringes

ELECTRICIAN (Low Voltage   Wiring and Installation of   Alarms)       Installer...................$ 24.25            12.38     Technician..................$ 33.08            10.91ELECTRICIAN......................$ 38.73            22.05‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐

Page 133: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

 ELEV0036‐002 01/01/2016

                                  Rates          Fringes

ELEVATOR MECHANIC................$ 47.73           30.285‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐* ENGI0324‐017 06/01/2016

                                  Rates          Fringes

OPERATOR:  Power Equipment       GROUP  1....................$ 39.64            22.90     GROUP  2....................$ 38.14            22.90     GROUP  3....................$ 36.64            22.90     GROUP  4....................$ 36.34            22.90     GROUP  5....................$ 35.52            22.90     GROUP  6....................$ 34.66            22.90     GROUP  7....................$ 33.69            22.90     GROUP  8....................$ 31.98            22.90     GROUP  9....................$ 23.64            22.90

FOOTNOTES:   Tower cranes: to be paid the crane operator rate determined  by the combined length of the mast and the boom.  If the  worker must climb 50 ft. or more to the work station, $.25  per hour additional.

  Derrick and cranes where the operator must climb 50 ft. or  more to the work station, $.25 per hour additional to the  applicable crane operator rate.

POWER EQUIPMENT OPERATOR CLASSIFICATIONS    

GROUP 1: Crane with boom and jib or leads 400' or longer    

GROUP 2: Crane with boom and jib or leads 300' or longer    

GROUP 3: Crane with boom and jib or leads 220' or longer    

GROUP 4: Crane with boom and jib or leads 140' or longer    

GROUP 5: Crane with boom and jib or leads 120' or longer    

  GROUP 6: Regular crane operator, and concrete pump with boom  operator

  GROUP 7: Backhoe/Excavator/Trackhoe, bobcat/skid Loader,  broom/sweeper, bulldozer, grader/blade, highlift, hoist,  loader, roller, scraper, tractor & trencher

Page 134: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

GROUP 8: Forklift & extend‐a‐boom forklift    

GROUP 9: Oiler

‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐ IRON0025‐019 06/01/2015

                                  Rates          Fringes

IRONWORKER       REINFORCING.................$ 28.30            24.60     STRUCTURAL..................$ 33.78            27.84‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐ IRON0025‐022 04/01/2014

                                  Rates          Fringes

IRONWORKER STRUCTURAL (Metal   Building Erection Only)..........$ 23.39            21.13‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐ LABO0259‐002 08/01/2016

                                  Rates          Fringes

LABORER:  Asbestos Abatement   (Removal from Floors, Walls &   Ceilings)........................$ 27.50            13.22‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐ LABO0334‐005 06/01/2015

                                  Rates          Fringes

LABORER:  Landscape &   Irrigation       GROUP 1.....................$ 19.76             9.15     GROUP 2.....................$ 15.54             9.15

CLASSIFICATIONS    

  GROUP 1: Landscape specialist, including air, gas and diesel  equipment operator, lawn sprinkler installer, skidsteer (or  equivalent)

  GROUP 2: Landscape laborer: small power tool operator,  material mover, truck driver and lawn sprinkler installer  tender

‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐

Page 135: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

 LABO1191‐002 06/01/2016

                                  Rates          Fringes

LABORER       Common or General; Grade      Checker; Mason Tender ‐      Brick/Cement/Concrete;      Pipelayer; Sandblaster......$ 24.10            20.27‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐ PAIN0022‐003 06/01/2015

                                  Rates          Fringes

PAINTER:  Brush and Roller.......$ 26.06            17.66PAINTER:  Drywall   Finishing/Taping.................$ 27.05            18.26PAINTER:  Spray..................$ 26.86            17.66‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐ PAIN0357‐002 06/01/2015

                                  Rates          Fringes

GLAZIER..........................$ 30.05            18.10

  PAID HOLIDAYS: New Year's Day, Decoration Day, Fourth of  July, Labor Day, Thanksgiving Day and Christmas Day;  provided that the employee has worked the last full regular  scheduled work day prior to the holiday, and the first full  regular scheduled work day following the holiday, provided  the employee is physically able to work.

‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐ PLAS0067‐001 04/01/2014

                                  Rates          Fringes

CEMENT MASON/CONCRETE FINISHER...$ 30.63            14.07‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐ PLAS0067‐004 04/01/2014

                                  Rates          Fringes

PLASTERER........................$ 30.63            14.07‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐ PLUM0098‐001 06/01/2016

                                  Rates          Fringes

Page 136: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

PLUMBER, Excludes HVAC Pipe   and Unit Installation............$ 38.87            27.23‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐ PLUM0636‐003 06/06/2016

                                  Rates          Fringes

PIPEFITTER, Includes HVAC   Pipe and Unit Installation.......$ 39.91            27.15‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐ ROOF0149‐001 06/01/2014

                                  Rates          Fringes

ROOFER...........................$ 29.10            20.83‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐ SFMI0704‐001 08/01/2016

                                  Rates          Fringes

SPRINKLER FITTER (Fire   Sprinklers)......................$ 43.15            23.76‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐ SHEE0080‐004 07/01/2015

                                  Rates          Fringes

SHEET METAL WORKER (Including   HVAC Duct Installation;   Excluding HVAC System   Installation)....................$ 37.24            26.56‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐ TEAM0247‐001 06/01/2015

                                  Rates          Fringes

TRUCK DRIVER       GROUP 1      Flatbed; Pickup; Dump &       Tandem.....................$ 25.69           0.60+a     GROUP 2      Semi.......................$ 25.84           0.60+a     GROUP 3      Lowboy.....................$ 25.94           0.60+a

  PAID HOLIDAYS: New Year's Day, Memorial Day, Independence  Day, Labor Day, Thanksgiving Day and Christmas Day.  If any  of the above holidays fall on a Sunday, the following  Monday shall be considered the holiday and, if work is

Page 137: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

  performed, the rate shall be double time.

FOOTNOTE: a. $404.45 per week, plus $59.60 per day.

‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐  SUMI2011‐026 02/01/2011

                                  Rates          Fringes

INSTALLER ‐ OVERHEAD DOOR........$ 27.98             0.00  IRONWORKER, ORNAMENTAL...........$ 18.48             7.93  TRUCK DRIVER:  Tractor Haul   Truck............................$ 13.57             1.18‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐

WELDERS ‐ Receive rate prescribed for craft performingoperation to which welding is incidental.

================================================================ 

Unlisted classifications needed for work not included withinthe scope of the classifications listed may be added afteraward only as provided in the labor standards contract clauses(29CFR 5.5 (a) (1) (ii)).

‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐ 

The body of each wage determination lists the classificationand wage rates that have been found to be prevailing for thecited type(s) of construction in the area covered by the wagedetermination. The classifications are listed in alphabeticalorder of "identifiers" that indicate whether the particularrate is a union rate (current union negotiated rate for local),a survey rate (weighted average rate) or a union average rate(weighted union average rate).

Union Rate Identifiers

A four letter classification abbreviation identifier enclosedin dotted lines beginning with characters other than "SU" or"UAVG" denotes that the union classification and rate wereprevailing for that classification in the survey. Example:PLUM0198‐005 07/01/2014. PLUM is an abbreviation identifier of

Page 138: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

the union which prevailed in the survey for thisclassification, which in this example would be Plumbers. 0198indicates the local union number or district council numberwhere applicable, i.e., Plumbers Local 0198. The next number,005 in the example, is an internal number used in processingthe wage determination. 07/01/2014 is the effective date of themost current negotiated rate, which in this example is July 1,2014.

Union prevailing wage rates are updated to reflect all ratechanges in the collective bargaining agreement (CBA) governingthis classification and rate.

Survey Rate Identifiers

Classifications listed under the "SU" identifier indicate thatno one rate prevailed for this classification in the survey andthe published rate is derived by computing a weighted averagerate based on all the rates reported in the survey for thatclassification.  As this weighted average rate includes allrates reported in the survey, it may include both union andnon‐union rates. Example: SULA2012‐007 5/13/2014. SU indicatesthe rates are survey rates based on a weighted averagecalculation of rates and are not majority rates. LA indicatesthe State of Louisiana. 2012 is the year of survey on whichthese classifications and rates are based. The next number, 007in the example, is an internal number used in producing thewage determination. 5/13/2014 indicates the survey completiondate for the classifications and rates under that identifier.

Survey wage rates are not updated and remain in effect until anew survey is conducted.

Union Average Rate Identifiers

Classification(s) listed under the UAVG identifier indicatethat no single majority rate prevailed for thoseclassifications; however, 100% of the data reported for theclassifications was union data. EXAMPLE: UAVG‐OH‐001008/29/2014. UAVG indicates that the rate is a weighted unionaverage rate. OH indicates the state. The next number, 0010 inthe example, is an internal number used in producing the wagedetermination. 08/29/2014 indicates the survey completion datefor the classifications and rates under that identifier.

A UAVG rate will be updated once a year, usually in January ofeach year, to reflect a weighted average of the currentnegotiated/CBA rate of the union locals from which the rate isbased.

Page 139: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

 

‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐

                   WAGE DETERMINATION APPEALS PROCESS

1.) Has there been an initial decision in the matter? This canbe:

*  an existing published wage determination*  a survey underlying a wage determination*  a Wage and Hour Division letter setting forth a position on   a wage determination matter*  a conformance (additional classification and rate) ruling

On survey related matters, initial contact, including requestsfor summaries of surveys, should be with the Wage and HourRegional Office for the area in which the survey was conductedbecause those Regional Offices have responsibility for theDavis‐Bacon survey program. If the response from this initialcontact is not satisfactory, then the process described in 2.)and 3.) should be followed.

With regard to any other matter not yet ripe for the formalprocess described here, initial contact should be with theBranch of Construction Wage Determinations.  Write to:

            Branch of Construction Wage Determinations            Wage and Hour Division            U.S. Department of Labor            200 Constitution Avenue, N.W.            Washington, DC 20210

2.) If the answer to the question in 1.) is yes, then aninterested party (those affected by the action) can requestreview and reconsideration from the Wage and Hour Administrator(See 29 CFR Part 1.8 and 29 CFR Part 7). Write to:

            Wage and Hour Administrator            U.S. Department of Labor            200 Constitution Avenue, N.W.            Washington, DC 20210

The request should be accompanied by a full statement of theinterested party's position and by any information (wagepayment data, project description, area practice material,etc.) that the requestor considers relevant to the issue.

Page 140: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

3.) If the decision of the Administrator is not favorable, aninterested party may appeal directly to the AdministrativeReview Board (formerly the Wage Appeals Board).  Write to:

            Administrative Review Board            U.S. Department of Labor            200 Constitution Avenue, N.W.            Washington, DC 20210

4.) All decisions by the Administrative Review Board are final.

================================================================

          END OF GENERAL DECISION

Page 141: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

U.S. Department of Labor PAYROLL (For Contractor's Optional Use; See Instructions at www.dol.gov/whd/forms/wh347instr.htm)Wage and Hour Division

Persons are not required to respond to the collection of information unless it displays a currently valid OMB control number.

NAME OF CONTRACTOR OR SUBCONTRACTOR ADDRESS OMB No.: 1235-0008 Expires: 02/28/2018

PAYROLL NO. FOR WEEK ENDING PROJECT AND LOCATION PROJECT OR CONTRACT NO.

(1) (2) (3) (4) DAY AND DATE (5) (6) (7) (9) (8)

DEDUCTIONS

O

O

O

O

O

O

O

O

NAME AND INDIVIDUAL IDENTIFYING NUMBER (e.g., LAST FOUR DIGITS OF SOCIAL SECURITY

NUMBER) OF WORKER NO

. OF

WIT

HH

OLD

iNG

E

XEM

PTI

ON

S

WORK CLASSIFICATION

OT.

OR

ST.

HOURS WORKED EACH DAY TOTAL HOURS

RATE OF PAY

GROSS AMOUNT EARNED FICA

WITH-HOLDING

TAX OTHER TOTAL

DEDUCTIONS

NET WAGES

PAID FOR WEEK

S

S

S

S

S

S

S

S

Rev. Dec. 2008

Rev. Dec. 2008

While completion of Form WH-347 is optional, it is mandatory for covered contractors and subcontractors performing work on Federally financed or assisted construction contracts to respond to the information collection contained in 29 C.F.R. §§ 3.3, 5.5(a). The Copeland Act (40 U.S.C. § 3145) contractors and subcontractors performing work on Federally financed or assisted construction contracts to "furnish weekly a statement with respect to the wages paid each employee during the preceding week." U.S. Department of Labor (DOL) regulations at 29 C.F.R. § 5.5(a)(3)(ii) require contractors to submit weekly a copy of all payrolls to the Federal agency contracting for or financing the construction project, accompanied by a signed "Statement of Compliance" indicating that the payrolls are correct and complete and that each laborer or mechanic has been paid not less than the proper Davis-Bacon prevailing wage rate for the work performed. DOL and federal contracting agencies receiving this information review the information to determine that employees have received legally required wages and fringe benefits.

Public Burden Statement

We estimate that is will take an average of 55 minutes to complete this collection, including time for reviewing instructions, searching existing data sources, gathering and maintaining the data needed, and completing and reviewing the collection of information. If you have any comments regarding these estimates or any other aspect of this collection, including suggestions for reducing this burden, send them to the Administrator, Wage and Hour Division, U.S. Department of Labor, Room S3502, 200 Constitution Avenue, N.W. Washington, D.C. 20210

(over)

nthai
nthai
nthai
nthai
Page 142: CONSTRUCTION OF THE VILLAGE ARTS FACTORY – DORMITORY PHASE 2

Date

I,(Name of Signatory Party) (Title)

do hereby state:

(1) That I pay or supervise the payment of the persons employed by

on the (Contractor or Subcontractor)

; that during the payroll period commencing on the (Building or Work)

day of , , and ending the day of , , all persons employed on said project have been paid the full weekly wages earned, that no rebates have been or will be made either directly or indirectly to or on behalf of said

from the full (Contractor or Subcontractor)

weekly wages earned by any person and that no deductions have been made either directly or indirectly from the full wages earned by any person, other than permissible deductions as defined in Regulations, Part 3 (29 C.F.R. Subtitle A), issued by the Secretary of Labor under the Copeland Act, as amended (48 Stat. 948, 63 Stat. 108, 72 Stat. 967; 76 Stat. 357; 40 U.S.C. § 3145), and described below:

(2) That any payrolls otherwise under this contract required to be submitted for the above period are correct and complete; that the wage rates for laborers or mechanics contained therein are not less than the applicable wage rates contained in any wage determination incorporated into the contract; that the classificationsset forth therein for each laborer or mechanic conform with the work he performed.

(3) That any apprentices employed in the above period are duly registered in a bona fide apprenticeshipprogram registered with a State apprenticeship agency recognized by the Bureau of Apprenticeship andTraining, United States Department of Labor, or if no such recognized agency exists in a State, are registeredwith the Bureau of Apprenticeship and Training, United States Department of Labor.

(4) That: (a) WHERE FRINGE BENEFITS ARE PAID TO APPROVED PLANS, FUNDS, OR PROGRAMS

− in addition to the basic hourly wage rates paid to each laborer or mechanic listed in the above referenced payroll, payments of fringe benefits as listed in the contract have been or will be made to appropriate programs for the benefit of such employees, except as noted in section 4(c) below.

(b) WHERE FRINGE BENEFITS ARE PAID IN CASH

− Each laborer or mechanic listed in the above referenced payroll has been paid, as indicated on the payroll, an amount not less than the sum of the applicable basic hourly wage rate plus the amount of the required fringe benefits as listed in the contract, except as noted in section 4(c) below.

(c) EXCEPTIONS

REMARKS:

EXCEPTION (CRAFT)

EXPLANATION

NAME AND TITLE SIGNATURE

THE WILLFUL FALSIFICATION OF ANY OF THE ABOVE STATEMENTS MAY SUBJECT THE CONTRACTOR OR SUBCONTRACTOR TO CIVIL OR CRIMINAL PROSECUTION. SEE SECTION 1001 OF TITLE 18 AND SECTION 231 OF TITLE 31 OF THE UNITED STATES CODE.

nthai
nthai
nthai
nthai
nthai
nthai
nthai