Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON: Friday, March 1, 2019 Inspector, Isaac McPhee 1411 Strong Foundations Home Inspection REVISED

Upload: others

Post on 30-Jun-2020

14 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Confidential Inspection Report

LOCATED AT:1110 S L St

Tacoma, Washington 98405

PREPARED EXCLUSIVELY FOR:Faira.com

INSPECTED ON:Friday, March 1, 2019

Inspector, Isaac McPhee 1411Strong Foundations Home Inspection

REVISED

Page 2: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 2 of 78Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

Executive Summary

This is a summary review of the inspectors' findings during this inspection. However, it does not contain every detailed observation. This is provided as an additional service to our client, and is presented in the form of a listing of the items which, in the opinion of your inspector, merit further attention, investigation, or improvement. Some of these conditions are of such a nature as to require repair or modification by a skilled craftsman, technician, or specialist. Others can be easily handled by a homeowner such as yourself.

Often, following the inspector's advice will result in improved performance and/or extended life of the component(s) in question. In listing these items, your inspector is not offering any opinion as to who, among the parties to this transaction, should take responsibility for addressing any of these concerns. As with most of the facets of your transaction, we recommend consultation with your Real Estate Professional for further advice with regards to the following items:

NOTESINTRODUCTORY NOTES

1: Sections of this building may have been added to or remodeled since original construction. We make not attempt to determine the presence of permitting or code violations regarding recent improvements. We recommend consultation with the owner to determine if all necessary permits were obtained, inspections performed and final signatures obtained.

2: The home was occupied at the time of the inspection, with personal possessions in every room of the home. The presence of personal possessions limited the inspection. Access was denied to a number of wall and floor surfaces, electrical outlets, heat registers, and other items. We recommend a full walkthrough of the home after all items have been removed in order to provide a more thorough evaluation.

EXTERIOR PLUMBINGEXTERIOR/SITE/GROUND

3: One or more of the hose bib handles is damaged/missing. We recommend replacement for full usage of this feature.

OUTDOOR RECEPTACLESEXTERIOR/SITE/GROUND

4: There are ungrounded three prong receptacles on the exterior. We recommend they be properly grounded or restored to their original two prong configuration. A much higher margin of safety would be achieved by upgrading with GFRI receptacles.

DOWNSPOUTSEXTERIOR/SITE/GROUND

5: The downspout at the front of the home does not fully extend into the subsurface drainage system. This could lead to rainwater accumulating near the foundation. Recommend extending the downspout fully into the drain.

WINDOWSKITCHEN

6: One or more of the windows do not operate properly because their counterweight spring mechanisms are damaged. We recommend these windows be repaired. We recommend great care when unlatching any windows with broken springs on the top sash.

Page 3: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 3 of 78Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

VENTILATIONMAIN FLOOR HALF BATH BATHROOM

7: There is no vent fan installed in the bathroom. Because there is an operable window in this bathroom, a fan is not required. Nevertheless, for maximum ventilation, we recommend a fan be installed.

SMOKE DETECTORMAIN FLOOR FRONT BEDROOM

8: There is no smoke detector in this area, as required. We recommend one be installed.

WINDOWSMAIN FLOOR LIVING ROOM ADDITIONAL ROOMS

9: One or more of the windows do not operate properly because their counterweight spring mechanisms are damaged. We recommend these windows be repaired. We recommend great care when unlatching any windows with broken springs on the top sash.

WINDOWSMAIN FLOOR FRONT ENTRY/BONUS ROOM ADDITIONAL ROOMS

10: One or more of the windows do not operate properly because their counterweight spring mechanisms are damaged. We recommend these windows be repaired. We recommend great care when unlatching any windows with broken springs on the top sash.

WINDOWS: OVERALLINTERIOR

11: A number of windows are not serviceable because their lift mechanisms are damaged. We recommend these windows be repaired and their functional use restored.

DETECTORS: OVERALLINTERIOR

12: The latest standards require smoke detectors in all bedrooms at time of construction and when any significant work is done on the residence. Whether or not installation is required prior to sale of this building, upgrading should be considered.

ACCESSBASEMENT/CRAWLSPACE

13: Portions of the home have a crawlspace area; the crawlspace access hatch was inaccessible due to personal storage items. We recommend further review of this area when access is made available.

BASE FOUNDATIONBASEMENT/CRAWLSPACE

14: There is a condition known as 'efflorescence' on portions of the foundation walls. This whitish, fuzzy material is a 'salt' deposit left when moisture in the foundation evaporates on the inside of the foundation. This indicates an occasional surplus of moisture on the outside of the foundation. Steps could be taken to improve the exterior drainage but no other action is indicated at this time.

FLOOR JOINTSBASEMENT/CRAWLSPACE

15: There is excessive notching in the floor framing below the half bathroom. This has weakened the framing in this area and we recommend repair or modification to conform to accepted standards. Further information can be obtained from a licensed contractor or structural engineer.

Page 4: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 4 of 78Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

SUMP PUMPBASEMENT/CRAWLSPACE

16: The sump pump discharges into the sewer line, which is a configuration that is typically not allowed. Further information may be obtained from the local building department. We recommend the sump water be properly discharged.

DRAIN LINESBASEMENT/CRAWLSPACE

17: The drain piping for the laundry sink in the basement drains directly into the sump pit. This is typically not an allowed configuration and should be upgraded per present building standards. Further information may be obtained from the local building department or from a licensed plumber.

OTHER RECEPTACLESBASEMENT/CRAWLSPACE

18: There is no GFCI (ground fault circuit interrupter) protection for this area. For an increased margin of safety, we recommend the installation of a GFCI receptacle.

19: There is a damaged receptacle cover. We recommend it be replaced during the course of normal maintenance.

SWITCHESBASEMENT/CRAWLSPACE

20: The cover plate for a switch in the stairwell is missing. Replacement is recommended.

MAIN SUPPLYPLUMBING

21: Portions of the main water supply piping were dripping with condensation. This condition can be caused by a lack of pipe insulation. We recommend drying and insulating the water piping.

INTERIOR SUPPLYPLUMBING

22: Minor leakage was observed at one or more pipe fittings in the plumbing system. We recommend a licensed plumber repair all existing leaks and continue to monitor for any signs of additional leaking going forward.

DRAIN LINESPLUMBING

23: Based on the age of the home, we recommend a full camera review of the main line and waste piping system.

GENERAL COMMENTPLUMBING

24: The home's main piping and supply piping consist either wholly are partly of older galvanized steel piping. Other than the typical rust/corrosion at some pipe joints, no specific issues were observed during the inspection related to the older piping; however, due to mineral deposit buildup and gradual reduction of flow, replacement of all remaining galvanized steel supply lines may eventually become necessary as a part of ongoing property maintenance and upgrading. For further evaluation and quotes for replacement, recommend contacting a licensed plumber.

Page 5: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 5 of 78Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

MAIN DISCONNECTELECTRICAL SYSTEM

25: The service equipment does not include a main shutoff and more than six(6) disconnects are present. A main shutoff is required by present standards. As an upgrade, we recommend installation of a main shutoff for maximum safety.

GFI PROTECTIONELECTRICAL SYSTEM

26: Some GFCI devices are installed in this home. We recommend adding these devices at all locations currently requiring this protection. This includes receptacles near sink basins, in bathrooms, garages, crawl spaces, and the exterior. In addition, we recommend upgrading all older devices (pre-2007) with newer devices for safety.

FLOOR INSULATIONINSULATION/ENERGY

27: There is no insulation beneath the visible portions of the floors, which is a common finding in older homes. While optional, upgrading would reduce cold air infiltration and make the home more comfortable.

COMMENTSCONCLUSION

28: Note: Structures built prior to the mid 1980s may contain lead and/or asbestos. Lead is commonly found in paint and in some plumbing components. The EPA does not recognize newer coats of paint as encapsulating older coats of lead-based paint. Asbestos is commonly found in various building materials such as insulation, siding, and/or floor and ceiling tiles. Laws were passed in 1978 to prohibit usage of lead and asbestos, but stocks of materials containing these substances remained in use for a number of years thereafter. Both lead and asbestos are known health hazards.

Evaluating for the presence of lead and/or asbestos is beyond the scope of this inspection. Any mention of these materials in this report is made as a courtesy only, and meant to refer the client to a specialist. Consult with specialists as necessary, such as industrial hygienists, professional labs, and/or abatement specialists for this type of evaluation.

The home inspector considers the age of the home while inspecting. It is common to have areas that no longer comply with current code. This is not a new home and this home cannot be expected to meet current code standards. While this inspection makes every effort to point out safety issues, it does not inspect for code. It is common that homes of any age will have had repairs performed and some repairs may not be in a workmanlike manner. Some areas may appear less than standard. This inspection looks for items that are not functioning as intended. It does not grade the repair. It is common to see old plumbing or mixed materials. Sometimes water signs in crawlspaces or basements could be years old or from a problem that no longer exists. Or, it may still need further attention and repair. Determining this can be difficult on an older home. Sometimes in older homes there are signs of damage to wood from wood eating organisms. Having this is typical and fairly common. If the home inspection reveals signs of damage you should have a pest control company inspect further for activity and possibly hidden damage.

Page 6: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 6 of 78Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

Friday, March 1, 2019Faira.com

1110 S L StTacoma, Washington 98405

Dear Faira.com,

We have enclosed the report for the property inspection we conducted for you on Friday, March 1, 2019 at:

1110 S L StTacoma, Washington 98405

Our report is designed to be clear, easy to understand, and helpful. Please take the time to review it carefully. If there is anything you would like us to explain, or if there is other information you would like, please feel free to call us. We would be happy to answer any questions you may have.

Throughout the report, you'll find special symbols at the front of certain comments. Below are the symbols and their meanings:

= Issue that should be addressed over the course of repairs/maintenance, but not time sensitive.

= Upgrade recommended, but not required

= Dangerous or potentially dangerous or hazardous situation that should be corrected as soon as possible.

= Item not operating at the time of the inspection, or unable to be inspected for another reason.

= Item that warrants continued monitoring or further evaluation by a licensed professional. Though issues may not necessarily exist at present or are not readily visible, ongoing monitoring or evaluation are recommended.

We thank you for the opportunity to be of service to you.

Sincerely,

Inspector, Isaac McPheeStrong Foundations Home Inspection

Page 7: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 7 of 78Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

Page 8: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

Table of Contents

Executive Summary.......................................................................................................................................2

Introduction....................................................................................................................................................9

Introductory Notes.........................................................................................................................................9

Exterior/Site/Ground....................................................................................................................................10

Roofing........................................................................................................................................................15

Kitchen.........................................................................................................................................................18

Bathroom.....................................................................................................................................................22

Laundry Area...............................................................................................................................................27

Bedroom......................................................................................................................................................28

Additional Rooms........................................................................................................................................31

Interior.........................................................................................................................................................33

Attic..............................................................................................................................................................34

Basement/Crawlspace.................................................................................................................................35

Plumbing......................................................................................................................................................40

Water Heater...............................................................................................................................................45

Heat.............................................................................................................................................................48

Electrical System.........................................................................................................................................49

Insulation/Energy.........................................................................................................................................53

Locations of Emergency Controls................................................................................................................54

Environmental Concerns.............................................................................................................................56

Conclusion...................................................................................................................................................57

Addenda......................................................................................................................................................58

Page 9: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 9 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

Introduction

We have inspected the major structural components and mechanical systems for signs of significant non- performance, excessive or unusual wear and general state of repair. The following report is an overview of the conditions observed.

In the report, there may be specific references to areas and items that were inaccessible. We can make no representations regarding conditions that may be present but were concealed or inaccessible for review. With access and an opportunity for inspection, reportable conditions may be discovered. Inspection of the inaccessible areas will be performed upon arrangement and at additional cost after access is provided.

We do not review plans, permits, recall lists, and/or government or local municipality documents. Information regarding recalled appliances, fixtures and any other items in this property can be found on the Consumer Product Safety website. These items may be present but are not reviewed.

Our recommendations are not intended as criticisms of the building, but as professional opinions regarding conditions present. As a courtesy, the inspector may list items that they feel have priority in the Executive Summary portion of the report. Although the items listed in this section may be of higher priority in the opinion of the inspector, it is ultimately the client's responsibility to review the entire report. If the client has questions regarding any of the items listed, please contact the inspector for further consultation.

Lower priority conditions contained in the body of the report that are neglected may become higher priority conditions. Do not equate low cost with low priority. Cost should not be the primary motivation for performing repairs. All repair and upgrade recommendations are important and need attention.

This report is a "snapshot" of the property on the date of the inspection. The structure and all related components will continue to deteriorate/wear out with time and may not be in the same condition at the close of escrow.

Anywhere in the report that the inspector recommends further review, it is strongly recommended that this be done PRIOR TO THE CLOSE OF ESCROW. This report is not intended for use by anyone other than the client named herein. No other persons should rely upon the information in this report. Client agrees to indemnify, defend and hold inspector harmless from any third party claims arising out of client's unauthorized distribution of the inspection report.

By accepting this inspection report, you acknowledge that you have reviewed and are in agreement with all of the terms contained in the standard contract provided by the inspector who prepared this report.

Introductory Notes

ORIENTATIONFor purposes of identification and reporting, the front of this building faces north.

For purposes of identification and reporting, the front of the building is the side containing the primary access.

NOTESThe house was estimated to be approximately 70+ years old, with more recent renovations.

Page 10: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 10 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

The weather was sunny at the time of our inspection.

Over the course of this inspection the temperature was estimated to be between 30 and 40 degrees.

We make no representations as to the extent or presence of code violations, nor do we warrant the legal use of this building. This information would have to be obtained from the local building and/or zoning department.

A driveway and/or street is shared with other properties. To determine if maintenance-sharing or liability agreements are in effect regarding the driveway or street, consult the owner of the subject property, neighboring owners or public records.

There may be information pertinent to this property which is a matter of public record. A search of public records is not within the scope of this inspection. We recommend the client or their representative review all appropriate public records.

Sections of this building may have been added to or remodeled since original construction. We make not attempt to determine the presence of permitting or code violations regarding recent improvements. We recommend consultation with the owner to determine if all necessary permits were obtained, inspections performed and final signatures obtained.

The scope of this inspection is limited to reasonably accessible areas. We make no attempt to move furnishings, stored personal property, and/or vegetation. Although no problems are anticipated, removal of these items may reveal reportable items.

Your inspector may choose to include photos in your inspection report. There are times when only a picture can fully explain the condition or if the client is unable to attend the inspection. Photo inclusion is at the discretion of the inspector and in no way is meant to emphasize or highlight the only conditions that were seen. We always recommend full review of the entire inspection report.

The home was occupied at the time of the inspection, with personal possessions in every room of the home. The presence of personal possessions limited the inspection. Access was denied to a number of wall and floor surfaces, electrical outlets, heat registers, and other items. We recommend a full walkthrough of the home after all items have been removed in order to provide a more thorough evaluation.

Exterior/Site/Ground

BASIC INFORMATIONGeneral lot topography: Flat lot

Page 11: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 11 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

Walkways: Concrete

Patio: Brick

Primary exterior wall covering: Brick

Primary exterior window material: Vinyl/plastic or vinyl clad

LIMITATIONSThis is a townhome pud and/or zero lot line home. Due to easements and/or lot configuration, some areas may be inaccessible.

FOUNDATIONThe foundation and other visible elements of the support structure have performed well and are in good condition for the age of the structure.

Page 12: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 12 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

EXTERIOR PLUMBINGTesting of the irrigation system and/or automatic timer is beyond the scope of this inspection.

One or more of the hose bib handles is damaged/missing. We recommend replacement for full usage of this feature.

OUTDOOR RECEPTACLES

There are ungrounded three prong receptacles on the exterior. We recommend they be properly grounded or restored to their original two prong configuration. A much higher margin of safety would be achieved by upgrading with GFRI receptacles.

OUTDOOR LIGHTSA representative number of exterior light fixtures were tested and found to be in working order.

MASONRY WALLSThe masonry walls appear to be properly installed and in good condition.

The masonry walls are only a veneer over the basic wood frame construction. The masonry is not a structural element of the house. Minor cracks are fairly typical and not considered a structural deficiency.

The method or condition of attachment between the wood frame and the masonry veneer is not visible and cannot be determined.

Page 13: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 13 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

DOORSThe exterior doors appear to be properly installed and in serviceable condition.

GRADINGThe grading of the lot appears to properly and adequately drain excess surface water and roof runoff away from the structure.

DOWNSPOUTS

The downspout at the front of the home does not fully extend into the subsurface drainage system. This could lead to rainwater accumulating near the foundation. Recommend extending the downspout fully into the drain.

PUBLIC WORKSThe owner may have rights and responsibilities concerning the public improvements associated with this property. We suggest inquiries of the local public works department, particularly regarding liabilities for future maintenance costs.

Page 14: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 14 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

The public sidewalks appear to be properly installed and are in serviceable condition.

WALKWAYSThe walkways appear to be properly installed and are in serviceable condition.

PATIO SURFACEThe patio appears to be installed in a workmanlike manner and is in good condition.

FENCINGThe fences appear to be properly installed and in serviceable condition.

GATESThe gate was operating. Routine maintenance will keep it functional and maximize its service life.

VEGETATIONWe recommend the vegetation on the property be maintained to prevent over growth and encroachment onto the structure.

TRIMThe exterior trim appears to be properly installed and is in good condition.

Page 15: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 15 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

GENERAL COMMENTThe exterior features of the building generally appear to be properly installed and in serviceable condition. Exceptions are discussed above and elsewhere in this report. Regular maintenance will prolong the service life of the 'weather shell'.

Roofing

A roof system consists of the surface materials, connections, penetrations and drainage (gutters and downspouts). We visually review these components for damage and deterioration and do not perform any destructive testing. If we find conditions suggesting damage, improper application, or limited remaining service life, these will be noted. We may also offer opinions concerning repair and replacement. Opinions stated herein concerning the roof are based on a limited visual inspection. These do not constitute a warranty that the roof is, or will remain, free of leaks.

Page 16: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 16 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

Built-up Roof System

BASIC INFORMATIONLocation: Covers whole building

Roof slope: Flat or very minimal pitchMaterial: TPO (PVC) MembraneLayers: Unknown, would require destructive testingAge: Approximately 1+ years oldConnections and penetrations: Sealed with metal and adhesive adhered membrane material

Roof drainage system: Internal roof drains

Page 17: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 17 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

SURFACE (BUILT-UP)The roofing surface appears to have been properly installed and is in good condition.

FLASHINGS: OVERALLThe accessible connection and penetration flashings appear to be properly installed and in serviceable condition. All of the connections and penetrations should be periodically examined for signs of leakage and repairs performed if necessary.

PLUMBING VENTSPlumbing vents at the roof appear properly installed and in satisfactory condition.

GENERAL COMMENTThis is a newer roof, and with routine maintenance should remain watertight for a number of years.

Page 18: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 18 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

Kitchen

The kitchen is visually inspected for proper function of components, active leakage, excessive or unusual wear, and general state of repair. We inspect built-in appliances to the extent possible using normal operating controls. Freestanding stoves are operated, but refrigerators, small appliances, portable dishwashers, and microwave ovens are not tested.

BASIC INFORMATIONEnergy: Electric appliances onlyVentilation: Exhaust ducted to the exteriorRefrigerators, wine coolers, and other cooling appliances are beyond the scope of this inspection

DRAIN TRAPSThe drain trap and associated piping are PVC plastic.

Page 19: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 19 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

SINKThe sink is porcelain.

RECEPTACLESThe receptacles appear to be properly installed and were operational.

GFCI (ground fault circuit interrupter) protection has been installed providing an increased margin of safety. We recommend testing the device on a monthly basis.

LIGHTSThe overhead lights were tested and were operating properly at the time of the inspection.

FLOORThe wood or laminate/vinyl flooring is in serviceable condition. Kitchen floors receive the most concentrated wear of any area in the house, especially at the sink and stove. We recommend these areas be coated every two to three years as preventive maintenance.

Page 20: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 20 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

COUNTERTOPSThe countertop is granite or other hard surface, such as quartz.

WINDOWS

One or more of the windows do not operate properly because their counterweight spring mechanisms are damaged. We recommend these windows be repaired. We recommend great care when unlatching any windows with broken springs on the top sash.

Page 21: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 21 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

VENTILATIONKitchen ventilation is provided by a range hood over the burners, venting to the exterior. The fan appears to be properly installed and in serviceable condition.

STOVEThe stove was turned on with the normal operating controls and found to be in satisfactory working condition.

OVENThe oven was turned on with the normal operating controls and found to be in satisfactory working condition.

DISPOSALThe disposal was turned on with normal user controls and observed to be in satisfactory working condition.

DISHWASHERThe dishwasher responded to normal user controls and was found in good condition.

GENERAL COMMENTThe finished surfaces, hardware, windows, and doors were found to be generally in good condition at the time of our inspection, with exceptions noted above.

Inspection of this area was limited to the surface coverings. The construction materials and manner of installation were concealed from view and inaccessible.

Page 22: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 22 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

Bathroom

Bathrooms are visually inspected for proper function of components, active leakage, excessive or unusual wear and general state of repair. Fixtures are tested using normal operating features and controls. Due to finished surfaces such as drywall/plaster, tile, and flooring, much of the bathroom is considered inaccessible. We do not test or confirm proper application of secondary equipment including but not limited to steam units, spa tubs, heated towel bars, etc.

Main Floor Half Bath Bathroom

BASIC INFORMATIONToilet: Ceramic unit with a porcelain finish

Wash basin: Ceramic unit with a porcelain finish

Page 23: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 23 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

DRAIN TRAPThe drain trap and associated piping are PVC plastic.

TOILETThe toilet was flushed and appeared to be functioning properly.

WATER BASINThe wash basin appears to be properly installed. When operated, it was observed to be fully functional and in serviceable condition.

RECEPTACLESThe receptacle appears to be properly installed and was operational.

GFCI (ground fault circuit interrupter) protection has been installed providing an increased margin of safety. We recommend testing the device on a monthly basis.

LIGHTSThe overhead lights were tested and found to be operational at the time of the inspection.

VENTILATION

There is no vent fan installed in the bathroom. Because there is an operable window in this bathroom, a fan is not required. Nevertheless, for maximum ventilation, we recommend a fan be installed.

Page 24: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 24 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

GENERAL COMMENTThe finished surfaces, hardware, windows, and doors were found to be generally in good condition at the time of our inspection. However, this area is in need of routine maintenance as noted above or in other sections of this report.

Inspection of this area was limited to the surface coverings. The construction materials and manner of installation were concealed from view and inaccessible.

Main Floor Master Bathroom

BASIC INFORMATIONToilet: Ceramic unit with a porcelain finish

Page 25: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 25 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

Wash basin: Ceramic unit with a porcelain finish

Shower walls: Painted wood paneling

DRAIN TRAPThe drain trap and associated piping are PVC plastic.

TOILETThe toilet was flushed and appeared to be functioning properly.

WATER BASINThe wash basin appears to be properly installed. When operated, it was observed to be fully functional and in serviceable condition.

Page 26: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 26 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

SHOWERThe shower was operated for the inspection and appeared to be in serviceable condition.

RECEPTACLESThe receptacle appears to be properly installed and was operational.

GFCI (ground fault circuit interrupter) protection has been installed providing an increased margin of safety. We recommend testing the device on a monthly basis.

LIGHTSThe overhead lights were tested and found to be operational at the time of the inspection.

SHOWER WALLSThe shower walls appear to be properly installed and in serviceable condition.

BATHROOM FLOORThe finish floor in this bathroom is tile.

The floor appears to be properly installed and is in serviceable condition.

VENTILATIONVentilation in this bathroom is provided by a ceiling fan. This fan was operated and was found to be working satisfactorily.

Page 27: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 27 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

GENERAL COMMENTThe finished surfaces, hardware, windows, and doors were found to be generally in good condition at the time of our inspection. However, this area is in need of routine maintenance as noted above or in other sections of this report.

Inspection of this area was limited to the surface coverings. The construction materials and manner of installation were concealed from view and inaccessible.

Laundry Area

Laundry areas and/or laundry rooms are visually inspected for general state of repair. Due to their hidden nature, we do not review appliances, connections, hookups, or venting.

DRYER VENTThe dryer vent appears properly installed and in serviceable condition.

Page 28: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 28 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

WASHER/DRYERThe hookups for the washer and dryer are properly installed and in serviceable condition. The appliances themselves were not tested.

GENERAL COMMENTThe finished surfaces, hardware, windows, and doors were found to be generally in good condition at the time of our inspection.

Inspection of this area was limited to the surface coverings. The construction materials and manner of installation were concealed from view and inaccessible.

Bedroom

Main Floor Master Bedroom

RECEPTACLESThe receptacles were found to be properly installed and in serviceable condition. The number of receptacles is considered adequate for the size of the room.

LIGHTS / FANThe overhead lights and/or ceiling fan were tested and appeared operational at the time of the inspection.

Page 29: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 29 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

FLOORThe wood or laminate flooring appears properly installed and in good condition.

SMOKE DETECTORThe smoke detector in this area appeared to be properly located and installed.

GENERAL COMMENTThe finished surfaces, hardware, windows, and doors were found to be generally in good condition at the time of our inspection.

Inspection of this area was limited to the surface coverings. The construction materials and manner of installation were concealed from view and inaccessible.

Page 30: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 30 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

Main Floor Front Bedroom

RECEPTACLESThe receptacles were found to be properly installed and in serviceable condition. The number of receptacles is considered adequate for the size of the room.

LIGHTS / FANThe overhead lights and/or ceiling fan were tested and appeared operational at the time of the inspection.

FLOORThe wood or laminate flooring appears properly installed and in good condition.

SMOKE DETECTOR

There is no smoke detector in this area, as required. We recommend one be installed.

GENERAL COMMENTThe finished surfaces, hardware, windows, and doors were found to be generally in good condition at the time of our inspection. However, this area is in need of routine maintenance as noted above or in other sections of this report.

Page 31: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 31 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

Additional Rooms

Main Floor Living Room Additional Rooms

RECEPTACLESThe receptacles were found to be properly installed and in serviceable condition. The number of receptacles is considered adequate for the size of the room.

LIGHTSThe light fixtures in this room were tested and appeared operational at the time of the inspection.

FLOORThe wood or laminate flooring appeared properly installed and in good condition at the time of the inspection.

WINDOWS

One or more of the windows do not operate properly because their counterweight spring mechanisms are damaged. We recommend these windows be repaired. We recommend great care when unlatching any windows with broken springs on the top sash.

Page 32: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 32 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

GENERAL COMMENTThe finished surfaces, hardware, windows, and doors were found to be generally in good condition at the time of our inspection. However, this area is in need of routine maintenance as noted above or in other sections of this report.

Inspection of this area was limited to the surface coverings. The construction materials and manner of installation were concealed from view and inaccessible.

Main Floor Front Entry/Bonus Room Additional Rooms

RECEPTACLESThe receptacles were found to be properly installed and in serviceable condition. The number of receptacles is considered adequate for the size of the room.

FLOORThe wood or laminate flooring appeared properly installed and in good condition at the time of the inspection.

Page 33: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 33 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

WINDOWS

One or more of the windows do not operate properly because their counterweight spring mechanisms are damaged. We recommend these windows be repaired. We recommend great care when unlatching any windows with broken springs on the top sash.

GENERAL COMMENTThe finished surfaces, hardware, windows, and doors were found to be generally in good condition at the time of our inspection. However, this area is in need of routine maintenance as noted above or in other sections of this report.

Inspection of this area was limited to the surface coverings. The construction materials and manner of installation were concealed from view and inaccessible.

Interior

Our review of the interior includes inspection of walls, ceilings, floors, doors, windows, steps, stairways, balconies and railings. These features are visually examined for proper function, excessive wear and general state of repair. Some of these components may not be visible/accessible because of furnishings and/or storage. In such cases these items are not inspected.

BASIC INFORMATIONNumber of bedrooms: TwoNumber of bathrooms: One and one-halfWindow material: Vinyl

Page 34: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 34 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

Window type: Combination of sliding, fixed, and awning windowsWindow glazing: Double panePrimary finished ceiling material: DrywallPrimary finished floor material: Wood and/or laminatePrimary finished wall material: Drywall

SURFACES: OVERALLThe interior wall, floor, and ceiling surfaces were properly installed and generally in good condition, taking into consideration normal wear and tear.

WALLS & CEILINGSThe interior wall and ceiling blemishes are cosmetic and can be repaired in the course of routine maintenance.

FLOORS: OVERALLThe floors have a good appearance and are in serviceable condition.

DOORS: OVERALLThe interior doors appear to be properly installed and in good condition.

WINDOWS: OVERALL

A number of windows are not serviceable because their lift mechanisms are damaged. We recommend these windows be repaired and their functional use restored.

DETECTORS: OVERALL

The latest standards require smoke detectors in all bedrooms at time of construction and when any significant work is done on the residence. Whether or not installation is required prior to sale of this building, upgrading should be considered.

Carbon monoxide detectors were observed in the home and were operating properly when tested.

GENERAL COMMENTThe interior surfaces, hardware, fixtures, doors and windows appear to be properly installed and generally in serviceable condition, with exceptions noted above.

We make no attempt to list all cosmetic flaws and suggest that most of these deficiencies will be addressed by normal maintenance and upgrading.

Attic

The attic contains the roof framing and serves as a raceway for components of the mechanical systems. There are often heating ducts, electrical wiring and appliance vents in the attic. We visually examine the attic components for proper function, excessive or unusual wear, general state of repair, leakage, venting and misguided improvements. Where walking in an unfinished attic can result in damage to the ceiling, inspection is from the access opening only.

ACCESS/ENTRYThe low slope roof design of this building does not feature an accessible attic or roof space. Therefore, the area containing the roof structure and related components could not be inspected.

Page 35: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 35 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

Basement/Crawlspace

The basement is where much of the building's structural elements and many of its mechanical systems are located. These include foundation, structural framing, electrical, plumbing and heating. Each accessible component and system is examined for proper function, excessive, or unusual wear and general state of repair. It is not unusual to find occasional moisture in basements. Substantial and/or frequent water accumulation can adversely affect the building foundation and support system and would indicate the need for further evaluation by a specialist. Although observed in the basement, some items will be reported under the individual systems to which the belong.

BASIC INFORMATIONFoundation type: Raised perimeterFoundation material: Poured concrete

Mudsill: Inaccessible, unknown if bolted, nailed or strappedFloor system: Wood joists supported by walls

ACCESSThe basement is accessible from an interior stair.

Portions of the home have a crawlspace area; the crawlspace access hatch was inaccessible due to personal storage items. We recommend further review of this area when access is made available.

Page 36: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 36 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

BASE FOUNDATIONThe foundation and other visible elements of the support structure have performed well and are generally in good condition for the age of the structure. We suggest attention to the items noted below.

There is a condition known as 'efflorescence' on portions of the foundation walls. This whitish, fuzzy material is a 'salt' deposit left when moisture in the foundation evaporates on the inside of the foundation. This indicates an occasional surplus of moisture on the outside of the foundation. Steps could be taken to improve the exterior drainage but no other action is indicated at this time.

WALLSThe basement walls have performed well and are in good condition for the age of the structure.

FLOORThe basement floor is a concrete slab. Minor cracks are visible. These cracks are considered cosmetic in nature and are not structurally significant. No action is indicated.

BELOW GRADEThe interior flooring is below the exterior grade level. Floor and wall surfaces below grade are susceptible to moisture entry if they are not completely waterproofed and drained.

There were stains present, but no actual moisture was observed during this inspection. The owner should be consulted to determine the extent and frequency of past moisture entry and to determine if corrective measures have been completed.

Page 37: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 37 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

FLOOR JOINTS

There is excessive notching in the floor framing below the half bathroom. This has weakened the framing in this area and we recommend repair or modification to conform to accepted standards. Further information can be obtained from a licensed contractor or structural engineer.

SUMP PUMP

The sump pump discharges into the sewer line, which is a configuration that is typically not allowed. Further information may be obtained from the local building department. We recommend the sump water be properly discharged.

Page 38: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 38 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

The sump pump in the basement was tested using the float valve and appeared to be operating normally at the time of the inspection.

DRAIN LINES

The drain piping for the laundry sink in the basement drains directly into the sump pit. This is typically not an allowed configuration and should be upgraded per present building standards. Further information may be obtained from the local building department or from a licensed plumber.

Page 39: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 39 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

OTHER RECEPTACLES

There is no GFCI (ground fault circuit interrupter) protection for this area. For an increased margin of safety, we recommend the installation of a GFCI receptacle.

There is a damaged receptacle cover. We recommend it be replaced during the course of normal maintenance.

SWITCHES

The cover plate for a switch in the stairwell is missing. Replacement is recommended.

Page 40: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 40 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

GENERAL COMMENTThe structural elements appear to be performing as would be expected for a building of this age and type, with exceptions noted above.

Plumbing

A plumbing system consists of the domestic water supply lines, drain, waste and vent lines and gas lines. Inspection of the plumbing system is limited to visible faucets, fixtures, valves, drains, traps, exposed pipes and fittings. These items are examined for proper function, excessive or unusual wear, leakage, and general state of repair. The hidden nature of piping prevents inspection of every pipe and joint. A sewer lateral test, necessary to determine the condition of the underground sewer lines, is beyond the scope of this inspection If desired, a qualified individual could be retained for such a test. Our review of the plumbing system does not include landscape watering, fire suppression systems, private water supply/waste disposal systems, or recalled plumbing supplies. Review of these systems requires a qualified and licensed specialist.

Page 41: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 41 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

BASIC INFORMATIONDomestic water source: Public supply

Landscape water source: Public supplyMain water line: Galvanized steel

Supply piping: Galvanized steel and plastic

Waste disposal: Municipal

Page 42: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 42 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

Waste piping: Plastic and Cast Iron

Water pressure: Mid-range of normal water pressure

Other installed systems: Landscape watering, not inspected

WATER SHUTOFF LOCATIONThe domestic water supply main shut-off valve is on the front wall in the basement.

WATER SHUTOFF COMMENTSThe main shut-off valve was located but testing the operation of this valve is not within the scope of our inspection. Operation of the valve from time to time will keep it functional and maximize its useful life.

Page 43: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 43 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

MAIN SUPPLY

Portions of the main water supply piping were dripping with condensation. This condition can be caused by a lack of pipe insulation. We recommend drying and insulating the water piping.

INTERIOR SUPPLY

Minor leakage was observed at one or more pipe fittings in the plumbing system. We recommend a licensed plumber repair all existing leaks and continue to monitor for any signs of additional leaking going forward.

WATER PRESSUREThe system water pressure, as measured at the exterior hose bibs, is within the range of normal.

DRAIN LINESThe visible drain piping appears to be generally properly installed and in serviceable condition. We recommend a full camera review of the entire waste system.

Based on the age of the home, we recommend a full camera review of the main line and waste piping system.

Page 44: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 44 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

SEWER CLEANOUTThe sewer cleanout is located in the basement.

VENT LINESThe vent piping for the waste system appears to be properly installed and in good condition.

GAS PIPINGThe gas piping appears to be properly installed and in serviceable condition. We detected no evidence of leakage at any of the exposed gas piping. Pressure testing may reveal leaks, but this procedure is beyond the scope of our inspection.

GAS METER LOCATIONThe gas meter is outside on the front of the building. The main gas supply shutoff valve is located on the riser pipe between the ground and the meter. This valve should be turned 90 degrees (either way) in order to shut off the gas.

GENERAL COMMENTThe plumbing system appears to be in good condition, with the exceptions noted above.

A representative number of fixtures were operated and we observed reasonable flow when other fixtures were operated simultaneously.

A representative number of drains were tested and each emptied in a reasonable amount of time and did not overflow when other fixtures were drained simultaneously.

Page 45: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 45 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

The home's main piping and supply piping consist either wholly are partly of older galvanized steel piping. Other than the typical rust/corrosion at some pipe joints, no specific issues were observed during the inspection related to the older piping; however, due to mineral deposit buildup and gradual reduction of flow, replacement of all remaining galvanized steel supply lines may eventually become necessary as a part of ongoing property maintenance and upgrading. For further evaluation and quotes for replacement, recommend contacting a licensed plumber.

Water Heater

Our review of water heaters includes the tank, water and gas connections, electrical connections, venting and safety valves. These items are examined for proper function, excessive or unusual wear, leakage and general state of repair. We do not fully review tankless/on-demand systems and suggest you consult a specialist. The hidden nature of piping and venting prevents inspection of every pipe, joint, vent and connection.

BASIC INFORMATIONLocation: In the basement

Energy source: Natural gasAge: Estimated to be 2+ years oldUnit type: Tankless coilWater heater temperature settings should be maintained in the mid-range to avoid injury from scalding

Page 46: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 46 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

T/P RELEASE VALVEThe water heater is equipped with a temperature and pressure relief valve. This device is an important safety device and should not be altered or tampered with. We observed no adverse conditions.

EXPANSION TANKThe water heater is equipped with an expansion tank that appears properly installed and in serviceable condition. However, review of this equipment is beyond the scope of this inspection.

GAS SUPPLYThe gas piping for the appliance includes a local 90 degree shut-off valve for use in an emergency or in case of repair. The valve was not tested at the time of inspection, but is of a type usually found to be serviceable.

The gas connector is an approved flexible type in good condition.

Page 47: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 47 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

VENTINGThe water heater vent is properly installed and appears in serviceable condition.

COMBUSTION AIRCombustion air provides the oxygen for fuel burning appliances. Adequate ventilation around all fuel burning appliances is vital for their safe operation. The air can come from inside or outside, providing industry standards are met.

The combustion air supply is adequate.

BURNERSBecause of the configuration of this water heater, which is a fully enclosed high efficiency design, the burner is not accessible for inspection.

WATER CONNECTORSThe cold water inlet and hot water outlet connections appear properly installed and in serviceable condition.

GENERAL COMMENTThis is a newer water heater, was operating and with routine maintenance should be reliable for a number of years.

Page 48: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 48 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

Heat

A heating system consists of the heating equipment, operating and safety controls, venting and the means of distribution. These items are visually examined for proper function, excessive or unusual wear and general state of repair. This is a non-evasive, basic function review only. We do not dismantle, uncover or calculate efficiency of any system. Regular servicing and inspection of heating systems is encouraged.

Hot Water Heat

BASIC INFORMATIONBoiler location: Basement (Water heater used for both potable water and heating water)Energy source: Natural gas

SYSTEM NOTESHot water (or hydronic) heating systems operate by warming water which is pumped through piping to radiators, baseboard heaters, or fan coils. Important elements include the boiler, exhaust venting, controls, and the piping and pumping system.

Hot water heating systems are clean, silent and generally quite efficient. However, response to the controls is much slower than for an air system. Frequent or large changes in control settings are counterproductive.

The most efficient operation of a hot water system can be obtained using an electronic thermostat programmed to turn on one to two hours prior to rising, then off an hour or more prior to retiring. A lower setting while at work is also suggested.

However, during very cold weather, the 'setback' should not exceed 5 degrees or the distribution system may freeze.

Page 49: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 49 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

RELIEF VALVEThe water heater is equipped with a temperature and pressure relief valve. This device is an important safety device and should not be altered or tampered with. We observed no adverse conditions.

WATER/STEAM PIPINGThe heating system piping appears to be properly installed and in serviceable condition.

RADIATORSThe radiators appear to be properly installed and in serviceable condition.

THERMOSTATThe thermostat appears to be properly installed and the unit responded to the user controls.

PRESSURE GAUGEThe pressure gauge appears to be properly installed and in serviceable condition.

GENERAL COMMENTThe heating system responded to normal operating controls. Components appear properly installed and serviceable. Routine maintenance will keep it functional and maximize its service life.

Electrical System

An electrical system consists of the service, distribution, wiring and convenience outlets (switches, lights, and receptacles). Our examination of the electrical system includes the exposed and accessible

Page 50: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 50 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

conductors, branch circuitry, panels, overcurrent protection devices, and a random sampling of convenience outlets. We look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature of the electrical wiring prevents inspection of every length of wire.

BASIC INFORMATIONService entry into building: Overhead service drop

Voltage supplied by utility: 120/240 voltsCapacity (available amperage): 200 amperesSystem grounding source: Driven copper rod

Branch circuit protection: Circuit breakersWiring material: Copper wiring where seenWiring method: Non-metallic sheathed cable or 'romex'

Page 51: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 51 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

ELECTRIC METERThe electric meter is outside on the front of the building.

MAIN SERVICEThe main electrical service panel is in the basement.

MAIN DISCONNECTThere is no single main electrical service disconnect. If all the devices in the main service panel are disconnected, electrical power will be completely shut off.

SERVICE DROPThe service drop appears to be properly installed and in good condition.

MAIN DISCONNECT

The service equipment does not include a main shutoff and more than six(6) disconnects are present. A main shutoff is required by present standards. As an upgrade, we recommend installation of a main shutoff for maximum safety.

Page 52: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 52 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

CB MAIN PANELThe main service panel is in good condition with circuitry installed and fused correctly.

The circuits in the panel are labeled. We did not verify the accuracy of the labeling, but it appears to be typical. When the opportunity arises, we suggest checking the labeling by actually operating the breakers.

SERVICE CAPACITYThe service entrance conductors are the wires between the utilities service drop and the main service disconnect or main service panel.

The service entrance conductors appear to be #4/0 Aluminum providing an ampacity of 200.

Our statement regarding service capacity is based upon the size of the service entrance conductors.

Page 53: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 53 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

The service capacity is normal for a house this size and age, and appears adequate for the present demand and minor additional loads.

SERVICE GROUNDINGThe system and equipment grounding appears to be correct.

BRANCH CIRCUITRYThe accessible branch circuitry was examined and appeared properly installed and in serviceable condition.

CONDUCTOR MATERIALThe accessible branch circuit wiring in this building is copper.

RECEPTACLES: OVERALLBased upon our inspection of a representative number, the receptacles were generally found to be in serviceable condition and operating properly, with exceptions noted elsewhere.

SWITCHES: OVERALLWe checked a representative number of switches and found they were operating and in serviceable condition.

LIGHTS: OVERALLThe light fixtures in this building are generally in serviceable condition.

GFI PROTECTIONGFCI (ground fault circuit interrupter) protection is a modern safety feature designed to prevent shock hazards. GFCI breakers and receptacles function to de-energize a circuit or a portion of a circuit when a hazardous condition exists.

GFCI protection is inexpensive and can provide a substantial increased margin of safety.

Some GFCI devices are installed in this home. We recommend adding these devices at all locations currently requiring this protection. This includes receptacles near sink basins, in bathrooms, garages, crawl spaces, and the exterior. In addition, we recommend upgrading all older devices (pre-2007) with newer devices for safety.

GENERAL COMMENTThe electrical system is generally in good condition, with only a few instances of needed repair or correction observed. See notes above for specific comments.

Insulation/Energy

Insulation, weatherstripping, dampers, double-glazed glass and set-back thermostats are features that help reduce heat loss and/or gain and increase system and appliance efficiency. Our visual inspection includes review to determine if these features are present in representative locations and we may offer suggestions for upgrading. Our review of insulation is based upon uniformly insulated or are insulated to current standards. It is our opinion that all homes could benefit from energy conservation upgrades, and we suggest that you consult professionals.

Page 54: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 54 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

ATTIC INSULATIONThe attic was inaccessible and could not be inspected.

WALL INSULATIONWe were unable to access the wall cavities and/or determine the presence or condition of insulation.

FLOOR INSULATION

There is no insulation beneath the visible portions of the floors, which is a common finding in older homes. While optional, upgrading would reduce cold air infiltration and make the home more comfortable.

GENERAL COMMENTThe areas normally accessible were concealed by finished surfaces and could not be inspected. We are unable to evaluate the presence or degree of insulation and/or energy efficiency.

Locations of Emergency Controls

In an emergency, you may need to know where to shut off the gas, the water and/or the electrical system. We have listed below these controls and their location for your convenience. We urge that you familiarize yourself with their location and operation.

WATER SHUTOFF LOCATIONPLUMBINGThe domestic water supply main shut-off valve is on the front wall in the basement.

Page 55: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 55 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

SEWER CLEANOUTPLUMBINGThe sewer cleanout is located in the basement.

GAS METER LOCATIONPLUMBINGThe gas meter is outside on the front of the building. The main gas supply shutoff valve is located on the riser pipe between the ground and the meter. This valve should be turned 90 degrees (either way) in order to shut off the gas.

Page 56: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 56 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

ELECTRIC METERELECTRICAL SYSTEMThe electric meter is outside on the front of the building.

MAIN SERVICEELECTRICAL SYSTEMThe main electrical service panel is in the basement.

MAIN DISCONNECTELECTRICAL SYSTEMThere is no single main electrical service disconnect. If all the devices in the main service panel are disconnected, electrical power will be completely shut off.

Environmental Concerns

Environmental issues include but are not limited to radon, fungi/mold, asbestos, lead paint, lead contamination, toxic waste, formaldehyde, electromagnetic radiation, buried fuel oil tanks, ground water contamination and soil contamination. We are not trained or licensed to recognize or discuss any of these materials. We may make reference to one of more of these materials in this report when we recognize one of the common forms of these substances. If further study or analysis seems prudent, the advice and services of the appropriate specialists are advised.

Page 57: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

Page 57 of 78

REVISED

Copyright© 2010-2019, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 19-03002

Conclusion

COMMENTSThis structure appears to be of standard quality, in need of miscellaneous repair and upgrading. There is also maintenance in need of attention. Examples of these conditions have been described in this report.

Most of the items that are in need of immediate attention and/or possible major cost items that would require repair in the near future are listed in the report summary. Please be sure to refer to this document for further useful information.

Many homes built prior to 1996 lack modern safety and energy efficient items.

Note: Structures built prior to the mid 1980s may contain lead and/or asbestos. Lead is commonly found in paint and in some plumbing components. The EPA does not recognize newer coats of paint as encapsulating older coats of lead-based paint. Asbestos is commonly found in various building materials such as insulation, siding, and/or floor and ceiling tiles. Laws were passed in 1978 to prohibit usage of lead and asbestos, but stocks of materials containing these substances remained in use for a number of years thereafter. Both lead and asbestos are known health hazards.

Evaluating for the presence of lead and/or asbestos is beyond the scope of this inspection. Any mention of these materials in this report is made as a courtesy only, and meant to refer the client to a specialist. Consult with specialists as necessary, such as industrial hygienists, professional labs, and/or abatement specialists for this type of evaluation.

The home inspector considers the age of the home while inspecting. It is common to have areas that no longer comply with current code. This is not a new home and this home cannot be expected to meet current code standards. While this inspection makes every effort to point out safety issues, it does not inspect for code. It is common that homes of any age will have had repairs performed and some repairs may not be in a workmanlike manner. Some areas may appear less than standard. This inspection looks for items that are not functioning as intended. It does not grade the repair. It is common to see old plumbing or mixed materials. Sometimes water signs in crawlspaces or basements could be years old or from a problem that no longer exists. Or, it may still need further attention and repair. Determining this can be difficult on an older home. Sometimes in older homes there are signs of damage to wood from wood eating organisms. Having this is typical and fairly common. If the home inspection reveals signs of damage you should have a pest control company inspect further for activity and possibly hidden damage.

Page 58: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

©2019 Strong Foundations Home Inspection

ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations to survey the readily accessible, easily visible material components, systems and equipment of the building. The inspection is designed to identify material physical deficiencies in the building’s components, systems and equipment, as they exist at the time of the inspection. The work product resulting from completing an inspection in accordance with this contract is an inspection report. The inspection report incorporates the information obtained during the inspection. The inspection report is for the sole use and benefit of the Client. Client agrees to read the entire inspection report when it is received and shall promptly call the Inspector with any questions or concerns Client may have regarding the inspection report or the inspection. The inspection report shall be considered the final and exclusive findings of the Inspector regarding the inspection of the building. Client shall not rely on any oral statement made by the Inspector prior to issuance of the inspection report. 2. Components and systems operated during the inspection will be identified in the inspection report. The identified components and systems shall be operated with normal user controls and as conditions permit. If a component or system is operated, it may be conducted without the aid of special protective clothing, exploratory probing, removing materials, testing, measuring, preparing, calculations or using special equipment, including meters or devices of any kind. Testing, measuring, or preparing calculations for any system or component to determine adequacy, capacity, or compliance with any standard is outside the scope of this contract. 3. The term “poor” or “major concern” in regard to a component mean the presence of conspicuous patent defects or material deferred maintenance of the building’s material systems, components, or building equipment as observed during the inspection. This definition specifically excludes deficiencies that may be remedied with routine maintenance, miscellaneous minor repairs, and normal operating maintenance, and excludes conditions that generally do not present material physical deficiencies of the building. 4. Inspector is an expert generalist and not acting as an expert in any SPECIFIC craft or

Page 59: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

©2019 Strong Foundations Home Inspection

trade. The inspector may make recommendations for further evaluation by an individual(s) who is an expert or specialist IN ONE OR MORE SPECIFIC BUILDING COMPONENTS OR SYSTEMS. 5. The inspection is not technically exhaustive. The cost obtaining information or the time required to conduct a technically exhaustive inspection and prepare the inspection report could outweigh the usefulness of the information and could be detrimental to the orderly and timely completion of Client’s transaction. 6. No inspection can wholly eliminate the uncertainty regarding the presence of physical deficiencies and the performance of the building’s systems. Preparation of an inspection report in accordance with this contract is intended to reduce, but not eliminate, the uncertainty regarding the potential for component or system failure and to reduce the potential that such component or system may not be initially observed. Client recognizes the inherent subjective nature of the inspector’s opinions as to issues such as workmanship, quality of original installation, and estimating the remaining useful life of any given component or system. The inspector’s opinions generally are formed without detailed knowledge from those specifically familiar with the component or system’s performance. 7. The inspection report will contain a representative indication of the property condition at the time of the inspection and is dependent on the information available to the inspector at that time. 8. It is the Client’s duty and obligation to exercise reasonable care to protect himself or herself regarding the condition of the building, including those facts that are known to or within the diligent attention and observation of the Client. SCOPE AND LIMITATIONS OF THIS INSPECTION This inspection is limited to a visual observation of the exposed and readily accessible areas of the home. The concealed and inaccessible areas are not included. The following locations are considered inaccessible due to limited height and excluded from this inspection unless otherwise stated:

• Crawl space areas less than 18 inches in height

• Attic spaces less than 5 feet in height

• Spaces under outdoor decks less than 5 feet high Observation includes operation of the systems or components by means of the normal user controls. Dismantling of equipment, and destructive testing is not included. Some specific items are also excluded, and these are listed in the following section. If you feel there is a need for evaluation of any of these items, then you will need to arrange for specific inspections.

Page 60: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

©2019 Strong Foundations Home Inspection

Items not Included 1. Recreational, leisure, playground or decorative equipment or appliances including but not limited to pools, hot tubs, saunas, steam baths, landscape lighting, fountains, shrubs, trees, and tennis courts; 2. Cosmetic conditions (wallpapering, painting, carpeting, scratches, scrapes, dents, cracks, stains, soiled or faded surfaces on the structure or equipment, soiled, faded, torn, or dirty floor, wall or window coverings etc.); 3. Noise pollution or air quality in the area; 4. Earthquake hazard, liquefaction, flood plain, soil, slide potential or any other geological conditions or evaluations; 5. Engineering level evaluations on any topic; 6. Existence or non-existence of solder or lead in water pipes, asbestos, hazardous waste, radon, urea formaldehyde urethane, lead paint or any other environmental, flammable or toxic contaminants or the existence of water or airborne diseases or illnesses and all other similar or potentially harmful substances (although the inspector may note the possible existence of asbestos in ceiling texture and furnace duct tape); 7. Zoning or municipal code (e.g. building, fire, housing (existing buildings), mechanical, electrical, plumbing, etc. code) restrictions or other legal requirements of any kind; 8. Any repairs which relate to some standard of interior decorating; 9. Cracked heat exchangers or similar devices in furnaces; 10. Any evaluation which requires the calculation of the capacity of any system or item that is expected to be part of the inspection. Examples include but are not limited to the calculation of appropriate wattage or wiring of kitchen appliances, appropriate sizing of flues or chimneys, appropriate ventilation to combustion-based items (e.g. furnaces, water heaters, fireplaces etc.), appropriate sizing, spacing and spanning of joists, beams, columns, girders, trusses, rafters, studs etc., appropriate sizing of plumbing and fuel lines, etc.; 11. Washers and dryers; 12. Circuit breaker operation; 13. Specialty evaluations such as private sewage, wells, solar heating systems, alarms, intercom systems, central vacuum systems, wood and coal stoves, pre-fab and zero clearance fireplaces, space heaters, sprinkler systems, gas logs, gas lights, elevators and common areas unless these have been specifically added to the inspection description above but only to the degree that the inspector is capable of evaluating these items;

Page 61: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

©2019 Strong Foundations Home Inspection

14. Items that are not visible and exposed including but not limited to concealed wiring, plumbing, water leaks, under bathtubs and shower stalls due to faulty pans or otherwise, vent lines, duct work, exterior foundation walls (below grade or covered by shrubs or wall/paneling, stored goods etc.) and footings, underground utilities, and systems and chimney flues; 15. Evaluations involving destructive testing; 16. Evaluation which requires moving personal goods, debris, furniture, equipment, floor covering, insulation or like materials; 17. Design problems and adequacy or operational capacity, quality or suitability; 18. Fireplace drafting; 19. To prevent damages to units, air conditioning when outside temperature below 60 degrees F or if the unit has not been warmed up or on for at least 24 hours prior to inspection; 20. Any evaluation which would involve scraping paint or other wall coverings; 21. Heating system accessories (e.g. humidifiers, electronic air cleaners etc.); 22. Legal description of property such as boundaries, egress/ingress, etc.; 23. Quality of materials; 24. Conformance with plan specifications or manufacturers specifications; 25. Flood conditions or plains; 26. Any other characteristics or items which are generally not included in a building inspection report on a regular basis. Services for inspecting or evaluating the excluded items listed above may be available from the Inspector for an additional fee or from specialists qualified to inspect or evaluate a particular category or item. Disclaimer In some cases we may recommend your consulting a specialist such as a structural engineer or licensed electrician. Hiring a specialist can be a prudent means of providing some protection of your financial investment in this property. WE DO NOT MAKE ANY TYPE OF WARRANTY OR GUARANTEE AS TO THE CONDITION OF THE PROPERTY. SOME THINGS MAY REMAIN HIDDEN OR

Page 62: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

©2019 Strong Foundations Home Inspection

BECOME DEFECTIVE AFTER THE INSPECTION. IT IS NOT POSSIBLE TO DETECT EVERY DEFECT WITHIN A BUILDING DURING THE COURSE OF A GENERAL INSPECTION. THIS REPORT SHOULD BE USED IN CONJUNCTION WITH, AND NOT A REPLACEMENT FOR , A PRE-CLOSING WALK-THROUGH BY THE CLIENT. THIS INSPECTION IS NOT AN INSURANCE POLICY AGAINST HIDDEN DEFECTS, OR CONDITIONS THAT ARE NOT VISIBLE AND READILY APPARENT AT THE TIME OF INSPECTION. THE COST OF THIS INSPECTION DOES NOT ENTITLE YOU TO ANY TYPE OF PROTECTION FROM HIDDEN FLAWS AND DEFECTS. THIS INSPECTION DOES NOT TRANSFER YOUR ULTIMATE RESPONSIBILITY TO ALL POINT HOME INSPECTIONS. ENVIRONMENTAL CONCERNS: Client acknowledges that what is being contracted for is a building inspection and not an environmental evaluation and the inspection is not intended to detect, identify or disclose any health or environmental concerns regarding this building or property, including, but not limited to, the presence of asbestos, radon, lead, urea formaldehyde, fungi, mold, mildew, PCB’s or other toxic materials or substances in the water, air, soil or building materials. CONFIDENTIAL REPORT: The inspection report to be prepared for the Client is solely and exclusively for the Client’s own information and may not be relied upon by any other person. Client agrees to maintain the confidentiality of the inspection report and agrees not to disclose any part of it to any other person. Client my distribute copies of the inspection report to other persons directly involved in this transaction, but the Client and Inspector do not in any way intend to benefit said other persons directly or indirectly through this Contract, the inspection or the inspection report. CLIENT AGREES TO INDEMNIFY, DEFEND AND HOLD THE INSPECTOR HARMLESS FROM ANY THRID PARTY CLAIMS ARISING OUT OF THE CLIENT’S UNAUTHORIZED DISTRIBUTION OF THE INSPECTION REPORT. LIQUIDATED DAMAGES: IT IS UNDERSTOOD AND AGREES BY AND BETWEEN THE PARTIES HERETO THAT THE INSPECTOR/INSPECTION COMPANY IS NOT AN INSURER, THAT THE PAYMENT FOR THE SUBJECT INSPECTION IS BASED SOLELY ON THE VALUE OF THE SERVICES PROVIDED BY THE INSPECTOR/INSPECTION COMPANY IN THE PREFORMANCE OF THE INSPECTION AND PRODUCTION OF THE INSPECTION REPORT AS DESCRIBED HEREIN, THATIT IS IMPRACTICABLE AND EXTREMELY DIFFICULT TO FIX THE ACTUAL DAMAGES, OF ANY, WHICH MAY RESULT FROM A FAILURE TO PERFORM SUCH SERVICES, AND IN CASE OF FAILURE TO PERFORM SUCH SERVICES AND A RESULTING LOSS, THE CLIENT’S DAMAGES HEREIN SHALL BE LIQUIDATER AND FIXED IN AN AMOUNT EQUAL TO THE INSPECTION FEE PAID MULTIPLIED BY ONE HUNDRED TWENT-FIVE PERCENT (125%) AS

Page 63: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

©2019 Strong Foundations Home Inspection

LIQUIDATED DAMAGES AND NOT AS A PENALTY, AND THIS REMEDY SHALL BE EXCLUSIVE. GENERAL PROVISIONS: A. This inspection contract, the inspection, and the inspection report do not constitute a warranty, guarantee, or insurance policy of any kind whatsoever. B. No legal action or proceeding of any kind, including in tort or contract can be commenced against Inspector/Inspection Company, or its officers, agents or employees more than one year after the date of the subject inspection. Time is expressly of the essence herein. THIS TIME PERIOD IS SHORTER THAN OTHERWISE PROVIDED BY LAW. C. In the event the Client discovers a material physical deficiency in a component, system or equipment of the building that was not identified and reported by the Inspector, Client shall so notify the Inspector in writing and allow Inspector and/or Inspector’s designated representative to re-inspect and document the condition(s) of the material physical deficiency prior to making any repair, alteration, or replacement to said physical deficiency. D. Should any provision of this contract be held by a court of competent jurisdiction to be either invalid or unenforceable, the remaining provisions of this contract shall remain in full force and effect, unimpaired by the court’s holding. E. This contract shall be binding upon and inure to the benefit of only the undersigned parties and their heirs, successors and assigns. F. This contract constitutes the entire integrated agreement between the parties hereto pertaining to the subject matter hereof, and may be modified only by a written agreement signed by all of the parties hereto. No oral agreements, understanding, or representations shall change, modify, or amend any part of this contract. G. Each party signing this contract warrants and represents that he/she has the full capacity and authority to execute this contract on behalf of the named party whether it is a corporation, partnership, or other entity. If this contract is executed on behalf of the Client by a third party, the person executing this contract expressly represents to the Inspector that he/she has the full and complete authority to execute this contract on the Client’s behalf and to fully and completely bind the Client to all of the terms, conditions, limitations, exceptions and exclusions of this contract. This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited. FOLLOW-UP INSPECTION POLICY Generally we discourage follow-up inspections for these reasons

Page 64: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

©2019 Strong Foundations Home Inspection

1. Quality of repairs

If repairs are made to a property based on the results of an inspection, the work should be performed by qualified contractors, not the seller. By qualified, we mean licensed, bonded, state-certified where applicable and with a reasonable amount of experience. Contractors providing repairs should provide legible documentation in the form of work orders and/or receipts. If repairs are made in this way, then there's generally no need for a follow-up inspection. Additionally, it may be better to negotiate a lower price on your home and have repairs made by contractors you choose rather than the seller making repairs as cheaply as possible. ________________________________________ As a part of our service, we sometimes provide approximate, cost of repair estimates for particular items. These estimates should be considered as background information only. It is beyond the scope of this inspection and report to supply you with accurate repair costs. Such estimates should be supplied by contractors who specialize in this type of work. Our estimates should be used only as guidelines. If you intend to negotiate the price of this property based on defects found during this inspection, we strongly suggest you obtain one or more written bids from a licensed contractor(s). It is a conflict of interest for Strong Foundations Home Inspection to recommend any specific contractor.

Page 65: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

©2019 Strong Foundations Home Inspection

Life Expectancy Charts for Homes PLEASE NOTE: These life expectancies have been determined through research and testing based on regular recommended maintenance and conditions of normal wear and tear, and not extreme weather or other conditions, neglect, over-use or abuse. Therefore, they should be used as guidelines only, and not relied upon as guarantees or warranties.

Surface preparation and paint quality are the most important determinants of a paint's life expectancy. Ultraviolet (UV) rays via sunshine can shorten life expectancy. Additionally, conditions of high humidity indoors or outdoors can affect the lifespan of these components, which is why they should be inspected and maintained seasonally.

ADHESIVES, CAULK &

PAINTS

YEARS

Caulking (interior & exterior) 5 to 10

Construction Glue 20+

Paint (exterior) 7 to 10

Paint (interior) 10 to 15

Roofing Adhesives/Cements 15+

Sealants 8

Stains 3 to 8

Appliance life expectancy depends to a great extent on the use it receives. Furthermore, consumers often replace appliances long before they become worn out due to changes in styling, technology and consumer preferences.

APPLIANCES YEARS

Air Conditioner (window) 5 to 7

Compactor (trash) 6

Dehumidifier 8

Dishwasher 9

Disposal (food waste) 12

Dryer Vent (plastic) 5

Dryer Vent (steel) 20

Dryer (clothes) 13

Exhaust Fans 10

Freezer 10 to 20

Gas Oven 10 to 18

Hand Dryer 10 to 12

Humidifier (portable) 8

Microwave Oven 9

Range/Oven Hood 14

Electric Range 13 to 15

Gas Range 15 to 17

Refrigerator 9 to 13

Page 66: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

©2019 Strong Foundations Home Inspection

Swamp Cooler 5 to 15

Washing Machine 5 to 15

Whole-House Vacuum System 20

Modern kitchens today are larger and more elaborate. Together with the family room, they now form the “great room.”

CABINETRY & STORAGE YEARS

Bathroom Cabinets 50+

Closet Shelves 100+

Entertainment Center/Home Office 10

Garage/Laundry Cabinets 70+

Kitchen Cabinets 50

Medicine Cabinet 25+

Modular (stock manufacturing-type) 50

Walls and ceilings last the full lifespan of the home.

CEILINGS & WALLS YEARS

Acoustical Tile Ceiling 40+ (older than 25 years may

contain asbestos)

Ceramic Tile 70+

Concrete 75+

Gypsum 75

Wood Paneling 20 to 50

Suspended Ceiling 25+

Natural stone countertops, which are less expensive than they were just a few years ago, are becoming more popular, and one can expect them to last a lifetime. Cultured marble countertops have a shorter life expectancy, however.

COUNTERTOPS YEARS

Concrete 50

Cultured Marble 20

Natural Stone 100+

Laminate 20 to 30

Resin 10+

Tile 100+

Wood 100+

Page 67: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

©2019 Strong Foundations Home Inspection

Decks are exposed to a wide range of conditions in different climates, from wind and hail in some areas, to relatively consistent, dry weather in others. See FASTENERS & STEEL section for fasteners.

DECKS YEARS

Deck Planks 15

Composite 8 to 25

Structural Wood 10 to 30

Exterior fiberglass, steel and wood doors will last as long as the house, while vinyl and screen doors have a shorter life expectancy. The gaskets/weatherstripping of exterior doors may have to be replaced every 5 to 8 years.

DOORS YEARS

Closet (interior) 100+

Fiberglass (exterior) 100+

Fire-Rated Steel (exterior) 100+

French (interior) 30 to 50

Screen (exterior) 30

Sliding Glass/Patio (exterior) 20 (for roller wheel/track

repair/replacement)

Vinyl (exterior) 20

Wood (exterior) 100+

Wood (hollow-core interior) 20 to 30

Wood (solid-core interior) 30 to 100+

Copper-plated wiring, copper-clad aluminum, and bare copper wiring are expected to last a lifetime, whereas electrical accessories and lighting controls, such as dimmer switches, may need to be replaced after 10 years. GFCIs could last 30 years, but much less if tripped regularly. Remember that faulty, damaged or overloaded electrical circuits or equipment are the leading cause of house fires, so they should be inspected regularly and repaired or updated as needed.

ELECTRICAL YEARS

Accessories 10+

Arc-Fault Circuit Interrupters

(AFCIs)

30

Bare Copper 100+

Bulbs (compact fluorescent) 8,000 to 10,000+ hours

Bulbs (halogen) 4,000 to 8,000+ hours

Bulbs (incandescent) 1,000 to 2,000+ hours

Bulbs (LED) 30,000 to 50,000+ hours

Copper-Clad Aluminum 100+

Copper-Plated 100+

Page 68: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

©2019 Strong Foundations Home Inspection

Fixtures 40

Ground-Fault Circuit Interrupters

(GFCIs)

up to 30

Lighting Controls 30+

Residential Propane Backup

Generators

12

Service Panel 60

Solar Panels 20 to 30

Solar System Batteries 3 to 12

Wind Turbine Generators 20

Floor and roof trusses and laminated strand lumber are durable household components, and engineered trim may last 30 years.

ENGINEERED LUMBER YEARS

Engineered Joists 80+

Laminated Strand Lumber 100+

Laminated Veneer Lumber 80+

Trusses 100+

Fastener manufacturers do not give lifespans for their products because they vary too much based on where the fasteners are installed in a home, the materials in which they're installed, and the local climate and environment. However, inspectors can use the guidelines below to make educated judgments about the materials they inspect.

FASTENERS, CONNECTORS &

STEEL

YEARS

Adjustable Steel Columns 50+

Fasteners (bright) 25 to 60

Fasteners (copper) 65 to 80+

Fasteners (galvanized) 10+

Fasteners (electro-galvanized) 15 to 45

Fasteners (hot-dipped galvanized) 35 to 60

Fasteners (stainless) 65 to 100+

Steel Beams 200+

Steel Columns 100+

Steel Plates 100+

Flooring life is dependent on maintenance and the amount of foot traffic the floor endures.

FLOORING YEARS

All Wood Floors 100+

Bamboo 100+

Brick Pavers 100+

Page 69: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

©2019 Strong Foundations Home Inspection

Carpet 8 to 10

Concrete 50+

Engineered Wood 50+

Exotic Wood 100+

Granite 100+

Laminate 15 to 25

Linoleum 25

Marble 100+

Other Domestic Wood 100+

Slate 100

Terrazzo 75+

Tile 75 to 100

Vinyl 25

Concrete and poured-block footings and foundations will last a lifetime, assuming they were properly built. Waterproofing with bituminous coating lasts 10 years, but if it cracks, it is immediately damaged.

FOUNDATIONS YEARS

Baseboard Waterproofing System 50

Bituminous-Coating Waterproofing 10

Concrete Block 100+

Insulated Concrete Forms (ICFs) 100

Permanent Wood Foundation (PWF;

treated)

75

Post and Pier 20 to 65

Post and Tensioned Slab on Grade 100+

Poured-Concrete Footings and

Foundation

100+

Slab on Grade (concrete) 100

Wood Foundation 5 to 40

Framing and structural systems have extended longevities; poured-concrete systems, timber frame houses and structural insulated panels will all last a lifetime.

FRAMING YEARS

Log 80 to 200

Poured-Concrete Systems 100+

Steel 100+

Structural Insulated Panels (SIPs) 100+

Timber Frame 100+

The quality and frequency of use will affect the longevity of garage doors and openers.

Page 70: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

©2019 Strong Foundations Home Inspection

GARAGES YEARS

Garage Doors 20 to 25

Garage Door Openers 10 to 15

Home technology systems have diverse life expectancies and may have to be upgraded due to evolution in technology.

HOME TECHNOLOGY YEARS

Built-In Audio 20

Carbon Monoxide Detectors* 5

Doorbells 45

Home Automation System 5 to 50

Intercoms 20

Security System 5 to 20

Smoke/Heat Detectors* less than 10

Wireless Home Networks 5+

* Batteries should be changed at least annually. Thermostats may last 35 years but they are usually replaced before they fail due to technological improvements.

HVAC YEARS

Air Conditioner (central) 7 to 15

Air Exchanger 15

Attic Fan 15 to 25

Boiler 40

Burner 10+

Ceiling Fan 5 to 10

Chimney Cap (concrete)

100+

Chimney Cap (metal) 10 to 20

Chimney Cap (mortar) 15

Chimney Flue Tile 40 to 120

Condenser 8 to 20

Dampers 20+

Dehumidifier 8

Diffusers, Grilles and Registers 25

Ducting 60 to 100

Electric Radiant Heater 40

Evaporative Cooler 15 to 25

Furnace 15 to 25

Gas Fireplace 15 to 25

Heat Exchanger 10 to 15

Page 71: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

©2019 Strong Foundations Home Inspection

Heat Pump 10 to 15

Heat-Recovery Ventilator 20

Hot-Water and Steam-Radiant

Boiler

40

Humidifier 12

Induction and Fan-Coil Units 10 to 15

Thermostats 35

Ventilator 7

As long as they are not punctured, cut or burned and are kept dry and away from UV rays, cellulose, fiberglass and foam insulation materials will last a lifetime. This is true regardless of whether they were installed as loose-fill, housewrap or batts/rolls.

INSULATION & INFILTRATION

BARRIERS

YEARS

Batts/Rolls 100+

Black Paper (felt paper) 15 to 30

Cellulose 100+

Fiberglass 100+

Foamboard 100+

Housewrap 80+

Liquid-Applied Membrane 50

Loose-Fill 100+

Rockwool 100+

Wrap Tape 80+

Masonry is one of the most enduring household components. Fireplaces, chimneys and brick veneers can last the lifetime of the home.

MASONRY & CONCRETE YEARS

Brick 100+

Insulated Concrete Forms (hybrid

block)

100+

Concrete Masonry Units (CMUs) 100+

Man-Made Stone 25

Masonry Sealant 2 to 20

Stone 100+

Stucco/EIFS 50+

Veneer 100+

Custom millwork and stair parts will last a lifetime and are typically only upgraded for aesthetic reasons.

Page 72: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

©2019 Strong Foundations Home Inspection

MOLDING, MILLWORK &

TRIM

YEARS

Attic Stairs (pull-down) 50

Custom Millwork 100+

Pre-Built Stairs 100+

Stair Parts 100+

Stairs 100+

The lifetime of any wood product depends heavily on moisture intrusion.

PANELS YEARS

Flooring Underlayment 25

Hardboard 40

Particleboard 60

Plywood 100

Softwood 30

Oriented Strand Board (OSB) 60

Wall Panels 100+

The quality of plumbing fixtures varies dramatically. The mineral content of water can shorten the life expectancy of water heaters and clog showerheads. Also, some finishes may require special maintenance with approved cleaning agents per the manufacturers in order to last their expected service lives.

PLUMBING, FIXTURES &

FAUCETS

YEARS

ABS and PVC Waste Pipe 50 to 80

Accessible/ADA Handles 100+

Acrylic Kitchen Sink 50

Cast-Iron Bathtub 100

Cast-Iron Waste Pipe (above

ground)

60

Cast-Iron Waste Pipe (below

ground)

50 to 60

Concrete Waste Pipe 100+

Copper Water Lines 70

Enameled Steel Kitchen Sink 5 to 10+

Faucets and Spray Hose 15 to 20

Fiberglass Bathtub and Shower 20

Gas Lines (black steel) 75

Gas Lines (flex) 30

Hose Bibs 20 to 30

Instant (on-demand) Water Heater 10

PEX 40

Page 73: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

©2019 Strong Foundations Home Inspection

Plastic Water Lines 75

Saunas/Steam Room 15 to 20

Sewer Grinder Pump 10

Shower Enclosure/Module 50

Shower Doors 20

Showerheads 100+ (if not clogged by

mineral/other deposits)

Soapstone Kitchen Sink 100+

Sump Pump 7

Toilet Tank Components 5

Toilets, Bidets and Urinals 100+

Vent Fan (ceiling) 5 to 10

Vessel Sink (stone, glass, porcelain,

copper)

5 to 20+

Water Heater (conventional) 6 to 12

Water Line (copper) 50

Water Line (plastic) 50

Water Softener 20

Well Pump 15

Whirlpool Tub 20 to 50

Radon systems have but one moving part: the radon fan.

RADON SYSTEMS YEARS

Air Exchanger 15

Barometric Backdraft

Damper/Fresh-Air Intake

20

Caulking 5 to 10

Labeling 25

Manometer 15

Piping 50+

Radon Fan 5 to 8

The life of a roof depends on local weather conditions, building and design, material quality, and adequate maintenance. Hot climates drastically reduce asphalt shingle life. Roofs in areas that experience severe weather, such as hail, tornadoes and/or hurricanes, may also experience a shorter-than-normal lifespan overall or may incur isolated damage that requires repair in order to ensure the service life of the surrounding roofing materials.

ROOFING YEARS

Aluminum Coating 3 to 7

Asphalt (architectural) 30

Asphalt Shingles (3-tab) 20

BUR (built-up roofing) 30

Page 74: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

©2019 Strong Foundations Home Inspection

Clay/Concrete 100+

Coal and Tar 30

Copper 70+

EPDM (ethylene propylene diene

monomer) Rubber

15 to 25

Fiber Cement 25

Green (vegetation-covered) 5 to 40

Metal 40 to 80

Modified Bitumen 20

Simulated Slate 10 to 35

Slate 60 to 150

TPO 7 to 20

Wood 25

Outside siding materials typically last a lifetime. Some exterior components may require protection through appropriate paints or sealants, as well as regular maintenance. Also, while well-maintained and undamaged flashing can last a long time, it is their connections that tend to fail, so seasonal inspection and maintenance are strongly recommended.

SIDINGS, FLASHING &

ACCESSORIES

YEARS

Aluminum Gutters, Downspouts,

Soffit and Fascia

20 to 40+

Aluminum Siding 25 to 40+

Asbestos Shingle 100

Brick 100+

Cementitious 100+

Copper Downspouts 100

Copper Gutters 50+

Engineered Wood 100+

Fiber Cement 100+

Galvanized Steel

Gutters/Downspouts

20

Manufactured Stone 100+

Stone 100+

Stucco/EIFS 50+

Trim 25

Vinyl Gutters and Downspouts 25+

Vinyl Siding 60

Wood/Exterior Shutters 20

Site and landscaping elements have life expectancies that vary dramatically.

SITE & LANDSCAPING YEARS

Page 75: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

©2019 Strong Foundations Home Inspection

American Red Clay 100+

Asphalt Driveway 15 to 20

Brick and Concrete Patio 15 to 25

Clay Paving 100+

Concrete Walks 40 to 50

Controllers 15

Gravel Walks 4 to 6

Mulch 1 to 2

Polyvinyl Fencing 100+

Sprinkler Heads 10 to 14

Underground PVC Piping 60+

Valves 20

Wood Chips 1 to 5

Wood Fencing 20

Swimming pools are composed of many systems and components, all with varying life expectancies.

SWIMMING POOLS YEARS

Concrete Shell 25+

Cover 7

Diving Board 10

Filter and Pump 10

Interior Finish 10 to 35

Pool Water Heater 8

Vinyl Liner 10

Waterline Tile 15+

Aluminum windows are expected to last between 15 and 20 years, while wooden windows should last nearly 30 years.

WINDOWS YEARS

Aluminum/Aluminum-Clad 15 to 20

Double-Pane 8 to 20

Skylights 10 to 20

Vinyl/Fiberglass Windows 20 to 40

Window Glazing 10+

Wood 30+

Note: Life expectancy varies with usage, weather, installation, maintenance and quality of materials. This list should be used only as a general guideline and not as a guarantee or warranty regarding the performance or life expectancy of any appliance, product, system or component.

Evaluations are made as to the present age, and remaining economic life of an item, i.e.

Page 76: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

©2019 Strong Foundations Home Inspection

water heaters, roofs, plumbing, furnaces, etc. These evaluations are based on visual observation, industry averages and prior experience. THEY ARE NOT OFFERED AS A WARRANTY OR CERTIFICATION OF REMAINING LIFE.

Page 77: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

©2019 Strong Foundations Home Inspection

HOME MAINTENANCE CHECK LIST: Monthly: 1. Clean any removable dishwasher filters. 2. Purge food disposal by filling the kitchen sink with clean water, then turn on the device until the water drains through. 3. Wash refrigerator/freezer interior walls and door gaskets with a solution of one quart of warm water to two tablespoons of baking soda and wipe dry. 4. Vacuum and clean “return” air ducts/grills. 5. Inspect lighting fixtures and replace any burned-out bulbs. 6. Clean clothes dryer lint trap and/or duct for better energy efficiency and to decrease the risk of fire. Quarterly: 1. Inspect and service doors by cleaning and lubricating latches, hinges or replacing weather-stripping as might be required. 2. Inspect and repair, if necessary, exterior caulking and finish around windows, doors, and siding. 3. Replace/clean, at least quarterly, furnace, heating and cooling system filters. 4. Re-tighten knobs and pulls on cabinets. Clean and lubricate drawer tracks and guides. Semi-annually: 1. Inspect and test smoke and carbon monoxide alarms. Replace backup batteries as might be required. 2. Test (GFCI) ground fault circuit interrupters and (AFCI) arc fault breakers. 3. Inspect and maintain/clean gutters and downspouts. Runoff water must be directed away from the home. 4. Inspect attics and substructure areas for rodent droppings or other signs of pests or leaks/standing water, etc. 5. Prior to the beginning of the rainy season, test sump pumps for adequacy and function. 6. Look for moisture or decay, outside and inside the house, where flat surface decks and landing attach to the house. This is especially important if the landings do not have proper flashings. 7. Clean range hood fan grills and housings. 8. Use a vacuum cleaner to remove dust on coils behind the refrigerator/freezer. Annually: 1. Licensed contractor to inspect and service heating and air-conditioning systems. 2. Professional contractor to inspect and service wood burning appliances and chimneys. 3. Seal any foundation cracks. 4. Inspect, clean and lubricate garage vehicle door tracks and test auto-reverse functions. 5. Clean and lubricate sliding glass door and window tracks. 6. Inspect exterior paint for cracking and wear. Repaint, caulk and seal as needed.

Page 78: Confidential Inspection Report · 2019-03-07 · Confidential Inspection Report LOCATED AT: 1110 S L St Tacoma, Washington 98405 PREPARED EXCLUSIVELY FOR: Faira.com INSPECTED ON:

©2019 Strong Foundations Home Inspection

7. Reseal, as required, wood decks and landings. 8. Inspect, for water damage, pests or rot, any substructure and attic areas. 9. Inspect roof flashings, chimney caps, shingles. 10. Inspect outside electrical service lines for damage, exposed wires or proximity to tree limbs. 11. Inspect all supply hoses at sinks, toilets and washing machines. 12. Clean and repair caulking or grout in bathrooms or kitchens. 13. Clean bathroom exhaust fan blades and grills. 14. Inspect all electric coeds and replace as needed. 15. Change water filters and have fresh water systems professionally services. Tips for keeping drains clear: 1. Pour a pot of hot water down the drain once a week to help clear away fat or grease that may have built-up in the drain line or the P-trap. 2. If a drain is clogged, try pouring 1/2 cup of white vinegar down the drain. Cover the drain and let the mixture sit for a few minutes. Then pour a pot of hot water down the drain. General Safety tips: Ensure that you know where the following items are located: 1. Emergency contact telephone numbers. 2. Fire extinguishers and water hose pipes. 3. Heating gas/fuel main shut off valve. 4. Main electrical disconnect circuit breaker (breaker box/service panel). 5. Main drain line clean-out. 6. Main water shut-off valve. 7. All window and door exits.