conext tl three-phase grid-tie solar inverters · 2014-10-06 · tl grid-tie solar inverters are...
TRANSCRIPT
Why choose Conext TL?
True bankability
• Warrantyfromatrustedpartnerwithover177yearsofexperience
• Worldleaderinindustrialpowerdrives,UPSandelectricaldistribution
• Strongserviceinfrastructureworldwidetosupportyourglobalneeds
Higher return on investment
• Highconversionefficiency:>98%peakefficiency
• Broadoperatingrangetoharvestmoreenergy(earlymorningsandlateafternoons)
• HigherROIwithdualMPPT
• Greatvalueformoney:DCswitch,ACconnectorsandRS485portsareincluded
Designed for reliability
• RobustdesignthroughrigorousMultipleEnvironmentalOverStressTesting(MEOST)andTemperatureHumidityBias(THB)
• IP65compliantrugged,completelysealedunittostandtheharshestenvironmentalconditions
• Designandqualifiedforapplicationsintropicalenvironmentsthroughconformalcoatingandsaltfogtesting
Flexible
• WideMPPTvoltagerange(350-850V)
• Modularsystemdesignsusingacombinationofmodels
• Easytoconnecttothirdpartymonitoringsolutions
• Appropriateforoutdoorinstallations(IP65electronics)
Easy to service
• Easilyreplaceablefanblockandcommunicationscard
• IntegratedDCswitch
• Abilitytoremotelydisable
Easy to install
• Easyandfastmountingwithincludedbracket
• PluggableACandDCConnectors(MC4)
• Autocountry/multilingualconfigurations
Product applications
Commercialgrid-tiedecentralised
Conext TL Three-phase grid-tie solar inverters
TheConextTMTL8,and10kWgrid-tiesolarinvertersaresuitedforoutdooruseandaretheidealsolutionforsmallcommercialbuildings.TheinvertersprovidedualMPP(MaximumPowerPoint)trackerswithawidevoltagerange,peakefficiencyofgreaterthan98%forfastROI.TheembeddedModbuscommunicationcardallowsconnectivitywithalargerangeofSchneiderElectricTMproducts,aswellastheoptiontoeasilyaddthirdpartymonitoringsolutions.BackedbySchneiderElectric’sglobalserviceinfrastructureanditsexpertiseinenergymanagement,theConextTLseriesaretheinvertersyoucantrustforqualityandreliability.
Ideal solar power generators for small commercial buildings
www.SEsolar.com
Conext TL series
DS20140505_ConextTL
Device short name TL 8000 E TL10000 E Electrical specificationsInput (DC)MPPTvoltagerange,fullpower 350-850V 350-850V
Operatingvoltagerange 200-1000V 200-1000V
Startingvoltage 250V 250V
Max.inputvoltage,opencircuit 1000V 1000V
NumberofMPPT 2 2
Max.inputcurrentperMPPT 17A 17A
Nominalinputpower(cosφ=1) 8.3kW 10.4kW
Max.DCinputpowerperMPPT 5.5kW 7.0kW
DCconnectiontype MC4,4pairs(2+2) MC4,4pairs(2+2)
DCswitch Integrated Integrated
Output (AC)Nominaloutputpower 8kVA 10kVA
Max.ACoutputpower 8.4kVA 10.5kVA
Nominaloutputvoltage 230/400V,three-phase 230/400V,three-phase
Isolation Transformerless Transformerless
ACvoltagerange 184-276V 184-276V
Frequency 50/60Hz 50/60Hz
Frequencyrange 50/60+/-3Hz 50/60+/-3Hz
Max.outputcurrent 12.8A 16.0A
Totalharmonicdistortion <3% <3%
Powerfactor(adjustable) 0.8leadto0.8lag 0.8leadto0.8lag
ACconnectiontype IP67connector IP67connector
EfficiencyPeak 98.2% 98.3%
European 97.4% 97.7%
General specificationsPowerconsumption,nighttime <2W <2W
IPdegreeofprotection IP65(electronics),IP55(balance) IP65(electronics),IP55(balance)
Cooling Fancooled Fancooled
Enclosurematerial Aluminium Aluminium
Productweight 41.0kg(90.2lb) 41.0kg(90.2lb)
Shippingweight 48.5kg(106.9lb) 48.5kg(106.9lb)
Productdimensions(HxWxD) 62.5x61.2x27.8cm 62.5x61.2x27.8cm (24.6x24.0x10.9in) (24.6x24.0x10.9in)
Shippingdimensions(HxWxD) 75.0x74.0x40.0cm 75.0x74.0x40.0cm (29.5x29.1x15.8in) (29.5x29.1x15.8in)
Ambientairtemperatureforoperation -20to60ºC(-4ºFto140ºF) -20to60ºC(-4ºFto140ºF)
Operatingaltitude Upto2000m Upto2000m
Relativehumidity 4-100%(condensing) 4-100%(condensing)
Noiseemission(at1mdistance) <50dBA <50dBA
Features and optionsEmbeddeddatalogger 365days
Display 5”GraphicLCD(320x240pixels),4buttons
Communicationinterface Modbus(RS485)
Multifunctionrelay Yes
Warrantyinyears(standard/optional) 5/10
Regulatory approvalElectricalsafety CEmarkedfortheLowVoltageDirectiveEN/IEC62109-1/EN/IEC62109-2
Gridinterconnection* VDE0126-1-1,VDE-AR-N4105,RD1663,RD661,RD1699,CEI0-21,A70,UTEC15-712-1,AS4777
Environmental RoHS,REACH
EMC CEmarkedfortheEMCdirective2004-108-EC Emissions:EN61000-6-3(residential) Immunity:EN61000-6-2(industrial)
Available product variantsStandard PVSNVC8000 PVSNVC10000Specificationsaresubjecttochangewithoutnotice.*Moreavailableuponrequest.
© 2014 Schneider Electric. All Rights Reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.
A bankable solution for commercial buildings, carports, and decentralised power plantsConext TL three-phase grid-tie inverters
02
Conext TL three-phase grid-tie inverters
Introducing the Conext TL three-phase grid-tie inverter
Backed by the Schneider Electric global service infrastructure and its expertise in energy management, the Conext TL series are the inverters you can trust for quality and reliability.
The new ConextTM TL grid-tie solar inverters are suited for outdoor use and are the ideal solution for commercial buildings, carports, and decentralised photovoltaic (PV) plants up to the MW range. The inverters provide dual maximum power point tracking (MPPT) with a wide voltage range and a peak efficiency of greater than 98 per cent for fast ROI.
The embedded Modbus communication card also allows for connectivity with a large range of Schneider ElectricTM products, as well as the option to easily add third party monitoring solutions.
Available in 8, 10, 15 and 20 kW
03
Why choose a Conext TL solar inverter?
True bankability• Warranty from a trusted partner with over 175 years
of experience• World leader in industrial power drives, UPS, and electrical distribution
• Strong service infrastructure worldwide to support your global needs
Higher return on investment• High efficiency >98%• Higher ROI with dual MPPT• Great value for money• Warranty from a trusted partner
Designed for reliability• Tested and qualified in harsher environmental conditions
(MEOST reliability testing)
Flexible• Wide MPPT voltage range (350 - 850 V)• Modular system designs using a combination of models• Easy to connect to third party monitoring solutions• Appropriate for outdoor installations (IP65 electronics)
Easy to service• Easily replaceable fan block and communications card• Integrated DC switch• Ability to remotely disable
Easy to install• Easy and fast mounting with included bracket• Pluggable AC and DC connectors (MC4)• Auto country/multilingual configurations
04
Conext TL three-phase grid-tie inverters
Applications for the Conext TL three-phase grid-tie inverter
Decentralised PV plants
Commercial buildings and carports
05
Designing a decentralised solar installation using Conext TL
Using Conext TL inverters in a decentralised PV architecture, the PV array is broken up into smaller sub-arrays, each with its own small power string inverters.
• Lower installation cost and time due to modular system design, reduced transportation costs, and no need for specialised installation equipment or personnel.
• Lower balance of system cost as inverters can be mounted outside, closer to the PV panels, thereby reducing DC cable costs and eliminating need for concrete pad or shelter.
• Increased energy harvest due to multiple MPPT trackers, and a wide MPPT input range offering string optimization per inverter.
• Lower maintenance cost & minimal system disruptions due to short replacement lead times and ease of servicing.
Hence, a decentralised approach with Conext TL inverters lowers the rated costs of the plant (including land costs, LV and MV cabling, civil works and fencing, security installations, heavy machinery, etc.). These savings, coupled with increased power production, decrease the payback period of the overall investment.
Conext TLEmergencystop
PVemergencycontrol
AC distributionbox
PV modules DC boxPV emergencybox
AC box
Monitoring
LV/MVswitchgear
Grid
LV/MVtransformer
06
Conext TL three-phase grid-tie inverters
Conext TL references
FranceSolution: 4 Conext TL and DC/AC enclosuresSystem size: 70 kWInstallation type: Commercial rooftop
GreeceSolution: 25 Conext TL invertersSystem size: 500 kWInstallation type: Ground mounted
ItalySolution: 8 Conext TL inverters, 3 Prisma and 5 array boxesSystem size: 145 kWInstallation type: Commercial rooftop
SlovakiaSolution: 4 Conext TL inverters, 2 Prisma and 20 array boxesSystem size: 80 kWInstallation type: Commercial rooftop
GermanySolution: 18 Conext TL, 18 DC boxes and 3 AC boxes including 6 Sarel-boxes and surge arrestersSystem size: 360 kWInstallation type: Commercial rooftop
ItalySolution: 17 Conext TL inverters, 2 Prisma and 50 array boxesSystem size: 335 kWInstallation type: Commercial rooftop
ItalySolution: 10 Conext TL inverters, 2 Prisma and 20 array boxesSystem size: 200 kWInstallation type: Commercial rooftop
SwitzerlandSolution: 5 Conext TL inverters, 3 DC boxes and 3 AC boxesSystem size: 95 kWInstallation type: Commercial rooftop
07
Technical specifications
Device short name TL 8000 E TL 10000 E TL 15000 E TL 20000 Electrical specificationsInput (DC)MPPT voltage range full power 350 - 850 V 350 - 850 V 350 - 800 V 350 - 800 VOperation voltage range 200 - 1000 V 200 - 1000 V 200 - 1000 V 200 - 1000 VStarting voltage 200 V 200 V 200 V 200 VMax. input voltage, open circuit 1000 V 1000 V 1000 V 1000 VNumber of MPPT 2 2 2 2Max. input current per MPPT 17 A 17 A 23 A 30 AMax. short circuit current per MPPT 24 A 24 A 30 A 30ANominal input power for max. output 8.3 kW 10.4 kW 17.0 kW 22.0 kWMax. DC input power per MPPT 5.5 kW 7.0 kW 8.5 kW 11.0 kWDC connection type MC4, 4 pairs (2+2) MC4, 4 pairs (2+2) MC4, 4 pairs (2+2) MC4, 4 pairs (2+2)DC switch Integrated Integrated Integrated IntegratedOutput (AC)Nominal output power 8 kVA 10 kVA 15 kVA 20 kVANominal output voltage 230 / 400 V, three-phase 230 / 400 V, three-phase 230 / 400 V, three-phase 230 / 400 V, three-phaseIsolation Transformerless Transformerless Transformerless TransformerlessAC voltage range 184 - 276 V 184 - 276 V 184 - 276 V 184 - 276 VFrequency 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 HzFrequency range 50 / 60 +/- 3 Hz 50 / 60 +/- 3 Hz 50 / 60 +/- 3 Hz 50 / 60 +/- 3 HzMax. output current 12.8 A 16.0 A 24.0 A 32.0 ATotal harmonic distortion < 3 % < 3 % < 3 % < 3 %Power factor (adjustable) 0.8 lead to 0.8 lag 0.8 lead to 0.8 lag 0.8 lead to 0.8 lag 0.8 lead to 0.8 lagAC connection type IP67 connector IP67 connector IP67 connector IP67 connectorEfficiencyPeak 98.2 % 98.3 % 98.0 % 98.0 %European 97.4 % 97.7 % 97.3 % 97.5 %General specificationsPower consumption, night time < 2 W < 2 W < 2 W < 2 WIP degree of protection IP65 (electronics)
IP55 (balance)IP65 (electronics)IP55 (balance)
IP65 (electronics)IP55 (balance)
IP65 (electronics)IP55 (balance)
Cooling Fan cooled Fan cooled Fan cooled Fan cooledEnclosure material Aluminium Aluminium Aluminium AluminiumProduct weight 41.0 kg (90.2 lb) 41.0 kg (90.2 lb) 67.2 kg (148.2 lb) 67.2 kg (148.2 lb)Shipping weight 48.5 kg (106.9 lb) 48.5 kg (106.9 lb) 122.0 kg (269.0 lb) 122.0 kg (269.0 lb)Product dimensions (H x W x D)
62.5 x 61.2 x 27.8 cm (24.6 x 24.0 x 10.9 in)
62.5 x 61.2 x 27.8 cm (24.6 x 24.0 x 10.9 in)
96.0 x 61.2 x 27.8 cm (37.8 x 24.1 x 10.9 in)
96.0 x 61.2 x 27.8 cm (37.8 x 24.1 x 10.9 in)
Shipping dimensions (H x W x D)
75.0 x 74.0 x 40.0 cm (29.5 x 29.1 x 15.8 in)
75.0 x 74.0 x 40.0 cm (29.5 x 29.1 x 15.8 in)
115.0 x 79.0 x 48.0 cm (45.3 x 31.1 x 18.9 in)
115.0 x 79.0 x 48.0 cm (45.3 x 31.1 x 18.9 in)
Ambient air temperature for operation -20 to 60ºC (-4ºF to 140ºF) -20 to 60ºC (-4ºF to 140ºF) -20 to 60ºC (-4ºF to 140ºF)** -20 to 60ºC (-4ºF to 140ºF)**Operating altitude Up to 2000 m Up to 2000 m Up to 2000 m Up to 2000 m
Relative humidity 4 - 100 % (condensing) 4 - 100 % (condensing) 4 - 100 % (condensing) 4 - 100 % (condensing)Noise emission (at 1 m distance) < 50 dBA < 50 dBA < 55 dBA < 55 dBAFeatures and optionsEmbedded data logger 365 daysDisplay 5” Graphic LCD (320 x 240 pixels), 4 buttonsCommunication interface Modbus (RS485)Multifunction relay YesWarranty in years (standard/optional) 5 / 10Regulatory approvalElectrical safety CE marked for the Low Voltage Directive EN/IEC 62109-1 / EN/IEC 62109-2
AS3100 (Australia / Israel***)Grid interconnection* BDEW***, VDE0126-1-1, VDE-AR-N 4105, RD1663, RD661, RD1699, ENEL-Guida***, CEI 0-21, A70, G59/2***, UTE C15-712-1,
AS4777/SI4777***, PO12.3***, IEC 62116***, IEC 61727***
Environmental RoHS, REACHEMC CE marked for the EMC directive 2004-108-EC
Emissions: EN 61000-6-3 (residential)Immunity: EN 61000-6-2 (industrial)
Available product variantsStandard PVSNVC8000 PVSNVC10000 PVSNVC15000 PVSNVC20000
Specifications are subject to change without notice. *More available upon request. **-15ºC cold start temperature. Vpv ≥500V, unit derates above 40ºC ambient. ***Only for TL 15000 E and TL 20000 E.
Schneider Electric Industries SAS
Head Office35 rue Joseph Monier92500 Rueil Malmaison Cedex- FranceTel.: +33 (0)1 41 29 70 00www.schneider-electric.com
Make the most of your energySM
You can also see our solutions on YouTube at www.youtube.com/schneidersolar
©2013 Schneider Electric. All Rights Reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.998-1191861_GMA-GB
Discover how our bankable solar solutions can reliably power your project. Visit www.schneider-electric.com/solar today to find out more!
[ APPLICATION NOTE ]
Conext TL – Changing Frequency Settings for Brazil David Miller, Global Product Line Manager
Make the most of your energyTM
Content This application note is to be used to change the frequency settings on a
Conext TL from 50Hz to 60Hz, for the Brazilian market only.
Frequency range values are not provided in this application note, it only
provides the instructions on how to access the proper menu systems
within the inverter, and change these settings. Actual frequency range
settings must be in compliance with local grid requirements.
This application note should only be used in conjunction with the
Installation and Operation guide and performed by qualified installers and service personnel.
Schneider Electric Solar Business. www.schneider-electric.com Document Number AN20121106_Conext TL V 1.0
©20
12 S
chne
ider
Ele
ctric
. All
right
s re
serv
ed. S
chneid
er
Ele
ctric
and M
ake t
he m
ost
of your
energ
y a
re t
radem
ark
s ow
ned b
y
Sch
neid
er
Ele
ctric
Indust
ries
SAS o
r its
aff
iliate
d c
om
panie
s. A
ll oth
er
tradem
ark
s are
pro
pert
y o
f th
eir r
esp
ect
ive o
wners
.
[ APPLICATION NOTE ]
Conext TL - Changing Frequency Settings for Brazil
Before you start: A technician password is required to change the frequency settings. Passwords will only be provided to qualified installers and service personnel. Please contact your sales representative to obtain this technician password. Step 1: Remove the top cover of the packaging to access the bottom terminals and front display. The inverter does not need to be removed from the bottom packaging (pallet). Step 2: Provide power to the inverter. Either DC or AC. Only one is required. Do not apply both AC and DC power, as this will cause the inverter to operate and produce power.
• DC input voltage should be > 200Vdc • AC voltage should be 230Vac • Keep DC switch off before connecting to the inverter. • If using AC plug = L1 to Pin 1, L2 to Pin 2, L3 to Pin 3, Neutral to Pin 4, Ground/PE to Pin 5. • Be aware that incorrect wiring of PE (ex. if PE and L1 were reversed) will cause electric shock or
damage computer and/or inverter. Step 3: Once inverter is powered, the initial start up menu is shown. Upon starting of the unit, select the country closest to grid connection settings in Brazil. Press “OK” to Select the Country. Press “OK” again to confirm your selection. Note - by selecting the county closest to Brazil’s grid connection settings, when the unit is switched to a “Custom” country (Step 7 & 8), all of the country settings from the original country selection are maintained. Step 4: Select the desired language. Press “OK” to confirm your selection.
Continued on next page...
Schneider Electric Solar Business. www.schneider-electric.com Document Number AN20121106_Conext TL V 1.0
©20
12 S
chne
ider
Ele
ctric
. All
right
s re
serv
ed. S
chneid
er
Ele
ctric
and M
ake t
he m
ost
of your
energ
y a
re t
radem
ark
s ow
ned b
y
Sch
neid
er
Ele
ctric
Indust
ries
SAS o
r its
aff
iliate
d c
om
panie
s. A
ll oth
er
tradem
ark
s are
pro
pert
y o
f th
eir r
esp
ect
ive o
wners
.
[ APPLICATION NOTE ]
Conext TL - Changing Frequency Settings for Brazil
Step 5: From the main menu, select, “Settings”, then press OK. Select Install Settings, then press OK. Step 6: Using the up and down arrows, set each of the four digits in the password. Press OK after each digit is entered, and then press OK. Step 7: Select “Country”, Press “OK” Step 8: Select “Custom”, Press “OK” Step 9: Select “Grid Settings” menu, and Press “OK” Step 10: The following frequency variables can then be set in this menu. To access these frequency settings, press Down arrow until you reach screen 3/4. • Fac High Off • Fac High On • Fac High Off T (disconnect time) • Fac Low Off • Fac Low On • Fac Low Off T (disconnect time) Step 11: Select the variable to be changed, Press “OK” and the variable will be highlighted. Using the up and down arrows, change the required frequency settings. Press “OK” to confirm the setting. If you make an error when changing the variable, press ESC to cancel. Step 12: Once all of the desired frequency settings have been selected/edited, press “ESC” button till you return to the main menu. All changed frequency settings will be saved. Step 13: Process completed. Turn off all power to unit and disconnect. Step 14: If required, repackage the inverter.
Contents
Application Note - Using Modbus With Conext™ TL Inverters
976-0301-01-01Revision A
Section Page
Introduction 3
Overview 3
Key Points 4
Related Documents 4
Modbus Physical Layer 5
RJ-45 Connection 6
Terminal Block Connection 7
Termination Resistor 8
Communication parameters 9
Inverter Configuration 10
Setting the Modbus Slave Address (Inverter ID) 10
Reviewing the Modbus Slave Address (Inverter ID) 11
Modbus Logical Layer 12
Modbus Packet Structure 12
Slave address field 12
Function field 12
Data field 12
Error check field (checksum) 13
Packet communications 13
Modbus functions supported by the inverter 13
Function 03: Read Holding Registers 13
Function 16: Preset Multiple Registers 14
Function 43: Device Discovery 16
Broadcasts 18
Application Note - Using Modbus With Conext™ TL Inverters
Modbus Data Types 19
16-bit integer format 19
32-bit integer format 19
8-bit Unsigned Character Format 20
Modbus Error Responses 21
Function Code Field 21
Data Field 21
Modbus Error Response Example 22
Event Logs 23
Logger Mode 23
Logger State 24
Event Log Size 24
Log Request Registers 25
Event Log Record 26
Clearing Logs 26
Conext TL Modbus Map 27
Modbus Address 27
Modbus Register Description 27
Modbus Register Access type 27
Modbus Register Units 27
Modbus Register Size 28
Invalid Registers 28
Modbus Map 29
Appendix A: CRC-16 calculation 36
Pseudocode For CRC-16 Generation 37
Appendix B: Leading and Lagging Power Factors 38
Section Page
2 976-0301-01-01 Revision A
Application Note - Using Modbus With Conext™ TL Inverters
Introduction
Overview
Modbus is a simple and robust open communication protocol used to provide interoperability between products from many different vendors. The purpose of this application note is to provide a brief overview of the Modbus hardware and software implementation of the Conext TL 15000 E and Conext TL 20000 E photovoltaic grid tie inverters so that you can quickly and easily interface the inverter with any third-party Modbus devices.
The inverter performs Modbus communications according to the Modbus Application Protocol v1.1. It is assumed that you are familiar with the Modbus protocol and with serial communications in general.
DANGER
HAZARD OF FIRE, ARC FLASH, OR ELECTRIC SHOCK FROM MULTIPLE SOURCES
• This Application Note is in addition to, and incorporates by reference, the installation and operation manual for the Conext™ TL 15000 E and 20000 E photovoltaic grid tie inverters. Before reviewing this Application Note you must read the Conext TL installation and operation manual. Unless specified, information on safety, specifications, installation, and operation is as shown in the primary documentation received with the product. Ensure you are familiar with that information before proceeding.
• To be installed and serviced only by qualified personnel.
• This document is intended for use by qualified installers only.
• Before servicing, disconnect all sources and wait at least 1 minute.
Failure to follow these instructions will result in death or serious injury.
976-0301-01-01 Revision A 3
Application Note - Using Modbus With Conext™ TL Inverters
Key Points
The inverter is capable of communicating via the RS-485 serial communication standard. The RS-485 medium allows for multiple devices on the same serial bus network.
All communications on the network conform to a Master/Slave scheme. In this scheme, information and data is transferred between a Modbus Master device and up to 254 Slave devices.
The Master device initiates and controls all information transfer on the Modbus serial bus network. There may be only one master for any Modbus network.
A Slave device never initiates a communication sequence, and must remain silent unless addressed specifically by the Master.
All communication activity on the Modbus serial bus network occurs in the form of packets. A packet is a serial string of up to 255 8-bit bytes.
All packets transmitted by the Master are requests. All packets transmitted by a Slave are responses.
At most, one Slave can respond to a single request from a Master.
The Modbus protocol supports RTU and ASCII protocols. The Conext TL 15000 E and Conext TL 20000 E photovoltaic grid tie inverters support only the Modbus/RTU protocol.
Related Documents
Table 1 Related documents
Document reference Document title Document number Version
1 Modbus Application Protocol Specification
From www.modbus.org
1.1b
2 Conext TL 15000 E and 20000 E Installation and Operation Manual
975-0609-01-01 AA
4 976-0301-01-01 Revision A
Application Note - Using Modbus With Conext™ TL Inverters
Modbus Physical LayerThe Conext TL inverter supports the Modbus communication protocol via an RS485 interface. Both an RJ-45 and terminal block wiring interface are supported. The module also provides an RID (Remote Inverter Disable) input and a dry (not energized) contact for signalling purposes. The module is shown in Figure 2-1.
Figure 2-1 Communication module
Dry contact terminals
5-position terminal block (for RS485)
Pin 8
Pin 1
Termination resistor (for RS485)
RJ-45 connectors(for RS485)
RID (Remote Inverter Disable) terminals
976-0301-01-01 Revision A 5
Application Note - Using Modbus With Conext™ TL Inverters
RJ-45 Connection
The RS-485 bus is a multi-drop bus implemented as a daisy chain. The RJ-45 connector is provided with two ports to allow ease of daisy chaining. Either port can be connected to the upstream or downstream devices.
A standard Ethernet (straight-through) patch cable may be used to connect to the upstream and downstream devices. Ethernet cross-over cables must not be used.
The RJ45 connector provides D+, D-, and signal Ground connections.
The pin definitions of the RJ-45 connection are shown in Table 2-1. For the location of pin 8, see Figure 2-1 on page 2–5.
Table 2-1 RJ-45 pin definitions
Pin Function
4 DATA+
5 DATA-
7 NC (Not connected)
8 Modbus ground
6 976-0301-01-01 Revision A
Application Note - Using Modbus With Conext™ TL Inverters
Terminal Block Connection
A five-position terminal block connector is also provided for Modbus interconnection. It provides the same D+, D-, and signal Ground connections that are provided on the RJ45 connector, and gives the user the flexibility to use a standard twisted pair cable to external equipment.
The pin definitions of the 5-position terminal block are shown in Table 2-2.
The location of the terminal block is shown in Figure 2-1 on page 2–5.
For pin numbering, see Figure 2-2.
Table 2-2 5-position terminal block pin definitions
Pin Function
1 DATA+
2 DATA-
3 Chassis ground
4 Modbus ground
5 NC (Not connected)
Figure 2-2 RS485 terminal block—pin numbering
Pin 1
Pin 5
976-0301-01-01 Revision A 7
Application Note - Using Modbus With Conext™ TL Inverters
Termination Resistor
You must enable the termination resistors if the inverter is on the end of the Modbus device chain. To do this, use a DIP switch on the communication interface board. If the inverter is the first or the last device of the RS485-chain, set the termination resistor to on; otherwise, set it to off.
The location of the termination resistor is shown in Figure 2-3. The settings are shown in Table 2-3.
Figure 2-3 Termination resistor—switch numbering
Table 2-3 Termination resistor settings
Switch 1 Switch 2 Result
Off Off The termination resistor is off.
Off On The termination resistor is on.
On Off The termination resistor is on.
On On The termination resistor is on.
Switch 2 Switch 1 (both switches are shown in the OFF position)
Termination resistor
8 976-0301-01-01 Revision A
Application Note - Using Modbus With Conext™ TL Inverters
Communication parameters
Table 3 on page 9 shows the communication parameters used by the RS-485 Modbus interface on the inverter.
These parameters must be set identically on the Modbus Master device or PC program used to communicate with the inverter. To determine how to set the communication parameters of the Modbus Master device, see the documentation that accompanies the device.
Table 3 RS485 communication parameters
Parameter Value Parameter Value
Baud rate 9600 Stop bits 1
Data bits 8 Parity None
976-0301-01-01 Revision A 9
Application Note - Using Modbus With Conext™ TL Inverters
Inverter Configuration
Setting the Modbus Slave Address (Inverter ID)
The Modbus Slave address (or Inverter ID) must be unique for each device on the Modbus network. The Modbus Slave address may be read and/or modified via the front panel display of the inverter.
To change the Inverter ID:
1. From the main menu, select Settings, and then press OK.
2. Select Install Settings, and then press OK.
3. Use the ▼ and ▲ buttons to set each of the four digits in the password. Press OK after each digit is entered, and then press OK.
The password for qualified installers is 5555.
Figure 3 Main menu
Figure 4 Settings menu
Menu 21. Feb 2012 13:50
Power Meter
Operation Data
Energy Log
Event Log
Inverter Information
Settings
E-Today
Personal Settings
Settings
Coefficient Settings
Operation Data
Install Settings
Active/Reactive Power Control
FRT
Italy Selftest
10 976-0301-01-01 Revision A
Application Note - Using Modbus With Conext™ TL Inverters
Once the correct password has been entered, the Install Settings Menu is displayed, as shown in Figure 5.
4. From the Install Settings Menu, select Inverter ID, and press OK.
5. Use the ▼ and ▲ buttons to set the Inverter ID. Press OK to confirm the new Inverter ID.
6. Press the ESC button to exit back to the main menu.
For the new Inverter ID setting to take effect, shut down and restart the inverter.
Reviewing the Modbus Slave Address (Inverter ID)
To review the current Modbus Slave Address (Inverter ID) setting:
1. From the main menu, select Inverter Information.
2. Press OK.
The Inverter ID is shown at the bottom of the screen.
Figure 5 Install Settings menu
Menu 21. Feb 2012 13:50
Insulation
Return to Factory
RCMU
DC Injection
Country/Grid
Grid Setting
Inverter ID
976-0301-01-01 Revision A 11
Application Note - Using Modbus With Conext™ TL Inverters
Modbus Logical Layer
Modbus Packet Structure
Every Modbus packet consists of four fields:
• Slave address field
• Function field
• Data field
• Error check field (checksum)
Slave address field
The slave address field of a Modbus packet is one byte in length and uniquely identifies the slave device involved in the transaction. Valid addresses range between 1 and 255.
A slave device performs the command specified in the packet when it receives a request packet with the slave address field matching its own address.
A response packet generated by the slave has the same value in the slave address field.
Function field
The function field of a Modbus request packet is one byte in length and tells the addressed slave which function to perform. Similarly, the function field of a response packet tells the master what function the addressed slave has just performed.
Data field
The data field of a Modbus request is of variable length, and depends on the function. This field contains information required by the slave device to perform the command specified in a request packet or data being passed back by the slave device in a response packet.
Data in this field is contained in 16-bit registers. Registers are transmitted in the order of high-order byte first, low-order byte second.
Example:
A 16-bit register contains the value 0x12AB. This register is transmitted:
• High order byte = 0x12
• Low order byte = 0xAB
This register is transmitted in the order 12 AB.
NOTICE
• The values shown in the packets are in hexadecimal format.
• In the tables that show the packet structure, white background denotes the DATA field of the packet.
Table 4 Modbus packet structure
Address Function Code Data Checksum
12 976-0301-01-01 Revision A
Application Note - Using Modbus With Conext™ TL Inverters
Error check field (checksum)
The checksum field lets the receiving device determine if a packet is corrupted with transmission errors. In Modbus RTU mode, a 16-bit Cyclic Redundancy Check (CRC-16) is used.
The sending device calculates a 16-bit value, based on every byte in the packet, using the CRC-16 algorithm. The calculated value is inserted in the error check field.
The receiving device performs the calculation, without the error check field, on the entire packet it receives. The resulting value is compared to the error check field. Transmission errors are indicated when the calculated checksum does not equal the checksum stored in the incoming packet. The receiving device ignores a bad packet.
For more information on CRC-16 calculations, see “Appendix A: CRC-16 calculation” on page 36.
Packet communications
This section describes the Modbus functions supported by the inverter.
Modbus functions supported by the inverter
Function 03: Read Holding Registers
To read inverter parameter values, a master must send the slave device (inverter) a Read Holding Registers request packet.
The Read Holding Registers request packet specifies a start register and a number of registers to read. (You can read 1 or more registers.) The start register may be from 0 to 65535 (0xFFFF).
The inverter responds with a packet containing the values of the registers in the range defined in the request.
Table 5 Modbus functions supported by the inverter
Function Meaning Action See this section:
03 Read Holding Registers
Reads a value from one or more consecutive holding registers in the inverter.
“Function 03: Read Holding Registers” on page 13
16 Write Multiple Registers
Writes a value into one or more consecutive holding registers in the inverter.
“Function 16: Preset Multiple Registers” on page 14
43 Read Device Identifier
Reads the Manufacturer, Model, and Version information for the device.
“Function 43: Device Discovery” on page 16
976-0301-01-01 Revision A 13
Application Note - Using Modbus With Conext™ TL Inverters
Example:
The inverter is configured as a Modbus slave device with slave address 1. The master requests to read all three voltage phases (A, B, C). These three parameters are made available in the Modbus map at address 0x17F8 (Vab), 0x17F9 (Vbc), and 0x17FA (Vca), with a scaling factor of 10. The request must read 3 registers starting at 0x17F8.
The master retrieves the data from the response:
• Register 0x17F8: 0x04B1 = 1201 (scaled: 120.1)
• Register 0x17F9: 0x04AE = 1198 (scaled: 119.8)
• Register 0x17FA: 0x04B3 = 1203 (scaled: 120.3)
Function 16: Preset Multiple Registers
The Preset Multiple Registers command packet allows a Modbus master to configure or control the slave inverter.
A Preset Multiple Registers data-field request packet contains a definition of a range of registers to write to, and the values that are written to those registers.
The slave inverter responds with a packet indicating that a write was performed to the range of registers specified in the request.
Table 6 Read Holding Registers packet structure
Request packet (master to slave) Response packet (slave to master)
Unit ID/slave address (1 byte) Unit ID/slave address (1 byte)
03 (function code) (1 byte) 03 (function code) (1 byte)
Start register (sr) (2 bytes) Byte count (2 x nr) (1 byte)
# of registers to read (nr) (2 bytes) First register in range (2 bytes)
CRC checksum Second register in range (2 bytes)
…
CRC checksum (2 bytes)
Table 7 Request packet
Slave Function Start register # of registers (3)CRC checksum
01 03 17 F8 00 03 81 8E
Table 8 Response packet
Slave FunctionByte count Register 1 Register 2 Register 3
CRC checksum
01 03 06 04 B1 04 AE 04 B3 7F 4F
14 976-0301-01-01 Revision A
Application Note - Using Modbus With Conext™ TL Inverters
The Preset Multiple Registers request and response packet formats are shown in the following example transaction.
NOTE: Except for the function field, the Preset Registers Response packet has the same fields as the Read Registers Request packet.
Example:
Write to the “Logger-Mode” register of the inverter at Modbus address 201 (0xC9) to enable reading of event logs from the inverter. The Logger-mode register is at address 0x4705, and it must be set to “2” (0x0002) to enable reading of the event logs.
For details about the Logger-Mode register, see “Logger Mode” on page 23.
Table 9 Preset Multiple Registers packet structure
Request packet (master to slave) Response packet (slave to master)
Unit ID/slave address (1 byte) Unit ID/slave address (1 byte)
16 (function code) (1byte) 16 (function code) (1 byte)
Start register (sr) (2 bytes) Start register (sr) (2 bytes)
# of registers to write (nr) (2 bytes) # of registers written (nr) (2 bytes)
Byte count (2 x nr) (1 byte) CRC checksum (2 bytes)
First register in range (2 bytes)
Second register in range (2 bytes)
...
CRC checksum (2 bytes)
Table 10 Request packet
Slave FunctionStart register
# of registers
Byte count Register 1 CRC checksum
C9 10 47 05 01 02 00 02 7F 7A
Table 11 Response packet
Slave FunctionStart register
# of registers CRC checksum
C9 10 47 05 00 01 15 34
976-0301-01-01 Revision A 15
Application Note - Using Modbus With Conext™ TL Inverters
Function 43: Device Discovery
Function code 43 checks for the presence of a device at a specific address on the Modbus device chain. A Modbus master may request Function Code 43 data from each Modbus address. A device with the requested address must report at least 3 pieces of data, as shown in Table 12.
In the case of the 20KW inverter (Conext TL 20000 E), it will report the following:
• Manufacturer Name: Schneider Electric
• Product Identification: PVSNVC20000
• Product Version Number: 000.000
Example:
The Modbus master asks the device at Modbus address 01 to identify itself.
Modbus function code 43 (0x2B) uses a sub-function code to distinguish different behaviors for the function. The Conext TL inverter supports sub-function 14 (0x0E).
The ID Code field supports four values:
• 01: request to get the basic device identification (stream access)
• 02: request to get the regular device identification (stream access)
• 03: request to get the extended device identification (stream access)
• 04: request to get one specific identification object (individual access)
Table 12 Mandatory components of a reply to Function Code 43
Object ID Object name / description Type
0x00 Manufacturer Name ASCII String
0x01 Product Identification ASCII String
0x02 Product Version Number ASCII String
NOTICE
The Product Version Number is not used on the Conext TL inverter. It will always report 000.000.
Table 13 Request packet
Slave Function Sub-function ID Code Object ID CRC checksum
01 2B 0E 01 00 70 77
NOTICE
The Conext TL inverter only supports ID code 01.
16 976-0301-01-01 Revision A
Application Note - Using Modbus With Conext™ TL Inverters
The value of Object ID determines the items in the response, as shown in Table 14.
Response Packet:
Table 14 Contents of response, depending on Object ID
Object ID Manufacturer name Product identificationProduct version number
0x00 ✓ ✓ ✓
0x01 ✓ ✓
0x02 ✓
Slave ID 01 Indicates the address of the responding slave device
Function Code
2B Indicates a function code 43 (0x2B) response
Sub Code 0E Sub code 14 (0x0E) is the only sub code supported
Read Device ID Code
01 Same as the Read Device ID code in the request packet
Conformity Level
01 Identifies the conformity level of the device to Function Code 43. 01 = basic identification, and is the only value supported by the Conext TL inverter.
More Follows 00 If there is not enough room in the packet, this field will indicate that more data follows with FF.
Next Object ID
00 Specifies the starting ID of the object in the next response if “More Follows” is FF.
Number of Objects
03 Specifies the number of objects contained in this response.
Object ID 00 The identifier for the following object: 00 = Manufacturer
Object Length 12 Specifies the length of the following object (in bytes). 0x12 = 18 bytes.
976-0301-01-01 Revision A 17
Application Note - Using Modbus With Conext™ TL Inverters
Broadcasts
Broadcast request packets from the master are supported. Broadcasts are valid only with Function 16 and are triggered by setting the slave address to zero (0). All slaves will receive and execute the request, but will not respond.
Object Data
53 63 68 6E 65 69 64 65 72 20
S c h n e i d e r
Object Data
45 6C 65 63 74 72 69 63
E l e c t r i c
Object ID 01 The identifier for the following object: 01 = Product Code
Object Length 0B Specifies the length of the following object (in bytes). 0x0B = 11 bytes.
Object Data
50 56 53 4E 56 43 32 30 30 30 30
P V S N V C 2 0 0 0 0
Object ID 02 The identifier for the following object: 01 = Product Code
Object Length 07 Specifies the length of the following object (in bytes). 0x07 = 7 bytes.
Object Data
30 30 30 2E 30 30 30
0 0 0 . 0 0 0
CRC Checksum
0D 03
18 976-0301-01-01 Revision A
Application Note - Using Modbus With Conext™ TL Inverters
Modbus Data Types
This section describes the data types supported by the inverter. The available formats may vary, depending on your inverter type and firmware.
16-bit integer format
Unsigned and signed 16-bit integer formats are the smallest addressable units when using the Modbus protocol. Each input register to the module corresponds to one 16-bit Modbus holding register output.
32-bit integer format
To accommodate values that can reach beyond the 16-bit range, the Modbus Slave module provides 32-bit integer format as an output option.
A 32-bit register is passed via communications as two 16-bit registers—one high-order register and one low-order register.
High-order register
• registerhigh=value/65536
Low-order register
• registerlow= value modulus 65536
• value = registerhigh x 65536 + registerlow or
• value = registerhigh | registerlow
Example (unsigned 32-bit):
Value 12345678 is passed in unsigned 32-bit integer format:
• 12345678 = 0x00BC614E
• Registerhigh = 0x00BC (unsigned) = 188
• Registerlow = 0x614E (unsigned) = 24910
• Value = 188 x 65536 + 24910 = 12345678
In unsigned 32-bit integer format, both the high-order and low-order registers are unsigned 16-bit integers.
Table 15 Modbus data types
Format Data type Range
UINT16 16-bit unsigned integer 0 to 65,535
INT16 16-bit signed integer -32,768 to +32,767
UINT32 32-bit unsigned integer 0 to 4,294,967,295
INT32 32-bit signed integer -2,147,483,648 to +2,147,483,647
UINT8 8-bit unsigned character 0 to 255
976-0301-01-01 Revision A 19
Application Note - Using Modbus With Conext™ TL Inverters
Example (signed 32-bit):
Value -12345678 is passed in signed 32-bit integer format:
• -12345678 = 0xFF439EB2
• Registerhigh = 0xFF43 (signed) = -189
• Registerlow = 0x9EB2 (unsigned) = 40626
• value = -189 x 65536 + 40626 = -12345678
In signed 32-bit integer format, the high-order register is a signed 16-bit number, but the low-order register is unsigned.
8-bit Unsigned Character Format
The 8-bit Unsigned Character format is used to encode ASCII strings within Modbus registers.
Characters are stored in the order they occur within the string, and populate the Most Significant Byte (MSB) of the Modbus 16-bit register followed by the Least Significant Byte (LSB) of the Modbus 16-bit register. For example, the ASCII string “HELLO!” would be encoded as 3 consecutive 16-bit registers with the values 0x4845, 0x4C4C, and 0x4F21.
Table 16 Modbus ASCII string encoding example
Register 1 Register 2 Register 3
4845 4C4C 4F21
48 45 4C 4C 4F 21
H E L L O !
20 976-0301-01-01 Revision A
Application Note - Using Modbus With Conext™ TL Inverters
Modbus Error Responses
If the inverter receives an unsupported Modbus request, it returns an exception response informing the Modbus master of the nature of the error.
The Modbus Error Response message has two fields that differentiate it from a normal response: Function Code Field, and Data Field.
Function Code Field
In a normal response, the inverter echoes the function code of the original request in the function code field of the response. All function codes have a most-significant bit (MSB) of 0 (their values are all below 0x80).
In an exception response, the inverter sets the MSB of the function code to 1. This makes the function code value in an exception response exactly 0x80 higher than the value would be for a normal response. For example, a normal response of 0x03 (Read Holding Registers), becomes 0x83 (Unable to Read Holding Registers).
Data Field
In an error response, the inverter uses the data field of the response packet to return an error code to the Modbus Master. Four error codes are supported, as shown in Table 17.
Table 17 Modbus error codes
Error code Error name Error description
01 Illegal Function The inverter does not support the function code specified in the Modbus Request Packet.
02 Illegal Address The address range specified in the Modbus Request Packet contains an illegal register address.
03 Illegal Data Value The Modbus Request Packet contains an illegal number of bytes in the data field.
04 Slave Device Failure An unrecoverable error occurred while the inverter (slave) was attempting to perform the requested action
976-0301-01-01 Revision A 21
Application Note - Using Modbus With Conext™ TL Inverters
Modbus Error Response Example
A Modbus master requests 12 registers at address 0x17F4 using the following query:
In this case, 0x17F4 is a valid address, but the range from 0x17F4 to 0x17FF has three missing registers at addresses 0x17F5, 0x17F6, and 0x17F7, so the inverter responds with an “Illegal Address” error response.
The response packet is shown in Table 19.
Table 18 Request packet
Slave Function Start registers # of registers (1) CRC checksum
C9 03 17 F4 00 0C 11 C1
Table 19 Response packet
Slave Function Error code CRC checksum
C9 83 02 41 0F
22 976-0301-01-01 Revision A
Application Note - Using Modbus With Conext™ TL Inverters
Event Logs
Events are stored whenever they occur. The maximum rate for storing is 4 events every 1.5 ms.
Event logs are time-stamped with a resolution of one millisecond.
The Logging function manages all aspects of event logging.
This function can be configured to be in different modes via the “Logger-mode” register. By default, it is set to “Log” mode where it continues to log events.
To extract any logs, the Logger has to be configured for “read” mode; in this mode, logging is stopped.
Logger Mode
The different modes of logging operation are shown in Table 21.
Table 20 Logger-mode register
Address Name Access Default Units / range
0x4705 Logger-mode R/W 0 UINT16, [0..5]
Table 21 Logger mode values
Logger-mode Action
0 Log Mode:Events will be logged. Log reading and configuration are disabled.
2 Read Event Log:The requested event will be read
5 Config Mode:Allow setting of RTC time and log interval.Allow clearing of the logs
976-0301-01-01 Revision A 23
Application Note - Using Modbus With Conext™ TL Inverters
Logger State
The state of the Logging function can be read with the Logger-state register, shown in Table 22.
The logger state is a bit field, described in Table 23. A set bit (bit = 1) indicates that status is true.
Event Log Size
The number of records stored in the log can be determined by reading register 0x4701 “Number of Event Log Records”.
Table 22 Logger-state register
Address Name Access Default Units / range
0x4706 Logger-state R 0 UINT16
Table 23 Logger State bit indicators
Bit Status
0 Board not ready (initialization not finished, communication error)
1 Log mode active
2 Read mode active
3 Config mode active
9 CRC error detected when reading NVRAM data. Data of the current record is corrupt.
10 Any other inverter error
Table 24 Number of Event Log Records register
Address Name Access Default Units / range
0x4701 Number of Event Log Records R 0 UINT16, [0..8192]
24 976-0301-01-01 Revision A
Application Note - Using Modbus With Conext™ TL Inverters
Log Request Registers
Table 25 describes the registers that control the reading of logs.
The “Log Request Index” is limited to the maximum number of records in the event log log.
When “Logger-mode” is written, you must reset the “Log Request Index” to 0. The register is only writeable when “Logger-mode” is configured to “Read Event Log”.
Index 0 means that nothing is to be read from Logger.
Index 1 means the most recent record of the event log.
The “Log Response Index” is set to the same value as the “Log Request Index” as soon as the data is available in the corresponding buffer registers. This register should be polled until the expected value is read.
To read logs:
1. Set the “Logger-mode” register to 2 (to enable reading of the event logs).
2. Write the index of the record to be read to register “Log Request Index”.
3. Poll the register “Log Response Index”. When this index equals the “Log Request Index”, the data is available in the particular buffer registers.
4. Read the buffer registers of the corresponding log.
5. Set the “Logger-mode” register to 0 (to resume logging).
Table 25 Log Request registers
Address Name Access Default Units / range
0x4703 Log Request Index R/W 0 UINT16, [0..Idx_max]
0x4704 Log Response Index R 0 UINT16, [0..Idx_max]
976-0301-01-01 Revision A 25
Application Note - Using Modbus With Conext™ TL Inverters
Event Log Record
The event log content is available from reading registers 0x4720 to 0x4726.
A record of the event log consists of 7 registers, described in Table 26.
The event log time stamp is calculated as:
(TimestampHigh * 65536) + TimestampLow + (Timestamp ms / 1000)
The event log can store a maximum of four simultaneous events. All valid events are non-zero numbers.
Clearing Logs
To clear logs:
◆ Write the value 0x2006 to the Clear Log register, described in Table 27.
Table 26 Event Log Record registers
Address Name Access Units / range
0x4720 Timestamp High R UINT32, Number of seconds since Jan 01 1970
0x4721 Timestamp Low R
0x4722 Timestamp ms R UINT16, ms, [0..999]
0x4723 Event 1 R UINT16
0x4724 Event 2 R UINT16
0x4725 Event 3 R UINT16
0x4726 Event 4 R UINT16
Table 27 Clear Log register
Address Name Access Default Units / range
0xF002 Clear Log W 0 UINT16
26 976-0301-01-01 Revision A
Application Note - Using Modbus With Conext™ TL Inverters
Conext TL Modbus MapThe Modbus map defines the location of the Conext TL registers, which can be used to retrieve status information or to control the inverter.
The Modbus map is defined as a data table, the columns of which define the register attributes. (The following sections describe each of the columns in the table.) Modbus registers are defined one per row.
The Modbus map is shown in Table 30 on page 29.
Modbus Address
Addresses in the Modbus map are zero-based and are specified in hexadecimal notation, so they correspond directly with the address field specified in the Modbus Request Packet. This makes it easier to troubleshoot when capturing data “over-the-wire”.
If you need to enter these values into the data definition file of a Modbus Master device, which is expecting a “Register Number”, you will need to convert the address to decimal (base 10), and add one to the address.
For example, the “Operational Mode State” register is at address 0x1700.
0x0x1700 = 5888 decimal.
Adding one to this gives a Register Number of 5889.
Modbus Register Description
The Description column provides brief details about the purpose of the Modbus register, for example, “Energy Since Commissioning”, or “Operational Mode State”.
Modbus Register Access type
Access types may be either “Read Only” or “R/W” (Read/Write). The values of “Read Only” registers cannot be changed via Modbus, so they cannot be used to configure or alter the behavior of the inverter in any way. “Read/Write” registers may be altered at run-time and may directly affect the operation of the inverter.
Modbus Register Units
The Units column specifies two pieces of information separated by a / symbol. The first is the units of the value contained in the register, for example, kWh, V, A, Vrms. The second is the scaling factor to convert the raw binary value contained within the register to the units specified before the / symbol.
For example, if the Units column is kWh/X10, and the raw value retrieved from the Modbus register is 24, divide this value by 10 to yield 2.4 kWh.
Table 28 Scale factor in the Units column
Scale factor Action
X1 No divide necessary: result equals raw value
X10 Divide raw value by 10 to yield the result
X100 Divide raw value by 100 to yield the result
976-0301-01-01 Revision A 27
Application Note - Using Modbus With Conext™ TL Inverters
Modbus Register Size
The Size column specifies the total size of the data at the register address specified by the Address column.
Examples:
Invalid Registers
In the inverter Modbus register map, there are gaps between some registers. For example, the next register after 0x17F4 is 0x17F8. Unmapped registers (0x17F5 through to 0x17F7) are invalid. Requests to read data from invalid registers generate an “Invalid Address” exception. When an invalid register is written, the inverter responds with an “Invalid Address” exception. For an example of this, see “Modbus Error Response Example” on page 22.
Invalid Data
If the value or data written to an address is out of range, the inverter returns ExceptionCode = 02.
For example, the valid ranges for address 0xFA61 are +80 to +100 and -80 to -100. If the value 35 or -150 is written to the address, the inverter returns ExceptionCode = 02.
Table 29 Modbus Register size and total size of data
Size Number of bytesNumber of 16-bit Modbus registers
8-bit unsigned integer x 20 20 bytes 10
32-bit unsigned integer 4 bytes 2
32-bit signed integer 4 bytes 2
16-bit signed integer 2 bytes 1
16-bit unsigned integer 2 bytes 1
28 976-0301-01-01 Revision A
Application Note - Using Modbus With Conext™ TL Inverters
Modbus Map
For a complete description of the Conext TL registers available via Modbus, see Table 30.
NOTICE
• To access the following addresses, the version of the inverter’s communication software must be higher than 1.22 (the version is displayed on the Inverter Information screen, as “Comm.-Version”):
• 0x182F (PV2 Power)
• 0xF9FB (User Phase Angle)
• 0xFA19 (User Active Power Limit)
• 0xFA1B (User Reactive Power Reference)
• From 0xFA60 (Reactive Power Mode Select) to 0xFA6E (kVar(U) Response Time)
• For “range”, the sign convention we use is from the supply network (that is, utility's) perspective, looking towards the inverter. In that context, “capacitive” means leading VArs and a positive phase angle; “inductive” means lagging VArs and a negative phase angle.
• For more information on leading and lagging power factors, see page 38.
Table 30 Modbus map
Address (hex) Description Access Units Size
0x0001 - 0x0009
Product Model Designation Read Only "C" style null terminated ASCII string
UINT8 x 18
0x0014 - 0x001D
Serial Number Read Only "C" style null terminated ASCII string
UINT8 x 20
0x0082 - 0x008B
Software Part Number for Processor A
Read Only "C" style null terminated ASCII string
UINT8 x 20
0x0096 - 0x009F
Software Part Number for Processor B
Read Only "C" style null terminated ASCII string
UINT8 x 20
0x00AA- 0x00B3
Software Part Number for Processor C
Read Only "C" style null terminated ASCII string
UINT8 x 20
976-0301-01-01 Revision A 29
Application Note - Using Modbus With Conext™ TL Inverters
0x0802 (H word) - 0x0803 (L word)
Energy Since Commissioning
Read Only KWhr/X10 UINT32
0x0804 (H word), 0x805 (L word)
Energy Today Read Only KWhr/X10 UINT32
0x0806, 0x807
Energy Today (1 day earlier)
Read Only KWhr/X10 UINT32
0x0808, 0x809
Energy Today (2 days earlier)
Read Only KWhr/X10 UINT32
0x080A, 0x80B
Energy Today (3 days earlier)
Read Only KWhr/X10 UINT32
0x080C, 0x80D
Energy Today (4 days earlier)
Read Only KWhr/X10 UINT32
0x080E, 0x80F
Energy Today (5 days earlier)
Read Only KWhr/X10 UINT32
0x0810, 0x811
Energy Today (6 days earlier)
Read Only KWhr/X10 UINT32
0x081E, 0x081F
Operating Hours Read Only Hr/x1 UINT32
0x1700 Operational Mode State Read Only Enum
• 0x0002 Reconnecting (Conext TL Countdown)
• 0x0003 Online (Conext TL ON)
• 0x0014 Standby
• 0x0015 No DC
• 0x0016 Alarm
UINT16
0x1701 Temperature 1, NTC on control board
Read Only C/X10 INT16
Table 30 Modbus map (Continued)
Address (hex) Description Access Units Size
30 976-0301-01-01 Revision A
Application Note - Using Modbus With Conext™ TL Inverters
0x1702 Temperature 2, Boost module 1
Read Only C/X10 INT16
0x1703 Temperature 3, Boost module 2
Read Only C/X10 INT16
0x1704 Temperature 4, Inverter module
Read Only C/X10 INT16
0x17F1 Apparent Power Read Only kVA/x10 UINT16
0x17F4 Reactive Power Read Only kVAr/X10 INT16
0x17F8 Inverter Vab Read Only Vrms/X10 INT16
0x17F9 Inverter Vbc Read Only Vrms/X10 INT16
0x17FA Inverter Vca Read Only Vrms/X10 INT16
0x17FB Phase A Current Read Only Arms/X10 INT16
0x17FC Phase B Current Read Only Arms/X10 INT16
0x17FD Phase C Current Read Only Arms/X10 INT16
0x17FE Real Power (Total) Read Only kW/X10 INT16
0x17FF PV1 Voltage Read Only V/X10 INT16
0x1800 PV1 Current Read Only A/X10 INT16
0x1801 PV1 Power Read Only kW/X10 INT16
0x1828 Fault Code Read Only See the Conext TL Installation and Operation Manual
UINT16
0x180D DC Voltage Read Only V/X10 UINT16
0x1818 Phase A Frequency Read Only Hz/x10 UINT16
0x1819 Phase B Frequency Read Only Hz/x10 UINT16
0x181A Phase C Frequency Read Only Hz/x10 UINT16
0x181B Phase A Real Power Read Only kW/x10 INT16
0x181C Phase B Real Power Read Only kW/x10 INT16
0x181D Phase C Real Power Read Only kW/x10 INT16
0x1829 PV2 Voltage Read Only V/X10 INT16
Table 30 Modbus map (Continued)
Address (hex) Description Access Units Size
976-0301-01-01 Revision A 31
Application Note - Using Modbus With Conext™ TL Inverters
0x182A PV2 Current Read Only A/X10 INT16
0x182F PV2 Powera Read Only kW/X10 INT16
0xF9FB User Phase Anglea
Note: You can use either this register or register 0xFA61 (Cos(φ); page 33) to specify the angle. The inverter uses the value from the most recently written of the two registers.
R/W Increments of 1 degrees
Range: +37 capacitive (leading) to -37 inductive (lagging)
Default = 0 degrees
INT16
0xFA19 User Active Power Limita R/W kW/X10 UINT16
0xFA1B User Reactive Power Referencea
Note: You can use either this register or register 0xFA66 (Fixed kVAr %; page 34) to specify the amount of reactive power sourced (capacitive) or sinked (inductive) by the inverter. The inverter uses the value from the most recently written of the two registers.
R/W kVAr/X10
Positive numbers make the inverter look capacitive (leading VAr) to the grid.
Negative numbers make the inverter look inductive (lagging VAr) to the grid.
INT16
0xFA60 Reactive Power Mode Selecta
R/W • 0 : Disable (Default)
• 1 : Fixed cos(φ)
• 2 : cos(φ) as function of P
• 3 : Fixed kVAr
• 4 : kVAr as function of U
UINT16
Table 30 Modbus map (Continued)
Address (hex) Description Access Units Size
32 976-0301-01-01 Revision A
Application Note - Using Modbus With Conext™ TL Inverters
0xFA61 Fixed Cos(φ)a
Note: You can use either this register or register 0xF9FB (User Phase Angle; page 32) to specify the angle. The inverter uses the value from the most recently written of the two registers.
R/W Increment = 1 unit
Range:
• Capacitive 0.80 to 1.00.Enter: +80 to +100
• Inductive: 0.80 to 1.00.Enter: -80 to -100
Default: 100
INT16
0xFA62 Cos(φ) with Powera
Upper limit
R/W Increment = 1 unit
Range:
• Capacitive 0.80 to 1.00.Enter: +80 to +100
• Inductive: 0.80 to 1.00.Enter: -80 to -100
Default: 90
INT16
0xFA63 Cos(φ) with Powera
Lower limit
R/W Increment = 1 unit
Range:
• Capacitive 0.80 to 1.00.Enter: +80 to +100
• Inductive: 0.80 to 1.00.Enter: -80 to -100
Default: -90
INT16
0xFA64 Cos(φ) with % powera
Lower limit
R/W Increment = 1%
Range: 0~100%
Default: 0%
UINT16
Table 30 Modbus map (Continued)
Address (hex) Description Access Units Size
976-0301-01-01 Revision A 33
Application Note - Using Modbus With Conext™ TL Inverters
0xFA65 Cos(φ) with % powera
Upper limit
R/W Increment = 1%
Range: 0~100%
Default: 100%
UINT16
0xFA66 Fixed kVAr %a
Note: You can use either this register or register 0xFA1B (User Reactive Power Reference; page 32) to specify the reactive power either sourced or sinked by the inverter. The inverter uses the value from the most recently written of the two registers.
R/W Increment = 1%
Range: -53 to +53%
Default: 0%
Positive numbers make the inverter look capacitive (leading VAr) to the grid.
Negative numbers make the inverter look inductive (lagging VAr) to the grid.
INT16
0xFA67 kVAr(U) as %a
Upper limit
R/W Increment = 1%
Range: -53 to +53%
Default: 44%
INT16
0xFA68 kVAr(U) as %a
Lower limit
R/W Increment = 1%
Range: -53 to +53%
Default: -44%
INT16
0xFA69 kVAr(U)a
Vmin
R/W Unit: 0.1 V
Range: 100~264 V
Default: 184 V
UINT16
0xFA6A kVAr(U)a
Vmax
R/W Unit: 0.1 V
Range: 100~264 V
Default: 253 V
UINT16
0xFA6B kVAr(U)a
UAC Lower limit
R/W Unit: 0.1 V
Range: 100~264 V
Default: 230 V
UINT16
Table 30 Modbus map (Continued)
Address (hex) Description Access Units Size
34 976-0301-01-01 Revision A
Application Note - Using Modbus With Conext™ TL Inverters
0xFA6C kVAr(U)a
UAC Upper limit
R/W Unit: 0.1 V
Range: 100~264 V
Default: 230 V
UINT16
0xFA6D kVAr(U)a
Hysteresis
R/W Unit: 0.1 V
Range: 0~30 V
Default: 0 V
UINT16
0xFA6E kVAr(U)a
Response Time
R/W Unit: 0.01 sec
Range: 10~60 sec
Default: 10 sec
UINT16
0x4701 Number of Event Log Records
Read Only NA
0x4703 Log Request Index R/W NA INT16
0x4704 Log Response Index Read Only NA INT16
0x4705 Logger-mode R/W NA INT16
0x4706 Logger-state Read Only NA INT16
0x4720 Timestamp High Read Only NA INT16
0x4721 Timestamp Low Read Only NA INT16
0x4722 Timestamp ms Read Only NA INT16
0x4723 Event 1 Read Only NA INT16
0x4724 Event 2 Read Only NA INT16
0x4725 Event 3 Read Only NA INT16
0x4726 Event 4 Read Only NA INT16
0xF002 Clear Log Write Only NA INT16
a.Communication software version must be higher than 1.22.
Table 30 Modbus map (Continued)
Address (hex) Description Access Units Size
976-0301-01-01 Revision A 35
Application Note - Using Modbus With Conext™ TL Inverters
Appendix A: CRC-16 calculationThis appendix describes how to obtain the CRC-16 error check field for a Modbus RTU frame.
A frame can be considered as a continuous, serial stream of binary data (ones and zeros). The 16-bit checksum is obtained by multiplying the serial data stream by 216 (10000000000000000) and then dividing it by the generator polynomial x16+x15+x2+1, which can be expressed as the 16-bit binary number 11000000000000101.
The quotient is ignored and the 16-bit remainder is the checksum, which is appended to the end of the frame.
In calculating the CRC, all arithmetic operations (additions and subtractions) are performed using MODULO TWO, or EXCLUSIVE OR operation. A step-by-step example shows how to obtain the checksum for a simple Modbus RTU frame.
To generate the CRC-16 checksum:
1. Drop the MSB (Most Significant Bit) of the generator polynomial and reverse the bit sequence to form a new polynomial. This yields the binary number 1010 0000 0000 0001, or 0xA001.
2. Load a 16-bit register with initial value 0xFFFF.
3. Exclusive OR the first data byte with the low-order byte of the 16-bit register. Store the result in the 16-bit register.
4. Shift the 16-bit register one bit to the right.
5. If the bit shifted out to the right is one (1), Exclusive OR the 16-bit register with the new generator polynomial, store the result in the 16-bit registers. Return to step 4.
6. If the bit shifted out to the right is zero (0), return to step 4.
7. Repeat steps 4 and 5 until 8 shifts have been performed.
8. Exclusive OR the next data byte with the 16-bit register.
9. Repeat steps 4 through 7 until all bytes of the frame are Exclusive OR with the 16-bit register and shifted 8 times.
The content of the 16-bit register is the checksum and is appended to the end of the frame.
36 976-0301-01-01 Revision A
Application Note - Using Modbus With Conext™ TL Inverters
Pseudocode For CRC-16 Generation
For users familiar with computer programming, the following is the pseudocode for calculating the 16-bit Cyclic Redundancy Check.
Initialize a 16-bit register to 0xFFFF
Initialize the generator polynomial to 0xA001
FOR n=1 to # of bytes in packet
BEGIN
XOR nth data byte with the 16-bit register
FOR bits_shifted = 1 to 8
BEGIN
SHIFT 1 bit to the right
IF (bit shifted out EQUAL 1)
XOR generator polynomial with the 16-bit register andstore result in the 16-bit register
END
END
The resultant 16-bit register contains the CRC-16 checksum.
976-0301-01-01 Revision A 37
Application Note - Using Modbus With Conext™ TL Inverters
Appendix B: Leading and Lagging Power Factors
Notes on the above figure:
• All the above is as seen from the utility’s perspective (looking toward the inverter).
• The direction of reactive power flow determines leading or lagging power factor.
• The terms leading and lagging always refer to the current with respect to the voltage.
38 976-0301-01-01 Revision A
Application Note - Using Modbus With Conext™ TL Inverters
In the above figure:
• S = Apparent power; has dimensions of volt-amps (VA)
• P = Active or real power; has dimensions of watts (W)
• Q = Reactive power; has dimensions of volt-amp-reactive (VAr)
• PF = power factor; has no units. It is defined as the cosine of angle (the ratio of P over S)
976-0301-01-01 Revision A 39
Application Note - Using Modbus With Conext™ TL Inverters
Schneider Electric, the Schneider Electric logo, and Conext are trademarks or registered trademarks of the Schneider Electric group of companies. Other trademarks, registered trademarks, and product names are the property of their respective owners and are used herein for identification purposes only.
Copyright © 2012 Schneider Electric SA. No part of this document may be reproduced in any form or disclosed to third parties without the express written consent of:Schneider Electric SA35 rue Joseph Monier92500 Rueil Malmaison - FranceThis documentation may be revised and content hereof changed from time to time without obligation to notify any person or entity or to organize such revisions or changes unless required to do so by prior arrangement.
Exclusion for DocumentationUNLESS SPECIFICALLY AGREED TO IN WRITING, SELLER(A) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION;(B) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMAGES, COSTS OR EXPENSES, WHETHER SPECIAL, DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER’S RISK; AND(C) REMINDS YOU THAT IF THIS MANUAL IS IN ANY LANGUAGE OTHER THAN ENGLISH, ALTHOUGH STEPS HAVE BEEN TAKEN TO MAINTAIN THE ACCURACY OF THE TRANSLATION, THE ACCURACY CANNOT BE GUARANTEED. APPROVED CONTENT IS CONTAINED WITH THE ENGLISH LANGUAGE VERSION WHICH IS POSTED AT WWW.SCHNEIDER-ELECTRIC.COM.
Date: March 2012 Revision: Revision A Document Number: 976-0301-01-01
Contact Informationwww.schneider-electric.com
☎ ✉N. America 1 408 987 6255 1 925 245 1022 re.techsupport@schneider-
electric.com
France +33 (0) 825 012 999
Deutschland +49 (0) 180 575 3 575 +49 (0) 2102 404 7101 [email protected]
España +34 902 101813 +34 93 305 5026 [email protected]
L'Italia +39 035 4151111 +39 035 4153200 [email protected]
Nederland 0031 235 124124 0031 235 124111 [email protected]
For other country details please contact your local Schneider Electric Sales Representative or visit our website at:http://www.schneider-electric.com/sites/corporate/en/support/operations/local-operations/local-operations.page
40 976-0301-01-01 Revision A
Effective 2013.09.01
Conext TL_cwtc_rscog_row_eng_v2.1_130901 Page 1 of 4
SCHNEIDER ELECTRIC CONTRACTUAL WARRANTY
This Schneider Electric Contractual Warranty applies to the following products:
CONEXT TL Small Three Phase Inverters Models: PVSNVC8000, PVSNVC10000, PVSNVC15000, PVSNVC20000
Geographic Validity:
Europe, Middle East, Caribbean, Australia, India, Indonesia, Malaysia, Singapore, Taiwan, Thailand, Vietnam, Brazil, Chile, Mexico
Length of Warranty:
5 years unless applicable law requires a longer period in which case it will be that period of time
“Schneider Electric” means the local legal entity of Schneider Electric that sold you (either directly or indirectly) the products.
“Product” means the Schneider Electric or related branded inverter product ( or other related device as identified above ) that you purchased from Schneider Electric or through an authorized reseller or retailer.
1. Warranty Claims
This Contractual Warranty is provided by Schneider Electric and covers defects in workmanship and materials in your Product. This warranty period lasts from the date of purchase at the point of sale to you, the original end user, unless otherwise agreed in writing (the "Warranty Period"). This Contractual Warranty is transferable to subsequent owners but only for the unexpired portion of the Warranty Period. 2. Warranty Coverage
If a Product becomes defective within the Schneider Electric Contractual Warranty Period, one of the following options, as selected by Schneider Electric, will be performed at no charge for materials or labor costs, unless this should be impossible or disproportionate. It is mandatory that customer notify Schneider Electric of the Product defect within the Warranty Period, and provided that Schneider Electric, or designated service partner, through inspection establishes the existence of such a defect and that it is covered by this Contractual Warranty: Repairing the Product onsite, Repairing the Product at Schneider Electric, or designated repair facility, or Exchange the Product with a Replacement Product (of equivalent value according to model and age) Alternatively, at Schneider Electric's sole discretion, cash compensation equal to the Product’s residual value may be offered1. The term “disproportionate” applies in particular if the costs to Schneider Electric were deemed unreasonable according to the following criteria:
With reference to the value the Product would have without the defect Taking into account the significance of the defect, and After consideration of alternative workaround possibilities available to the customer without significant inconvenience
1as determined by annual linear method
Effective 2013.09.01
Conext TL_cwtc_rscog_row_eng_v2.1_130901 Page 2 of 4
If Schneider Electric, or designated service partner, repairs or replaces a Product, its warranty continues for the remaining portion of the original Warranty Period, or six (6) months from the date of the return shipment to the customer, whichever is greater. All replaced Products and all parts removed from repaired Products become the property of Schneider Electric. 3. Warranty Limitations
This Contractual Warranty does not warrant uninterrupted or error-free operation of the Product or cover normal wear and tear of the Product or costs related to the removal, installation, or troubleshooting of the customer's electrical systems. The warranty claims that relate to defects caused by any of the following factors are not covered by the Contractual Warranty: Improper Use or Non-compliance with installation, commissioning, operation or maintenance instructions (i.e. not according to the
operation & installation manual) Unauthorized modifications, changes or attempted repairs, Vandalism, destruction through external influence and/or persons/animals Use in an unsuitable environment, including any environment or location that causes excessive wear and tear or dirt or dust or debris
buildup within the system or that is difficult or unsafe for Schneider Electric representatives to access Insufficient ventilation Installation in a corrosive environment Failure to observe applicable safety standards & regulations Damages during transportation or storage Force majeure, examples include, but not limited to: fire, flood, earthquakes, storm damage, overvoltage & lightning strikes Exposure to fire, water, snow, moisture, or liquid ingress (except for any such exposure to environmental conditions that your Product
was specifically designed to withstand as indicated in the applicable specifications for your Product) Used as a component part of another product expressly warranted by another manufacturer If the original identification (trade-mark, serial number) markings have been defaced, altered, or removed Consumable components of any type are not covered, including but not limited to fuses and filters, etc. Cosmetic shortcoming which do not impair the use of the Product for the intended purpose i.e. supply of energy Warranty claims also exclude: Damages arising due to the fact that the use of the Product for the intended purpose is no longer possible or only possible with
restrictions as a result of amendments to the statutory provisions applicable to the operation of the Product made after the delivery of the Product
Compensation for damages related to loss of power production or business operation or any expenses incurred by customer towards repair & replacement of the Product (including but not limited to labor, transportation, temporary power)
Cost arising from changes to existing PV systems or building installations and like Additional costs and expenses (i.e. shipping costs, travel, accommodation, meals, etc.) arising due to remote locations of the
indicated geographies, including but not limited to islands and overseas territories 4. Warranty Return and Repair Process
Contact Schneider Electric Customer Service representative with brief description of the error to evaluate & troubleshoot the issue while Product is in the field as many problems can be solved on site. Please contact your Local Schneider Electric Customer Service Center or visit our website at:
http://www.schneider-electric.com/sites/corporate/en/support/operations/local-operations/local-operations.page
i. Return Material Authorization (RMA)
After attempts to correct the problem with customer’s assistance, if the Product must be returned to Schneider Electric or designated service partner for replacement or repair, the customer must obtain a Return Material Authorization (RMA) number and the correct return center "Ship To" address. Product shipments will be refused and returned at your expense if they are unauthorized or returned without an RMA number clearly marked on the outside of the shipping box or if they are shipped collect or if they are shipped to the wrong location. When you contact Schneider Electric to obtain service, please have your instruction manual ready for reference and be prepared to supply: The serial number and product code of your Product Information about the installation or inspection certificate Information about the failure and/or reason for the return A copy of your dated proof of purchase
Effective 2013.09.01
Conext TL_cwtc_rscog_row_eng_v2.1_130901 Page 3 of 4
Schneider Electric reserves the right to refuse exchange requests for lack of proper documentation and information.
ii. Once an RMA has been issued for exchange
Schneider Electric will generally ship an equivalent replacement Product to the specified customer or the distributor location within 48-72 hours. The allegedly defective Product must be returned to Schneider Electric in the same transport packaging that the replacement unit was provided in. Schneider Electric will supply all labels and documentation for the return of the defective Product. The defective Product must be shipped back to Schneider Electric within 10 working days after receiving the replacement Product. If we do not receive the Product within this timeframe, the unit cost will be billed back to the customer (including shipping and handling fees).
iii. Once an RMA has been issued for repair Schneider Electric will arrange for the repair of the Product on-site or at a repair facility. The allegedly defective Product being returned for repair at Schneider Electric, or designated service partner, must be packaged in a suitable manner to prevent damage during transportation (equivalent to original packaging or better). Schneider Electric will provide the necessary instructions to correctly ship the Product (including designated freight carrier, documentation information, address, etc.) to the repair facility.
Standard ground shipping costs are covered by Schneider Electric both ways. Any expedited shipping costs will be the responsibility of the customer and billed accordingly. Visually evident damage caused by shipping or mishandling is to be reported to the freight carrier within 24 hours. Shipping damage is the responsibility of the freight carrier, not Schneider Electric, and should always be duly noted with the freight carrier prior to accepting and signing for the Product. Any Products that are damaged during the returned shipping process are not covered by this warranty. Schneider Electric assumes no liability for this damage. 5. Service Reimbursement
Schneider Electric in its sole discretion may offer a service reimbursement for the services of a qualified installer performing specific Product replacement and re-commissioning under the terms of this warranty. Please contact your local Schneider Electric office for details and application related to your Product. 6. Invalid Warranty Claim
If the returned defective Product to Schneider Electric (or service partner) pursuant to this Policy, and is found by Schneider Electric to be free of defects that would qualify it for repair or replacement under this Policy, Schneider Electric will charge a flat-rate inspection charge for each Product of €2002, plus shipping and packaging costs. In the event the defect free unit is returned to the customer then to also charge for the replacement unit. 7. Out of Warranty Service
If the Warranty Period for your Product has expired, if the unit was damaged by misuse or incorrect installation, if other conditions of the warranty have not been met, or if no dated proof of purchase is available, your unit may be serviced or replaced for a flat fee, as determined by Schneider Electric in its sole discretion. Please contact your local Schneider Electric office to determine if out of warranty service is available for your Product. To return your Product for out of warranty service, contact Schneider Electric Customer Service for a Return Material Authorization (RMA) number and follow the appropriate steps outlined in "Return Procedure". Payment options such as credit card or money order will be explained by the Customer Service Representative. In cases where the minimum flat fee does not apply, as with incomplete units or units with excessive damage, an additional fee will be charged. If applicable, you will be contacted by Customer Service once your unit has been received.
2 or equivalent in local currency at the sole discretion of Schneider Electric
Effective 2013.09.01
Conext TL_cwtc_rscog_row_eng_v2.1_130901 Page 4 of 4
8. Disclaimer of Implied and Other Warranties and Limitation of Liability
THIS CONTRACTUAL WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY PROVIDED BY SCHNEIDER ELECTRIC IN CONNECTION WITH YOUR SCHNEIDER ELECTRIC PRODUCT AND IS, WHERE PERMITTED BY LAW, IN LIEU OF ALL OTHER WARRANTIES, CONDITIONS, GUARANTEES, REPRESENTATIONS, OBLIGATIONS AND LIABILITIES, EXPRESS OR IMPLIED, STATUTORY OR OTHERWISE IN CONNECTION WITH THE PRODUCT, HOWEVER ARISING (WHETHER BY CONTRACT, TORT, NEGLIGENCE, PRINCIPLES OF MANUFACTURER'S LIABILITY, OPERATION OF LAW, CONDUCT, STATEMENT OR OTHERWISE), INCLUDING WITHOUT RESTRICTION ANY IMPLIED WARRANTY OR CONDITION OF QUALITY, MERCHANTABILITY, MERCHANTABLE QUALITY, OR FITNESS FOR A PARTICULAR PURPOSE. ANY IMPLIED WARRANTY OR CONDITION OF MERCHANTABILITY, MERCHANTABLE QUALITY, OR FITNESS FOR A PARTICULAR PURPOSE TO THE EXTENT REQUIRED UNDER APPLICABLE LAW TO APPLY TO THE PRODUCT SHALL BE LIMITED IN DURATION TO THE PERIOD STIPULATED UNDER THIS CONTRACTUAL WARRANTY. IN NO EVENT WILL SCHNEIDER ELECTRIC BE LIABLE FOR: (A) ANY SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES, INCLUDING LOST PROFITS, LOST REVENUES, FAILURE TO REALIZE EXPECTED SAVINGS, OR OTHER COMMERCIAL OR ECONOMIC LOSSES OF ANY KIND, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED, OR HAD REASON TO KNOW, OF THE POSSIBILITY OF SUCH DAMAGE; (B) ANY LIABILITY ARISING IN TORT, WHETHER OR NOT ARISING OUT OF SCHNEIDER ELECTRIC 'S NEGLIGENCE, AND ALL LOSSES OR DAMAGES TO ANY PROPERTY OR FOR ANY PERSONAL INJURY OR ECONOMIC LOSS OR DAMAGE CAUSED BY THE CONNECTION OF A PRODUCT TO ANY OTHER PRODUCT OR SYSTEM; AND (C) ANY DAMAGE OR INJURY ARISING FROM OR AS A RESULT OF MISUSE OR ABUSE, OR THE INCORRECT INSTALLATION, INTEGRATION OR OPERATION OF THE PRODUCT BY PERSONS NOT AUTHORIZED BY SCHNEIDER ELECTRIC. LIMITATION OF LIABILITY WHERE APPLICABLE LAW ALLOWS AND DOES NOT PROHIBIT OR RESTRICT SUCH LIMITATION, SCHNEIDER ELECTRIC’S LIABILITY FOR ANYTHING RELATING TO THIS PRODUCT SHALL BE LIMITED TO THE PRICE PAID FOR THE PRODUCT. IF APPLICABLE LAW DOES NOT ALLOW AN EXCLUSION OF IMPLIED WARRANTIES, LIMITATION OF LIABILITY, ON THE DURATION OF AN IMPLIED WARRANTY, OR ON THE LIMITATION OR EXCLUSION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, THE ABOVE LIMITATION(S) OR EXCLUSION(S) WILL ONLY APPLY TO THE EXTENT PERMITTED BY APPLICABLE LAW. THIS CONTRACTUAL WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS. YOU MAY HAVE OTHER RIGHTS WHICH WILL VARY FROM JURISDICTION TO JURISDICTION.
Grid-tie, off-grid solar and backup power solutionsFor residential and commercial installations
2
Grid-tie and off-grid backup PV solutions
Smarter investment in photovoltaic solutions forall grid-tie, off-grid solar and backup installations
When it comes to grid-tie and off-grid and backup residential and commercial installations, Schneider Electric has both the experience and the proven technology to help make your investment a success.
Schneider Electric solutions for residential and commercial installations are specially designed by keeping your needs in mind. Our balance-of-system solutions include everything you need to efficiently distribute and manage locally generated solar energy, from the DC output to the AC grid connection.
Partnering with Schneider Electric gives you a higher return on investment and peace of mind
Broadportfoliofor your grid-tie and off-grid installations
Bestin classproducts
Globalsupportpresence in 100 + countries
Superiortechnicalservice
Schneider Electric is ranked among Top 3 Most Competitive Inverter Companies in the world according to GTM Research
3
Why choose Schneider Electric's solar products and solutions?
True bankability
Higher return on investment
Designed for reliability
Flexible
Easy to service
Easy to install
4
Grid-tie and off-grid backup PV solutions
Solutions to cover all customer needs
Grid-tie residential and commercial building solutions1. Residential buildings2. Commercial buildings and carports3. Decentralised PV plants
1
2
4
5
6
7
5
Off-grid solar and backup power solutions
9
3
8
10
4. Residential off-grid solar5. Residential backup power6. Residential grid-interactive solar with battery backup7. Remote community electrification
8. Commercial off-grid solar9. Commercial backup power10. Commercial grid-interactive solar with battery backup
6
Grid-tie and off-grid backup PV solutions
Acce
ssor
ies
Unique portfolio of grid-tie, off-grid solarand backup power products
Small 3-phase transformerless grid-tie inverters1-phase grid-tie inverter
Conext RL(3, 4, 5 kW)
Conext Monitor 20
Mon
itorin
g
Residential buildings Commercial buildings and carports Decentralised PV plants
PV emergencybox
DC box
AC box AC distribution box
Circuit protectors and switches
Conext TL(8, 10 kW)
Conext TL(15, 20 kW)
7
Acce
ssor
ies
Inverters/chargers and charge controllers
Conext XW(4, 4.5, 6 kW)
MPPT 80 600
Universal DC Breaker Panel
System Control Panel (SCP)
AC Breaker Panel(120 / 240 V)
Automatic Generator Start (AGS)
AC Breaker Panel(230 V)
XW Power Distribution Panel (PDP)
C12 / C60MPPT 60 150
Residential off-grid solarand backup power
Commercial off-grid solar and backup power
Remote communityelectrification
Conext SW(2.5, 4 kW)
Mon
itorin
g
Conext ComBox
Grenoble, FranceCommercial rooftop 50 kWp
9
Conext RL ACdistribution
box
PV modules DC boxPV emergencybox
AC box Grid
Emergencystop
PV emergencycontrol
Schneider Electric solutions for grid-tie residential and commercial building applications include everything you need from the DC output to the grid connection.
Conext TLEmergencystop
ACdistribution
box
LV/MVtransformer
PVmodules
DC boxPVemergency
box
AC box
PV emergencycontrol
LV/MVswitchgear
GridMonitoring
Using Conext TL inverters in a decentralised PV architecture, the PV array is broken up into smaller sub-arrays, each with its own small power string inverters.
Commercial buildings and decentralised PV plants solutions using Conext TL
Residential solar solution using Conext RL
Designing your grid-tie residential and commercial solar solutions
10
Grid-tie and off-grid backup PV solutions
Why choose Conext RL?
True bankability
Warranty from a trusted partner with over 177 years of experience
World leader in industrial power drives, UPS and electrical distribution
Strong service infrastructure worldwide to support your global needs
Higher return on investment
Best in class conversion efficiency: 97.5% peak efficiency
Broad operating range to harvest more energy (early mornings and late afternoons)
Higher ROI with dual MPPT
Shade tolerant MPPT algorithm designed to minimize the effect of partial shading on the energy output
Designed for reliability
Robust design through rigorous Multiple Environmental Over Stress Testing (MEOST) and Temperature Humidity Bias (THB)
IP65 compliant rugged, completely sealed unit to stand the harshest environmental conditions
Flexible
Dual MPPTs with wide MPPT voltage range (160-500V*) to support multiple roof orientations
Ability to support unbalanced arrays
Local as well as remote monitoring options available to track PV plant performance
Easy to service
No moving parts (e.g. fans) for low maintenance and increased uptime
Easily replaceable communication card
Integrated DC switch (optional)
Easy to install
Conext RL single-phase grid-tie inverter
The Schneider Electric Conext™ RL inverters are specially designed to maximize yields for a wide range of rooftops of detached houses and multiple dwellings. The rich MPPT features, high energy efficiency, partial shading algorithm and a wide temperature and voltage operating range enables you to maximize your ROI. Backed by Schneider Electric’s global service infrastructure and expertise in energy management, the Conext RL series are the inverters you can trust for quality and reliability.
Flexible and efficient residential solar solution
Available in 3, 4 and 5 kW
Product applications
Flat roofs
Multiple pitched roofs
Partial shading
Odd number of modules
Different orientation roofs
(East − West)
11
Device short name RL 3000 E RL 4000 E RL 5000 E*Electrical specificationsInput (DC)MPPT voltage range, full power 160 - 500 V 180 - 500 V 180 - 500 V
Operating voltage range 90 - 550 V 90 - 550 V 90 - 550 V
Starting voltage 100 V 100 V 100 V
Max. input voltage, open circuit 550 V 550 V 550 V
Number of MPPT 2 2 2
Max. input current per MPPT 10 A 12 A 18 A
Max. short circuit current per MPPT 13.9 A 16.7 A 25.0 A
Nominal input power for max. output 3.2 kW 4.2 kW 5.3 kW
Max. DC input power per MPPT 3.2 kW 3.2 kW 3.5 kW
DC connection type MC4, 2 pairs (1+1) MC4, 4 pairs (2+2) MC4, 4 pairs (2+2)
DC switch Integrated (optional) Integrated (optional) Integrated (optional)
Output (AC)Nominal output power 3 kVA 4 kVA 5 kVA
Nominal output voltage 230 V, single-phase 230 V, single-phase 230 V, single-phase
Isolation Transformerless Transformerless Transformerless
AC voltage range 184 V - 276 V 184 V - 276 V 184 V - 276 V
Max. output current 13.9 A 18.2 A 23.2 A
Total harmonic distortion <3 % <3 % <3 %
Power factor (adjustable) 0.8 lead to 0.8 lag 0.8 lead to 0.8 lag 0.8 lead to 0.8 lag
AC connection type IP67 connector IP67 connector IP67 connector
EfficiencyPeak 97.5% 97.5% 97.5%
European 97.0% 97.0% 97.0%
General specificationsPower consumption, night time <1 W <1 W <1 W
IP degree of protection IP65 (electronics and balance) IP65 (electronics and balance) IP65 (electronics and balance)
Climatic category (per IEC 60721-3-4) 4K4H 4K4H 4K4H
Cooling Natural convection Natural convection Natural convection
Enclosure material Aluminium Aluminium Aluminium
Product weight 20.0 kg (44.1 lb) 21.0 kg (46.3 lb) 24.0 kg (52.9 lb)
Shipping weight 25.0 kg (55.1 lb) 25.0 kg (55.1 lb) 30.0 kg (66.1 lb)
Product dimensions (H x W x D) 42.0 x 48.0 x 16.0 cm 42.0 x 48.0 x 16.0 cm 44.5 x 51.0 x 17.7 cm (16.5 x 18.9 x 6.3 in) (16.5 x 18.9 x 6.3 in) (17.5 x 20.1 x 7.0 in)
Shipping dimensions (H x W x D) 50.5 x 59.5 x 29.5 cm 50.5 x 59.5 x 29.5 cm 56.6 x 61.9 x 33.1 cm
(19.9 x 23.4 x 11.6 in) (19.9 x 23.4 x 11.6 in) (22.3 x 24.4 x 13.0 in)
Ambient air temperature for operation -20 to 65ºC (-4ºF to 149ºF)** -20 to 65ºC (-4ºF to 149ºF)** -20 to 65ºC (-4ºF to 149ºF)**
Operating altitude Up to 2000 m Up to 2000 m Up to 2000 m
Relative humidity 4 - 100% condensing 4 - 100% condensing 4 - 100% condensing
Noise emission (at 1 m distance) <40 dbA <40 dbA <40 dbA
Features and optionsEmbedded data logger 365 days
Display LCD 2 -line 16 digits, 2 Buttons
Multifunction relay Yes
Regulatory approvals
Environmental RoHS, REACH
EMC CE marked for the EMC directive 2004-108-EC Emissions: EN 61000-6-3 (residential) Immunity: EN 61000-6-2 (industrial)
Available product variantsStandard PVSNVC3000 (RL 3000 E) PVSNVC4000 (RL 4000 E) PVSNVC5000 (RL 5000 E)
With integrated DC switch PVSNVC3000S (RL 3000 E-S) PVSNVC4000S (RL 4000 E-S) PVSNVC5000S (RL 5000 E-S)
Monitoring accessoriesLocal monitoring Ethernet card (PVSCMC1105)
Remote monitoring Conext Monitor 20 (PVSCMC1120) Specifications are subject to change without notice. *4.6 kW for Germany. **-20°C cold start remperature.
12
Grid-tie and off-grid backup PV solutions
Why choose Conext TL?
True bankability
Warranty from a trusted partner with over 177 years of experience
World leader in industrial power drives, UPS and electrical distribution
Strong service infrastructure worldwide to support your global needs
Higher return on investment
High conversion efficiency: >98% peak efficiency
Broad operating range to harvest more energy (early mornings and late afternoons)
Higher ROI with dual MPPT
Great value for money: DC switch, AC connectors and RS485 ports are included
Designed for reliability
Robust design through rigorous Multiple Environmental Over Stress Testing (MEOST) and Temperature Humidity Bias (THB)
IP65 compliant rugged, completely sealed unit to stand the harshest environmental conditions
Design and qualified for applications in tropical environments through conformal coating and salt fog testing
Flexible
Wide MPPT voltage range (350 - 850 V)
Modular system designs using a combination of models
Easy to connect to third party monitoring solutions
Easy to service
Easily replaceable fan block and communications card
Integrated DC switch
Ability to remotely disable
Easy to install
Easy and fast mounting with included bracket
Pluggable AC and DC Connectors (MC4)
Product applications
Commercial buildings
Decentralised PV plants
Carports
The new Conext™ TL 8, 10, 15 kW and TL 20 kW grid-tie solar inverters are suited for outdoor use and are the ideal solution for commercial buildings, carports and decentralised PV plants up to the MW range. The inverters provide dual MPP (Maximum Power Point) trackers with a wide voltage range, peak efficiency of greater than 98% for fast ROI. The embedded Modbus communication card allows connectivity with a large range of Schneider Electric products, as well as the option to easily add third party monitoring solutions. Backed by Schneider Electric’s global service infrastructure and its expertise in energy management, the Conext TL series are the inverters you can trust for quality and reliability.
Available in15 and 20 kW
Available in8 and 10 kW
Conext TL three-phase grid-tie inverters
Ideal solution for commercial buildings, carports and decentralised power plants
13
Device short name TL 8000 E TL10000 E TL 15000 E TL 20000 E Electrical specificationsInput (DC)MPPT voltage range, full power 350 - 850 V 350 - 850 V 350 - 800 V 350 - 800 V
Operating voltage range 200 - 1000 V 200 - 1000 V 200 - 1000 V 200 - 1000 V
Starting voltage 200 V 200 V 200 V 200 V
Max. input voltage, open circuit 1000 V 1000 V 1000 V 1000 V
Number of MPPT 2 2 2 2
Max. input current per MPPT 17 A 17 A 23 A 30 A
Max. short circuit current per MPPT 24 A 24 A 30 A 30 A
Nominal input power for max. output 8.3 kW 10.4 kW 17.0 kW 22.0 kW
Max. DC input power per MPPT 5.5 kW 7.0 kW 8.5 kW 11.0 kW
DC connection type MC4, 4 pairs (2+2) MC4, 4 pairs (2+2) MC4, 4 pairs (2+2) MC4, 4 pairs (2+2)
DC switch Integrated Integrated Integrated Integrated
Output (AC)Nominal output power 8 kVA 10 kVA 15 kVA 20 kVA
Isolation Transformerless Transformerless Transformerless Transformerless
AC voltage range 184 - 276 V 184 - 276 V 184 - 276 V 184 - 276 V
Max. output current 12.8 A 16.0 A 24.0 A 32.0 A
Total harmonic distortion < 3 % < 3 % < 3 % < 3 %
Power factor (adjustable) 0.8 lead to 0.8 lag 0.8 lead to 0.8 lag 0.8 lead to 0.8 lag 0.8 lead to 0.8 lag
AC connection type IP67 connector IP67 connector IP67 connector IP67 connector
EfficiencyPeak 98.2 % 98.3 % 98.0% 98.0 %
European 97.4 % 97.7 % 97.3 % 97.5 %
General specificationsPower consumption, night time < 2 W < 2 W < 2 W < 2 W
IP degree of protection IP65 (electronics), IP65 (electronics), IP65 (electronics), IP65 (electronics),
IP55 (balance) IP55 (balance) IP55 (balance) IP55 (balance)
Cooling Fan cooled Fan cooled Fan cooled Fan cooled
Enclosure material Aluminium Aluminium Aluminium Aluminium
Product weight 41.0 kg (90.2 lb) 41.0 kg (90.2 lb) 67.2 kg (148.2 lb) 67.2 kg (148.2 lb)
Shipping weight 48.5 kg (106.9 lb) 48.5 kg (106.9 lb) 122.0 kg (269.0 lb) 122.0 kg (269.0 lb)
Product dimensions (H x W x D) 62.5 x 61.2 x 27.8 cm 62.5 x 61.2 x 27.8 cm 96.0 x 61.2 x 27.8 cm 96.0 x 61.2 x 27.8 cm (24.6 x 24.0 x 10.9 in) (24.6 x 24.0 x 10.9 in) (37.8 x 24.1 x 10.9 in) (37.8 x 24.1 x 10.9 in)
Shipping dimensions (H x W x D) 75.0 x 74.0 x 40.0 cm 75.0 x 74.0 x 40.0 cm 115.0 x 79.0 x 48.0 cm 115.0 x 79.0 x 48.0 cm (29.5 x 29.1 x 15.8 in) (29.5 x 29.1 x 15.8 in) (45.3 x 31.1 x 18.9 in) (45.3 x 31.1 x 18.9 in)
Ambient air temperature for operation -20 to 60ºC (-4ºF to 140ºF) -20 to 60ºC (-4ºF to 140ºF) -20 to 60ºC (-4ºF to 140ºF)** -20 to 60ºC (-4ºF to 140ºF)**
Operating altitude Up to 2000 m Up to 2000 m Up to 2000 m Up to 2000 m
Relative humidity 4 - 100 % (condensing) 4 - 100 % (condensing) 4 - 100 % (condensing) 4 - 100 % (condensing)
Noise emission (at 1 m distance) < 50 dBA < 50 dBA < 55 dBA < 55 dBA
Features and optionsEmbedded data logger 365 days
Display 5” Graphic LCD (320 x 240 pixels), 4 buttons
Communication interface Modbus (RS485)
Multifunction relay Yes
Regulatory approval
Environmental RoHS, REACH
EMC CE marked for the EMC directive 2004-108-EC Emissions: EN 61000-6-3 (residential) Immunity: EN 61000-6-2 (industrial)
Available product variantsStandard PVSNVC8000 PVSNVC10000 PVSNVC15000 PVSNVC20000 Specifications are subject to change without notice. *More available upon request. **-15ºC cold start temperature. Vpv 500V. ***Only for TL 15000 E and TL 20000 E.
14
Grid-tie and off-grid backup PV solutions
Why choose Conext Monitor 20?
True bankability
Warranty from a trusted partner with over 177 years of experience
World leader in industrial power drives, UPS and electrical distribution
Strong service infrastructure worldwide to support your global needs
Higher return on investment
Energy generation charts and regional benchmarking to proactively address PV plant performance issues, if any
reduction e.g. in Germany
Designed for reliability
Undergone extensive safety, quality and reliability testing
Flexible
Compatible with Conext RL and TL series of inverters
Easy to service
Provision to backup and to load data logger configuration
Easy to install
Compact unit that is very easy to mount
Product applications
Residential
Small commercial
Conext Monitor 20 communication device
Conext™ Monitor 20 is a compact monitoring and control unit. This data logger allows simple configuration and operation. Connecting the data logger to the internet via ethernet allows the operating data to be visualized and monitored regardless of location using the web portal. The key data displayed in the web portal includes current and historical energy generation, environmental impact and system set-up data.
With four digital inputs and a power control function, it also meets the grid feed-in management requirements by allowing the connection of a ripple control receiver to the inverter through the datalogger.
Conext Monitor 20 is suitable for Conext RL and Conext TL series of inverters for PV systems up to 20 kW (not more than three inverters).
Compact and easy to use remote monitoring solution for residential PV installations
Conext Monitor 20 monitoring system
15
Device short name Conext Monitor 20Electrical specificationsCommunication interfacesInverter (Modbus-RS 485) Connector: 1x RJ12, 2-wire serial, termination: 120 Ohms Inverter connect cable (length: 2m) and RJ45 - RJ45 adapter for extension provided Products supported: Conext RL, Conext TL (max. plant size 20 kW, max. number of inverters: 3)
Ethernet Connector: 1 x RJ45, 10 Mbps (HTTP(s), DHCP, REST) Ethernet conect cable provided (length: 1.8 m)
USB-device Connector: USB-MicroB, full speed 12 Mbps, protocols: CDC, RS232 emulation USB connect cable provided (length: 1m)
Other interfacesRipple control receiver Connector: 1x RJ45, 4x digital inputs (EN62053-31)
Power supply options
AC frequency of power adapter 47 to 63 Hz
AC voltage of power adapter 100 to 240 VAC
Power consumption 1.7 W typical
MemoryInternal flash 5 days data
General specificationsProduct weight 0.2 kg (0.4 lb)
Shipping weight 0.7 kg (1.5 lb)
Product dimensions (H x W x D) 10.7 x 15.2 x 3.7 cm (4.2 x 6.0 x 1.5 in)
Shipping dimensions (H x W x D) 16.0 x 33.2 x 12.2 cm (6.3 x 13.1 x 4.8 in)
Status display 8x LEDs
Push buttons 3x (menu, action and reset)
Temperature Operating: 0 to 40°C; storage: -20 to 650°C
Humidity Rel. 20 to 90% (non-condensing)
Part number PVSCMC1120
Features and optionsWarranty 2 years
Portal compatibility with browsers IE8 and above, Firefox 13.0.1 and above, Google Chrome 20.0.1132.47m and above, Apple Safari 5.1.7 and above
Regulatory approvalsMarking CE, RCM
Safety EN 60950-1
EMC inmmunity EN 61000-3-2, EN 61000-3-3, EN61000-6-1:2007, EN61000-4-11
EMC emission EN55022 class B
Disposal WEEE
Works withConext TL TL 8000 E product no. PVSNVC8000, TL 1000 E product no. PVSNVC10000, TL 15000 E product no. PVSNVC15000, TL 20000 E product no. PVSNVC20000
Specifications are subject to change without notice.
Refuge du Goûter, FranceOff-grid solar 12 kWp
17
Schneider Electric solutions for the off-grid solar and battery back market allow you to install your system for multiple configurations to suit your project requirements.
Residential load
Conext SW / Conext XW
Battery
Solar chargecontroller
Generator
PV modules
Battery
Grid
Residential load
GeneratorConext SW / Conext XW
Residential backup power solutions using Conext SW or Conext XW
Residential off-grid solutions using Conext SW or Conext XW
Ontario, CanadaOff-grid solar 10 kWp
Designing your off-grid solarand backup power solutions
18
Grid-tie and off-grid backup PV solutions
Commercial load
Conext XW
Battery
Generator
Grid
Commercial backup power solutions using Conext XW
Grid
Residential load
Conext XW
Battery
Solar chargecontroller
Generator
PV modules
Residential grid-interactive solar with backup solutions using Conext XW
Designing your solar solution
California, USAOff-grid solar4.5 kWp
19
Conext SW / Conext XW
Solar chargecontroller
PV modules Battery
Community loads
Generator
Community electrification using Conext SW or Conext XW
Solar chargecontroller
Battery
Conext XW
Commercial load
Generator
PV modules
Commercial off-grid solar solutions using Conext XW
Commercial load
Grid
Conext XW
Battery
Solar chargecontroller
Generator
PV modules
Commercial grid-interactive solar with battery backup solutions using Conext XW
20
Grid-tie and off-grid backup PV solutions
Why choose Conext SW?
True bankability
Warranty from a trusted partner with over 177 years of experience
World leader in industrial power drives, UPS and electrical distribution
Strong service infrastructure worldwide to support your global needs
Higher return on investment
Cost effective residential and community system
Harness the continuously declining production cost of solar power
Designed for reliability
Robust design through rigorous reliability testing (HALT)
Flexible
All models support both 50 Hz and 60 Hz output
Support stackable power up to 8 kW
Easy to service
Remote monitoring and configuration
Global support
Easy to install
Configures quickly into compact wall mounted system
Companion breaker panels integrate inverter with battery bank and solar charge controllers
Product applications
Residential backup power
Off-grid solar
Community electrification
Conext SW inverter/charger
Conext™ SW delivers new value and a new price point to the marketplace in 2013. Conext SW is a pure sine wave,
North American units feature split-phase input and output without the need for an external transformer. Available DC and AC switchgear panels, display control panel, remote monitoring and automated generator control modules present even more value. Stacking Conext SW units will double the power and available solar charge controllers allow for the integration of solar capacity as required.
New value in off-grid solar and backup power
21
Device short name SW 2524 120 SW 4024 120 SW 2524 230 SW 4024 230Electrical specifications - inverterOutput power (continuous) at 25°C 2500 W 3400 W 2500 W 3500 W
Output power (30 min) at 25°C 2700 W 4000 W 2800 W 4000 W
Output power (5 sec) at 25°C 4000 W 7000 W 5000 W 7000 W
Peak current 24.3 A 41 A 24.3 A 42 A
Output wave form True sine wave True sine wave True sine wave True sine wave
Optimal efficiency 91.5% 92% 91.5% 92%
Idle consumption search mode <8 W <8 W <8 W <8 W
Input DC voltage range 20 - 34 Vdc 20 - 34 Vdc 20 - 34 Vdc 20 - 34 Vdc
Electrical specifications - chargerOutput current 65 A 90 A 65 A 90 A
Nominal output voltage 24 Vdc 24 Vdc 24 Vdc 24 Vdc
Output voltage range 12- 32 Vdc 12 - 32 Vdc 12 - 32 Vdc 12 - 32 Vdc
Charge control 3 stage 3 stage 3 stage 3 stage
Charge temperature compensation Yes - BTS included Yes - BTS included Yes - BTS included Yes - BTS included
Optimal efficiency 90% 90% 90% 90%
AC input power factor > 0.98 > 0.98 > 0.98 > 0.98
Input current 9 A 13 A 10.6 A 14.0 A
Input AC voltage range line to neutral 95 - 135 Vac single phase 95 - 135 Vac single phase 170 - 270 Vac 170 - 270 Vac 135 - 270 Vac split phase 135 - 270 Vac split phase
Dead battery charge Yes Yes Yes Yes
General specificationsCompatible battery types FLA, Gel, AGM, Custom FLA, Gel, AGM, Custom FLA, Gel, AGM, Custom FLA, Gel, AGM, Custom
Transfer relay rating 30 A 30 A 30 A 30 A
Transfer time <1 cycle (16.7 ms) <1 cycle (16.7 ms) <1 cycle (20 ms) <1 cycle (20 ms)
(AC to inverter and inverter to AC)
Optimal operating temperature range -20°C to 60°C -20°C to 60°C -20°C to 60°C -20°C to 60°C (-4°F to 140°F) (-4°F to 140°F) (-4°F to 140°F) (-4°F to 140°F)
Storage ambient temperature range -40°C to 85°C -40°C to 85°C -40°C to 85°C -40°C to 85°C (-40°F to 185°F) (-40°F to 185°F) (-40°F to 185°F) (-40°F to 185°F)
Product weight 23.0 kg (50.6 lb) 30.5 kg (67.1 lb) 23.0 kg (50.6 lb) 30.5 kg (67.1 lb)
Shipping weight 27.2 kg (60.0 lb) 35.0 kg (77.0 lb) 27.2 kg (60.0 lb) 35.0 kg (77.0 lb)
Product dimensions (H x W x D) 41.8 x 34.1 x 19.7 cm 41.8 x 34.1 x 19.7 cm 38.7 x 34.3 x 19.7 cm 38.7 x 34.3 x 19.7 cm (16.5 x 13.4 x 7.6 in) (16.5 x 13.4 x 7.6 in) (15.2 x 13.5 x 7.6 in) (15.2 x 13.5 x 7.6 in)
Shipping dimensions (H x W x D) 56.0 x 44.0 x 32.0 cm 56.0 x 44.0 x 32.0 cm 56.0 x 44.0 x 32.0 cm 56.0 x 44.0 x 32.0 cm (22.0 x 17.3 x 12.6 in) (22.0 x 17.3 x 12.6 in) (22.0 x 17.3 x 12.6 in) (22.0 x 17.3 x 12.6 in)
System network and remote monitoring Available Available Available Available
Warranty (Depending on the 2 or 5 years 2 or 5 years 2 or 5 years 2 or 5 years country of installation)
Part number 865-2524 865-4024 865-2524-61 865-4024-61
Regulatory approvalsSafety c(CSA) us mark c(CSA) us mark CE mark CE mark CSA C22.2 No. 107.1-01 CSA C22.2 No. 107.1-01 RCM mark RCM mark
Optional accessories Universal DC breaker panel 865-1016
AC breaker panel (230 V) 865-1017-61
System Control Panel (SCP) 865-1050
Automatic Generator Start (AGS) 865-1060
Conext ComBox 865-1058
MPPT 60 150 solar charge controller 865-1030-1 Specifications are subject to change without notice.
22
Grid-tie and off-grid backup PV solutions
Why choose Conext XW (230 V / 50 Hz)?
True bankability
Warranty from a trusted partner with over 177 years of experience
World leader in industrial power drives, UPS and electrical distribution
Strong service infrastructure worldwide to support your global needs
Higher return on investment
Hybrid integration of generator reduces diesel fuel costs
Designed for reliability
applications and environments
Flexible
Easy to service
Easy to install
Product applications
Residential, backup power and grid-tie
Off-grid solar
Community electrification
Small commercial, backup power and grid-tie
Conext XW inverter/charger(230 V / 50 Hz)
One solution for global power
grid-tie functionality and dual AC power inputs. Available solar charge controllers, monitoring, and automated generator control modules enable further adaptability. From single Conext XW unit to multiple clusters of units, up to 36 kW each, the Conext XW is a scalable system that allows for the integration of solar capacity as required.
Adaptable and scalable, the Schneider Electric Conext XW system is the one solution for global grid-interactive and off-grid, residential and commercial, solar and backup power applications.
23
Device short name XW4024 230 50 XW4548 230 50 XW6048 230 50Electrical specificationsContinuous power 4.0 kVA 4.5 kVA 6.0 kVA
Surge rating 8.0 kVA (20 sec) 9.0 kVA (15 sec) 12.0 kVA (15 sec)
Output current 17.4 A 19.6 A 26.1 A
Peak output current (rms) 35 A 40 A 53 A
Input current at rated power 178 A 96 A 131 A
Type of signal True sine wave True sine wave True sine wave
Automatic transfer relay 56 A 56 A 56 A
Typical transfer time 8 ms 8 ms 8 ms
DC input voltage (nominal) 25.2 V 50.4 V 50.4 V
Input voltage limits 20 to 32 V 40 to 64 V 40 to 64 V
Charging current 150 A 85 A 100 A
Power factor corrected charging 0.98 0.98 0.98
Auxiliary relay output 0 to 12 V, maximum 250 mA DC 0 to 12 V, maximum 250 mA DC 0 to 12 V, maximum 250 mA DC
Power consumption (search mode) < 7 W < 7 W < 7 W
Total harmonic distortion (THD) < 5% at rated power < 5% at rated power < 5% at rated power
AC connections AC1 (Grid), AC2 (Generator) AC1 (Grid), AC2 (Generator) AC1 (Grid), AC2 (Generator)
AC input breaker 60 A single-pole 60 A single-pole 60 A single-pole
EfficiencyPeak 94.0% 95.6% 95.4%
General specificationsIP degree of protection IP20 (sensitive electric components sealed inside enclosure)
Product weight 52.5 kg (116.0 lb) 53.5 kg (118.0 lb) 55.2 kg (121.7 lb)
Shipping weight 74.0 kg (163.0 lb) 75.0 kg (165.0 lb) 76.7 kg (169.0 lb)
Product dimensions (H x W x D) 58 x 41 x 23 cm (23 x 16 x 9 in) 58 x 41 x 23 cm (23 x 16 x 9 in) 58 x 41 x 23 cm (23 x 16 x 9 in)
Shipping dimensions (H x W x D) 71.1 x 57.2 x 39.4 cm 71.1 x 57.2 x 39.4 cm 71.1 x 57.2 x 39.4 cm (28.0 x 22.5 x 15.5 in) (28.0 x 22.5 x 15.5 in) (28.0 x 22.5 x 15.5 in)
Device mounting Wall mount (backplate included) Wall mount (backplate included) Wall mount (backplate included)
Ambient air temperature for operation -25°C to 70°C (-13°F to 158°F) (power derated above 45°C (113°F)
System network and remote monitoring Available Available Available
Warranty (Depending on the country of installation) 2 or 5 years 2 or 5 years 2 or 5 years
Part number 865-1045-61 865-1040-61 865-1035-61
Features and options
Three-character display indicates output power or charge current
Supported battery types Flooded (default), Gel, AGM, custom Flooded (default), Gel, AGM, custom Flooded (default), Gel, AGM, custom
Battery bank size 100 to 2000 Ah (scaled to PV array size)
Battery temperature sensor Included Included
Non volatile memory Yes Yes
Multiple unit configurations Single-phase: up to four parallel units. Three-phase: two units per phase
Regulatory approvalCE marked according to the following EU directives and standards:
EMC directive EN61000-6-1, EN61000-6-3, EN61000-3-2, EN61000-3-3
Low voltage directive EN50178
AccessoriesXW Product Distribution Panel (PDP) Product no. 865-1015
XW Conection Kit (CK) Product no. 865-1020
System Control Panel (SCP) Product no. 865-1050
Automatic Generator Start (AGS) Product no. 865-1060
MPPT 60 150 solar charge controller Product no. 865-1030-1
MPPT 80 600 solar charge controller Product no. 865-1032
XW Configuration Tool (CT) Product no. 865-1155
Conext ComBox Product no. 865-1058 Specifications are subject to change without notice.
24
Grid-tie and off-grid backup PV solutions
Why choose Conext XW (120 V / 240 v / 60 Hz)?
True bankability
Warranty from a trusted partner with over 177 years of experience
World leader in industrial power drives, UPS and electrical distribution
Strong service infrastructure worldwide to support your global needs
Higher return on investment
Designed for reliability
applications and environments
Flexible
Easy to service
Easy to install
charge controllers
Product applications
Residential, backup power and grid-tie
Off-grid solar
Community electrification
Small commercial, backup power and grid-tie
Conext XW inverter/charger(120 / 240 V / 60 Hz)
One solution for global power
global grid-tie functionality and dual AC power inputs. Available solar charge controllers, monitoring, and automated generator control modules enable further adaptability. From single Conext XW unit to multiple clusters of units, up to 36 kW each, the Conext XW is a scalable system that allows for the integration of solar capacity as required.
Adaptable and scalable, the Schneider Electric Conext XW system is the one solution for global grid-interactive and off-grid, residential and commercial, solar and backup power applications.
Products shown:
XW Power Distribution Panel and XW Conduit Box
25
Device short name XW4024 120 240 60 XW4548 120 240 60 XW6048 120 240 60Electrical specifications Continuous power 4.0 kVA 4.5 kVA 6.0 kVA
Surge rating 8.0 kVA (20 sec) 9.0 kVA (15 sec) 12.0 kVA (15 sec)
Peak output current (rms) L-N: 70 A (20 sec), L-L: 35 A (20 sec) L-N: 75 A (20 sec), L-L: 40 A (20 sec) L-N: 105 A (15 sec), L-L: 52.5 A (15 sec)
Input current at rated power 178 A 96 A 130 A
Type of signal True sine wave True sine wave True sine wave
Automatic transfer relay 60 A 60 A 60 A
Typical transfer time 8 ms 8 ms 8 ms
DC input voltage (nominal) 25.2 V 50.4 V 50.4 V
Input voltage limits 20 to 32 V 40 to 64 V 40 to 64 V
Charging current 150 A 85 A 100 A
Power factor corrected charging 0.98 0.98 0.98
Auxiliary relay output 0 to 12 V, maximum 250 mA DC 0 to 12 V, maximum 250 mA DC 0 to 12 V, maximum 250 mA DC
Idle consumption (search mode) < 8 W < 8 W < 8 W
Total harmonic distortion (THD) at rated power < 5% < 5% < 5%
AC connections AC1 (Grid), AC2 (Generator) AC1 (Grid), AC2 (Generator) AC1 (Grid), AC2 (Generator)
AC input breaker 60 A two-pole 60 A two-pole 60 A two-pole
Utility interactive Yes Yes Yes
CEC power rating 4.0 kW 4.5 kW 5.760 kW
EfficiencyPeak 94.0% 95.6% 95.4%
CEC weighted 91.0% 93.0% 92.5%
General specificationsNEMA degree of protection NEMA1R (indoor rating) (sensitive electronic components sealed inside enclosure)
Product weight 52.5 kg (116.0 lb) 53.5 kg (118.0 lb) 55.2 kg (121.7 lb)
Shipping weight 74.0 kg (163.0 lb) 75.0 kg (165.0 lb) 76.7 kg (169.0 lb)
Product dimensions (H x W x D) 58 x 41 x 23 cm (23.0 x 16.0 x 9.0 in) 58 x 41 x 23 cm (23.0 x 16.0 x 9.0 in) 58 x 41 x 23 cm (23.0 x 16.0 x 9.0 in)
Shipping dimensions (H x W x D) 71.1 x 56.5 x 26.7 cm (28.0 x 22.3 x 10.5 in) 71.1 x 56.5 x 26.7 cm (28.0 x 22.3 x 10.5 in) 71.1 x 56.5 x 26.7 cm (28.0 x 22.3 x 10.5 in)
Ambient air temperature for operation -25 to 70°C (-13 to 158°F) (power derated above 45°C (113°F)
System network and remote monitoring Available Available Available
Warranty (Depending on the country of installation) 2 or 5 years 2 or 5 years 2 or 5 years
Part number 865-1010 865-1005 865-1000-01
Features and options
Supported battery types Flooded (default), Gel, AGM, custom
Battery bank size 100 to 2000 Ah (scaled to PV array size)
Battery temperature sensor Included
Regulatory approvalsSafety UL1741, CSA 107.1
EMC FCC and Industry Canada Class B
Interconnect IEEE 1547 and CSA 107.1
AccessoriesXW Product Distribution Panel (PDP) Product no. 865-1015
XW Conection Kit (CK) Product no. 865-1020
System Control Panel (SCP) Product no. 865-1050
Automatic Generator Start (AGS) Product no. 865-1060
MPPT 60 150 solar charge controller Product no. 865-1030-1
MPPT 80 600 solar charge controller Product no. 865-1032
XW Configuration Tool (CT) Product no. 865-1155
Conext ComBox Product no. 865-1058 Specifications are subject to change without notice.
26
Grid-tie and off-grid backup PV solutions
Conext ComBox communication device
Operators of Conext™ solar systems can now remotely monitor yield performance using devices of their choice, such as personal computers, tablet devices, or building management systems. Data logs and event logs for each device, as well as graphical displays of historical and solar system harvest, and plant yield are easily reviewed using a web browser or Android tablet device. Installers can change the settings of Conext devices during commissioning and
packages and building management systems. Integrated Micro-SD card provides for additional data storage. Conext ComBox is compatible with Xanbus protocol devices.
New remote monitoring from Schneider Electric
Why choose Conext ComBox?
True bankability
Warranty from a trusted partner with over 177 years of experience
World leader in industrial power drives, UPS and electrical distribution
Strong service infrastructure worldwide to support your global needs
Higher return on investment
Monitor solar system harvest and yield
Designed for reliability
(MEOST) and Temperature Humidity Bias (THB)
Flexible
Configure up to twenty Xanbus protocol devices
Works with Conext XW, SW, TX, GT-AUS, MPPT 60-150, MPPT 80-600, AGS, SCP
Access Conext devices over Modbus protocol
Easy to service
Remotely upgrade ComBox and Conext device firmware
Settings are maintained during power or network interruptions
Easy to install
Configure devices using web page interface or Android tablet
Surface or DIN-Rail mounting
Multiple power supply options
Product applications
Residential, backup power and grid-tie
Small commercial, backup power and grid-tie
Off-grid solar
Community electrification
Conext ComBox monitoring system
27
Device short name Conext ComBoxElectrical specificationsCommunication interfacesXanbus Connector: 2 x RJ45
RS485 Modbus (1 x Connector: Screw 5-terminal, 16-24AWG, 2-wire serial, 19200 bps)
Data InterfacesUSB 2.0-Host Connector: USB-A, Protocols: MSD (firmware upgrades and device locator)
USB 2.0-Device Connector: USB-mini B, Protocols: CDC, MSD (data extraction)
Power supply options
RS485 24 Vdc (safety extra low-voltage only)
MemoryInternal 96 MB flash
External Micro-SD Card (2GB or more, class 2 or better recommended)
General specificationsWeight 0.25 kg (0.55 lb)
Dimensions (H x W x D) 11.4 x 16.9 x 5.4 cm (4.5 x 6.7 x 2.1 in)
Status display 5 x LEDs
Part number 865-1058
FeaturesProgrammable dry contact relay Screw 3-terminal, 16-24 AWG, NC-Com-NO, Form: Class 2, 24 Vdc 4 A max
Graphical user interface Internet Browser, Android tablet app
Remote firmware upgrades Yes (ComBox and connected Xanbus devices)
Custom datalogger Yes (requires Micro-SD card)
Warranty 5 years
Number of Xanbus devices Up to 20 (depending on device type)
Regulatory approvalsMarking CE, RCM
EMC emission EN61000-6-3, FCC Part 15 Class B, Ind. Canada ICES-003 Class B
Works with
XW 6048 product no. 865-1035-61
XW 6048 product no. 865-1000-01
(120 V) SW 4024 product no. 865-3524
(230 V) SW 4024 product no. 865-3524-61
Conext TX inverter (N. America) TX 2800 product no. 878-2801 TX 3300 product no. 878-3301 TX 3800 product no. 878-3801 TX 5000 product no. 878-5001
MPPT 60 150 solar charge controller Product no. 865-1030-1
MPPT 80 600 solar charge controller Product no. 865-1032
System Control Panel (SCP) Product no. 865-1050
Automatic Generator Start (AGS) Product no. 865-1060
GT-AUS inverter GT 2.8 product no. 864-1030 GT 5.0 product no. 864-1039-01 Specifications are subject to change without notice.
28
Grid-tie and off-grid backup PV solutions
Selected customer references
Global support that makes any size installation a success story
California, USAOff-grid solar 4.5 kWp
Madrid, SpainOff-grid solar 18 kWp
Refuge du Goûter, FranceOff-grid solar 12 kWp
Grenoble, FranceCommercial rooftop 70 kWp
Gipuzkoa, SpainOff-grid solar1.5 kWp
Ontario, CanadaOff-grid solar 10 kWp
29
Marovato ,MadagascarCommercial rooftop 1.5 kWp
Lunamatrona, ItalyCommercial rooftop145 kWp
Grenoble, FranceCommercial rooftop 50 kWp
Aquila, ItalyCommercial rooftop 200 kWp
Lamig, GreeceDecentralised power plant500 kWp
Dorna, RomaniaOff-grid solar360 kWp
Ostwind, GermanyCommercial rooftop 360 kWp
Monthey, SwitzerlandCommercial rooftop95 kWp
Aquila, ItalyCommercial rooftop 65 kWp
Uta, ItalyCommercial rooftop 355 kWp
Schneider Electric Industries SAS
Head Office35 rue Joseph Monier92500 Rueil Malmaison Cedex- FranceTel.: +33 (0)1 41 29 70 00www.schneider-electric.com
Make the most of your energySM
See our solutions on YouTube at www.youtube.com/schneidersolar
©2013 Schneider Electric. All Rights Reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.
CT20130606_Transactional