conduit and cable schedule
DESCRIPTION
Conduit And Cable ScheduleTRANSCRIPT
-
Conduit and Cable Schedule
MCCDate: Sunday, Dec. 06, 2009
Prepared By: Eric Kench, P.E.
Company: Kench Engineering Consultant
Ckt Item / Raceway Name Raceway Type and Size Length From Voltage Load(kW)
MCC 208VAC 23.35
1 - Conduit #4 1-1/4 in. - Rigid Steel Conduit 1 Feet
3 - 4 ga. THHN - Cu conductor 90C Conductor rated at 600V
1 - 4 ga. THHN - Cu neutral 90C Conductor rated at 600V
1 - 6 ga. THHN - Cu ground 90C Conductor rated at 600V
1, 3, 5 Motor #1 208VAC 7.46
1 - Conduit #1 3/4 in. - Rigid Steel Conduit 100 Feet MCC
3 - 8 ga. THHN - Cu conductor 90C Conductor rated at 600V
1 - 10 ga. THHN - Cu ground 90C Conductor rated at 600V
2, 4 Motor #2 208VAC 2.24
1 - Conduit #2 1/2 in. - Rigid Steel Conduit 100 Feet MCC
2 - 10 ga. THHN - Cu conductor 90C Conductor rated at 600V
1 - 10 ga. THHN - Cu ground 90C Conductor rated at 600V
6 Motor #3 120VAC 2.24
1 - Conduit #3 1/2 in. - Rigid Steel Conduit 100 Feet MCC
1 - 6 ga. THHN - Cu conductor 90C Conductor rated at 600V
1 - 6 ga. THHN - Cu neutral 90C Conductor rated at 600V
1 - 10 ga. THHN - Cu ground 90C Conductor rated at 600V