condensing units hs29 - lennox emeawebmanuals.lennoxeurope.com/out of...

59
HS29 Bulletin No. 210304 September 2003 Supersedes September 2000 ELITE ® SERIES 1 to 5 Ton SEER up to 12.95 Cooling Capacity − 12,000 to 62,500 Btuh CONDENSING UNITS ENGINEERING DATA Copeland Scrollt Compressor Enhanced PVC Coated Coil Guard Direct Drive Fan Lanced Aluminum Fins Brass Service Valves Copper Tube Outdoor Coil Heavy−Duty, Louvered Steel Fan Guard Heavy Gauge Steel Cabinet with Powder Paint Finish MODEL NUMBER IDENTIFICATION 036 HS 29 - Unit Type HS = High Side Condensing Unit Series Nominal Cooling Capacity 012 = 1 ton (3.5 kW) 018 = 1.5 tons (5.3 kW) 024 = 2 tons (7.0 kW) 030 = 2.5 tons (8.8 kW) 036 = 3 tons (10.6 kW) 042 = 3.5 tons (12.3 kW) 048 = 4 tons (14.1 kW) 060 = 5 tons (17.6 kW) 062 = 5+ tons (17.6+ kW) Voltage P = 208/230V−1 phase−60hz Y = 208/230Vɢ3 phaseɢ60hz G = 460Vɢ3 phaseɢ60hz J = 575Vɢ3 phaseɢ60hz Minor Revision Number 2 P - FEATURES CONTENTS ARI Rating Tables Pages 8−17 . . . . . . . . . . . . . . . . . . . . . . . . . Dimensions Page 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Features Pages 1−2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Field Wiring Page 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installation Clearances Page 3 . . . . . . . . . . . . . . . . . . . . . . . . . Model Number Identification Page 1 . . . . . . . . . . . . . . . . . . . . Optional Accessories Page 3 . . . . . . . . . . . . . . . . . . . . . . . . . . Outdoor Sound Data Page 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . Specifications Pages 4−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Warranty Compressor − Ten year limited warranty in residential applicaɢ tions, five year limited warranty in non−residential applications. All other covered components − Five year limited warranty in resɢ idential applications, one year limited warranty in non−residential applications. Refer to Lennox Equipment Limited Warranty certificate inɢ cluded with unit for specific details. Applications SEER up to 12.95. 1 through 5+ ton (3.5 through 17.6+ kW) matches with TXV or RFC. Single or three phase power supply. Vertical air discharge allows concealment behind shrubs at grade level or out of sight on a roof. Matching blower powered or add−on furnace evaporator units provide a wide range of cooling capacities and applications. See ARI Ratings table. For evaporator unit data, see Coils − Blower Coil Units section. Units shipped completely factory assembled, piped and wired. Each unit is test operated at the factory ensuring proper operation. Installer must set condensing unit, connect refrigerant lines and make electrical connections to complete job. NOTE − Due to Lennox’ ongoing committment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency. ©2003 Lennox Industries Inc. Visit us at www.lennox.com For the latest technical information, www.lennoxdavenet.com

Upload: vuthu

Post on 02-Feb-2018

269 views

Category:

Documents


6 download

TRANSCRIPT

Page 1: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

HS29

Bulletin No. 210304

September 2003

Supersedes September 2000

ELITE® SERIES1 to 5 Ton

SEER up to 12.95Cooling Capacity − 12,000 to 62,500 Btuh

CONDENSING UNITS

ENGINEERING DATA

Copeland Scroll�Compressor

EnhancedPVC CoatedCoil Guard

DirectDriveFan

LancedAluminum Fins

Brass ServiceValves

Copper TubeOutdoor Coil

Heavy−Duty,Louvered Steel

Fan Guard

Heavy GaugeSteel Cabinetwith PowderPaint Finish

MODEL NUMBER IDENTIFICATION

036HS 29 −

Unit TypeHS = High Side Condensing Unit

Series

Nominal Cooling Capacity012 = 1 ton (3.5 kW)

018 = 1.5 tons (5.3 kW)024 = 2 tons (7.0 kW)

030 = 2.5 tons (8.8 kW)036 = 3 tons (10.6 kW)

042 = 3.5 tons (12.3 kW)048 = 4 tons (14.1 kW)060 = 5 tons (17.6 kW)

062 = 5+ tons (17.6+ kW)

VoltageP = 208/230V−1 phase−60hzY = 208/230V�3 phase�60hzG = 460V�3 phase�60hzJ = 575V�3 phase�60hz

Minor Revision Number

2 P−

FEATURES

CONTENTS

ARI Rating Tables Pages 8−17. . . . . . . . . . . . . . . . . . . . . . . . . Dimensions Page 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Features Pages 1−2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Field Wiring Page 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installation Clearances Page 3. . . . . . . . . . . . . . . . . . . . . . . . . Model Number Identification Page 1. . . . . . . . . . . . . . . . . . . . Optional Accessories Page 3. . . . . . . . . . . . . . . . . . . . . . . . . . Outdoor Sound Data Page 7. . . . . . . . . . . . . . . . . . . . . . . . . . . Specifications Pages 4−6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

WarrantyCompressor − Ten year limited warranty in residential applica�tions, five year limited warranty in non−residential applications.All other covered components − Five year limited warranty in res�idential applications, one year limited warranty in non−residentialapplications.Refer to Lennox Equipment Limited Warranty certificate in�cluded with unit for specific details.

ApplicationsSEER up to 12.95.1 through 5+ ton (3.5 through 17.6+ kW) matches with TXV or RFC.Single or three phase power supply.Vertical air discharge allows concealment behind shrubs atgrade level or out of sight on a roof.Matching blower powered or add−on furnace evaporator unitsprovide a wide range of cooling capacities and applications. See ARI Ratings table.For evaporator unit data, see Coils − Blower Coil Units section.Units shipped completely factory assembled, piped and wired.Each unit is test operated at the factory ensuring proper operation.Installer must set condensing unit, connect refrigerant lines andmake electrical connections to complete job.

NOTE − Due to Lennox’ ongoing committment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.Installation and service must be performed by a qualified installer and servicing agency. ©2003 Lennox Industries Inc.

Visit us at www.lennox.comFor the latest technical information, www.lennoxdavenet.com

Page 2: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RFCIV METERING SYSTEMRFCIV

�BULLET"ORIFICE

ORIFICE BODY(On Coil)

SEALNUT SWEAT

CONNECTION

O−RINGLIQUIDLINE

LIQUIDLINE SCREEN

FEATURES

ApprovalsCertified in accordance with the USE certification program,which is based on ARI Standard 210/240.Sound rated in Lennox reverberant sound test room in accor�dance with test conditions included in ARI Standard 270−95.Tested in the Lennox Research Laboratory environmental testroom.Rated according to US Department of Energy (DOE) test pro�cedures and approved rating methods.Condensing units and components within bonded for grounding tomeet safety standards for servicing required by UL, NEC and CEC.Units are UL and ULC listed.Energy rating verified by CSA.ISO 9001 Registered Manufacturing Quality System.

REFRIGERATION SYSTEM

Refrigerant Flow ControlUnits applicable to expansion valve systems or RFC systemswhen matched with specific evaporator coils.RFCIV:Accurately metersrefrigerant in sys�tem.Refrigerant controlis accomplished byexact sizing of re�frigerant meteringorifice.The principle in�volves matchingevaporator coil withproper bore size oforifice in meteringdevice.Equalizes pressure shortly after compressor stops, unit starts un�loaded, eliminating need for additional controls.Furnished with condensing unit.

Copper Tube/Enhanced Fin CoilLennox designed and fabricated coil.Ripple−edged aluminum fins.Copper tube construction.Lanced fins provide maximum exposure of fin surface to airstream resulting in excellent heat transfer.Fin collars grip tubing for maximum contact area.Flared shoulder tubing connections/silver soldering construction.Coil is factory tested under high pressure to insure leakproofconstruction.Entire coil is accessible for cleaning.PVC coated steel wire coil guard furnished as standard.

Condenser FanDirect drive fan moves large air volumes uniformly through entirecondenser coil for high refrigerant cooling capacity.Vertical air discharge minimizes operating sounds and elimi�nates damage to lawn and shrubs.Fan motor has sleeve bearings and is inherently protected.Motor totally enclosed for maximum protection from weather,dust and corrosion.Rain shield on motor provides additional protection from moisture.Louvered steel top fan guard furnished as standard.Fan service access accomplished by removal of top panel.

CabinetHeavy gauge steel cabinet with five station metal wash process.Powder paint finish provides superior rust and corrosion protection.Painted base section.ontrol box is conveniently located with all controls factory wired.Corner patch plate allows access to compressor.Drainage holes are provided in base section for moisture removal.

Refrigerant Line Connections, Electrical Inlets, Service ValvesSweat connection suction and liquid lines are located on cornerof unit cabinet.Fully serviceable brass service valves prevent corrosion andprovide access to refrigerant system. Suction valve can be fullyshut off, while liquid valve may be front seated to manage refrig�erant charge while servicing system.45� elbow furnished for ease of suction line connection.HS29−012−018−024−030 models are stubbed with 3/8 in. (9.5mm) liquid line connection. 3/8 in. x 5/16 in. (9.5 mm x 7.9 mm) reducer bushing furnished for liquid line connection.Refrigerant line connections and field wiring inlets are located inone central area of cabinet for easy access. See dimensiondrawing.

COMPRESSOR

Reciprocating Compressor (HS29−012−018, 1−phase mod�els and HS29−036, 3−phase models)Designed for dependable efficiency with minimum operating cost.Suction cooled and overload protected with internal pressure relief.Hermetically sealed with built−in protection from excessive cur�rent and temperatures.Crankcase heater assures proper compressor lubrication (threephase models only).Running gear assembly resiliently suspended internally insidecase. Compressor installed in unit on resilient rubber mounts as�suring low sound and vibration free operation.HS29−012 model equipped with rotary compressor.HS29−036 3−phase models have an internal crankcase heater.

Copeland Scroll� Compressor (HS29−024 thru −060,1−phase models and HS29−042 thru −062, 3−phase models)Compressor features high effi�ciency with uniform suction flow,constant discharge flow and highvolumetric efficiency and quiet op�eration.Compressor consists of two invo�lute spiral scrolls matched togeth�er to generate a series of crescentshaped gas pockets betweenthem.During compression, one scroll re�mains stationary while the otherscroll orbits around it.Gas is drawn into the outer pocket,the pocket is sealed as the scrollrotates.As the spiral movement contin�ues, gas pockets are pushed tothe center of the scrolls. Volumebetween the pockets is simultaneously reduced.When pocket reaches the center, gas is now at high pressureand is forced out of a port located in the center of the fixed scrolls.During compression, several pockets are compressed simulta�neously resulting in a smooth continuous compression cycle.Continuous flank contact, maintained by centrifugal force, mini�mizes gas leakage and maximizes efficiency.Scroll compressor is tolerant to the effects of slugging and con�taminants. If this occurs, scrolls separate, allowing liquid or con�taminants to to be worked toward the center and discharged.Low gas pulses during compression reduces operational soundlevels.Compressor motor is internally protected from excessive currentand temperature.Compressor is installed in the unit on resilient rubber mounts forvibration free operation.

Start ControlsFurnished on HS29−012 and−018 models.Provides assistance for compressor start under loaded condi�tions or in case of low voltage.

HS29 / Page 2

Page 3: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

OPTIONAL ACCESSORIES − MUST BE ORDERED EXTRA

CONTROLS

FreezestatInstalls on or near the discharge line of the evaporator or on thesuction line.Senses suction line temperature and cycles the compressor offwhen suction line temperature falls below it’s setpoint.Opens at 29°F (−2°C) and closes at 58°F (14°C).

Low Ambient Kit (Expansion Valve Systems Only)Condensing units operate satisfactorily down to 45�F (7�C) out�door air temperature without any additional controls.Low Ambient Control Kit can be field installed, allowing unit op�eration down to 30�F (−1�C).

ThermostatThermostat not furnished with unit. See Thermostats bulletin inthe Controls Section and Lennox Price Book.

Timed−Off ControlPrevents compressor short−cycling and allows time for suction anddischarge pressure to equalize.Permits compressor start−up in an unloaded condition.Automatic reset with 5 minute delay between compressor shut−off and start−up.

REFRIGERATION SYSTEM

Expansion Valve Kits (Expansion Valve Systems)Must be ordered extra and field installed on certain evaporatorunits. See ARI Ratings table.

High Pressure Switch KitProtects the system from high pressure conditions that can be aresult of fan failure or a blocked/dirty coil.Manual reset.

Loss of Charge KitHelps protect the compressor from damage due to a loss of re�frigerant charge.SPST, normally−closed switch, automatic reset.

Refrigerant Line KitsRefrigerant lines (suction & liquid) are shipped refrigerationclean.Lines are cleaned, dried, pressurized and sealed at factory.Suction line fully insulated.L15 lines are stubbed at both ends.Kits are not available for HS29�060−062 models and must befield fabricated.

CABINET

Hail GuardsConstructed of louvered heavy gauge steel painted to matchcabinet.Surrounds unit on all four sides to prevent damage to the coil.

Mounting BaseHigh density polyethylene mounting base is lightweight, sturdy,sound absorbing and will withstand the effects of sun, heat, cold,moisture, oil and refrigerant.Provides permanent foundation for condensing units.22−1/4 x 22−1/4 x 3 in. (565 x 565 x 76 mm) shipping weight 6 lbs.(3 kg) each.

Unit Stand−Off KitBlack high density polyethylene feet are available to raise unit offof mounting surface away from damaging moisture.Four feet are furnished per order number.

COMPRESSOR

Compressor Low Ambient Cut−OutNon�adjustable switch (low ambient cut�out) prevents compres�sor operation when outdoor temperature is below 35�F (2�C).

Crankcase HeaterCrankcase heater prevents migration of liquid refrigerant intocompressor and ensures proper compressor lubrication.Not available for HS29−036 3−phase models.

Compressor Hard Start KitSingle−phase units are equipped with a PSC compressor motor.This type of motor normally doesn’t need a potential relay andstart capacitor.In conditions such as low voltage, this kit may be required to in�crease the compressor starting torque.

Compressor Sound CoverA reinforced vinyl compressor cover containing a 1−1/2 inch(38.1 mm) thick batt of fiberglass insulation.All open edges are sealed with a one−inch wide hook and loopfastening tape.

INSTALLATION CLEARANCES − IN. (MM)

1 36(914)

1 36(914)

1 36(914)

1 36(914)

1 One of the coil sides adjacent to control box must be 30 in.(762 mm) for service.One of the remaining sides may be 12 in. (914 mm)One of the remaining sides may be 6 inches (305 mm)

NOTE � 48 in. (1219 mm) clearance required on top of unit.NOTE � 24 in. (610 mm) required between two units

FIELD WIRING

A � Two or Three Wire Power

B � Two or Three Wire Power � See Electrical Data

C � Two Wire Low Voltage � 18 ga. minimum

D � Four Wire Low Voltage (Electro−Mechanical) 18 ga. minimum

Five Wire Low Voltage (Electronic) 18 ga. minimum

NOTE � Field Wiring Not Furnished

All wiring must conform to NEC or CEC and local electrical codes.

B

DISCONNECTSWITCH

(By Others)

LENNOXCONDENSING

UNIT

LENNOXHEATING UNIT

ORBLOWER COILEVAPORATOR

UNIT

DISCONNECTSWITCH

(By Others)

THERMOSTAT(Optional)

C

D A

HS29 / Page 3

Page 4: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

SPECIFICATIONS − 1 PHASE

Cooling Model No. HS29−012 HS29�018 HS29�024 HS29�030CoolingData

Nominal Size − Tons (kW) 1 (3.5) 1.5 (5.3) 2 (7.0) 2.5 (8.8)

Connections(sweat)

Liquid line o.d. − in. (mm) 1 3/8 (9.5) 1 3/8 (9.5) 1 3/8 (9.5) 1 3/8 (9.5)(sweat)

Suction line o.d. − in. (mm) 5/8 (15.9) 5/8 (15.9) 3/4 (19.1) 3/4 (19.1)

2 Refrigerant (HCFC�22) furnished 3 lbs. 1 oz. (1.39 kg) 3 lbs. 7 oz. (1.56 kg) 3 lbs. 10 oz. (1.64 kg) 4 lbs. 1 oz. (1.84 kg)

CondenserCoil

Net face area − sq. ft. (m2) − Outer Coil 7.56 (0.70) 11.33 (1.05) 11.33 (1.05) 13.22 (1.23)Coil

Tube diameter − in. (mm) & no. of rows 5/16 (7.9) − 1 5/16 (7.9) − 1 5/16 (7.9) − 1 5/16 (7.9) − 1

Fins per inch (m) 22 (866) 22 (866) 22 (866) 18 (748)

CondenserFan

Diameter − in. (mm) & no. of blades 18 (457) − 3 18 (457) − 3 18 (457) − 3 18 (457) − 3Fan

Motor hp (W) 1/6 (124) 1/6 (124) 1/6 (124) 1/6 (124)

Cfm (L/s) 2400 (1135) 2400 (1135) 2400 (1135) 2454 (1200)

Rpm 1105 1105 1105 1110

Watts 180 180 180 195

Shipping weight − lbs. (kg) 1 package 107 (49) 140 (64) 143 (65) 140 (64)

ELECTRICAL DATA

ElectricalData (60 hz)

Line voltage data − 1 phase 208/230V 208/230V 208/230V 208/230VData (60 hz)

3 Maximum overcurrent protection (amps) 15 20 20 30

4 Minimum circuit ampacity 7.3 11.9 14.6 19.5

Compressor Rated load amps 4.9 8.6 10.8 14.7

Locked Rotor Amps 26.3 48.3 60.0 84.0

Power Factor .97 .97 .96 .90

CondenserFan

Full load amps 1.1 1.1 1.1 1.1Fan

Locked Rotor Amps 1.9 1.9 1.9 1.9

Optional Accessories − MUST BE ORDERED EXTRA

Compressor Crankcase Heater 68887 68887 90P12 90P12

Compressor Hard Start Kit − − − − − − 10J42 10J42

Compressor Low Ambient Cut−Off 45F08 45F08 45F08 45F08

Compressor Sound Cover − − − 53J39 69J17 69J03

Compressor Time�Off Control 47J27 47J27 47J27 47J27

Hail Guards 17L71 17L71 17L71 17L72

High Pressure Switch Kit 94J46 94J46 94J46 94J46

Loss of Charge Kit 94J47 94J47 94J47 94J47

Low Ambient Kit 24H77 24H77 24H77 24H77

Freezestat 93G35 93G35 93G35 93G35

39H29 39H29 39H29 39H29

50A93 50A93 50A93 50A93

Mounting Base (MB2−S) − Ship. Wt. 69J06 − 6 lbs. (3 kg) 69J06 − 6 lbs. (3 kg) 69J06 − 6 lbs. (3 kg) 69J06 − 6 lbs. (3 kg)

RefrigerantLine Set

15 ft. (4.6 m) length L15−21−15 L15−21−15 L15−31−15 L15−31−15Line Set

20 ft. (6 m) length L15−21−20 L15−21−20 L15−31−20 L15−31−20

25 ft. (8 m) length L15−21−25 L15−21−25 − − − − − −

30 ft. (9.1 m) length − − − − − − L15−31−30 L15−31−30

35 ft. (11 m) length L15−21−35 L15−21−35 − − − − − −

40 ft. (12.2 m) length − − − − − − L15−31−40 L15−31−40

50 ft. (15.2 m) length L15−21−50 L15−21−50 L15−31−50 L15−31−50

Unit Stand�Off Kit 94J45 94J45 94J45 94J45

NOTE − Extremes of operating range are plus 10% and minus 5% of line voltage.1 3/8 x 5/16 in. (9.5 x 7.9 mm) adaptor furnished for liquid line connection.� Refrigerant charge is sufficient for 15 ft. (4.6 m) length line set.3 HACR type breaker or fuse.4 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.

HS29 / Page 4

Page 5: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

SPECIFICATIONS − 1 PHASE

Cooling Model No. HS29�036 HS29�042 HS29�048 HS29�060CoolingData

Nominal Size − Tons (kW) 3 (10.6) 3.5 (12.3) 4 (14.1) 5 (17.6)

Connections(sweat)

Liquid line o.d. − in. (mm) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5)(sweat)

Suction line o.d. − in. (mm) 3/4 (19.1) 7/8 (22.2) 7/8 (22.2) 1�1/8 (28.6)

1 Refrigerant (HCFC�22) furnished 4 lbs. 6 oz. (1.98 kg) 5 lbs. 7 oz. (2.47 kg) 5 lbs. 8 oz. (2.49 kg) 8 lbs. 0 oz. (3.63 kg)

CondenserCoil

Net face area − sq. Outer Coil 15.11 (1.40) 15.11 (1.40) 15.11 (1.40) 15.11 (1.40)Coil

Net face area − sq.ft. (m2) Inner Coil − − − 5.40 (0.50) 5.40 (0.50) 14.40 (1.34)

Tube diameter − in. (mm) & no. of rows 5/16 (7.9) − 1 5/16 (7.9) − 1.37 5/16 (7.9) − 1.37 5/16 (7.9) − 2

Fins per inch (m) 22 (866) 18 (748) 18 (748) 18 (748)

CondenserFan

Diameter − in. (mm) & no. of blades 18 (457) − 4 18 (457) − 4 18 (457) − 4 18 (457) − 4Fan

Motor hp (W) 1/6 (124) 1/6 (124) 1/3 (249) 1/3 (249)

Cfm (L/s) 2520 (1195) 2610 (1230) 3115 (1470) 2930 (1385)

Rpm 1110 1105 1125 1100

Watts 200 200 325 310

Shipping weight − lbs. (kg) 1 package 148 (67) 161 (73) 194 (88) 212 (96)

ELECTRICAL DATA

ElectricalData (60 hz)

Line voltage data − 1 phase 208/230V 208/230V 208/230V 208/230VData (60 hz)

2 Maximum overcurrent protection (amps) 35 40 45 60

3 Minimum circuit ampacity 21.1 26.5 25.9 37.9

Compressor Rated load amps 16.0 20.3 19.2 28.8

Locked rotor amps 100.0 127.0 137.0 169.0

Power Factor .91 .84 .98 .95

Condenser Fan Full load amps 1.1 1.1 1.9 1.9

Locked rotor amps 1.9 1.9 4.1 4.1

Optional Accessories − MUST BE ORDERED EXTRA

Compressor Crankcase Heater 90P12 90P12 90P12 90P12

Compressor Hard Start Kit 10J42 10J42 81J69 81J69

Compressor Low Ambient Cut−Off 45F08 45F08 45F08 45F08

Compressor Sound Cover 69J03 69J03 69J03 69J03

Compressor Time�Off Control 47J27 47J27 47J27 47J27

Hail Guards 17L73 17L73 17L73 17L73

High Pressure Switch Kit 94J46 94J46 94J46 94J46

Loss of Charge Kit 94J47 94J47 94J47 94J47

Low Ambient Kit 24H77 24H77 24H77 24H77

Freezestat 3/8 in. tubing 93G35 93G35 93G35 93G35

1/2 in. tubing 39H29 39H29 39H29 39H29

5/8 in. tubing 50A93 50A93 50A93 50A93

Mounting Base (MB2−S) − Shipping Weight 69J06 − 6 lbs. (3 kg) 69J06 − 6 lbs. (3 kg) 69J06 − 6 lbs. (3 kg) 69J06 − 6 lbs. (3 kg)

RefrigerantLine Set

15 ft. (4.6 m) length L15−41−15 L15−65−15 L15−65−15 Field FabricateLine Set

20 ft. (6 m) length L15−41−20 − − − − − − Field Fabricate

30 ft. (9.1 m) length L15−41−30 L15−65−30 L15−65−30 Field Fabricate

40 ft. (12.2 m) length L15−41−40 L15−65−40 L15−65−40 Field Fabricate

50 ft. (15.2 m) length L15−41−50 L15−65−50 L15−65−50 Field Fabricate

Unit Stand�Off Kit 94J45 94J45 94J45 94J45

NOTE − Extremes of operating range are plus 10% and minus 5% of line voltage.1 Refrigerant charge is sufficient for 15 ft. (4.6 m) length line set.2 HACR type breaker or fuse.3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.

HS29 / Page 5

Page 6: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

SPECIFICATIONS − 3 PHASE

General Model No. HS29−036 HS29−042 HS29�048 HS29�060 HS29�062GeneralData

Nominal Size − Tons (kW) 3 (10.6) 3.5 (12.3) 4 (14.1) 5 (17.6) 5+ (17.6+)

Connections(sweat)

Liquid line o.d. − in. (mm) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5)(sweat)

Suction line o.d. − in. (mm) 3/4 (19.1) 7/8 (22.2) 7/8 (22.2) 1�1/8 (28.6) 1�1/8 (28.6)

1 Refrigerant (HCFC�22) furnished 4 lbs. 13 oz.(2.18 kg)

5 lbs. 6 oz.(2.44 kg)

6 lbs. 0 oz.(2.72 kg)

7 lbs. 7 oz.(3.37 kg)

8 lbs. 0 oz.(3.63 kg)

CondenserC il

Net face area2

Outer Coil 15.11 (1.40) 15.11 (1.40) 15.11 (1.40) 15.11 (1.40) 15.11 (1.40)Coil

Net face area− sq. ft. (m2) Inner Coil − − − 5.40 (0.50) 5.40 (0.50) 14.40 (1.34) 14.40 (1.34)

Tube diameter − in. (mm) 5/16 (7.9) 5/16 (7.9) 5/16 (7.9) 5/16 (7.9) 5/16 (7.9)

Number of rows 1 1.37 1.37 2 2

Fins per inch (m) 22 (866) 18 (748) 18 (748) 18 (748) 18 (748)

CondenserF

Diameter − in. (mm) & no. of blades 18 (457) − 4 18 (457) − 4 18 (457) − 4 18 (457) − 4 18 (457) − 4Fan Motor hp (W) 1/6 (124) 1/6 (124) 1/3 (249) 1/3 (249) 1/3 (249)

Cfm (L/s) 2520 (1195) 2610 (1230) 3115 (1470) 2930 (1385) 2930 (1385)

Rpm 1110 1105 1125 1100 1100

Watts 200 200 325 310 310

CondenserFan

Diameter − in. (mm) 18 (457) 18 (457) 18 (457) 18 (457) 18 (457)Fan

Number of blades 4 4 4 4 4

Motor output − hp (W) 1/6 (124) 1/6 (124) 1/3 (249) 1/3 (249) 1/3 (249)

Shipping Data − lbs. (kg) 1 package 145 (66) 158 (72) 191 (87) 207 (94) 254 (115)

ELECTRICAL DATA

ElectricalData (60 hz)

Line voltage data − 3 phase 208/230V 460V 208/230V 460V 208/230V 460V 575V 208/230V 460V 575V 208/230V 460VData (60 hz)

2 Maximum overcurrent protection (amps) 20 10 25 15 30 15 10 40 20 15 40 20

3 Minimum circuit ampacity 14.0 6.9 16.6 8.6 18.8 10.2 8.2 23.5 12.2 9.8 23.5 12.2

Compressor Rated load amps 10.3 5.1 12.4 6.4 13.5 7.4 5.8 17.3 9.0 7.1 17.3 9.0

Locked rotor amps 77.0 39.0 88.0 44.0 91.0 49.0 40.0 128.0 64.0 50.0 137 62.0

Power factor .83 .83 .93 .93 .88 .88 .88 .86 .86 .86 .86 .86

Condenser Fan Full load amps 1.1 0.55 1.1 0.55 1.9 0.9 0.9 1.9 0.9 0.9 1.9 0.9

Locked rotor amps 1.9 1.0 1.9 1.0 4.1 2.1 2.1 4.1 2.1 2.1 4.1 2.1

Optional Accessories − MUST BE ORDERED EXTRA

Compressor Crankcase Heater − − − − − − 90P12 31J21 90P12 31J21 42J85 90P12 31J21 42J85 90P12 31J21

Compressor Low Ambient Cut−Off 45F08 45F08 45F08 45F08 45F08

Compressor Time−Off Control 47J27 47J27 47J27 47J27 47J27

Compressor Sound Cover 53J40 69J03 69J03 69J03 69J03

Freezestat 3/8 in. tubing 93G35 93G35 93G35 93G35 93G35

1/2 in. tubing 39H29 39H29 39H29 39H29 39H29

5/8 in. tubing 50A93 50A93 50A93 50A93 50A93

Hail Guards 17L73 17L73 17L73 17L73 17L73

Loss of Charge Kit 94J47 94J47 94J47 94J47 94J47

Low Ambient Kit 24H77 24H77 24H77 24H77 24H77

High Pressure Switch Kit 94J46 94J46 94J46 94J46 94J46

Mounting Base (MB2−S) − Ship. Weight − lbs. (kg) 69J06 − 6 (3) 69J06 − 6 (3) 69J06 − 6 (3) 69J06 − 6 (3) 69J06 − 6 (3)

RefrigerantLine Set

15 ft. (4.6 m) length L15−41−15 L15−41−15 L15−65−15 L15−65−15 Field FabricateLine Set

20 ft. (6 m) length L15−41−20 L15−41−20 − − − − − − Field Fabricate

30 ft. (9.1 m) length L15−41−30 L15−41−30 L15−65−30 L15−65−30 Field Fabricate

40 ft. (12.2 m) length L15−41−40 L15−41−40 L15−65−40 L15−65−40 Field Fabricate

50 ft. (15.2 m) length L15−41−50 L15−41−50 L15−65−50 L15−65−50 Field Fabricate

Unit Stand�Off Kit 94J45 94J45 94J45 94J45 94J45

NOTE − Extremes of operating range are plus 10% and minus 5% of line voltage.1 3/8 x 5/16 in. (9.5 x 7.9 mm) adaptor furnished for liquid line connection.� Refrigerant charge is sufficient for 15 ft. (4.6 m) length line set.3 HACR type breaker or fuse.4 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.

HS29 / Page 6

Page 7: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

DIMENSIONS − INCHES (MM)

24−1/4(616)

24−1/4(616)

SIDE VIEW

SUCTION &LIQUID LINE

CONNECTION

INLET

AIR

INLET

AIR

DISCHARGE AIR

SIDE VIEW

TOP VIEW

A

CONDENSERCOIL FAN

COMPRESSOR

INLET AIR

INLET AIR

B

2−3/4 (70)

ELECTRICALINLETS

OPTIONAL UNITSTAND−OFF KIT (4)

(Field Installed)

4−3/8(111)

6−3/8(162)

6−3/8(162)

TOP VIEW BASE SECTION

2 (51)

3/4(19)

4−3/8(111)

4−3/8(111)

4−3/8(111)

4−3/8(111)

4−3/8(111)

COMPRESSOR

COIL DRAIN OUTLETS(Around perimeter of base)

OPTIONAL UNITSTAND−OFF KIT (4)

(Field Installed)

LIQUID LINECONNECTION

SUCTION LINECONNECTION

Model No. A B

HS29−012, HS29−018 in. 25 24−1/4HS29−012, HS29−018HS29−024 mm 635 616

HS29−030 in. 29 28−1/4

mm 737 718

HS29−036, HS29−042 in. 33 32−1/4HS29−036, HS29−042HS29−048, HS29−060, HS29−062 mm 838 819

OUTDOOR SOUND DATA

1 ModelN b

Octave Band Sound Power Levels dBA, re 10−12 Watts 1 Sound RatingN b (dB)Number 125 250 500 1000 2000 4000 8000

gNumber (dB)

HS29�018 70 69 70 68 69 63 61 76

HS29�024 71 71 70 70 68 64 62 76

HS29�030 71 66 70 73 66 65 62 76

HS29�036 71 68 71 73 67 64 61 78

HS29�042 71 70 72 72 69 66 64 78

HS29�048 76 73 76 75 73 69 64 80

HS29�060 75 73 76 76 73 70 64 80

NOTE − the octave sound power data does not include tonal correction.1 Tested according to ARI Standard 270�95 test conditions.

HS29 / Page 7

Page 8: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

ARI RATINGS

Outdoor Unit Model No2 ARI Standard 210/240 Ratings

Outdoor Unit Model No.Unit Size1 S d R ti N b

Cooling Capacity Efficiency TotalUnit

RefrigerantMetering

Unit Size1 Sound Rating Number

Btuh kW SEER EERUnit

Watts Indoor Unit Model No.

gMeteringDevice

HS29�0121 T

Expansion Valve1 Ton(74 dB)

Up�FlowC il

12,200 3.6 10.05 9.95 1225 C33−18A 26K49 Order separately(74 dB)1 phase

pCoils 12,200 3.6 10.05 9.95 1225 C23−21 26K49 Order separately

1 phase12,500 3.7 11.00 10.05 1245 C26−21 Factory Installed

12,700 3.7 11.00 10.15 1250 C33−30A/B 26K49 Order separately

12,700 3.7 11.00 10.15 1250 3 C26−26 Factory Installed

Down�FlowCoils

12,300 3.6 11.00 9.90 1245 CR26−18 26K49 Order separately

HorizontalC il

12,000 3.5 10.00 9.70 1235 CH33−18A−F 26K49 Order separatelyCoils 12,000 3.5 10.00 9.70 1235 CH23−21 26K49 Order separately

12,500 3.7 10.30 10.10 1235 CH33−36−A/B/C−F 26K49 Order separately

12,500 3.7 10.30 10.10 1235 CH23−31 26K49 Order separately

Blower CoilU it

12,800 3.8 10.50 10.15 1260 CB29M−21/26 (Multi−Position) Factory InstalledUnits 12,800 3.8 10.50 10.15 1260 CB28UH−018/024 (Up−Flow/Horizontal) Factory Installed

13,200 3.9 11.05 10.25 1290 CB30M−21/26 (Multi−Position) Factory Installed

13,200 3.9 11.05 10.25 1290 CB30U−21/26 (Up−Flow) Factory Installed

12,400 3.6 11.00 9.95 1245 4 CVP10−26/EC10Q3 (Up−Flow) Factory Installed

RFCIV Metering Orifice

Up�FlowC il

12,200 3.6 10.05 9.95 1225 C33−18A 5 0.047 (42J35)pCoils 12,200 3.6 10.05 9.95 1225 C23−21 5 0.047 (42J35)

Down�FlowCoils

12,300 3.6 10.05 9.90 1245 CR26−18 5 0.047 (42J35)

HorizontalC il

12,000 3.5 10.00 9.70 1235 CH33−18A−F 5 0.047 (42J35)Coils 12,000 3.5 10.00 9.70 1235 CH23−21 5 0.047 (42J35)

12,500 3.7 10.30 10.10 1235 CH33−36A/B/C−F 5 0.047 (42J35)

12,500 3.7 10.30 10.10 1235 CH23−31 5 0.047 (42J35)

HS29�0181 5 T

Expansion Valve1.5 Ton(76 dB)

Up�FlowC il

18,000 5.3 10.20 10.20 1765 C33−18A 26K49 Order separately(76 dB)1 phase

pCoils 18,000 5.3 10.20 10.20 1765 C23−21 26K49 Order separately

1 phase19,000 5.6 11.50 10.95 1735 C33−30A/B 26K49 Order separately

19,000 5.6 11.50 10.95 1735 3 C23−26 26K49 Order separately

19,000 5.6 11.55 11.00 1730 C26−21 Factory Installed

19,400 5.7 11.75 11.15 1740 C26−26 Factory Installed

Down�FlowCoils

19,000 5.6 11.50 11.00 1730 CR26−18 26K49 Order separately

HorizontalC il

18,000 5.3 11.20 10.45 1720 CH33−30A−F 26K49 Order separatelyCoils 18,000 5.3 11.20 10.45 1720 CH23−21 26K49 Order separately

18,700 5.5 10.75 10.20 1830 CH33−36A/B/C−F 26K49 Order separately

18,700 5.5 10.75 10.20 1830 CH23−31 26K49 Order separately

Blower CoilU it

19,000 5.6 11.50 11.00 1725 CB29M−21/26 (Multi−Position) Factory InstalledUnits 19,000 5.6 11.50 11.00 1725 CB28UH−018/024 (Up−Flow/Horizontal) Factory Installed

19,600 5.7 12.00 11.15 1755 CB30M−21/26 (Multi−Position) Factory Installed

19,600 5.7 12.00 11.15 1755 CB30U−21/26 (Up−Flow) Factory Installed

18,900 5.5 11.50 10.90 1730 4 CVP10−26/EC10Q3 (Up−Flow) Factory Installed

RFCIV Metering Orifice

Up�FlowC il

18,000 5.5 10.20 10.20 1765 C33−18A 5 0.055 (42J39)pCoils 18,000 5.5 10.20 10.20 1765 C23−21 5 0.055 (42J39)

19,000 5.6 11.50 10.95 1735 C33−30A/B 5 0.055 (42J39)

19,000 5.6 11.50 10.95 1735 C23−26 5 0.055 (42J39)

Down�FlowCoils

18,000 5.3 11.00 10.45 1720 CR26−18 5 0.055 (42J39)

HorizontalC il

18,700 5.5 10.75 10.20 1830 CH33−36A/B/C−F 5 0.055 (42J39)Coils 18,700 5.5 10.75 10.20 1830 CH23−31 5 0.055 (42J39)

19,000 5.6 11.00 11.00 1730 CH33−30A−F 5 0.055 (42J39)

19,000 5.6 11.00 11.00 1730 CH23−21 5 0.055 (42J39)

NOTE − Ratings for all C23, C26 and C33 coils include both cased and uncased coils.1 Sound Rating Number rated in accordance with test conditions included in ARI Standard 270.2 Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95�F (35�C) outdoor air temperature, 80�F (27�C) db�/�67�F (19�C) wb

entering evaporator air with 25 ft. (7.6 m) of connecting refrigerant lines.3 Most popular evaporator coil.4 Canada Only5 RFCIV metering device is furnished with condensing unit for field installation in evaporator unit.

HS29 / Page 8

Page 9: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

ARI RATINGS

Outdoor Unit Model No2 ARI Standard 210/240 Ratings

Outdoor Unit Model No.Unit Size1 S d R ti N b

Cooling Capacity Efficiency TotalUnit

RefrigerantMetering

Unit Size1 Sound Rating Number

Btuh kW SEER EERUnit

Watts Indoor Unit Model No.

gMeteringDevice

HS29�0242 T

With Expansion Valve2 Ton(76 dB)

Up�FlowCoils

22,600 6.6 10.20 9.70 2330 C23−21 26K49 Order separately(76 dB)1 phase

Coils23,800 7.0 11.00 9.90 2405 C26−21 Factory Installed

24,200 7.1 11.00 10.00 2420 C33−24A/B 26K49 Order separately

24,200 7.1 11.00 10.00 2420 3 C23−26 26K49 Order separately

24,400 7.1 11.05 10.05 2425 C23−31 26K49 Order separately

24,800 7.3 11.20 10.20 2435 C33−30A/B 26K49 Order separately

24,800 7.3 11.20 10.20 2435 C26−26 Factory Installed

25,800 7.6 11.50 10.45 2470 C26−31 Factory Installed

Up�FlowCoils/Furnace

25,800 7.6 12.15 11.10 2325 C33−24A/B−2 with 4 G60UHV−36 26K49 Order separatelyCoils/Furnace

26,200 7.7 12.40 11.20 2340 C33−30A/B−2 with 4 G60UHV−36 26K49 Order separately

26,600 7.8 12.55 11.30 2350 C33−36A/B−2 with 4 G60UHV−36 26K49 Order separately

27,400 8.0 12.95 11.55 2375 C33−38A/B−2 with 4 G60UHV−36 26K49 Order separately

Down�FlowCoils

23,200 6.8 10.60 9.70 2390 CR26−18 26K49 Order separatelyCoils

25,400 7.4 11.30 10.35 2455 CR26−30 26K49 Order separately

HorizontalCoils

24,000 7.0 10.85 9.95 2415 CH33−30A−F 26K49 Order separatelyCoils

24,000 7.0 10.85 9.95 2415 CH23−31 26K49 Order separately

25,400 7.4 11.40 10.60 2395 CH33−36A/B/C−F 26K49 Order separately

25,400 7.4 11.40 10.60 2395 CH23−41 26K49 Order separately

HorizontalCoils/Furnace

26,000 7.6 12.30 11.15 2335 CH33−24/30A−2F with 4 G60UHV−36 26K49 Order separatelyCoils/Furnace

26,600 7.8 12.65 11.30 2350 CH33−36A/B−2F with 4 G60UHV−36 26K49 Order separately

27,400 8.0 12.90 11.55 2370 CH33−42B−2F with 4 G60UHV−36 26K49 Order separately

Blower CoilUnits

23,800 7.0 11.05 9.95 2390 CB29M−21/26 (Multi−Position) Factory InstalledUnits

23,800 7.0 11.05 9.95 2390 CB28UH−018/024 (Up−Flow/Horizontal) Factory Installed

24,000 7.0 11.05 9.90 2425 CB29M−31 (Multi−Position) Factory Installed

24,000 7.0 11.05 9.90 2425 CB28UH−030 (Up−Flow/Horizontal) Factory Installed

25,000 7.3 11.50 10.20 2450 CB30M−21/26 (Multi−Position) Factory Installed

25,000 7.3 11.50 10.20 2450 CB30U−21/26 (Up−Flow) Factory Installed

26,000 7.6 12.05 10.80 2410 CB30M−31(Multi−Position) Factory Installed

26,000 7.6 12.05 10.80 2410 CB30U−31 (Up−Flow) Factory Installed

24,200 7.1 11.00 10.00 2420 5 CVP10−26/EC10Q3 (Up−Flow) Factory Installed

With RFCIV Metering Orifice

Up�FlowCoils

24,200 7.1 11.00 10.00 2420 C33−24A/B 6 0.062 (66J87)Coils

24,200 7.1 11.00 10.00 2420 C23−26 6 0.062 (66J87)

24,400 7.1 11.05 10.05 2425 C23−31 6 0.062 (66J87)

24,400 7.1 11.05 10.05 2425 C33−30A/B 6 0.062 (66J87)

Down�FlowCoils

23,200 6.8 10.00 9.70 2390 CR26−18 6 0.062 (66J87)Coils

25,400 7.4 11.00 10.35 2455 CR26−30 6 0.062 (66J87)

HorizontalCoils

24,000 7.0 10.65 9.95 2415 CH33−30A−F 6 0.062 (66J87)Coils

24,000 7.0 10.65 9.95 2415 CH23−31 6 0.062 (66J87)

25,400 7.4 11.40 10.60 2395 CH33−36A/B/C−F 6 0.062 (66J87)

25,400 7.4 11.40 10.60 2395 CH23−41 6 0.062 (66J87)

NOTE − Ratings for all C23, C26 and C33 coils include both cased and uncased coils.1 Sound Rating Number rated in accordance with test conditions included in ARI Standard 270.2 Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95�F (35�C) outdoor air temperature, 80�F (27�C) db�/�67�F (19�C) wb

entering evaporator air with 25 ft. (7.6 m) of connecting refrigerant lines.3 Most popular evaporator coil.4 Includes all heat sizes for this model.5 Canada Only6 RFCIV metering device is furnished with condensing unit for field installation in evaporator unit.

HS29 / Page 9

Page 10: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

ARI RATINGS

Outdoor Unit Model No2 ARI Standard 210/240 Ratings

Outdoor Unit Model No.Unit Size1 S d R ti N b

Cooling Capacity Efficiency TotalUnit

RefrigerantMetering

Unit Size1 Sound Rating Number

Btuh kW SEER EERUnit

Watts Indoor Unit Model No.

gMeteringDevice

HS29�0302 5 T

With Expansion Valve2.5 Ton(78 dB)

Up�FlowC il

29,000 8.5 10.20 9.25 3135 C23−26 26K34 Order separately(78 dB)1 phase

pCoils 29,800 8.7 10.35 9.40 3170 C33−30A/B 26K34 Order separately

1 phase29,800 8.7 10.35 9.40 3170 C23−31 26K34 Order separately

30,200 8.9 10.35 9.50 3180 C33−36A/B/C 26K34 Order separately

30,200 8.9 10.35 9.50 3180 C23−41 26K34 Order separately

30,200 8.9 10.35 9.50 3180 C26−26 Factory Installed

30,200 8.9 10.85 9.80 3085 C26−31 Factory Installed

31,400 9.2 11.00 9.85 3190 C33−38A/B 26K34 Order separately

31,400 9.2 11.00 9.85 3190 3 C26−41 Factory Installed

Up�FlowC il /F

31,000 9.1 11.65 10.20 3045 C33−30A/B−2 with 4 G60UHV−36 26K34 Order separatelypCoils/Furnace 31,400 9.2 11.80 10.30 3055 C33−36A/B−2 with 4 G60UHV−36 26K34 Order separately

32,400 9.5 12.10 10.55 3075 C33−38A/B−2 with 4 G60UHV−36 26K34 Order separately

Down�FlowC il

28,000 8.2 10.00 9.00 3130 CR26−18 26K34 Order separatelyCoils 30,200 8.9 10.35 9.50 3180 CR26−30 26K34 Order separately

30,200 8.9 11.00 9.85 3070 CR26−36 26K34 Order separately

HorizontalC il

29,000 8.5 10.20 9.25 3135 CH23−21 26K34 Order separatelyCoils 29,200 8.6 10.25 9.35 3125 CH33−30A−F 26K34 Order separately

29,200 8.6 10.25 9.35 3125 CH23−31 26K34 Order separately

30,200 8.9 11.00 9.85 3070 CH33−36A/B/C−F 26K34 Order separately

30,200 8.9 11.00 9.85 3070 CH23−41 26K34 Order separately

31,400 9.2 11.00 9.85 3190 CH33−42B−F 26K34 Order separately

31,400 9.2 11.00 9.85 3190 CH23−51 26K34 Order separately

HorizontalC il /F

30,800 9.0 11.55 10.15 3040 CH33−24/30A−2F with 4 G60UHV−36 26K34 Order separatelyCoils/Furnace 31,400 9.2 11.80 10.30 3050 CH33−36A/B−2F with 4 G60UHV−36 26K34 Order separately

32,400 9.5 12.10 10.55 3075 CH33−42B−2F with 4 G60UHV−36 26K34 Order separately

Blower CoilU it

29,800 8.7 10.00 9.00 3315 CB29M−21/26 (Multi−Position) Factory InstalledUnits 29,800 8.7 10.00 9.00 3315 CB28UH−018/024 (Up−Flow/Horizontal) Factory Installed

29,800 8.7 10.20 9.35 3190 CB29M−31 (Multi−Position) Factory Installed

29,800 8.7 10.20 9.35 3190 CB28UH−030 (Up−Flow/Horizontal) Factory Installed

30,200 8.9 10.25 9.45 3195 CB29M−41 (Multi−Position) Factory Installed

30,200 8.9 10.25 9.45 3195 CB28UH−036 (Up−Flow/Horizontal) Factory Installed

30,400 8.9 10.50 9.80 3100 CB30M−21/26 (Multi−Position) Factory Installed

30,400 8.9 10.50 9.80 3100 CB30U−21/26 (Up−Flow) Factory Installed

31,800 9.3 11.10 10.20 3120 CB30M−31 (Multi−Position) Factory Installed

31,800 9.3 11.10 10.20 3120 CB30U−31 (Up−Flow) Factory Installed

32,000 9.4 11.05 10.10 3170 CB30M−41 (Multi−Position) Factory Installed

32,000 9.4 11.05 10.10 3170 CB30U−41/46 (Up−Flow) Factory Installed

32,200 9.4 11.50 10.60 3040 CB31MV−41 (Multi−Position) Factory Installed

29,800 8.7 10.00 9.35 3185 5 CVP10−31/EC10Q3 Factory Installed

30,200 8.9 10.00 9.45 3195 5 CVP10−41/EC10Q3 Factory Installed

With RFCIV Metering Orifice

Up�FlowC il

29,000 8.5 10.00 9.25 3135 C23−26 6 0.067 (42J45)pCoils 29,800 8.7 10.15 9.40 3170 C33−30A/B 6 0.067 (42J45)

29,800 8.7 10.15 9.40 3170 C23−31 6 0.067 (42J45)

30,200 8.9 10.15 9.50 3180 C33−36A/B/C 6 0.067 (42J45)

30,200 8.9 10.15 9.50 3180 C23−41 6 0.067 (42J45)

Down�FlowC il

28,000 8.2 10.00 9.00 3110 CR26−18 6 0.067 (42J45)Coils 30,200 8.9 10.15 9.50 3180 CR26−30 6 0.067 (42J45)

30,200 8.9 10.50 9.85 3065 CR26−36 6 0.067 (42J45)

HorizontalC il

29,000 8.5 10.00 9.25 3135 CH23−21 6 0.067 (42J45)Coils 29,200 8.6 10.00 9.35 3125 CH33−30A−F 6 0.067 (42J45)

29,200 8.6 10.00 9.35 3125 CH23−31 6 0.067 (42J45)

30,200 8.9 10.50 9.85 3065 CH33−36A/B/C−F 6 0.067 (42J45)

30,200 8.9 10.50 9.85 3065 CH23−41 6 0.067 (42J45)

NOTE − Ratings for all C23, C26 and C33 coils include both cased and uncased coils.1 Sound Rating Number rated in accordance with test conditions included in ARI Standard 270.2 Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95�F (35�C) outdoor air temperature, 80�F (27�C) db�/�67�F (19�C) wb

entering evaporator air with 25 ft. (7.6 m) of connecting refrigerant lines.3 Most popular evaporator coil.4 Includes all heat sizes for this model.5 Canada Only6 RFCIV metering device is furnished with condensing unit for field installation in evaporator unit.

HS29 / Page 10

Page 11: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

ARI RATINGS

Outdoor Unit Model No2 ARI Standard 210/240 Ratings

Outdoor Unit Model No.Unit Size1 S d R ti N b

Cooling Capacity Efficiency TotalUnit

RefrigerantMetering

Unit Size1 Sound Rating Number

Btuh kW SEER EERUnit

Watts Indoor Unit Model No.

gMeteringDevice

HS29�0363 T

With Expansion Valve3 Ton(78 dB)

Up�FlowCoils

33,000 9.7 10.00 9.00 3665 C23−31 26K34 Order separately(78 dB)1 phase

pCoils

34,000 10.0 10.15 9.20 3695 C33−36A/B/C 26K34 Order separately1 phase

34,000 10.0 10.15 9.20 3695 C23−41 26K34 Order separately

34,800 10.2 10.50 9.55 3645 C26−31 Factory Installed

35,400 10.4 10.30 9.30 3805 C33−42B 26K34 Order separately

35,400 10.4 10.30 9.30 3805 C23−46 26K34 Order separately

35,400 10.4 11.00 9.80 3610 C33−38A/B 26K34 Order separately

35,400 10.4 11.00 9.80 3610 3 C26−41 Factory Installed

36,400 10.7 10.50 9.85 3695 C33−48B/C 26K34 Order separately

36,400 10.7 10.50 9.85 3695 C23−51 26K34 Order separately

36,600 10.7 11.00 9.85 3715 C33−44C 26K34 Order separately

36,600 10.7 11.00 9.85 3715 C26−46 26K34 Order separately

37,000 10.8 11.10 9.85 3755 C26−51/65 26K34 Order separately

Up�FlowCoils/Furnace

37,400 11.0 11.55 10.25 3655 C33−36A/B−2 with 4 G60UHV−36 26K34 Order separatelypCoils/Furnace

39,500 11.6 12.20 10.70 3700 C33−38A/B−2 with 4 G60UHV−36 26K34 Order separately

Down�FlowCoils

34,800 10.2 10.50 9.50 3665 CR26−36N Only 26K34 Order separatelyCoils

35,800 10.5 10.50 9.60 3730 CR26−36W Only 26K34 Order separately

36,000 10.6 11.00 9.80 3675 CR26−48 26K34 Order separately

HorizontalCoils

34,800 10.2 10.30 9.30 3745 CH33−36A/B/C−F 26K34 Order separatelyCoils

34,800 10.2 10.30 9.30 3745 CH23−41 26K34 Order separately

35,400 10.4 11.00 9.80 3610 CH33−48C−F 26K34 Order separately

35,400 10.4 11.00 9.80 3610 CH23−51 26K34 Order separately

HorizontalCoils/Furnace

37,400 11.0 11.65 10.25 3650 CH33−36A/B−2F with 4 G60UHV−36 26K34 Order separatelyCoils/Furnace

39,000 11.4 12.05 10.55 3690 CH33−42B−2F with 4 G60UHV−36 26K34 Order separately

39,500 11.6 12.20 10.70 3700 CH33−44/48B−2F with 4 G60UHV−36 26K34 Order separately

Blower CoilUnits

33,400 9.8 10.00 9.20 3630 CB29M−31 (Multi−Position) Factory InstalledUnits

33,400 9.8 10.00 9.20 3630 CB28UH−030 (Up−Flow/Horizontal) Factory Installed

34,000 10.0 10.00 9.20 3695 CB29M−41 (Multi−Position) Factory Installed

34,000 10.0 10.00 9.20 3695 CB28UH−036 (Up−Flow/Horizontal) Factory Installed

35,000 10.3 10.80 9.65 3625 CB30M−31 (Multi−Position) Factory Installed

35,000 10.3 10.80 9.65 3625 CB30U−31 (Up−Flow) Factory Installed

36,000 10.6 10.50 9.60 3750 CB29M−46 (Multi−Position) 6 26K34

36,000 10.6 10.50 9.60 3750 CB28UH−042 (Up−Flow/Horizontal) 6 26K34

36,400 10.7 11.00 10.00 3640 CB30M−41 (Multi−Position) Factory Installed

36,400 10.7 11.00 10.00 3640 CB30U−41/46 (Up−Flow) 6 26K34

36,400 10.7 11.10 10.00 3640 CB30M−46 (Multi−Position) 6 26K34

36,400 10.7 11.20 10.10 3605 CB31MV−41 (Multi−Position) Factory Installed

34,600 10.1 10.00 9.30 3720 5 CVP10−41/EC10Q3 Factory Installed

34,600 10.1 10.00 9.30 3720 5 CVP10−46/EC10Q4 Factory Installed

With RFCIV Metering Orifice

Up�FlowCoils

34,000 10.0 10.00 9.20 3695 C33−36A/B/C 0.073 (42J48)pCoils

34,000 10.0 10.00 9.20 3695 C23−41 0.073 (42J48)

35,400 10.4 10.10 9.30 3805 C33−42B 0.073 (42J48)

35,400 10.4 10.10 9.30 3805 C23−46 0.073 (42J48)

Down�FlowCoils

34,800 10.2 10.20 9.50 3665 CR26−36N 0.073 (42J48)Coils

35,800 10.5 10.20 9.60 3730 CR26−36W 0.073 (42J48)

HorizontalCoils

34,800 10.2 10.10 9.30 3740 CH33−36A/B/C−F 0.073 (42J48)Coils

34,800 10.2 10.10 9.30 3740 CH23−41 0.073 (42J48)

NOTE − Ratings for all C23, C26 and C33 coils include both cased and uncased coils.1 Sound Rating Number rated in accordance with test conditions included in ARI Standard 270.2 Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95�F (35�C) outdoor air temperature, 80�F (27�C) db�/�67�F (19�C) wb enter�ing evaporator air with 25 ft. (7.6 m) of connecting refrigerant lines.3 Most popular evaporator coil.4 Includes all heat sizes for this model.5 Canada Only6 Factory installed expansion valve on indoor unit MUST be replaced with valve specified, order separately.7 RFCIV metering device is furnished with condensing unit for field installation in evaporator unit.

HS29 / Page 11

Page 12: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

ARI RATINGS

Outdoor Unit Model No2 ARI Standard 210/240 Ratings

Outdoor Unit Model No.Unit Size1 S d R ti N b

Cooling Capacity Efficiency TotalUnit

RefrigerantMetering

Unit Size1 Sound Rating Number

Btuh kW SEER EERUnit

Watts Indoor Unit Model No.

gMeteringDevice

HS29�0363 T

With Expansion Valve3 Ton(78 dB)

Up�FlowCoils

34,000 10.0 10.00 9.40 3620 C33−36A/B/C 26K34 Order separately(78 dB)3 phase

Coils34,000 10.0 10.00 9.40 3620 C23−41 26K34 Order separately

34,800 10.2 10.00 9.80 3560 C26−31 Factory Installed

35,400 10.4 10.00 9.60 3685 C33−42B 26K34 Order separately

35,400 10.4 10.00 9.60 3685 C23−46 26K34 Order separately

36,200 10.6 10.00 9.80 3700 C33−38A/B Factory Installed

36,200 10.6 10.00 9.80 3700 C26−41 26K34 Order separately

36,600 10.7 10.00 9.85 3725 C33−44C 3 26K34

36,600 10.7 10.00 9.85 3725 C26−46 26K34 Order separately

36,800 10.8 10.00 9.85 3740 C33−48B/C 26K34 Order separately

36,800 10.8 10.00 9.85 3740 C23−51 26K34 Order separately

Down�FlowCoils

35,800 10.5 10.00 9.80 3655 CR26−36 26K34 Order separately

HorizontalCoils

35,600 10.4 10.00 9.65 3695 CH33−36A/B/C−F 26K34 Order separatelyCoils

35,600 10.4 10.00 9.65 3695 CH23−41 26K34 Order separately

Blower CoilUnits

33,400 9.8 10.05 9.40 3560 CB29M−31 (Multi−Position) Factory InstalledUnits

33,400 9.8 10.05 9.40 3560 CB28UH−030 (Up−Flow/Horizontal) Factory Installed

34,000 10.0 10.05 9.25 3675 CB29M−41 (Multi−Position) Factory Installed

34,000 10.0 10.05 9.25 3675 CB28UH−036 (Up−Flow/Horizontal) Factory Installed

35,000 10.3 10.80 9.65 3625 CB30M−31 (Multi−Position) Factory Installed

35,000 10.3 10.80 9.65 3625 CB30U−31 (Up−Flow) Factory Installed

36,000 10.5 10.50 9.60 3750 CB29M−46 (Multi−Position) 3 26K34

36,000 10.5 10.50 9.60 3750 CB28UH−042 (Up−Flow/Horizontal) 3 26K34

36,400 10.7 10.30 9.50 3830 CB30M−41 (Multi−Position) Factory Installed

36,400 10.7 10.30 9.50 3830 CB30U−41/46 (Up−Flow) 3 26K34

36,400 10.7 10.50 10.00 3645 CB30M−46 (Multi−Position) 3 26K34

36,400 10.7 10.50 10.10 3600 CB31MV−41 (Multi−Position) Factory Installed

37,000 10.8 10.70 10.10 3660 CB30M−51 (Multi−Position) 3 26K34

37,000 10.8 10.70 10.10 3660 CB30U−51 (Up−Flow) 3 26K34

37,400 11.0 11.05 10.55 3535 CB31MV−51 (Multi−Position) 3 26K34

35,400 10.4 10.00 9.65 3675 4 CVP10−41/EC10Q3 (Up−Flow) Factory Installed

35,400 10.4 10.00 9.65 3675 4 CVP10−46/EC10Q4 (Up−Flow) Factory Installed

With RFCIV Metering Orifice

Up�FlowCoils

34,000 10.0 10.00 9.50 3615 C33−36A/B/C 5 0.073 (42J48)Coils

34,000 10.0 10.00 9.50 3615 C23−41 5 0.073 (42J48)

35,200 10.3 10.00 9.55 3685 C33−42B 5 0.073 (42J48)

35,200 10.3 10.00 9.55 3685 C23−46 5 0.073 (42J48)

36,400 10.7 10.00 9.75 3740 C23−51 5 0.073 (42J48)

Down�FlowCoils 35,600 10.4 10.00 9.75 3655 CR26−36 5 0.073 (42J48)

HorizontalCoils

35,400 10.4 10.00 9.60 3695 CH33−36A/B/C−F 5 0.073 (42J48)Coils

35,400 10.4 10.00 9.60 3695 CH23−41 5 0.073 (42J48)

NOTE − Ratings for all C23, C26 and C33 coils include both cased and uncased coils.1 Sound Rating Number rated in accordance with test conditions included in ARI Standard 270.2 Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95�F (35�C) outdoor air temperature, 80�F (27�C) db�/�67�F (19�C) wb

entering evaporator air with 25 ft. (7.6 m) of connecting refrigerant lines.3 Factory installed expansion valve on indoor unit MUST be replaced with valve specified, order separately.4 Canada Only5 RFCIV metering device is furnished with condensing unit for field installation in evaporator unit.

HS29 / Page 12

Page 13: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

ARI RATINGS

Outdoor Unit Model No2 ARI Standard 210/240 Ratings

Outdoor Unit Model No.Unit Size1 S d R ti N b

Cooling Capacity Efficiency TotalUnit

RefrigerantMetering

Unit Size1 Sound Rating Number

Btuh kW SEER EERUnit

Watts Indoor Unit Model No.

gMeteringDevice

HS29�0423 5 T

With Expansion Valve3.5 Ton(78 dB)

Up�FlowC il

39,000 11.4 10.20 9.00 4335 C23−41 26K35 Order separately(78 dB)1 and 3

pCoils 40,000 11.7 10.25 9.15 4375 C33−42B 26K35 Order separately

1 and 3phase 40,000 11.7 10.25 9.15 4375 C23−46 26K35 Order separatelyphase

40,000 11.7 10.30 9.35 4280 C26−41 Factory Installed

41,000 12.0 10.50 9.45 4340 C33−44C 26K35 Order separately

41,000 12.0 10.50 9.45 4340 C26−46 Factory Installed

42,000 12.3 10.50 9.50 4420 C33−48B/C 26K35 Order separately

42,000 12.3 10.50 9.50 4420 C23−51 26K35 Order separately

42,000 12.3 11.00 9.80 4285 C33−50/60C 26K35 Order separately

42,000 12.3 11.00 9.80 4285 3 C26−51/65 Factory Installed

42,000 12.3 11.00 9.80 4285 C33−60D 26K35 Order separately

42,000 12.3 11.00 9.80 4285 C23−51/65 26K35 Order separately

Up�FlowC il /F

45,000 13.2 11.85 10.45 4310 C33−44C−2 with G60UHV−60C−090 26K35 Order separatelypCoils/Furnace 45,000 13.2 11.90 10.45 4315 C33−48C−2 with G60UHV−60C−090 26K35 Order separately

45,500 13.3 12.00 10.50 4325 C33−50/60C−2 with G60UHV−60C−090 26K35 Order separately

Down�FlowC il

37,600 11.0 10.00 9.15 4110 CR26−36N Only 26K35 Order separatelyCoils 40,000 11.7 10.20 9.35 4280 CR26−36W Only 26K35 Order separately

41,000 12.0 10.30 9.35 4385 CR26−48 26K35 Order separately

42,000 12.3 11.00 9.80 4285 CR26−60 26K35 Order separately

HorizontalC il

40,500 11.9 10.20 9.30 4355 CH33−42B−F 26K35 Order separatelyCoils 40,500 11.9 10.20 9.30 4355 CH23−41 26K35 Order separately

41,500 12.2 10.30 9.45 4395 CH33−48C−F 26K35 Order separately

41,500 12.2 10.30 9.45 4395 CH23−51 26K35 Order separately

42,000 12.3 11.00 9.80 4285 CH33−60D−F 26K35 Order separately

42,000 12.3 11.00 9.80 4285 CH23−65 26K35 Order separately

HorizontalCoils/Furnace

45,500 13.3 12.05 10.50 4330 CH33−48C−2F withG60UHV−60C−090

26K35 Order separately

46,000 13.5 12.15 10.60 4345 CH33−50/60C−2F withG60UHV−60C−090

26K35 Order separately

Blower CoilU it

39,000 11.4 10.00 8.90 4385 CB29M−41 (Multi−Position) Factory InstalledUnits 39,000 11.4 10.00 8.90 4385 CB28UH−036 (Up−Flow/Horizontal) Factory Installed

40,000 11.7 10.50 9.55 4190 CB30M−41 (Multi−Position) Factory Installed

41,000 12.0 10.50 9.40 4365 CB29M−46 (Multi−Position) Factory Installed

41,000 12.0 10.50 9.40 4365 CB28UH−042 (Up−Flow/Horizontal) Factory Installed

41,000 12.0 10.25 9.15 4480 CB29M−51 (Multi−Position) Factory Installed

41,000 12.0 10.25 9.15 4480 CB28UH−048 (Up−Flow/Horizontal) Factory Installed

41,500 12.2 11.00 9.80 4235 CB30M−46 (Multi−Position) Factory Installed

41,500 12.2 11.00 9.80 4235 CB30U−41/46 (Up−Flow) Factory Installed

41,500 12.2 11.00 9.80 4235 CB31MV−41 (Multi−Position) Factory Installed

42,500 12.5 11.05 9.85 4315 CB30M−51 (Multi−Position) Factory Installed

42,500 12.5 11.05 9.85 4315 CB30U−51 (Up−Flow) Factory Installed

42,500 12.5 11.20 10.05 4230 CB31MV−51 (Multi−Position) Factory Installed

40,000 11.7 10.00 9.05 4420 4 CVP10−46/EC10Q4 (Up−Flow) Factory Installed

40,000 11.7 10.00 9.05 4420 4 CVP10−51/EC10Q4 (Up−Flow) Factory Installed

With RFCIV Metering Orifice

Up�FlowC il

39,000 11.4 10.00 9.00 4335 C23−41 5 0.078 (42J51)pCoils 40,000 11.7 10.00 9.15 4375 C33−42B 5 0.078 (42J51)

40,000 11.7 10.00 9.15 4375 C23−46 5 0.078 (42J51)

42,000 12.3 10.20 9.50 4420 C33−48B/C 5 0.078 (42J51)

42,000 12.3 10.20 9.50 4420 C23−51 5 0.078 (42J51)

Down�FlowC il

40,000 11.7 10.00 9.35 4280 CR26−36W 5 0.078 (42J51)Coils 41,000 12.0 10.00 9.35 4385 CR26−48 5 0.078 (42J51)

HorizontalC il

40,500 11.9 10.00 9.30 4355 CH33−42B−F 5 0.078 (42J51)Coils 40,500 11.9 10.00 9.30 4355 CH23−41 5 0.078 (42J51)

41,500 12.2 10.00 9.45 4395 CH33−48C−F 5 0.078 (42J51)

41,500 12.2 10.00 9.45 4395 CH23−51 5 0.078 (42J51)

NOTE − Ratings for all C23, C26 and C33 coils include both cased and uncased coils.1 Sound Rating Number rated in accordance with test conditions included in ARI Standard 270.2 Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95�F (35�C) outdoor air temperature, 80�F (27�C) db�/�67�F (19�C) wb

entering evaporator air with 25 ft. (7.6 m) of connecting refrigerant lines.3 Most popular evaporator coil.4 Canada Only5 RFCIV metering device is furnished with condensing unit for field installation in evaporator unit.

HS29 / Page 13

Page 14: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

ARI RATINGS

Outdoor Unit Model No2 ARI Standard 210/240 Ratings

Outdoor Unit Model No.Unit Size1 S d R ti N b

Cooling Capacity Efficiency TotalUnit

RefrigerantMetering

Unit Size1 Sound Rating Number

Btuh kW SEER EERUnit

Watts Indoor Unit Model No.

gMeteringDevice

HS29�0484 T

With Expansion Valve4 Ton(80 dB)

Up�FlowC il

44,000 12.9 10.80 9.60 4585 C26−41 3 26K35(80 dB)1 phase

pCoils 45,000 13.2 10.85 9.75 4615 C33−44C 26K35 Order separately

1 phase45,000 13.2 10.85 9.75 4615 C26−46 Factory Installed

46,500 13.6 10.75 9.55 4870 C33−48B/C 26K35 Order separately

46,500 13.6 10.75 9.55 4870 C23−51 26K35 Order separately

46,500 13.6 11.00 9.80 4745 C33−50/60C 26K35 Order separately

46,500 13.6 11.00 9.80 4745 4 C26−51/65 Factory Installed

47,000 13.8 10.80 9.70 4845 C33−60D 26K35 Order separately

47,000 13.8 10.80 9.70 4845 C23−51/65 26K35 Order separately

48,000 14.1 11.05 10.00 4800 C33−62D 26K35 Order separately

48,000 14.1 11.05 10.00 4800 C26−65EAP Factory Installed

Up�FlowC il /F

48,500 14.2 11.70 10.10 4805 C33−48C−2 with G60UHV−60C−090 26K35 Order separatelypCoils/Furnace 49,000 14.4 11.80 10.20 4810 C33−50/60C−2 with

G60UHV−60C−09026K35 Order separately

Down�FlowC il

45,000 13.2 10.65 9.50 4735 CR26−48 26K35 Order separatelyCoils 46,000 13.5 11.00 9.80 4695 CR26−60 26K35 Order separately

HorizontalC il

46,000 13.5 10.85 9.65 4770 CH33−44B−F 26K35 Order separatelyCoils 46,000 13.5 10.85 9.65 4770 CH23−51 26K35 Order separately

46,500 13.6 11.00 9.75 4770 CH33−50C−F 26K35 Order separately

46,500 13.6 11.00 9.75 4770 CH23−65 26K35 Order separately

48,000 14.1 11.00 10.00 4800 CH33−62D−F 26K35 Order separately

48,000 14.1 11.00 10.00 4800 CH23−68 26K35 Order separately

HorizontalCoils/Furnace

49,500 14.5 11.80 10.30 4815 CH33−48C−2F withG60UHV−60C−090

26K35 Order separately

50,000 14.7 11.95 10.35 4830 CH33−50/60C−2F withG60UHV−60C−090

26K35 Order separately

Blower CoilU it

44,000 12.9 10.75 9.55 4605 CB30M−41 (Multi−Position) 3 26K35Units 44,000 12.9 10.75 9.55 4605 CB30U−41/46 (Up−Flow) 4 Factory Installed

44,000 12.9 10.85 9.70 4535 CB31MV−41 (Multi−Position) 3 26K35

45,500 13.3 10.50 9.35 4865 CB29M−46 (Multi−Position) 4 Factory Installed

45,500 13.3 10.50 9.35 4865 CB28UH−042 (Up−Flow/Horizontal) 4 Factory Installed

45,500 13.3 10.60 9.40 4840 CB29M−51 (Multi−Position) 4 Factory Installed

45,500 13.3 10.60 9.40 4840 CB28UH−048 (Up−Flow/Horizontal) 4 Factory Installed

45,500 13.3 11.00 9.80 4645 CB30M−46 (Multi−Position) 4 Factory Installed

46,000 13.5 10.55 9.40 4895 CB29M−65 (Multi−Position) 4 Factory Installed

46,000 13.5 10.55 9.40 4895 CB28UH−060 (Up−Flow/Horizontal) 4 Factory Installed

46,500 13.6 11.05 9.90 4700 CB30M−51 (Multi−Position) 4 Factory Installed

46,500 13.6 11.05 9.90 4700 CB30U−51 (Up−Flow) 4 Factory Installed

46,500 13.6 11.25 10.10 4605 CB31MV−51 (Multi−Position) 4 Factory Installed

47,000 13.8 11.05 9.90 4750 CB30M−65 (Multi−Position) 4 Factory Installed

47,000 13.8 11.05 9.90 4750 CB30U−65 (Up−Flow) 4 Factory Installed

47,000 13.8 11.35 10.25 4585 CB31MV−65 (Multi−Position) 4 Factory Installed

44,000 12.9 10.00 9.15 4810 5 CVP10−51/EC10Q4 (Up−Flow) 4 Factory Installed

44,000 12.9 10.00 9.15 4810 5 CVP10−65/EC10Q5 (Up−Flow) 4 Factory Installed

With RFCIV Metering Orifice

Up�FlowC il

46,500 13.6 10.50 9.55 4870 C33−48B/C 6 0.086 (42J55)pCoils 46,500 13.6 10.50 9.55 4870 C23−51 6 0.086 (42J55)

47,000 13.8 10.50 9.70 4845 C33−60D 6 0.086 (42J55)

47,000 13.8 10.50 9.70 4845 C23−51/65 6 0.086 (42J55)

Down�FlowC il

45,000 13.2 10.25 9.50 4735 CR26−48 6 0.086 (42J55)Coils 46,000 13.5 10.60 9.80 4695 CR26−60 6 0.086 (42J55)

HorizontalC il

46,000 13.5 10.50 9.65 4770 CH33−44B−F 6 0.086 (42J55)Coils 46,000 13.5 10.50 9.65 4770 CH23−51 6 0.086 (42J55)

46,000 13.5 10.50 9.65 4770 CH33−48C−F 6 0.086 (42J55)

46,500 13.6 10.60 9.75 4770 CH33−60D−F 6 0.086 (42J55)

46,500 13.6 10.60 9.75 4770 CH23−65 6 0.086 (42J55)

NOTE − Ratings for all C23, C26 and C33 coils include both cased and uncased coils.1 Sound Rating Number rated in accordance with test conditions included in ARI Standard 270.2 Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95�F (35�C) outdoor air temperature, 80�F (27�C) db�/�67�F (19�C) wb

entering evaporator air with 25 ft. (7.6 m) of connecting refrigerant lines.3 Factory installed expansion valve on indoor unit MUST be replaced with valve specified, order separately.4 Most popular evaporator coil.5 Canada Only6 RFCIV metering device is furnished with condensing unit for field installation in evaporator unit.

HS29 / Page 14

Page 15: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

ARI RATINGS

Outdoor Unit Model No2 ARI Standard 210/240 Ratings

Outdoor Unit Model No.Unit Size1 S d R ti N b

Cooling Capacity Efficiency TotalUnit

RefrigerantMetering

Unit Size1 Sound Rating Number

Btuh kW SEER EERUnit

Watts Indoor Unit Model No.

gMeteringDevice

HS29�0484 T

With Expansion Valve4 Ton(80 dB)

Up�FlowCoils

43,500 12.7 10.00 9.20 4730 C26−41 3 26K35(80 dB)3 phase

pCoils

45,000 13.2 10.00 9.25 5705 C33−44C 26K35 Order separately3 phase

45,000 13.2 10.00 9.25 5705 C26−46 Factory Installed

46,000 13.5 10.00 9.25 4980 C33−48B/C 26K35 Order separately

46,000 13.5 10.00 9.25 4980 C23−51 26K35 Order separately

46,000 13.5 10.00 9.25 4975 C33−50/60C 26K35 Order separately

46,000 13.5 10.00 9.25 4975 C26−51/65 Factory Installed

47,000 13.8 10.00 9.35 5020 C33−60D 26K35 Order separately

47,000 13.8 10.00 9.35 5020 C23−51/65 26K35 Order separately

48,000 14.1 10.00 9.50 5065 C33−62D 26K35 Order separately

48,000 14.1 10.00 9.50 5065 C26−65EAP Factory Installed

Down�FlowCoils

46,000 13.5 10.00 9.25 4975 CR26−48 26K35 Order separatelyCoils

46,500 13.6 10.00 9.30 5010 CR26−60 26K35 Order separately

HorizontalCoils

45,500 13.3 10.00 9.15 4970 CH33−44B−F 26K35 Order separatelyCoils

45,500 13.3 10.00 9.15 4970 CH23−51 26K35 Order separately

46,000 13.5 10.00 9.20 4990 CH33−50C−F 26K35 Order separately

46,000 13.5 10.00 9.20 4990 CH23−65 26K35 Order separately

48,000 14.1 10.00 9.50 5065 CH33−62D−F 26K35 Order separately

48,000 14.1 10.00 9.50 5065 CH23−68 26K35 Order separately

Blower CoilUnits

43,500 12.7 10.20 9.35 4655 CB30M−41 (Multi−Position) 3 26K35Units

43,500 12.7 10.25 9.35 4640 CB31MV−41 (Multi−Position) 3 26K35

45,000 13.2 10.05 9.00 5000 CB29M−51 (Multi−Position) Factory Installed

45,000 13.2 10.05 9.00 5000 CB28UH−048 (Up−Flow/Horizontal) Factory Installed

45,000 13.2 10.50 9.50 4725 CB30M−46 (Multi−Position) Factory Installed

45,000 13.2 10.50 9.50 4725 CB30U−41/46 (Up−Flow) Factory Installed

45,500 13.3 10.00 9.00 5050 CB29M−65 (Multi−Position) Factory Installed

45,500 13.3 10.00 9.00 5050 CB28UH−060 (Up−Flow/Horizontal) Factory Installed

46,000 13.5 10.50 9.45 4855 CB30M−51 (Multi−Position) Factory Installed

46,000 13.5 10.50 9.45 4855 CB30U−51 (Up−Flow) Factory Installed

46,000 13.5 10.60 9.55 4805 CB31MV−51 (Multi−Position) Factory Installed

46,500 13.6 10.50 9.35 4965 CB30M−65 (Multi−Position) Factory Installed

46,500 13.6 10.50 9.35 4965 CB30U−65 (Up−Flow) Factory Installed

47,000 13.8 10.70 9.60 4885 CB31MV−65 (Multi−Position) Factory Installed

44,500 13.0 10.00 9.05 4915 4 CVP10−51/EC10Q4 (Up−Flow) Factory Installed

45,500 13.3 10.00 9.15 4965 4 CVP10−65/EC10Q5 (Up−Flow) Factory Installed

With RFCIV Metering Orifice

Up�FlowCoils

46,000 13.5 10.00 9.25 4960 C33−48B/C 5 0.086 (42J55)pCoils

46,000 13.5 10.00 9.25 4960 C23−51 5 0.086 (42J55)

47,000 13.8 10.00 9.35 5020 C33−60D 5 0.086 (42J55)

47,000 13.8 10.00 9.35 5020 C23−51/65 5 0.086 (42J55)

Down�FlowCoils

46,000 13.5 10.00 9.25 4975 CR26−48 5 0.086 (42J55)Coils

46,500 13.6 10.00 9.30 5010 CR26−60 5 0.086 (42J55)

HorizontalCoils

45,500 13.3 10.00 9.15 4970 CH33−48C−F 5 0.086 (42J55)Coils

45,500 13.3 10.00 9.15 4970 CH33−44B−F 5 0.086 (42J55)

45,500 13.3 10.00 9.15 4970 CH23−51 5 0.086 (42J55)

46,000 13.5 10.00 9.20 4990 CH33−60D−F 5 0.086 (42J55)

46,000 13.5 10.00 9.20 4990 CH23−65 5 0.086 (42J55)

NOTE − Ratings for all C23, C26 and C33 coils include both cased and uncased coils.1 Sound Rating Number rated in accordance with test conditions included in ARI Standard 270.2 Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95�F (35�C) outdoor air temperature, 80�F (27�C) db�/�67�F (19�C) wb

entering evaporator air with 25 ft. (7.6 m) of connecting refrigerant lines.3 Factory installed expansion valve on indoor unit MUST be replaced with valve specified, order separately.4 Canada Only5 RFCIV metering device is furnished with condensing unit for field installation in evaporator unit.

HS29 / Page 15

Page 16: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

ARI RATINGS

Outdoor Unit Model No2 ARI Standard 210/240 Ratings

Outdoor Unit Model No.Unit Size1 S d R ti N b

Cooling Capacity Efficiency TotalUnit

RefrigerantMetering

Unit Size1 Sound Rating Number

Btuh kW SEER EERUnit

Watts Indoor Unit Model No.

gMeteringDevice

HS29�0605 T

With Expansion Valve5 Ton(80 dB)

Up�FlowCoils

55,500 16.3 10.50 8.90 6235 C33−50/60C Factory Installed(80 dB)1 phase

Coils55,500 16.3 10.50 8.90 6235 C26−51/65 Factory Installed

58,000 17.0 10.50 9.20 6305 C33−60D 26K35 Order separately

58,000 17.0 10.50 9.20 6305 C23−51/65 26K35 Order separately

61,000 17.9 11.00 9.35 6525 C33−62D 26K35 Order separately

61,000 17.9 11.00 9.35 6525 3 C26−65EAP Factory Installed

Up�FlowCoils/Furnace

59,000 17.3 11.70 10.20 5780 C33−50/60C−2 withG60UHV−60C−090

26K35 Order separately

59,000 17.3 11.75 10.25 5755 C33−60D−2 with G60UHV−60D−135 26K35 Order separately

60,500 17.7 12.05 10.50 5770 C33−62D−2 with G60UHV−60D−135 26K35 Order separately

Down�FlowCoils

52,500 15.4 10.00 8.55 6140 CR26−48 26K35 Order separatelyCoils

54,500 16.0 10.50 8.85 6160 CR26−60N Only 26K35 Order separately

57,000 16.7 10.50 9.00 6335 CR26−60W Only 26K35 Order separately

HorizontalCoils

56,000 16.4 10.00 8.55 6550 CH33−50C−F 26K35 Order separatelyCoils

56,000 16.4 10.00 8.55 6550 CH23−51 26K35 Order separately

57,000 16.7 10.50 9.00 6335 CH33−60D−F 26K35 Order separately

57,000 16.7 10.50 9.00 6335 CH23−65 26K35 Order separately

61,000 17.9 11.00 9.35 6525 CH33−62D−F 26K35 Order separately

61,000 17.9 11.00 9.35 6525 CH23−68 26K35 Order separately

HorizontalCoils/Furnace

60,000 17.6 11.90 10.35 5795 CH33−50/60C−2F withG60UHV−60C−090

26K35 Order separately

59,500 17.4 11.90 10.30 5770 CH33−60D−2F with G60UHV−60D−135 26K35 Order separately

60,000 17.6 12.00 10.40 5765 CH33−62D−2F with G60UHV−60D−135 26K35 Order separately

Blower CoilUnits

54,500 16.0 10.05 8.65 6300 CB29M−51 (Multi−Position) Factory InstalledUnits

54,500 16.0 10.05 8.65 6300 CB28UH−048 (Up−Flow/Horizontal) Factory Installed

55,500 16.3 10.05 8.50 6530 CB29M−65 (Multi−Position) Factory Installed

55,500 16.3 10.05 8.50 6530 CB28UH−060 (Up−Flow/Horizontal) Factory Installed

55,500 16.3 10.50 8.90 6235 CB30M−51 (Multi−Position) Factory Installed

55,500 16.3 10.50 8.90 6235 CB30U−51 (Up−Flow) Factory Installed

55,500 16.3 11.00 9.55 5810 CB31MV−51 (Multi−Position) Factory Installed

58,000 17.0 11.00 9.35 6205 CB30M−65 (Multi−Position) Factory Installed

58,000 17.0 11.00 9.35 6205 CB30U−65 (Up−Flow) Factory Installed

58,000 17.0 11.00 9.35 6205 CB31MV−65 (Multi−Position) Factory Installed

53,000 15.5 10.00 8.50 6235 4 CVP10−51/EC10Q4 (Up−Flow) Factory Installed

54,500 16.0 10.00 8.50 6410 4 CVP10−65/EC10Q5 (Up−Flow) Factory Installed

With RFCIV Metering Orifice

Up�FlowCoils

58,000 17.0 10.00 9.20 6375 C33−60D 5 0.093 (78L74)Coils

58,000 17.0 10.00 9.20 6375 C23−51/65 5 0.093 (78L74)

Down�FlowCoils 57,000 16.7 10.00 9.00 6335 CR26−60W 5 0.093 (78L74)

HorizontalCoils

57,000 16.7 10.00 9.00 6335 CH33−60D−F 5 0.093 (78L74)Coils

57,000 16.7 10.00 9.00 6335 CH23−65 5 0.093 (78L74)

58,000 17.0 10.50 9.35 6205 CH33−62D−F 5 0.093 (78L74)

58,000 17.0 10.50 9.35 6205 CH23−68 5 0.093 (78L74)

NOTE − Ratings for all C23, C26 and C33 coils include both cased and uncased coils.1 Sound Rating Number rated in accordance with test conditions included in ARI Standard 270.2 Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95�F (35�C) outdoor air temperature, 80�F (27�C) db�/�67�F (19�C) wb

entering evaporator air with 25 ft. (7.6 m) of connecting refrigerant lines.3 Most popular evaporator coil.4 Canada Only8 RFCIV metering device is furnished with condensing unit for field installation in evaporator unit.

HS29 / Page 16

Page 17: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

ARI RATINGS

Outdoor Unit Model No2 ARI Standard 210/240 Ratings

Outdoor Unit Model No.Unit Size1 S d R ti N b

Cooling Capacity Efficiency TotalUnit

RefrigerantMetering

Unit Size1 Sound Rating Number

Btuh kW SEER EERUnit

Watts Indoor Unit Model No.

gMeteringDevice

HS29�0605 T

With Expansion Valve5 Ton(84 dB)

Up�FlowCoils

55,500 16.3 10.00 8.85 6285 C33−50/60C 26K35 Order separately(84 dB)3 phase

pCoils

55,500 16.3 10.00 8.85 6285 C26−51/65 Factory Installedp

57,500 16.8 10.00 9.20 6245 C33−60D 26K35 Order separately

57,500 16.8 10.00 9.20 6245 C23−51/65 26K35 Order separately

58,500 17.1 10.00 9.35 6270 C33−62D 26K35 Order separately

58,500 17.1 10.00 9.35 6270 C26−65EAP Factory Installed

Down�FlowCoils

55,500 16.3 10.00 9.30 5980 CR26−48 26K35 Order separatelyCoils

57,500 16.8 10.00 9.50 6060 CR26−60 26K35 Order separately

HorizontalCoils

58,000 17.0 10.00 9.30 6250 CH33−60D−F 26K35 Order separatelyCoils

58,000 17.0 10.00 9.30 6250 CH23−65 26K35 Order separately

58,500 17.1 10.00 9.35 6270 CH33−62D−F 26K35 Order separately

58,500 17.1 10.00 9.35 6270 CH23−68 26K35 Order separately

Blower CoilUnits

55,000 16.1 10.05 8.65 6360 CB29M−51 (Multi−Position) Factory InstalledUnits

55,000 16.1 10.05 8.65 6360 CB28UH−048 (Up−Flow/Horizontal) Factory Installed

55,500 16.3 10.05 8.80 6315 CB29M−65 (Multi−Position) Factory Installed

55,500 16.3 10.05 8.80 6315 CB28UH−060 (Up−Flow/Horizontal) Factory Installed

56,000 16.4 10.50 9.45 5915 CB30M−51 (Multi−Position) Factory Installed

56,000 16.4 10.50 9.45 5915 CB30U−51 (Up−Flow) Factory Installed

56,000 16.4 10.60 9.55 5865 CB31MV−51 (Multi−Position) Factory Installed

57,500 16.8 10.50 9.30 6190 CB30M−65 (Multi−Position) Factory Installed

57,500 16.8 10.50 9.30 6190 CB30U−65 (Up−Flow) Factory Installed

57,500 16.8 10.60 9.35 6155 CB31MV−65 (Multi−Position) Factory Installed

54,500 16.0 10.00 9.20 5935 3 CVP10−51/EC10Q4 (Up−Flow) Factory Installed

56,000 16.4 10.00 9.30 6010 3 CVP10−65/EC10Q5 (Up−Flow) Factory Installed

HS29�0625 T +

With Expansion Valve5 Ton +(82 dB)

Up�FlowCoils

58,500 17.1 10.05 9.60 6085 C33−50/60C Factory Installed(82 dB)3 phase

pCoils

58,500 17.1 10.05 9.60 6085 C26−51/65 26K35 Order separatelyp

60,000 17.6 10.25 9.80 6115 C33−60D 26K35 Order separately

60,000 17.6 10.25 9.80 6115 4 C23−51/65 26K35 Order separately

62,500 18.3 10.50 10.00 6255 C33−62D Factory Installed

62,500 18.3 10.50 10.00 6255 C26−65EAP 26K35 Order separately

Down�FlowCoils

55,500 16.3 10.00 9.15 6055 CR26−48 26K35 Order separatelyCoils

58,500 17.1 10.00 9.40 6235 CR26−60 26K35 Order separately

HorizontalCoils

59,000 17.3 9.45 9.45 6245 CH33−60D−F 26K35 Order separatelyCoils

59,000 17.3 9.45 9.45 6245 CH23−65 26K35 Order separately

62,500 18.3 10.75 10.05 6230 CH33−62D−F 26K35 Order separately

62,500 18.3 10.75 10.05 6230 CH23−68 26K35 Order separately

Blower CoilUnits

58,000 17.0 11.05 10.60 5460 CB30M−51 (Multi−Position) Factory InstalledUnits

58,000 17.0 11.05 10.60 5460 CB30U−51 (Up−Flow) Factory Installed

58,000 17.0 11.10 10.70 5410 CB31MV−51 (Multi−Position) Factory Installed

59,000 17.3 10.05 9.85 5995 CB29M−65 (Multi−Position) Factory Installed

59,000 17.3 10.05 9.85 5995 CB28UH−060 (Up−Flow/Horizontal) Factory Installed

59,500 17.4 11.05 10.50 5665 CB30M−65 (Multi−Position) Factory Installed

59,500 17.4 11.05 10.50 5665 CB30U−65 (Up−Flow) Factory Installed

60,000 17.6 11.30 10.65 5635 CB31MV−65 (Multi−Position) Factory Installed

58,000 17.0 10.00 9.40 6170 3 CVP10−65/EC10Q5 Factory Installed

NOTE − Ratings for all C23, C26 and C33 coils include both cased and uncased coils.1 Sound Rating Number rated in accordance with test conditions included in ARI Standard 270.2 Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95�F (35�C) outdoor air temperature, 80�F (27�C) db�/�67�F (19�C) wb

entering evaporator air with 25 ft. (7.6 m) of connecting refrigerant lines.3 Canada Only4 Most popular evaporator coil.

HS29 / Page 17

Page 18: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 1 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS29−012 � C33−18A − C23−21 COOLING CAPACITY − RFC or TXV SystemsOutdoor Air Temperature Entering Outdoor Coil

Total85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)

EnteringWet BulbTempera�

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Tempera�ture

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F300 140 11.5 3.4 .80 .69 .81 .92 11.1 3.3 .89 .69 .82 .94 10.7 3.1 .98 .70 .83 .95 10.2 3.0 1.07 .72 .85 .97

63�F(17�C)

400 190 12.1 3.5 .81 .74 .89 .99 11.7 3.4 .90 .76 .91 1.00 11.3 3.3 .99 .77 .92 1.00 10.8 3.2 1.08 .79 .94 1.00(17�C)

500 235 12.6 3.7 .82 .80 .95 1.00 12.2 3.6 .90 .82 .97 1.00 11.7 3.4 1.00 .83 .98 1.00 11.2 3.3 1.09 .85 1.00 1.00

67�F300 140 12.3 3.6 .81 .55 .67 .78 11.9 3.5 .90 .55 .67 .79 11.4 3.3 .99 .56 .68 .80 11.0 3.2 1.09 .56 .69 .82

67�F(19�C)

400 190 12.9 3.8 .82 .58 .72 .85 12.5 3.7 .91 .58 .73 .87 12.0 3.5 1.00 .59 .74 .89 11.5 3.4 1.10 .60 .76 .91(19�C)

500 235 13.3 3.9 .83 .61 .78 .92 12.8 3.8 .91 .63 .80 .94 12.3 3.6 1.01 .63 .81 .96 11.8 3.5 1.10 .64 .82 .98

71�F300 140 13.2 3.9 .82 .42 .53 .64 12.8 3.8 .91 .42 .53 .64 12.3 3.6 1.01 .42 .54 .65 11.8 3.5 1.10 .42 .54 .66

71�F(22�C)

400 190 13.8 4.0 .83 .43 .57 .70 13.3 3.9 .92 .44 .57 .71 12.8 3.8 1.01 .44 .58 .72 12.3 3.6 1.11 .44 .59 .73(22�C)

500 235 14.2 4.2 .84 .44 .60 .75 13.7 4.0 .93 .45 .61 .77 13.1 3.8 1.02 .45 .62 .78 12.6 3.7 1.12 .45 .63 .80

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C140 300 3.5 12,100 800 .69 .81 .93 3.4 11,700 880 .69 .82 .95 3.3 11,200 970 .70 .84 .97 3.1 10,700 1060 .72 .86 .99

190 400 3.8 12,800 810 .75 .90 1.00 3.6 12,300 900 .76 .92 1.00 3.5 11,800 990 .77 .94 1.00 3.3 11,300 1080 .79 .96 1.00

235 500 3.9 13,300 820 .81 .97 1.00 3.8 12,800 910 .83 .99 1.00 3.6 12,300 1000 .84 1.00 1.00 3.5 11,800 1100 .87 1.00 1.00

140 300 3.8 12,900 820 .54 .66 .77 3.7 12,500 900 .55 .67 .79 3.5 12,000 990 .55 .68 .80 3.4 11,500 1090 .56 .69 .82

190 400 4.0 13,600 830 .58 .72 .86 3.8 13,100 920 .58 .73 .88 3.7 12,500 1010 .59 .75 .90 3.5 12,000 1100 .60 .77 .93

235 500 4.1 14,000 840 .61 .79 .95 3.9 13,400 930 .62 .80 .96 3.8 12,900 1020 .63 .82 .98 3.6 12,300 1110 .65 .84 1.00

140 300 4.1 13,900 840 .42 .52 .63 3.9 13,300 920 .42 .53 .64 3.8 12,800 1010 .42 .54 .65 3.6 12,300 1110 .42 .54 .66

190 400 4.2 14,500 850 .43 .56 .70 4.1 13,900 940 .43 .57 .71 3.9 13,400 1030 .43 .58 .72 3.7 12,700 1120 .44 .59 .74

235 500 4.4 14,900 860 .44 .60 .76 4.2 14,300 950 .44 .61 .78 4.0 13,700 1040 .45 .62 .80 3.8 13,000 1130 .45 .64 .82

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�012 � C26�21 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C140 300 3.6 12,200 800 .68 .81 .93 3.5 11,800 890 .69 .82 .95 3.3 11,300 980 .70 .84 .97 3.2 10,800 1070 .71 .86 .99

190 400 3.8 12,900 820 .74 .90 1.00 3.6 12,400 900 .76 .92 1.00 3.5 11,900 990 .77 .94 1.00 3.3 11,400 1090 .79 .96 1.00

235 500 4.0 13,500 830 .81 .98 1.00 3.8 13,000 920 .83 .99 1.00 3.7 12,500 1010 .84 1.00 1.00 3.5 12,000 1110 .87 1.00 1.00

140 300 3.8 13,100 820 .54 .66 .77 3.7 12,600 910 .55 .67 .79 3.5 12,100 1000 .55 .68 .80 3.4 11,600 1090 .56 .69 .82

190 400 4.0 13,800 840 .58 .72 .86 3.9 13,200 920 .58 .73 .88 3.7 12,700 1010 .59 .75 .90 3.5 12,100 1110 .60 .77 .93

235 500 4.2 14,200 850 .61 .78 .95 4.0 13,600 930 .62 .80 .97 3.8 13,000 1020 .63 .82 .99 3.6 12,400 1120 .65 .84 1.00

140 300 4.1 14,000 840 .42 .52 .63 4.0 13,500 930 .42 .53 .64 3.8 13,000 1020 .42 .53 .65 3.6 12,400 1120 .42 .54 .66

190 400 4.3 14,700 860 .42 .56 .69 4.1 14,100 940 .43 .57 .71 4.0 13,500 1040 .43 .58 .72 3.8 12,900 1130 .43 .59 .74

235 500 4.4 15,100 870 .44 .60 .76 4.2 14,500 950 .44 .61 .78 4.1 13,900 1050 .45 .62 .80 3.9 13,200 1140 .45 .64 .82

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�012 � C33−30A/B − C26�26 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C140 300 3.5 11,900 790 .68 .80 .93 3.4 11,500 880 .69 .82 .94 3.3 11,100 960 .70 .83 .96 3.1 10,600 1060 .71 .85 .98

190 400 3.7 12,600 810 .74 .89 1.00 3.5 12,100 890 .75 .90 1.00 3.4 11,600 980 .76 .92 1.00 3.3 11,100 1080 .78 .95 1.00

235 500 3.8 13,100 820 .79 .96 1.00 3.7 12,600 900 .81 .98 1.00 3.5 12,100 990 .83 .99 1.00 3.4 11,600 1090 .85 1.00 1.00

140 300 3.8 12,800 810 .54 .65 .77 3.6 12,300 900 .55 .66 .78 3.5 11,800 990 .55 .67 .80 3.3 11,300 1080 .56 .68 .81

190 400 3.9 13,400 830 .57 .71 .85 3.8 12,900 910 .58 .72 .87 3.6 12,400 1000 .59 .74 .89 3.5 11,800 1100 .60 .76 .91

235 500 4.0 13,800 840 .60 .77 .93 3.9 13,300 920 .61 .79 .95 3.7 12,700 1010 .62 .81 .97 3.5 12,100 1110 .64 .83 .99

140 300 4.0 13,700 830 .42 .52 .63 3.9 13,200 920 .42 .53 .64 3.7 12,700 1010 .42 .53 .65 3.5 12,100 1110 .42 .54 .66

190 400 4.2 14,300 850 .42 .55 .69 4.0 13,800 930 .43 .56 .70 3.9 13,200 1020 .43 .57 .71 3.7 12,600 1120 .43 .58 .73

235 500 4.3 14,700 860 .44 .59 .75 4.1 14,100 940 .44 .60 .76 4.0 13,500 1030 .44 .61 .78 3.8 12,900 1130 .45 .63 .80

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�012 � CR26�18 − RFC or TXV Systems

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

HS29 / Page 18

Page 19: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 1 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C140 300 3.4 11,500 790 .68 .81 .93 3.3 11,100 870 .69 .82 .95 3.1 10,600 960 .70 .84 .97 3.0 10,200 1050 .71 .86 .98

190 400 3.6 12,200 800 .74 .90 1.00 3.4 11,700 890 .76 .91 1.00 3.3 11,200 980 .77 .93 1.00 3.1 10,700 1070 .79 .96 1.00

235 500 3.7 12,600 820 .81 .97 1.00 3.6 12,200 900 .82 .99 1.00 3.4 11,700 990 .84 1.00 1.00 3.3 11,200 1090 .86 1.00 1.00

140 300 3.6 12,300 810 .54 .66 .77 3.5 11,900 890 .55 .67 .79 3.3 11,400 980 .55 .68 .80 3.2 10,900 1080 .56 .69 .82

190 400 3.8 12,900 820 .57 .72 .86 3.6 12,400 910 .58 .73 .88 3.5 11,900 1000 .59 .75 .90 3.3 11,400 1090 .60 .76 .92

235 500 3.9 13,300 830 .61 .78 .94 3.8 12,800 920 .62 .80 .96 3.6 12,200 1010 .63 .82 .98 3.4 11,700 1100 .65 .84 1.00

140 300 3.9 13,200 830 .42 .52 .63 3.7 12,700 910 .42 .53 .64 3.6 12,200 1000 .42 .53 .65 3.4 11,700 1100 .42 .54 .66

190 400 4.0 13,800 840 .42 .56 .69 3.9 13,300 930 .43 .57 .71 3.7 12,700 1020 .43 .58 .72 3.5 12,100 1120 .43 .59 .74

235 500 4.2 14,200 850 .44 .60 .76 4.0 13,600 940 .44 .61 .78 3.8 13,000 1030 .45 .62 .80 3.6 12,400 1120 .45 .64 .82

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�012 � CH33−18A−F − CH23�21 − RFC or TXV Systems

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

HS29−012 � CH33−36A/B/C−F − CH23−31 COOLING CAPACITY RFC or TXV SystemsOutdoor Air Temperature Entering Outdoor Coil

Total 85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)

EnteringWet BulbTempera�

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Tempera�ture

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F300 140 11.5 3.4 .79 .71 .83 .95 11.1 3.3 .87 .71 .84 .97 10.7 3.1 .96 .73 .86 .99 10.2 3.0 1.05 .74 .88 1.00

63�F(17�C)

400 190 12.2 3.6 .80 .76 .92 1.00 11.7 3.4 .89 .77 .93 1.00 11.2 3.3 .97 .79 .96 1.00 10.7 3.1 1.07 .81 .98 1.00(17�C)

500 235 12.7 3.7 .81 .83 .99 1.00 12.2 3.6 .90 .84 1.00 1.00 11.7 3.4 .99 .87 1.00 1.00 11.2 3.3 1.08 .88 1.00 1.00

67�F300 140 12.4 3.6 .81 .56 .68 .80 11.9 3.5 .89 .57 .69 .81 11.4 3.3 .98 .58 .70 .83 10.9 3.2 1.07 .58 .71 .85

67�F(19�C)

400 190 13.0 3.8 .82 .59 .74 .89 12.5 3.7 .91 .60 .75 .91 12.0 3.5 .99 .61 .76 .93 11.4 3.3 1.09 .62 .79 .94(19�C)

500 235 13.4 3.9 .83 .63 .81 .96 12.9 3.8 .92 .64 .82 .98 12.3 3.6 1.00 .65 .85 1.00 11.8 3.5 1.10 .66 .86 1.00

71�F300 140 13.2 3.9 .83 .44 .55 .66 12.8 3.8 .91 .43 .55 .66 12.3 3.6 1.00 .44 .55 .68 11.7 3.4 1.10 .44 .56 .69

71�F(22�C)

400 190 13.9 4.1 .84 .44 .58 .71 13.4 3.9 .93 .45 .58 .72 12.8 3.8 1.02 .45 .60 .74 12.2 3.6 1.11 .46 .61 .76(22�C)

500 235 14.3 4.2 .85 .45 .62 .78 13.8 4.0 .94 .46 .63 .79 13.2 3.9 1.03 .46 .64 .81 12.5 3.7 1.12 .47 .66 .83

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C140 300 3.6 12,300 800 .69 .82 .93 3.5 11,800 890 .70 .83 .95 3.3 11,400 980 .71 .85 .97 3.2 10,900 1070 .73 .86 .99

190 400 3.8 13,000 820 .75 .90 1.00 3.7 12,500 900 .77 .92 1.00 3.5 12,000 990 .78 .94 1.00 3.4 11,500 1090 .80 .96 1.00

235 500 4.0 13,500 830 .81 .97 1.00 3.8 13,000 920 .83 .99 1.00 3.7 12,500 1010 .85 1.00 1.00 3.5 12,000 1110 .87 1.00 1.00

140 300 3.8 13,100 820 .55 .67 .78 3.7 12,700 910 .56 .68 .80 3.6 12,200 1000 .56 .69 .81 3.4 11,600 1100 .57 .70 .83

190 400 4.0 13,800 840 .58 .73 .87 3.9 13,300 920 .59 .74 .89 3.7 12,700 1010 .60 .76 .90 3.5 12,100 1110 .61 .77 .93

235 500 4.2 14,200 850 .62 .79 .94 4.0 13,600 930 .63 .81 .96 3.8 13,100 1020 .64 .83 .98 3.7 12,500 1120 .65 .85 1.00

140 300 4.1 14,100 840 .42 .53 .64 4.0 13,600 930 .42 .54 .65 3.8 13,000 1020 .42 .54 .66 3.7 12,500 1120 .43 .55 .67

190 400 4.3 14,700 860 .43 .57 .70 4.1 14,100 950 .43 .58 .72 4.0 13,600 1040 .44 .59 .73 3.8 13,000 1130 .44 .60 .75

235 500 4.4 15,100 870 .45 .61 .77 4.2 14,500 950 .45 .62 .78 4.1 13,900 1050 .45 .63 .80 3.9 13,300 1140 .46 .64 .82

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−012 � CB29M−21/26 − CB28UH−018/024 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C165 350 3.8 12,900 820 .72 .86 .98 3.6 12,400 900 .73 .87 1.00 3.5 11,900 990 .75 .89 1.00 3.3 11,400 1090 .76 .91 1.00

210 450 4.0 13,500 830 .78 .94 1.00 3.8 13,000 920 .80 .96 1.00 3.7 12,500 1010 .82 .98 1.00 3.5 11,900 1100 .84 1.00 1.00

260 550 4.1 14,100 840 .85 1.00 1.00 4.0 13,600 930 .86 1.00 1.00 3.8 13,100 1020 .89 1.00 1.00 3.7 12,500 1120 .91 1.00 1.00

165 350 4.0 13,800 840 .56 .69 .82 3.9 13,300 920 .57 .71 .84 3.7 12,700 1020 .58 .72 .86 3.6 12,200 1110 .59 .73 .88

210 450 4.2 14,400 850 .60 .76 .91 4.0 13,800 940 .61 .78 .93 3.9 13,200 1030 .62 .79 .95 3.7 12,600 1130 .63 .81 .98

260 550 4.3 14,800 860 .64 .82 .99 4.2 14,200 950 .65 .84 1.00 4.0 13,500 1040 .66 .86 1.00 3.8 12,900 1130 .68 .89 1.00

165 350 4.3 14,800 860 .43 .55 .67 4.2 14,200 950 .43 .55 .68 4.0 13,600 1040 .43 .56 .69 3.8 13,000 1140 .43 .57 .71

210 450 4.5 15,300 870 .44 .59 .74 4.3 14,700 960 .44 .60 .75 4.1 14,100 1050 .45 .61 .77 3.9 13,400 1150 .45 .62 .79

260 550 4.6 15,700 880 .45 .63 .80 4.4 15,100 970 .46 .64 .82 4.2 14,400 1060 .46 .66 .84 4.0 13,700 1160 .47 .67 .87

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−012 � CB30M−21/26 − CB30U−21/26 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

HS29 / Page 19

Page 20: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 1 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C140 300 3.5 11,900 800 .68 .81 .93 3.4 11,500 890 .69 .82 .95 3.2 11,000 980 .70 .84 .97 3.1 10,500 1070 .72 .86 .99

190 400 3.7 12,600 820 .75 .90 1.00 3.5 12,100 910 .76 .92 1.00 3.4 11,600 1000 .78 .94 1.00 3.3 11,100 1090 .79 .97 1.00

235 500 3.9 13,200 830 .82 .98 1.00 3.7 12,700 920 .83 1.00 1.00 3.6 12,200 1010 .85 1.00 1.00 3.4 11,700 1110 .88 1.00 1.00

140 300 3.8 12,800 820 .54 .66 .77 3.6 12,300 910 .55 .67 .79 3.5 11,800 1000 .55 .68 .80 3.3 11,300 1090 .56 .69 .82

190 400 3.9 13,400 840 .58 .72 .87 3.8 12,900 930 .59 .74 .89 3.6 12,400 1020 .59 .75 .91 3.5 11,800 1110 .60 .77 .93

235 500 4.1 13,900 850 .62 .79 .96 3.9 13,300 940 .63 .81 .98 3.7 12,700 1030 .64 .83 .99 3.5 12,100 1120 .65 .85 1.00

140 300 4.0 13,700 850 .42 .52 .63 3.9 13,200 930 .42 .53 .64 3.7 12,600 1020 .42 .54 .65 3.5 12,100 1120 .42 .54 .66

190 400 4.2 14,300 860 .43 .56 .70 4.0 13,800 950 .43 .57 .71 3.9 13,200 1040 .43 .58 .73 3.7 12,600 1140 .44 .59 .75

235 500 4.3 14,700 870 .44 .61 .77 4.1 14,100 960 .45 .62 .79 4.0 13,500 1050 .45 .63 .81 3.8 12,900 1150 .46 .64 .83

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�012 � CVP10�26/EC10Q3 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

HS29−018 � C33−18A − C23−21 COOLING CAPACITY − RFC or TXV SystemsOutdoor Air Temperature Entering Outdoor Coil

Total85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)

EnteringWet BulbTempera�

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Tempera�ture

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F400 190 16.9 5.0 1.16 .68 .79 .91 16.1 4.7 1.26 .69 .81 .93 15.3 4.5 1.35 .70 .83 .95 14.4 4.2 1.44 .72 .85 .97

63�F(17�C)

600 285 18.2 5.3 1.19 .75 .90 .99 17.4 5.1 1.29 .77 .91 1.00 16.5 4.8 1.39 .79 .94 1.00 15.6 4.6 1.49 .81 .96 1.00(17�C)

800 380 19.2 5.6 1.21 .82 .97 1.00 18.3 5.4 1.32 .84 .99 1.00 17.4 5.1 1.42 .87 1.00 1.00 16.6 4.9 1.52 .89 1.00 1.00

67�F400 190 18.2 5.3 1.19 .54 .65 .76 17.3 5.1 1.29 .55 .66 .77 16.4 4.8 1.39 .55 .68 .79 15.5 4.5 1.48 .56 .69 .81

67�F(19�C)

600 285 19.4 5.7 1.22 .58 .73 .86 18.5 5.4 1.32 .59 .74 .88 17.5 5.1 1.42 .61 .76 .90 16.5 4.8 1.52 .62 .79 .93(19�C)

800 380 20.2 5.9 1.23 .62 .80 .95 19.2 5.6 1.34 .64 .82 .96 18.1 5.3 1.44 .65 .85 .98 17.1 5.0 1.54 .67 .87 1.00

71�F400 190 19.5 5.7 1.22 .42 .52 .62 18.6 5.5 1.32 .42 .53 .63 17.7 5.2 1.43 .42 .53 .64 16.7 4.9 1.53 .43 .54 .66

71�F(22�C)

600 285 20.8 6.1 1.24 .43 .57 .70 19.8 5.8 1.35 .43 .58 .72 18.8 5.5 1.46 .44 .59 .73 17.7 5.2 1.56 .44 .60 .76(22�C)

800 380 21.5 6.3 1.25 .45 .61 .78 20.5 6.0 1.36 .45 .62 .80 19.4 5.7 1.47 .46 .64 .82 18.3 5.4 1.58 .46 .66 .85

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C235 500 5.5 18,800 1210 .70 .84 .96 5.2 17,900 1310 .71 .86 .98 5.0 16,900 1410 .73 .88 1.00 4.7 15,900 1510 .75 .91 1.00

285 600 5.7 19,500 1220 .73 .89 1.00 5.4 18,500 1330 .75 .92 1.00 5.1 17,500 1430 .78 .94 1.00 4.8 16,500 1530 .80 .97 1.00

330 700 5.9 20,000 1230 .77 .94 1.00 5.6 19,000 1340 .80 .96 1.00 5.3 18,000 1440 .82 .99 1.00 5.0 17,100 1550 .85 1.00 1.00

235 500 5.9 20,200 1230 .55 .67 .80 5.6 19,200 1340 .55 .68 .82 5.3 18,100 1450 .56 .70 .84 5.0 17,100 1550 .57 .72 .87

285 600 6.1 20,800 1240 .57 .71 .85 5.8 19,700 1350 .58 .72 .88 5.5 18,600 1460 .59 .75 .91 5.1 17,500 1560 .60 .77 .94

330 700 6.2 21,200 1250 .59 .75 .91 5.9 20,100 1360 .60 .77 .93 5.6 19,000 1470 .61 .80 .96 5.2 17,900 1580 .63 .82 .98

235 500 6.4 21,700 1260 .41 .53 .64 6.0 20,600 1370 .41 .53 .66 5.7 19,500 1480 .42 .54 .67 5.4 18,400 1590 .42 .56 .69

285 600 6.5 22,300 1270 .42 .55 .68 6.2 21,100 1380 .42 .56 .70 5.9 20,000 1500 .43 .57 .72 5.5 18,800 1610 .43 .59 .74

330 700 6.7 22,700 1270 .43 .57 .72 6.3 21,600 1390 .43 .59 .74 5.9 20,300 1510 .44 .60 .77 5.6 19,100 1620 .44 .62 .80

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�018 � C33−30A/B − C23�26 − RFC or TXV Systems

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C235 500 5.6 19,000 1210 .70 .84 .96 5.3 18,000 1310 .71 .86 .99 5.0 17,000 1420 .73 .89 1.00 4.7 16,100 1510 .75 .91 1.00

285 600 5.7 19,600 1230 .74 .89 1.00 5.5 18,600 1330 .76 .92 1.00 5.2 17,600 1430 .78 .95 1.00 4.9 16,600 1530 .80 .97 1.00

330 700 5.9 20,200 1230 .78 .95 1.00 5.6 19,200 1340 .80 .97 1.00 5.3 18,200 1450 .83 .99 1.00 5.0 17,200 1550 .86 1.00 1.00

235 500 5.9 20,300 1240 .55 .67 .80 5.7 19,300 1340 .55 .69 .82 5.3 18,200 1450 .56 .70 .85 5.0 17,200 1550 .58 .72 .87

285 600 6.1 20,900 1250 .57 .71 .86 5.8 19,800 1360 .58 .73 .88 5.5 18,700 1460 .59 .75 .91 5.2 17,600 1570 .60 .78 .94

330 700 6.3 21,400 1250 .59 .75 .91 5.9 20,300 1370 .60 .77 .94 5.6 19,100 1470 .62 .80 .96 5.3 18,000 1580 .63 .83 .99

235 500 6.4 21,800 1260 .41 .53 .64 6.1 20,700 1380 .41 .54 .66 5.7 19,600 1490 .42 .55 .68 5.4 18,500 1600 .42 .56 .70

285 600 6.6 22,400 1270 .42 .55 .68 6.2 21,300 1390 .42 .56 .70 5.9 20,100 1500 .43 .58 .72 5.5 18,900 1610 .43 .59 .75

330 700 6.7 22,900 1280 .43 .58 .73 6.4 21,700 1390 .43 .59 .75 6.0 20,500 1510 .44 .60 .77 5.7 19,300 1620 .44 .62 .80

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�018 � C26�21 TXV Systems Only � CR26�18 RFC or TXV Systems

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

HS29 / Page 20

Page 21: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 1 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C235 500 5.7 19,500 1230 .69 .83 .96 5.4 18,400 1330 .71 .86 .99 5.1 17,400 1430 .73 .88 1.00 4.8 16,400 1530 .75 .91 1.00

285 600 5.9 20,100 1240 .73 .89 1.00 5.6 19,100 1350 .75 .92 1.00 5.3 18,100 1450 .78 .95 1.00 5.0 17,000 1550 .80 .97 1.00

330 700 6.1 20,700 1250 .78 .94 1.00 5.8 19,700 1360 .80 .97 1.00 5.5 18,600 1470 .82 .99 1.00 5.2 17,600 1570 .85 1.00 1.00

235 500 6.1 20,900 1250 .54 .67 .79 5.8 19,800 1360 .55 .68 .82 5.5 18,700 1470 .56 .70 .84 5.2 17,600 1570 .57 .72 .87

285 600 6.3 21,500 1260 .57 .71 .85 6.0 20,400 1370 .58 .72 .88 5.6 19,200 1480 .59 .75 .91 5.3 18,100 1590 .60 .77 .94

330 700 6.4 22,000 1270 .59 .75 .91 6.1 20,800 1380 .60 .77 .94 5.8 19,700 1490 .62 .80 .96 5.4 18,500 1600 .63 .83 .99

235 500 6.6 22,400 1270 .41 .53 .64 6.2 21,300 1390 .41 .53 .65 5.9 20,100 1500 .42 .54 .67 5.5 18,900 1620 .42 .56 .69

285 600 6.8 23,100 1280 .42 .55 .68 6.4 21,900 1400 .42 .56 .70 6.1 20,700 1520 .43 .57 .72 5.7 19,400 1630 .43 .59 .74

330 700 6.9 23,600 1290 .43 .57 .72 6.5 22,300 1410 .43 .59 .74 6.2 21,100 1530 .44 .60 .77 5.8 19,800 1640 .44 .62 .80

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�018 � C26�26 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C235 500 5.3 18,200 1220 .69 .83 .96 5.1 17,300 1320 .71 .86 .98 4.8 16,400 1420 .73 .88 1.00 4.5 15,400 1520 .75 .91 1.00

285 600 5.5 18,900 1230 .73 .89 1.00 5.2 17,900 1330 .75 .92 1.00 5.0 16,900 1440 .78 .94 1.00 4.7 16,000 1540 .80 .97 1.00

330 700 5.7 19,400 1240 .77 .94 1.00 5.4 18,400 1340 .80 .97 1.00 5.1 17,500 1450 .82 .99 1.00 4.8 16,500 1560 .85 1.00 1.00

235 500 5.7 19,600 1240 .55 .67 .80 5.5 18,600 1350 .55 .68 .82 5.1 17,500 1450 .56 .70 .84 4.8 16,500 1560 .57 .72 .87

285 600 5.9 20,100 1250 .57 .71 .85 5.6 19,100 1360 .58 .72 .88 5.3 18,000 1470 .59 .75 .91 5.0 17,000 1570 .60 .77 .94

330 700 6.0 20,600 1260 .59 .75 .91 5.7 19,500 1370 .60 .77 .93 5.4 18,400 1480 .62 .80 .96 5.1 17,300 1580 .63 .82 .99

235 500 6.2 21,000 1260 .41 .53 .64 5.8 19,900 1380 .41 .53 .66 5.5 18,900 1490 .42 .54 .67 5.2 17,800 1600 .42 .56 .69

285 600 6.3 21,600 1270 .42 .55 .68 6.0 20,500 1390 .42 .56 .70 5.7 19,400 1500 .43 .57 .72 5.3 18,200 1610 .43 .59 .74

330 700 6.4 22,000 1280 .43 .57 .72 6.1 20,900 1400 .43 .59 .74 5.8 19,700 1510 .44 .60 .77 5.4 18,500 1630 .44 .62 .80

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�018 � CH33−30A−F − CH23�21 RFC or TXV Systems

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

HS29−018 � CH33−36A/B/C−F − CH23−31 COOLING CAPACITY RFC or TXV SystemsOutdoor Air Temperature Entering Outdoor Coil

Total 85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)

EnteringWet BulbTempera�

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Tempera�ture

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F500 235 17.8 5.2 1.29 .71 .84 .96 16.7 4.9 1.38 .73 .87 .98 15.6 4.6 1.47 .75 .90 1.00 14.5 4.2 1.56 .77 .92 1.00

63�F(17�C)

600 285 18.5 5.4 1.30 .75 .89 1.00 17.4 5.1 1.40 .77 .91 1.00 16.2 4.7 1.50 .79 .95 1.00 15.1 4.4 1.59 .82 .98 1.00(17�C)

700 330 19.0 5.6 1.31 .78 .94 1.00 17.9 5.2 1.42 .81 .96 1.00 16.7 4.9 1.52 .83 1.00 1.00 15.6 4.6 1.62 .87 1.00 1.00

67�F500 235 19.2 5.6 1.32 .56 .68 .80 18.1 5.3 1.42 .57 .70 .82 16.9 5.0 1.52 .58 .72 .85 15.7 4.6 1.62 .59 .74 .88

67�F(19�C)

600 285 19.9 5.8 1.33 .58 .72 .85 18.7 5.5 1.44 .59 .74 .88 17.4 5.1 1.54 .60 .76 .91 16.2 4.7 1.64 .62 .79 .94(19�C)

700 330 20.4 6.0 1.34 .60 .76 .90 19.1 5.6 1.45 .61 .78 .92 17.9 5.2 1.56 .63 .80 .96 16.5 4.8 1.66 .65 .84 1.00

71�F500 235 20.7 6.1 1.35 .43 .54 .65 19.5 5.7 1.46 .43 .55 .67 18.3 5.4 1.57 .43 .56 .69 17.0 5.0 1.68 .44 .58 .71

71�F(22�C)

600 285 21.4 6.3 1.36 .43 .56 .69 20.1 5.9 1.48 .44 .57 .71 18.8 5.5 1.59 .44 .59 .73 17.5 5.1 1.70 .45 .61 .76(22�C)

700 330 21.9 6.4 1.37 .44 .59 .73 20.6 6.0 1.49 .45 .60 .75 19.2 5.6 1.61 .45 .62 .78 17.8 5.2 1.72 .46 .64 .81

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C190 400 5.4 18,500 1200 .68 .80 .91 5.2 17,600 1290 .69 .81 .93 4.9 16,700 1390 .70 .83 .95 4.6 15,700 1480 .72 .86 .97

285 600 5.9 20,100 1230 .76 .90 1.00 5.6 19,100 1330 .77 .92 1.00 5.3 18,000 1430 .79 .95 1.00 5.0 17,000 1530 .82 .97 1.00

375 800 6.2 21,200 1240 .83 .98 1.00 5.9 20,100 1350 .85 1.00 1.00 5.6 19,200 1460 .88 1.00 1.00 5.3 18,200 1570 .91 1.00 1.00

190 400 5.8 19,900 1220 .54 .65 .76 5.6 19,000 1330 .55 .66 .78 5.3 18,000 1430 .56 .68 .80 5.0 16,900 1530 .56 .69 .82

285 600 6.3 21,400 1250 .58 .73 .87 5.9 20,300 1360 .59 .75 .89 5.6 19,200 1460 .61 .77 .92 5.3 18,100 1570 .62 .79 .94

375 800 6.5 22,300 1260 .63 .81 .96 6.2 21,100 1370 .64 .83 .98 5.8 19,900 1480 .66 .86 .99 5.5 18,700 1590 .68 .88 1.00

190 400 6.3 21,500 1250 .42 .52 .62 6.0 20,400 1360 .42 .53 .63 5.7 19,300 1470 .42 .53 .65 5.4 18,300 1570 .42 .54 .66

285 600 6.7 23,000 1270 .43 .57 .70 6.4 21,800 1390 .43 .58 .72 6.0 20,600 1500 .44 .59 .74 5.7 19,400 1610 .44 .61 .77

375 800 7.0 23,800 1280 .45 .62 .78 6.6 22,500 1400 .45 .63 .81 6.2 21,300 1520 .46 .65 .83 5.9 20,000 1630 .47 .67 .86

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−018 � CB29M−21/26 − CB28UH−018/024 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

HS29 / Page 21

Page 22: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 1 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C190 400 5.4 18,400 1210 .68 .79 .90 5.1 17,500 1310 .69 .81 .92 4.8 16,500 1410 .70 .83 .95 4.5 15,500 1500 .72 .85 .97

285 600 5.9 20,100 1240 .75 .90 1.00 5.6 19,000 1340 .77 .92 1.00 5.3 18,000 1450 .79 .95 1.00 5.0 16,900 1550 .82 .98 1.00

375 800 6.2 21,200 1250 .83 .99 1.00 5.9 20,200 1370 .85 1.00 1.00 5.6 19,200 1480 .88 1.00 1.00 5.3 18,200 1600 .91 1.00 1.00

190 400 5.8 19,900 1230 .54 .65 .75 5.5 18,900 1340 .55 .66 .77 5.2 17,800 1450 .55 .67 .79 4.9 16,800 1550 .56 .69 .81

285 600 6.3 21,500 1260 .58 .72 .86 6.0 20,400 1370 .59 .74 .89 5.6 19,200 1480 .60 .76 .91 5.3 18,000 1590 .62 .79 .94

375 800 6.6 22,400 1270 .63 .81 .96 6.2 21,200 1390 .64 .83 .98 5.9 20,000 1500 .66 .86 1.00 5.5 18,700 1610 .68 .89 1.00

190 400 6.3 21,400 1260 .42 .52 .62 6.0 20,400 1370 .42 .52 .63 5.7 19,300 1480 .42 .53 .64 5.3 18,200 1590 .42 .54 .66

285 600 6.8 23,100 1280 .43 .56 .70 6.4 21,900 1400 .43 .58 .72 6.1 20,700 1520 .44 .59 .74 5.7 19,400 1630 .44 .60 .76

375 800 7.0 24,000 1290 .45 .62 .78 6.7 22,700 1410 .45 .63 .80 6.3 21,400 1530 .46 .65 .83 5.9 20,100 1650 .47 .67 .86

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−018 � CB30M−21/26 − CB30U−21/26 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C235 500 5.5 18,800 1230 .69 .83 .96 5.2 17,800 1330 .70 .85 .98 4.9 16,800 1430 .72 .88 1.00 4.6 15,800 1530 .74 .91 1.00

285 600 5.7 19,500 1240 .73 .89 1.00 5.4 18,500 1350 .75 .91 1.00 5.1 17,400 1450 .77 .94 1.00 4.8 16,400 1550 .80 .97 1.00

330 700 5.9 20,000 1250 .77 .94 1.00 5.6 19,000 1360 .79 .96 1.00 5.3 18,000 1470 .82 .99 1.00 5.0 17,000 1580 .85 1.00 1.00

235 500 5.9 20,200 1250 .54 .66 .79 5.6 19,100 1360 .55 .68 .81 5.3 18,100 1470 .56 .69 .84 5.0 17,000 1570 .57 .71 .86

285 600 6.1 20,800 1260 .56 .70 .85 5.8 19,700 1370 .57 .72 .87 5.5 18,600 1480 .58 .74 .90 5.1 17,500 1590 .60 .77 .93

330 700 6.2 21,300 1270 .59 .74 .90 5.9 20,200 1380 .60 .76 .93 5.6 19,000 1500 .61 .79 .96 5.2 17,900 1600 .63 .82 .99

235 500 6.4 21,700 1280 .41 .52 .64 6.0 20,600 1390 .41 .53 .65 5.7 19,500 1510 .42 .54 .67 5.4 18,300 1620 .42 .55 .69

285 600 6.6 22,400 1280 .42 .55 .68 6.2 21,200 1400 .42 .56 .69 5.9 20,000 1520 .42 .57 .71 5.5 18,800 1640 .43 .58 .74

330 700 6.7 22,900 1290 .43 .57 .71 6.4 21,700 1410 .43 .58 .74 6.0 20,400 1530 .44 .60 .76 5.6 19,200 1650 .44 .62 .79

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�018� CVP10�26/EC10Q3 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

HS29−024 � C23−21 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

Total85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)

EnteringWet BulbTempera�

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Tempera�ture

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F600 285 22.6 6.6 1.71 .71 .84 .95 21.5 6.3 1.84 .72 .86 .97 20.3 5.9 1.97 .74 .88 .98 19.2 5.6 2.09 .76 .90 1.00

63�F(17�C)

700 330 23.2 6.8 1.73 .74 .88 .98 22.1 6.5 1.86 .75 .90 1.00 20.9 6.1 1.99 .77 .92 1.00 19.7 5.8 2.11 .79 .94 1.00(17�C)

800 380 23.7 6.9 1.74 .76 .91 1.00 22.6 6.6 1.88 .78 .93 1.00 21.4 6.3 2.01 .81 .95 1.00 20.2 5.9 2.14 .83 .98 1.00

67�F600 285 24.2 7.1 1.75 .56 .68 .80 23.0 6.7 1.89 .57 .69 .82 21.7 6.4 2.02 .57 .71 .84 20.5 6.0 2.15 .59 .73 .87

67�F(19�C)

700 330 24.8 7.3 1.77 .57 .71 .84 23.5 6.9 1.91 .58 .73 .86 22.2 6.5 2.04 .59 .75 .88 20.9 6.1 2.17 .61 .77 .91(19�C)

800 380 25.2 7.4 1.78 .59 .74 .88 23.9 7.0 1.92 .60 .76 .90 22.6 6.6 2.06 .62 .78 .93 21.3 6.2 2.18 .63 .80 .95

71�F600 285 25.9 7.6 1.79 .42 .54 .65 24.6 7.2 1.94 .43 .54 .67 23.3 6.8 2.08 .43 .56 .68 22.0 6.4 2.21 .43 .57 .70

71�F(22�C)

700 330 26.5 7.8 1.81 .43 .55 .68 25.2 7.4 1.96 .43 .56 .70 23.8 7.0 2.10 .43 .58 .72 22.5 6.6 2.23 .44 .59 .74(22�C)

800 380 26.9 7.9 1.82 .43 .58 .71 25.6 7.5 1.97 .44 .59 .73 24.2 7.1 2.11 .44 .60 .76 22.8 6.7 2.25 .45 .61 .78

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C305 650 6.9 23,700 1780 .68 .82 .96 6.6 22,400 1900 .70 .85 .98 6.2 21,100 2020 .71 .88 1.00 5.8 19,800 2120 .74 .91 1.00

375 800 7.2 24,600 1810 .72 .89 1.00 6.8 23,300 1930 .75 .92 1.00 6.4 22,000 2050 .77 .95 1.00 6.0 20,600 2160 .80 .98 1.00

450 950 7.4 25,300 1830 .77 .95 1.00 7.0 24,000 1960 .80 .97 1.00 6.7 22,700 2080 .83 .99 1.00 6.3 21,400 2200 .86 1.00 1.00

305 650 7.4 25,300 1830 .53 .66 .78 7.0 24,000 1950 .54 .67 .81 6.6 22,600 2080 .55 .69 .84 6.2 21,100 2190 .56 .71 .87

375 800 7.6 26,100 1850 .56 .70 .85 7.2 24,700 1980 .57 .72 .88 6.8 23,200 2100 .58 .74 .91 6.4 21,700 2220 .60 .77 .94

450 950 7.8 26,700 1860 .58 .75 .91 7.4 25,300 2000 .60 .77 .94 6.9 23,700 2120 .61 .80 .97 6.5 22,200 2240 .63 .83 .99

305 650 7.9 27,100 1870 .40 .52 .63 7.5 25,700 2010 .41 .52 .64 7.1 24,200 2140 .41 .54 .66 6.7 22,700 2260 .41 .55 .68

375 800 8.2 28,000 1890 .41 .54 .67 7.8 26,500 2030 .41 .55 .69 7.3 24,900 2170 .42 .57 .71 6.8 23,300 2290 .43 .58 .74

450 950 8.4 28,500 1910 .42 .57 .72 7.9 27,000 2050 .43 .58 .74 7.4 25,400 2180 .43 .60 .77 6.9 23,700 2310 .44 .62 .81

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�024 � C26�21 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

HS29 / Page 22

Page 23: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 1 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C305 650 7.1 24,200 1780 .68 .82 .95 6.7 22,900 1900 .69 .84 .97 6.3 21,600 2010 .71 .87 .99 5.9 20,200 2110 .73 .90 1.00

375 800 7.4 25,100 1800 .72 .89 1.00 7.0 23,800 1930 .74 .91 1.00 6.6 22,400 2040 .77 .94 1.00 6.2 21,000 2150 .80 .97 1.00

450 950 7.6 25,800 1820 .77 .94 1.00 7.2 24,500 1950 .79 .97 1.00 6.8 23,200 2070 .82 .99 1.00 6.4 21,800 2190 .85 1.00 1.00

305 650 7.6 25,900 1820 .53 .65 .78 7.2 24,500 1950 .54 .67 .80 6.8 23,100 2070 .55 .68 .83 6.3 21,600 2180 .56 .71 .86

375 800 7.8 26,700 1840 .56 .69 .85 7.4 25,300 1970 .57 .71 .87 7.0 23,800 2100 .58 .74 .90 6.5 22,200 2210 .59 .77 .94

450 950 8.0 27,300 1860 .58 .74 .91 7.6 25,800 1990 .59 .76 .93 7.1 24,300 2120 .61 .79 .96 6.7 22,700 2230 .63 .83 .99

305 650 8.1 27,800 1870 .40 .52 .63 7.7 26,300 2010 .40 .52 .64 7.3 24,800 2130 .41 .53 .66 6.8 23,200 2250 .41 .55 .68

375 800 8.4 28,600 1890 .41 .54 .67 7.9 27,100 2030 .41 .55 .69 7.5 25,500 2160 .42 .56 .71 7.0 23,800 2280 .42 .58 .74

450 950 8.6 29,200 1900 .42 .57 .71 8.1 27,600 2040 .42 .58 .74 7.6 26,000 2180 .43 .60 .77 7.1 24,300 2300 .44 .61 .80

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�024 � C33−24A/B − C23�26 − RFC or TXV Systems

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C305 650 7.1 24,300 1790 .67 .81 .95 6.7 23,000 1910 .69 .84 .97 6.4 21,700 2020 .70 .87 .99 5.9 20,300 2130 .73 .90 1.00

375 800 7.4 25,300 1810 .71 .88 1.00 7.0 23,900 1940 .73 .90 1.00 6.6 22,500 2060 .76 .93 1.00 6.2 21,100 2170 .79 .97 1.00

450 950 7.6 26,000 1830 .76 .93 1.00 7.2 24,700 1960 .78 .96 1.00 6.8 23,300 2090 .81 .98 1.00 6.4 21,900 2200 .85 1.00 1.00

305 650 7.6 26,100 1830 .53 .65 .77 7.2 24,700 1960 .54 .66 .80 6.8 23,300 2080 .55 .68 .82 6.4 21,700 2200 .56 .70 .86

375 800 7.9 27,000 1860 .55 .69 .84 7.5 25,500 1990 .56 .71 .87 7.0 24,000 2110 .57 .73 .90 6.6 22,400 2230 .59 .76 .93

450 950 8.1 27,600 1870 .57 .73 .90 7.6 26,100 2010 .59 .76 .93 7.2 24,500 2130 .60 .78 .96 6.7 22,900 2250 .62 .82 .99

305 650 8.2 28,000 1880 .40 .51 .62 7.8 26,500 2020 .40 .52 .63 7.3 25,000 2150 .41 .53 .65 6.9 23,400 2270 .41 .54 .67

375 800 8.5 28,900 1900 .41 .54 .66 8.0 27,300 2040 .41 .55 .68 7.5 25,700 2180 .42 .56 .70 7.0 24,000 2300 .42 .58 .73

450 950 8.6 29,500 1920 .42 .56 .70 8.2 27,900 2060 .42 .57 .73 7.7 26,200 2200 .43 .59 .76 7.2 24,500 2320 .43 .61 .79

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�024 � C23�31 − RFC or TXV Systems − C33−30A/B RFC Systems Only (see next table for TXV ratings)

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C305 650 7.2 24,700 1810 .68 .82 .95 6.9 23,400 1940 .69 .84 .98 6.4 22,000 2050 .71 .87 1.00 6.0 20,600 2160 .73 .91 1.00

375 800 7.5 25,700 1840 .72 .88 1.00 7.1 24,300 1970 .74 .91 1.00 6.7 22,900 2090 .77 .94 1.00 6.3 21,400 2200 .80 .98 1.00

450 950 7.8 26,500 1860 .77 .94 1.00 7.4 25,100 1990 .79 .97 1.00 6.9 23,700 2120 .82 .99 1.00 6.5 22,300 2240 .86 1.00 1.00

305 650 7.8 26,500 1860 .53 .65 .78 7.4 25,100 1990 .54 .67 .80 6.9 23,600 2110 .55 .68 .83 6.4 22,000 2230 .56 .70 .86

375 800 8.0 27,400 1880 .56 .69 .85 7.6 25,900 2020 .57 .71 .87 7.1 24,300 2140 .58 .74 .91 6.7 22,700 2260 .59 .77 .94

450 950 8.2 28,100 1900 .58 .74 .91 7.8 26,500 2040 .59 .77 .94 7.3 24,900 2160 .61 .80 .97 6.8 23,200 2280 .63 .83 .99

305 650 8.4 28,500 1910 .40 .51 .62 7.9 26,900 2050 .40 .52 .64 7.4 25,300 2180 .41 .53 .66 6.9 23,700 2310 .41 .55 .68

375 800 8.6 29,400 1930 .41 .54 .67 8.1 27,800 2070 .41 .55 .69 7.6 26,100 2210 .42 .56 .71 7.1 24,300 2340 .42 .58 .74

450 950 8.8 30,000 1940 .42 .57 .71 8.3 28,300 2090 .42 .58 .74 7.8 26,600 2230 .43 .60 .77 7.3 24,800 2360 .44 .62 .80

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�024 � C33−30A/B TXV Systems Only (see table above for RFC ratings) − C26�26 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C305 650 7.4 25,400 1840 .67 .81 .95 7.0 24,000 1970 .69 .83 .97 6.6 22,500 2090 .70 .86 1.00 6.2 21,000 2200 .73 .90 1.00

375 800 7.8 26,500 1870 .71 .88 1.00 7.3 25,000 2000 .74 .91 1.00 6.9 23,500 2130 .76 .94 1.00 6.4 21,900 2250 .79 .98 1.00

450 950 8.0 27,300 1890 .76 .94 1.00 7.6 25,800 2030 .79 .97 1.00 7.1 24,300 2160 .82 .99 1.00 6.7 22,900 2290 .85 1.00 1.00

305 650 8.0 27,300 1890 .53 .65 .77 7.6 25,800 2030 .54 .66 .79 7.1 24,200 2160 .55 .68 .82 6.6 22,600 2280 .56 .70 .86

375 800 8.3 28,300 1920 .55 .69 .84 7.8 26,700 2060 .56 .71 .87 7.3 25,000 2190 .58 .73 .90 6.8 23,300 2310 .59 .76 .94

450 950 8.5 29,100 1930 .58 .73 .90 8.0 27,300 2080 .59 .76 .93 7.5 25,600 2210 .61 .79 .97 7.0 23,800 2340 .62 .83 1.00

305 650 8.6 29,400 1940 .40 .51 .62 8.1 27,800 2090 .40 .52 .63 7.6 26,100 2230 .41 .53 .65 7.1 24,300 2360 .41 .54 .67

375 800 8.9 30,400 1970 .41 .54 .66 8.4 28,700 2120 .41 .55 .68 7.9 26,900 2260 .42 .56 .70 7.3 25,000 2390 .42 .58 .73

450 950 9.1 31,100 1980 .42 .56 .71 8.6 29,300 2140 .42 .58 .73 8.0 27,400 2280 .43 .59 .76 7.5 25,500 2410 .44 .61 .80

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�024 � C26�31 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

HS29 / Page 23

Page 24: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 1 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT t

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTemperat

ure

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbure

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

HS29−024 � C33−24A/B−2 with G60UHV−36 COOLING CAPACITY − TXV Systems Only

63�F750 355 25.7 7.5 1.76 .75 .89 1.00 24.4 7.2 1.91 .76 .91 1.00 23.0 6.7 2.04 .79 .94 1.00 21.7 6.4 2.17 .81 .96 1.00

63�F(17�C)

850 400 26.3 7.7 1.78 .78 .92 1.00 24.9 7.3 1.92 .80 .95 1.00 23.6 6.9 2.06 .82 .97 1.00 22.3 6.5 2.19 .85 .99 1.00(17�C)

950 450 26.8 7.9 1.79 .81 .96 1.00 25.4 7.4 1.94 .83 .98 1.00 24.1 7.1 2.08 .85 1.00 1.00 22.8 6.7 2.21 .88 1.00 1.00

67�F750 355 27.4 8.0 1.81 .58 .72 .86 26.0 7.6 1.95 .59 .74 .88 24.5 7.2 2.09 .60 .76 .91 23.0 6.7 2.22 .62 .79 .93

67�F(19�C)

850 400 27.8 8.1 1.82 .60 .76 .90 26.4 7.7 1.96 .61 .77 .92 24.9 7.3 2.11 .63 .80 .94 23.4 6.9 2.24 .64 .82 .97(19�C)

950 450 28.2 8.3 1.83 .62 .78 .93 26.7 7.8 1.98 .63 .81 .95 25.2 7.4 2.12 .64 .83 .97 23.7 6.9 2.25 .66 .86 .99

71�F750 355 29.3 8.6 1.85 .43 .56 .70 27.8 8.1 2.01 .44 .58 .72 26.3 7.7 2.15 .44 .59 .73 24.7 7.2 2.29 .44 .60 .76

71�F(22�C)

850 400 29.8 8.7 1.86 .44 .58 .73 28.2 8.3 2.02 .44 .60 .75 26.6 7.8 2.17 .45 .61 .77 25.0 7.3 2.30 .45 .63 .80(22�C)

950 450 30.2 8.9 1.87 .44 .60 .76 28.6 8.4 2.03 .45 .62 .78 26.9 7.9 2.18 .45 .63 .80 25.3 7.4 2.31 .46 .65 .83

HS29−024 � C33−30A/B−2 with G60UHV−36 COOLING CAPACITY − TXV Systems Only

63�F750 355 26.1 7.6 1.78 .75 .89 .99 24.7 7.2 1.92 .76 .91 1.00 23.3 6.8 2.06 .78 .94 1.00 21.9 6.4 2.19 .81 .96 1.00

63�F(17�C)

850 400 26.7 7.8 1.79 .77 .92 1.00 25.3 7.4 1.94 .79 .94 1.00 23.9 7.0 2.08 .82 .97 1.00 22.5 6.6 2.21 .85 .99 1.00(17�C)

950 450 27.2 8.0 1.80 .80 .96 1.00 25.8 7.6 1.95 .83 .98 1.00 24.4 7.2 2.10 .85 1.00 1.00 23.1 6.8 2.23 .88 1.00 1.00

67�F750 355 27.8 8.1 1.82 .58 .72 .85 26.3 7.7 1.97 .59 .74 .88 24.8 7.3 2.11 .60 .76 .90 23.3 6.8 2.24 .61 .78 .93

67�F(19�C)

850 400 28.3 8.3 1.83 .60 .75 .89 26.8 7.9 1.98 .61 .77 .92 25.2 7.4 2.13 .62 .79 .94 23.7 6.9 2.26 .64 .82 .97(19�C)

950 450 28.8 8.4 1.84 .61 .78 .92 27.2 8.0 1.99 .63 .80 .95 25.6 7.5 2.14 .64 .82 .97 24.0 7.0 2.27 .66 .85 1.00

71�F750 355 29.8 8.7 1.87 .43 .56 .69 28.3 8.3 2.03 .43 .57 .71 26.6 7.8 2.18 .43 .59 .73 25.0 7.3 2.31 .44 .60 .76

71�F(22�C)

850 400 30.3 8.9 1.88 .44 .58 .72 28.7 8.4 2.04 .44 .59 .74 27.1 7.9 2.19 .44 .61 .77 25.4 7.4 2.33 .45 .62 .80(22�C)

950 450 30.7 9.0 1.89 .44 .60 .75 29.1 8.5 2.05 .45 .61 .78 27.4 8.0 2.20 .45 .63 .80 25.7 7.5 2.34 .46 .65 .83

HS29−024 � C33−36A/B−2 with G60UHV−36 COOLING CAPACITY − TXV Systems Only

63�F750 355 26.4 7.7 1.78 .74 .88 .99 25.0 7.3 1.93 .76 .91 1.00 23.5 6.9 2.06 .78 .94 1.00 22.1 6.5 2.19 .81 .96 1.00

63�F(17�C)

850 400 27.0 7.9 1.80 .77 .92 1.00 25.6 7.5 1.94 .79 .95 1.00 24.1 7.1 2.09 .82 .97 1.00 22.7 6.7 2.22 .84 .99 1.00(17�C)

950 450 27.6 8.1 1.81 .80 .95 1.00 26.1 7.6 1.96 .82 .98 1.00 24.7 7.2 2.11 .85 1.00 1.00 23.3 6.8 2.24 .88 1.00 1.00

67�F750 355 28.2 8.3 1.82 .58 .72 .85 26.7 7.8 1.98 .58 .73 .87 25.1 7.4 2.12 .60 .75 .90 23.5 6.9 2.25 .61 .78 .93

67�F(19�C)

850 400 28.8 8.4 1.84 .59 .74 .89 27.2 8.0 1.99 .60 .76 .91 25.6 7.5 2.14 .62 .79 .94 23.9 7.0 2.27 .64 .82 .97(19�C)

950 450 29.2 8.6 1.85 .61 .77 .93 27.6 8.1 2.00 .63 .80 .95 25.9 7.6 2.15 .64 .83 .97 24.3 7.1 2.28 .66 .85 1.00

71�F750 355 30.3 8.9 1.87 .43 .56 .69 28.7 8.4 2.03 .43 .57 .70 27.0 7.9 2.18 .44 .58 .73 25.3 7.4 2.32 .44 .60 .75

71�F(22�C)

850 400 30.8 9.0 1.89 .44 .58 .72 29.1 8.5 2.05 .44 .59 .74 27.4 8.0 2.20 .45 .61 .76 25.7 7.5 2.34 .45 .62 .79(22�C)

950 450 31.3 9.2 1.90 .44 .59 .75 29.5 8.6 2.06 .45 .61 .77 27.8 8.1 2.21 .45 .63 .80 26.0 7.6 2.35 .46 .65 .83

HS29−024 � C33−38A/B−2 with G60UHV−36 COOLING CAPACITY − TXV Systems Only

63�F750 355 27.1 7.9 1.81 .73 .87 .99 25.6 7.5 1.95 .75 .90 1.00 24.1 7.1 2.09 .77 .93 1.00 22.6 6.6 2.22 .80 .96 1.00

63�F(17�C)

850 400 27.8 8.1 1.82 .76 .91 1.00 26.2 7.7 1.97 .78 .94 1.00 24.7 7.2 2.12 .81 .97 1.00 23.2 6.8 2.25 .83 1.00 1.00(17�C)

950 450 28.4 8.3 1.84 .79 .95 1.00 26.8 7.9 1.99 .82 .98 1.00 25.3 7.4 2.14 .84 1.00 1.00 23.9 7.0 2.28 .87 1.00 1.00

67�F750 355 29.1 8.5 1.85 .57 .71 .84 27.5 8.1 2.01 .58 .72 .86 25.8 7.6 2.16 .59 .75 .89 24.1 7.1 2.29 .61 .77 .92

67�F(19�C)

850 400 29.7 8.7 1.87 .59 .74 .88 28.0 8.2 2.02 .60 .76 .91 26.3 7.7 2.17 .62 .78 .93 24.6 7.2 2.31 .63 .81 .97(19�C)

950 450 30.2 8.9 1.88 .61 .77 .92 28.5 8.4 2.04 .62 .79 .94 26.7 7.8 2.19 .64 .82 .97 25.0 7.3 2.32 .65 .85 1.00

71�F750 355 31.3 9.2 1.90 .42 .55 .68 29.6 8.7 2.07 .43 .56 .70 27.8 8.1 2.22 .44 .58 .72 26.0 7.6 2.36 .44 .59 .74

71�F(22�C)

850 400 31.9 9.3 1.92 .43 .57 .71 30.1 8.8 2.08 .44 .58 .73 28.3 8.3 2.24 .44 .60 .76 26.5 7.8 2.38 .45 .62 .78(22�C)

950 450 32.4 9.5 1.93 .44 .59 .74 30.5 8.9 2.10 .45 .61 .76 28.7 8.4 2.25 .45 .62 .79 26.8 7.9 2.39 .46 .64 .82

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C305 650 6.8 23,100 1770 .67 .81 .94 6.4 21,900 1890 .68 .83 .97 6.1 20,700 2000 .70 .86 .99 5.7 19,400 2100 .73 .89 1.00

375 800 7.0 24,000 1790 .71 .87 .99 6.7 22,800 1910 .73 .90 1.00 6.3 21,500 2030 .75 .93 1.00 5.9 20,100 2140 .78 .96 1.00

450 950 7.2 24,700 1810 .75 .93 1.00 6.9 23,400 1940 .78 .95 1.00 6.5 22,100 2060 .80 .98 1.00 6.1 20,800 2170 .84 1.00 1.00

305 650 7.3 24,900 1810 .53 .65 .77 6.9 23,500 1940 .54 .66 .79 6.5 22,200 2060 .55 .68 .82 6.1 20,800 2170 .56 .70 .85

375 800 7.5 25,700 1840 .55 .68 .83 7.1 24,300 1970 .56 .70 .86 6.7 22,800 2090 .57 .72 .89 6.3 21,400 2200 .59 .75 .92

450 950 7.7 26,300 1850 .57 .72 .89 7.3 24,800 1980 .58 .75 .92 6.8 23,300 2110 .60 .78 .95 6.4 21,800 2220 .61 .81 .98

305 650 7.8 26,700 1860 .40 .51 .62 7.4 25,300 2000 .40 .52 .63 7.0 23,800 2120 .41 .53 .65 6.5 22,300 2240 .41 .54 .67

375 800 8.1 27,500 1880 .41 .53 .66 7.6 26,000 2020 .41 .54 .68 7.2 24,500 2150 .42 .56 .70 6.7 22,900 2270 .42 .57 .72

450 950 8.2 28,100 1900 .42 .56 .70 7.8 26,600 2040 .42 .57 .72 7.3 25,000 2170 .43 .58 .75 6.9 23,400 2290 .43 .60 .78

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�024 � CR26�18 − RFC or TXV Systems

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

HS29 / Page 24

Page 25: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 1 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C305 650 7.3 24,800 1820 .67 .81 .95 6.9 23,400 1950 .69 .84 .97 6.4 22,000 2060 .71 .87 1.00 6.0 20,600 2170 .73 .90 1.00

375 800 7.6 25,800 1850 .72 .88 1.00 7.2 24,400 1980 .74 .91 1.00 6.7 22,900 2100 .76 .94 1.00 6.3 21,500 2210 .79 .97 1.00

450 950 7.8 26,600 1870 .76 .94 1.00 7.4 25,200 2000 .79 .97 1.00 6.9 23,700 2130 .82 .99 1.00 6.5 22,300 2250 .85 1.00 1.00

305 650 7.8 26,600 1870 .53 .65 .77 7.4 25,200 2000 .54 .66 .80 6.9 23,600 2130 .55 .68 .82 6.5 22,100 2240 .56 .70 .86

375 800 8.1 27,600 1890 .55 .69 .84 7.6 26,000 2030 .56 .71 .87 7.2 24,400 2160 .58 .73 .90 6.7 22,700 2280 .59 .76 .94

450 950 8.3 28,200 1910 .58 .73 .90 7.8 26,600 2050 .59 .76 .93 7.3 25,000 2180 .61 .79 .96 6.8 23,300 2300 .62 .83 .99

305 650 8.4 28,600 1920 .40 .51 .62 7.9 27,100 2060 .40 .52 .64 7.4 25,400 2200 .41 .53 .65 7.0 23,800 2320 .41 .54 .67

375 800 8.6 29,500 1940 .41 .54 .66 8.2 27,900 2090 .41 .55 .68 7.7 26,200 2220 .42 .56 .70 7.2 24,400 2350 .42 .58 .73

450 950 8.9 30,200 1960 .42 .56 .71 8.4 28,500 2100 .42 .58 .73 7.8 26,700 2240 .43 .59 .76 7.3 24,900 2370 .44 .61 .80

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�024 � CR26�30 − RFC or TXV Systems

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C305 650 7.0 24,000 1810 .68 .82 .95 6.7 22,800 1930 .69 .84 .97 6.3 21,400 2050 .71 .87 1.00 5.9 20,000 2150 .73 .90 1.00

375 800 7.3 25,000 1830 .72 .88 1.00 6.9 23,700 1960 .74 .91 1.00 6.5 22,300 2080 .76 .94 1.00 6.1 20,900 2190 .79 .97 1.00

450 950 7.6 25,800 1850 .77 .94 1.00 7.2 24,400 1990 .79 .97 1.00 6.8 23,100 2110 .82 .99 1.00 6.4 21,700 2240 .85 1.00 1.00

305 650 7.6 25,800 1850 .53 .65 .78 7.2 24,400 1980 .54 .66 .80 6.7 22,900 2110 .55 .68 .83 6.3 21,400 2220 .56 .70 .86

375 800 7.8 26,700 1880 .55 .69 .84 7.4 25,200 2010 .56 .71 .87 6.9 23,700 2140 .58 .74 .90 6.5 22,100 2250 .59 .77 .94

450 950 8.0 27,300 1890 .58 .74 .90 7.6 25,800 2030 .59 .76 .93 7.1 24,200 2160 .61 .79 .96 6.6 22,600 2280 .63 .83 .99

305 650 8.1 27,700 1900 .40 .51 .62 7.7 26,200 2040 .40 .52 .64 7.2 24,700 2180 .41 .53 .65 6.8 23,100 2300 .41 .54 .68

375 800 8.4 28,600 1920 .41 .54 .67 7.9 27,000 2070 .41 .55 .68 7.4 25,400 2200 .42 .56 .71 6.9 23,700 2330 .42 .58 .74

450 950 8.6 29,200 1940 .42 .56 .71 8.1 27,600 2090 .42 .58 .74 7.6 25,900 2220 .43 .59 .76 7.1 24,200 2350 .44 .61 .80

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�024 � CH33−30A−F − CH23�31 − RFC or TXV Systems

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

Outdoor Air Temperature Entering Outdoor Coil

Total 85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)

EnteringWet BulbTempera�

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Tempera�ture

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

HS29−024 � CH33−36A/B/C−F − CH23−41 COOLING CAPACITY TXV or RFC Systems

63�F600 285 23.7 6.9 1.73 .71 .83 .95 22.4 6.6 1.84 .72 .85 .97 21.1 6.2 1.95 .74 .87 .99 19.7 5.8 2.05 .75 .90 1.00

63�F(17�C)

800 380 25.1 7.4 1.76 .76 .91 1.00 23.7 6.9 1.89 .78 .93 1.00 22.3 6.5 2.00 .80 .96 1.00 20.9 6.1 2.11 .83 .99 1.00(17�C)

1000 470 26.1 7.6 1.79 .81 .97 1.00 24.7 7.2 1.92 .84 1.00 1.00 23.3 6.8 2.04 .87 1.00 1.00 21.9 6.4 2.16 .90 1.00 1.00

67�F600 285 25.5 7.5 1.77 .56 .68 .79 24.1 7.1 1.90 .57 .69 .81 22.7 6.7 2.02 .58 .71 .84 21.2 6.2 2.13 .59 .73 .86

67�F(19�C)

800 380 26.8 7.9 1.81 .59 .73 .87 25.4 7.4 1.94 .60 .75 .90 23.8 7.0 2.06 .61 .78 .93 22.2 6.5 2.17 .63 .80 .96(19�C)

1000 470 27.7 8.1 1.83 .62 .79 .94 26.1 7.6 1.96 .64 .81 .97 24.5 7.2 2.09 .65 .84 1.00 22.8 6.7 2.20 .67 .87 1.00

71�F600 285 27.4 8.0 1.82 .43 .54 .65 26.0 7.6 1.96 .43 .55 .66 24.5 7.2 2.08 .43 .55 .67 22.9 6.7 2.20 .44 .57 .69

71�F(22�C)

800 380 28.8 8.4 1.85 .44 .57 .70 27.2 8.0 1.99 .44 .58 .72 25.6 7.5 2.12 .45 .59 .75 23.9 7.0 2.25 .45 .61 .77(22�C)

1000 470 29.7 8.7 1.87 .45 .61 .76 28.0 8.2 2.02 .46 .62 .79 26.3 7.7 2.15 .46 .64 .81 24.5 7.2 2.27 .47 .66 .85

HS29−024 � CH33−24/30A−2F with G60UHV−36 COOLING CAPACITY − TXV Systems Only

63�F750 355 25.9 7.6 1.77 .74 .89 .99 24.6 7.2 1.91 .76 .91 1.00 23.2 6.8 2.05 .78 .94 1.00 21.9 6.4 2.18 .81 .96 1.00

63�F(17�C)

850 400 26.5 7.8 1.79 .78 .92 1.00 25.1 7.4 1.93 .80 .95 1.00 23.8 7.0 2.07 .82 .97 1.00 22.4 6.6 2.20 .84 .99 1.00(17�C)

950 450 27.0 7.9 1.80 .80 .96 1.00 25.7 7.5 1.94 .83 .98 1.00 24.3 7.1 2.09 .85 .99 1.00 23.0 6.7 2.22 .88 1.00 1.00

67�F750 355 27.6 8.1 1.81 .58 .72 .86 26.2 7.7 1.96 .59 .74 .88 24.7 7.2 2.10 .60 .76 .90 23.2 6.8 2.23 .62 .78 .93

67�F(19�C)

850 400 28.1 8.2 1.82 .60 .75 .89 26.6 7.8 1.97 .61 .77 .92 25.1 7.4 2.12 .62 .79 .94 23.6 6.9 2.25 .64 .82 .97(19�C)

950 450 28.5 8.4 1.83 .61 .78 .93 27.0 7.9 1.99 .63 .80 .95 25.5 7.5 2.13 .64 .83 .97 23.9 7.0 2.26 .66 .85 .99

71�F750 355 29.6 8.7 1.86 .43 .56 .70 28.1 8.2 2.02 .43 .57 .71 26.5 7.8 2.16 .44 .58 .73 24.9 7.3 2.30 .44 .60 .76

71�F(22�C)

850 400 30.1 8.8 1.87 .44 .58 .72 28.5 8.4 2.03 .44 .59 .75 26.9 7.9 2.18 .45 .61 .77 25.2 7.4 2.32 .45 .63 .79(22�C)

950 450 30.5 8.9 1.88 .44 .60 .76 28.9 8.5 2.04 .45 .61 .78 27.2 8.0 2.19 .46 .63 .80 25.5 7.5 2.33 .46 .65 .83

HS29−024 � CH33−36A/B−2F with G60UHV−36 COOLING CAPACITY − TXV Systems Only

63�F750 355 26.3 7.7 1.78 .73 .87 .99 24.9 7.3 1.92 .75 .90 1.00 23.5 6.9 2.06 .77 .92 1.00 22.0 6.4 2.18 .79 .95 1.00

63�F(17�C)

850 400 26.9 7.9 1.79 .76 .91 1.00 25.5 7.5 1.94 .78 .93 1.00 24.0 7.0 2.08 .80 .96 1.00 22.6 6.6 2.21 .83 .98 1.00(17�C)

950 450 27.5 8.1 1.81 .79 .94 1.00 26.0 7.6 1.95 .81 .97 1.00 24.5 7.2 2.10 .83 .99 1.00 23.2 6.8 2.23 .86 1.00 1.00

67�F750 355 28.2 8.3 1.82 .57 .71 .84 26.7 7.8 1.97 .58 .72 .86 25.1 7.4 2.12 .59 .75 .89 23.6 6.9 2.25 .60 .76 .92

67�F(19�C)

850 400 28.8 8.4 1.84 .59 .73 .88 27.2 8.0 1.99 .60 .75 .90 25.6 7.5 2.13 .61 .78 .93 24.0 7.0 2.26 .63 .80 .95(19�C)

950 450 29.2 8.6 1.85 .60 .76 .91 27.6 8.1 2.00 .62 .78 .94 26.0 7.6 2.15 .63 .81 .96 24.3 7.1 2.28 .65 .84 .99

71�F750 355 30.3 8.9 1.87 .43 .55 .68 28.7 8.4 2.03 .43 .56 .69 27.0 7.9 2.18 .43 .57 .71 25.4 7.4 2.32 .44 .59 .74

71�F(22�C)

850 400 30.9 9.1 1.88 .43 .57 .71 29.2 8.6 2.04 .43 .58 .73 27.5 8.1 2.20 .44 .60 .75 25.8 7.6 2.34 .45 .61 .78(22�C)

950 450 31.3 9.2 1.89 .44 .59 .74 29.6 8.7 2.06 .44 .60 .76 27.9 8.2 2.21 .45 .62 .78 26.1 7.6 2.35 .46 .64 .81

HS29 / Page 25

Page 26: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 1 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS29−024 � CH33−42B−2F with G60UHV−36 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

63�F750 355 27.1 7.9 1.79 .73 .87 .99 25.6 7.5 1.94 .75 .89 1.00 24.1 7.1 2.08 .77 .92 1.00 22.6 6.6 2.21 .79 .95 1.00

63�F(17�C)

850 400 27.7 8.1 1.81 .76 .91 1.00 26.2 7.7 1.96 .78 .94 1.00 24.7 7.2 2.10 .80 .96 1.00 23.2 6.8 2.23 .83 .99 1.00(17�C)

950 450 28.3 8.3 1.82 .79 .94 1.00 26.8 7.9 1.97 .81 .97 1.00 25.2 7.4 2.12 .83 .99 1.00 23.8 7.0 2.26 .86 1.00 1.00

67�F750 355 29.1 8.5 1.84 .57 .70 .83 27.5 8.1 1.99 .58 .72 .86 25.8 7.6 2.14 .59 .74 .88 24.2 7.1 2.27 .60 .76 .92

67�F(19�C)

850 400 29.7 8.7 1.86 .59 .73 .87 28.0 8.2 2.01 .60 .75 .90 26.3 7.7 2.16 .61 .78 .93 24.6 7.2 2.29 .63 .80 .96(19�C)

950 450 30.2 8.9 1.87 .60 .76 .91 28.5 8.4 2.02 .61 .78 .94 26.8 7.9 2.17 .63 .81 .96 25.0 7.3 2.31 .65 .84 .99

71�F750 355 31.3 9.2 1.89 .42 .55 .67 29.6 8.7 2.05 .43 .56 .69 27.8 8.1 2.21 .44 .58 .71 26.1 7.6 2.35 .44 .59 .74

71�F(22�C)

850 400 31.9 9.3 1.91 .43 .57 .71 30.1 8.8 2.07 .44 .58 .72 28.3 8.3 2.22 .44 .59 .75 26.5 7.8 2.36 .45 .61 .78(22�C)

950 450 32.4 9.5 1.92 .44 .59 .73 30.6 9.0 2.08 .44 .60 .75 28.7 8.4 2.24 .45 .62 .78 26.9 7.9 2.38 .45 .64 .81

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C305 650 6.9 23,600 1760 .72 .85 .96 6.6 22,400 1870 .73 .87 .98 6.2 21,100 1980 .75 .89 1.00 5.8 19,800 2090 .77 .92 1.00

375 800 7.2 24,500 1780 .76 .90 1.00 6.8 23,200 1900 .78 .93 1.00 6.4 21,900 2020 .80 .95 1.00 6.0 20,500 2130 .82 .98 1.00

450 950 7.4 25,200 1800 .80 .95 1.00 7.0 23,900 1930 .82 .97 1.00 6.6 22,600 2050 .85 .99 1.00 6.2 21,300 2160 .88 1.00 1.00

305 650 7.4 25,300 1800 .56 .69 .81 7.0 23,900 1930 .57 .70 .83 6.6 22,600 2040 .58 .72 .86 6.2 21,100 2150 .59 .74 .88

375 800 7.6 26,100 1820 .59 .73 .87 7.2 24,700 1950 .60 .75 .89 6.8 23,200 2070 .61 .77 .92 6.4 21,700 2180 .63 .80 .95

450 950 7.8 26,700 1840 .61 .77 .92 7.4 25,200 1970 .62 .80 .94 6.9 23,700 2090 .64 .82 .97 6.5 22,200 2200 .66 .85 .99

305 650 7.9 27,100 1850 .42 .54 .66 7.5 25,700 1980 .43 .55 .67 7.1 24,200 2110 .43 .56 .69 6.7 22,700 2230 .43 .57 .72

375 800 8.2 27,900 1870 .43 .57 .70 7.7 26,400 2000 .44 .58 .72 7.3 24,900 2130 .44 .59 .75 6.8 23,300 2260 .45 .61 .77

450 950 8.4 28,500 1880 .44 .60 .75 7.9 27,000 2020 .45 .61 .77 7.4 25,400 2150 .45 .63 .80 6.9 23,700 2270 .46 .65 .83

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−024 � CB29M−21/26 − CB28UH−018/024 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C330 700 7.1 24,200 1780 .73 .86 .98 6.7 22,900 1900 .74 .89 .99 6.3 21,600 2010 .76 .91 1.00 5.9 20,200 2120 .79 .94 1.00

375 800 7.3 24,800 1790 .75 .90 1.00 6.9 23,500 1920 .77 .92 1.00 6.5 22,100 2030 .80 .95 1.00 6.1 20,700 2140 .82 .98 1.00

425 900 7.4 25,300 1810 .78 .93 1.00 7.0 24,000 1930 .80 .96 1.00 6.6 22,600 2050 .83 .98 1.00 6.2 21,300 2170 .86 1.00 1.00

330 700 7.6 25,900 1820 .57 .70 .83 7.2 24,500 1950 .58 .72 .85 6.8 23,100 2070 .59 .74 .88 6.3 21,500 2180 .60 .76 .91

375 800 7.8 26,500 1830 .58 .73 .87 7.3 25,000 1970 .59 .75 .89 6.9 23,500 2090 .61 .77 .92 6.4 22,000 2200 .62 .80 .95

425 900 7.9 26,900 1840 .60 .76 .90 7.4 25,400 1980 .61 .78 .93 7.0 23,900 2100 .63 .80 .95 6.5 22,300 2220 .65 .83 .98

330 700 8.1 27,800 1870 .43 .55 .67 7.7 26,300 2010 .43 .56 .69 7.3 24,800 2140 .43 .57 .71 6.8 23,200 2260 .44 .59 .73

375 800 8.3 28,300 1880 .43 .57 .70 7.9 26,800 2020 .43 .58 .72 7.4 25,200 2150 .44 .59 .74 6.9 23,500 2270 .45 .61 .77

425 900 8.4 28,800 1890 .44 .59 .73 8.0 27,200 2030 .44 .60 .75 7.5 25,600 2160 .45 .61 .78 7.0 23,900 2290 .46 .63 .81

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−024 � CB29M−31 − CB28UH−030 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C330 700 7.4 25,100 1810 .72 .86 .97 6.9 23,700 1940 .74 .88 .99 6.5 22,300 2060 .76 .91 1.00 6.1 20,800 2170 .78 .94 1.00

375 800 7.5 25,700 1830 .75 .90 1.00 7.1 24,300 1960 .77 .92 1.00 6.7 22,800 2080 .79 .95 1.00 6.2 21,300 2190 .82 .98 1.00

425 900 7.7 26,300 1840 .78 .93 1.00 7.3 24,800 1970 .80 .96 1.00 6.9 23,400 2100 .83 .98 1.00 6.4 21,900 2220 .86 1.00 1.00

330 700 7.9 26,900 1860 .56 .69 .82 7.4 25,400 1990 .57 .71 .84 7.0 23,800 2120 .59 .73 .87 6.5 22,200 2230 .60 .76 .90

375 800 8.1 27,500 1870 .58 .72 .86 7.6 25,900 2010 .59 .74 .89 7.1 24,300 2140 .61 .77 .92 6.7 22,700 2260 .62 .79 .95

425 900 8.2 28,000 1880 .60 .75 .90 7.7 26,400 2020 .61 .78 .93 7.2 24,700 2150 .63 .80 .95 6.7 23,000 2270 .65 .83 .98

330 700 8.5 28,900 1910 .42 .55 .67 8.0 27,300 2050 .43 .56 .68 7.5 25,600 2190 .43 .57 .70 7.0 23,900 2310 .44 .58 .73

375 800 8.6 29,500 1920 .43 .56 .70 8.1 27,800 2070 .43 .58 .72 7.6 26,100 2200 .44 .59 .74 7.1 24,300 2330 .45 .61 .77

425 900 8.8 30,000 1930 .44 .58 .73 8.3 28,300 2080 .44 .60 .75 7.8 26,500 2220 .45 .61 .78 7.2 24,700 2350 .45 .63 .81

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−024 � CB30M−21/26 − CB30U−21/26 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

HS29 / Page 26

Page 27: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 1 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C285 600 7.3 25,000 1790 .69 .81 .93 6.9 23,600 1910 .71 .83 .95 6.5 22,200 2030 .72 .86 .98 6.1 20,700 2140 .74 .89 1.00

375 800 7.8 26,600 1830 .75 .89 1.00 7.3 25,000 1960 .77 .92 1.00 6.9 23,500 2080 .79 .95 1.00 6.4 21,900 2200 .82 .98 1.00

470 1000 8.1 27,700 1860 .81 .96 1.00 7.7 26,200 1990 .83 .99 1.00 7.2 24,700 2130 .86 1.00 1.00 6.8 23,200 2250 .89 1.00 1.00

285 600 7.9 27,000 1840 .55 .66 .78 7.5 25,500 1970 .56 .68 .80 7.0 23,900 2100 .56 .69 .82 6.5 22,300 2210 .58 .71 .85

375 800 8.3 28,400 1870 .58 .72 .86 7.9 26,800 2010 .59 .74 .88 7.4 25,100 2140 .60 .76 .91 6.9 23,400 2260 .62 .79 .95

470 1000 8.6 29,400 1900 .61 .78 .93 8.1 27,700 2040 .63 .81 .96 7.6 25,900 2170 .65 .83 .99 7.1 24,100 2290 .67 .87 1.00

285 600 8.5 29,100 1890 .42 .53 .63 8.1 27,500 2030 .42 .54 .65 7.6 25,800 2170 .42 .54 .66 7.1 24,100 2290 .43 .56 .68

375 800 9.0 30,600 1920 .43 .56 .69 8.4 28,800 2070 .43 .57 .71 7.9 27,000 2210 .44 .59 .74 7.4 25,100 2340 .44 .61 .77

470 1000 9.2 31,500 1950 .44 .60 .76 8.7 29,600 2100 .45 .62 .78 8.1 27,700 2240 .46 .63 .81 7.6 25,800 2370 .46 .66 .84

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−024 � CB30M−31 − CB30U−31 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C305 650 7.1 24,100 1820 .67 .81 .95 6.7 22,800 1940 .69 .84 .97 6.3 21,500 2060 .70 .86 .99 5.9 20,100 2160 .73 .90 1.00

375 800 7.4 25,100 1840 .71 .88 1.00 7.0 23,800 1970 .74 .91 1.00 6.5 22,300 2090 .76 .94 1.00 6.1 20,900 2210 .79 .97 1.00

450 950 7.6 26,000 1860 .76 .94 1.00 7.2 24,600 2000 .79 .97 1.00 6.8 23,100 2130 .82 .99 1.00 6.4 21,800 2250 .85 1.00 1.00

305 650 7.6 25,900 1860 .53 .65 .77 7.2 24,500 2000 .54 .66 .79 6.7 23,000 2120 .55 .68 .82 6.3 21,500 2240 .56 .70 .86

375 800 7.9 26,800 1890 .55 .69 .84 7.4 25,300 2020 .56 .71 .87 7.0 23,800 2150 .58 .73 .90 6.5 22,200 2270 .59 .76 .94

450 950 8.1 27,500 1900 .58 .73 .90 7.6 26,000 2040 .59 .76 .93 7.2 24,400 2170 .60 .79 .96 6.7 22,700 2290 .62 .82 .99

305 650 8.1 27,800 1910 .40 .51 .62 7.7 26,300 2050 .40 .52 .63 7.3 24,800 2190 .41 .53 .65 6.8 23,100 2320 .41 .54 .67

375 800 8.4 28,800 1940 .41 .54 .66 8.0 27,200 2080 .41 .55 .68 7.5 25,500 2220 .42 .56 .70 7.0 23,800 2350 .42 .58 .73

450 950 8.6 29,500 1950 .42 .56 .71 8.1 27,800 2100 .42 .58 .73 7.6 26,100 2240 .43 .59 .76 7.1 24,300 2370 .44 .61 .80

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�024 � CVP10�26/EC10Q3 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

Outdoor Air Temperature Entering Outdoor Coil

Total85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)

EnteringWet BulbTempera�

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Tempera�ture

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

HS29−030 � C23−26 COOLING CAPACITY − RFC or TXV Systems

63�F900 425 29.2 8.6 2.27 .74 .88 .99 28.2 8.3 2.54 .75 .89 1.00 27.1 7.9 2.84 .77 .91 1.00 26.0 7.6 3.19 .78 .93 1.00

63�F(17�C)

1000 470 29.6 8.7 2.28 .77 .91 1.00 28.7 8.4 2.55 .77 .92 1.00 27.6 8.1 2.85 .79 .94 1.00 26.5 7.8 3.20 .81 .95 1.00(17�C)

1100 520 30.1 8.8 2.29 .79 .94 1.00 29.1 8.5 2.56 .80 .95 1.00 28.0 8.2 2.86 .82 .97 1.00 26.9 7.9 3.21 .83 .98 1.00

67�F900 425 30.9 9.1 2.30 .58 .72 .85 29.9 8.8 2.57 .58 .73 .86 28.7 8.4 2.88 .59 .74 .88 27.5 8.1 3.22 .60 .76 .90

67�F(19�C)

1000 470 31.3 9.2 2.31 .59 .74 .88 30.2 8.9 2.58 .60 .75 .90 29.1 8.5 2.89 .60 .77 .91 27.8 8.1 3.23 .62 .78 .93(19�C)

1100 520 31.7 9.3 2.32 .60 .76 .91 30.6 9.0 2.59 .61 .78 .93 29.4 8.6 2.89 .62 .79 .94 28.2 8.3 3.24 .63 .81 .96

71�F900 425 32.9 9.6 2.34 .43 .56 .69 31.8 9.3 2.61 .43 .57 .70 30.6 9.0 2.92 .43 .58 .72 29.3 8.6 3.27 .44 .58 .73

71�F(22�C)

1000 470 33.3 9.8 2.35 .43 .58 .72 32.2 9.4 2.62 .43 .58 .73 30.9 9.1 2.93 .44 .59 .74 29.6 8.7 3.28 .44 .60 .76(22�C)

1100 520 33.6 9.8 2.35 .44 .59 .74 32.5 9.5 2.63 .44 .60 .76 31.2 9.1 2.94 .45 .61 .77 29.9 8.8 3.29 .45 .62 .79

HS29−030 � C33−30A/B − C23−31 − CH23−21 COOLING CAPACITY − RFC or TXV Systems

63�F900 425 29.8 8.7 2.29 .73 .88 .98 28.8 8.4 2.57 .75 .89 .99 27.7 8.1 2.87 .76 .91 1.00 26.6 7.8 3.22 .77 .92 1.00

63�F(17�C)

1000 470 30.3 8.9 2.30 .75 .90 1.00 29.3 8.6 2.57 .77 .92 1.00 28.2 8.3 2.88 .78 .93 1.00 27.0 7.9 3.23 .80 .95 1.00(17�C)

1100 520 30.8 9.0 2.31 .78 .93 1.00 29.7 8.7 2.58 .79 .95 1.00 28.6 8.4 2.89 .81 .96 1.00 27.5 8.1 3.24 .83 .97 1.00

67�F900 425 31.7 9.3 2.33 .57 .71 .84 30.6 9.0 2.60 .58 .72 .86 29.4 8.6 2.91 .59 .73 .87 28.1 8.2 3.26 .59 .75 .89

67�F(19�C)

1000 470 32.1 9.4 2.33 .59 .73 .87 31.0 9.1 2.61 .59 .75 .89 29.8 8.7 2.92 .60 .76 .90 28.5 8.4 3.27 .61 .78 .93(19�C)

1100 520 32.5 9.5 2.34 .60 .76 .90 31.3 9.2 2.62 .61 .77 .92 30.1 8.8 2.93 .62 .78 .93 28.8 8.4 3.27 .63 .80 .95

71�F900 425 33.7 9.9 2.36 .43 .56 .69 32.6 9.6 2.64 .43 .56 .69 31.4 9.2 2.95 .43 .57 .71 30.0 8.8 3.31 .44 .58 .72

71�F(22�C)

1000 470 34.2 10.0 2.37 .43 .57 .71 33.0 9.7 2.65 .44 .58 .72 31.7 9.3 2.96 .44 .59 .74 30.3 8.9 3.32 .44 .60 .75(22�C)

1100 520 34.6 10.1 2.38 .44 .58 .73 33.4 9.8 2.66 .44 .59 .75 32.0 9.4 2.97 .44 .60 .76 30.6 9.0 3.32 .45 .61 .78

HS29−030 − C33−36A/B/C − C23−41 RFC or TXV Systems − C26−26 TXV Systems Only COOLING CAPACITY

63�F900 425 30.2 8.9 2.30 .73 .87 .98 29.2 8.6 2.58 .74 .89 .99 28.1 8.2 2.88 .76 .90 1.00 26.9 7.9 3.23 .77 .92 1.00

63�F(17�C)

1000 470 30.7 9.0 2.32 .75 .90 1.00 29.7 8.7 2.59 .77 .92 1.00 28.6 8.4 2.90 .78 .93 1.00 27.4 8.0 3.24 .80 .95 1.00(17�C)

1100 520 31.2 9.1 2.32 .78 .93 1.00 30.1 8.8 2.60 .79 .94 1.00 29.0 8.5 2.91 .81 .96 1.00 27.8 8.1 3.26 .82 .97 1.00

67�F900 425 32.2 9.4 2.34 .57 .70 .84 31.0 9.1 2.61 .58 .72 .86 29.8 8.7 2.92 .59 .73 .87 28.5 8.4 3.27 .59 .75 .89

67�F(19�C)

1000 470 32.6 9.6 2.35 .59 .73 .87 31.4 9.2 2.62 .59 .75 .89 30.2 8.9 2.93 .60 .76 .90 28.9 8.5 3.28 .61 .78 .92(19�C)

1100 520 33.0 9.7 2.36 .60 .75 .90 31.8 9.3 2.63 .61 .77 .92 30.5 8.9 2.94 .62 .78 .94 29.2 8.6 3.29 .63 .80 .95

71�F900 425 34.3 10.1 2.38 .43 .55 .68 33.1 9.7 2.66 .43 .56 .69 31.8 9.3 2.97 .43 .57 .71 30.4 8.9 3.32 .43 .58 .72

71�F(22�C)

1000 470 34.7 10.2 2.39 .43 .57 .71 33.5 9.8 2.67 .43 .58 .72 32.2 9.4 2.98 .44 .59 .74 30.7 9.0 3.33 .44 .60 .75(22�C)

1100 520 35.1 10.3 2.40 .44 .58 .73 33.8 9.9 2.67 .44 .59 .75 32.5 9.5 2.99 .44 .60 .76 31.0 9.1 3.34 .45 .62 .78

HS29 / Page 27

Page 28: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 1 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

Outdoor Air Temperature Entering Outdoor Coil

Total85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)

EnteringWet BulbTempera�

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Tempera�ture

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

HS29−030 − C26−31 COOLING CAPACITY − TXV Systems Only

63�F800 380 29.9 8.8 2.24 .71 .84 .96 28.8 8.4 2.51 .72 .86 .97 27.7 8.1 2.80 .73 .87 .99 26.5 7.8 3.14 .75 .89 1.00

63�F(17�C)

900 425 30.5 8.9 2.26 .73 .88 .99 29.5 8.6 2.52 .75 .89 1.00 28.3 8.3 2.82 .76 .91 1.00 27.0 7.9 3.15 .78 .93 1.00(17�C)

1000 470 31.1 9.1 2.27 .76 .91 1.00 30.0 8.8 2.53 .77 .92 1.00 28.8 8.4 2.83 .79 .94 1.00 27.5 8.1 3.17 .81 .96 1.00

67�F800 380 31.9 9.3 2.28 .56 .69 .81 30.8 9.0 2.55 .56 .69 .82 29.5 8.6 2.85 .57 .71 .84 28.2 8.3 3.19 .58 .72 .86

67�F(19�C)

900 425 32.5 9.5 2.30 .57 .71 .84 31.3 9.2 2.56 .58 .72 .86 30.0 8.8 2.86 .59 .74 .87 28.7 8.4 3.20 .60 .75 .90(19�C)

1000 470 33.0 9.7 2.31 .59 .73 .88 31.8 9.3 2.57 .59 .75 .89 30.5 8.9 2.87 .61 .76 .91 29.1 8.5 3.21 .61 .78 .93

71�F800 380 34.1 10.0 2.33 .43 .54 .66 32.9 9.6 2.60 .43 .55 .67 31.5 9.2 2.90 .43 .56 .68 30.1 8.8 3.24 .43 .56 .69

71�F(22�C)

900 425 34.7 10.2 2.34 .43 .56 .68 33.4 9.8 2.61 .43 .56 .69 32.0 9.4 2.91 .43 .57 .71 30.6 9.0 3.26 .43 .58 .73(22�C)

1000 470 35.1 10.3 2.35 .43 .57 .71 33.9 9.9 2.62 .43 .58 .72 32.5 9.5 2.92 .44 .59 .74 31.0 9.1 3.27 .44 .60 .76

HS29−030 − C33−38A/B − C26−41 − CH33−42B−F − CH23−51 COOLING CAPACITY − TXV Systems Only

63�F900 425 31.4 9.2 2.31 .73 .87 .99 30.2 8.9 2.58 .74 .89 1.00 29.0 8.5 2.88 .76 .91 1.00 27.7 8.1 3.22 .77 .93 1.00

63�F(17�C)

1000 470 31.9 9.3 2.32 .76 .91 1.00 30.8 9.0 2.59 .77 .92 1.00 29.6 8.7 2.89 .78 .94 1.00 28.2 8.3 3.24 .80 .96 1.00(17�C)

1100 520 32.5 9.5 2.33 .78 .94 1.00 31.3 9.2 2.60 .80 .95 1.00 30.0 8.8 2.91 .81 .97 1.00 28.7 8.4 3.25 .83 .99 1.00

67�F900 425 33.4 9.8 2.35 .57 .71 .84 32.2 9.4 2.62 .58 .72 .85 30.8 9.0 2.93 .59 .73 .87 29.4 8.6 3.27 .60 .75 .90

67�F(19�C)

1000 470 33.9 9.9 2.36 .59 .73 .87 32.6 9.6 2.63 .60 .75 .89 31.3 9.2 2.94 .60 .76 .91 29.9 8.8 3.28 .61 .78 .93(19�C)

1100 520 34.3 10.1 2.37 .60 .76 .90 33.0 9.7 2.64 .61 .78 .92 31.7 9.3 2.95 .62 .79 .94 30.2 8.9 3.30 .63 .81 .96

71�F900 425 35.6 10.4 2.40 .43 .56 .68 34.3 10.1 2.67 .43 .56 .70 32.9 9.6 2.98 .43 .57 .71 31.4 9.2 3.33 .44 .58 .73

71�F(22�C)

1000 470 36.1 10.6 2.41 .43 .57 .71 34.8 10.2 2.68 .43 .58 .72 33.4 9.8 2.99 .44 .59 .74 31.8 9.3 3.34 .44 .60 .76(22�C)

1100 520 36.5 10.7 2.42 .44 .59 .73 35.2 10.3 2.69 .44 .60 .75 33.7 9.9 3.00 .45 .61 .77 32.1 9.4 3.35 .45 .62 .79

HS29−030 � C33−30A/B−2 with G60UHV−36 COOLING CAPACITY − TXV Systems Only

63�F850 400 30.4 8.9 2.31 .73 .87 .98 29.3 8.6 2.59 .74 .88 .99 28.2 8.3 2.90 .75 .90 1.00 27.0 7.9 3.25 .77 .91 1.00

63�F(17�C)

950 450 30.9 9.1 2.33 .76 .90 1.00 29.9 8.8 2.60 .77 .91 1.00 28.7 8.4 2.91 .78 .93 1.00 27.5 8.1 3.26 .80 .95 1.00(17�C)

1050 495 31.4 9.2 2.34 .78 .93 1.00 30.3 8.9 2.61 .79 .94 1.00 29.2 8.6 2.92 .81 .96 1.00 28.0 8.2 3.27 .83 .98 1.00

67�F850 400 32.3 9.5 2.35 .57 .70 .83 31.1 9.1 2.62 .58 .72 .85 29.9 8.8 2.93 .59 .73 .86 28.6 8.4 3.29 .59 .74 .89

67�F(19�C)

950 450 32.7 9.6 2.36 .58 .73 .87 31.6 9.3 2.63 .59 .74 .88 30.3 8.9 2.94 .60 .76 .90 29.0 8.5 3.30 .61 .77 .92(19�C)

1050 495 33.1 9.7 2.37 .60 .76 .90 31.9 9.3 2.64 .61 .77 .91 30.7 9.0 2.95 .62 .79 .93 29.3 8.6 3.30 .63 .80 .95

71�F850 400 34.4 10.1 2.39 .43 .55 .68 33.2 9.7 2.67 .43 .56 .69 31.9 9.3 2.98 .43 .57 .70 30.5 8.9 3.34 .43 .58 .72

71�F(22�C)

950 450 34.8 10.2 2.40 .43 .57 .71 33.6 9.8 2.68 .43 .58 .72 32.3 9.5 2.99 .44 .59 .73 30.9 9.1 3.35 .44 .60 .75(22�C)

1050 495 35.2 10.3 2.41 .44 .59 .73 34.0 10.0 2.68 .44 .59 .75 32.6 9.6 3.00 .44 .60 .76 31.2 9.1 3.36 .45 .62 .78

HS29−030 � C33−36A/B−2 with G60UHV−36 COOLING CAPACITY − TXV Systems Only

63�F850 400 30.7 9.0 2.32 .73 .86 .98 29.6 8.7 2.59 .74 .88 .99 28.5 8.4 2.90 .75 .89 1.00 27.2 8.0 3.25 .77 .92 1.00

63�F(17�C)

950 450 31.3 9.2 2.33 .75 .89 1.00 30.2 8.9 2.61 .76 .91 1.00 29.0 8.5 2.92 .78 .93 1.00 27.7 8.1 3.27 .80 .95 1.00(17�C)

1050 495 31.8 9.3 2.34 .78 .92 1.00 30.7 9.0 2.62 .79 .94 1.00 29.5 8.6 2.93 .80 .96 1.00 28.2 8.3 3.28 .82 .98 1.00

67�F850 400 32.6 9.6 2.36 .57 .70 .83 31.5 9.2 2.63 .57 .71 .84 30.2 8.9 2.94 .58 .73 .86 28.9 8.5 3.29 .59 .74 .88

67�F(19�C)

950 450 33.1 9.7 2.37 .58 .73 .86 32.0 9.4 2.64 .59 .74 .88 30.7 9.0 2.95 .60 .75 .90 29.3 8.6 3.31 .61 .77 .92(19�C)

1050 495 33.6 9.8 2.38 .60 .75 .90 32.4 9.5 2.65 .61 .77 .91 31.0 9.1 2.96 .62 .78 .93 29.6 8.7 3.32 .63 .80 .95

71�F850 400 34.8 10.2 2.40 .43 .55 .68 33.6 9.8 2.68 .43 .56 .69 32.2 9.4 2.99 .43 .57 .70 30.8 9.0 3.35 .44 .57 .72

71�F(22�C)

950 450 35.3 10.3 2.41 .43 .57 .70 34.1 10.0 2.69 .44 .57 .72 32.7 9.6 3.01 .44 .58 .73 31.2 9.1 3.36 .44 .60 .75(22�C)

1050 495 35.7 10.5 2.42 .44 .58 .73 34.4 10.1 2.70 .44 .59 .74 33.0 9.7 3.01 .44 .60 .76 31.5 9.2 3.37 .45 .62 .78

HS29−030 � C33−38A/B−2 with G60UHV−36 COOLING CAPACITY − TXV Systems Only

63�F850 400 31.6 9.3 2.34 .72 .86 .98 30.4 8.9 2.61 .73 .87 .99 29.2 8.6 2.92 .74 .89 1.00 27.9 8.2 3.27 .76 .91 1.00

63�F(17�C)

950 450 32.2 9.4 2.36 .74 .89 1.00 31.1 9.1 2.63 .76 .90 1.00 29.8 8.7 2.93 .77 .93 1.00 28.5 8.4 3.29 .79 .94 1.00(17�C)

1050 495 32.8 9.6 2.36 .77 .92 1.00 31.6 9.3 2.64 .79 .94 1.00 30.3 8.9 2.95 .80 .96 1.00 29.0 8.5 3.30 .82 .98 1.00

67�F850 400 33.7 9.9 2.38 .57 .69 .82 32.5 9.5 2.66 .57 .70 .84 31.1 9.1 2.97 .58 .72 .86 29.7 8.7 3.32 .59 .73 .88

67�F(19�C)

950 450 34.3 10.1 2.39 .58 .72 .86 33.0 9.7 2.67 .58 .73 .88 31.6 9.3 2.98 .59 .75 .89 30.2 8.9 3.33 .60 .76 .91(19�C)

1050 495 34.7 10.2 2.41 .59 .75 .89 33.5 9.8 2.68 .60 .76 .91 32.1 9.4 2.99 .61 .78 .93 30.5 8.9 3.35 .62 .80 .95

71�F850 400 36.0 10.6 2.43 .43 .55 .67 34.7 10.2 2.71 .43 .55 .68 33.3 9.8 3.02 .43 .56 .70 31.7 9.3 3.38 .43 .57 .71

71�F(22�C)

950 450 36.6 10.7 2.44 .43 .56 .70 35.2 10.3 2.72 .43 .57 .71 33.8 9.9 3.03 .43 .58 .72 32.2 9.4 3.39 .44 .59 .74(22�C)

1050 495 37.0 10.8 2.45 .44 .58 .72 35.7 10.5 2.73 .44 .59 .74 34.2 10.0 3.05 .44 .60 .75 32.6 9.6 3.40 .44 .61 .77

HS29−030 − CR26−18 COOLING CAPACITY − RFC or TXV Systems

63�F900 425 28.1 8.2 2.26 .73 .87 .98 27.1 7.9 2.53 .74 .88 .99 26.1 7.6 2.83 .75 .90 1.00 25.1 7.4 3.17 .77 .91 1.00

63�F(17�C)

1000 470 28.5 8.4 2.27 .75 .90 .99 27.6 8.1 2.53 .76 .91 1.00 26.6 7.8 2.84 .77 .92 1.00 25.5 7.5 3.18 .79 .94 1.00(17�C)

1100 520 28.9 8.5 2.27 .77 .92 1.00 28.0 8.2 2.54 .78 .94 1.00 26.9 7.9 2.85 .80 .96 1.00 25.9 7.6 3.19 .82 .97 1.00

67�F900 425 29.9 8.8 2.29 .57 .70 .84 28.9 8.5 2.56 .57 .71 .85 27.8 8.1 2.86 .58 .73 .87 26.6 7.8 3.21 .59 .74 .88

67�F(19�C)

1000 470 30.3 8.9 2.30 .58 .73 .87 29.2 8.6 2.57 .59 .74 .88 28.1 8.2 2.87 .60 .75 .90 26.9 7.9 3.22 .61 .77 .92(19�C)

1100 520 30.6 9.0 2.30 .59 .75 .90 29.6 8.7 2.57 .60 .76 .91 28.4 8.3 2.88 .61 .78 .92 27.2 8.0 3.22 .62 .79 .94

71�F900 425 31.8 9.3 2.32 .43 .55 .68 30.7 9.0 2.60 .43 .56 .69 29.6 8.7 2.90 .43 .57 .70 28.3 8.3 3.25 .43 .58 .72

71�F(22�C)

1000 470 32.2 9.4 2.33 .43 .57 .70 31.1 9.1 2.60 .43 .57 .71 29.9 8.8 2.91 .44 .58 .73 28.7 8.4 3.26 .44 .59 .74(22�C)

1100 520 32.5 9.5 2.34 .44 .58 .73 31.4 9.2 2.61 .44 .59 .74 30.2 8.9 2.92 .44 .60 .75 28.9 8.5 3.27 .45 .61 .77

HS29−030 − CR26−30 COOLING CAPACITY − RFC or TXV Systems

63�F800 380 29.9 8.8 2.33 .71 .85 .96 28.9 8.5 2.61 .72 .86 .97 27.8 8.1 2.92 .74 .87 .99 26.6 7.8 3.27 .75 .89 1.00

63�F(17�C)

900 425 30.5 8.9 2.35 .74 .88 .98 29.4 8.6 2.62 .75 .89 1.00 28.3 8.3 2.93 .76 .91 1.00 27.1 7.9 3.29 .77 .93 1.00(17�C)

1000 470 31.0 9.1 2.36 .76 .91 1.00 30.0 8.8 2.63 .77 .92 1.00 28.8 8.4 2.94 .79 .94 1.00 27.6 8.1 3.30 .81 .96 1.00

67�F800 380 31.9 9.3 2.37 .56 .69 .81 30.8 9.0 2.65 .56 .69 .82 29.6 8.7 2.96 .57 .71 .84 28.2 8.3 3.31 .58 .72 .86

67�F(19�C)

900 425 32.4 9.5 2.38 .57 .71 .84 31.3 9.2 2.66 .58 .72 .86 30.0 8.8 2.97 .59 .74 .87 28.7 8.4 3.32 .60 .75 .90(19�C)

1000 470 32.9 9.6 2.39 .59 .74 .88 31.7 9.3 2.67 .60 .75 .89 30.4 8.9 2.98 .61 .76 .91 29.1 8.5 3.34 .61 .78 .93

71�F800 380 34.0 10.0 2.41 .42 .54 .66 32.8 9.6 2.69 .43 .55 .67 31.5 9.2 3.01 .43 .56 .68 30.2 8.9 3.37 .43 .56 .70

71�F(22�C)

900 425 34.6 10.1 2.42 .43 .56 .68 33.3 9.8 2.70 .43 .56 .70 32.0 9.4 3.02 .43 .57 .71 30.6 9.0 3.38 .43 .58 .73(22�C)

1000 470 35.0 10.3 2.43 .43 .57 .71 33.8 9.9 2.71 .43 .58 .73 32.4 9.5 3.03 .44 .59 .74 31.0 9.1 3.39 .44 .60 .76

HS29 / Page 28

Page 29: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 1 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

HS29−030 − CR26−36 COOLING CAPACITY − RFC or TXV Systems

63�F800 380 29.9 8.8 2.23 .71 .84 .96 28.8 8.4 2.50 .72 .86 .97 27.7 8.1 2.79 .73 .87 .99 26.5 7.8 3.13 .75 .89 1.00

63�F(17�C)

900 425 30.5 8.9 2.25 .73 .88 .99 29.4 8.6 2.51 .74 .89 1.00 28.3 8.3 2.81 .76 .91 1.00 27.0 7.9 3.14 .78 .93 1.00(17�C)

1000 470 31.1 9.1 2.26 .76 .91 1.00 30.0 8.8 2.52 .77 .92 1.00 28.8 8.4 2.82 .79 .94 1.00 27.5 8.1 3.15 .81 .96 1.00

67�F800 380 31.9 9.3 2.28 .56 .68 .81 30.8 9.0 2.54 .56 .69 .82 29.5 8.6 2.83 .57 .71 .84 28.2 8.3 3.17 .58 .72 .86

67�F(19�C)

900 425 32.5 9.5 2.29 .57 .71 .84 31.3 9.2 2.55 .58 .72 .86 30.0 8.8 2.85 .59 .74 .87 28.7 8.4 3.19 .60 .75 .90(19�C)

1000 470 33.0 9.7 2.30 .59 .73 .88 31.8 9.3 2.56 .60 .75 .89 30.5 8.9 2.86 .61 .76 .91 29.1 8.5 3.20 .61 .78 .93

71�F800 380 34.1 10.0 2.32 .43 .54 .66 32.9 9.6 2.58 .43 .55 .67 31.5 9.2 2.88 .43 .56 .68 30.1 8.8 3.23 .43 .56 .69

71�F(22�C)

900 425 34.7 10.2 2.33 .43 .56 .68 33.4 9.8 2.60 .43 .56 .69 32.0 9.4 2.90 .43 .57 .71 30.6 9.0 3.24 .43 .58 .73(22�C)

1000 470 35.1 10.3 2.34 .43 .57 .71 33.9 9.9 2.61 .43 .58 .72 32.5 9.5 2.91 .44 .59 .74 31.0 9.1 3.25 .44 .60 .76

HS29−030 − CH33−30A−F − CH23−31 COOLING CAPACITY − RFC or TXV Systems

63�F900 425 29.3 8.6 2.25 .74 .88 .99 28.3 8.3 2.52 .75 .89 1.00 27.2 8.0 2.82 .76 .91 1.00 26.1 7.6 3.16 .78 .93 1.00

63�F(17�C)

1000 470 29.8 8.7 2.26 .76 .91 1.00 28.8 8.4 2.53 .77 .92 1.00 27.7 8.1 2.83 .79 .94 1.00 26.5 7.8 3.17 .81 .96 1.00(17�C)

1100 520 30.3 8.9 2.27 .79 .94 1.00 29.3 8.6 2.54 .80 .95 1.00 28.2 8.3 2.84 .82 .96 1.00 27.0 7.9 3.18 .83 .98 1.00

67�F900 425 31.1 9.1 2.28 .57 .71 .85 30.0 8.8 2.55 .58 .73 .86 28.9 8.5 2.85 .59 .74 .88 27.6 8.1 3.19 .60 .75 .90

67�F(19�C)

1000 470 31.6 9.3 2.29 .59 .74 .88 30.4 8.9 2.56 .60 .75 .89 29.2 8.6 2.86 .61 .77 .91 28.0 8.2 3.20 .62 .78 .93(19�C)

1100 520 31.9 9.3 2.30 .61 .76 .91 30.8 9.0 2.57 .61 .78 .93 29.6 8.7 2.87 .62 .79 .94 28.3 8.3 3.21 .63 .81 .96

71�F900 425 33.2 9.7 2.32 .43 .56 .69 32.0 9.4 2.59 .43 .57 .70 30.8 9.0 2.90 .43 .57 .71 29.4 8.6 3.24 .44 .59 .73

71�F(22�C)

1000 470 33.6 9.8 2.33 .43 .57 .71 32.4 9.5 2.60 .44 .58 .73 31.1 9.1 2.91 .44 .59 .74 29.7 8.7 3.25 .44 .60 .76(22�C)

1100 520 34.0 10.0 2.34 .44 .59 .74 32.7 9.6 2.61 .44 .60 .76 31.4 9.2 2.92 .45 .61 .77 30.0 8.8 3.26 .45 .62 .79

HS29−030 − CH33−36A/B/C−F − CH23−41 COOLING CAPACITY − RFC or TXV Systems

63�F900 425 30.2 8.9 2.21 .74 .88 .99 29.1 8.5 2.46 .75 .90 1.00 28.0 8.2 2.75 .76 .91 1.00 26.8 7.9 3.08 .78 .93 1.00

63�F(17�C)

1000 470 30.8 9.0 2.22 .76 .91 1.00 29.7 8.7 2.48 .78 .93 1.00 28.5 8.4 2.77 .79 .95 1.00 27.3 8.0 3.10 .81 .96 1.00(17�C)

1100 520 31.3 9.2 2.23 .79 .94 1.00 30.2 8.9 2.48 .80 .96 1.00 29.0 8.5 2.78 .82 .98 1.00 27.7 8.1 3.11 .84 .99 1.00

67�F900 425 32.1 9.4 2.24 .58 .71 .85 31.0 9.1 2.50 .58 .72 .86 29.7 8.7 2.80 .59 .74 .88 28.3 8.3 3.12 .60 .76 .90

67�F(19�C)

1000 470 32.6 9.6 2.25 .59 .74 .88 31.4 9.2 2.51 .60 .75 .90 30.1 8.8 2.81 .61 .77 .91 28.7 8.4 3.14 .62 .79 .93(19�C)

1100 520 33.0 9.7 2.26 .61 .77 .91 31.8 9.3 2.52 .61 .78 .93 30.5 8.9 2.81 .63 .80 .95 29.1 8.5 3.15 .64 .81 .97

71�F900 425 34.3 10.1 2.29 .43 .56 .69 33.0 9.7 2.55 .43 .57 .70 31.7 9.3 2.84 .43 .57 .71 30.2 8.9 3.18 .44 .59 .73

71�F(22�C)

1000 470 34.7 10.2 2.30 .44 .58 .72 33.5 9.8 2.56 .44 .58 .73 32.1 9.4 2.85 .44 .59 .74 30.6 9.0 3.19 .44 .60 .76(22�C)

1100 520 35.1 10.3 2.30 .44 .59 .74 33.8 9.9 2.57 .44 .60 .76 32.4 9.5 2.86 .45 .61 .77 30.9 9.1 3.20 .45 .62 .79

HS29−030 � CH33−24/30A−2F with G60UHV−36 COOLING CAPACITY − TXV Systems Only

63�F850 400 30.2 8.9 2.31 .73 .87 .98 29.2 8.6 2.59 .74 .88 .99 28.1 8.2 2.90 .75 .90 1.00 26.9 7.9 3.25 .77 .92 1.00

63�F(17�C)

950 450 30.7 9.0 2.32 .75 .90 1.00 29.7 8.7 2.60 .77 .91 1.00 28.6 8.4 2.91 .78 .93 1.00 27.4 8.0 3.26 .80 .95 1.00(17�C)

1050 495 31.2 9.1 2.33 .78 .93 1.00 30.2 8.9 2.61 .79 .94 1.00 29.0 8.5 2.92 .81 .96 1.00 27.8 8.1 3.27 .82 .97 1.00

67�F850 400 32.0 9.4 2.34 .57 .71 .84 30.9 9.1 2.62 .58 .72 .85 29.7 8.7 2.93 .58 .73 .87 28.4 8.3 3.28 .59 .75 .89

67�F(19�C)

950 450 32.5 9.5 2.35 .58 .73 .87 31.4 9.2 2.63 .59 .74 .88 30.1 8.8 2.94 .60 .76 .90 28.8 8.4 3.29 .61 .77 .92(19�C)

1050 495 32.9 9.6 2.36 .60 .76 .90 31.7 9.3 2.64 .61 .77 .92 30.5 8.9 2.95 .62 .79 .94 29.2 8.6 3.30 .63 .80 .95

71�F850 400 34.1 10.0 2.38 .43 .55 .68 32.9 9.6 2.66 .43 .56 .69 31.7 9.3 2.98 .43 .57 .71 30.3 8.9 3.33 .44 .58 .72

71�F(22�C)

950 450 34.5 10.1 2.39 .43 .57 .71 33.4 9.8 2.67 .43 .58 .72 32.1 9.4 2.99 .44 .59 .74 30.7 9.0 3.34 .44 .60 .75(22�C)

1050 495 35.0 10.3 2.40 .44 .59 .74 33.7 9.9 2.68 .44 .60 .75 32.4 9.5 2.99 .44 .60 .76 31.0 9.1 3.35 .45 .62 .78

HS29−030 � CH33−36A/B−2F with G60UHV−36 COOLING CAPACITY − TXV Systems Only

63�F850 400 30.6 9.0 2.32 .72 .85 .97 29.6 8.7 2.59 .73 .86 .98 28.4 8.3 2.90 .74 .88 .99 27.2 8.0 3.25 .76 .90 1.00

63�F(17�C)

950 450 31.2 9.1 2.33 .74 .88 .99 30.1 8.8 2.61 .75 .90 1.00 28.9 8.5 2.92 .76 .92 1.00 27.7 8.1 3.27 .78 .94 1.00(17�C)

1050 495 31.7 9.3 2.34 .77 .91 1.00 30.6 9.0 2.62 .78 .93 1.00 29.4 8.6 2.93 .79 .95 1.00 28.1 8.2 3.28 .81 .96 1.00

67�F850 400 32.7 9.6 2.36 .56 .69 .82 31.5 9.2 2.64 .57 .70 .83 30.3 8.9 2.95 .57 .71 .85 28.9 8.5 3.30 .58 .73 .87

67�F(19�C)

950 450 33.2 9.7 2.37 .58 .72 .85 32.0 9.4 2.65 .58 .73 .87 30.7 9.0 2.96 .59 .74 .88 29.4 8.6 3.31 .60 .76 .91(19�C)

1050 495 33.6 9.8 2.38 .59 .74 .88 32.4 9.5 2.66 .60 .75 .90 31.1 9.1 2.97 .61 .77 .92 29.7 8.7 3.32 .62 .78 .94

71�F850 400 34.8 10.2 2.40 .43 .55 .67 33.6 9.8 2.68 .43 .55 .68 32.3 9.5 3.00 .43 .56 .69 30.9 9.1 3.35 .43 .57 .70

71�F(22�C)

950 450 35.4 10.4 2.41 .43 .56 .69 34.1 10.0 2.69 .43 .57 .70 32.8 9.6 3.01 .43 .58 .72 31.3 9.2 3.36 .44 .58 .73(22�C)

1050 495 35.8 10.5 2.42 .43 .58 .72 34.5 10.1 2.70 .44 .58 .73 33.1 9.7 3.02 .44 .59 .75 31.7 9.3 3.37 .44 .60 .76

HS29−030 � CH33−42B−2F with G60UHV−36 COOLING CAPACITY − TXV Systems Only

63�F850 400 31.5 9.2 2.33 .71 .85 .97 30.4 8.9 2.61 .73 .87 .98 29.2 8.6 2.92 .74 .88 .99 27.9 8.2 3.27 .75 .90 1.00

63�F(17�C)

950 450 32.1 9.4 2.35 .74 .88 .99 31.0 9.1 2.62 .75 .90 1.00 29.7 8.7 2.93 .76 .92 1.00 28.4 8.3 3.28 .78 .94 1.00(17�C)

1050 495 32.7 9.6 2.36 .76 .91 1.00 31.5 9.2 2.63 .78 .93 1.00 30.3 8.9 2.94 .79 .95 1.00 28.9 8.5 3.29 .81 .97 1.00

67�F850 400 33.7 9.9 2.38 .56 .69 .82 32.4 9.5 2.65 .57 .70 .83 31.1 9.1 2.96 .58 .71 .85 29.7 8.7 3.31 .58 .73 .87

67�F(19�C)

950 450 34.3 10.1 2.39 .57 .71 .85 33.0 9.7 2.66 .58 .73 .86 31.6 9.3 2.98 .59 .74 .88 30.2 8.9 3.32 .60 .76 .90(19�C)

1050 495 34.7 10.2 2.40 .59 .74 .88 33.4 9.8 2.67 .60 .75 .90 32.1 9.4 2.99 .61 .77 .92 30.6 9.0 3.34 .61 .78 .94

71�F850 400 35.9 10.5 2.42 .43 .55 .67 34.6 10.1 2.70 .43 .55 .68 33.3 9.8 3.01 .43 .56 .69 31.7 9.3 3.37 .43 .57 .70

71�F(22�C)

950 450 36.5 10.7 2.44 .43 .56 .69 35.2 10.3 2.71 .43 .57 .70 33.7 9.9 3.03 .43 .58 .72 32.2 9.4 3.38 .44 .58 .73(22�C)

1050 495 37.0 10.8 2.45 .43 .57 .71 35.6 10.4 2.72 .44 .58 .73 34.2 10.0 3.04 .44 .59 .74 32.6 9.6 3.40 .44 .60 .76

HS29−030 − CB29M−21/26 − CB28UH−018/024 COOLING CAPACITY − TXV Systems Only

63�F900 425 30.0 8.8 2.45 .74 .88 .99 29.0 8.5 2.74 .75 .90 .99 28.0 8.2 3.07 .77 .91 1.00 26.8 7.9 3.45 .78 .93 1.00

63�F(17�C)

950 450 30.3 8.9 2.46 .75 .90 .99 29.3 8.6 2.75 .76 .91 1.00 28.2 8.3 3.08 .78 .93 1.00 27.0 7.9 3.45 .79 .94 1.00(17�C)

1000 470 30.5 8.9 2.46 .76 .91 1.00 29.5 8.6 2.75 .78 .93 1.00 28.4 8.3 3.08 .79 .94 1.00 27.3 8.0 3.46 .81 .96 1.00

67�F900 425 31.9 9.3 2.48 .58 .71 .85 30.8 9.0 2.78 .58 .73 .86 29.6 8.7 3.11 .59 .74 .88 28.3 8.3 3.48 .60 .76 .90

67�F(19�C)

950 450 32.1 9.4 2.49 .58 .73 .87 31.0 9.1 2.78 .59 .74 .88 29.8 8.7 3.11 .60 .75 .90 28.5 8.4 3.49 .61 .77 .91(19�C)

1000 470 32.3 9.5 2.49 .59 .74 .88 31.1 9.1 2.79 .60 .75 .89 30.0 8.8 3.12 .60 .77 .91 28.7 8.4 3.49 .62 .78 .93

71�F900 425 33.9 9.9 2.52 .43 .56 .69 32.7 9.6 2.82 .43 .57 .70 31.5 9.2 3.15 .43 .57 .71 30.2 8.9 3.53 .44 .58 .73

71�F(22�C)

950 450 34.1 10.0 2.53 .43 .57 .70 32.9 9.6 2.82 .43 .57 .72 31.7 9.3 3.16 .44 .58 .73 30.3 8.9 3.54 .44 .59 .75(22�C)

1000 470 34.3 10.1 2.53 .43 .57 .72 33.2 9.7 2.83 .44 .58 .73 31.9 9.3 3.16 .44 .59 .74 30.5 8.9 3.54 .44 .60 .76

HS29 / Page 29

Page 30: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 1 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

HS29−030 − CB29M−31 − CB28UH−030 COOLING CAPACITY − TXV Systems Only

63�F900 425 29.9 8.8 2.31 .74 .88 .98 28.9 8.5 2.59 .75 .89 1.00 27.8 8.1 2.90 .76 .91 1.00 26.6 7.8 3.25 .78 .93 1.00

63�F(17�C)

1000 470 30.4 8.9 2.32 .76 .91 1.00 29.4 8.6 2.60 .77 .92 1.00 28.3 8.3 2.91 .79 .94 1.00 27.1 7.9 3.26 .81 .96 1.00(17�C)

1100 520 30.9 9.1 2.33 .79 .94 1.00 29.8 8.7 2.61 .80 .95 1.00 28.7 8.4 2.92 .81 .97 1.00 27.5 8.1 3.27 .83 .98 1.00

67�F900 425 31.7 9.3 2.35 .57 .71 .85 30.6 9.0 2.62 .58 .73 .86 29.4 8.6 2.93 .59 .74 .88 28.2 8.3 3.28 .60 .75 .90

67�F(19�C)

1000 470 32.2 9.4 2.36 .59 .74 .88 31.0 9.1 2.63 .59 .75 .89 29.8 8.7 2.94 .60 .77 .91 28.5 8.4 3.29 .61 .78 .93(19�C)

1100 520 32.5 9.5 2.36 .60 .76 .91 31.4 9.2 2.64 .61 .78 .92 30.1 8.8 2.95 .62 .79 .94 28.8 8.4 3.30 .63 .81 .96

71�F900 425 33.8 9.9 2.39 .43 .56 .69 32.6 9.6 2.66 .43 .57 .70 31.4 9.2 2.98 .43 .57 .72 30.0 8.8 3.33 .44 .58 .73

71�F(22�C)

1000 470 34.2 10.0 2.39 .43 .57 .71 33.0 9.7 2.67 .44 .58 .73 31.7 9.3 2.99 .44 .59 .74 30.3 8.9 3.34 .45 .60 .76(22�C)

1100 520 34.6 10.1 2.40 .44 .59 .74 33.4 9.8 2.68 .44 .60 .75 32.1 9.4 3.00 .45 .61 .77 30.6 9.0 3.35 .45 .62 .79

HS29−030 − CB29M−41 − CB28UH−036 COOLING CAPACITY − TXV Systems Only

63�F900 425 30.3 8.9 2.31 .74 .88 .99 29.3 8.6 2.58 .75 .89 1.00 28.2 8.3 2.88 .76 .90 1.00 26.9 7.9 3.23 .78 .93 1.00

63�F(17�C)

1000 470 30.9 9.1 2.32 .76 .91 1.00 29.8 8.7 2.59 .77 .92 1.00 28.7 8.4 2.90 .79 .94 1.00 27.4 8.0 3.24 .80 .96 1.00(17�C)

1100 520 31.3 9.2 2.33 .78 .94 1.00 30.3 8.9 2.60 .80 .95 1.00 29.1 8.5 2.91 .81 .97 1.00 27.9 8.2 3.25 .83 .98 1.00

67�F900 425 32.3 9.5 2.34 .57 .71 .85 31.1 9.1 2.62 .58 .72 .86 29.9 8.8 2.92 .59 .74 .88 28.6 8.4 3.27 .60 .75 .90

67�F(19�C)

1000 470 32.7 9.6 2.35 .59 .74 .88 31.5 9.2 2.62 .60 .75 .89 30.3 8.9 2.93 .60 .76 .91 28.9 8.5 3.28 .61 .78 .93(19�C)

1100 520 33.1 9.7 2.36 .60 .76 .91 31.9 9.3 2.63 .61 .77 .92 30.6 9.0 2.94 .62 .79 .94 29.2 8.6 3.29 .63 .81 .96

71�F900 425 34.4 10.1 2.38 .43 .56 .69 33.2 9.7 2.66 .43 .56 .70 31.9 9.3 2.97 .43 .57 .71 30.4 8.9 3.32 .44 .58 .73

71�F(22�C)

1000 470 34.8 10.2 2.39 .43 .57 .71 33.6 9.8 2.67 .43 .58 .72 32.2 9.4 2.98 .44 .59 .74 30.8 9.0 3.34 .44 .60 .76(22�C)

1100 520 35.2 10.3 2.40 .44 .59 .74 33.9 9.9 2.68 .44 .60 .75 32.6 9.6 2.99 .44 .61 .77 31.1 9.1 3.34 .45 .62 .79

HS29−030 − CB30M−21/26 − CB30U−21/26 COOLING CAPACITY − TXV Systems Only

63�F800 380 30.1 8.8 2.25 .71 .84 .96 29.1 8.5 2.52 .72 .86 .97 27.9 8.2 2.82 .73 .87 .99 26.7 7.8 3.16 .75 .89 1.00

63�F(17�C)

900 425 30.8 9.0 2.27 .74 .87 .99 29.7 8.7 2.53 .75 .89 1.00 28.5 8.4 2.83 .76 .91 1.00 27.3 8.0 3.17 .78 .93 1.00(17�C)

1000 470 31.3 9.2 2.28 .76 .91 1.00 30.2 8.9 2.54 .77 .92 1.00 29.0 8.5 2.84 .79 .94 1.00 27.8 8.1 3.18 .81 .96 1.00

67�F800 380 32.1 9.4 2.29 .56 .69 .81 31.0 9.1 2.56 .56 .70 .82 29.8 8.7 2.86 .57 .71 .84 28.4 8.3 3.20 .58 .72 .86

67�F(19�C)

900 425 32.7 9.6 2.30 .57 .71 .84 31.5 9.2 2.57 .58 .72 .86 30.3 8.9 2.87 .59 .74 .88 28.9 8.5 3.21 .60 .75 .90(19�C)

1000 470 33.2 9.7 2.31 .59 .73 .88 32.0 9.4 2.58 .59 .75 .89 30.7 9.0 2.88 .60 .76 .91 29.3 8.6 3.23 .62 .78 .93

71�F800 380 34.3 10.1 2.34 .43 .54 .66 33.1 9.7 2.60 .43 .55 .67 31.8 9.3 2.91 .43 .55 .68 30.4 8.9 3.25 .43 .56 .69

71�F(22�C)

900 425 34.9 10.2 2.35 .43 .56 .68 33.6 9.8 2.62 .43 .57 .70 32.3 9.5 2.92 .43 .57 .71 30.8 9.0 3.27 .44 .58 .73(22�C)

1000 470 35.3 10.3 2.36 .43 .57 .71 34.1 10.0 2.63 .43 .58 .72 32.7 9.6 2.93 .44 .59 .74 31.2 9.1 3.28 .44 .60 .76

HS29−030 − CB30M−31 − CB30U−31 COOLING CAPACITY − TXV Systems Only

63�F850 400 31.1 9.1 2.33 .72 .86 .97 30.0 8.8 2.60 .73 .87 .99 28.8 8.4 2.91 .74 .89 1.00 27.5 8.1 3.25 .76 .91 1.00

63�F(17�C)

1000 470 32.0 9.4 2.35 .76 .91 1.00 30.8 9.0 2.62 .77 .92 1.00 29.6 8.7 2.93 .79 .94 1.00 28.3 8.3 3.28 .81 .96 1.00(17�C)

1150 545 32.7 9.6 2.36 .80 .95 1.00 31.6 9.3 2.64 .81 .97 1.00 30.3 8.9 2.95 .83 .98 1.00 29.0 8.5 3.30 .85 1.00 1.00

67�F850 400 33.1 9.7 2.37 .57 .70 .82 31.9 9.3 2.64 .57 .71 .84 30.6 9.0 2.95 .58 .72 .86 29.2 8.6 3.30 .59 .74 .87

67�F(19�C)

1000 470 33.9 9.9 2.39 .59 .73 .87 32.7 9.6 2.66 .59 .75 .89 31.3 9.2 2.97 .60 .76 .91 29.9 8.8 3.32 .61 .78 .93(19�C)

1150 545 34.5 10.1 2.40 .61 .77 .92 33.3 9.8 2.67 .62 .79 .94 31.9 9.3 2.99 .63 .80 .96 30.4 8.9 3.34 .64 .82 .98

71�F850 400 35.4 10.4 2.42 .42 .55 .67 34.1 10.0 2.69 .43 .55 .68 32.7 9.6 3.01 .43 .56 .69 31.2 9.1 3.36 .43 .57 .71

71�F(22�C)

1000 470 36.2 10.6 2.43 .43 .57 .71 34.8 10.2 2.71 .44 .58 .72 33.4 9.8 3.02 .44 .59 .74 31.9 9.3 3.38 .44 .60 .76(22�C)

1150 545 36.8 10.8 2.45 .44 .60 .75 35.4 10.4 2.72 .44 .60 .77 33.9 9.9 3.04 .45 .62 .78 32.3 9.5 3.39 .46 .63 .80

HS29−030 − CB30M−41 − CB30U−41/46 COOLING CAPACITY − TXV Systems Only

63�F900 425 31.7 9.3 2.34 .73 .87 .99 30.6 9.0 2.61 .75 .89 1.00 29.3 8.6 2.92 .76 .91 1.00 28.0 8.2 3.27 .77 .93 1.00

63�F(17�C)

1000 470 32.3 9.5 2.35 .76 .91 1.00 31.2 9.1 2.62 .77 .92 1.00 29.9 8.8 2.93 .79 .94 1.00 28.5 8.4 3.28 .80 .96 1.00(17�C)

1100 520 32.9 9.6 2.36 .78 .94 1.00 31.6 9.3 2.64 .80 .96 1.00 30.4 8.9 2.95 .81 .97 1.00 29.0 8.5 3.29 .83 .99 1.00

67�F900 425 33.8 9.9 2.38 .57 .71 .84 32.5 9.5 2.66 .58 .72 .85 31.2 9.1 2.96 .59 .73 .87 29.8 8.7 3.31 .59 .75 .90

67�F(19�C)

1000 470 34.3 10.1 2.39 .59 .73 .87 33.0 9.7 2.67 .59 .75 .89 31.7 9.3 2.98 .60 .76 .91 30.2 8.9 3.33 .61 .78 .93(19�C)

1100 520 34.8 10.2 2.40 .60 .76 .91 33.5 9.8 2.68 .61 .77 .93 32.0 9.4 2.99 .62 .79 .94 30.5 8.9 3.34 .63 .81 .96

71�F900 425 36.1 10.6 2.43 .43 .55 .68 34.8 10.2 2.71 .43 .56 .69 33.3 9.8 3.02 .43 .57 .71 31.8 9.3 3.37 .43 .58 .72

71�F(22�C)

1000 470 36.6 10.7 2.44 .43 .57 .71 35.2 10.3 2.72 .43 .58 .72 33.8 9.9 3.03 .44 .59 .74 32.2 9.4 3.39 .44 .60 .76(22�C)

1100 520 37.0 10.8 2.45 .44 .59 .73 35.7 10.5 2.73 .44 .59 .75 34.1 10.0 3.04 .45 .61 .77 32.5 9.5 3.40 .45 .62 .79

HS29−030 − CB31MV−41 COOLING CAPACITY − TXV Systems Only

63�F900 425 31.6 9.3 2.34 .73 .87 .99 30.5 8.9 2.61 .74 .89 1.00 29.3 8.6 2.92 .76 .90 1.00 27.9 8.2 3.27 .78 .93 1.00

63�F(17�C)

975 460 32.1 9.4 2.35 .75 .90 1.00 30.9 9.1 2.62 .77 .92 1.00 29.7 8.7 2.93 .78 .93 1.00 28.3 8.3 3.28 .80 .95 1.00(17�C)

1090 515 32.7 9.6 2.36 .78 .93 1.00 31.5 9.2 2.64 .79 .95 1.00 30.2 8.9 2.95 .81 .97 1.00 28.9 8.5 3.30 .83 .99 1.00

67�F900 425 33.7 9.9 2.38 .57 .71 .84 32.4 9.5 2.66 .58 .72 .86 31.1 9.1 2.97 .59 .73 .87 29.7 8.7 3.32 .60 .75 .90

67�F(19�C)

975 460 34.1 10.0 2.39 .58 .73 .87 32.8 9.6 2.67 .59 .74 .88 31.5 9.2 2.98 .60 .75 .90 30.0 8.8 3.33 .61 .77 .92(19�C)

1090 515 34.6 10.1 2.40 .60 .76 .90 33.3 9.8 2.68 .61 .77 .92 31.9 9.3 2.99 .62 .79 .94 30.4 8.9 3.34 .63 .81 .96

71�F900 425 36.0 10.6 2.43 .43 .56 .68 34.6 10.1 2.71 .43 .56 .69 33.2 9.7 3.02 .43 .57 .71 31.7 9.3 3.38 .44 .58 .73

71�F(22�C)

975 460 36.4 10.7 2.44 .43 .57 .70 35.0 10.3 2.72 .43 .57 .71 33.6 9.8 3.03 .44 .58 .73 32.0 9.4 3.39 .44 .59 .75(22�C)

1090 515 36.9 10.8 2.45 .44 .59 .73 35.5 10.4 2.73 .44 .59 .75 34.0 10.0 3.04 .44 .61 .76 32.4 9.5 3.40 .45 .62 .78

HS29−030 − CVP10−31/EC10Q3 COOLING CAPACITY − TXV Systems Only

63�F800 380 29.3 8.6 2.28 .71 .84 .96 28.2 8.3 2.54 .72 .85 .97 27.1 7.9 2.84 .73 .87 .99 25.9 7.6 3.19 .74 .89 1.00

63�F(17�C)

1000 470 30.4 8.9 2.30 .76 .90 1.00 29.4 8.6 2.57 .77 .92 1.00 28.2 8.3 2.87 .78 .94 1.00 27.0 7.9 3.21 .80 .96 1.00(17�C)

1200 565 31.4 9.2 2.32 .81 .96 1.00 30.3 8.9 2.59 .82 .97 1.00 29.2 8.6 2.89 .84 .99 1.00 27.9 8.2 3.24 .86 1.00 1.00

67�F800 380 31.2 9.1 2.32 .56 .69 .81 30.1 8.8 2.58 .56 .69 .82 28.9 8.5 2.89 .57 .71 .83 27.6 8.1 3.23 .58 .72 .86

67�F(19�C)

1000 470 32.3 9.5 2.34 .59 .73 .87 31.1 9.1 2.61 .59 .75 .89 29.8 8.7 2.91 .60 .76 .91 28.5 8.4 3.26 .61 .78 .93(19�C)

1200 565 33.1 9.7 2.35 .62 .78 .93 31.8 9.3 2.62 .63 .80 .95 30.5 8.9 2.93 .64 .82 .96 29.1 8.5 3.28 .65 .84 .98

71�F800 380 33.3 9.8 2.36 .42 .54 .66 32.2 9.4 2.63 .43 .55 .66 30.9 9.1 2.94 .43 .55 .68 29.5 8.6 3.28 .43 .56 .69

71�F(22�C)

1000 470 34.4 10.1 2.38 .43 .57 .71 33.2 9.7 2.65 .43 .58 .72 31.8 9.3 2.96 .44 .59 .74 30.4 8.9 3.31 .44 .60 .75(22�C)

1200 565 35.2 10.3 2.40 .44 .60 .76 33.8 9.9 2.67 .45 .61 .78 32.4 9.5 2.98 .45 .62 .79 31.0 9.1 3.33 .45 .64 .82

HS29 / Page 30

Page 31: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 1 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

Outdoor Air Temperature Entering Outdoor Coil

Total85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)

EnteringWet BulbTempera�

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Tempera�ture

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

HS29−030 − CVP10−41/EC10Q3 COOLING CAPACITY − TXV Systems Only

63�F800 380 29.6 8.7 2.28 .71 .84 .95 28.5 8.4 2.55 .72 .85 .97 27.4 8.0 2.85 .73 .87 .99 26.2 7.7 3.19 .74 .89 1.00

63�F(17�C)

1000 470 30.8 9.0 2.31 .76 .90 1.00 29.7 8.7 2.57 .77 .92 1.00 28.5 8.4 2.88 .78 .94 1.00 27.2 8.0 3.22 .80 .96 1.00(17�C)

1200 565 31.8 9.3 2.33 .80 .96 1.00 30.7 9.0 2.60 .82 .97 1.00 29.5 8.6 2.90 .84 .99 1.00 28.3 8.3 3.25 .86 1.00 1.00

67�F800 380 31.6 9.3 2.32 .56 .68 .80 30.5 8.9 2.59 .56 .69 .82 29.3 8.6 2.89 .57 .70 .83 27.9 8.2 3.24 .58 .72 .85

67�F(19�C)

1000 470 32.8 9.6 2.35 .59 .73 .87 31.5 9.2 2.62 .59 .75 .89 30.2 8.9 2.92 .60 .76 .91 28.9 8.5 3.26 .61 .78 .93(19�C)

1200 565 33.6 9.8 2.36 .61 .78 .93 32.3 9.5 2.63 .62 .80 .95 31.0 9.1 2.94 .63 .81 .96 29.5 8.6 3.29 .65 .83 .99

71�F800 380 33.8 9.9 2.37 .42 .54 .65 32.6 9.6 2.64 .42 .54 .66 31.3 9.2 2.95 .42 .55 .67 29.9 8.8 3.30 .43 .56 .69

71�F(22�C)

1000 470 34.9 10.2 2.39 .43 .57 .71 33.6 9.8 2.67 .43 .58 .72 32.3 9.5 2.97 .44 .59 .73 30.8 9.0 3.32 .44 .60 .75(22�C)

1200 565 35.7 10.5 2.41 .44 .60 .76 34.4 10.1 2.68 .45 .61 .77 32.9 9.6 3.00 .45 .62 .79 31.4 9.2 3.34 .46 .64 .82

HS29−036 − C23−31 COOLING CAPACITY − TXV Systems Only

63�F900 425 32.7 9.6 2.73 .70 .83 .94 31.6 9.3 3.05 .71 .84 .96 30.5 8.9 3.42 .72 .86 .97 29.3 8.6 3.84 .73 .87 .98

63�F(17�C)

1000 470 33.3 9.8 2.74 .72 .86 .97 32.2 9.4 3.06 .73 .87 .98 31.0 9.1 3.43 .74 .88 .99 29.8 8.7 3.86 .76 .90 1.00(17�C)

1100 520 33.8 9.9 2.75 .74 .88 .99 32.7 9.6 3.07 .75 .90 .99 31.5 9.2 3.44 .76 .91 1.00 30.2 8.9 3.87 .78 .93 1.00

67�F900 425 34.8 10.2 2.77 .56 .68 .80 33.7 9.9 3.09 .56 .69 .81 32.5 9.5 3.46 .57 .70 .82 31.2 9.1 3.89 .57 .71 .84

67�F(19�C)

1000 470 35.4 10.4 2.78 .56 .69 .82 34.2 10.0 3.10 .57 .70 .84 32.9 9.6 3.47 .58 .72 .85 31.6 9.3 3.90 .59 .73 .87(19�C)

1100 520 35.8 10.5 2.79 .58 .72 .85 34.6 10.1 3.11 .58 .73 .86 33.3 9.8 3.48 .59 .74 .88 32.0 9.4 3.91 .60 .75 .90

71�F900 425 37.1 10.9 2.81 .42 .54 .65 35.9 10.5 3.14 .42 .54 .66 34.6 10.1 3.51 .42 .55 .67 33.3 9.8 3.94 .43 .56 .68

71�F(22�C)

1000 470 37.6 11.0 2.82 .43 .55 .67 36.4 10.7 3.15 .43 .55 .68 35.1 10.3 3.52 .43 .56 .69 33.7 9.9 3.95 .43 .57 .71(22�C)

1100 520 38.1 11.2 2.83 .43 .56 .69 36.8 10.8 3.16 .43 .57 .70 35.5 10.4 3.53 .43 .57 .72 34.1 10.0 3.96 .44 .58 .73

HS29−036 − C33−36A/B/C − C23−41 COOLING CAPACITY − RFC or TXV Systems

63�F1000 470 33.8 9.9 2.69 .72 .86 .97 32.7 9.6 3.00 .73 .87 .98 31.5 9.2 3.36 .74 .88 .99 30.2 8.9 3.78 .75 .90 1.00

63�F(17�C)

1200 565 34.8 10.2 2.71 .76 .91 1.00 33.6 9.8 3.03 .77 .92 1.00 32.4 9.5 3.39 .79 .94 1.00 31.1 9.1 3.80 .80 .95 1.00(17�C)

1400 660 35.6 10.4 2.72 .80 .95 1.00 34.4 10.1 3.04 .81 .96 1.00 33.2 9.7 3.40 .82 .97 1.00 31.9 9.3 3.82 .84 .99 1.00

67�F1000 470 36.0 10.6 2.73 .56 .69 .82 34.7 10.2 3.04 .57 .71 .84 33.5 9.8 3.41 .58 .71 .85 32.1 9.4 3.83 .59 .73 .87

67�F(19�C)

1200 565 36.8 10.8 2.74 .59 .73 .87 35.5 10.4 3.06 .59 .75 .89 34.2 10.0 3.43 .60 .76 .91 32.8 9.6 3.84 .61 .78 .92(19�C)

1400 660 37.5 11.0 2.76 .61 .77 .92 36.2 10.6 3.07 .62 .79 .94 34.8 10.2 3.44 .63 .80 .95 33.4 9.8 3.86 .64 .82 .97

71�F1000 470 38.3 11.2 2.77 .43 .55 .67 37.0 10.8 3.09 .43 .55 .68 35.6 10.4 3.46 .43 .56 .69 34.2 10.0 3.88 .43 .57 .70

71�F(22�C)

1200 565 39.2 11.5 2.79 .43 .57 .71 37.8 11.1 3.11 .44 .58 .72 36.4 10.7 3.48 .44 .59 .74 35.0 10.3 3.90 .44 .60 .75(22�C)

1400 660 39.8 11.7 2.80 .44 .60 .75 38.4 11.3 3.12 .45 .60 .77 37.0 10.8 3.49 .45 .61 .78 35.5 10.4 3.92 .45 .63 .80

HS29−036 − C26−31 COOLING CAPACITY − TXV Systems Only

63�F900 425 34.5 10.1 2.71 .70 .83 .94 33.2 9.7 3.02 .71 .84 .96 32.0 9.4 3.38 .72 .86 .97 30.7 9.0 3.80 .73 .87 .99

63�F(17�C)

1000 470 35.1 10.3 2.72 .72 .86 .97 33.9 9.9 3.03 .73 .87 .98 32.6 9.6 3.40 .74 .89 1.00 31.2 9.1 3.81 .76 .90 1.00(17�C)

1100 520 35.7 10.5 2.73 .74 .88 .99 34.4 10.1 3.05 .75 .90 1.00 33.1 9.7 3.40 .77 .92 1.00 31.8 9.3 3.82 .78 .93 1.00

67�F900 425 36.7 10.8 2.75 .56 .68 .79 35.5 10.4 3.06 .56 .68 .81 34.1 10.0 3.43 .57 .70 .82 32.7 9.6 3.85 .57 .71 .84

67�F(19�C)

1000 470 37.4 11.0 2.76 .56 .70 .82 36.0 10.6 3.08 .57 .71 .84 34.6 10.1 3.45 .58 .72 .85 33.2 9.7 3.87 .58 .73 .87(19�C)

1100 520 37.9 11.1 2.77 .58 .72 .85 36.5 10.7 3.09 .58 .73 .87 35.1 10.3 3.46 .59 .74 .88 33.7 9.9 3.87 .60 .76 .90

71�F900 425 39.2 11.5 2.80 .42 .54 .65 37.9 11.1 3.12 .42 .54 .66 36.5 10.7 3.49 .42 .55 .67 35.0 10.3 3.91 .43 .55 .68

71�F(22�C)

1000 470 39.8 11.7 2.81 .42 .55 .67 38.4 11.3 3.13 .43 .55 .68 37.0 10.8 3.50 .43 .56 .69 35.5 10.4 3.93 .43 .57 .71(22�C)

1100 520 40.4 11.8 2.82 .43 .56 .69 38.9 11.4 3.14 .43 .57 .70 37.5 11.0 3.52 .43 .58 .71 35.9 10.5 3.94 .44 .58 .73

HS29−036 − C33−42B − C23−46 COOLING CAPACITY − RFC or TXV Systems

63�F1000 470 35.0 10.3 2.78 .72 .85 .97 33.8 9.9 3.10 .73 .87 .98 32.6 9.6 3.47 .74 .88 .99 31.2 9.1 3.91 .75 .90 1.00

63�F(17�C)

1200 565 36.1 10.6 2.80 .75 .90 1.00 34.8 10.2 3.13 .77 .92 1.00 33.5 9.8 3.50 .78 .93 1.00 32.2 9.4 3.93 .80 .95 1.00(17�C)

1400 660 37.0 10.8 2.82 .79 .95 1.00 35.7 10.5 3.15 .81 .96 1.00 34.4 10.1 3.52 .82 .97 1.00 33.1 9.7 3.95 .84 .99 1.00

67�F1000 470 37.3 10.9 2.82 .56 .69 .82 36.0 10.6 3.15 .57 .70 .83 34.7 10.2 3.52 .57 .71 .85 33.2 9.7 3.95 .58 .73 .87

67�F(19�C)

1200 565 38.2 11.2 2.84 .59 .73 .87 36.9 10.8 3.17 .59 .74 .89 35.5 10.4 3.54 .60 .76 .90 34.0 10.0 3.98 .61 .77 .92(19�C)

1400 660 38.9 11.4 2.85 .61 .77 .92 37.5 11.0 3.18 .62 .79 .93 36.1 10.6 3.56 .63 .80 .95 34.6 10.1 3.99 .64 .82 .97

71�F1000 470 39.7 11.6 2.87 .43 .55 .67 38.4 11.3 3.20 .43 .55 .68 37.0 10.8 3.58 .43 .56 .69 35.5 10.4 4.01 .43 .57 .70

71�F(22�C)

1200 565 40.7 11.9 2.89 .43 .57 .71 39.3 11.5 3.22 .44 .58 .72 37.8 11.1 3.60 .44 .59 .74 36.3 10.6 4.04 .44 .60 .75(22�C)

1400 660 41.4 12.1 2.91 .44 .59 .75 39.9 11.7 3.24 .44 .60 .76 38.4 11.3 3.62 .45 .61 .78 36.8 10.8 4.06 .45 .63 .80

HS29−036 − C33−38A/B − C26−41 − CH33−48C−F − CH23−51 COOLING CAPACITY − TXV Systems Only

63�F900 425 34.7 10.2 2.63 .70 .83 .94 33.5 9.8 2.94 .71 .84 .96 32.2 9.4 3.29 .72 .85 .97 30.8 9.0 3.69 .73 .87 .99

63�F(17�C)

1100 520 35.9 10.5 2.66 .74 .88 .99 34.7 10.2 2.96 .75 .90 1.00 33.3 9.8 3.32 .76 .92 1.00 32.0 9.4 3.72 .78 .93 1.00(17�C)

1300 615 36.9 10.8 2.68 .78 .93 1.00 35.6 10.4 2.99 .79 .95 1.00 34.3 10.1 3.34 .81 .97 1.00 32.9 9.6 3.75 .83 .98 1.00

67�F900 425 37.0 10.8 2.68 .55 .67 .79 35.7 10.5 2.99 .56 .68 .80 34.3 10.1 3.34 .57 .69 .82 32.9 9.6 3.75 .57 .71 .84

67�F(19�C)

1100 520 38.2 11.2 2.70 .58 .71 .85 36.8 10.8 3.01 .58 .73 .86 35.4 10.4 3.37 .59 .74 .88 33.9 9.9 3.77 .60 .76 .90(19�C)

1300 615 39.0 11.4 2.72 .60 .76 .90 37.6 11.0 3.03 .61 .77 .92 36.1 10.6 3.39 .62 .79 .94 34.6 10.1 3.80 .63 .80 .95

71�F900 425 39.5 11.6 2.73 .42 .54 .65 38.1 11.2 3.04 .43 .54 .66 36.7 10.8 3.40 .43 .54 .67 35.2 10.3 3.81 .43 .55 .68

71�F(22�C)

1100 520 40.7 11.9 2.75 .43 .56 .69 39.2 11.5 3.07 .43 .57 .70 37.8 11.1 3.43 .43 .57 .71 36.2 10.6 3.84 .44 .59 .73(22�C)

1300 615 41.5 12.2 2.77 .44 .59 .73 40.1 11.8 3.09 .44 .59 .75 38.5 11.3 3.45 .44 .61 .76 36.9 10.8 3.87 .45 .62 .78

HS29−036 − C33−48B/C − C23−51 COOLING CAPACITY − TXV Systems Only

63�F1000 470 35.9 10.5 2.68 .72 .85 .97 34.7 10.2 2.99 .73 .86 .98 33.3 9.8 3.34 .74 .88 .99 32.0 9.4 3.75 .75 .90 1.00

63�F(17�C)

1200 565 37.1 10.9 2.70 .76 .90 1.00 35.8 10.5 3.01 .77 .92 1.00 34.4 10.1 3.37 .78 .94 1.00 33.0 9.7 3.79 .80 .95 1.00(17�C)

1400 660 38.0 11.1 2.72 .80 .95 1.00 36.7 10.8 3.04 .81 .96 1.00 35.3 10.3 3.40 .82 .98 1.00 33.9 9.9 3.81 .84 .99 1.00

67�F1000 470 38.3 11.2 2.73 .56 .69 .82 36.9 10.8 3.04 .57 .70 .83 35.5 10.4 3.40 .57 .71 .85 34.1 10.0 3.81 .58 .72 .87

67�F(19�C)

1200 565 39.4 11.5 2.75 .58 .73 .87 37.9 11.1 3.06 .59 .74 .89 36.5 10.7 3.42 .60 .76 .90 34.9 10.2 3.84 .61 .77 .93(19�C)

1400 660 40.2 11.8 2.76 .61 .77 .92 38.7 11.3 3.08 .62 .79 .94 37.2 10.9 3.45 .63 .80 .95 35.6 10.4 3.86 .64 .82 .98

71�F1000 470 40.9 12.0 2.78 .43 .55 .67 39.5 11.6 3.10 .43 .55 .67 38.0 11.1 3.46 .43 .56 .69 36.4 10.7 3.88 .43 .57 .70

71�F(22�C)

1200 565 42.0 12.3 2.80 .43 .57 .71 40.5 11.9 3.12 .43 .58 .72 38.9 11.4 3.48 .44 .59 .74 37.3 10.9 3.91 .44 .60 .75(22�C)

1400 660 42.8 12.5 2.82 .44 .60 .75 41.2 12.1 3.14 .44 .60 .76 39.6 11.6 3.51 .45 .61 .78 37.9 11.1 3.92 .45 .63 .80

HS29 / Page 31

Page 32: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 1 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

Outdoor Air Temperature Entering Outdoor Coil

Total85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)

EnteringWet BulbTempera�

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Tempera�ture

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

HS29−036 − C33−44C − C26−46 COOLING CAPACITY − TXV Systems Only

63�F1000 470 36.1 10.6 2.70 .72 .86 .97 34.8 10.2 3.00 .73 .87 .99 33.5 9.8 3.36 .74 .89 1.00 32.1 9.4 3.77 .76 .90 1.00

63�F(17�C)

1200 565 37.3 10.9 2.72 .76 .91 1.00 35.9 10.5 3.03 .78 .93 1.00 34.6 10.1 3.39 .79 .95 1.00 33.1 9.7 3.80 .81 .97 1.00(17�C)

1400 660 38.3 11.2 2.74 .81 .96 1.00 36.9 10.8 3.05 .82 .98 1.00 35.6 10.4 3.41 .84 .99 1.00 34.2 10.0 3.82 .86 1.00 1.00

67�F1000 470 38.4 11.3 2.74 .56 .70 .82 37.1 10.9 3.05 .57 .71 .84 35.6 10.4 3.41 .58 .72 .85 34.1 10.0 3.83 .59 .73 .87

67�F(19�C)

1200 565 39.5 11.6 2.76 .59 .74 .88 38.1 11.2 3.08 .60 .75 .90 36.5 10.7 3.44 .61 .77 .92 35.0 10.3 3.85 .61 .78 .94(19�C)

1400 660 40.3 11.8 2.78 .62 .78 .93 38.9 11.4 3.10 .62 .80 .95 37.3 10.9 3.46 .63 .82 .97 35.7 10.5 3.87 .65 .83 .99

71�F1000 470 41.1 12.0 2.79 .42 .55 .67 39.6 11.6 3.11 .43 .55 .68 38.1 11.2 3.48 .43 .56 .69 36.5 10.7 3.90 .43 .57 .71

71�F(22�C)

1200 565 42.1 12.3 2.81 .43 .57 .71 40.6 11.9 3.14 .44 .58 .73 39.0 11.4 3.50 .44 .59 .74 37.4 11.0 3.92 .44 .60 .76(22�C)

1400 660 42.9 12.6 2.84 .44 .60 .76 41.3 12.1 3.16 .45 .61 .78 39.7 11.6 3.52 .45 .62 .79 38.0 11.1 3.94 .46 .64 .81

HS29−036 − C26−51/65 COOLING CAPACITY − TXV Systems Only

63�F1000 470 36.5 10.7 2.72 .72 .85 .98 35.1 10.3 3.04 .73 .87 .99 33.7 9.9 3.40 .74 .89 1.00 32.3 9.5 3.81 .76 .90 1.00

63�F(17�C)

1200 565 37.7 11.0 2.75 .76 .91 1.00 36.3 10.6 3.07 .78 .93 1.00 34.9 10.2 3.43 .79 .95 1.00 33.4 9.8 3.85 .81 .96 1.00(17�C)

1400 660 38.7 11.3 2.77 .80 .96 1.00 37.3 10.9 3.09 .82 .98 1.00 35.9 10.5 3.46 .84 .99 1.00 34.5 10.1 3.87 .85 1.00 1.00

67�F1000 470 38.9 11.4 2.77 .56 .69 .82 37.5 11.0 3.10 .57 .70 .83 36.0 10.6 3.46 .58 .71 .85 34.5 10.1 3.87 .58 .73 .87

67�F(19�C)

1200 565 40.0 11.7 2.80 .59 .74 .88 38.5 11.3 3.12 .59 .75 .89 37.0 10.8 3.48 .60 .76 .91 35.4 10.4 3.90 .61 .78 .94(19�C)

1400 660 40.8 12.0 2.82 .62 .78 .93 39.3 11.5 3.14 .63 .80 .95 37.7 11.0 3.50 .64 .81 .97 36.1 10.6 3.92 .64 .83 .99

71�F1000 470 41.6 12.2 2.83 .42 .55 .67 40.1 11.8 3.16 .43 .55 .68 38.5 11.3 3.53 .43 .56 .69 36.9 10.8 3.95 .43 .57 .70

71�F(22�C)

1200 565 42.7 12.5 2.86 .43 .57 .71 41.1 12.0 3.18 .44 .58 .73 39.5 11.6 3.55 .44 .59 .74 37.8 11.1 3.97 .44 .60 .76(22�C)

1400 660 43.5 12.7 2.87 .44 .60 .76 41.9 12.3 3.20 .45 .61 .77 40.2 11.8 3.57 .45 .62 .79 38.5 11.3 4.00 .45 .63 .81

HS29−036 � C33−36A/B−2 with G60UHV−36 COOLING CAPACITY − TXV Systems Only

63�F1020 480 36.8 10.8 2.74 .73 .87 .98 35.5 10.4 3.06 .74 .88 .99 34.2 10.0 3.43 .76 .90 1.00 32.8 9.6 3.85 .77 .91 1.00

63�F(17�C)

1220 575 37.8 11.1 2.76 .77 .92 1.00 36.5 10.7 3.09 .78 .93 1.00 35.2 10.3 3.45 .80 .95 1.00 33.8 9.9 3.87 .81 .97 1.00(17�C)

1420 670 38.7 11.3 2.78 .81 .96 1.00 37.4 11.0 3.10 .83 .98 1.00 36.1 10.6 3.47 .84 .99 1.00 34.7 10.2 3.89 .86 1.00 1.00

67�F1020 480 39.0 11.4 2.78 .57 .71 .83 37.7 11.0 3.11 .58 .72 .85 36.2 10.6 3.47 .59 .73 .87 34.8 10.2 3.90 .59 .74 .88

67�F(19�C)

1220 575 39.9 11.7 2.80 .59 .75 .89 38.5 11.3 3.12 .60 .76 .91 37.1 10.9 3.49 .61 .77 .92 35.5 10.4 3.92 .62 .79 .94(19�C)

1420 670 40.6 11.9 2.81 .62 .79 .94 39.2 11.5 3.14 .63 .80 .95 37.7 11.0 3.51 .64 .82 .97 36.2 10.6 3.93 .65 .84 .98

71�F1020 480 41.6 12.2 2.83 .43 .55 .68 40.1 11.8 3.16 .43 .56 .69 38.6 11.3 3.53 .43 .57 .70 37.1 10.9 3.96 .43 .58 .72

71�F(22�C)

1220 575 42.5 12.5 2.85 .44 .58 .72 41.0 12.0 3.18 .44 .59 .74 39.4 11.5 3.55 .44 .60 .75 37.8 11.1 3.98 .45 .61 .77(22�C)

1420 670 43.1 12.6 2.86 .45 .61 .77 41.6 12.2 3.19 .45 .62 .78 40.0 11.7 3.57 .45 .63 .80 38.4 11.3 4.00 .46 .64 .82

HS29−036 � C33−38A/B−2 with G60UHV−36 COOLING CAPACITY − TXV Systems Only

63�F1020 480 38.5 11.3 2.78 .72 .86 .98 37.1 10.9 3.10 .73 .88 .99 35.7 10.5 3.46 .75 .89 1.00 34.2 10.0 3.89 .76 .91 1.00

63�F(17�C)

1220 575 39.7 11.6 2.80 .77 .91 1.00 38.3 11.2 3.12 .78 .93 1.00 36.8 10.8 3.49 .79 .95 1.00 35.3 10.3 3.92 .81 .97 1.00(17�C)

1420 670 40.7 11.9 2.82 .81 .96 1.00 39.3 11.5 3.14 .82 .97 1.00 37.9 11.1 3.51 .84 .99 1.00 36.4 10.7 3.94 .85 1.00 1.00

67�F1020 480 41.0 12.0 2.82 .57 .70 .82 39.5 11.6 3.15 .57 .71 .84 38.0 11.1 3.52 .58 .72 .86 36.4 10.7 3.94 .59 .74 .88

67�F(19�C)

1220 575 42.0 12.3 2.85 .59 .74 .88 40.5 11.9 3.17 .60 .76 .90 39.0 11.4 3.54 .61 .77 .92 37.3 10.9 3.97 .62 .79 .94(19�C)

1420 670 42.9 12.6 2.86 .62 .78 .93 41.3 12.1 3.19 .63 .80 .95 39.7 11.6 3.57 .63 .81 .97 38.0 11.1 3.99 .65 .83 .98

71�F1020 480 43.7 12.8 2.87 .43 .55 .67 42.2 12.4 3.21 .43 .55 .68 40.6 11.9 3.59 .43 .56 .69 39.0 11.4 4.01 .43 .57 .71

71�F(22�C)

1220 575 44.8 13.1 2.90 .43 .58 .72 43.2 12.7 3.23 .44 .58 .73 41.6 12.2 3.60 .44 .59 .75 39.8 11.7 4.04 .44 .60 .76(22�C)

1420 670 45.6 13.4 2.91 .44 .60 .76 44.0 12.9 3.25 .45 .61 .78 42.3 12.4 3.62 .45 .62 .79 40.5 11.9 4.06 .45 .63 .81

HS29−036 − CR26−36N COOLING CAPACITY − RFC or TXV Systems

63�F800 380 34.1 10.0 2.75 .68 .80 .91 32.9 9.6 3.07 .69 .81 .92 31.7 9.3 3.44 .70 .82 .94 30.4 8.9 3.87 .71 .84 .95

63�F(17�C)

900 425 34.9 10.2 2.77 .70 .83 .94 33.6 9.8 3.09 .71 .84 .96 32.4 9.5 3.46 .72 .85 .97 31.1 9.1 3.88 .73 .87 .98(17�C)

1000 470 35.5 10.4 2.78 .72 .86 .97 34.3 10.1 3.10 .73 .87 .99 33.0 9.7 3.47 .74 .88 1.00 31.6 9.3 3.90 .76 .91 1.00

67�F800 380 36.4 10.7 2.80 .55 .66 .77 35.2 10.3 3.12 .55 .66 .78 33.9 9.9 3.49 .55 .67 .79 32.5 9.5 3.92 .56 .68 .81

67�F(19�C)

900 425 37.2 10.9 2.81 .56 .67 .80 35.9 10.5 3.14 .56 .69 .81 34.5 10.1 3.51 .57 .70 .82 33.1 9.7 3.94 .57 .71 .84(19�C)

1000 470 37.8 11.1 2.82 .57 .70 .82 36.5 10.7 3.15 .57 .70 .84 35.1 10.3 3.53 .58 .72 .85 33.6 9.8 3.95 .59 .73 .87

71�F800 380 38.9 11.4 2.85 .42 .52 .63 37.6 11.0 3.17 .42 .53 .64 36.2 10.6 3.55 .42 .53 .65 34.8 10.2 3.98 .42 .54 .66

71�F(22�C)

900 425 39.7 11.6 2.86 .42 .54 .65 38.3 11.2 3.19 .43 .54 .66 36.9 10.8 3.57 .43 .55 .67 35.4 10.4 4.01 .43 .55 .68(22�C)

1000 470 40.3 11.8 2.88 .42 .55 .67 38.9 11.4 3.21 .43 .56 .68 37.5 11.0 3.58 .43 .56 .69 35.9 10.5 4.02 .43 .57 .71

HS29−036 − CR26−36W COOLING CAPACITY − RFC or TXV Systems

63�F900 425 35.1 10.3 2.74 .70 .83 .94 33.8 9.9 3.06 .71 .84 .96 32.6 9.6 3.42 .72 .86 .97 31.2 9.1 3.84 .73 .87 .98

63�F(17�C)

1100 520 36.3 10.6 2.76 .74 .88 .99 35.0 10.3 3.08 .75 .90 1.00 33.7 9.9 3.45 .76 .91 1.00 32.4 9.5 3.86 .78 .93 1.00(17�C)

1300 615 37.3 10.9 2.78 .78 .93 1.00 36.0 10.6 3.10 .79 .95 1.00 34.7 10.2 3.47 .81 .96 1.00 33.3 9.8 3.89 .83 .98 1.00

67�F900 425 37.4 11.0 2.78 .56 .68 .79 36.1 10.6 3.10 .56 .68 .81 34.7 10.2 3.47 .56 .69 .82 33.3 9.8 3.90 .57 .71 .84

67�F(19�C)

1100 520 38.6 11.3 2.80 .58 .72 .85 37.2 10.9 3.13 .58 .73 .87 35.8 10.5 3.50 .59 .74 .88 34.3 10.1 3.92 .60 .76 .90(19�C)

1300 615 39.4 11.5 2.82 .60 .76 .90 38.0 11.1 3.15 .61 .77 .92 36.5 10.7 3.52 .62 .79 .94 35.0 10.3 3.95 .63 .81 .95

71�F900 425 39.9 11.7 2.83 .42 .54 .65 38.6 11.3 3.16 .42 .54 .66 37.1 10.9 3.53 .43 .55 .67 35.6 10.4 3.96 .43 .55 .68

71�F(22�C)

1100 520 41.1 12.0 2.86 .43 .56 .69 39.7 11.6 3.18 .43 .57 .70 38.2 11.2 3.56 .43 .58 .71 36.6 10.7 3.98 .44 .58 .73(22�C)

1300 615 42.0 12.3 2.87 .44 .59 .73 40.5 11.9 3.20 .44 .60 .75 38.9 11.4 3.58 .44 .60 .77 37.3 10.9 4.01 .45 .62 .78

HS29−036 − CR26−48 COOLING CAPACITY − TXV Systems Only

63�F900 425 35.1 10.3 2.68 .70 .82 .93 33.9 9.9 2.99 .70 .83 .95 32.6 9.6 3.35 .71 .85 .97 31.2 9.1 3.75 .72 .86 .98

63�F(17�C)

1100 520 36.4 10.7 2.71 .73 .87 .99 35.1 10.3 3.02 .74 .89 1.00 33.8 9.9 3.37 .76 .90 1.00 32.4 9.5 3.79 .77 .92 1.00(17�C)

1300 615 37.5 11.0 2.72 .77 .92 1.00 36.1 10.6 3.04 .78 .94 1.00 34.7 10.2 3.40 .80 .95 1.00 33.3 9.8 3.81 .81 .97 1.00

67�F900 425 37.6 11.0 2.72 .55 .67 .78 36.3 10.6 3.04 .56 .67 .80 34.9 10.2 3.40 .56 .69 .81 33.5 9.8 3.81 .57 .70 .83

67�F(19�C)

1100 520 38.8 11.4 2.75 .57 .71 .84 37.4 11.0 3.07 .58 .72 .85 36.0 10.6 3.43 .58 .73 .87 34.5 10.1 3.85 .59 .74 .89(19�C)

1300 615 39.7 11.6 2.77 .59 .75 .89 38.3 11.2 3.09 .60 .76 .91 36.8 10.8 3.45 .61 .77 .92 35.2 10.3 3.86 .62 .79 .94

71�F900 425 40.2 11.8 2.78 .42 .53 .64 38.8 11.4 3.10 .42 .54 .65 37.3 10.9 3.46 .42 .54 .66 35.8 10.5 3.88 .42 .55 .67

71�F(22�C)

1100 520 41.4 12.1 2.80 .43 .55 .68 40.0 11.7 3.12 .43 .56 .69 38.5 11.3 3.49 .43 .57 .70 36.9 10.8 3.91 .43 .58 .72(22�C)

1300 615 42.4 12.4 2.82 .43 .58 .72 40.8 12.0 3.14 .44 .59 .74 39.3 11.5 3.52 .44 .60 .75 37.6 11.0 3.93 .44 .61 .77

HS29 / Page 32

Page 33: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 1 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

Outdoor Air Temperature Entering Outdoor Coil

Total85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)

EnteringWet BulbTempera�

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Tempera�ture

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

HS29−036 − CH33−36A/B/C−F − CH23−41 COOLING CAPACITY − RFC or TXV Systems

63�F1000 470 34.5 10.1 2.73 .72 .86 .97 33.3 9.8 3.04 .74 .87 .99 32.0 9.4 3.41 .75 .89 1.00 30.7 9.0 3.82 .76 .91 1.00

63�F(17�C)

1200 565 35.6 10.4 2.75 .77 .92 1.00 34.3 10.1 3.06 .78 .93 1.00 33.1 9.7 3.42 .80 .95 1.00 31.7 9.3 3.85 .81 .97 1.00(17�C)

1400 660 36.5 10.7 2.76 .81 .96 1.00 35.3 10.3 3.08 .82 .97 1.00 34.0 10.0 3.45 .84 .99 1.00 32.7 9.6 3.87 .86 1.00 1.00

67�F1000 470 36.7 10.8 2.77 .57 .70 .83 35.4 10.4 3.09 .57 .71 .84 34.0 10.0 3.45 .58 .72 .86 32.6 9.6 3.87 .59 .74 .88

67�F(19�C)

1200 565 37.6 11.0 2.79 .59 .74 .88 36.3 10.6 3.11 .60 .75 .90 34.9 10.2 3.47 .61 .77 .92 33.4 9.8 3.89 .62 .79 .94(19�C)

1400 660 38.3 11.2 2.81 .62 .79 .94 37.0 10.8 3.12 .63 .80 .95 35.5 10.4 3.49 .64 .82 .97 34.1 10.0 3.92 .65 .84 .98

71�F1000 470 39.1 11.5 2.82 .43 .55 .67 37.7 11.0 3.14 .43 .56 .68 36.3 10.6 3.51 .43 .56 .70 34.8 10.2 3.94 .43 .57 .71

71�F(22�C)

1200 565 40.0 11.7 2.84 .44 .58 .72 38.6 11.3 3.16 .44 .59 .73 37.1 10.9 3.53 .44 .60 .75 35.6 10.4 3.96 .44 .61 .76(22�C)

1400 660 40.7 11.9 2.85 .44 .61 .76 39.3 11.5 3.18 .45 .62 .78 37.8 11.1 3.55 .45 .62 .80 36.2 10.6 3.98 .46 .64 .82

HS29−036 � CH33−36A/B−2F with G60UHV−36 COOLING CAPACITY − TXV Systems Only

63�F1020 480 36.6 10.7 2.75 .72 .86 .97 35.3 10.3 3.06 .73 .87 .98 34.0 10.0 3.43 .74 .89 .99 32.7 9.6 3.85 .75 .90 1.00

63�F(17�C)

1220 575 37.7 11.0 2.77 .76 .90 1.00 36.4 10.7 3.09 .77 .92 1.00 35.0 10.3 3.46 .78 .94 1.00 33.6 9.8 3.88 .80 .96 1.00(17�C)

1420 670 38.6 11.3 2.78 .80 .95 1.00 37.3 10.9 3.11 .81 .96 1.00 35.9 10.5 3.47 .82 .98 1.00 34.6 10.1 3.89 .84 .99 1.00

67�F1020 480 39.0 11.4 2.79 .56 .69 .82 37.6 11.0 3.11 .57 .70 .84 36.2 10.6 3.48 .58 .72 .85 34.7 10.2 3.90 .59 .73 .87

67�F(19�C)

1220 575 39.9 11.7 2.80 .59 .73 .88 38.5 11.3 3.13 .59 .75 .89 37.1 10.9 3.49 .60 .76 .91 35.5 10.4 3.93 .61 .78 .93(19�C)

1420 670 40.6 11.9 2.82 .61 .77 .92 39.2 11.5 3.14 .62 .79 .94 37.7 11.0 3.51 .63 .80 .95 36.1 10.6 3.94 .64 .82 .97

71�F1020 480 41.5 12.2 2.83 .42 .55 .67 40.1 11.8 3.16 .43 .55 .68 38.6 11.3 3.53 .43 .56 .69 37.1 10.9 3.96 .43 .57 .70

71�F(22�C)

1220 575 42.5 12.5 2.85 .43 .57 .71 41.0 12.0 3.18 .43 .58 .72 39.5 11.6 3.55 .44 .59 .74 37.9 11.1 3.98 .44 .60 .75(22�C)

1420 670 43.2 12.7 2.86 .44 .60 .75 41.7 12.2 3.19 .44 .60 .76 40.1 11.8 3.57 .45 .62 .78 38.5 11.3 4.00 .45 .63 .80

HS29−036 � CH33−42B−2F with G60UHV−36 COOLING CAPACITY − TXV Systems Only

63�F1020 480 37.9 11.1 2.77 .72 .85 .97 36.6 10.7 3.10 .73 .87 .98 35.2 10.3 3.47 .74 .88 .99 33.8 9.9 3.89 .75 .90 1.00

63�F(17�C)

1220 575 39.1 11.5 2.80 .76 .90 1.00 37.7 11.0 3.12 .77 .92 1.00 36.3 10.6 3.49 .78 .94 1.00 34.8 10.2 3.92 .80 .95 1.00(17�C)

1420 670 40.1 11.8 2.81 .80 .95 1.00 38.7 11.3 3.14 .81 .96 1.00 37.2 10.9 3.51 .83 .98 1.00 35.8 10.5 3.94 .84 .99 1.00

67�F1020 480 40.5 11.9 2.82 .56 .69 .82 39.0 11.4 3.14 .57 .70 .83 37.5 11.0 3.52 .58 .71 .85 36.0 10.6 3.95 .58 .73 .87

67�F(19�C)

1220 575 41.5 12.2 2.84 .59 .73 .88 40.0 11.7 3.17 .59 .75 .89 38.5 11.3 3.54 .60 .76 .91 36.9 10.8 3.97 .61 .78 .93(19�C)

1420 670 42.3 12.4 2.86 .61 .77 .92 40.8 12.0 3.18 .62 .79 .94 39.2 11.5 3.56 .63 .80 .95 37.5 11.0 3.99 .64 .82 .97

71�F1020 480 43.2 12.7 2.87 .42 .54 .67 41.7 12.2 3.20 .43 .55 .68 40.1 11.8 3.58 .43 .56 .69 38.5 11.3 4.01 .43 .57 .70

71�F(22�C)

1220 575 44.2 13.0 2.89 .43 .57 .71 42.6 12.5 3.23 .43 .58 .72 41.0 12.0 3.60 .44 .59 .73 39.4 11.5 4.04 .44 .60 .75(22�C)

1420 670 45.0 13.2 2.91 .44 .60 .75 43.4 12.7 3.24 .44 .60 .76 41.7 12.2 3.62 .45 .61 .78 40.0 11.7 4.06 .45 .63 .80

HS29−036 � CH33−44/48B−2F with G60UHV−36 COOLING CAPACITY − TXV Systems Only

63�F1020 480 38.4 11.3 2.77 .72 .85 .97 37.1 10.9 3.10 .73 .87 .98 35.6 10.4 3.47 .74 .88 .99 34.2 10.0 3.89 .75 .90 1.00

63�F(17�C)

1220 575 39.6 11.6 2.80 .76 .90 1.00 38.2 11.2 3.12 .77 .92 1.00 36.8 10.8 3.49 .78 .93 1.00 35.2 10.3 3.92 .80 .95 1.00(17�C)

1420 670 40.6 11.9 2.81 .79 .95 1.00 39.2 11.5 3.14 .81 .96 1.00 37.7 11.0 3.51 .82 .98 1.00 36.2 10.6 3.94 .85 .99 1.00

67�F1020 480 41.0 12.0 2.82 .56 .69 .82 39.5 11.6 3.14 .57 .70 .83 38.0 11.1 3.52 .58 .71 .85 36.4 10.7 3.95 .59 .73 .87

67�F(19�C)

1220 575 42.0 12.3 2.84 .59 .73 .87 40.5 11.9 3.17 .59 .75 .89 38.9 11.4 3.54 .60 .76 .91 37.3 10.9 3.97 .61 .77 .93(19�C)

1420 670 42.8 12.5 2.86 .61 .77 .92 41.3 12.1 3.18 .62 .79 .94 39.7 11.6 3.56 .63 .80 .96 38.0 11.1 3.99 .64 .82 .97

71�F1020 480 43.7 12.8 2.87 .43 .54 .67 42.2 12.4 3.20 .43 .55 .68 40.6 11.9 3.58 .43 .56 .69 38.9 11.4 4.01 .43 .57 .70

71�F(22�C)

1220 575 44.8 13.1 2.89 .43 .57 .71 43.2 12.7 3.23 .44 .58 .72 41.5 12.2 3.60 .44 .59 .73 39.8 11.7 4.04 .44 .60 .75(22�C)

1420 670 45.6 13.4 2.91 .44 .59 .75 44.0 12.9 3.24 .44 .60 .76 42.3 12.4 3.62 .45 .61 .78 40.5 11.9 4.06 .45 .62 .80

HS29−036 − CB29M−31 − CB28UH−030 COOLING CAPACITY − TXV Systems Only

63�F950 450 33.4 9.8 2.67 .72 .85 .96 32.3 9.5 2.98 .72 .86 .97 31.1 9.1 3.34 .74 .88 .98 29.9 8.8 3.76 .75 .89 .99

63�F(17�C)

1050 495 33.9 9.9 2.68 .74 .88 .98 32.8 9.6 2.99 .75 .89 .99 31.6 9.3 3.36 .76 .91 1.00 30.4 8.9 3.77 .77 .92 1.00(17�C)

1150 545 34.4 10.1 2.69 .75 .90 .99 33.3 9.8 3.00 .77 .91 1.00 32.1 9.4 3.37 .78 .93 1.00 30.8 9.0 3.78 .79 .95 1.00

67�F950 450 35.5 10.4 2.71 .56 .69 .82 34.3 10.1 3.02 .57 .70 .83 33.0 9.7 3.38 .57 .71 .85 31.7 9.3 3.80 .58 .73 .86

67�F(19�C)

1050 495 36.0 10.6 2.71 .58 .71 .84 34.8 10.2 3.03 .58 .72 .86 33.5 9.8 3.39 .59 .73 .88 32.1 9.4 3.81 .60 .75 .89(19�C)

1150 545 36.4 10.7 2.72 .59 .73 .87 35.1 10.3 3.04 .59 .74 .89 33.8 9.9 3.40 .60 .76 .90 32.5 9.5 3.81 .61 .77 .92

71�F950 450 37.8 11.1 2.75 .42 .54 .66 36.5 10.7 3.07 .43 .55 .67 35.2 10.3 3.43 .43 .56 .69 33.8 9.9 3.85 .43 .57 .70

71�F(22�C)

1050 495 38.3 11.2 2.76 .43 .56 .69 37.0 10.8 3.08 .43 .56 .70 35.6 10.4 3.44 .43 .57 .71 34.2 10.0 3.86 .44 .58 .73(22�C)

1150 545 38.7 11.3 2.76 .43 .57 .71 37.4 11.0 3.08 .43 .58 .72 36.0 10.6 3.45 .44 .59 .73 34.6 10.1 3.87 .44 .60 .75

HS29−036 − CB29M−41 − CB28UH−036 COOLING CAPACITY − TXV Systems Only

63�F1000 470 33.9 9.9 2.66 .72 .86 .97 32.7 9.6 2.96 .73 .87 .98 31.5 9.2 3.32 .75 .89 .99 30.3 8.9 3.73 .76 .90 1.00

63�F(17�C)

1200 565 34.9 10.2 2.68 .76 .91 1.00 33.7 9.9 2.99 .78 .93 1.00 32.5 9.5 3.35 .79 .94 1.00 31.2 9.1 3.76 .81 .96 1.00(17�C)

1400 660 35.8 10.5 2.69 .80 .95 1.00 34.6 10.1 3.01 .82 .97 1.00 33.3 9.8 3.36 .83 .98 1.00 32.1 9.4 3.77 .85 .99 1.00

67�F1000 470 36.1 10.6 2.69 .57 .70 .83 34.8 10.2 3.01 .57 .71 .84 33.5 9.8 3.36 .58 .72 .85 32.1 9.4 3.77 .59 .74 .87

67�F(19�C)

1200 565 36.9 10.8 2.71 .59 .74 .88 35.6 10.4 3.02 .60 .75 .89 34.3 10.1 3.38 .60 .76 .91 32.9 9.6 3.79 .61 .78 .93(19�C)

1400 660 37.6 11.0 2.72 .61 .78 .93 36.3 10.6 3.04 .62 .79 .94 34.9 10.2 3.40 .63 .81 .96 33.5 9.8 3.81 .64 .83 .97

71�F1000 470 38.4 11.3 2.74 .42 .55 .67 37.1 10.9 3.06 .43 .56 .68 35.7 10.5 3.42 .43 .56 .69 34.3 10.1 3.83 .43 .57 .71

71�F(22�C)

1200 565 39.3 11.5 2.76 .43 .58 .72 37.9 11.1 3.07 .44 .58 .73 36.5 10.7 3.44 .44 .59 .74 35.0 10.3 3.85 .44 .60 .76(22�C)

1400 660 39.9 11.7 2.77 .44 .60 .76 38.5 11.3 3.09 .45 .61 .77 37.1 10.9 3.45 .45 .62 .79 35.6 10.4 3.87 .46 .63 .81

HS29−036 − CB30M−31 − CB30U−31 COOLING CAPACITY − TXV Systems Only

63�F1050 495 34.9 10.2 2.71 .73 .87 .98 33.6 9.8 3.02 .74 .88 .99 32.4 9.5 3.38 .75 .90 1.00 31.0 9.1 3.79 .77 .92 1.00

63�F(17�C)

1150 545 35.4 10.4 2.72 .75 .90 1.00 34.2 10.0 3.03 .76 .91 1.00 32.8 9.6 3.39 .78 .93 1.00 31.5 9.2 3.81 .79 .95 1.00(17�C)

1250 590 35.9 10.5 2.73 .77 .92 1.00 34.6 10.1 3.04 .78 .94 1.00 33.3 9.8 3.41 .80 .95 1.00 32.0 9.4 3.82 .82 .97 1.00

67�F1050 495 37.1 10.9 2.75 .57 .70 .84 35.8 10.5 3.07 .58 .72 .85 34.4 10.1 3.43 .58 .73 .87 33.0 9.7 3.85 .59 .74 .89

67�F(19�C)

1150 545 37.6 11.0 2.77 .58 .73 .86 36.2 10.6 3.08 .59 .74 .88 34.8 10.2 3.44 .60 .75 .89 33.4 9.8 3.86 .61 .77 .92(19�C)

1250 590 38.0 11.1 2.77 .59 .75 .89 36.6 10.7 3.09 .60 .76 .91 35.2 10.3 3.46 .61 .78 .92 33.7 9.9 3.88 .62 .79 .94

71�F1050 495 39.6 11.6 2.80 .43 .55 .68 38.2 11.2 3.13 .43 .56 .69 36.7 10.8 3.49 .43 .57 .70 35.2 10.3 3.91 .43 .58 .72

71�F(22�C)

1150 545 40.0 11.7 2.81 .43 .57 .70 38.6 11.3 3.14 .43 .58 .72 37.2 10.9 3.50 .44 .58 .73 35.6 10.4 3.93 .44 .59 .74(22�C)

1250 590 40.5 11.9 2.83 .43 .58 .72 39.0 11.4 3.15 .44 .59 .73 37.5 11.0 3.51 .44 .60 .75 35.9 10.5 3.94 .45 .61 .77

HS29 / Page 33

Page 34: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 1 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

Outdoor Air Temperature Entering Outdoor Coil

Total85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)

EnteringWet BulbTempera�

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Tempera�ture

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

HS29−036 − CB29M−46 − CB28UH−042 COOLING CAPACITY − TXV Systems Only

63�F1000 470 35.6 10.4 2.72 .72 .85 .97 34.3 10.1 3.04 .73 .87 .98 33.0 9.7 3.40 .74 .88 .99 31.7 9.3 3.81 .76 .90 1.00

63�F(17�C)

1200 565 36.7 10.8 2.74 .76 .91 1.00 35.4 10.4 3.06 .77 .92 1.00 34.1 10.0 3.42 .79 .94 1.00 32.7 9.6 3.84 .80 .96 1.00(17�C)

1400 660 37.6 11.0 2.76 .80 .95 1.00 36.3 10.6 3.08 .82 .97 1.00 35.0 10.3 3.45 .83 .98 1.00 33.6 9.8 3.86 .85 1.00 1.00

67�F1000 470 37.9 11.1 2.77 .56 .69 .82 36.6 10.7 3.09 .57 .70 .83 35.1 10.3 3.45 .58 .72 .85 33.7 9.9 3.87 .58 .73 .87

67�F(19�C)

1200 565 38.9 11.4 2.79 .59 .74 .88 37.5 11.0 3.11 .59 .75 .89 36.1 10.6 3.47 .61 .76 .91 34.5 10.1 3.90 .61 .78 .93(19�C)

1400 660 39.7 11.6 2.80 .61 .78 .93 38.2 11.2 3.13 .62 .79 .95 36.7 10.8 3.50 .63 .81 .96 35.2 10.3 3.91 .64 .83 .97

71�F1000 470 40.4 11.8 2.82 .43 .55 .67 39.0 11.4 3.14 .43 .55 .68 37.6 11.0 3.51 .43 .56 .69 36.0 10.6 3.93 .43 .57 .71

71�F(22�C)

1200 565 41.4 12.1 2.84 .43 .57 .71 40.0 11.7 3.17 .44 .58 .73 38.5 11.3 3.53 .44 .59 .74 36.9 10.8 3.96 .44 .60 .76(22�C)

1400 660 42.2 12.4 2.85 .44 .60 .76 40.7 11.9 3.18 .44 .61 .77 39.1 11.5 3.56 .45 .62 .79 37.5 11.0 3.98 .45 .63 .81

HS29−036 − CB30M−41 − CB30M−46 − CB30U−41/46 COOLING CAPACITY − TXV Systems Only

63�F1000 470 35.8 10.5 2.68 .72 .85 .97 34.5 10.1 2.98 .73 .87 .99 33.2 9.7 3.34 .74 .88 1.00 31.8 9.3 3.75 .76 .90 1.00

63�F(17�C)

1200 565 36.9 10.8 2.70 .76 .91 1.00 35.6 10.4 3.01 .77 .92 1.00 34.2 10.0 3.36 .79 .94 1.00 32.8 9.6 3.77 .80 .96 1.00(17�C)

1400 660 37.9 11.1 2.72 .80 .96 1.00 36.5 10.7 3.03 .81 .97 1.00 35.2 10.3 3.39 .83 .98 1.00 33.8 9.9 3.80 .85 1.00 1.00

67�F1000 470 38.1 11.2 2.72 .56 .69 .82 36.8 10.8 3.03 .57 .70 .83 35.3 10.3 3.39 .58 .72 .85 33.9 9.9 3.80 .58 .73 .87

67�F(19�C)

1200 565 39.2 11.5 2.74 .59 .73 .88 37.7 11.0 3.05 .60 .75 .89 36.3 10.6 3.42 .60 .76 .91 34.7 10.2 3.83 .61 .78 .93(19�C)

1400 660 39.9 11.7 2.76 .61 .78 .93 38.5 11.3 3.08 .62 .79 .94 36.9 10.8 3.43 .63 .81 .96 35.4 10.4 3.85 .64 .83 .98

71�F1000 470 40.7 11.9 2.77 .43 .55 .67 39.3 11.5 3.09 .43 .55 .68 37.8 11.1 3.45 .43 .56 .69 36.2 10.6 3.87 .43 .57 .70

71�F(22�C)

1200 565 41.7 12.2 2.79 .43 .57 .71 40.3 11.8 3.11 .43 .58 .72 38.7 11.3 3.48 .44 .59 .74 37.1 10.9 3.89 .44 .60 .75(22�C)

1400 660 42.5 12.5 2.81 .44 .60 .76 41.0 12.0 3.13 .44 .61 .77 39.4 11.5 3.50 .45 .62 .79 37.7 11.0 3.91 .45 .63 .80

HS29−036 − CB31MV−41 COOLING CAPACITY − TXV Systems Only

63�F1135 535 36.0 10.6 2.72 .75 .89 1.00 34.7 10.2 3.04 .76 .91 1.00 33.4 9.8 3.40 .77 .92 1.00 32.0 9.4 3.81 .79 .94 1.00

63�F(17�C)

1275 600 36.7 10.8 2.74 .77 .93 1.00 35.4 10.4 3.05 .79 .94 1.00 34.0 10.0 3.42 .80 .96 1.00 32.7 9.6 3.83 .82 .98 1.00(17�C)

1400 660 37.3 10.9 2.75 .80 .95 1.00 36.0 10.6 3.07 .81 .97 1.00 34.6 10.1 3.43 .83 .99 1.00 33.3 9.8 3.84 .85 1.00 1.00

67�F1135 535 38.2 11.2 2.77 .58 .72 .86 36.9 10.8 3.09 .59 .73 .87 35.4 10.4 3.45 .60 .75 .89 33.9 9.9 3.87 .60 .76 .91

67�F(19�C)

1275 600 38.9 11.4 2.78 .60 .75 .90 37.4 11.0 3.10 .60 .76 .91 35.9 10.5 3.47 .62 .78 .93 34.4 10.1 3.88 .63 .80 .95(19�C)

1400 660 39.3 11.5 2.79 .61 .78 .93 37.9 11.1 3.11 .62 .79 .94 36.4 10.7 3.48 .63 .81 .96 34.8 10.2 3.89 .64 .83 .98

71�F1135 535 40.8 12.0 2.82 .43 .56 .70 39.3 11.5 3.15 .43 .57 .71 37.8 11.1 3.51 .44 .58 .72 36.2 10.6 3.94 .44 .59 .74

71�F(22�C)

1275 600 41.4 12.1 2.84 .44 .58 .73 39.9 11.7 3.16 .44 .59 .74 38.3 11.2 3.53 .44 .60 .76 36.7 10.8 3.95 .45 .61 .77(22�C)

1400 660 41.8 12.3 2.85 .44 .60 .75 40.3 11.8 3.17 .45 .61 .77 38.8 11.4 3.54 .45 .62 .79 37.1 10.9 3.96 .45 .63 .80

HS29−036 − CVP10−41/EC10Q3 − CVP10−46/EC10Q4 COOLING CAPACITY − TXV Systems Only

63�F1000 470 34.1 10.0 2.73 .72 .85 .97 32.9 9.6 3.05 .73 .87 .98 31.7 9.3 3.40 .74 .88 .99 30.3 8.9 3.82 .75 .90 1.00

63�F(17�C)

1200 565 35.2 10.3 2.75 .76 .91 1.00 34.0 10.0 3.07 .77 .92 1.00 32.7 9.6 3.43 .78 .94 1.00 31.3 9.2 3.85 .80 .96 1.00(17�C)

1400 660 36.1 10.6 2.77 .80 .95 1.00 34.9 10.2 3.09 .81 .97 1.00 33.6 9.8 3.45 .83 .98 1.00 32.3 9.5 3.87 .85 .99 1.00

67�F1000 470 36.4 10.7 2.77 .56 .69 .82 35.1 10.3 3.09 .57 .70 .83 33.7 9.9 3.46 .58 .72 .85 32.3 9.5 3.88 .58 .73 .87

67�F(19�C)

1200 565 37.3 10.9 2.80 .59 .73 .87 36.0 10.6 3.11 .59 .75 .89 34.6 10.1 3.48 .60 .76 .91 33.1 9.7 3.91 .61 .78 .93(19�C)

1400 660 38.1 11.2 2.81 .61 .78 .92 36.7 10.8 3.14 .62 .79 .94 35.3 10.3 3.50 .63 .81 .96 33.8 9.9 3.92 .64 .83 .98

71�F1000 470 38.8 11.4 2.82 .43 .54 .66 37.4 11.0 3.15 .43 .55 .68 36.0 10.6 3.52 .43 .56 .69 34.5 10.1 3.94 .43 .57 .70

71�F(22�C)

1200 565 39.8 11.7 2.85 .43 .57 .71 38.4 11.3 3.17 .43 .58 .72 36.9 10.8 3.54 .44 .59 .74 35.4 10.4 3.97 .44 .60 .75(22�C)

1400 660 40.6 11.9 2.86 .44 .60 .75 39.1 11.5 3.19 .45 .61 .77 37.6 11.0 3.57 .45 .62 .78 36.0 10.6 3.99 .45 .63 .80

RATINGS − 3 PHASE

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C450 950 10.0 34,100 2700 .71 .85 .96 9.5 32,400 2890 .73 .87 .98 9.0 30,700 3060 .74 .89 .99 8.5 28,900 3220 .77 .91 1.00

520 1100 10.3 35,000 2720 .74 .88 .99 9.8 33,300 2920 .76 .91 1.00 9.2 31,500 3100 .78 .93 1.00 8.7 29,600 3260 .80 .95 1.00

590 1250 10.5 35,700 2750 .77 .92 1.00 10.0 34,000 2950 .79 .94 1.00 9.4 32,200 3130 .81 .96 1.00 8.9 30,300 3300 .84 .98 1.00

450 950 10.7 36,400 2770 .56 .69 .81 10.1 34,600 2980 .57 .70 .83 9.6 32,800 3160 .58 .72 .85 9.0 30,800 3330 .59 .74 .88

520 1100 10.9 37,200 2800 .58 .72 .85 10.4 35,400 3000 .59 .73 .87 9.8 33,400 3190 .60 .75 .90 9.2 31,400 3360 .61 .78 .92

590 1250 11.1 37,900 2820 .59 .75 .89 10.6 36,000 3030 .60 .77 .91 9.9 33,900 3220 .62 .79 .94 9.3 31,900 3390 .63 .81 .96

450 950 11.4 39,000 2860 .42 .54 .66 10.9 37,100 3070 .43 .55 .67 10.3 35,100 3270 .43 .56 .69 9.7 33,000 3450 .43 .57 .71

520 1100 11.7 39,800 2880 .43 .56 .69 11.1 37,800 3100 .43 .57 .71 10.5 35,800 3300 .44 .58 .73 9.8 33,600 3480 .44 .60 .75

590 1250 11.8 40,400 2900 .43 .58 .72 11.3 38,400 3120 .44 .59 .74 10.6 36,300 3330 .44 .60 .76 10.0 34,100 3510 .45 .62 .79

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�036 � C33−36A/B/C − C23�41 − RFC or TXV Systems

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

HS29 / Page 34

Page 35: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 3 PHASE

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C360 760 9.9 33,900 2740 .68 .79 .90 9.4 32,200 2930 .69 .81 .92 8.9 30,400 3110 .70 .83 .94 8.4 28,500 3270 .72 .85 .97

455 960 10.4 35,500 2790 .72 .85 .96 9.9 33,700 2990 .73 .87 .98 9.3 31,800 3180 .75 .89 1.00 8.8 29,900 3350 .77 .92 1.00

545 1160 10.8 36,800 2830 .76 .90 1.00 10.2 34,900 3040 .77 .92 1.00 9.6 32,900 3240 .80 .95 1.00 9.1 30,900 3410 .82 .97 1.00

360 760 10.7 36,400 2820 .54 .65 .76 10.1 34,600 3030 .55 .66 .77 9.6 32,700 3220 .55 .67 .79 9.0 30,700 3390 .56 .69 .82

455 960 11.1 38,000 2880 .56 .69 .81 10.6 36,000 3090 .57 .70 .83 10.0 34,000 3290 .58 .72 .86 9.3 31,900 3460 .59 .74 .89

545 1160 11.5 39,100 2910 .58 .73 .87 10.9 37,100 3130 .59 .75 .89 10.2 34,900 3330 .61 .77 .92 9.6 32,700 3510 .62 .80 .95

360 760 11.4 39,000 2910 .42 .52 .62 10.9 37,100 3140 .42 .53 .63 10.3 35,100 3340 .42 .53 .65 9.7 33,000 3530 .42 .54 .66

455 960 11.9 40,700 2970 .42 .54 .66 11.3 38,600 3200 .43 .55 .68 10.7 36,500 3410 .43 .56 .69 10.0 34,200 3590 .43 .58 .72

545 1160 12.3 41,800 3010 .43 .57 .70 11.6 39,600 3240 .44 .58 .72 11.0 37,400 3450 .44 .59 .74 10.3 35,000 3640 .45 .61 .77

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�036 � C26�31 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C470 1000 10.3 35,300 2760 .72 .86 .97 9.8 33,500 2960 .74 .88 .99 9.3 31,600 3150 .76 .91 1.00 8.7 29,700 3310 .78 .93 1.00

565 1200 10.7 36,400 2800 .76 .91 1.00 10.1 34,600 3010 .78 .93 1.00 9.6 32,700 3200 .80 .96 1.00 9.0 30,800 3370 .83 .98 1.00

660 1400 11.0 37,400 2830 .80 .95 1.00 10.4 35,500 3040 .82 .97 1.00 9.8 33,600 3240 .85 .99 1.00 9.3 31,800 3430 .88 1.00 1.00

470 1000 11.0 37,700 2840 .57 .70 .83 10.5 35,700 3060 .58 .71 .85 9.9 33,700 3250 .59 .73 .87 9.3 31,600 3420 .60 .75 .90

565 1200 11.3 38,600 2880 .59 .74 .88 10.8 36,700 3090 .60 .76 .90 10.1 34,600 3290 .61 .78 .93 9.5 32,400 3460 .63 .81 .96

660 1400 11.5 39,400 2900 .61 .78 .93 10.9 37,300 3120 .63 .80 .95 10.3 35,200 3320 .64 .83 .97 9.7 33,000 3500 .66 .85 .99

470 1000 11.8 40,300 2930 .43 .55 .67 11.2 38,300 3160 .43 .56 .69 10.6 36,200 3360 .43 .57 .71 9.9 33,900 3550 .44 .58 .73

565 1200 12.1 41,300 2970 .43 .57 .71 11.5 39,200 3190 .44 .59 .73 10.8 37,000 3400 .44 .60 .76 10.2 34,700 3590 .45 .62 .78

660 1400 12.3 42,000 2990 .44 .60 .76 11.7 39,800 3220 .45 .61 .78 11.0 37,600 3430 .45 .63 .80 10.3 35,200 3620 .46 .65 .83

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�036 � C33−42B − C23�46 − RFC or TXV Systems

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C450 950 10.6 36,000 2810 .71 .84 .96 10.0 34,100 3010 .73 .86 .98 9.4 32,200 3200 .74 .89 1.00 8.9 30,200 3370 .77 .92 1.00

540 1150 10.9 37,300 2850 .75 .90 1.00 10.3 35,300 3060 .77 .92 1.00 9.8 33,300 3260 .79 .95 1.00 9.2 31,300 3430 .82 .97 1.00

635 1350 11.2 38,300 2890 .79 .95 1.00 10.7 36,400 3110 .81 .97 1.00 10.1 34,400 3310 .84 .99 1.00 9.5 32,400 3500 .87 1.00 1.00

450 950 11.3 38,500 2900 .56 .69 .81 10.7 36,500 3110 .57 .70 .83 10.1 34,400 3310 .58 .72 .85 9.5 32,300 3490 .59 .74 .88

540 1150 11.6 39,700 2940 .58 .73 .86 11.0 37,600 3160 .59 .74 .89 10.4 35,400 3360 .61 .77 .91 9.7 33,100 3540 .62 .79 .94

635 1350 11.9 40,600 2970 .61 .77 .91 11.3 38,400 3190 .62 .79 .94 10.6 36,100 3400 .63 .81 .97 9.9 33,800 3580 .65 .84 .99

450 950 12.1 41,300 2990 .42 .54 .66 11.5 39,200 3220 .43 .55 .67 10.8 37,000 3430 .43 .56 .69 10.1 34,600 3620 .43 .57 .71

540 1150 12.5 42,500 3030 .43 .57 .70 11.8 40,200 3260 .43 .58 .72 11.1 37,900 3480 .44 .59 .74 10.4 35,500 3670 .44 .61 .77

635 1350 12.7 43,300 3060 .44 .59 .74 12.0 41,000 3300 .44 .61 .77 11.3 38,600 3510 .45 .62 .79 10.6 36,100 3700 .46 .64 .82

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�036 � C33−38A/B − C26�41 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C470 1000 10.7 36,600 2830 .72 .86 .97 10.2 34,700 3040 .74 .88 .99 9.6 32,700 3230 .76 .90 1.00 9.0 30,700 3400 .78 .93 1.00

565 1200 11.1 37,900 2880 .76 .91 1.00 10.5 35,900 3090 .78 .94 1.00 9.9 33,900 3290 .81 .96 1.00 9.3 31,800 3460 .83 .99 1.00

660 1400 11.4 38,900 2910 .80 .96 1.00 10.8 36,900 3130 .83 .98 1.00 10.2 34,900 3340 .85 1.00 1.00 9.7 33,000 3530 .88 1.00 1.00

470 1000 11.5 39,100 2920 .57 .70 .82 10.9 37,100 3140 .57 .71 .84 10.3 35,000 3340 .59 .73 .87 9.6 32,700 3520 .60 .75 .90

565 1200 11.8 40,300 2960 .59 .74 .88 11.2 38,100 3180 .60 .76 .90 10.5 35,900 3390 .61 .78 .93 9.8 33,600 3570 .63 .81 .96

660 1400 12.0 41,100 2990 .61 .78 .93 11.4 38,900 3210 .63 .80 .95 10.7 36,600 3420 .64 .83 .98 10.0 34,200 3600 .66 .86 1.00

470 1000 12.3 41,900 3020 .43 .55 .67 11.6 39,700 3250 .43 .56 .69 11.0 37,500 3460 .43 .57 .70 10.3 35,100 3650 .44 .58 .73

565 1200 12.6 43,000 3050 .43 .57 .71 11.9 40,700 3290 .44 .59 .73 11.3 38,400 3510 .44 .60 .76 10.5 35,900 3700 .45 .62 .78

660 1400 12.8 43,800 3080 .44 .60 .76 12.2 41,500 3320 .45 .61 .78 11.4 39,000 3540 .45 .63 .80 10.7 36,500 3730 .46 .65 .84

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�036 � C33−44C − C26�46 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

HS29 / Page 35

Page 36: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 3 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C470 1000 10.8 37,000 2800 .72 .85 .97 10.3 35,100 3000 .73 .87 .99 9.7 33,200 3190 .75 .90 1.00 9.1 31,100 3350 .77 .93 1.00

565 1200 11.2 38,300 2840 .76 .90 1.00 10.6 36,300 3050 .78 .93 1.00 10.0 34,200 3240 .80 .95 1.00 9.4 32,200 3410 .82 .98 1.00

660 1400 11.5 39,300 2870 .80 .95 1.00 10.9 37,300 3090 .82 .97 1.00 10.3 35,300 3290 .84 .99 1.00 9.8 33,300 3480 .87 1.00 1.00

470 1000 11.6 39,600 2880 .56 .69 .82 11.0 37,600 3100 .57 .71 .84 10.4 35,500 3300 .58 .72 .86 9.7 33,200 3470 .59 .75 .89

565 1200 12.0 40,800 2920 .59 .73 .87 11.3 38,600 3140 .60 .75 .89 10.6 36,300 3340 .61 .77 .92 10.0 34,000 3520 .62 .80 .95

660 1400 12.2 41,600 2950 .61 .77 .92 11.5 39,300 3170 .62 .79 .94 10.8 37,000 3370 .64 .82 .97 10.2 34,700 3550 .65 .85 .99

470 1000 12.5 42,500 2980 .42 .54 .66 11.8 40,300 3210 .43 .55 .68 11.1 38,000 3420 .43 .56 .70 10.4 35,600 3610 .43 .58 .72

565 1200 12.8 43,600 3010 .43 .57 .71 12.1 41,300 3250 .44 .58 .72 11.4 38,900 3460 .44 .59 .75 10.7 36,500 3650 .45 .61 .77

660 1400 13.0 44,400 3040 .44 .59 .75 12.3 42,000 3280 .45 .61 .77 11.6 39,600 3490 .45 .62 .79 10.8 37,000 3680 .46 .64 .82

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�036 � C33−48B/C TXV Systems − C23�51 − RFC or TXV Systems

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C425 900 10.4 35,400 2800 .70 .83 .94 9.8 33,600 3000 .72 .85 .97 9.3 31,700 3180 .73 .87 .99 8.7 29,700 3350 .75 .90 1.00

520 1100 10.8 36,800 2840 .74 .88 .99 10.2 34,800 3050 .76 .91 1.00 9.6 32,900 3250 .78 .93 1.00 9.0 30,800 3420 .81 .96 1.00

615 1300 11.1 37,800 2880 .78 .93 1.00 10.5 35,900 3100 .80 .96 1.00 9.9 33,900 3300 .83 .98 1.00 9.3 31,900 3480 .85 1.00 1.00

425 900 11.1 37,900 2880 .56 .68 .79 10.6 36,000 3100 .56 .69 .81 9.9 33,900 3300 .57 .70 .84 9.3 31,800 3470 .58 .73 .86

520 1100 11.5 39,200 2930 .58 .72 .85 10.9 37,100 3150 .59 .73 .87 10.3 35,000 3350 .60 .75 .90 9.6 32,700 3530 .61 .78 .93

615 1300 11.8 40,100 2960 .60 .76 .90 11.1 38,000 3180 .61 .78 .93 10.5 35,700 3390 .63 .80 .95 9.8 33,400 3570 .64 .83 .98

425 900 11.9 40,600 2980 .42 .54 .65 11.3 38,600 3210 .42 .54 .66 10.7 36,400 3420 .43 .55 .68 10.0 34,200 3610 .43 .56 .70

520 1100 12.3 41,900 3020 .43 .56 .69 11.6 39,700 3260 .43 .57 .71 11.0 37,500 3470 .44 .58 .73 10.3 35,100 3660 .44 .60 .75

615 1300 12.6 42,900 3050 .44 .59 .73 11.9 40,600 3290 .44 .60 .75 11.2 38,200 3510 .45 .61 .78 10.5 35,700 3700 .45 .63 .81

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�036 � CR26�36 − RFC or TXV Systems

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C470 1000 10.5 35,700 2810 .73 .86 .98 9.9 33,900 3010 .74 .88 .99 9.4 32,000 3200 .76 .91 1.00 8.8 30,000 3370 .78 .94 1.00

565 1200 10.8 36,900 2850 .77 .92 1.00 10.3 35,000 3060 .79 .94 1.00 9.7 33,100 3260 .81 .96 1.00 9.1 31,100 3430 .84 .99 1.00

660 1400 11.1 37,900 2890 .81 .96 1.00 10.6 36,000 3110 .83 .98 1.00 10.0 34,100 3310 .86 1.00 1.00 9.4 32,200 3500 .89 1.00 1.00

470 1000 11.2 38,100 2890 .57 .70 .83 10.6 36,100 3110 .58 .72 .85 10.0 34,000 3310 .59 .74 .88 9.3 31,900 3480 .60 .76 .90

565 1200 11.5 39,100 2930 .59 .74 .89 10.9 37,100 3150 .60 .76 .91 10.2 34,900 3350 .62 .79 .94 9.6 32,700 3530 .63 .81 .96

660 1400 11.7 40,000 2960 .62 .79 .94 11.1 37,800 3180 .63 .81 .96 10.4 35,600 3380 .65 .83 .98 9.8 33,300 3570 .67 .86 1.00

470 1000 12.0 40,800 2980 .43 .55 .67 11.3 38,700 3210 .43 .56 .69 10.7 36,500 3430 .43 .57 .71 10.0 34,200 3610 .44 .59 .73

565 1200 12.3 41,800 3020 .43 .58 .72 11.6 39,600 3250 .44 .59 .74 10.9 37,300 3470 .44 .60 .76 10.2 34,900 3660 .45 .62 .79

660 1400 12.5 42,600 3050 .44 .60 .76 11.8 40,300 3280 .45 .62 .79 11.1 37,900 3500 .46 .64 .81 10.4 35,500 3690 .46 .66 .84

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�036 � CH33−36A/B/C−F − CH23�41 − RFC or TXV Systems

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C450 950 9.9 33,800 2670 .72 .85 .96 9.4 32,100 2850 .73 .87 .98 8.9 30,400 3030 .75 .90 1.00 8.4 28,700 3180 .77 .92 1.00

495 1050 10.1 34,400 2690 .74 .88 .99 9.6 32,700 2880 .76 .90 1.00 9.1 31,000 3050 .77 .92 1.00 8.6 29,200 3210 .80 .95 1.00

540 1150 10.2 34,900 2700 .76 .91 1.00 9.7 33,200 2900 .78 .93 1.00 9.2 31,400 3080 .80 .95 1.00 8.7 29,600 3240 .82 .97 1.00

450 950 10.6 36,000 2740 .56 .69 .82 10.1 34,300 2940 .57 .71 .84 9.5 32,400 3120 .58 .73 .86 8.9 30,500 3290 .59 .75 .89

495 1050 10.7 36,600 2760 .58 .71 .85 10.2 34,800 2960 .58 .73 .87 9.6 32,900 3150 .60 .75 .89 9.1 30,900 3310 .61 .77 .92

540 1150 10.8 37,000 2770 .59 .73 .87 10.3 35,200 2980 .60 .75 .90 9.8 33,300 3160 .61 .77 .92 9.1 31,200 3330 .62 .80 .95

450 950 11.3 38,500 2820 .42 .55 .67 10.8 36,700 3040 .43 .55 .68 10.2 34,700 3230 .43 .57 .70 9.6 32,700 3410 .43 .58 .72

495 1050 11.4 39,000 2840 .43 .56 .69 10.9 37,100 3050 .43 .57 .70 10.3 35,200 3250 .44 .58 .72 9.7 33,100 3430 .44 .59 .75

540 1150 11.6 39,500 2850 .43 .57 .71 11.0 37,600 3070 .44 .58 .73 10.4 35,500 3270 .44 .60 .75 9.8 33,400 3450 .45 .61 .77

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−036 � CB29M−31 − CB28UH−030 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

HS29 / Page 36

Page 37: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 3 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C470 1000 10.1 34,300 2680 .73 .86 .97 9.6 32,600 2880 .74 .88 .99 9.0 30,800 3060 .76 .91 1.00 8.5 29,000 3210 .78 .93 1.00

565 1200 10.4 35,400 2720 .77 .91 1.00 9.8 33,600 2920 .78 .93 1.00 9.3 31,800 3100 .81 .96 1.00 8.8 30,000 3270 .83 .98 1.00

660 1400 10.6 36,300 2750 .80 .96 1.00 10.1 34,500 2960 .83 .97 1.00 9.6 32,700 3150 .85 .99 1.00 9.1 30,900 3330 .88 1.00 1.00

470 1000 10.7 36,600 2760 .57 .70 .83 10.2 34,800 2960 .58 .71 .85 9.6 32,800 3150 .59 .73 .87 9.0 30,800 3320 .60 .76 .90

565 1200 11.0 37,500 2790 .59 .74 .88 10.4 35,600 3000 .60 .76 .90 9.8 33,600 3190 .61 .78 .93 9.2 31,500 3360 .63 .81 .96

660 1400 11.2 38,300 2820 .61 .78 .93 10.6 36,300 3030 .63 .80 .95 10.0 34,200 3220 .64 .83 .97 9.4 32,100 3390 .66 .86 .99

470 1000 11.5 39,100 2840 .43 .55 .67 10.9 37,200 3060 .43 .56 .69 10.3 35,200 3260 .43 .57 .71 9.7 33,000 3440 .44 .58 .73

565 1200 11.8 40,100 2880 .43 .57 .72 11.2 38,100 3100 .44 .59 .73 10.5 35,900 3300 .44 .60 .76 9.9 33,700 3480 .45 .62 .78

660 1400 12.0 40,800 2900 .44 .60 .76 11.3 38,700 3120 .45 .61 .78 10.7 36,500 3330 .45 .63 .80 10.0 34,200 3510 .46 .65 .83

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−036 � CB29M−41 − CB28UH−036 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C495 1050 10.3 35,300 2770 .73 .87 .98 9.8 33,500 2970 .75 .89 1.00 9.2 31,500 3160 .77 .92 1.00 8.7 29,600 3320 .79 .95 1.00

540 1150 10.5 35,900 2790 .75 .90 1.00 10.0 34,000 2990 .77 .92 1.00 9.4 32,100 3180 .79 .95 1.00 8.8 30,100 3350 .82 .97 1.00

590 1250 10.7 36,400 2800 .77 .92 1.00 10.1 34,500 3010 .79 .95 1.00 9.6 32,600 3210 .82 .97 1.00 9.0 30,700 3380 .84 .99 1.00

495 1050 11.0 37,700 2850 .57 .71 .84 10.5 35,700 3060 .58 .72 .86 9.9 33,700 3260 .59 .74 .88 9.2 31,500 3430 .61 .77 .91

540 1150 11.2 38,200 2870 .58 .73 .86 10.6 36,200 3080 .59 .74 .89 10.0 34,100 3280 .61 .77 .91 9.3 31,900 3450 .62 .79 .94

590 1250 11.3 38,700 2880 .59 .75 .89 10.7 36,600 3100 .61 .77 .91 10.1 34,500 3300 .62 .79 .94 9.4 32,200 3470 .64 .82 .97

495 1050 11.8 40,400 2940 .43 .55 .68 11.2 38,300 3170 .43 .56 .70 10.6 36,100 3380 .43 .58 .72 9.9 33,800 3560 .44 .59 .74

540 1150 12.0 40,900 2960 .43 .57 .70 11.3 38,700 3190 .43 .58 .72 10.7 36,500 3400 .44 .59 .74 10.0 34,200 3580 .44 .61 .77

590 1250 12.1 41,300 2970 .44 .58 .72 11.5 39,100 3200 .44 .59 .74 10.8 36,800 3420 .44 .61 .77 10.1 34,500 3600 .45 .62 .79

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−036 � CB30M−31 − CB30U−31 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C470 1000 10.6 36,100 2770 .72 .86 .97 10.0 34,200 2970 .74 .88 .99 9.5 32,300 3160 .76 .90 1.00 8.9 30,200 3320 .78 .93 1.00

565 1200 10.9 37,300 2810 .76 .91 1.00 10.3 35,300 3020 .78 .93 1.00 9.8 33,400 3210 .80 .96 1.00 9.2 31,300 3380 .83 .98 1.00

660 1400 11.2 38,300 2840 .80 .96 1.00 10.6 36,300 3060 .82 .98 1.00 10.1 34,400 3260 .85 1.00 1.00 9.5 32,500 3450 .88 1.00 1.00

470 1000 11.3 38,600 2850 .57 .69 .82 10.7 36,600 3070 .57 .71 .84 10.1 34,500 3260 .58 .73 .87 9.5 32,300 3440 .60 .75 .90

565 1200 11.6 39,700 2890 .59 .74 .88 11.0 37,500 3110 .60 .76 .90 10.3 35,300 3310 .61 .78 .93 9.7 33,100 3480 .63 .81 .96

660 1400 11.9 40,500 2920 .61 .78 .93 11.2 38,300 3140 .63 .80 .95 10.6 36,000 3340 .64 .83 .98 9.9 33,700 3520 .66 .86 1.00

470 1000 12.1 41,300 2950 .43 .55 .67 11.5 39,200 3170 .43 .56 .68 10.8 37,000 3380 .43 .57 .70 10.1 34,600 3570 .44 .58 .73

565 1200 12.4 42,400 2980 .43 .57 .71 11.8 40,200 3210 .44 .58 .73 11.1 37,800 3420 .44 .60 .75 10.4 35,400 3610 .45 .62 .78

660 1400 12.7 43,200 3010 .44 .60 .75 12.0 40,900 3240 .45 .61 .78 11.3 38,500 3450 .45 .63 .80 10.6 36,000 3640 .46 .65 .83

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−036 � CB29M−46 − CB28UH−042 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C470 1000 10.6 36,300 2880 .72 .86 .97 10.1 34,400 3090 .74 .88 .99 9.5 32,400 3290 .75 .90 1.00 8.9 30,300 3460 .78 .93 1.00

565 1200 11.0 37,500 2930 .76 .91 1.00 10.4 35,500 3150 .78 .93 1.00 9.8 33,500 3350 .80 .96 1.00 9.2 31,500 3530 .83 .99 1.00

660 1400 11.3 38,500 2960 .80 .96 1.00 10.7 36,500 3190 .82 .98 1.00 10.1 34,600 3400 .85 1.00 1.00 9.6 32,600 3590 .88 1.00 1.00

470 1000 11.4 38,800 2970 .56 .69 .82 10.8 36,800 3200 .57 .71 .84 10.1 34,600 3400 .58 .73 .87 9.5 32,400 3580 .60 .75 .90

565 1200 11.7 39,900 3010 .59 .74 .88 11.1 37,800 3240 .60 .75 .90 10.4 35,500 3450 .61 .78 .93 9.7 33,200 3630 .63 .80 .96

660 1400 12.0 40,800 3040 .61 .78 .93 11.3 38,500 3270 .63 .80 .95 10.6 36,200 3480 .64 .83 .98 9.9 33,900 3670 .66 .85 1.00

470 1000 12.2 41,600 3070 .42 .55 .67 11.5 39,400 3310 .43 .56 .68 10.9 37,200 3530 .43 .57 .70 10.2 34,800 3720 .44 .58 .72

565 1200 12.5 42,700 3110 .43 .57 .71 11.8 40,400 3350 .44 .58 .73 11.2 38,100 3570 .44 .60 .75 10.4 35,600 3770 .45 .61 .78

660 1400 12.7 43,500 3140 .44 .60 .75 12.0 41,100 3380 .45 .61 .78 11.3 38,700 3610 .45 .63 .80 10.6 36,200 3800 .46 .65 .83

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−036 � CB30M−41 − CB30U−41/46 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

HS29 / Page 37

Page 38: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 3 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C470 1000 10.6 36,100 2750 .72 .86 .97 10.0 34,200 2950 .74 .88 .99 9.5 32,300 3140 .75 .90 1.00 8.9 30,200 3300 .78 .93 1.00

565 1200 11.0 37,400 2790 .76 .91 1.00 10.4 35,400 3000 .78 .93 1.00 9.8 33,400 3190 .80 .96 1.00 9.2 31,300 3360 .83 .99 1.00

660 1400 11.3 38,400 2830 .80 .96 1.00 10.7 36,400 3040 .82 .98 1.00 10.1 34,400 3240 .85 1.00 1.00 9.5 32,500 3430 .88 1.00 1.00

470 1000 11.3 38,700 2840 .56 .69 .82 10.7 36,600 3050 .57 .71 .84 10.1 34,500 3250 .58 .73 .87 9.5 32,300 3420 .60 .75 .90

565 1200 11.7 39,800 2870 .59 .74 .88 11.0 37,600 3090 .60 .75 .90 10.4 35,400 3290 .61 .78 .93 9.7 33,100 3460 .63 .80 .96

660 1400 11.9 40,600 2900 .61 .78 .93 11.3 38,400 3120 .63 .80 .95 10.6 36,100 3320 .64 .83 .98 9.9 33,800 3500 .66 .85 1.00

470 1000 12.1 41,400 2930 .42 .55 .67 11.5 39,300 3160 .43 .56 .68 10.8 37,000 3370 .43 .57 .70 10.2 34,700 3550 .44 .58 .72

565 1200 12.5 42,500 2970 .43 .57 .71 11.8 40,200 3200 .44 .58 .73 11.1 37,900 3410 .44 .60 .75 10.4 35,400 3600 .45 .61 .78

660 1400 12.7 43,300 3000 .44 .60 .75 12.0 41,000 3230 .45 .61 .78 11.3 38,500 3440 .45 .63 .80 10.6 36,000 3630 .46 .65 .83

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−036 � CB30M−46 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C535 1135 10.7 36,600 2770 .75 .90 1.00 10.1 34,600 2980 .77 .92 1.00 9.6 32,700 3170 .79 .95 1.00 9.0 30,700 3340 .82 .97 1.00

600 1275 10.9 37,300 2800 .78 .93 1.00 10.3 35,300 3000 .80 .95 1.00 9.8 33,300 3200 .82 .98 1.00 9.2 31,300 3370 .85 1.00 1.00

660 1400 11.1 37,900 2820 .80 .96 1.00 10.5 35,900 3030 .82 .98 1.00 10.0 34,000 3230 .85 1.00 1.00 9.4 32,000 3420 .88 1.00 1.00

535 1135 11.4 39,000 2860 .58 .72 .86 10.8 36,900 3070 .59 .74 .89 10.2 34,700 3270 .61 .77 .91 9.5 32,500 3440 .62 .79 .94

600 1275 11.6 39,600 2870 .60 .75 .90 11.0 37,400 3090 .61 .77 .92 10.3 35,200 3290 .62 .80 .95 9.6 32,900 3460 .64 .82 .98

660 1400 11.8 40,100 2890 .61 .78 .93 11.1 37,900 3110 .63 .80 .95 10.4 35,600 3310 .64 .83 .98 9.8 33,300 3490 .66 .85 1.00

535 1135 12.2 41,700 2950 .43 .56 .70 11.6 39,500 3180 .43 .58 .72 10.9 37,200 3390 .44 .59 .74 10.2 34,800 3570 .44 .61 .77

600 1275 12.4 42,300 2970 .44 .58 .73 11.7 40,000 3200 .44 .59 .75 11.0 37,700 3410 .45 .61 .77 10.3 35,200 3590 .45 .63 .80

660 1400 12.5 42,800 2980 .44 .60 .75 11.8 40,400 3210 .45 .61 .78 11.1 38,000 3430 .45 .63 .80 10.4 35,500 3610 .46 .65 .83

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−036 � CB31MV−41 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C470 1000 10.7 36,600 2750 .72 .85 .97 10.1 34,600 2960 .73 .87 .99 9.5 32,500 3140 .75 .90 1.00 8.9 30,400 3310 .78 .93 1.00

565 1200 11.1 37,800 2800 .76 .91 1.00 10.5 35,800 3010 .78 .93 1.00 9.9 33,700 3200 .80 .96 1.00 9.3 31,600 3370 .83 .99 1.00

660 1400 11.4 38,900 2840 .80 .96 1.00 10.8 36,800 3050 .82 .98 1.00 10.2 34,800 3250 .85 1.00 1.00 9.6 32,800 3440 .88 1.00 1.00

470 1000 11.5 39,200 2850 .56 .69 .82 10.9 37,100 3060 .57 .71 .84 10.2 34,900 3260 .58 .72 .86 9.6 32,600 3430 .59 .75 .89

565 1200 11.8 40,400 2890 .59 .73 .87 11.2 38,200 3110 .60 .75 .90 10.5 35,800 3310 .61 .78 .93 9.8 33,400 3480 .63 .80 .96

660 1400 12.1 41,300 2920 .61 .77 .93 11.4 39,000 3140 .62 .80 .95 10.7 36,600 3340 .64 .82 .98 10.0 34,100 3520 .66 .86 1.00

470 1000 12.3 42,000 2950 .42 .54 .66 11.7 39,800 3170 .43 .55 .68 11.0 37,500 3380 .43 .56 .70 10.3 35,000 3570 .43 .58 .72

565 1200 12.7 43,200 2990 .43 .57 .71 12.0 40,900 3220 .44 .58 .73 11.3 38,400 3430 .44 .60 .75 10.5 35,800 3620 .45 .61 .78

660 1400 12.9 44,100 3020 .44 .60 .75 12.2 41,600 3250 .45 .61 .77 11.5 39,100 3460 .45 .63 .80 10.7 36,500 3650 .46 .65 .83

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−036 � CB30M−51 − CB30U−51 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

570 1205 11.1 37,800 2800 .76 .91 1.00 10.5 35,800 3010 .78 .93 1.00 9.9 33,700 3200 .80 .96 1.00 9.3 31,600 3370 .83 .99 1.00

650 1375 11.4 38,800 2830 .79 .95 1.00 10.8 36,700 3050 .82 .98 1.00 10.1 34,600 3250 .84 1.00 1.00 9.6 32,600 3430 .87 1.00 1.00

570 1205 11.8 40,400 2890 .59 .73 .87 11.2 38,100 3110 .60 .75 .90 10.5 35,800 3310 .61 .78 .93 9.8 33,400 3480 .63 .80 .96

650 1375 12.1 41,200 2910 .61 .77 .92 11.4 38,800 3140 .62 .79 .95 10.7 36,500 3340 .64 .82 .98 10.0 34,000 3510 .66 .85 1.00

570 1205 12.7 43,200 2990 .43 .57 .71 12.0 40,800 3220 .44 .58 .73 11.3 38,400 3430 .44 .60 .75 10.5 35,800 3620 .45 .61 .78

650 1375 12.9 44,000 3010 .44 .59 .74 12.2 41,500 3250 .45 .61 .77 11.4 39,000 3460 .45 .62 .79 10.7 36,400 3650 .46 .64 .83

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−036 � CB31MV−51 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

HS29 / Page 38

Page 39: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 3 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C470 1000 10.4 35,400 2820 .72 .85 .97 9.8 33,500 3030 .73 .88 .99 9.3 31,600 3210 .75 .90 1.00 8.7 29,600 3380 .78 .93 1.00

565 1200 10.7 36,600 2860 .76 .91 1.00 10.2 34,700 3080 .78 .93 1.00 9.6 32,700 3270 .80 .96 1.00 9.0 30,700 3450 .83 .98 1.00

660 1400 11.0 37,600 2900 .80 .95 1.00 10.5 35,700 3120 .82 .98 1.00 9.9 33,800 3320 .85 .99 1.00 9.3 31,900 3510 .88 1.00 1.00

470 1000 11.1 37,800 2910 .56 .69 .82 10.5 35,900 3120 .57 .71 .84 9.9 33,800 3330 .58 .73 .86 9.3 31,700 3500 .60 .75 .89

565 1200 11.4 39,000 2950 .59 .73 .87 10.8 36,900 3170 .60 .75 .90 10.2 34,700 3370 .61 .78 .93 9.5 32,500 3550 .63 .80 .95

660 1400 11.7 39,800 2970 .61 .78 .92 11.0 37,600 3200 .62 .80 .95 10.4 35,400 3410 .64 .82 .97 9.7 33,100 3590 .66 .85 1.00

470 1000 11.9 40,500 3000 .42 .54 .67 11.3 38,500 3230 .43 .55 .68 10.6 36,300 3450 .43 .57 .70 10.0 34,000 3640 .44 .58 .72

565 1200 12.2 41,700 3040 .43 .57 .71 11.6 39,500 3280 .44 .58 .73 10.9 37,200 3490 .44 .60 .75 10.2 34,800 3680 .45 .61 .78

660 1400 12.5 42,500 3070 .44 .60 .75 11.8 40,200 3310 .45 .61 .77 11.1 37,800 3530 .45 .63 .80 10.4 35,400 3720 .46 .65 .83

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�036 � CVP10�41/EC10Q3 � CVP10�46/EC10Q4 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

RATINGS − 1 AND 3 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

Outdoor Air Temperature Entering Outdoor Coil

E t iTotal 85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)

EnteringWet BulbTempera�

TotalAir

Volume TotalCooling Comp

M t

Sensible To TotalRatio (S/T)

TotalCooling Comp

M t

Sensible To TotalRatio (S/T)

TotalCooling Comp

M t

Sensible To TotalRatio (S/T)

TotalCooling Comp

M t

Sensible To TotalRatio (S/T)

Tempera�ture

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

HS29−042 − C23−41 COOLING CAPACITY − RFC or TXV Systems

63�F1250 590 39.2 11.5 3.19 .73 .88 .98 38.0 11.1 3.56 .74 .89 .99 36.6 10.7 3.98 .76 .90 1.00 35.1 10.3 4.47 .77 .92 1.00

63�F(17�C)

1400 660 39.9 11.7 3.21 .76 .90 1.00 38.6 11.3 3.58 .77 .92 1.00 37.3 10.9 4.00 .78 .93 1.00 35.8 10.5 4.49 .80 .95 1.00(17�C)

1550 730 40.5 11.9 3.22 .78 .93 1.00 39.2 11.5 3.59 .80 .95 1.00 37.8 11.1 4.01 .81 .96 1.00 36.4 10.7 4.50 .83 .98 1.00

67�F1250 590 41.6 12.2 3.23 .57 .71 .84 40.2 11.8 3.61 .58 .72 .86 38.7 11.3 4.03 .59 .73 .87 37.1 10.9 4.52 .59 .75 .89

67�F(19�C)

1400 660 42.1 12.3 3.25 .59 .74 .88 40.7 11.9 3.62 .59 .75 .89 39.3 11.5 4.04 .60 .76 .91 37.7 11.0 4.53 .61 .78 .92(19�C)

1550 730 42.6 12.5 3.26 .60 .76 .91 41.2 12.1 3.63 .61 .77 .92 39.7 11.6 4.05 .62 .79 .94 38.1 11.2 4.54 .63 .81 .95

71�F1250 590 44.2 13.0 3.29 .43 .56 .69 42.7 12.5 3.66 .43 .56 .70 41.2 12.1 4.09 .43 .57 .71 39.5 11.6 4.58 .44 .58 .72

71�F(22�C)

1400 660 44.7 13.1 3.30 .43 .57 .71 43.3 12.7 3.67 .44 .58 .72 41.7 12.2 4.10 .44 .59 .74 40.0 11.7 4.59 .44 .60 .76(22�C)

1550 730 45.2 13.2 3.31 .44 .59 .74 43.7 12.8 3.68 .44 .60 .75 42.1 12.3 4.11 .44 .61 .77 40.4 11.8 4.60 .45 .62 .78

HS29−042 − C33−42B − C23−46 COOLING CAPACITY − RFC or TXV Systems

63�F1250 590 40.1 11.8 3.23 .73 .87 .98 38.8 11.4 3.60 .74 .88 .99 37.4 11.0 4.03 .75 .90 1.00 35.8 10.5 4.51 .77 .92 1.00

63�F(17�C)

1400 660 40.8 12.0 3.24 .75 .90 1.00 39.5 11.6 3.62 .77 .91 1.00 38.0 11.1 4.04 .78 .93 1.00 36.5 10.7 4.53 .80 .95 1.00(17�C)

1550 730 41.4 12.1 3.26 .78 .93 1.00 40.1 11.8 3.63 .79 .94 1.00 38.6 11.3 4.06 .81 .96 1.00 37.1 10.9 4.55 .82 .97 1.00

67�F1250 590 42.6 12.5 3.28 .57 .70 .84 41.2 12.1 3.65 .58 .71 .85 39.6 11.6 4.08 .58 .73 .87 38.0 11.1 4.57 .59 .74 .89

67�F(19�C)

1400 660 43.2 12.7 3.29 .59 .73 .87 41.7 12.2 3.66 .59 .74 .89 40.1 11.8 4.09 .60 .76 .90 38.5 11.3 4.57 .61 .77 .92(19�C)

1550 730 43.7 12.8 3.30 .60 .76 .90 42.2 12.4 3.67 .61 .77 .92 40.6 11.9 4.10 .62 .78 .93 38.9 11.4 4.59 .62 .80 .95

71�F1250 590 45.3 13.3 3.33 .43 .55 .68 43.8 12.8 3.71 .43 .56 .69 42.1 12.3 4.14 .43 .57 .71 40.4 11.8 4.63 .43 .58 .72

71�F(22�C)

1400 660 45.9 13.5 3.34 .43 .57 .71 44.3 13.0 3.72 .44 .58 .72 42.7 12.5 4.15 .44 .59 .73 40.9 12.0 4.64 .44 .60 .75(22�C)

1550 730 46.4 13.6 3.35 .44 .59 .73 44.8 13.1 3.73 .44 .59 .75 43.1 12.6 4.16 .44 .60 .76 41.3 12.1 4.66 .45 .62 .78

HS29−042 − C26−41 TXV Systems Only − CR26−36W RFC or TXV Systems COOLING CAPACITY

63�F1000 470 39.1 11.5 3.19 .69 .82 .92 37.9 11.1 3.56 .70 .82 .94 36.4 10.7 3.98 .71 .84 .96 34.9 10.2 4.46 .72 .86 .97

63�F(17�C)

1200 565 40.4 11.8 3.22 .72 .86 .98 39.1 11.5 3.59 .74 .87 .99 37.6 11.0 4.01 .75 .89 .99 36.0 10.6 4.49 .76 .91 1.00(17�C)

1400 660 41.5 12.2 3.24 .76 .90 1.00 40.0 11.7 3.61 .77 .92 1.00 38.5 11.3 4.03 .79 .94 1.00 36.9 10.8 4.51 .80 .96 1.00

67�F1000 470 41.8 12.3 3.25 .55 .67 .78 40.4 11.8 3.62 .55 .67 .79 38.8 11.4 4.04 .56 .69 .80 37.2 10.9 4.51 .56 .69 .82

67�F(19�C)

1200 565 43.0 12.6 3.27 .57 .70 .83 41.5 12.2 3.64 .57 .71 .84 39.9 11.7 4.06 .58 .72 .86 38.2 11.2 4.55 .59 .74 .88(19�C)

1400 660 43.9 12.9 3.29 .59 .73 .88 42.3 12.4 3.66 .60 .75 .89 40.7 11.9 4.09 .60 .76 .91 38.9 11.4 4.57 .61 .78 .93

71�F1000 470 44.5 13.0 3.31 .42 .53 .64 43.0 12.6 3.68 .42 .53 .65 41.4 12.1 4.10 .43 .54 .66 39.7 11.6 4.58 .43 .55 .67

71�F(22�C)

1200 565 45.8 13.4 3.33 .43 .55 .67 44.2 13.0 3.71 .43 .56 .69 42.5 12.5 4.13 .43 .56 .70 40.7 11.9 4.61 .43 .57 .71(22�C)

1400 660 46.7 13.7 3.35 .43 .57 .71 45.0 13.2 3.73 .44 .58 .72 43.3 12.7 4.15 .44 .59 .74 41.4 12.1 4.64 .44 .60 .76

HS29−042 − C33−44C − C26−46 COOLING CAPACITY − TXV Systems Only

63�F1000 470 40.1 11.8 3.24 .69 .81 .93 38.7 11.3 3.61 .70 .83 .94 37.3 10.9 4.03 .71 .84 .96 35.7 10.5 4.52 .72 .86 .98

63�F(17�C)

1200 565 41.5 12.2 3.27 .73 .86 .98 40.0 11.7 3.65 .74 .88 .99 38.5 11.3 4.07 .75 .89 1.00 36.9 10.8 4.55 .77 .91 1.00(17�C)

1400 660 42.6 12.5 3.30 .76 .91 1.00 41.1 12.0 3.67 .78 .92 1.00 39.5 11.6 4.09 .79 .94 1.00 37.9 11.1 4.58 .80 .96 1.00

67�F1000 470 42.8 12.5 3.30 .55 .67 .78 41.3 12.1 3.67 .55 .67 .79 39.7 11.6 4.09 .56 .69 .81 38.0 11.1 4.59 .57 .69 .82

67�F(19�C)

1200 565 44.1 12.9 3.32 .57 .70 .83 42.5 12.5 3.70 .57 .71 .84 40.8 12.0 4.13 .58 .73 .86 39.1 11.5 4.61 .59 .74 .88(19�C)

1400 660 45.0 13.2 3.35 .59 .74 .88 43.4 12.7 3.73 .60 .75 .89 41.7 12.2 4.15 .60 .77 .91 39.9 11.7 4.64 .62 .78 .93

71�F1000 470 45.6 13.4 3.36 .42 .53 .64 44.1 12.9 3.74 .42 .54 .65 42.4 12.4 4.17 .42 .54 .66 40.6 11.9 4.66 .43 .55 .67

71�F(22�C)

1200 565 46.9 13.7 3.39 .43 .55 .68 45.3 13.3 3.77 .43 .56 .69 43.5 12.7 4.20 .43 .57 .70 41.7 12.2 4.69 .43 .58 .71(22�C)

1400 660 47.9 14.0 3.41 .43 .57 .72 46.2 13.5 3.79 .44 .58 .73 44.4 13.0 4.22 .44 .59 .74 42.4 12.4 4.71 .44 .60 .76

HS29−042 − C33−48B/C − C23−51 COOLING CAPACITY − RFC or TXV Systems

63�F1250 590 42.0 12.3 3.27 .73 .87 .98 40.5 11.9 3.64 .74 .88 .99 39.0 11.4 4.07 .75 .90 1.00 37.4 11.0 4.55 .77 .91 1.00

63�F(17�C)

1400 660 42.8 12.5 3.28 .76 .90 1.00 41.3 12.1 3.66 .77 .92 1.00 39.7 11.6 4.08 .78 .93 1.00 38.1 11.2 4.56 .80 .95 1.00(17�C)

1550 730 43.5 12.7 3.30 .78 .93 1.00 42.0 12.3 3.67 .79 .95 1.00 40.4 11.8 4.09 .81 .96 1.00 38.8 11.4 4.58 .82 .98 1.00

67�F1250 590 44.6 13.1 3.32 .57 .70 .83 43.1 12.6 3.70 .58 .71 .85 41.4 12.1 4.12 .58 .73 .87 39.6 11.6 4.61 .59 .74 .88

67�F(19�C)

1400 660 45.3 13.3 3.34 .58 .73 .87 43.7 12.8 3.71 .59 .74 .88 42.0 12.3 4.14 .60 .76 .90 40.2 11.8 4.62 .61 .77 .92(19�C)

1550 730 45.9 13.5 3.35 .60 .76 .90 44.3 13.0 3.73 .61 .77 .92 42.5 12.5 4.16 .62 .79 .93 40.7 11.9 4.64 .63 .80 .95

71�F1250 590 47.5 13.9 3.38 .43 .55 .68 45.9 13.5 3.76 .43 .56 .69 44.1 12.9 4.19 .43 .57 .70 42.2 12.4 4.68 .43 .58 .72

71�F(22�C)

1400 660 48.2 14.1 3.40 .43 .57 .71 46.5 13.6 3.78 .43 .58 .72 44.7 13.1 4.21 .44 .59 .73 42.8 12.5 4.70 .44 .60 .75(22�C)

1550 730 48.8 14.3 3.41 .44 .59 .73 47.1 13.8 3.79 .44 .59 .75 45.2 13.2 4.22 .44 .60 .76 43.3 12.7 4.71 .45 .61 .78

HS29 / Page 39

Page 40: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 1 AND 3 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

Outdoor Air Temperature Entering Outdoor Coil

Total85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)

EnteringWet BulbTempera�

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Tempera�ture

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

HS29−042 − C33−50/60C −C26−51/65 − C33−60D − C23−51/65 − CR26−60 −CH33−60D−F −CH23−65 COOLING CAPACITY TXV Systems Only

63�F1000 470 41.0 12.0 3.19 .69 .81 .92 39.6 11.6 3.55 .70 .82 .94 38.0 11.1 3.97 .71 .84 .96 36.4 10.7 4.44 .72 .85 .98

63�F(17�C)

1200 565 42.4 12.4 3.22 .72 .86 .98 40.9 12.0 3.59 .73 .88 .99 39.4 11.5 4.00 .74 .89 1.00 37.6 11.0 4.48 .76 .91 1.00(17�C)

1400 660 43.6 12.8 3.24 .76 .91 1.00 42.0 12.3 3.61 .77 .93 1.00 40.4 11.8 4.03 .79 .94 1.00 38.7 11.3 4.51 .80 .96 1.00

67�F1000 470 43.8 12.8 3.25 .55 .66 .78 42.2 12.4 3.62 .55 .67 .79 40.6 11.9 4.03 .56 .68 .80 38.9 11.4 4.51 .56 .69 .82

67�F(19�C)

1200 565 45.1 13.2 3.28 .57 .70 .83 43.5 12.7 3.65 .57 .71 .84 41.8 12.3 4.06 .58 .72 .86 40.0 11.7 4.54 .59 .74 .88(19�C)

1400 660 46.2 13.5 3.30 .59 .74 .88 44.5 13.0 3.67 .60 .75 .89 42.7 12.5 4.09 .61 .76 .91 40.8 12.0 4.57 .61 .78 .93

71�F1000 470 46.7 13.7 3.31 .42 .53 .64 45.1 13.2 3.68 .42 .53 .65 43.4 12.7 4.11 .42 .54 .65 41.5 12.2 4.58 .42 .55 .67

71�F(22�C)

1200 565 48.1 14.1 3.35 .43 .55 .67 46.4 13.6 3.72 .43 .56 .68 44.6 13.1 4.14 .43 .56 .70 42.6 12.5 4.62 .43 .57 .71(22�C)

1400 660 49.2 14.4 3.37 .43 .57 .71 47.4 13.9 3.74 .44 .58 .73 45.4 13.3 4.17 .44 .59 .74 43.4 12.7 4.64 .44 .60 .76

HS29−042 � C33−44C−2 with G60UHV−60C−090 COOLING CAPACITY − TXV Systems Only

63�F1180 555 44.0 12.9 3.32 .71 .85 .96 42.5 12.5 3.70 .72 .86 .98 40.9 12.0 4.14 .74 .88 .99 39.2 11.5 4.64 .75 .90 1.00

63�F(17�C)

1330 630 44.9 13.2 3.34 .74 .88 .99 43.4 12.7 3.72 .75 .89 1.00 41.7 12.2 4.16 .76 .91 1.00 40.0 11.7 4.66 .78 .93 1.00(17�C)

1480 700 45.7 13.4 3.36 .76 .91 1.00 44.1 12.9 3.74 .78 .93 1.00 42.5 12.5 4.18 .79 .94 1.00 40.7 11.9 4.67 .81 .96 1.00

67�F1180 555 46.9 13.7 3.38 .56 .69 .82 45.3 13.3 3.76 .57 .70 .83 43.6 12.8 4.19 .57 .71 .84 41.7 12.2 4.69 .58 .72 .86

67�F(19�C)

1330 630 47.7 14.0 3.40 .58 .71 .85 46.0 13.5 3.78 .58 .73 .86 44.3 13.0 4.21 .59 .74 .88 42.3 12.4 4.72 .60 .75 .90(19�C)

1480 700 48.4 14.2 3.41 .59 .74 .88 46.7 13.7 3.79 .60 .75 .90 44.8 13.1 4.23 .60 .77 .91 42.9 12.6 4.73 .62 .78 .94

71�F1180 555 49.9 14.6 3.44 .42 .55 .66 48.2 14.1 3.83 .43 .55 .67 46.4 13.6 4.27 .43 .56 .69 44.5 13.0 4.77 .43 .56 .70

71�F(22�C)

1330 630 50.8 14.9 3.46 .43 .56 .69 49.0 14.4 3.85 .43 .57 .70 47.1 13.8 4.28 .43 .58 .72 45.1 13.2 4.79 .44 .58 .73(22�C)

1480 700 51.4 15.1 3.47 .43 .58 .72 49.6 14.5 3.86 .44 .58 .73 47.7 14.0 4.30 .44 .59 .74 45.7 13.4 4.80 .44 .60 .76

HS29−042 � C33−48C−2 with G60UHV−60C−090 COOLING CAPACITY − TXV Systems Only

63�F1180 555 44.0 12.9 3.32 .71 .85 .96 42.5 12.5 3.70 .72 .86 .98 40.9 12.0 4.14 .74 .88 .99 39.2 11.5 4.64 .75 .90 1.00

63�F(17�C)

1330 630 44.9 13.2 3.34 .74 .88 .99 43.4 12.7 3.72 .75 .89 1.00 41.7 12.2 4.16 .76 .91 1.00 40.0 11.7 4.66 .78 .93 1.00(17�C)

1480 700 45.7 13.4 3.36 .76 .91 1.00 44.1 12.9 3.74 .78 .93 1.00 42.5 12.5 4.18 .79 .94 1.00 40.7 11.9 4.67 .81 .96 1.00

67�F1180 555 46.9 13.7 3.38 .56 .69 .82 45.3 13.3 3.76 .57 .70 .83 43.6 12.8 4.19 .57 .71 .84 41.7 12.2 4.69 .58 .72 .86

67�F(19�C)

1330 630 47.7 14.0 3.40 .58 .71 .85 46.0 13.5 3.78 .58 .73 .86 44.3 13.0 4.21 .59 .74 .88 42.3 12.4 4.72 .60 .75 .90(19�C)

1480 700 48.4 14.2 3.41 .59 .74 .88 46.7 13.7 3.79 .60 .75 .90 44.8 13.1 4.23 .60 .77 .91 42.9 12.6 4.73 .62 .78 .94

71�F1180 555 49.9 14.6 3.44 .42 .55 .66 48.2 14.1 3.83 .43 .55 .67 46.4 13.6 4.27 .43 .56 .69 44.5 13.0 4.77 .43 .56 .70

71�F(22�C)

1330 630 50.8 14.9 3.46 .43 .56 .69 49.0 14.4 3.85 .43 .57 .70 47.1 13.8 4.28 .43 .58 .72 45.1 13.2 4.79 .44 .58 .73(22�C)

1480 700 51.4 15.1 3.47 .43 .58 .72 49.6 14.5 3.86 .44 .58 .73 47.7 14.0 4.30 .44 .59 .74 45.7 13.4 4.80 .44 .60 .76

HS29−042 � C33−50/60C−2 with G60UHV−60C−090 COOLING CAPACITY − TXV Systems Only

63�F1180 555 44.4 13.0 3.33 .71 .85 .96 42.9 12.6 3.71 .72 .86 .98 41.2 12.1 4.14 .73 .88 .99 39.5 11.6 4.64 .75 .89 1.00

63�F(17�C)

1330 630 45.3 13.3 3.35 .74 .88 .99 43.8 12.8 3.73 .75 .89 1.00 42.1 12.3 4.16 .76 .91 1.00 40.3 11.8 4.65 .78 .93 1.00(17�C)

1480 700 46.1 13.5 3.37 .76 .91 1.00 44.5 13.0 3.74 .78 .93 1.00 42.8 12.5 4.17 .79 .95 1.00 41.0 12.0 4.67 .81 .96 1.00

67�F1180 555 47.3 13.9 3.39 .56 .69 .81 45.7 13.4 3.77 .57 .70 .83 44.0 12.9 4.20 .57 .71 .84 42.0 12.3 4.70 .58 .72 .86

67�F(19�C)

1330 630 48.2 14.1 3.40 .57 .71 .85 46.5 13.6 3.79 .58 .72 .86 44.7 13.1 4.22 .59 .74 .88 42.7 12.5 4.72 .60 .75 .90(19�C)

1480 700 48.9 14.3 3.42 .59 .74 .88 47.1 13.8 3.80 .60 .75 .90 45.3 13.3 4.24 .60 .77 .91 43.3 12.7 4.73 .61 .78 .94

71�F1180 555 50.5 14.8 3.45 .42 .54 .66 48.7 14.3 3.84 .43 .55 .67 46.9 13.7 4.28 .43 .56 .68 44.8 13.1 4.78 .43 .56 .70

71�F(22�C)

1330 630 51.3 15.0 3.47 .43 .56 .69 49.5 14.5 3.86 .43 .57 .70 47.6 14.0 4.30 .43 .57 .71 45.5 13.3 4.79 .44 .58 .73(22�C)

1480 700 52.0 15.2 3.48 .43 .58 .72 50.2 14.7 3.88 .44 .58 .73 48.2 14.1 4.31 .44 .59 .74 46.1 13.5 4.81 .44 .60 .76

HS29−042 − CR26−36N COOLING CAPACITY − TXV Systems Only

63�F800 380 36.6 10.7 3.14 .66 .77 .87 35.4 10.4 3.50 .67 .78 .88 34.1 10.0 3.92 .67 .79 .90 32.7 9.6 4.40 .68 .80 .91

63�F(17�C)

900 425 37.5 11.0 3.16 .68 .79 .90 36.2 10.6 3.53 .69 .80 .91 34.9 10.2 3.94 .69 .81 .93 33.5 9.8 4.42 .70 .83 .94(17�C)

1000 470 38.2 11.2 3.18 .69 .82 .92 37.0 10.8 3.54 .70 .83 .94 35.6 10.4 3.96 .71 .84 .96 34.1 10.0 4.44 .72 .86 .97

67�F800 380 39.1 11.5 3.20 .53 .63 .73 37.8 11.1 3.56 .54 .64 .74 36.5 10.7 3.98 .54 .65 .75 35.0 10.3 4.46 .55 .66 .77

67�F(19�C)

900 425 40.0 11.7 3.21 .54 .65 .76 38.7 11.3 3.58 .55 .66 .77 37.3 10.9 4.00 .55 .66 .78 35.7 10.5 4.48 .56 .68 .79(19�C)

1000 470 40.8 12.0 3.23 .55 .67 .78 39.4 11.5 3.60 .56 .68 .79 38.0 11.1 4.02 .56 .68 .81 36.4 10.7 4.50 .57 .70 .82

71�F800 380 41.8 12.3 3.25 .42 .51 .61 40.4 11.8 3.62 .42 .52 .61 39.0 11.4 4.05 .42 .52 .62 37.4 11.0 4.53 .42 .52 .63

71�F(22�C)

900 425 42.7 12.5 3.27 .42 .52 .62 41.3 12.1 3.64 .42 .53 .63 39.8 11.7 4.06 .42 .53 .64 38.2 11.2 4.55 .42 .54 .65(22�C)

1000 470 43.5 12.7 3.29 .42 .53 .64 42.0 12.3 3.66 .42 .54 .65 40.5 11.9 4.09 .43 .54 .66 38.8 11.4 4.56 .43 .55 .67

HS29−042 − CR26−48 COOLING CAPACITY − RFC or TXV Systems

63�F1250 590 40.9 12.0 3.23 .72 .86 .98 39.5 11.6 3.60 .73 .88 .99 38.0 11.1 4.02 .74 .89 1.00 36.4 10.7 4.50 .76 .91 1.00

63�F(17�C)

1400 660 41.7 12.2 3.25 .75 .89 1.00 40.2 11.8 3.62 .76 .91 1.00 38.7 11.3 4.04 .77 .93 1.00 37.1 10.9 4.52 .79 .94 1.00(17�C)

1550 730 42.3 12.4 3.27 .77 .92 1.00 40.9 12.0 3.63 .78 .94 1.00 39.3 11.5 4.05 .80 .95 1.00 37.7 11.0 4.54 .82 .97 1.00

67�F1250 590 43.6 12.8 3.29 .57 .70 .83 42.1 12.3 3.66 .57 .71 .84 40.4 11.8 4.08 .58 .72 .86 38.7 11.3 4.57 .59 .73 .88

67�F(19�C)

1400 660 44.3 13.0 3.31 .58 .72 .86 42.7 12.5 3.67 .59 .74 .88 41.0 12.0 4.10 .60 .75 .90 39.2 11.5 4.58 .60 .77 .91(19�C)

1550 730 44.8 13.1 3.32 .59 .75 .89 43.2 12.7 3.69 .60 .76 .91 41.6 12.2 4.11 .61 .77 .93 39.7 11.6 4.59 .62 .79 .95

71�F1250 590 46.4 13.6 3.35 .43 .55 .67 44.8 13.1 3.73 .43 .56 .68 43.1 12.6 4.15 .43 .56 .70 41.2 12.1 4.64 .43 .57 .71

71�F(22�C)

1400 660 47.1 13.8 3.37 .43 .56 .70 45.5 13.3 3.74 .43 .57 .71 43.7 12.8 4.17 .43 .58 .73 41.8 12.3 4.65 .44 .59 .74(22�C)

1550 730 47.7 14.0 3.38 .44 .58 .72 46.0 13.5 3.76 .44 .59 .74 44.2 13.0 4.19 .44 .60 .75 42.3 12.4 4.67 .45 .61 .77

HS29−042 − CH33−42B−F − CH23−41 COOLING CAPACITY − RFC or TXV Systems

63�F1250 590 40.7 11.9 3.21 .74 .88 .99 39.3 11.5 3.58 .75 .90 1.00 37.9 11.1 4.00 .76 .91 1.00 36.3 10.6 4.48 .78 .93 1.00

63�F(17�C)

1400 660 41.5 12.2 3.23 .77 .91 1.00 40.1 11.8 3.60 .78 .93 1.00 38.6 11.3 4.02 .79 .95 1.00 37.0 10.8 4.49 .81 .96 1.00(17�C)

1550 730 42.2 12.4 3.24 .79 .94 1.00 40.7 11.9 3.61 .81 .96 1.00 39.3 11.5 4.03 .82 .97 1.00 37.7 11.0 4.51 .84 .99 1.00

67�F1250 590 43.1 12.6 3.26 .58 .71 .85 41.6 12.2 3.63 .58 .73 .86 40.0 11.7 4.05 .59 .74 .88 38.3 11.2 4.53 .60 .75 .90

67�F(19�C)

1400 660 43.8 12.8 3.27 .59 .74 .88 42.2 12.4 3.64 .60 .76 .90 40.6 11.9 4.06 .61 .77 .92 38.9 11.4 4.55 .62 .79 .93(19�C)

1550 730 44.3 13.0 3.28 .61 .77 .92 42.8 12.5 3.65 .62 .79 .93 41.1 12.0 4.08 .63 .80 .95 39.3 11.5 4.56 .64 .82 .97

71�F1250 590 45.9 13.5 3.32 .43 .56 .69 44.3 13.0 3.69 .43 .57 .70 42.6 12.5 4.12 .43 .58 .72 40.8 12.0 4.59 .44 .59 .73

71�F(22�C)

1400 660 46.5 13.6 3.33 .43 .58 .72 44.9 13.2 3.71 .44 .59 .73 43.2 12.7 4.13 .44 .59 .75 41.3 12.1 4.62 .45 .61 .77(22�C)

1550 730 47.0 13.8 3.34 .44 .60 .75 45.4 13.3 3.72 .44 .60 .76 43.6 12.8 4.14 .45 .61 .78 41.7 12.2 4.63 .45 .63 .80

HS29 / Page 40

Page 41: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 1 AND 3 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

Outdoor Air Temperature Entering Outdoor Coil

Total85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)

EnteringWet BulbTempera�

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Tempera�ture

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

HS29−042 − CH33−48C−F − CH23−51 COOLING CAPACITY − RFC or TXV Systems

63�F1250 590 41.6 12.2 3.24 .74 .88 .99 40.2 11.8 3.61 .75 .89 1.00 38.6 11.3 4.03 .76 .91 1.00 37.0 10.8 4.51 .78 .93 1.00

63�F(17�C)

1400 660 42.4 12.4 3.26 .76 .91 1.00 40.9 12.0 3.63 .78 .93 1.00 39.4 11.5 4.05 .79 .94 1.00 37.8 11.1 4.53 .81 .96 1.00(17�C)

1550 730 43.1 12.6 3.28 .79 .94 1.00 41.6 12.2 3.64 .81 .96 1.00 40.1 11.8 4.06 .82 .97 1.00 38.5 11.3 4.55 .84 .99 1.00

67�F1250 590 44.1 12.9 3.29 .57 .71 .84 42.5 12.5 3.66 .58 .72 .86 40.9 12.0 4.09 .59 .74 .88 39.1 11.5 4.57 .60 .75 .90

67�F(19�C)

1400 660 44.8 13.1 3.31 .59 .74 .88 43.2 12.7 3.68 .60 .75 .90 41.5 12.2 4.11 .61 .77 .91 39.7 11.6 4.59 .62 .79 .93(19�C)

1550 730 45.3 13.3 3.32 .61 .77 .91 43.7 12.8 3.70 .62 .78 .93 42.0 12.3 4.11 .62 .80 .95 40.2 11.8 4.60 .64 .82 .97

71�F1250 590 46.9 13.7 3.36 .43 .56 .69 45.3 13.3 3.73 .43 .57 .70 43.6 12.8 4.16 .43 .57 .71 41.7 12.2 4.64 .44 .58 .73

71�F(22�C)

1400 660 47.6 14.0 3.37 .43 .58 .72 45.9 13.5 3.74 .44 .58 .73 44.1 12.9 4.18 .44 .59 .75 42.2 12.4 4.66 .44 .60 .76(22�C)

1550 730 48.1 14.1 3.38 .44 .59 .75 46.4 13.6 3.76 .44 .60 .76 44.6 13.1 4.19 .45 .61 .78 42.7 12.5 4.67 .45 .63 .79

HS29−042 � CH33−48C−2F with G60UHV−60C−090 COOLING CAPACITY − TXV Systems Only

63�F1180 555 44.5 13.0 3.33 .71 .85 .96 42.9 12.6 3.71 .72 .86 .98 41.3 12.1 4.15 .74 .88 .99 39.5 11.6 4.64 .75 .90 1.00

63�F(17�C)

1330 630 45.4 13.3 3.35 .74 .88 .99 43.8 12.8 3.73 .75 .89 1.00 42.2 12.4 4.16 .76 .91 1.00 40.4 11.8 4.66 .78 .93 1.00(17�C)

1480 700 46.2 13.5 3.37 .76 .91 1.00 44.6 13.1 3.75 .77 .93 1.00 42.9 12.6 4.18 .79 .94 1.00 41.1 12.0 4.68 .81 .96 1.00

67�F1180 555 47.4 13.9 3.39 .56 .69 .81 45.8 13.4 3.77 .57 .70 .83 44.0 12.9 4.21 .57 .71 .84 42.1 12.3 4.71 .58 .72 .86

67�F(19�C)

1330 630 48.3 14.2 3.41 .58 .71 .85 46.5 13.6 3.79 .58 .72 .86 44.7 13.1 4.23 .59 .74 .88 42.8 12.5 4.72 .60 .75 .90(19�C)

1480 700 49.0 14.4 3.42 .59 .74 .88 47.2 13.8 3.81 .60 .75 .90 45.3 13.3 4.24 .60 .77 .91 43.4 12.7 4.74 .62 .78 .94

71�F1180 555 50.5 14.8 3.46 .42 .54 .66 48.8 14.3 3.84 .43 .55 .67 46.9 13.7 4.28 .43 .56 .68 44.9 13.2 4.78 .43 .56 .70

71�F(22�C)

1330 630 51.4 15.1 3.48 .43 .56 .69 49.6 14.5 3.86 .43 .56 .70 47.7 14.0 4.30 .43 .57 .71 45.6 13.4 4.80 .44 .58 .73(22�C)

1480 700 52.1 15.3 3.49 .43 .57 .71 50.2 14.7 3.88 .44 .58 .73 48.3 14.2 4.32 .44 .59 .74 46.2 13.5 4.82 .44 .60 .76

HS29−042 � CH33−50/60C−2F with G60UHV−60C−090 COOLING CAPACITY − TXV Systems Only

63�F1180 555 44.9 13.2 3.34 .71 .85 .96 43.3 12.7 3.72 .72 .86 .98 41.6 12.2 4.15 .73 .88 .99 39.8 11.7 4.64 .75 .89 1.00

63�F(17�C)

1330 630 45.8 13.4 3.37 .74 .88 .99 44.2 13.0 3.74 .75 .90 1.00 42.5 12.5 4.18 .76 .91 1.00 40.6 11.9 4.67 .78 .93 1.00(17�C)

1480 700 46.7 13.7 3.38 .76 .91 1.00 45.0 13.2 3.76 .78 .93 1.00 43.2 12.7 4.20 .79 .95 1.00 41.4 12.1 4.69 .81 .97 1.00

67�F1180 555 47.9 14.0 3.40 .56 .69 .81 46.2 13.5 3.79 .56 .70 .83 44.4 13.0 4.22 .57 .71 .84 42.5 12.5 4.72 .58 .72 .86

67�F(19�C)

1330 630 48.8 14.3 3.43 .57 .71 .85 47.0 13.8 3.81 .58 .73 .86 45.2 13.2 4.24 .59 .74 .88 43.1 12.6 4.74 .60 .75 .90(19�C)

1480 700 49.5 14.5 3.44 .59 .74 .88 47.7 14.0 3.82 .60 .75 .90 45.8 13.4 4.27 .61 .77 .92 43.7 12.8 4.76 .62 .78 .94

71�F1180 555 51.1 15.0 3.47 .42 .54 .66 49.3 14.4 3.86 .43 .55 .67 47.4 13.9 4.30 .43 .55 .68 45.3 13.3 4.80 .43 .57 .70

71�F(22�C)

1330 630 52.0 15.2 3.49 .43 .56 .69 50.1 14.7 3.88 .43 .56 .70 48.2 14.1 4.32 .43 .57 .71 46.0 13.5 4.83 .44 .58 .73(22�C)

1480 700 52.7 15.4 3.51 .43 .57 .72 50.8 14.9 3.90 .44 .58 .73 48.7 14.3 4.34 .44 .59 .74 46.6 13.7 4.84 .44 .60 .76

HS29−042 − CB29M−41 − CB28UH−036 COOLING CAPACITY − TXV Systems Only

63�F1250 590 39.5 11.6 3.22 .73 .88 .98 38.2 11.2 3.59 .75 .89 .99 36.8 10.8 4.02 .76 .90 1.00 35.3 10.3 4.51 .77 .92 1.00

63�F(17�C)

1350 635 40.0 11.7 3.23 .75 .90 1.00 38.7 11.3 3.60 .76 .91 1.00 37.3 10.9 4.03 .78 .92 1.00 35.8 10.5 4.52 .79 .94 1.00(17�C)

1450 685 40.4 11.8 3.24 .77 .92 1.00 39.1 11.5 3.61 .78 .93 1.00 37.7 11.0 4.04 .79 .95 1.00 36.2 10.6 4.53 .81 .96 1.00

67�F1250 590 41.9 12.3 3.27 .57 .71 .85 40.5 11.9 3.64 .58 .72 .86 39.0 11.4 4.07 .59 .73 .87 37.3 10.9 4.55 .60 .75 .89

67�F(19�C)

1350 635 42.3 12.4 3.27 .58 .73 .87 40.8 12.0 3.65 .59 .74 .88 39.3 11.5 4.07 .60 .76 .90 37.7 11.0 4.56 .61 .77 .92(19�C)

1450 685 42.6 12.5 3.28 .59 .75 .89 41.2 12.1 3.66 .60 .76 .90 39.7 11.6 4.08 .61 .77 .92 38.0 11.1 4.57 .62 .79 .94

71�F1250 590 44.5 13.0 3.32 .43 .56 .69 43.0 12.6 3.70 .43 .57 .70 41.4 12.1 4.13 .43 .57 .71 39.7 11.6 4.62 .44 .58 .73

71�F(22�C)

1350 635 44.9 13.2 3.33 .43 .57 .71 43.4 12.7 3.71 .43 .58 .72 41.8 12.3 4.14 .44 .58 .73 40.1 11.8 4.63 .44 .59 .75(22�C)

1450 685 45.3 13.3 3.33 .43 .58 .73 43.7 12.8 3.71 .44 .59 .74 42.1 12.3 4.14 .44 .60 .75 40.4 11.8 4.63 .45 .61 .77

HS29−042 − CB30M−41 COOLING CAPACITY − TXV Systems Only

63�F1050 495 39.2 11.5 3.15 .70 .82 .94 37.8 11.1 3.51 .71 .84 .95 36.4 10.7 3.92 .72 .85 .97 34.9 10.2 4.39 .73 .87 .98

63�F(17�C)

1250 590 40.4 11.8 3.18 .73 .87 .99 39.0 11.4 3.54 .74 .88 .99 37.5 11.0 3.95 .76 .90 1.00 35.9 10.5 4.42 .77 .92 1.00(17�C)

1450 685 41.4 12.1 3.20 .77 .92 1.00 40.0 11.7 3.56 .78 .93 1.00 38.5 11.3 3.97 .79 .95 1.00 36.8 10.8 4.45 .81 .97 1.00

67�F1050 495 41.8 12.3 3.21 .55 .67 .79 40.4 11.8 3.57 .56 .68 .80 38.8 11.4 3.98 .56 .69 .82 37.1 10.9 4.46 .57 .70 .84

67�F(19�C)

1250 590 42.9 12.6 3.23 .57 .71 .84 41.4 12.1 3.59 .58 .72 .85 39.8 11.7 4.01 .59 .73 .87 38.1 11.2 4.48 .59 .75 .89(19�C)

1450 685 43.8 12.8 3.25 .59 .74 .89 42.2 12.4 3.62 .60 .76 .90 40.6 11.9 4.03 .61 .77 .92 38.8 11.4 4.50 .62 .79 .94

71�F1050 495 44.6 13.1 3.27 .42 .53 .65 43.0 12.6 3.63 .42 .54 .66 41.4 12.1 4.05 .43 .55 .66 39.7 11.6 4.52 .43 .55 .68

71�F(22�C)

1250 590 45.7 13.4 3.29 .43 .56 .68 44.1 12.9 3.66 .43 .56 .69 42.4 12.4 4.08 .43 .57 .71 40.6 11.9 4.56 .43 .58 .72(22�C)

1450 685 46.6 13.7 3.31 .43 .58 .72 44.9 13.2 3.68 .44 .59 .73 43.1 12.6 4.10 .44 .59 .75 41.3 12.1 4.57 .44 .61 .77

HS29−042 − CB29M−46 − CB28UH−042 COOLING CAPACITY − TXV Systems Only

63�F1200 565 41.0 12.0 3.23 .73 .86 .97 39.6 11.6 3.60 .74 .87 .99 38.1 11.2 4.02 .75 .89 1.00 36.5 10.7 4.50 .76 .91 1.00

63�F(17�C)

1350 635 41.8 12.3 3.25 .75 .89 1.00 40.4 11.8 3.62 .76 .91 1.00 38.8 11.4 4.04 .78 .93 1.00 37.2 10.9 4.52 .79 .94 1.00(17�C)

1500 710 42.5 12.5 3.26 .78 .92 1.00 41.0 12.0 3.63 .79 .94 1.00 39.5 11.6 4.05 .81 .96 1.00 37.9 11.1 4.53 .82 .97 1.00

67�F1200 565 43.6 12.8 3.28 .57 .70 .83 42.0 12.3 3.65 .57 .71 .84 40.4 11.8 4.07 .58 .72 .86 38.7 11.3 4.56 .59 .74 .88

67�F(19�C)

1350 635 44.3 13.0 3.30 .58 .72 .86 42.7 12.5 3.67 .59 .74 .88 41.1 12.0 4.09 .60 .75 .90 39.3 11.5 4.58 .61 .77 .92(19�C)

1500 710 44.8 13.1 3.31 .60 .75 .90 43.3 12.7 3.68 .61 .76 .91 41.6 12.2 4.11 .61 .78 .93 39.8 11.7 4.58 .62 .80 .95

71�F1200 565 46.4 13.6 3.34 .43 .55 .67 44.8 13.1 3.72 .43 .56 .69 43.1 12.6 4.14 .43 .56 .70 41.3 12.1 4.63 .43 .57 .71

71�F(22�C)

1350 635 47.1 13.8 3.36 .43 .57 .70 45.4 13.3 3.74 .43 .57 .72 43.7 12.8 4.16 .44 .58 .73 41.8 12.3 4.65 .44 .59 .75(22�C)

1500 710 47.7 14.0 3.37 .44 .58 .73 46.0 13.5 3.75 .44 .59 .74 44.2 13.0 4.18 .44 .60 .76 42.3 12.4 4.66 .45 .61 .78

HS29−042 − CB29M−51 − CB28UH−048 COOLING CAPACITY − TXV Systems Only

63�F1200 565 41.3 12.1 3.23 .72 .86 .97 39.9 11.7 3.60 .74 .87 .99 38.4 11.3 4.02 .75 .89 1.00 36.8 10.8 4.49 .76 .91 1.00

63�F(17�C)

1350 635 42.1 12.3 3.25 .75 .90 1.00 40.7 11.9 3.62 .76 .91 1.00 39.1 11.5 4.04 .78 .93 1.00 37.5 11.0 4.51 .79 .94 1.00(17�C)

1500 710 42.9 12.6 3.27 .77 .93 1.00 41.4 12.1 3.63 .79 .94 1.00 39.8 11.7 4.05 .80 .96 1.00 38.2 11.2 4.54 .82 .97 1.00

67�F1200 565 43.9 12.9 3.29 .57 .70 .83 42.4 12.4 3.65 .57 .71 .84 40.8 12.0 4.08 .58 .72 .86 39.0 11.4 4.56 .59 .74 .88

67�F(19�C)

1350 635 44.7 13.1 3.30 .58 .72 .86 43.1 12.6 3.67 .59 .74 .88 41.4 12.1 4.10 .60 .75 .89 39.6 11.6 4.58 .61 .77 .92(19�C)

1500 710 45.3 13.3 3.31 .60 .75 .89 43.7 12.8 3.69 .61 .76 .91 42.0 12.3 4.11 .61 .78 .93 40.1 11.8 4.59 .62 .80 .95

71�F1200 565 46.8 13.7 3.35 .43 .55 .67 45.2 13.2 3.72 .43 .56 .68 43.4 12.7 4.15 .43 .56 .70 41.6 12.2 4.63 .43 .57 .71

71�F(22�C)

1350 635 47.6 14.0 3.37 .43 .57 .70 45.9 13.5 3.74 .43 .57 .71 44.1 12.9 4.17 .44 .58 .73 42.2 12.4 4.65 .44 .59 .74(22�C)

1500 710 48.1 14.1 3.38 .44 .58 .73 46.4 13.6 3.76 .44 .59 .74 44.6 13.1 4.18 .44 .60 .76 42.7 12.5 4.66 .45 .61 .78

HS29 / Page 41

Page 42: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 1 AND 3 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

Outdoor Air Temperature Entering Outdoor Coil

Total85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)

EnteringWet BulbTempera�

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Tempera�ture

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

HS29−042 − CB30M−46 − CB30U−41/46 COOLING CAPACITY − TXV Systems Only

63�F1250 590 41.2 12.1 3.17 .73 .87 .98 39.8 11.7 3.54 .74 .88 .99 38.3 11.2 3.95 .75 .90 1.00 36.7 10.8 4.41 .77 .92 1.00

63�F(17�C)

1400 660 42.0 12.3 3.19 .76 .90 1.00 40.5 11.9 3.56 .77 .92 1.00 39.0 11.4 3.96 .78 .94 1.00 37.4 11.0 4.43 .80 .95 1.00(17�C)

1550 730 42.7 12.5 3.21 .78 .93 1.00 41.2 12.1 3.57 .80 .95 1.00 39.7 11.6 3.98 .81 .96 1.00 38.0 11.1 4.45 .83 .98 1.00

67�F1250 590 43.8 12.8 3.23 .57 .71 .84 42.2 12.4 3.59 .58 .72 .85 40.6 11.9 4.01 .59 .73 .87 38.9 11.4 4.48 .60 .75 .89

67�F(19�C)

1400 660 44.5 13.0 3.24 .59 .73 .87 42.9 12.6 3.61 .59 .75 .89 41.2 12.1 4.02 .60 .76 .91 39.4 11.5 4.49 .61 .78 .93(19�C)

1550 730 45.0 13.2 3.26 .60 .76 .91 43.4 12.7 3.62 .61 .77 .92 41.7 12.2 4.03 .62 .79 .94 39.9 11.7 4.51 .63 .81 .96

71�F1250 590 46.6 13.7 3.29 .43 .56 .68 45.0 13.2 3.65 .43 .56 .69 43.3 12.7 4.08 .43 .57 .71 41.4 12.1 4.55 .43 .58 .72

71�F(22�C)

1400 660 47.3 13.9 3.30 .43 .57 .71 45.6 13.4 3.67 .44 .58 .72 43.9 12.9 4.09 .44 .59 .74 42.0 12.3 4.56 .44 .60 .75(22�C)

1550 730 47.9 14.0 3.31 .44 .59 .74 46.1 13.5 3.69 .44 .60 .75 44.3 13.0 4.10 .44 .61 .77 42.4 12.4 4.58 .45 .62 .79

HS29−042 − CB31MV−41 COOLING CAPACITY − TXV Systems Only

63�F1265 595 41.3 12.1 3.21 .73 .87 .99 39.8 11.7 3.58 .74 .89 1.00 38.3 11.2 4.00 .76 .91 1.00 36.7 10.8 4.47 .77 .92 1.00

63�F(17�C)

1400 660 41.9 12.3 3.23 .76 .90 1.00 40.5 11.9 3.60 .77 .92 1.00 39.0 11.4 4.01 .78 .94 1.00 37.3 10.9 4.49 .80 .96 1.00(17�C)

1545 730 42.6 12.5 3.25 .78 .93 1.00 41.1 12.0 3.61 .80 .95 1.00 39.6 11.6 4.03 .81 .96 1.00 37.9 11.1 4.50 .83 .98 1.00

67�F1265 595 43.8 12.8 3.27 .57 .71 .84 42.3 12.4 3.63 .58 .72 .86 40.6 11.9 4.06 .59 .73 .88 38.9 11.4 4.53 .60 .75 .90

67�F(19�C)

1400 660 44.4 13.0 3.28 .59 .73 .87 42.8 12.5 3.65 .59 .75 .89 41.2 12.1 4.07 .60 .76 .91 39.4 11.5 4.54 .61 .78 .93(19�C)

1545 730 45.0 13.2 3.29 .60 .76 .91 43.4 12.7 3.66 .61 .77 .92 41.7 12.2 4.08 .62 .79 .94 39.8 11.7 4.56 .63 .81 .96

71�F1265 595 46.7 13.7 3.33 .43 .56 .69 45.0 13.2 3.70 .43 .56 .70 43.3 12.7 4.13 .43 .57 .71 41.4 12.1 4.61 .43 .58 .73

71�F(22�C)

1400 660 47.3 13.9 3.34 .43 .57 .71 45.6 13.4 3.71 .43 .58 .72 43.8 12.8 4.14 .44 .59 .74 41.9 12.3 4.62 .44 .60 .76(22�C)

1545 730 47.8 14.0 3.35 .44 .59 .74 46.1 13.5 3.73 .44 .60 .75 44.3 13.0 4.15 .44 .61 .77 42.3 12.4 4.63 .45 .62 .79

HS29−042 − CB30M−51 − CB30U−51 COOLING CAPACITY − TXV Systems Only

63�F1200 565 41.8 12.3 3.26 .72 .86 .98 40.4 11.8 3.62 .73 .87 .99 38.8 11.4 4.04 .74 .89 1.00 37.1 10.9 4.52 .76 .91 1.00

63�F(17�C)

1400 660 43.0 12.6 3.28 .76 .90 1.00 41.4 12.1 3.65 .77 .92 1.00 39.8 11.7 4.07 .78 .94 1.00 38.0 11.1 4.55 .80 .96 1.00(17�C)

1600 755 43.9 12.9 3.30 .79 .95 1.00 42.3 12.4 3.67 .80 .96 1.00 40.7 11.9 4.10 .82 .98 1.00 39.0 11.4 4.58 .84 .99 1.00

67�F1200 565 44.6 13.1 3.32 .57 .70 .82 43.0 12.6 3.69 .57 .70 .84 41.3 12.1 4.11 .58 .72 .86 39.4 11.5 4.59 .59 .73 .87

67�F(19�C)

1400 660 45.6 13.4 3.34 .59 .73 .87 43.9 12.9 3.72 .59 .74 .89 42.2 12.4 4.13 .60 .76 .91 40.3 11.8 4.61 .61 .78 .93(19�C)

1600 755 46.4 13.6 3.36 .61 .77 .92 44.7 13.1 3.73 .62 .78 .93 42.9 12.6 4.15 .63 .80 .95 40.9 12.0 4.63 .64 .82 .98

71�F1200 565 47.6 14.0 3.38 .43 .55 .67 45.9 13.5 3.76 .43 .55 .68 44.0 12.9 4.18 .43 .56 .69 42.1 12.3 4.67 .43 .57 .71

71�F(22�C)

1400 660 48.6 14.2 3.41 .43 .57 .71 46.8 13.7 3.79 .44 .58 .72 44.9 13.2 4.21 .44 .59 .73 42.9 12.6 4.69 .44 .60 .75(22�C)

1600 755 49.4 14.5 3.43 .44 .59 .74 47.5 13.9 3.81 .44 .60 .76 45.6 13.4 4.23 .45 .61 .78 43.5 12.7 4.71 .45 .63 .80

HS29−042 − CB31MV−51 COOLING CAPACITY − TXV Systems Only

63�F1205 570 41.4 12.1 3.27 .72 .86 .98 39.9 11.7 3.64 .73 .87 .99 38.3 11.2 4.06 .74 .89 1.00 36.6 10.7 4.54 .76 .91 1.00

63�F(17�C)

1425 675 42.6 12.5 3.30 .76 .91 1.00 41.1 12.0 3.67 .77 .92 1.00 39.4 11.5 4.09 .79 .94 1.00 37.7 11.0 4.57 .81 .96 1.00(17�C)

1625 765 43.5 12.7 3.32 .80 .95 1.00 42.0 12.3 3.69 .81 .97 1.00 40.3 11.8 4.11 .83 .99 1.00 38.7 11.3 4.60 .84 1.00 1.00

67�F1205 570 44.1 12.9 3.33 .56 .70 .82 42.5 12.5 3.70 .57 .71 .84 40.8 12.0 4.13 .58 .72 .86 38.9 11.4 4.61 .59 .74 .88

67�F(19�C)

1425 675 45.2 13.2 3.36 .59 .73 .88 43.5 12.7 3.73 .60 .75 .89 41.7 12.2 4.15 .60 .76 .91 39.9 11.7 4.63 .62 .78 .94(19�C)

1625 765 45.9 13.5 3.37 .61 .77 .92 44.2 13.0 3.75 .62 .79 .94 42.4 12.4 4.17 .63 .80 .96 40.5 11.9 4.66 .64 .82 .98

71�F1205 570 47.0 13.8 3.40 .43 .55 .67 45.3 13.3 3.78 .43 .55 .68 43.6 12.8 4.20 .43 .56 .69 41.6 12.2 4.69 .43 .57 .71

71�F(22�C)

1425 675 48.1 14.1 3.43 .43 .57 .71 46.4 13.6 3.81 .44 .58 .72 44.5 13.0 4.23 .44 .59 .74 42.5 12.5 4.72 .44 .60 .76(22�C)

1625 765 48.9 14.3 3.44 .44 .60 .75 47.1 13.8 3.82 .44 .61 .76 45.1 13.2 4.25 .45 .62 .78 43.0 12.6 4.74 .45 .63 .80

HS29−042 − CVP10−46/EC10Q4 − CVP10−51/EC10Q4 COOLING CAPACITY − TXV Systems Only

63�F1200 565 40.0 11.7 3.18 .72 .86 .97 38.7 11.3 3.54 .73 .87 .98 37.2 10.9 3.95 .74 .89 .99 35.7 10.5 4.43 .76 .90 1.00

63�F(17�C)

1400 660 41.1 12.0 3.20 .76 .90 1.00 39.7 11.6 3.57 .77 .92 1.00 38.2 11.2 3.98 .78 .93 1.00 36.6 10.7 4.45 .80 .95 1.00(17�C)

1600 755 42.0 12.3 3.22 .79 .94 1.00 40.6 11.9 3.58 .81 .96 1.00 39.1 11.5 4.00 .82 .97 1.00 37.5 11.0 4.48 .84 .99 1.00

67�F1200 565 42.6 12.5 3.23 .57 .70 .82 41.1 12.0 3.60 .57 .71 .84 39.5 11.6 4.01 .58 .72 .85 37.8 11.1 4.49 .59 .74 .87

67�F(19�C)

1400 660 43.5 12.7 3.25 .59 .73 .87 42.0 12.3 3.62 .59 .75 .89 40.3 11.8 4.04 .60 .76 .91 38.6 11.3 4.51 .61 .78 .92(19�C)

1600 755 44.3 13.0 3.27 .61 .77 .92 42.7 12.5 3.64 .62 .78 .93 41.0 12.0 4.05 .62 .80 .95 39.2 11.5 4.53 .64 .82 .97

71�F1200 565 45.4 13.3 3.29 .43 .55 .67 43.8 12.8 3.66 .43 .55 .68 42.1 12.3 4.08 .43 .56 .70 40.3 11.8 4.56 .43 .57 .71

71�F(22�C)

1400 660 46.3 13.6 3.31 .43 .57 .71 44.7 13.1 3.68 .43 .58 .72 42.9 12.6 4.10 .44 .59 .74 41.1 12.0 4.58 .44 .60 .75(22�C)

1600 755 47.0 13.8 3.33 .44 .59 .75 45.4 13.3 3.70 .44 .60 .76 43.6 12.8 4.12 .45 .61 .78 41.7 12.2 4.60 .45 .62 .80

RATINGS − 1 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

Outdoor Air Temperature Entering Outdoor Coil

Total85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)

EnteringWet BulbTempera�

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Tempera�ture

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

HS29−048 � C26−41 COOLING CAPACITY − TXV Systems Only

63�F1100 520 43.1 12.6 3.33 .70 .82 .93 41.6 12.2 3.77 .70 .83 .95 39.9 11.7 4.27 .72 .85 .96 38.2 11.2 4.86 .73 .86 .98

63�F(17�C)

1300 615 44.4 13.0 3.36 .72 .86 .97 42.8 12.5 3.79 .74 .88 .99 41.1 12.0 4.30 .75 .89 1.00 39.3 11.5 4.89 .76 .91 1.00(17�C)

1500 710 45.5 13.3 3.38 .76 .90 1.00 43.8 12.8 3.81 .77 .92 1.00 42.1 12.3 4.32 .79 .93 1.00 40.2 11.8 4.92 .80 .96 1.00

67�F1100 520 46.0 13.5 3.38 .55 .67 .78 44.4 13.0 3.82 .56 .68 .80 42.6 12.5 4.33 .56 .69 .81 40.7 11.9 4.92 .57 .70 .83

67�F(19�C)

1300 615 47.2 13.8 3.40 .57 .70 .83 45.5 13.3 3.84 .57 .71 .84 43.6 12.8 4.35 .58 .72 .86 41.7 12.2 4.94 .59 .74 .88(19�C)

1500 710 48.1 14.1 3.42 .59 .73 .87 46.3 13.6 3.86 .59 .75 .89 44.4 13.0 4.37 .60 .76 .91 42.4 12.4 4.96 .61 .78 .93

71�F1100 520 49.1 14.4 3.43 .42 .53 .64 47.3 13.9 3.88 .42 .54 .65 45.4 13.3 4.39 .43 .54 .66 43.5 12.7 4.99 .43 .55 .67

71�F(22�C)

1300 615 50.3 14.7 3.45 .43 .55 .67 48.4 14.2 3.90 .43 .56 .69 46.5 13.6 4.42 .43 .57 .70 44.5 13.0 5.02 .43 .57 .71(22�C)

1500 710 51.2 15.0 3.47 .43 .57 .71 49.3 14.4 3.92 .43 .58 .72 47.3 13.9 4.44 .44 .59 .74 45.2 13.2 5.03 .44 .60 .75

HS29 / Page 42

Page 43: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 1 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

Outdoor Air Temperature Entering Outdoor Coil

Total85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)

EnteringWet BulbTempera�

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Tempera�ture

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

HS29−048 � C33−44C − C26−46 COOLING CAPACITY − TXV Systems Only

63�F1200 565 44.4 13.0 3.36 .71 .84 .96 42.7 12.5 3.79 .72 .86 .97 41.0 12.0 4.30 .73 .87 .99 39.2 11.5 4.89 .75 .89 1.00

63�F(17�C)

1400 660 45.6 13.4 3.38 .74 .89 .99 43.9 12.9 3.82 .76 .90 1.00 42.1 12.3 4.32 .77 .92 1.00 40.3 11.8 4.91 .79 .94 1.00(17�C)

1600 755 46.6 13.7 3.40 .78 .93 1.00 44.9 13.2 3.84 .79 .94 1.00 43.1 12.6 4.34 .81 .96 1.00 41.2 12.1 4.94 .83 .98 1.00

67�F1200 565 47.2 13.8 3.40 .56 .69 .81 45.5 13.3 3.84 .56 .69 .82 43.6 12.8 4.35 .57 .71 .84 41.7 12.2 4.94 .58 .72 .86

67�F(19�C)

1400 660 48.3 14.2 3.42 .58 .72 .86 46.5 13.6 3.86 .58 .73 .87 44.6 13.1 4.38 .60 .75 .89 42.6 12.5 4.98 .60 .76 .91(19�C)

1600 755 49.2 14.4 3.44 .60 .75 .90 47.3 13.9 3.88 .61 .77 .92 45.3 13.3 4.40 .62 .79 .93 43.3 12.7 4.99 .63 .80 .95

71�F1200 565 50.3 14.7 3.46 .43 .54 .66 48.5 14.2 3.91 .42 .55 .67 46.5 13.6 4.42 .43 .55 .68 44.5 13.0 5.02 .43 .56 .70

71�F(22�C)

1400 660 51.4 15.1 3.48 .43 .56 .69 49.5 14.5 3.93 .43 .57 .71 47.5 13.9 4.44 .44 .58 .72 45.4 13.3 5.05 .44 .59 .74(22�C)

1600 755 52.3 15.3 3.50 .44 .58 .73 50.3 14.7 3.94 .44 .59 .75 48.2 14.1 4.46 .44 .60 .76 46.0 13.5 5.06 .45 .62 .78

HS29−048 � C33−48B/C − C23−51 COOLING CAPACITY − RFC or TXV Systems

63�F1400 660 46.5 13.6 3.49 .74 .88 .99 44.8 13.1 3.94 .75 .89 1.00 43.0 12.6 4.46 .76 .91 1.00 41.1 12.0 5.08 .78 .93 1.00

63�F(17�C)

1600 755 47.5 13.9 3.50 .77 .92 1.00 45.8 13.4 3.96 .78 .93 1.00 43.9 12.9 4.49 .80 .95 1.00 42.1 12.3 5.10 .81 .97 1.00(17�C)

1800 850 48.4 14.2 3.52 .80 .95 1.00 46.6 13.7 3.98 .81 .97 1.00 44.9 13.2 4.50 .83 .98 1.00 43.0 12.6 5.12 .85 .99 1.00

67�F1400 660 49.4 14.5 3.53 .57 .71 .84 47.6 14.0 3.99 .58 .72 .86 45.6 13.4 4.52 .59 .74 .88 43.6 12.8 5.13 .60 .75 .90

67�F(19�C)

1600 755 50.2 14.7 3.55 .59 .75 .89 48.4 14.2 4.01 .60 .76 .90 46.4 13.6 4.53 .61 .77 .92 44.3 13.0 5.15 .62 .79 .94(19�C)

1800 850 51.0 14.9 3.56 .61 .77 .92 49.0 14.4 4.01 .62 .79 .94 47.0 13.8 4.55 .63 .81 .96 44.9 13.2 5.17 .64 .83 .98

71�F1400 660 52.6 15.4 3.59 .43 .56 .69 50.6 14.8 4.05 .43 .57 .70 48.6 14.2 4.59 .43 .57 .71 46.5 13.6 5.20 .44 .58 .73

71�F(22�C)

1600 755 53.4 15.6 3.60 .43 .58 .72 51.4 15.1 4.07 .44 .59 .74 49.3 14.4 4.60 .44 .60 .75 47.2 13.8 5.23 .44 .61 .77(22�C)

1800 850 54.1 15.9 3.62 .44 .60 .75 52.1 15.3 4.08 .45 .61 .77 49.9 14.6 4.61 .45 .62 .79 47.7 14.0 5.24 .45 .63 .81

HS29−048 � C33−50/60C − C26−51/65 COOLING CAPACITY − TXV Systems Only

63�F1400 660 46.6 13.7 3.38 .74 .88 .99 44.8 13.1 3.82 .76 .90 1.00 43.0 12.6 4.32 .77 .92 1.00 41.1 12.0 4.92 .78 .94 1.00

63�F(17�C)

1600 755 47.7 14.0 3.40 .77 .92 1.00 45.9 13.5 3.83 .79 .94 1.00 44.0 12.9 4.35 .80 .96 1.00 42.1 12.3 4.94 .82 .98 1.00(17�C)

1800 850 48.6 14.2 3.42 .81 .96 1.00 46.8 13.7 3.86 .82 .98 1.00 45.0 13.2 4.37 .84 .99 1.00 43.2 12.7 4.96 .86 1.00 1.00

67�F1400 660 49.5 14.5 3.43 .58 .72 .85 47.6 14.0 3.87 .59 .73 .87 45.6 13.4 4.38 .59 .74 .88 43.5 12.7 4.97 .60 .76 .91

67�F(19�C)

1600 755 50.4 14.8 3.45 .60 .75 .89 48.4 14.2 3.89 .61 .77 .91 46.4 13.6 4.41 .62 .78 .93 44.2 13.0 5.01 .63 .80 .95(19�C)

1800 850 51.1 15.0 3.46 .62 .79 .93 49.1 14.4 3.91 .63 .80 .95 47.1 13.8 4.42 .64 .82 .97 44.9 13.2 5.02 .65 .84 .99

71�F1400 660 52.7 15.4 3.49 .43 .56 .69 50.7 14.9 3.94 .43 .57 .70 48.6 14.2 4.45 .43 .58 .72 46.4 13.6 5.05 .44 .59 .74

71�F(22�C)

1600 755 53.6 15.7 3.51 .44 .58 .73 51.5 15.1 3.95 .44 .59 .74 49.4 14.5 4.47 .44 .60 .76 47.1 13.8 5.08 .45 .61 .78(22�C)

1800 850 54.3 15.9 3.52 .44 .60 .76 52.2 15.3 3.97 .45 .61 .78 50.0 14.7 4.49 .45 .63 .80 47.7 14.0 5.09 .46 .64 .82

HS29−048 − C33−60D − C23−51/65 COOLING CAPACITY − RFC or TXV Systems

63�F1400 660 47.1 13.8 3.43 .74 .87 .99 45.3 13.3 3.88 .75 .89 1.00 43.5 12.7 4.39 .76 .91 1.00 41.5 12.2 4.98 .78 .93 1.00

63�F(17�C)

1600 755 48.1 14.1 3.45 .77 .92 1.00 46.3 13.6 3.89 .78 .93 1.00 44.5 13.0 4.41 .80 .95 1.00 42.5 12.5 5.01 .81 .97 1.00(17�C)

1800 850 49.1 14.4 3.46 .80 .95 1.00 47.3 13.9 3.91 .81 .97 1.00 45.4 13.3 4.43 .83 .98 1.00 43.4 12.7 5.03 .85 1.00 1.00

67�F1400 660 50.1 14.7 3.48 .57 .71 .84 48.2 14.1 3.93 .58 .72 .86 46.1 13.5 4.45 .59 .74 .88 44.1 12.9 5.05 .60 .75 .90

67�F(19�C)

1600 755 51.0 14.9 3.50 .59 .74 .88 49.0 14.4 3.95 .60 .76 .90 47.0 13.8 4.47 .61 .77 .92 44.8 13.1 5.08 .62 .79 .94(19�C)

1800 850 51.7 15.2 3.51 .61 .77 .92 49.7 14.6 3.96 .62 .79 .94 47.6 14.0 4.49 .63 .81 .96 45.4 13.3 5.10 .64 .83 .98

71�F1400 660 53.4 15.6 3.54 .43 .56 .68 51.3 15.0 3.99 .43 .56 .70 49.2 14.4 4.52 .43 .57 .71 47.1 13.8 5.13 .44 .58 .73

71�F(22�C)

1600 755 54.3 15.9 3.55 .43 .58 .72 52.2 15.3 4.01 .44 .58 .73 50.0 14.7 4.54 .44 .60 .75 47.8 14.0 5.15 .45 .61 .77(22�C)

1800 850 55.0 16.1 3.57 .44 .60 .75 52.9 15.5 4.03 .44 .61 .77 50.7 14.9 4.55 .45 .62 .79 48.4 14.2 5.17 .45 .63 .81

HS29−048 − C33−62D − C26−65EAP − CH33−62D−F − CH23−68 COOLING CAPACITY − TXV Systems Only

63�F1400 660 48.0 14.1 3.39 .73 .88 .99 46.2 13.5 3.82 .75 .89 1.00 44.3 13.0 4.33 .76 .91 1.00 42.3 12.4 4.93 .78 .93 1.00

63�F(17�C)

1600 755 49.2 14.4 3.41 .77 .92 1.00 47.3 13.9 3.85 .78 .94 1.00 45.3 13.3 4.36 .80 .96 1.00 43.2 12.7 4.95 .82 .98 1.00(17�C)

1800 850 50.1 14.7 3.43 .80 .96 1.00 48.2 14.1 3.87 .82 .98 1.00 46.2 13.5 4.38 .84 .99 1.00 44.3 13.0 4.97 .86 1.00 1.00

67�F1400 660 51.1 15.0 3.44 .58 .71 .84 49.1 14.4 3.88 .58 .73 .86 47.1 13.8 4.39 .59 .74 .88 44.9 13.2 5.00 .60 .76 .90

67�F(19�C)

1600 755 52.1 15.3 3.46 .59 .74 .89 50.0 14.7 3.91 .60 .76 .91 47.9 14.0 4.42 .61 .78 .93 45.7 13.4 5.01 .62 .79 .95(19�C)

1800 850 52.8 15.5 3.48 .61 .78 .93 50.7 14.9 3.92 .62 .79 .95 48.6 14.2 4.43 .63 .81 .97 46.3 13.6 5.03 .65 .83 .99

71�F1400 660 54.5 16.0 3.51 .43 .56 .69 52.4 15.4 3.95 .43 .56 .70 50.2 14.7 4.47 .43 .57 .71 47.9 14.0 5.08 .44 .58 .73

71�F(22�C)

1600 755 55.4 16.2 3.52 .44 .58 .72 53.3 15.6 3.97 .44 .59 .74 51.0 14.9 4.49 .44 .60 .75 48.6 14.2 5.09 .45 .61 .77(22�C)

1800 850 56.2 16.5 3.54 .44 .60 .76 54.0 15.8 3.99 .45 .61 .77 51.6 15.1 4.51 .45 .62 .79 49.2 14.4 5.11 .46 .64 .81

HS29−048 � C33−48C−2 with G60UHV−60C−090 COOLING CAPACITY − TXV Systems Only

63�F1430 675 47.6 14.0 3.55 .74 .88 .99 45.8 13.4 4.01 .75 .90 1.00 44.0 12.9 4.54 .76 .91 1.00 42.1 12.3 5.17 .78 .93 1.00

63�F(17�C)

1630 770 48.6 14.2 3.56 .77 .92 1.00 46.8 13.7 4.03 .78 .93 1.00 44.9 13.2 4.57 .80 .95 1.00 43.0 12.6 5.19 .82 .97 1.00(17�C)

1830 865 49.5 14.5 3.58 .80 .95 1.00 47.7 14.0 4.04 .81 .96 1.00 45.8 13.4 4.59 .83 .98 1.00 43.9 12.9 5.20 .85 .99 1.00

67�F1430 675 50.6 14.8 3.59 .58 .71 .85 48.7 14.3 4.06 .58 .72 .86 46.7 13.7 4.60 .59 .74 .88 44.6 13.1 5.22 .60 .76 .90

67�F(19�C)

1630 770 51.4 15.1 3.61 .59 .74 .89 49.5 14.5 4.07 .60 .76 .90 47.5 13.9 4.61 .61 .77 .92 45.3 13.3 5.25 .62 .79 .94(19�C)

1830 865 52.1 15.3 3.62 .61 .78 .92 50.1 14.7 4.09 .62 .79 .94 48.1 14.1 4.62 .63 .81 .96 45.9 13.5 5.26 .64 .83 .97

71�F1430 675 53.8 15.8 3.65 .43 .56 .69 51.8 15.2 4.12 .43 .57 .70 49.7 14.6 4.66 .43 .58 .71 47.6 14.0 5.30 .44 .58 .73

71�F(22�C)

1630 770 54.7 16.0 3.66 .44 .58 .72 52.6 15.4 4.14 .44 .59 .73 50.5 14.8 4.68 .44 .60 .75 48.3 14.2 5.31 .45 .61 .77(22�C)

1830 865 55.4 16.2 3.68 .44 .60 .75 53.3 15.6 4.15 .44 .61 .77 51.1 15.0 4.70 .45 .62 .78 48.8 14.3 5.33 .45 .63 .80

HS29−048 � C33−50/60C−2 with G60UHV−60C−090 COOLING CAPACITY − TXV Systems Only

63�F1430 675 48.1 14.1 3.56 .74 .88 .99 46.3 13.6 4.02 .75 .89 1.00 44.4 13.0 4.56 .76 .91 1.00 42.4 12.4 5.18 .78 .93 1.00

63�F(17�C)

1630 770 49.1 14.4 3.57 .77 .92 1.00 47.3 13.9 4.04 .78 .93 1.00 45.4 13.3 4.57 .80 .95 1.00 43.4 12.7 5.19 .81 .97 1.00(17�C)

1830 865 50.0 14.7 3.59 .80 .95 1.00 48.2 14.1 4.05 .81 .97 1.00 46.3 13.6 4.59 .83 .98 1.00 44.4 13.0 5.22 .85 .99 1.00

67�F1430 675 51.1 15.0 3.61 .58 .71 .85 49.2 14.4 4.07 .58 .72 .86 47.2 13.8 4.61 .59 .74 .88 45.0 13.2 5.24 .60 .76 .90

67�F(19�C)

1630 770 52.0 15.2 3.62 .59 .74 .89 50.0 14.7 4.08 .60 .76 .90 47.9 14.0 4.63 .61 .77 .92 45.8 13.4 5.25 .62 .79 .94(19�C)

1830 865 52.7 15.4 3.63 .61 .77 .92 50.7 14.9 4.10 .62 .79 .94 48.6 14.2 4.65 .63 .81 .96 46.4 13.6 5.27 .64 .83 .98

71�F1430 675 54.4 15.9 3.67 .43 .56 .69 52.4 15.4 4.14 .43 .56 .70 50.3 14.7 4.68 .43 .57 .71 48.0 14.1 5.32 .44 .58 .73

71�F(22�C)

1630 770 55.3 16.2 3.68 .43 .58 .72 53.2 15.6 4.15 .44 .59 .73 51.0 14.9 4.70 .44 .60 .75 48.8 14.3 5.34 .44 .61 .77(22�C)

1830 865 56.0 16.4 3.70 .44 .60 .75 53.9 15.8 4.16 .45 .61 .77 51.7 15.2 4.72 .45 .62 .79 49.4 14.5 5.35 .45 .63 .81

HS29 / Page 43

Page 44: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 1 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

Outdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet BulbT

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

HS29−048 − CR26−48 COOLING CAPACITY − RFC or TXV Systems

63�F1200 565 44.4 13.0 3.39 .70 .83 .94 42.8 12.5 3.83 .71 .84 .96 41.1 12.0 4.34 .72 .86 .97 39.2 11.5 4.94 .73 .88 .99

63�F(17�C)

1400 660 45.6 13.4 3.41 .73 .87 .98 43.9 12.9 3.85 .74 .89 .99 42.1 12.3 4.37 .75 .90 1.00 40.3 11.8 4.97 .77 .92 1.00(17�C)

1600 755 46.6 13.7 3.43 .76 .91 1.00 44.9 13.2 3.87 .77 .92 1.00 43.0 12.6 4.39 .79 .94 1.00 41.2 12.1 4.99 .81 .96 1.00

67�F1200 565 47.4 13.9 3.44 .55 .68 .80 45.7 13.4 3.89 .56 .68 .81 43.8 12.8 4.40 .57 .70 .82 41.9 12.3 5.01 .57 .71 .84

67�F(19�C)

1400 660 48.5 14.2 3.46 .57 .71 .84 46.7 13.7 3.91 .58 .72 .85 44.8 13.1 4.43 .58 .73 .87 42.8 12.5 5.02 .59 .75 .89(19�C)

1600 755 49.4 14.5 3.48 .59 .73 .88 47.5 13.9 3.92 .60 .75 .90 45.6 13.4 4.44 .60 .76 .91 43.5 12.7 5.05 .61 .78 .93

71�F1200 565 50.6 14.8 3.50 .42 .54 .65 48.7 14.3 3.95 .43 .54 .66 46.8 13.7 4.47 .43 .55 .67 44.8 13.1 5.08 .43 .56 .68

71�F(22�C)

1400 660 51.7 15.2 3.52 .43 .55 .68 49.8 14.6 3.97 .43 .56 .69 47.8 14.0 4.49 .43 .57 .71 45.7 13.4 5.10 .44 .58 .72(22�C)

1600 755 52.5 15.4 3.53 .43 .57 .71 50.6 14.8 3.99 .43 .58 .72 48.5 14.2 4.51 .44 .59 .74 46.4 13.6 5.12 .44 .60 .76

HS29−048 � CR26−60 COOLING CAPACITY − RFC or TXV Systems

63�F1400 660 45.9 13.5 3.37 .74 .88 .99 44.1 12.9 3.81 .75 .90 1.00 42.3 12.4 4.31 .76 .91 1.00 40.4 11.8 4.90 .78 .93 1.00

63�F(17�C)

1600 755 46.9 13.7 3.39 .77 .92 1.00 45.1 13.2 3.82 .78 .94 1.00 43.3 12.7 4.33 .80 .95 1.00 41.4 12.1 4.92 .82 .97 1.00(17�C)

1800 850 47.8 14.0 3.40 .80 .96 1.00 46.0 13.5 3.84 .82 .97 1.00 44.2 13.0 4.35 .83 .99 1.00 42.4 12.4 4.94 .86 1.00 1.00

67�F1400 660 48.7 14.3 3.42 .57 .71 .85 46.9 13.7 3.86 .58 .72 .86 44.9 13.2 4.37 .59 .74 .88 42.9 12.6 4.96 .60 .76 .90

67�F(19�C)

1600 755 49.6 14.5 3.44 .59 .75 .89 47.7 14.0 3.87 .60 .76 .91 45.7 13.4 4.39 .61 .78 .93 43.6 12.8 4.99 .62 .80 .95(19�C)

1800 850 50.3 14.7 3.45 .61 .78 .93 48.4 14.2 3.89 .62 .80 .95 46.3 13.6 4.41 .63 .81 .97 44.2 13.0 5.00 .65 .83 .98

71�F1400 660 51.9 15.2 3.48 .43 .56 .69 49.9 14.6 3.93 .43 .57 .70 47.9 14.0 4.44 .43 .57 .71 45.8 13.4 5.04 .44 .59 .73

71�F(22�C)

1600 755 52.8 15.5 3.50 .44 .58 .72 50.8 14.9 3.94 .44 .59 .74 48.6 14.2 4.46 .44 .60 .75 46.4 13.6 5.07 .45 .61 .77(22�C)

1800 850 53.5 15.7 3.51 .44 .60 .76 51.4 15.1 3.96 .45 .61 .77 49.2 14.4 4.48 .45 .62 .79 47.0 13.8 5.08 .46 .64 .81

HS29−048 −CH33−44B−F − CH23−51 − CH33−48C−F RFC Systems Only − COOLING CAPACITY

63�F1400 660 46.3 13.6 3.38 .75 .89 .99 44.6 13.1 3.82 .76 .90 1.00 42.8 12.5 4.33 .77 .92 1.00 41.0 12.0 4.92 .79 .94 1.00

63�F(17�C)

1600 755 47.4 13.9 3.40 .78 .93 1.00 45.6 13.4 3.84 .79 .95 1.00 43.8 12.8 4.35 .81 .96 1.00 42.0 12.3 4.94 .83 .98 1.00(17�C)

1800 850 48.3 14.2 3.41 .81 .96 1.00 46.5 13.6 3.86 .83 .98 1.00 44.8 13.1 4.36 .84 .99 1.00 43.0 12.6 4.96 .86 1.00 1.00

67�F1400 660 49.1 14.4 3.42 .58 .72 .86 47.2 13.8 3.87 .59 .74 .87 45.3 13.3 4.37 .60 .75 .89 43.3 12.7 4.98 .61 .76 .91

67�F(19�C)

1600 755 49.9 14.6 3.44 .60 .76 .90 48.0 14.1 3.88 .61 .77 .92 46.1 13.5 4.39 .62 .79 .94 44.0 12.9 4.99 .63 .80 .95(19�C)

1800 850 50.6 14.8 3.45 .62 .79 .94 48.7 14.3 3.89 .63 .80 .95 46.7 13.7 4.41 .64 .82 .97 44.6 13.1 5.01 .65 .84 .98

71�F1400 660 52.2 15.3 3.48 .43 .56 .70 50.3 14.7 3.92 .43 .57 .71 48.2 14.1 4.44 .44 .58 .73 46.1 13.5 5.04 .44 .59 .74

71�F(22�C)

1600 755 53.0 15.5 3.49 .44 .59 .73 51.0 14.9 3.94 .44 .60 .75 48.9 14.3 4.46 .45 .61 .77 46.8 13.7 5.07 .45 .62 .78(22�C)

1800 850 53.7 15.7 3.50 .45 .61 .77 51.6 15.1 3.95 .45 .62 .79 49.5 14.5 4.47 .45 .63 .80 47.3 13.9 5.08 .46 .64 .82

HS29−048 − CH33−60D−F RFC Systems Only − CH33−50C−F TXV Systems Only − CH23−65 RFC or TXV Systems

63�F1400 660 46.7 13.7 3.37 .74 .89 .99 45.0 13.2 3.81 .76 .90 1.00 43.2 12.7 4.32 .77 .92 1.00 41.3 12.1 4.90 .79 .94 1.00

63�F(17�C)

1600 755 47.8 14.0 3.39 .78 .93 1.00 46.0 13.5 3.83 .79 .94 1.00 44.2 13.0 4.33 .81 .96 1.00 42.3 12.4 4.93 .82 .98 1.00(17�C)

1800 850 48.8 14.3 3.41 .81 .96 1.00 47.0 13.8 3.84 .82 .98 1.00 45.1 13.2 4.35 .84 .99 1.00 43.3 12.7 4.95 .86 1.00 1.00

67�F1400 660 49.5 14.5 3.42 .58 .72 .85 47.7 14.0 3.86 .58 .73 .87 45.7 13.4 4.37 .59 .75 .89 43.7 12.8 4.96 .60 .76 .91

67�F(19�C)

1600 755 50.4 14.8 3.43 .60 .75 .90 48.5 14.2 3.88 .61 .77 .92 46.5 13.6 4.38 .62 .78 .93 44.4 13.0 4.98 .63 .80 .95(19�C)

1800 850 51.2 15.0 3.45 .62 .79 .94 49.2 14.4 3.89 .63 .80 .95 47.2 13.8 4.40 .64 .82 .97 45.0 13.2 5.01 .65 .84 .99

71�F1400 660 52.8 15.5 3.48 .43 .56 .69 50.8 14.9 3.92 .43 .57 .71 48.7 14.3 4.44 .44 .58 .72 46.5 13.6 5.04 .44 .59 .74

71�F(22�C)

1600 755 53.6 15.7 3.49 .44 .58 .73 51.6 15.1 3.94 .44 .59 .74 49.4 14.5 4.46 .44 .60 .76 47.2 13.8 5.06 .45 .62 .78(22�C)

1800 850 54.3 15.9 3.50 .45 .61 .76 52.2 15.3 3.95 .45 .62 .78 50.0 14.7 4.47 .45 .63 .80 47.8 14.0 5.08 .46 .64 .82

HS29−048 � CH33−48C−2F with G60UHV−60C−090 COOLING CAPACITY − TXV Systems Only

63�F1430 675 48.5 14.2 3.55 .74 .88 .99 46.7 13.7 4.01 .75 .89 1.00 44.8 13.1 4.55 .76 .91 1.00 42.8 12.5 5.17 .78 .93 1.00

63�F(17�C)

1630 770 49.6 14.5 3.57 .77 .92 1.00 47.7 14.0 4.03 .78 .93 1.00 45.8 13.4 4.56 .80 .95 1.00 43.8 12.8 5.18 .81 .97 1.00(17�C)

1830 865 50.5 14.8 3.59 .80 .95 1.00 48.6 14.2 4.04 .81 .97 1.00 46.7 13.7 4.58 .83 .98 1.00 44.8 13.1 5.21 .85 .99 1.00

67�F1430 675 51.6 15.1 3.60 .57 .71 .85 49.6 14.5 4.07 .58 .72 .86 47.6 14.0 4.60 .59 .74 .88 45.4 13.3 5.23 .60 .76 .90

67�F(19�C)

1630 770 52.5 15.4 3.62 .59 .74 .89 50.5 14.8 4.08 .60 .76 .90 48.4 14.2 4.62 .61 .77 .92 46.2 13.5 5.24 .62 .79 .94(19�C)

1830 865 53.2 15.6 3.63 .61 .77 .92 51.2 15.0 4.10 .62 .79 .94 49.0 14.4 4.64 .63 .81 .96 46.8 13.7 5.26 .64 .83 .98

71�F1430 675 54.9 16.1 3.66 .43 .56 .69 52.9 15.5 4.13 .43 .57 .70 50.7 14.9 4.67 .43 .57 .71 48.5 14.2 5.31 .44 .58 .73

71�F(22�C)

1630 770 55.8 16.4 3.68 .44 .58 .72 53.7 15.7 4.15 .44 .59 .73 51.5 15.1 4.69 .44 .60 .75 49.2 14.4 5.33 .45 .61 .77(22�C)

1830 865 56.6 16.6 3.69 .44 .60 .75 54.4 15.9 4.16 .44 .61 .77 52.1 15.3 4.71 .45 .62 .78 49.8 14.6 5.34 .45 .63 .80

HS29−048 � CH33−50/60C−2F with G60UHV−60C−090 COOLING CAPACITY − TXV Systems Only

63�F1430 675 48.9 14.3 3.56 .74 .88 .99 47.0 13.8 4.02 .75 .89 1.00 45.1 13.2 4.55 .76 .91 1.00 43.1 12.6 5.17 .78 .93 1.00

63�F(17�C)

1630 770 49.9 14.6 3.58 .76 .92 1.00 48.1 14.1 4.03 .78 .93 1.00 46.1 13.5 4.57 .80 .95 1.00 44.1 12.9 5.20 .81 .97 1.00(17�C)

1830 865 50.9 14.9 3.59 .80 .95 1.00 49.0 14.4 4.06 .81 .97 1.00 47.0 13.8 4.59 .83 .99 1.00 45.0 13.2 5.22 .85 1.00 1.00

67�F1430 675 52.0 15.2 3.61 .58 .71 .84 50.0 14.7 4.08 .58 .72 .86 47.9 14.0 4.61 .59 .74 .88 45.8 13.4 5.24 .60 .75 .90

67�F(19�C)

1630 770 53.0 15.5 3.63 .59 .74 .89 51.0 14.9 4.09 .60 .75 .90 48.8 14.3 4.63 .61 .77 .92 46.5 13.6 5.27 .62 .79 .94(19�C)

1830 865 53.8 15.8 3.64 .61 .77 .92 51.6 15.1 4.11 .62 .79 .94 49.4 14.5 4.65 .63 .81 .96 47.2 13.8 5.28 .64 .83 .98

71�F1430 675 55.5 16.3 3.67 .43 .56 .69 53.3 15.6 4.15 .43 .56 .70 51.1 15.0 4.69 .43 .57 .71 48.9 14.3 5.32 .44 .58 .73

71�F(22�C)

1630 770 56.4 16.5 3.69 .43 .58 .72 54.2 15.9 4.16 .44 .58 .73 52.0 15.2 4.71 .44 .59 .75 49.6 14.5 5.35 .45 .61 .77(22�C)

1830 865 57.1 16.7 3.71 .44 .60 .75 54.9 16.1 4.18 .44 .61 .77 52.6 15.4 4.73 .45 .62 .79 50.2 14.7 5.36 .45 .63 .81

HS29−048 − CB30M−41 − CB30U−41/46 COOLING CAPACITY − TXV Systems Only

63�F1050 495 42.9 12.6 3.37 .69 .80 .92 41.3 12.1 3.81 .69 .82 .93 39.6 11.6 4.32 .70 .83 .95 37.9 11.1 4.91 .72 .85 .97

63�F(17�C)

1250 590 44.3 13.0 3.40 .72 .85 .96 42.6 12.5 3.84 .73 .86 .98 40.9 12.0 4.35 .74 .88 .99 39.1 11.5 4.95 .75 .90 1.00(17�C)

1450 685 45.4 13.3 3.42 .75 .89 1.00 43.7 12.8 3.86 .76 .91 1.00 41.9 12.3 4.38 .77 .93 1.00 40.1 11.8 4.96 .79 .95 1.00

67�F1050 495 45.8 13.4 3.42 .55 .66 .77 44.1 12.9 3.87 .55 .67 .78 42.4 12.4 4.38 .56 .68 .80 40.5 11.9 4.98 .56 .69 .82

67�F(19�C)

1250 590 47.1 13.8 3.44 .56 .69 .82 45.4 13.3 3.89 .57 .70 .83 43.5 12.7 4.41 .57 .71 .85 41.6 12.2 5.00 .58 .73 .87(19�C)

1450 685 48.1 14.1 3.46 .58 .72 .86 46.3 13.6 3.91 .59 .74 .88 44.4 13.0 4.42 .60 .75 .89 42.4 12.4 5.03 .61 .77 .91

71�F1050 495 48.9 14.3 3.47 .42 .53 .63 47.1 13.8 3.92 .42 .53 .64 45.2 13.2 4.45 .42 .54 .65 43.3 12.7 5.05 .42 .54 .66

71�F(22�C)

1250 590 50.2 14.7 3.50 .42 .54 .67 48.4 14.2 3.95 .43 .55 .68 46.4 13.6 4.47 .43 .56 .69 44.4 13.0 5.07 .43 .57 .70(22�C)

1450 685 51.2 15.0 3.52 .43 .56 .70 49.3 14.4 3.97 .43 .57 .71 47.3 13.9 4.49 .44 .58 .73 45.2 13.2 5.10 .44 .59 .74

HS29 / Page 44

Page 45: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 1 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

Outdoor Air Temperature Entering Outdoor Coil

Total85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)

EnteringWet BulbTempera�

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Tempera�ture

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

HS29−048 − CB31MV−41 COOLING CAPACITY − TXV Systems Only

63�F1265 595 43.6 12.8 3.34 .72 .85 .97 42.0 12.3 3.77 .73 .87 .98 40.3 11.8 4.28 .74 .88 .99 38.5 11.3 4.87 .76 .90 1.00

63�F(17�C)

1400 660 44.3 13.0 3.35 .74 .88 .99 42.7 12.5 3.79 .75 .90 1.00 41.0 12.0 4.30 .76 .91 1.00 39.2 11.5 4.88 .78 .93 1.00(17�C)

1545 730 45.0 13.2 3.37 .76 .91 1.00 43.4 12.7 3.81 .78 .93 1.00 41.6 12.2 4.31 .79 .94 1.00 39.8 11.7 4.89 .81 .96 1.00

67�F1265 595 46.4 13.6 3.39 .56 .69 .82 44.6 13.1 3.82 .57 .70 .83 42.8 12.5 4.33 .58 .72 .85 40.9 12.0 4.92 .59 .73 .87

67�F(19�C)

1400 660 47.0 13.8 3.40 .58 .71 .85 45.3 13.3 3.84 .58 .73 .87 43.4 12.7 4.34 .59 .74 .88 41.5 12.2 4.94 .60 .76 .90(19�C)

1545 730 47.6 14.0 3.41 .59 .74 .88 45.8 13.4 3.85 .60 .75 .90 43.9 12.9 4.36 .61 .77 .92 42.0 12.3 4.96 .62 .79 .94

71�F1265 595 49.4 14.5 3.44 .43 .55 .67 47.6 14.0 3.88 .43 .55 .68 45.7 13.4 4.40 .43 .56 .69 43.7 12.8 4.99 .43 .57 .70

71�F(22�C)

1400 660 50.1 14.7 3.45 .43 .56 .69 48.2 14.1 3.90 .43 .57 .70 46.3 13.6 4.41 .43 .57 .72 44.2 13.0 5.01 .44 .59 .74(22�C)

1545 730 50.7 14.9 3.47 .43 .57 .71 48.8 14.3 3.91 .44 .58 .73 46.8 13.7 4.42 .44 .59 .75 44.7 13.1 5.03 .44 .60 .76

HS29−048 − CB29M−46 − CB28UH−042 COOLING CAPACITY − TXV Systems Only

63�F1450 685 46.4 13.6 3.42 .75 .89 1.00 44.7 13.1 3.86 .76 .91 1.00 42.9 12.6 4.38 .77 .93 1.00 41.1 12.0 4.98 .79 .94 1.00

63�F(17�C)

1550 730 46.9 13.7 3.43 .76 .91 1.00 45.2 13.2 3.87 .78 .93 1.00 43.4 12.7 4.39 .79 .94 1.00 41.6 12.2 4.99 .81 .96 1.00(17�C)

1650 780 47.4 13.9 3.44 .78 .93 1.00 45.6 13.4 3.88 .79 .95 1.00 43.8 12.8 4.40 .81 .96 1.00 42.0 12.3 5.00 .83 .98 1.00

67�F1450 685 49.2 14.4 3.46 .58 .72 .86 47.3 13.9 3.91 .59 .74 .88 45.4 13.3 4.43 .60 .75 .89 43.4 12.7 5.03 .61 .77 .92

67�F(19�C)

1550 730 49.6 14.5 3.47 .59 .74 .88 47.7 14.0 3.92 .60 .75 .90 45.8 13.4 4.43 .61 .77 .92 43.7 12.8 5.05 .62 .79 .94(19�C)

1650 780 49.9 14.6 3.48 .60 .76 .90 48.1 14.1 3.93 .61 .77 .92 46.1 13.5 4.44 .62 .79 .94 44.0 12.9 5.05 .63 .81 .96

71�F1450 685 52.3 15.3 3.52 .43 .57 .70 50.4 14.8 3.97 .43 .57 .71 48.4 14.2 4.49 .44 .58 .73 46.2 13.5 5.10 .44 .59 .74

71�F(22�C)

1550 730 52.7 15.4 3.52 .43 .58 .72 50.8 14.9 3.98 .44 .58 .73 48.7 14.3 4.50 .44 .59 .75 46.6 13.7 5.11 .44 .61 .76(22�C)

1650 780 53.1 15.6 3.53 .44 .59 .73 51.1 15.0 3.98 .44 .59 .75 49.0 14.4 4.51 .44 .61 .77 46.8 13.7 5.12 .45 .62 .78

HS29−048 − CB29M−51 − CB28UH−048 COOLING CAPACITY − TXV Systems Only

63�F1300 615 45.8 13.4 3.40 .72 .86 .97 44.1 12.9 3.85 .74 .88 .99 42.3 12.4 4.36 .75 .89 1.00 40.5 11.9 4.96 .76 .91 1.00

63�F(17�C)

1450 685 46.7 13.7 3.42 .75 .89 1.00 44.9 13.2 3.86 .76 .91 1.00 43.1 12.6 4.38 .77 .93 1.00 41.2 12.1 4.97 .79 .94 1.00(17�C)

1600 755 47.4 13.9 3.43 .77 .92 1.00 45.6 13.4 3.88 .79 .94 1.00 43.8 12.8 4.39 .80 .95 1.00 41.9 12.3 4.99 .82 .97 1.00

67�F1300 615 48.7 14.3 3.45 .57 .70 .83 46.9 13.7 3.90 .57 .71 .84 45.0 13.2 4.42 .58 .72 .86 43.0 12.6 5.01 .59 .74 .88

67�F(19�C)

1450 685 49.4 14.5 3.47 .58 .72 .86 47.6 14.0 3.91 .59 .74 .88 45.6 13.4 4.43 .60 .75 .90 43.6 12.8 5.04 .61 .77 .92(19�C)

1600 755 50.1 14.7 3.48 .59 .75 .89 48.2 14.1 3.92 .60 .76 .91 46.2 13.5 4.45 .61 .78 .93 44.1 12.9 5.05 .62 .80 .95

71�F1300 615 51.9 15.2 3.51 .43 .55 .67 50.0 14.7 3.96 .43 .56 .68 48.0 14.1 4.48 .43 .56 .70 45.9 13.5 5.09 .43 .57 .71

71�F(22�C)

1450 685 52.6 15.4 3.52 .43 .56 .70 50.7 14.9 3.97 .43 .57 .71 48.6 14.2 4.49 .44 .58 .73 46.4 13.6 5.11 .44 .59 .74(22�C)

1600 755 53.2 15.6 3.53 .44 .58 .73 51.2 15.0 3.99 .44 .59 .74 49.1 14.4 4.51 .44 .60 .76 47.0 13.8 5.12 .45 .61 .77

HS29−048 − CB30M−46 COOLING CAPACITY − TXV Systems Only

63�F1250 590 45.0 13.2 3.41 .72 .85 .96 43.4 12.7 3.85 .73 .86 .98 41.6 12.2 4.36 .74 .88 .99 39.8 11.7 4.96 .75 .90 1.00

63�F(17�C)

1400 660 45.9 13.5 3.42 .74 .88 .99 44.2 13.0 3.87 .75 .90 1.00 42.4 12.4 4.38 .77 .92 1.00 40.6 11.9 4.98 .78 .93 1.00(17�C)

1550 730 46.7 13.7 3.44 .76 .91 1.00 44.9 13.2 3.88 .78 .93 1.00 43.1 12.6 4.40 .79 .95 1.00 41.3 12.1 4.99 .81 .96 1.00

67�F1250 590 47.9 14.0 3.45 .56 .69 .82 46.2 13.5 3.90 .57 .70 .83 44.3 13.0 4.42 .58 .71 .85 42.3 12.4 5.02 .58 .73 .87

67�F(19�C)

1400 660 48.7 14.3 3.47 .58 .71 .85 46.9 13.7 3.92 .58 .73 .87 45.0 13.2 4.43 .59 .74 .88 42.9 12.6 5.04 .60 .76 .90(19�C)

1550 730 49.4 14.5 3.48 .59 .74 .88 47.5 13.9 3.92 .60 .75 .90 45.5 13.3 4.45 .61 .77 .92 43.5 12.7 5.06 .62 .79 .94

71�F1250 590 51.1 15.0 3.51 .42 .54 .67 49.2 14.4 3.96 .43 .55 .68 47.2 13.8 4.49 .43 .56 .69 45.2 13.2 5.09 .43 .57 .70

71�F(22�C)

1400 660 51.9 15.2 3.52 .43 .56 .69 49.9 14.6 3.98 .43 .57 .70 47.9 14.0 4.50 .43 .58 .72 45.8 13.4 5.12 .44 .59 .73(22�C)

1550 730 52.5 15.4 3.54 .43 .58 .72 50.5 14.8 3.99 .44 .58 .73 48.5 14.2 4.51 .44 .59 .75 46.3 13.6 5.13 .44 .60 .76

HS29−048 − CB29M−65 − CB28UH−060 COOLING CAPACITY − TXV Systems Only

63�F1400 660 46.5 13.6 3.41 .74 .88 .99 44.8 13.1 3.86 .75 .90 1.00 43.0 12.6 4.38 .77 .91 1.00 41.1 12.0 4.97 .78 .93 1.00

63�F(17�C)

1600 755 47.5 13.9 3.43 .77 .92 1.00 45.8 13.4 3.88 .78 .94 1.00 44.0 12.9 4.39 .80 .95 1.00 42.1 12.3 4.99 .82 .97 1.00(17�C)

1800 850 48.4 14.2 3.45 .80 .95 1.00 46.7 13.7 3.89 .82 .97 1.00 44.9 13.2 4.41 .83 .98 1.00 43.0 12.6 5.01 .85 1.00 1.00

67�F1400 660 49.4 14.5 3.46 .58 .71 .85 47.5 13.9 3.91 .58 .73 .87 45.6 13.4 4.42 .59 .74 .88 43.5 12.7 5.03 .60 .76 .90

67�F(19�C)

1600 755 50.2 14.7 3.48 .60 .75 .89 48.3 14.2 3.92 .60 .76 .91 46.3 13.6 4.45 .61 .78 .93 44.2 13.0 5.05 .62 .80 .95(19�C)

1800 850 50.9 14.9 3.49 .61 .78 .93 49.0 14.4 3.94 .62 .80 .95 46.9 13.7 4.46 .63 .81 .96 44.9 13.2 5.06 .65 .83 .98

71�F1400 660 52.6 15.4 3.52 .43 .56 .69 50.6 14.8 3.97 .43 .57 .70 48.6 14.2 4.49 .43 .58 .72 46.4 13.6 5.11 .44 .59 .73

71�F(22�C)

1600 755 53.4 15.6 3.53 .44 .58 .72 51.4 15.1 3.99 .44 .59 .74 49.3 14.4 4.51 .44 .60 .75 47.1 13.8 5.12 .45 .61 .77(22�C)

1800 850 54.1 15.9 3.55 .44 .60 .76 52.0 15.2 3.99 .45 .61 .77 49.9 14.6 4.53 .45 .62 .79 47.6 14.0 5.14 .46 .64 .81

HS29−048 − CB30M−51 − CB30U−51 COOLING CAPACITY − TXV Systems Only

63�F1400 660 46.2 13.5 3.42 .74 .88 .99 44.5 13.0 3.86 .75 .89 1.00 42.6 12.5 4.36 .76 .91 1.00 40.7 11.9 4.97 .78 .93 1.00

63�F(17�C)

1600 755 47.3 13.9 3.43 .77 .92 1.00 45.5 13.3 3.88 .78 .94 1.00 43.6 12.8 4.39 .80 .96 1.00 41.6 12.2 4.99 .82 .98 1.00(17�C)

1800 850 48.2 14.1 3.45 .80 .96 1.00 46.4 13.6 3.90 .82 .97 1.00 44.5 13.0 4.41 .83 .99 1.00 42.6 12.5 5.01 .85 1.00 1.00

67�F1400 660 49.1 14.4 3.47 .57 .71 .85 47.2 13.8 3.91 .58 .72 .86 45.3 13.3 4.43 .59 .74 .88 43.2 12.7 5.04 .60 .75 .90

67�F(19�C)

1600 755 50.1 14.7 3.49 .59 .74 .89 48.1 14.1 3.93 .60 .76 .91 46.0 13.5 4.45 .61 .78 .93 43.9 12.9 5.05 .62 .79 .95(19�C)

1800 850 50.8 14.9 3.50 .61 .78 .93 48.8 14.3 3.95 .62 .80 .95 46.7 13.7 4.47 .63 .81 .97 44.6 13.1 5.07 .65 .83 .98

71�F1400 660 52.4 15.4 3.53 .43 .56 .69 50.4 14.8 3.98 .43 .57 .70 48.3 14.2 4.50 .43 .57 .71 46.1 13.5 5.12 .44 .58 .73

71�F(22�C)

1600 755 53.3 15.6 3.55 .44 .58 .72 51.2 15.0 4.00 .44 .59 .74 49.0 14.4 4.53 .44 .60 .75 46.8 13.7 5.13 .45 .61 .77(22�C)

1800 850 54.0 15.8 3.56 .44 .60 .76 51.9 15.2 4.02 .45 .61 .77 49.7 14.6 4.54 .45 .62 .79 47.4 13.9 5.15 .46 .64 .81

HS29−048 − CB31MV−51 COOLING CAPACITY − TXV Systems Only

63�F1425 675 46.1 13.5 3.37 .74 .88 1.00 44.3 13.0 3.80 .75 .90 1.00 42.5 12.5 4.31 .77 .92 1.00 40.5 11.9 4.90 .78 .94 1.00

63�F(17�C)

1625 765 47.1 13.8 3.39 .77 .93 1.00 45.3 13.3 3.83 .79 .94 1.00 43.4 12.7 4.33 .80 .96 1.00 41.5 12.2 4.92 .82 .98 1.00(17�C)

1805 850 47.9 14.0 3.40 .80 .96 1.00 46.1 13.5 3.84 .82 .97 1.00 44.2 13.0 4.35 .84 .99 1.00 42.4 12.4 4.94 .86 1.00 1.00

67�F1425 675 48.9 14.3 3.42 .58 .72 .85 47.1 13.8 3.86 .58 .73 .87 45.1 13.2 4.37 .59 .74 .89 43.0 12.6 4.97 .60 .76 .91

67�F(19�C)

1625 765 49.8 14.6 3.44 .60 .75 .89 47.9 14.0 3.88 .60 .76 .91 45.8 13.4 4.39 .61 .78 .93 43.7 12.8 4.98 .62 .80 .95(19�C)

1805 850 50.5 14.8 3.45 .61 .78 .93 48.5 14.2 3.90 .62 .80 .95 46.4 13.6 4.40 .63 .81 .97 44.3 13.0 5.00 .65 .83 .99

71�F1425 675 52.2 15.3 3.48 .43 .56 .69 50.2 14.7 3.93 .43 .57 .70 48.1 14.1 4.44 .43 .58 .72 45.9 13.5 5.05 .44 .59 .74

71�F(22�C)

1625 765 53.0 15.5 3.50 .44 .58 .73 51.0 14.9 3.94 .44 .59 .74 48.8 14.3 4.47 .44 .60 .76 46.6 13.7 5.06 .45 .61 .78(22�C)

1805 850 53.7 15.7 3.51 .44 .60 .76 51.6 15.1 3.96 .45 .61 .77 49.4 14.5 4.48 .45 .62 .79 47.1 13.8 5.08 .46 .63 .81

HS29 / Page 45

Page 46: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 1 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

Outdoor Air Temperature Entering Outdoor Coil

Total85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)

EnteringWet BulbTempera�

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Tempera�ture

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

HS29−048 − CB30M−65 − CB30U−65 COOLING CAPACITY − TXV Systems Only

63�F1400 660 46.7 13.7 3.43 .74 .88 .99 45.0 13.2 3.87 .75 .89 1.00 43.1 12.6 4.38 .76 .91 1.00 41.2 12.1 4.99 .78 .93 1.00

63�F(17�C)

1600 755 47.8 14.0 3.45 .77 .92 1.00 46.0 13.5 3.89 .78 .94 1.00 44.1 12.9 4.41 .80 .96 1.00 42.1 12.3 5.01 .82 .98 1.00(17�C)

1800 850 48.7 14.3 3.47 .80 .96 1.00 46.9 13.7 3.91 .82 .97 1.00 45.0 13.2 4.43 .84 .99 1.00 43.1 12.6 5.03 .86 1.00 1.00

67�F1400 660 49.7 14.6 3.48 .57 .71 .85 47.8 14.0 3.93 .58 .72 .86 45.8 13.4 4.45 .59 .74 .88 43.7 12.8 5.06 .60 .76 .90

67�F(19�C)

1600 755 50.6 14.8 3.50 .59 .75 .89 48.7 14.3 3.95 .60 .76 .91 46.6 13.7 4.47 .61 .77 .93 44.5 13.0 5.07 .62 .79 .95(19�C)

1800 850 51.4 15.1 3.52 .61 .78 .93 49.4 14.5 3.97 .62 .79 .95 47.3 13.9 4.48 .63 .81 .97 45.1 13.2 5.09 .65 .83 .98

71�F1400 660 53.0 15.5 3.55 .43 .56 .69 51.0 14.9 4.00 .43 .56 .70 48.8 14.3 4.52 .43 .57 .72 46.6 13.7 5.14 .44 .58 .73

71�F(22�C)

1600 755 53.9 15.8 3.56 .44 .58 .72 51.8 15.2 4.01 .44 .59 .74 49.6 14.5 4.55 .44 .60 .75 47.3 13.9 5.15 .45 .61 .77(22�C)

1800 850 54.6 16.0 3.58 .44 .60 .76 52.5 15.4 4.03 .45 .61 .77 50.3 14.7 4.56 .45 .62 .79 47.9 14.0 5.17 .46 .63 .81

HS29−048 − CB31MV−65 COOLING CAPACITY − TXV Systems Only

63�F1425 675 46.6 13.7 3.36 .74 .88 1.00 44.8 13.1 3.79 .75 .90 1.00 43.0 12.6 4.29 .77 .92 1.00 41.0 12.0 4.88 .79 .94 1.00

63�F(17�C)

1625 765 47.6 14.0 3.37 .77 .93 1.00 45.8 13.4 3.81 .79 .94 1.00 43.9 12.9 4.31 .80 .96 1.00 42.0 12.3 4.90 .82 .98 1.00(17�C)

1805 850 48.5 14.2 3.39 .80 .96 1.00 46.6 13.7 3.83 .82 .97 1.00 44.8 13.1 4.33 .84 .99 1.00 42.9 12.6 4.92 .86 1.00 1.00

67�F1425 675 49.5 14.5 3.41 .58 .72 .85 47.6 14.0 3.84 .58 .73 .87 45.6 13.4 4.35 .59 .74 .89 43.5 12.7 4.95 .60 .76 .91

67�F(19�C)

1625 765 50.4 14.8 3.42 .60 .75 .90 48.4 14.2 3.87 .61 .76 .91 46.4 13.6 4.38 .61 .78 .93 44.3 13.0 4.96 .62 .80 .96(19�C)

1805 850 51.1 15.0 3.44 .61 .78 .93 49.1 14.4 3.88 .62 .79 .95 47.0 13.8 4.39 .63 .81 .97 44.8 13.1 4.98 .65 .83 .99

71�F1425 675 52.8 15.5 3.47 .43 .56 .69 50.8 14.9 3.91 .43 .57 .70 48.7 14.3 4.42 .43 .58 .72 46.4 13.6 5.03 .44 .59 .74

71�F(22�C)

1625 765 53.7 15.7 3.49 .44 .58 .73 51.6 15.1 3.93 .44 .59 .74 49.4 14.5 4.45 .44 .60 .76 47.1 13.8 5.04 .45 .61 .78(22�C)

1805 850 54.3 15.9 3.50 .44 .60 .76 52.2 15.3 3.94 .45 .61 .77 50.0 14.7 4.46 .45 .62 .79 47.6 14.0 5.06 .46 .64 .81

HS29−048 − CVP10−51/EC10Q5 − CVP10−65/EC10Q5 COOLING CAPACITY − TXV Systems Only

63�F1400 660 44.4 13.0 3.32 .74 .88 .99 42.8 12.5 3.75 .75 .89 1.00 41.0 12.0 4.25 .76 .91 1.00 39.2 11.5 4.82 .78 .93 1.00

63�F(17�C)

1600 755 45.5 13.3 3.34 .77 .92 1.00 43.8 12.8 3.77 .78 .93 1.00 42.0 12.3 4.26 .80 .95 1.00 40.1 11.8 4.85 .82 .97 1.00(17�C)

1800 850 46.4 13.6 3.35 .80 .95 1.00 44.7 13.1 3.79 .81 .97 1.00 42.9 12.6 4.29 .83 .98 1.00 41.1 12.0 4.87 .85 1.00 1.00

67�F1400 660 47.3 13.9 3.37 .57 .71 .84 45.5 13.3 3.80 .58 .72 .86 43.6 12.8 4.31 .59 .74 .88 41.6 12.2 4.89 .60 .75 .90

67�F(19�C)

1600 755 48.1 14.1 3.38 .59 .74 .89 46.3 13.6 3.82 .60 .76 .90 44.4 13.0 4.32 .61 .77 .92 42.3 12.4 4.91 .62 .79 .94(19�C)

1800 850 48.9 14.3 3.40 .61 .78 .93 47.0 13.8 3.83 .62 .79 .94 45.0 13.2 4.34 .63 .81 .96 42.9 12.6 4.93 .64 .83 .98

71�F1400 660 50.3 14.7 3.43 .43 .56 .69 48.4 14.2 3.86 .43 .56 .70 46.4 13.6 4.37 .43 .57 .71 44.4 13.0 4.96 .44 .58 .73

71�F(22�C)

1600 755 51.2 15.0 3.44 .44 .58 .72 49.3 14.4 3.88 .44 .59 .73 47.2 13.8 4.39 .44 .60 .75 45.1 13.2 4.98 .45 .61 .77(22�C)

1800 850 51.9 15.2 3.46 .44 .60 .76 49.9 14.6 3.90 .44 .61 .77 47.8 14.0 4.41 .45 .62 .79 45.6 13.4 5.01 .46 .63 .81

RATINGS − 3 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C520 1100 12.6 43,100 3570 .69 .81 .92 12.0 41,100 3800 .70 .82 .94 11.4 39,000 4060 .71 .84 .96 10.8 37,000 4350 .73 .86 .98

615 1300 13.0 44,400 3610 .72 .85 .96 12.4 42,400 3850 .73 .87 .98 11.8 40,300 4130 .75 .89 .99 11.2 38,100 4430 .76 .91 1.00

710 1500 13.3 45,500 3650 .75 .89 .99 12.7 43,400 3900 .76 .91 1.00 12.1 41,200 4180 .78 .93 1.00 11.5 39,100 4490 .80 .95 1.00

520 1100 13.5 46,000 3670 .55 .66 .77 12.9 43,900 3920 .55 .67 .79 12.3 41,800 4210 .56 .69 .81 11.6 39,600 4530 .57 .70 .83

615 1300 13.9 47,300 3720 .56 .69 .82 13.2 45,100 3980 .57 .70 .83 12.6 42,900 4270 .58 .72 .86 11.9 40,600 4600 .59 .74 .88

710 1500 14.2 48,300 3750 .58 .72 .86 13.5 46,100 4020 .59 .74 .88 12.8 43,700 4320 .60 .76 .90 12.1 41,300 4650 .61 .78 .92

520 1100 14.4 49,200 3780 .42 .53 .63 13.8 47,000 4060 .42 .53 .65 13.1 44,700 4370 .42 .54 .66 12.4 42,400 4720 .43 .55 .67

615 1300 14.8 50,500 3820 .42 .54 .66 14.1 48,200 4110 .43 .55 .68 13.4 45,800 4430 .43 .56 .69 12.7 43,400 4790 .43 .57 .71

710 1500 15.1 51,500 3860 .43 .56 .70 14.4 49,100 4150 .43 .57 .71 13.7 46,700 4480 .44 .58 .73 13.0 44,200 4840 .44 .60 .75

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�048 � C26�41 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C565 1200 13.0 44,300 3640 .70 .83 .94 12.4 42,300 3890 .72 .85 .96 11.8 40,100 4170 .73 .87 .98 11.1 38,000 4480 .75 .89 1.00

660 1400 13.4 45,600 3690 .73 .87 .98 12.7 43,500 3950 .75 .89 1.00 12.1 41,300 4230 .77 .91 1.00 11.5 39,100 4550 .79 .94 1.00

755 1600 13.7 46,700 3730 .76 .91 1.00 13.0 44,500 3990 .78 .93 1.00 12.4 42,300 4290 .80 .95 1.00 11.8 40,100 4620 .82 .98 1.00

565 1200 13.9 47,300 3750 .56 .68 .80 13.2 45,100 4020 .56 .69 .81 12.6 42,900 4320 .57 .70 .83 11.9 40,500 4650 .58 .72 .86

660 1400 14.2 48,500 3790 .57 .71 .84 13.5 46,200 4070 .58 .72 .86 12.8 43,800 4380 .59 .74 .88 12.1 41,400 4720 .60 .76 .91

755 1600 14.5 49,400 3820 .59 .74 .88 13.8 47,000 4110 .60 .76 .90 13.1 44,600 4420 .61 .78 .93 12.4 42,200 4770 .63 .80 .95

565 1200 14.8 50,500 3860 .42 .54 .65 14.1 48,200 4160 .42 .54 .66 13.4 45,800 4490 .43 .55 .68 12.7 43,400 4850 .43 .56 .69

660 1400 15.2 51,700 3900 .43 .56 .68 14.4 49,300 4200 .43 .56 .70 13.7 46,800 4540 .43 .57 .72 13.0 44,300 4910 .44 .59 .74

755 1600 15.4 52,600 3930 .43 .58 .72 14.7 50,200 4240 .44 .59 .73 14.0 47,600 4590 .44 .60 .75 13.2 45,000 4960 .45 .61 .78

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�048 � C33−44C − C26�46 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

HS29 / Page 46

Page 47: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 3 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C660 1400 13.7 46,700 3600 .73 .86 .98 13.0 44,500 3840 .74 .88 .99 12.4 42,300 4110 .76 .90 1.00 11.8 40,100 4410 .78 .93 1.00

755 1600 14.0 47,700 3640 .75 .90 1.00 13.3 45,500 3880 .77 .92 1.00 12.7 43,300 4160 .79 .94 1.00 12.0 41,100 4470 .81 .96 1.00

850 1800 14.2 48,600 3670 .78 .93 1.00 13.6 46,400 3920 .80 .95 1.00 13.0 44,200 4200 .82 .97 1.00 12.3 41,900 4530 .84 .99 1.00

660 1400 14.6 49,700 3700 .57 .70 .83 13.9 47,400 3960 .58 .71 .85 13.2 45,100 4250 .59 .73 .87 12.5 42,700 4570 .60 .75 .90

755 1600 14.9 50,700 3730 .58 .73 .87 14.2 48,300 3990 .59 .75 .89 13.4 45,800 4290 .60 .77 .91 12.7 43,400 4620 .62 .79 .94

850 1800 15.1 51,400 3760 .60 .76 .90 14.4 49,000 4020 .61 .78 .93 13.6 46,500 4330 .62 .80 .95 12.9 44,000 4660 .64 .82 .97

660 1400 15.6 53,100 3810 .43 .55 .67 14.8 50,600 4090 .43 .56 .69 14.1 48,200 4410 .43 .57 .71 13.4 45,600 4760 .44 .58 .73

755 1600 15.8 54,000 3840 .43 .57 .71 15.1 51,500 4130 .43 .58 .72 14.3 48,900 4450 .44 .59 .74 13.6 46,300 4810 .44 .60 .76

850 1800 16.0 54,700 3860 .44 .59 .74 15.3 52,200 4150 .44 .60 .75 14.5 49,500 4480 .45 .61 .78 13.7 46,900 4840 .45 .63 .80

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�048 � C33−48B/C − C23�51 − RFC or TXV Systems

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C660 1400 13.6 46,400 3740 .73 .87 .98 12.9 44,100 4000 .75 .89 1.00 12.3 41,900 4300 .76 .91 1.00 11.6 39,600 4620 .78 .94 1.00

755 1600 13.9 47,500 3780 .76 .91 1.00 13.2 45,200 4050 .78 .93 1.00 12.6 42,900 4350 .80 .95 1.00 11.9 40,600 4690 .82 .98 1.00

850 1800 14.2 48,500 3810 .79 .95 1.00 13.5 46,200 4090 .81 .97 1.00 12.9 43,900 4410 .83 .99 1.00 12.2 41,700 4770 .86 1.00 1.00

660 1400 14.5 49,400 3840 .57 .70 .83 13.8 47,000 4130 .58 .72 .86 13.1 44,600 4450 .59 .74 .88 12.3 42,100 4800 .60 .76 .90

755 1600 14.7 50,300 3880 .59 .74 .88 14.0 47,900 4170 .60 .75 .90 13.3 45,400 4490 .61 .77 .92 12.6 42,900 4850 .62 .80 .95

850 1800 15.0 51,100 3900 .61 .77 .92 14.2 48,600 4200 .62 .79 .94 13.5 46,100 4530 .63 .81 .96 12.7 43,500 4900 .65 .84 .99

660 1400 15.4 52,700 3960 .43 .55 .68 14.7 50,200 4270 .43 .56 .69 14.0 47,600 4620 .43 .57 .71 13.2 45,000 5000 .44 .59 .73

755 1600 15.7 53,600 3990 .43 .57 .71 15.0 51,100 4310 .44 .58 .73 14.2 48,500 4660 .44 .60 .75 13.4 45,800 5060 .45 .61 .77

850 1800 15.9 54,400 4010 .44 .59 .75 15.2 51,800 4340 .44 .61 .77 14.4 49,100 4700 .45 .62 .79 13.6 46,300 5100 .46 .64 .81

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�048 � C33−50/60C − C26�51/65 − TXV Systems Only � CR26�48 − RFC or TXV Systems

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C660 1400 13.4 45,800 3660 .72 .86 .98 12.8 43,700 3910 .74 .88 .99 12.2 41,500 4190 .76 .90 1.00 11.5 39,200 4500 .78 .93 1.00

755 1600 13.7 46,900 3700 .75 .90 1.00 13.1 44,700 3950 .77 .92 1.00 12.4 42,400 4240 .79 .94 1.00 11.8 40,200 4560 .81 .96 1.00

850 1800 14.0 47,800 3730 .78 .93 1.00 13.4 45,600 3990 .80 .95 1.00 12.7 43,300 4290 .82 .97 1.00 12.0 41,100 4630 .84 .99 1.00

660 1400 14.3 48,900 3770 .57 .70 .83 13.7 46,600 4040 .57 .71 .85 13.0 44,200 4340 .58 .73 .87 12.3 41,800 4670 .60 .75 .89

755 1600 14.6 49,800 3800 .58 .73 .87 13.9 47,400 4070 .59 .74 .89 13.2 45,000 4380 .60 .76 .91 12.5 42,500 4720 .62 .79 .94

850 1800 14.8 50,600 3820 .60 .76 .90 14.1 48,100 4100 .61 .78 .93 13.4 45,600 4420 .62 .80 .95 12.6 43,100 4770 .64 .82 .97

660 1400 15.3 52,200 3880 .43 .55 .67 14.6 49,800 4170 .43 .56 .69 13.9 47,300 4510 .43 .57 .70 13.1 44,800 4870 .44 .58 .72

755 1600 15.6 53,100 3910 .43 .57 .70 14.8 50,600 4210 .43 .58 .72 14.1 48,100 4550 .44 .59 .74 13.3 45,500 4920 .44 .60 .76

850 1800 15.8 53,800 3930 .44 .59 .73 15.0 51,300 4240 .44 .60 .75 14.3 48,700 4580 .45 .61 .77 13.5 46,000 4960 .45 .63 .80

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�048 � C33−60D − C23�51/65 − RFC or TXV Systems

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C660 1400 14.2 48,300 3760 .72 .86 .98 13.5 46,000 4030 .74 .88 1.00 12.8 43,600 4330 .76 .91 1.00 12.1 41,200 4660 .78 .93 1.00

755 1600 14.5 49,500 3800 .76 .90 1.00 13.8 47,000 4080 .77 .93 1.00 13.1 44,600 4390 .79 .95 1.00 12.4 42,200 4730 .82 .97 1.00

850 1800 14.8 50,500 3840 .79 .94 1.00 14.1 48,000 4120 .81 .96 1.00 13.4 45,600 4440 .83 .98 1.00 12.7 43,200 4800 .85 1.00 1.00

660 1400 15.1 51,500 3880 .57 .70 .83 14.4 49,000 4160 .58 .71 .85 13.6 46,500 4490 .59 .73 .87 12.9 43,900 4850 .60 .75 .90

755 1600 15.4 52,600 3910 .59 .73 .87 14.7 50,000 4210 .60 .75 .89 13.9 47,300 4540 .61 .77 .92 13.1 44,700 4900 .62 .79 .94

850 1800 15.6 53,400 3940 .60 .76 .91 14.9 50,800 4240 .61 .78 .93 14.1 48,100 4580 .63 .80 .96 13.3 45,400 4950 .64 .83 .98

660 1400 16.1 55,000 3990 .43 .55 .67 15.4 52,400 4310 .43 .56 .69 14.6 49,700 4670 .43 .57 .71 13.8 47,000 5060 .44 .58 .73

755 1600 16.4 56,100 4030 .43 .57 .71 15.6 53,400 4350 .44 .58 .72 14.8 50,600 4720 .44 .59 .74 14.0 47,800 5120 .44 .61 .77

850 1800 16.7 56,900 4050 .44 .59 .74 15.9 54,100 4390 .44 .60 .76 15.0 51,300 4760 .45 .61 .78 14.2 48,400 5160 .45 .63 .80

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�048 � C33−62D − C26�65EAP − CH33−62D−F − CH23�68 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

HS29 / Page 47

Page 48: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 3 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C660 1400 13.7 46,900 3730 .73 .86 .98 13.1 44,600 3990 .74 .88 1.00 12.4 42,400 4280 .76 .91 1.00 11.8 40,100 4600 .78 .93 1.00

755 1600 14.1 48,000 3770 .76 .90 1.00 13.4 45,700 4030 .77 .93 1.00 12.7 43,400 4340 .79 .95 1.00 12.0 41,100 4670 .82 .97 1.00

850 1800 14.4 49,000 3800 .79 .94 1.00 13.7 46,600 4070 .81 .96 1.00 13.0 44,300 4390 .83 .98 1.00 12.3 42,000 4740 .85 1.00 1.00

660 1400 14.7 50,000 3830 .57 .70 .83 14.0 47,600 4120 .58 .72 .85 13.2 45,100 4430 .59 .73 .87 12.5 42,600 4780 .60 .75 .90

755 1600 14.9 51,000 3870 .59 .73 .87 14.2 48,500 4160 .60 .75 .89 13.5 45,900 4480 .61 .77 .92 12.7 43,400 4840 .62 .79 .94

850 1800 15.2 51,700 3890 .60 .76 .91 14.4 49,200 4190 .62 .78 .93 13.7 46,600 4520 .63 .80 .96 12.9 44,000 4880 .64 .83 .98

660 1400 15.6 53,300 3950 .43 .55 .68 14.9 50,900 4260 .43 .56 .69 14.2 48,300 4610 .43 .57 .71 13.4 45,600 4990 .44 .58 .73

755 1600 15.9 54,300 3980 .43 .57 .71 15.2 51,700 4300 .44 .58 .73 14.4 49,100 4650 .44 .59 .75 13.6 46,400 5040 .45 .61 .77

850 1800 16.1 55,100 4010 .44 .59 .74 15.4 52,400 4330 .44 .60 .76 14.6 49,700 4690 .45 .62 .78 13.8 47,000 5080 .45 .63 .81

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−048 � CR26�60 − RFC or TXV Systems

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C660 1400 13.5 46,200 3660 .74 .87 .98 12.9 44,000 3910 .75 .89 1.00 12.3 41,800 4190 .77 .92 1.00 11.6 39,600 4500 .79 .94 1.00

755 1600 13.8 47,200 3690 .77 .91 1.00 13.2 45,000 3950 .78 .93 1.00 12.5 42,800 4240 .80 .96 1.00 11.9 40,600 4560 .83 .98 1.00

850 1800 14.1 48,200 3720 .80 .95 1.00 13.5 45,900 3990 .82 .97 1.00 12.8 43,700 4290 .84 .99 1.00 12.2 41,600 4630 .86 1.00 1.00

660 1400 14.4 49,000 3750 .57 .71 .84 13.7 46,700 4020 .58 .73 .86 13.0 44,300 4320 .59 .74 .88 12.3 41,900 4660 .60 .76 .91

755 1600 14.6 49,900 3790 .59 .74 .88 13.9 47,500 4060 .60 .76 .90 13.2 45,100 4370 .61 .78 .93 12.5 42,700 4710 .63 .80 .95

850 1800 14.9 50,700 3810 .61 .78 .92 14.1 48,200 4090 .62 .79 .94 13.4 45,800 4400 .64 .82 .96 12.7 43,300 4750 .65 .84 .98

660 1400 15.3 52,200 3860 .43 .56 .69 14.6 49,800 4150 .43 .57 .70 13.9 47,300 4480 .43 .58 .72 13.1 44,800 4850 .44 .59 .74

755 1600 15.6 53,100 3890 .43 .58 .72 14.8 50,600 4190 .44 .59 .74 14.1 48,100 4530 .44 .60 .76 13.3 45,500 4890 .45 .61 .78

850 1800 15.8 53,800 3920 .44 .60 .75 15.0 51,300 4220 .45 .61 .77 14.3 48,700 4560 .45 .62 .79 13.5 46,000 4930 .46 .64 .82

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�048 � CH33−48C−F RFC Systems − CH33−44B−F − CH23�51 − RFC or TXV Systems

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C660 1400 13.7 46,600 3700 .73 .87 .98 13.0 44,300 3960 .75 .89 1.00 12.3 42,100 4250 .77 .91 1.00 11.7 39,800 4570 .79 .94 1.00

755 1600 14.0 47,600 3740 .76 .91 1.00 13.3 45,400 4000 .78 .93 1.00 12.6 43,100 4300 .80 .95 1.00 12.0 40,900 4640 .82 .98 1.00

850 1800 14.2 48,600 3770 .80 .95 1.00 13.6 46,300 4050 .81 .97 1.00 12.9 44,100 4360 .84 .99 1.00 12.3 41,900 4710 .86 1.00 1.00

660 1400 14.5 49,500 3800 .57 .71 .84 13.8 47,100 4080 .58 .72 .86 13.1 44,700 4390 .59 .74 .88 12.4 42,300 4740 .60 .76 .91

755 1600 14.8 50,500 3840 .59 .74 .88 14.1 48,000 4120 .60 .76 .90 13.3 45,500 4440 .61 .78 .93 12.6 43,000 4790 .63 .80 .95

850 1800 15.0 51,200 3860 .61 .77 .92 14.3 48,700 4150 .62 .79 .94 13.5 46,200 4480 .63 .81 .96 12.8 43,700 4830 .65 .84 .98

660 1400 15.5 52,800 3920 .43 .55 .68 14.7 50,300 4220 .43 .56 .70 14.0 47,800 4560 .43 .57 .71 13.2 45,200 4940 .44 .59 .73

755 1600 15.7 53,700 3950 .43 .58 .72 15.0 51,200 4260 .44 .59 .73 14.2 48,600 4600 .44 .60 .75 13.5 45,900 4990 .45 .61 .78

850 1800 15.9 54,400 3970 .44 .60 .75 15.2 51,900 4290 .45 .61 .77 14.4 49,200 4640 .45 .62 .79 13.6 46,500 5020 .46 .64 .81

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�048 � CH33−50C−F TXV Systems − CH33−60D−F RFC Systems − CH23�65 − RFC or TXV Systems

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C495 1050 12.5 42,600 3530 .68 .80 .90 11.9 40,600 3760 .69 .81 .92 11.3 38,600 4020 .70 .83 .94 10.7 36,600 4310 .72 .85 .97

590 1250 12.9 44,100 3580 .71 .84 .95 12.3 42,000 3820 .72 .86 .97 11.7 39,900 4090 .74 .88 .99 11.1 37,800 4400 .75 .90 1.00

685 1450 13.3 45,300 3620 .74 .88 .99 12.6 43,100 3870 .75 .90 1.00 12.0 41,000 4150 .77 .92 1.00 11.4 38,800 4460 .79 .94 1.00

495 1050 13.4 45,600 3640 .54 .65 .76 12.7 43,500 3890 .55 .66 .78 12.1 41,400 4170 .55 .67 .79 11.5 39,200 4490 .56 .69 .81

590 1250 13.8 47,100 3680 .56 .68 .80 13.2 44,900 3950 .56 .69 .82 12.5 42,600 4240 .57 .71 .84 11.8 40,300 4560 .58 .73 .86

685 1450 14.1 48,100 3720 .57 .71 .84 13.5 45,900 3990 .58 .73 .87 12.7 43,500 4290 .59 .74 .89 12.0 41,100 4620 .60 .77 .91

495 1050 14.3 48,800 3750 .42 .52 .62 13.7 46,600 4020 .42 .53 .64 13.0 44,300 4340 .42 .54 .65 12.3 42,000 4680 .42 .54 .66

590 1250 14.7 50,200 3790 .42 .54 .66 14.1 48,000 4080 .42 .55 .67 13.4 45,600 4400 .43 .56 .68 12.7 43,200 4760 .43 .57 .70

685 1450 15.0 51,300 3830 .43 .56 .69 14.4 49,000 4120 .43 .57 .70 13.6 46,500 4450 .43 .58 .72 12.9 44,000 4820 .44 .59 .74

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−048 � CB30M−41 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

HS29 / Page 48

Page 49: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 3 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C595 1265 12.7 43,300 3550 .71 .84 .95 12.1 41,300 3790 .72 .86 .97 11.5 39,200 4060 .74 .88 .99 10.9 37,100 4360 .75 .90 1.00

660 1400 13.0 44,200 3580 .73 .87 .98 12.3 42,100 3830 .74 .89 .99 11.7 40,000 4100 .76 .91 1.00 11.1 37,800 4410 .78 .93 1.00

730 1545 13.2 44,900 3610 .75 .90 1.00 12.5 42,800 3860 .77 .92 1.00 11.9 40,700 4140 .79 .94 1.00 11.3 38,500 4450 .81 .96 1.00

595 1265 13.6 46,300 3650 .56 .68 .80 12.9 44,100 3910 .57 .69 .82 12.3 41,900 4200 .57 .71 .84 11.6 39,600 4530 .58 .73 .87

660 1400 13.8 47,000 3680 .57 .70 .83 13.1 44,800 3940 .58 .72 .85 12.5 42,500 4240 .59 .74 .88 11.8 40,200 4570 .60 .76 .90

730 1545 14.0 47,700 3700 .58 .73 .86 13.3 45,400 3970 .59 .74 .89 12.6 43,100 4270 .60 .76 .91 11.9 40,700 4610 .62 .78 .93

595 1265 14.5 49,400 3760 .42 .54 .66 13.8 47,100 4050 .43 .55 .67 13.1 44,800 4370 .43 .56 .68 12.4 42,400 4720 .43 .57 .70

660 1400 14.7 50,100 3790 .43 .55 .68 14.0 47,800 4080 .43 .56 .69 13.3 45,400 4400 .43 .57 .71 12.6 43,000 4760 .44 .58 .73

730 1545 14.9 50,800 3810 .43 .57 .70 14.2 48,400 4100 .43 .58 .72 13.5 46,000 4430 .44 .59 .74 12.7 43,500 4800 .44 .60 .76

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−048 � CB31MV−41 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C615 1300 13.3 45,400 3660 .72 .85 .96 12.7 43,200 3910 .73 .87 .98 12.0 41,100 4190 .74 .89 .99 11.4 38,900 4490 .76 .91 1.00

685 1450 13.6 46,300 3690 .74 .88 .99 12.9 44,000 3940 .75 .90 1.00 12.3 41,800 4230 .77 .92 1.00 11.6 39,600 4550 .79 .94 1.00

755 1600 13.8 47,000 3720 .76 .91 1.00 13.1 44,800 3980 .78 .93 1.00 12.5 42,600 4270 .80 .95 1.00 11.8 40,300 4590 .82 .97 1.00

615 1300 14.2 48,400 3760 .56 .69 .81 13.5 46,100 4030 .57 .70 .83 12.8 43,800 4340 .58 .72 .85 12.1 41,400 4670 .59 .74 .88

685 1450 14.4 49,200 3790 .57 .71 .84 13.7 46,800 4060 .58 .73 .87 13.0 44,500 4370 .59 .74 .89 12.3 42,000 4710 .60 .77 .91

755 1600 14.6 49,800 3820 .59 .73 .87 13.9 47,500 4090 .60 .75 .90 13.2 45,000 4400 .61 .77 .92 12.5 42,500 4750 .62 .79 .94

615 1300 15.1 51,600 3880 .42 .54 .66 14.4 49,200 4170 .43 .55 .68 13.7 46,800 4500 .43 .56 .69 13.0 44,300 4870 .43 .57 .71

685 1450 15.4 52,400 3900 .43 .56 .69 14.7 50,000 4200 .43 .57 .70 13.9 47,500 4540 .43 .58 .72 13.2 45,000 4910 .44 .59 .74

755 1600 15.6 53,100 3920 .43 .57 .71 14.8 50,600 4230 .44 .58 .73 14.1 48,100 4570 .44 .59 .75 13.3 45,500 4940 .45 .61 .77

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−048 � CB29M−51 − CB28UH−048 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C590 1250 13.2 44,900 3600 .71 .84 .95 12.5 42,700 3840 .72 .86 .97 11.9 40,600 4110 .74 .88 .99 11.3 38,400 4420 .75 .90 1.00

660 1400 13.4 45,800 3630 .73 .87 .98 12.8 43,600 3880 .74 .89 .99 12.1 41,400 4160 .76 .91 1.00 11.5 39,200 4470 .78 .93 1.00

730 1550 13.7 46,600 3660 .75 .90 1.00 13.0 44,400 3910 .77 .92 1.00 12.4 42,200 4200 .79 .94 1.00 11.7 39,900 4520 .81 .96 1.00

590 1250 14.0 47,900 3700 .56 .68 .80 13.4 45,600 3960 .56 .69 .82 12.7 43,300 4260 .57 .71 .84 12.0 41,000 4590 .58 .73 .86

660 1400 14.3 48,700 3730 .57 .70 .83 13.6 46,400 4000 .58 .72 .85 12.9 44,000 4300 .59 .74 .88 12.2 41,600 4630 .60 .76 .90

730 1550 14.5 49,400 3760 .58 .73 .86 13.8 47,100 4030 .59 .74 .89 13.1 44,600 4330 .60 .76 .91 12.4 42,200 4670 .62 .78 .93

590 1250 15.0 51,100 3810 .42 .54 .66 14.3 48,800 4100 .42 .55 .67 13.6 46,400 4430 .43 .56 .68 12.9 43,900 4780 .43 .57 .70

660 1400 15.2 51,900 3840 .43 .55 .68 14.5 49,600 4130 .43 .56 .69 13.8 47,100 4460 .43 .57 .71 13.1 44,600 4830 .44 .58 .73

730 1550 15.4 52,600 3860 .43 .57 .70 14.7 50,200 4160 .43 .58 .72 14.0 47,700 4500 .44 .59 .74 13.2 45,100 4860 .44 .60 .76

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−048 � CB30M−46 − CB30U−41/46 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C660 1400 13.5 46,200 3670 .73 .87 .98 12.9 44,100 3920 .74 .89 .99 12.3 41,900 4200 .76 .91 1.00 11.6 39,600 4510 .78 .93 1.00

755 1600 13.9 47,300 3700 .76 .91 1.00 13.2 45,100 3960 .78 .93 1.00 12.5 42,800 4250 .80 .95 1.00 11.9 40,600 4580 .82 .97 1.00

850 1800 14.1 48,200 3730 .79 .94 1.00 13.5 46,000 4000 .81 .96 1.00 12.8 43,700 4300 .83 .98 1.00 12.2 41,500 4640 .85 1.00 1.00

660 1400 14.4 49,200 3770 .57 .70 .83 13.7 46,900 4040 .58 .72 .85 13.0 44,500 4340 .59 .74 .88 12.3 42,100 4680 .60 .76 .90

755 1600 14.7 50,100 3800 .59 .73 .87 14.0 47,800 4080 .60 .75 .90 13.3 45,300 4390 .61 .77 .92 12.5 42,800 4730 .62 .79 .94

850 1800 14.9 50,900 3820 .60 .77 .91 14.2 48,400 4110 .62 .78 .93 13.5 45,900 4420 .63 .81 .96 12.7 43,400 4770 .64 .83 .98

660 1400 15.4 52,500 3880 .43 .55 .68 14.7 50,100 4170 .43 .56 .69 14.0 47,600 4510 .43 .57 .71 13.2 45,000 4880 .44 .58 .73

755 1600 15.6 53,400 3910 .43 .57 .71 14.9 50,900 4210 .44 .58 .73 14.2 48,400 4550 .44 .59 .75 13.4 45,800 4920 .45 .61 .77

850 1800 15.9 54,100 3930 .44 .59 .74 15.1 51,600 4240 .44 .60 .76 14.3 48,900 4580 .45 .62 .78 13.6 46,300 4960 .45 .63 .81

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−048 � CB29M−65 − CB28UH−060 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

HS29 / Page 49

Page 50: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 3 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C660 1400 13.5 46,000 3660 .73 .86 .98 12.8 43,800 3910 .74 .88 1.00 12.2 41,500 4200 .76 .91 1.00 11.5 39,200 4530 .78 .93 1.00

755 1600 13.8 47,100 3700 .76 .90 1.00 13.1 44,800 3960 .77 .93 1.00 12.5 42,500 4260 .79 .95 1.00 11.8 40,200 4590 .82 .97 1.00

850 1800 14.1 48,000 3730 .79 .94 1.00 13.4 45,700 4000 .81 .96 1.00 12.7 43,400 4310 .83 .98 1.00 12.1 41,200 4660 .85 1.00 1.00

660 1400 14.4 49,000 3760 .57 .70 .83 13.7 46,700 4050 .58 .71 .85 13.0 44,200 4360 .59 .73 .87 12.3 41,800 4700 .60 .75 .90

755 1600 14.7 50,000 3800 .59 .73 .87 13.9 47,500 4080 .60 .75 .89 13.2 45,100 4410 .61 .77 .92 12.5 42,500 4760 .62 .79 .94

850 1800 14.9 50,800 3820 .60 .76 .91 14.2 48,300 4120 .62 .78 .93 13.4 45,700 4440 .63 .80 .96 12.7 43,200 4800 .64 .83 .98

660 1400 15.3 52,300 3880 .43 .55 .67 14.6 49,900 4190 .43 .56 .69 13.9 47,300 4530 .43 .57 .71 13.1 44,800 4910 .44 .58 .73

755 1600 15.6 53,300 3910 .43 .57 .71 14.9 50,800 4220 .44 .58 .72 14.1 48,100 4580 .44 .59 .74 13.3 45,500 4960 .45 .61 .77

850 1800 15.9 54,100 3940 .44 .59 .74 15.1 51,500 4260 .44 .60 .76 14.3 48,800 4610 .45 .62 .78 13.5 46,100 5000 .45 .63 .80

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−048 � CB30M−51 − CB30U−51 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C670 1425 13.5 46,000 3660 .73 .87 .99 12.8 43,800 3920 .75 .89 1.00 12.2 41,500 4220 .77 .92 1.00 11.5 39,200 4540 .79 .94 1.00

765 1625 13.7 46,900 3700 .76 .91 1.00 13.1 44,700 3960 .78 .93 1.00 12.4 42,400 4260 .80 .95 1.00 11.8 40,100 4600 .82 .98 1.00

850 1805 14.0 47,800 3730 .79 .94 1.00 13.3 45,500 4000 .81 .96 1.00 12.7 43,200 4310 .83 .98 1.00 12.0 41,000 4660 .85 1.00 1.00

670 1425 14.4 49,000 3770 .57 .71 .84 13.7 46,600 4050 .58 .72 .86 13.0 44,200 4370 .59 .74 .88 12.2 41,700 4710 .60 .76 .91

765 1625 14.6 49,900 3800 .59 .74 .88 13.9 47,400 4090 .60 .75 .90 13.2 44,900 4410 .61 .77 .92 12.4 42,400 4760 .62 .80 .95

850 1805 14.8 50,500 3820 .60 .76 .91 14.1 48,000 4110 .62 .78 .93 13.3 45,500 4440 .63 .81 .96 12.6 43,000 4800 .64 .83 .98

670 1425 15.3 52,300 3880 .43 .55 .68 14.6 49,800 4190 .43 .56 .70 13.9 47,300 4540 .43 .57 .72 13.1 44,700 4920 .44 .59 .74

765 1625 15.6 53,100 3910 .43 .57 .71 14.8 50,600 4230 .44 .58 .73 14.1 48,000 4580 .44 .60 .75 13.3 45,300 4960 .45 .61 .77

850 1805 15.8 53,800 3930 .44 .59 .74 15.0 51,200 4250 .44 .60 .76 14.2 48,500 4610 .45 .62 .78 13.4 45,800 5000 .45 .63 .81

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−048 � CB31MV−51 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C660 1400 13.6 46,500 3720 .73 .86 .98 13.0 44,300 3980 .74 .88 1.00 12.3 42,000 4280 .76 .91 1.00 11.6 39,700 4610 .78 .93 1.00

755 1600 14.0 47,600 3760 .76 .90 1.00 13.3 45,300 4030 .77 .93 1.00 12.6 43,000 4340 .79 .95 1.00 11.9 40,700 4670 .82 .97 1.00

850 1800 14.2 48,600 3790 .79 .94 1.00 13.5 46,200 4070 .81 .96 1.00 12.9 43,900 4390 .83 .98 1.00 12.2 41,600 4750 .85 1.00 1.00

660 1400 14.5 49,600 3830 .57 .70 .83 13.8 47,200 4120 .58 .71 .85 13.1 44,700 4440 .59 .73 .87 12.4 42,200 4790 .60 .75 .90

755 1600 14.8 50,600 3870 .59 .73 .87 14.1 48,100 4160 .60 .75 .89 13.4 45,600 4490 .61 .77 .92 12.6 43,000 4840 .62 .79 .94

850 1800 15.1 51,400 3890 .60 .76 .91 14.3 48,800 4190 .61 .78 .93 13.6 46,300 4520 .63 .80 .96 12.8 43,700 4890 .64 .83 .98

660 1400 15.5 53,000 3950 .43 .55 .67 14.8 50,400 4260 .43 .56 .69 14.0 47,900 4610 .43 .57 .71 13.3 45,300 5000 .44 .58 .73

755 1600 15.8 53,900 3980 .43 .57 .71 15.1 51,400 4300 .44 .58 .72 14.3 48,700 4660 .44 .59 .74 13.5 46,000 5050 .44 .61 .77

850 1800 16.0 54,700 4010 .44 .59 .74 15.3 52,100 4330 .44 .60 .76 14.5 49,400 4700 .45 .61 .78 13.7 46,600 5100 .45 .63 .80

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−048 � CB30M−65 − CB30U−65 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C670 1425 13.8 47,000 3740 .73 .87 .99 13.1 44,700 4010 .75 .89 1.00 12.4 42,400 4300 .77 .92 1.00 11.8 40,100 4630 .79 .94 1.00

765 1625 14.0 47,900 3770 .76 .91 1.00 13.4 45,600 4050 .78 .93 1.00 12.7 43,300 4350 .80 .95 1.00 12.0 41,000 4690 .82 .98 1.00

850 1805 14.3 48,800 3800 .79 .94 1.00 13.6 46,400 4080 .81 .96 1.00 12.9 44,100 4400 .83 .98 1.00 12.3 41,800 4760 .85 1.00 1.00

670 1425 14.7 50,000 3850 .57 .71 .84 14.0 47,600 4130 .58 .72 .86 13.2 45,100 4460 .59 .74 .88 12.5 42,600 4810 .60 .76 .91

765 1625 14.9 50,900 3880 .59 .74 .88 14.2 48,400 4170 .60 .75 .90 13.5 45,900 4500 .61 .77 .92 12.7 43,300 4860 .62 .80 .95

850 1805 15.1 51,600 3900 .60 .76 .91 14.4 49,000 4200 .62 .78 .93 13.6 46,500 4530 .63 .81 .96 12.9 43,900 4900 .64 .83 .98

670 1425 15.6 53,400 3960 .43 .55 .68 14.9 50,900 4280 .43 .56 .70 14.2 48,300 4630 .43 .57 .72 13.4 45,600 5020 .44 .59 .74

765 1625 15.9 54,200 3990 .43 .57 .71 15.2 51,700 4310 .44 .58 .73 14.4 49,000 4670 .44 .60 .75 13.6 46,300 5070 .45 .61 .77

850 1805 16.1 54,900 4010 .44 .59 .74 15.3 52,300 4340 .44 .60 .76 14.5 49,600 4710 .45 .62 .78 13.7 46,800 5110 .45 .63 .81

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−048 � CB31MV−65 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

HS29 / Page 50

Page 51: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 3 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C660 1400 13.2 44,900 3710 .73 .86 .98 12.5 42,700 3960 .74 .88 .99 11.9 40,500 4260 .76 .90 1.00 11.2 38,300 4570 .78 .93 1.00

755 1600 13.5 46,000 3750 .76 .90 1.00 12.8 43,800 4010 .77 .92 1.00 12.2 41,500 4310 .79 .95 1.00 11.5 39,300 4640 .81 .97 1.00

850 1800 13.7 46,900 3780 .79 .94 1.00 13.1 44,700 4050 .80 .96 1.00 12.5 42,500 4360 .83 .98 1.00 11.8 40,300 4710 .85 1.00 1.00

660 1400 14.0 47,800 3820 .57 .70 .83 13.4 45,600 4090 .58 .71 .85 12.7 43,200 4410 .59 .73 .87 12.0 40,800 4750 .60 .75 .90

755 1600 14.3 48,800 3850 .58 .73 .87 13.6 46,500 4140 .59 .75 .89 12.9 44,000 4460 .61 .77 .92 12.2 41,600 4810 .62 .79 .94

850 1800 14.5 49,600 3880 .60 .76 .91 13.8 47,200 4170 .61 .78 .93 13.1 44,700 4490 .63 .80 .95 12.4 42,200 4850 .64 .83 .98

660 1400 15.0 51,100 3930 .43 .55 .67 14.3 48,700 4230 .43 .56 .69 13.5 46,200 4580 .43 .57 .71 12.8 43,700 4960 .44 .58 .72

755 1600 15.2 52,000 3960 .43 .57 .71 14.5 49,600 4270 .44 .58 .72 13.8 47,100 4630 .44 .59 .74 13.0 44,500 5010 .44 .61 .76

850 1800 15.5 52,800 3990 .44 .59 .74 14.7 50,300 4310 .44 .60 .76 14.0 47,700 4660 .45 .61 .78 13.2 45,000 5050 .45 .63 .80

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−048 � CVP10�51/EC10Q4 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C660 1400 13.5 46,000 3720 .73 .87 .99 12.8 43,800 3980 .75 .89 1.00 12.2 41,600 4270 .77 .92 1.00 11.5 39,300 4590 .79 .94 1.00

755 1600 13.8 47,100 3760 .77 .92 1.00 13.2 44,900 4020 .78 .94 1.00 12.5 42,600 4330 .80 .96 1.00 11.8 40,400 4660 .83 .98 1.00

850 1800 14.1 48,100 3790 .80 .95 1.00 13.5 45,900 4070 .82 .97 1.00 12.8 43,600 4390 .84 .99 1.00 12.2 41,500 4740 .86 1.00 1.00

660 1400 14.3 48,900 3820 .57 .71 .84 13.7 46,600 4100 .58 .72 .86 13.0 44,200 4420 .59 .74 .88 12.3 41,800 4760 .60 .76 .91

755 1600 14.6 49,900 3860 .59 .74 .88 13.9 47,500 4140 .60 .76 .91 13.2 45,000 4460 .61 .78 .93 12.5 42,500 4820 .63 .80 .95

850 1800 14.9 50,700 3880 .61 .78 .92 14.1 48,200 4180 .62 .80 .95 13.4 45,700 4500 .64 .82 .97 12.7 43,200 4870 .65 .84 .99

660 1400 15.3 52,200 3940 .43 .56 .68 14.6 49,800 4240 .43 .57 .70 13.8 47,200 4590 .43 .58 .72 13.1 44,700 4970 .44 .59 .74

755 1600 15.6 53,200 3970 .43 .58 .72 14.8 50,600 4280 .44 .59 .74 14.1 48,000 4630 .44 .60 .76 13.3 45,400 5020 .45 .61 .78

850 1800 15.8 53,900 3990 .44 .60 .75 15.0 51,300 4310 .45 .61 .77 14.3 48,700 4670 .45 .63 .80 13.5 46,000 5060 .46 .64 .82

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�048 � CVP10�65/EC10Q5 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

RATINGS − 1 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

Outdoor Air Temperature Entering Outdoor Coil

Total85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)

EnteringWet BulbTempera�

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Tempera�ture

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

HS29−060 � C33−50/60C − C26−51/65 COOLING CAPACITY − TXV Systems Only

63�F1500 710 54.7 16.0 4.72 .70 .83 .94 52.8 15.5 5.33 .71 .84 .95 50.8 14.9 6.04 .72 .85 .97 48.8 14.3 6.83 .73 .87 .98

63�F(17�C)

1700 800 56.0 16.4 4.71 .72 .86 .97 54.1 15.9 5.33 .73 .87 .99 52.0 15.2 6.04 .75 .89 1.00 49.9 14.6 6.83 .76 .91 1.00(17�C)

1900 895 57.1 16.7 4.73 .75 .89 1.00 55.2 16.2 5.34 .76 .91 1.00 53.1 15.6 6.05 .77 .92 1.00 50.9 14.9 6.85 .79 .94 1.00

67�F1500 710 58.3 17.1 4.76 .55 .68 .79 56.3 16.5 5.37 .56 .68 .81 54.2 15.9 6.07 .56 .69 .82 52.0 15.2 6.89 .57 .71 .84

67�F(19�C)

1700 800 59.5 17.4 4.78 .57 .70 .83 57.4 16.8 5.40 .57 .71 .84 55.2 16.2 6.11 .58 .72 .86 52.9 15.5 6.94 .59 .74 .87(19�C)

1900 895 60.4 17.7 4.80 .58 .73 .86 58.3 17.1 5.42 .59 .74 .88 56.1 16.4 6.14 .60 .75 .89 53.7 15.7 6.96 .61 .77 .91

71�F1500 710 62.2 18.2 4.84 .42 .54 .65 60.0 17.6 5.47 .43 .54 .66 57.8 16.9 6.20 .43 .55 .67 55.5 16.3 7.02 .43 .55 .68

71�F(22�C)

1700 800 63.3 18.6 4.87 .43 .55 .67 61.1 17.9 5.50 .43 .56 .69 58.8 17.2 6.23 .43 .56 .70 56.4 16.5 7.07 .43 .57 .71(22�C)

1900 895 64.3 18.8 4.89 .43 .57 .70 62.0 18.2 5.53 .43 .57 .71 59.6 17.5 6.26 .44 .58 .73 57.2 16.8 7.11 .44 .59 .74

HS29−060 − C33−60D − C23−51/65 COOLING CAPACITY − RFC or TXV Systems

63�F1700 800 57.8 16.9 4.65 .72 .85 .97 55.8 16.4 5.26 .73 .87 .98 53.7 15.7 5.96 .74 .88 .99 51.5 15.1 6.74 .75 .90 1.00

63�F(17�C)

1900 895 59.0 17.3 4.65 .74 .88 .99 56.9 16.7 5.26 .75 .90 1.00 54.8 16.1 5.96 .76 .91 1.00 52.6 15.4 6.74 .78 .93 1.00(17�C)

2100 990 59.9 17.6 4.67 .76 .91 1.00 57.9 17.0 5.27 .78 .93 1.00 55.7 16.3 5.97 .79 .94 1.00 53.5 15.7 6.75 .81 .96 1.00

67�F1700 800 61.6 18.1 4.70 .56 .69 .82 59.5 17.4 5.31 .57 .70 .83 57.2 16.8 6.01 .58 .71 .85 54.9 16.1 6.80 .58 .72 .86

67�F(19�C)

1900 895 62.6 18.3 4.72 .58 .71 .85 60.4 17.7 5.33 .58 .73 .86 58.1 17.0 6.02 .59 .74 .88 55.6 16.3 6.84 .60 .76 .90(19�C)

2100 990 63.4 18.6 4.73 .59 .74 .88 61.1 17.9 5.34 .60 .75 .90 58.8 17.2 6.05 .61 .77 .91 56.3 16.5 6.86 .61 .78 .93

71�F1700 800 65.6 19.2 4.78 .42 .55 .67 63.3 18.6 5.40 .43 .55 .68 61.0 17.9 6.12 .43 .56 .69 58.5 17.1 6.93 .43 .57 .70

71�F(22�C)

1900 895 66.6 19.5 4.80 .43 .56 .69 64.3 18.8 5.43 .43 .57 .70 61.8 18.1 6.15 .43 .58 .72 59.3 17.4 6.97 .44 .58 .73(22�C)

2100 990 67.4 19.8 4.82 .43 .57 .72 65.0 19.0 5.45 .44 .58 .73 62.5 18.3 6.16 .44 .59 .74 59.9 17.6 7.00 .44 .60 .76

HS29−060 � C33−62D − C26−65EAP COOLING CAPACITY − TXV Systems Only

63�F1600 755 60.6 17.8 4.80 .71 .84 .95 58.5 17.1 5.43 .72 .85 .97 56.3 16.5 6.15 .73 .87 .98 54.0 15.8 6.96 .74 .88 .99

63�F(17�C)

1800 850 61.9 18.1 4.83 .73 .87 .98 59.7 17.5 5.46 .74 .88 .99 57.4 16.8 6.18 .75 .90 1.00 55.1 16.1 6.99 .77 .92 1.00(17�C)

2000 945 62.9 18.4 4.86 .75 .90 1.00 60.8 17.8 5.48 .77 .91 1.00 58.5 17.1 6.20 .78 .93 1.00 56.1 16.4 7.03 .80 .95 1.00

67�F1600 755 64.6 18.9 4.89 .56 .68 .80 62.3 18.3 5.52 .56 .69 .82 59.9 17.6 6.25 .57 .70 .83 57.4 16.8 7.09 .58 .71 .85

67�F(19�C)

1800 850 65.7 19.3 4.91 .57 .71 .84 63.4 18.6 5.55 .58 .72 .85 60.9 17.8 6.28 .58 .73 .87 58.4 17.1 7.12 .59 .74 .89(19�C)

2000 945 66.7 19.5 4.93 .58 .73 .87 64.3 18.8 5.58 .59 .74 .88 61.8 18.1 6.30 .60 .76 .90 59.2 17.3 7.15 .61 .77 .92

71�F1600 755 68.8 20.2 4.98 .42 .54 .66 66.4 19.5 5.62 .42 .55 .67 63.9 18.7 6.37 .43 .55 .68 61.3 18.0 7.24 .43 .56 .69

71�F(22�C)

1800 850 70.0 20.5 5.01 .43 .55 .68 67.5 19.8 5.65 .43 .56 .69 64.9 19.0 6.41 .43 .57 .71 62.3 18.3 7.27 .43 .58 .72(22�C)

2000 945 71.0 20.8 5.02 .43 .57 .71 68.4 20.0 5.69 .43 .58 .72 65.8 19.3 6.44 .44 .59 .73 63.0 18.5 7.30 .44 .60 .75

HS29 / Page 51

Page 52: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 1 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

Outdoor Air Temperature Entering Outdoor Coil

Total85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)

EnteringWet BulbTempera�

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Tempera�ture

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

HS29−060 � C33−50/60C with G60UHV−60C−090 COOLING CAPACITY − TXV Systems Only

63�F1560 735 57.5 16.9 4.47 .71 .84 .96 55.5 16.3 5.04 .72 .86 .97 53.4 15.6 5.67 .73 .87 .98 51.1 15.0 6.37 .74 .89 .99

63�F(17�C)

1760 830 58.7 17.2 4.46 .73 .87 .98 56.7 16.6 5.03 .74 .89 .99 54.6 16.0 5.67 .76 .90 1.00 52.3 15.3 6.36 .77 .92 1.00(17�C)

1960 925 59.8 17.5 4.46 .76 .90 1.00 57.8 16.9 5.03 .77 .92 1.00 55.6 16.3 5.66 .78 .93 1.00 53.3 15.6 6.36 .80 .95 1.00

67�F1560 735 61.4 18.0 4.46 .56 .68 .81 59.4 17.4 5.02 .56 .69 .82 57.2 16.8 5.66 .57 .70 .83 54.8 16.1 6.35 .58 .72 .85

67�F(19�C)

1760 830 62.6 18.3 4.45 .57 .71 .84 60.5 17.7 5.02 .58 .72 .85 58.2 17.1 5.65 .58 .73 .87 55.8 16.4 6.34 .59 .74 .89(19�C)

1960 925 63.6 18.6 4.45 .58 .73 .87 61.4 18.0 5.01 .59 .74 .89 59.0 17.3 5.64 .60 .76 .90 56.6 16.6 6.33 .61 .77 .92

71�F1560 735 65.7 19.3 4.46 .42 .54 .66 63.6 18.6 5.01 .42 .54 .67 61.3 18.0 5.63 .43 .55 .68 58.8 17.2 6.33 .43 .56 .69

71�F(22�C)

1760 830 66.8 19.6 4.47 .43 .55 .68 64.6 18.9 5.03 .43 .56 .69 62.2 18.2 5.65 .43 .57 .70 59.8 17.5 6.34 .43 .58 .72(22�C)

1960 925 67.7 19.8 4.49 .43 .57 .71 65.4 19.2 5.05 .43 .58 .72 63.0 18.5 5.67 .44 .59 .73 60.5 17.7 6.35 .44 .60 .75

HS29−060 � C33−60D−2 with G60UHV−60D−135 COOLING CAPACITY − TXV Systems Only

63�F1560 735 57.4 16.8 4.47 .71 .84 .96 55.5 16.3 5.04 .72 .85 .97 53.3 15.6 5.67 .73 .87 .98 51.1 15.0 6.37 .74 .88 .99

63�F(17�C)

1760 830 58.7 17.2 4.46 .73 .87 .98 56.7 16.6 5.03 .74 .89 .99 54.5 16.0 5.67 .75 .90 1.00 52.2 15.3 6.36 .77 .92 1.00(17�C)

1960 925 59.8 17.5 4.46 .75 .90 1.00 57.7 16.9 5.03 .77 .92 1.00 55.6 16.3 5.66 .78 .93 1.00 53.3 15.6 6.36 .80 .95 1.00

67�F1560 735 61.5 18.0 4.46 .56 .68 .80 59.4 17.4 5.02 .56 .69 .82 57.1 16.7 5.65 .57 .70 .83 54.8 16.1 6.35 .58 .71 .85

67�F(19�C)

1760 830 62.7 18.4 4.45 .57 .70 .84 60.5 17.7 5.02 .58 .72 .85 58.2 17.1 5.65 .58 .73 .87 55.8 16.4 6.34 .59 .74 .89(19�C)

1960 925 63.6 18.6 4.45 .58 .73 .87 61.4 18.0 5.01 .59 .74 .88 59.0 17.3 5.64 .60 .76 .90 56.6 16.6 6.33 .61 .77 .92

71�F1560 735 65.7 19.3 4.48 .42 .54 .66 63.5 18.6 5.04 .42 .54 .66 61.2 17.9 5.66 .43 .55 .67 58.8 17.2 6.34 .43 .56 .69

71�F(22�C)

1760 830 66.8 19.6 4.50 .43 .55 .68 64.5 18.9 5.06 .43 .56 .69 62.2 18.2 5.68 .43 .57 .70 59.7 17.5 6.36 .43 .58 .72(22�C)

1960 925 67.7 19.8 4.52 .43 .57 .70 65.4 19.2 5.07 .43 .58 .72 63.0 18.5 5.70 .44 .58 .73 60.4 17.7 6.37 .44 .59 .75

HS29−060 � C33−62D−2 with G60UHV−60D−135 COOLING CAPACITY − TXV Systems Only

63�F1560 735 59.0 17.3 4.47 .71 .84 .96 56.9 16.7 5.03 .72 .86 .97 54.7 16.0 5.67 .73 .87 .99 52.4 15.4 6.37 .75 .89 1.00

63�F(17�C)

1760 830 60.3 17.7 4.46 .74 .88 .99 58.2 17.1 5.03 .75 .89 1.00 56.0 16.4 5.66 .76 .91 1.00 53.7 15.7 6.36 .78 .93 1.00(17�C)

1960 925 61.5 18.0 4.46 .76 .91 1.00 59.4 17.4 5.02 .77 .92 1.00 57.1 16.7 5.66 .79 .94 1.00 54.8 16.1 6.35 .81 .96 1.00

67�F1560 735 63.1 18.5 4.46 .56 .69 .81 60.9 17.8 5.02 .56 .69 .82 58.6 17.2 5.65 .57 .71 .84 56.2 16.5 6.34 .58 .72 .85

67�F(19�C)

1760 830 64.2 18.8 4.48 .57 .71 .84 62.0 18.2 5.04 .58 .72 .86 59.6 17.5 5.66 .59 .74 .88 57.2 16.8 6.34 .60 .75 .89(19�C)

1960 925 65.2 19.1 4.50 .59 .74 .88 62.9 18.4 5.06 .60 .75 .89 60.5 17.7 5.67 .60 .76 .91 58.0 17.0 6.36 .61 .78 .93

71�F1560 735 67.2 19.7 4.53 .43 .54 .66 65.0 19.0 5.09 .42 .55 .67 62.6 18.3 5.71 .43 .55 .68 60.0 17.6 6.40 .43 .56 .70

71�F(22�C)

1760 830 68.4 20.0 4.55 .43 .56 .69 66.0 19.3 5.11 .43 .57 .70 63.6 18.6 5.74 .43 .57 .71 61.0 17.9 6.42 .44 .58 .73(22�C)

1960 925 69.3 20.3 4.56 .43 .57 .71 66.9 19.6 5.13 .44 .58 .73 64.4 18.9 5.76 .44 .59 .74 61.8 18.1 6.44 .44 .60 .76

HS29−060 − CR26−48 COOLING CAPACITY − TXV Systems Only

63�F1200 565 50.7 14.9 4.74 .66 .77 .88 49.0 14.4 5.35 .67 .78 .89 47.2 13.8 6.06 .68 .79 .90 45.3 13.3 6.84 .69 .81 .92

63�F(17�C)

1400 660 52.3 15.3 4.74 .68 .80 .91 50.5 14.8 5.35 .69 .81 .93 48.7 14.3 6.06 .70 .83 .94 46.7 13.7 6.84 .71 .84 .96(17�C)

1600 755 53.6 15.7 4.73 .70 .83 .94 51.8 15.2 5.35 .71 .85 .96 49.9 14.6 6.05 .72 .86 .97 47.9 14.0 6.84 .74 .87 .99

67�F1200 565 54.4 15.9 4.73 .54 .64 .74 52.6 15.4 5.34 .54 .64 .75 50.8 14.9 6.05 .54 .65 .76 48.8 14.3 6.85 .55 .66 .77

67�F(19�C)

1400 660 56.1 16.4 4.72 .55 .66 .77 54.2 15.9 5.34 .55 .66 .78 52.2 15.3 6.04 .55 .67 .79 50.2 14.7 6.85 .56 .68 .80(19�C)

1600 755 57.4 16.8 4.71 .56 .68 .80 55.5 16.3 5.33 .56 .68 .81 53.4 15.6 6.04 .57 .69 .82 51.2 15.0 6.85 .57 .71 .84

71�F1200 565 58.3 17.1 4.71 .42 .51 .61 56.4 16.5 5.33 .42 .52 .61 54.5 16.0 6.04 .42 .52 .62 52.4 15.4 6.84 .42 .52 .63

71�F(22�C)

1400 660 59.9 17.6 4.75 .42 .52 .63 58.0 17.0 5.37 .42 .53 .64 55.9 16.4 6.08 .42 .53 .65 53.7 15.7 6.89 .42 .54 .66(22�C)

1600 755 61.2 17.9 4.78 .42 .54 .65 59.2 17.3 5.40 .42 .54 .66 57.0 16.7 6.11 .42 .55 .67 54.7 16.0 6.94 .43 .56 .68

HS29−060 � CR26−60N COOLING CAPACITY − TXV Systems Only

63�F1800 850 54.1 15.9 4.66 .73 .87 .98 52.2 15.3 5.27 .74 .89 .99 50.2 14.7 5.97 .76 .90 1.00 48.2 14.1 6.75 .77 .92 1.00

63�F(17�C)

2000 945 55.0 16.1 4.68 .76 .90 1.00 53.1 15.6 5.28 .77 .92 1.00 51.2 15.0 5.98 .78 .93 1.00 49.1 14.4 6.77 .80 .95 1.00(17�C)

2200 1040 55.9 16.4 4.70 .78 .93 1.00 54.0 15.8 5.31 .79 .94 1.00 52.0 15.2 6.00 .81 .96 1.00 49.9 14.6 6.81 .82 .98 1.00

67�F1800 850 57.4 16.8 4.73 .57 .71 .84 55.4 16.2 5.34 .58 .72 .85 53.3 15.6 6.04 .59 .73 .87 51.1 15.0 6.86 .59 .75 .89

67�F(19�C)

2000 945 58.2 17.1 4.75 .59 .73 .87 56.2 16.5 5.36 .59 .74 .89 54.0 15.8 6.07 .60 .76 .90 51.8 15.2 6.89 .61 .77 .92(19�C)

2200 1040 58.9 17.3 4.77 .60 .76 .90 56.8 16.6 5.38 .61 .77 .92 54.6 16.0 6.10 .62 .79 .93 52.3 15.3 6.91 .63 .80 .95

71�F1800 850 61.1 17.9 4.82 .43 .55 .68 59.0 17.3 5.44 .43 .56 .69 56.8 16.6 6.16 .43 .57 .71 54.4 15.9 6.99 .44 .58 .72

71�F(22�C)

2000 945 61.9 18.1 4.84 .43 .57 .71 59.8 17.5 5.47 .43 .58 .72 57.5 16.9 6.19 .44 .59 .73 55.1 16.1 7.03 .44 .60 .75(22�C)

2200 1040 62.6 18.3 4.85 .44 .59 .73 60.4 17.7 5.49 .44 .59 .75 58.0 17.0 6.22 .44 .60 .76 55.6 16.3 7.05 .45 .62 .78

HS29−060 � CR26−60W − CH33−60D−F − CH23−65 COOLING CAPACITY − RFC or TXV Systems

63�F1800 850 57.1 16.7 4.71 .74 .88 .99 55.1 16.1 5.33 .75 .89 .99 53.1 15.6 6.03 .76 .91 1.00 51.0 14.9 6.82 .78 .93 1.00

63�F(17�C)

2000 945 58.1 17.0 4.71 .76 .91 1.00 56.2 16.5 5.32 .78 .92 1.00 54.1 15.9 6.03 .79 .94 1.00 52.0 15.2 6.82 .81 .96 1.00(17�C)

2200 1040 59.0 17.3 4.73 .79 .94 1.00 57.1 16.7 5.34 .80 .95 1.00 55.0 16.1 6.05 .82 .97 1.00 52.9 15.5 6.84 .83 .98 1.00

67�F1800 850 60.5 17.7 4.76 .58 .71 .85 58.4 17.1 5.37 .58 .73 .86 56.2 16.5 6.07 .59 .74 .88 53.9 15.8 6.88 .60 .75 .90

67�F(19�C)

2000 945 61.3 18.0 4.77 .59 .74 .88 59.2 17.3 5.39 .60 .75 .90 57.0 16.7 6.10 .61 .77 .91 54.6 16.0 6.91 .62 .78 .93(19�C)

2200 1040 62.1 18.2 4.79 .61 .77 .91 59.9 17.6 5.40 .61 .78 .93 57.6 16.9 6.12 .62 .80 .94 55.2 16.2 6.94 .63 .81 .96

71�F1800 850 64.4 18.9 4.84 .43 .56 .69 62.1 18.2 5.47 .43 .57 .70 59.8 17.5 6.19 .43 .58 .72 57.4 16.8 7.02 .44 .58 .73

71�F(22�C)

2000 945 65.2 19.1 4.86 .43 .58 .72 62.9 18.4 5.49 .44 .58 .73 60.5 17.7 6.22 .44 .59 .74 58.0 17.0 7.04 .44 .60 .76(22�C)

2200 1040 65.9 19.3 4.87 .44 .59 .75 63.5 18.6 5.50 .44 .60 .76 61.1 17.9 6.24 .45 .61 .77 58.6 17.2 7.07 .45 .62 .79

HS29−060 − CH33−50C−F − CH23−51 COOLING CAPACITY − TXV Systems Only

63�F1600 755 55.6 16.3 4.98 .72 .85 .96 53.7 15.7 5.63 .73 .87 .98 51.8 15.2 6.38 .74 .88 .99 49.7 14.6 7.20 .75 .90 1.00

63�F(17�C)

1800 850 56.8 16.6 4.98 .74 .88 .99 54.9 16.1 5.63 .76 .90 1.00 52.9 15.5 6.37 .77 .91 1.00 50.8 14.9 7.20 .78 .93 1.00(17�C)

2000 945 57.8 16.9 4.97 .77 .92 1.00 55.9 16.4 5.62 .78 .93 1.00 53.9 15.8 6.37 .79 .94 1.00 51.8 15.2 7.20 .81 .96 1.00

67�F1600 755 59.2 17.3 4.97 .56 .69 .82 57.2 16.8 5.62 .57 .70 .83 55.1 16.1 6.36 .58 .72 .85 52.9 15.5 7.22 .58 .73 .86

67�F(19�C)

1800 850 60.3 17.7 4.97 .58 .72 .85 58.2 17.1 5.61 .58 .73 .87 56.1 16.4 6.36 .59 .74 .88 53.8 15.8 7.22 .60 .76 .90(19�C)

2000 945 61.1 17.9 4.99 .59 .74 .88 59.0 17.3 5.63 .60 .76 .90 56.8 16.6 6.37 .61 .77 .91 54.5 16.0 7.22 .62 .79 .93

71�F1600 755 63.1 18.5 5.03 .42 .55 .67 61.0 17.9 5.69 .43 .55 .68 58.7 17.2 6.44 .43 .56 .69 56.4 16.5 7.30 .43 .57 .70

71�F(22�C)

1800 850 64.0 18.8 5.05 .43 .56 .70 61.9 18.1 5.71 .43 .57 .71 59.6 17.5 6.47 .43 .58 .72 57.2 16.8 7.34 .44 .59 .73(22�C)

2000 945 64.8 19.0 5.07 .44 .58 .72 62.6 18.3 5.73 .44 .59 .73 60.3 17.7 6.49 .44 .60 .75 57.9 17.0 7.36 .44 .61 .77

HS29 / Page 52

Page 53: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 1 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

Outdoor Air Temperature Entering Outdoor Coil

Total85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)

EnteringWet BulbTempera�

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Tempera�ture

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

HS29−060 − CH33−62D−F − CH23−68 COOLING CAPACITY − RFC or TXV Systems

63�F1800 850 61.9 18.1 4.84 .74 .88 .99 59.7 17.5 5.46 .75 .89 1.00 57.4 16.8 6.19 .76 .91 1.00 55.0 16.1 7.01 .78 .93 1.00

63�F(17�C)

2000 945 63.0 18.5 4.86 .76 .91 1.00 60.8 17.8 5.49 .78 .93 1.00 58.4 17.1 6.22 .79 .95 1.00 56.0 16.4 7.05 .81 .96 1.00(17�C)

2200 1040 64.0 18.8 4.89 .79 .94 1.00 61.8 18.1 5.52 .80 .96 1.00 59.4 17.4 6.25 .82 .98 1.00 57.0 16.7 7.08 .84 .99 1.00

67�F1800 850 65.6 19.2 4.92 .58 .71 .85 63.2 18.5 5.56 .58 .72 .86 60.8 17.8 6.29 .59 .74 .88 58.2 17.1 7.14 .60 .75 .90

67�F(19�C)

2000 945 66.6 19.5 4.94 .59 .74 .88 64.2 18.8 5.58 .60 .75 .90 61.6 18.1 6.33 .61 .77 .92 59.0 17.3 7.17 .62 .78 .94(19�C)

2200 1040 67.4 19.8 4.97 .61 .77 .91 65.0 19.0 5.61 .62 .78 .93 62.4 18.3 6.35 .63 .80 .95 59.7 17.5 7.20 .64 .82 .97

71�F1800 850 69.8 20.5 5.02 .43 .56 .69 67.3 19.7 5.67 .43 .57 .70 64.7 19.0 6.42 .43 .57 .71 61.9 18.1 7.30 .44 .58 .73

71�F(22�C)

2000 945 70.8 20.7 5.04 .43 .58 .72 68.2 20.0 5.69 .44 .58 .73 65.4 19.2 6.46 .44 .59 .75 62.7 18.4 7.32 .44 .60 .76(22�C)

2200 1040 71.6 21.0 5.06 .44 .59 .74 68.9 20.2 5.72 .44 .60 .76 66.2 19.4 6.48 .45 .61 .78 63.3 18.6 7.35 .45 .63 .79

HS29−060 � CH33−50/60C−2 with G60UHV−60C−090 COOLING CAPACITY − TXV Systems Only

63�F1560 735 58.4 17.1 4.49 .71 .84 .95 56.3 16.5 5.06 .72 .85 .97 54.2 15.9 5.70 .73 .87 .98 51.9 15.2 6.40 .74 .88 .99

63�F(17�C)

1760 830 59.7 17.5 4.48 .73 .87 .98 57.6 16.9 5.05 .74 .89 .99 55.4 16.2 5.69 .75 .90 1.00 53.1 15.6 6.39 .77 .92 1.00(17�C)

1960 925 60.8 17.8 4.48 .75 .90 1.00 58.7 17.2 5.05 .77 .92 1.00 56.5 16.6 5.69 .78 .93 1.00 54.1 15.9 6.38 .80 .95 1.00

67�F1560 735 62.5 18.3 4.48 .56 .68 .80 60.4 17.7 5.05 .56 .69 .82 58.1 17.0 5.68 .57 .70 .83 55.7 16.3 6.37 .57 .71 .85

67�F(19�C)

1760 830 63.7 18.7 4.48 .57 .70 .84 61.5 18.0 5.04 .58 .72 .85 59.2 17.3 5.67 .58 .73 .87 56.7 16.6 6.37 .59 .74 .89(19�C)

1960 925 64.7 19.0 4.50 .58 .73 .87 62.4 18.3 5.05 .59 .74 .88 60.1 17.6 5.68 .60 .75 .90 57.6 16.9 6.36 .61 .77 .92

71�F1560 735 66.7 19.5 4.53 .42 .54 .66 64.5 18.9 5.09 .42 .54 .66 62.1 18.2 5.71 .43 .55 .67 59.7 17.5 6.40 .43 .56 .69

71�F(22�C)

1760 830 67.9 19.9 4.55 .43 .55 .68 65.6 19.2 5.11 .43 .56 .69 63.2 18.5 5.73 .43 .57 .70 60.6 17.8 6.43 .43 .58 .72(22�C)

1960 925 68.8 20.2 4.56 .43 .57 .70 66.5 19.5 5.12 .43 .58 .72 64.0 18.8 5.76 .44 .58 .73 61.4 18.0 6.44 .44 .59 .75

HS29−060 � CH33−60D−2 with G60UHV−60D−135 COOLING CAPACITY − TXV Systems Only

63�F1560 735 57.9 17.0 4.49 .71 .84 .95 55.9 16.4 5.06 .72 .85 .97 53.7 15.7 5.70 .73 .87 .98 51.5 15.1 6.40 .74 .89 .99

63�F(17�C)

1760 830 59.1 17.3 4.48 .73 .87 .98 57.1 16.7 5.05 .74 .89 .99 54.9 16.1 5.69 .75 .90 1.00 52.6 15.4 6.39 .77 .92 1.00(17�C)

1960 925 60.2 17.6 4.48 .75 .90 1.00 58.2 17.1 5.05 .77 .92 1.00 56.0 16.4 5.69 .78 .93 1.00 53.7 15.7 6.39 .80 .95 1.00

67�F1560 735 61.9 18.1 4.48 .56 .68 .80 59.8 17.5 5.05 .56 .69 .82 57.6 16.9 5.68 .57 .70 .83 55.2 16.2 6.38 .58 .71 .85

67�F(19�C)

1760 830 63.1 18.5 4.47 .57 .71 .84 61.0 17.9 5.04 .58 .72 .85 58.6 17.2 5.67 .58 .73 .87 56.2 16.5 6.37 .59 .74 .89(19�C)

1960 925 64.1 18.8 4.47 .59 .73 .87 61.9 18.1 5.04 .59 .74 .88 59.5 17.4 5.67 .60 .76 .90 57.0 16.7 6.36 .61 .77 .92

71�F1560 735 66.2 19.4 4.50 .42 .54 .66 64.0 18.8 5.06 .42 .54 .66 61.6 18.1 5.69 .43 .55 .68 59.2 17.3 6.37 .43 .56 .69

71�F(22�C)

1760 830 67.3 19.7 4.52 .43 .55 .68 65.0 19.0 5.08 .43 .56 .69 62.6 18.3 5.71 .43 .57 .70 60.1 17.6 6.39 .43 .58 .72(22�C)

1960 925 68.2 20.0 4.54 .43 .57 .71 65.9 19.3 5.10 .43 .58 .72 63.5 18.6 5.72 .44 .58 .73 60.9 17.8 6.40 .44 .59 .75

HS29−060 � CH33−62D−2 with G60UHV−60D−135 COOLING CAPACITY − TXV Systems Only

63�F1560 735 58.4 17.1 4.48 .71 .84 .95 56.3 16.5 5.05 .72 .85 .97 54.1 15.9 5.69 .73 .87 .98 51.8 15.2 6.39 .74 .88 1.00

63�F(17�C)

1760 830 59.7 17.5 4.48 .73 .87 .98 57.6 16.9 5.04 .74 .88 .99 55.4 16.2 5.68 .75 .90 1.00 53.0 15.5 6.38 .77 .92 1.00(17�C)

1960 925 60.8 17.8 4.47 .75 .90 1.00 58.7 17.2 5.04 .77 .91 1.00 56.5 16.6 5.67 .78 .93 1.00 54.1 15.9 6.37 .80 .95 1.00

67�F1560 735 62.5 18.3 4.47 .56 .68 .80 60.4 17.7 5.04 .56 .69 .82 58.1 17.0 5.67 .57 .70 .83 55.7 16.3 6.36 .57 .71 .85

67�F(19�C)

1760 830 63.7 18.7 4.49 .57 .70 .84 61.5 18.0 5.04 .58 .71 .85 59.2 17.3 5.67 .58 .73 .87 56.7 16.6 6.35 .59 .74 .88(19�C)

1960 925 64.7 19.0 4.50 .58 .73 .87 62.4 18.3 5.07 .59 .74 .88 60.0 17.6 5.69 .60 .76 .90 57.5 16.9 6.37 .61 .77 .92

71�F1560 735 66.7 19.5 4.54 .42 .54 .65 64.4 18.9 5.10 .42 .54 .66 62.1 18.2 5.72 .43 .55 .67 59.6 17.5 6.42 .43 .56 .69

71�F(22�C)

1760 830 67.8 19.9 4.56 .43 .55 .68 65.6 19.2 5.12 .43 .56 .69 63.1 18.5 5.75 .43 .57 .70 60.5 17.7 6.44 .43 .58 .72(22�C)

1960 925 68.8 20.2 4.58 .43 .57 .70 66.4 19.5 5.14 .43 .58 .72 63.9 18.7 5.77 .44 .58 .73 61.4 18.0 6.45 .44 .59 .75

HS29−060 − CB29M−51 − CB28UH−048 COOLING CAPACITY − TXV Systems Only

63�F1400 660 53.9 15.8 4.70 .69 .81 .92 52.1 15.3 5.31 .70 .82 .94 50.2 14.7 6.01 .71 .84 .95 48.2 14.1 6.79 .72 .85 .97

63�F(17�C)

1600 755 55.3 16.2 4.70 .71 .84 .96 53.4 15.6 5.31 .72 .86 .97 51.4 15.1 6.01 .73 .87 .98 49.4 14.5 6.79 .75 .89 .99(17�C)

1800 850 56.4 16.5 4.69 .73 .88 .98 54.5 16.0 5.30 .75 .89 .99 52.5 15.4 6.01 .76 .90 1.00 50.4 14.8 6.79 .77 .92 1.00

67�F1400 660 57.7 16.9 4.69 .55 .66 .78 55.8 16.4 5.30 .55 .67 .79 53.7 15.7 6.00 .56 .68 .80 51.5 15.1 6.80 .56 .69 .82

67�F(19�C)

1600 755 59.0 17.3 4.68 .56 .69 .81 57.0 16.7 5.29 .56 .69 .82 54.9 16.1 6.00 .57 .71 .84 52.6 15.4 6.80 .58 .72 .85(19�C)

1800 850 60.0 17.6 4.70 .57 .71 .84 58.0 17.0 5.31 .58 .72 .86 55.8 16.4 6.01 .59 .73 .87 53.6 15.7 6.80 .59 .75 .89

71�F1400 660 61.6 18.1 4.73 .42 .53 .64 59.6 17.5 5.35 .42 .53 .64 57.4 16.8 6.06 .42 .54 .66 55.2 16.2 6.87 .42 .54 .66

71�F(22�C)

1600 755 62.8 18.4 4.76 .43 .54 .66 60.7 17.8 5.38 .43 .55 .67 58.5 17.1 6.09 .43 .55 .68 56.2 16.5 6.91 .43 .56 .69(22�C)

1800 850 63.8 18.7 4.78 .43 .56 .68 61.7 18.1 5.40 .43 .56 .70 59.4 17.4 6.12 .43 .57 .71 57.0 16.7 6.94 .44 .58 .72

HS29−060 − CB29M−65 − CB28UH−060 COOLING CAPACITY − TXV Systems Only

63�F1600 755 55.7 16.3 4.76 .71 .84 .96 53.8 15.8 5.38 .72 .86 .97 51.8 15.2 6.10 .73 .87 .98 49.7 14.6 6.89 .75 .89 .99

63�F(17�C)

1800 850 56.8 16.6 4.76 .73 .88 .98 54.9 16.1 5.38 .75 .89 .99 52.9 15.5 6.10 .76 .90 1.00 50.8 14.9 6.89 .77 .92 1.00(17�C)

2000 945 57.9 17.0 4.76 .76 .90 1.00 55.9 16.4 5.38 .77 .92 1.00 53.8 15.8 6.09 .79 .93 1.00 51.7 15.2 6.89 .80 .95 1.00

67�F1600 755 59.4 17.4 4.75 .56 .69 .81 57.4 16.8 5.37 .57 .70 .82 55.3 16.2 6.08 .57 .71 .84 53.0 15.5 6.90 .58 .72 .85

67�F(19�C)

1800 850 60.4 17.7 4.77 .57 .71 .84 58.4 17.1 5.39 .58 .72 .86 56.2 16.5 6.10 .59 .73 .87 53.9 15.8 6.90 .60 .75 .89(19�C)

2000 945 61.3 18.0 4.79 .59 .73 .87 59.1 17.3 5.41 .59 .75 .89 56.9 16.7 6.12 .60 .76 .90 54.6 16.0 6.93 .61 .78 .92

71�F1600 755 63.3 18.6 4.83 .42 .54 .66 61.2 17.9 5.46 .42 .55 .67 58.9 17.3 6.18 .43 .56 .68 56.6 16.6 7.01 .43 .56 .69

71�F(22�C)

1800 850 64.3 18.8 4.85 .43 .56 .68 62.1 18.2 5.48 .43 .56 .70 59.8 17.5 6.21 .43 .57 .71 57.4 16.8 7.04 .44 .58 .72(22�C)

2000 945 65.1 19.1 4.87 .43 .57 .71 62.8 18.4 5.50 .44 .58 .72 60.5 17.7 6.23 .44 .59 .74 58.0 17.0 7.06 .44 .60 .75

HS29−060 − CB30M−51 − CB30U−51 COOLING CAPACITY − TXV Systems Only

63�F1400 660 54.6 16.0 4.64 .68 .81 .91 52.8 15.5 5.24 .69 .82 .93 50.8 14.9 5.94 .70 .83 .95 48.7 14.3 6.71 .71 .85 .96

63�F(17�C)

1600 755 56.2 16.5 4.63 .71 .84 .95 54.2 15.9 5.24 .72 .85 .97 52.1 15.3 5.93 .73 .87 .98 50.0 14.7 6.71 .74 .88 .99(17�C)

1800 850 57.3 16.8 4.65 .73 .87 .98 55.3 16.2 5.25 .74 .88 .99 53.2 15.6 5.95 .75 .90 1.00 51.1 15.0 6.73 .77 .92 1.00

67�F1400 660 58.5 17.1 4.68 .55 .66 .77 56.5 16.6 5.28 .55 .67 .78 54.4 15.9 5.97 .56 .67 .80 52.2 15.3 6.77 .56 .69 .81

67�F(19�C)

1600 755 59.8 17.5 4.70 .56 .68 .80 57.7 16.9 5.31 .56 .69 .82 55.5 16.3 6.01 .57 .70 .83 53.2 15.6 6.82 .58 .72 .85(19�C)

1800 850 60.9 17.8 4.73 .57 .71 .84 58.7 17.2 5.34 .58 .72 .85 56.4 16.5 6.05 .59 .73 .87 54.1 15.9 6.85 .59 .74 .89

71�F1400 660 62.4 18.3 4.76 .42 .53 .63 60.3 17.7 5.38 .42 .53 .64 58.0 17.0 6.09 .42 .54 .65 55.7 16.3 6.91 .42 .54 .66

71�F(22�C)

1600 755 63.8 18.7 4.79 .42 .54 .66 61.5 18.0 5.42 .42 .54 .67 59.2 17.3 6.13 .43 .55 .68 56.8 16.6 6.96 .43 .56 .69(22�C)

1800 850 64.8 19.0 4.82 .43 .55 .68 62.6 18.3 5.44 .43 .56 .69 60.2 17.6 6.16 .43 .57 .70 57.7 16.9 7.00 .44 .58 .72

HS29 / Page 53

Page 54: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 1 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

Outdoor Air Temperature Entering Outdoor Coil

Total 85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)

EnteringWet BulbTempera�

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Tempera�ture

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

HS29−060 − CB31MV−51 COOLING CAPACITY − TXV Systems Only

63�F1425 675 53.9 15.8 4.46 .69 .81 .92 52.0 15.2 5.04 .70 .82 .94 50.0 14.7 5.71 .71 .84 .95 48.0 14.1 6.46 .72 .85 .97

63�F(17�C)

1625 765 55.3 16.2 4.45 .71 .84 .96 53.4 15.6 5.04 .72 .86 .97 51.4 15.1 5.71 .73 .87 .98 49.3 14.4 6.46 .74 .89 1.00(17�C)

1805 850 56.3 16.5 4.47 .73 .87 .98 54.4 15.9 5.05 .74 .88 .99 52.3 15.3 5.72 .76 .90 1.00 50.2 14.7 6.48 .77 .92 1.00

67�F1425 675 57.6 16.9 4.50 .55 .66 .77 55.7 16.3 5.09 .55 .67 .79 53.6 15.7 5.75 .56 .68 .80 51.4 15.1 6.52 .56 .69 .82

67�F(19�C)

1625 765 58.9 17.3 4.53 .56 .69 .81 56.9 16.7 5.12 .56 .69 .82 54.7 16.0 5.79 .57 .71 .84 52.4 15.4 6.57 .58 .72 .85(19�C)

1805 850 59.8 17.5 4.55 .57 .71 .84 57.7 16.9 5.13 .58 .72 .85 55.5 16.3 5.82 .59 .73 .87 53.2 15.6 6.59 .59 .74 .89

71�F1425 675 61.5 18.0 4.59 .42 .53 .63 59.4 17.4 5.18 .42 .53 .64 57.2 16.8 5.86 .42 .54 .65 54.9 16.1 6.65 .42 .54 .66

71�F(22�C)

1625 765 62.8 18.4 4.61 .43 .54 .66 60.6 17.8 5.21 .43 .55 .67 58.3 17.1 5.90 .43 .55 .68 55.9 16.4 6.70 .43 .56 .69(22�C)

1805 850 63.7 18.7 4.64 .43 .55 .68 61.5 18.0 5.23 .43 .56 .69 59.1 17.3 5.93 .43 .57 .71 56.7 16.6 6.73 .43 .58 .72

HS29−060 � CB30M−65 − CB30MU−65 COOLING CAPACITY − TXV Systems Only

63�F1600 755 57.4 16.8 4.63 .71 .84 .95 55.4 16.2 5.24 .72 .85 .97 53.3 15.6 5.94 .73 .86 .98 51.1 15.0 6.72 .74 .88 .99

63�F(17�C)

1800 850 58.6 17.2 4.66 .73 .87 .98 56.5 16.6 5.26 .74 .88 .99 54.4 15.9 5.95 .75 .90 1.00 52.2 15.3 6.74 .77 .92 1.00(17�C)

2000 945 59.6 17.5 4.68 .76 .90 1.00 57.5 16.9 5.29 .77 .92 1.00 55.3 16.2 5.98 .78 .93 1.00 53.1 15.6 6.78 .80 .95 1.00

67�F1600 755 61.1 17.9 4.71 .56 .68 .80 59.0 17.3 5.32 .56 .69 .82 56.7 16.6 6.02 .57 .70 .83 54.4 15.9 6.83 .58 .72 .85

67�F(19�C)

1800 850 62.2 18.2 4.73 .57 .71 .84 60.0 17.6 5.34 .58 .72 .85 57.7 16.9 6.06 .58 .73 .87 55.3 16.2 6.86 .59 .74 .89(19�C)

2000 945 63.1 18.5 4.75 .58 .73 .87 60.8 17.8 5.37 .59 .74 .89 58.5 17.1 6.08 .60 .76 .90 56.0 16.4 6.89 .61 .77 .92

71�F1600 755 65.1 19.1 4.80 .42 .54 .66 62.9 18.4 5.42 .42 .55 .66 60.5 17.7 6.14 .43 .55 .68 58.0 17.0 6.97 .43 .56 .69

71�F(22�C)

1800 850 66.3 19.4 4.82 .43 .55 .68 63.9 18.7 5.44 .43 .56 .69 61.5 18.0 6.17 .43 .57 .71 58.9 17.3 7.00 .43 .58 .72(22�C)

2000 945 67.2 19.7 4.84 .43 .57 .71 64.8 19.0 5.47 .43 .58 .72 62.2 18.2 6.20 .44 .59 .73 59.7 17.5 7.03 .44 .60 .75

HS29−060 − CB31MV−65 COOLING CAPACITY − TXV Systems Only

63�F1625 765 57.4 16.8 4.67 .71 .84 .96 55.4 16.2 5.28 .72 .85 .97 53.2 15.6 5.98 .73 .87 .99 51.1 15.0 6.77 .74 .89 1.00

63�F(17�C)

1805 850 58.4 17.1 4.69 .73 .87 .98 56.4 16.5 5.29 .74 .88 .99 54.2 15.9 5.99 .76 .90 1.00 52.0 15.2 6.78 .77 .92 1.00(17�C)

2005 945 59.4 17.4 4.71 .75 .90 1.00 57.4 16.8 5.32 .77 .92 1.00 55.2 16.2 6.02 .78 .93 1.00 52.9 15.5 6.82 .80 .95 1.00

67�F1625 765 61.1 17.9 4.74 .56 .69 .81 58.9 17.3 5.36 .56 .69 .82 56.7 16.6 6.06 .57 .71 .84 54.3 15.9 6.88 .58 .72 .85

67�F(19�C)

1805 850 62.0 18.2 4.77 .57 .71 .84 59.8 17.5 5.38 .58 .72 .85 57.5 16.9 6.10 .58 .73 .87 55.1 16.1 6.91 .59 .75 .89(19�C)

2005 945 62.9 18.4 4.78 .59 .73 .87 60.7 17.8 5.41 .59 .74 .89 58.3 17.1 6.13 .60 .76 .90 55.9 16.4 6.93 .61 .77 .92

71�F1625 765 65.1 19.1 4.83 .42 .54 .66 62.8 18.4 5.46 .43 .55 .67 60.5 17.7 6.18 .43 .55 .68 58.0 17.0 7.02 .43 .56 .69

71�F(22�C)

1805 850 66.1 19.4 4.86 .43 .55 .68 63.7 18.7 5.48 .43 .56 .69 61.3 18.0 6.21 .43 .57 .71 58.7 17.2 7.05 .43 .58 .72(22�C)

2005 945 67.0 19.6 4.88 .43 .57 .71 64.6 18.9 5.51 .43 .58 .72 62.1 18.2 6.24 .44 .59 .73 59.5 17.4 7.08 .44 .60 .75

HS29−060 − CVP10−51/EC10Q4 COOLING CAPACITY − TXV Systems Only

63�F1600 755 53.3 15.6 4.59 .71 .84 .95 51.5 15.1 5.19 .72 .85 .97 49.6 14.5 5.87 .73 .86 .98 47.6 14.0 6.64 .74 .88 .99

63�F(17�C)

1700 800 54.0 15.8 4.58 .72 .85 .97 52.1 15.3 5.18 .73 .87 .98 50.1 14.7 5.87 .74 .88 .99 48.1 14.1 6.64 .76 .90 1.00(17�C)

1800 850 54.5 16.0 4.58 .73 .87 .98 52.7 15.4 5.18 .74 .88 .99 50.7 14.9 5.87 .75 .90 1.00 48.6 14.2 6.64 .77 .92 1.00

67�F1600 755 57.0 16.7 4.62 .56 .68 .80 55.0 16.1 5.22 .56 .69 .82 52.9 15.5 5.90 .57 .70 .83 50.8 14.9 6.68 .57 .71 .85

67�F(19�C)

1700 800 57.5 16.9 4.63 .56 .69 .82 55.5 16.3 5.23 .57 .70 .83 53.4 15.6 5.92 .58 .72 .85 51.2 15.0 6.70 .58 .73 .87(19�C)

1800 850 58.0 17.0 4.64 .57 .71 .84 56.0 16.4 5.24 .58 .72 .85 53.8 15.8 5.92 .58 .73 .87 51.6 15.1 6.72 .59 .74 .89

71�F1600 755 60.7 17.8 4.70 .42 .54 .66 58.6 17.2 5.31 .42 .54 .66 56.4 16.5 6.01 .43 .55 .68 54.1 15.9 6.81 .43 .56 .69

71�F(22�C)

1700 800 61.2 17.9 4.71 .42 .55 .67 59.1 17.3 5.32 .43 .55 .68 56.9 16.7 6.03 .43 .56 .69 54.6 16.0 6.83 .43 .57 .70(22�C)

1800 850 61.7 18.1 4.72 .43 .55 .68 59.6 17.5 5.34 .43 .56 .69 57.3 16.8 6.05 .43 .57 .71 55.0 16.1 6.85 .43 .58 .72

HS29−060 − CVP10−65/EC10Q5 COOLING CAPACITY − TXV Systems Only

63�F1600 755 54.8 16.1 4.65 .72 .85 .96 52.9 15.5 5.26 .73 .86 .98 50.9 14.9 5.96 .74 .88 .99 48.9 14.3 6.73 .75 .90 1.00

63�F(17�C)

1800 850 56.0 16.4 4.64 .74 .88 .99 54.1 15.9 5.25 .75 .90 1.00 52.1 15.3 5.95 .77 .91 1.00 50.0 14.7 6.73 .78 .93 1.00(17�C)

2000 945 57.0 16.7 4.66 .77 .92 1.00 55.1 16.1 5.26 .78 .93 1.00 53.1 15.6 5.96 .80 .95 1.00 51.0 14.9 6.75 .81 .96 1.00

67�F1600 755 58.3 17.1 4.68 .56 .69 .82 56.3 16.5 5.29 .57 .70 .83 54.2 15.9 5.98 .58 .71 .84 52.0 15.2 6.78 .58 .73 .86

67�F(19�C)

1800 850 59.4 17.4 4.71 .58 .72 .85 57.3 16.8 5.31 .58 .73 .87 55.1 16.1 6.01 .59 .74 .88 52.9 15.5 6.82 .60 .76 .90(19�C)

2000 945 60.2 17.6 4.73 .59 .75 .88 58.1 17.0 5.33 .60 .76 .90 55.9 16.4 6.04 .61 .77 .92 53.6 15.7 6.85 .62 .79 .94

71�F1600 755 62.2 18.2 4.77 .42 .55 .67 60.1 17.6 5.39 .43 .55 .68 57.8 16.9 6.10 .43 .56 .69 55.5 16.3 6.91 .43 .57 .70

71�F(22�C)

1800 850 63.2 18.5 4.79 .43 .56 .69 61.0 17.9 5.42 .43 .57 .70 58.7 17.2 6.13 .43 .58 .72 56.3 16.5 6.95 .44 .59 .73(22�C)

2000 945 64.0 18.8 4.81 .44 .58 .72 61.8 18.1 5.44 .44 .59 .73 59.4 17.4 6.16 .44 .60 .75 57.0 16.7 6.99 .45 .61 .77

RATINGS − 3 PHASE

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C660 1400 15.9 54,200 4690 .69 .82 .93 15.2 51,800 5050 .71 .83 .95 14.4 49,300 5400 .72 .85 .97 13.6 46,500 5770 .73 .87 .99

755 1600 16.3 55,700 4750 .72 .85 .97 15.6 53,100 5110 .73 .87 .98 14.8 50,500 5480 .75 .89 1.00 14.0 47,700 5840 .77 .92 1.00

850 1800 16.6 56,800 4800 .74 .89 .99 15.9 54,200 5170 .76 .91 1.00 15.1 51,500 5540 .78 .93 1.00 14.2 48,600 5920 .80 .95 1.00

660 1400 16.9 57,800 4850 .55 .67 .78 16.2 55,300 5220 .56 .68 .80 15.4 52,500 5600 .56 .69 .82 14.5 49,600 5980 .57 .71 .84

755 1600 17.3 59,200 4900 .56 .69 .82 16.6 56,500 5290 .57 .71 .84 15.7 53,600 5670 .58 .72 .86 14.8 50,500 6050 .59 .74 .88

850 1800 17.6 60,200 4950 .58 .72 .85 16.8 57,400 5340 .59 .73 .87 16.0 54,500 5720 .60 .75 .90 15.0 51,300 6110 .61 .78 .92

660 1400 18.1 61,800 5020 .42 .53 .64 17.3 59,000 5420 .42 .54 .65 16.4 56,100 5820 .42 .55 .67 15.5 53,000 6220 .43 .56 .68

755 1600 18.5 63,100 5080 .42 .55 .67 17.6 60,200 5480 .43 .55 .68 16.8 57,200 5890 .43 .56 .70 15.8 54,000 6290 .43 .58 .72

850 1800 18.8 64,100 5120 .43 .56 .69 17.9 61,200 5530 .43 .57 .71 17.0 58,100 5940 .44 .58 .73 16.0 54,700 6350 .44 .60 .75

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�060 � C33−50/60C − C26�51/65 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

HS29 / Page 54

Page 55: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 3 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C800 1700 16.7 57,100 4730 .72 .86 .97 16.0 54,500 5090 .74 .88 .99 15.2 51,800 5460 .75 .90 1.00 14.3 48,900 5820 .77 .92 1.00

895 1900 17.1 58,200 4780 .75 .89 1.00 16.3 55,500 5140 .76 .91 1.00 15.4 52,700 5510 .78 .93 1.00 14.6 49,800 5880 .80 .96 1.00

990 2100 17.3 59,100 4810 .77 .92 1.00 16.5 56,400 5190 .79 .94 1.00 15.7 53,600 5560 .81 .96 1.00 14.9 50,700 5950 .83 .98 1.00

800 1700 17.8 60,800 4880 .57 .70 .83 17.0 57,900 5260 .57 .71 .85 16.1 55,000 5650 .58 .73 .87 15.2 51,900 6030 .60 .75 .89

895 1900 18.1 61,700 4930 .58 .72 .86 17.2 58,800 5310 .59 .74 .88 16.4 55,900 5690 .60 .76 .90 15.4 52,600 6080 .61 .78 .93

990 2100 18.3 62,500 4960 .59 .75 .89 17.5 59,600 5350 .60 .76 .91 16.6 56,500 5730 .62 .79 .94 15.6 53,300 6120 .63 .81 .96

800 1700 19.0 64,700 5060 .43 .55 .67 18.1 61,800 5460 .43 .56 .69 17.2 58,700 5860 .43 .57 .70 16.2 55,400 6270 .44 .58 .72

895 1900 19.3 65,700 5100 .43 .56 .70 18.4 62,700 5500 .43 .57 .71 17.5 59,600 5910 .44 .59 .73 16.5 56,200 6320 .44 .60 .76

990 2100 19.5 66,500 5130 .44 .58 .72 18.6 63,400 5540 .44 .59 .74 17.6 60,200 5950 .44 .60 .76 16.6 56,700 6360 .45 .62 .79

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�060 � C33−60D − C23�51/65 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C755 1600 16.9 57,700 4800 .71 .85 .96 16.1 55,100 5160 .73 .86 .98 15.3 52,300 5530 .74 .88 1.00 14.4 49,300 5900 .76 .91 1.00

850 1800 17.3 58,900 4850 .74 .88 .99 16.5 56,200 5220 .75 .90 1.00 15.6 53,300 5600 .77 .92 1.00 14.7 50,300 5970 .79 .95 1.00

945 2000 17.6 60,000 4890 .76 .91 1.00 16.8 57,200 5270 .78 .93 1.00 15.9 54,300 5650 .80 .95 1.00 15.0 51,300 6040 .82 .98 1.00

755 1600 18.0 61,500 4960 .56 .69 .81 17.2 58,700 5350 .57 .70 .83 16.3 55,700 5730 .58 .72 .85 15.4 52,500 6120 .59 .74 .88

850 1800 18.3 62,600 5010 .57 .71 .84 17.5 59,700 5400 .58 .73 .87 16.6 56,600 5790 .59 .75 .89 15.6 53,300 6180 .61 .77 .92

945 2000 18.6 63,600 5050 .59 .74 .88 17.7 60,500 5440 .60 .75 .90 16.8 57,400 5840 .61 .77 .92 15.8 54,000 6230 .62 .80 .95

755 1600 19.3 65,700 5140 .42 .54 .66 18.4 62,700 5550 .43 .55 .67 17.4 59,500 5960 .43 .56 .69 16.4 56,100 6380 .43 .57 .71

850 1800 19.6 66,800 5190 .43 .56 .69 18.7 63,700 5610 .43 .57 .70 17.7 60,400 6020 .43 .58 .72 16.7 56,900 6430 .44 .59 .74

945 2000 19.8 67,700 5230 .43 .57 .71 18.9 64,500 5650 .44 .58 .73 17.9 61,200 6070 .44 .60 .75 16.9 57,600 6480 .45 .61 .77

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�060 � C33−62D − C26�65EAP � CH33−62D−F − CH23�68 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C710 1500 16.0 54,600 4630 .71 .83 .95 15.3 52,200 4980 .72 .85 .96 14.6 49,700 5330 .73 .87 .98 13.8 47,000 5690 .75 .89 1.00

800 1700 16.4 55,800 4680 .73 .87 .98 15.6 53,300 5040 .74 .88 .99 14.9 50,700 5400 .76 .91 1.00 14.0 47,900 5760 .78 .93 1.00

895 1900 16.6 56,800 4720 .75 .90 1.00 15.9 54,300 5080 .77 .92 1.00 15.1 51,600 5450 .79 .94 1.00 14.3 48,800 5820 .81 .96 1.00

710 1500 17.1 58,200 4780 .56 .68 .80 16.3 55,600 5150 .56 .69 .82 15.5 52,900 5520 .57 .71 .84 14.6 49,900 5900 .58 .72 .86

800 1700 17.3 59,200 4830 .57 .70 .83 16.6 56,600 5200 .58 .72 .85 15.8 53,800 5570 .59 .73 .87 14.9 50,700 5950 .60 .76 .90

895 1900 17.6 60,100 4860 .58 .73 .87 16.8 57,400 5240 .59 .74 .89 16.0 54,500 5620 .60 .76 .91 15.1 51,400 6000 .62 .79 .93

710 1500 18.2 62,000 4940 .42 .54 .65 17.4 59,300 5330 .42 .54 .67 16.5 56,400 5730 .43 .55 .68 15.6 53,300 6130 .43 .56 .70

800 1700 18.5 63,100 4990 .43 .55 .68 17.7 60,300 5380 .43 .56 .69 16.8 57,300 5780 .43 .57 .71 15.9 54,100 6180 .44 .58 .73

895 1900 18.8 64,000 5020 .43 .57 .71 17.9 61,100 5420 .43 .58 .72 17.0 58,100 5830 .44 .59 .74 16.1 54,800 6230 .44 .60 .76

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�060 � CR26�48 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C850 1800 17.1 58,300 4780 .74 .88 .99 16.3 55,600 5150 .75 .90 1.00 15.5 52,800 5520 .77 .92 1.00 14.6 49,900 5890 .79 .95 1.00

945 2000 17.4 59,300 4830 .76 .91 1.00 16.6 56,600 5200 .78 .93 1.00 15.8 53,800 5570 .80 .95 1.00 14.9 50,800 5960 .82 .98 1.00

1040 2200 17.6 60,200 4860 .79 .94 1.00 16.9 57,500 5240 .81 .96 1.00 16.0 54,700 5620 .83 .98 1.00 15.2 51,700 6020 .85 1.00 1.00

850 1800 18.1 61,800 4930 .58 .71 .85 17.3 59,000 5320 .58 .73 .87 16.4 56,000 5710 .59 .75 .89 15.5 52,800 6090 .61 .77 .92

945 2000 18.4 62,700 4970 .59 .74 .88 17.5 59,800 5360 .60 .76 .90 16.6 56,700 5750 .61 .78 .92 15.6 53,400 6140 .63 .80 .95

1040 2200 18.6 63,500 5000 .60 .76 .91 17.7 60,500 5400 .62 .78 .93 16.8 57,300 5790 .63 .80 .95 15.8 54,000 6180 .64 .83 .98

850 1800 19.3 65,900 5110 .43 .56 .69 18.4 62,900 5520 .43 .57 .70 17.5 59,700 5920 .44 .58 .72 16.5 56,300 6330 .44 .59 .74

945 2000 19.6 66,800 5150 .43 .57 .72 18.7 63,700 5560 .44 .59 .73 17.7 60,400 5970 .44 .60 .75 16.7 57,000 6380 .45 .61 .78

1040 2200 19.8 67,500 5180 .44 .59 .74 18.9 64,400 5590 .44 .60 .76 17.9 61,000 6000 .45 .62 .78 16.9 57,500 6420 .45 .63 .81

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�060 � CR26�60 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

HS29 / Page 55

Page 56: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 3 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C850 1800 17.0 58,100 4740 .75 .89 .99 16.3 55,500 5100 .76 .91 1.00 15.5 52,800 5470 .78 .93 1.00 14.6 49,900 5840 .80 .95 1.00

945 2000 17.3 59,100 4780 .77 .92 1.00 16.6 56,500 5150 .79 .94 1.00 15.7 53,700 5530 .81 .96 1.00 14.9 50,800 5910 .83 .98 1.00

1040 2200 17.6 60,000 4820 .80 .95 1.00 16.8 57,400 5200 .82 .97 1.00 16.0 54,600 5580 .84 .98 1.00 15.2 51,800 5970 .86 1.00 1.00

850 1800 18.0 61,500 4880 .58 .72 .86 17.2 58,700 5260 .59 .74 .88 16.3 55,700 5640 .60 .76 .90 15.4 52,600 6030 .61 .78 .93

945 2000 18.3 62,300 4920 .60 .75 .89 17.4 59,500 5300 .61 .77 .91 16.6 56,500 5690 .62 .79 .93 15.6 53,200 6070 .63 .81 .96

1040 2200 18.5 63,100 4950 .61 .78 .92 17.6 60,200 5340 .62 .79 .94 16.7 57,100 5720 .64 .82 .96 15.8 53,800 6110 .65 .84 .98

850 1800 19.2 65,400 5050 .43 .56 .70 18.3 62,500 5450 .43 .57 .71 17.4 59,400 5850 .44 .58 .73 16.4 56,000 6260 .44 .60 .75

945 2000 19.4 66,300 5080 .44 .58 .73 18.6 63,300 5490 .44 .59 .74 17.6 60,100 5890 .44 .60 .76 16.6 56,600 6300 .45 .62 .79

1040 2200 19.6 67,000 5110 .44 .60 .75 18.7 63,900 5520 .45 .61 .77 17.8 60,600 5930 .45 .62 .79 16.7 57,100 6340 .46 .64 .82

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�060 � CH33−60D−F − CH23�65 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C825 1750 16.7 57,100 4630 .74 .88 .98 16.0 54,600 4980 .75 .89 1.00 15.2 52,000 5330 .77 .91 1.00 14.4 49,100 5700 .79 .94 1.00

850 1800 16.8 57,400 4640 .74 .88 .99 16.1 54,900 4990 .76 .90 1.00 15.3 52,200 5350 .77 .92 1.00 14.4 49,300 5710 .79 .95 1.00

875 1850 16.9 57,600 4650 .75 .89 .99 16.1 55,100 5000 .76 .91 1.00 15.4 52,400 5360 .78 .93 1.00 14.5 49,600 5730 .80 .95 1.00

825 1750 17.8 60,600 4770 .57 .71 .84 17.0 57,900 5140 .58 .73 .86 16.1 55,000 5510 .59 .74 .88 15.2 51,900 5880 .60 .76 .91

850 1800 17.8 60,800 4780 .58 .72 .85 17.0 58,100 5150 .59 .73 .87 16.2 55,200 5520 .60 .75 .89 15.3 52,100 5890 .61 .77 .92

875 1850 17.9 61,000 4790 .58 .72 .86 17.1 58,300 5160 .59 .74 .88 16.2 55,400 5530 .60 .76 .90 15.3 52,200 5900 .61 .78 .93

825 1750 18.9 64,500 4930 .43 .56 .69 18.1 61,600 5320 .43 .57 .70 17.2 58,600 5710 .43 .58 .72 16.2 55,300 6110 .44 .59 .74

850 1800 19.0 64,700 4940 .43 .56 .69 18.1 61,800 5330 .43 .57 .71 17.2 58,800 5720 .44 .58 .73 16.3 55,500 6120 .44 .59 .75

875 1850 19.0 64,900 4950 .43 .57 .70 18.2 62,000 5340 .43 .57 .71 17.3 59,000 5730 .44 .59 .73 16.3 55,700 6130 .44 .60 .76

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−060 � CB29M−51 − CB28UH−048 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C755 1600 16.6 56,600 4590 .72 .85 .96 15.9 54,100 4940 .73 .87 .98 15.1 51,500 5290 .75 .89 .99 14.2 48,600 5650 .76 .91 1.00

850 1800 16.9 57,700 4640 .74 .88 .99 16.1 55,100 4990 .76 .90 1.00 15.4 52,400 5350 .77 .92 1.00 14.5 49,600 5710 .79 .95 1.00

945 2000 17.2 58,600 4680 .77 .91 1.00 16.4 56,000 5040 .78 .93 1.00 15.6 53,300 5400 .80 .95 1.00 14.8 50,500 5770 .82 .97 1.00

755 1600 17.6 60,100 4740 .56 .69 .82 16.9 57,500 5100 .57 .70 .84 16.0 54,700 5470 .58 .72 .86 15.1 51,600 5840 .59 .74 .88

850 1800 17.9 61,100 4780 .58 .72 .85 17.1 58,400 5150 .59 .73 .87 16.3 55,500 5520 .60 .75 .89 15.3 52,300 5890 .61 .77 .92

945 2000 18.1 61,900 4810 .59 .74 .88 17.3 59,200 5180 .60 .76 .90 16.5 56,200 5560 .61 .78 .93 15.5 53,000 5940 .63 .80 .95

755 1600 18.8 64,000 4900 .42 .55 .67 17.9 61,200 5280 .43 .55 .68 17.1 58,300 5670 .43 .56 .70 16.1 55,000 6070 .43 .57 .72

850 1800 19.0 65,000 4940 .43 .56 .69 18.2 62,200 5330 .43 .57 .71 17.3 59,100 5720 .44 .58 .73 16.4 55,800 6120 .44 .59 .75

945 2000 19.3 65,800 4970 .43 .58 .72 18.4 62,900 5360 .44 .59 .74 17.5 59,800 5760 .44 .60 .76 16.5 56,400 6160 .45 .61 .78

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−060 � CB29M−65 − CB28UH−060 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C660 1400 16.2 55,200 4560 .69 .81 .92 15.5 52,800 4910 .70 .83 .94 14.7 50,100 5250 .71 .85 .96 13.9 47,300 5600 .73 .87 .99

755 1600 16.6 56,700 4620 .71 .85 .96 15.9 54,100 4970 .73 .86 .98 15.0 51,300 5320 .74 .88 1.00 14.2 48,400 5690 .76 .91 1.00

850 1800 16.9 57,800 4670 .74 .88 .99 16.2 55,200 5030 .75 .90 1.00 15.4 52,400 5390 .77 .92 1.00 14.5 49,400 5750 .79 .95 1.00

660 1400 17.3 59,000 4710 .55 .66 .78 16.5 56,400 5080 .56 .67 .79 15.7 53,500 5450 .56 .69 .81 14.8 50,500 5820 .57 .70 .83

755 1600 17.7 60,300 4770 .56 .69 .81 16.9 57,600 5150 .57 .70 .83 16.0 54,700 5520 .58 .72 .85 15.1 51,500 5890 .59 .74 .88

850 1800 18.0 61,400 4820 .58 .71 .85 17.2 58,600 5190 .58 .73 .87 16.3 55,500 5570 .59 .75 .89 15.3 52,300 5950 .61 .77 .92

660 1400 18.5 63,000 4890 .42 .53 .64 17.6 60,200 5280 .42 .54 .65 16.8 57,200 5670 .42 .54 .66 15.9 54,100 6060 .43 .55 .68

755 1600 18.9 64,400 4940 .42 .54 .66 18.0 61,500 5340 .43 .55 .68 17.1 58,400 5740 .43 .56 .69 16.1 55,100 6130 .43 .57 .71

850 1800 19.2 65,500 4990 .43 .56 .69 18.3 62,500 5390 .43 .57 .70 17.4 59,300 5790 .44 .58 .72 16.4 55,900 6190 .44 .59 .74

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−060 � CB30M−51 − CB30U−51 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

HS29 / Page 56

Page 57: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 3 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C670 1425 16.2 55,300 4570 .70 .82 .93 15.5 52,800 4920 .71 .84 .95 14.7 50,100 5270 .72 .86 .97 13.9 47,300 5620 .74 .88 .99

765 1625 16.6 56,500 4620 .72 .85 .97 15.8 53,900 4970 .73 .87 .98 15.0 51,200 5330 .75 .89 1.00 14.2 48,300 5680 .77 .91 1.00

850 1805 16.9 57,600 4660 .74 .88 .99 16.1 54,900 5020 .75 .90 1.00 15.3 52,100 5380 .77 .92 1.00 14.4 49,200 5750 .79 .95 1.00

670 1425 17.3 59,100 4720 .55 .67 .79 16.5 56,400 5090 .56 .68 .80 15.7 53,500 5460 .56 .69 .82 14.8 50,500 5830 .57 .71 .84

765 1625 17.6 60,200 4780 .56 .69 .82 16.8 57,400 5150 .57 .70 .83 16.0 54,500 5520 .58 .72 .86 15.1 51,400 5890 .59 .74 .88

850 1805 17.9 61,100 4820 .58 .71 .85 17.1 58,300 5190 .58 .73 .87 16.2 55,300 5570 .59 .75 .89 15.2 52,000 5940 .61 .77 .92

670 1425 18.5 63,000 4900 .42 .53 .64 17.6 60,200 5290 .42 .54 .65 16.8 57,200 5680 .42 .55 .67 15.8 54,000 6070 .43 .56 .69

765 1625 18.8 64,200 4950 .42 .54 .66 18.0 61,300 5340 .43 .55 .68 17.1 58,200 5740 .43 .56 .70 16.1 54,900 6130 .43 .57 .72

850 1805 19.1 65,200 4990 .43 .56 .69 18.2 62,200 5390 .43 .57 .70 17.3 59,000 5780 .44 .58 .72 16.3 55,600 6180 .44 .59 .74

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−060 � CB31MV−51 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C780 1650 16.9 57,800 4730 .72 .85 .97 16.1 55,100 5090 .73 .87 .99 15.3 52,300 5460 .75 .89 1.00 14.5 49,400 5820 .77 .92 1.00

850 1800 17.2 58,700 4770 .74 .88 .99 16.4 56,000 5140 .75 .90 1.00 15.6 53,100 5500 .77 .92 1.00 14.7 50,100 5870 .79 .95 1.00

920 1950 17.4 59,400 4800 .76 .90 1.00 16.6 56,700 5170 .77 .92 1.00 15.8 53,800 5550 .79 .95 1.00 14.9 50,800 5920 .81 .97 1.00

780 1650 18.0 61,500 4890 .56 .69 .82 17.2 58,700 5270 .57 .71 .84 16.3 55,700 5650 .58 .72 .86 15.4 52,500 6040 .59 .74 .89

850 1800 18.3 62,300 4920 .57 .71 .85 17.4 59,500 5310 .58 .73 .87 16.5 56,300 5690 .59 .75 .89 15.6 53,100 6080 .61 .77 .92

920 1950 18.5 63,000 4950 .59 .73 .87 17.6 60,100 5340 .59 .75 .89 16.7 56,900 5730 .61 .77 .92 15.7 53,600 6120 .62 .79 .94

780 1650 19.2 65,600 5070 .42 .55 .67 18.4 62,700 5470 .43 .55 .68 17.4 59,500 5880 .43 .56 .70 16.4 56,100 6280 .43 .58 .72

850 1800 19.5 66,400 5100 .43 .56 .69 18.6 63,400 5510 .43 .57 .70 17.6 60,100 5920 .43 .58 .72 16.6 56,700 6320 .44 .59 .74

920 1950 19.7 67,100 5130 .43 .57 .71 18.8 64,000 5540 .44 .58 .72 17.8 60,700 5950 .44 .59 .74 16.8 57,200 6360 .44 .61 .77

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−060 � CB30M−65 − CB30U−65 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C765 1625 16.7 57,000 4700 .71 .85 .96 15.9 54,400 5050 .73 .86 .98 15.2 51,700 5410 .74 .89 1.00 14.3 48,700 5780 .76 .91 1.00

850 1805 17.1 58,200 4750 .74 .88 .99 16.3 55,600 5110 .75 .90 1.00 15.4 52,700 5480 .77 .92 1.00 14.6 49,800 5850 .79 .95 1.00

945 2005 17.3 59,200 4790 .76 .91 1.00 16.6 56,500 5160 .78 .93 1.00 15.7 53,700 5530 .80 .95 1.00 14.9 50,700 5910 .82 .98 1.00

765 1625 17.8 60,800 4850 .56 .69 .81 17.0 58,000 5230 .57 .70 .83 16.1 55,000 5610 .58 .72 .85 15.2 51,900 5990 .59 .74 .88

850 1805 18.1 61,800 4900 .58 .71 .85 17.3 59,000 5280 .58 .73 .87 16.4 55,900 5670 .59 .75 .89 15.4 52,700 6050 .61 .77 .92

945 2005 18.4 62,700 4940 .59 .74 .88 17.5 59,800 5320 .60 .76 .90 16.6 56,700 5710 .61 .78 .93 15.6 53,400 6100 .63 .80 .95

765 1625 19.0 64,800 5030 .42 .54 .66 18.1 61,900 5430 .43 .55 .68 17.2 58,800 5830 .43 .56 .69 16.2 55,400 6240 .43 .57 .71

850 1805 19.3 65,900 5080 .43 .56 .69 18.4 62,900 5480 .43 .57 .70 17.5 59,700 5890 .44 .58 .72 16.5 56,300 6290 .44 .59 .74

945 2005 19.6 66,800 5110 .43 .57 .72 18.7 63,700 5520 .44 .59 .73 17.7 60,400 5930 .44 .60 .75 16.7 56,900 6340 .45 .61 .78

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−060 � CB31MV−65 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C710 1500 16.2 55,200 4680 .70 .83 .94 15.4 52,700 5030 .71 .85 .96 14.7 50,100 5390 .73 .86 .98 13.9 47,300 5750 .74 .89 1.00

800 1700 16.5 56,400 4730 .73 .86 .98 15.8 53,900 5090 .74 .88 .99 15.0 51,200 5460 .76 .90 1.00 14.2 48,400 5820 .78 .93 1.00

895 1900 16.9 57,500 4780 .75 .89 1.00 16.1 54,900 5150 .77 .91 1.00 15.3 52,200 5510 .78 .94 1.00 14.4 49,300 5890 .81 .96 1.00

710 1500 17.2 58,800 4830 .56 .68 .80 16.5 56,200 5210 .56 .69 .81 15.6 53,400 5580 .57 .70 .83 14.8 50,400 5970 .58 .72 .86

800 1700 17.6 60,000 4890 .57 .70 .83 16.8 57,300 5260 .58 .71 .85 15.9 54,400 5640 .58 .73 .87 15.0 51,300 6030 .60 .75 .90

895 1900 17.9 61,000 4930 .58 .73 .86 17.1 58,200 5310 .59 .74 .88 16.2 55,200 5690 .60 .76 .91 15.2 52,000 6080 .62 .78 .93

710 1500 18.4 62,800 5000 .42 .54 .65 17.6 60,000 5400 .42 .54 .66 16.7 57,100 5800 .43 .55 .68 15.8 53,900 6200 .43 .56 .69

800 1700 18.8 64,000 5050 .43 .55 .67 17.9 61,100 5460 .43 .56 .69 17.0 58,100 5860 .43 .57 .71 16.1 54,800 6270 .44 .58 .73

895 1900 19.0 65,000 5100 .43 .57 .70 18.2 62,000 5510 .43 .58 .72 17.3 58,900 5910 .44 .59 .74 16.3 55,500 6320 .44 .60 .76

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29−060 � CVP10�51/EC10Q4 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

HS29 / Page 57

Page 58: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 3 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

29°C24°C 27°C29°C27°C24°C29°C27°C24°C29°C27°C24°C685 1450 16.1 54,900 4670 .71 .83 .94 15.4 52,500 5030 .72 .85 .96 14.6 49,900 5390 .73 .87 .98 13.8 47,100 5750 .75 .89 1.00

780 1650 16.5 56,300 4730 .73 .87 .98 15.8 53,800 5090 .74 .89 .99 15.0 51,100 5460 .76 .91 1.00 14.2 48,300 5830 .78 .93 1.00

875 1850 16.8 57,400 4780 .76 .90 1.00 16.1 54,800 5150 .77 .92 1.00 15.3 52,100 5520 .79 .94 1.00 14.4 49,300 5900 .81 .97 1.00

685 1450 17.1 58,500 4830 .56 .68 .80 16.4 55,900 5200 .56 .69 .81 15.6 53,100 5580 .57 .70 .83 14.7 50,100 5960 .58 .72 .86

780 1650 17.5 59,800 4880 .57 .70 .83 16.7 57,000 5260 .58 .72 .85 15.9 54,200 5640 .59 .74 .87 15.0 51,100 6030 .60 .76 .90

875 1850 17.8 60,700 4920 .59 .73 .87 17.0 58,000 5310 .60 .75 .89 16.1 55,000 5690 .61 .77 .91 15.2 51,900 6080 .62 .79 .94

685 1450 18.3 62,500 5000 .42 .54 .65 17.5 59,800 5400 .42 .54 .66 16.6 56,800 5800 .43 .55 .68 15.7 53,600 6200 .43 .56 .70

780 1650 18.7 63,800 5050 .43 .55 .68 17.8 60,900 5450 .43 .56 .69 16.9 57,800 5860 .43 .57 .71 16.0 54,600 6260 .44 .59 .73

875 1850 19.0 64,700 5090 .43 .57 .71 18.1 61,800 5500 .44 .58 .72 17.2 58,600 5910 .44 .59 .74 16.2 55,300 6320 .45 .61 .77

Enter�ingWetBulb

Temper�ature

TotalAir

Volume

L/s cfm

TotalCoolingCapacity

Btuh

Com�pressorMotorWattsInput

SensibleTo Total

Ratio (S/T)Dry Bulb Dry Bulb Dry Bulb Dry Bulb

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)

SensibleTo Total

Ratio (S/T)Com�

pressorMotorWattsInput

Com�pressorMotorWattsInput

Com�pressorMotorWattsInput

TotalCoolingCapacity

TotalCoolingCapacity

TotalCoolingCapacity

Outdoor Air Temperature Entering Condenser Coil

63°F(17.2°C)

67°F(19.4°C)

71°F(21.7°C)

BtuhkW kW kWBtuh BtuhkW

85°F (29°C) 95°F (35°C) 105°F (41°C) 115°F (46°C)

HS29�060 � CVP10�65/EC10Q5 − TXV Systems Only

75°F 80°F 85°F 75°F 80°F 85°F 75°F 80°F85°F 75°F 80°F85°F

Outdoor Air Temperature Entering Outdoor Coil

Total85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)

EnteringWet BulbTempera�

TotalAir

VolumeTotal

Cooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Tempera�ture

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

HS29−062 � C33−50/60C − C26−51/65 COOLING CAPACITY − TXV Systems Only

63�F1500 710 58.1 17.0 4.92 .69 .83 .95 56.0 16.4 5.47 .70 .85 .97 53.4 15.6 6.09 .72 .87 .99 50.4 14.8 6.78 .74 .89 1.00

63�F(17�C)

1700 800 59.5 17.4 4.96 .72 .87 .99 57.3 16.8 5.51 .73 .88 1.00 54.7 16.0 6.13 .75 .91 1.00 51.6 15.1 6.83 .77 .94 1.00(17�C)

1900 895 60.7 17.8 5.00 .75 .90 1.00 58.4 17.1 5.55 .76 .92 1.00 55.7 16.3 6.17 .78 .95 1.00 52.6 15.4 6.88 .81 .97 1.00

67�F1500 710 62.1 18.2 5.04 .55 .67 .79 59.7 17.5 5.59 .55 .68 .81 56.9 16.7 6.21 .56 .69 .83 53.6 15.7 6.92 .57 .71 .86

67�F(19�C)

1700 800 63.3 18.6 5.07 .56 .69 .83 60.8 17.8 5.62 .57 .71 .85 57.9 17.0 6.25 .57 .72 .87 54.5 16.0 6.96 .59 .75 .90(19�C)

1900 895 64.3 18.8 5.10 .57 .72 .87 61.8 18.1 5.66 .58 .74 .89 58.9 17.3 6.28 .59 .75 .91 55.3 16.2 6.99 .61 .78 .94

71�F1500 710 66.3 19.4 5.16 .41 .53 .64 63.8 18.7 5.72 .41 .53 .65 60.8 17.8 6.36 .41 .54 .67 57.2 16.8 7.08 .42 .55 .69

71�F(22�C)

1700 800 67.6 19.8 5.20 .42 .54 .67 64.9 19.0 5.76 .42 .55 .68 61.8 18.1 6.40 .42 .56 .70 58.2 17.1 7.11 .43 .57 .72(22�C)

1900 895 68.5 20.1 5.23 .42 .56 .70 65.8 19.3 5.79 .42 .57 .71 62.6 18.3 6.43 .43 .58 .73 58.9 17.3 7.15 .43 .59 .76

HS29−062 � C33−60D − C23−51/65 COOLING CAPACITY − TXV Systems Only

63�F1750 825 59.9 17.6 4.55 .73 .87 .99 57.6 16.9 5.05 .74 .89 1.00 55.0 16.1 5.62 .76 .91 1.00 51.9 15.2 6.26 .78 .94 1.00

63�F(17�C)

1950 920 61.0 17.9 4.58 .76 .91 1.00 58.7 17.2 5.08 .77 .92 1.00 56.0 16.4 5.65 .79 .95 1.00 52.9 15.5 6.30 .81 .97 1.00(17�C)

2150 1015 62.0 18.2 4.61 .78 .94 1.00 59.7 17.5 5.11 .80 .95 1.00 57.0 16.7 5.68 .82 .97 1.00 53.9 15.8 6.34 .84 .99 1.00

67�F1750 825 63.8 18.7 4.65 .57 .70 .84 61.3 18.0 5.16 .58 .72 .86 58.4 17.1 5.73 .58 .73 .88 55.0 16.1 6.39 .60 .75 .91

67�F(19�C)

1950 920 64.7 19.0 4.67 .58 .73 .87 62.2 18.2 5.18 .59 .74 .89 59.2 17.3 5.76 .60 .76 .91 55.8 16.4 6.41 .61 .79 .94(19�C)

2150 1015 65.6 19.2 4.70 .60 .76 .91 63.0 18.5 5.21 .61 .77 .92 59.9 17.6 5.78 .62 .79 .95 56.4 16.5 6.44 .63 .82 .97

71�F1750 825 68.1 20.0 4.76 .42 .55 .68 65.5 19.2 5.28 .43 .56 .69 62.4 18.3 5.86 .43 .57 .71 58.7 17.2 6.52 .43 .58 .73

71�F(22�C)

1950 920 69.1 20.3 4.79 .43 .57 .71 66.4 19.5 5.31 .43 .58 .72 63.2 18.5 5.89 .44 .59 .74 59.4 17.4 6.55 .44 .60 .76(22�C)

2150 1015 69.9 20.5 4.81 .43 .58 .73 67.1 19.7 5.33 .44 .59 .75 63.8 18.7 5.92 .44 .61 .77 60.0 17.6 6.58 .45 .62 .80

HS29−062 � C33−62D − C26−65EAP − CH33−62D−F − CH23−68 COOLING CAPACITY − TXV Systems Only

63�F1600 755 62.0 18.2 4.99 .71 .85 .97 59.6 17.5 5.54 .72 .86 .99 56.8 16.6 6.16 .73 .89 1.00 53.6 15.7 6.87 .75 .91 1.00

63�F(17�C)

1800 850 63.3 18.6 5.03 .73 .88 1.00 60.9 17.8 5.58 .74 .90 1.00 58.1 17.0 6.20 .76 .92 1.00 54.7 16.0 6.92 .79 .95 1.00(17�C)

2000 945 64.5 18.9 5.06 .76 .92 1.00 62.0 18.2 5.62 .77 .94 1.00 59.1 17.3 6.25 .79 .96 1.00 55.7 16.3 6.96 .82 .98 1.00

67�F1600 755 66.2 19.4 5.11 .55 .68 .81 63.6 18.6 5.66 .56 .69 .83 60.6 17.8 6.30 .57 .71 .85 57.0 16.7 7.01 .58 .73 .88

67�F(19�C)

1800 850 67.4 19.8 5.14 .57 .71 .85 64.7 19.0 5.70 .58 .72 .87 61.6 18.1 6.33 .59 .74 .89 57.9 17.0 7.05 .60 .76 .92(19�C)

2000 945 68.4 20.0 5.18 .58 .73 .88 65.7 19.3 5.73 .59 .75 .90 62.4 18.3 6.37 .60 .77 .93 58.6 17.2 7.08 .62 .80 .96

71�F1600 755 70.8 20.7 5.25 .42 .54 .65 68.0 19.9 5.80 .42 .54 .67 64.7 19.0 6.45 .42 .55 .68 60.9 17.8 7.17 .42 .56 .70

71�F(22�C)

1800 850 72.0 21.1 5.28 .42 .55 .68 69.1 20.3 5.85 .42 .56 .69 65.7 19.3 6.49 .43 .57 .71 61.7 18.1 7.21 .43 .58 .74(22�C)

2000 945 72.9 21.4 5.31 .43 .57 .71 70.1 20.5 5.87 .43 .58 .72 66.6 19.5 6.52 .43 .59 .74 62.4 18.3 7.24 .44 .60 .77

HS29−062 � CR26−48 COOLING CAPACITY − TXV Systems Only

63�F1500 710 55.2 16.2 4.91 .71 .84 .96 53.2 15.6 5.45 .72 .86 .97 50.9 14.9 6.07 .74 .87 .99 48.1 14.1 6.78 .75 .90 1.00

63�F(17�C)

1700 800 56.4 16.5 4.94 .73 .87 .99 54.3 15.9 5.49 .75 .89 1.00 51.9 15.2 6.11 .76 .91 1.00 49.0 14.4 6.83 .78 .93 1.00(17�C)

1900 895 57.4 16.8 4.97 .76 .90 1.00 55.3 16.2 5.52 .77 .92 1.00 52.9 15.5 6.15 .79 .94 1.00 50.0 14.7 6.87 .81 .96 1.00

67�F1500 710 59.1 17.3 5.01 .56 .69 .81 56.9 16.7 5.57 .57 .70 .82 54.3 15.9 6.20 .57 .71 .84 51.3 15.0 6.92 .58 .72 .86

67�F(19�C)

1700 800 60.2 17.6 5.05 .57 .71 .84 57.9 17.0 5.60 .58 .72 .86 55.3 16.2 6.24 .59 .73 .88 52.1 15.3 6.95 .60 .76 .90(19�C)

1900 895 61.1 17.9 5.07 .59 .73 .87 58.8 17.2 5.63 .59 .75 .89 56.1 16.4 6.27 .60 .76 .91 52.9 15.5 6.97 .62 .78 .94

71�F1500 710 63.1 18.5 5.13 .43 .54 .66 60.8 17.8 5.69 .43 .55 .67 58.1 17.0 6.34 .43 .55 .68 54.8 16.1 7.06 .43 .57 .70

71�F(22�C)

1700 800 64.2 18.8 5.17 .43 .56 .68 61.9 18.1 5.73 .43 .56 .69 59.0 17.3 6.37 .43 .57 .71 55.7 16.3 7.10 .44 .58 .73(22�C)

1900 895 65.2 19.1 5.19 .44 .57 .71 62.7 18.4 5.76 .44 .58 .72 59.8 17.5 6.40 .44 .59 .74 56.4 16.5 7.13 .45 .60 .76

HS29−062 � CR26−60 COOLING CAPACITY − TXV Systems Only

63�F1800 850 59.1 17.3 4.99 .75 .89 1.00 56.9 16.7 5.54 .76 .91 1.00 54.3 15.9 6.15 .78 .93 1.00 51.2 15.0 6.86 .80 .95 1.00

63�F(17�C)

2000 945 60.1 17.6 5.02 .77 .92 1.00 57.9 17.0 5.57 .79 .94 1.00 55.3 16.2 6.19 .81 .96 1.00 52.2 15.3 6.91 .83 .98 1.00(17�C)

2200 1040 61.1 17.9 5.05 .80 .95 1.00 58.8 17.2 5.60 .81 .97 1.00 56.2 16.5 6.23 .83 .98 1.00 53.2 15.6 6.94 .86 1.00 1.00

67�F1800 850 62.8 18.4 5.10 .58 .72 .86 60.4 17.7 5.65 .59 .74 .88 57.5 16.9 6.28 .60 .75 .90 54.1 15.9 6.99 .61 .78 .92

67�F(19�C)

2000 945 63.7 18.7 5.12 .59 .75 .89 61.2 17.9 5.68 .60 .76 .91 58.3 17.1 6.31 .62 .78 .93 54.8 16.1 7.02 .63 .81 .96(19�C)

2200 1040 64.5 18.9 5.14 .61 .78 .92 61.9 18.1 5.70 .62 .79 .94 58.9 17.3 6.33 .63 .81 .96 55.4 16.2 7.05 .65 .84 .99

71�F1800 850 67.1 19.7 5.23 .43 .56 .70 64.5 18.9 5.79 .43 .57 .71 61.3 18.0 6.43 .44 .58 .73 57.7 16.9 7.15 .44 .60 .75

71�F(22�C)

2000 945 67.9 19.9 5.25 .44 .58 .72 65.3 19.1 5.81 .44 .59 .74 62.1 18.2 6.46 .44 .60 .76 58.4 17.1 7.18 .45 .62 .78(22�C)

2200 1040 68.7 20.1 5.28 .44 .60 .75 65.9 19.3 5.84 .44 .61 .77 62.7 18.4 6.48 .45 .62 .79 58.9 17.3 7.20 .46 .64 .82

HS29 / Page 58

Page 59: CONDENSING UNITS HS29 - LENNOX EMEAwebmanuals.lennoxeurope.com/Out of Production/Condensing_units/HS... · mizes gas leakage and maximizes efficiency. Scroll compressor is tolerant

RATINGS − 3 PHASENOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

Outdoor Air Temperature Entering Outdoor Coil

Total 85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)

EnteringWet BulbTempera�

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Tempera�ture

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulb

CoolingCapacity

CompMotor

kWDry Bulbture

cfm L/s kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

kBtuh kW

kWInput 75�F

24�C80�F27�C

85�F29�C

HS29−062 � CH33−60D−F − CH23−65 COOLING CAPACITY − TXV Systems Only

63�F1800 850 59.9 17.6 4.97 .76 .90 1.00 57.7 16.9 5.52 .77 .92 1.00 55.1 16.1 6.14 .79 .94 1.00 52.1 15.3 6.85 .81 .96 1.00

63�F(17�C)

2000 945 61.0 17.9 5.00 .78 .93 1.00 58.7 17.2 5.55 .80 .95 1.00 56.1 16.4 6.18 .82 .97 1.00 53.1 15.6 6.88 .84 .99 1.00(17�C)

2200 1040 62.0 18.2 5.03 .81 .96 1.00 59.8 17.5 5.58 .82 .97 1.00 57.2 16.8 6.20 .84 .99 1.00 54.1 15.9 6.92 .87 1.00 1.00

67�F1800 850 63.5 18.6 5.07 .59 .73 .87 61.1 17.9 5.62 .59 .74 .89 58.2 17.1 6.25 .60 .76 .91 54.8 16.1 6.96 .62 .78 .93

67�F(19�C)

2000 945 64.4 18.9 5.10 .60 .76 .90 61.9 18.1 5.65 .61 .77 .92 59.0 17.3 6.28 .62 .79 .94 55.5 16.3 6.99 .64 .82 .96(19�C)

2200 1040 65.2 19.1 5.12 .62 .79 .93 62.6 18.3 5.67 .63 .80 .95 59.7 17.5 6.30 .64 .82 .97 56.2 16.5 7.02 .66 .85 .99

71�F1800 850 67.7 19.8 5.19 .43 .57 .71 65.1 19.1 5.75 .43 .58 .72 62.0 18.2 6.39 .44 .59 .74 58.4 17.1 7.11 .44 .60 .76

71�F(22�C)

2000 945 68.6 20.1 5.22 .44 .59 .73 65.9 19.3 5.78 .44 .60 .75 62.8 18.4 6.42 .45 .61 .77 59.0 17.3 7.15 .45 .63 .79(22�C)

2200 1040 69.3 20.3 5.24 .44 .60 .76 66.6 19.5 5.80 .45 .61 .78 63.3 18.6 6.44 .45 .63 .80 59.6 17.5 7.16 .46 .65 .83

HS29−062 � CB30M−51 − CB30U−51 COOLING CAPACITY − TXV Systems Only

63�F1400 660 56.6 16.6 4.03 .68 .81 .93 54.5 16.0 4.48 .69 .83 .95 52.0 15.2 4.99 .71 .85 .97 49.0 14.4 5.56 .72 .87 .99

63�F(17�C)

1600 755 58.1 17.0 4.07 .71 .85 .97 55.9 16.4 4.52 .72 .86 .98 53.3 15.6 5.03 .73 .88 1.00 50.2 14.7 5.60 .76 .91 1.00(17�C)

1800 850 59.3 17.4 4.11 .73 .88 1.00 57.1 16.7 4.55 .75 .90 1.00 54.4 15.9 5.06 .77 .92 1.00 51.3 15.0 5.65 .79 .95 1.00

67�F1400 660 60.6 17.8 4.13 .54 .66 .77 58.3 17.1 4.59 .55 .67 .79 55.6 16.3 5.09 .55 .68 .81 52.3 15.3 5.68 .56 .70 .83

67�F(19�C)

1600 755 62.0 18.2 4.17 .55 .68 .81 59.6 17.5 4.62 .56 .69 .83 56.8 16.6 5.14 .57 .71 .85 53.4 15.6 5.72 .58 .73 .88(19�C)

1800 850 63.1 18.5 4.20 .57 .71 .85 60.6 17.8 4.65 .58 .72 .87 57.7 16.9 5.17 .58 .74 .89 54.2 15.9 5.75 .60 .76 .92

71�F1400 660 64.9 19.0 4.24 .41 .52 .63 62.4 18.3 4.70 .41 .53 .64 59.5 17.4 5.22 .42 .53 .65 56.0 16.4 5.81 .42 .54 .67

71�F(22�C)

1600 755 66.3 19.4 4.28 .42 .54 .65 63.7 18.7 4.74 .42 .54 .67 60.6 17.8 5.26 .42 .55 .68 57.1 16.7 5.85 .43 .56 .70(22�C)

1800 850 67.4 19.8 4.31 .42 .55 .68 64.7 19.0 4.77 .42 .56 .70 61.6 18.1 5.29 .43 .57 .71 57.8 16.9 5.88 .43 .58 .74

HS29−062 � CB31MV−51 COOLING CAPACITY − TXV Systems Only

63�F1625 765 57.5 16.9 3.94 .71 .85 .97 55.3 16.2 4.37 .72 .87 .99 52.7 15.4 4.86 .74 .89 1.00 49.7 14.6 5.42 .76 .92 1.00

63�F(17�C)

1825 860 58.7 17.2 3.97 .74 .89 1.00 56.5 16.6 4.40 .75 .91 1.00 53.8 15.8 4.89 .77 .93 1.00 50.7 14.9 5.46 .79 .96 1.00(17�C)

2025 955 59.8 17.5 3.99 .76 .92 1.00 57.5 16.9 4.42 .78 .94 1.00 54.8 16.1 4.92 .80 .96 1.00 51.7 15.2 5.49 .82 .99 1.00

67�F1625 765 61.3 18.0 4.03 .56 .68 .82 59.0 17.3 4.46 .56 .70 .83 56.1 16.4 4.96 .57 .71 .85 52.8 15.5 5.53 .58 .73 .88

67�F(19�C)

1825 860 62.4 18.3 4.06 .57 .71 .85 59.9 17.6 4.49 .58 .72 .87 57.1 16.7 4.99 .59 .74 .89 53.6 15.7 5.55 .60 .77 .92(19�C)

2025 955 63.3 18.6 4.08 .58 .74 .89 60.8 17.8 4.51 .59 .75 .91 57.8 16.9 5.01 .60 .77 .93 54.3 15.9 5.58 .62 .80 .96

71�F1625 765 65.6 19.2 4.13 .42 .54 .66 63.0 18.5 4.58 .42 .55 .67 60.0 17.6 5.08 .42 .55 .69 56.4 16.5 5.65 .43 .57 .71

71�F(22�C)

1825 860 66.6 19.5 4.16 .42 .55 .69 64.0 18.8 4.61 .42 .56 .70 60.9 17.8 5.11 .43 .57 .72 57.2 16.8 5.68 .43 .59 .74(22�C)

2025 955 67.5 19.8 4.18 .43 .57 .71 64.8 19.0 4.63 .43 .58 .73 61.6 18.1 5.13 .43 .59 .75 57.8 16.9 5.70 .44 .61 .77

HS29−062 � CB29M−65 − CB28UH−060 COOLING CAPACITY − TXV Systems Only

63�F1900 895 60.7 17.8 4.10 .76 .91 1.00 58.5 17.1 4.55 .77 .92 1.00 55.9 16.4 5.07 .79 .94 1.00 52.9 15.5 5.65 .81 .97 1.00

63�F(17�C)

2000 945 61.2 17.9 4.11 .77 .92 1.00 59.1 17.3 4.56 .78 .94 1.00 56.4 16.5 5.08 .80 .96 1.00 53.4 15.6 5.67 .83 .98 1.00(17�C)

2100 990 61.7 18.1 4.12 .78 .94 1.00 59.5 17.4 4.57 .80 .95 1.00 56.9 16.7 5.10 .82 .97 1.00 53.9 15.8 5.68 .84 .99 1.00

67�F1900 895 64.4 18.9 4.18 .58 .73 .87 61.9 18.1 4.63 .59 .75 .89 59.1 17.3 5.15 .60 .76 .91 55.6 16.3 5.74 .62 .79 .94

67�F(19�C)

2000 945 64.8 19.0 4.19 .59 .74 .89 62.3 18.3 4.64 .60 .76 .91 59.4 17.4 5.16 .61 .78 .93 56.0 16.4 5.75 .63 .80 .96(19�C)

2100 990 65.2 19.1 4.19 .60 .76 .91 62.7 18.4 4.65 .61 .77 .92 59.8 17.5 5.17 .62 .79 .94 56.3 16.5 5.76 .63 .82 .97

71�F1900 895 68.6 20.1 4.27 .43 .57 .71 66.1 19.4 4.74 .43 .58 .72 63.0 18.5 5.27 .44 .59 .74 59.3 17.4 5.86 .44 .60 .76

71�F(22�C)

2000 945 69.0 20.2 4.28 .43 .58 .72 66.4 19.5 4.75 .44 .59 .74 63.3 18.6 5.28 .44 .60 .75 59.6 17.5 5.87 .45 .61 .78(22�C)

2100 990 69.4 20.3 4.29 .44 .58 .73 66.7 19.5 4.76 .44 .59 .75 63.6 18.6 5.29 .44 .61 .77 59.9 17.6 5.88 .45 .62 .80

HS29−062 � CB30M−65 − CB30U−65 COOLING CAPACITY − TXV Systems Only

63�F1850 875 60.2 17.6 4.02 .75 .89 1.00 57.9 17.0 4.45 .76 .91 1.00 55.2 16.2 4.95 .78 .93 1.00 52.0 15.2 5.52 .80 .96 1.00

63�F(17�C)

1950 920 60.7 17.8 4.03 .76 .91 1.00 58.4 17.1 4.47 .77 .93 1.00 55.7 16.3 4.97 .79 .95 1.00 52.5 15.4 5.54 .82 .98 1.00(17�C)

2050 970 61.3 18.0 4.04 .77 .93 1.00 59.0 17.3 4.48 .79 .94 1.00 56.2 16.5 4.99 .81 .96 1.00 53.0 15.5 5.56 .83 .99 1.00

67�F1850 875 64.0 18.8 4.10 .58 .72 .86 61.5 18.0 4.55 .59 .73 .88 58.5 17.1 5.05 .60 .75 .90 55.0 16.1 5.62 .61 .77 .93

67�F(19�C)

1950 920 64.5 18.9 4.12 .59 .73 .88 61.9 18.1 4.57 .59 .75 .90 58.9 17.3 5.07 .60 .77 .92 55.3 16.2 5.64 .62 .79 .95(19�C)

2050 970 64.9 19.0 4.13 .59 .75 .90 62.3 18.3 4.57 .60 .76 .91 59.3 17.4 5.08 .61 .78 .94 55.7 16.3 5.65 .63 .81 .97

71�F1850 875 68.3 20.0 4.21 .43 .56 .70 65.6 19.2 4.66 .43 .57 .71 62.4 18.3 5.17 .43 .58 .73 58.6 17.2 5.75 .44 .60 .75

71�F(22�C)

1950 920 68.8 20.2 4.22 .43 .57 .71 66.0 19.3 4.68 .43 .58 .72 62.8 18.4 5.19 .44 .59 .74 58.9 17.3 5.76 .44 .61 .77(22�C)

2050 970 69.1 20.3 4.23 .43 .58 .72 66.4 19.5 4.69 .44 .59 .74 63.1 18.5 5.20 .44 .60 .76 59.3 17.4 5.77 .45 .62 .78

HS29−062 � CB31MV−65 COOLING CAPACITY − TXV Systems Only

63�F1805 850 59.6 17.5 4.15 .72 .87 1.00 57.3 16.8 4.60 .73 .89 1.00 54.7 16.0 5.11 .75 .92 1.00 51.5 15.1 5.70 .77 .95 1.00

63�F(17�C)

2005 945 60.7 17.8 4.17 .74 .91 1.00 58.4 17.1 4.62 .76 .93 1.00 55.6 16.3 5.15 .78 .96 1.00 52.5 15.4 5.74 .81 .98 1.00(17�C)

2205 1040 61.7 18.1 4.19 .77 .94 1.00 59.3 17.4 4.65 .79 .96 1.00 56.6 16.6 5.18 .81 .98 1.00 53.5 15.7 5.77 .84 1.00 1.00

67�F1805 850 63.4 18.6 4.24 .56 .69 .84 60.9 17.8 4.70 .56 .71 .86 58.0 17.0 5.22 .57 .72 .88 54.5 16.0 5.81 .59 .74 .91

67�F(19�C)

2005 945 64.3 18.8 4.26 .57 .72 .88 61.8 18.1 4.72 .58 .73 .89 58.8 17.2 5.24 .59 .75 .92 55.2 16.2 5.83 .60 .78 .95(19�C)

2205 1040 65.1 19.1 4.29 .59 .74 .91 62.5 18.3 4.74 .60 .76 .93 59.4 17.4 5.27 .61 .79 .96 55.8 16.4 5.86 .62 .82 .98

71�F1805 850 67.7 19.8 4.35 .41 .54 .67 65.0 19.0 4.82 .42 .55 .68 61.9 18.1 5.34 .42 .56 .70 58.1 17.0 5.94 .42 .57 .72

71�F(22�C)

2005 945 68.6 20.1 4.37 .42 .56 .70 65.8 19.3 4.84 .42 .57 .71 62.6 18.3 5.37 .42 .58 .73 58.8 17.2 5.96 .43 .59 .76(22�C)

2205 1040 69.3 20.3 4.39 .42 .57 .72 66.5 19.5 4.86 .43 .58 .74 63.2 18.5 5.39 .43 .60 .76 59.3 17.4 5.98 .44 .61 .79

HS29−062 � CVP10−65/EC10Q5 COOLING CAPACITY − TXV Systems Only

63�F1640 775 58.3 17.1 4.95 .74 .88 .99 56.2 16.5 5.50 .75 .89 1.00 53.6 15.7 6.13 .77 .91 1.00 50.6 14.8 6.83 .78 .94 1.00

63�F(17�C)

1840 870 59.6 17.5 4.99 .77 .91 1.00 57.3 16.8 5.54 .78 .93 1.00 54.8 16.1 6.16 .79 .95 1.00 51.8 15.2 6.87 .82 .97 1.00(17�C)

2040 965 60.7 17.8 5.03 .79 .94 1.00 58.5 17.1 5.58 .81 .96 1.00 55.9 16.4 6.20 .83 .98 1.00 52.8 15.5 6.92 .85 1.00 1.00

67�F1640 775 62.1 18.2 5.06 .57 .71 .84 59.7 17.5 5.61 .58 .72 .86 57.0 16.7 6.24 .59 .74 .88 53.6 15.7 6.95 .60 .76 .91

67�F(19�C)

1840 870 63.1 18.5 5.09 .59 .74 .88 60.7 17.8 5.65 .60 .75 .90 57.8 16.9 6.28 .61 .77 .92 54.4 15.9 6.99 .62 .80 .94(19�C)

2040 965 64.0 18.8 5.12 .61 .77 .91 61.5 18.0 5.67 .62 .79 .93 58.6 17.2 6.31 .63 .80 .95 55.2 16.2 7.02 .64 .83 .98

71�F1640 775 66.4 19.5 5.19 .43 .56 .69 63.8 18.7 5.75 .43 .56 .70 60.8 17.8 6.39 .43 .57 .72 57.2 16.8 7.11 .44 .59 .74

71�F(22�C)

1840 870 67.4 19.8 5.22 .43 .57 .72 64.8 19.0 5.78 .44 .58 .73 61.6 18.1 6.42 .44 .60 .75 58.0 17.0 7.14 .45 .61 .77(22�C)

2040 965 68.2 20.0 5.25 .44 .59 .75 65.5 19.2 5.81 .44 .60 .76 62.3 18.3 6.45 .45 .62 .78 58.6 17.2 7.17 .45 .63 .81

HS29 / Page 59