    Block 07 Calculation sheet

    Two 400mm pipes are used to handle the condenser water of Block 07(supply & return). We use a base platform at LL3 to cater the total weight of the pipes.

    1. Calculations for base platform

    Data

    - Selected beam for base platform 150x150 Data sheet is attached (Annex 01)

    B 150 mm

    D 150 mm

    t 7 mm

    Ix-x 1623 cm4

    Figure 1 : I - Beam detail

    - Yield strength of steel S 275 16 mm Data sheet is attached (Annex 02)

    275 Mpa

    - Technical data for anchor bolts are taken from fischer catalog

    - Condensor water riser height (m) 46.667 m Refer attached drawing (Annex 03)

    - Linear density of pipe (400mm),sch 40 with water 237.3 kg/m data sheet attached (Annex 04)

    Notes/Assumptions:- Self weight of I - beam is negligible

    - Load on the platform is considered as an UDL

    - Concreate wall is considered as cracked concreate

    - Beam is considered as simply supported beam

    w

    B

    1 Designed by : Chathura Siriwardhana

  • 7/25/2019 Condenser Water Pipe Base Support

    2/4

    Block 07 Calculation sheet

    Figure 2 : Forces on base platform at LL3

    a. Calculation for the beam

    Nos of beams 5

    Beam length 2.5

    Load per pipe with water 108.64 m

    Nos of pipes 2

    Total load 217.27 kNWith 1.5 safety factor (2W) 326 kN

    UDL(w) 130.40 kN/m

    UDL(w) per beam 26.08 kN/m

    Nos of brackets 9 Nos

    Considering vertical forces on the beams RA= RB(=wl/2) 32.60 kN

    Maximum bending moment on the beam (wl2/8) 20.38 kNm

    Maximum bending stress of the beam ( = -My/I) 188.31 Mpa < 275 Mpa OK

    b. Base plate design (refer ASD procedure)

    Allowable bearing stress on the MS plate (0.7 f'c) 192.5 Mpa f'c is compressive strengh of steel (=275Mpa)

    Required plate area (Axial force/bearing stress) 0.0008468 m2 N'xB' 0.03 0.029 m

    N and B are the diamentions of the base plate

    Considering vertical 250 mm pipe, 300 x 300 x 16 mm plate is selected.

    Plate thickness according to the Allowable Stree Design (ASD) Procedure (tp= max{m or n} (fp/(0.25Fy))) 0.0041 m

    4.18 mm < 16 mm OK

    l

    x

    A

    RA RB

    2 Designed by : Chathura Siriwardhana

  • 7/25/2019 Condenser Water Pipe Base Support

    3/4

    Block 07 Calculation sheet

    The base plate is checked for bending

    Note/ Assumptions:

    - Plate is considered as cantilevered beam

    - Axial force due to pipe riser act on the base plate as an UDL.

    UDL (w) 543.33 kN/m

    250 Maximum moment (wl2/8) 0.04 kNm

    Bending stress 3.32 Mpa < 0.75x275 Mpa OK

    Therefore plate does not fail due to bending

    Figure 3 : Bending moment on base plate

    c. Anchor bolts for vertical wall

    Note:

    - Nos of required bolts are calculated considering shear load

    - Fischer model FAZ ll 16 is considered for the analysis. Data sheet is attached (Annex 05)

    - Friction force between concrete wall and the end plate has not been considered.

    wl

    3 Designed by : Chathura Siriwardhana

  • 7/25/2019 Condenser Water Pipe Base Support

    4/4

    Block 07 Calculation sheet

    Fischer

    model

    FAZ ll

    Permissible

    shear load V

    perm

    RA

    (kN)

    bolts

    per

    beam

    (RA/Vpe

    rm)

    Required

    min bolts

    16 31.4 32.60 2 10 OK

    Figure 4 : Shear force on side plate of the base platform at LL3

    C1

    C2

    RA

    4 Designed by : Chathura Siriwardhana