7/25/2019 Condenser Water Pipe Base Support
1/4
Block 07 Calculation sheet
Two 400mm pipes are used to handle the condenser water of Block 07(supply & return). We use a base platform at LL3 to cater the total weight of the pipes.
1. Calculations for base platform
Data
- Selected beam for base platform 150x150 Data sheet is attached (Annex 01)
B 150 mm
D 150 mm
t 7 mm
Ix-x 1623 cm4
Figure 1 : I - Beam detail
- Yield strength of steel S 275 16 mm Data sheet is attached (Annex 02)
275 Mpa
- Technical data for anchor bolts are taken from fischer catalog
- Condensor water riser height (m) 46.667 m Refer attached drawing (Annex 03)
- Linear density of pipe (400mm),sch 40 with water 237.3 kg/m data sheet attached (Annex 04)
Notes/Assumptions:- Self weight of I - beam is negligible
- Load on the platform is considered as an UDL
- Concreate wall is considered as cracked concreate
- Beam is considered as simply supported beam
w
B
1 Designed by : Chathura Siriwardhana
-
7/25/2019 Condenser Water Pipe Base Support
2/4
Block 07 Calculation sheet
Figure 2 : Forces on base platform at LL3
a. Calculation for the beam
Nos of beams 5
Beam length 2.5
Load per pipe with water 108.64 m
Nos of pipes 2
Total load 217.27 kNWith 1.5 safety factor (2W) 326 kN
UDL(w) 130.40 kN/m
UDL(w) per beam 26.08 kN/m
Nos of brackets 9 Nos
Considering vertical forces on the beams RA= RB(=wl/2) 32.60 kN
Maximum bending moment on the beam (wl2/8) 20.38 kNm
Maximum bending stress of the beam ( = -My/I) 188.31 Mpa < 275 Mpa OK
b. Base plate design (refer ASD procedure)
Allowable bearing stress on the MS plate (0.7 f'c) 192.5 Mpa f'c is compressive strengh of steel (=275Mpa)
Required plate area (Axial force/bearing stress) 0.0008468 m2 N'xB' 0.03 0.029 m
N and B are the diamentions of the base plate
Considering vertical 250 mm pipe, 300 x 300 x 16 mm plate is selected.
Plate thickness according to the Allowable Stree Design (ASD) Procedure (tp= max{m or n} (fp/(0.25Fy))) 0.0041 m
4.18 mm < 16 mm OK
l
x
A
RA RB
2 Designed by : Chathura Siriwardhana
-
7/25/2019 Condenser Water Pipe Base Support
3/4
Block 07 Calculation sheet
The base plate is checked for bending
Note/ Assumptions:
- Plate is considered as cantilevered beam
- Axial force due to pipe riser act on the base plate as an UDL.
UDL (w) 543.33 kN/m
250 Maximum moment (wl2/8) 0.04 kNm
Bending stress 3.32 Mpa < 0.75x275 Mpa OK
Therefore plate does not fail due to bending
Figure 3 : Bending moment on base plate
c. Anchor bolts for vertical wall
Note:
- Nos of required bolts are calculated considering shear load
- Fischer model FAZ ll 16 is considered for the analysis. Data sheet is attached (Annex 05)
- Friction force between concrete wall and the end plate has not been considered.
wl
3 Designed by : Chathura Siriwardhana
-
7/25/2019 Condenser Water Pipe Base Support
4/4
Block 07 Calculation sheet
Fischer
model
FAZ ll
Permissible
shear load V
perm
RA
(kN)
bolts
per
beam
(RA/Vpe
rm)
Required
min bolts
16 31.4 32.60 2 10 OK
Figure 4 : Shear force on side plate of the base platform at LL3
C1
C2
RA
4 Designed by : Chathura Siriwardhana