condenser erection.doc

Upload: mohankrishna372

Post on 03-Apr-2018

231 views

Category:

Documents


2 download

TRANSCRIPT

  • 7/28/2019 condenser erection.doc

    1/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    Issued to Date of IssueTN VARDARAJAN/ CM/RIHAND

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    Prepared By Reviewed by Approved by Issued by

    O. D.SHARMA D K SHRIVASTAVA ML SAH B.P.RAO

    Sr.Mgr./ TS/PSWR SDGM/TSX/PSWR GM/TSX & SAS/PSWR Head/TSX

    1

    ERECTION MANUAL FOR CONDENSER

    RIHAND # 3&4 - 500 MW

  • 7/28/2019 condenser erection.doc

    2/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    PREFACE

    The erection manual of condenser for Rihand 3&4- 500 MW project

    provides guidelines for erection of Condenser. The procedure may require

    some minor alterations at site to meet the local site conditions.

    BHEL reserves the right to adopt alternate procedure, if necessasity

    arises.

    Feed back and suggestions from the users/task performers are solicited

    for further improvements.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    2

  • 7/28/2019 condenser erection.doc

    3/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    3

    CODIFICATIONFOR

    INSTRUCTION NUMBER

  • 7/28/2019 condenser erection.doc

    4/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    The following codification system is used for numbering of instructions and the

    codification of Log sheets is as per FAQ document.

    XX X XX XX XX XAlpha Numeric Numeric Numeric Numeric Alpha

    Type ofInstruction

    System Instuction No.

    System Designation

    Rating of Main Equipment

    Type of Manual

    Product Code

    1.1 Product Code

    B - BoilerBA - Boiler Aux.T - TurbineTA - Turbine Aux.

    G - GeneratorGA - Generator Aux.P - Power Plant PipingCI - C&I

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    4

  • 7/28/2019 condenser erection.doc

    5/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    1.2 Type of Manual

    1. - Erection

    2. - Commissioning

    3. - Services

    1.3 Rating of Main Equipment

    1. - 200/210 MW

    2. - 120 MW

    03. - 110 MW

    04. - 60 MW

    05. - 30 MW

    06. - 100 MW

    07. - 235 MW

    08. - 500 MW -KWU Design

    09. - 210 MW -KWU Design

    10. - 120 MW -KWU Design

    11. - 60 MW -KWU Design

    12. - 70MW -KWU Design

    13. - Industrial Units

    14. - 210 MW -Tower Type Concrete Pylem

    15. - 210MW -Tower Type Steel Structure

    16. - 500MW -Tower Type Once Through

    17. - 250MW

    18. - CCP

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    5

  • 7/28/2019 condenser erection.doc

    6/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    1.4 System Designation

    01 - General Instuction

    02 - Technical Data

    03 - Erection Strategy - Condenser

    4 - Erection Procedure- Condenser

    1.5 System Instuction No.

    01 - General Description02 - Technical Data

    03 - Erection Strategy - Condenser

    04 - Erection Procedure - Condenser

    1.6 System Instruction No.

    01 - General Instruction

    02 - Technical Data

    03 - Erection Strategy - Condenser

    04 - Erection Procedure - Condenser

    1.7 Type of Instruction

    G - General

    T - Technical

    L - Log Sheet

    C - Check List

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    6

  • 7/28/2019 condenser erection.doc

    7/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    7

    INDEX

  • 7/28/2019 condenser erection.doc

    8/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    INDEX

    S. NO. DESCRIPTIONINSTN NO.

    1. GENERAL DESCRIPTION TA1-08-0101G

    2. TECHNICAL DATA TA1-08-0202G

    3. ERECTION STRATEGY TA1-08-0303G

    4. ERECTION PROCEDURE TA1-08-0404G

    5. LIST OF DRAWINGS

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    8

  • 7/28/2019 condenser erection.doc

    9/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    9

    GENERAL DESCRIPTION

  • 7/28/2019 condenser erection.doc

    10/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    1.0 INTRODUCTION

    The condenser is a box type construction with divided water box

    design double flow; two pass which facilitates the operation of one half of

    the condenser while other half is under maintenance. The steam space is

    of rectangular cross-section with integral air-cooling section from where

    air and noncondensable gases are drawn out with the help of air

    evacuation equipment.

    2.0 CONSTRUCTION

    2.1 The surface condenser is mounted on spring supports. The

    condenser is welded with the exhaust hood of the low-pressure turbine.

    The tube plates are welded with the water chambers. Condensers are

    provided with domed shape water box. The condenser tubes aresupported within the condenser shell by tube support plates, which are so

    spaced that the vibrations of the tubes are prevented under normal

    operating conditions. The condenser is installed in such a way that all

    condenser tubes are drained automatically into the condenser water

    boxes.

    2.2 NECK

    Condition has been provided with an extension suitably to connect it to

    the turbine exhaust opening. Adequate internal clearance is provided. The

    rigid construction results in a sound-condenser combination for trouble

    free operation.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    10

  • 7/28/2019 condenser erection.doc

    11/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    2.3 TUBE LAYOUT

    The tube layout is of modular type reinforced having properly sized tube

    bundles. Steam lanes are designed from thermo-hydraulic considerations

    resulting into better heat transfer, effective deaeration and minimum

    pressure drop. Air-cooling zone is suitability located for effective venting.

    2.4 WATER BOX

    The water boxes of the condenser have been designed for smooth entry

    and uniform distribution of cooling water to all the tubes. The water boxes

    are removable type and have been provided with necessary hinged

    manholes for easy access to the interior for inspection. Each water box

    has been provided with a vent and drain connection. The circulating water

    connections of adequate size have been provided with water boxes.

    Safety guards have been provided to protect the operating personnel

    from failing during inspection or maintenance.

    2.5 HOT WELL

    Hot well (of adequate capacity) is divided longitudinally for detecting

    contamination of the condenser half. Suitable manholes are provided in

    each of the hot well sections for easy access and inspection. The

    condensate produced in the condenser & drains entering through flash

    vessels collect in the hot well from where the pass to the condensate

    pumps.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    11

  • 7/28/2019 condenser erection.doc

    12/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    12

    TECHNICAL DATA

  • 7/28/2019 condenser erection.doc

    13/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    STEAM SURFACE CONDENSER

    1. Manufacturer - BHEL / HARDWAR

    2. No. of passes -Two

    3. Tube length between tube plates (mm) -14630

    4. Total no. of tubes -24398

    5. Tube outside diameter

    and thickness (mm x mm) -OD 31.75 X 0.7112mm thick. Top 2 rows 0.889 mm thick.

    6. Tube material -Welded stainless steelASTMA249, TP304

    7. Water box design pr. Kg/cm (g) -5.0

    8. Water test pr. Kg/cm2 (g) -7.5

    9. Duration of test (min) -30

    10.Shell design pr. Kg/cm2 (abs) -Full vacuum and 1.08kg/cm2g

    11. Shell test pr. Kg/cm2 (abs) -Water fill up to LPTblade tip

    12. Duration of test hrs. -24 (min)

    13. No. of support plates -2 x 18

    14. No. of spring elements - 36

    15. Method of supporting the condenser. -Spring mounted

    16. Type of condenser neck to LP turbine casing -Welded joint

    17. WEIGHTS (approx)

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    13

  • 7/28/2019 condenser erection.doc

    14/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    a). EMPTY WEIGHT

    i. Condenser (without spring) with LP heater no.1 - 710,000kgs.

    b). OPERATING WEIGHT

    Condenser + LP heater no.1 - 1260,000 kgs.

    c). FLOODED WEIGHT

    Water filled up to LPT blade tip of last stage - 2100,000 kgs.

    with CW side and LP heater no.1

    d). Weight of cooling water - 448,000 kgs.

    e). Weight of spring elements - 32,000 kgs.

    Ref: Drg No: - 0-160-10-700 43c 80 Rev 02 Condenser assembly.

    f). Weight of single heaviest part (front water box) - 30,000kgs.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    14

  • 7/28/2019 condenser erection.doc

    15/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    15

    ERECTION STRATEGY

  • 7/28/2019 condenser erection.doc

    16/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    ERECTION STRATEGY

    The condenser to be assembled and erected at Rihand 2 x 500MW is

    supplied in various components from the works.

    * Loose parts mainly comprise of the following:

    i) Bottem plate.

    ii) Turbine & Generator side wall plates.

    Iii Dome walls.

    iv) Front water chambers and Rear water chambers with tube plates.

    v) Tube support plates 2 x 18 nos.

    vi) Hot well.

    vii) Spring elements - 36 nos.

    viii) Steam throw devices - 2 nos.

    ix) Condenser tubes.

    (I) PREPARATION FOR ERECTION

    1. Approach to TG hall should be suitable for movement of heavy

    equipment to transport the components.

    2. The EOT Crane should be available covering the complete

    condenser area.

    3. Sufficient area should be available for pre-assembling preferably on

    the turbine floor.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    16

  • 7/28/2019 condenser erection.doc

    17/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    4. Power source of 200 Amps should be available.

    (II)TOOLS & PLANTS

    -All normal small tools should be available.

    -Apart from this the following shall be required during erection: -

    1. Welding Generators 4 nos.

    2. Chain pulley blocks 5T 4 nos.

    3. Slings (40mm) 4 nos.

    4. Angle grinders 1 set

    5. Tube expander with tools 2 nos.

    6. Tube cutting bits 2 sets

    7. Trailer with pulling unit Sufficient Qty.

    8. Trailer with pulling unit for tubes 1 no.

    9. Rolled steel section for pre assy. 1 no.

    10.Wooden planks for condenser covering. 1 MT App.

    11.GI / Black sheet for condenser covering Sufficient Qty.

    12.UV Lamp 1 set

    (III) PREASSEMBLIES

    a) BOTTOM PLATES

    Depending on site conditions, the preassembly of the plate will be

    done.If the foundation and approach is ready then it would be directly

    assembled on the foundation. However, if the foundations are not

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    17

  • 7/28/2019 condenser erection.doc

    18/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    ready it would be assembled separately outside. The bottom plate is in

    four parts and two of them will be pre-assembled outside. On each

    half the hot well and the spring supports will be welded/tacked. As the

    opening on the foundation is big enough the preassembled bottom

    plate can be lowered flat without any risk.

    b) SIDE WALLES

    Both sidewalls are carrying in four parts. Two joints would be welded

    outside the foundation.

    c) WATER CHAMBER / BOXES

    The assemblies of these would be checked and lowered in an assembledcondition.d) STIFFNERS

    These would be assembled and welded in twos.

    e) DOME WALLS

    Each dome wall, both upper and lower is in two parts. These would be

    assembled together before erection.

    f) DOME SHIFTING STRUCTURE

    The central portion of the structure shall be assembled outside.

    g) CLEANING OF COMPONENTSThe cleaning of components shall be done either by sand blasting using

    low-pressure air (2.5 kg) or by alkali and hot water.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    18

  • 7/28/2019 condenser erection.doc

    19/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    (VI) ERECTION

    This would be carried out as per the normal erection procedure given in

    next chapter taking due care of all the normal / quality checks.

    (V) TUBING

    The tubing of the condenser shall be carried out from the end of the

    condenser. The opening in A row in front of the condenser is not to

    be closed till tubing is complete. Tubes shall be transported on a long bedtrailer so that the overhang is not more than 1.5mm either side. In case a

    small crane and space is available the tube boxes shall be unloaded near

    A row columns. However, in normal cases the boxes shall be unloaded

    inside the TG hall by EOT crane and shifted to position manually.

    (VII) WATER BOX HANDLING DEVICE

    This would be erected when the welding of internals is in the progress. In

    case this is not available it would be better to have suitable openings on

    TG Floor and oil canal from where the slings can be inserted to handle

    the water boxes when they are opened for tube inspection.

    (VIII) HYDRAULIC TEST

    - Steam space

    This would be tested by filling the water in the steam spaces to the

    required level and the fluorescent powder shall be mixed with it. It would

    be inspected by UV Light.

    -Water space

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    19

  • 7/28/2019 condenser erection.doc

    20/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    This would be tested along with the RE joints and the butterfly valves.

    This would ensure tightness of the RE joints flanges along with the

    condenser. Moreover the time for fixing blanks can be saved.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    20

  • 7/28/2019 condenser erection.doc

    21/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    21

    ERECTION PROCEDURE

  • 7/28/2019 condenser erection.doc

    22/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    A. BOTTOM PLATE

    I. PREPARATORY WORK

    1. Check the foundation for dimensional accuracy in accordance with

    the plate foundation drawings.

    2. Set the support plates in mortar and align with the positions in

    which the spring elements will be mounted.

    II. ASSEMBLY SEQUENCE

    1. Tack the base plates to the spring elements.

    2. Lower hot well below and place it on the ground.

    3. Lower the sections making up the bottom plate onto the support

    plates of the condenser foundation.

    4. Assemble and align the sections which have been lowered onto

    the foundation.

    5. Weld bottom plate as per sequence.

    6. Lift hot well and weld with bottom plate. Align the bottom plate

    to the turbine axis in zero elevation.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    22

  • 7/28/2019 condenser erection.doc

    23/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    7. Raise bottom plate in axial direction and into zero elevation,

    taking care that when condenser is finally tilted, its centerline

    would match with turbine axis.

    8. When the bottom plate is at zero elevation, shim plates under all

    spring elements.

    9. In order to avoid displacement of the bottom plate during

    assembly of the water boxes and condenser shell internals, the

    support bolts of all the spring elements must be in their

    uppermost positions before the work is commenced.

    10. Detach the tack welded base plates from the spring elements

    and eliminate the weld spots.

    PREASSEMBLY

    1. Preassemble tube plates (L & R) and check for any distoration

    of main tube plate.

    2. Any deviation in alignment of holes should be similar in both

    front and rear assemblies. In case of variation the matter

    should be referred to the BHEL /HWR.

    3. Assemble the water box covers with the water chambers

    without gasket and check whether:

    a) All bolts are fitting and

    b) Any clearance in the parting plane, rectify if necessary.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    23

  • 7/28/2019 condenser erection.doc

    24/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    4. In case suitable slings for lifting the complete assembly are

    available then welding of the two halves should be done. In

    case of any doubt, the assemblies can be lowered in parts.

    B. CONDENSER SHELL

    General preparatory work

    1. Place the sidewall sections side by side, align and weld together

    to from one complete sidewall. After welding together check

    the sidewall for warpage and rectify, if necessary.

    2. Welding of two or more pieces together outside the foundation

    may be carried out.

    3. Prepare the water boxes for installation by passing shackles and

    wire cable through the lifting lugs.

    Assembly Sequence

    1.Hook up the prepared water box units to the crane and lower

    through the foundation cavity, using hydraulic jacks as required

    to secure the units against tilting.

    2. As soon as the lowered water box unit is standing upright on the

    bottom plate, match the center to the transverse axis.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    24

  • 7/28/2019 condenser erection.doc

    25/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    3. Align the water box unit in the horizontal plane using water

    level. Select two symmetric holes in the lowest outermost row of holes

    on the right and left side. Insert guide pins in the selected holes, to be

    used as oriented points for alignment.

    4. Drop a plumb bob to the bottom plate at each other edge

    and move the water box unit into the vertical position. When the water

    box unit has been aligned in the horizontal and vertical planes, tack weld

    to the bottom plate.

    5. Before the crane hook carrying the water box is lowered and

    the load removed, the water box unit must be secured by means of

    cables and stiffeners.

    6. Repeat the assembly procedure described above for the secondwater box unit of the condenser.

    7. After tack welding, tack flat guides to the water box units and

    bottom plate.

    8. Do not weld the water box units to the bottom plate until the

    sidewalls have been assembled, as otherwise weld warpage

    may occur.

    9. Hook up the sidewalls by means of shackles and cables passed

    through the lifting lugs, move over the foundation cavity and

    lowered onto the prepared location.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    25

  • 7/28/2019 condenser erection.doc

    26/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    10. Align the side walls in lowered position and tack weld them at

    several points to the water box units and to the bottom plate.

    11. Remove the bracing cables, hosting gear, bracing lugs, etc.

    from the sidewalls & dome walls & from the bottom plate.

    12. Weld the complete shell.

    CONDENSER SHELL INTERNALS

    1. Preparation of the shell

    Remove any accessories inside the shell & sweep the whole interior

    clean. When preparatory work has been concluded, commence

    installation of landing bars.

    2. Installation of the landing bars

    Mark the installation locations for the landing bars on the bottom plate

    according to the drawings.

    Locations are measured from the tubes, which will be and are marked on

    the outer edges and the centerline of the bottom plate sides. Then move

    the landing bars in to position, align and tack weld. Weld using the back

    step method from both sides simultaneously.

    Erect the vertical landing bars parallel to the landing bars on the bottom

    plats. For this purpose, drop perpendiculars to the landing bars already

    mounted on the bottom plate, mark the installation locations for the

    vertical bars on sidewalls and tack weld the landing bars in position. Do

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    26

  • 7/28/2019 condenser erection.doc

    27/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    not permanently weld the vertical landings bars until the condenser has

    been completely welded together namely after preassembly of the steam

    dome. Remove weld residue from the weld zones using a chisel and wire

    brush.

    Preparing for installation of the tube support sections

    1. Mount the flat iron supports for the air cooler shields and weld

    onto the tube supportplate sections with the aid of a template at the

    time of attaching the landing bars onto the bottom plate. It is important

    to place wooden beams under the tubesupport plate sections to prevent

    deformation.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    27

  • 7/28/2019 condenser erection.doc

    28/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    2. Installation of the tube support plate sections may then be taken

    up. Use the lifting device to transport the tube support plate sections.

    Installation of the tube support plate sections and internals.

    1. Hook up each tube support plate sections upto crane. Lower into the

    condenser shell and insert into the landing bars on the bottom plate and

    sidewall, beginning at the front and the rear water boxes. During this

    procedure, it is important that connection holes for the circulating water

    pipe, countersunk by the manufacturer, face the tubing side.

    2. Fix each tube support plate sections at least 4 / 6 points using

    adjustable spacers.

    3. Move sufficient tube support plate sections into the condenser shell and

    fix them in position relative to each other by means of spacers to enable

    the internals to be set down in the spaces provided in the tube support

    plate sections. They consist of the following; steam baffle plates, part of

    the air extraction line, as well as various bracing assemblies such as flat

    irons and tubes necessary for later assembly of all the internals.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    28

  • 7/28/2019 condenser erection.doc

    29/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    4. Insert stiffening rods inside the tube support plates.

    5. Suitable tie rods should be used to hold the support plates against any

    tilting.

    6.Secure all tube support plate sections against tilting, since it is notpossible to commence alignment of the tube support plate sections

    and assembly of the internals until after the steam dome including the

    dome bracing has been preassembled and the condenser shell has

    been welded together.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    29

  • 7/28/2019 condenser erection.doc

    30/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    Alignment and welding of the condenser shell internals

    1.Insert thin steel wires at four identical points in each tube plate of a

    water box and feed the wires through the holes at the corresponding

    points in the tube support plate sections. Hold the ends of the wires in

    the centers of the tube plate holes using a special device and attach

    the weights to keep the wire taut. Then align each tube support plate

    sections in such a way that the tensioned steel wire passes through

    the center points of the holes for the circulating water tube

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    30

  • 7/28/2019 condenser erection.doc

    31/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    2. Tack weld the tube support plate sections aligned with the center

    point to the slot profiles on the bottom plate and sidewalls. After

    tack welding, verify that the holes in the support plates lie in the

    vertical and the horizontal planes. Enter the actual measurements on

    the measurement data record provided.

    The thin steel wire and alignment devices can now be removed, as

    they are no longer for further assembly of the condenser shell

    internals.

    Move the internals temporarily housed in the spaces in the tube

    support plate sections into their correct positions, align and tack

    weld. Assembly the center joining plate and the bracing assemblies

    such as flat irons and tubes.

    3. Note: The stem baffles and bracing units must not be tacked

    to the tube of the water boxes. This operation is not

    performed until all the internals have been welded to one

    another.

    4. Align the various sections of the air extraction line, weld them

    together to form one unit and tack weld to the tube support plates.

    5. During alignment, ensure that air extraction openings are directed

    towards the bottom plate and that therefore the connection holes for

    the connecting piping systems are necessarily in the correct

    positions. Pass out and fit the pipe work to the connecting piping

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    31

  • 7/28/2019 condenser erection.doc

    32/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    system through the connection holes. Set down the shields on the flat

    iron supports, align and tack weld.

    6. After assembly of all the steam space internals which, to allow for

    welding warpage, may only be tack welded, commence welding of all

    the condenser shell internals, the welding sequence being of up most

    importance.

    7 First weld the steam baffle plates, central joining plate, feed water

    heating plate form, condensate drain sheets for the cooler tube nests,

    bracing assemblies such as flat irons and tubes. Then weld the tube

    support plates to the landing bar strips on the bottom plate.

    8. Then weld the vertical landing bar strips to the sidewalls and tube

    support plates. During this procedure, welders should as far as

    possible work simultaneously. When the condenser shell internalshave been completely welded together, tack and weld steam baffle

    plates, the bracing assemblies and the air extraction line and the

    connecting piping system at the front and rear tube plates. When all

    the welding work has been concluded, remove all weld residue from

    the weld seams and weld zones in the entire condenser shell.

    9. Note:

    a) To prevent welding warpage, all welds must be performed

    simultaneously from both sides using the back step method.

    Vertical joints must be welded from top to bottom, i.e. from

    the upper edge of the tube support plate to the bottom plate.

    b) Welding with main tube plate should be done after all

    internal welding has been completed.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    32

  • 7/28/2019 condenser erection.doc

    33/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    Assembly of LPH in condenser

    General:

    Prior to the erection of LP heater and platform, the pipes for the

    extraction system and throw device have to be erected/ placed in the

    steam space.

    Erection of the LP heater platform

    Erection of the feed water heater platform start with mounting on the U-

    profile steel support in the area of the central butt- strapping of thetube-supporting sheet.

    This involves firstly mating and bracing the support for LP heater

    platform with the cut-to-size sheets and the ends of the associated U-

    profiles. The I-profile girders for the feed water heater platform are

    mounted on top these. The support brackets for the LP heater platform

    support are then mounted on the dome walls on the water box side.

    The elevations for the feed water heater platform support must

    be assured.

    Then the feed water heater platform and the dome bracing are installed,

    aligned and welded as a unit.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    33

  • 7/28/2019 condenser erection.doc

    34/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    Installation of the Feed water Heater through the Turbine

    Foundation/Condenser Steam Dome Cavity

    The LP heater held in the lifting tackle is inserted the turbine

    foundation/condenser steam dome cavity and tilled to the required

    angle. Insert the feed water heater through the turbine foundation into

    the condenser by lowering crane hook and by gradually straightening out

    the lifting bracket towards the horizontal plane.

    Then move the feed water heater into the prescribed horizontal position

    parallel to the feed water heater platform.

    As soon as the horizontal assembly position is achieved, adjust the feed

    water heater to the prescribed vertical elevation.

    Mount support jacks on the I-profile girders supporting the feed water

    heater platform and at the feet of the feed water heater to support the

    feed water heater when it is set down from the lifting bracket.

    Adjust all the support to the prescribed pressure and tack the load off

    the lifting bracket.

    Then take the actual dimension for the LP heater support, fabricate the

    parts required and insert under the heater. Tack the load off the support

    jacks as the permanent supports are inserted.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    34

  • 7/28/2019 condenser erection.doc

    35/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    After completion of alignment of the feed water heater along the

    longitudinal and transverse axis, the upper halves of the dome walls can

    be installed, aligned and welded to the feed water heater as per the

    drawing.

    Note: The two upper halves of the dome wall on the water box

    side are not to be installed and assembled until the installation of

    the feed water heater through the turbine foundation/ condenser

    cavity has been completed.

    STEAM DOME AND BRACING

    General

    The assembly of steam dome is commenced when the condenser shell

    has been adequately tack welded. Prepare the support points at the

    upper edges of the condenser shell for assembly of the steam dome. Tilt

    the condenser shell as per drawings. Ensure that centerlines are not

    disturbed.

    Preassembly of the steam dome walls

    1. Preassemble the dome walls, divided into section for shipment,

    according to the plant drawings. During this procedure the sections

    making up a dome wall are assembled on the turbine floor with their

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    35

  • 7/28/2019 condenser erection.doc

    36/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    ribs facing upwards, aligned, adequately tack welded and then

    welded to form one integral unit.

    2. After completion of welding, clean the welding zone and examine the

    dome wall unit for warpage. If necessary, realign the dome wall unit

    to match the mounting dimension to the other component.

    3. Prior to installing the dome wall unit, coat inaccessible weld locations

    with anti-corrosive paint.

    4. After this has been affected, measures out the dome wall units and

    Mark the center points by punching.

    Installation and Assembly of the dome walls

    1. There is no specific sequence for the assembly of the dome walls.

    Depending on on-site condition assembly may commence either with

    the dome walls on the turbine and generator sides or those on the

    water box sides. The dome wall units are hooked up using suitable

    cable passed through their transport lungs, moved over the

    foundation cavity and lowered into position on the upper edges of the

    condenser shell.

    2. The sloping edged metal fixtures mentioned above facilitate insertion

    when assembling the dome wall on the turbine or generator side.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    36

  • 7/28/2019 condenser erection.doc

    37/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    3. The dome wall remains suspended from the crane unit it has been

    secured against tilting and slipping by suitable clamping.

    4. Then the opposite dome wall is installed. When the two opposite dome

    walls have been installed and secured, they are to be aligned with the

    longitudinal or transverse axis. For this purpose, drop perpendiculars

    from the steel wires on the longitudinal and transverse axes onto the

    upper edge of the dome walls.

    5. When the two opposite dome walls have been aligned, secure them by

    tack welding to the steam shell.

    5. Insert and install the adjacent dome walls as per drawing, as dome

    walls are identical and must be moved into the correct position.

    Assembly of Dome Bracing

    1. Commence assembly of the dome bracing parallel to welding work

    and after completion of the shell internals.

    2. Lower the dome bracing, supplied in required lengths, into the steam

    dome by crane, align in position and track weld.

    3. When all the sections of bracing have been preassembled and track

    welded, welding of the dome bracing to form one integral unit to be

    carried out. However the connection with the LP cylinder should be

    done only neck welding.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    37

  • 7/28/2019 condenser erection.doc

    38/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    Assembly of Steam throw nozzles

    After the dome walls have been tacked in position, the steam throw off

    nozzles are lowered and rough aligned.

    The final alignment is dome along with the LP Bypass down stream

    piping.

    WELD CONNECTION BETWEEN CONDENSER AND LOW PRESSURE

    TURBINE

    Welding the condenser to the low pressure turbine

    1. After the condenser has been brought to operating weight by filling

    water in the hot well or by the springs as indicated in condensererection drag and the spring supports have been adjusted to

    compensate for welding contraction, prepare for welding the

    condenser to the low pressure turbine.

    2. Then fit the intermediate, corner and web plates as per gaps available

    and prepare the weld edges.

    3. Tack these parts to the condenser dome with welds with a tack length

    of three times the plate thickness at intervals of 25 times the plate

    thickness.

    4. When all the aforementioned parts have been welded to the

    condenser dome, tack weld to the low-pressure turbine.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    38

  • 7/28/2019 condenser erection.doc

    39/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    5. Weld the joint using the back step method form tack to tack (see

    diagram). When the base layer has been completed, make the

    following filler weld layers, each in a single pass, and reversing

    direction for each layer (see diagram).

    6. After welding, clean the weld zone using suitable tools. When the

    condenser has been completely welded to the low-pressure turbine.

    Relieve the spring supports of the load applied to facilitate welding

    and measure in relieved condition.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    39

  • 7/28/2019 condenser erection.doc

    40/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    7. The spring supports must return to within +/- 1 mm of their settings.

    If the deviations exceed this tolerance range, spacers must be used

    to return the pretension of the spring supports to their original

    settings.

    8. Then immobilize the spring supports again.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    40

  • 7/28/2019 condenser erection.doc

    41/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    INSTALLATION OF THE CONDENSER TUBING

    General

    The circulating water tubes, cut to length and provided with guide heads

    delivered in crates to the site.

    Erection of an assembly platform

    Before erecting the assembly platform, remove the water box covers and

    set down on wooden beams in a suitable location.

    The assembly platform must be erected in such a way that it is safe to walk

    on and presents no danger of falling off. In addition, it must be stable

    enough to withstand the weight of the crates containing the circulating

    water tubes.

    Preparation of the holes for the circulating water tubes

    The holes in the tube plates must be clean to the base metal. Clean all

    holes using round steel brushes or reamers. Use of chemicals/ solvents is

    not desirable. If the hinge assembly has been installed then one condenser

    box can be opened at a time.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    41

  • 7/28/2019 condenser erection.doc

    42/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    Installation of tubing

    The tubings are inserted manually, Insert the tube from the bottom end

    and pull through towards the top end until the same length of tubing

    protrudes from the front and rear tube plates. Remove the guide heads

    from the circulating water tubes. In case the insertion is difficult then the

    tube should be taken out and the support plates rectified by reaming.

    Tube expander

    Use electronically controlled tube end expanders to roll the cw tubes into

    tube plates. When the desired pressure is reached, the expander switches

    to reverse speed.

    The following points must be observed when expanding tube ends:

    The tube plate holes and the tube ends must be clean to the

    bare metal and free from axial draglines.

    Before expanding in the tube ends, moisten the roller with at

    least two drops of glycerin or vegetable oil. Moistening is

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    42

  • 7/28/2019 condenser erection.doc

    43/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    necessary to ensure that expander rollers rotate smoothly and

    with minimum wear.

    The complete tube end expander unit consisting of the monitor

    and the tube expander be kept together as one unit. If one part

    is replaced the setting must be re-adjusted to give the correct

    expansion as required for tight connection.

    The locking device on the roller head must be set to block the

    rollers to a depth of 80% of main tube plate thickness before

    reaching the steam compartment side of the tube plate. If the

    tubes are expanded beyond the steam compartment side of the

    tube plate, they will be damaged.

    Finishing work on the tube plates and cw tubes

    1. Remove any burrs at the tube inlet edges.

    2. After expanding into the opposite tube plate, mill off the protruding

    tube ends to the stipulated dimension and deburr the inner edges.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    43

  • 7/28/2019 condenser erection.doc

    44/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    Preparing the water box covers and tube plates

    Clean the joints of the water box covers and tube plates.

    Note: When cementing the gasket, the joints must be free of

    grease, clean and dry.

    Assemble the rubber cord and spacer gaskets.

    Assembly of the water box covers

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    44

  • 7/28/2019 condenser erection.doc

    45/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    The water box covers are attached to the lifting equipment using

    appropriate cables, swiveled into the assembly position and moved in front

    of the respective water box.

    The hexagonal bolts and nuts necessary for the assembly of the water

    boxes must be coated with a lubricant / graphite and subsequently

    tightened.

    The initial phase of this procedure is to tighten four bolts marked x in

    figure. Afterwards all the bolts in the fig. are consecutively tightened

    starting from the middle with x1, x2, x3, x4,x5, x6.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    45

  • 7/28/2019 condenser erection.doc

    46/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    Caution: It is imperative that the bolts be tightened in two stages

    HYDRAULIC TEST OF WATER BOXES

    The condensers are subjected to a hydraulic pressure test on the cw side.

    For this purpose, the cw inlet and outlet pipes must be blanked using

    suitable hydro-test flanges and the manholes using the original covers. The

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    46

  • 7/28/2019 condenser erection.doc

    47/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    water box covers must be mounted ready for operation and a protective

    coating must have been applied to the water boxes.

    The hydro-test can also be done by closing the butterfly valves in the inlet

    and outlet of condensers. This apart from also ensuring the tightness of

    B.F. valves and expansion joints, reduce the time cycle as the temporary

    test flanges need not be erected.

    After the hydro test, drain the cw.

    Hydro fill test on steam side

    After the tubing has been completed, including the trimming of the tubes

    the hydro fill test is to be conducted on the steam space.

    1. Lock the spring supports in position.

    2. Gradually fill the steam space with water. A water tube arrangement

    is to be installed so that the level of water can be monitored.

    3. During filling, constantly check the tubes for any leakage. In case

    any leakage is observed, that particular tube should be further

    expanded.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    47

  • 7/28/2019 condenser erection.doc

    48/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    4. In case any tube is not getting sealed, it may be plugged.

    Caution: This should be done as a last resort.

    5. Fill the water upto last stage blade tip of LP Turbine and leave for 24

    hours. Check thoroughly for any leakage.

    6. Add a fluorescent dye (Sodium floursceine) 2-3 ppm (approx. 2 Kg)

    to the filled water in the condenser. Stir the complete water and dye

    with compressed air.

    7. Leave the water for another 24/36 hours.

    8. Finally inspect the tubes by ultra violet light with the help of U-V

    lamp.9. When no fluorescence is observed it can be inferred that there is no

    leakage.

    10.During this test, other connected areas (falling under vacuum during

    operation) can be inspected for any leakages.

    11.Release the condenser springs, after all water has been drained from

    both the steam space / cw side. The springs are finally set as per

    drawings.

    NOTE: Water should never be filled on both steam and CW side at

    the same time.

    SPECIAL PRECAUTIONS TO BE TAKEN DURING ERECTION:

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    48

  • 7/28/2019 condenser erection.doc

    49/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    1. The joining plates between the water chambers should be welded

    and checked before lowering of condenser intervals.

    2. The corners of the neck joint with LP turbine should be checked to

    ensure completeness.

    3. The welding of the stiffeners with the main tube plate should be

    done only after welding of all support plates with the shell and

    stiffness has been completed.

    4. Welding sequence should be reversed for every layers of welding.

    5. During preassembly of bottom plates / sidewalls & dome walls it is

    advisable to put a packer below the joint so that during welding theplates straighten out.

    6. Not more than four welders should be deployed during the welding

    of the internals. Adequate supervision should be exercised to ensure

    proper welding sequence.

    7. It is desirable that after 50% of the welding of internals has been

    completed the alignment of the tube plates is rechecked. Subsequent

    welding sequence should be decided based on the observation made.

    8. During tubing in case the tube is not going freely the holes of the

    tubes support plates may be reamed suitably.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    49

  • 7/28/2019 condenser erection.doc

    50/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    POWER SECTOR-WESTERN REGION TECHNICAL SERVICES NAGPUR-440 001

    50

    LIST OF DRAWINGS

  • 7/28/2019 condenser erection.doc

    51/51

    Station:NTPC- Rihand

    BHELRef No:PW/TSX/RIT/TUR-PR/001/REV00

    Plant area:CONDENSER

    Document- TypeERECTION MANUAL

    Revalidated document prepared based on doc, BHEL/PSNR/TSX/VSTPP/TA-08 for internal use.

    S Description Drawing No.

    1. CONDENSER ASSLY (GA) 0 160 10 70043 C 802. CONDENSER GENERAL ASSLY.

    (3 SHEETS)

    0 160 10 70043 ER

    3. INSTALLATION OF LEVEL

    INSTRUMENTS ON CONDENSER

    2 160 00 70001 C 80

    4. HANDLING ARRANGEMENT FOR

    FRONT WATER BOX

    0 160 00 70023 C 80

    5. HANDLING ARRANGEMENT FOR

    REAR WATER BOX

    1 160 00 70060 C 80

    6. BOTTOM PLATE 0 160 11 70010 ER

    7. LOWER DOME WALL (TUR END) 0 160 12 70025 ER

    8. LOWER DOME WALL (GEN. END) 0 160 13 70030 ER

    9. SIDE WALL (TUR. END) 1 160 14 70005 ER

    10. LOWER DOME WALL (FWB SIDE) 0 160 15 70032 ER

    11. LOWER DOME WALL (RWB SIDE) 0 160 16 70036 ER

    12. SIDE WALL (GEN. END) 1 160 17 70005 ER

    13. DOME INTERNAL STIFFENING 0 160 27 70027 ER

    14. SHELL INTERNAL DETAILS 0 160 28 70031 ER

    15. AIR EXTRACTION PIPING 1 160 71 70027 ER16. LP HEATER SUPPORT ARRGT. 0 160 38- 70001 ER

    17. HOT WELL 0 160 28 70028 ER

    18. CONDENSER SUPPORTS 1 160 71 70027 ER