compact ventilation unit lg 3200 - pichlerluft · compact ventilation unit lg 3200 page 3 layout...

16
COMPACT VENTILATION UNIT LG 3200 Systematic ventilation. COMFORT VENTILATION EU Regulation 1253/2014 EN13141-7:2010 for residential buildings for non-residential buildings ErP 2018

Upload: others

Post on 26-Mar-2020

14 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: COMPACT VENTILATION UNIT LG 3200 - Pichlerluft · COMPACT VENTILATION UNIT LG 3200 PAGE 3 Layout sketch LG 3200 S (free-standing installation) Air line connection: outdoor air / extract

COMPACT VENTILATION UNIT LG 3200

Systematic ventilation.

COMFORT VENTILATION

EU Regulation 1253/2014

EN13141-7:2010

for residential buildingsfor non-residential buildings

ErP2018

Page 2: COMPACT VENTILATION UNIT LG 3200 - Pichlerluft · COMPACT VENTILATION UNIT LG 3200 PAGE 3 Layout sketch LG 3200 S (free-standing installation) Air line connection: outdoor air / extract

COMPACT VENTILATION UNIT LG 3200 PAGE 2

Product description

Area of application

The LG 3200 comfort ventilation unit with passive house certificate consists of a compact, thermal bridge-free and 50 mm heat insulated housing made of galvanised steel sheeting, external powder coating in RAL 9010, a highly efficient heat recovery system with air/air counter-flow heat exchanger, an

automatic 100% bypass with energy-saving radial fans in the latest EC motor technology with optional CO

2 sensor

module for demand-based comfort ventilation operation, filter ODA ISO ePM1 55% in the outdoor air and filter ETA ISO Coarse 90% in the extract air, internally wired control electronics.

Optional enhancements such as constant volume flow regulation, constant pressure regulation or our enhanced, efficiency-optimised fan optimiser regulation complement the extensive basic functions. Compact ventilation unit suitable for free-standing installation in frost-free rooms.

The LG 3200 and LG 3200 S comfort ventilation unit is used as a central unit for up to 40 apartments, schools, doctor's surgeries, offices and similar

applications and for the controlled mechanical aeration and ventilation of larger apartment buildings. The range of use extends fundamentally to residential

buildings in passive or low-energy construction, with an adjustable air volume flow up to approx. 3400 m³/h.

1 Supply air 300 x 800 mm 2 Extract air 300 x 800 mm 3 Outdoor air 300 x 800 mm 4 Exhaust air 300 x 800 mm 5 Counterflow heat exchanger 6 Exhaust air fan 7 Supply air fan 8 Control system 9 Bypass damper with actuator 10 Extract air filter 11 outdoor air filter 12 Condensate tray 13 Cable inlets 1 x M32, 2 x M20, 10 x M16 14 Electric preheater battery (optional),

with an optional heat insulation 15 Electric reheater battery (optional) 16 Outdoor air shut-off valve (optional) 17 Exhaust air shut-off valve (optional) 18 Pre-filter box for electric heating

radiators (optional, recommended by the manufacturer)

19 Height adjustable feet 20 Condensate drain 21 Flexible connections top

Optional: Hot water preheater battery and hot water reheater battery for duct installation

Figure: LG 3200 R (right-hand version)The PI-HMI operating unit is delivered separately.

Layout sketch LG 3200 (free-standing installation)Air line connection: outdoor air / exhaust air / supply air / extract air (W x H) 300 x 800 mmAir line connection: with connecting profile P30

1652

20401980

800

805

170

1370

125

480685

300

5911

1614

8

10

7

1920

12

6

4 3 13 1

983,

4

300

51,2121

30051,2

17

2

21 2121

121

300

490

2120

15

21

18

245

580

450

1652

20401980

800

805

170

1370

125

480685

300

5911

1614

8

10

7

1920

12

6

4 3 13 1

983,

4

300

51,2121

30051,2

17

2

21 2121

121

300

490

2120

15

21

18

245

580

450

Page 3: COMPACT VENTILATION UNIT LG 3200 - Pichlerluft · COMPACT VENTILATION UNIT LG 3200 PAGE 3 Layout sketch LG 3200 S (free-standing installation) Air line connection: outdoor air / extract

COMPACT VENTILATION UNIT LG 3200 PAGE 3

Layout sketch LG 3200 S (free-standing installation)Air line connection: outdoor air / extract air (W x H) 300 x 800 mmAir line connection: exhaust air / supply air (W x H) 486 x 786 mmAir line connection: with connecting profile P30

1 Supply air 486 x 786 mm 2 Extract air 300 x 800 mm 3 Outdoor air 300 x 800 mm 4 Exhaust air 486 x 786 mm 5 Counterflow heat exchanger 6 Exhaust air fan 7 Supply air fan 8 Control system 9 Bypass damper with actuator 10 Extract air filter 11 Outdoor air filter 12 Condensate pan 13 Cable inlets 1 x M32, 2 x M20, 10 x M16 14 Electric preheater battery (optional),

with an optional heat insulation 15 Electric reheater battery (optional) 16 Outdoor air shut-off valve (optional) 17 Exhaust air shut-off valve (optional) 18 Pre-filter box for electric heating

radiators (optional, recommended by the manufacturer)

19 Height adjustable feet 20 Condensate drain 21 Flexible connections top 22 Flexible connections side

Optional: Hot water preheater battery and hot water reheater battery for duct installation

Figure: LG 3200 SR (right-hand version)The PI-HMI operating unit is delivered separately.

1652

20401980

580

486

786

2120

805

170

1370

480685

475 300 490 300 475

2550

59

17

11

1416 8 10

15

7

1920

12

6

4

3 13 2 1

983,

4

21

21

22

22

18

12524

5

450

1652

20401980

580

486

786

2120

805

170

1370

480685

475 300 490 300 475

2550

59

17

11

1416 8 10

15

7

1920

12

6

4

3 13 2 1

983,

4

21

21

22

22

18

12524

5

450

Page 4: COMPACT VENTILATION UNIT LG 3200 - Pichlerluft · COMPACT VENTILATION UNIT LG 3200 PAGE 3 Layout sketch LG 3200 S (free-standing installation) Air line connection: outdoor air / extract

COMPACT VENTILATION UNIT LG 3200 PAGE 4

The compact ventilation unit LG 3200 is available in several different versions:• Right or left-hand depending on the

position of the supply air connection• With side exhaust air and supply air

connecting pieces, type LG 3200 S

• With or without electrical preheater battery built up to the compact ventilation unit for frost protection of the heat exchanger

• With or without electrical reheater battery built up to the compact ventilation unit

The unit may also be optionally equipped with the following additional functions:• See optional accessories

Versions

LG 3200 version Left-hand version Right-hand version

Item no. without preheater and reheater battery 08LG3200-L 08LG3200-R

Item no. with a built up electrical preheater battery

08LG3200-L-V 08LG3200-R-V

Item no. with a built up electrical reheater battery

08LG3200-L-N 08LG3200-R-N

Item no. with a built up electrical pre and reheater battery

08LG3200-L-V-N 08LG3200-R-V-N

Item no. optional with hot water reheater battery for external assembly in a horizontal duct (type dep. on heating output requirement)

40LG080200 or 40LG080260

40LG080200 or 40LG080260

Item no. shut-off valve with motor LM 24 A

08AKE800300 08AKE800300

LG3200L

LG3200R

LG 3200 S version Left-hand version Right-hand version

Item no. without preheater and reheater battery 08LG3200-SL 08LG3200-SR

Item no. with a built up electrical preheater battery

08LG3200-SL-V 08LG3200-SR-V

Item no. with a built up electrical reheater battery

08LG3200-SL-N 08LG3200-SR-N

Item no. with a built up electrical pre and reheater battery

08LG3200-SL-V-N 08LG3200-SR-V-N

Item no. optional with hot water reheater battery for external assembly in a horizontal duct (type dep. on heating output requirement)

40LG080200 or 40LG080260

40LG080200 or 40LG080260

Item no. shut-off valve with motor LM 24 A

08AKE800300 + 08AKE786486 08AKE800300 + 08AKE786486 LG3200SL LG3200SR

12

3

4

14

3 2

14

3

2

32 1

4

1 Outdoor air

2 Supply air

3 Extract air

4 Exhaust air

1 Outdoor air

2 Supply air

3 Extract air

4 Exhaust air

Page 5: COMPACT VENTILATION UNIT LG 3200 - Pichlerluft · COMPACT VENTILATION UNIT LG 3200 PAGE 3 Layout sketch LG 3200 S (free-standing installation) Air line connection: outdoor air / extract

COMPACT VENTILATION UNIT LG 3200 PAGE 5

Technical specificationsThe technical specifications were measured by Lucerne Polytechnic – Engineering & Architecture, Centre for Integral Building Technology.

COMFORT VENTILATION UNIT

Dimensions: (W x H x D) 2040 x 1655 x 1000 mmHousing in double-shell construction made of galvanized sheet steel, 50 mm heat insulationAir line connections LG 1400: outdoor air / exhaust air / supply air / extract air (W x H) 300 x 800 mm Air line connections LG 1400 S: outdoor air / exctract air (W x H) 300 x 800 mm and exhaust air / supply air (W x H) 486 x 786 mm Connection profile: P30Condensate connection with syphon and mechanical sealing device ø 40 mm at the bottom Electrical connection without preheater battery: 400 V/50 Hz/20 AElectrical connection with preheater battery: 400 V/50 Hz/40 ADegree of protection: IP 20Permitted ambient temperature for the unit: + 5° C to + 40° CWeight without accessories: approx. 390 kg

FANS (factory setting)

Air volume flow:Fan speed/low speed: 1600 m³/h Fan speed/high speed: 3000 m³/h

Air volume flow setting range: 900 – 3400 m³/hStop operating condition: 6.5 W

The characteristic curves shown are valid for the device design with an outdoor air filter of quality class F7 (EN 779), extract air filter of quality class G4 (EN 779).

CHARACTERISTIC EXTERNAL PRESSURE INCREASE - AIR VOLUME FLOW (for volume flow constant function)

The characteristic curves provide the external pressure (p

ext.) available for the

duct system.

TOTAL OUTPUT

The SFP values shown [Wh/m³] take into account power consumption for both fans for supply air and exhaust air as well as the power consumption of the control system.

DEGREE OF RECOVERY IN ACCORDANCE WITH EN 308

(where extract air is 21 °C / 40% r.H.)

PRESSURE-VOLUME FLOW CHARACTERISTIC CURVE FOR LG 3200 WITH V CONSTANT FUNCTION

PRESSURE-VOLUME FLOW CHARACTERISTIC CURVE FOR LG 3200 WITHOUT V CONSTANT FUNCTION

PASSIVE HOUSE CERTIFIED IN ACCORDANCE WITH PHI CRITERIA

Non-residential building:Area of application: 950 to 1800 m³/h at an external pressure of 259 PaHousing seal-tightness: external leakage 0,3 %, internal leakage 0,9 %Heat recovery rate: ŋ

HR, eff = 84 %

Comfort criterion: Tsupply air= +16,5 °C bei Toutdoor air= -10 °CFlow efficiency: ŋ

el = 0,41 Wh/m³

Residential building:Area of application: 950 to 2200 m³/h at an external pressure of 236 PaHousing seal-tightness: external leakage 0,3 %, internal leakage 0,9 %Heat recovery rate: ŋ

HR, eff = 82 %

Comfort criterion: Tsupply air= +16,5 °C bei Toutdoor air= -10 °CFlow efficiency: ŋ

el = 0,41 Wh/m³

CERTIFIED ACCORDING TO EN13141-7:2010

Thermodynamic tests at air volume flow rates 908/2120/3075 m³/h (at outdoor-temp. +7 °C (+1 x Ref. +2 °C), at extract air temp.+20 °C): Extract air side = 76 %/75 %/70 % and supply air side = 88 %/87 %/88 %Flow efficiency: ŋel = 0,19/0,28/0,45 Wh/m³

900

800

700

600

500

400

300

200

100

500 1000 1500 2000 2500 3000 3500 4000

ext

. pre

ssur

e in

crea

se [

Pa]

Air volume flow [m3/h]

Speed 3000 m3/hSpeed 2400 m3/hSpeed 1600 m3/hSpeed 1000 m3/h

0.70 Wh/m3

0.60 Wh/m3

0.50 Wh/m3

0.40 Wh/m3

0.30 Wh/m3

900

800

700

600

500

400

300

200

100

500 1000 1500 2000 2500 3000 3500 4000

ext

. pre

ssur

e in

crea

se [

Pa]

Air volume flow [m3/h]

Speed 10 VSpeed 8 VSpeed 6 VSpeed 4 V

0.70 Wh/m3

0.60 Wh/m3

0.50 Wh/m3

0.40 Wh/m3

0.30 Wh/m3

92

90

88

86

84

82

80

800 1200 1600 2000 2400 2800 3200

Eff

icie

ncy

leve

l [%

]

Air volume flow [m3/h]

TABL

= + 21 °C and + 23 °C for 40 % r.H. - 10 °CT

AUL= - 6 °C

- 3 °C

ŋ = T

ZUL - T

AUL

T

ABL - T

AUL

Page 6: COMPACT VENTILATION UNIT LG 3200 - Pichlerluft · COMPACT VENTILATION UNIT LG 3200 PAGE 3 Layout sketch LG 3200 S (free-standing installation) Air line connection: outdoor air / extract

COMPACT VENTILATION UNIT LG 3200 PAGE 6

SOUND DATA

(with an external pressure increase of 100/200 Pa)

Technical specifications

Volu

me

flow

V

[m³/

h]pt = 100 pa pt = 200 pa

Lw [dB/Oct]

L W [d

B]

L WA [d

B(A

)]

Lw [dB/Oct]

L W [d

B]

L WA [d

B(A

)]

63 H

z

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

8000

Hz

63 H

z

125

Hz

250

Hz

500

Hz

1000

Hz

2000

Hz

4000

Hz

8000

Hz

Supply air connecting pieces

1600 34 43 58 61 67 64 57 44 70 70 40 49 64 67 73 70 63 50 76 76

2200 42 49 68 69 74 71 64 53 77 77 48 55 74 75 80 77 70 59 83 83

2400 45 51 71 72 76 73 66 56 80 79 51 57 77 78 82 79 72 62 86 85

3000 53 57 82 79 84 80 74 65 88 87 59 63 88 85 90 86 80 71 94 93

3200 56 59 85 82 86 82 76 68 90 89 62 65 91 88 92 88 82 74 96 95

outdoor air connecting pieces

1600 25 37 49 46 44 38 22 11 52 48 31 43 55 52 50 44 28 17 58 54

2200 30 42 55 52 50 44 30 19 58 54 36 48 61 58 56 50 36 25 64 60

2400 32 44 57 54 52 46 33 21 60 56 38 50 63 60 58 52 39 27 66 62

3000 37 49 63 60 58 52 40 25 66 62 43 55 69 66 64 58 46 31 72 68

3200 39 51 65 62 60 54 43 27 68 64 45 57 71 68 66 60 49 33 74 70

Extract air connecting pieces

1600 24 40 57 48 43 37 22 15 57 51 30 46 63 54 49 43 28 21 63 57

2200 31 45 62 54 49 43 27 14 63 56 37 51 68 60 55 49 33 20 69 62

2400 33 47 64 56 51 45 29 14 65 58 39 53 70 62 57 51 35 20 71 64

3000 40 52 69 62 57 51 34 13 70 64 46 58 75 68 63 57 40 19 76 70

3200 42 54 71 64 59 53 36 13 72 66 48 60 77 70 65 59 42 19 78 72

Exhaust air connecting pieces

1600 34 43 71 60 67 65 56 47 73 71 40 49 77 66 73 71 62 53 79 77

2200 42 49 76 68 74 71 62 54 79 77 48 55 82 74 80 77 68 60 85 83

2400 45 51 78 71 76 73 64 56 81 79 51 57 84 77 82 79 70 62 87 85

3000 52 57 83 79 83 79 70 63 88 86 58 63 89 85 89 85 76 69 94 92

3200 55 59 85 82 85 81 72 65 90 88 61 65 91 88 91 87 78 71 96 94

Housing

1600 32 45 49 44 44 40 36 10 52 48 38 51 55 50 50 46 42 16 58 54

2200 39 49 58 49 50 47 44 19 60 55 45 55 64 55 56 53 50 25 66 61

2400 41 50 61 51 52 49 47 22 63 58 47 56 67 57 58 55 53 28 69 64

3000 48 54 70 56 58 57 54 31 71 65 54 60 76 62 64 63 60 37 77 71

3200 50 55 73 58 60 59 57 34 74 68 56 61 79 64 66 65 63 40 80 74

Remark: Tolerances ± 2 dB for acoustic data

Page 7: COMPACT VENTILATION UNIT LG 3200 - Pichlerluft · COMPACT VENTILATION UNIT LG 3200 PAGE 3 Layout sketch LG 3200 S (free-standing installation) Air line connection: outdoor air / extract

COMPACT VENTILATION UNIT LG 3200 PAGE 7

CONTROL UNIT

The ventilation units come equipped as standard with an inte-grated control and regulation system. The settings on the venti-lation unit are carried out using an integrated web server, limit-ed settings can also be carried out via the colour touch display PI-HMI. In addition, the current operating status conditions and system values such as operating type, fan speed, temperatures, etc. are displayed on the control system. Signal lamps display the operation (green) and faults (flashing red) including as plain text displays. Auto matic or manual mode can be selected.

DIMENSIONS

Item Dimensions Item Number

PI-HMI with Connec-ting cable, length 1 m and double-sided RJ12 connector

(W x H x D) 80 x 121 x 42 mm

included in the delivery

OPTIONAL: BUILDING AUTOMATION – NETWORKING OPTIONSThe Pichler-Air2-System offers multiple networking options as integration into a higher level building automation system.• Integratred webserver• Modbus RTU• Modbus TCP/IP• BACnet• KNX-GatewayThe corresponding bus connection is activated/parameterized at the factory according to the customer's order.

SIGNAL EXCHANGE• Low rpm input• High rpm input• Error message Level A (shutdown of the system)• External start input• External stop input (optional)• External fire alarm input (optional)• Operational

FUNCTIONS OF THE PICHLER CONTROL• Preheater battery, electric or PWW• Reheater battery, electric or PWW• Cooling battery PKW / DX• Air ventilation and humidification• Continuously controlled heat/"cold" recovery

via the counterflow heat exchanger and bypass• Air filter monitoring with pressure sensors

(static or dynamic)• External air compensation• Summer nights cooling (only for weekly program)• Weekly program

CONTROL METHODS

• Constant volume flow control• Constant pressure control (optional)• PICHLER System Optimiser (optional)• Air quality control CO

2 (sensor required)

• Air quality control VOC VOC (sensor required)• External control signal 0-10 V (optional)

Operation

Colour touch display PI-HMI Optimized operation with the Pichler-System-Optimizer

Page 8: COMPACT VENTILATION UNIT LG 3200 - Pichlerluft · COMPACT VENTILATION UNIT LG 3200 PAGE 3 Layout sketch LG 3200 S (free-standing installation) Air line connection: outdoor air / extract

COMPACT VENTILATION UNIT LG 3200 PAGE 8

Integrated webserver plant status

Function Description Standard Optional*

Ventilation control method:

Constant volume flow control

Constant pressure control

PICHLER System Optimiser

Air quality control CO2

Air quality control VOC

External control signal 0-10 V

Temperature control method

Constant supply air temperature

Constant extract air temperature

Ancillary functions External air compensation

Summer nights cooling (only for weekly program)

Possible heating and cooling components

External electric pre-heater battery

Control of an external E-re-heater battery

DX cooler controller

Control of a water pre-heater battery

Control of a water re-heater battery

Control of a water cooling battery

Control of a water combi battery

Communication Integrated web server

Modbus TCP/IP

Modbus RTU (not possible with System Optimiser!)

BACnet

KNX-Gateway

Signal exchange hardware

Analog input for VOC/CO2 sensor (on terminal)

Low rpm input

High rpm input

Shut-off valves 2x Belimo LM24A control (on terminal)

Error message Level A (floating max. 30V / 3A)

Error message Level B (Maintenance message)

External start input (inverted)

External stop input (on terminal)

External fire alarm input (on terminal)

Operational (floating max. 30V / 3A)

* The options must be specified in the order and will attract additional costs!

Functional overview

Page 9: COMPACT VENTILATION UNIT LG 3200 - Pichlerluft · COMPACT VENTILATION UNIT LG 3200 PAGE 3 Layout sketch LG 3200 S (free-standing installation) Air line connection: outdoor air / extract

COMPACT VENTILATION UNIT LG 3200 PAGE 9

SPARE FILTER

Will ensure perfect hygiene and air quality given regular replacement, also proper functionality and efficient operation of the equipment.

Item Item number

Filter ODA ISO ePM1 55% (outdoor air)

40LG050170 (standard)

Filter ETA ISO Coarse 90% (extract air)

40LG050180 (standard)

Filter ODA ISO ePM1 85% (outdoor air)

50LG050190

Filter ETA ISO ePM10 70% (extract air)

40LG050200

DEMAND-ORIENTED VENTILATION CONTROL

CO2 or VOC sensors for demand-oriented ventilation control.

The ventilation unit will automatically increase or reduce the air volumes depending on the quality of the air in the room. The sensors are designed for flush and surface mounting.Colour: whiteDimensions: W x H x D = 85 x 85 x 35 mmAmbient temperature: 10-50°CMeasuring range: 0-2000 ppmSensor supply voltage: 24V AC/DCControl signal: 0-10 V

Item Item number

CO2 sensor 07RCO248330

Needs-based operation via the CO2 or VOC sensor module only functions in automatic mode. The assignment of the fan speeds, the ppm and humidity values can be changed via the integrated web server.

BUTTERFLY VALVES

Frames and galvanised slats, with mounted actuator LM24A-F.LG 3200: 2 x 08AKE800300LG 3200S: 1 x AKE800300 + 1 x AKE786486

Item Dimensions Item number

Butterfly valve for devices with overhead connections with a flan-ge: P30, actuator LM24A-F

Connection: W x H = 800 x 300 mm

08AKE800300

Butterfly valve for devices with connections with a flange, which are positioned at the side: P30, actuator LM24A-F

Connection: W x H = 786 x 486 mm

08AKE786486

CANVAS CONNECTION

Made of laminated and highly tear-resistant fabric and with double-sided flanges made of galvanized sheet steel. P30 flange. Elongated length : 150 mmLG 3200: 4 x 08STELG3200LG 3200S: 2 x 08STELG3200 + 2 x 08STELG3200S

Item Dimensions Item number

Canvas connection for devices with overhead connections

Connection: W x H = 800 x 300 mm

08STELG3200

Canvas connections for devices with connections that are positioned at the side

Connection: W x H = 786 x 486 mm

08STELG3200S

ELECTRIC PREHEATING RADIATOR

Can be connected to the external air connection pipe of the comfort ventilation device. Electric preheating module with in-finitely variable control 0 to 10 V as freeze protection for the counter current heat exchanger.Power: 12 kW We strongly recommend the use of an additional pre-filter (item number 08VFBG4800300).

Item Item number

Item no. with electric preheating radiator for right-hand version

08LG3200-R-V, SR-V

Item no. with electric preheating radiator for left-hand version

08LG3200-L-V, SL-V

Item no. with electric preheating and reheating radiator for right-hand version

08LG3200-R-V-N, SR-V-N

Item no. with electric preheating and reheating radiatorfor left-hand version

08LG3200-L-V-N, SL-V-N

CO2 sensor

Accessories

Page 10: COMPACT VENTILATION UNIT LG 3200 - Pichlerluft · COMPACT VENTILATION UNIT LG 3200 PAGE 3 Layout sketch LG 3200 S (free-standing installation) Air line connection: outdoor air / extract

COMPACT VENTILATION UNIT LG 3200 PAGE 10

PRE-FILTER BOX FOR ELECTRIC HEATING COILS

The external filter box is to be used as a pre-filter for devices with electric preheating coils. Filter class ISO Coarse 70%. The pre-filter box must be insulated on site and can be installed directly on the heating radiator.

DIMENSIONS

Item Dimensions Item number

Pre-filter box for LG 3200, with pre-filter mat ISO Coarse 70%, galvanised

(W x H x D) 800 x 300 x 200 mm

08VFBG4800300

Spare filter mat ISO Coarse 70% for LG 3200

(W x H) 795 x 283 mm

08EFG4283795

FILTER AND WARM WATER PREHEATING RADIATOR BOX

Insulated enclosure, consisting of a filter unit and a hot water pre-heating battery. The outside air filter of the ventilation unit is inserted into the filter and hot water pre-heating battery box. Only in connection with an additional duct temperature sensor (item number 40LG0400011A) and a three-way motor control valve (Art. Nr. 07R3..LR24ASR).Air volume: 3200 m³/hAir inlet temperature: -16 °CAir outlet temperature: 0 °CMedium: 55/45 °CGlycol fraction: 30%Power: 17,51 kW

Item Dimensions Item number

Filter and warm water preheating radiator box, isolated

(W x H x D) 800 x 695 x 960 mm

08HBOXLG3200

Filter and warm water preheating radiator box

Pre-filter box for protecting the electric preheating coil

0,27 kgStahlbl. verz. DX51D+Z275MAC 0,9 mm

LG3200 Vorfilterbox Filterauflage006_VFB_A_LG32002006

0,425 kgStahlbl. verz. DX51D+Z275MAC 0,9 mm

LG3200 Vorfilterbox Filter Deckel005_VFB_A_LG32001005

0,535 kgStahlbl. verz. DX51D+Z275MAC 0,9 mm

LG3200 Vorfilterbox Filter 2004_VFB_A_LG32001004

0,517 kgStahlbl. verz. DX51D+Z275MAC 0,9 mm

LG3200 Vorfilterbox Filter 1003_VFB_A_LG32001003

1,864 kgStahlbl. verz. DX51D+Z275MAC 0,9 mm

LG3200 Vorfilterbox Rahmen 2002_VFB_A_LG32001002

2,126 kgStahlbl. verz. DX51D+Z275MAC 0,9 mm

LG3200 Vorfilterbox Rahmen 1001_VFB_A_LG32001001

0 kgDichtband Dichtband 3x15 L=173,240LG060170270 kgDichtband Dichtband 3x15 L=271,840LG06017026

0,005 kgCr(III) Linsenschraube M6x16 BN4825 ecosyn-fix verzinkt

40LG03213045

0 kgStahl, weich, unlegiert EINNIETMUTTER M6 mit Rändelung Stahl verz.

40LG03024044

0,064 kgFiltermatte G4 LG3200 Vorfilterbox Filter14FILTERMATTEEU40,23 m²

2

0,068 kgStahlbl. verz. 1,5 mm ECKWINKEL C3012JKSBPW3081

StücklisteGewichtMATERIALZULIEFERERBenennungArtikel Nr.Stk.Pos

A

123

C

E

1

D

23

B

7

A

EINBAUVORSCHLAG

C

4

4567

E

D

56

B

Benennung:

Datum:Gezeichnet:

Kunde:Blatt Nr.

Dateiname:Maßstab:DIESER PLANUNGSVORSCHLAG IST NUR IN VERBINDUNG MIT UNSEREN VORBEMERKUNGEN GÜLTIG!

BEHÖRDENAUFLAGEN SIND BAUSEITIG ABZUKLÄREN UND UNBEDINGT EINZUHALTEN!

NATURMASZE UND HÖHENKOTEN SIND ZU ÜBERPRÜFEN!UNSTIMMIGKEITEN SIND MIT DEM PLANVERFASSER ABZUKLÄREN!ALLE MASZE SIND VOR DER AUSFÜHRUNG VOM KUNDEN ZU PRÜFEN!

Geprüft:Diese Zeichnung stellt nach den Urh. Ges § 24 unser geistiges Eigentum dar und darf ohne unsere ausdrückliche Zustimmung weder Konkurrenzfirmen, noch dritten Personen weitergegeben werden. Die unbefugte bzw. bestimmungswidrige Verwendung dieser Unterlagen ist nicht gestattet und wird gerichtlich verfolgt.

LG3200 Vorfilterbox

LG3200 Vorfilterbox.idw

19.05.2017

MTreiber

Prüfer:

1 von 1 1 : 5

Freimaßtoleranz nach DIN ISO 2768-mHZeichnungsstatus: Freigegeben

Revision:

A

Gespeichert: 12.10.2017 07:11:34

Bauvorhaben: Gewicht:6,633 kg

Auftragsnummer:

J. Pichler Gesellschaft m.b.H 9021 Klagenfurt, Karlweg 5, Postfach 32T +43 (0)46332769, F +43 (0)463 [email protected], www.pichlerluft.at

AMessner08.06.2017Zeichnungsnummer:

000_VFB_A_LG3200Artikelnummer.08VFBG4800300

005

2

0011

006002

5

4

200

359,6

859,6

800

300

004

7

6

7

003

0,27 kgStahlbl. verz. DX51D+Z275MAC 0,9 mm

LG3200 Vorfilterbox Filterauflage006_VFB_A_LG32002006

0,425 kgStahlbl. verz. DX51D+Z275MAC 0,9 mm

LG3200 Vorfilterbox Filter Deckel005_VFB_A_LG32001005

0,535 kgStahlbl. verz. DX51D+Z275MAC 0,9 mm

LG3200 Vorfilterbox Filter 2004_VFB_A_LG32001004

0,517 kgStahlbl. verz. DX51D+Z275MAC 0,9 mm

LG3200 Vorfilterbox Filter 1003_VFB_A_LG32001003

1,864 kgStahlbl. verz. DX51D+Z275MAC 0,9 mm

LG3200 Vorfilterbox Rahmen 2002_VFB_A_LG32001002

2,126 kgStahlbl. verz. DX51D+Z275MAC 0,9 mm

LG3200 Vorfilterbox Rahmen 1001_VFB_A_LG32001001

0 kgDichtband Dichtband 3x15 L=173,240LG060170270 kgDichtband Dichtband 3x15 L=271,840LG06017026

0,005 kgCr(III) Linsenschraube M6x16 BN4825 ecosyn-fix verzinkt

40LG03213045

0 kgStahl, weich, unlegiert EINNIETMUTTER M6 mit Rändelung Stahl verz.

40LG03024044

0,064 kgFiltermatte G4 LG3200 Vorfilterbox Filter14FILTERMATTEEU40,23 m²

2

0,068 kgStahlbl. verz. 1,5 mm ECKWINKEL C3012JKSBPW3081

StücklisteGewichtMATERIALZULIEFERERBenennungArtikel Nr.Stk.Pos

A

123

C

E

1

D

23

B

7

A

EINBAUVORSCHLAG

C

4

4567

E

D

56

B

Benennung:

Datum:Gezeichnet:

Kunde:Blatt Nr.

Dateiname:Maßstab:DIESER PLANUNGSVORSCHLAG IST NUR IN VERBINDUNG MIT UNSEREN VORBEMERKUNGEN GÜLTIG!

BEHÖRDENAUFLAGEN SIND BAUSEITIG ABZUKLÄREN UND UNBEDINGT EINZUHALTEN!

NATURMASZE UND HÖHENKOTEN SIND ZU ÜBERPRÜFEN!UNSTIMMIGKEITEN SIND MIT DEM PLANVERFASSER ABZUKLÄREN!ALLE MASZE SIND VOR DER AUSFÜHRUNG VOM KUNDEN ZU PRÜFEN!

Geprüft:Diese Zeichnung stellt nach den Urh. Ges § 24 unser geistiges Eigentum dar und darf ohne unsere ausdrückliche Zustimmung weder Konkurrenzfirmen, noch dritten Personen weitergegeben werden. Die unbefugte bzw. bestimmungswidrige Verwendung dieser Unterlagen ist nicht gestattet und wird gerichtlich verfolgt.

LG3200 Vorfilterbox

LG3200 Vorfilterbox.idw

19.05.2017

MTreiber

Prüfer:

1 von 1 1 : 5

Freimaßtoleranz nach DIN ISO 2768-mHZeichnungsstatus: Freigegeben

Revision:

A

Gespeichert: 12.10.2017 07:11:34

Bauvorhaben: Gewicht:6,633 kg

Auftragsnummer:

J. Pichler Gesellschaft m.b.H 9021 Klagenfurt, Karlweg 5, Postfach 32T +43 (0)46332769, F +43 (0)463 [email protected], www.pichlerluft.at

AMessner08.06.2017Zeichnungsnummer:

000_VFB_A_LG3200Artikelnummer.08VFBG4800300

005

2

0011

006002

5

4

200

359,6

859,6

800

300

004

7

6

7

003

80096

0

750

595

695

800

960

750

595

695

800

960

750

595

695

revision

Page 11: COMPACT VENTILATION UNIT LG 3200 - Pichlerluft · COMPACT VENTILATION UNIT LG 3200 PAGE 3 Layout sketch LG 3200 S (free-standing installation) Air line connection: outdoor air / extract

COMPACT VENTILATION UNIT LG 3200 PAGE 11

ELECTRIC REHEATING RADIATOR

Can be connected to the supply air connection pipe of the comfort ventilation unit. Electric re-heating module with infi-nitely variable control of 0 to 10V for re-heating the supply air.Power: 4 kW

Item Item number

Item no. with electric reheating radiator for right-hand version

08LG3200-R-N, SR-N

Item no. with electric reheating radiator for left-hand version

08LG3200-L-N, SL-N

Item no. with electric preheating and reheating radiator for right-hand version

08LG3200-R-V-N, SR-V-N

Item no. with electric preheating and reheating radiatorfor left-hand version

08LG3200-L-V-N, SL-V-N

EXTERNAL WARM WATER REHEATING RADIATOR

For reheating the supply air for duct installation (W x H = 800 x 500 mm). Only in connection with an additional duct temperature sensor (item number 40LG0400011A) and a three-way motor control valve (item number 07R3..LR24ASR).Air volume: 3400 m³/hMedium: 60/40 °CDuct connection: W x H = 800 x 500 mmDimensions: W x H x D = 838 x 538 x 450 mm

Number of pipe rows Power Item number

2 PCS approx. 15 kW 40LG080200

3 PCS approx. 20 kW 40LG080260

EXTERNAL COLD WATER COIL

For cooling the supply air for duct installation (W x H = 800 x 500 mm), with integrated condensate drain, housing uninsulated. Only in connection with an additional duct temperature sensor (item number 40LG0400011A) and a three-way motor control valve (item number 07R3..LR24ASR).

Air volume: 3400 m³/hMedium: 7/12 °CNumber of pipe rows: 3 PCSPower: approx. 17 kWDuct connection: W x H = 800 x 500 mmDimensions: W x H x D = 928 x 530 x 395 mm

Item Item number

Cold water coil 40LG080210

Droplet separator for cold water coils

01DE8050

EXTERNAL SUPPLY AIR TEMPERATURE SENSOR

Item Item number

Duct temperature sensor – PT1000 sensor with flange, cable length 5 m

40LG0400011A

ROOM TEMPERATURE SENSOR

Item Item number

Room temperature sensor – PT1000 sensor in the surface-mounted housing

40LG041330

THREE-WAY MOTOR CONTROL VALVE

Three-way control ball valve for the continuous closed-loop con-trol of cold and warm water with a mounted closed-loop control actuator.Belimo drive: LR 24ASRDrive voltage: 24V AC/DCControl signal: 0-10V DCControl ball valve: R3015Mounting position: optional

KVS value Item number

0,63 m³/h 07R309LR24ASR

1,0 m³/h 07R310LR24ASR

1,6 m³/h 07R311LR24ASR

2,5 m³/ 07R312LR24ASR

Warm water reheating radiator Cold water coil Duct temperature sensor

Page 12: COMPACT VENTILATION UNIT LG 3200 - Pichlerluft · COMPACT VENTILATION UNIT LG 3200 PAGE 3 Layout sketch LG 3200 S (free-standing installation) Air line connection: outdoor air / extract

COMPACT VENTILATION UNIT LG 3200 PAGE 12

Data in accordance with EU Regulations 1253-2014

Download from: www.pichlerluft.at

Product fiche System Ventech LG 3200

Seite 1 von 2

Model IDType Two-way ventilation plant for non-residential useDrive type

Internal specific fan power SVLint 1153 [W/(m³/s)]

Thermal transmission ηt_nwla 86,00% [-]

Enclosure sound power level LWA 72 [dB(A)]

1 [m³/s]

3600 [m³/h]actual electrical input power Pel,ges 1,69 [kW]

Airflow speed vnom 1,96 [m/s]

Nominal outside pressure ZUL Δps,ext ZUL 94 [Pa]

Nominal outside pressure ABL Δps,ext ABL 94 [Pa]

Internal pressure drop across ventilation components, ZUL Δps,int ZUL 380 [Pa]

Internal pressure drop across ventilation components, ABL Δps,int ABL 313 [Pa]

Internal pressure drop across non-ventilation components, ZUL Δps,add ZUL 0 [Pa]

Internal pressure drop across non-ventilation components, ABL Δps,add ABL 0 [Pa]

Fan efficiency, ZUL, at nominal external pressure loss and internal pressure loss across ventilation components

ηfan ZUL 60,89 [%]

Fan efficiency, ABL, at nominal external pressure loss and internal pressure loss across ventilation components

ηfan ABL 59,23 [%]

External air leakage (at ±400 Pa) < 1 [%]Internal air leakage (at 250 Pa) < 1 [%]Energy class, ZUL-filter (F7) ** 2100,4 [kWh]Energy class, ABL-filter (G4) ** 1294,1 [kWh]

PICHLER System Ventech LG 3200

Speed control

Other heat recovery system counterflowheat exchanger

Produktdatenblatt PICHLER System Ventech LG 1400

Type of heat recovery *

Nominal airflow qnom

Point 1

Area of application

The apparatus complies with the Eco-design Directive inside the cross-hatched areaThe diagram applies to the reference coNominal air flow [m³/h]ext. pressure [Pa]Point 1Point 2Point 4Point 5Point 3nfiguration (fans, filters, heat

exchangers) without assemblies not for ventilation (e.g. heating coils, louvre flaps, etc.). Additional loss of pressure must be taken into account when installing assemblies not for ventilation.

Page 1 of 2

ZUL = supply airABL = extract air

Page 13: COMPACT VENTILATION UNIT LG 3200 - Pichlerluft · COMPACT VENTILATION UNIT LG 3200 PAGE 3 Layout sketch LG 3200 S (free-standing installation) Air line connection: outdoor air / extract

COMPACT VENTILATION UNIT LG 3200 PAGE 13

Download from: www.pichlerluft.at

Seite 2 von 2

Internal specific fan power SVLint 1177 [W/(m³/s)]

Thermal transmission ηt_nwla 86,00% [-]

Enclosure sound power level LWA 68 [dB(A)]

1 [m³/s]3600 [m³/h]

Nominal external pressure, ZUL Δps,ext ZUL 50 [Pa]

Nominal external pressure, ABL Δps,ext ABL 50 [Pa]

Internal specific fan power SVLint 972 [W/(m³/s)]

Thermal transmission ηt_nwla 86,50% [-]

Enclosure sound power level LWA 73 [dB(A)]

0,917 [m³/s]

2200 [m³/h]Nominal external pressure, ZUL Δps,ext ZUL 272 [Pa]

Nominal external pressure, ABL Δps,ext ABL 272 [Pa]

Internal specific fan power SVLint 291 [W/(m³/s)]

Thermal transmission ηt_nwla 92,00% [-]

Enclosure sound power level LWA 74 [dB(A)]

0,236 [m³/s]850 [m³/h]

Nominal external pressure, ZUL Δps,ext ZUL 829 [Pa]

Nominal external pressure, ABL Δps,ext ABL 829 [Pa]

Internal specific fan power SVLint 267 [W/(m³/s)]

Thermal transmission ηt_nwla 92,00% [-]Enclosure sound power level LWA 65 [dB(A)]

0,236 [m³/s]

850 [m³/h]Nominal outside pressure ZUL Δps,ext ZUL 50 [Pa]

Nominal outside pressure ABL Δps,ext ABL 50 [Pa]

Filter class Final pressuredifference

G1-G4 150 Pa

M5-F7 200 Pa

F8 - F9 300 Pa

Nominal airflow qnom

Nominal airflow qnom

Nominal airflow qnom

Nominal airflow qnom

* Types of heat recovery:

none

Fluid circulation heat exchanger

other heat recovery system

The ventilation unit complies with Eco-design Directive (EU Regulation 1253/2014) as required for 2018.

Visual filter warningThe ventilation unit has a visual warning to replace the filter. An error message will be displayed on the control panel when the set pressure difference is exceeded.WARNING: The plant will not work efficiently unless the filter is replaced regularly, causing power consumption to increase.

DisposalEquipment that is no longer functional must be uninstalled by a specialist firm and properly disposed of at a suitable facility. The Electrical and Electronic Equipment Act (EAG-VO), implementing Community law Directives 202/95/EC (RoHS) and 2002/96/EC (WEEE Directive) applies.

Point 2

Point 3

Point 4

Point 5

** The energy class is calculated based on the annual operating hours (8760 h) and average pressure loss (see table below for final pressure loss pursuant to ÖNORM EN 13053).

Max. pressure drop across filter pursuant to ÖNORM EN 13053:

Information based on the current state of knowledge of EU Regulation 1253/2014 Download from: www.pichlerluft.at

Page 2 of 2

Systematic ventilation.

J. PICHLERGesellschaft m.b.H.

[email protected]

ÖSTERREICH9021 KLAGENFURT AM WÖRTHERSEEKarlweg 5T +43 (0)463 32769F +43 (0)463 37548

ÖSTERREICH1100 WIENDoerenkampgasse 5T +43 (0)1 6880988F +43 (0)1 6880988-13

Sales offices in Slovenia and Serbia. Sales partners in Germany, Switzerland and Italy.

Responsible for the content: J. Pichler Gesellschaft m.b.H.Photos: Archiv J. Pichler Gesellschaft m.b.H. | Text: J. Pichler Gesellschaft m.b.H. All rights reserved | All photos are symbolic photos | Subject to change without notice | Version: 03/2016 db

Page 14: COMPACT VENTILATION UNIT LG 3200 - Pichlerluft · COMPACT VENTILATION UNIT LG 3200 PAGE 3 Layout sketch LG 3200 S (free-standing installation) Air line connection: outdoor air / extract

COMPACT VENTILATION UNIT LG 3200 PAGE 14

Fans: energy-saving radial fans with state-of-the-art EC motor technology with optional automatic constant volume flow control with an optional constant volume flow control or constant pressure control

Counterflow heat exchanger: highly efficient heat recovery system with an air/air counterflow heat exchanger with an automatic 100% bypass

Air volume flow: of 900 to 3400 m³/h with an external pressure of 100 to 600 Pa

Filters: Filter ODA ISO ePM2,5 65% (outdoor air), Filter ETA ISO Coarse 90% (extract air).

Electric preheater battery: able to be connected to the outdoor air connecting piece of the comfort ventilation unit, with an optional heat insulation.

Hot water reheater battery: for reheating the supply air (for external duct installation)

Housing: made from zinc-plated steel plate with 50 mm thermal insulation

Air line connections LG 1400: outdoor air / exhaust air / supply air / extract air (W x H) 300 x 800 mm

Air line connections LG 1400 S: outdoor air / exctract air (W x H) 300 x 800 mm and exhaust air / supply air (W x H) 486 x 786 mm

Connection profile: P30

Installation position: Free-standing installation

Summer changeover: integrated 100% bypass damper with seal

Optional: building automation – networking options:• Integratred webserver• Modbus RTU• Modbus TCP/IP• BACnet• KNX-GatewayThe corresponding bus connection is activated/parameterized at the factory according to the customer's order.

Electrical connection: using terminals

Service – maintenance – initial startup

OUR COMPACT VENTILATION UNIT LG 3200 HAS BEEN EXTERNALLY INSPECTED BY

• Lucerne Polytechnic – Engineering & Architecture

• TÜV-AUSTRIA Services GmbH, Testing, Inspection and Certification Centre/Vienna

OUR COMPACT VENTILATION UNIT LG 3200 HAS BEEN CERTIFIED BY

• Passivhausinstitut (Passive House Institute) Darmstadt

• energie-cluster.ch, Declaration report by Lucerne Polytechnic

Notice: Our product range includes units with a size up to 10,000 m³/h as well as comprehensive accessories.

LG 3200 and LG 3200 S at a glance!

Page 15: COMPACT VENTILATION UNIT LG 3200 - Pichlerluft · COMPACT VENTILATION UNIT LG 3200 PAGE 3 Layout sketch LG 3200 S (free-standing installation) Air line connection: outdoor air / extract

COMPACT VENTILATION UNIT LG 3200 PAGE 15

Notes

Page 16: COMPACT VENTILATION UNIT LG 3200 - Pichlerluft · COMPACT VENTILATION UNIT LG 3200 PAGE 3 Layout sketch LG 3200 S (free-standing installation) Air line connection: outdoor air / extract

J. PICHLERGesellschaft m.b.H.

[email protected]

AUSTRIA9021 KLAGENFURT AM WÖRTHERSEEKarlweg 5T +43 (0)463 32769F +43 (0)463 37548

AUSTRIA1100 WIENDoerenkampgasse 5T +43 (0)1 6880988F +43 (0)1 6880988-13

Sales offices in Slovenia and Serbia. Sales partners in Germany, Switzerland and Italy.

Responsible for the content: J. Pichler Gesellschaft m.b.H. | Graphics and layout: WERK1Photos: Ferdinand Neumüller, Archiv J. Pichler Gesellschaft m.b.H. | Text: J. Pichler Gesellschaft m.b.H. All rights reserved | All photos are symbolic photos | Subject to change without notice | Version: 02/2020 en/P

Your partner/installer:

Systematic ventilation.

ÖSTERREICH

CROATIA

SLOVENIA

SERBIA

GERMANY

CZECH REPUBLIC

SLOVAKIA

HUNGARY

ITALY

BOSNIA AND HERZEGOVINA

Klagenfurt

Wien

Maribor

Beograd

COMPACT VENTILATION UNIT LG 3200 PAGE 16

ErP 2018Fulfils the requirements of the Ecodesign Directive, in accordance with EU Regulation 1253/2014.

ErP2018