120 S. Glasgow Avenue Inglewood, California 90301 U.S.A. This access control equipment must be installed inside of a controlled, protected or restricted area to comply with UL 294 certification. Request to Exit (Free Exit) Card Reader DK Prox Reader Wiegand Access Control Device 26, 30, 31-Bit Wiegand Single Board Enclosure with Built-In Card Reader and Lighting DK Prox Reader - P/N 1815-333 HID Reader - P/N 1815-392 AWID Reader - P/N 1815-292 Single Board Enclosure P/N 2351-080 Quad Board Enclosure P/N 2351-082 Quad Board Enclosure Pre-wired P/N 2351-082 Door Lock Control Power for electric strike or magnetic lock is NOT provided by the board. Use separate UL listed power supply. 6 conductor, stranded with overall shield, 18-22 gauge. 500 ft max. DO NOT use twisted pair. Maglock Electric strike #20-Card Reader LED OR Beeper Control (Available on certain card readers) Gate Operator Control Board Power 16.5 VAC, 20 VA Required 18 GA. Wire 100 ft max 16 GA. Wire 200 ft max 34 33 32 31 30 29 28 27 26 25 24 23 22 21 14 15 16 17 18 19 20 13 12 11 10 9 8 7 6 5 4 3 2 1 ON 1 0 BOARD ADDRESS 0 9 8 7 6 5 4 3 2 1 NC OUTPUT RELAY NO NC ALARM RELAY NO NC AUX RELAY NO ENT RESET 2358-010 RF DATA RF SECURE RF STATUS CODE SENT CODE GOOD CODE BAD 34 33 32 31 30 29 28 27 26 25 24 23 22 21 14 15 16 17 18 19 20 13 12 11 10 9 8 7 6 5 4 3 2 1 ON 1 0 BOARD ADDRESS 0 9 8 7 6 5 4 3 2 1 NC OUTPUT RELAY NO NC ALARM RELAY NO NC AUX RELAY NO ENT RESET 2358-010 RF DATA RF SECURE RF STATUS CODE SENT CODE GOOD CODE BAD NC NO RING ON CLK SEN SPK VOL FEED BACK RS 232 ELEVATOR 1 2 3 4 5 6 7 8 9 10 11 12 13 14 1 2 3 MIC VOL OFF KEYPAD 3 2 1 3 2 1 3 2 1 MASTER CODE 16AC 16AC BAT 1NO 1NC 1C 2RY 2C A Z IMC 5VDC IMD SPKR COM MIC PSW CGND PHONE 1 2 3 4 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 NO NC C Tracker Expansion Board Address 3 Tracker Expansion Board Address 4 Relay 2 Communication 2 Communication Line Tracker Expansion Board Enclosure Options Typical BASIC Tracker Expansion Board Wiring Options for Access Point NO “optional” tracker features or standby battery wiring shown, see manual for details. Auxiliary Terminal Relay 0 Relay 1 Central Office phone line - touch tone, loop start. Switch closure across terminals 4 & 6 will activate relay 1 for its programmed strike time. (Postal Lock) Important Note: Relay 2 is used to control tracker expansion board addresses 3-10, Relay 1 or Relay 0 can be used as the Primary Relay that will open a visitor door or gate when the resident pushes “9” on their telephone. Tracker Expansion Board Notes: All tracker expansion boards can be wired with desired options for their access points like shown on tracker expansion board address 3. Communication line will continue for each board like shown on tracker expansion board address 4. Board addresses MUST start at 3 and contiunue thru board address 10 (up to 12 boards using Zone Addresses) if required. Tracker expansion boards connected to Wiegand 2 will activate Relay 2 in the access control system. Main Door/Gate Relay 1 or Relay 0 Auxiliary Terminal Black #9-Com White #8-Data 1 Green #7-Data 0 Black #27-Com White #28-Data 1 Green #29-Data 0 Black #27-Com White #28-Data 1 Green #29-Data 0 Green #29-Data 1 White #28-Data 0 Black #27-Com Brown #19 Brown #19 To #18 To #18 Blue #17 Blue #17 Red #10 Tracker Expansion Board “Busy” #10 Red #10 Output Relay #25 & #26 Brown #13 Blue #14 To Board Addresses 5 thru 10 Ground #32 Set Output Relay Jumper Relay 2 Jumper Relay Jumper Relay Jumper N.O. Com To #8 Com To #8 Ground 12 GA. Wire Aux Power Main Power Power #33 Power #34 Blue - Beeper Yellow - LED Board Power Ground #32 Ground Power #33 Power #34 #10 connects ONLY to tracker expansion boards NC NO First Board Address Starts at 3 ON OFF 1 0 BOARD ADDRESS 0 9 8 7 6 5 4 3 2 1 Switch MUST be ON (1) for board address 10. Switch MUST be OFF (0) for board addresses 3 thru 9. Second Board Address Set to 4 Board Address 10 Setting ON OFF 1 0 BOARD ADDRESS 0 9 8 7 6 5 4 3 2 1 #6-Green = Data 0 #7-White = Data 1 #8-Black = Common #9-Red = 12 VDC Power Relay Jumper NO OUTPUT RELAY NC NO OUTPUT RELAY NC NO OUTPUT RELAY NC NO OUTPUT RELAY NC EXIT PUSH TO Relay 2 Jumper IMPORTANT: The maximum distance for a tracker expansion board HARDwire run is 4000 feet TOTAL (1 to 12 boards can be in a HARDwire run). The farthest board can be NO more than 2000 feet away from the access control system. See manual for multiple tracker expansion boards layout limitations. Up to 12 tracker expansion boards can be HARDwired to relay 2/wiegand 2 at the access control system. OR ON OFF 1 0 BOARD ADDRESS 0 9 8 7 6 5 4 3 2 1 For COMPLETE installation instructions, please refer to the HARDwired Installation/Owner’s manual P/N 2358-065. Lock Power Card Reader Electric Strike Door Lock Black #27-Com White #28-Data 1 Green #29-Data 0 OR Request to Exit (Free Exit) EXIT PUSH TO Use 6 conductor stranded with overall shield. 18 - 22 gauge. ONLY use 18 gauge when wiring more than 8 boards. DO NOT connect shield to 2358-010 board common. DO NOT use twisted pair. Note: If card reader has additional lighting for outdoor use, separate power must be provided. CONTROLLED AREA: A room, office, building, facility, premises, or grounds to which access is monitored, limited, or controlled. PROTECTED AREA: A room, office, building, facility, premise or grounds to which access is monitored, and limited and/or controlled, whereby the authorized person of the Access Control System may grant access to non-authorized persons. RESTRICTED AREA: A room, office, building, facility, premise or grounds to which access is monitored, and limited and strictly controlled, whereby only the administrator of the Access Control System shall issue credentials that will lead to access. Do Not Connect Power To A Receptacle Controlled By A Switch. Do Not Connect Power To A Receptacle Controlled By A Switch. Do Not Connect Power To A Receptacle Controlled By A Switch. Do Not Connect Power To A Receptacle Controlled By A Switch. 1830 Series Access Control Board 1830’s relay strike time MUST be programmed to “00” or tracker expansion board will NOT function. QUICKSTART “BASIC” HARDWIRE TRACKER EXPANSION BOARD TO RELAY 2/WIEGAND 2 GUIDELINES

Upload: others

Post on 16-Oct-2021

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Communication 2 - Doorking

120 S. Glasgow AvenueInglewood, California 90301

U.S.A.

This access control equipment must be installed inside of a controlled,protected or restricted area to comply with UL 294 certification.

Request to Exit(Free Exit)

Card ReaderDK Prox Reader

Wiegand AccessControl Device

26, 30, 31-Bit Wiegand

Single Board Enclosure withBuilt-In Card Reader and Lighting

DK Prox Reader - P/N 1815-333HID Reader - P/N 1815-392

AWID Reader - P/N 1815-292

Single Board EnclosureP/N 2351-080

Quad Board EnclosureP/N 2351-082

Quad BoardEnclosure Pre-wired

P/N 2351-082

Door Lock Control

Power for electric strike or magnetic

lock is NOT provided by the

board. Use separate UL listed

power supply.

6 conductor, stranded with overall shield, 18-22 gauge. 500 ft max.DO NOT use twisted pair.

Maglock

Electric strike

#20-Card Reader LEDOR Beeper Control

(Available on certaincard readers)

Gate Operator Control

Board Power16.5 VAC, 20 VA

Required18 GA. Wire 100 ft max16 GA. Wire 200 ft max

3433323130292827262524232221

14151617181920

13121110

987654321

ON1

0

BOARD ADDRESS

0987

65

4 3 2

1

NC

OUTPUTRELAY

NONC

ALARMRELAY

NONC

AUXRELAY

NO

ENT

RESET

2358-010RFDATA

RFSECURE RF

STATUSCODESENT

CODEGOOD

CODEBAD

3433323130292827262524232221

14151617181920

13121110

987654321

ON1

0

BOARD ADDRESS

0987

65

4 3 2

1

NC

OUTPUTRELAY

NONC

ALARMRELAY

NONC

AUXRELAY

NO

ENT

RESET

2358-010RFDATA

RFSECURE RF

STATUSCODESENT

CODEGOOD

CODEBAD

NCNORING

ON

CLKSEN

SPKVOLFEED

BACK

RS 232

ELEVATOR

12

34

56

78

910

1112

1314

1

2

3

MICVOL

OFFKEYPAD

3 2 1

3 2 1

321

MASTERCODE

16AC16ACBAT1NO1NC1C2RY2CAZIMC5VDCIMDSPKRCOMMICPSWCGNDPHONE

1 2 3 4 201918171615141312111098765

NO NC C

Tracker ExpansionBoard Address 3

TrackerExpansion

BoardAddress 4

Relay 2

Communication 2

Communication Line

Tracker Expansion Board Enclosure Options

Typical BASIC TrackerExpansion BoardWiring Optionsfor Access Point

NO “optional” tracker features or standby battery wiring shown, see manual for details.

Auxi

liary

Ter

min

al

Relay 0

Relay 1

Central Office phone line - touch tone, loop start. Switch closure across

terminals 4 & 6 will activate relay 1 for its programmed strike time.

(Postal Lock)

Important Note: Relay 2 is used to control tracker expansion board addresses 3-10, Relay 1 or Relay 0 can be used as the Primary Relay that will open a visitor door or gate when the resident pushes “9” on their telephone.

Tracker Expansion Board Notes:

All tracker expansion boards can be wired with desired options for their access points like shown on tracker expansion board address 3.

Communication line will continue for each board like shown on tracker expansion board address 4.

Board addresses MUST start at 3 and contiunue thru board address 10 (up to12 boards using Zone Addresses) if required.

Tracker expansion boards connected to Wiegand 2 will activate Relay 2 in the access control system.

Main Door/GateRelay 1 or Relay 0

AuxiliaryTerminalBlack #9-ComWhite #8-Data 1Green #7-Data 0

Black #27-ComW

hite #28-Data 1Green #29-Data 0

Black #27-ComW

hite #28-Data 1Green #29-Data 0

Green #29-Data 1W

hite #28-Data 0Black #27-Com

Brown #19 Brown #19

To #18

To #18Blue #17 Blue #17

Red

#10

Tracker ExpansionBoard “Busy” #10

Red #10

Output Relay#25 & #26

Brown #13

Blue #14

To Board Addresses 5 thru 10

Ground #32

Set OutputRelay Jumper

Relay 2Jumper

RelayJumper

RelayJumper

N.O.

Com

To #8 Com

To #8

Ground12 GA. Wire

AuxPower

MainPower

Power #33

Power #34

Blue - Beeper

Yellow - LED

Board Power

Ground #32

Ground

Power #33

Power #34

#10 connectsONLY to tracker

expansion boards

NC

NO

First Board AddressStarts at 3

ON

OFF

1

0

BOARD ADDRESS

0987

65

4 3 2

1

Switch MUST be ON (1) for board address 10.

Switch MUST be OFF (0)for board addresses 3 thru 9.

Second Board AddressSet to 4

Board Address 10SettingON

OFF

1

0

BOARD ADDRESS

0987

65

4 3 2

1

#6-Green = Data 0#7-White = Data 1

#8-Black = Common#9-Red = 12 VDC Power

RelayJumper

NO

OUTPUT

RELAY

NC

NO

OUTPUT

RELAY

NC

NO

OUTPUT

RELAY

NC

NO

OUTPUT

RELAY

NC

EXIT

PUSH TO

Rela

y 2

Jum

per

IMPORTANT: The maximum distance for a tracker expansion board HARDwire run is 4000 feet TOTAL (1 to 12 boards can be in a HARDwire run). The farthest board can be NO more than 2000 feet away from the access control system.See manual for multiple tracker expansion boards layout limitations.

Up to 12 tracker expansion boards can be HARDwired to relay 2/wiegand 2 at the access control system.

OR

ON

OFF

1

0

BOARD ADDRESS

0987

65

4 3 2

1For COMPLETE installation instructions, please refer to the HARDwired Installation/Owner’s manual P/N 2358-065.

LockPower

Card Reader

Electric StrikeDoor Lock

Black #27-ComW

hite #28-Data 1Green #29-Data 0

OR

Request to Exit(Free Exit)

EXIT

PUSH TO

Use 6 conductor stranded with overall shield. 18 - 22 gauge. ONLY use 18 gauge when wiring more than 8 boards.DO NOT connect shield to 2358-010 board common.DO NOT use twisted pair.

Note: If card reader has additional

lighting for outdoor use,

separate power must be

provided.

CONTROLLED AREA: A room, office, building, facility, premises, or grounds to which access is monitored, limited, or controlled.

PROTECTED AREA: A room, office, building, facility, premise or grounds to which access is monitored, and limited and/or controlled, whereby the authorized person of the Access Control System may grant access to non-authorized persons.

RESTRICTED AREA: A room, office, building, facility, premise or grounds to which access is monitored, and limited and strictly controlled, whereby only the administrator of the Access Control System shall issue credentials that will lead to access.

Do Not Connect Power To A Receptacle Controlled By A Switch.

Do Not Connect Power To A Receptacle Controlled By A Switch.

Do Not Connect Power To A Receptacle Controlled By A Switch.

Do Not Connect Power To A Receptacle Controlled By A Switch.

1830 Series AccessControl Board

1830’s relay strike time MUST be programmed to “00” or tracker expansion board will NOT function.

QUICKSTART “BASIC” HARDWIRE TRACKER EXPANSION BOARD TO RELAY 2/WIEGAND 2 GUIDELINES

Page 2: Communication 2 - Doorking

120 S. Glasgow AvenueInglewood, California 90301

U.S.A.

Copyright 2021 DoorKing®, Inc. All rights reserved. 2358-066-M-1-21

3433323130292827262524232221

14151617181920

13121110

987654321

ON1

0

BOARD ADDRESS

0987

65

4 3 2

1

NC

OUTPUTRELAY

NONC

ALARMRELAY

NONC

AUXRELAY

NO

ENT

RESET

2358-010RFDATA

RFSECURE RF

STATUSCODESENT

CODEGOOD

CODEBAD

LED DisplayProgramming

Buttons

Aux Relay

Alarm Relay

Output Relay

Tracker Communication Line

Ground - Required

Relay Communication Line (NO)Request to Exit

Tracker Expansion Board Busy

Access Control Device26, 30, 31-Bit Wiegand

Relay Communication Line (Com)Card Reader LED/Beeper Control

Follow these basic steps to perform desired programming, See programming options table for PROGRAM STEPS.

After all tracker expansion boards have been programmed.....

1. Press arrow buttons or ENT button to ACTIVATE LED display.

2. Press arrow buttons again to CHOOSE desired PROGRAM STEP.

3. Press ENT button to ENTER desired PROGRAM STEP. (LED display number will blink after ENT button has been pressed).

4. Press arrow buttons to choose SELECTION NUMBER for desired function of program step.

5. Press ENT button to program SELECTION NUMBER for desired function of program step. (Function has now been programmed into board).

6. Press ENT button again to exit programming OR after 10 seconds, board will automatically exit programming.

Note: Repeat these steps for all other desired programming functions.Each tracker expansion board will have to be INDIVIDUALLY programmed with desired functions.

Basic Programming Sequence on EACH Tracker Expansion Board

Manage the Complete Access Control System from Your PC

SOFTWAREINSTALLED

7 8 9

4 5 6

1 2 3

0OPER

WXYZTUVPQRS

MNOJKLGHI

DEFABCSP

CALL

ZA

TELEPHONE ENTRY SYSTEM

HOLD TO SCAN

OPERATING INSTRUCTIONSUse “A to Z” Buttons to LocateName and Code Number on Display.Names are In Alphabetical Order.To Call, Enter Code Number onKeypad or Press “Call” Button. IfLine is Busy, Press “#” or “Call” toHang Up. Try Again.Enter on Open Display and Tone.

1.

2.

3.

Refer to the DKS Remote Account Manager Software to program and manage the complete system.

Board addresses MUST be set for each board used.

Relay jumpers MUST be set for each relay used.

Programming Options on EACH Tracker Expansion Board

Board Power16.5 VAC, 20 VA

Required

Your PC connected to the access control system. Either IM Server OR TCP/IP OR RS-232 OR Modem to Modem Connection. See PC Programmable Telephone Entry and Access Control Systems Installation/Owner’s manual for more information about connection options.

ComData 1Data 0(-) 12VDC(+) 12VDC

Data 0Data 1

Com12 VDC

StandbyBattery

IMPORTANT Display Decimal Point Note

When decimal point is displayed: Indicates that you are SELECTING a program step.

When decimal point is NOT displayed: Indicates that you are IN a program step.

1

2

3

4

5

6

7

8

9

10

11

12

1314

15

16

1718192021

22

00 - 99

00 - 99

00 - 99

00 - 99

00 - 99

0 or 1

0 or 1

0 or 1

0 or 1

0 or 1

0 or 1

0 - 12

0 - 4

5

0 or 1

0001 - 99

0001 - 99

0001 - 99

0001 - 99

0001 - 99

01

01

01

01

0

1

0

1

0123

4

5

6

789

101112

0

1

2

3

4

5

ProgramStep

FactoryDefaultDescription Options

SelectionNumber Function

Door Strike Timer

Free Exit Timer, Strike Time

Door Ajar Timer

Aux Relay Timer

Free Exit Timer, Aux Relay

Free Exit, No Strike

Not Used

Door Contact Switch Logic

Auto Relock

Beeper / LED Hold Open

Hold Open or Hold Egress functions

Dual Door Mode

Not UsedNot Used

Aux Relay Functions

Alarm Relay Functions

Not UsedNot UsedReset to Factory DefaultsView RF POT SettingView RF Signal Loss

Card Code Forwarding

01 - 1 second

01 - 1 second

12 - 60 secs

12 - 60 secs

01 - 1 second

1 - Activate

0 - N.O.

0 - Disabled 0

0 - No relayfunctions

0 - Disabled

0 - Disabled

0 - Disabled

0 - Off

Adjustable SettingDisplays on LED

Door Operation Note:PROPER Condition: The access control system OR request to exit device HAS activated the OUTPUT RELAY on the tracker expansion board and the door contact switch is CLOSED (Door is OPEN). This indicates that the door has been PROPERLY OPENED.FORCED Condition: The access control system OR request to exit device has NOT activated the OUTPUT RELAY on the tracker expansion board and the door contact switch is CLOSED (Door is OPEN). This indicates that the door has been FORCED OPENED.

Sets Strike Time for output relay (term 25 & 26)0.25 second strike timeStrike time in 1-second incrementsSet Strike Time for RX (Request to Exit) of output relay (input at term 18)0.25 second Egress Strike timeEgress Strike time in 1-second incrementsTimer starts when valid access has been granted.1 second Door Ajar TimerTimer set in 5-second increments: 01 = 5 seconds, 10 = 50 secondsTimer setting for Aux Relay activation in 5-second increments1 second Door Ajar TimerTimer set in 5-second increments: 01 = 5 seconds, 10 = 50 secondsSet Strike Time for RX (Request to Exit) of Aux relay (ONLY available if Dual Door Mode step 12 is ON)0.25 second Egress Strike timeEgress Strike time in 1-second incrementsSet RX (Request to Exit) function. Activate Output Relay or do not Activate Output RelayDo Not Activate Output Relay or Reader Beeper/LED when RX input is receivedActivate Output Relay and Reader Beeper/LED for Free Exit Strike Time when RX received

Sets type of Door Switch contactsN.O. contact from door switch with Door Closed (Circuit Open - CO)N.C. contact from door switch with Door Closed (Circuit Close - CC)Turns on Auto Relock function (not available if Dual Door Mode, step 12 is ON)Output Relay is activated for Strike TimeDoor Contact Switch required. If door returns to closed position during Strike Timedoor will “relock” after 1 second, even if strike time has not expired.Sets how BEEPER or LED will function during Hold OpenWhen Hold Open occurs, Beeper or LED is active only during Strike TimerWhen Hold Open occurs, Beeper or LED will remain active during Hold Open Sets how Aux & Alarm Relay responds during Hold Open or Hold Egress situationNo Aux Relay functions. Alarm will be in “Reset”. If Alarm Relay is set for “integral” mode, Alarm relay will not activate. If Alarm Relay set for “Bypass” mode, Alarm Relay will activate for Hold Open period or Extended Egress Hold.Aux Relay will function for all settings. If Alarm Relay is set for “integral” mode, Alarm relay will not activate. If Alarm Relay set for “Bypass” mode, Alarm Relay will activate for Hold Open period or Extended Egress Hold.Sets Tracker to function as 2 Access Points (2 tracker addresses)Disabled, Tracker functions as single access pointDual Mode: Tracker functions as set board address and next sequential addressCard Read will be sent to controller as set board address, access is granted or deniedCard then sent as set address +1, access granted or denied. Aux Relay becomes 2nd output relay. All other Aux Relay functions disabled. Door Contact switch becomes RX (Request to Exit) for 2nd address.

Sets function for Aux RelayAlarm Relay DisabledNo Door Ajar Timer: Requires Door Contact Switch. Aux Relay activates when Door Not Closed.No Door Ajar Timer, Pulse: Requires Door Contact Switch. Aux Relay “pulses” when Door Not Closed.Door Ajar Timer: Requires Door Contact Switch. When door opens, start Door Ajar Timer. When timer expires Aux Relay activates for Aux Relay timer or until door closes, whichever occurs first.Door Ajar Timer, Pulse: Requires Door Contact Switch. When door opens, start Door Ajar Timer. When timer expires Aux Relay Pulses for Aux Relay timer or until door closes, whichever occurs first.Door Ajar, Pulse warning the ON: Requires Door Contact Switch. When door opens, Pulse Aux Relay and start Door Ajar Timer. When timer expires Aux Relay ON for Aux Relay timer or until door closes, whichever occurs first.Door opens for any reason, Start Door Ajar timer and pulse Aux Relay. When Door Ajar timer expires, start Aux Timer and continue Pulsing Aux Relay.When Door Closes or both timers expire, turn off Aux RelayAux Relay as 2nd Alarm Relay. Aux Relay will mirror Alarm Relay functions.Aux Relay as 2nd Alarm Relay, PULSE. Aux relay will Pulse during any Alarm Relay activation.Good Card: Aux Relay will activate for Aux Relay timer for any Access Granted CardAny Card: Aux Relay will activate for Aux Relay Timer when any card has been presented.Bad Card: Aux Relay will activate for Aux Relay timer when a card has been deniedWarn before Hold Open or Release of Hold Open: Aux relay will activate for Aux Relay timer when scheduled Hold Open begins or ends. Output Relay will be delayed until Aux Timer expires. DO NOT set Aux Timer above 60 seconds in this mode.Sets function for Alarm RelayAux Relay DisabledBypass Mode: Alarm Relay provides “Bypass” to Alarm Door Switch. With proper door input (access or egress) activate Alarm Relay, start Strike timer and Door Ajar timer. When Door Ajar timer expires, deactivate Alarm Relay.If second Door Contact Switch is provided, generate transaction for Door Ajar and Door Closed following Door Forced condition. Also generate transaction for Door Forced condition.Integral Mode, Door Ajar Timer: Door Contact Switch connected to Tracker, Alarm Relay provides connection directly to Alarm System. When door is opened for any reason, start Door Ajar timer. When Door Ajar timer expires and Door is still OPEN, activate Alarm Relay. Reset when door closes. Send Door Ajar and Door Close transactions.Integral Mode, Proper and Forced condition: Door Contact Switch connected to Tracker, Alarm Relay provides connection directly to Alarm System. With proper door input (access or egress) start Strike timer and Door Ajar timer. When Door Ajar timer expires and Door is still OPEN, activate Alarm Relay. Reset when door closes. If door is opened without proper condition, activate alarm relay. When door closes deactivate Alarm Relay. Send Door Ajar, Door Close and Door Forced transactions.Gate Alarm Function: Alarm Relay will activate for 1 second when tracker board receives a “Gate Forced” or “Gate Obstructed” transaction from the operator control board.

Sets all parameters to Factory DefaultSets maximum amount of allowable signal strength lossDisplays current signal loss between Base and Tracker.Sets Wireless Tracker to act as RepeaterONLY USE AS DIRECTED BY DOORKING TECH SUPPORT 0=Repeater Mode OFF 1=Repeater Mode ON

For COMPLETE installation instructions, please refer to the HARDwired Installation/Owner’s manual P/N 2358-065.

E1 - Relay connected to 4-pin terminal pins 1 & 2 is on for more than 5 seconds. Relay 1 in 1830 should be set for 00 seconds (0.25 second strike time)E2 - Relay connected to 4-pin terminal pins 3 & 4 is on for more than 5 seconds. Relay 2 in 1830 should be set for 00 seconds (0.25 second strike time)CO - One or more non-paired remotes has been detected but base unit's PAIRED switch is on. A1 - Board address is invalid for Tracker. Board address is improperly set as 0, 1, 2 or 19.A2 - Dual Mode - Bad Address, 18 or 19 not allowed.

Error codes on LED Displays for Baseboard and Tracker Board

Rev-E 1-13-14

QUICKSTART PROGRAMMING OPTIONS ON EACH HARDWIRED TRACKER EXPANSION BOARD GUIDELINES