18
Arrows indication circulation flow Entrance Plaza 4 STOREY WING 2 STOREY WING IC IC Green Area RING ROAD Open Storm Drain Open Storm Drain Open Storm Drain Open Storm Drain Pedestrian and Vehicular crossing Pedestrian and Vehicular crossing 137' 316' ENTRANCE TO PARKING EXIT FROM PARKING Side Walks and walkways PARKING FOR 102 VEHICLES Indicates slope Indicates slope to storm drain 1/8" drop per 1'-0" horizontal length 129' Indicates 18'-0" tall aluminium lamp posts with Metal Halide head lamp Indicates LIGHTING BOLLARD for public areas; Vandal Proof; ground mounting; glare free-light distribution; with either LED or Compact Fluorescent lamp. Pedestrian access walkway IC 6" Ø Schedule 40 PVC pipe to Sewer Main TO FOLLOW CONTOUR OF RING ROAD LEGEND ALL RIGHTS RESERVED. SITE PLAN (PARKING) Scale: 1/32"=1'-0"

Upload: others

Post on 04-May-2022

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Commercial Building Binder - UNDP

Arrows indicationcirculation flow

EntrancePlaza

4 STOREY WING

2 STOREY WING

IC IC

Green Area

RING ROAD

Open Storm DrainOpen Storm Drain Open Storm Drain Open Storm Drain

Pedestrian and Vehicular crossing

Pedestrian and Vehicular crossing

137'

316'ENTRANCE TO PARKINGEXIT FROM PARKING

Side Walks andwalkways

PARKING FOR102 VEHICLES

Indicates slope

Indicates slope to storm drain1/8" drop per 1'-0" horizontallength

129'

Indicates 18'-0" tallaluminium lamp posts withMetal Halide head lamp

Indicates LIGHTINGBOLLARD for public areas;Vandal Proof; groundmounting; glare free-lightdistribution; with eitherLED or CompactFluorescent lamp.

Pedestrian access walkway

IC6" Ø Schedule40 PVC pipe toSewer Main

TO FOLLOW CONTOUR OF RING ROAD

LEGEND

ALL RIGHTS RESERVED.

SITE PLAN (PARKING)Scale: 1/32"=1'-0"

Page 2: Commercial Building Binder - UNDP

MAIN ENTRANCEPLAZA

Electrical ducts

Elevators

AA

EE

B

B

C

C

D

DFF

G

G

24'-6" 24'-6" 24'-6" 24'-6" 24'-6" 24'-6"

22'-7

1 2"

1 2 3 4 5 6 7 8 9

A

B

C

D E

F

G

E

GROUND FLOOR PLANScale: 1/16"=1'-0"

22'-7

1 2"

22'-7

1 2"

22'-7

1 2"

1'-9

"

67'-1

01 2"

22'-7

1 2"

147'

6 7 8 9

D

optionalpartition

FOYER

MaleToilet

FemaleToilet Janitor/Duct

Janitor/Duct

UP

3'

75'-3"

Covintec

Covintec

24'-6" 24'-6" 24'-6"76'-7"

6"

8"

8"

6"

R.CR.C

6"

Covintec

69'-1

1 2"

149'-038"

Covintec

6"

6"

149'-10"70'-1

11 2"

Ferro-cement insulated paneled walls made of polystyrenewith Welded steel mesh on both side (Covintec/Monolith orsimilar)

1. Toilet Walls2. 4 storey Wing End Walls3. Two Storey Wing Right Side Wall4. Storage Building in Roof

8" Thick Concrete Block Wall1. Main Entrance into 2 Storey Wing2. Two Storey Wing Left Side Wall (by Grid 6)

6" Thick Concrete Block Wall1. Emergency Exit Stairs Walls Enclosures2. Walls bordering Windows at GRIDS3. Bathroom Wall proximate to GRID 74. Parapet Walls.

8" Thick Reinforced Concrete Wall1. Elevator Shaft2. Main Entrance into 4 Storey Building

WALL TYPE LEGEND

48'-4

"

See detail One indrawing 09/20

See detail Two indrawing 10/20

See detail Three indrawing 11/20

See detail Four indrawing 12/20

See detail ofEntrance Plaza indrawing 15/20

See detail of Ramp& Plaza in drawingx/x

UP

UP

UP

UP

UP

Emergency Stairs

EmergencyStairs

5'-1"10'-4"5'-1"4'5'-1"10'-4"5'-1"4'5'-1"10'-4"5'-1"4'5'-1"10'-4"5'-1"4'5'-1"10'-4"5'-1"4'5'-1"10'-4"5'-1"3'-5" 3'-5"1'-5

"20'-6

"17'-2

7 8"

3'

4'-9

5 8"

20'-6

"2'-6

" 3'-312"

10'-2"10'-4"4'10'-4"10'-9"

24'-6" 24'-6"

6'-5"

46'-6

"

cw1

cw2

W1

cw1

cw1

cw2

cw2

cw2

cw2

cw2

cw2

cw2

cw2

cw1

cw1

cw1

cw1

cw1

NOTE:

Indicates Glass CurtainWalls Type.(See Drg. Finishes 04/06)

3'-4"10'-4"4'20'-6"4'20'-6"4'20'-6"3'-5"

Y

Y

Z

Z

X

X

ALL RIGHTSRESERVED.

6"

6"

6"

6"

6"

6"

90'-7"

28'-9

1 2"

38'-1158"

36'-5

3 8"

8'-312"

21'-1

01 2"

69'-1

1 2"17'-1"

24'-612"

48'

25'-934"

10'-1

58

"

14'-2"

2'-4"

5'-4"

3'

W3 W

3

Emergency Door

Emergency Door

Page 3: Commercial Building Binder - UNDP

SECOND FLOOR PLANScale: 1/16"=1'-0"

Access Ramp

Electrical ducts

Elevators

AA

EE

B

B

C

C

D

D

FF

G

G

24'-6" 24'-6" 24'-6" 24'-6" 24'-6" 24'-6" 24'-6" 24'-6"

1'-9

"22'-7

1 2"

22'-7

1 2"

22'-7

1 2"

1 2 3 4 5 6 7 8 9

A

B

C

D E

F

G

E

6 7 8 9

D

1'-9

"22'-7

1 2"

22'-7

1 2"

24'-6"24'-6"24'-6"

75'-4"

47'-4

"

69'-1

1 2"

148'-11"

73'-6"

UP

UP

Emergency Stairs

cw1

cw1

cw1

cw1

cw2

cw2

cw2

cw2

cw2

cw2

cw2

cw1

cw1

1'-1112"

6'-5"10'-4"6'-5"1'-4"

6'-5"10'-4"6'-5"

1'-4"

6'-5"10'-4"6'-5"1'-4"

6'-5"10'-4"6'-5"

1'-4"

6'-5"10'-4"6'-5"1'-4"

6'-5"10'-4"6'-5"2'-1"

70'-5

1 2"

2'-5

"20'-6

"25'-0

1 2"

20'-6

"2'-6

"

2'-1" 1'-4"20'-6"

1'-4"1'-4"

1'-4"20'-6"

1'-4"1'-4"

1'-4"20'-6"

1'-4"1'-4"

1'-4"13'-8"

20'-6"

48'-4

"

49'

47'

25'-6"

cw1 Indicates Glass Curtain

Walls Type.(See Drg. Finishes 04/06)

76'-4"

ALL RIGHTSRESERVED.

Ferro-cement insulated paneled walls made of polystyrenewith Welded steel mesh on both side (Covintec/Monolith orsimilar)

1. Toilet Walls2. 4 storey Wing End Walls3. Two Storey Wing Right Side Wall4. Storage Building in Roof

8" Thick Concrete Block Wall1. Main Entrance into 2 Storey Wing2. Two Storey Wing Left Side Wall (by Grid 6)

6" Thick Concrete Block Wall1. Emergency Exit Stairs Walls Enclosures2. Walls bordering Windows at GRIDS3. Bathroom Wall proximate to GRID 74. Parapet Walls.

8" Thick Reinforced Concrete Wall1. Elevator Shaft2. Main Entrance into 4 Storey Building

WALL TYPE LEGEND

24'-6"

17'-1"

14'-2"

4'

Page 4: Commercial Building Binder - UNDP

THIRD FLOOR PLANScale: 1/16"=1'-0"

Electrical ducts

Elevators

11"

AA

EE

B

B

C

C

D

D

FF

G

G

24'-6" 24'-6" 24'-6" 24'-6" 24'-6" 24'-6"

1 2 3 4 5 6 7

A

B

C

D

67'-1

01 2"

22'-7

1 2"

22'-7

1 2"

22'-7

1 2"

147'

FOYER

optionalpartition

optionalpartition

69'-1

1 2"

148'-11"

6 7 8 924'-6"24'-6"24'-6"

73'-6"

Down

Down

Emergency Stairs

cw1

cw1

cw1

cw1

cw2

cw2

cw2

cw2

cw2

cw2

cw1

cw1

cw2

1'-1012"

6'-6"10'-4"6'-5"

1'-4"

6'-5"10'-4"6'-5"1'-4"

6'-5"10'-4"6'-5"1'-4"

6'-5"10'-4"6'-5"

1'-4"

6'-5"10'-4"6'-5"1'-4"

6'-5"10'-4"6'-5"2'-1"

70'-5

1 2"

2'-5

"20'-6

"25'-0

1 2"

20'-6

"2'-6

"

cw1 Indicates Glass Curtain

Walls Type.(See Drg. Finishes 04/06)

13'-558"10'-4"

1'-4"25'-10"

1'-4"20'-6"4'20'-6"4'20'-6"4'20'-6"

3'-5"

ALL RIGHTSRESERVED.

Ferro-cement insulated paneled walls made of polystyrenewith Welded steel mesh on both side (Covintec/Monolith orsimilar)

1. Toilet Walls2. 4 storey Wing End Walls3. Two Storey Wing Right Side Wall4. Storage Building in Roof

8" Thick Concrete Block Wall1. Main Entrance into 2 Storey Wing2. Two Storey Wing Left Side Wall (by Grid 6)

6" Thick Concrete Block Wall1. Emergency Exit Stairs Walls Enclosures2. Walls bordering Windows at GRIDS3. Bathroom Wall proximate to GRID 74. Parapet Walls.

8" Thick Reinforced Concrete Wall1. Elevator Shaft2. Main Entrance into 4 Storey Building

WALL TYPE LEGEND

Page 5: Commercial Building Binder - UNDP

ROOF PLANScale: 1/16"=1'-0"

AA

EE

B

B

C

C

D

D

G

G

1 2 3 4 5 6 7

A

B

C

D

Thickness of Roof at centre = 6"

Thickness of roof at both edge = 4.5"

Thickness of roof at both edge = 4.5"

Surface of the roof is tobe treated with a SNOWROOF PRIMER and ONECOAT OF SNOW ROOFSEALANT OR SIMILAR.

All drain pipes are to be3" Ø, schedule 40, PVCpipes and to include acast iron gratingappropriately bolted tothe concrete slab.

Ferro-cementinsulated paneledwalls made ofpolystyrene withWelded steel mesh onboth side(Covintec/Monolith orsimilar)

6 7 8 9

Thickness of Roof at centre = 6"

Thickness of roof at both edge = 4.5"

Thickness of roof at both edge = 4.5"

Slope = 1.5" fromcentre to edge

Slope = 1.5" fromcentre to edge

Slope = 1.5" fromcentre to edge

Slope = 1.5" fromcentre to edge

Electrical ducts

Ferro-cement insulated paneledwalls made of polystyrene withWelded steel mesh on both side(Covintec/Monolith or similar) tobe installed strictly withaccordance to themanufacturers' specifications.

NOTES:

26'

22'-6

1 2"

17'-7

7 8"

3'-4

"19'-9

3 4"

3'-4

"3'-5

3 4"

5'-1118"3'-4"6'-8"3'-4"

5'-1078"

4'-6" 4'-6"

149'-812"

70'-1

11 2"

7'-9

1 2"

ALL RIGHTSRESERVED.

Ferro-cement insulated paneled walls made of polystyrenewith Welded steel mesh on both side (Covintec/Monolith orsimilar)

1. Toilet Walls2. 4 storey Wing End Walls3. Two Storey Wing Right Side Wall4. Storage Building in Roof

8" Thick Concrete Block Wall1. Main Entrance into 2 Storey Wing2. Two Storey Wing Left Side Wall (by Grid 6)

6" Thick Concrete Block Wall1. Emergency Exit Stairs Walls Enclosures2. Walls bordering Windows at GRIDS3. Bathroom Wall proximate to GRID 74. Parapet Walls.

8" Thick Reinforced Concrete Wall1. Elevator Shaft2. Main Entrance into 4 Storey Building

WALL TYPE LEGEND47'-7

3 8"

Page 6: Commercial Building Binder - UNDP

GROUND FLOOR ELECTRICAL INSTALLATION PLAN(TRUNKING, JUNCTION BOXES, POWER OUTLETS)Scale: 1/16"=1'-0"

telephone terminal to run ina separate compartment inall trunkings

computer terminal to run ina separate compartment inall trunkings

cable terminal to run in aseparate compartment in alltrunkings

infloor flush ducting systems8" wide by 3 inches deepwith junction boxes locatedas per drawings

ALL RIGHTS RESERVED.

D C

BA

D C B A

122'-1112"

116'-1112"

74'-1112"

6'-1112"

56'-1112"

8'-1112"4

8'-1

11 2"

24'-1

11 2"

Page 7: Commercial Building Binder - UNDP

FIRST FLOOR ELECTRICAL INSTALLATION PLAN(TRUNKING, JUNCTION BOXES, POWER OUTLETS)Scale: 1/16"=1'-0"

FIRST FLOOR ELECTRICAL INSTALLATIONPLAN (TRUNKING, JUNCTION BOXES,POWER OUTLETS)

ALL RIGHTS RESERVED.

G F

E

G F E

Page 8: Commercial Building Binder - UNDP

SECOND FLOOR ELECTRICAL INSTALLATION PLAN(TRUNKING, JUNCTION BOXES, POWER OUTLETS)Scale: 1/16"=1'-0"

SECOND FLOOR ELECTRICALINSTALLATION PLAN (TRUNKING,JUNCTION BOXES, POWER OUTLETS)

ALL RIGHTS RESERVED.

K J

JK

Page 9: Commercial Building Binder - UNDP

THIRD FLOOR ELECTRICAL INSTALLATION PLAN(TRUNKING, JUNCTION BOXES, POWER OUTLETS)Scale: 1/16"=1'-0"

THIRD FLOOR ELECTRICAL INSTALLATIONPLAN (TRUNKING, JUNCTION BOXES,POWER OUTLETS)

ALL RIGHTS RESERVED.

M L

LM

Page 10: Commercial Building Binder - UNDP

UP

UP

UP

UP

Emergency Stairs

EmergencyStairs

GROUND FLOOR PLAN ELECTRICAL INSTALLATION PLAN(CEILING AND LIGHTING)Scale: 1/16"=1'-0"

MAIN DISTRIBUTION PANEL.The Main Distribution Panels to be 10N 3 Ph,200 A, 42 Cir. Square D and 1N 3Ph,200A, 30 Cir.

Vandal proof light fixturewith 26 watts fluorescenttubes

Double gang switch 4'-0" above ffl

Vandal proof wall light with 35watts hps light fixture

Single gang switch 4'-0" above ffl

Vandal proof lighting fixturewith 75 watts fluorescentbulb

Photocell 110 volts

Emergency lighting

Security cameras

EL

PCC

Double 110/115 voltoutlet grounded at 1'-0"except kitchen and modularfurniture

Exterior wall lamp withcompact halogen bi pin, a19 or 13 watts compactfluorescent twin. photo celloperated.

Ducting for light fixtures tobe in ceiling & all others infloor slabs

WALL LIGHTS.

Ceiling lamp with aluminumbody coated withelectrostatically appliedmicropulverized polyesterwith a glazed crystaldiffuser. lamp: 50 wattshalogen bi pin lamp.

Extractor fans grounded inbathrooms & toilets

AIR CONDITION NOTES:

The Projected over view of Air Conditioningfor the opened space areas is 599,960 BTUsper floor in the 4 Storey Wing, and 198,000BTUs per floor in the 2 Storey Wing. Afterconstruction and floor designs have beendetailed then an exact or specific designdistribution can be ascertained.

The Electrical Power entry is based on thisprojection.

EL

EL

Ground floor 4 storey wing

Emergency Exit

Emergency Exit

Toilet Blocks

Entrance Plaza

Main Entrance intoGround floor 4storey wing

Ground floor 2 storey wing

PC

2"X4" parabolictroffers fixtures

ALL RIGHTS RESERVED.

ELEVATORS NOTES ;3 phase installation with 3 lines ,neutraland a good earth . so 5 wires.this panel will be outside shaft so in caseof emergency lift can be switched off.A ground-rod for the lift will be in the inthe pit ,which is usually a better option asit gives a good ground with no impedance.Wires will need to be run to the top of theshaft and an isolation switch (breaker )installed at top .This is used when themotor is being services .A hook will need to be installed at the topof the shaft .This is used during installation.Shaft lighting must be install and a light andoutlet point installed at each floor level andin pit We also recommend two largeflorescent (40 watt) lights be installed atthe top if the shaft .

LED 30 LED external light fixtures.

Page 11: Commercial Building Binder - UNDP

UP

UP

UP

UP

Emergency Stairs

EmergencyStairs

FIRST FLOOR PLAN ELECTRICAL INSTALLATION PLAN(CEILING AND LIGHTING)Scale: 1/16"=1'-0"

EL

EL

First floor 4 storey wing

Toilet Blocks

First floor 2 storey wing

ALL RIGHTS RESERVED.

ELEVATORS NOTES ;3 phase installation with 3 lines ,neutraland a good earth . so 5 wires.this panel will be outside shaft so in caseof emergency lift can be switched off.A ground-rod for the lift will be in the inthe pit ,which is usually a better option asit gives a good ground with no impedance.Wires will need to be run to the top of theshaft and an isolation switch (breaker )installed at top .This is used when themotor is being services .A hook will need to be installed at the topof the shaft .This is used during installation.Shaft lighting must be install and a light andoutlet point installed at each floor level andin pit We also recommend two largeflorescent (40 watt) lights be installed atthe top if the shaft .

AIR CONDITION NOTES:

The Projected over view of Air Conditioningfor the opened space areas is 599,960 BTUsper floor in the 4 Storey Wing, and 198,000BTUs per floor in the 2 Storey Wing. Afterconstruction and floor designs have beendetailed then an exact or specific designdistribution can be ascertained.

The Electrical Power entry is based on thisprojection.

Page 12: Commercial Building Binder - UNDP

UP

UP

Emergency Stairs

LED 30LED 30LED 30

SECOND FLOOR PLAN ELECTRICAL INSTALLATION PLAN(CEILING AND LIGHTING)Scale: 1/16"=1'-0"

LED 30LED 30LED 30

LED 30LED 30 LED 30 LED 30

LED 30

LED 30

EL

Second floor 4 storey wing

Toilet Blocks

2 Storey wing roof plan

ALL RIGHTS RESERVED.

ELEVATORS NOTES ;3 phase installation with 3 lines ,neutraland a good earth . so 5 wires.this panel will be outside shaft so in caseof emergency lift can be switched off.A ground-rod for the lift will be in the inthe pit ,which is usually a better option asit gives a good ground with no impedance.Wires will need to be run to the top of theshaft and an isolation switch (breaker )installed at top .This is used when themotor is being services .A hook will need to be installed at the topof the shaft .This is used during installation.Shaft lighting must be install and a light andoutlet point installed at each floor level andin pit We also recommend two largeflorescent (40 watt) lights be installed atthe top if the shaft .

AIR CONDITION NOTES:

The Projected over view of Air Conditioningfor the opened space areas is 599,960 BTUsper floor in the 4 Storey Wing, and 198,000BTUs per floor in the 2 Storey Wing. Afterconstruction and floor designs have beendetailed then an exact or specific designdistribution can be ascertained.

The Electrical Power entry is based on thisprojection.

Page 13: Commercial Building Binder - UNDP

UP

UP

Emergency Stairs

THIRD FLOOR PLAN ELECTRICAL INSTALLATION PLAN(CEILING AND LIGHTING)Scale: 1/16"=1'-0"

EL

Third floor 4 storey wing

Toilet Blocks

2 Storey wing roof plan

ALL RIGHTS RESERVED.

ELEVATORS NOTES ;3 phase installation with 3 lines ,neutraland a good earth . so 5 wires.this panel will be outside shaft so in caseof emergency lift can be switched off.A ground-rod for the lift will be in the inthe pit ,which is usually a better option asit gives a good ground with no impedance.Wires will need to be run to the top of theshaft and an isolation switch (breaker )installed at top .This is used when themotor is being services .A hook will need to be installed at the topof the shaft .This is used during installation.Shaft lighting must be install and a light andoutlet point installed at each floor level andin pit We also recommend two largeflorescent (40 watt) lights be installed atthe top if the shaft .

AIR CONDITION NOTES:

The Projected over view of Air Conditioningfor the opened space areas is 599,960 BTUsper floor in the 4 Storey Wing, and 198,000BTUs per floor in the 2 Storey Wing. Afterconstruction and floor designs have beendetailed then an exact or specific designdistribution can be ascertained.

The Electrical Power entry is based on thisprojection.

Page 14: Commercial Building Binder - UNDP

LED 30 LED 30 LED 30 LED 30

LED 30 LED 30 LED 30 LED 30 LED 30 LED 30 LED 30

LED 30

ROOF ELECTRICAL INSTALLATION PLAN(LIGHTING)Scale: 1/16"=1'-0"

2 Storey wing roof plan

PC

PC

PC

ALL RIGHTS RESERVED.

Page 15: Commercial Building Binder - UNDP

GROUND FLOOR PLANScale: 1/16"=1'-0"

Ground floor 4 storey wing

Main Entrance intoGround floor 2storey wing

Emergency Exit

Emergency Exit

Emergency stairs

Emergency stairs

Toilet Blocks

Elevator &Stairs Shaft

Entrance Plaza

Main Entrance intoGround floor 4storey wing

SD SD SD SD

SD SD SD SD

SD SD SD SD SD SD

SD SD

SDSD

SD

PS

PS

PS

ALARM ALARM GBD

GBD

S.D.

P.S.

D.E.D.

ALARM

G.B.D.

SMOKE DETECTORS

PULL STATION

DOOR ENTRY DETECTOR

ALARMS

GLASS BREAK DETECTOR

NOTE:

FIRE ALARM SYSTEM TO INCLUDE: - MAIN FIRE CONTROL PANEL WITHPROVISION FOR TEN ZONES INCLUDINGSECURITY ALARMS. - BREAK GLASS STATIONS, PULL PORTSTATIONS - FIRE ALARM SENSORS - FIRE ALARM STROBES - SMOKE DETECTORS - FIRE ALARM CABLES - FIRE EXTINGUISHERS

SD

SD

ALL RIGHTS RESERVED.

Page 16: Commercial Building Binder - UNDP

FIRST FLOOR PLANScale: 1/16"=1'-0"

SD SD SD SD

SD SD SD SD

SD SD SD SD SD SD

SD SD

SDSDSD

PS

S.D.

P.S.

D.E.D.

ALARM

G.B.D.

SMOKE DETECTORS

PULL STATION

DOOR ENTRY DETECTOR

ALARMS

GLASS BREAK DETECTOR

NOTE:

FIRE ALARM SYSTEM TO INCLUDE: - MAIN FIRE CONTROL PANEL WITHPROVISION FOR TEN ZONES INCLUDINGSECURITY ALARMS. - BREAK GLASS STATIONS, PULL PORTSTATIONS - FIRE ALARM SENSORS - FIRE ALARM STROBES - SMOKE DETECTORS - FIRE ALARM CABLES - FIRE EXTINGUISHERS

PS

PS

ALARM ALARM GBD

GBD

First floor 4 storey wing

First floor 2 storey wing

Emergency stairs

Emergency stairs

Toilet Blocks

Elevator &Stairs Shaft

SD

SD

ALL RIGHTS RESERVED.

Page 17: Commercial Building Binder - UNDP

SECOND FLOOR INSTALLATION PLAN(FIRE ALARM SYSTEM)Scale: 1/16"=1'-0"

SD SD SD SD

SD SD SD SD

SD SD SD SD SD SD

PS

PS

ALARM ALARM GBD

Emergency stairs

Toilet Blocks

Elevator &Stairs Shaft

S.D.

P.S.

D.E.D.

ALARM

G.B.D.

SMOKE DETECTORS

PULL STATION

DOOR ENTRY DETECTOR

ALARMS

GLASS BREAK DETECTOR

NOTE:

FIRE ALARM SYSTEM TO INCLUDE: - MAIN FIRE CONTROL PANEL WITHPROVISION FOR TEN ZONES INCLUDINGSECURITY ALARMS. - BREAK GLASS STATIONS, PULL PORTSTATIONS - FIRE ALARM SENSORS - FIRE ALARM STROBES - SMOKE DETECTORS - FIRE ALARM CABLES - FIRE EXTINGUISHERS

2 Storey wing roof plan

SD

SD

Second floor 4 storey wing

13ALL RIGHTS RESERVED.

Page 18: Commercial Building Binder - UNDP

THIRD FLOOR INSTALLATION PLAN(FIRE ALARM SYSTEM)Scale: 1/16"=1'-0"

Emergency stairs

Toilet Blocks

Elevator &Stairs Shaft

SD SD SD SD

SD SD SD SD

SD SD SD SD SD SD

PS

PS

ALARM ALARM GBD

S.D.

P.S.

D.E.D.

ALARM

G.B.D.

SMOKE DETECTORS

PULL STATION

DOOR ENTRY DETECTOR

ALARMS

GLASS BREAK DETECTOR

NOTE:

FIRE ALARM SYSTEM TO INCLUDE: - MAIN FIRE CONTROL PANEL WITHPROVISION FOR TEN ZONES INCLUDINGSECURITY ALARMS. - BREAK GLASS STATIONS, PULL PORTSTATIONS - FIRE ALARM SENSORS - FIRE ALARM STROBES - SMOKE DETECTORS - FIRE ALARM CABLES - FIRE EXTINGUISHERS

2 Storey wing roof plan

SD

SD

Third floor 4 storey wing

ALL RIGHTS RESERVED.