color of water - pb heat...water flow carries the heat from the boiler to the radiation. if we know...

30

Upload: others

Post on 31-Jan-2021

0 views

Category:

Documents


0 download

TRANSCRIPT

  • Gerry 2015 MacBookColor of Water

  • Choosing the Right BoilerQuestions to be asked before choosing the boiler:

    Good for cast iron:What is the heat load of the building?

    What is the heat capacity of the connected radiation?

    Is it more or less than than the building heat load?

    What is the radiation made up of: baseboard, cast iron radiators, air handlers?

    Is it a steam or hot water boiler?

    Good for modcon:

    Depends…

  • Proper Boiler SizingEvery contractor worries about undersizing, but few give a thought to oversizing…

    Is bigger always better?

    If the boiler’s too small, my customer will be cold and unhappy

    at the worst possible time. The boiler will run without stopping.

    If the boiler’s too big, what’s the worst that can happen?

    Nobody ever complains they are too warm, right?

    Boiler Short-Cycling

    Higher fuel usage

    Boiler stops working at the worst possible time

    Reduced component lifetime/Boiler needs parts all the time

    Boiler fails after a few years and must be replaced

  • Cast Iron vs ModCon BoilersWhich one is more likely to short-cycle? ModCon boilers are smaller and can down-fire to a fraction of the full input. Shouldn’t that help? Maybe. Or not…

    + Cast iron boilers have (6x) more water and more mass to absorb heat at start up.

    - They have only one level of heat input – full.+ They cool down more slowly.

    Causes of Boiler Short-Cycling

    Boiler btu input is much higher than the heat loss of the building.

    Water flow through the boiler is restricted by pipe design, pipe

    size or lack of circulator capacity.

    Many small heating zones

    + ModCon boilers control btu input from high-fire through low-fire as the water

    temperature gets near the target.

    - They heat up and cool down quickly.

  • Radiators & Other Heat EmittersModern hydronic systems can have many types of radiation to provide heat throughout

    a structure, including baseboard, convectors, radiators, hydro air coils, radiant, etc.

    Heat emitters receive heat from the hot water circulating through the piping and deliver heat to the areas where they are installed. 150-180˚

    150-180˚

    120-160˚

  • DOs AND DON’Ts OF SIZING REPLACEMENT BOILERS

    For Steam

    Do size according to the installed radiation load. Be sure to make appropriate allowance for additional piping and pick-up.

    Don’t size based on a heat loss.

    Use the existing boiler size and firing rate as a guide and/or cross-reference only.

    For Hot Water

    Do size based on a heat loss if the system is copper baseboard. OK to size a copper baseboard system based on the lineal footage of installed radiation.

    Do size according to the installed radiation load if the system is cast iron radiation. Be sure to make appropriate allowances for additional piping and pick-up.

    Use the existing boiler size and firing rate as a guide and/or cross-reference only.

    TECHNICAL TIDBITS

    Piping and pick-up factors for I = B = R Rated Boilers: Hot Water = 1.15 Steam = 1.33

    1 Boiler Horsepower = 33,475 BTUH

    1 Lb. Steam (212°F) = 970.3 BTU

    1 Sq. Ft. of Steam = 240 BTUH

    1 Sq. Ft. of Water = See Table Below

    HEAT EMISSION BASED ON ROOM TEMPERATURE OF 70°F

    Avg water temp in radiation… 150 160 170 180 190 200 210 215 Heat emission BTUH/sq. ft… 110 130 150 170 190 210 230 240

  • IfyouareintheTrade,it’seasytogetaUserName&Passwordatpeerlessboilers.com:1.Fromhomepageclick“register”2.FillinUSERREGISTRATION(youselectyourownUserName&Password)3.EntertheSecurityCode,thenclick“Register”

    NextPage….

    1

    23

  • YouwillreceiveconfirmationwithinabusinessdaythatyourUserNameandPasswordareactive.Thenyoucansignintoview:

  • Room Name§ Feet of Copper

    Baseboard ElementNumber of

    CI Radiators# of Tubes or Columns

    Number of Sections

    Cast Iron Height

    Cast Iron Width

    Feet of CI Baseboard

    EDR*/Section or /Foot from Chart Total

    12345678910111213141516171819202122232425

    = Total Feet of Copper BB Element TOTAL EDR == Element x 600 BTUH§ (@180˚) EDR x 150 BTUH† (@170˚) =

    §Water temperature other than 170˚ see capacity chart † For water temperature other than 170˚, see EDR Output Chart

    *EDR = Square feet of Equivalent Direct Radiation

    (Enter #T for Tubes or #C for Columns)

    RadiationMeasuringSheet

  • Room by Room Calculation

  • Block Calculation

  • Peerless Heat Load Quick Enter Sheet.xls

    f Peerless Heat Load Quick Enter SheetDATE

    JOB NAME

    WHOLESALER __________________________ CONTRACTOR ft ft ft ft sq ft sq ft sq ft sq ft sq ft sq ft ft sq ft sq ft sq ft

    # Room Name Room Room Exp. Ceil North East / South Skylight SE / SW Floor Floor Exposed Standard Patio Loss GainLength Width Wall Height Window West Area Edge Ceiling Doors Doors BTUH BTUH

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    18

    19

    20

    Construction & Insulation Factors ("R" Value / Inches of Insulation) {0"=R3, 2"=R7, 3.5"=R12, 6"=R20, 9"=R30, 12"=R40}Circle below all factors that apply: Glazing

    ** Exposed Wall 0" / 2" / 3.5" / 6" ** Glass Door sgl/dbl **Cold Floor Perimeter 1" / 2" Heating Temp. ( O F Outside) ** ** Ceiling 0" / 3.5" / 6" / 9" / 12" ** Skylight sgl/dbl ** Standard Doors Y / N Cooling Temp. ( O F Outside) **

    ** Cold Floor Area 0" / 3.5" / 6" / 9" / 12" ** Glass sgl/dbl _______ Air Change / Hour .5 / 1.0

    All Areas with ** are needed in order to complete load calculation

  • PEERLESS® BOILER – Basic Hydronics

    Water enters through the eye.Vanes “slap” the water – adding velocity.Discharge side turns velocity to pressure.

    It uses centrifugal force.

    How Do Circulators Work?

    The wider the impeller, the more flow.The larger the diameter or pitch, the more velocity & pressure.Increase the speed - more flow and pressure.

    It’s a “circulator” not just a pump.It creates pressure differential.

    Pressure differential creates flow.Enough pressure differential

    = enough flow.

    44

  • PEERLESS® BOILER – Basic Hydronics

    Sizing Circulators – What is Feet of Head?

    1 PSI = 2.31’ head pressure

    12 PSI 2.31’ = 27.72’

    Keep radiation pressurized

    on upper levels

    Static head (from PRV): Pressure needed to fill system to highest point, typically 12 PSIFriction head: Pressure needed to overcome friction loss in piping

    Pump head: Amount of pressure the pump can produce (PSI 2.31)

    vs

    Atmospheric Pressure

    100’

    43.3 psi

    pos pr

    neg pr

    47

  • Number'of'Baths

    Number'of'Bedrooms

    Wired'for'Priority

    Wired'for'Non5Priority

    2 5,100 10,4001'5'1½

    3 5,100 10,400

    2 5,100 10,400

    3 6,100 13,0002'5'2½

    4 7,000 14,300

    5 10,400 20,500

    3 7,000 14,300

    4 8,200 17,3003'5'3½

    5 10,400 20,500

    6 11,000 21,500

    Add'to'Heat'Load

    Sizing'Additional'Boiler'Load'for'DHW

  • PEERLESS® BOILER – Basic Hydronics

    Water flow carries the heat from the boiler to the radiation. If we know how many btus of heat are needed, we can convert them into gpm using the universal hydronics formula.

    gpm = btuh/(∆T x 500)

    Sizing Circulators - Flow Needed

    Formula

    Btu (British Thermal Unit) = heat required to raise 1 pound of water by 1 degree Fahrenheit

    Btuh = btus created or used per hour

    ∆T = change in temperature

    1 gallon of water = 8.31 pounds

    60 minutes (as in gpm) = 1 hour (as in btuh)

    Convert pounds and minutes to gallons and hours8.31 x 60 = 498.6 (round to 500)

    BTUH / ∆T x 500

    Example

    180˚ - 160˚ = 20˚ ∆T (typical for heating systems)

    Using formula:

    63,000/(20 x 500) = ? gpm

    63,000/10,000 = 6.3 gpm

    To calculate flow for a zone circulator, calculate how many mbh the zone

    requires and divide by 10,000.

    46

  • PEERLESS® BOILER – Basic Hydronics

    For residential cast iron boilers with zone valves, measure the length of only the longest run.The circulator has to overcome the resistance in that run. The shorter runs are easier.

    In our example all the runs have the same length.

    Sizing Circulators – Feet of Head Restriction

    To convert measured length of longest run to feet of head:

    Multiply measured length x 1.5 (factor to account for all the fittings)

    Multiply that number x .04

    Example:90 ft x 1.5 = 135

    135 x .04 = 5.4

    Or

    90 x .06 = 5.4

    Measured length =

    90 ft

    50

  • PEERLESS® BOILER – Basic Hydronics

    Our sample heat loss was 63 mbh, which would make the MI85-04 a good choice.

    6.7 gpm is required. Our longest run of 90 feet requires 5.4 feet of head.

    The Taco pump curves show that a model 007 has more than enough capacity.

    Sizing Circulators –Cast Iron Boiler Example

    X

    51

  • PEERLESS® BOILER – Basic Hydronics

    Sizing Circulators – Modcon Boiler Example

    The PF210 requires more flow and head capacity than standard Taco 00 series provides even with a 25˚ ∆T.

    Taco model 2420 is a good match for the PF210.

    X

    XX

    53

  • PEERLESS® BOILER – Basic Hydronics

    Maximum Btus for Pipe SizeUsing 20˚ ∆T from the universal hydronics formula, the

    two tables below show the maximum water floe and maximum btu capacity for each size steel or copper pipe.

    Example for boiler piping on PF210:

    PF210 heating capacity = 195 mbh = 19.5 gpm

    From the tables – 1¼” pipe is too small at 16 gpm max

    1½” pipe has enough capacity at 25 gpm max

    The boiler loop on the PF210 should be piped with 1½"

    57