code citations – how to find · copyright 1999-2015 dan dudley 250.53(a)(2) (2) supplemental...

77
Copyright 1999-2015 Dan Dudley Code Citations – how to find 110.14(C)(1)(a) Chapter (1) Article (110) Section (14) Subsection (C) Subsection (1) under (C) Subsection (a) under (1) T.220.55 Table 8/29/2016 Copyright 2016 Dan Dudley & Associates Page 1

Upload: doancong

Post on 13-Aug-2019

213 views

Category:

Documents


0 download

TRANSCRIPT

Copyright 1999-2015 Dan Dudley

Code Citations – how to find110.14(C)(1)(a)

Chapter (1)Article (110)

Section (14)

Subsection (C)

Subsection (1) under (C)

Subsection (a) under (1)

T.220.55

Table

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 1

Copyright 1999-2015 Dan Dudley

Two of 198 code violations in a 1999 5mil school gym

Condensatedrain andwater on

floor

314.25Covers to be on

all finishedboxes

110.12(A)Openings to be

closed 110.3(A)(8)Safeguarding of

persons

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 2

Copyright 1999-2015 Dan Dudley

More violations314.23Independent

support for boxes

314.25Covers to be

on all finishedboxes

110.12(A)Openings to be

closed

314.29Boxes to beaccessible

A/C Ductwork isnot an approved

support for conduit

358.30Fastening of

conduit

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 3

Copyright 1999-2015 Dan Dudley

300.11Ceiling support

wires not allowedas conduit support

300.11Support wires

must be securedat both ends and

identified asconduit supportwires separatefrom the ceiliggrid support

wires

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 4

Copyright 1999-2015 Dan Dudley

EMT358.30(A)

Support within3 ft. of box is

required

Ceiling tiles arenot approvedfor conduit

support

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 5

Copyright 1999-2015 Dan Dudley

#9ceiling support

wire is notapproved for

conduit support

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 6

Copyright 1999-2015 Dan Dudley

#9ceiling support

wire is notapproved for

conduit support

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 7

Copyright 1999-2015 Dan Dudley

358.30(b)EMT SUPPORTrequired within

3ft oftermination

Box needs to besupported

independentlysince EMT is not

approved forsupport

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 8

Copyright 1999-2015 Dan Dudley

The BUMPER onyour truck is notapproved as aconduit bender

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 9

Copyright 1999-2015 Dan Dudley

Plumbers strapis not approvedfor BONDING

Conduitrequires

support otherthan connector

to box orenclosure

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 10

Copyright 1999-2015 Dan Dudley

More dangerous violations

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 11

Copyright 1999-2015 Dan Dudley

Factoryends leftHOT andexposed

277 Volts onyellow and

orange leads

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 12

Copyright 1999-2015 Dan Dudley

Clearance… WhatClearance ???

110.26(F)(2)

No Less than 3 ftof working

clearance in frontof the equipment.

ArchitecturalBarrier is illegally

located in the“Dedicated

Equipment Space”

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 13

Copyright 1999-2015 Dan Dudley

Framing member isa permanent

support

Terminationlocation is through

front panel

110.26(F)(2)

No Less than 3 ftof working

clearance in frontof the equipment.

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 14

Copyright 1999-2015 Dan Dudley

Not a GroundedReceptacle

Not GFCI protected

Enclosure notlisted and/or

labeled for the use

Receptacle notmounted properly

ImproperConductorEntrance

Conductor notproperly secured

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 15

Copyright 1999-2015 Dan DudleyPlumbing Elbows ??

Plumbing pipe andfittings are notapproved as araceway forconductors.

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 16

Copyright 1999-2015 Dan Dudley

What the heck,they won’t everneed to use thatfire escape ??!!

225.7(C)“…Not less than 3ft from windows,

platforms, fireescapes and the

like…”

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 17

Copyright 1999-2015 Dan Dudley

This truck won’t ever be moved ??

PortableServce

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 18

Copyright 1999-2015 Dan Dudley

Individual InsulatedConductors are onlyallowed in Dwellings

if they are in aRaceway.

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 19

Copyright 1999-2015 Dan Dudley

Exam – vs – Field Experience

• The following slides are information asked on over 90% of the variouselectrical exams across the U.S.

• Jobs electricians perform everyday with the test related questionsand key information points

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 20

Copyright 1999-2015 Dan Dudley

Door must open90 degrees

Four things usually asked:

Headroom 6 1/2ft

Space in front 3ft

Working clearance ≥ 30in

Door open ≥ 90 degrees

≥ = “not less than”

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 21

Copyright 1999-2015 Dan Dudley

Article 110.26(A)(2), (3), (E)

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 22

Copyright 1999-2015 Dan Dudley

Different System Grounded Conductors

NEC Section 200.6(A) & (B)

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 23

Copyright 1999-2015 Dan Dudley

Multiwire Circuits – More than one Voltage System

NEC Section 210.5 (C)(3)

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 24

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 25

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 26

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 27

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 28

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 29

Copyright 1999-2015 Dan Dudley

250.53(A)(3)

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 30

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 31

Copyright 1999-2015 Dan Dudley

250.53(A)(2)

(2) Supplemental Electrode Required. A single rod, pipe,or plate electrode shall be supplemented by an additionalelectrode of a type specified in 250.52(A)(2) through(A)(8). The supplemental electrode shall be permitted to bebonded to one of the following:(1) Rod, pipe, or plate electrode(2) Grounding electrode conductor(3) Grounded service-entrance conductor(4) Nonflexible grounded service raceway(5) Any grounded service enclosure

Exception: If a single rod, pipe, or plate grounding electrodehas a resistance to earth of 25 ohms or less, thesupplemental electrode shall not be required.

(3) Supplemental Electrode. If multiple rod, pipe, or plateelectrodes are installed to meet the requirements of thissection, they shall not be less than 1.8 m (6 ft) apart.

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 32

Copyright 1999-2015 Dan Dudley

250.52(3)

“UFER” orConcreteEncasedElectrode

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 33

Copyright 1999-2015 Dan Dudley

250.53(G)

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 34

Copyright 1999-2015 Dan Dudley

250.52(B)(2)

250.52(A)(5)

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 35

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 36

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 37

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 38

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 39

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 40

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 41

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 42

Copyright 1999-2015 Dan Dudley

250.66(A)

•Connections to Rod, Pipe, or Plate Electrodes.Where the grounding electrode conductor isconnected to rod, pipe, or plate electrodes aspermitted in 250.52(A)(5) or (A)(7), that portionof the conductor that is the sole connection tothe grounding electrode shall not be requiredto be larger than 6 AWG copper wire or 4AWG aluminum wire.

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 43

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 44

Copyright 1999-2015 Dan Dudley

Not enoughsurface area incontact to carry

fault current

250.92(B)

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 45

Copyright 1999-2015 Dan Dudley

Various methodsof bonding

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 46

Copyright 1999-2015 Dan Dudley

Service Bonding

Article 250.92(A) & (B)

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 47

Copyright 1999-2015 Dan Dudley

Zinc Plated – Pan Headself tapping screws arenot listed for grounding

250.8(A)

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 48

Copyright 1999-2015 Dan Dudley

General Wiring MethodsNEC 518.4(A)

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 49

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 50

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 51

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 52

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 53

Copyright 1999-2015 Dan Dudley

Article 300.14

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 54

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 55

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 56

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 57

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 58

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 59

Copyright 1999-2015 Dan Dudley

2014 NEC change: Max number ofreceptacles on branch circuits otherthan general lighting and outlet circuits

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 60

Copyright 1999-2015 Dan Dudley

Number of Circuits Commercial Buildings

Article 220.18

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 61

Copyright 1999-2015 Dan DudleyNote use of 60°C ampacity of #6 THHN

210.20(a)

60 A Protection Device

#6 AWG THHN Cu

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 62

Copyright 1999-2015 Dan Dudley

30 amp single itemcircuit =80%

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 63

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 64

Copyright 1999-2015 Dan DudleyArticle 210.12(b)

All 120-volt, singlephase, 15- and 20-

ampere branchcircuits supplyingoutlets installed indwelling unit family

rooms, dining rooms,living rooms, parlors,

libraries, dens,bedrooms, sunrooms,

recreation rooms,closets, hallways, or

similar rooms orareas shall be

protected by a listedarc-fault circuit

interrupter,combination-type,installed to provideprotection of thebranch circuit.

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 65

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 66

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 67

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 68

Copyright 1999-2015 Dan Dudley

230.9

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 69

Copyright 1999-2015 Dan Dudley

230.24(A)

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 70

Copyright 1999-2015 Dan Dudley

230.24(A)Exceptions1,2 and 3

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 71

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 72

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 73

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 74

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 75

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 76

Copyright 1999-2015 Dan Dudley

8/29/2016 Copyright 2016 Dan Dudley & Associates Page 77