co2 sensor - renewaire...co2 com pwr n.o. relay co2-w or co2-d control 2 the normally open contacts...
TRANSCRIPT
EV-Series HE-Series LE-Series SL-Series
CO2 SensorSupplemental Wiring Manual for Accessories
CO2-DCO2-W
1.800.627.44992
CO2 SensorACCESSORY
Figure 3.1.0 Wiring Schematic for EV90, EV90P, EV130, EV200, EV240, EV300 Units Only ................... 4Figure 3.1.1 Wiring Schematic for EV450, HE1Xin, and HE1.5IN Units without ECM ............................... 4Figure 3.1.2 Wiring Schematic for HE1XRT, HE1.5RT, LE-Series, and all HE2X and Larger Units without VFDs or EC Motors ............................................................................................................................. 5Figure 3.1.3 Wiring Schematic for HE- and LE-Series Units with Factory-Installed VFDs ....................... 5Figure 3.1.4 Wiring Schematic for EV450 Units with ECM ..................................................................... 6Figure 3.1.5 Wiring Schematic for HE1XIN and HE1.5IN Units with ECM ................................................ 6Figure 3.1.6 Wiring Schematic for SL-Series Units ............................................................................... 7
TABLE OF ILLUSTRATIONS
1.0 OVERVIEW 3
1.1 DESIGN CRITERIA .................................................................................................... 3
2.0 DIMENSIONS 3
2.1 GENERAL INSTALLATION .......................................................................................... 3
3.0 ELECTRICAL 4
3.1 WIRING SCHEMATICS............................................................................................... 4
4.0 FACTORY ASSISTANCE 7
31.800.627.4499
CO2 Sensor ACCESSORY
1.0 OVERVIEWThe CO2 monitor uses a highly accurate and reliable Non-dispersive Infrared (NDIR) with state-of-the-art digital linearization and temperature compensated circuitry to detect CO2 levels in an attractive, low profile enclosure for room applications and a duct mount version provide a linear analog signal output of 4-20 mA, 0-5 or 0-10 VDC and a Normally Open (N.O.) relay to control an alarm or ventilation fan in various ways. 2.0 DIMENSIONS2.1 CO2-W
2.2 CO2-D
7.0"
1.15"3.3"
2.5"
Conduit/EMT ConnectionØ 0.875"
Mounting Holes
(X4) Ø 0.200"
1"
4.7"
2.3"
3.25"
5.7"
4.5"
4" 3.5"
This was created from Greystone brochure KMC JUL19
7.0"
1.15"3.3"
2.5"
Conduit/EMT ConnectionØ 0.875"
Mounting Holes
(X4) Ø 0.200"
1"
4.7"
2.3"
3.25"
5.7"
4.5"
4" 3.5"
This was created from Greystone brochure KMC JUL19
7.0"
1.15"3.3"
2.5"
Conduit/EMT ConnectionØ 0.875"
Mounting Holes
(X4) Ø 0.200"
1"
4.7"
2.3"
3.25"
5.7"
4.5"
4" 3.5"
This was created from Greystone brochure KMC JUL19
1.800.627.44994
CO2 SensorACCESSORY
CO2-W or CO2-D Control connected to RenewAire EV-series residential ERV.
The Normally Open contacts of one or more additional Low Voltage Controls may be connected to ERV unit in parallel with the CO2-W or CO2-D.
This schematic applies to EV90, EV90P, EV130, EV200, EV240, EV300 models only.
Control Terminals
Unit Internal Wiring
24VAC Class II Power Supply provided by other
Volt
mA
LCDROLL
SAVE
MENU
CO2
COM
PWR
N.O.Relay
ERV INTERNAL CONTROL WIRING
CO2-W or CO2-D CONTROL
1
CO2-W or CO2-D Control connected to RenewAire HE-1XIN, HE1.5IN, EV450 ERVs without ECM Motors.
This schematic applies to EV450 models (excepting units with EC motors) and HE1X, HE1.5 indoor models (excepting units with EC motors).
Unit's 24VAC Power Supply
ERV INTERNAL CONTROL
C Isolation Relay Coil
WIRING (SIMPLIFIED)
BLUE
YEL
YEL
RED
Volt
mA
LCDROLL
SAVE
MENU
CO2
COM
PWR
N.O.Relay
CO2-W or CO2-D CONTROL
2
The Normally Open contacts of one or more additional Low Voltage Controls may be connected to ERV unit in parallel with the CO2-W or CO2-D.
3.0 ELECTRICAL 3.1 WIRING SCHEMATICS
FIGURE 3.1.0 WIRING SCHEMATIC FOR EV90, EV90P, EV130, EV200, EV240, EV300 UNITS ONLY
FIGURE 3.1.1 WIRING SCHEMATIC FOR EV450, HE1XIN, AND HE1.5IN UNITS WITHOUT ECM
51.800.627.4499
CO2 Sensor ACCESSORY
CO2-W or CO2-D Control connected to RenewAire HE- and LE-series commercial ERV with terminal strip connections for controls.
This schematic applies to HE1XRT, HE1.5RT (outdoor) models, LE models, and all HE2X and larger models without VFDs or ECM motors.
Unit's 24VAC Power Supply
ERV INTERNAL CONTROL
C Isolation Relay Coil
WIRING (SIMPLIFIED)
12345
Volt
mA
LCDROLL
SAVE
MENU
CO2
COM
PWR
N.O.Relay
CO2-W or CO2-D CONTROL
3
The Normally Open contacts of one or more additional Low Voltage Controls may be connected to ERV unit in parallel with the CO2-W or CO2-D.
9 10 11 12 15
8
7
6
5
4
3
2
1
AGND
A01
AGND
AI2
10V
AGND
AI1
SCR
VFD
(EA)
Signal cable shield (screen)
Frequency Input (set to 4-20mA)
Frequency Input Common (ground)
AI1 AI2
For 4-20mA input, place Jumper AI1 at TOP.
9 10 11 12 15
8
7
6
5
4
3
2
1
AGND
A01
AGND
AI2
10V
AGND
AI1
SCR
VFD
(FA)
Signal cable shield (screen)
Frequency Input (set for 0-10vdc)
Frequency Input Common (ground)
Install jumper between 9 & 12 for constant operation.
AI1 AI2
For 0-10vdc input, place Jumper AI1 at BOTTOM.
Install jumper between 9 & 12 for constant operation.
1
2
3
4
5
On-board 24VAC Power supplied by ERV
Volt
mA
LCDROLL
SAVE
MENU
CO2
COM
PWR
N.O.Relay
Frequency Output (4-20mA)
Frequency Output Common (ground)CO2-W or CO2-D CONTROL
CO2-W or CO2-D Control connected to RenewAire HE- and LE-series commercial ERV with factory-installed Variable Frequency Drives.
4FIGURE 3.1.2 WIRING SCHEMATIC FOR HE1XRT, HE1.5RT, LE-SERIES, AND ALL HE2X AND LARGER UNITS WITHOUT VFDS OR EC MOTORS
FIGURE 3.1.3 WIRING SCHEMATIC FOR HE- AND LE-SERIES UNITS WITH FACTORY-INSTALLED VFDS
1.800.627.44996
CO2 SensorACCESSORY
1
2
3
4
5
On-board 24VAC Power
EXAMPLE ONLY: See also ECM MOTOR MANUAL SUPPLEMENT
In this example, ERV runs constantly at low Speed 1.During occupancy, ERV runs at higher, variable Speed 2.
JUMPER FOR CONSTANT ON.SPEED 1 SET BY RESISTORS.TIME CLOCK ACTIVATES SPEED 2.CO2 CONTROLLER SETS SPEED 2.
6
7
8
9
10
Master ON/OFF Relay
Analog Signal IN
C HIGH/LOW Relay
To Motor ControllerFactory-installed Resisters between terminals 5, 7 & 9 determine SPEED 1
1
2
3
4
5
TIME CLOCK
FIELD-INSTALLED TIME CLOCK ACTIVATES SPEED 2 Analog Signal REFERENCE
Analog Signal GROUND
TC7D-W/E
DISCONNECT FACTORY-INSTALLED POTENTIOMETER FROM TERMINALS 6, 8 & 9.
C
FIELD-INSTALLED JUMPER
FACTORY WIRING
Volt
mA
LCDROLL
SAVE
MENU
CO2
COM
PWR
N.O.Relay
FIELD-INSTALLED CO2 CONTROLLER SETS SPEED 2
CO2-W or CO2-D CONTROL
CO2-W or CO2-D Control connected to RenewAire EV-450 ERV with ECM motor.5
Connect the analog signal grounds.
SPEED 2 SIGNAL
1
2
3
4
5
On-board 24VAC Power
6
7
8
Analog Signal IN FAN 1
To EA Motor Controller FAN 1
Analog Signal REFERENCE FAN 1
Analog Signal GROUND FAN 1
1
2
3
4
5
6
7
8
Analog Signal IN FAN 2
To FA Motor Controller FAN 2
Analog Signal REFERENCE FAN 2
Analog Signal GROUND FAN 2
Factory-installed jumpers passes "ON" and "MODE" signals to Fan 2
EA
FA
REMOVE FACTORY-INSTALLED RESISTORS, DISCONNECT POTENTIOMETERS.
CMaster ON/OFF Relay FAN 1
CSPEED 2 Relay FAN 1
CMaster ON/OFF Relay FAN 2
CSPEED 2 Relay FAN 2
FACTORY WIRING
Volt
mA
LCDROLL
SAVE
MENU
CO2
COM
PWR
N.O.Relay
SPEED 1 SIGNAL
CO2-W or CO2-D CONTROL
EXAMPLE ONLY: See also ECM MOTOR MANUAL SUPPLEMENT
In this example, CO2 Controller turns ERV on at Speed 1 when CO2 level exceeds Controller Relay setting.
CO2 Controller Analog output sets Speed 1.
CO2-W or CO2-D Control connected to RenewAire HE-1XIN, HE1.5IN ERV with ECM motors.6
Connect the analog signal grounds.
FIGURE 3.1.4 WIRING SCHEMATIC FOR EV450 UNITS WITH ECM
FIGURE 3.1.5 WIRING SCHEMATIC FOR HE1XIN AND HE1.5IN UNITS WITH ECM
71.800.627.4499
CO2 Sensor ACCESSORY
INSTALLATION
CO2-W or CO2-D Control connected to RenewAire SL series.
Volt
mA
LCDROLL
SAVE
MENU
CO2
COM
PWR
N.O.Relay
CO2-W or CO2-D CONTROL
7
The Normally Open contacts of one or more additional Low Voltage Controls may be connected to ERV unit in parallel with the CO2-W or CO2-D.
24 VAC
SL70 EXTERNAL CONNECTION
COMM
HIGH OR LOW SPEED INPUT
This schematic applies to SL70 models.
FIGURE 3.1.6 WIRING SCHEMATIC FOR SL-SERIES UNITS
In the unlikely event that you need assistance from the factory for a specific issue, make sure that you have the information called for in the Unit Records page in the Owner Information section of this manual. The person you speak with at the factory will need that information to properly identify the unit and the installed options.
To contact RenewAire Customer Service:
Call 800-627-4499
Email: [email protected]
4.0 FACTORY ASSISTANCE
About RenewAireFor over 30 years, RenewAire has been a pioneer in enhancing indoor air quality (IAQ) in commercial and residential buildings of every size.This is achieved while maximizing sustainability through our fifth-generation, static-plate, enthalpic-core Energy Recovery Ventilators (ERVs) that optimize energy efficiency, lower capital costs via load reduction and decrease operational expenses by minimizing equipment needs, resulting in significant energy savings. Our ERVs are competitively priced, simple to install, easy to use and maintain and have a quick payback. They also enjoy the industry’s best warranty with the lowest claims due to long-term reliability derived from innovative design practices, expert workmanship and Quick Response Manufacturing (QRM).
As the pioneer of static-plate core technology in North America, RenewAire is the largest ERV producer in the USA. We’re committed to sustainable manufacturing and lessening our environmental footprint, and to that end our Waunakee, WI plant is 100% powered by wind turbines. The facility is also one of the few buildings worldwide to be LEED and Green Globes certified, as well as having achieved ENERGY STAR Building status. In 2010, RenewAire joined the Soler & Palau (S&P) Ventilation Group in order to provide direct access to the latest in energy-efficient air-moving technologies. For more information, visit: renewaire.com
Member of the S&P Group Family of Brands
2019 © RenewAire LLC138201_006_JUL19
201 Raemisch Road | Waunakee, WI | 53597 | 800.627.4499 | RenewAire.com