co-generation power plant
TRANSCRIPT
-
8/9/2019 Co-generation Power Plant.
1/43
CONTENTS
CHAPTER.1
COGENERATION
1. Cogeneration - 1
2. Introduction - 1
3. Choice of site - 2
CHAPTER.2
MAIN REQUIREMENTS - 3
1. Fuel - 4
2. Feed water - 4
3. Water treatment plant - 4
4. Boiler - 4
5. Boiler furnace - 6
6. Super heater - 7
7. Economiser - 8
8. Air preheater & types - 9
9. Condenser - 11
10. Turbines - 16
11. Alternators - 17
11.1. Introduction - 17
11.2. Operating principle - 17
11.3. Classification - 17
11.4. Types of alternators - 18
11.5. Construction - 19
-
8/9/2019 Co-generation Power Plant.
2/43
11.6. Types of rotor - 19
11.7. Classification based on the prime mover - 20
12. Transformers
12.1. Single phase transformers - 21
12.2. Construction - 21
12.3. Three phase transformers - 22
12.4. Three phase connections - 25
12.4.1. - Connection -25
12.4.2. Y- connection - 26
12.5. Instrument transformers - 26
12.5.1. Current transformers
12.5.2. Potential transformers
12.6. Losses in transformers - 27
12.7. Cooling methods - 28
13. VFD - 29
14. ESP - 30
CHAPTER.3
SCHEMATIC ARRANGEMENT OF PLANT - 30-34
CONCLUSION
BIBLIOGRAPHY
-
8/9/2019 Co-generation Power Plant.
3/43
-
8/9/2019 Co-generation Power Plant.
4/43
-
8/9/2019 Co-generation Power Plant.
5/43
CHOICE OF SITE FOR CO-GENERATION PLANT:
1. Supply of fuel: Bagasse is available from sugar factory. So such a plant isto be installed in or near sugar factory.
2. Availability of water: A huge amount of water is required for thecondenser; therefore, such a plant should be located atthe bank of a river
or near the canal or bore wells to ensure continuous supply of water.
3. Transport facilities: A co-generation plant often requires thetransportation of sugarcane and machinery.
4. Nearness to load centers: In order to reduce the transmission cost theplant should be located near the centre of the load. In thecase of A.Csupply system the transformation of energy from lower voltage to higher
voltage and vice versa is possible.
5. Distance from populated area: Due to air pollution it has to beconstructed far away from the population.
6. Land requirement: The land is required not only for setting of the plant but for other purposes such as staff colony, disposal of ash or fuel
storage. Land should be also available for future extensions
7. Ash disposal: Ash is the main waste product of the steam power plant.The ash may be purchased by building contractors, or it can be used for
brick making near plant site. The site is nearer to river or sea or lay ash
can be dumped into it. If the waste land is available near the site then thearea of 40 hectares excavated to a depth of 6.5 meters will be required
per year for a 2000 MW plant.
8. Labour supplies : Skilled and unskilled labours must be available atreasonable rates near the site of the plant
9. Type of the land: Land should be available such that it has good bearingcapacity to with stand not only the dead load of the plant but also the
forces transmitted to the foundation due to the operation of the plant and
this total land may amount to about 7kg/cm more over the land should bereasonably level and not low lying.
-
8/9/2019 Co-generation Power Plant.
6/43
2.
-
8/9/2019 Co-generation Power Plant.
7/43
MAIN REQUIREMENTS
FUEL
FEED WATER PLANT
BOILER
SUPER HEATER
ECONOMIZER
AIRPREHEATER
CONDENSER
COOLING TOWER
INDUCED DRAUGHT FAN
FORCED DRAUGHT FAN
CHIMNEY
TURBINES
REDUCTION GEAR BOX
ALTERNATOR
TRANSFORMERS
-
8/9/2019 Co-generation Power Plant.
8/43
3.
FUEL
The main source of energy is fuels. The fuels may be solid, liquid, or gases such as coal,oil and coal gas.
Here we use Bagasse as fuel for generation of electrical energy
Sugarcane waste is known as Bagasse. It is available from sugar industry, where
sugarcane is crushed to get sugarcane juice and Bagasse is used to generate electric power. The
calorific value of Bagasse is 2500 kcal/kg. It is also used in paper industry. To generate a ton of
steam, two tones of Bagasse; has to be burnt.30 to 33% of Bagasse is present in sugarcane.
Bagasse is a good firing material.
FEED WATER
The condensate from the condenser is used as feed water to the boiler. Some water maybe lost in the cycle which is suitably made up from external source. The feed water on its way tothe boiler is heated by water heaters and economizer. This helps in raising the overall efficiency
of the plant.
WATER TREATMENT PLANT
Boilers require clean and soft water for long life and better efficiency. However the
source of boiler feed water is generally a river or a lake or bore wells which may containsuspended and dissolved impurities, dissolved gases etc. Therefore, it is very important that
water is first purified and softened by chemical treatment and then delivered to the boiler.
The suspended impurities are removed through sedimentation, coagulation and filtration.
Dissolved gases are removed by aeration and degasification. The water is then softened by
removing temporary and permanent hardness through different chemical processes. The pure andsoft water thus available is fed to the boiler for steam generation.
Here we use reverse osmosis plant for removing the impurities in the raw water. This
method consists of thin permeable membrane for removing impurities.
BOILER:
Boilers or steam generators convert water into steam and form one of the majorequipments of the plant.
A boiler is a closed vessel in which water is converted into steam by utilizing the heat
combustion of Bagasse. Boilers are twoTypes. They are;
1. Water tube boiler
2. Fire tube boiler
-
8/9/2019 Co-generation Power Plant.
9/43
4.
In fire tube boilers the tubes containing the hot products of combustion pass through the
tubes surrounded by water. Water tube boiler has number of advantages over fire tube boiler,
requires less space, smaller size of tubes and drum, high working pressure due to small drum,
less liable to explosion etc. Therefore, the use of water tube boiler has become universal. Fromthe above advantages we are using water tube boilers in Co-generation plant. Boiler capacity is
64 tones in 6MW co-generation plant
In the water tubes boilers the water is inside the tubes and the hot gases are outside the
tubes as the water and steam are in the same shell, higher pressure of steam are not possible. The
output steam has a pressure of 42Kg/cm2 and temperature of 4150c the temperature of boiler is
14000c.
Here we use Water tube boilers.
Water tube boilers consist of drums and tubes. The tubes are always external to drum. In
comparison to fire tube boilers the drum in such boiler dont contain any tubular heating surfaces
so they can be build in smaller diameters and consequently they will withstand the high pressure.
The advantages of water tube boilers over the fire tube boilers are as under;
High evaporation capacity due to availability of large heating surfaces
Better heat transfer to the mass of water and better efficiency of plant and owing
to rapid and uniform circulation of water in tubes
High working pressure due to smaller size of drum
Quick raising of steam owing to large ratio of heating surface to water volume
Safety in operation Less space occupied
Better overall control
Easy removal of scale from inside of the tubes
It is one of the best types of vertical multi-tubular boiler, and has a number of horizontalfire tubes. Cochran boiler consists of a cylindrical shell with a dome shaped top where the space
is provided for steam. The furnace is one piece construction and seamless. Its crown has a
hemispherical shape and thus provides maximum volume of space.
BABCOCK AND WILCOX WATER TUBE BOILER:
The water tube boilers are used exclusively, when pressure above 10 bars and capacity inexcess of 7000 Kg of steam per hour is required. Babcock and Wilcox water tube boiler is an
example of horizontal straight tube boiler.
A Babcock and Wilcox water tube boiler with cross drum differs from
longitudinal drum boiler in a way that how drum is placed with reference to the axis of the watertubes of the boiler. The longitudinal drum restricts number of tubes that can be connected to one
drum circumferentially and limits the capacity of the boiler. In the cross drum there is no
limitation of the number of connecting tubes.
-
8/9/2019 Co-generation Power Plant.
10/43
5.
The fuel is burnt on the grate and ash is collected and disposed of from ash pit. The gasesof combustion produced by burning of fuel enter the combustion chamber through the flue tube
and strike against fire brick lining which directs them to pass through number of horizontal
tubes, being surrounded by water. After which the gases escape to the atmosphere through smokebox and chimney. A number of hand holes are provided around the outer shell for cleaning
purposes.
The selection and size of the boiler depends upon
1. Output requires in terms of amount of steam/hour, operating temperature and pressure
2. Availability of fuel and water3. The probable load factor
The other factors which influence the choice of a boiler are availability, initial cost,
maintenance cost, labor cost, fuel cost and space requirements.
The water tube boilers are used where large amount of steam are to be produced at a hightemperature and pressure and weight and space considerations are important. To meet a required
demand, the choice between two boilers will be based on economic considerations I.e., total
annual; cost (fixed cost running cost). The worth nothing point is that the total cost of the fuel
used by the boiler in its life time may be 3 to 4 times the initial investment.
BOILER FURNACE
It is a chamber in which fuel is burnt to liberate the heat energy. The boiler furnace walls
are made of refractory materials such as fire clay, silica, kaolin etc; Bagasse is thrown into boiler
furnace through elevator.
The construction of boiler furnaces varies from plain refractory walls to completely to
water cooled walls, depending upon the characteristics of fuel used and ash produced, firingmethods , natural of load demand, combustion space required, excess air used, operating
temperature, initial and operating cost.
The plain refractory walls are suitable for small plants where the furnaces temperaturemay not be high. The arrangement may consists of a single section of homogenous refractory or
insulation may be placed in between the refractory and casing.
For large plants, where the furnace temperature is quite high refractory walls are made
hallow and air is circulated through hallow space to keep the temperature of the furnace walls
low. This type of arrangement is no more preferred.
Practically water cooled walls similar to plain refractory type with a portion of surface
covered by water tubes. A proper balance can be made between the water cooled section and the
-
8/9/2019 Co-generation Power Plant.
11/43
refractory section to give best results. This type is used for both stoker fired and pulverized fuel
fired boilers.
6.The recent development is to use water walls. The water walls are built of tubes of
diameter ranging from 25mm to 100mm variously spaced with or without fins or studs and bear
or with different thickness of moldable refractory on the inner face. Heat transfer rates run from0.5*106 to 1.4*106kcal/hour/m3of surface to meet these requirements of heat transmission,
circulation on the water side must be adequate, obtained by convection or by pumps. This type is
suitable for pulverized fuel fired boilers and high steaming rates can be maintained.
SUPERHEATER
A superheater is a device which superheats the steam. It raises the temperature of steamabove boiling point of water. A superheater consists of a group of tubes made of special alloy
steel such as chromium-molybdenum. These tubes are heated by the heat of flue gases during
their journey from the furnace to the chimney. The steam produced in the boiler is led through
the superheater where it is superheated by the heat of flue gases.
Super heaters consists of groups of tubes made of steel (carbon steel for steamtemperature up to 9500f, carbon-molybdenum steel for steam temperature of 10500f and stain less
steel for steam temperature of 12000f) with an outside diameter ranging from 25mm to 64mm.
tube handle location and arrangement, with counter current, and /or parallel flow is dictated by
type of firing, and required steam temperature, and steam temperature characteristic. Thesuperheater tubes are heated by heat of combustion gases during their passage from furnace to
chimney.
Super heaters are mainly classified into two types according to the system of heat transfer
from flue gases to steam. They are;
1. Radiant superheater
2. Convection superheater
Here in this power generation we are using radiant type superheater.
The radiant superheater is placed in the furnace between the water walls and receives heat
from the burning fuel through radiation process. It has two main disadvantages firstly, owing tohigh furnace temperature; it may get over heated and, therefore, requires a careful design.
Secondly it gives drooping characteristics i.e., the temperature falls with the increase in steam
output, the furnace temperature raises at a much less rapid rate then the steam output and theradiant heat transfer being a function of furnace temperature increases slowly with the steam
flow or the steam temperature falls.
On the other hand, a convection superheater is placed in the boiler tube bank and receives
heat from flue gases entirely through the convention process. It gives raising characteristics i.e.,
the temperature of the superheat increases with the increase in steam output because with the
-
8/9/2019 Co-generation Power Plant.
12/43
-
8/9/2019 Co-generation Power Plant.
13/43
8.
The use of an economiser entails the following advantages
o The temperature range between various parts of the boiler is reduced which
results in reduction of stress due to unequal expansion.
o If the boiler is fed with cold water it may result in chilling the boiler metal. Hot
feed water checks it.
o Evaporative capacity of the boiler is increased.
o Overall efficiency of the plant is increased.
o Reduces temperature stresses in boiler joints.
In the modern economiser the temperature of feed water is raised from about 247 0c to
2760c
AIR PRE-HEATER
Super heaters and economizers generally cannot fully extract the heat from flue gases.
Therefore, pre-heaters are employed which recover some of the heat in the escaping gases.
The function of an air pre-heater is to extract heat from the flue gases and give it to the
air being supplied to furnace for fuel combustion. This raises the furnace temperature and
increases the thermal efficiency of the plant. Depending upon the method of transfer of heat from
flue gases to air, air pre-heaters are divided into the following two classes
1. Recuperative type
2. Regenerative type
The recuperative type air pre-heater consists of a group of steel tubes. The flue gases are
passed through the tubes while the air flows externally to the tubes. Thus heat of flue gases istransferred to air.
There are two types of Air preheaters
1. Tubular type
2. Plate type
1. Tubular type
After leaving the boiler or economizer the gaseous products of combustion travel
through the inside of the tubes of air preheater in a direction opposite to that of air travel and
transfer some of their heat to the air to be supplied to the furnace. Thus the air gets initially
-
8/9/2019 Co-generation Power Plant.
14/43
heated before being supplied to the furnace. The gases reverse their direction near the bottom of
the air heater, and a soot hopper is fitted to the bottom of air heater casing to collect soot
9.
2. Plate type
In the plate type Air preheater the air absorbs heat from the hot gases being sweptthrough the heater at high velocity on opposite side of a plate.
REGENERATIVE TYPE
The regenerative type air pre-heater consists of slowly moving drum made of corrugated
metal plates. The flue gases flow continuously on one side of the drum and air on the other side.
This action permits the transference of heat of flue gases to the air being supplied to the furnace
for fuel combustion.
-
8/9/2019 Co-generation Power Plant.
15/43
10.
CONDENSER
Steam after expansion through the prime mover goes through the condenser which
condenses the exhaust steam and also removes air and other non condensable gases from steam
while passing through them. The recovery exhaust steam in the condenser reduces the make up
feed water that must be added to the system from 100% when exhausted to atmosphere to about
1-5% and there by reduce condensable the capacity of water treatment plant. The exhaust
pressure may be lowered from the standard atmospheric pressure to about 25mm of Hg absolute
and there by permitting expansion of steam in the prime mover to very low pressure and
increasing plant efficiency. Maintenance of high vacuum in the condenser is essential for
efficient operation. Any leakage of air in to the condenser destroys the vacuum and causes
i. Any increase in the condenser pressure which limits the useful heat drop in the
prime mover
ii. A lower of the partial pressure of the steam and of the saturation temperature
along with it. This means that the latent heat increase and therefore, more cooling
water are required. Also, the under cooling of the condensate is likely to be more
severe.
This will result in lower efficiency. As it is not possible to eliminate air leakage
completely, a vacuum pump is necessary to remove the air leakage in to the condenser.
Condensers are of two types. Namely
Jet or contact condenser
Surface condenser
The essential differences between a jet condenser and surface condenser is that in the
former, the exhaust steam mixes with the cooling water and the temperature of the condensate
and the cooling water is the same when leaving the condenser; and the condensate cannot be
recovered for use as feed water to the boiler; heat transfer is by direct conduction; in the later i.e.
in surface condenser the exhaust steam and cooling water do not mix with each other, the water
being circulated through the nest of tubes, the heat transfer being by convection. The temperature
-
8/9/2019 Co-generation Power Plant.
16/43
of the condensate may be higher than the temperature of the cooling water at outlet and the
condensate is recovered as feed water to the boiler.
11.
Both the cooling water and the condensate are separately with drawn. Advantages of jetcondensers are;
Low initial cost
Low requirements of floor area and cooling water and
Low maintenance charge
Disadvantages
Condensate is wasted
High power is required for pumping water
Hence the use of jet condenser is limited to small industrial applications (1000kW) where
high vacuum is not required (50mm-125mm Hg abs).
The jet condensers may be further classified as
1. Parallel flow type jet condensers
2. Counter- flow type jet condensers
-
8/9/2019 Co-generation Power Plant.
17/43
12.
-
8/9/2019 Co-generation Power Plant.
18/43
13.
-
8/9/2019 Co-generation Power Plant.
19/43
14.
-
8/9/2019 Co-generation Power Plant.
20/43
15.
-
8/9/2019 Co-generation Power Plant.
21/43
Steam turbines are generally classified
into two types according to the action of
steam on moving blades viz.
Impulse turbines
Reaction turbines
THE IMPULSE TURBINE
In the case of the impulse turbine,
high velocity gases operate on the concave
surfaces of the blades almost exclusively. Inother words, this is a "bucket effect" means
of extracting energy.
Gas directed into the concave surfaceof the blades and at an angle of about 45 to85 degrees, relative to the shaft, will transfer
power to the shaft through impulse.
The unique characteristic of impulseengines is that the velocity of the gas
decreases upon exiting the blades, whereas
the pressure remains constant. Energy is
transferred by changing the velocity of thegas -- not its pressure.
The reaction blade acts like a wing
section of a plane, whereas the impulse
blade acts like the piston of an engine.
THE REACTION TURBINE
In the reaction turbine, kinetic gas
energy is converted to shaft power by
decreasing the velocity of the gas andlowering gas pressure -- just like on an
airplane wing. As gas enters from the left ofthe blade section and travels across the bladesurface, there is a decrease in pressure on
the upper surface, and an increase in
pressure on the lower surface. As the gas
leaves the trailing edge there is a decrease in
gas velocity, pressure, and a downwardangle -- resulting in a lifting or reaction
force.
Fig impulse turbine
Fig reaction turbine
16.
-
8/9/2019 Co-generation Power Plant.
22/43
ALTERNATORS
Introduction
A synchronous machine is an ac machine in which the rotor moves at a speed which
bears a constant relationship to the frequency of currents, in the armature winding. A
synchronous machine is one of the important types of electrical machines. Large ac networks
operating at constant frequency of 50Hz (or60Hz) rely almost exclusively on synchronous
generators, also called the alternators.
Synchronous motors provide constant speed industrial drives with the possibility of
power factor correction.
Synchronous machines are generally constructed in larger sizes. Small sizes alternators
are not economical. The modern trend is to build alternators of very large sizes capable of
generating 500MVA or even more. The synchronous motor is rarely built in small sizes owing to
superior performance characteristics and economical construction of induction motors.
Operating principle
The operating principle of a synchronous machine is fundamentally is same that of a dc
machine, but ,unlike the latter, in the synchronous machine there is no need to rectify the time
varying emf which is induced in the armature winding consequently a synchronous machine does
not require a commutator it is , in fact quite possible to use a dc generator as an alternator by
placing a set of collector rings on the shaft and connecting these rings to the proper points on the
armature winding; brushes riding on the rings can be collected to the load but unlike dc generatorthey are to be driven at a very definite constant speed as the frequency of a generated emf is
determined by that speed the latter is usually referred to as synchronous speed , for which reason
these machines are called frequently synchronous generators.
Synchronous generators, because of the absence of commutator are comparatively
simple and possesses several important advantages over the dc generators
Classification of Synchronous Machines
Synchronous machines, according to their applications, may be synchronous generators,
synchronous motors or synchronous compensators. A synchronous generator is a synchronous
machine which receives mechanical energy from a prime mover to which it is mechanically
coupled and delivers electrical energy. A synchronous motor receives electrical energy from ac
supply main and drives mechanical load.
17.
-
8/9/2019 Co-generation Power Plant.
23/43
(a) Based on the construction of the machines, the synchronous machines can be classified as
1. Rotating Armature type,
2. Rotating Field type.
Rotating Armature type Alternator
It looks very much like a dc generator except that there are three slip rings in place of
commutator in such generators the required magnetic field is produced by dc electro magnets
placed on the stationary member called thestatorand the current generated is collected by the
means of brushes and slip rings on the revolving member called the rotorsuch an arrangement is
a economical for a small low voltage generator. Rotating armature type alternators are built only
in small ratings up to 200 or 250 KVA, because the voltage generated is comparatively low and
the current to be collected by the brushes are small. It practically all medium and large machines
are always constructed with revolving field.
1. This type of alternator has stationary field poles and rotating armature
2. It is mainly for small KVA capacity and low voltage rating
3. It resembles dc generator except that it has slip rings instead of commutator
4. Field poles are excited by an external dc source.
Rotating field type alternator
1. It has stationary armature (stator) and a rotating field poles
2. In this structure the rotor has slip rings and brushes to supply an excitation current from an
outside dc source.
3. The armature coils are placed in slots in a laminated core called the stator which is made up of
thin steel laminations and are placed in the frame of generators.
4. The amount of power delivered to the field circuit is relatively small that is 100-250 volts.
5. Most of the alternators are of this type and they are used for high KVA capacity and high
voltage rating.
Advantages of Rotating field type alternator:
1. The armature winding must be insulated for a high voltage while the voltage of field circuit is
low, because it is much easier insulate the high voltage winding. When it is mounted on
18.
-
8/9/2019 Co-generation Power Plant.
24/43
Stationary structure
2. Only a small amount of power at low voltage is handled by the slip ring contacts.
3. It is easier to build and balance high speed rotor when they carry field structure.
4. The armature winding is cooled more readily because the stator can made up of many air
passages or ducts for forced air circulation.
Construction of an Alternator:
In alternator consists of two parts
1. Stator
2. Rotor
The stator of the alternator consist of the alternator consist of a cast iron or welded steel
frame which supports the armature core having slots on its periphery for similar
conductors are connected together in groups to form a winding of desired no. of faces.(generally
star connected).
Ventilating ducts are provided parallel to the axis of frame to facilitate improved cooling
conditions.
The stator is made up of steel alloy laminations and the laminations are insulated fromeach other by a layer of oxide and enamel.
It is made up of laminations to reduce iron losses due to eddy currents.
Open windings are permitted because it is easy for the installation of stator coils and forthe removal in case of repair.
A fractional rather than integral no. of slots for pole is used to eliminate the harmonics inthe waveform.
Rotor
The rotors are classified into two types.
1. Salient pole type rotor
2. Smooth cylindrical type rotor
Salient Pole Type Rotor
This type of rotor is used carries large no. of poles (p>4).this type of rotor is used for
slow speed machines which have larger diameter and small axial length.
-
8/9/2019 Co-generation Power Plant.
25/43
Special features of salient pole type rotors:
19.
1Tthey have larger diameter and small axial length.
2. The pole shoe covers 2/3of the pole pitch.
3. The poles are laminated to reduce eddy currents losses. These types of rotors are employed
with water or hydro turbines and internal combustion engines.
4. Low operating speed.
5. This rotor have always vertical configuration.
Smooth cylindrical Type rotor (non salient pole)
The no. of poles of the rotor is less i.e. either two or four. This type of rotor is used for
alternators which are couple to steam turbines which run at very high speed.
Special features of cylindrical type rotors
1. They have smaller diameter and long axial length.
2. Robust construction.
3. Dynamic balancing is better.
4. High operating speeds.
5. Less windage losses.
7. Better emf waveform.
(b)Classification of synchronous machines based on prime mover
Synchronous machines are classified into two types based on the type of prime mover
1. Turbo generators
2. Hydro generators.
Turbo generators
If the generators are driven by steam turbines they are called as turbo generators. They
run at high speeds and the rotor will be of cylindrical type.
-
8/9/2019 Co-generation Power Plant.
26/43
2. Hydro generators
If the generators are driven by water turbines then they are called as hydro generators.
They run at low operation speeds. The rotor is if salient pole type.
20.
SINGLE PHASE TRANSFORMER
The transformer is probably one of the most useful electrical devices ever invented .It can
raise or lower the voltage or current in an AC Circuit, it can isolate circuits from each other, & it
can increase or decrease the apparent value of capacitor, an in doctor or a resistor. Further more,
the transformer enables us to transmit electrical energy over great distances & to distribute it
safely in factories & homes.
A transformer is static piece of apparatus by means of which electrical power in one
circuit is transformed into electrical power of the same frequency in another circuit. The physical
basis of transformer is mutual induction between two circuits linked by a common magnetic flux.
In its simplest form, it consists of two inductive coils which are electrically separated but
magnetically coupled through a path of low reluctance. The two coils possess high mutual
inductance. If one of the coil is connected to a source of alternating voltage, an alternating flux is
set up in the laminated core, most of which is linked with the other coil in which it produces
mutually induced emf according to Faradays laws of electromagnetic induction. If the second
coil is closed, a current flow in it & so electrical energy is transferred from first coil to second
coil. The first coil, in which electrical energy is fed from the AC supply, is called primary
winding and the other from which energy is drawn out, is called secondary winding.
Construction of the transformer
The simplest elements of the transformer consist of two coils having mutual inductance
and a laminated steel core. The two coils are insulated from each other and the steel core. Other
necessary parts are:
A suitable medium for insulating the core & its windings from itscontainer
A suitable bushings for insulating & bringing out the terminals of
the windings from the tank
In all types of transformers, the core is constructed of transformer sheet steel laminations
assembled to provide continuous magnetic paths with minimum of air gap included. The steel
used is of high silicon content, some times heat treated to produce a high permeability and a low
hysteresis loss at usual operating flux densities. The eddy current loss is minimized by
-
8/9/2019 Co-generation Power Plant.
27/43
laminating the core, the laminations being insulated from each other by a light coat of core plate
varnish or by an oxide layer on the surface.
21.
Transformer rating
Cu loss of a transformer depends on current and iron loss on voltage. Hence, total
transformer loss depends on volt-ampere (VA) and not on phase angle between voltage and
current i.e. it is independent of load power factor. Thats why rating of transformer is in KVA
and not in KW.
THREE PHASE TRANSFORMER
Large scale generation of electric power is usually 3-phase at generated voltages of
110,132,275,400 and 750 kV for which purpose 3-phase transformers are necessary to step up
the generated voltage to that of the transmission line. Next, at load centers, the transmission
voltages are reduced to distribution voltages of 6600, 4600 and 2300 volts. Further, at most of
the consumers, the distribution voltages are still reduced to utilization voltages of 440, 220 or
110 volts.
Years ago, it was a common practice to use suitably interconnected three single-phase
transformers instead of a single three phase transformer. But these days, the latter is gaining
popularity because of improvement in design and manufacture but principally because of better
acquaintance of operating men with the three phase type. As compared to a bank of single phase
transformer, the main advantages of a 3-phase transformer are that it occupies less floor space for
equal rating, weighs less, costs about 15% less and further, that only one unit is to be handled
and connected.
Like single phase transformers, the 3-phase transformers are also of the core type or shell
type. The basic principle of a 3-phase transformer is illustrated in figure 1in which only primary
windings have been shown inter connected in star and put across three phase supply. The three
cores are 1200 apart and their empty legs are shown in contact with each other. The center leg
formed by these three carries the flux produced by 3-phase currents IR, IY and IB. as at any instant
IR+ IY +IB=0
Hence the sum of three fluxes is also zero. Therefore, it will make no difference if the
common leg is removed. In that case any two legs will act as the return for the third just as in a
three phase system any two conductors act as the return current in the third conductor. This
improved design is shown in fig2.Where dotted rectangles indicate the 3 windings and numbers
in the cores and yokes represent the directions and magnitudes of fluxes at a particular instant. It
-
8/9/2019 Co-generation Power Plant.
28/43
will be seen that at any instant, the amount of up flux in any leg is equal to the sum of down
fluxes in the other two legs. The core type transformers are usually wound with circular
cylindrical coils.
22.
-
8/9/2019 Co-generation Power Plant.
29/43
Fig.1
23.
-
8/9/2019 Co-generation Power Plant.
30/43
Fig2
In a similar way, three 1-phase shell type transformers can be combined together to form
a 3-phase shell type unit. But some saving in iron can be achieved in constructing a single 3-
phase transformer. It does not differ from three 1-phase transformers put side by side. Saving in
iron is due to the joint use of magnetic paths between the coils. The three phases, in this case, are
more independent then they are in the core type transformers, because each phase has a magnetic
circuit independent of the other.
One main drawback in 3-phase transformer is that if any one phase becomes disabled,
then the whole transformer has to be ordinarily removed from service for repairs. However, in
the case of a 3-phase bank of 1-phase transformers if one transformer goes out of order, the
system can still be run open at reduced capacity or the faulty transformer can be readilyreplaced by a single spare.
24.
-
8/9/2019 Co-generation Power Plant.
31/43
Three-phase transformer connections:
There are various methods available for transforming 3-phase voltages to higher or lower
3-phase voltages i.e. for handling a considerable amount of power. The most common
connections are
Y-Y
-
Y-
-Y
Open or V-V
Scott connection or T-T connectionBut here we are using only - and Y- as a bidirectional connections.
Delta-Delta or - connection
This connection is economical for large, low-voltage transformers in which insulation
problem is not so urgent, because it increases the number of turns per phase. The transformer
connections and voltage triangles. The ratio of transformation between primary and secondary
line voltage is exactly the same as that of each transformer. Further, the secondary voltage
triangle abc occupies the same relative position as the primary voltage triangle ABC i.e. there is
no angular displacement between the two. Moreover, there is no internal phase shift betweenphase and line voltages on either side as was the case in Y-Y connection. This connection has
following advantages
1. To make the output voltage sinusoidal it is necessary that the magnetizing currentof the transformer must contain a third harmonic component. So, third harmonic
component can flow in a delta connected transformer primaries without flowing
in the line wires. The three phases are 1200 apart which is 31200=3600 with
respect to the third harmonic component; hence it merely circulates in the delta.
Therefore, the flux is sinusoidal which results in sinusoidal voltages.
2. No difficulty is experienced from unbalanced loading as was the case in Y-Yconnection.
3. If the transformer becomes disabled the system can be continued to operate inopen Delta or V-V although with reduced available capacity.
25.
-
8/9/2019 Co-generation Power Plant.
32/43
Wye/Delta or Y/ connection:The main use of this connection is at the sub-station end of the transmission line where
the voltage is to be stepped down. The primary winding is Y connected with grounded neutral.
The ratio between secondary and primary line voltage is 1/3 times the transformation ratio ofeach transformer. There is a 300 shift between the primary and its secondary line voltages which
means that Y- transformer bank cannot be paralleled with either a Y-Y or a - bank.
Instrument transformers:
To measure large currents & voltages in alternating circuits specially constructed
accurate ratio Instrument transformers are employed in conjunction with standard low range AC
instruments.
They are of two types
1. Current transformers &
2. Potential transformers
26.
-
8/9/2019 Co-generation Power Plant.
33/43
Current transformers:
These transformers are used with low range ammeters to measure currents in high voltage
AC circuits. The current transformer has a primary coil of one or more turns of thick wire
connected in series with the line whose current is to be measured. The secondary consists of a
large number of turns of fine wire and is connected across the ammeter terminals.
Here the voltage stepped up and current is stepped down. One of the most commonly
used current transformers is known as Clamp ON or Clip ON type. Since the ammeter resistance
is very less the current transformer normally works short-circuited. If it is not done large amount
of primary flux will be setup .It damages insulation and core gets saturated.
Potential Transformers:
These transformers are extremely accurate ratio step down transformers and are used in
conjunction with standard low range voltmeters. They are of shell type transformers but there
power rating is extremely small. Up to voltages of 5000, potential transformers are usually of the
dry type, between 5000 & 13800 V they are always oil immersed type. For safety, the secondary
should be completely insulated from the high voltage primary and should be, in addition,
grounded for affording protection to operator.
Losses in a transformer:
In a static transformer there are no friction or windage losses hence the only losses
occurring are
1. Core Loss or Iron Loss
2. Copper Loss
Core or Iron Losses:
It includes both Hysteresis and eddy current losses. Because the core flux in a
transformer remains practically constant for all loads hence the core losses are constant.
Hysteresis losses occur due to application of varying strengths of AC and eddy current
losses occur due to the flow of currents in a closed path due to induced emf. These currents are
called as eddy currents.
Hysteresis Loss Wh = B1.6maxfv watt
Eddy Current loss We= PB2
maxf2t2 watts
Hysteresis losses can be minimized by using steel of high Si content for the core and
eddy current loss can be minimized by using very thin laminations. Iron Loss can be found from
Open Circuit Test. 27.
-
8/9/2019 Co-generation Power Plant.
34/43
Copper Losses:
This is due to the ohmic resistance of the transformer windings.
Total cu Losses = I12R1+I2
2R2 = I12R01 = I2
2R02
It is clear that Cu loss is proportional to (current) 2. The value of Cu losses can be found
by Short Circuit test.
The losses appear in the form of it and a drop in efficiency. Normally, the efficiency of
transformers is high about 99.5%.Cu loss inversely vary with Power Factor because current is
inversely proportional to power factor.
Cooling Methods:
To prevent rapid deterioration of the insulating materials inside a transformer, adequate
cooling of the windings and core must be provided.
Indoor transformers below 200kVA can be directly cooled by the natural flow of the
surrounding air. The metallic housing is fitted with ventilating louvers so that convection
currents may flow over the windings and around the core. Large transformers can be built the
same way, but forced circulation of clean air must be provided. Such dry type transformers are
used inside buildings, away from hostile atmospheres.
Distribution transformers below 200 kVA are usually immersed in mineral oil and
enclosed in a steel tank. Oil carries the heat away to the tank, where it is dissipated by radiation
and convection to the outside air. Oil is much better insulator than air is; consequently, it is
invariably used on high voltage transformers. As power rating increases, external radiators areadded to increase the cooling surface of the oil filled tank. Oil circulates around the transformer
windings and move through radiators, where the heat is again released to surrounding air. For
still higher ratings cooling fans blow air over the radiators. For the transformers in megawatt
range cooling may be affected by an oil water heat exchanger. Hot air drawn from the
transformer tank is pumped to a heat exchanger where it flows through pipes that are in contact
with cool water. Such a heat exchanger is very effective and costly.
28.
-
8/9/2019 Co-generation Power Plant.
35/43
VARIABLE FREQUENCY DRIVE MOTORS
There are a wide range of motors ranging from 0.75kW to
500kW due to their cost and ability to perform under extremeconditions. With the continuing advances in power electronics and
microprocessor technology, AC variable speed drive has becomevery popular. With new technology, manufacturer with the use of
variable frequency drives can incorporate greater control, reduceswitching losses and provide greater power handling capability.
The motor used in a variable frequency drive system is usually a three-phase induction
motor. Some types of single-phase motors can be used, but three-phase motors are usually
preferred. Various types of synchronous motors offer advantages in some situations, butinduction motors are suitable for most purposes and are generally the most economical choice.
Motors that are designed for fixed-speed mains voltage operation are often used, but certain
enhancements to the standard motor designs offer higher reliability and better variable frequency
drive performance. A variable frequency drive system generally consists of an AC motor, acontroller and an operator interface.
Benefits of Variable Frequency Drives:
Increased Drive Efficiency (usually 97-98%) Reduced Volume and Weight Lower Price Reduced Audible Noise Level Improved Power Factor Reduced Harmonic Distortion to Supply
Improved Reliability Larger Voltage and Current Rating High Switching Speeds and lower Losses
Constant Torque Application:
Constant Torque applications are where the same amount of torque is required at low
speed as at high speed. Some applications may include conveyors, mixers, screw feeders,extruders and positive displacement pumps.
Constant Power Applications:
Constant power applications are where a high torque is required at low speed and a low
torque at high speed. Examples of applications are machine tools, tractions.
29.
-
8/9/2019 Co-generation Power Plant.
36/43
Variable Torque Application
Variable torque is where a low torque is required at a low speed and higher torque at high
speed. Some applications are centrifugal loads such as fans, pumps and blowers. With theseapplications we will see the most energy saving by using a variable frequency drive.
Working
At the heart of an electric motor are the stator and the rotor. A magnetic field is generated
when a current is applied and the north/south field rotates through the stationary stator as the
rotor spins to catch up to the rotating field. The spinning of the rotor provides the torquenecessary to drive a load.
An electric motor turns at a given speed depending on the number of poles in the motor
and the frequency of the alternating current applied. Motor speed can be changed by changing
the alternating current frequency.
Nearly all variable frequency drives manufactured today are referred to as pulse width
modulation drives. These drives contain electronic circuitry that converts the 60 Hertz line power
to direct current, then pulses the output voltage for varying lengths of time to mimic an
alternating current at the frequency desired.
The use of variable frequency drive application is use majority for centrifugal pumps and
fans. The savings potential is the largest in these devices since the theoretical input power varies
with the cube of fan/pump speed and volume. A fan operating a half speed will require onlyabout 13 percent of full speed power. Losses in the variable frequency drive will reduce saving
somewhat, but the saving are still very impressive.
ELECTRO-STATIC PRECIPITATOR
The electro-static precipitator consists of metal plates which are electrically charged.
Dust and grit in the flue gases are attracted on to these plates, so that they do not pass up the
chimney to pollute the atmosphere. Regular mechanical hammer blows because theaccumulations of ash, dust and grit to fall to the bottom of the precipitator, where they collect in
a hopper for disposal Additional accumulations of ash also collect in hoppers beneath the
furnace.
30.
-
8/9/2019 Co-generation Power Plant.
37/43
SCHEMATIC ARRANGEMENT OF THE PLANT
-
8/9/2019 Co-generation Power Plant.
38/43
Although steam power station simply involves the conversation of heat of bagasse into
electrical energy, it embraces many arrangements for proper working and efficiency. The whole
arrangement can be divided into the following stages for the sake of simplicity.
1. Fuel and ash handling arrangement
2. Steam generating plant
3. Steam turbine
4. Alternator
5. Feed water
6. Cooling arrangement
A. Fuel and ash handling arrangement
The bagasse coal is feed to the boiler by belt conveyers. The fuel is burnt in the boiler and the
ash produced after the complete combustion of bagasse is removed to the ash handling plant and
then delivered to the ash storage plant for disposal. The removal of the ash from the boiler
furnace is necessary for proper burning of fuel.
Here in this power generating station there is not much cost spent in purchasing the fuel. As
it is wastage of sugarcane left in sugar processing plant.
B. Steam generating plant
The Steam generating plant consists of a boiler for the production of steam and other
auxiliary equipment for the utilization of flue gases.
I. Boiler
The heat of combustion of bagasse in the boiler is utilized to convert water into a steam at
high pressure and temperature. The flue gases from the boiler make their journey through
superheater, economiser, air pre-heater and are finally exhausted to atmosphere though the
chimney.
The calorific value of the bagasse is 2400kCal/kg. The boiler is designed to produce 64 tonesof steam per hour at a temperature of 4150c and at a pressure of 42kg/cm2. The boiler
temperature is 14000c.
31.
-
8/9/2019 Co-generation Power Plant.
39/43
32.
-
8/9/2019 Co-generation Power Plant.
40/43
II. Superheater
The steam produced in the boiler is wet and is passed through a superheater where it is dried
and is superheated. (Steam temperature increased above that of boiling point of water) the flue
gases on their way to chimney. Superheating provides two principle benefits. Firstly, the overall
efficiency is increased. Secondly, too much condensation in the last stages of turbine (whichwould cause blade corrosion) is avoided. The superheated steam from the superheater is fed to
steam turbine through the main valve.
III. Economiser
An economiser is essentially a feed water heater and derives heat from the flue gases for this
purpose. The feed water is fed to the economiser before supplying to the boiler. The economiser
extracts a part of heat of flue gases to increase the feed water temperature.
IV. Air-preheater
An air-preheater increase the temperature of the air supplied for bagasse burning by deriving
heat from the flue gases. Air is drawn from the atmosphere by forced draught fan and is passed
through air-preheater before supplying to the boiler furnace. The air-preheater extracts heat from
flue gases and increases the temperature of air used for bagasse combustion. The principle
benefits of preheating the air are:
Increased thermal efficiency
Increased steam capacity per square meter of boiler surface
In KBD sugars the forced draught fan is 75Hp and is one in number.
C. Steam turbine
The dry and superheated steam from the superheater is fed to the steam turbine through main
valve. The heat energy of steam when passing over the blades of turbine is the converted into
mechanical energy. After giving heat energy to the turbine, the steam is exhausted to the
condenser which condenses the exhausted steam by means of cold water circulation. The
governor mechanism is employed to control the fuel falling into the boiler. The speed of the
steam impulse turbine is 8250rpm.
D. Alternator
The steam turbine is coupled to an alternator. The alternator converts mechanical energy of
turbine into electrical energy. The electrical output from the alternator is delivered to the bus bars
through transformer, circuit breakers and isolators.
33.
-
8/9/2019 Co-generation Power Plant.
41/43
The alternator rotates with the 1500rpm delivers the 6MW output at a voltage of 11Kv.
The steam turbine is coupled to the alternator by means of reduction gear box. The reduction
gear box reduces the speed to be matched with the alternator.
E. Feed water
The condensate from the condenser is used as feed water to the boiler. Some water may be
lost in the cycle which is suitably made up from external sources. The feed water on its way to
the boiler is heated by the water heaters and economizer. This help in rising overall efficiency of
the plant.
F. Cooling arrangement
In order to improve the efficiency of the plant, the steam exhausted from the turbine is
condensed by means of condenser. Water is drawn from a bore well and is circulated through the
condenser. The circulating water takes up the heat of exhausted steam and itself become hot.Since the water availability is less, cooling towers are used. Hot water from the condenser is
passed on the cooling towers where it is cooled. The cold water from the cooling towers is
residue in the condenser.
34.
-
8/9/2019 Co-generation Power Plant.
42/43
The survival of industrial undertakings and our social structures depends primarily upon
low cost and interrupted supply of electrical energy. In fact, the advancement of country is
measured in terms of per capita consumption of electrical energy.
The conversion of energy available in different forms in nature into electrical energy is
known asgeneration of electrical energy.
Energy is available in various forms from different natural sources such as pressure head
of water, chemical energy of fuels, nuclear energy of radioactive substances etc.
All these forms of energy can be converted into electrical energy by the use of suitable
arrangement. In this project we studied that the production of electrical energy from the wastage
of sugar cane i.e., bagasse.
The arrangement essentially employs an alternator coupled to a prime mover. The prime
mover is driven by the energy obtained from burning of bagasse. Heat energy of bagasse can be
used to produce steam at high temperature and pressure.
The steam is fed to steam turbine. The turbine converts heat energy of steam into
mechanical energy which is further converted into electrical energy by the alternator. The energy
produced is utilized for the operation the industrial plant.
CONCLUSION
-
8/9/2019 Co-generation Power Plant.
43/43
BIBLIOGRAPHY
1. PRINCIPLES OF POWER SYSTEM - V.K. MEHTA
2. ELECTRICAL POWER - C.L. WARDHWA
3. ELECTRICAL POWER - J.B. GUPTHA
4. ELECTRICAL TECHNOLOGY -B.L.THERAJA
A.K.THERAJA