CO 110
KEY POINTS
ABS V0
- duct model : IP65- ambient model : IP20
LCD 10 digits. Size : 50 x 17 mm
Height of digits : Value : 10 mm ; Unit : 5 mm
: for cables Ø 8 mm
maximum
138 g (ambient model) ; 150 g (duct model)
- “¼ turn” system mounting with wall-mount plate
ppm
From 0 to 500 ppm
±3 ppm or 3% of the measured value
Electrochemical sensor
5 years
T63 = 35 s
0.1 ppm
Air and neutral gas
From 0 to +50 °C
From -10 to +70 °C
CO110
Power supply / OutputA : Active – 24 Vac/Vdc – 0-10 VP : Passive – 16/30 Vdc – 4-20 mA
DisplayO : with displayN : without display
Example : CO110-POA
*All the accuracies indicated in this technical datasheet were stated in laboratory conditions, and can be guaranteed for measurements carried out in the same conditions, or carried out with calibration compensation.
Type of probeA : DuctS : ambient
90 mm41 mm
80
mm
150 mm46 mm 90 mm
10
9m
m
- 측정 범위 0 ~ 500ppm
or 4-20 mA passive loop 출력, 전원공급 16~30 Vdc (2wire)
- 0~10V active 출력, 전원공급 24 Vac/Vdc (3-4 wires)
- ABS V0 하우징, IP65(모델에 따라), 디스플레이 선택 가능
- 설치형 플레이트를 이용 간단한 설치
기술 자료
측정단위
측정범위
정밀도
센서 타입
센서 수명
응답 시간
분해능
측정환경
보관 환경 온도
측정 환경 온도
재 료 :
보호등급 :
ambient model
Duct model
디스플레이 :
케이블 그랜드(덕트 모델 적용)
무게 :
제품 선정
CO 트랜스미터, 4-20mA passive 출력,
디스플레이 구성, 덕트 프로브 타입 입니다.
CO 트랜스미터
제품 사이즈
사양에 맞는 번호를 선택 제품 선정 :
- active 0-10 V (power supply 24 Vac/Vdc ± 10%), 3-4 wires- passive loop 4-20 mA (power supply 16/30 Vdc), 2 wires- maximum load : 500 Ohms (4-20 mA)- minimum load : 1 K Ohms (0-10 V)
2 VA (0-10 V) or max. 22 mA (4-20 mA)
EN61326
Screw terminal block for cables Ø0.05 to 2.5 mm2
Kimo USB-mini Din cable
Air and neutral gas
This connection must be made by a qualified technician. To make the connection, the transmitter must not be energized.
V
- +
0-10 V output
76LN
24 Vac class II
N L
1 2+5
VCO
4
GND-
7
+
6-
24 Vdc-
+
or
4 wires
To make a 3-wire connection, before powering up the transmitter, please connect the output ground to the input ground. See drawing below.
1 2 3+54
-7
+
6-
- 24 Vdc
+
-
3 wires
4 wires 3 wires
+
1 2 3+54
N7L
6-
- 24 Vacclass II
L
N
3 wires
+
For CO110-A models with 0-10 V output – active :
passive type
V
V
passive type
0-10 V output
passive type
0-10 V output
VCOGND
3
LCC-S
or
기술사양
출력 / 전원
소비량
전자환경적합성
전원 연결
PC 통신
파워서플라이
결 선
사용하지 않는 연결부
소프트웨어
센서스위치
사용하는
스위치
전기화학
전원터미널블럭
케이블그랜드
출력 터미널블럭
분리 가능한 앞면고정 가능한 하우징
결 선 도 - NFC15-100 standard
적용 환경
파워서플라이파워서플라이
파워서플라이
디스플레이 PLC /BMS
디스플레이 PLC /BMS
디스플레이 PLC /BMS
전면부 내부 전면부 내부
For CO110-P models with 4-20 mA output – passive :
2 wires
Ico
57+
6-
16-30 Vdc
VdcA
+
-
Ico
57+
6-
Vdc
-2 wires
+A2 wires
➢
To configure the transmitter, it must not be energized. Then you can make the required settings thanks to the DIP switches as shown on the drawing below. When the transmitter is configured, you can power it up.
12
3
4
... ... ......
passive type
1
2
3
4Combination 1
1
2
3
4Combination 2
active type+ -
On-off switch
Setting of measuring range
From 0 to 500 ppm :
1
2
3
4Combination 3
From 0 to 100 ppm : From 0 to 200 ppm :
7.5
8
4.5
40
50
68
75
37.5
23
.75
14
A
A
16-30 Vdc
Example : for a 0-500 ppm transmitter, the minimum delta is 20 ppm. So the transmitter could be configure from 0 to 70 ppm from 0 to 20 ppm.•
•
1234
Switch 1
or
파워서플라이
디스플레이 PLC /BMS
디스플레이 PLC /BMS
셋팅 및 사용 방법
컨트롤 트랜스미터 나사 4개를 풀어 오픈 합니다.
DIP 스위치를 이용 범위에 맞는 셋팅을 진행 합니다.
> 측정 범위 셋팅
셋팅 하고자 하는 범위를 1,2,3번 스위치를 이용 레이지 설정 :
LCC 소프트웨어 구성 (옵션)
PC 소프트웨어를 통한 쉽고 간편한 설정
소프트웨어로 설정하기 전에 DIP 스위치를 우측 그림과 같이 정렬 후 전용 케이블로 PC와 트랜스미터 연결
트랜스미터와 함께 공급되는 ABS 플레이트로 간단한 설치
트랜스미터와 함께 공급되는 나사로 플레이트 고정
오른쪽 그림 "A" 위치에 트랜스미터를 맞추어 시계방향 30도 회전으로 고정
부식성 및 폭발성 물질 또는 환경에 적용 불가
트랜스미터 및 프로브에 일반적인 크리링 도구 사용 불가
크린룸 및 일반공조에 적용
브랏켓
-트랜스미터에 LCC-S 케이블 접속
-우측 그림과 같이 DIP스위치 정렬
구 성
소프트웨어를 통해 접속 할 수 있는 방법
LCC-S(소프트웨어) 메뉴얼을 참조 하세요.
DIP스위치 또는 소프트웨어 중 하나만 선택 해서 사용 할 수 있습니다.
* 주의 : 매개 변수의 구성 중 두가지 조작 방법을 동시에 사용 할 수 없습니다.
FTan
g –
trans
mitt
er_C
O11
0 –
25/0
7/13
– R
CS
(24)
Pér
igue
ux 3
49 2
82 0
95 N
on-c
ontra
ctua
l doc
umen
t – W
e re
serv
e th
e rig
ht to
mod
ify th
e ch
arac
teris
tics
of o
ur p
rodu
cts
with
out p
rior n
otic
e.
● KIAL-100A : Power supply class 2 , 230 Vac input, 24 Vac output● LCC-S : configuration software with USB cable
➢
➢
➢
프로브의 위치 결정
유지
옵션 및 악세서리
부식성 및 폭발성 물질의 환경에서는 적용이 안됩니다. 본체 와 프로브는 주의해서 관리 부탁 드립니다.
크린룸 및 일반공조에 적용 됩니다.
프로브 끝
구멍
나사
나사를 풀어주세요.프로브의 단부를 돌리기 : 구멍에 공기가 잘 흐를 수 있도록 해주세요.
나사를 조여 주세요.
덕트형 모델 프로브는 위치를 정확하게 측정하는 것이 중요합니다.
프로브 끝에 위치한 나사 구멍이 공기 흐름에 직면 해야 합니다.
프로브의 끝부분의 위치를 변경하는 절차 :
www.kimocorea.com
EXPROT DEPARTMENT
Tel : 02-338-0023 Fax : 02-338-0083
e-mail : [email protected]