class 1a buildings - bretts · perpendicular to the boundary) of a class 1a building within 600 mm...
TRANSCRIPT
Class 1aBuildingsDESIGN & CONSTRUCTION MANUAL
National Timber Development Council
MULTI-RESIDENTIALTIMBER FRAMED CONSTRUCTION
PREFACE
Thedeemedto satisfyprovisionsof the BuildingCodeofAustralia(BCA96) describethe requirementsandlimitationsfor timberframedmulti-residentialbuildings. Theseprovisionsallow timberframingin:-
All Class1 buildings
Class2 buildingsto 3 storeys
(4 storeys wheregroundstorey is concrete/masonrycarparking)
Class3 buildingsto 2 storeys.
Thismanualoutlinesthe BCArequirementsfor Class1a buildingsandassociatedClass10 buildingswithrespectto fire separationandnoisecontrolanddescribesthe materials,detailsandconstructionpracticesthat are recommendedto satisfytheserequirements.
"
"
"
The information provided will enable designers,local authorities, developers and builders toachieve practical and economical solutions forMulti-Residential Timber Framed Construction(MRTFC).
A companion publication ”MRTFC Design &Construction Manual – Class 2 & 3 Buildings”describes the requirements for these buildingclassifications.
The information, opinions, advice andrecommendations contained in this publicationhave been prepared with due care. They areoffered only for the purpose of providing usefulinformation to assist those interested intechnical matters associated with thespecification and use of timber and timberproducts.
Whilst every effort has been made to ensure thatthis publication is in accordance with currenttechnology, it is not intended as an exhaustivestatement of all relevant data, and as successfuldesign and construction depends uponnumerous factors outside the scope of thispublication, the authors and publishers acceptno responsibility for errors in, or omissions from,this publication, nor for specifications or workdone or omitted to be done in reliance on thispublication.
© FWPRDC 2000
First Edition - June 2000
CONTENTS
Section 1 SCOPE 2
Section 2 ABBREVIATIONS, DEFINITIONS,TERMINOLOGY 2
Section 3 BCA REQUIREMENTS 5
Section 4 STRUCTURAL REQUIREMENTS 8
Section 5 FIRE SEPARATION 9
Section 6 SOUND CONTROL 12
Section 7 CONSTRUCTION PRACTICEANDDETAILS 14
Section 8 FIXING OF LININGS 39
3.1 Performance Provisions 53.2 Deemed to Satisfy Provisions 53.3 SeparatingWalls 63.4 ExternalWalls 73.5 Roof Lights 73.6 SmokeAlarms 7
4.1 Timber Member Design 84.2 Noggings 84.3 Notches, Cuts and Holes 8
5.1 Fire Resistance Level (FRL) 95.2 SolidTimber at Intersections 105.3 Strengthened Joints 11
6.1 Weighted Sound Reduction Index (Rw) 126.2 Wall Framing Options 13
7.1 Sub-floor SeparatingWalls 157.2 Double Stud SeparatingWalls 16
1920202122232324
7.3 Staggered Stud SeparatingWalls 26
2829
31313232
7.4 Single Stud SeparatingWalls 337.5 347.6 367.7 Boxed Gutters 38
Intersections between suspended floorsand separating wall
Bearers supported off separating wall
Non-aligned floors
Separating walls above ceilings
Intersections with internal walls
Intersection with brick veneer external wall
Non-aligned external walls
Intersection with lightweight clad external wall.
Intersections between suspended floors andseparating walls
Bearers supported off separating wall
Separating walls above ceilings
Intersection with brick veneer external wall
Non-aligned external wall
Intersection with lightweight clad external wall.
Intersection with internal walls 30
ExternalWallsPlumbing and Electrical Services
MRTFC Class 1a - Design & Construction Manual 1
2 ABBREVIATIONS, DEFINITIONS,TERMINOLOGY
Thefollowingabbreviationsanddefinitionsapplyinthe use of thismanual.
BuildingCodeofAustralia1996-Volume2,
(a) complieswith the deemedto satisfyprovisionsofthe BCAor
(b) is an alternative solutionwhichcomplieswith theperformancerequirements.
BCA
BUILDINGSOLUTION
Class1andClass10 BuildingsHousingProvisions.
A solutionwhicheither:-
SCOP
E
1TE
RMIN
OLOG
Y
2
1 SCOPE
Thismanualcontainsthe timberindustry’srecommendationsfor the designandconstructionoftimberframedClass1a attacheddwellings(duplexes,townhouses,villasetc) andassociatedClass10buildings(carportsetc). It providesinformationonmaterialsandsystemsthathave beendeveloped,aswellas detailsandbuildingpracticesthat are necessaryto satisfythe fire resistance,andsoundcontrolrequirementscontainedin the “deemedto satisfy”provisionof the BuildingCodeofAustralia(BCA96).
Theconstructiondetailsandpracticesincluded,willgenerallycover the majorityof situations. Theyshould,however be regardedas typical,withmodificationspermitted,as longas the requiredfireandsoundperformanceis maintained.
NOTE: This manual describes the requirements forClass 1a attached dwellings and associated Class10abuildings.
NOTE:Buildingswhich containseparate residentialunits above or below one another, as well as side byside or which have common space above or belowdwellings(ie. commonceilingspaces, commonsub-floor space, commercial car parking etc.) areclassified as Class 2 or 3. These are described insupporting publication “MRTFC Design andConstructionManual– Class2 and3 Buildings”.
NOTE: It is not intendedthat this manualprovide anexhaustive statement of all the methods orconstruction details appropriate for this form ofconstruction. Although the majority of systemsavailable at the time of publication have beenincluded, manufacturers will continue to developnew and alternative systems, and practices willinvariably evolve which meet either the deemed tosatisfyorperformancerequirementsof theBCA.
2 MRTFC Class 1a - Design & Construction Manual
CAULKING(FIREGRADESEALANT)
CLASS1
Class1a
Class1b
CLASS10
Class10a
Class10b
DEEMEDTO SATISFYPROVISIONS
DWELLING
FRL- FIRERESISTANCELEVEL
Firegradematerialused to fill gaps at jointsandintersectionsin fire gradeliningsto maintainthe fireresistancelevel (referalso“IntumescentSealant”).
Oneor morebuildings,whichin associationconstitute–(a) – a singledwellingbeing– a detached
house;oroneor moreattacheddwellings,eachbeingabuilding,separatedby a fire-resistingwall,includinga row house,terracehouse,town houseor villaunit;or
(b) – a boardinghouse,guesthouse,hostelorthe like witha total floorareanot exceeding300mand in whichnot morethan12 personswouldordinarilybe resident;
whichis not locatedabove or below anotherdwellingoranotherClassof buildingother thana private garage.
A non-habitablebuildingor structurebeing–
(a) – a non-habitablebuildingbeingaprivate garage,carport,shed,or the like; or
(b) – a structurebeinga fence,mast,antenna,retainingor free-standingwall, swimmingpool,orthe like.
Provisionscontainedin Section3 of the BCAwhicharedeemedto complywith the performancerequirements.
A Class1a building
Thefire resistance,expressedas a time(in minutes)thata structuralmemberor partof a buildingmustachieve withrespectto -
(a) structuraladequacy - (ie. maintainstabilityandadequateloadbearingcapacity)
(b) integrity-(ie. resistpassageof flames,smoke andhot gases)
(c) insulation- (ie. maintaina specified temperatureon the surface not exposedto fire)
andexpressedin thatorder(e.g.FRL60/60/60forseparatingwalls).
NOTE: Caulking material may also need to beflexible to allowfor movementand/orwaterproof forexternalorwetareaapplications.
NOTE:A dash,for examplein 60/ - / - , meansthere isno integrity or insulation requirement for thatmemberorpartof thebuilding
2
NOTE: Class 1a detached houses and Class 1bbuildings (small boarding houses) have no fireresistanceandsoundcontrol requirements.
.
TERM
INOL
OGY
2
MRTFC Class 1a - Design & Construction Manual 3
FIRE-SOURCEFEATURE
FIRESTOP
FIREGRADELINING
HABITABLEROOM
INTUMESCENTSEALANT(INTUMESCENTPUTTY)
MINERALWOOL(FIRERESISTANT)
MRTFC
(a) the far boundaryof a roadadjoiningtheallotment;or
(b) a sideor rearboundaryof the allotment;or
(c) an externalwall of anotherbuildingon theallotmentwhichis not of Class10.
Firegradematerialused to closea gap or imperfectionof fit thatoccurswherea servicepassesthrougha fire-ratedelementor system.
Firegradeplasterboardor a combinationof fire gradeplasterboardand fibrecementusedto provide therequiredFRLin a separatingwall or externalwall.
A roomusedfor normaldomesticactivities,and–
(a) includesa bedroom,livingroom,loungeroom,musicroom,televisionroom,kitchen,diningroom,sewingroom,study, playroom,familyroomandsunroom;but
(b) excludesa bathroomlaundry, watercloset,pantry,walk-inwardrobe,corridor, hallway, lobby,photographicdarkroom,clothes-dryingroom,andotherspacesof a specialisednatureoccupiedneitherfrequentlynor for extendedperiods.
A fire resistantmaterialused in fire gradelinings(atjoints,penetrationsetc)whichexpandswhenexposedto fire to fill and/orsealgaps andmaintainsthe requiredfire resistancelevel.
Compressible,non-combustible,fire resistantmaterialused to fill cavitiesandmaintainthe fire resistanceorrestrictthe passageof smoke andgases.
Multi-ResidentialTimberFramedConstruction.
NOTE: The mineral wool to be used in allapplications in this manual, must be fire resistantand therefore must have a fusion temperature inexcess of 1160°C. ‘Rockwool’ type productsgenerally meet these requirements, whilst‘glasswool’productsdonot.
To maintainFRL 60/60/60 the fire resistant mineralwool must be a minimum width of 120 mm andcompressesto85%oforiginalthickness.
NON-COMBUSTIBLE
PERFORMANCEREQUIREMENTS
RESILIENTCHANNEL/MOUNT
Rw
SEPARATINGWALL(PARTYWALL)
STC(SOUNDTRANSMISSIONCLASS)
SITE
(a) appliedto a material- meansnot deemedunderAS 1530.1-
CombustibilityTests for Materials;and
(b) appliedto constructionor partof a building-meansconstructedwhollyof materialsthatare not deemed .
Requirementsin the BCAwhichstate the level ofperformancewhicha buildingsolutionmustmeet.
Proprietarysupportfor liningsdesignedto improvesoundinsulationand reducesoundtransmission.
(refer“WeightedSoundReductionIndex”)
A wall that is commonto adjoiningClass1a buildings(referFigure1 andSection3.2).
Themethodof ratingthe airbornesoundtransmissionperformanceof a wall or floor/ceilingelementprior to1999.
Thepartof the allotmentof landon whicha buildingstandsor is to be erected.
combustible
combustible
NOTE: Walls that are common to or betweenadjoining buildings other than Class 1(a), or wallsbetween a Class 1(a) building and anotherclassificationare referred to as commonwallsor firewalls (refer “MRTFC – Design & ConstructionManual– Class2 &3 Buildings”).
NOTE:Class1a buildingsmaybe on theirownseparate allotmentwithina group title, communitytitleorTorrens title subdivision(ie. where the separatingwall is on the site boundary).AlternativelyseveralClass1a buildingsmaybe on a singleallotment,witheach dwellingsoldunderBuildingUnitor Strata title.
NOTE: The acoustic ratings required by the BCA(Amendment6 - 1999) are now called the “weightedsound reduction index” with the symbol ,consistentwithAS/ NZS1276.11999.
Test results for buildingsand building elementswithSTC values in accordance with the 1979 version ofAS 1276 remain valid (the STC value being the Rwvalue).
Rw
Theratingof soundinsulationin a buildingor buildingelementas describedinAS/NZS1267.11999.
WEIGHTEDSOUNDREDUCTIONINDEX(Rw)
dwelling 1
dwelling 5
dwelling 10
dwelling 2
dwelling 6
dwelling 11
dwelling 3
dwelling 7
dwelling 12 dwelling 13
dwelling 4
dwelling 9dwelling 8
Parapets above combustible roof
Suspended floor Separating wall continueddown to ground
Attached carports or garages(class 10 a)
Private garages may be underor within class 1a dwelling
Fire rated external wallabove lower roof
Separating wall continued up tounderside of non-combustible roof
FIGURE 1 - TYPICAL CLASS 1a BUILDINGS
External walls to be fire-ratedif within 900 mm of boundary or1800 mm of another building
Fire rated external wall continued upto underside of combustible roofor non combustible eaves lining
TERM
INOL
OGY
2
4 MRTFC Class 1a - Design & Construction Manual
BCAR
EQUI
REME
NTS3
MRTFC Class 1a - Design & Construction Manual 5
3 BCA REQUIREMENTS
3.1 PerformanceProvisions
Structure
DampandWeatherproofing
Fire Safety
HealthandAmenity
SafeMovementandAccess
Thefollowingsummarisesthe BCA’s objectives andperformancerequirementsfor Class1 and10 buildingswithrespectto:
a) - withstandthe combinationof loadsandotheractionsto whichthey maybe reasonablysubjected.
b) – provideresistanceto moisturefromthe outsideandmoisturerisingfromthe ground.
c) – protectbuildingsfromthe spreadoffire andprovidesafeguardsso thatoccupantsmaysafelyevacuate.
d)
i) WetAreasnot to createunhealthy or dangerousconditions
ii) Roomheightsto be suitablefor the intendeduse
iii)Providefacilitiesfor personalhygiene,laundering,foodpreparationandcooking
iv) Provideadequatenaturalandartificial light
v) Provideadequateventilation
vi) Prevent unduesoundtransmissionbetweendwellings.
e)
i) Providesafeaccessto andwithinthe building
ii) Restrictaccess(youngchildren)to swimmingpools.
A buildingsolutionmustsatisfyall of the performanceprovisionsof the BCA. Thebuildingmayeithersatisfythe “deemedto satisfy”provisionsof the BCA(andasdescribedin the manual)or be an “alternative solution”whichcan be shown to satisfythe performanceprovisions.
NOTE: For guidance on gaining approval for analternative solution using the performanceprovisions of the BCA refer to MRTFC InformationBulletinNo.2.
3.2 Deemedto SatisfyProvisions
fire separationbetweendwellings
soundcontrol betweendwellings
TheBCAcontains“deemedto satisfyprovisions”thatare acceptableformsof constructionwhichcomplywith the performancerequirements.Thesimplestwayto obtainapproval or certificationfor a projectis tocomplywith the deemedto satisfyprovisions.
For attachedClass1a MRTFCprojectsthe majorityofthe deemedto satisfyrequirements(as wellas theperformanceprovisions)are the sameas therequirementsfor detachedhouses. The requirementsare the samefor:-
• structuraldesign(useAS 1684-1999‘ResidentialTimberFramedConstruction)
• dampandweatherproofing
• kitchensand wetareas
• roomsizesandheights
• lightandventilation
• safeaccess.
TheBCArequirementsfor attacheddwellingswhichare in additionto or differentfromthosefor detacheddwellingsare:-
(a) - separatingwalls mustbe of fire resistingconstruction.Externalwalls mustalsobe fire resistingif closeto aboundaryor anotherbuilding.
(b) - separatingwalls must reducesoundtransmission(noise).
NOTE:Thismanualcontainstimberframedsystems,construction details and building practices whichsatisfy the “deemed to satisfy” fire separation andsoundcontrol requirementsof theBCA.
BCA R
EQUI
REME
NTS3
3.3 SeparatingWalls
To satisfythe BCAdeemedto satisfyfire andsoundrequirements,separatingwalls betweenClass1adwellingsshall:-
(a) be continuousfromfooting(or concreteslabonground)to undersideof non-combustibleroofcoveringor 450mmabove combustibleroof.(refer Figure1).
(b) have a fire resistancelevel not less thanFRL60/60/60(-/60/60if non-loadbearing)(referSection5.1)
(c) not be crossedby timbermembers(or othercombustiblebuildingelements)other thanroofbattens(maximumsize75 x 50 mm).
(d) have any void betweentop of wall andundersideofroofing (ie. betweenbattens)filledwithsolidtimber, fire resistantmineralwool or othersuitablefire resistingmaterial.
(e) extendthroughto the outsideof externalwalls(ie. have cavities in brickveneerexternalwallspacked withfire resistantmineralwool, solidtimberblockingor othersuitablefire resistingmaterial- (referFigure16).
NOTE: All intersectionsmust be constructedso thatin the event of fire, floors, ceilings, roof, internalwalls etc (within the dwelling on fire) are able tocollapsebut leavetheseparatingwallintact.
NOTE: Cavities to be maximum 50 mm width.flashing, dpc etc to be provided to maintainweatherproofingwhere cavitiesare packed.
NOTE: The above BCA sound requirements shouldbe regarded as minimum regulatory standards.Higher levels of sound resistance are recommendedtosatisfyconsumerexpectations.
(f) extendthroughto the outsideof andeffectivelyseparatevoids in boxed eaves etc (referFigure30).
(g) have a soundtransmissionclassof not less than:-
i) Rw 45 betweenhabitableroomsin adjoiningdwellings.
ii) Rw 45 betweenkitchensor wetareas inadjoiningdwellings.
iii)Rw 50 (as wellas resistanceto impactsound)betweena kitchen,bathroom,WCor laundryinonedwellinganda habitableroomin anadjoiningdwelling.
Boundary
dwelling 1
dwelling 2 dwelling 3
dwelling 4
Walls within 1800 mm of anotherbuilding to have FRL 60/60/60
The portion of thewall within 900 mmof boundary FRL60/60/60
Wall within 900 mm ofboundary measured atright angles to have FRL 60/60/60
Note:These portions of wall notrequired to be fire rated becausethey are greater than 900 mmfrom boundary and greater than1800 mm from other buildingsmeasured at right angles
Note: These walls not requiredto be fire rated because they aregreater than 900 mm fromboundary and greater than1800 mm from other buildingsmeasured at right angles
1800 mm
900mm
900mm
FIGURE 2 - FIRE RESISTING EXTERNAL WALLS
6 MRTFC Class 1a - Design & Construction Manual
3.4 ExternalWalls
In all statesexceptSouthAustralia,externalwalls inClass1a buildingsare requiredto be fire-resistingifless than900mmfromrearor sideboundariesor lessthan1800mmfromanotherbuilding.Theclearancesare measuredat rightangles(90°) to eithertheboundaryor the externalwall of anotherbuilding(referFigure2).
Fire resistingexternalwalls musthave a fire resistancelevel not less thanFRL60/60/60whenmeasuredfromthe outside.( - /60/60if non-loadbearing).
Fire resistingexternalwalls mustextendto theundersideof a non-combustibleroofcoveringor to anon-combustibleeaves lining(referFigure27).
Openings(doors,windows etc) in fire resistingexternalwalls mustbe protected.
The followingare regardedas beingprotected:-
(a) self closingsolidcoredoors
(b)non-openablefire windows (FRL- /60/ -) tohabitablerooms.
(c) maximum900x 600mmwindows withsteel frameandno openingsashesto non-habitablerooms.(Note: Canbe permanentlyvented).
(d)Translucenthollow glassblocks.
NOTE: State and Local authorities throughoutAustralia may have planning regulations whichcontaindifferentsitingrequirements.
TheSouthAustralianHousingCoderequires: -
External walls (including those at an angle orperpendicular to the boundary) of a Class 1abuilding within 600 mm of the allotment boundary,or within 1200 mm of another building on the sameallotment, shall be of fire-resisting construction tothe underside of non-combustibleroof liningor non-combustible eaves lining to resist the spread of firefrom the outsideexcept where protectedby a wall offire-resistingconstruction(e.g. a ‘wingwall’).
NOTE: Fire rated external walls in Class 1abuildings do not require fire resistance from theinside.
NOTE: Eaves soffit lining must be non-combustiblebut it is not required to be fire rated or have a fireresistance level. Normal fibre cement products areacceptable.
3.5 RoofLights
3.6 SmokeAlarms
Rooflights,(skylightsetc)whichcontaincombustiblematerial,maybe installedin a roofwhichis requiredtohave a non-combustiblecoveringprovided:-
(a) the areaof the roof light is not morethan20%of theroofarea
(b)the roof light is not less than900mmfromtheallotmentboundary
(c) the roof light is not less than900mmfromtheverticalprojectionof any separatingwall whichextendsto the undersideof the roofcovering
(d)the roof light is not less than1.8 m fromany rooflight in anotherbuildingon the allotment.
TheBCArequiresthat all Class1a buildingshaveautomaticsmoke alarmsinstalled.
Smoke alarmsmustcomplywithAS 3786andbeconnectedto mainspower.
Alarmsshallbe installedon or near the ceiling(at leastonealarmper storey), locatedbetweeneachpartof thedwellingcontainingbedroomsand the remainderof thedwelling.
NOTE: Where any of these limitationsare exceeded,the roof covering is regarded as combustible.Separating walls would therefore be required toproject450mmabove theroof.
NOTE: The intention of smoke alarms is to detectsmoke before it reaches sleeping occupants, wakethem,andgivethemtimetoevacuatetosafety.
BCAR
EQUI
REME
NTS3
MRTFC Class 1a - Design & Construction Manual 7
4 STRUCTURAL REQUIREMENTS
4.1 TimberMemberDesign
4.2 Noggings
4.3 Notches,Cuts,Holes
Timbermembersizesfor Class1(a)buildingsshallbedeterminedin accordancewithAS 1684-1999ResidentialTimberFramedConstruction.
In separatingwalls and fire ratedexternalwalls thestudsandplatesshallalsobe the sizedeterminedfromAS 1684.Theminimumsizeof studsshallbe 70 x 45mmor 90 x 35 mmstudsin loadbearingseparatingwalls.70 x 35 mmstudscan onlybe usedin non-loadbearingseparatingwalls.
Thestudspacingin separatingwalls and fire ratedexternalwalls shallnot be greaterthan600mm.
Timberspeciesshallhave an averagedry densityof notless than450kg/m .
(Note: Normalsoftwood,cypressandhardwoodframingmaterialmeetsthis requirement).
Noggingsshallbe providedin all loadbearingwalls at amaximumspacingof 1350mm.Noggingsmaybestaggered(by up to the noggingdepth).
Wherever possible,notches,cutsandholesshouldbeavoidedin structuralmemberswithinfire ratedwalls.Wherethesecannotbe avoided,sizesandspacingsshallbe limitedto thoseinAS 1684 - 1999.
3
NOTE: To achieve satisfactorysound performancein double stud and staggered stud walls, noggingsbetween studs supporting linings to one dwellingmust be kept clear of studs and nogging supportingthe linings to the adjoiningdwelling(refer Figures 9and19).
STRU
CTUR
ALRE
QUIR
EMEN
TS
4
Stud
Stud depth
(D)
Bottom plate
E
E
F
A
A
B
Stud width
(W)
C
P
FIGURE 3 - CUTS, NOTCHES AND HOLES.
TABLE A CUTS, HOLES AND NOTCHES IN STUDS ANDPLATES
DESCRIPTION LIMITS
A Distance between holesand/or notches in studbreadth Minimum 3 x D
H Hole (studs and plates) Maximum 25 mm inwide face only
C Notch into stud breadth Maximum 10 mm
E Notch into stud depth • Maximum 20 mm atevery fifth stud
• Maximum 20 mm fordiagonal bracing
• Up to 25 mm forinstallation of bath
• Not permitted where studsare designed as “notnotched”
F Distance betweennotches in stud depth Minimum 12 x B
P Trenches in plates 3 mm maximum
8 MRTFC Class 1a - Design & Construction Manual
FIRES
EPER
ATION
5
5 FIRE SEPARATION
5.1 Fire ResistanceLevel
Separationwalls betweenClass1 attacheddwellings,mustbe constructedto limit the spreadof fire andallowthe occupantsto safelyevacuate. The level of fireresistancerequiredby the BCAis for the separatingwall to remainstructurallyintactandnot allow thepassageof flame,heat, smoke andhot gases for aperiodof at least1 hour. This fire resistancelevel isexpressedas FRL60/60/60(or FRL- /60/60for non-loadbearing).
WhereClass1 buildingsare within900 mmof a sideorrearboundary, or closerthan1800mmto anotherbuilding(In SouthAustralia,within600mmofboundaryor within1200mmof anotherbuilding),externalwalls also requirea fire resistancelevel ofFRL60/60/60(or - /60/60for non-loadbearing). TheFRLfor an externalwall onlyrequiresto be measuredfromthe outside.
To achieve the fire resistancelevel in timberframedwalls, fire gradeliningsare fixed to studswithalljoints, intersectionsandpenetrationssealed.
Liningmanufacturers(in associationwith the timberindustry)have developedvarioussystemswhichhavebeentestedandcertified by recognisedtestingauthorities(CSIRO or BRANZ). FRL60/60/60separatingwalls have eithera singlelayerof 16 mmthickfire gradeplasterboardeachside,or a layerof 13mmfire gradeplasterboardplusa layerof 6 mmfibrecementto bothsides. (Manufacturer’srecommendationsfor fixingsheetsmustbe strictlyadheredto).
To ensurethe fire resistanceis maintainedat joints,intersectionsandpenetrations,the variousbuildingpracticesanddetailscontainedin thispublicationshouldbe followed(referSection7).
MRTFC Class 1a - Design & Construction Manual 9
FIRE S
EPER
ATION
5
10 MRTFC Class 1a - Design & Construction Manual
5.2 SolidTimberat Intersections
Many of the constructiondetailsin thismanualincorporateadditionalsolid timber(blockingor extrastuds, joists,etc.) in lieuof the fire gradeliningtoprotectthe timberframeandmaintainthe fireresistancelevel at intersectionsetc. Thissystemhasbeendevelopedto simplifyandspeedup theconstructionprocessby allowingall framingto becompletedand roof installedbeforefixingplasterboardlinings.
NOTE: Whentimberburns,it chars relativelyslowlyfrom the outside at a predictable rate. This allowsadditional,sacrificial timberto be used in lieu of firegradelining, toprotectstructuralmembers.
To maintainFRL60/60/60at intersectionsa minimumof 45 mmthicknessof solid timber(minimumaveragedry densityof 450kg/m ) is required. This is inadditionto any structuralmemberwithinthe fire ratedwall.
Figure4 shows typicaljunctionswhere45 mmthicknesssolid timberis used in lieuof fire gradelining.
3
NOTE: The timber used to maintain the FRL cannotcarry out a structural function within the separatingwall. It can however be used to support non-ratedfloors or partitions. No additional fixing is required(for ledgers etc.) other than required to support loads.
NOTE: Any timber grade and species (hardwood,softwood, LVL) commonly used for framing has anaverage drydensityin excessof 450kg/m andcanbeusedforblocking.
3
FIGURE 4 - TYPICAL JUNCTIONS WITH ADDITIONAL SOLID TIMBER
1 x 45 or 2 x 35 mm studs tomaintain fire resistance where
fire grade linings do notcontinue through intersection
Fire grade linings
Non-rated partition
Non-rated timber floor
Fire grade linings
Separating walls(double studs or staggered studs)
Separating walls(double studs or staggered studs)
Additional 45 mm thick joist, ledger, trimmeror blocking to maintain fire resistance
Nogging tosupport edgeof lining Joist/bearer to support upper wall
4(a) - Typical intersections between separating wall and internal partition
4(b) - Typical intersections between separating wall and timber floor
Caulking
FIRES
EPER
ATION
5
35 mm x 35 mm plasterers’ angle
Intumescent sealant
Fire grade plasterboard
Fibre cement lining continuousthrough intersection
Studs positioned tosupport angles
Studs behind sealant
Noggings or topplate to supportedge of lining
Noggings on top plate
Noggings at 600 mmmaximum centres if studsare not at intersection
5(a) - Using 35 x 35 mm Plasterer’s angles
5(b) - Using intumescent sealant
5(c) - Using continuous fibre cement lining
MRTFC Class 1a - Design & Construction Manual 11
5.3 StrengthenedJoints
Wherethe intersectionbetweenthe fire gradeliningsisstrengthenedby either:-
• 35 x 35 mmplasterer’s angle
• intumescentsealeror
• fibrecementliningcontinuedthroughjoint
Thenthe thicknessof solid timberto maintainFRL60/60/60can be reducedto 35 mm. Figure5shows typicalintersectionswhichhave beenstrengthenedandallow the use the reducedtimberthickness.
FIGURE 5 - STRENGTHENED JOINTS
Caulking
Caulking
SOUN
DCO
NTRO
L
6
6 SOUND CONTROL
6.1 WeightedSoundReductionIndex(Rw)
TheBCArequiresthe weightedSoundReductionIndex (Rw)and the resistanceto impactin separatingwalls as shown in TableB.
TABLE B BCA REQUIREMENTSRw AND SOUND IMPACT LEVELS FORSEPARATING WALLS
NOTE: The BCA requirements for sound controlbetween dwellings listed above should only beregarded as the absoluteminimumto meet statutoryrequirements. It is recommendedthat a minimumofRw50 be providedandresistanceto impactsoundbeconsidered in all separating walls. Rw 50 withimpact resistance is considered necessaryto reduceairborneand structure borne noise to an acceptablelevel.
Test results for buildings or building elements withSTC values in accordance with the 1979 version ofAS 1276 remain valid.The STC value is the same astheRwvalue.
COMMENTARY:
Thereare two typesof soundswhichneedto becontrolled. Theseare fromairbornesourcessuchas speech,musicalinstrumentsand loudspeakersand the otherbeingimpactsources,suchasfootstepsand the movingof furniture.
Soundtransmissioncan be reducedby:-
Increasingmasscan be achieved byincreasingliningthicknessor densityor usingmorelayersof linings.
Oneof the mosteffective ways of reducingsoundtransmission(airborneand impact)isto isolatethe wall surfacesof adjoiningdwellings. This is achieved throughthe use ofdoublestudor staggeredstudwall.
Fillingthe cavitywithabsorptive insulationmaterial(cellulosefibre,glassfibreormineralwool)can reduceairbornetransmissionsubstantially, especiallywhenthe cavity is large.
Soundleakscan easilyoccurat the peripheryof walls and floors,or wherea hole is madefor electricityor plumbingservices. Toreducesoundleaks,all gaps in a wall or floormustbe thoroughlycaulked, or sealed.
Oneof the simplestmeansof controllingnoiseis to distancenoisesourcesfromsensitive receivingareas. Laundries,serviceshafts,stairsandothernoisyareas inbuildingsshouldbe locatedas far as possiblefromsensitive livingor sleepingareas.Placingrelatively quietareassuchasbedroomsor loungeroomsnext to eachotheralsohelpsto minimisethe noisereductionrequiredfor occupantsatisfaction. Care isrequiredin locatingthe windows to ensurethey do not face noisyareasand that there isadequateseparationbetweenwindows inadjoiningdwellings.
• IncreasingMass
• UsingCavityConstruction(Isolatingwallsurfaces)
• UsingAbsorptive Material
• Sealing/CaulkingVoids
• BuildingLayout
• AvoidingRigidConnections
Rigidconnectionsbetweenadjoiningdwellingscan transmitsoundenergy. Whereconnectionsare requiredfor structurestabilityetc., resislientconnectorsshouldbeused.
12 MRTFC Class 1a - Design & Construction Manual
LOCATION IMPACT RwSOUND LEVEL
RESISTANCE
SEPARATING WALLS
SOIL AND WASTE PIPES
(a) Between a bathroom,sanitary compartment,laundry or kitchen in one Required 50Class 1 building and ahabitable room (other thana kitchen) in an adjoiningClass 1 building.
(b) All other separating walls. Not Required 45
A waste pipe or otherpenetration that serves orpasses through a separatingwall between houses –(a) If the adjacent room is a
habitable room (other thana kitchen); or Not Required 45
(b) if the room is a kitchen orany other room. Not Required 30
SOUN
DCO
NTRO
L
6
Adjacent studs to alignwith opposite sides
Lining fixed toevery second stud
6(b) - Staggered stud walls
Resilient channels ormounts when requiredfor sound insulation
6(c) - Single stud walls
FIGURE 6 - WALL FRAMING OPTIONS
MRTFC Class 1a - Design & Construction Manual 13
Studs are not requiredto be in line
6(a) - Double stud walls
Two walls separatedby cavity (minimum20 mm recommended)
6.2 Wall FramingOptions
For separatingwalls betweendwellingsit isrecommendedthatdoublestudor staggeredstudsystemsbe used(referFigure6).Theseare the onlysystemswhichprovideadequateresistanceto impactsoundas wellas airbornesound.
Singlestudwalls shouldonlybe usedin situationswheresoundcontrolis not critical,suchas in spaces,below sub-floorsor betweengarages.
Wheresuspendedfloorsin adjoiningunitsare atdifferent levels, it is recommendedthatonlydoublestudwall systemsbe used(referFigure13).Satisfactoryimpactsoundresistancecannotbeachieved withstaggeredstudwalls or singlestudwalls(even withresilientchannels)wherefloorsare non-aligned.
Note: The variouswall systemsand fire grade liningoptionsare summarisedin tablesC,D and E. Liningsto be fixed in accordance with manufacturersrecommendationsandasoutlinedinSection8.
CONS
TRUC
TION
&DE
TAILS
7
Nogging NoggingJoists, trimmer ledger45 mm minimum thick
45 mm thick blockingor fire grade liningbetween bearers
Note:All details suitable for double stud orstaggered stud separating walls
Additional joists 45 mmminimum thick
Minimum45 mm thickblocking
Bearer
Joist
Bearer may be either sheeted with2 x 13 mm fire grade plasterboard
or additional 45 mm thicktimber blocking
Joists and bearers totransfer loads from
separating wall to masonry
7(a) - Masonry wall taken up to joists
7(b) - Masonry wall taken up to bearers
7(c) - Separating wall supported off masonry wall
7 CONSTRUCTION DETAILSAND BUILDING PRACTICE
Masonry wall minimum 90 mm widewith attached piers
Additional joists 45 mmminimum thick to maintainfire resistence
Joists as required to transfer loadsfrom separating wall to masonry
Termite barriers(through or overmasonry wall)
Additional 45 mm thick trimmer or blockingto maintain fire resistence
JoistSolid timber as requiredto transfer loads fromseparating wall tomasonry
FIGURE 7 - MASONRY SUB-FLOOR SEPARATING WALLS
To satisfy the BCA requirements and meet consumerexpectations the following details and practicesshould be adopted.
14 MRTFC Class 1a - Design & Construction Manual
Caulking
Sawcut
Bearer Bearer
Bearer
Caulking Caulking
Caulking
Sawcut
Caulking
Sawcut
Caulking
Sawcut
Caulking
Sawcut
Caulking
Sawcut
Caulking
SawcutSawcut
Caulking
CONS
TRUC
TION
&DE
TAILS
7
45 mm thick blocking
Bearer
Joist
Single stud wall between posts(termite resistant framing
below termite barrier)
75 mm
Timber sole plate
DPC
45 mmminimumthick joistsor ledger
Minimum 45 mm thickblocking, ledgeror trimmer
Joist
Joist supportedoff hangers or ledgers
Solid timber or framing to transfer wall loads to sub-floor wall
Structural post orpier (timber, brick or masonry)
Additionalblocking(minimum45 mm thick)
Solid timber totransfer wall loadsto sub-floor wall
Additional45 mm thick joist
Note:This detail only to be usedwhere no termite hazard exists
8(b) - Separating wall (double or staggered studs) supported off footing
8(a) - Single stud wall between concrete or masonry piers
FIGURE 8 - TIMBER FRAMED SUB-FLOOR SEPARATING WALLS
7.1 Sub-FloorSeparatingWalls
Separatingwalls mustbe continuousfromthe groundto the undersideof a non-combustibleroofor 450mmabove a combustibleroof. Walls below suspendedgroundfloorsmaybe masonry(referFigure7) ortimberframedwithfire gradelining(referFigure8).
Timberframedsub-floorseparatingwalls maybe eitherloadbearingextensionsof the separatingwall above, oralternatively non-loadbearinginfill walls betweenstructuralpiers.
MRTFC Class 1a - Design & Construction Manual 15
Either 2 x 13 mm thick fire gradeplasterboard or additional 45 mm
thick timber to protect bearer
Caulking
Sawcut
Caulking
Sawcut
Caulking Caulking
Sawcut
Caulking
Sawcut
Caulking
1 x 16 mm fire grade plasterboard or1 x 13 mm fire grade plasterboard plus
6 mm fibre cement to both sides
CONS
TRUC
TION
&DE
TAILS
7
Note:Refer figure 11-13 for floorintersections and figure 14for roof/ceiling intersections
Fire grade linings
Nogging may be staggered for2 layer linings or where singlelayer linings are fixed vertically
Acoustic insulation may beprovided (either betweenstuds in one leaf or in wallcavity)
5 - 10 mm gap below lining(refer manufacturer’srecommendation) gaps tobe caulked
20 mm minimum cavity toachieve Rw listed in table C
Overall width refer table C
Lining optionsa. 6 mm fibre cement plus 13 mm fire grade plasterboard
both sides (fibre cement may be inner or outer layer)
b.16 mm fire grade plasterboard to both sides(13 mm in non-load bearing walls)
Studs
600 mm max c/s
Opposing studs in thetwo leaves may bein-line or offset
FIGURE 9 - DOUBLE STUD WALLS (FRL 60/60/60)
7.2 DoubleStudSeparatingWalls
Separatingwalls maybe constructedwith twoindividualstudframedwalls (referFigure9 andTableC).
Intersectionsmustbe constructedto maintainthe fireresistancelevel andsoundperformance. Thefollowingtypicaldetailsshow recommendedbuildingpracticefor doublestudseparatingwalls:-
Figure10 - Two storey doublestudwalls
Figure12 - Bearerssupportedin separatingwall
Figure13 - Non-alignedfloors
Figure14 - Separatingwalls above ceilings
Figure15 - Intersectionswith internalwalls
Figure16 - Intersectionwithbrickveneerexternalwall
Figure17 - Non-alignedexternalwalls
Figure18 - Intersectionwith lightweightcladexternalwall.
NOTE: Complete isolation of the two structuralframes in double stud walls provides the bestairborneandimpactsoundresistance.
Figure9 - Doublestudwalls (typical)
Figure11 - Intersectionsbetweensuspendedfloorsandseparatingwall
16 MRTFC Class 1a - Design & Construction Manual
Note:Refer figure 15-18or wall intersections
CONS
TRUC
TION
&DE
TAILS
7
MRTFC Class 1a - Design & Construction Manual 17
TABLE C DOUBLE STUD WALLS FRL 60/60/60
Fire Grade Linings Studs Nominal Rw Overall Width(minimum size) Insulation (refer notes) (20 mm cavity)
One layer 16 mm fire grade 90 x 35 mm @ 50 mm 53 - 55to plasterboard both sides. 600 mm max. centres. 232 mm
Nil 47
(loadbearing or non-loadbearing walls) 70 x 45 mm of 50 mm 50 - 52600 mm max. centres 192 mm
(See Note 3)Nil 46
One layer 13 mm fire grade plasterboard 90 x 35 mm a 50 mm 53 - 55to both sides. 600 mm max.centres 226 mm
Nil 45
(non-loadbearing walls only) 70 x 35 mm at 50 mm 50 -52600 mm max. centres 186 mm
Nil 45
6 mm fibre cement plus 13 mm fire grade 90 x 35 mm @ 50 mm 58 -61plasterboard to both sides. 600 mm max. centres 238 mm
Nil 53 - 54
(See Note 4) 70 x 45 mm @ 50 mm 57 - 59600 mm max. centres. 198 mm
(70 x 35 mm innon-loadbearing walls) Nil 51 - 52
NOTES: 1. All of the above have “satisfactory resistance to impact sound”.2. The nominal Rw ratings listed are based upon a 20 mm cavity between walls with acoustic insulation (where listed)
50 mm thick polyester 350 kg/m . Different thicknesses and types of insulation will alter Rw values.(Refer lining manufacturer for actual tested Rw values).
3. 70 x 35 mm studs are not allowed in loadbearing fire rated walls.4. The fibre cement can be either the first layer (against the studs) or the second layer.
3
18 MRTFC Class 1a - Design & Construction Manual
CONS
TRUC
TION
&DE
TAILS
7
Nogging behind edgeof lining
Studs continuous forfull 2 storey height
Resilient structuralconnections atmid floor level
Note:Isolating stairs fromwall provides superiorsound performance
10(a) - Studs continuous for two storeys
FIGURE 10 - TWO STOREY DOUBLE STUD WALLS
Caulking
Blocking or framing to transferupper wall loads to lower wall
Note:For load-bearing walls orwhere length of 2 storeywall exceeds 3.5 metresadditional lateral restraintmay be required
10(b) - Upper wall supported off lower wall
Caulking
Note:Isolating stairs fromwall provides superiorsound performance
Resilient structuralconnections atmid floor level
45 mm thick ledger
Note:For load-bearing walls orwhere length of 2 storeywall exceeds 3.5 metresadditional lateral restraintmay be required
CONS
TRUC
TION
&DE
TAILS
7
MRTFC Class 1a - Design & Construction Manual 19
45 mm thicksolid timber
45 mm thickledger
Floor trussI beam etc.
Additional 45 mm thickjoists or ledgers to
maintain fire resistence
45 mm thick or 35 mm iffibre cement continued
through intersection
Fibre cementmay continuethrough
Note:In all cases, floors must be able to collapse in theevent of fire and leave the separating wall intact.
Joist
Joist
Joist hangeror angle
Joist hangeror angle
Top chord msupported off ledger
ay be
Joists to transfer loadfrom upper wall to
lower wall
Upper wall supported directlyoff lower walls
Fire grade linings(all layers) mustcontinue throughintersection or 45 mmthick solid timber providedto maintain fire resistence
FIGURE 11- INTERSECTIONS BETWEEN SUSPENDED FLOOR AND SEPARATING WALLS
11(b) - Joists perpendicular to separating walls11(a) - Joists paralled to separating walls
Caulking
Sawcut
Caulking
Sawcut
Caulking
Sawcut
Caulking
Sawcut
CaulkingCaulking
CaulkingCaulking
Caulking
Caulking
20 MRTFC Class 1a - Design & Construction Manual
CONS
TRUC
TION
&DE
TAILS
7
Bottom plate
Bottom plateupper wall
Top platelower wall
Nogging(45 mm thick)
45 mm thickjoists
Bearer
Slope top of bearerto allow rotation in theevent of collapse
Compressedmineral wool
Top platelower wall
Compressedmineral wool
Studs each side ofbearer to supportwall plates(45 mm thick)
Bearer
Fire grade liningsealed against bearer
Posts/joists directlybelow to supportbearer
Note:Upper wall must notbe supported off bearers
Note:Any of the floor intersection detailsfor double stud walls are suitablefor non aligned floors (refer figure 11).
Note:Staggered stud and single studwalls do not provide satisfactorilysound performance where floorsare non-aligned.
Additional 45 mm thick timberto maintain fire resistence
FIGURE 12 - BEARERS SUPPORTED OFF SEPARATING WALL
FIGURE 13 - NON-ALIGNED FLOORS
12(a) - Section / Elevation 12(b) - Plan view
Caulking
Sawcut
Caulking
Sawcut
CONS
TRUC
TION
&DE
TAILS
7
MRTFC Class 1a - Design & Construction Manual 21
Notes:1. Additional ledgers/battens may be required to
support ceilings.
2. Top of wall cavity may need to be sealed to preventmoisture from entering cavity during construction.
3. These details are also suitable above staggeredstud walls.
Compressed fire resistantmineral woolbetween battens
Cavity between top ofwall and underside ofroof to be filled withcompressed fireresistant mineral wool
Ceiling
Double stud orstaggered studwalls
Fire grade liningmay continuethrough
45 mm thickledger
Single studwall
Truss
Two nailed gable trusses.Vertical truss members atmaximum 600 mm centres
Fire grade liningsas for separatingwall
Nogging tosupportedge oflining
Compressed fire resistant mineral woolbetween roof battens
70 mm minimumwidth betweenlinings
Compressed mineralwool to fill irregularitiesbetween truss and wall
14(b) - Separating wall continued up to roof
Figure 14(a) - Single stud wall
14(c) - Sheeted trusses
FIGURE 14 - SEPARATING WALLS ABOVE CEILINGS
Note:Refer to trussmanufacturers forminimum bearingrequirements
Batten(where required)to support ceiling
22 MRTFC Class 1a - Design & Construction Manual
CONS
TRUC
TION
&DE
TAILS
7
Fibre cement first layercontinuous through joint
Minimum 35 mm thick studNogging at 600 mmspacing where no studsat intersecting wall
Fire grade lining continuousthrough joint
Nogging at 600 mmspacing where no studsat intersecting wall
15(a) - Fire grade linings continuous
Additional studsto fix linings
Additional stud
2 x 35 mm or 1 x 45 mm studs tomaintain fire resistence.
1 x 35 mm or 1 x 45 mm if jointreinforced with plasterers angle orintumescent sealant (refer figure 5)
15(b) - First layer (fibre cement) continuous
15(c) - Studs in intersecting wall used to maintain fire resistance
FIGURE 15 - INTERSECTIONS WITH INTERNAL WALLS
CONS
TRUC
TION
&DE
TAILS
7
MRTFC Class 1a - Design & Construction Manual 23
Additional studs tosupport wall linings
Fire grade lining
Compressed mineralwool to fill cavity
Vertical DPC
DPC andfire-stoppingif required
Fire grade linings continuedthrough to brickwork
Additional studs tosupport wall linings
Fire grade lining
45 mm thick solid timber blocking
Vertical DPC
16(a) - Cavity blocked with timber 16(b) - Cavity filled with mineral wool
16(c) - Fire grade linings continued across cavity
FIGURE 16 - INTERSECTION WITH BRICK VENEER EXTERNAL WALL
dpc
Cavities blocked withmineral wool or solidtimber 45 mm thick)
Fire grade lining
Minimum45 mm thick
See note
Note:Although fire grade linings are not requiredin external walls, the linings would normallybe extended to the next intersection orconstruction joint
FIGURE 17 - INTERSECTION WITH NON-ALIGNED EXTERNAL WALL
Wall plate not to be continuousacross separating wall
Wall plate not to be continuousacross separating wall
Wall plate not to be continuousacross separating wall
24 MRTFC Class 1a - Design & Construction Manual
CONS
TRUC
TION
&DE
TAILS
7
Additional studs tosupport wall linings
Fire gradelining
Compressed fire resistant mineral woolto fill any voids in external cladding(e.g. lapped weatherboards)
Minimum45 mm
thickstuds
Cladding
Breathertype
sarking
Note:Top and bottom plate to externalwall not to continue acrossseparating wall
Cladding
Mineralwool
Breathertype
sarking
18(a) - Non rated external wall
FIGURE 18 - INTERSECTION WITH LIGHTWEIGHT CLAD EXTERNAL WALL
CONS
TRUC
TION
&DE
TAILS
7
MRTFC Class 1a - Design & Construction Manual 25
Additional studs tosupport wall linings
Fire grade lining
Fire grade lining
45 mmthick studs
Cladding
Breathertype
sarking
Cladding
Breathertype
sarking
Note:Top and bottom plate to external wallnot to continue across separating wall
Fire grade lining
Note:Any external cladding materials(e.g. Timber weatherboards)may be used over the top offire grade linings in fire ratedexternal walls
Figure 18(b) - External wall FRL 60/60/60(measured from outside only)
CONS
TRUC
TION
&DE
TAILS
7
Full width top plate (refer table D)
Full width bottom plate
Noggings kept clear of studswhich support lining toadjoining dwelling
Fire grade linings
35 mm thick noggings onedge between alternate studs
5 - 10 mm gap below lining(refer manufacturer’srecommendation) gap to becaulked
Overall width (refer table D)
Note:Figures 23, 25, 26 & 27for wall intersections
Note:Refer figures 20,21,22 & 24 forfloor and ceiling intersections
600 mm
300 mm 300 mm
Lining optionsa. 6mm fibre cement plus 13 mm fire grade plasterboard
both sides (fibre cement may be inner or outer layer)
b. Single layer fire grade plasterboard both sides (16 mmfor loadbearing walls, 13 mm for non-loadbearing walls)
Nogging betweenalternate studs
FIGURE 19 - STAGGERED STUD WALLS (FRL 60/60/60)
7.3 Staggered StudSeparatingWalls
Separatingwalls maybe constructedusinga singletopandbottomplate(120mmor 140mmwide)withalternatestudsstaggeredto alignwithoppositeedges.Firegradeliningsare fixed to alternatestuds. (referFigure19 andTableD).
Isolationof the structuralframe(exceptfor plates)providessatisfactoryresistanceto impactsoundaswellas airbornesound.
The followingtypicaldetailsshow recommendedbuildingpracticefor staggeredstudseparatingwalls tomaintainfire resistanceandsoundperformance:-
Figure21 - Intersectionsbetweensuspendedfloorsandseparatingwalls.
Figure22 - Bearerssupportedoff separatingwall.
Figure23 - Separatingwalls above ceilings.
Figure24 - Intersectionswith internalwalls
Figure25 - Intersectionwithbrickveneerexternalwall.
Figure26 - Non-alignedexternalwall.
Figure27 - Intersectionwith lightweightcladexternalwall.
NOTE: Staggered stud walls are not recommendedfor separating walls between units where floors arenotaligned. Satisfactorysoundperformancecannotbeachievedat floorintersections. Doublestudwallsare recommendedfornon-alignedfloors.
Figure19 - Staggeredstudwalls (typical)
Figure20 - Two storey staggeredstudwalls
26 MRTFC Class 1a - Design & Construction Manual
Caulking
CONS
TRUC
TION
&DE
TAILS
7
Nogging behind edgeof lining
Studs continuous for2 storeys
Resilient structural connectionsat mid floor level
Note:For loadbearing walls or wherelength of two storey wall exceeds3.5 metres additional lateralrestraint may be required
Note:Isolating stairs fromwall provides superiorsound performance
Refer figure 21 & 22 forintersection details
Full width top andbottom plates providelateral restraints
TABLE D STAGGERED STUD WALLS FRL 60/60/60
Fire Grade Linings Nominal Rw Studs Top and OverallInsulation (refer notes) (minimum size) bottom plates Width
One layer 16 mm fire grade 50 mm 49 - 51 90 x 35 140 x 35 172 mmto plasterboard both sides.
(loadbearing or non-loadbearing walls) Nil less than 45 90 x 35 120 x 35 152 mm(see Note 2)
less than 45 70 x 45 120 x 35 152 mm
One layer 13 mm fire grade plasterboard 50 mm 45 - 47 90 x 35 or 120 x 35 146mmto both sides. 70 x 35
(non-loadbearing walls only) Nil less than 45 (see Note 4)
6 mm fibre cement plus 13 mm fire grade 50 mm 56 - 57 90 x 25 140 x 35 178 mmplasterboard to both sides.
(See Note 5) Nil 50 120 x 35 158 mm(see Note 2)
50 mm 55 - 56 70 x 45 120 x 35 158 mm
Nil 49
NOTES: 1. All the above have “satisfactory resistance to impact sound”.. 2. 120 mm wide top and bottom plates with 90 mm wide studs do not allow
clearance for timber noggings. Studs in structural walls, designed in accordance with AS 1684, require solid nogging at 1350 mmmax. spacing. Studs in structural walls with no nogging or metal strapping require alternative design and certification.
3. The Rw values listed are based upon 50 mm thick polyester acoustic insulation 350 kg/m . Different types of insulation will givedifferent values. Refer lining manufacturers for actual tested Rw ratings.
4. 70 x 35 mm studs are not allowed in loadbearing fire rated walls.5. Fibre cement may be either first or second layer.
3
20(a) -Studs continuousfor 2 storeys
20(b) -Upper wall supportedby lower wall
FIGURE 20 - TWO STOREY STAGGERED STUD WALLS
MRTFC Class 1a - Design & Construction Manual 27
CONS
TRUC
TION
&DE
TAILS
7
45 mm thick solid timber(35 mm if reinforced orfibre cement continuous)
45 mm thickor 35 mm thickif joint reinforcedor fibre cement sheetcontinued through(refer figure 5)
Additional 45 mm thick joist orledger (35 mm if reinforced) tomaintain fire resistance
Joists/blockingas necessary tosupport wall above
Joists/blockingas necessary to
support wall above
45 mm thick joists(35 mm if reinforced)to maintain fireresistance
Fibre cement firstlayer may continuethrough joint
Fibre cement firstlayer may continuethrough joint
Floor trussesmay be supportedby top chordoff ledger
Hanger orangle
Upper wall supported directly off lower wall
Note:Where ‘I’ beams or floor trusses are used, either fire gradelinings (all layers) must continue through intersection orsubstituted with solid timber to maintain fire resistance.
21(a) - Joists paralled to separating wall 21(b) - Joists perpendicular to separating wall
28 MRTFC Class 1a - Design & Construction Manual
FIGURE 21 - INTERSECTIONS BETWEEN SUSPENDED FLOORS ON SEPARATING WALL
Caulking
Sawcut
Caulking
Sawcut
Caulking
Sawcut
Caulking
Caulking
Sawcut
Caulking
CONS
TRUC
TION
&DE
TAILS
7
Notes:1. Bearers must be
continuous through wall
2. Upper wall must besupported off bearers
NOT
NOT
Sawcut
Bottom plate
Top plate
Slope tops of bearersto allow bearers torotate in the event ofcollapse
Fire gradelinings Fire grade
linings
Bearers supported offadditional studs (posts)
Bearerssupportedoff additionalstuds (posts)
Seal aroundbearer
Studs to supporttop plate andwall above
Studs to supporttop plate andwall above
Upper wall supporteddirectly off lower wall
45 mm thick joists
Compressedmineral wool
Blocking (additional joists) to transfer upperwall loads to lower wall (not supported off bearer)
Seal around bearer
Additional joist45 mm thick
FIGURE 22 - BEARER SUPPORTED OFF STAGGERED STUD WALL
22(b) - Timber blocking to transfer wall loads
22(c) - Plan views
MRTFC Class 1a - Design & Construction Manual 29
22(a) - Upper wall supported off lower wall
Caulking Caulking
CONS
TRUC
TION
&DE
TAILS
7
Additional studs tosupport linings
45 mm minimumthickness (35 mm ifjoint reinforced)
Gap
Additional studs tosupport linings
45 mm thickness(35 mm if reinforced)
Gap
Gap
1 x 45 mm or2 x 35 mm joists
Gap
FIGURE 23 - INTERSECTION WITH INTERNAL WALLS
30 MRTFC Class 1a - Design & Construction Manual
CONS
TRUC
TION
&DE
TAILS
7
MRTFC Class 1a - Design & Construction Manual 31
Additional studs tosupport wall linings
Cavity to be blocked with eitherfire resistant mineral wool,solid timber or fire grade liningscontinued to masonry(as for double stud walls - figure 16)
Top plate and bottom platemust not be continued overseparating wall
FIGURE 25 - INTERSECTION WITH EXTERNAL BRICK VENEER WALL
Note:Single stud walls or sheeted trusses may be usedin ceiling spaces above staggered stud separatingwalls. Refer figure 14 for typical details.
Cavity between top of walland underside of roofto be filled with compressedfire resistant mineral wool
Fire-rated wall
Truss
45 mm thick ledgerto support ceilingand trusses.
Use truss boots asrequired to supporttrusses on ledger
Nogging behindedge of linings
FIGURE 24 - SEPARATING WALLS ABOVE CEILINGS
32 MRTFC Class 1a - Design & Construction Manual
CONS
TRUC
TION
&DE
TAILS
7
Compressedfire resistantmineral wooland d.p.c.
See note
Additional stud tosupport lining
Note:Although fire grade liningis not required in external walls,the linings would normally beextended to the next intersection
FIGURE 26 - INTERSECTION WITH NON-ALIGNED EXTERNAL WALLS
Cladding
fire resistantmineral woolto fill voids inexternalcladding
Breather typesarking
Additional studs tosupport wall linings
Top and bottom plate toexternal wall must notcontinue acrossseparating wall
Cladding
Mineralwool
Breathertypesarking
Note:External wall may be fire rated (from the outside) withcontinuous fire grade lining inside cladding and sarking
FIGURE 27 - INTERSECTION WITH LIGHTWEIGHT CLAD EXTERNAL WALLS
CONS
TRUC
TION
&DE
TAILS
7
MRTFC Class 1a - Design & Construction Manual 33
TABLE E SINGLE STUD WALLS FRL 60/60/60
Fire Grade Linings Nominal Rw Studs OverallFixing Insulation (refer notes) (minimum size) Width
One layer 16 mm fire grade Resilient channels 50 49 90 x 35 135 mmto plasterboard both sides. or mount to
one side (129 mmfor 13 mm
Nil less than 45 lining)
(13 mm in non-loadbearing walls) Furring channels 50 50 90 x 35 157 mmwith resilient
mounted clips (151 mmto one side Nil less than 45 for 13 mm
lining)
Direct to Nil to less than 45 90 x 35 122 mmstuds filled cavity (116 mm
for 13 mmlining)
6 mm fibre cement plus 13 mm Direct to Nil 47 - 49 90 x 35 128 mmfire grade plasterboard to both sides. studs
Nil less than 45 70 x 45 108 mm
NOTE: 1. Lining fixed with resilient channels or mounts should face likely noise source (eg. wet areas) to provide impact sound resistance.Single stud walls with linings fixed to studs should only be used in locations where sound insulation is not critical (eg.between garages or in sub-floor or roof spaces above ceilings).
2. The nominal Rw ratings listed are based upon a 20 mm cavity between walls with acoustic insulation (where listed)50 mm thick polyester 350 kg/m . Different thicknesses and types of insulation will alter Rw values.(Refer lining manufacturer for actual tested Rw values).
3. 70 x 35 mm studs are not allowed in loadbearing fire rated walls.4. The fibre cement can be either the first layer (against the studs) or the second layer.
3
7.4 SingleStudSeparatingWalls
Wherenoisereductionis not requiredby the BCA(eg.BetweenClass10 a garagesor carports)or in situationswheresoundtransmissionis lesscritical(eg. In sub-floorandceilingspaces),singlestudframedseparatingwalls maybe used. (referTableE).
Note:An acceptablelevel of sound transmissionlosscan only be achieved in singlestud wallswith the useof resilient channels or resiliently mounted furringchannels. These systems however are onlyrecommended for single storey, single roomapplications (e.g. wet areas) because soundperformancecannotbemaintainedat intersections.
34 MRTFC Class 1a - Design & Construction Manual
CONS
TRUC
TION
&DE
TAILS
7
Compressed mineral wool
Compressed fire resistant mineral wool
45 mm thick blocking orfire grade lining takenup to roofing (where noeaves lining provided)
45 mm thick blocking wherefire grade lining not takenup to roofing
Cladding
Breather typesarking
Fire grade lining
Non ratedinternal linings
Non ratedinternal linings
Note:Fire rating needsonly to be fromthe outside
Non combustibleeaves lining(e.g. Fibre cement)
Masonry90 mmminimumthicknessprovidesFRL 60/60/60
Note:Floor may be supported withinfire rated external wall
FIGURE 28 - FIRE GRADE LINING ORBLOCKING CONTINUED UP TO ROOF
FIGURE 29 - FIRE RATED WALL(MASONRY OR FIRE GRADE LINING)
TO NON-COMBUSTIBLE EAVES LINING
7.5 ExternalWalls
Externalwalls within900mmof a sideor nearboundaryor closerthan1800mmto anotherbuildingare requiredto be FRL60/60/60( -/60/60if non-loadbearing). This fire resistancelevel needsonly to be attainedfromthe outside.
FRL60/60/60externalwalls can be either:-
• Brickveneer(minimum90 mmthick)brickswithany ratedor non-ratedinternallinings.
• 2 x 13 mmfire gradeplasterboardto externalfacecoveredby waterproofcladding(maybecombustiblematerial).Any ratedor non-ratedinternallining
• Any FRL60/60/60wall systems(referTablesC, DandE) withfire gradeliningto bothsides,withexternalface coveredby waterproofcladding(maybe combustiblematerial).
Fire ratedwall to extendup to non-combustibleroofingor non-combustibleeaves lining(referFigure28 &29).
Detailingof intersectionsbetweenfire ratedexternalwalls andseparatingwalls is exactlythe sameas fornon-ratedexternalwalls. (Fire resistanceof separatingwall to be effectively continuedthroughexternalwallandany associatedcavity) (referFigures17,18,25and27).
Separatingwalls musteffectively extendthroughanyvoid in ceilingsandeaves (referFigure30).
Wherefloorsare non-alignedor wherea singlestoreydwellingadjoinsa two storey dwelling,the separatingwall andexternalwall above the lower roofshallbe asshown on Figure31. Theseparatingwall betweendwellingsor betweendwellingandceilingspaceshallbe FRL60/60/60frombothsides. Theexternalwallabove the lower roof requiresFRL60/60/60measuredfromthe outsideonly. ( - /60/60for non-loadbearingwalls).
(ReferFigure2)
• 1 x 16 mmwetarea fire gradeplasterboardtoexternalface coveredby waterproofcladdingfixedto verticalor horizontalbattensat 600mmcentres.10 mmstandardplasterboardinternallining.
NOTE: Eaves linings are required to be non-combustiblebut not fire rated.Fibre cementproductssatisfythisrequirement.
NOTE: Suspendedfloors may be supporteddirectlyoff rated or non-rated external walls. There is norequirement for floors to collapse away fromexternalwallsin theeventof fire.
CONS
TRUC
TION
&DE
TAILS
7
MRTFC Class 1a - Design & Construction Manual 35
Fire grade lining, and framingto extend through eaves
Cavity between top of wall and underside of roofing to befilled with compressed fire resistant mineral wool
Non-combustible eaves lining
Fire rated separating wallto be continued throughtimber wall and cavity(refer figure 16, 17, 18, 25 & 27)
Fire rated separating wallextended to underside ofroofing
Non fire-rated ceiling
Fire-rated separating wall
Note:Internal firegrade linings maynot be necessaryabove roof butare generallycontinued up toceiling
Fire grade linings toseparate unit fromceiling space
Mineral wool betweenbattens
Ledger to support ceiling
45 mm thick blocking or ledger
Note:The external wall above a lowerroof to have FRL 60/60/60measured from the outside
Flashing
Fire grade lining
Breather type sarking
External cladding
FIGURE 30 -EXTENDING SEPARATING WALLTHROUGH EAVES
FIGURE 31 -EXTERNAL WALL ABOVE LOWER ROOF
Caulking
Sawcut
36 MRTFC Class 1a - Design & Construction Manual
CONS
TRUC
TION
&DE
TAILS
7
300 mmmin.
300 mmmin.
Not more than one electrical recess ineach wall face between any two studs
16 mm fire gradeplasterboard baffle
Gap between baffle and oppositestuds in staggered stud walls
16 mm fire gradeplasterboard baffle Wet area sealant
Acousticinsulation
Timber supportbattens
50 mmminimum
300 mm
16 mm fire grade plasterboard baffle
Wet area sealant
Acoustic insulationbetween plumbingfixtures and fittings
Fire grade linings
Resilient mounts
Timber battens
300 mm
FIGURE 32 -BAFFLE BETWEEN ELECTRICAL OUTLETS
OR SWITCHES
FIGURE 33 - BAFFLE AND INSULATION BETWEEN PLUMBING OUTLETS
7.6 PlumbingandElectricalServices
The installationof plumbingor electricalservicesinseparatingwalls have the potentialto reducethe fireresistanceandsoundperformance. Wherepossibletheseservicesshouldnot be locatedwithinfireresistantwalls (ie. placedin adjoiningpartitions,ducts,or over the face of fire gradelinings(behindbattenedout falsewall).
Whereserviceswithinseparatingwalls cannotbeavoided,the integrityof the wall mustbe maintainedfor bothfire resistanceandsoundinsulation. Thefollowingpracticesshouldbe adopted:-
(a) All holes,gaps or other irregularitiesassociatedwithpenetrationsthroughfire-ratedelementsmustbe sealedor mustsealduringa fire.
(b) Plumbingfittingsand/orelectricaloutletsshouldpreferablynot be backto back(ie. penetrateonlyone face betweentwo studs).
(c) Electricaloutletswhichare backto back,shouldhave eitherfire ratedboxes (withintumescentbacking)or be installedwith16 mmthickfiregradeplasterboardbaffle extending300mmaboveandbelow fittings(referFigure32).
(d) Backto back plumbingpenetrationsshouldbeseparatedby a 16 mmfire gradeplasterboardbaffle extending300mmabove and300mmbelow penetration. 50 mmthickacousticinsulationshouldalsobe installed(referFigure33).
(e) Penetrationsfor servicesshouldbe kept aminimumof 50 mmfromstuds.
(f) Pipesmustnot be fixed to linings.
(g) Pipesshouldbe supportedoff battensbetweenstudsor kept clearof studswithresilientmounts).
(h) Baths,showerbases,sinks,basinsmustnot berecessedinto fire ratedwalls. Firegradeliningsmustbe continuousbehindfixtures(referFigure34).
NOTE: Where plumbing services are required onnoise sensitivewalls, it is recommendedthat a falsewall be built in front of the fire and sound-rated wallandtheplumbingbeplacedintothis falsewall.
NOTE: Plastic pipes and fittings generally havebettersoundperformancethanmetal.
CONS
TRUC
TION
&DE
TAILS
7
MRTFC Class 1a - Design & Construction Manual 37
Void created bybattens can beused for services
Lining boardsuitablefor wet areas
Timber batten
Timber supportbatten fixed tostuds
Fire grade lining(e.g. 16 mm firegrade plasterboard)
Edge of bath/shower not tobe recessedinto fire-rated wall
Timber supportbatten fixed tostuds
Lining board suitablefor wet areas
Vanity or kitchen unitnot to be recessedinto fire-rated wall
Fire grade linings(e.g. 6 mm fibre cement plus13 mm fire grade plasterboard)
Lining board suitablefor wet areas
Fire grade linings
Caulking to 5-10 mm gapFlashing fixed toface of rated wall
34(a) - Edge of bath
34(b) - Vanity or kitchen bench
34(c) - Wet area floors
FIGURE 34 - WET AREA INSTALLATION
38 MRTFC Class 1a - Design & Construction Manual
CONS
TRUC
TION
&DE
TAILS
7
FIGURE 35 - BOX GUTTERS
45 mm thick ledger Hanger (truss boot)
35(b) - Roof framing supported offhangers and ledgers
45 mm thick blockingbetween trusses
Bottom chords extended(refer truss manufacturer)
35(a) - Roof framing on top ofseparating wall (not to be continuous)
Breather type sarking
Firegradelinings
Hanger (truss boot)
45 mm thick ledger
Cladding
Flashing
Note:Bottom chord extended to boxgutter width (refer truss manufacturer)
35(c) - Box gutter at parapet or for lower roof
7.7 BoxedGutters
Figure35 shows typicaldetailsfor boxed guttersatseparatingwalls.
MRTFC Class 1a - Design & Construction Manual 39
FIXIN
GOF
LININ
GS
8
8 FIXINGS OF LININGS
To achieve FRL60/60/60in separatingwalls thefollowingfire gradeliningsand required:-
(a)- 1 x 16 mmfire gradeplasterboardto bothfaces
or
- 1 x 13 mmfire gradeplasterboardplus1 x 6 mmfibrecementto bothfaces (eithersheet fixedfirst)
(b)- 1 x 13 mmfire gradeplasterboardto bothfaces
(or eitherof the loadbearingoptions).
Different liningmanufacturershave differentrequirementsfor nail sizesandspacings. Liningsmustbe installedstrictlyin accordancewithmanufacturer’sinstructions.
Internalandexternalcornerjunctionsmustbe arrangedto providesupportto both liningboards.Additionalstudsor noggingsmaybe required.
All verticalbutt jointsshallbe on studswith jointsstaggered. (ie. sheetson sameface as wellas sheetsonthe oppositeface mustnot have verticaljointson thesamestud).
Wheremultiplelayer liningsare used,horizontalandverticaljointsshallbe staggered. Sheetscan be fixedhorizontally, verticallyor a mixtureof both. The fibrecementsheetsmaybe eitherthe first or secondlayer.
At internalwall junctionsandat intersectionsbetweenseparatingwalls andceilings,any gaps betweenliningsshallbe sealedwithflexiblefire resistantsealer.
LoadbearingWalls
Non-LoadbearingWalls
NOTE: Staggered nogging may be used for duallayer systems, or where single layers are fixedverticallywithnohorizontaljoints.
NOTE: In FRL 60/60/60systemsfibre cementsheetsmaybeeitherfirst orsecondlayer.
NOTE: (ReferFigure 4 for the use of timberblockingand Figure 5 for strengthening of joints with eitherintumescent putty, plasterer’s angle or continuouslinings.
A gap of between5 and10 mmshallbe kept at thebottomof fire gradeliningsat floor level. Gap to becaulked witha fire resistantsealer.
NOTE: Caulking should generally be flexible toallow for timber movement. Non-flexible caulking(eg. Vermiculite plaster) may be used to seal gapsbetween lining and concrete floors where seasonedframingisused.
40 MRTFC Class 1a - Design & Construction Manual
FIXIN
GOF
LININ
GS
8
Studs at 600 mmcentres
Studs at 600 mmcentres
Joints centred onstud
Nail spacings to manufacturers’requirements
Nail spacings to manufacturers’requirements
Note:Vertical joints on oppositefaces to be staggered(i.e. Not on the same stud)
Nail spacings to manufacturers’requirements
Nail spacings to manufacturers’requirements
Vertical jointsstaggered
Vertical jointsstaggered
36(a) - Single layer fire grade plasterboard fixed horizontally
36(b) - Single layer fire grade plasterboard fixed vertically
36(c) - Fibre cement in conjunction with fire grade plasterboard
FIGURE 36 - FIXING OF LININGS
For informationregardingMRTFCpleasecontact:
New South Wales - TDA
Telephone (02) 9360 3088
Queensland - TRADAC
Telephone (07) 3358 1400
South Australia - TDA
Telephone (08) 8297 0044
Victoria - TAC
Telephone (03) 9877 2011
Western Australia - TAC
Telephone (08) 9380 4411
Tasmania - TTPB
Phone (03) 6224 1033
Timber Development Association of NSW
13-29 Nichols Street, Surrey Hills
New South Wales 2010
Fax (02) 9360 3464
Timber Research And Development Advisory Council
500 Brunswick Street, Fortitude Valley
Queensland 4006
Fax (07) 3358 1411
Timber Development Association of South Australia
113 Anzac Highway, Ashford
South Australia 5035
Fax (08) 8297 2772
Timber Advisory Centre
180 Whitehorse Road, Blackburn
Victoria 3130
Fax (03) 9877 6663
Timber Advisory Centre of Western Australia
55 Salvado Road, Subiaco
Western Australia 6008
Fax (08) 9380 4477
Tasmanian Timber Promotion Board
Suite 22, 11 Morrison Street, Hobart,
Tasmania 7000
Fax (03) 6224 1030
Plywood Association of Australia
Phone (07) 3854 1228
Pine Australia
Phone (Free Call) 1800 007 463
3 Dunlop Street, Newstead
Queensland 4006
Fax (07) 3252 4769
830 High Street, Kew East
Victoria 3102
Fax (03) 9859 2466
w bee www.timber.org.au/mrtfc
This publication is a joint venture between the National Timber Development Counciland the Forest and Wood Products Research and Development Corporation.
The FWPRDC is jointly funded by the Commonwealth Government and theAustralian forest and wood products industry.
© FWPRDC 2000 ,Printed June 2000
Members of theNational Timber Development Council
ATIF - Australian Timber Importers Federation
FIAT - Forest Industries Association of Tasmania
FIFWA - Forest Industries Federation (Western Australia) Inc.
FPA - New South Wales Forest Products Association Ltd.
FWPRDC - Forest & Wood Products Reseach & Development Corporation
PA - Pine Australia Ltd.
PAA - Plywood Association of Australia Ltd.
QTB - Queensland Timber Board
TDA (NSW) - Timber Development Association (New South Wales) Ltd.
TDA (SA) -
NAFI - National Association of Forest Industries
Timber Development Association (South Australia) Inc.
TPC - Timber Promotion Council of Victoria
TRADAC - Timber Research and Development Advisory Council (Qld)
VAFI - Victorian Association of Forest Industries
MULTI-RESIDENTIALTIMBER FRAMED CONSTRUCTION
FOREST & WOOD PRODUCTSRESEARCH & DEVELOPMENT CORPORATION