Study of energy efficiency in air handling unitsHeat recovery and electric power efficiencies in AHU´s

Dr.-Ing. Christoph [email protected]

Page 2: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

distribution of air flow rates

Markterhebung 2© Dr.-Ing. Christoph Kaup 2

Air flow distribution

0,00%

1,00%

2,00%

3,00%

4,00%

5,00%

6,00%

7,00%

8,00%

9,00%

10,00%

130.

000

110.

000

90.0

00

70.0

00

50.0

00

40.0

00

30.0

00

25.0

00

20.0

00

18.0

00

16.0

00

14.0

00

12.0

00

10.0

00

8.00

0

6.00

0

4.00

0

2.00

0

1.00

0

500

Air flow in m³/h

Air

flow

as

%

Study 1 Study 2

Page 3: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

heating and cooling devices of 13.893 units

supply units 13,3 %

exhaust units 5,8 %

combined units 80,9 %

heating devices installed (11.083 units) 79,8 %

cooling devices installed (5.630 units) 40,5 %

average heating capacity 96,3 KW

average cooling capacity 88,9 KW

energy devices

Markterhebung 3© Dr.-Ing. Christoph Kaup 3

Page 4: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

pressure losses

Markterhebung 4© Dr.-Ing. Christoph Kaup 4

average external pressure loss supply air 587 Pa

External pressure - flow rate distribution

y = 74,9Ln(x) - 90,517

0200400600800

1.0001.2001.4001.6001.8002.000

0 20.000 40.000 60.000 80.000 100.000

Flow rate in m³/h

Pres

sure

in P

a

External pressure to supply air flow rateLogarithmic (External pressure to supply air flow rate)

Page 5: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

pressure losses

Markterhebung 5© Dr.-Ing. Christoph Kaup 5

average external pressure loss exhaust air 544 Pa

External pressure - flow rate distribution

y = 49,564Ln(x) + 74,601

0

200

400

600

800

1.000

1.200

1.400

0 20.000 40.000 60.000 80.000 100.000

Flow rate in m³/h

Pres

sure

in P

a

External pressure to exhaust air flow rateLogarithmic (External pressure to exhaust air flow rate)

Page 6: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

pressure losses

Markterhebung 6© Dr.-Ing. Christoph Kaup 6

average supply air total pressure 1.115 Pa

Total pressure - flow rate distribution

y = 149,26Ln(x) - 235,56

0

500

1.000

1.500

2.000

2.500

3.000

0 20.000 40.000 60.000 80.000 100.000

Flow rate in m³/h

Pres

sure

in P

a

Total pressure to supply air flow rateLogarithmic (Total pressure to supply air flow rate)

Page 7: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

pressure losses

Markterhebung 7© Dr.-Ing. Christoph Kaup 7

average exhaust air total pressure 902 Pa

Total pressure - flow rate distribution

y = 130,94Ln(x) - 35,585

0

500

1.000

1.500

2.000

2.500

3.000

0 20.000 40.000 60.000 80.000 100.000

Flow rate in m³/h

Pres

sure

in P

a

Total pressure to exhaust air flow rateLogarithmic (Total pressure to exhaust air low rate)

Page 8: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

efficiencies

Markterhebung 8© Dr.-Ing. Christoph Kaup 8

average fan efficiency supply air 0,692 with Ps = 6,18 KW

Fan efficiency - flow rate distribution

y = 0,9723Ln(x) + 60,515

0102030405060708090

0 20.000 40.000 60.000 80.000 100.000

Flow rate in m³/h

η as

%

Fan efficiency to supply air flow rateLogarithmic (Fan efficiency to supply air flow rate)

Page 9: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

efficiencies

Markterhebung 9© Dr.-Ing. Christoph Kaup 9

average fan efficiency exhaust air 0,693 with Ps = 4,84 KW

Fan efficiency - flow rate distribution

y = 1,4537Ln(x) + 56,114

010203040

5060708090

0 20.000 40.000 60.000 80.000 100.000

Flow rate in m³/h

η as

%

Fan efficiency to exhaust air flow rateLogarithmic (Fan efficiency to exhaust air flow rate)

Page 10: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

efficiencies

Markterhebung 10© Dr.-Ing. Christoph Kaup 10

average system efficiency supply air 0,545 with Pm = 7,30 KW

System efficiency - flow rate distribution

y = 4,2626Ln(x) + 15,774

0

10

20

30

40

50

60

70

80

0 20.000 40.000 60.000 80.000 100.000

Flow rate in m³/h

η as

%

System efficiency to supply air flow rateLogarithmic (System efficiency to supply air flow rate)

Page 11: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

efficiencies

Markterhebung 11© Dr.-Ing. Christoph Kaup 11

average system efficiency exhaust air 0,538 mit Pm = 5,75 KW

System efficiency - flow rate distribution

y = 4,6099Ln(x) + 12,736

0

10

20

30

40

50

60

70

80

0 20.000 40.000 60.000 80.000 100.000

Flow rate in m³/h

η as

%

System efficiency to exhaust air flow rateLogarithmic (System efficiency to exhaust air flow rate)

Page 12: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

specific fan power

Markterhebung 12© Dr.-Ing. Christoph Kaup 12

average supply air SFP 1.916 W/(m³/s)

SFP - flow rate distributiony = 2042,8e-5E-06x

0500

1.0001.5002.0002.5003.0003.5004.0004.5005.000

0 20.000 40.000 60.000 80.000 100.000

Air flow in m³/h

SFP

in W

/(m³/s

)

SFP-values to supply air flow rateExponential (SFP-values to supply air flow rate)

Page 13: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

specific fan power

Markterhebung 13© Dr.-Ing. Christoph Kaup 13

average supply air SFP 1.799 W/(m³/s) (without add. SFP-values)

SFP - flow rate distribution

y = 1819,1e-6E-06x

0500

1.0001.5002.0002.5003.0003.5004.0004.5005.000

0 20.000 40.000 60.000 80.000 100.000

Air flow in m³/h

SFP

in W

/(m³/s

)

SFP-values to supply air flow rateExponetial (SFP-values to supply air flow rate)

Page 14: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

specific fan power

Markterhebung 14© Dr.-Ing. Christoph Kaup 14

average exhaust air SFP 1.571 W/(m³/s)

SFP - flow rate distributiony = 1517,5e7E-08x

0500

1.0001.5002.0002.5003.0003.5004.0004.5005.000

0 20.000 40.000 60.000 80.000 100.000

Air flow in m³/h

SFP

in W

/(m³/s

)

SFP-values to exhaust air flow rateExponential (SFP-values to exhaust air flow rate)

Page 15: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

specific fan power

Markterhebung 15© Dr.-Ing. Christoph Kaup 15

average ehaust air SFP 1.512 W/(m³/s) (without add. SFP-values)

SFP - flow rate distribution

y = 1454e-4E-07x

0500

1.0001.5002.0002.5003.0003.5004.0004.5005.000

0 20.000 40.000 60.000 80.000 100.000

Air flow in m³/h

SFP

in W

/(m³/s

)

SFP-values to exhaust air flow rateExponetial (SFP-values to exhaust air flow rate)

Page 16: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

specific fan power

Markterhebung 16© Dr.-Ing. Christoph Kaup 16

Average SFP-values

1400

1500

1600

1700

1800

1900

2000

2006 2007 2008 2009 2010

SFP

in W

/(m³/s

)

Supply Exhaust

Page 17: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

heatrecovery

Markterhebung 17© Dr.-Ing. Christoph Kaup 17

average transfer efficiency 0,624 at a 52,4 % use of HR

Transfer efficiency - Flow rate distribution

y = 1,2874Ln(x) + 48,249

20

30

40

50

60

70

80

90

0 20.000 40.000 60.000 80.000 100.000

Air flow in m³/h

Tran

sfer

effi

cien

cy a

s %

Transfer efficiency to air flow rateLogarithmic (Transfer efficiency to air flow rate)

h

Page 18: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

heatrecovery

Markterhebung 18© Dr.-Ing. Christoph Kaup 18

average HR pressure loss 168 Pa (supply) and 177 Pa (exhaust)

HR dP - Flow rate distribution

y = 22,602Ln(x) - 42,783

0

100

200

300

400

0 20.000 40.000 60.000 80.000 100.000

Air flow in m³/h

dP in

Pa

HR pressure loss to air flow rateLogarithmic (HR pressure loss to air low rate)

Page 19: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

heatrecovery development

Markterhebung 19© Dr.-Ing. Christoph Kaup 19

average transfer efficiency 0,624 (UCB) and 0,628 (Hoval 2009)

Distribution of heat recovery transfer efficiency

0,0%

5,0%

10,0%

15,0%

20,0%

25,0%

40 45 50 55 60 65 70 75 80 > 80,0

HR transfer efficiency

Tran

sfer

effi

cien

cy a

s a

%

Environmental Campus study Hoval AG Survey

Page 20: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

heatrecovery development

Markterhebung 20© Dr.-Ing. Christoph Kaup 20

Average HR transfer efficiency

5052

54565860

626466

6870

2009 2008 2007 2006 2005

Years

Tran

sfer

effi

cien

cy a

s %

Average HR transfer efficiency

50,0

55,0

60,0

65,0

70,0

2005 2006 2007 2008 2009 2010

Page 21: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

20,0%

25,0%

30,0%

35,0%

40,0%

45,0%

50,0%

55,0%

60,0%

65,0%

70,0%

2006 2007 2008 2009 2010

heatrecovery development

Markterhebung 21© Dr.-Ing. Christoph Kaup 21

The use of heatrecovery

Page 22: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

heatrecovery development

Markterhebung 22© Dr.-Ing. Christoph Kaup 22

Average HR pressure loss

100

120

140

160

180

200

2009 2008 2007 2006 2005

Years

Pres

sure

loss

in P

a

Average pressure loss

100

120

140

160

180

200

2005 2006 2007 2008 2009 2010

Page 23: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

heatrecovery

Markterhebung 23© Dr.-Ing. Christoph Kaup 23

Transfer efficiency - pressure drop distribution

y = 0,0012x3 - 0,1586x2 + 7,8077x

50

100

150

200

250

300

350

400

30 40 50 60 70 80 90

Transfer level in %

Pres

sure

dro

p in

Pa

Transfer efficiency to air flow rate

Polynomic (Transfer efficiency to air flow rate)

Page 24: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

market datas RLT (survey RLT)

31,111.10843.75927,288,1323,82006

36,712.87343.21727,4101,9373,6∅

45,515.56942.23625,8111,3431,42008

33,411.94143.65629,1106,2365,52007

HR%

withHR

UnitsExport%

ExportMio.€

Turn-overMio.€

Year

general market values

Markterhebung 24© Dr.-Ing. Christoph Kaup 24

Page 25: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

market datas RLT (survey RLT)

45,515.56942.23625,8111,3431,42008

55,316.83637.39625,9101,9400,4∅

67,019.79136.47626,4103,2390,42010

55,115.14833.47625,596,6379,42009

HR%

withHR

UnitsExport%

ExportMio.€

Turn-overMio.€

Year

general market values

Markterhebung 25© Dr.-Ing. Christoph Kaup 25

Page 26: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

market datas RLT (survey RLT)

turnover of association 400,4 Mio. €

additional turnovers 167,6 Mio. €

total 568,0 Mio. €

ratio RLT 70,5 %(acc. Dissertation Dr. Beck 2000 University Kassel 70 %)

general market values

Markterhebung 26© Dr.-Ing. Christoph Kaup 26

Page 27: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

market datas RLT

possible Units (AHU) with heatrecovery 80,5 %(Study Dr. Kaup 2009 UCB university of applied science Trier)

average overall ratio HR (RLT ∅ 08 bis 10) 44,5 %

Possible ratio HR 55,3 %

strong positiv development2010 ratio 55,1 % in total or (possible units) 67,0 %

heatrecovery

Markterhebung 27© Dr.-Ing. Christoph Kaup 27

Page 28: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

Statistik Wärmerückgewinnungair flow rate distribution

Markterhebung 28© Dr.-Ing. Christoph Kaup 28

Distribution of air flow rates AHU

0,00%

2,00%

4,00%

6,00%

8,00%

10,00%

12,00%

130.

000

110.

000

90.0

00

70.0

00

50.0

00

40.0

00

30.0

00

25.0

00

20.0

00

18.0

00

16.0

00

14.0

00

12.0

00

10.0

00

8.00

0

6.00

0

4.00

0

2.00

0

1.00

0

500

air flow rates in m³/h

Air

flow

rate

s as

%

Manufacturer A Amnufacturer B

Page 29: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

Statistik Wärmerückgewinnungair flow rate distribution

Markterhebung 29© Dr.-Ing. Christoph Kaup 29

Average distribution of air flow rates AHU

0,00%

1,00%

2,00%

3,00%

4,00%

5,00%

6,00%

7,00%

8,00%

9,00%

10,00%

130.

000

110.

000

90.0

00

70.0

00

50.0

00

40.0

00

30.0

00

25.0

00

20.0

00

18.0

00

16.0

00

14.0

00

12.0

00

10.0

00

8.00

0

6.00

0

4.00

0

2.00

0

1.00

0

500

Air flow rates in m³/h

Air

flow

rate

s as

%

Page 30: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

Distribution of air flow rates AHU

y = 2E-06x4 - 0,0001x3 + 0,0028x2 - 0,0151x + 0,0201

0,00%

10,00%

20,00%

30,00%

40,00%

50,00%

60,00%

70,00%

80,00%

90,00%

100,00%

150.

000

130.

000

110.

000

90.0

00

70.0

00

50.0

00

40.0

00

30.0

00

25.0

00

20.0

00

18.0

00

16.0

00

14.0

00

12.0

00

10.0

00

8.00

0

6.00

0

4.00

0

2.00

0

1.00

0

Air flow rates in m³/h

Dis

trib

utio

n as

%

Air flow rates (Distribution summ) Polynomic air flow distribution

EnEV

= 7.500 m³/h∅

Statistik Wärmerückgewinnungair flow rate distribution

Markterhebung 30© Dr.-Ing. Christoph Kaup 30

Page 31: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

heat energies

specific energy for heating (24 h/d) 31,33 kWh/(m³/h)/a(Disseration Dr. Beck 2000 University Kassel)

operating time (average) 2.350 h(Disseration Dr. Beck 2000 University Kassel)

specific energy for heating at 2.350 h 8,4 kWh/(m³/h)/a

lifetime of the units 20,0 years

rated lifetime (base interest 2 %) 13,4 years(1 % new units [38.000 in ´97 to 43.200 in ´09] + 1 % waste rate)

energy consumption of heating

Markterhebung 31© Dr.-Ing. Christoph Kaup 31

Page 32: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

energy consumption of heating

Markterhebung 32© Dr.-Ing. Christoph Kaup 32

Distribution of energy for heating

y = 4E-09x6 - 5E-07x5 + 2E-05x4 - 0,0004x3 + 0,0031x2 - 0,002x + 0,0045

0,00%

1,00%

2,00%

3,00%

4,00%

5,00%

6,00%

7,00%13

5.00

0

115.

000

95.0

00

75.0

00

55.0

00

42.5

00

32.5

00

26.7

50

21.2

50

18.5

00

16.5

00

14.5

00

12.5

00

10.5

00

8.50

0

6.50

0

4.50

0

2.50

0

875

Air flow rates in m³/h

Dis

trib

utio

n as

%

Distribution of energy for heating Polynomic (Distribution of enery for heating)

Page 33: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

Summ of energy for heating

y = 3E-07x5 - 3E-05x4 + 0,0009x3 - 0,0108x2 + 0,0061x + 0,9451

0,0%

10,0%

20,0%

30,0%

40,0%

50,0%

60,0%

70,0%

80,0%

90,0%

100,0%

105.

000

85.0

00

65.0

00

47.5

00

37.5

00

28.7

50

23.7

50

19.5

00

17.5

00

15.5

00

13.5

00

11.5

00

9.50

0

7.50

0

5.50

0

3.50

0

1.50

0

air flow rates in m³/h

Dis

trib

utio

n as

%

Distribution of energy for heating Polynomic (Distribution of energy for heating)

EnEV

= 28.750 m³/h∅

energy consumption of heating

Markterhebung 33© Dr.-Ing. Christoph Kaup 33

Page 34: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

energy saving potential in Germany 2010

AHU´s 53.043 units

airflow 2010 (without export) 562,5 Mio. m³/h

heat energy demand 4.724.806 MWh/a

HR-ratio 54,3 %

efficiency 67,2 %

HR potential 1.722.716 MWh/a

CO2 Saving 566.774 to/a

installed electric power 492.633 KW/a

Markterhebung 34© Dr.-Ing. Christoph Kaup 34

AHU general market values

Page 35: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

energy linked to the Gross domestic product

electroenergy demand in germany 492.633 kW/a

GDP Germany 3.667,5 Bil. $

value = 492.633 / 3.667,5 • GDP

Markterhebung 35© Dr.-Ing. Christoph Kaup 35

AHU general market values

Page 36: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

Markterhebung 36© Dr.-Ing. Christoph Kaup 36

AHU electric power demand EU

7.3840,3%54,970,1%493.300Luxembourg6.3540,3%47,300,7%3.354.700Lithuania4.5740,2%34,050,5%2.261.294Latvia

310.81012,6%2.313,8912,1%60.245.846Italy36.7151,5%273,330,9%4.239.848Irland

359.19314,5%2.674,0912,3%61.113.205Great Britain48.0271,9%357,552,2%11.141.740Greece

384.93515,6%2.865,7312,6%62.793.432France36.8021,5%273,981,1%5.326.314Finland3.1200,1%23,230,3%1.342.000Estonia

492.63319,9%3.667,5116,4%81.882.342Germany 46.0641,9%342,931,1%5.475.791Denmark6.9830,3%51,991,5%7.606.551Bulgaria

68.0202,8%506,392,1%10.666.860BelgiumkW/aBil. $

demandGDPpopulationbase 2008

Page 37: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

Markterhebung 37© Dr.-Ing. Christoph Kaup 37

AHU electric power demand EU

2.470.561100,0%18.392,61100,0%498.371.164sum

3.1500,1%23,450,2%950.000Cyprus20.9920,8%156,282,0%10.020.000Hungary29.1591,2%217,082,1%10.501.197Czechia

216.4998,8%1.611,779,4%46.661.950Spain7.3390,3%54,640,4%2.019.614Slovenia

12.8140,5%95,401,1%5.455.407Slowakia65.0862,6%484,551,9%9.269.986Sweden

26.8201,1%199,674,3%21.498.616Romania32.8411,3%244,492,1%10.617.575Portugal70.6192,9%525,747,7%38.153.389Poland55.7872,3%415,321,7%8.376.761Austria

116.7194,7%868,943,3%16.493.156Netherlands1.1200,0%8,340,1%410.290MaltakW/aBil. $

demandGDPpopulationbase 2008

Page 38: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

AHU saving potential in europe 2011

electroenergy demand 77,80 TWh/abase Lifetime 13,4 a and 2.350 h/a

CO2 equivalent 42,09 Mil.to/aBase 541 g/kWh Mix.

saving potential 15,56 TWh/aBase 20 % increase of efficiency

CO2 saving 8,42 Mil.to/a

Markterhebung 38© Dr.-Ing. Christoph Kaup 38

AHU general market values EU

Page 39: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

units linked to the gross domestic product

AHUs in germany 53.043 units

GDP Germany 3.667,5 Bil. $

value = 53.043 / 3.667,5 • GDP

link to population

value = 53.043 / 81.882.342 • P

Markterhebung 39© Dr.-Ing. Christoph Kaup 39

AHU general market values

Page 40: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

Markterhebung 40© Dr.-Ing. Christoph Kaup 40

AHU market EU

7950,3%54,970,1%493.300Luxembourg6840,3%47,300,7%3.354.700Lithuania4920,2%34,050,5%2.261.294Latvia

33.46612,6%2.313,8912,1%60.245.846Italy3.9531,5%273,330,9%4.239.848Irland

38.67514,5%2.674,0912,3%61.113.205Great Britain5.1711,9%357,552,2%11.141.740Greece

41.44715,6%2.865,7312,6%62.793.432France3.9631,5%273,981,1%5.326.314Finland

3360,1%23,230,3%1.342.000Estonia53.04319,9%3.667,5116,4%81.882.342Germany 4.9601,9%342,931,1%5.475.791Denmark

7520,3%51,991,5%7.606.551Bulgaria7.3242,8%506,392,1%10.666.860Belgium

Bil. $unitsGDPpopulationbase 2008

Page 41: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

Markterhebung 41© Dr.-Ing. Christoph Kaup 41

AHU market EU

266.011100,0%18.392,61100,0%498.371.164sum

3390,1%23,450,2%950.000Cyprus2.2600,8%156,282,0%10.020.000Hungary3.1401,2%217,082,1%10.501.197Czechia

23.3118,8%1.611,779,4%46.661.950Spain7900,3%54,640,4%2.019.614Slovenia

1.3800,5%95,401,1%5.455.407Slowakia7.0082,6%484,551,9%9.269.986Sweden

2.8881,1%199,674,3%21.498.616Romania3.5361,3%244,492,1%10.617.575Portugal7.6042,9%525,747,7%38.153.389Poland6.0072,3%415,321,7%8.376.761Austria

12.5674,7%868,943,3%16.493.156Netherlands1210,0%8,340,1%410.290Malta

Bil. $unitsGDPpopulationbase 2008

Page 42: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

AHU market 2011

number of production 266.011 units

+34,8 % CHRV units 356.455 units

AHU´s + CHRV´s 320.000 unitsbase Lot 6 / Task 2

check (link to population) 322.843 Units (AHU)

435.192 Units (incl. CHRV)

Markterhebung 42© Dr.-Ing. Christoph Kaup 42

AHU general market values EU

Page 43: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

AHU market 2011

Markterhebung 43© Dr.-Ing. Christoph Kaup 43

AHU general market values EU

source: Lot 6 / Task 2

Page 44: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

energy linked to the gross domestic product

thermal energy saving in germany 1.722.716 MWh/a

GDP Germany 3.667,5 Bil $

average temp. in Germany 9,0 °C

heatrecovery use • efficiency 36,4 %

nominal supply temperature 21,0 °C

heatrecovery value (U) = 36,4 % / (21 – 9) • (21 – T)

energy = 1.722.716 / 3.667,5 / 36,4 • U

• GDP / (21 – 9) • (21 – T)

Markterhebung 44© Dr.-Ing. Christoph Kaup 44

AHU general market values

Page 45: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

Markterhebung 45© Dr.-Ing. Christoph Kaup 45

AHU heat consumption EU

25.82170.8179,036,454,97Luxembourg32.44073.6316,544,047,30Lithuania26.34156.2955,646,734,05Latvia

318.8961.614.68414,519,72.313,89Italy107.883322.78410,033,4273,33Irland

1.055.4593.157.91310,033,42.674,09Great Britain10.497115.15718,09,1357,55Greece

934.7923.076.56911,030,32.865,73France228.791470.6205,048,5273,98Finland

20.63041.1504,550,123,23Estonia1.722.7164.724.8069,036,43.667,51Germany

189.048478.6088,039,4342,93Denmark18.69758.60610,531,951,99Bulgaria

199.871598.01110,033,4506,39BelgiumMWh/aMWh/a°C%Bil. $target 21°C

HRheataverageHR (U)GDPbase 2008

Page 46: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

Markterhebung 46© Dr.-Ing. Christoph Kaup 46

6.572.61419.742.78110,933,218.392,61sum

0021,00,023,45Cyprus65.094189.5899,734,3156,28Hungary

121.518305.2977,939,7217,08Czechia84.121692.14117,012,11.611,77Spain21.17663.93910,133,154,64Slovenia61.868144.4116,942,895,40Slowakia

288.062702.2697,541,0484,55Sweden86.137246.5149,534,9199,67Romania12.760104.99117,012,1244,49Portugal

385.863846.6306,045,5525,74Poland179.167512.7589,534,9415,32Austria374.8571.0772.8019,534,9868,94Netherlands

1091.79119,06,18,34MaltaMWh/aMWh/a°C%Bil. $target 21 °C

HRheataverageHR (U)GDPbase 2008

AHU heat consumption EU

Page 47: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

AHU saving potential in europe 2011

heating demand 19.724.781MWh/a

heatrecovery 6.572.614MWh/a

CO2 saving 2.162.195 to/abase 329 kg/MWh

electroenergy demand 2.470.561 KW/a

Markterhebung 47© Dr.-Ing. Christoph Kaup 47

AHU general market values EU

Page 48: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

AHU saving potential in europe 2011

heating demand during lifetime 264,55 TWh/abase Lifetime 13,4 a and 2.350 h/a

heatrecovery 88,00 TWh/astate of the art 2010

CO2 saving equivalent 28,98 Mil.to/abase 329 kg/MWh

average heatrecovery 53,28 TWh/a0,58 average efficiency and 47 % use

max. potential heatrecovery 146,62 TWh/abase 0,75 efficiency and 81 % balanced units

Markterhebung 48© Dr.-Ing. Christoph Kaup 48

AHU general market values EU

Page 49: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

energy linked to the gross domestic product

colth energy saving in germany 111.273 MWh/a

GDP Germany 3.667,5 Bil. $

average temp. in Germany 9,0 °C

nominal ODA temperature for cooling 25,0 °C

cooling factor relativ to germany f = (25 – 9) / (25 – T)

energy demand = 111.273 / 3.667,5 • GDP • f(sensible capacity without dehumification)

energy recovery = energy • U

Markterhebung 49© Dr.-Ing. Christoph Kaup 49

AHU general market values EU

Page 50: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

Markterhebung 50© Dr.-Ing. Christoph Kaup 50

AHU colth consumption EU

1.6684.5821,0036,454,97Luxembourg1.5003.4100,8644,047,30Lithuania1.0932.3410,8246,734,05Latvia

57.946293.8931,5219,72.313,89Italy8.10924.3011,0733,4273,33Irland

79.329237.7501,0733,42.674,09Great Britain6.19968.1202,299,1357,55Greece

82.806272.9881,1430,32.865,73France8.86718.2690,8048,5273,98Finland

7561.5110,7850,123,23Estonia111.273305.6941,0036,43.667,51Germany

10.60926.9020,9439,4342,93Denmark1.5234.7821,1031,951,99Bulgaria

15.02345.0221,0733,4506,39BelgiumMWh/aMWh/afactor%Bil. $target 16 °C / 25 °C

HRcolthcollingHR (U)GDPbase 2008

Page 51: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

Markterhebung 51© Dr.-Ing. Christoph Kaup 51

516.8281.872.66233,218.392,61sum

07.8184,000,023,45Cyprus4.66913.6221,0534,3156,28Hungary6.72716.9300,9439,7217,08Czechia

32.601268.6882,0012,11.611,77Spain1.6174.8911,0733,154,64Slovenia3.0067.0290,8842,895,40Slowakia

15.12136.9260,9141,0484,55Sweden5.99317.1801,0334,9199,67Romania4.94540.7572,0012,1244,49Portugal

16.79136.9020,8445,5525,74Poland12.46535.7341,0334,9415,32Austria26.08074.7641,0334,9868,94Netherlands

1121.8542,676,18,34MaltaMWh/aMWh/afactor%Bil. $target 16 °C / 25 °C

HRcolthcoolingHR (U)GDPbase 2008

AHU heat consumption EU

Page 52: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

Markterhebung 52© Dr.-Ing. Christoph Kaup 52

AHU electric power demand EU+

7.3721,4%54,883,4%10.829.175Serbia-Montenegro66.16813,0%492,602,4%7.701.900Swiss

1590,0%1,180,0%31.538San Marino225.20644,1%1.676,5944,4%142.400.000Russia

61.28212,0%456,231,5%4.825.500Norway

8220,2%6,121,4%4.455.421Moldava1.2850,3%9,570,6%2.063.122Macedonia9.3131,8%69,331,4%4.489.409Croatia2.9580,6%22,021,5%4.693.892Georgia 2.4810,5%18,471,4%4.552.000Bosnia-Herzegovina8.0981,6%60,293,0%9.489.000Belarus

4700,1%3,500,0%83.888Andorra 1.7410,3%12,961,0%3.170.048AlbaniakW/aBil. $

demandGDPpopulationbase 2008

Page 53: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

Markterhebung 53© Dr.-Ing. Christoph Kaup 53

AHU electric power demand EU+

510.632100,0%3.801,51100,0%320.711.325sum

6620,1%4,930,0%35.789Lichtenstein4930,1%3,670,0%32.796Monaco

24.1424,7%179,7314,3%45.994.247Ukraine 97.98119,2%729,4423,7%75.863.600Turkey

kW/aBil. $demandGDPpopulationbase 2008

Page 54: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

Markterhebung 54© Dr.-Ing. Christoph Kaup 54

AHU heat consumption EU+

456,236,12

17.90258.91811,030,354,88Serbia-Montenegro267.395682.2068,139,1492,60Swiss

16382314,519,71,18San-Marino1.330.9322.807.9085,447,31.676,59Russia

334.847734.6946,045,5Norway3.2208.3448,338,5Moldava3.77711.30110,033,49,57Macedonia

22.61574.43111,030,369,33Croatia4.71319.14812,924,622,02Georgia 4.88017.84612,027,318,47Bosnia-Herzegovina

47.860100.9725,447,360,29Belarus1.3814.13310,033,43,50Andorra 1.0576.95716,015,212,96Albania

MWh/aMWh/a°C%Bil. $HRheataverageuseGDPbase 2008

Page 55: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

Markterhebung 55© Dr.-Ing. Christoph Kaup 55

2.258.1425.314.1008,542,53.801,51sum

1.7065.45110,731,24,93Lichtenstein2531.81216,414,03,67Monaco

114.910270.1347,042,5179,73Ukraine 100.530509.01914,519,7729,44TurkeyMWh/aMWh/a°C%Bil. $

HRheataverageuseGDPbase 2008

AHU Heat consumption EU+

Page 56: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

for yourAttention

Thank you

Study of energy efficiency in air handling unitsHeat recovery and electric power efficiencies in AHU´s

Dr.-Ing. Christoph [email protected]

Page 57: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

LCC influence - location

Markterhebung 57© Dr.-Ing. Christoph Kaup 57

LCC Total in €

0

50.000

100.000

150.000

200.000

250.000

300.000

Berlin Munich Hamburg Frankfurt

Page 58: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

LCC influence - location

Markterhebung 58© Dr.-Ing. Christoph Kaup 58

LCC heating in €

010.00020.00030.00040.00050.00060.00070.00080.00090.000

100.000

Berlin Munich Hamburg Frankfurt

Page 59: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

LCC influence - conditions

Markterhebung 59© Dr.-Ing. Christoph Kaup 59

18 / 16 °CHigh cooling demand

20 / 26 °C Higher load

5

22 / 20 °CHigh heat demand

18 / 24 °CLower load

4

20 / 18 °CLower heat demand

20 / 26 °CHigher load

3

21 / 19 °C Higher heat demand

18 / 24 °CLower load

2

21 / 19 °C Higher heat demand

20 / 26 °C Higher load

1

supply air conditions winter/summer

extract air conditions winter/summer

calculation variant

Page 60: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

LCC influence - conditions

Markterhebung 60© Dr.-Ing. Christoph Kaup 60

LCC heating in €

0

20.000

40.000

60.000

80.000

100.000

120.000

140.000

160.000

21/19 21/19 20/18 22/20 18/16

20/26 18/24 20/26 18/24 20/26target values / exhaust conditions (winter/summer)

Page 61: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

LCC influence - conditions

Markterhebung 61© Dr.-Ing. Christoph Kaup 61

LCC cooling in €

0

5.000

10.000

15.000

20.000

25.000

21/19 21/19 20/18 22/20 18/16

20/26 18/24 20/26 18/24 20/26target values / exhaust conditions (winter/summer)

Page 62: c.kaup@umwelt-campus · heating and cooling devices of 13.893 units supply units 13,3 % exhaust units 5,8 % combined units 80,9 % heating devices installed (11.083 units) 79,8 %

LCC influence - conditions

Markterhebung 62© Dr.-Ing. Christoph Kaup 62

LCC Total in €

0

50.000

100.000

150.000

200.000

250.000

300.000

350.000

21/19 21/19 20/18 22/20 18/16

20/26 18/24 20/26 18/24 20/26target values / exhaust conditions (winter/summer)