M Circuit Protection Series L8 Supplementary Protectors - General Description .....................M2 Selection Guide - Trip Curve “B” ............................................................M4 Selection Guide - Trip Curve “C” ............................................................M6 Selection Guide - Trip Curve “D” ............................................................M8 Accessories .........................................................................................M10 Technical Information...........................................................................M12 Dimensions..........................................................................................M17 Series L9 Miniature Circuit Breakers - General Description ...................M24 Selection Guide - Trip Curve “C” ..........................................................M26 Selection Guide - Trip Curve “D” ..........................................................M27 Accessories .........................................................................................M28 Technical Information...........................................................................M30 Dimensions..........................................................................................M31 Methods Of Applying Circuit Protection ................................................M35 Applying L8 Supplementary Protectors with UL and NEC Guidelines .....M37 Applying L9 Miniature Circuit Breakers with UL and NEC Guidelines.....M38 Defining Electrical Standards ...............................................................M43 Series FH8 DIN-rail Mountable Fuse Holders ........................................M44 Accessories .........................................................................................M49 Fuse Block Selection Guide ..................................................................M50 Circuit Protection

Upload: ngodien

Post on 10-Jun-2018

220 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Circuit Breakers - Series L8 Supplementary Circuit ... · Series L8 Supplementary Protectors are ... contact with live parts. To aid troubleshooting, a color-coded indicator provides

M

Circuit Protection

Series L8 Supplementary Protectors - General Description .....................M2Selection Guide - Trip Curve “B” ............................................................M4Selection Guide - Trip Curve “C” ............................................................M6Selection Guide - Trip Curve “D” ............................................................M8Accessories .........................................................................................M10Technical Information ...........................................................................M12Dimensions ..........................................................................................M17

Series L9 Miniature Circuit Breakers - General Description ...................M24Selection Guide - Trip Curve “C” ..........................................................M26Selection Guide - Trip Curve “D” ..........................................................M27Accessories .........................................................................................M28Technical Information ...........................................................................M30Dimensions ..........................................................................................M31

Methods Of Applying Circuit Protection ................................................M35Applying L8 Supplementary Protectors with UL and NEC Guidelines .....M37Applying L9 Miniature Circuit Breakers with UL and NEC Guidelines .....M38Defining Electrical Standards ...............................................................M43

Series FH8 DIN-rail Mountable Fuse Holders ........................................M44Accessories .........................................................................................M49Fuse Block Selection Guide ..................................................................M50

Cir

cuit

Pro

tect

ion

Page 2: Circuit Breakers - Series L8 Supplementary Circuit ... · Series L8 Supplementary Protectors are ... contact with live parts. To aid troubleshooting, a color-coded indicator provides

M2

Circ

uit

Prot

ectio

nL8

visit www.sprecherschuh.com/ecatalog for the most up to date information SSNA2012

M

Series L8 Supplementary Protectors

Supplemental short circuit protection for a variety of applications

Sprecher+Schuh Series L8 Supplemen-tary Protectors provide supplemental overcurrent protection for control circuits, solenoids, actuators, appli-ances, business equipment and a range of other applications where a high performance current limiting device is required. Advanced features and global approvals make them ideal for use in equipment installed throughout the world.

Broad product rangeSeries L8 Supplementary Protectors are available in up to 20 different current ratings from 0.5A to 63A, in one, two and three pole configurations. Over 180 base models are available with a full compliment of accessories.

Devices can be used in applications up to 480V AC and 48V DC with inter-rupting capacities up to 10kA.

Safety features provide enhanced protectionThe terminals of Series L8 Supple-mentary Protectors provide IP20 protection to guard against accidental contact with live parts.

To aid troubleshooting, a color-coded indicator provides positive visual indica-tion of the device status (green for OFF, red for ON) and isolation function.

Sprecher+Schuh Supplementary Protectors also incorporate a trip-free mechanism - ensuring that the device operation cannot be defeated by hold-ing the operator in the ON position.

Easy installationSprecher+Schuh Supplementary Pro-tectors mount on a standard 35mm DIN-rail. Wire terminals accept multiple conductors, and UL 508 ap-proved bus bars can be used to quickly distribute power to many Supple-mentary Protectors simultaneously. In addition, power to the circuit breakers can be fed from the line or load side.

Global approvals for worldwide acceptanceSeries L8 Supplementary Protec-tors are UL Recognized for use in the United States in accordance with NFPA 79 (NEC, National Electrical Code). The devices comply with UL 1077 and CSA 22.2 No.235, meeting the requirements for supplementary protectors intended for use as overcur-rent protection where branch circuit protection is not required, or is pro-vided by another device such as a fuse or molded case circuit breaker. These Supplementary Protectors also comply with IEC 60898 for use in commercial and residential applications and are CE marked.

®

17.5mm 35mm 52.5mm (≈11/16˝) (≈1-3/8˝) (≈2-1/8˝)

One Pole Two Pole Three Pole

Page 3: Circuit Breakers - Series L8 Supplementary Circuit ... · Series L8 Supplementary Protectors are ... contact with live parts. To aid troubleshooting, a color-coded indicator provides

M3

Circ

uit

Prot

ectio

nL8

visit www.sprecherschuh.com/ecatalog for the most up to date informationSSNA2012

M

Three trip characteristicsAll Sprecher+Schuh L8 Supplemen-tary Protectors are available with three different tripping characteristics, Type “B”, “C”, and “D”. The tripping char-acteristic defines the device’s speed of response (trip-time) to various levels of overcurrent. Figure 1 shows trip-time versus overcurrent for Type B, C, and D devices. The time-current character-istics enable the device to be opti-mally matched to the application. For example, PLC outputs that can only tolerate minimal overcurrents are best protected by Supplementary Protectors with Type B trip characteristics.

Sprecher+Schuh L8 Supplementary Protectors are also current limiting - interrupting fault currents within one half cycle. Current limiting devices protect circuit components from dam-age by reducing the peak let-through current which causes damaging magnetic forces and let-through energy which generates heat.

Type “B” CharacteristicDeveloped primarily to protect conductors and low level signal devices such as PLCs. Instantaneous trip is three to five times the rated current of the Supplementary Protector (3~5 x In). The fast trip time of these devices minimizes damage to control circuit conductors from low-level faults.

Type “C” CharacteristicDeveloped primarily for applications with moderate inrush currents such as lighting, control circuits and coils, computers and appliances. Instantaneous trip is five to ten times the rated current of the Supple-mentary Protector (5~10 x In). The higher instantaneous trip level prevents nuisance tripping, and components being protected can typically withstand higher fault currents without being damaged.

Type “D” CharacteristicDeveloped primarily for applications with high inrush currents, i.e., transformers, power supplies and heaters. Instantaneous trip is ten to twenty times the rated cur-rent of the Supplementary Protector (10~20 x In). The high instantaneous trip level prevents nuisance tripping, and components being protected can typically withstand higher fault currents without being damaged.

Figure 1Sprecher+Schuh Series L8 Supplementary Protector

Trip Characteristics

Compare these advanced features

1 2 3 4 5 6 7 8 9 10 15 20 30 40 50

I / IN

t [se

c]t [

min

]

0.0005

0.001

0.002

0.005

0.01

0.02

0.05

0.1

0.2

0.5

1

2

5

10

30

1

2

5

10

20

60

120

(Curves at 30º C)

Line and load side terminals accept bus bar connections for reduced costs and more efficient installation of multiple devices.

Guarded pozidrive terminal screws with finger-safe protection to IEC 947-1

Trip-free mechanism; device operation cannot be defeated by holding the operator in the ON position

Color coded indicator provides visual indication of the device status and isolation function

Available in one, two and three pole; one pole + neutral and three pole + neutral

Box lug terminals accept #18…#4 (1.0…25mm2) wire as standard

Ratings to 480Y/277V AC @ 240/415V AC - 10kA Interrupt Rating

Devices install on standard 35mm DIN-rail (EN 50022)

Magnetic trip elements provide Type B, C and D trip characteristics

(IEC and EN 60898), while bimetallic elements protect against slight

overloads.

Amp rating and trip curve characteristic clearly marked on the device for easy

identification

Page 4: Circuit Breakers - Series L8 Supplementary Circuit ... · Series L8 Supplementary Protectors are ... contact with live parts. To aid troubleshooting, a color-coded indicator provides

M4

Circ

uit

Prot

ectio

nL8

visit www.sprecherschuh.com/ecatalog for the most up to date information SSNA2012

M

Discount Schedule B-8

L8 Supplementary ProtectorsTrip Characteristic B

Rated Current

(A)

1 Pole ➊ 2 Pole ➋ 3 Pole ➋

Catalog Number PriceStd.Pkg. Catalog Number Price

Std.Pkg. Catalog Number Price

Std.Pkg.

1 L8-1/1/B 38 12 L8-1/2/B 82 6 L8-1/3/B 124 4

2 L8-2/1/B 38 12 L8-2/2/B 82 6 L8-2/3/B 124 4

3 L8-3/1/B 38 12 L8-3/2/B 82 6 L8-3/3/B 124 4

4 L8-4/1/B 38 12 L8-4/2/B 82 6 L8-4/3/B 124 4

5 L8-5/1/B 38 12 L8-5/2/B 82 6 L8-5/3/B 124 4

6 L8-6/1/B 38 12 L8-6/2/B 82 6 L8-6/3/B 124 4

7 L8-7/1/B 38 12 L8-7/2/B 82 6 L8-7/3/B 124 4

8 L8-8/1/B 38 12 L8-8/2/B 82 6 L8-8/3/B 124 4

10 L8-10/1/B 38 12 L8-10/2/B 82 6 L8-10/3/B 124 4

13 L8-13/1/B 38 12 L8-13/2/B 82 6 L8-13/3/B 124 4

15 L8-15/1/B 38 12 L8-15/2/B 82 6 L8-15/3/B 124 4

16 L8-16/1/B 38 12 L8-16/2/B 82 6 L8-16/3/B 124 4

20 L8-20/1/B 40 12 L8-20/2/B 90 6 L8-20/3/B 137 4

25 L8-25/1/B 40 12 L8-25/2/B 90 6 L8-25/3/B 137 4

30 L8-30/1/B 40 12 L8-30/2/B 90 6 L8-30/3/B 137 4

32 L8-32/1/B 42 12 L8-32/2/B 99 6 L8-32/3/B 149 4

40 L8-40/1/B 44 12 L8-40/2/B 103 6 L8-40/3/B 155 4

50 L8-50/1/B 50 12 L8-50/2/B 118 6 L8-50/3/B 179 4

63 L8-63/1/B 59 12 L8-63/2/B 134 6 L8-63/3/B 204 4

Trip Characteristic B (3~5 x IN) – Resistive or slightly inductive loads ➌

L8 Supplementary Protector Features:• UL-1077 Approved, CSA 22.2 No. 235 and IEC/EN 60898• Thermal Magnetic Overcurrent Protection• Trip characteristics based on 40ºC ambient for UL/CSA• Up to 10kA interruption ratings• Finger safe design• DIN-rail mounting

➊ 1-Pole ratings: UL/CSA 277VAC 48VDC, IEC 240/415VAC➋ Multi-pole ratings: UL/CSA 480Y/277VAC 96VDC, IEC 415VAC➌ See UL Short Circuit ratings U1/U2 in the technical data sections.

Page 5: Circuit Breakers - Series L8 Supplementary Circuit ... · Series L8 Supplementary Protectors are ... contact with live parts. To aid troubleshooting, a color-coded indicator provides

L8

M5

Circ

uit

Prot

ectio

n

M

visit www.sprecherschuh.com/ecatalog for the most up to date informationSSNA2012

Discount Schedule B-8

Upda

ted

06-2

5-13

L8 Supplementary ProtectorsTrip Characteristic B

Rated Current

(A)

1 Pole + Neutral 3 Pole + Neutral

Catalog Number PriceStd.Pkg. Catalog Number Price

Std.Pkg.

1 L8-1/1N-2/B 65 6 L8-1/3N/B 149 3

2 L8-2/1N-2/B 65 6 L8-2/3N/B 149 3

4 L8-4/1N-2/B 65 6 L8-4/3N/B 149 3

6 L8-6/1N-2/B 65 6 L8-6/3N/B 149 3

8 L8-8/1N-2/B 65 6 L8-8/3N/B 149 3

10 L8-10/1N-2/B 65 6 L8-10/3N/B 149 3

13 L8-13/1N-2/B 65 6 L8-13/3N/B 149 3

16 L8-16/1N-2/B 65 6 L8-16/3N/B 149 3

20 L8-20/1N-2/B 78 6 L8-20/3N/B 174 3

25 L8-25/1N-2/B 78 6 L8-25/3N/B 174 3

32 L8-32/1N-2/B 78 6 L8-32/3N/B 174 3

40 L8-40/1N-2/B 78 6 L8-40/3N/B 174 3

50 L8-50/1N-2/B 99 8 L8-50/3N/B 227 3

63 L8-63/1N-2/B 107 8 L8-63/3N/B 252 3

Trip Characteristic B (3~5 x IN) – Resistive or slightly inductive loads

All Supplementary Protectors + neutral are special order.

DISCONTINUED

Page 6: Circuit Breakers - Series L8 Supplementary Circuit ... · Series L8 Supplementary Protectors are ... contact with live parts. To aid troubleshooting, a color-coded indicator provides

M6

Circ

uit

Prot

ectio

nL8

visit www.sprecherschuh.com/ecatalog for the most up to date information SSNA2012

M

Discount Schedule B-8

Rated Current

(A)

1 Pole ➊ 2 Pole ➋ 3 Pole ➋

Catalog Number PriceStd.Pkg. Catalog Number Price

Std.Pkg. Catalog Number Price

Std.Pkg.

0.5 L8-.5/1/C 44 12 L8-.5/2/C 101 6 L8-.5/3/C 145 4

1 L8-1/1/C 44 12 L8-1/2/C 101 6 L8-1/3/C 145 4

2 L8-2/1/C 44 12 L8-2/2/C 101 6 L8-2/3/C 145 4

3 L8-3/1/C 44 12 L8-3/2/C 101 6 L8-3/3/C 145 4

4 L8-4/1/C 44 12 L8-4/2/C 101 6 L8-4/3/C 145 4

5 L8-5/1/C 44 12 L8-5/2/C 101 6 L8-5/3/C 145 4

6 L8-6/1/C 44 12 L8-6/2/C 101 6 L8-6/3/C 145 4

7 L8-7/1/C 44 12 L8-7/2/C 101 6 L8-7/3/C 145 4

8 L8-8/1/C 44 12 L8-8/2/C 101 6 L8-8/3/C 145 4

10 L8-10/1/C 44 12 L8-10/2/C 101 6 L8-10/3/C 145 4

13 L8-13/1/C 44 12 L8-13/2/C 101 6 L8-13/3/C 145 4

15 L8-15/1/C 44 12 L8-15/2/C 101 6 L8-15/3/C 145 4

16 L8-16/1/C 44 12 L8-16/2/C 101 6 L8-16/3/C 145 4

20 L8-20/1/C 44 12 L8-20/2/C 101 6 L8-20/3/C 145 4

25 L8-25/1/C 48 12 L8-25/2/C 111 6 L8-25/3/C 164 4

30 L8-30/1/C 48 12 L8-30/2/C 111 6 L8-30/3/C 164 4

32 L8-32/1/C 50 12 L8-32/2/C 111 6 L8-32/3/C 166 4

40 L8-40/1/C 55 12 L8-40/2/C 122 6 L8-40/3/C 183 4

50 L8-50/1/C 63 12 L8-50/2/C 143 6 L8-50/3/C 210 4

63 L8-63/1/C 71 12 L8-63/2/C 160 6 L8-63/3/C 239 4

L8 Supplementary ProtectorsTrip Characteristic C

Trip Characteristic C (5~10 x IN) – Inductive loads ➌

L8 Supplementary Protector Features:• UL-1077 Approved, CSA 22.2 No. 235 and IEC/EN 60898• Thermal Magnetic Overcurrent Protection• Trip characteristics based on 40ºC ambient for UL/CSA• Up to 10kA interruption ratings• Finger safe design• DIN-rail mounting

➊ 1-Pole ratings: UL/CSA 277VAC 48VDC, IEC 240/415VAC➋ Multi-pole ratings: UL/CSA 480Y/277VAC 96VDC, IEC 415VAC➌ See UL Short Circuit ratings U1/U2 in the technical data sections.

Page 7: Circuit Breakers - Series L8 Supplementary Circuit ... · Series L8 Supplementary Protectors are ... contact with live parts. To aid troubleshooting, a color-coded indicator provides

L8

M7

Circ

uit

Prot

ectio

n

M

visit www.sprecherschuh.com/ecatalog for the most up to date informationSSNA2012

Discount Schedule B-8

Upda

ted

06-2

5-13

L8 Supplementary ProtectorsTrip Characteristic C

Rated Current

(A)

1 Pole + Neutral 3 Pole + Neutral

Catalog Number PriceStd.Pkg. Catalog Number Price

Std.Pkg.

1 L8-1/1N-2/C 88 6 L8-1/3N/C 210 3

2 L8-2/1N-2/C 88 6 L8-2/3N/C 210 3

4 L8-4/1N-2/C 88 6 L8-4/3N/C 210 3

5 L8-5/1N-2/C 88 6 Not Available ~ ~

6 L8-6/1N-2/C 88 6 L8-6/3N/C 210 3

8 L8-8/1N-2/C 88 6 L8-8/3N/C 210 3

10 L8-10/1N-2/C 88 6 L8-10/3N/C 210 3

13 L8-13/1N-2/C 88 6 L8-13/3N/C 210 3

16 L8-16/1N-2/C 88 6 L8-16/3N/C 210 3

20 L8-20/1N-2/C 88 6 L8-20/3N/C 210 3

25 L8-25/1N-2/C 95 6 L8-25/3N/C 221 3

32 L8-32/1N-2/C 97 6 L8-32/3N/C 223 3

40 L8-40/1N-2/C 101 6 L8-40/3N/C 239 3

50 L8-50/1N-2/C 128 8 L8-50/3N/C 290 3

63 L8-63/1N-2/C 137 8 L8-63/3N/C 319 3

Trip Characteristic C (5~10 x IN) – Inductive loads

All Supplementary Protectors + neutral are special order.

DISCONTINUED

Page 8: Circuit Breakers - Series L8 Supplementary Circuit ... · Series L8 Supplementary Protectors are ... contact with live parts. To aid troubleshooting, a color-coded indicator provides

M8

Circ

uit

Prot

ectio

nL8

visit www.sprecherschuh.com/ecatalog for the most up to date information SSNA2012

M

Discount Schedule B-8

L8 Supplementary ProtectorsTrip Characteristic D

Trip Characteristic D (10~20 x IN) – Highly inductive loads ➌

Rated Current

(A)

1 Pole ➊ 2 Pole ➋ 3 Pole ➋

Catalog Number PriceStd.Pkg. Catalog Number Price

Std.Pkg. Catalog Number Price

Std.Pkg.

0.5 L8-.5/1/D 44 12 L8-.5/2/D 101 6 Not Available ~ ~

1 L8-1/1/D 44 12 L8-1/2/D 101 6 L8-1/3/D 145 4

2 L8-2/1/D 44 12 L8-2/2/D 101 6 L8-2/3/D 145 4

3 L8-3/1/D 44 12 L8-3/2/D 101 6 L8-3/3/D 145 4

4 L8-4/1/D 44 12 L8-4/2/D 101 6 L8-4/3/D 145 4

5 L8-5/1/D 44 12 L8-5/2/D 101 6 L8-5/3/D 145 4

6 L8-6/1/D 44 12 L8-6/2/D 101 6 L8-6/3/D 145 4

7 L8-7/1/D 44 12 L8-7/2/D 101 6 L8-7/3/D 145 4

8 L8-8/1/D 44 12 L8-8/2/D 101 6 L8-8/3/D 145 4

10 L8-10/1/D 44 12 L8-10/2/D 101 6 L8-10/3/D 145 4

13 L8-13/1/D 44 12 L8-13/2/D 101 6 L8-13/3/D 145 4

15 L8-15/1/D 44 12 L8-15/2/D 101 6 L8-15/3/D 145 4

16 L8-16/1/D 44 12 L8-16/2/D 101 6 L8-16/3/D 145 4

20 L8-20/1/D 44 12 L8-20/2/D 101 6 L8-20/3/D 145 4

25 L8-25/1/D 48 12 L8-25/2/D 111 6 L8-25/3/D 164 4

30 L8-30/1/D 48 12 L8-30/2/D 111 6 L8-30/3/D 164 4

32 L8-32/1/D 50 12 L8-32/2/D 111 6 L8-32/3/D 166 4

40 L8-40/1/D 55 12 L8-40/2/D 122 6 L8-40/3/D 183 4

L8 Supplementary Protector Features:• UL-1077 Approved, CSA 22.2 No. 235 and IEC/EN 60898• Thermal Magnetic Overcurrent Protection• Trip characteristics based on 40ºC ambient for UL/CSA• Up to 10kA interruption ratings• Finger safe design• DIN-rail mounting

➊ 1-Pole ratings: UL/CSA 277VAC 48VDC, IEC 240/415VAC➋ Multi-pole ratings: UL/CSA 480Y/277VAC 96VDC, IEC 415VAC➌ See UL Short Circuit ratings U1/U2 in the technical data sections.

Page 9: Circuit Breakers - Series L8 Supplementary Circuit ... · Series L8 Supplementary Protectors are ... contact with live parts. To aid troubleshooting, a color-coded indicator provides

L8

M9

Circ

uit

Prot

ectio

n

M

visit www.sprecherschuh.com/ecatalog for the most up to date informationSSNA2012

Discount Schedule B-8

Upda

ted

06-2

5-13

L8 Supplementary ProtectorsTrip Characteristic D

Rated Current

(A)

1 Pole + Neutral 3 Pole + Neutral

Catalog Number PriceStd.Pkg. Catalog Number Price

Std.Pkg.

1 L8-1/1N-2/D 88 6 L8-1/3N/D 210 3

2 L8-2/1N-2/D 88 6 L8-2/3N/D 210 3

4 L8-4/1N-2/D 88 6 L8-4/3N/D 210 3

6 L8-6/1N-2/D 88 6 L8-6/3N/D 210 3

8 L8-8/1N-2/D 88 6 L8-8/3N/D 210 3

10 L8-10/1N-2/D 88 6 L8-10/3N/D 210 3

13 L8-13/1N-2/D 88 6 L8-13/3N/D 210 3

16 L8-16/1N-2/D 88 6 L8-16/3N/D 210 3

20 L8-20/1N-2/D 88 6 L8-20/3N/D 210 3

25 L8-25/1N-2/D 95 6 L8-25/3N/D 221 3

32 L8-32/1N-2/D 97 6 L8-32/3N/D 223 3

40 L8-40/1N-2/D 101 6 L8-40/3N/D 239 3

Trip Characteristic D (10~20 x IN) – Highly inductive loads

All Supplementary Protectors + neutral are special order.

DISCONTINUED

Page 10: Circuit Breakers - Series L8 Supplementary Circuit ... · Series L8 Supplementary Protectors are ... contact with live parts. To aid troubleshooting, a color-coded indicator provides

M10

Circ

uit

Prot

ectio

nL8

visit www.sprecherschuh.com/ecatalog for the most up to date information SSNA2012

M

Discount Schedule B-8

AccessoriesSeries L8 Supplementary Protectors

Accessories

Module DescriptionFor use with…

ConnectionDiagrams Catalog Number Price

Selectable Two Pole Auxiliary Contact or Auxiliary / Signal Alarm Module –

• Small set-screw alternates between operational modes• Two Form C (two changeover contacts)• Installs on left side of L8• Auxiliary contact switches when L8 is operated manually or tripped electrically• Signal Alarm contact switches only when L8 is tripped electrically

All L8s& ShuntTrip

Two pole auxiliary mode

Auxiliary / Signal alarm mode

LX-AHS3 71

Shunt Trip –

• Remotely trips the device• Installs on left side of L8

All L8s

12…110VAC(12…60VDC)

110…415VAC(110…230VDC)

Z8-ASA24

Z8-ASA230

145

145

Undervoltage Release –

• Prevents device from operating unless voltage is present• Installs on left side of L8• Test button

All L8s

50…115 VAC110…230 VAC

Z8-USA115Z8-USA230

307

Allowable Combinations of Field Installed Modules(1) Auxiliary Contact Module

(1) Selectable Two Pole Auxiliary Contact Module / Auxiliary & Signal Alarm Contact Module

(1) Shunt Trip Module

(1) Undervoltage Release Module

(1) Auxiliary Contact Module + (1) Shunt Trip Module

All modules install on the left side of the L8.

Page 11: Circuit Breakers - Series L8 Supplementary Circuit ... · Series L8 Supplementary Protectors are ... contact with live parts. To aid troubleshooting, a color-coded indicator provides

M11

Circ

uit

Prot

ectio

nL8

visit www.sprecherschuh.com/ecatalog for the most up to date informationSSNA2012

M

Discount Schedule B-8

Accessory DescriptionDevices per Meter For use with… Catalog Number

PriceEach

Bus Bar, Pin Style 1-Phase ➋➌Qty 1 bar at 1 meter

57L8 1-pole, 80A max FHL8-A1B8 74

L8 1-pole, 100A max FHL8-A1B1 83

36L8 1-pole w/ Aux, 80A max FHL8-A1B8H 76

L8 1-pole w/ Aux, 100A max FHL8-A1B1H 87

Bus Bar, Pin Style 2-Phase ➋➌Qty 1 bar at 1 meter

29L8 2-pole, 80A max FHL8-A2B8 167

L8 2-pole, 100A max FHL8-A2B1 185

22L8 2-pole w/ Aux, 80A max FHL8-A2B8H 163

L8 2-pole w/ Aux, 100A max FHL8-A2B1H 188

Bus Bar, Pin Style 3-Phase ➋➌Qty 1 bar at 1 meter

19L8 3-pole, 80A max FHL8-A3B8 192

L8 3-pole, 100A max FHL8-A3B1 227

16L8 3-pole w/ Aux, 80A max FHL8-A3B8H 193

L8 3-pole w/ Aux, 100A max FHL8-A3B1H 234

1-Phase 2- & 3-Phase

End Caps, sold only in pkgs of 10 ➊FHL8 1-Phase Bus Bar FHL8-A1E 2FHL8 2-/3-Phase Bus Bar FHL8-AME 3

Protective Shroud, sold only in pkgs of 10 ➊ All FHL8 bus bars FHL8-AAP 7

Terminal Lug, sold only in pkgs of 10 ➊ 80A / 100A FHL8-AAT1 17

Padlock Hasp –• Fits securely over switch handle. Prevents unauthorized activation of L8 during maintenance• Provision for one padlock

All L8 MCBs L8-ASPLOA 12

AccessoriesSeries L8 Supplementary Protectors

Accessories

➊ Sold in packages of 10. Price indicated is price per piece. Minimum order quantity 10. Example, one package of 10 pcs of FHL8-A1E is $20 (10 x $2).

➋ Cuttable, copper bus bar provided in 1 m length. UL 508 Listed, E332470, Category NMTR, cULus. CE to IEC 664 10 kA SCCR for use with L8 Supplementary protectors. Bus Bars may also be used with FH8 Type CC and Midget Fuse Holders on page M45. See page M18 for Dimensions.

➌ FHL8-_H are designed to accomodate the LX-AHS3 Auxiliary Contact module, excludes Shunt Trip and Undervoltage Release.

Available 2012

Page 12: Circuit Breakers - Series L8 Supplementary Circuit ... · Series L8 Supplementary Protectors are ... contact with live parts. To aid troubleshooting, a color-coded indicator provides

M12

Circ

uit

Prot

ectio

nL8

visit www.sprecherschuh.com/ecatalog for the most up to date information SSNA2012

M

Discount Schedule B-8

Technical InformationSeries L8 Supplementary Protectors

Technical Information

General Data B Curve C Curve D Curve

Resistive or slightly resistive Inductive Loads Highly Inductive LoadsTripping Characteristic In 3…5 x In 5…10 x In 10…20 x InApprovals UR, CSA, CE UR, CSA, CE UR, CSA, CE

(All models ) IEC-EN 60 898 / DIN 43 880

Supplementary ProtectorApprovals UL 1077 - Recognized Component QVNU2 - E304759

CSA 22.2 No. 235 Certified Component

Use Group (UG) UG A - General Industrial

Terminals (FW) FW 3 Line and Load evaluated for field wiring

Overload Rating (OL) OL 0 (general use)

1-Pole, 1-Pole + N

Maximum Volts 277V AC 48V DC

Tripping Current (TC) TC 1, 40 °C TC 1, 40 °C

Short-Circuit Current Rating (SC) SC U2 SC U1

< 35 A 10 kA @ 277V AC; B and C Curve 10 kA @ 48V DC; B, C, and D Curve

5 kA @ 277V AC; D Curve

40, 50, 63 A 5 kA @ 277V AC; B, C, and D Curve 10 kA @ 48V DC; B, C, and D Curve

2-Pole, 3-Pole, 3-Pole + N

Maximum Volts 480Y/277V AC 96V DC (2-pole - series)

Tripping Current TC 2, 40 °C TC 2, 40 °C

Short-Circuit Current Rating (SC) SC U2 SC U1

< 35 A 10 kA @ 480Y/277V AC; B and C Curve 10 kA @ 96V DC; B, C, and D Curve

5 kA @ 480Y/277V AC; D Curve

40, 50, 63 A 5 kA @ 480Y/277V AC; B, C, and D Curve 10 kA @ 96V DC; B, C, and D Curve

Miniature Circuit Breaker IEC/EN 60898 (VDC)IEC/EN 60947-2 (GL) (not including D Curve 50A and 63A)

CQC (GB-10963) (not including D Curve 50A and 63A)Approvals

Current Range [A] 1…63 0.5…63 0.5…40

Thermal Tripping Characteristic >1 hr. at 1.13 x In<1 hr. at 1.45 x In

Interrupt Rating; 1 pole [kA] 10 @ 240VAC

Interrupt Rating; multi-pole [kA] 10 @ 415VAC

Rated Impulse Withstand Voltage U [V] 4000V

Rated Insulation Voltage U [VAC] 440VAC

Overload Category / Pollution Degree III / 2

Rated Operation Voltage U [VAC] 240 / 415Rated Ultimate Short Circuit Breaking Capacity

15 – 0.5 cos @240 / 415VAC

Page 13: Circuit Breakers - Series L8 Supplementary Circuit ... · Series L8 Supplementary Protectors are ... contact with live parts. To aid troubleshooting, a color-coded indicator provides

M13

Circ

uit

Prot

ectio

nL8

visit www.sprecherschuh.com/ecatalog for the most up to date informationSSNA2012

M

Discount Schedule B-8

Environmental and General SpecificationsDielectric Strength [VAC] 1960

Shock [G] 25 (half sine wave for 11ms - 3 axis)

Vibration Frequency range: 10…2000Hz

Maximum amplitude (p - p) = 0.030 in.

Maximum acceleration = 5G

2 hours each of 3 axis

Operating Temperature Range [°F] 23…+104 (–5…+40°C) non-condensingShipment and Short Term Temperature Limits

[°F] –22…+158ºF (–30…+70°C)

Housing Material Nylon

Switched Neutral Rating [VAC] 277

Electromechanical Life6000 operations

(1 operation = 2 switching events) ON/OFF

Circuit Diagrams 1 pole 1 pole + neutral 2 pole 3 pole 3 pole + neutral

Back up ProtectionSupplementary Protectors / Fuses: The following table shows the maximum short circuit current when fuses meeting the requirements of IEC 60269-1 are used as backup protection to MCBs.

Miniature Circuit Breaker

RatedCurrent (In)

Upstream Fuse100A 160A 200A

Characteristic B

Characteristic C

1…10A 40kA 25kA 25kA

10…50A 50kA 40kA 25kA

63A 50kA 40kA 10kA

Mechanical DataDegree of Protection IP20

Mechanical endurance [ops.] 6,000 (1 operation = 2 switching movements – ON/OFF

Method of mounting 35mm mounting rail (EN50022)

Supply connection Line or load side

TerminationsWire size #18…8 AWG (1.0…10 mm2)

solid / stranded

Tightening Torque — 2.4 N•m (21 lb-in.)#6…4 AWG (1.6…25 mm2)

Tightening Torque — 3.1 N•m (27 lb-in.)Recommended Wire Strip Length in (mm) 0.51 (13)

Weight / pole [g] / [lb] 120 / 0.32

Mounting Position 360˚ 360˚

Technical InformationSeries L8 Supplementary Protectors

Technical Information (continued)

Page 14: Circuit Breakers - Series L8 Supplementary Circuit ... · Series L8 Supplementary Protectors are ... contact with live parts. To aid troubleshooting, a color-coded indicator provides

M14

Circ

uit

Prot

ectio

nL8

visit www.sprecherschuh.com/ecatalog for the most up to date information SSNA2012

M

Discount Schedule B-8

Technical Information (continued)

Continuous Current Rating Factor Rated Diversity Factor

When multiple supplementary protectors are mounted side by side, they must be derated to determine the load carrying capacity.

Technical InformationSeries L8 Supplementary Protectors

➊ When using two wires, use same cross section.

AccessoriesAuxiliaries Undervoltage Release Shunt Trip

Z8-AHK, NHK Z8-USA… Z8-ASA…Degree of protection (Field Wiring Terminals) IP20 (IP 00) IP20 (IP 00) IP20 (IP 00)Minimum Impulse Duration [ms] ~ ~ >15Minimum Command Time [ms] ~ ~ ≤200Operating Voltage [V] ~ Un - 115V (Z7-USA115) 12…110VAC (Z7-ASA24)

Umin - 50V 12…60VDC~ Un - 230/240 (Z7-USA230) 110…415VAC (Z7-ASA230)

Umin - 110V 110…230VDCInrush Current [mA] ~ 3.6 / 44 (AC/DC) 25 / 12 (AC

15 / 2 (DC)Dropout ~ 0.7…0.35 x Us ~Voltage Range [V] ~ ~ 0.7…1.1 x Us

Max. operational current Ie ~ ~AC13 250V [A] 3 ~ ~

IEC AC15 250V [A] 0.5 ~ ~DC12 110V [A] 0.5 ~ ~

Umin - 5V CDCUL1077 / AC 230V [A] 2 ~ ~CSA22.2 DC 110V [A] 0.5 ~ ~

Umin - 5V CDCAuxiliaries Undervoltage Release Shunt Trip

Z8-AHK, NHK Z8-USA… Z8-ASA…Mechanical Life-span [ops] 6000 10000 4000Terminations ➊

Terminal type

Wire size

solid / stranded1 conductor

2 conductors0.5…2.5 (18…14)0.5…2.5 (18…14)

0.5…4 (18…14)0.5…2.5 (18…14)

1.0…25 (18…8)1.0…4 (18…12)

Tightening torque [Nm] / [lb-in] 0.8 / 7 1.1 / 10 2.4 / 21

Weight [g] / [lbs] 45 / 0.1 155 / 0.4 155 / 0.4

Page 15: Circuit Breakers - Series L8 Supplementary Circuit ... · Series L8 Supplementary Protectors are ... contact with live parts. To aid troubleshooting, a color-coded indicator provides

M15

Circ

uit

Prot

ectio

nL8

visit www.sprecherschuh.com/ecatalog for the most up to date informationSSNA2012

M

Discount Schedule B-8

1500

0

5000

6000

7000

80

00

9000

10

000

1000

1500

2000

3000

4000

500

300

400

70000

50000

30000

15000

900

9000

7000

5000

3000

1500

700

500

80000

60000

40000

20000

10000

8000

6000

4000

2000

1000

800

600

B2

B4 B6

B10 B13 B16 B20 B25 B32 B40 B63

B50

Available short-circuit current [A]

Maximum let-through energy L8 Type B

Let

-thr

ough

ene

rgy

I2 t [A2 s

ec]

10000 9000

1500

0

1000

0 90

00

8000

70

00

8000

7000

6000

5000

4000

3000

2000

1500

1000

500

6000

4000

3000

2000

1500

1000

B2

B4 B6 B10 B13 B16 B20 B2

5 B32 B4

0 B50 B6

3

500

Available short circuit current [A]

Let-

thro

ugh

curr

ent [

A]

Maximum let-through current L8 Type B

Technical Information (continued)

Technical InformationSeries L8 Supplementary Protectors

1500

0

5000

6000

7000

80

00

9000

10

000

1000

1500

2000

3000

4000

500

300

400

70000

50000

30000

15000

900

9000

7000

5000

3000

1500

700

500

80000

60000

40000

20000

10000

8000

6000

4000

2000

1000

800

600

C3.5 C4

C13 C16 C20 C25 C40

C63

C50

Available short-circuit current [A]

Maximum let-through energy L8Type C

Let

-thr

ough

ene

rgy

I2 t [A2 s

ec]

C0.5

C1

C1.5 C2 C2.5

C3

C6

C32

C10

10000 9000

1500

0

1000

0 90

00

8000

70

00

8000

7000

6000

5000

4000

3000

2000

1500

1000

500

6000

4000

3000

2000

1500

1000

C1.5

C3 C3.5

500

Available short circuit current [A]

Let-

thro

ugh

curr

ent [

A]

Maximum let-through current L8 Type C

C1

C2.5

C2

C4 C6 C10 C13 C16 C20 C25 C32 C40 C50 C63

Page 16: Circuit Breakers - Series L8 Supplementary Circuit ... · Series L8 Supplementary Protectors are ... contact with live parts. To aid troubleshooting, a color-coded indicator provides

M16

Circ

uit

Prot

ectio

nL8

visit www.sprecherschuh.com/ecatalog for the most up to date information SSNA2012

M

Discount Schedule B-8

1500

0

5000

6000

7000

80

00

9000

10

000

1000

1500

2000

3000

4000

500

300

400

70000

50000

30000

15000

900

9000

7000

5000

3000

1500

700

500

80000

60000

40000

20000

10000

8000

6000

4000

2000

1000

800

600

D10 D13 D16 D25 D40

D32

Available short-circuit current [A]

Maximum let-through energy L8Type D

Let

-thr

ough

ene

rgy

I2 t [A2 s

ec]

D2

D4

D20

D6

10000 9000

1500

0

1000

0 90

00

8000

70

00

8000

7000

6000

5000

4000

3000

2000

1500

1000

500

6000

4000

3000

2000

1500

1000

500

Available short circuit current [A]

Let-

thro

ugh

curr

ent [

A]

Maximum let-through current L8 Type D

D2 D4

D6 D10 D13 D16 D20 D25 D32 D40

Technical InformationSeries L8 Supplementary Protectors

Technical Information (continued)

Page 17: Circuit Breakers - Series L8 Supplementary Circuit ... · Series L8 Supplementary Protectors are ... contact with live parts. To aid troubleshooting, a color-coded indicator provides

M17

Circ

uit

Prot

ectio

nL8

visit www.sprecherschuh.com/ecatalog for the most up to date informationSSNA2012

M

Discount Schedule B-8

DimensionsSeries L8 Supplementary Protectors

1-pole 2-pole and 3-pole 3-pole + neutral 1-pole + neutral

L8 Supplementary Protectors (Series L8…B, C & D)

One & Two Pole Auxiliary Contact, Signal Alarm Contact (LX-AHS3)

Shunt Trip & Undervoltage Release Modules (Z8-ASA…& Z8-USA…)

Shunt Trip Undervoltage Release Module

Dimensions are in millimeters (inches). Dimensions not intended for manufacturing purposes.

Page 18: Circuit Breakers - Series L8 Supplementary Circuit ... · Series L8 Supplementary Protectors are ... contact with live parts. To aid troubleshooting, a color-coded indicator provides

M18

Circ

uit

Prot

ectio

nL8

visit www.sprecherschuh.com/ecatalog for the most up to date information SSNA2012

M

Discount Schedule B-8

FHL8 - 1 Pole Bus Bars

15

15

5

5.5

17.8

56 x 17.7 = 996.8

2

15

15

5

2.5

1009- 0+2

FHL8-A1B8 FHL8-A1B1

FHL8-A1B8H FHL8-A1B1H

5

15

15

2

5

15

15

2.55.5

2736 x 27 = 972

985- 0+2

FHL8 - 1 Pole Bus Bars w/ Auxiliary

15

15

5

5.5

17.8

56 x 17.7 = 996.8

2

15

15

5

2.5

1009- 0+2

FHL8-A1B8 FHL8-A1B1

FHL8-A1B8H FHL8-A1B1H

5

15

15

2

5

15

15

2.55.5

2736 x 27 = 972

985- 0+2

DimensionsSeries L8/FH8 UL508 Bus Bars

Dimensions are in millimeters (inches). Dimensions not intended for manufacturing purposes.

Page 19: Circuit Breakers - Series L8 Supplementary Circuit ... · Series L8 Supplementary Protectors are ... contact with live parts. To aid troubleshooting, a color-coded indicator provides

M19

Circ

uit

Prot

ectio

nL8

visit www.sprecherschuh.com/ecatalog for the most up to date informationSSNA2012

M

Discount Schedule B-8

FHL8-A2B8 - 2 Pole Bus Bars

991 - 0+2

21.2

(23)

36.5

14

6 1.5

17.8

44.555 x 17.8 = 979

FHL8-A2B1 - 2 Pole Bus Bars

(23)

21.2

14

1009 - 0+2

36.5

6

17.8

56 x 17.8 = 996.8

2

FHL8-A2B8H - 2 Pole Bus Bars w/ Auxiliary

1009 - 0+2

21.2

(23)

36.5

14

6 1.5

17.8

44.522 x 44.5 = 979

DimensionsSeries L8/FH8 UL508 Bus Bars

Dimensions are in millimeters (inches). Dimensions not intended for manufacturing purposes.

Page 20: Circuit Breakers - Series L8 Supplementary Circuit ... · Series L8 Supplementary Protectors are ... contact with live parts. To aid troubleshooting, a color-coded indicator provides

M20

Circ

uit

Prot

ectio

nL8

visit www.sprecherschuh.com/ecatalog for the most up to date information SSNA2012

M

Discount Schedule B-8

FHL8-A2B1H - 2 Pole Bus Bars w/ Auxiliary

1009 - 0+2

14

(23)

36.5

21.2

2617.8

4422 x 44 = 968

FHL8-A3B8 - 3 Pole Bus Bars

6

17.8

56 x 17.8 = 996.8

14

1.5

1009 - 0+2

(23)

37

21.2

FHL8-A3B1 - 3 Pole Bus Bars

14

(23)

36.5

21.2

1009 +2

26

17.8

56 x 17.8 = 996.8

DimensionsSeries L8/FH8 UL508 Bus Bars

Dimensions are in millimeters (inches). Dimensions not intended for manufacturing purposes.

Page 21: Circuit Breakers - Series L8 Supplementary Circuit ... · Series L8 Supplementary Protectors are ... contact with live parts. To aid troubleshooting, a color-coded indicator provides

M21

Circ

uit

Prot

ectio

nL8

visit www.sprecherschuh.com/ecatalog for the most up to date informationSSNA2012

M

Discount Schedule B-8

FHL8-A3B8H - 3 Pole Bus Bars w/ Auxiliary

(23)

37

21.2

982 - 0+2

62.3

15 x 62.3 = 934.5

14

1.56

17.8

2 x 17.8 = 35.6

FHL8-A3B1H - 3 Pole Bus Bars w/ Auxiliary

982 - 0+2

(23)

36.5

21.2

14

26

17.8

2 x 17.8 = 35.6

62.3

15 x 62.3 = 934.5

FHL8-AAP - Protective Shroud

5.7

23.8

24

14 3.8

85.2

R0.5

17.84 x 17.8 = 71.2

DimensionsSeries L8/FH8 UL508 Bus Bars

Dimensions are in millimeters (inches). Dimensions not intended for manufacturing purposes.

Page 22: Circuit Breakers - Series L8 Supplementary Circuit ... · Series L8 Supplementary Protectors are ... contact with live parts. To aid troubleshooting, a color-coded indicator provides

M22

Circ

uit

Prot

ectio

nL8

visit www.sprecherschuh.com/ecatalog for the most up to date information SSNA2012

M

Discount Schedule B-8

DimensionsSeries L8/FH8 UL508 Bus Bars

Dimensions are in millimeters (inches). Dimensions not intended for manufacturing purposes.

FHL8-A1E - End Cap 1-Phase FHL8-AME - End Cap 2- & 3-Phase

2.15

1.1

1.7

8.5

14

1

24

9.521.6

18.6

4

12

4

(2:1)

60

18.5

6.8

16.2 28.5

ø11

3

21

2.15

1.1

1.7

8.5

14

1

24

9.521.6

18.6

4

12

4

(2:1)

60

18.5

6.8

16.2 28.5

ø11

3

21

FHL8-AAT1 - Terminal Lug

2.15

1.1

1.7

8.5

14

1

24

9.521.6

18.6

4

12

4

(2:1)

60

18.5

6.8

16.2 28.5

ø11

3

21

Page 23: Circuit Breakers - Series L8 Supplementary Circuit ... · Series L8 Supplementary Protectors are ... contact with live parts. To aid troubleshooting, a color-coded indicator provides

M23

Circ

uit

Prot

ectio

nL8

visit www.sprecherschuh.com/ecatalog for the most up to date informationSSNA2012

M

Discount Schedule B-8

Applying FHL8 Bus Bars & Accessories

FHL8-AAP

L8... orFH8...

4 mm

Z2

Ampacity of devices

AWG lb-in NmL8 Tightening Torque

18...46...4

2127

2.43.1

AWG lb-in Nm10...2 50 5.5

FHL8-AAT1

*

Ampacity of FHL8-A_B8_ Bus-bar

Temperature in Celsius

Ampa

city

in A

mps

15 20 25 30 35 40 45 50 5560

65

70

75

80

85

90

95

100

FH8

L8

Temperature in Celsius

Ampa

city

in A

mps

15 20 25 30 35 40 45 50 5560

65

70

75

80

85

90

95

100

Ampacity of FHL8-A_B1_ Bus-bar

FH8L8

AWG lb-in NmFH8 Tightening Torque

16...4 18...22 2...2.5

DimensionsSeries L8/FH8 UL508 Bus Bars

Dimensions are in millimeters (inches). Dimensions not intended for manufacturing purposes.