3 RV 1011 - 0 DA 15 CIRCUIT - BREAKER , SIZE S 00 , Low-Voltage Controls and Distribution > Industrial Controls > Protection Equipment > Circuit Breakers/Motor Starter Protectors > Motor Starter Protectors SIRIUS 3RV1 up to 100 A CIRCUIT-BREAKER, SIZE S00, FOR MOTOR PROTECTION, CLASS 10, A REL.0.22...0.32A, N REL.4.2A SCREW CONNECTION, STANDARD BREAKING CAPACITY W. TRANSV. AUX. SWITCH 1NO/1NC General technical data: Size of the circuit-breaker S00 Trip class CLASS 10 Protection class IP IP20 Ambient temperature / during the operating phase -20 °C…70 °C Item designation according to DIN 40719 extendable after IEC 204-2 / according to IEC 750 Q according to DIN EN 61346-2 Q Design of the auxiliary switch transverse Type of the driving mechanism / Motor drive No design of the operating mechanism rocker Product function Overload protection Yes Short-circuit to earth recognition No Phase disturbance recognition Yes Product component auxiliary switch Yes Undervoltage release mechanism No trip indicator Yes product extension / optional / Motor drive No Main circuit: Type of voltage AC/DC Number of poles 3 Service power / at AC-3 at 400 V / rated value 0.09 kW Service power / for three-phase servomotors rated value 0.09 kW Arrangement of electrical connectors for main current circuit front side Adjustable response current of the non-delayed short-circuit release 4.2 A…4.2 A of the current-dependent overload release 0.22 A…0.32 A Technical Data

Upload: others

Post on 16-Jul-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CIRCUIT-BREAKER, SIZE S00, FOR REL.0.220.32A, N REL.4.2A ...s3-us-west-1.amazonaws.com/media.groupbbi.com/attachments/... · General data for SIRIUS motor starter protectors Selection

3RV1011-0DA15 CIRCUIT-BREAKER, SIZE S00,

Low-Voltage Controls and Distribution > Industrial Controls > Protection Equipment > CircuitBreakers/Motor Starter Protectors > Motor Starter Protectors SIRIUS 3RV1 up to 100 A

CIRCUIT-BREAKER, SIZE S00, FORMOTOR PROTECTION, CLASS 10, AREL.0.22...0.32A, N REL.4.2ASCREW CONNECTION, STANDARDBREAKING CAPACITY W. TRANSV.AUX. SWITCH 1NO/1NC

General technical data:

Size of the circuit-breaker S00

Trip class CLASS 10

Protection class IP IP20

Ambient temperature / during the operating phase -20 °C…70 °C

Item designation according to DIN 40719 extendable after IEC 204-2 /according to IEC 750

Q

according to DIN EN 61346-2 Q

Design of the auxiliary switch transverse

Type of the driving mechanism / Motor drive No

design of the operating mechanism rocker

Product function Overload protection YesShort-circuit to earth recognition NoPhase disturbance recognition Yes

Product component auxiliary switch YesUndervoltage release mechanism Notrip indicator Yes

product extension / optional / Motor drive NoMain circuit:

Type of voltage AC/DC

Number of poles 3

Service power / at AC-3 at 400 V / rated value 0.09 kW

Service power / for three-phase servomotors rated value 0.09 kW

Arrangement of electrical connectors for main current circuit front side

Adjustable response current of the non-delayed short-circuit release 4.2 A…4.2 Aof the current-dependent overload release 0.22 A…0.32 A

Technical Data

Page 2: CIRCUIT-BREAKER, SIZE S00, FOR REL.0.220.32A, N REL.4.2A ...s3-us-west-1.amazonaws.com/media.groupbbi.com/attachments/... · General data for SIRIUS motor starter protectors Selection

Continuous current / rated value 0.32 AAuxiliary circuit:

number of NC contacts / for auxiliary contact 1

number of NO contacts / for auxiliary contact 1

number of change-over switches / for auxiliary contact 0Short-circuit:

Switch-off capacity limit short-circuit current at 400 V / rated value 100 kA

Design of the overcurrent release and short-circuitrelease

thermomagnetic

Installation/mounting/dimensions:

Type of fixing/fixation screw and snap-on mounting onto35 mm standard mounting railaccording to DIN EN 50022

Width 45 mm

Height 90 mm

Depth 81 mmConnections:

Design of the electrical connection for main current circuit screw-type terminals

Further information:Information- and Downloadcenter (Catalogs, Brochures,…)http://www.siemens .com/lowvoltage/catalogs

Global Industry Mall (Online ordering system)http://www.siemens .com/lowvoltage/mall

Service&Support (Manuals, Certificates, Characteristics, FAQs,...)http://support.automation.siemens .com/WW/view/en/3RV1011-0DA15/all

last change: 04/06/2009

© Siemens AG 2009 - Corporate Information - Privacy Policy - Terms of Use

Page 3: CIRCUIT-BREAKER, SIZE S00, FOR REL.0.220.32A, N REL.4.2A ...s3-us-west-1.amazonaws.com/media.groupbbi.com/attachments/... · General data for SIRIUS motor starter protectors Selection

SiemIndus

1/4 Siemens Energy & Automation, Inc.Industrial Controls Catalog

Discount Code: SIRIUS Contactors, OL’s, MSP’s

3RV10 Class 10up to 12A

3RV1 Motor Starter ProtectorsFor Motor Protection SIRIUS

Siemens / Industrial Controls Previous folio: 272 IC 2000

UL short- Screw connection Cage clampInstanta- circuit connectionneous breaking

Single- short circuit capacityFLA Phase release @ 480 V List ListAdjustment HP Ratings Three-Phase HP Ratings� I > Icu Price Price

Illustration Range 115V 230V 200V 230V 460V 575V A kA Catalog No $ Catalog No $

Description Ordering Information

� ON/OFF rocker mechanism with lockout. � Adjustment dial for setting to motor FLA.� Class 10 overload trip characteristics.� Short circuit trip at 12 times the maximum setting of the FLA adjustment dial.� Short circuit current rating:� Ambient compensated up to 140° F (applies to side by side mounting).� Phase loss sensitivity.� Test trip function.� Cage Clamp version. � Auxiliaries and Accessories see pages 1/8–1/15.� General Information see pages 1/28–1/31.� Technical Data see pages 1/20–1/27.� Dimensions see page 1/32.

Note: Select MSP by motor Full Load Amperes. Horsepower ratings are for reference only.

The 3RV101 MSP’s, can be used as components in GroupInstallation per NEC 430-53(C) to turn motors on and off. Eachdevice has built-in heater elements that provide overload pro-tection and magnetic trip elements to protect the motor. Whenthe 3RV101 is used as a component in Group Installation, mul-tiple MSP’s can be installed below one circuit breaker to pro-tect its own motor. A contactor can be mounted to the MSP toprovide a remotely operated starter.

3RV101 Frame Size S00�

0.11–0.16 — — — — — — 2.1 65 3RV1011-0AA10 116. 3RV1011-0AA20 121.

0.14–0.2 — — — — — — 2.6 65 3RV1011-0BA10 116. 3RV1011-0BA20 121.

0.18–0.25 — — — — — — 3.3 65 3RV1011-0CA10 116. 3RV1011-0CA20 121.

0.22–0.32 — — — — — — 4.2 65 3RV1011-0DA10 116. 3RV1011-0DA20 121.

0.28–0.4 — — — — — — 5.2 65 3RV1011-0EA10 116. 3RV1011-0EA20 121.

0.35–0.5 — — — — — — 6.5 65 3RV1011-0FA10 130. 3RV1011-0FA20 135.

0.45–0.63 — — — — — 1⁄4 8.2 65 3RV1011-0GA10 130. 3RV1011-0GA20 135.

0.55–0.8 — — — — 1⁄4 1⁄2 10 65 3RV1011-0HA10 130. 3RV1011-0HA20 135.

0.7–1 — — — — 1⁄2 1⁄2 13 65 3RV1011-0JA10 130. 3RV1011-0JA20 135.

0.9–1.25 — — — 1⁄4 3⁄4 3⁄4 16 65 3RV1011-0KA10 130. 3RV1011-0KA20 135.

1.1–1.6 — 1⁄101⁄4 1⁄3 3⁄4 1 21 65 3RV1011-1AA10 130. 3RV1011-1AA20 135.

1.4–2 — 1⁄8 1⁄3 1⁄2 1 11⁄2 26 65 3RV1011-1BA10 130. 3RV1011-1BA20 135.

1.8–2.5 — 1⁄6 1⁄2 1⁄2 11⁄2 11⁄2 33 65 3RV1011-1CA10 130. 3RV1011-1CA20 135.

2.2–3.2 1⁄101⁄4 3⁄4 3⁄4 11⁄2 2 42 65 3RV1011-1DA10 130. 3RV1011-1DA20 135.

2.8–4 1⁄8 1⁄3 3⁄4 1 2 3 52 65 3RV1011-1EA10 130. 3RV1011-1EA20 135.

3.5–5 1⁄6 1⁄2 1 1 3 3 65 65 3RV1011-1FA10 130. 3RV1011-1FA20 135.

4.5–6.3 1⁄4 3⁄4 11⁄2 11⁄2 5 5 82 65 3RV1011-1GA10 130. 3RV1011-1GA20 135.

5.5–8 1⁄3 1 2 2 5 5 104 65 3RV1011-1HA10 130. 3RV1011-1HA20 135.

7–10 1⁄2 11⁄2 3 3 71⁄2 10� 130 65 3RV1011-1JA10 130. 3RV1011-1JA20 135.

9–12 1⁄2 2 3 3 71⁄2 10 156 65 3RV1011-1KA10 159. 3RV1011-1KA20 164.

� Select MSP by motor full load amps. Horse power ratings for reference only.

� Size S00 MSP are listed for group installation only.� For additional auxiliary switches refer to

Accessories, Page 1/8 (screw connection) and Page 1/15 (Cage Clamp connection).

� All setting ranges are suitable for use in groupinstallation for the following ratings. Maximum short-circuit rating: S00-480 V, 3 phase, 65,000 rms symmetrical amps;

600 V, 3 phase, 10,000 rms symmetrical amps.

The 3RT1011 devices except suffix -1J and -1K aresuitable for tap conductor protection in groupapplications used on the above levels.

3RV19 01-1E 24. 3RV19 01-2E 26.

Accessories

Transverse auxiliary switch� Approx. weight .02 kg1 NO + 1 NC separately

06IC01_01-12.qxd 2/14/06 1:20 PM Page 1/4

Page 4: CIRCUIT-BREAKER, SIZE S00, FOR REL.0.220.32A, N REL.4.2A ...s3-us-west-1.amazonaws.com/media.groupbbi.com/attachments/... · General data for SIRIUS motor starter protectors Selection

1/2 Siemens Energy & Automation, Inc.Industrial Controls Catalog

SiemIndus

IEC ControlsMotor Starter Protectors

Siemens / Industrial Controls Previous folio: 2/2

SIRIUS 3RV1 motor starter protectors up to 100 A

For motor protectionCLASS 10

For motor protectionCLASS 20

General data for SIRIUSmotor starter protectors

Selection and ordering data Selection and ordering dataSize Rated current Page Size Rated current Page PageS00 up to 12 A 1/4 S2 up to 50 A 1/6 Technical data 1/20S0 up to 25 A 1/5 S3 up to 100 A 1/6 Overview 1/28S2 up to 50 A 1/5 Characteristics 1/31S3 up to 100 A 1/5 Circuit diagrams 1/31

Dimension drawings 1/32

Ciruit Breaker 3RV17 SIRIUS 3RV19 Cage Clamp infeed system

3RV MSP auxiliaries and accessories

Page Page Page

Selection and ordering data 1/7 Selection and ordering data 1/18-19 Selection and ordering data 1/8

Circuit diagrams 1/7 Technical data 1/16 Technical data 1/2633/1weivrevO61/1weivrevO7/1sgniward noisnemiD

Dimension drawings 1/47 Circuit diagrams 1/35Dimension drawings 1/36

Size S00

Size S0

Size S2

Size S3

06IC01_1/2.ps 1/23/06 7:34 PM Page 1/2

Page 5: CIRCUIT-BREAKER, SIZE S00, FOR REL.0.220.32A, N REL.4.2A ...s3-us-west-1.amazonaws.com/media.groupbbi.com/attachments/... · General data for SIRIUS motor starter protectors Selection

1/20 Siemens Energy & Automation, Inc.Industrial Controls Catalog

SiemIndus

3RV1 up to 100 A(Domestic applications)

3RV1 Motor Starter ProtectorsGeneral Data SIRIUS

hp rating = Power rating in horse power (maximum motor rating)FLA = Full Load Amps / Motor full load current

■Technical data

Permissible ratings of devices approved for North America, u s

Motor Starter Protectors of the SIRIUS 3RV1 series are ap-proved for u/s. According to UL 508 and C22.2 No.14

they can also be used with a load feeder contactor. TheseMotor Starter Protectors can

be used as "Manual Motor Starter" for "Group Fusing", or for "Group Installation" or as

"Combination Motor Controller Type E". Additional information is found on 1/29.

3RV1 as "Manual Motor Starter"If used as "Manual Motor Starter", the MSP is always oper-ated in combination with a short-circuit protection device (upstream short-circuit protec-tion device).

As short-circuit protection device any fusible link ("group fusing") or circuit-breaker ("group installation") of a type

and size compliant with Ameri-can Basic Standard NFPA 70, Article 430-53 (c) can be selected for sufficient protec-tion of the power supply cables.

Approvals are found under the following file numbers contain-ing the data listed:u Number File No. E156943, Product Class NLRVs File No. LR12730, Product Class 3211 05.

MSP hp rating Rated current up to AC 240 V up to AC 480 Y/277 V up to AC 600 Y/347 Vfor FLA max. In Icu

1) Icu1) Icu

1)Type V single-

phase3-phase

A kA kA kA

0.11 ... 2 65 65 303RV10 11 2.5 65 65 30

115 1/2 – 3.2 65 65 30200 11/2 3 4 65 65 30

Size S00 230 2 3 5 65 65 30460 – 71/2 6.3 65 65 30

FLA max. 12 A, 600 V 575/600 – 10 8 65 65 3010 65 65 3012 65 65 30

0.11 ... 3.2 65 65 303RV10 21 4 65 65 30

5 65 65 30115 2 – 6.3 65 65 30

Size S0 200 3 71/2 8 65 65 30230 5 71/2 10 65 65 30

FLA max. 25 A, 600 V 460 – 15 12.5 65 65 30575/600 – 20 16 65 65 30

20 65 65 3022 65 65 3025 65 65 30

3RV10 31 11 ... 16 65 65 2520 65 65 25

115 3 – 25 65 65 25Size S2 200 71/2 15 32 65 65 25

230 10 20 40 65 65 25FLA max. 50 A, 600 V 460 – 40 45 65 65 25

575/600 – 50 50 65 65 25

11 ... 16 65 65 303RV10 41/3RV10 42 20 65 65 30

115 10 – 25 65 65 30200 20 30 32 65 65 30230 20 40 40 65 65 30

Size S3 460 – 75 50 65 65 30575/600 – 100 63 65 65 30

FLA max. 99 A, 600 V 75 65 65 3090 65 65 30

100 (99) 65 65 30

1) Complies with "short circuit breaking capacity" to UL.

Siemens / Industrial Controls Previous folio: 2/14, 1/21, 1/20, 1/21

06IC01_13-24.qxd 2/8/06 6:54 PM Page 1/20

Page 6: CIRCUIT-BREAKER, SIZE S00, FOR REL.0.220.32A, N REL.4.2A ...s3-us-west-1.amazonaws.com/media.groupbbi.com/attachments/... · General data for SIRIUS motor starter protectors Selection

1/28 Siemens Energy & Automation, Inc.Industrial Controls Catalog

SiemIndus

3RV1up to 100 A

3RV1 Motor Starter ProtectorsGeneral Data SIRIUS

Overview

S00 MSP with laterally mounted undervoltage re-lease with leading auxiliary switch 3RV10 Motor Starter Protectors

(MSP’s) are built for a world of applications while meeting the requirements of control users worldwide. Each MSP features a manual ON/OFF switch, a Class 10 adjustable bimetallic overload relay (Class 20 avail-able in the two largest frame sizes), and magnetic trip ele-ments for short circuit protec-tion.

Construction

The motor starter protectors are available in four sizes:

• Size S00 - 3RV101Maximum rated current is 12 Amps. Suitable for motors up to 10 hp at 600V. Available in both screw terminal and Cage Clamp versions.

• Size S0 - 3RV102Maximum rated current is 25 Amps. Suitable for motors up to 20 hp at 600V.

• Size S2 - 3RV103Maximum rated current is 50 Amps. Suitable for motors up to 50 hp at 600V.

• Size S3 - 3RV104Maximum rated current is 100 Amps. Suitable for motors up to 100 hp at 600V.

Functions

Releases

3RV1 motor starter protectors are equipped with bimetallic-based, inverse-time delayed overload releases - electromag-netic short-circuit releases.

The overload releases can be set in accordance with the load current. The overcurrent re-leases are permanently set to a value 13 times the rated current and thus enable trouble-free start-up of motors.

The scale cover can be sealed to prevent unauthorized adjust-ments to the set current.

Release classes

The release classes of thermally delayed releases are based on the tripping time (tA) at 7.2 times the operational current in cold state (excerpt from IEC 60 947-4):

• CLASS 10 A 2 s < tA w 10 s• CLASS 10 4 s < tA w 10 s• CLASS 20 6 s < tA w 20 s• CLASS 30 9 s < tA w 30 s

The release must trip within this time!

Operating mechanisms

S00 MSP are actuated via a rocker operating mechanism and S0, S2 and S3 MSP’s via a rotary operating mechanism. If the MSP trips, the rotary operat-ing mechanism switches to the tripped position to indicate this. Before the MSP is reclosed, the rotary operating mechanism must be reset manually to 0 position, in order to prevent the former from closing by mistake before the fault has been cleared.

In the case of MSP’s with rotary operating mechanisms, an electrical signal can be output via a signalling switch to indi-cate that the MSP has tripped.

All operating mechanisms can be locked in 0 position with a padlock (shackle diameter 3.5 to 4.5 mm).

Application

Operating conditions

3RV1 MSP’s are suitable for use in any climate. They are designed for operation in closed rooms under normal conditions (e.g. no dust, corro-sive vapours or harmful gases). Suitable enclosures must be provided for installation in dusty or damp rooms.

Motor Protection

3RV MSP’s use bimetallic heater elements to provide class 10 or 20 overcurrent pro-tection for both AC and DC motors. The bimetallic heaters sense the motor current directly, so the overloads are insensitive to high frequencies, harmonic waves and sinusoi-dal currents and voltages.

Each MSP has a fourth bimetal-lic strip that reacts only to the ambient temperature inside the control panel. This ambient compensation prevents the MSP from nuisance tripping when the panel temperature is higher than the ambient tem-perature of the motor.

A built-in differential trip bar causes the MSP to trip faster on a phase loss condition, to help reduce motor damage from phase loss.

Magnetic trip elements in each MSP take the device off line when it senses currents of 12 times the maximum FLA dial setting.

3RV1 0 1 1 - 0 A A 1 0

SIRIUS MSP or Circuit Breaker

Application Frame Size Standard Amperage Range Class Terminal Type Auxiliary Switch0 = Motor Protection 1 = S00

2 = S0

3 = S2

4 = S3

Possible choices listed below see page 1/4-1/7 for an entire listing

A = 10 1 = Screw

2 = Spring Loaded7 = UL 489 B = 20

0, 1, 4 B through K

Note: MPS’s and Contactors of the same frame size are made to easily fit together with the use of a link module.

Siemens / Industrial Controls Previous folio: 2/22, 1/29, 1/28, 1/29