TECHNICAL REPORT Ultrasonic testing in the welds of Upper Wagon Central Deck Rev: 0 March 2015 Page 1 of 12 WDS INGENIERIA, S.A. Inspected by: Report by: Eng. Cuicas Wisthon Eng. Cuicas Wisthon Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panamá +507 6662 4768 / +507 68604245 [email protected] ULTRASONIC INSPECTION AND REINSPECTION OF WELDS OF UPPER WAGON CENTRAL DECK March 2015

Upload: wisthon-griman

Post on 25-Sep-2015

32 views

Category:

Documents


4 download

DESCRIPTION

modelo inforne insoeccion oir ultrasonido segun practica recomendada

TRANSCRIPT

  • TECHNICAL REPORT Ultrasonic testing in the welds of

    Upper Wagon Central Deck

    Rev: 0 March 2015 Page 1 of 12

    WDS INGENIERIA, S.A. Inspected by: Report by:

    Eng. Cuicas Wisthon Eng. Cuicas Wisthon

    Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam +507 6662 4768 / +507 68604245 [email protected]

    ULTRASONIC INSPECTION AND

    REINSPECTION OF WELDS OF UPPER

    WAGON CENTRAL DECK

    March 2015

  • TECHNICAL REPORT Ultrasonic testing in the welds of

    Upper Wagon Central Deck

    Rev: 0 March 2015 Page 2 of 12

    WDS INGENIERIA, S.A. Inspected by: Report by:

    Eng. Cuicas Wisthon Eng. Cuicas Wisthon

    Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam +507 6662 4768 / +507 68604245 [email protected]

    Panama, March 2015

    Gentlemen:

    Cimolai Technology, S. p. A. Attention. Alessandro Boscaro.

    REF: Ultrasonic Inspection and Reinspection of welds of Upper

    Wagon Central Deck Cot C1502-021S

    Respected Engineer

    Attached Technical Report Ultrasonic inspection, by WDS Ingeniera, S.A.,

    Testing conducted in welds of Upper Wagon Central Deck in the Panama

    Canal expansion.

    This report contains observations and conclusions relating to the service.

    Best regards

    ENG. Daniel Rivero ASNT-TC-1A Level II PT, VT, MT.

    Level I UT, ECT AWS Member No 675950

  • TECHNICAL REPORT Ultrasonic testing in the welds of

    Upper Wagon Central Deck

    Rev: 0 March 2015 Page 3 of 12

    WDS INGENIERIA, S.A. Inspected by: Report by:

    Eng. Cuicas Wisthon Eng. Cuicas Wisthon

    Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam +507 6662 4768 / +507 68604245 [email protected]

    REPORT CONTENTS

    1. OBJECTIVE

    2. INSPECTION DATE, PERSONNEL AND EQUIPMENTS

    3. ACCEPTANCE AND REJECT CRITERIA

    4. INSPECTION RESULTS AND ANALYSIS

    5. ANNEXES

  • TECHNICAL REPORT Ultrasonic testing in the welds of

    Upper Wagon Central Deck

    Rev: 0 March 2015 Page 4 of 12

    WDS INGENIERIA, S.A. Inspected by: Report by:

    Eng. Cuicas Wisthon Eng. Cuicas Wisthon

    Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam +507 6662 4768 / +507 68604245 [email protected]

    1. OBJECTIVE

    Evaluate by ultrasonic testing (UT) 50% of the welds belonging to the

    Upper Wagon Central Deck

    2. DATE OF INSPECTION, PERSONNEL AND EQUIPMENT

    Inspection of the unions was held on February 28th and March 4th 2015

    in Cocol, Panama.

    The staff was involved for inspection:

    - Eng Cuicas Wisthon, ASNT-TC-1A Level II: VT, PT, MT, and UT.

    EQUIPMENT USED:

    - Ultrasound Equipment Olympus EPOCH LTX.

    - Calibration block IIW Type 1.

    - Digital Camera.

    - Coupling Gel.

    - Tape Measure.

    3. CRITERIA FOR ACCEPTANCE OR REJECTION:

    Evaluation, acceptance and rejection took place following from AWS

    D1.1 STRUCTURAL WELDING CODE.

  • TECHNICAL REPORT Ultrasonic testing in the welds of

    Upper Wagon Central Deck

    Rev: 0 March 2015 Page 5 of 12

    WDS INGENIERIA, S.A. Inspected by: Report by:

    Eng. Cuicas Wisthon Eng. Cuicas Wisthon

    Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam +507 6662 4768 / +507 68604245 [email protected]

    4. INSPECTION RESULTS, ANALYSIS AND RECOMMENDATIONS

    During the ultrasound inspection of the 50% of every weld

    belonging to Upper Wagon Central Deck Q1000/D and Q1000/C relevant

    discontinuities were detected and repaired.

    After the repairment no relevant discontinuities were detected.

  • TECHNICAL REPORT Ultrasonic testing in the welds of

    Upper Wagon Central Deck

    Rev: 0 March 2015 Page 6 of 12

    WDS INGENIERIA, S.A. Inspected by: Report by:

    Eng. Cuicas Wisthon Eng. Cuicas Wisthon

    Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam +507 6662 4768 / +507 68604245 [email protected]

    INSPECTION REPORT ULTRASONIC FLAW DETECTOR

    Project: Welding Inspection Area: Report N: 01

    Client: Cimolai Technology Datum:

    SPECIFICATIONS MATERIAL UNDER TEST

    Equipment Thickness Diameter shaft Pre TT Post TT

    Q1000/C 10mm N/A N/A

    Welding Procedure: N/A Welding Type Surface condition Temperature

    Code / applied standard: AWS D1.1 N/A Environment

    EQUIPMENT USED

    Brand: Olympus Serial: SD010312 Model: EPOCH LTC

    Transducer: Sonatest Dimensions: 0.250 " Frecuency: 2.25 MHz

    Pattern calibration : ASME SECC V, ART 4 Pattern Reference: N / A Others:

    TECHNICAL PARAMETERS AND INSPECTION

    Technique: Defectology Range: 50 mm Reference level: 45 dB

    DAC calibration beam path: N / A Reference Reflector: Scanning Level (dB):

    Incident angle: 70 Beam exit: Normal and Tilt Coupling: Methylcellulose

    Delay Probe delay Velocity PCS DSS

    0,0 s 6,0 s 3280 m/s N/A N/A

    Defects determination %DAC Defect type

    Result

    Weld Stamping Sector Ubicac. Length Depth height 45 60 70 Acept Reject

    W1 X

    W2 N/A Internal Weld 90mm and 30mm 4,3mm 1,7mm X

    W3 X

    W4 X

    W5 X

    W6 X

    W7 X

    W8 X

    Equipment presentation/line: Weld sketch: N/A

    COMMENTS:

    MADE BY REVIEWED BY APPROVED BY

    COMPANY

    SIGNATURE

    NAME ENG. Wisthon Cuicas ENG. Wisthon Cuicas ENG. Daniel Rivero

    DATE 03-09-2015 03-09-2015 03-09-2015

  • TECHNICAL REPORT Ultrasonic testing in the welds of

    Upper Wagon Central Deck

    Rev: 0 March 2015 Page 7 of 12

    WDS INGENIERIA, S.A. Inspected by: Report by:

    Eng. Cuicas Wisthon Eng. Cuicas Wisthon

    Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam +507 6662 4768 / +507 68604245 [email protected]

    REINSPECTION REPORT ULTRASONIC FLAW DETECTOR

    Project: Welding Inspection Area: Report N: 01

    Client: Cimolai Technology Datum:

    SPECIFICATIONS MATERIAL UNDER TEST

    Equipment Thickness Diameter shaft Pre TT Post TT

    Q1000/C 10mm N/A N/A

    Welding Procedure: N/A Welding Type Surface condition Temperature

    Code / applied standard: AWS D1.1 N/A Environment

    EQUIPMENT USED

    Brand: Olympus Serial: SD010312 Model: EPOCH LTC

    Transducer: Sonatest Dimensions: 0.250 " Frecuency: 2.25 MHz

    Pattern calibration : ASME SECC V, ART 4 Pattern Reference: N / A Others:

    TECHNICAL PARAMETERS AND INSPECTION

    Technique: Defectology Range: 50 mm Reference level: 45 dB

    DAC calibration beam path: N / A Reference Reflector: Scanning Level (dB):

    Incident angle: 70 Beam exit: Normal and Tilt Coupling: Methylcellulose

    Delay Probe delay Velocity PCS DSS

    0,0 s 6,0 s 3280 m/s N/A N/A

    Defects determination %DAC Defect type

    Result

    Weld Stamping Sector Ubicac. Length Depth height 45 60 70 Acept Reject

    W2 N/A X

    Equipment presentation/line: Weld sketch: N/A

    COMMENTS:

    MADE BY REVIEWED BY APPROVED BY

    COMPANY

    SIGNATURE

    NAME ENG. Wisthon Cuicas ENG. Wisthon Cuicas ENG. Daniel Rivero

    DATE 03-09-2015 03-09-2015 03-09-2015

  • TECHNICAL REPORT Ultrasonic testing in the welds of

    Upper Wagon Central Deck

    Rev: 0 March 2015 Page 8 of 12

    WDS INGENIERIA, S.A. Inspected by: Report by:

    Eng. Cuicas Wisthon Eng. Cuicas Wisthon

    Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam +507 6662 4768 / +507 68604245 [email protected]

    INSPECTION REPORT ULTRASONIC FLAW DETECTOR

    Project: Welding Inspection Area: Report N: 01

    Client: Cimolai Technology Datum:

    SPECIFICATIONS MATERIAL UNDER TEST

    Equipment Thickness Diameter shaft Pre TT Post TT

    Q1000/D 10mm N/A N/A

    Welding Procedure: N/A Welding Type Surface condition Temperature

    Code / applied standard: AWS D1.1 N/A Environment

    EQUIPMENT USED

    Brand: Olympus Serial: SD010312 Model: EPOCH LTC

    Transducer: Sonatest Dimensions: 0.250 " Frecuency: 2.25 MHz

    Pattern calibration : ASME SECC V, ART 4 Pattern Reference: N / A Others:

    TECHNICAL PARAMETERS AND INSPECTION

    Technique: Defectology Range: 50 mm Reference level: 45 dB

    DAC calibration beam path: N / A Reference Reflector: Scanning Level (dB):

    Incident angle: 70 Beam exit: Normal and Tilt Coupling: Methylcellulose

    Delay Probe delay Velocity PCS DSS

    0,0 s 6,0 s 3280 m/s N/A N/A

    Defects determination %DAC Defect type

    Result

    Weld Stamping Sector Ubicac. Length Depth height 45 60 70 Acept Reject

    W1 X

    W2 X

    W3 X

    W4 X

    W5 X

    W6 N/A Internal Weld 48mm and 60mm 4,5mm 2mm X

    W7 X

    W8 X

    Equipment presentation/line: Weld sketch: N/A

    COMMENTS:

    MADE BY REVIEWED BY APPROVED BY

    COMPANY

    SIGNATURE

    NAME ENG. Wisthon Cuicas ENG. Wisthon Cuicas ENG. Daniel Rivero

    DATE 03-09-2015 03-09-2015 03-09-2015

  • TECHNICAL REPORT Ultrasonic testing in the welds of

    Upper Wagon Central Deck

    Rev: 0 March 2015 Page 9 of 12

    WDS INGENIERIA, S.A. Inspected by: Report by:

    Eng. Cuicas Wisthon Eng. Cuicas Wisthon

    Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam +507 6662 4768 / +507 68604245 [email protected]

    REINSPECTION REPORT ULTRASONIC FLAW DETECTOR

    Project: Welding Inspection Area: Report N: 01

    Client: Cimolai Technology Datum:

    SPECIFICATIONS MATERIAL UNDER TEST

    Equipment Thickness Diameter shaft Pre TT Post TT

    Q1000/D 10mm N/A N/A

    Welding Procedure: N/A Welding Type Surface condition Temperature

    Code / applied standard: AWS D1.1 N/A Environment

    EQUIPMENT USED

    Brand: Olympus Serial: SD010312 Model: EPOCH LTC

    Transducer: Sonatest Dimensions: 0.250 " Frecuency: 2.25 MHz

    Pattern calibration : ASME SECC V, ART 4 Pattern Reference: N / A Others:

    TECHNICAL PARAMETERS AND INSPECTION

    Technique: Defectology Range: 50 mm Reference level: 45 dB

    DAC calibration beam path: N / A Reference Reflector: Scanning Level (dB):

    Incident angle: 70 Beam exit: Normal and Tilt Coupling: Methylcellulose

    Delay Probe delay Velocity PCS DSS

    0,0 s 6,0 s 3280 m/s N/A N/A

    Defects determination %DAC Defect type

    Result

    Weld Stamping Sector Ubicac. Length Depth height 45 60 70 Acept Reject

    W6 N/A X

    Equipment presentation/line: Weld sketch: N/A

    COMMENTS:

    MADE BY REVIEWED BY APPROVED BY

    COMPANY

    SIGNATURE

    NAME ENG. Wisthon Cuicas ENG. Wisthon Cuicas ENG. Daniel Rivero

    DATE 03-09-2015 03-09-2015 03-09-2015

  • TECHNICAL REPORT Ultrasonic testing in the welds of

    Upper Wagon Central Deck

    Rev: 0 March 2015 Page 10 of 12

    WDS INGENIERIA, S.A. Inspected by: Report by:

    Eng. Cuicas Wisthon Eng. Cuicas Wisthon

    Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam +507 6662 4768 / +507 68604245 [email protected]

    5. ANNEXES

  • TECHNICAL REPORT Ultrasonic testing in the welds of

    Upper Wagon Central Deck

    Rev: 0 March 2015 Page 11 of 12

    WDS INGENIERIA, S.A. Inspected by: Report by:

    Eng. Cuicas Wisthon Eng. Cuicas Wisthon

    Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam +507 6662 4768 / +507 68604245 [email protected]

    PHOTOGRAPHIC RECORD

  • TECHNICAL REPORT Ultrasonic testing in the welds of

    Upper Wagon Central Deck

    Rev: 0 March 2015 Page 12 of 12

    WDS INGENIERIA, S.A. Inspected by: Report by:

    Eng. Cuicas Wisthon Eng. Cuicas Wisthon

    Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam +507 6662 4768 / +507 68604245 [email protected]